Lennox SLO183BF101/114V42, SLO183BF135/150V60, SLO183BR101/114V42, SLO183BR135/150V60 Installation Instructions Manual

Page 1
Page 1
506905−01
*P506905-01*
04/12
*2P0412*
E 2012 Lennox Industries Inc.
Dallas, Texas, USA
Flue Model
Shown
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
IMPORTANT
This unit must be serviced annually by a licensed professional technician, or equivalent.
WARNING
Improper installation, adjustment, alteration, ser­vice, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information, consult a licensed profes­sional installer, or equivalent, or service agency.
WARNING
Do not store or use gasoline or other flammable va­pors and liquids in the vicinity of this or any other ap­pliance.
CAUTION
When venting this appliance, keep vent terminal free of snow, ice and debris.
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
INSTALLATION INSTRUCTIONS
SLO183BV SERIES UNITS
OIL UNITS
506905−01 04/2012
Table of Contents
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping & Packing List 1. . . . . . . . . . . . . . . . . . . . . . .
SLO183BV Unit Dimensions 2. . . . . . . . . . . . . . . . . . .
SLO183BV Start−Up & Performance Check List 2. .
SLO183BV Unit Parts Arrangement 3. . . . . . . . . . . . .
SLO183BV AFG Burner Parts Arrangement 3. . . . .
Requirements 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Combustion and Ventilation Air 5. . . . . . . . . . . . . . . . .
Locate & Level Unit 6. . . . . . . . . . . . . . . . . . . . . . . . . . .
Nozzle Adjustments 7. . . . . . . . . . . . . . . . . . . . . . . . . .
Indoor Coil Placement 8. . . . . . . . . . . . . . . . . . . . . . . .
Venting 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Flue Connections 10. . . . . . . . . . . . . . . . . . . . . . . . . . .
Supply & Return Air Plenums 11. . . . . . . . . . . . . . . . .
Oil Supply Line Sizing 11. . . . . . . . . . . . . . . . . . . . . . .
Oil Supply Line and Filter Connections 13. . . . . . . . .
Leak Check 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Wiring 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blower Control (A54) 17. . . . . . . . . . . . . . . . . . . . . . . .
Start−Up & Adjustment 19. . . . . . . . . . . . . . . . . . . . . . .
Service 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GeniSyst Primary Control 22. . . . . . . . . . . . . . . . . . .
Heating Sequence 24. . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General
These instructions are intended as a general guide and do not supersede local codes in any way. Only licensed pro­fessional technicians, or equivalent, can install and service the Dave Lennox Signature
®
Collection SLO183BV oil fur­naces. In Canada, refer to CSA B139 for recommended installation procedures. Consult authorities who have juris­diction before installation.
CAUTION
Never burn garbage or paper in the heating system. Never leave papers near or around the unit.
Shipping & Packing List
1 − Assembled oil furnace
1 − Barometric draft control
1 − Oil nozzle (used with SLO183BV−114 and −150 only)
Check the components for shipping damage. If you find any damage, immediately contact the last carrier.
Litho U.S.A.
Page 2
Page 2
SLO183BV Unit Dimensions − Inches (mm)
FLUE CONNECTION
SLO183BR101/114V42
1
(25)
2−1/2
(64)
RETURN
AIR
OPENING
SUPPLY
AIR
OPENING
OIL PIPING INLET
(Both Sides)
ELECTRICAL INLETS
(Right Side Only)
TOP VIEW
SIDE VIEW FRONT VIEW
A
E
D
E
3/4
(19)
FLUE CONNECTION
SLO183BF101/114V42 &
SLO183B5F135/150V60
(On Heat Exchanger)
AIR FLOW
AIR FLOW
3/4
(19)
3/4
(19)
3/4
(19)
1-1/2
(38)
3-1/4
(83)
5−1/4 (133)
B
C
FG
SIDE
FLUE OUTLET
CENTERING HOLE
(Field−Fabricate
Either Side)
TOP FLUE
OUTLET
Model No.
A B C D E x F (Supply) E x G (Return)
in. mm in. mm in. mm in. mm in. mm in. mm
SLO183BF101/114V42 19-1/2 495 37 940 52−1/2 1334 27 686 18 x 21 457 x 533 18 x 16 457 x 406
SLO183BR101/114V42 19-1/2 495 37 940 52−1/2 1334 27 686 18 x 21 457 x 533 18 x 16 457 x 406
SLO183BF135/150V60 22-1/2 572 37 940 52−1/2 1334 27 686 21 x 21 533 x 533 21 x 16 533 x 406
SLO183BR135/150V60 22-1/2 572 37 940 52−1/2 1334 27 686 21 x 21 533 x 533 21 x 16 533 x 406
SLO183BV Start−Up & Performance Check List
Filter Clean & Secure?
Supply Voltage
Electrical Connections Tight?
Job Name
Job Location Installer Unit Model No.
Oil Pump Pressure [recommended minimum 140 psi]
Job No.
City
City
Serial No.
Date
State
Serviceman
Draft Reading (recommended .03−.04 inches w.c.)
Flue Connections Tight?
HEATING SECTION
THERMOSTAT
Calibrated? Heat Anticipator Properly Set? Level?
Blower Motor Amps
Blower Motor H.P.
Piping Connections Tight?
Vent Clear?
State
Temperature RiseExternal Static Pressure
Net Stack Temp
Burner Model No.
Serial Number
All Valves Open?
PROPER DRAFT
% CO
2
% O
2
ppm CO
Stack Draft Overfire Draft
Ambient Temp
Smoke Test
Page 3
Page 3
SLO183BV Unit Parts Arrangement
Figure 1
Limit Switch
ST9103A Control −− A15
BeckettR AFG Burner
Blower
(Variable Speed Motor
on Other Side)
Observation Port
Clean−Out Port
Flue Opening
Heat Exchanger
Blower Control
A54
(Not Visible −−
Located on
blower housing)
Clean−Out Port
SLO183BV AFG Burner Parts Arrangement
ESCUTCHEON
PLATE
MAIN
HOUSING
HEAT
SHIELD
BURNER CONTROL
(with Reset Button)
OIL DELAY
VALV E
AIR TUBE WITH
ELECTRODE
ASSEMBLY AND
NOZZLE INSIDE
BLOWER WHEEL
WITH AIR GUIDE
(Inside housing)
COPPER OIL
TUBE
BLOWER
MOTOR
IGNITER
AIR BAND AND
AIR SHUTTER
Figure 2
FUEL PUMP
Page 4
Page 4
Requirements
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc.
P.O. Box 799900 Dallas, TX 75379−9900
Installation of Lennox oil−fired furnaces must conform with the National Fire Protection Association Standard for the Installation of Oil Burning Equipment, NFPA No. 31, the National Electrical Code, ANSI/NFPA No.70 (in the U.S.A.), CSA Standard CAN/CSA−B139 (in Canada), Installation Code for Oil Burning Equipment, the Canadian Electrical Code Part1, CSA 22.1 (Canada), the recommen­dations of the National Environmental Systems Contrac­tors Association and any state or provincial laws or local or­dinances. Authorities having jurisdiction should be consulted before installation. Such applicable regulations or requirements take precedence over general instructions in this manual.
Chimneys and chimney connectors must be of the type and construction outlined in section 160 of NFPA No. 31.
Air for combustion and ventilation must conform to stan­dards outlined in section 140 of NFPA No. 31 or, in Canada, CSA Standard B139. When installing SLO183B units in confined spaces such as utility rooms, two combustion air openings are required. Dimensions of combustion air openings are shown in table 1. One opening shall be below burner level and the other opening shall be no more than 6" (152 mm) from the room’s ceiling.
The combustion air opening should provide a minimum free area one-half square inch per 1,000 Btu per hour input. This combustion air should be brought into the area containing the furnace below the level of the furnace burner.
IMPORTANT
An opening to the outside for combustion air is strongly recommended, especially in new homes. Refer to table 1 or the unit plate for specific combus­tion air opening dimensions.
Table 1
Combustion Air Opening Dimensions
Model No.
Combustion Air Opening
Dimensions (2 required)
SLO183BF101/114V SLO183BR101/114V
10" X 20" (254 mm X 508 mm)
SLO183BF135/150V
SLO183BR135/150V
11" X 22" (279 mm X 559 mm)
This unit is approved for use on combustible flooring and for clearances to combustible material as listed on unit rating plate and in table 2. Unit service and accessibility clearances take precedence over fire protection clearances.
Table 2
Installation Clearances
Clearances
All Unit Sizes
inches (mm)
top of plenum and duct 2 (51)
plenum sides 3 (76)
sides* 6 (152)
rear 24 (610)
front 4 (102)
flue pipe measured vertical**
(measured from above)
9 (229)
NOTE−Service access clearance must be maintained.
*Clearance to allow inspection of furnace and flue connector shall be provided. 24" (610 mm) at rear and on one side of furnace should be allowed for cleaning and service of the blower. **Minimum clearance shown for flue pipe may be reduced by using special protection as provided by local building codes and the National Fire Protection Association Standards and CSA 189.
NOTE − When service clearances are greater than fire protection clearances, service clearances take prece­dence.
Obtain a temperature rise within the range listed in table 8 in the Start-Up section of this manual.
When installed, furnace must be electrically grounded in accordance with local codes or, in the absence of local codes, with the current National Electric Code, ANSI/NFPA No. 70, or Canadian Electric Code (CEC) if an external electrical source is utilized.
Field wiring connection with unit must meet or exceed specifications of type T wire and withstand a 63_F (17_C) temperature rise.
Notice to Home Owner
This furnace is equipped with safety devices that protect you and your property. If one or more of these devices is activated, furnace operation will stop. If your home is left unattended for an extended period of time, equipment op­eration must be checked periodically. If this is not possible, the water supply to the house should be shut off and the pipes should be drained. This will prevent problems associ­ated with a NO HEAT condition (frozen pipes, etc.)
Page 5
Page 5
Combustion and Ventilation Air
Homes built with energy conservation in mind use tight construction practices. These houses are sealed so well that it becomes necessary to provide a means of bringing in air from outside for combustion. Also, exhaust fans, ap­pliance vents, chimneys and fireplaces force additional air that could be used for combustion out of the house. Unless outside air is brought into the home for combustion, nega­tive pressure (pressure outside is greater than inside pres­sure) will build to the point that a down draft can occur in the furnace vent pipe or chimney. Combustion gases enter the living space creating a potentially dangerous situation. Ne­gative pressure may also interfere with proper combustion, causing sooting within the heat exchanger.
The importance of the previous paragraph cannot be over­stated. Users may inadvertently block fresh air intakes after installation.
In the absence of local codes concerning air for combus­tion and ventilation, the following section outlines guide­lines and recommends procedures for operating oil fur­naces in a manner that ensures efficient and safe operation. Special consideration must be given to combus­tion air needs as well as requirements for exhaust vents and oil piping.
Combustion Air Requirements
CAUTION
Insufficient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rust­ing and premature heat exchanger failure. It can also cause property damage.
All oil-fired appliances require air to be used for the com­bustion process. If sufficient amounts of combustion air are not available, the furnace or other appliance will operate in an inefficient and unsafe manner. Enough air must be pro­vided to meet the needs of all fuel-burning appliances, as well as appliances such as exhaust fans which force air out of the home. When fireplaces, exhaust fans, or clothes dry­ers are used at the same time as the furnace, much more air is required to ensure proper combustion and to prevent a down-draft situation. Insufficient amounts of air also cause incomplete combustion which can result in sooting. Requirements for providing air for combustion and ventila­tion depend largely on whether the furnace is installed in an unconfined or confined space.
Unconfined Space
An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.4 cubic meters) per 1,000 Btu (293 W) per hour of the combined input rating of all appliances installed in that space. This space also includes adjacent rooms which are
not separated by a door. Though an area may appear to be unconfined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures outlined for using air from the outside for combustion and ventilation.
Confined Space
A confined space is an area with volume less than 50 cubic feet (1.4 cubic meters) per 1,000 Btu (293 W) per hour of the combined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms.
When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space con­taining the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the confined space ei­ther from inside the building or from outside.
Air from an Adjacent Space
If the confined space housing the furnace adjoins space categorized as unconfined, air can be brought in by provid­ing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch
(6.4 square centimeters) per 1,000 Btu (293 W) per
hour of the total input rating of all fuel-fired equipment in the confined space. Each opening must be at least 100 square inches (614.5 square centimeters). One opening shall be within 12" (305 mm) of the top of the enclosure and one opening within 12" (305 mm) of the bottom (See figure 3).
Equipment In Confined Space
All Air From Inside
Chimney or
Oil Ven
t
Water
Heater
Openings
(To Adjacent Room)
Figure 3
NOTE−Each opening shall have a free area of at least 1 square inch (6.4 square centimeters) per 1,000 Btu (293 W) per hour of the total input rating of all equipment in the enclosure, but not less than 100 square inches
(614.5 square centimeters).
Oil
Furnace
Page 6
Page 6
Air from Outside
If air from outside is brought in for combustion and ventila­tion, the confined space shall be provided with two perma­nent openings. One opening shall be within 12" (305 mm) of the top of the enclosure and one within 12" (305 mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (6.4 square centimeters) per 4,000 Btu (1172 W) per hour of total input rating of all equipment in the enclosure. (See figure 4.) When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (6.4 square centimeters) per 2,000 Btu (586 W) per total input rating of all equipment in the enclosure (See figure 5).
Ventilation
Louvers
(For unheated
crawl space)
Outlet
Ai
r
Equipment In Confined Space
All Air From Outside
(Inlet Air from Crawl Space and Outlet Air to
Ventilated Attic)
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (6.4 square centimeters) per 4,000 Btu (1172 W) per hour of the total input rating of all equipment in the enclosure.
Ventilation Louvers (Each End Of Attic)
Water
Heater
Inlet
Air
Chimney or
Oil Vent
Figure 4
Oil
Furnace
When ducts are used, they shall be of the same cross−sec­tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3" (76 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protective cover­ing is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 per­cent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation.
Equipment In Confined Space
All Air From Outside
Outlet Air
Inlet Air
Water
Heate
r
Chimney
Or Oil
Vent
Figure 5
NOTE−Each air duct opening shall have a free area of at least one square inch (6.4 square centimeters) per 2,000 Btu (586 W) per hour of the total input rating of all equipment in the enclosure. If the equip­ment room is located against an outside wall and the air openings communicate directly with the outdoors, each opening shall have a free area of at least one square inch (6.4 square centimeters) per 4,000 Btu (1172 W) per hour of the total input rating of all other equip­ment in the enclosure.
Oil
Furnace
CAUTION
Combustion air openings in the front of the furnace must be kept free of obstructions. Any obstruction will cause improper burner operation and may result in a fire hazard or injury.
CAUTION
The barometric draft control shall be in the same at­mospheric pressure zone as the combustion air inlet to the furnace. Deviation from this practice will cause improper burner operation and may result in a fire hazard or injury.
Locate & Level the Unit
The compact design of this furnace makes it ideal for a basement or utility room installation. Choose a central location for the furnace so that supply air ducts approxi­mately the same length. This will allow each room to re­ceive the proper amount of heat. The furnace should be placed within 10 feet of the chimney, so that the flue con­nection to the chimney will be of minimum length and have a minimum number of elbows.
1 − Set the unit in desired location keeping in mind the
clearances listed in table 2. Also keep in mind oil sup­ply connections, electrical supply, flue connections and sufficient clearance for installing and servicing unit.
Page 7
Page 7
2 − Level the unit from side−to−side and from front−to−rear.
If the furnace is not level, place fireproof wedges or shims between the low side of the furnace and the floor. Make sure the weight of the furnace is distributed evenly on all four corners. Strain on sides of cabinet may occur if furnace weight is not evenly distributed. This strain can cause cracking and popping noises.
Adjustments
Neither the nozzle setting nor the air adjustments are facto­ry set. The furnace is fire−tested and the limit control is checked to make sure it functions properly; no factory set­tings are made. During installation, the furnace must be ad­justed to ensure proper operation. The installing dealer/ contractor must have and use proper test equipment in order to correctly adjust the oil furnace. Proper testing equipment is required to ensure correct operation of the unit. The use of test equipment is more critical than ever due to tighter tolerances needed to keep the furnace oper­ating efficiently. Among the required test equipment for an oil furnace, the proper combustion test kit should contain the following:
D Draft gauge D CO
2
or O2 Analyzer
D Smoke tester D Pressure gauge D High temperature thermometer D Oil vacuum gauge D Beckett T−501 or Z−2000 nozzle gauge D Knowledge of proper test equipment operation
CAUTION
Improper nozzle and/or air adjustment of this unit may result in sooting problems. Refer to the follow­ing section for correct adjustment procedures.
Nozzle Adjustment
Proper adjustment of the nozzle assembly is critical. Before the flue pipe and oil lines are installed, the nozzle assembly must be checked for proper depth and alignment. You must remove the entire burner assembly (not just the nozzle) from the furnace to check the nozzle depth and alignment. The smaller sized firing nozzle has been factory−installed. This should be verified by the installer. A larger nozzle has been provided in the bag assembly for use with SLO183BV114 and 150 units. Inspect the spark transformer leads also to en­sure they are still attached to the electrodes.
The burner assembly is attached to the vestibule panel by three nuts. Slots are provided in the mounting flange for re­moving the burner assembly from the vestibule. Loosen the nuts and turn the whole burner assembly clockwise (figure
6) to remove the entire burner assembly from the furnace. There is adequate wire to remove the burner without discon-
necting wires. Once removed, turn the burner around in the vest panel area.
Figure 6
SLO183BV Series Burner Removal
First, loosen three nuts which
attach burner to vest panel.
Next, rotate burner clockwise on slots then pull toward you.
To correctly check and adjust the nozzle depth and align­ment, use the Beckett T−501 or Z−2000 gauge.
To check the oil nozzle depth, insert the small end of the gauge into the end of the cone and measure from the flat of the end cone to the face of the nozzle. When nozzle depth is correct, the tip of the nozzle should just touch the end of the gauge. Refer to the illustration sheet provided with the gauge. Note that the scale side of the gauge is not used for this purpose. If necessary, loosen the escutcheon plate se­curing screw and slide the entire nozzle assembly forward or backward within the air tube (figure 7). Re−secure es­cutcheon plate screw when adjustment is completed.
To check nozzle alignment, again insert the small end of gauge into the end cone and measure the nozzle and electrode alignment against the center lines marked on the gauge (again refer to enclosed illustration sheet). If the nozzle is not centered, but found to be too far left or right, a new nozzle assembly will need to be ordered. Do not attempt to adjust by bending the 90 degree elbow in the oil line.
Take care to properly re−install burner assembly when nozzle adjustment has been completed.
Figure 7
Beckett Oil Burner Nozzle Adjustment
Burner must be removed from
furnace for this procedure.
1
2
T−501 Gauge
Escutcheon Plate
To Adjust Nozzle
1−Loosen escutcheon plate screw.
2−Slide entire nozzle/electrode assembly back and forth inside air tube until nozzle just touches gauge.
Page 8
Page 8
Indoor Coil Placement
In cooling / heat pump applications, Lennox recommends that the indoor coil be installed at least 4 inches above the top of the furnace cabinet to allow proper airflow. If coil cabinet does not provide proper clearance, use field−fabricated transition.
Venting
WARNING
Combustion air openings in front of the furnace must be kept free of obstructions. Any obstruction will cause improper burner operation and may result in a fire hazard.
WARNING
The barometric draft control shall be in the same at­mospheric pressure zone as the combustion air inlet to the furnace. Deviation from this practice will cause improper burner operation and may result in a fire hazard.
CAUTION
Do not store combustible materials near the furnace or supply air ducts. The material (such as paint, mo­tor oil, gasoline, paint thinner, etc.) may ignite by spontaneous combustion creating a fire hazard.
WARNING
This furnace is certified for use with type L" vent. B" vent must not be used with oil furnaces.
Prior to installation of unit, make a thorough inspection of the chimney to determine whether repairs are necessary. Make sure the chimney is properly constructed and sized accord­ing to the requirements of the National Fire Protection Asso­ciation. The smallest dimensions of the chimney should be at least equal to the diameter of the furnace vent connector.
Make sure the chimney will produce a steady draft sufficient to remove all the products of combustion from the furnace. A draft of at least .04" w.c. (9.9 Pa) is required during burner operation.
1 − Local building codes may have more stringent installa-
tion requirements and should be consulted before installation of unit.
2 − The vent connector should be as short as possible to
do the job.
3 − The vent connector should not be smaller than the out-
let diameter of the vent outlet of the furnace.
4 − Pipe should be at least 24 gauge galvanized.
5 − Single wall vent pipe should not run outside or through
any unconditioned space.
6 − Chimney should extend 3 feet (0.9 m) above highest
point where the vent passes through the roof, and 2 feet (0.6 m) higher than any portion of a building within a horizontal distance of 10 feet (3 m).
7 − The vent must not pass through a floor or ceiling.
Clearances to single wall vent pipe should be no less than 6" (152 mm); more if local codes require it.
8 − The vent may pass through a wall where provisions
have been made for a thimble as specified in the Stan­dards of the National Board of Fire Underwriters. See fig­ure 8.
Wall Thimble
Figure 8
Thimble
Vent Pipe
Combustible
Wall
Page 9
Page 9
Front Flue / Masonry Chimney
Rear Flue / Masonry Chimney
Liner
Barometric
Draft
Control* (in either location)
Clean Out
Liner
Masonry
Chimney
Figure 9
*Barometric draft control may be installed in either vertical or horizontal section of flue pipe no less than 12" and no more than 18" from furnace flue outlet.
Barometric Draft
Control*
(in either location)
Clean Out
Masonry Chimney
9 − The vent pipe should slope upward toward the chim-
ney on horizontal run at least 1/4 inch (6 mm) to the foot (0.3 m) and should be supported by something other than the furnace, such as isolation hangers. See figure 9.
10 − Extend the vent pipe into the chimney so that it is flush
with the inside of the chimney liner. Seal the joint be­tween the pipe and the liner.
11 − The furnace shall be connected to either a factory−built
chimney or vent which complies with a recognized standard, or to a masonry or concrete chimney which has been lined with a material acceptable to the au­thority having jurisdiction.
12 − When two or more appliances vent into a common
vent, the area of the common vent should not be less than the area of the largest vent or vent connection plus 50% of the area of the additional vent or vent con­nection. Chimney must be able to sufficiently vent all appliances operating at the same time.
Front Flue / Factory−Built Chimney
Rear Flue / Factory−Built Chimney
Figure 10
Condensate
Drain
Factory−
Built
Chimney
Barometric Draft
Control*
(in either location)
Barometric Draft
Control*
(in either location)
Factory−
Built
Chimney
Condensate
Drain
*Barometric draft control may be installed in either vertical or horizontal section of flue pipe no less than 12" and no more than 18" from furnace flue outlet.
13 − The vent pipe shall not be connected to a chimney
vent serving a solid fuel appliance or any mechanical draft system.
14 − All unused chimney openings should be closed.
15 − All vent pipe run through unconditioned areas or out-
side shall be constructed of factory built chimney sec­tions. See figure 10.
16 − Where condensation of vent gas is apparent, the vent
should be repaired or replaced. Accumulation of con­densation in the vent is unacceptable.
17 − Vent connectors serving this appliance shall not be
connected into any portion of mechanical draft sys­tems operating under positive pressure.
18 − Keep the area around the vent terminal free of snow,
ice and debris.
Page 10
Page 10
NOTE − If vent pipe needs to exit from side of cabinet, use the pilot hole (located on either side of the unit) to cut a 6" (152 mm) round hole. Attach finishing plate (provided) with four sheet metal screws to cover rough edges.
Removal of Unit from Common Venting System
In the event that an existing furnace is removed from a venting system commonly run with separate appliances, the venting system is likely to be too large to properly vent the remaining attached appliances. The following test should be conducted while each appliance is in operation and the other appliances not in operation remain con­nected to the common venting system. If venting system has been installed improperly, the system must be cor­rected as outlined in the previous section.
1 − Seal any unused openings in the common venting
system.
2 − Visually inspect venting system for proper size and
horizontal pitch and determine there is no blockage or restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
3 − Insofar as is practical, close all building doors and win-
dows and all doors between the space in which the ap­pliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliances not con­nected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom ex­hausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace damp­ers.
4 − Following the lighting instruction on the unit, place the
appliance being inspected in operation. Adjust ther­mostat so appliance will operate continuously.
5 − Test for spillage using a draft gauge.
6 − After it has been determined that each appliance re-
maining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other fuel burning appliance to its previous condi­tion of use.
7 − If improper venting is observed during any of the
above tests, the common venting system must be cor­rected.
Flue Connections
IMPORTANT
When flue pipe is installed at less than minimum clearance listed in table 2, radiation shields must be installed. See figure 11.
For front flue models, the enclosed exhaust pipe ring may be used for pipe to exit the left or right side of cabinet. Cen­ter line marks are provided in cabinet.
Use 24 gauge or heavier galvanized smoke pipe and fit­tings to connect furnace to vent. Connect flue pipe to chim­ney using the least number of elbows and angles possible. Flue pipe or vent connector must be inserted into the chim­ney so that it is flush with the inside of the vent liner. No re­duction in diameter of flue pipe is acceptable. It is best to have flue pipe as short and direct as possible. Where two or more appliances vent into a common flue, the area of the common flue should be at least equal to the area of the larg­est flue or vent connector, plus 50% of the area of any addi­tional flues or vent connectors. Install the barometric draft control (provided) and flue pipe according to instructions packed with control.
Inspect flue pipe annually. Clean soot or ash from flue pipe, if necessary. If pipe is rusted, replace.
Page 11
Page 11
A
1" (25 mm)
min
A
Figure 11
combustible
material
Radiation Shield Installation
SLO183B
unit
(top)
SLO183B
unit
(front)
radiation
shields
flue
pipe
B
unit
cabinet
NOTE 1−Radiation shields must be constructed of 24 gauge sheet metal minimum.
NOTE 2−Radiation shields required when A is less than 9" (229 mm).
NOTE 3−Radiation shields should extend from the top of the unit to the top of the flue pipe.
noncombustible
spacers
radiation shields
(see note 1)
12" (305 mm)
min
7" (178 mm)
min
see note 2
see note 3
Barometric Draft Control Installation
Install the provided barometric draft control in the flue pipe at least 12 inches beyond the furnace flue outlet to provide space for flue gas sampling. The barometric draft control may be installed in either vertical or horizontal sections of the flue pipe; however, it should be positioned no more than 18" beyond the furnace flue outlet. Follow the instruc­tions packed with the barometric draft control.
Alternate Side Flue Connections
The vent pipe may exit the top or sides of the cabinet. A hole is provided in the top cap for top exit. For side exit, lo­cate the center hole punched in the side of the cabinet. See unit dimensions on page 2. Using it as the center point, cut a 6 inch (152 mm) round hole in the cabinet’s side. Install the barometric draft control within 18 inches of the furnace flue outlet. Attach the provided finishing plate to cover rough edges.
Supply & Return Air Plenums
Secure return air plenum to unit using sheet metal screws.
NOTE − The following are suggested procedures that should be followed when installing the supply air plenum.
1 − Use sealing strips of fiberglass.
2 − In all cases, the plenum should be secured to furnace
or evaporator cabinet with sheet metal screws.
3 − Install supply and return air ducts as desired.
Oil Supply Line Sizing
Ensure that the restrictions of the piping system, plus any lift involved, do not exceed the capability of the oil pump. Use the following guidelines and table 5 when determining whether to use a single−or two−stage oil pump.
One−Pipe System
When using a one−pipe system with the oil tank above the burner, or a one−pipe system with no more than an 8−ft. (2.4m) lift and a vacuum of 6" (152 mm) Hg or less, a single− stage fuel pump with a supply line should be adequate with­out a separate return line. See figure 12. Manual bleeding of the fuel pump is required on initial start up. Failure to bleed air from the oil pump could result in an air lock/oil starvation condition.
NOTE − As an extra precaution, cycle heating on and off ten times after bleeding air from the oil pump. This will elimi­nate air in the gun assembly.
To determine pipe sizing for a one−pipe application, refer to table 3.
Figure 12
Oil Piping
Air Vent
Fill
Pipe
Oil
Tank
Fuel
Pump
Aux
Filter
Shut−Off
Valve
8 ft (2.4 m)
Maximum
Lift
One-Pipe System
Table 3
One−Pipe Oil Line Sizing
Line Length
Pipe Diameter (OD Tubing)
0−50’ (15 m) 3/8" (10 mm)
51−100’ (15 m) 1/2" (12 mm)
Two−Pipe System
When using a two−pipe system with the oil tank below the level of the burner, a single−stage fuel pump should be used in lift conditions of up to 10 feet (3 m) and/or a vacuum of 12" Hg or less. See figure 13. Use a two−stage fuel pump when lift exceeds 10 feet (3 m) and/or the vacuum is in the range of 12" Hg to 17" Hg.
Page 12
Page 12
Both conditions require that you use a two−pipe system, which consists of a return line that purges the fuel pump of air by returning it to the tank. To determine the run and lift for piping, refer to table 4.
Figure 13
Oil Piping
ООООООООООООО
ООООООООООООО
ООООООООООООО
ООООООООООООО
Fuel
Pump
Aux
Filter
Return
pipe
Fill
Pipe
Air Vent
Oil
Tank
Inlet
Return
Pipe
H
3"−4"
(76 mm −102 mm)
R
Outside tank fuel pump above bottom of tank
Two-Pipe System
Use continuous lengths of heavy wall copper tubing or steel pipe for oil supply pipe. Install oil supply pipe under floor or near walls to protect it from damage. Avoid running pipes along joists or reverberating surfaces. Always use flare fittings. All fittings must be accessible. Do not use compression fittings.
IMPORTANT
Both oil supply and return pipes must be submerged in oil in the supply tank.
Table 4
Two−Pipe Maximum Pipe Length (H + R)
Lift H"
3450 RPM − 3 GPH (11.4 LPH)
3/8" (10 mm) OD
Tubing
1/2" (12 mm) OD
Tubing
Single
Stage
Two
Stage
Single
Stage
Two
Stage
0’
(0.0 m)
84’
(25.6 m)
93’
(28.3 m)
100’
(30.5 m)
100’
(30.5 m)
2’
(0.6 m)
73’
(22.3 m)
85’
(25.9 m)
100’
(30.5 m)
100’
(30.5 m)
4’
(1.2m)
63’
(19.2 m)
77’
(23.5 m)
100’
(30.5 m)
100’
(30.5 m)
6’
(1.8m)
52’
(15.8 m)
69’
(21.0 m)
100’
(30.5 m)
100’
(30.5 m)
8’
(2.4m)
42’
(12.8 m)
60’
(18.3 m)
100’
(30.5 m)
100’
(30.5 m)
10’
(3.0m)
31’
(9.4 m)
52’
(15.9 m)
100’
(30.5 m)
100’
(30.5 m)
12’
(3.7m)
21’
(6.4 m)
44’
(13.4 m)
83’
(25.3 m)
100’
(30.5 m)
14’
(4.3m)
−−−
36’
(11.0 m)
41’
(12.5 m)
100’
(30.5 m)
16’
(4.9m)
−−−
27’
(8.2 m)
−−−
100’
(30.5 m)
18’
(5.5m)
−−− −−− −−−
76’
(23.2 m)
Table 5
Fuel Pump Usage
Pump Piping Application Maximum Lift (vacuum)
Single−Stage Pump
One−Pipe System 8 ft. (6" Hg vacuum)
Two−Pipe System 10 ft. (12" Hg vacuum)
Two−Stage Pump Two−Pipe System
10 ft. or greater
(12" to 17" Hg vacuum)
Page 13
Page 13
Oil Supply Line & Filter Connections
One−Pipe Systems
CAUTION
Do not install the bypass plug into the pump on one− pipe systems.
The burner is shipped with a single−stage fuel pump set for one−pipe operation. For one−pipe systems, the oil supply pipe is connected to the inlet tap on the pump. A one−pipe system should only be used where there is gravity oil flow to the pump or there is no more than 8 ft. of vertical lift (or 6 in. Hg) from the oil tank to the fuel pump.
1 − Connect the inlet pipe to the pump inlet. Start the burner. 2 − Turn the bleed valve one turn counterclockwise. 3 − Bleed the unit until all air bubbles disappear.
NOTE − Hurried bleeding will prevent the unit from op­erating properly.
4 − If necessary, put GeniSyst primary control into its
4−minute pump priming mode. Refer to table 10.
5 − Tighten the bleed valve securely. Two−Pipe Systems (Figure 13)
If the installation requires a two−pipe operation, install the bypass plug included in the bag which is attached to the pump. To convert the pump, install the bypass plug accord­ing to the provided pump instructions. Notice in the two-pipe system the return pipe must terminate in the tank 3" (76 mm) to 4" (102 mm) above the supply inlet. Ensure the return pipe terminates at the correct measurement or air may escape into the system. This could result in loss of prime.
NOTE− If using an outside tank in cold climates a number one fuel or an oil treatment is strongly recommended. Con­tact your oil supplier for oil treatment, if necessary.
1 − Remove 1/4" plug from return port. 2 − Insert bypass plug and tighten it. 3 − Attach the return and inlet pipes. Start the burner. Air
bleeding is automatic.
NOTE − If a faster bleed is necessary, open the bleed valve.
4 − The return pipe must terminate 3" to 4" above the sup-
ply pipe inlet.
NOTE − If the return pipe does not terminate where it should, air may enter the system, and prime may be lost.
An oil filter is required for all models. Install filter inside the building between the tank shut-off valve and the burner. Locate filter close to (but at least 3 feet away from) the burn­er for easy maintenance. Table 6 lists the filters for the SLO183B furnace.
Consult the burner manufacturer’s instructions that are in­cluded with the unit for further details concerning oil supply pipe connections.
Table 6
Oil Filters (All Models)
Oil Filters
Cat.
Number
10 micron filter (no mounting bracket) 81P89
10 micron filter (mounting bracket) 53P92
10 micron replacement cartridge for filter, 45 gph 53P93
Filter restriction indicator gauge 53P90
Leak Check
After oil piping is completed, carefully check all piping con­nections (factory and field) for oil leaks.
Oil Line Heater (Optional)
A heater for the oil pipe is available for applications that are located in cold climates. The heater warms the oil pipe to assist the initial start−up. An oil line heater is available from Beckett using part number 51621 (Beckett Start Helper).
Electrical Wiring
All wiring must conform to the National Electric Code (NEC), or Canadian Electric Code (CEC) and any local codes. Refer to figure 14 for typical unit wiring diagram. See figures and for field wiring. Refer to figure 18 for termi­nal designations on blower control.
1 − Refer to appliance rating plate for proper fuse size. 2 − Install room thermostat and make wire connections to
the fan control board. Avoid installing thermostat on an outside wall or where it can be affected by radiant heat. Set the adjustable heat anticipator on thermostat ac­cording to the wiring diagram sticker provided on unit.
3 − Install a separate fused disconnect switch near unit so
power can be shut off for servicing.
4 − Complete line voltage wiring from disconnect switch
near unit to make-up box.
NOTE − An equipment ground screw is provided. Refer to unit wiring diagram. Ground unit using a suitable ground wire.
5 − Any 120V accessory rated up to 1 amp can be con-
nected to the EAC terminal on the A15 ST9103A con­trol. The EAC terminal is energized when the blower is in operation.
6 − A 24V dehumidistat or ComfortSense
®
7000 input (from terminal D) can be connected to the reverse−act­ing HUM terminal on the A54 blower control. See figure
18.
Page 14
Page 14
WARNING
Run 24V Class II wiring only through specified low voltage opening. Run line voltage wiring only through specified high voltage opening. Do not com­bine voltage in one opening.
CAUTION
Use copper conductors only.
IMPORTANT
If using a programmable thermostat, be sure to use a type of thermostat that retains its memory in event of a power loss.
Figure 14
Typical SLO183BV Wiring Diagram
OIL DELAY
A15
A54
9
1
ST9103A
Page 15
Page 15
Figure 15
Field Wiring Diagrams
1 Heat / 1 Cool
ComfortSense
®
7000 L7724U
1 Heat / 2 Cool
ComfortSense® 7000 L7724U
1 Heat / 1 Cool
ComfortSense® 7000 L7724U
with Thermostat Dehumidification Mode
1 Heat / 2 Cool
ComfortSense
®
7000 L7724U
with Thermostat Dehumidification Mode
Page 16
Page 16
Figure 16
Field Wiring Diagrams (Continued)
Dual Fuel Single−Stage Heat Pump
ComfortSense
®
7000 L7724U
with Dual Fuel Control Mode
Dual Fuel Two−Stage Heat Pump
ComfortSense
®
7000 L7724U
with Dual Fuel Control Mode
Dual Fuel Two−Stage Heat Pump
ComfortSense
®
7000 L7724U
with Dual Fuel Control Mode
and Thermostat Dehumidification Mode
Page 17
Page 17
Blower Control (A54)
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
SLO183BV units are equipped with a variable speed blow­er motor which is capable of maintaining a specified CFM throughout the external static range. The blower motor is controlled by jumper selections made on the A54 blower control. Jumpers are available to select both heating and cooling blower speeds, as well as adjustment rates for cooling blower speeds and a test mode. Blower control set­tings and operation are described in this section.
The units are factory−set for nominal airflow for each mod­el. Figure 18 shows the blower control. Use table 7 to deter­mine the correct air volume for operation in heat and cool mode.
Read this section thoroughly before adjusting the jumpers to obtain the appropriate blower speed.
To change jumper positions, gently pull the jumper off the pins and re−position it across the pins that will give the desired blow­er speed. The following section outlines the different jumper selections available and conditions associated with each one (see figure 18).
IMPORTANT
The unit is not designed for use with the Harmony zone control system.
COOL (single-stage systems)
The COOL jumper is used to determine the CFM during cooling operation. This jumper selection is activated for cooling when Y1 is energized. A factory−installed jumper from Y1 to Y2 allows single−stage cooling.
The blower motor runs at 82% CFM for the first 7−1/2 min­utes of each cooling demand to allow for greater humidity removal and to conserve energy. If, after 7−1/2 minutes, the Y demand is not met, 100% CFM is supplied until the de­mand is satisfied.
OFFCALL
100%
82%
Y
60 sec
7.5 minutes
82%
y
Y − Cool Demand Present
y − Cool Demand Satisfied
When the demand for cool is met, the blower ramps down to 82% CFM for 60 seconds, then turns off.
COOL (two-stage systems)
This unit is factory−wired for single−stage cooling. For two−stage cooling operation, you must cut the jumper wire from Y1 to Y2 on the A54 blower control. Cut the
jumper close to the Y1 terminal to allow a pigtail connection with the remaining wire from the Y2 terminal and a wire connected to the Y2 terminal of the two−stage thermostat. Refer to field wiring diagrams.
A thermostat call for first-stage cooling closes the R to Y1 circuit on the A54 blower control. The blower motor runs at 57% CFM for the first 7−1/2 minutes of the 1st−stage cooling demand. After 7−1/2 minutes, the blower motor runs at 70% CFM until the first−stage demand is satisfied.
OFFCALL
100%
70%
57%
Y1
7−1/2 minutes
60 sec
y2/Y1
Y1 − 1st−stage COOL Demand Present y1
− 1st−stage COOL Demand Satisfied Y2 − 2nd−stage COOL Demand Present y2
− 2nd−stage COOL Demand Satisfied
Y1/Y2
70%
57%
y1
y1
OFF
60 sec
If first−stage cooling does not satisfy the demand, the ther­mostat calls for 2nd-stage cooling, closing the R to Y2 cir­cuit on the A54 blower control. The blower motor ramps up to 100% CFM.
When the Y2 demand is met, the blower ramps down to Y1 at 70% CFM until Y1 is met, and ramps down to 57% CFM for 1 minute, then turns off.
Heat Pump
IMPORTANT
For heat pump operation, cut the jumper between R and O near the R terminal of A54 and connect the pig­tail to the thermostat O wire (A54 board O" to ther­mostat O"). See figure 17.
In heat pump mode, a call for heat pump operation follows the same sequence as a call for cooling, with the exception that there is a 30−second blower ramp−up to blower CFM.
Figure 17
A54
A15
Heat Pump Applications
Clip red jumper from R to O close to R terminal.
Make pigtail connection and run wire from terminal O to O terminal on thermostat.
To blower
motor
Page 18
Page 18
ADJUST
The ADJUST pins affect blower motor speed during cool­ing operation only. The ADJUST feature allows the motor to run at normal speed, approximately 15% higher than nor­mal speed, or 15% lower than normal speed during the cooling mode. Table 7 gives three rowsNORM, (+), and (–) with their respective CFM volumes. Notice that the nor­mal NORM" adjustment setting for cool speed position C in table 7 is 800 CFM. The (+)" adjustment setting for that position is 920 CFM (115% of 800 CFM) and the (–)" ad­justment setting is 680 CFM (85% of 800 CFM). After the adjustment setting has been determined, choose the re­maining speed settings from those offered in the table in that row.
HEAT
The unit is factory−set to run at the middle of heating rise range as shown on the unit rating plate. The jumper on the tap marked HEAT must remain in the position given in table
7. The HEAT jumper is used to determine CFM during heating
operation only. These jumper selections are activated only when W1 is energized.
During the heat ON delay, the blower runs at 13% CFM for the first minute, 50% CFM for the second minute, and full CFM after two minutes.
OFFCALL
100%
82%
50%
13%
W
60 sec60sec
210 seconds
w
W − Heat Demand Present
w − Heat Demand Satisfied
When the demand for heat is met, the blower ramps down to 82% CFM for 3−1/2 minutes, then turns off.
TEST
The TEST pin is available to bypass the blower control and run the motor at approximately 70% to make sure that the motor is operational. This is used mainly in troubleshoot­ing. The G terminal must be energized for the motor to run.
CFM LED
The CFM LED located on the blower control flashes one time per 100 cfm to indicate selected blower speed. For ex­ample, if the unit is operating at 1000 CFM, the CFM LED will flash 10 times.
At times, the light may appear to flicker or glow. This takes place when the control is communicating with the motor be­tween cycles. This is normal operation.
After the CFM for each application has been determined, the jumper settings must be adjusted to reflect those given in table 7. From the table, determine which row most close­ly matches the desired CFM. Once a specific row has been chosen (+, NORMal, or −), CFM volumes from other rows cannot be used. Below are descriptions of the jumper selections.
The variable speed motor slowly ramps up to and down from the selected air flow during both cooling and heating demand. This minimizes noise and eliminates the initial blast of air when the blower is initially energized.
Continuous Fan
When the thermostat is set for Continuous Fan" operation and there is no demand for heating or cooling, the blower control will provide 50% of the COOL CFM selected.
OFFCALL
50%
G
g
G − Fan switch ON
g − Fan switch OFF
NOTE − With the proper thermostat and subbase, continu­ous blower operation is possible by closing the R to G cir­cuit.
Dehumidification
The A54 blower control (see figure 18) includes a HUM ter­minal which provides for connection of a humidistat. The JW1 jumper on the blower control must be cut to activate the HUM terminal. The humidistat must be wired to open on humidity rise. When the dehumidification circuit is used, the variable speed motor will reduce the selected air flow rate by 18% when humidity levels are high. An LED (D1) lights when the blower is operating in the dehumidification mode.
Humidification
Terminals are provided on the A15 control for 120 volt out­put to operate a humidifier. The HUM" terminal is ener­gized when there is a call for heat. See figure 14.
Indoor Air Quality (IAQ) Accessory
An EAC terminal is provided on the A15 control for 120 volt output to an indoor air quality accessory. The EAC terminal is energized when there is a call for heat, cool, or continu­ous blower. See figure 14.
Page 19
Page 19
Table 7
Blower Performance
(0 through 0.50 in. w.g. External Static Pressure Range)
ADJUST"
Jumper
Setting
HEAT" Jumper Speed Position [kBtuh heat input] COOL" Jumper Speed Position
A B C D
A
B
C D
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
Model SLO183BV101/114V42 Units
Do not use [−114] Do not use [−101]
(+)
N/A N/A
Same as
NORM
N/A N/A
Same as
NORM
1610 760 1380 650 1150 540 920 435
NORM
N/A N/A 1450 684 N/A N/A 1200 565 1400 660 1200 565 1000 470 800 380
(–)
N/A N/A
Same as
NORM
N/A N/A
Same as
NORM
1190 560 1020 480 850 400 680 320
Model SLO183BV135/150V60 Units
Do not use [−150] Do not use [−135]
(+)
N/A N/A
Same as
NORM
N/A N/A
Same as
NORM
2300 1085 2070 975 1840 870 1380 650
NORM
N/A N/A 1730 816 N/A N/A 1450 684 2000 945 1800 850 1600 755 1200 565
(–)
N/A N/A
Same as
NORM
N/A N/A
Same as
NORM
1700 800 1530 720 1360 640 1020 480
NOTE − Continuous Fan air volume is 50% of COOL speed.
Blower Control (A54)
Figure 18
16−PIN PLUG
(BOARD TO MOTOR)
CFM LED
ADJUST SELECTOR PINS (Setting affects cooling only)
HEATING SPEED SELECTOR PINS (SEE TABLE)
COOLING SPEED SELECTOR PINS
NOTE − The JW1 resistor must be cut to activate the HUM terminal.
SLO183B3/4−12 0
SLO183B3/4−10 5
SLO183B5−135
SLO183B5−150
HEAT SPEED PINS (JUMPERS)
NOTE − Do NOT move heat speed jumpers from factory settings.
Start−Up & Adjustment
Before starting unit, make sure the oil tank is adequately filled with clean No. 1 or No. 2 furnace oil.
NOTE − Water, rust or other contaminants in oil supply sys­tem will cause malfunction and failure of the internal parts of the fuel unit.
CAUTION
Never burn garbage or paper in the heating system. Never leave papers near or around the unit.
CAUTION
Blower access door must be in place before start-up.
Page 20
Page 20
Burner Start−Up
1 − Set thermostat for heating demand and turn on electri-
cal supply to unit.
2 − Open all shut−off valves in the oil supply line to the
burner.
3 − While the ignition is on, press and release the reset
button on the burner control (hold 1/2 second or less).
4 − Bleed the pump until all froth and bubbles are purged.
The bleed port is located on the bottom of the fuel pump. To bleed, attach a clear plastic hose over the vent plug. Loosen the plug and catch the oil in an empty container. Tighten the plug when all the air has been purged.
NOTE − A two−line fuel system will normally bleed itself by forcing air back to the tank through the return line. This type of bleeding procedure is not necessary.
5 − If burner fails to start within the set time, the burner
control will lock out operation. Press the reset button to reset the control as in step 3. See figure 2 for burner parts arrangement.
CAUTION
Do not push the reset button on the primary control more than one time.
6 − Repeat steps 4 and 5, if necessary, until pump is fully
primed and oil is free of bubbles. Then, terminate the call for heat. The burner control will resume normal op­eration
Fuel Pump Pressure Adjustment
Measure fuel pump pressure with unit off. Attach pressure gauge to pump outlet. Turn unit on and check pressure and compare to table 9. Adjust if necessary.
Temperature Rise Adjustment
To measure temperature rise, place plenum thermometers in warm air and return air plenums. Locate thermometer in warm air plenum where thermometer will not see" the heat exchanger to prevent it from picking up radiant heat. Set thermostat to its highest setting to start unit. After plenum thermometers have reached their highest and steadiest readings, subtract the readings. The difference in tempera­tures in the supply and return air plenums should approxi­mate the temperatures listed in table 8 and on the ap­pliance rating plate.
If the temperature rise is not within the range listed, check the following items:
D Make sure that properly sized nozzle has been
used (table 9).
D Make sure that fuel pump pressure is correct. D If furnace is in cutback mode, check for:
Dirty filters, Dirty indoor coil, Restricted ducts, closed registers, etc.
Table 8
Temperature Rise
Unit Temperature Rise °F
SLO183BV101 65 − 75
SLO183BV114 70 − 80
SLO183BV135 65 − 75
SLO183BV150 70 − 80
Limit Control
Limit Control  Do not adjust from factory setting.
Burner Adjustment
The following instructions are essential to the proper op­eration of SLO183BV series oil furnaces. To prevent soot­ing, these instructions must be followed in sequence:
1. DraftThis test should be taken at the breach be-
tween the outlet of the vent connector and the baro­metric draft control. Generally a 1/4" hole will need to be drilled for the draft gauge to be inserted into the vent connector.
A minimum of 0.03 draft must be established without the burner in operation. With the burner in operation, the draft should be 0.04 to 0.05. This is VERY critical to the flame retention head burners.
Oil furnace installations also require careful inspection to make sure the chimney is in good shape and can ac­commodate the products of combustion. The tempera­ture in the unconditioned space will also affect the draft if long vent connectors are allowed to get too cold.
2. Overfire DraftThis test should be taken with the
burner in operation. Remove the plug from the center of the inspection port. Insert your draft gauge into the hole.
A reading of the overfire draft should be 0.02 less than the reading found in the vent connector. If a positive reading is seen at this point, the combustion fan is pumping too much air into the heat exchanger. Make the necessary adjustments with the air shutter or air band.
Page 21
Page 21
Table 9
Burner Specifications
Unit
Burner
Number
Beckett
Spec. No.
Beckett
Air Tube Part
No.
Input
Rating
BTU/HR
Nozzle Size,
Spray, Angle, &
Pattern
Pump
Pres-
sure
Head
Insertion
Length
Static
Plate
Diameter
SLO183B3/4−101/114V 100591−05 ARM2008 AF46XNHS 101,000 0.65gph X 80° B 140 F3 4−3/4 2−3/4
SLO183B3/4−101/114V 100591−05 ARM2008 AF46XNHS 114,000 *0.65gph X 80° B 140 F3 4−3/4 2−3/4
SLO183B5−135/150V 100591−06 ARM2009 AF46WPHS 135,000 1.00gph x 80° 140 F4 4−3/4 3−3/8
SLO183B5−135/150V 100591−06 ARM2009 AF46WPHS 150,000 *1.00gph X 80° B 140 F4 4−3/4 3−3/8
*Nozzle must be field−installed for conversion to higher heating input. NOTE − All nozzles are Delavan brand.
Air Band
(Secondary)
Air Shutter / Band Adjustment
Loosen this screw to adjust air band.
Air Shutter
Air Band
Figure 19
3. Smoke TestThe smoke test should be taken at the
hole drilled in step 1. Using a smoke test gun, adjust the air so that you will
have just a trace (between 0 and #1) of smoke. If the burner is producing more than #1 smoke, adjust the air shutter (primary) and air band (secondary) to reduce the smoke. See figure 19. To adjust the air shutter, loosen the top screw on the air shutter (and lower screw, if necessary). Then, rotate the shutter until the desired smoke level is achieved. If smoke cannot be reduced to the desired level by moving the air shutter, adjust the air band to increase the air. To adjust the air band, loosen the air band screw and rotate the band.This is the starting point. Do not stop here.
4. CO
2
TestAgain, take this sample at the vent pipe.
With the unit firing at a trace of smoke, take a sample of the CO
2
. From the results of this test, a window of op­eration" will be determined. This window of operation establishes some tolerance. The tolerance the installer builds in provides room within the set-up for those things which might affect combustion. Those things which might affect combustion can then do so without
causing the unit to start sooting/smoking. Things which might affect combustion include a nozzle going bad, draft that changes during different climatic conditions, dirty oil, dirt obstructing the air inlet, etc.
To build in a window of operation," set up the burner to be 2% less in CO
2
. For example, if you find a reading of
12% CO
2
, adjust the air shutter (and air band, if neces-
sary) to increase the air and drop the CO
2
to 10%.
5. Retest the SmokeWith a drop in the CO
2
and in­crease in the air you should see that the smoke has re­turned to 0.
6. Retest the Overfire DraftThis test serves to confirm
that you have not increased the air too much. Again you do not want a positive pressure at the test port. It should still be 0.02 less than the draft pressure reading taken at the breach. You may need to increase the stack draft by adjusting the barometric draft control.
7. Stack TemperatureTake a stack temperature read-
ing in the vent pipe. Subtract the room air temperature from the stack temperature. This will give you the net stack temperature. Use the efficiency charts provided in most CO
2
analyzers to determine furnace efficiency.
8. When the proper combustion and smoke readings have been achieved, re−tighten the air shutter screw(s) and air band screw.
Service
A − Servicing Filter
NOTE − Under no circumstances should the access panels to the blower compartment be left off or left partially open.
1 − Throw-Away Type Filters  Filters should be checked
monthly and replaced when necessary to assure prop­er furnace operation. Replace filters with like kind and size filters.
2 − Reusable Type Filters  Filters should be checked
monthly and cleaned when necessary to assure prop­er furnace operation. Use warm water and a mild de­tergent. Replace filter when dry. Permanent filters supplied with SLO183B furnaces do not require oiling after cleaning. Examine filter label for any for special instructions that may apply.
Page 22
Page 22
B − Blower
Blower motor is pre-lubricated and sealed for extended op­eration. No further lubrication is required. Disconnect pow­er to unit before cleaning blower wheel for debris.
C − Flue Pipe Inspection
The flue pipe should be inspected annually by a qualified service technician. Remove and clean any soot or ash found in the flue pipe. Inspect pipe for holes or rusted areas. If replacement is necessary, replace with the same size and type as required by code. Inspect the flue baro­metric draft control and replace if found to have failed.
D − Cleaning Heat Exchanger
1 − Remove the vent pipe from the furnace. 2 − Remove the locking screws and the caps from the
clean out tubes. Remove flue access elbow.
3 − Using a long spiral wire brush, sweep down the outer
drum of the heat exchanger. Then using the hose at­tachment, vacuum out loose debris.
4 − Remove the locking screw and cap from the observa-
tion tube and with the spiral wire brush, reach upward toward the rear of the heat exchanger to clean out the crossover tube.
CAUTION
Do not attempt to clean the combustion chamber. It can be easily damaged.
5 − Replace the clean out caps and flue access elbow.
Make sure locking screws are secure.
6 − Brush out and vacuum the vent outlet area of the outer
drum and replace vent pipe.
7 − Clean around burner, blower deck and vestibule area.
NOTE − A heat exchanger clean-out kit ABRSH380 (35K09) is available from Lennox. The kit includes a ra­diator brush, a tapered brush and a non−metallic 36" spiral wire handle.
GeniSyst Primary Burner Control
SLO183B units are equipped with the Beckett GeniSyst 7505B primary burner control. The control is positioned on the upper right−hand side of the Beckett AFG burner as­sembly. The control includes a reset button and three sta-
tus lights. See figure 20 for location of reset buttons and status lights. Table 10 details reset button operation. Table 11 details status light function.
Additional information on the GeniSyst 7505B primary burner control is provided with this furnace.
Figure 20
Beckett GeniSyst 7505B Primary Burner Control
Reset Button
with Red Status Light
Yellow Pump
Prime Status Light
Green Flame
Status Light
FRONT VIEW
Wiring
Connections
REAR VIEW
Cad Cell
Connections
Page 23
Page 23
If the burner is in the
below state:
Pushing the reset button will:
Button Click
(press < 1 second)
Button Hold
(press > 1 second)
Button Hold
(press 15+ seconds)
tuokcoLtfoSmorfteseRtuokcoL
Reset from Restricted (Hard) Lockout
Valve−on Delay, Trial for Ignition, Ignition Carryover
Go to pump prime (see Priming the Pump" above)
Disable the Burner: Any time the burner is running, press and hold the reset button to disable the burner. The burner will remain off as long as the button is held.
Enables pump priming After the reset button has been held for 15 seconds. The button can then be clicked during the next ignition sequence to enter pump prime mode.
Run (igniter is shut off) No action
No action
Pump Prime No action Exit Pump Prime mode and return to Standby
gnihsalFylsuounitnoCnOroloCthgiL
tuokcoLtfoStuokcoL)draH(detcirtseRde
R
Green
Flame Sensed during normal operation (Could be stray light during standby)
Recycle
Yellow
Control is in pump prime mode or
N/A
Table 10
Reset Button Operation
Table 11
Status Light Function
Reset button currently held for 15+ seconds.
Page 24
Page 24
Heating Sequence − Actions & Responses
1. Action: Thermostat calls for heat (W terminal is en-
ergized)
Response:
D ST9103A control (A15) closes oil primary control
TR−TW contacts.
D After 15−second prepurge, power is sent to the oil
delay valve, ignition occurs and flame is established.
D Igition sequence continues for 10 seconds after
flame is sensed. Oil will continue to flow as long as cad cell senses flame.
D Heat fan on ramp timing begins. When timing is
complete, the indoor blower is at heat speed and warm air is delivered to the controlled space.
2. Action: Thermostat ends call for heat (W terminal is
de−energized)
Response:
D After the thermostat is satisfied, the thermostat
circuit opens. The oil delay valve and burner are de−energized.
D Burner is de−energized. D Heat fan off ramp timing begins. When timing is
complete, indoor blower is de−energized.
D Blower control returns to standby mode (oil prima-
ry control and indoor blower are off).
3. Action: Burner fails to light
Response:
D Oil primary control enters soft lockout after ignition
failure (15 seconds without flame being sensed). Push reset button on primary control for one sec­ond to reset soft lockout.
D After soft lockout reset, oil primary control allows
second ignition attempt. Primary control enters hard lockout after second ignition failure (15 sec­onds without flame being sensed). Push reset but­ton on primary control for 15 seconds until light on control turns yellow to reset hard lockout.
D Burner motor is de−energized.
4. Action: Established flame fails
Response:
D Burner motor is de−energized and oil primary con-
trol goes into recycle mode.
D If the fan off delay is longer than the recycle timing,
the indoor blower continues to run on heating speed through the next trial for ignition.
5. Action: Limit Switch Opens
Response:
D Oil primary control de−energizes burner. D Indoor blower is energized immediately at cool
speed.
D A15 control opens oil primary control TR−TW con-
tacts.
D Indoor blower runs as long as limit stays open.
6. Action: Limit Switch Closes
Response: If there is a heating demand, A15 control energizes oil primary control and ignition sequence be­gins.
Troubleshooting
Burner failure or improper operation can result from a num­ber of different causes. Often the cause can be pinpointed by observing the different types of failure or by the process of elimination. The following troubleshooting charts list some failures, causes and a sequence of steps to isolate the point of failure. Check the simplest and most obvious items before progressing to other items.
Page 25
Page 25
Troubleshooting: Blower Control Operating Sequence
Action System Response
Thermostat calls for heat. (W terminal is energized.)
ST9103A closes oil primary control TR−TW contacts.
Ignition system and oil primary control start the furnace. Oil flows as long as cad cell senses flame.
Call for heat energizes burner motor and blower ramping begins for heating mode. When ramping is complete, the indoor blower is energized at heat speed and warm air is deliv­ered to the controlled space.
Thermostat ends call for heat. (W terminal is de−energized.)
Oil primary control is de−energized, terminating the burner cycle.
Heat fan off delay timing begins. When timing is complete, the indoor blower is de−ener­gized.
ST9103A returns to standby mode (oil primary control and circulating fan are off).
Burner fails to light. Oil primary control locks out within lockout timing (timing depends on oil primary control).
Burner motor is de−energized.
If heat fan has started, it continues through the selected delay off period.
Established flame fails. Burner motor is de−energized and oil primary control goes into recycle mode.
If selected heat fan off delay is longer than the recycle delay timing, the heat fan contin­ues to run through the next trial for ignition.
Thermostat begins call for cool. (G and Y terminals are energized.)
Indoor blower is energized at the cool speed.
Cooling compressor turns on immediately.
Thermostat ends call for cool. (G and Y terminals are de−energized.)
Cooling compressor turns off immediately and indoor blower speed ramps down. Circulat­ing fan shuts off after 60 seconds.
Thermostat begins call for fan. (G terminal is energized.)
Indoor blower is energized immediately at 50% of cool speed.
ST9103A may be factory−configured to operate heat speed in this mode.
Thermostat ends call for fan. (G terminal is de−energized.)
Indoor blower is de−energized.
Limit switch string opens. Oil primary control shuts off the burner.
Indoor blower is energized immediately at heat speed.
ST9103A opens oil primary control TR−TW contacts.
Indoor blower runs as long as limit string stays open.
If there is a call for cooling or fan, the indoor blower switches from heat speed to cool speed.
Limit switch string closes. ST9103A begins heat fan off delay sequence.
Indoor blower turns off after the selected heat fan off delay timing.
ST9103A closes oil primary control TR−TW contacts.
Oil primary control is energized, initiating burner ignition.
Continuous circulating fan is connected. (Optional connectors are available for separate circu­lating fan speed tap.)
Indoor blower is energized at 50% of cool speed when there is no call for heat, cool or fan.
If fan operation is required by a call for heat, cool, or fan, the ST9103A switches off the continuous fan speed tap before energizing the other fan speed.
IAQ accessory is connected. (Optional connectors are available for 120 Vac acces­sories.)
EAC terminals (for IAQ accessories) are energized when the indoor blower is energized in either the heat or cool speed. EAC terminals are not energized when the optional con­tinuous fan terminal is energized.
Humidity control is connected. (Optional connectors are available for 120 Vac humidi­fier.)
Humidifier connections are energized when the burner motor is energized.
Page 26
Page 26
Troubleshooting: Burner fails to start.
Source Procedure Causes Correction
Thermostat Check thermostat settings.
Thermostat in OFF or COOL Switch to HEAT.
Thermostat is set too low
Turn thermostat to higher tem­perature.
Safety Overloads
Check burner motor, primary safety control, & auxiliary limit switch.
Burner motor overload tripped Push reset button pump motor.
Primary control tripped on safe­ty
Reset primary control.
Auxiliary limit switch tripped on safety
Reset auxiliary limit.
Power
Check furnace disconnect switch & main disconnect.
Open switch Close switch.
Blown fuse or tripped circuit breaker
Replace fuse or reset circuit breaker.
Thermostat
Touch jumper wire across TR− TW terminals on primary control. If burner starts, then fault is in the thermostat circuit.
Broken or loose thermostat wires
Repair or replace wires.
Loose thermostat screw con­nection
Tighten connection.
Dirty thermostat contacts Clean contacts.
Thermostat not level Level thermostat.
Faulty thermostat Replace thermostat.
Open circuit in wiring between ST9103A and oil primary con­trol.
Check wiring between ST9103A and oil primary control.
Cad Cell
Disconnect the flame detector wires at the primary control. If the burner starts, fault is in the detector circuit.
Flame detector leads are shorted
Separate leads.
Flame detector exposed to light Seal off false source of light.
short circuit in the flame detec­tor
Replace detector.
Primary Control
Place trouble light between the orange and white leads. No light indicates that no power is going to the control.
Primary or auxiliary control switch is open
Check adjustment. Set the maximum setting.
Jumper terminals; if burner starts, switch is faulty, replace control.
Open circuit between discon­nect switch and limit control
Trace wiring and repair or re­place it.
Low line voltage or power fail­ure
Call the power company.
Place trouble light between the orange and white leads. No light indicates faulty control.
Failed internal control circuit Replace the control.
Burner
Place the trouble light between the orange and white leads to the burner motor. No light indi­cates that no power is getting to the motor.
Blown fuse Replace the fuse.
Place trouble light between the black and white leads to the blower motor. Light indicates power to the motor and burner fault.
Binding burner blower wheel
Turn off power and rotate the blower wheel by hand. If seized, free the wheel or replace the fuel pump.
Seized fuel pump
Failed burner motor Replace the motor.
Page 27
Page 27
Troubleshooting: Burner starts, but no flame is established.
Source Procedure Causes Correction
Oil Supply
Check tank gauge or use dip stick.
No oil in tank Fill tank.
Coat dip stick with litmus paste and insert into bottom of tank.
Water in oil tank
If water depth exceeds 1 inch, pump or drain water.
Listen for pump whine. Tank shut−off valve closed Open valve.
Oil Filters & Oil Line
Listen for pump whine.
Oil line filter is plugged Replace filter cartridges.
Kinks or restriction in oil line Repair or replace oil line.
Plugged fuel pump strainer Clean strainer or replace pump.
Open bleed valve or gauge port. Start the burner. No oil or milky oil indicates loss or prime.
Air leak in oil supply line
Locate and correct leak.
Tighten all connections.
Oil Pump
Install pressure gauge on pump and read pressure. Should not be less than 140 psi.
Pump is partially or completely frozen. No pressure and the motor locks out on overload.
Replace pump.
Coupling disengaged or broken
− no pressure
Re−engage or replace coupling.
Fuel pressure too low Adjust to 140 psi.
Nozzle
Observe the oil spray (gun as­sembly must be removed from unit). Inspect the nozzle for plugged orifice or carbon build− up around orifice.
Nozzle orifice plugged
Replace nozzle with the same size, spray angle, and spray pattern.
Nozzle strainer plugged
Poor or off center spray
Ignition Electrodes
Remove gun assembly and in­spect electrodes.
Fouled or shorted electrodes
Clean or replace electrodes.
Dirty electrodes
Eroded electrode tips
Clean electrode tips and use T−501 gauge to reset the gap to 5/32 inches and correctly posi­tion tips.
Improper electrode gap spacing
Improper position of electrode tips
Bad buss bar connection Retension and realign.
Cracked or chipped insulators Replace electrode.
Ignition
Transformer
Start burner and observe spark. Check line voltage to transform­er primary.
Low line voltage
Check voltage at power source. Correct cause of voltage drop or call the power company.
Burned out transformer wind­ings.
Replace the transformer.
No spark or weak spark
Properly ground the transformer case.
Burner Motor
Motor does not come up to speed and trips out on overload. Turn off power and rotate blower wheel by hand to check for bind­ing or excessive drag.
Low line voltage
Check voltage at power source. Correct cause of voltage drop or the call power company.
Pump or blower overloading motor
Correct cause of overloading.
Faulty motor Replace motor.
Page 28
Page 28
Troubleshooting: Burner starts and fires, but lock out on safety.
Source Procedure Causes Correction
Poor Fire
After burner fires, immedi­ately jumper across flame detector termi­nals at the pri­mary control.
If burner con­tinues to run, this may be due to poor fire. Inspect fire.
Unbalanced fire Replace nozzle
Too much air − −lean short fire
Reduce combustion air − check combustion.
Too little air − − long dirty fire
Increase combustion air − check combustion.
Excessive draft
Adjust barometric draft control for correct draft.
Too little draft or restriction
Correct draft or remove restric­tion.
Flame Detector
If fire is good, fault is in the flame detector. Check detec­tor circuit.
Faulty cad cell (open circuit) Replace cad cell.
Loose connections or broken cad cell wires
Secure connections or replace cad cell holder and wire leads.
Cad cell cannot sense flame
Check cad cell for proper align­ment. Check cad cell face and clean, if necessary.
Primary Control
If burner locks out on safety, fault is in the primary con­trol.
Primary control circuit failed Replace primary control.
Troubleshooting: Burner Starts and Fires, but Loses Flame and Lock Out on Safety
Source Procedure Causes Correction
Poor Fire
After burner fires, immedi­ately jumper across flame detector termi­nals at the pri­mary control.
If burner con­tinues to run (does not lock out of safety), fault may be due to poor fire. Inspect fire.
Unbalanced fire Replace nozzle
Too much air − − lean short fire
Reduce combustion air − check combustion.
Too little air − − long dirty fire
Increase combustion air − check combustion.
Excessive draft
Adjust barometric draft control for correct draft.
Too little draft or restriction
Correct draft or remove restric­tion.
Flame Detector
If fire is good, fault is in the flame detector. Check detec­tor circuit.
Faulty cad cell (open circuit) Replace cad cell.
Loose connections or broken cad cell wires
Secure connections or replace cad cell holder and wire leads.
Cad cell cannot sense flame
Check cad cell for proper align­ment. Check cad cell face and clean, if necessary.
Oil Supply
If burner loses flame (does not lock out on safety), fault is in the fuel sys­tem.
Pump loses prime − air slug Prime pump at bleed port
Pump loses prime − air leak in supply line
Check supply line for loose con­nections and tighten fittings.
Water slug in line Check oil tank for water (over 1
inch) pump or drain out water.
Partially plugged nozzle or nozzle strainer
Replace nozzle.
Listen for pump whine
Restriction in oil line Clear restriction.
Plugged fuel pump strainer Clean strainer or replace pump.
Cold oil − outdoor tank Change to number 1 oil.
Page 29
Page 29
Troubleshooting: Burner starts and fires, but short cycles (too little heat)
Source Procedure Causes Correction
Thermostat Check thermostat.
Heat anticipator set too low Correct heat anticipator setting.
Vibration at thermostat Correct source of vibration.
Thermostat in the path of a warm air draft
Shield thermostat from draft or relocate.
Limit Control
Connect voltmeter between line voltage connections to primary control (black & white leads). If burner cycles due to power inter­ruption, it is cycling on limit.
Dirty furnace air filters Clean or replace filter.
Temperature rise too high
Check fo proper nozzle size. Replace nozzle, if necessary. Check for restrictions and re­move, if necessary. Check speed tap jumper and make sure it is still in factory position.
Blower motor seized or burned out
Replace motor.
Blower wheel dirty Clean blower wheel.
Wrong motor rotation Replace motor.
Restrictions in return or supply air system
Correct cause of restriction.
Power
If voltage fluctuates, fault is in the power source. Recheck voltage at the power source.
Loose wiring connection Locate and secure connection.
Low or fluctuating line voltage Call power company.
Troubleshooting: Burner runs continuously (too much heat).
Source Procedure Causes Correction
Thermostat
Disconnect thermostat wires at the pri­mary control.
If burner turns off, fault is in the thermostat circuit.
Shorted or welded thermostat contacts
Repair or replace the thermo­stat.
Stuck thermostat bimetal
Clear obstruction or replace thermostat.
Thermostat not level Level thermostat.
Shorted thermostat wires Repair short or replace wires.
Thermostat out of calibration Replace thermostat.
Thermostat in cold draft
Correct draft or relocate the thermostat.
Primary control
If burner does not turn off, fault is in the primary control.
Failed primary control Replace the primary control.
Page 30
Page 30
Troubleshooting: Burner runs continuously (too little heat).
Source Procedure Causes Correction
Combustion
Check burner combustion for CO2, stack tem­perature, and smoke
Low CO
2
less
than 10%.
Too much combustion air Reduce combustion air.
Air leaks into heat exchanger around inspection door, etc.
Correct cause of air leak.
Excessive overfire draft
Adjust barometric draft con­trol for correct draft.
Incorrect nozzle assembly depth
Set to 1.13.
High smoke reading more than a trace.
Dirty or plugged heat exchanger
Clean heat exchanger.
Readjust burner.
Insufficient overfire draft Increase draft.
Incorrect nozzle assembly depth
Set to 1.13.
Too little combustion air Increase combustion air.
High stack tem­perature is more than 550
_F Net.
Low volume indoor blower air
Check pump coupling for wear / slippage.
Dirty heat exchanger Clean heat exchanger.
Dirty burner blower wheel Clean burner blower wheel.
Dirty furnace air filters Clean or replace filter.
Restricted or closed registers or dampers
Readjust registers or damp­ers.
Oil Pressure
Inspect fire and check
oil pressure.
Partially plugged or bad nozzle Replace nozzle.
Oil pressure is too low (less than 140 psi.)
Increase oil pressure to 140 psi.
Loading...