SL280DFV series units are 80% efficiency gas furnaces
used for downflow applications only, manufactured with
Lennox Duralok heat exchangers formed of aluminized
steel. Units are available in heating capacities of 66,000 to
110,000 Btuh and cooling applications up to 5 tons. Refer to
Engineering Handbook for proper sizing.
Units are factory equipped for use with natural gas. Kits are
available for conversion to LPG operation. SL280DFV mod
®
el units are equipped with the icomfort
two-stage variable speed integrated control. All units use a
redundant gas valve to assure safety shut-off as required by
CSA.
All specifications in this manual are subject to change. Pro
cedures outlined in this manual are presented as a recom
mendation only and do not supersede or replace local or
state codes. In the absence of local or state codes, the
guidelines and procedures outlined in this manual (except
where noted) are recommendations only and do not consti
tute code.
TABLE OF CONTENTS
SpecificationsPage 2.............................
Parts IdentificationPage 3.........................
I Unit ComponentsPage 4........................
II InstallationPage 29............................
III Start UpPage 29..............................
IV Heating System Service ChecksPage 31.........
V Typical Operating CharacteristicsPage 34.........
VI MaintenancePage 34..........................
enabled SureLight
SL280DFV
®
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, person
al injury or loss of life. Installation and service must
be performed by a licensed professional HVAC in
staller (or equivalent), service agency or the gas sup
plier.
WARNING
Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at discon
nect switch(es). Unit may have multiple
power supplies.
VII Wiring and Sequence of OperationPage 38......
VIII Program Unit Capacity Size ModePage 42......
IX Field Wiring and Jumper SettingsPage 43........
X Troubleshooting Flow ChartPage 47..............
Page 1
CAUTION
As with any mechanical equipment, contact with
sharp sheet metal edges can result in personal in
jury. Take care while handling this equipment and
wear gloves and protective clothing.
Wheel nominal diameter x width - in.10 x 811 x 911 x 10 11 x 10
Blower
Tons of add-on cooling2 - 33 - 43.5 - 53.5 - 5
Air Volume Range - cfm589 - 1514830 - 1996899 - 2273882 - 2120
Electrical
Data
Blower motor full load amps7.712.812.812.8
Maximum overcurrent protection15202020
Shipping Datalbs. - 1 package130153164173
NOTE - Filters and provisions for mounting are not furnished and must be eld provided.
1
Annual Fuel Utilization Efciency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
Model No. SL280DF070V36A SL280DF090V48B SL280DF090V60C SL280DF110V60C
1
AFUE80%80%80%80%
Input - Btuh66,00088,00088,000110,000
Output - Btuh52,00069,00070,00087,000
3.5 / 10.03.5 / 10.03.5 / 10.03.5 / 10.0
Input - Btuh43,00057,00057,00072,000
Output - Btuh35,00046,00046,00059,000
1.7 / 4.91.7 / 4.91.7 / 4.91.7 / 4.9
Cooling1.01.01.01.0
Gas pipe size IPS1/21/21/21/2
Motor output - hp1/2111
Voltage 120 volts - 60 hertz - 1 phase
OPTIONAL ACCESSORIES - MUST BE ORDERED EXTRA
“A” Width
Models
CABINET ACCESSORIES
Downow Combustible Flooring Base11M5911M6011M61
CONTROLS
ComfortSense® 7000 ThermostatY0349Y0349Y0349
Remote Outdoor Sensor (for dual fuel and Humiidtrol
®
)X2658X2658X2658
DOWNFLOW FILTER KITS
Downow Filter Kit51W0651W0751W08
No. and Size of lter - in.(1) 20 x 16 x 1(2) 20 x 20 x 1(2) 20 x 20 x 1
NIGHT SERVICE KITS
Night Service Kit16S3616S3616S36
Safety Service Kit89W19
“B” Width
Models
“C” Width
Models
89W1989W19
GAS HEAT ACCESSORIES
Models
Natural Gas to
LPG/Propane Kit
all11K5111K46
LPG/Propane to
Natural Gas Kit
Page 2
FLUE CHASE
CONTROL BOX
(Includes two-stage integrated control,
transformer and circuit breaker)
INTERNAL FLUE
PIPE ASSEMBLY
PARTS IDENTIFICATION
BLOWER ASSEMBLY
GASKET
SECONDARY LIMIT
DOOR INTERLOCK SWITCH
ROLLOUT SWITCH
INNER BLOWER ACCESS PANEL
ACCESS PANEL
PRIMARY LIMIT LOCATION
HEAT EXCHANGER
COMBUSTION AIR INDUCER
PRESSURE SWITCHES
COMBUSTION AIR INDUCER
GAS VALVE
BURNER BOX ASSEMBLY
FIGURE 1
Page 3
I-UNIT COMPONENTS
Unit components are shown in figure 1. The gas valve,
combustion air inducer and burners can be accessed by re
moving the access panel. Electrical components are in the
control box (figure 2) found in the blower section.
CIRCUIT BREAKER CB8
PRESS TO RESET
FIGURE 3
CAUTION
Electrostatic discharge can affect elec
tronic components. Take precautions
to neutralize electrostatic charge by
touching your hand and tools to metal
prior to handling the control.
A- Control Box
1. Control Transformer (T1)
A transformer located in the control box provides power to
the low voltage section of the unit. Transformers on all
models are rated 40VA with a 120V primary and a 24V sec
ondary.
2. Door Interlock Switch (S51)
An interlock switch rated 14A at 125VAC is wired in series
with line voltage. When the indoor blower access panel is
removed the unit will shut down.
CONTROL BOX SL280DFV
Transformer
Interlock Switch
WARNING
Shock hazard.
Disconnect power before servicing. Integrated
control is not field repairable.
If control is inoperable, simply replace entire con
trol.
Can cause injury or death. Unsafe operation will
result if repair is attempted.
4. SureLight Integrated Control (A92)
Units are equipped with the icomfort enabled Sur
®
eLight
control is used with the icomfort Wi-Fi
of a communicating comfort system. The control can also
operate with a non-communicating conventional single or
two-stage thermostat. The system consists of a ignition /
blower control (figures 4 and 5) with control pin designa
tions in tables 1, 2 and 3 and ignitor (figure 13). The control
and ignitor work in combination to ensure furnace ignition
and ignitor durability. The control provides gas ignition,
safety checks and indoor blower control with two-stage gas
heating. The furnace combustion air inducer, gas valve and
indoor blower are controlled in response to various system
inputs such as thermostat signal, pressure and limit switch
signal and flame signal. The control features a seven-seg
ment LED display, indicating furnace status (including in
door blower) and error codes. The LED flashes in single
digits. For example using table 5 under LIMIT CODE, an
“E” followed by “2” followed by “5” followed by “0”, the limit
switch circuit is open. The control also has two unpowered
(dry) 1/4” contacts for a humidifier and a 120 volt accessory
terminal. Both rated at (1) one amp each.
two-stage, variable speed integrated control. This
®
thermostat as part
Circuit Breaker
SureLight
®
Integrated Control
FIGURE 2
3. Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box.
The switch provides overcurrent protection to the trans
former (T1). The breaker is rated 3A at 32V. If the current
exceeds this limit the breaker will trip and all unit opera
tion will shutdown. The breaker can be manually reset
by pressing the button on the face. See figure 3.
Electronic Ignition
At the beginning of the heat cycle the integrated control
monitors the first stage and second stage combustion air
inducer prove switch. The control will not begin the heating
cycle if the first stage prove switch is closed (by-passed).
Likewise the integrated control will not begin the second
stage heating cycle if the second stage prove switch is
closed, and will remain in first stage heat. However, if the
second stage prove switch closes during the first stage
heat pre-purge, the control will allow second stage heat.
Once the first stage prove switch is determined to be open,
Page 4
the combustion air inducer is energized on low (first stage)
heat speed. When the differential in the prove switch is
great enough, the prove switch closes and a 15-second
pre-purge begins.
NOTE - During abnormal conditions such as low supply
voltage or low outdoor temperatures and the low fire pres
sure switch does not close, the combustion air inducer will
switch to high fire. After a 15 second pre-purge the high fire
pressure switch will close and the unit will begin operation
on high fire. After 10 to 20 seconds of high fire operation the
unit will switch to low fire
After the 15-second pre-purge period, the SureLight ignitor
warms up for 20 seconds after which the gas valve opens
for a 4-second trial for ignition. The ignitor energizes during
the trial until flame is sensed. If ignition is not proved during
the 4-second period, the control will try four more times with
an inter purge and warm-up time between trials of 35 sec
onds. After a total of five trials for ignition (including the ini
tial trial), the control goes into Watchguard-Flame Failure
mode. After a 60-minute reset period, the control will begin
the ignition sequence again.
Two Stage Operation / Thermostat Selection DIP
Switch
The control can be utilized in two modes: SINGLE-STAGE
thermostat or TWO-STAGE thermostat. The thermostat
selection is made using a DIP switch and must be posi
tioned for the particular application. DIP switch 1, labeled
T”STAT HEAT STAGE is factory-set in the OFF position for
use with a two-stage thermostat. Move the DIP switch to
ON for use with a single stage thermostat.
While in the single-stage thermostat mode (single DIP
switch setting), the burners will always fire on first-stage
heat. The combustion air inducer will operate on low speed
and indoor blower will operate on low heat speed. After a
factory default 10 minute recognition period, the unit will
switch to second stage heat. While in the two-stage ther
mostat mode (two DIP switch setting) the burners will fire
on first-stage heat. The combustion air inducer will operate
on low speed and indoor blower will operate on low heat
speed. The unit will switch to second-stage heat on call
from the indoor thermostat. If there is a simultaneous call
for first and second stage heat, the unit will fire an first stage
heat and switch to second stage heat after 30 seconds of
operation. See Sequence of Operation flow charts in the
back of this manual for more detail.
TABLE 1
SureLight
®
Control 5 Pin Terminal Designation
PIN #Function
1Ignitor
2Combustion Air Inducer High Speed
3Combustion Air Inducer Low Speed
4Combustion Air Inducer Neutral
5Ignitor Neutral
TABLE 2
SureLight
®
Control 12 Pin Terminal Designation
PIN #Function
1Gas Valve High Fire
2Second Stage Prove Switch
3Rollout In
4Ground
524V Hot
6Primary Limit In
7Gas Valve Low Stage
8Gas Valve Common
924V Neutral
10Ground
11Rollout Switch Out
121st Stage Prove Switch
TABLE 3
SureLight
®
Control 6 Pin Terminal Designation
PIN #Function
1Data Input From Motor
2Common
3Not Used
4Data Output To Motor
55 Volt Bias Supply
6Not Used
Page 5
HUM
LINE 1
7 SEGMENT LED
FLAME SENSE
DIAGNOSTIC
PUSH BUTTON
DIP SWITCHES
INTEGRATED CONTROL
ACC
HS/ CAI
INDOOR
BLOWER
CONNECTOR
NEUTRAL
OUTDOOR AIR
SENSOR
TERMINALS
DISCHARGE AIR
SENSOR
TERMINALS
TB83
COMMUNICATING
OUTDOOR
EQUIPMENT
I + I -CRI + I -
TB84
COMMUNICATING
INDOOR
THERMOSTAT
R
RS-BUS LINK (TB82, future use)
I+ = DATA HIGH CONNECTION
I - = DATA LOW CONNECTION
RS-BUS OUTDOOR (TB83)
R = 24VAC
I + = DATA HIGH CONNECTION
I - = DATA LOW CONNECTION
C = 24VAC COMMON
RS-BUS INDOOR (TB84)
R = 24VAC
I + = DATA HIGH CONNECTION
I - = DATA LOW CONNECTION
C = 24VAC COMMON
1/4” QUICK CONNECT TERMINALS
HUM = UNPOWERED NORMALLY OPEN (DRY) CONTACTS
XMFR = 120 VAC OUTPUT TO TRANSFORMER
LI = 120 VAC INPUT TO CONTROL
ACC = 120 VAC OUTPUT TO OPTIONAL ACCESSORY
NEUTRALS = 120 VAC NEUTRAL
C
W1 W2 GY2Y1
NON-COMMUNICATINGNG
24V TERMINALS
12 PIN LOW
VOLTAGE
CONNECTOR
W915 Y1 TO Y2
2 STAGE COMPR
W951 R TO O
HEAT PUMP
W914 R TO DS
DEHUM OR
CC
RDHLODS
HARMONY
THERMOSTAT CONNECTIONS (TB1)
DS = DEHUMIDIFICATION SIGNAL
W2 = HEAT DEMAND FROM 2ND STAGE T/STAT
W1 = HEAT DEMAND FROM 1ST STAGE T/STAT
R = CLASS 2 VOLTAGE TO THERMOSTAT
G = MANUAL FAN FROM T'STAT
C = THERMOSTAT SIGNAL GROUND CONNECTED TO
TRANSFORMER GRD (TR) & CHASIS GROUND (GRD)
Y1 = THERMOSTAT 1ST STAGE COOL SIGNAL
Y2 = THERMOSTAT 2ND STAGE COOL SIGNAL
O = THERMOSTAT SIGNAL TO HEAT PUMP
DH = DEHUMIDIFICATION OUTPUT COMMUNICATING
L = USE ONLY WITH A COMMUNICATING THERMOSTAT
AND A NON-COMMUNICATING OUTDOOR UNIT
REVERSING VALVE
THERMOSTAT ONLY
FIGURE 4
Page 6
THERMOSTAT SELECTION
1
2
3
*
TWO STAGE
THERMOSTAT
1−STAGE
THERMOSTAT
(TIMED STAGING)
−SEE SW #2
HEATING BLOWER−OFF DELAY
*
90 SECOND
HTG BLOWER
OFF DELAY
60 SECOND
HTG BLOWER
OFF DELAY
120 SECOND
HTG BLOWER
OFF DELAY
180 SECOND
HTG BLOWER
OFF DELAY
−BLOWER ON DELAY − 30 SEC. FIXED
4
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
HEATING MODE BLOWER SPEED
9
11
10
+ 24%
+ 18%
+ 12%
INCREASE AIR HTG CFM
+ 6%
*
FACTORY
DEFAULT
− 6%
− 12%
DECREASE AIR HTG CFM
− 18%
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
INTEGRATED CONTROL CONFIGURATION GUIDE
2ND STAGE HEAT ON DELAY
1
2
3
4
5
2
3
4
S1
7
8
15
14
INDOOR EQUIPMENT
1
6
5
6
HEAT PUMP LINK
(JUMPERS R to O)
*
5
6
7
8
5
6
7
8
5
6
7
8
5
6
7
8
5
6
7
8
5
6
7
8
13
12
15
14
13
12
15
14
13
12
15
14
13
12
15
14
13
12
15
14
ON
7 MIN
UPSTAGE
DELAY
ON
12 MIN
UPSTAGE
DELAY
DIAGNOSTIC
PUSH BUTTON
FLAME
SENSE
123456
ON
S4S3
911
10
12
ON
OUTDOOR
SENSOR
DISCHARGE
AIR SENSOR
I+ I−
RI+ I−CRI+ I− C
OUTDOOR EQUIPMENT
1−STG COMPRESSOR
W915
2 STAGE
COMPR
1
13
DO NOT CUT
13
12
15
14
13
12
15
14
13
12
15
14
2−STG COMPRESSOR
W915
2 STAGE
COMPR
CUT LINK
2−STAGE
COMPRESSOR LINK
(JUMPERS Y1 to Y2)
W915
CLG BLOWER SPEED ADJUSTMENT
*
7
7
HUM
W1W2 G Y2 Y1 C CDHL O DSR
HEAT PUMP UNIT
DEFAULT
8
8
ACC
W1
W2GY2
ON−BOARD LINK
OPTION SELECTION
A/C UNIT
W951
HEAT
PUMP
DO NOT CUT
W951
HEAT
PUMP
CUT LINK
1
W951
ON
ON
+ 10%
ON
− 10%
L1
DIAGNOSTIC
LED
SureLight
C
C
Y1
1
2
3
4
5
6
7
1
2
3
4
5
6
7
1
2
3
4
5
6
7
HSI/CAI
1
5
J3
N
N
IGN
CAI1
CAI2
P79
14
®
R
NO HARMONY ZONING
NO SIGNATURESTAT
W/ DS CONNECTION
6
3
110
4 7
3
12
CUT FOR
OPTION
SELECTION
W915
2 STAGE
COMPR
W951
HEAT
PUMP
W914
DEHUM
HARMONY
L
DH
OR
DO NOT CUT
W914
DEHUM
or
HARMONY
HARMONY ZONING
OR
SIGNATURESTAT W/
DS CONNECTION
CUT LINK
1
W914
DEHUM
or
HARMONY
DEHUMIDIFICATION−
HARMONY LINK
(JUMPERS R to DS)
W914
8
CONTINUOUS FAN MODE BLOWER SPEED
8
8
NEUTRALS
MEDIUM−LOW
*
SPEED
(38%)
MEDIUM−HIGH
SPEED
(70%)
LOW
SPEED
(28%)
HIGH
SPEED
(100%)
9
11
10
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
COOLING MODE BLOWER SPEED
1
2
3
*
HIGH
SPEED
MEDIUM−HIGH
J2
SPEED
MEDIUM−LOW
SPEED
LOW
SPEED
COOLING MODE BLOWER RAMPING
*
OPTION A
OFF−50%−82%−
100%−50%−OFF
OPTION B
OFF−82%−100%−OFF
OPTION C
OFF−100%−100%−OFF
OPTION D
OFF−100%−OFF
−CUT ON−BOARD LINK (SOLDER TRACE) COMPLETELY THROUGH
1
BOTH LAYERS ON THE CONTROL BOARD
−LINKS CUT IN ERROR −INSTALL A JUMPER ON THE APPROPRIATE
TERMINALS ON THE TERMINAL STRIP
−PROTECTIVE PLASTIC FILM ON DIP SWITCHES MAY BE
REMOVED FOR EASE IN SETTING OF DIP SW.
* FACTORY DEFAULT
ON
1
2
3
ON
1
2
3
ON
1
2
3
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
13
12
15
14
12
15
14
12
15
14
12
15
14
4
5
6
7
8
4
5
6
7
8
4
5
6
7
8
4
5
6
7
8
13
15
12
14
13
12
15
14
13
12
15
14
13
12
15
14
FIGURE 5
Page 7
TABLE 4
Integrated Control Diagnostic Modes
DisplayAction (when button released)
No change (idle)*Remain in idle mode
Solid “E”Enter diagnostic recall mode
Solid “D”Discharge Air Installed
Solid “F”Enter flame signal mode
Solid “P” (variable speed only)Program unit capacity/size (Unit Code)
* No change implies the display will continue to show whatever is currently being displayed for normal operation (blinking
decimal, active error code, heat state, etc..)
Diagnostic LED (Figure 4)
The seven-segment diagnostic LED displays operating
status, target airflow, error codes and other information.
The table beginning on Page 9 lists diagnostic LED
codes.
Flame Signal Mode
Select ”F” from the menu to access the flame signal mode.
The integrated control will display the flame current on 7
segment LED in in micro amps (uA).
Flame signal mode is exited after any of the following:
Diagnostic Push Button (Figure 4)
The diagnostic push button is located adjacent to the
seven-segment diagnostic LED. This button is used to en
able the Error Code Recall “E” mode and the Flame Signal
“F” mode. Press the button and hold it to cycle through a
menu of options. Every five seconds a new menu item will
be displayed. When the button is released, the displayed
item will be selected. Once all items in the menu have been
displayed, the menu resumes from the beginning until the
button is released.
Error Code Recall Mode
Select ”E” from the menu to access the most recent 10 error
codes. Select “c” from the Error Code Recall menu to clear
all error codes. Button must be pressed a second time
while “c” is flashing to confirm command to delete codes.
Press the button until a solid “≡” is displayed to exit the Error
Code Recall mode.
Power is reset
Pressing and holding push button until 3 horizontal
lines “≡” are displayed
10 minutes after entering the flame sense mode.
Program Unit Capacity/Size Mode
After the “P” is selected (by releasing the push button) the
integrated control will start flashing the “P” on display for 90
seconds. If push button is pressed again and held during
that time, the control will start to display characters corre
sponding to different variable speed furnace models for 3
seconds each. While the wanted character-model is dis
played push button has to be released. Selected option will
flash display for 10 seconds and during that time push but
ton has to be pressed and held for 5 seconds. Once control
accepts new setting it will store data in non-volatile memory
and reset itself. If 10 seconds expires or push button is held
less than 5 seconds, control will exit field test mode and go
into idle without changing programming the unit size.
Page 8
TABLE 5
Integrated Diagnostic Codes/Status of Equipment I.
CodeDiagnostic Codes/Status of EquipmentAction Required to Clear and Recover
.
Idle mode (Decimal blinks at 1 Hertz -- 0.5 second ON, 0.5 second OFF).
A
C
d
h
H
dF
U
E 105
E 110
E 111
E 112
E 113
E 114
E 115
E 116
E 117
E 120
Cubic feet per minute (cfm) setting for indoor blower (1 second ON, 0.5
second OFF) / cfm setting for current mode displayed.
Cooling stage (1 second ON, 0.5 second OFF) / 1 or 2 displayed / Pause
/ cfm setting displayed / Pause / Repeat codes).
Dehumidification mode (1 second ON) / 1 second OFF) / cfm setting dis
played / Pause / Repeat Codes).
Heat pump stage (1 second ON, 0.5 second OFF) / % of input rate dis
played / Pause / cfm setting / Pause / Repeat codes.
Gas Heat Stage (1 second ON, 0.5 second OFF) / 1 or 2 displayed /
Pause / cfm
setting displayed / Pause / Repeat codes. Blinking during ignition.
Defrost mode.
Discharge Air Temperature
Device communication problem - No other devices on RS BUS (Commu
nication
system).
Low line voltage.Line Voltage Low (Voltage lower than nameplate
Line voltage polarity reversed.Reverse line power voltage wiring. System resumes
Ground not detectedSystem shuts down. Provide proper earth ground.
High line voltage.Line Voltage High (Voltage higher than nameplate
Line voltage frequency out-of-range.No 60 Hertz Power.Check voltage and line power
Low 24V - Control will restart if the error recovers.24-Volt Power Low (Range is 18 to 30 volts). Check
High 24V.24 Volt Power High (Range is 18 to 30 volts). Check
Poor ground detected (Warning only)Provide proper grounding for unit. Check for proper
Unresponsive device. Communication only.Usually caused by delay in outdoor unit responding
Equipment is unable to communicate. Indicates
numerous message errors. In most cases errors are
related to electrical noise. Make sure high voltage
power is separated from RSBus. Check for miswired and/or loose connections between the stat,
indoor unit and outdoor unit. Check for a high volt
age source of noise close to the system. Fault
clears after communication is restored.
rating).Check power line voltage and correct. Alarm
clears 5 seconds after fault recovered.
normal operation 5 seconds after fault recovered.
System resumes normal operation 5 seconds after
fault recovered.
rating). Provide power voltage within proper range.
System resumes normal operation 5 seconds after
fault recovered.
frequency. Correct voltage and frequency problems.
System resumes normal operation 5 seconds after
fault recovered.
and correct voltage. Check for additional power-rob
bing equipment connected to system. May require
installation of larger VA transformer to be installed
in furnace / air handler. Clears after fault recovered.
and correct voltage. Check for proper line voltage
(120V, 240V, etc.) to equipment. Clears when con
trol senses proper voltage.
earth ground to the system. Warning only will clear
30 seconds after fault recovered.
to indoor unit poling. Recycle power. Check all wir
ing connections. Cleared after unresponsive device
responds to any inquiry.
Page 9
TABLE 5 Continued
CodeDiagnostic Codes/Status of EquipmentAction Required to Clear and Recover
E 124
Active communicating thermostat signal missing for more than 3 min
utes.
E 125
Control failed self-check, internal error, failed hardware. Will restart if
error
recovers. Integrated control not communicating. Covers hardware errors
(flame sense circuit faults, pin shorts, etc.).
E 126
Control internal communication problem. Hardware problem on the control. Cycle power on
E 131
Corrupted control parameters (Verify configuration of system). Communi
cating only.
E 180
Outdoor air temperature sensor failure. Only shown if shorted or out-ofrange.
E 200
Hard lockout - Rollout circuit open or previously open.Correct cause of rollout trip, or replace flame rollout
E 201
Indoor blower communication failure - Unable to communicate with blow
er motor.
E 202
Indoor blower motor mis-match - Indoor motor horsepower does not
match unit capacity. See Page 41.
E 203
Appliance capacity / size is NOT programmed. Invalid unit codes refer to
configuration flow chart. See Page 41.
E 204
Gas valve mis-wired.Check gas valve operation and wiring. Clears when
E 205
Gas valve control relay contact shorted.Check wiring on control and gas valve. If wiring is
Equipment lost communication with the thermostat.
Check four wiring connections, ohm wires and cycle
power at the thermostat. Alert stops all services and
waits for heartbeat message from thermostat (sub
net controller). Cleared after valid thermostat (sub
net controller) message is received.
Hardware problem on the control. Cycle power on
control. Replace if problem prevents service and is
persistent. Critical alert. Cleared 300 seconds after
fault recovered.
control. Replace if problem prevents service and is
persistent. Cleared 300 seconds after fault recov
ered.
Reconfigure the system. Replace control if heating
or cooling is not available. Only applicable in the
communicating mode, not in startup. Exit from Com
missioning and Execute 'Set Factory Default mode'.
Control will still operate on default parameter set
tings.
Compare outdoor sensor resistance to temperature/
resistance charts in unit installation instructions.
Replace sensor pack if necessary. At beginning of
(any) configuration, furnace or air handler control
will sense outdoor air and discharge air temperature
sensor(s). If detected (reading in range), appropri
ate feature will be set as 'installed' and that could be
seen in 'About' screen. In normal operation after
control recognizes sensors, alarm will be sent if
valid temperature reading is lost. To get rid of set
ting and alarm, redo configuration and make sure
that temperature sensor is marked as 'not installed'
in Indoor Unit 'About' screen. When Indoor unit con
trol is replaced, thermostat will 'tell' new control if
temperature sensor is in system or not. Clears 30
seconds after fault recovered.
switch. Test furnace operation. Cleared after fault
recovered.
Indoor blower communication failure (including pow
er outage). Lost communication with indoor blower
motor. Possible causes: motor not powered, loose
wiring. Problem may be on control or motor side.
Cleared after fault recovered.
Incorrect appliance capacity code selected. Check
for proper configuring under: Unit Size Codes for
Furnace/Air Handler on configuration guide or in
installation instructions. Cleared after the correct
match is detected following a reset. (Remove ther
mostat from system while applying power and re
programming.)
No appliance capacity code selected. Check for
proper configuring under: Unit Size Codes for Fur
nace on configuration guide or in installation instruc
tions. Critical Alert. Cleared after valid unit code is
read following a reset. (Remove thermostat from
system while applying power and reprogramming.)
repaired.
correct, replace control.
Page 10
TABLE 5 Continued
CodeDiagnostic Codes/Status of EquipmentAction Required to Clear and Recover
E 206
E 207
E 223
E 224
E 225
E 226
E 227
E 228
E 229
E 240
E 241
E 250
E 252
E 270
Gas valve second-stage relay failureFurnace will operate on 1st stage for remainder of
the heating demand. Will clear after fault recovered.
If unable to operate 2nd stage, replace control.
Hot surface ignitor sensed open - Refer to troubleshooting. SeePage 46.Measure resistance of hot surface ignitor. Replace if
open or not within specified range found in IOM.
Resumes normal operation after fault is cleared.
closing on heat call. Measure operating pressure
(inches w.c.). Inspect vent and combustion air in
ducer for correct operation and restriction. Re
sumes normal operation after fault is cleared
Low pressure switch failed closed - Refer to troubleshooting. See
Page 46.
High pressure switch failed open - Refer to troubleshooting. See
Page 46.
High pressure switch failed closed - Refer to troubleshooting. See
Page 46.
Low pressure switch open during trial for ignition or run mode. Refer to
troubleshooting. See Page 46.
Combustion air inducer calibration failureUnable to perform pressure switch calibration.
Ignition on High Fire - Information Only Code is displayed if 1) low pressure switch fails to
Low flame current - Run mode - Refer to troubleshooting. See Page 46.Check micro-amperes of flame sensor using control
Flame sensed out of sequence - Flame still present.Shut off gas. Check for gas valve leak. Replace, if
Limit switch circuit open - Refer to troubleshooting. See Page 46Check for proper firing rate on furnace. Ensure
Discharge air temperature too high (gas heat only).Check temperature rise, air flow and input rate.
Soft lockout - Exceeded maximum number of retries. No flame current
sensed.
Check operation of low pressure switch to see if it is
stuck closed on heat call longer than 150 seconds.
Measure operating pressure (inches w.c.). Inspect
vent and combustion air inducer for correct opera
tion and restriction. Resumes normal operation after
fault is cleared.
Check pressure (inches w.c.) of high pressure
switch closing on heat call. Measure operating pres
sure (inches w.c.). Inspect vent and combustion air
inducer for correct operation and restriction. Re
sumes normal operation after fault is cleared.
Check operation of high pressure switch closing on
heat call. Measure operating pressure (inches w.c.).
Inspect vent and combustion air inducer for correct
operation and restriction. Resumes normal opera
tion after fault is cleared.
Check pressure (inches w.c.) of low pressure switch
closing on heat call. Measure operating pressure
(inches w.c.). Inspect vent and combustion air in
ducer for correct operation and restriction. Re
sumes normal operation after fault is cleared.
Check vent system and pressure switch wiring con
nections. Resumes normal operation after fault is
cleared.
close, then furnace will switch to high speed inducer
to close both low and high pressure switches, then
furnace lights on high fire, or 2) if continuous fan is
active, furnace lights on high fire for 60 seconds to
improve heat exchanger warm up time.
diagnostics or field-installed mode. Clean or replace
sensor. Measure voltage of neutral to ground to
ensure good unit ground. Alert clears after current
heat call has been completed.
necessary. Alert clears when fault is recovered.
there is no blockage in heater. Check for proper air
flow. If limit not closed within 3 minutes, unit will go
into 1-hour soft lockout. Resumes normal operation
after fault is cleared.
Cleared when heat call is finished.
Check for proper gas flow. Ensure that ignitor is
lighting burner. Check flame sensor current. Clears
when heat call finishes successfully.
Page 11
TABLE 5 Continued
CodeDiagnostic Codes/Status of EquipmentAction Required to Clear and Recover
E 271
Soft lockout - Exceeded maximum number of retries. Last retry failed due
to the pressure switch opening.
E 272
Soft lockout - Exceeded maximum number of recycles. Last recycle due
to the pressure switch opening.
E 273
Soft lockout - Exceeded maximum number of recycles. Last recycle due
to flame failure.
E 274
Soft lockout - Exceeded maximum number of recycles. Last recycle
failed due to the limit circuit opening or limit remained open longer than
3 minutes.
E 275
Soft lockout - Flame sensed out of sequence. Flame signal is gone.Shut off gas. Check for gas valve leak. 1-hour soft
E 276
Watchguard calibration failure.Unable to perform pressure switch calibration.
E 290
Ignitor circuit fault - Failed ignitor or triggering circuitry.Measure resistance of hot surface ignitor. Replace if
E 291
Heat air flow restricted below the minimum.Check for dirty filter and air flow restriction. Check
E 292
Indoor blower motor unable to start due to obstructed wheel, seized
bearings.
E 294
Combustion air inducer over current. Check combustion blower bearings, wiring and
E 295
Indoor blower motor temperature is too high.Indoor blower motor over temperature (motor
E 310
Discharge error temperature sensor failure. Only shown if shorted or
out of range.
E 311
Heat rate reduced to match indoor blower air flow.Warning Only. Furnace blower in cutback mode due
Check pressure (inches w.c.) of low pressure switch
closing on heat call. Measure operating pressure
(inches w.c.). Inspect vent and combustion air in
ducer for correct operation and restriction. Clears
when heat call finishes successfully.
Check operation of low pressure switch to see if it is
stuck closed on heat call. Check pressure (inches
w.c.) of high pressure switch closing on heat call.
Measure operating pressure (inches w.c.). Inspect
vent and combustion air inducer for correct opera
tion and restriction. Clears when heat call finishes
successfully.
Check micro-amperes of flame sensor using control
diagnostics or field-installed mode. Clean or replace
sensor. Measure voltage of neutral to ground to
ensure good unit ground. Clears when heat call
finishes successfully.
Shut down system. 1-hour soft lockout. Check firing
rate and air flow. Check for blockage. Clears when
heat call finishes successfully.
lockout. Clears when flame has been proven stable.
Check vent system and pressure switch wiring con
nections. 1-hour soft lockout. Clears when calibra
tion has finished successfully.
open or not within specifications. 1-hour soft lock
out. Clears when flame has been proven stable.
Indoor blower motor unable to start (seized bear
ing, stuck wheel, etc.). Replace motor or wheel if
assembly does not operate or meet performance
standards. 1-hour soft lockout. Clears after circula
tor successfully starts.
amps. Replace if does not operate or does not meet
performance standards. Clears after inducer current
is sensed to be in-range after the ignition following
the soft lockout or reset.
tripped on internal protector). Check motor bearings
and amps. Replace if necessary. Cleared after
blower demand is satisfied.
Compare outdoor sensor resistance to temperature/
resistance charts in installation instructions. Re
place sensor if necessary. Cleared in Communicat
ing mode: 30 seconds after fault recovered. In NonCommunicating mode: Cleared after the current
heat call is completed.
to restricted airflow. Reduce firing rate every 60
seconds to match available CFM. Check filter and
duct system. To clear, replace filter if needed or re
pair/add duct. 2-stage controls will reduce firing rate
st
stage. Clears when heat call finishes success
to 1
fully.
Page 12
TABLE 5 Continued
CodeDiagnostic Codes/Status of EquipmentAction Required to Clear and Recover
E 312
E 313
E 331
E 334
E 347
E 348
E 349
E 370
E 400
E 401
E 402
E 403
E 404
E 405
Restricted air flow in cooling or continuous fan mode is lower than cfm
setting.
Indoor or outdoor unit capacity mismatch. Communication only.Incorrect indoor/outdoor capacity code selected.
Global network connection - Communication link problem.For Future Use.
Relay “Y1” stuck on interated control.Replace integrated control.
No 24 Volt output on Y1 of ”integrated control” with non communicating
outdoor unit.
No 24 Volt output on Y2 of ”integrated control” with non?communicating
outdoor unit.
No 24 Volts between R & O on ”integrated control” with non communi
cating outdoor unit (Dual fuel module required for heat pump applica
tion).
Interlock switch sensed open for 2 minutes.Control sees the loss of 24VAC for 2 minutes .Ter
LSOM Compressor long run cycle or low system pressure.Compressor ran more than 18 hours to satisfy a
LSOM - Outdoor unit system pressure trip.Discharge or suction pressure out-of-limits, or
LSOM - Compressor short-cycling. .(Running less than 4 minutes).
Outdoor unit pressure trip
LSOM - Compressor rotor locked. Compressor short-cycling. (Running
less than 4 minutes).
LSOM - Compressor open circuit.Compressor circuit open (due to power disconnec
Warning Only. Restricted airflow - Indoor blower is
running at a reduced CFM (Cutback Mode - The
variable speed motor has pre-set speed and
torque limiters to protect the motor from damage
caused by operating outside of design parameters
(0 to 0.8” W.C.. total external static pressure).
Check filter and duct system. To clear, replace
filter if needed or repair/add duct. Cleared after the
current service demand is satisfied.
Check for proper configuring in installation instruc
tions. Alarm is just a warning. The system will op
erate, but might not meet efficiency and capacity
parameters. Alarm will clear when commissioning
is exited. Cleared after commissioning is com
plete.
Operation stopped. Y1 relay / Stage 1 failed. (Pilot
relay contacts did not close or the relay coil did not
energize; no input back to IFC chip). Critical Alert.
Cleared after reset and Y1 input sensed.
Y2 relay / Stage 2 failed. (Pilot relay contacts did
not close or the relay coil did not energize; no in
put back to IFC chip). Critical Alert. Cleared after
reset and Y1 input sensed.
Configuration link R to O needs to be restored.
Replace link or hard-wire. Applicable in non com
municating mode. Critical Alert.
minate all services and wait for interlock switch to
close. The alarm will clear when 24VAC is continu
ously sensed on DS terminal for a minimum of 10
seconds or on a power reset.
sor is not running. Check power to outdoor unit.
Clears the error after current is sensed in both
RUN and START sensors for at least 2 seconds,
or after service is removed, or after power reset.
single thermostat demand. Critical Alert. Clears
the error after 30 consecutive normal run cycles or
power reset. Also monitors low pressure switch
trips.
compressor overloaded. Clears the error after 4
consecutive normal compressor run cycles.
Compressor runs less than 3 minutes to satisfy a
thermostat demand. Clears the error after 4 con
secutive normal run cycles or power reset.
Compressor rotor locked up due to run capacitor
short, bearings are seized, excessive liquid refrig
erant, etc. Clears the error after 4 consecutive nor
mal run cycles or after power reset.
tion, open fuse, etc.) Clears the error after 1 nor
mal compressor run cycle.
Page 13
TABLE 5 Continued
CodeDiagnostic Codes/Status of EquipmentAction Required to Clear and Recover
E 406
E 407
E 408
E 409
LSOM - Compressor open start circuit.Required amount of current is not passing through
Start current transformer. Clears the error after cur
rent is sensed in START sensor, or after power re
set.
LSOM - Compressor open run circuit.Required amount of current is not passing through
Run current transformer. Clears the error after cur
rent is sensed in RUN sensor, or 1 normal compres
sor run cycle, or after power reset.
LSOM - Compressor contactor is welded.Compressor runs continuously. Clears the error
after 1 normal compressor run cycle or after power
reset.
LSOM - Compressor low voltage.Secondary voltage is below 18VAC. After 10 min
utes, operation is discontinued. Clears the code
after voltage is higher than 20 VAC for 2 seconds or
after power reset.
DIP Switch Settings
NOTE - All icomfortt settings are set at the icomfort Wi-Fi
thermostat. See icomfortt installation instruction. In icom
fortt communication system all DIP switch and clippable
link settings are ignored. For conventional thermostats pro
ceed with DIP switch and clippable link settings as outlined
in the following.
Heating Operation DIP Switch Settings
Switch 1 -- Thermostat Selection -- This unit may be
used with either a single-stage or two-stage thermostat.
The thermostat selection is made using a DIP switch which
must be properly positioned for the particular application.
The DIP switch is factory-positioned for use with a twostage thermostat. If a single-stage thermostat is to be used,
the DIP switch must be repositioned.
a - Select “OFF” for two-stage heating operation con
trolled by a two-stage heating thermostat (factory set
ting);
b - Select “ON” for two-stage heating operation con
trolled by a single-stage heating thermostat. This set
ting provides a timed delay before second-stage heat
is initiated.
Switch 2 -- Second Stage Delay (Used with SingleStage Thermostat Only) -- This switch is used to deter
mine the second stage on delay when a single-stage ther
mostat is being used. The switch is factory-set in the OFF
position, which provides a 7-minute delay before secondstage heat is initiated. If the switch is toggled to the ON
position, it will provide a 12-minute delay before secondstage heat is initiated. This switch is only activated when
the thermostat selector jumper is positioned for SINGLEstage thermostat use.
Switches 3 and 4 -- Blower-Off Delay -- The blower-on
delay of 30 seconds is not adjustable. The blower-off delay
(time that the blower operates after the heating demand
has been satisfied) can be adjusted by moving switches 3
and 4 on the integrated control. The unit is shipped from the
factory with a blower-off delay of 90 seconds. The blower
off delay affects comfort and is adjustable to satisfy individ
®
ual applications. Adjust the blower off delay to achieve a
supply air temperature between 90° and 110°F at the exact
moment that the blower is de-energized. Longer off delay
settings provide lower supply air temperatures; shorter set
tings provide higher supply air temperatures.Table 6 pro
vides the blower off timings that will result from different
switch settings.
TABLE 6
Blower Off Delay Switch Settings
Blower Off Delay
(Seconds)
Switch 3Switch 4
60OnOff
90 (Factory)OffOff
120OffOn
180OnOn
Indoor Blower Operation DIP Switch Settings
Switches 5 and 6 -- Cooling Mode Blower Speed -- The
unit is shipped from the factory with the dip switches posi
tioned for high speed (4) indoor blower motor operation
during the cooling mode. Table 7 provides the cooling
mode blower speeds that will result from different switch
settings. Switches 5 and 6 set the blower cfm for secondstage cool. The integrated control automatically ramps
down to 70% of the second-stage cfm for first-stage cfm.
Refer to blower tables for corresponding cfm values.
TABLE 7
Cooling Mode Blower Speeds
Speed
Switch 5Switch 6
LowOnOn
Medium LowOffOn
Medium HighOnOff
High (Factory)OffOff
Switches 7 and 8 -- Cooling Blower Speed Adjustment
-- The unit is shipped from the factory with the dip switches
positioned for NORMAL (no) adjustment. The dip switches
may be positioned to adjust the blower speed by +10% or
Page 14
-10% to better suit the application. Table 8 below provides
blower speed adjustments that will result from different
switch settings. Refer to blower tables for corresponding
cfm values.
TABLE 8
Cooling Blower Speed Adjustment
Adjustment
Switch 7Switch 8
+10% (approx.)OnOff
Factory DefaultOffOff
-10% (approx.)OffOn
Switches 9 and 10 -- Cooling Mode Blower Speed
Ramping -- Blower speed ramping may be used to en
hance dehumidification performance. The switches are
factory set at option A which has the greatest effect on dehumidification performance. Table 9 provides the cooling
mode blower speed ramping options that will result from
different switch settings. The cooling mode blower speed
ramping options are detailed below.
NOTE - The off portion of the selected ramp profile also ap
plies during heat pump operation in dual fuel applications.
TABLE 9
Cooling Mode Blower Speed Ramping
Ramping Option
Switch 9Switch 10
A (Factory)OffOff
BOffOn
COnOff
DOnOn
Ramping Option A (Factory Selection)
Motor runs at 50% for 30 seconds.
Motor then runs at 82% for approximately 7-1/2 minu
tes.
If demand has not been satisfied after 7-1/2 minutes,
motor runs at 100% until demand is satisfied.
Once demand is met, motor runs at 50% for 30 sec
onds then ramps down to stop.
OFF
1/2 MIN
50% CFM
7 1/2 MIN
82% CFM
COMPRESSOR DEMAND
100%
CFM
1/2 MIN
50% CFM
OFF
Ramping Option B
Motor runs at 82% for approximately 7-1/2 minutes. If
demand has not been satisfied after 7-1/2 minutes,
motor runs at 100% until demand is satisfied.
Once demand is met, motor ramps down to stop.
OFF
7 1/2 MIN
82%CFM
COMPRESSOR DEMAND
100% CFM
OFF
Ramping Option C
Motor runs at 100% until demand is satisfied.
Once demand is met, motor runs at 100% for 45 sec
The switches are factory set to the OFF position which pro
vides factory default heat speed. Refer to table 10 for
switches 11, 12 and 13 that provided the corresponding in
creases or decrease to both high and low heat demand.
TABLE 10
Heating Mode Blower Speeds
Heat Speed
Switch
11
Switch12Switch
13
Increase 24%OnOnOn
Increase 18%OnOnOff
Increase 12%OnOffOn
Increase 6%OnOffOff
Factory DefaultOffOffOff
Decrease 6%OffOffOn
Decrease 12%OffOnOff
Decrease18%OffOnOn
Switches 14 and 15 -- Continuous Blower Speed --
Table 11 provides continuous blower speed adjustments
that will result from different switch settings.
TABLE 11
Continuous Blower Speed
Continuous
Blower Speed
Switch 14Switch 15
28% of High Cool SpeedOffOn
38% of High Cool Speed
(Factory)
OffOff
70% of High Cool SpeedOnOff
100% of High Cool SpeedOnOn
Page 15
BLOWER DATA
SL280DF070V36A BLOWER PERFORMANCE (less lter)
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
+24%10651170
+18%10101115
+12%9601055
+6%9101000
Factory Default860945
–6%805885
–12%755830
–18%705775
1
Cooling Speed
DIP Switch
Settings
LowMedium-LowMedium-High
+745870102510751100124014251515
Factory Default6657809259851015111513051380
–590690815865900102511701250
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specic DIP Switch
Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 250 cfm.
Lennox Harmony III™ Zone Control Applications - Minimum blower speed is 250 cfm.