Lennox SL280UH090V36B, SL280DF070V36A, SL280UH070V36A, SL280UH090V48B, SL280UH090V60C Unit Information

...
Corp. 1117-L4
Service Literature
Revised 06-2016
icomfort® ENABLED SL280DFV SERIES UNITS
SL280DFV series units are 80% efficiency gas furnaces
used for downflow applications only, manufactured with
Lennox Duralok heat exchangers formed of aluminized
steel. Units are available in heating capacities of 66,000 to
110,000 Btuh and cooling applications up to 5 tons. Refer to
Engineering Handbook for proper sizing.
Units are factory equipped for use with natural gas. Kits are
available for conversion to LPG operation. SL280DFV mod
®
el units are equipped with the icomfort
two-stage variable speed integrated control. All units use a
redundant gas valve to assure safety shut-off as required by
CSA.
All specifications in this manual are subject to change. Pro
cedures outlined in this manual are presented as a recom
mendation only and do not supersede or replace local or
state codes. In the absence of local or state codes, the
guidelines and procedures outlined in this manual (except
where noted) are recommendations only and do not consti
tute code.
TABLE OF CONTENTS
Specifications Page 2.............................
Parts Identification Page 3.........................
I Unit Components Page 4........................
II Installation Page 29............................
III Start Up Page 29..............................
IV Heating System Service Checks Page 31.........
V Typical Operating Characteristics Page 34.........
VI Maintenance Page 34..........................
enabled SureLight
SL280DFV
®
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person al injury or loss of life. Installation and service must be performed by a licensed professional HVAC in staller (or equivalent), service agency or the gas sup plier.
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at discon nect switch(es). Unit may have multiple power supplies.
VII Wiring and Sequence of Operation Page 38......
VIII Program Unit Capacity Size Mode Page 42......
IX Field Wiring and Jumper Settings Page 43........
X Troubleshooting Flow Chart Page 47..............
Page 1
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal in jury. Take care while handling this equipment and wear gloves and protective clothing.
© 2016 Lennox Industries Inc.
SPECIFICATIONS
Gas Heating Performance
High Fire
Temperature rise range - °F 35-65 35-65 35-65 35-65
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
Low Fire
Temperature rise range - °F 25-55 25-55 25-55 25-55
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
High static - in. w.g. Heating 0.8 0.8 0.8 0.8
Connections
Flue connection - in. round 4 4 4 4
in.
Indoor
Wheel nominal diameter x width - in. 10 x 8 11 x 9 11 x 10 11 x 10
Blower
Tons of add-on cooling 2 - 3 3 - 4 3.5 - 5 3.5 - 5
Air Volume Range - cfm 589 - 1514 830 - 1996 899 - 2273 882 - 2120
Electrical Data
Blower motor full load amps 7.7 12.8 12.8 12.8
Maximum overcurrent protection 15 20 20 20
Shipping Data lbs. - 1 package 130 153 164 173
NOTE - Filters and provisions for mounting are not furnished and must be eld provided.
1
Annual Fuel Utilization Efciency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
Model No. SL280DF070V36A SL280DF090V48B SL280DF090V60C SL280DF110V60C
1
AFUE 80% 80% 80% 80%
Input - Btuh 66,000 88,000 88,000 110,000
Output - Btuh 52,000 69,000 70,000 87,000
3.5 / 10.0 3.5 / 10.0 3.5 / 10.0 3.5 / 10.0
Input - Btuh 43,000 57,000 57,000 72,000
Output - Btuh 35,000 46,000 46,000 59,000
1.7 / 4.9 1.7 / 4.9 1.7 / 4.9 1.7 / 4.9
Cooling 1.0 1.0 1.0 1.0
Gas pipe size IPS 1/2 1/2 1/2 1/2
Motor output - hp 1/2 1 1 1
Voltage 120 volts - 60 hertz - 1 phase
OPTIONAL ACCESSORIES - MUST BE ORDERED EXTRA
“A” Width
Models
CABINET ACCESSORIES
Downow Combustible Flooring Base 11M59 11M60 11M61
CONTROLS
ComfortSense® 7000 Thermostat Y0349 Y0349 Y0349
Remote Outdoor Sensor (for dual fuel and Humiidtrol
®
) X2658 X2658 X2658
DOWNFLOW FILTER KITS
Downow Filter Kit 51W06 51W07 51W08
No. and Size of lter - in. (1) 20 x 16 x 1 (2) 20 x 20 x 1 (2) 20 x 20 x 1
NIGHT SERVICE KITS
Night Service Kit 16S36 16S36 16S36
Safety Service Kit 89W19
“B” Width
Models
“C” Width
Models
89W19 89W19
GAS HEAT ACCESSORIES
Models
Natural Gas to
LPG/Propane Kit
all 11K51 11K46
LPG/Propane to
Natural Gas Kit
Page 2
FLUE CHASE
CONTROL BOX
(Includes two-stage integrated control,
transformer and circuit breaker)
INTERNAL FLUE PIPE ASSEMBLY

PARTS IDENTIFICATION

BLOWER ASSEMBLY
GASKET
SECONDARY LIMIT
DOOR INTERLOCK SWITCH
ROLLOUT SWITCH
INNER BLOWER ACCESS PANEL
ACCESS PANEL
PRIMARY LIMIT LOCATION
HEAT EXCHANGER
COMBUSTION AIR INDUCER
PRESSURE SWITCHES
COMBUSTION AIR INDUCER
GAS VALVE
BURNER BOX ASSEMBLY
FIGURE 1
Page 3
I-UNIT COMPONENTS
Unit components are shown in figure 1. The gas valve, combustion air inducer and burners can be accessed by re moving the access panel. Electrical components are in the control box (figure 2) found in the blower section.
CIRCUIT BREAKER CB8
PRESS TO RESET
FIGURE 3
CAUTION
Electrostatic discharge can affect elec tronic components. Take precautions to neutralize electrostatic charge by touching your hand and tools to metal prior to handling the control.
A- Control Box
1. Control Transformer (T1)
A transformer located in the control box provides power to the low voltage section of the unit. Transformers on all models are rated 40VA with a 120V primary and a 24V sec ondary.
2. Door Interlock Switch (S51)
An interlock switch rated 14A at 125VAC is wired in series with line voltage. When the indoor blower access panel is removed the unit will shut down.
CONTROL BOX SL280DFV
Transformer
Interlock Switch
WARNING
Shock hazard. Disconnect power before servicing. Integrated
control is not field repairable.
If control is inoperable, simply replace entire con trol.
Can cause injury or death. Unsafe operation will result if repair is attempted.
4. SureLight Integrated Control (A92)
Units are equipped with the icomfort enabled Sur
®
eLight control is used with the icomfort Wi-Fi of a communicating comfort system. The control can also operate with a non-communicating conventional single or two-stage thermostat. The system consists of a ignition / blower control (figures 4 and 5) with control pin designa tions in tables 1, 2 and 3 and ignitor (figure 13). The control and ignitor work in combination to ensure furnace ignition and ignitor durability. The control provides gas ignition, safety checks and indoor blower control with two-stage gas heating. The furnace combustion air inducer, gas valve and indoor blower are controlled in response to various system inputs such as thermostat signal, pressure and limit switch signal and flame signal. The control features a seven-seg ment LED display, indicating furnace status (including in door blower) and error codes. The LED flashes in single digits. For example using table 5 under LIMIT CODE, an “E” followed by “2” followed by “5” followed by “0”, the limit switch circuit is open. The control also has two unpowered (dry) 1/4” contacts for a humidifier and a 120 volt accessory terminal. Both rated at (1) one amp each.
two-stage, variable speed integrated control. This
®
thermostat as part
Circuit Breaker
SureLight
®
Integrated Control
FIGURE 2
3. Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box. The switch provides overcurrent protection to the trans former (T1). The breaker is rated 3A at 32V. If the current exceeds this limit the breaker will trip and all unit opera tion will shutdown. The breaker can be manually reset by pressing the button on the face. See figure 3.
Electronic Ignition
At the beginning of the heat cycle the integrated control monitors the first stage and second stage combustion air inducer prove switch. The control will not begin the heating cycle if the first stage prove switch is closed (by-passed). Likewise the integrated control will not begin the second stage heating cycle if the second stage prove switch is closed, and will remain in first stage heat. However, if the second stage prove switch closes during the first stage heat pre-purge, the control will allow second stage heat. Once the first stage prove switch is determined to be open,
Page 4
the combustion air inducer is energized on low (first stage) heat speed. When the differential in the prove switch is great enough, the prove switch closes and a 15-second pre-purge begins.
NOTE - During abnormal conditions such as low supply voltage or low outdoor temperatures and the low fire pres sure switch does not close, the combustion air inducer will switch to high fire. After a 15 second pre-purge the high fire pressure switch will close and the unit will begin operation on high fire. After 10 to 20 seconds of high fire operation the unit will switch to low fire
After the 15-second pre-purge period, the SureLight ignitor warms up for 20 seconds after which the gas valve opens for a 4-second trial for ignition. The ignitor energizes during the trial until flame is sensed. If ignition is not proved during the 4-second period, the control will try four more times with an inter purge and warm-up time between trials of 35 sec onds. After a total of five trials for ignition (including the ini tial trial), the control goes into Watchguard-Flame Failure mode. After a 60-minute reset period, the control will begin the ignition sequence again.
Two Stage Operation / Thermostat Selection DIP Switch
The control can be utilized in two modes: SINGLE-STAGE thermostat or TWO-STAGE thermostat. The thermostat selection is made using a DIP switch and must be posi tioned for the particular application. DIP switch 1, labeled T”STAT HEAT STAGE is factory-set in the OFF position for use with a two-stage thermostat. Move the DIP switch to ON for use with a single stage thermostat. While in the single-stage thermostat mode (single DIP switch setting), the burners will always fire on first-stage heat. The combustion air inducer will operate on low speed and indoor blower will operate on low heat speed. After a factory default 10 minute recognition period, the unit will switch to second stage heat. While in the two-stage ther mostat mode (two DIP switch setting) the burners will fire on first-stage heat. The combustion air inducer will operate on low speed and indoor blower will operate on low heat speed. The unit will switch to second-stage heat on call from the indoor thermostat. If there is a simultaneous call for first and second stage heat, the unit will fire an first stage heat and switch to second stage heat after 30 seconds of operation. See Sequence of Operation flow charts in the back of this manual for more detail.
TABLE 1
SureLight
®
Control 5 Pin Terminal Designation
PIN # Function
1 Ignitor
2 Combustion Air Inducer High Speed
3 Combustion Air Inducer Low Speed
4 Combustion Air Inducer Neutral
5 Ignitor Neutral
TABLE 2
SureLight
®
Control 12 Pin Terminal Designation
PIN # Function
1 Gas Valve High Fire
2 Second Stage Prove Switch
3 Rollout In
4 Ground
5 24V Hot
6 Primary Limit In
7 Gas Valve Low Stage
8 Gas Valve Common
9 24V Neutral
10 Ground
11 Rollout Switch Out
12 1st Stage Prove Switch
TABLE 3
SureLight
®
Control 6 Pin Terminal Designation
PIN # Function
1 Data Input From Motor
2 Common
3 Not Used
4 Data Output To Motor
5 5 Volt Bias Supply
6 Not Used
Page 5
HUM
LINE 1
7 SEGMENT LED
FLAME SENSE
DIAGNOSTIC
PUSH BUTTON
DIP SWITCHES
INTEGRATED CONTROL
ACC
HS/ CAI
INDOOR
BLOWER
CONNECTOR
NEUTRAL
OUTDOOR AIR
SENSOR
TERMINALS
DISCHARGE AIR
SENSOR
TERMINALS
TB83
COMMUNICATING
OUTDOOR
EQUIPMENT
I + I -CRI + I -
TB84
COMMUNICATING
INDOOR
THERMOSTAT
R
RS-BUS LINK (TB82, future use)
I+ = DATA HIGH CONNECTION I - = DATA LOW CONNECTION
RS-BUS OUTDOOR (TB83)
R = 24VAC I + = DATA HIGH CONNECTION I - = DATA LOW CONNECTION C = 24VAC COMMON
RS-BUS INDOOR (TB84)
R = 24VAC I + = DATA HIGH CONNECTION I - = DATA LOW CONNECTION C = 24VAC COMMON
1/4” QUICK CONNECT TERMINALS
HUM = UNPOWERED NORMALLY OPEN (DRY) CONTACTS
XMFR = 120 VAC OUTPUT TO TRANSFORMER
LI = 120 VAC INPUT TO CONTROL
ACC = 120 VAC OUTPUT TO OPTIONAL ACCESSORY
NEUTRALS = 120 VAC NEUTRAL
C
W1 W2 GY2Y1
NON-COMMUNICATINGNG
24V TERMINALS
12 PIN LOW
VOLTAGE
CONNECTOR
W915 Y1 TO Y2
2 STAGE COMPR
W951 R TO O HEAT PUMP
W914 R TO DS
DEHUM OR
CC
RDHLODS
HARMONY
THERMOSTAT CONNECTIONS (TB1)
DS = DEHUMIDIFICATION SIGNAL W2 = HEAT DEMAND FROM 2ND STAGE T/STAT W1 = HEAT DEMAND FROM 1ST STAGE T/STAT
R = CLASS 2 VOLTAGE TO THERMOSTAT
G = MANUAL FAN FROM T'STAT
C = THERMOSTAT SIGNAL GROUND CONNECTED TO
TRANSFORMER GRD (TR) & CHASIS GROUND (GRD)
Y1 = THERMOSTAT 1ST STAGE COOL SIGNAL
Y2 = THERMOSTAT 2ND STAGE COOL SIGNAL
O = THERMOSTAT SIGNAL TO HEAT PUMP
DH = DEHUMIDIFICATION OUTPUT COMMUNICATING
L = USE ONLY WITH A COMMUNICATING THERMOSTAT
AND A NON-COMMUNICATING OUTDOOR UNIT
REVERSING VALVE
THERMOSTAT ONLY
FIGURE 4
Page 6
THERMOSTAT SELECTION
1
2
3
*
TWO STAGE
THERMOSTAT
1−STAGE
THERMOSTAT
(TIMED STAGING)
−SEE SW #2
HEATING BLOWER−OFF DELAY
*
90 SECOND
HTG BLOWER
OFF DELAY
60 SECOND
HTG BLOWER
OFF DELAY
120 SECOND
HTG BLOWER
OFF DELAY
180 SECOND
HTG BLOWER
OFF DELAY
−BLOWER ON DELAY − 30 SEC. FIXED
4
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
HEATING MODE BLOWER SPEED
9
11
10
+ 24%
+ 18%
+ 12%
INCREASE AIR HTG CFM
+ 6%
*
FACTORY
DEFAULT
− 6%
− 12%
DECREASE AIR HTG CFM
− 18%
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
INTEGRATED CONTROL CONFIGURATION GUIDE
2ND STAGE HEAT ON DELAY
1
2
3
4
5
2
3
4
S1
7
8
15
14
INDOOR EQUIPMENT
1
6
5
6
HEAT PUMP LINK
(JUMPERS R to O)
*
5
6
7
8
5
6
7
8
5
6
7
8
5
6
7
8
5
6
7
8
5
6
7
8
13
12
15
14
13
12
15
14
13
12
15
14
13
12
15
14
13
12
15
14
ON
7 MIN
UPSTAGE
DELAY
ON
12 MIN
UPSTAGE
DELAY
DIAGNOSTIC
PUSH BUTTON
FLAME SENSE
123456
ON
S4S3
911
10
12
ON
OUTDOOR
SENSOR
DISCHARGE
AIR SENSOR
I+ I−
RI+ I−CRI+ I− C
OUTDOOR EQUIPMENT
1−STG COMPRESSOR
W915
2 STAGE
COMPR
1
13
DO NOT CUT
13
12
15
14
13
12
15
14
13
12
15
14
2−STG COMPRESSOR
W915
2 STAGE
COMPR
CUT LINK
2−STAGE
COMPRESSOR LINK
(JUMPERS Y1 to Y2)
W915
CLG BLOWER SPEED ADJUSTMENT
*
7
7
HUM
W1W2 G Y2 Y1 C C DHL O DSR
HEAT PUMP UNIT
DEFAULT
8
8
ACC
W1
W2GY2
ON−BOARD LINK
OPTION SELECTION
A/C UNIT
W951
HEAT PUMP
DO NOT CUT
W951
HEAT PUMP
CUT LINK
1
W951
ON
ON
+ 10%
ON
− 10%
L1
DIAGNOSTIC
LED
SureLight
C
C
Y1
1
2
3
4
5
6
7
1
2
3
4
5
6
7
1
2
3
4
5
6
7
HSI/CAI
1
5
J3
N
N
IGN
CAI1
CAI2
P79
14
®
R
NO HARMONY ZONING
NO SIGNATURESTAT
W/ DS CONNECTION
6
3
110
4 7
3
12
CUT FOR
OPTION
SELECTION
W915
2 STAGE
COMPR
W951 HEAT
PUMP W914
DEHUM
HARMONY
L
DH
OR
DO NOT CUT
W914
DEHUM
or
HARMONY
HARMONY ZONING
OR
SIGNATURESTAT W/
DS CONNECTION
CUT LINK
1
W914
DEHUM
or
HARMONY
DEHUMIDIFICATION−
HARMONY LINK
(JUMPERS R to DS)
W914
8
CONTINUOUS FAN MODE BLOWER SPEED
8
8
NEUTRALS
MEDIUM−LOW
*
SPEED
(38%)
MEDIUM−HIGH
SPEED
(70%)
LOW
SPEED
(28%)
HIGH SPEED (100%)
9
11
10
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
COOLING MODE BLOWER SPEED
1
2
3
*
HIGH
SPEED
MEDIUM−HIGH
J2
SPEED
MEDIUM−LOW
SPEED
LOW
SPEED
COOLING MODE BLOWER RAMPING
*
OPTION A
OFF−50%−82%−
100%−50%−OFF
OPTION B
OFF−82%−100%−OFF
OPTION C
OFF−100%−100%−OFF
OPTION D
OFF−100%−OFF
−CUT ON−BOARD LINK (SOLDER TRACE) COMPLETELY THROUGH
1
BOTH LAYERS ON THE CONTROL BOARD
−LINKS CUT IN ERROR −INSTALL A JUMPER ON THE APPROPRIATE TERMINALS ON THE TERMINAL STRIP
−PROTECTIVE PLASTIC FILM ON DIP SWITCHES MAY BE REMOVED FOR EASE IN SETTING OF DIP SW.
* FACTORY DEFAULT
ON
1
2
3
ON
1
2
3
ON
1
2
3
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
13
12
15
14
12
15
14
12
15
14
12
15
14
4
5
6
7
8
4
5
6
7
8
4
5
6
7
8
4
5
6
7
8
13
15
12
14
13
12
15
14
13
12
15
14
13
12
15
14
FIGURE 5
Page 7
TABLE 4
Integrated Control Diagnostic Modes
Display Action (when button released)
No change (idle)* Remain in idle mode
Solid “E” Enter diagnostic recall mode
Solid “D” Discharge Air Installed
Solid “F” Enter flame signal mode
Solid “P” (variable speed only) Program unit capacity/size (Unit Code)
* No change implies the display will continue to show whatever is currently being displayed for normal operation (blinking decimal, active error code, heat state, etc..)
Diagnostic LED (Figure 4)
The seven-segment diagnostic LED displays operating status, target airflow, error codes and other information. The table beginning on Page 9 lists diagnostic LED codes.
Flame Signal Mode
Select ”F” from the menu to access the flame signal mode. The integrated control will display the flame current on 7 segment LED in in micro amps (uA).
Flame signal mode is exited after any of the following:
Diagnostic Push Button (Figure 4)
The diagnostic push button is located adjacent to the seven-segment diagnostic LED. This button is used to en able the Error Code Recall “E” mode and the Flame Signal “F” mode. Press the button and hold it to cycle through a menu of options. Every five seconds a new menu item will be displayed. When the button is released, the displayed item will be selected. Once all items in the menu have been displayed, the menu resumes from the beginning until the button is released.
Error Code Recall Mode
Select ”E” from the menu to access the most recent 10 error codes. Select “c” from the Error Code Recall menu to clear all error codes. Button must be pressed a second time while “c” is flashing to confirm command to delete codes. Press the button until a solid “” is displayed to exit the Error Code Recall mode.
Power is reset Pressing and holding push button until 3 horizontal
lines “” are displayed
10 minutes after entering the flame sense mode.
Program Unit Capacity/Size Mode
After the “P” is selected (by releasing the push button) the integrated control will start flashing the “P” on display for 90 seconds. If push button is pressed again and held during that time, the control will start to display characters corre sponding to different variable speed furnace models for 3 seconds each. While the wanted character-model is dis played push button has to be released. Selected option will flash display for 10 seconds and during that time push but ton has to be pressed and held for 5 seconds. Once control accepts new setting it will store data in non-volatile memory and reset itself. If 10 seconds expires or push button is held less than 5 seconds, control will exit field test mode and go into idle without changing programming the unit size.
Page 8
TABLE 5
Integrated Diagnostic Codes/Status of Equipment I.
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
.
Idle mode (Decimal blinks at 1 Hertz -- 0.5 second ON, 0.5 second OFF).
A
C
d
h
H
dF U E 105
E 110
E 111
E 112
E 113
E 114
E 115
E 116
E 117
E 120
Cubic feet per minute (cfm) setting for indoor blower (1 second ON, 0.5 second OFF) / cfm setting for current mode displayed.
Cooling stage (1 second ON, 0.5 second OFF) / 1 or 2 displayed / Pause / cfm setting displayed / Pause / Repeat codes).
Dehumidification mode (1 second ON) / 1 second OFF) / cfm setting dis played / Pause / Repeat Codes).
Heat pump stage (1 second ON, 0.5 second OFF) / % of input rate dis played / Pause / cfm setting / Pause / Repeat codes.
Gas Heat Stage (1 second ON, 0.5 second OFF) / 1 or 2 displayed / Pause / cfm setting displayed / Pause / Repeat codes. Blinking during ignition.
Defrost mode.
Discharge Air Temperature
Device communication problem - No other devices on RS BUS (Commu nication system).
Low line voltage. Line Voltage Low (Voltage lower than nameplate
Line voltage polarity reversed. Reverse line power voltage wiring. System resumes
Ground not detected System shuts down. Provide proper earth ground.
High line voltage. Line Voltage High (Voltage higher than nameplate
Line voltage frequency out-of-range. No 60 Hertz Power. Check voltage and line power
Low 24V - Control will restart if the error recovers. 24-Volt Power Low (Range is 18 to 30 volts). Check
High 24V. 24 Volt Power High (Range is 18 to 30 volts). Check
Poor ground detected (Warning only) Provide proper grounding for unit. Check for proper
Unresponsive device. Communication only. Usually caused by delay in outdoor unit responding
Equipment is unable to communicate. Indicates numerous message errors. In most cases errors are related to electrical noise. Make sure high voltage power is separated from RSBus. Check for mis­wired and/or loose connections between the stat, indoor unit and outdoor unit. Check for a high volt age source of noise close to the system. Fault clears after communication is restored.
rating). Check power line voltage and correct. Alarm clears 5 seconds after fault recovered.
normal operation 5 seconds after fault recovered.
System resumes normal operation 5 seconds after fault recovered.
rating). Provide power voltage within proper range. System resumes normal operation 5 seconds after fault recovered.
frequency. Correct voltage and frequency problems. System resumes normal operation 5 seconds after fault recovered.
and correct voltage. Check for additional power-rob bing equipment connected to system. May require installation of larger VA transformer to be installed in furnace / air handler. Clears after fault recovered.
and correct voltage. Check for proper line voltage (120V, 240V, etc.) to equipment. Clears when con trol senses proper voltage.
earth ground to the system. Warning only will clear 30 seconds after fault recovered.
to indoor unit poling. Recycle power. Check all wir ing connections. Cleared after unresponsive device responds to any inquiry.
Page 9
TABLE 5 Continued
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E 124
Active communicating thermostat signal missing for more than 3 min utes.
E 125
Control failed self-check, internal error, failed hardware. Will restart if error recovers. Integrated control not communicating. Covers hardware errors (flame sense circuit faults, pin shorts, etc.).
E 126
Control internal communication problem. Hardware problem on the control. Cycle power on
E 131
Corrupted control parameters (Verify configuration of system). Communi cating only.
E 180
Outdoor air temperature sensor failure. Only shown if shorted or out-of­range.
E 200
Hard lockout - Rollout circuit open or previously open. Correct cause of rollout trip, or replace flame rollout
E 201
Indoor blower communication failure - Unable to communicate with blow er motor.
E 202
Indoor blower motor mis-match - Indoor motor horsepower does not match unit capacity. See Page 41.
E 203
Appliance capacity / size is NOT programmed. Invalid unit codes refer to configuration flow chart. See Page 41.
E 204
Gas valve mis-wired. Check gas valve operation and wiring. Clears when
E 205
Gas valve control relay contact shorted. Check wiring on control and gas valve. If wiring is
Equipment lost communication with the thermostat. Check four wiring connections, ohm wires and cycle power at the thermostat. Alert stops all services and waits for heartbeat message from thermostat (sub net controller). Cleared after valid thermostat (sub net controller) message is received.
Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Critical alert. Cleared 300 seconds after fault recovered.
control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recov ered.
Reconfigure the system. Replace control if heating or cooling is not available. Only applicable in the communicating mode, not in startup. Exit from Com missioning and Execute 'Set Factory Default mode'. Control will still operate on default parameter set tings.
Compare outdoor sensor resistance to temperature/ resistance charts in unit installation instructions. Replace sensor pack if necessary. At beginning of (any) configuration, furnace or air handler control will sense outdoor air and discharge air temperature sensor(s). If detected (reading in range), appropri ate feature will be set as 'installed' and that could be seen in 'About' screen. In normal operation after control recognizes sensors, alarm will be sent if valid temperature reading is lost. To get rid of set ting and alarm, redo configuration and make sure that temperature sensor is marked as 'not installed' in Indoor Unit 'About' screen. When Indoor unit con trol is replaced, thermostat will 'tell' new control if temperature sensor is in system or not. Clears 30 seconds after fault recovered.
switch. Test furnace operation. Cleared after fault recovered.
Indoor blower communication failure (including pow er outage). Lost communication with indoor blower motor. Possible causes: motor not powered, loose wiring. Problem may be on control or motor side. Cleared after fault recovered.
Incorrect appliance capacity code selected. Check for proper configuring under: Unit Size Codes for Furnace/Air Handler on configuration guide or in installation instructions. Cleared after the correct match is detected following a reset. (Remove ther mostat from system while applying power and re programming.)
No appliance capacity code selected. Check for proper configuring under: Unit Size Codes for Fur nace on configuration guide or in installation instruc tions. Critical Alert. Cleared after valid unit code is read following a reset. (Remove thermostat from system while applying power and reprogramming.)
repaired.
correct, replace control.
Page 10
TABLE 5 Continued
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E 206
E 207
E 223
E 224
E 225
E 226
E 227
E 228
E 229
E 240
E 241
E 250
E 252
E 270
Gas valve second-stage relay failure Furnace will operate on 1st stage for remainder of
the heating demand. Will clear after fault recovered. If unable to operate 2nd stage, replace control.
Hot surface ignitor sensed open - Refer to troubleshooting. SeePage 46. Measure resistance of hot surface ignitor. Replace if
open or not within specified range found in IOM. Resumes normal operation after fault is cleared.
Low pressure switch failed open. Check pressure (inches w.c.) of low pressure switch
closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air in ducer for correct operation and restriction. Re sumes normal operation after fault is cleared
Low pressure switch failed closed - Refer to troubleshooting. See Page 46.
High pressure switch failed open - Refer to troubleshooting. See Page 46.
High pressure switch failed closed - Refer to troubleshooting. See Page 46.
Low pressure switch open during trial for ignition or run mode. Refer to troubleshooting. See Page 46.
Combustion air inducer calibration failure Unable to perform pressure switch calibration.
Ignition on High Fire - Information Only Code is displayed if 1) low pressure switch fails to
Low flame current - Run mode - Refer to troubleshooting. See Page 46. Check micro-amperes of flame sensor using control
Flame sensed out of sequence - Flame still present. Shut off gas. Check for gas valve leak. Replace, if
Limit switch circuit open - Refer to troubleshooting. See Page 46 Check for proper firing rate on furnace. Ensure
Discharge air temperature too high (gas heat only). Check temperature rise, air flow and input rate.
Soft lockout - Exceeded maximum number of retries. No flame current sensed.
Check operation of low pressure switch to see if it is stuck closed on heat call longer than 150 seconds. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct opera tion and restriction. Resumes normal operation after fault is cleared.
Check pressure (inches w.c.) of high pressure switch closing on heat call. Measure operating pres sure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Re sumes normal operation after fault is cleared.
Check operation of high pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal opera tion after fault is cleared.
Check pressure (inches w.c.) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air in ducer for correct operation and restriction. Re sumes normal operation after fault is cleared.
Check vent system and pressure switch wiring con nections. Resumes normal operation after fault is cleared.
close, then furnace will switch to high speed inducer to close both low and high pressure switches, then furnace lights on high fire, or 2) if continuous fan is active, furnace lights on high fire for 60 seconds to improve heat exchanger warm up time.
diagnostics or field-installed mode. Clean or replace sensor. Measure voltage of neutral to ground to ensure good unit ground. Alert clears after current heat call has been completed.
necessary. Alert clears when fault is recovered.
there is no blockage in heater. Check for proper air flow. If limit not closed within 3 minutes, unit will go into 1-hour soft lockout. Resumes normal operation after fault is cleared.
Cleared when heat call is finished.
Check for proper gas flow. Ensure that ignitor is lighting burner. Check flame sensor current. Clears when heat call finishes successfully.
Page 11
TABLE 5 Continued
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E 271
Soft lockout - Exceeded maximum number of retries. Last retry failed due to the pressure switch opening.
E 272
Soft lockout - Exceeded maximum number of recycles. Last recycle due to the pressure switch opening.
E 273
Soft lockout - Exceeded maximum number of recycles. Last recycle due to flame failure.
E 274
Soft lockout - Exceeded maximum number of recycles. Last recycle failed due to the limit circuit opening or limit remained open longer than 3 minutes.
E 275
Soft lockout - Flame sensed out of sequence. Flame signal is gone. Shut off gas. Check for gas valve leak. 1-hour soft
E 276
Watchguard calibration failure. Unable to perform pressure switch calibration.
E 290
Ignitor circuit fault - Failed ignitor or triggering circuitry. Measure resistance of hot surface ignitor. Replace if
E 291
Heat air flow restricted below the minimum. Check for dirty filter and air flow restriction. Check
E 292
Indoor blower motor unable to start due to obstructed wheel, seized bearings.
E 294
Combustion air inducer over current. Check combustion blower bearings, wiring and
E 295
Indoor blower motor temperature is too high. Indoor blower motor over temperature (motor
E 310
Discharge error temperature sensor failure. Only shown if shorted or out of range.
E 311
Heat rate reduced to match indoor blower air flow. Warning Only. Furnace blower in cutback mode due
Check pressure (inches w.c.) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air in ducer for correct operation and restriction. Clears when heat call finishes successfully.
Check operation of low pressure switch to see if it is stuck closed on heat call. Check pressure (inches w.c.) of high pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct opera tion and restriction. Clears when heat call finishes successfully.
Check micro-amperes of flame sensor using control diagnostics or field-installed mode. Clean or replace sensor. Measure voltage of neutral to ground to ensure good unit ground. Clears when heat call finishes successfully.
Shut down system. 1-hour soft lockout. Check firing rate and air flow. Check for blockage. Clears when heat call finishes successfully.
lockout. Clears when flame has been proven stable.
Check vent system and pressure switch wiring con nections. 1-hour soft lockout. Clears when calibra tion has finished successfully.
open or not within specifications. 1-hour soft lock out. Clears when flame has been proven stable.
blower performance. 1-hour soft lockout. Cleared when heat call finishes successfully.
Indoor blower motor unable to start (seized bear ing, stuck wheel, etc.). Replace motor or wheel if assembly does not operate or meet performance standards. 1-hour soft lockout. Clears after circula tor successfully starts.
amps. Replace if does not operate or does not meet performance standards. Clears after inducer current is sensed to be in-range after the ignition following the soft lockout or reset.
tripped on internal protector). Check motor bearings and amps. Replace if necessary. Cleared after blower demand is satisfied.
Compare outdoor sensor resistance to temperature/ resistance charts in installation instructions. Re place sensor if necessary. Cleared in Communicat ing mode: 30 seconds after fault recovered. In Non­Communicating mode: Cleared after the current heat call is completed.
to restricted airflow. Reduce firing rate every 60 seconds to match available CFM. Check filter and duct system. To clear, replace filter if needed or re pair/add duct. 2-stage controls will reduce firing rate
st
stage. Clears when heat call finishes success
to 1 fully.
Page 12
TABLE 5 Continued
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E 312
E 313
E 331 E 334 E 347
E 348
E 349
E 370
E 400
E 401
E 402
E 403
E 404
E 405
Restricted air flow in cooling or continuous fan mode is lower than cfm setting.
Indoor or outdoor unit capacity mismatch. Communication only. Incorrect indoor/outdoor capacity code selected.
Global network connection - Communication link problem. For Future Use.
Relay “Y1” stuck on interated control. Replace integrated control.
No 24 Volt output on Y1 of ”integrated control” with non communicating outdoor unit.
No 24 Volt output on Y2 of ”integrated control” with non?communicating outdoor unit.
No 24 Volts between R & O on ”integrated control” with non communi cating outdoor unit (Dual fuel module required for heat pump applica tion).
Interlock switch sensed open for 2 minutes. Control sees the loss of 24VAC for 2 minutes .Ter
LSOM - Compressor internal overload tripped. Thermostat demand Y1 is present; but, compres
LSOM Compressor long run cycle or low system pressure. Compressor ran more than 18 hours to satisfy a
LSOM - Outdoor unit system pressure trip. Discharge or suction pressure out-of-limits, or
LSOM - Compressor short-cycling. .(Running less than 4 minutes). Outdoor unit pressure trip
LSOM - Compressor rotor locked. Compressor short-cycling. (Running less than 4 minutes).
LSOM - Compressor open circuit. Compressor circuit open (due to power disconnec
Warning Only. Restricted airflow - Indoor blower is running at a reduced CFM (Cutback Mode - The variable speed motor has pre-set speed and torque limiters to protect the motor from damage caused by operating outside of design parameters (0 to 0.8” W.C.. total external static pressure). Check filter and duct system. To clear, replace filter if needed or repair/add duct. Cleared after the current service demand is satisfied.
Check for proper configuring in installation instruc tions. Alarm is just a warning. The system will op erate, but might not meet efficiency and capacity parameters. Alarm will clear when commissioning is exited. Cleared after commissioning is com plete.
Operation stopped. Y1 relay / Stage 1 failed. (Pilot relay contacts did not close or the relay coil did not energize; no input back to IFC chip). Critical Alert. Cleared after reset and Y1 input sensed.
Y2 relay / Stage 2 failed. (Pilot relay contacts did not close or the relay coil did not energize; no in put back to IFC chip). Critical Alert. Cleared after reset and Y1 input sensed.
Configuration link R to O needs to be restored. Replace link or hard-wire. Applicable in non com municating mode. Critical Alert.
minate all services and wait for interlock switch to close. The alarm will clear when 24VAC is continu ously sensed on DS terminal for a minimum of 10 seconds or on a power reset.
sor is not running. Check power to outdoor unit. Clears the error after current is sensed in both RUN and START sensors for at least 2 seconds, or after service is removed, or after power reset.
single thermostat demand. Critical Alert. Clears the error after 30 consecutive normal run cycles or power reset. Also monitors low pressure switch trips.
compressor overloaded. Clears the error after 4 consecutive normal compressor run cycles.
Compressor runs less than 3 minutes to satisfy a thermostat demand. Clears the error after 4 con secutive normal run cycles or power reset.
Compressor rotor locked up due to run capacitor short, bearings are seized, excessive liquid refrig erant, etc. Clears the error after 4 consecutive nor mal run cycles or after power reset.
tion, open fuse, etc.) Clears the error after 1 nor mal compressor run cycle.
Page 13
TABLE 5 Continued
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E 406
E 407
E 408
E 409
LSOM - Compressor open start circuit. Required amount of current is not passing through
Start current transformer. Clears the error after cur rent is sensed in START sensor, or after power re set.
LSOM - Compressor open run circuit. Required amount of current is not passing through
Run current transformer. Clears the error after cur rent is sensed in RUN sensor, or 1 normal compres sor run cycle, or after power reset.
LSOM - Compressor contactor is welded. Compressor runs continuously. Clears the error
after 1 normal compressor run cycle or after power reset.
LSOM - Compressor low voltage. Secondary voltage is below 18VAC. After 10 min
utes, operation is discontinued. Clears the code after voltage is higher than 20 VAC for 2 seconds or after power reset.
DIP Switch Settings
NOTE - All icomfortt settings are set at the icomfort Wi-Fi thermostat. See icomfortt installation instruction. In icom fortt communication system all DIP switch and clippable link settings are ignored. For conventional thermostats pro ceed with DIP switch and clippable link settings as outlined in the following.
Heating Operation DIP Switch Settings Switch 1 -- Thermostat Selection -- This unit may be
used with either a single-stage or two-stage thermostat. The thermostat selection is made using a DIP switch which must be properly positioned for the particular application. The DIP switch is factory-positioned for use with a two­stage thermostat. If a single-stage thermostat is to be used, the DIP switch must be repositioned.
a - Select “OFF” for two-stage heating operation con
trolled by a two-stage heating thermostat (factory set ting);
b - Select “ON” for two-stage heating operation con
trolled by a single-stage heating thermostat. This set ting provides a timed delay before second-stage heat is initiated.
Switch 2 -- Second Stage Delay (Used with Single­Stage Thermostat Only) -- This switch is used to deter
mine the second stage on delay when a single-stage ther mostat is being used. The switch is factory-set in the OFF position, which provides a 7-minute delay before second­stage heat is initiated. If the switch is toggled to the ON position, it will provide a 12-minute delay before second­stage heat is initiated. This switch is only activated when the thermostat selector jumper is positioned for SINGLE­stage thermostat use.
Switches 3 and 4 -- Blower-Off Delay -- The blower-on delay of 30 seconds is not adjustable. The blower-off delay (time that the blower operates after the heating demand has been satisfied) can be adjusted by moving switches 3 and 4 on the integrated control. The unit is shipped from the factory with a blower-off delay of 90 seconds. The blower
off delay affects comfort and is adjustable to satisfy individ
®
ual applications. Adjust the blower off delay to achieve a supply air temperature between 90° and 110°F at the exact moment that the blower is de-energized. Longer off delay settings provide lower supply air temperatures; shorter set tings provide higher supply air temperatures.Table 6 pro vides the blower off timings that will result from different switch settings.
TABLE 6
Blower Off Delay Switch Settings
Blower Off Delay
(Seconds)
Switch 3 Switch 4
60 On Off
90 (Factory) Off Off
120 Off On 180 On On
Indoor Blower Operation DIP Switch Settings Switches 5 and 6 -- Cooling Mode Blower Speed -- The
unit is shipped from the factory with the dip switches posi tioned for high speed (4) indoor blower motor operation during the cooling mode. Table 7 provides the cooling mode blower speeds that will result from different switch settings. Switches 5 and 6 set the blower cfm for second­stage cool. The integrated control automatically ramps down to 70% of the second-stage cfm for first-stage cfm. Refer to blower tables for corresponding cfm values.
TABLE 7
Cooling Mode Blower Speeds
Speed
Switch 5 Switch 6
Low On On
Medium Low Off On
Medium High On Off
High (Factory) Off Off
Switches 7 and 8 -- Cooling Blower Speed Adjustment
-- The unit is shipped from the factory with the dip switches
positioned for NORMAL (no) adjustment. The dip switches may be positioned to adjust the blower speed by +10% or
Page 14
-10% to better suit the application. Table 8 below provides blower speed adjustments that will result from different switch settings. Refer to blower tables for corresponding cfm values.
TABLE 8
Cooling Blower Speed Adjustment
Adjustment
Switch 7 Switch 8
+10% (approx.) On Off Factory Default Off Off
-10% (approx.) Off On
Switches 9 and 10 -- Cooling Mode Blower Speed Ramping -- Blower speed ramping may be used to en
hance dehumidification performance. The switches are factory set at option A which has the greatest effect on de­humidification performance. Table 9 provides the cooling mode blower speed ramping options that will result from different switch settings. The cooling mode blower speed ramping options are detailed below.
NOTE - The off portion of the selected ramp profile also ap plies during heat pump operation in dual fuel applications.
TABLE 9
Cooling Mode Blower Speed Ramping
Ramping Option
Switch 9 Switch 10
A (Factory) Off Off
B Off On C On Off D On On
Ramping Option A (Factory Selection)
Motor runs at 50% for 30 seconds. Motor then runs at 82% for approximately 7-1/2 minu
tes.
If demand has not been satisfied after 7-1/2 minutes,
motor runs at 100% until demand is satisfied.
Once demand is met, motor runs at 50% for 30 sec
onds then ramps down to stop.
OFF
1/2 MIN 50% CFM
7 1/2 MIN 82% CFM
COMPRESSOR DEMAND
100% CFM
1/2 MIN 50% CFM
OFF
Ramping Option B
Motor runs at 82% for approximately 7-1/2 minutes. If
demand has not been satisfied after 7-1/2 minutes, motor runs at 100% until demand is satisfied.
Once demand is met, motor ramps down to stop.
OFF
7 1/2 MIN
82%CFM
COMPRESSOR DEMAND
100% CFM
OFF
Ramping Option C
Motor runs at 100% until demand is satisfied.
Once demand is met, motor runs at 100% for 45 sec
onds then ramps down to stop.
OFF
100% CFM
COMPRESSOR
DEMAND
100% CFM
45 SEC.
OFF
Ramping Option D
Motor runs at 100% until demand is satisfied.
Once demand is met, motor ramps down to stop.
100% CFM
COMPRESSOR
DEMAND
OFFOFF
Switches 11, 12 and 13 -- Heating Mode Blower Speed --
The switches are factory set to the OFF position which pro vides factory default heat speed. Refer to table 10 for switches 11, 12 and 13 that provided the corresponding in creases or decrease to both high and low heat demand.
TABLE 10
Heating Mode Blower Speeds
Heat Speed
Switch
11
Switch12Switch
13
Increase 24% On On On
Increase 18% On On Off
Increase 12% On Off On
Increase 6% On Off Off
Factory Default Off Off Off
Decrease 6% Off Off On
Decrease 12% Off On Off
Decrease18% Off On On
Switches 14 and 15 -- Continuous Blower Speed --
Table 11 provides continuous blower speed adjustments that will result from different switch settings.
TABLE 11
Continuous Blower Speed
Continuous
Blower Speed
Switch 14 Switch 15
28% of High Cool Speed Off On
38% of High Cool Speed
(Factory)
Off Off
70% of High Cool Speed On Off
100% of High Cool Speed On On
Page 15
BLOWER DATA
SL280DF070V36A BLOWER PERFORMANCE (less lter) 0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
+24% 1065 1170
+18% 1010 1115
+12% 960 1055
+6% 910 1000
Factory Default 860 945
–6% 805 885
–12% 755 830
–18% 705 775
1
Cooling Speed
DIP Switch
Settings
Low Medium-Low Medium-High
+ 745 870 1025 1075 1100 1240 1425 1515
Factory Default 665 780 925 985 1015 1115 1305 1380
590 690 815 865 900 1025 1170 1250
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specic DIP Switch
Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 250 cfm. Lennox Harmony III™ Zone Control Applications - Minimum blower speed is 250 cfm.
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
COOLING
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
2
High Low Medium-Low Medium-High2 High
SL280DF070V36A BLOWER MOTOR WATTS (COOLING)
1
Cooling Speed
DIP Switch
Settings
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Motor Watts @ Various External Static Pressures - in. wg.
First Stage Second Stage
+ Setting
Low 46 63 83 96 115 128 144 170 181 138 162 177 212 229 247 270 288 320 342 363
Cooling
Speed
Med-low 66 81 104 127 144 160 175 195 219 185 210 238 266 293 317 349 374 399 432 448
Med-High 100 123 138 167 191 211 234 255 271 299 328 354 380 412 434 477 499 528 557 570
High 124 146 170 192 214 226 255 273 307 376 378 414 458 493 507 558 571 604 613 585
Factory Default
Low 38 57 64 85 98 107 133 147 158 104 125 144 166
Cooling
Speed
Med-low 49 72 87 96 122 135 160 176 197 141 167 184 216 237 256 288 304 326 356 383
Med-High 70 90 109 132 158 172 201 222 231 218 245 276 306 323 357 374 403 444 472 489
High 90 108 138 154 170 192 223 235 260 259 280 317 350 381 405 449 469 496 532 544
– Setting
Low 33 45 60 73 89 104 114 123 144 73 89 111 124 155 175 196 210 224 243 263
Cooling
Speed
Med-low 40 54 74 86 106 115 134 142 170 108 118 153 170 196 219 227 253 266 286 316
Med-High 52 74 85 107 128 149 161 181 201 156 181 208 222 253 284 305 333
High 64 82 98 129 139 157 183 197 214 176 198 228 267 283 317 355 382 396 425 450
192 212 230 261 267 295 315
356 374 398
Page 16
Loading...
+ 35 hidden pages