DAVE LENNOX SIGNATURE
COLLECTION GAS FURNACE
UPFLOW / HORIZONTAL AIR DISCHARGE
506763−01
06/2011
Supersedes 03/2011
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
This a safety alert symbol and should never be ignored.
When you see this symbol on labels or in manuals, be alert
to the potential for personal injury or death.
CAUTION
As with any mechanical equipment, personal injury
can result from contact with sharp sheet metal
edges. Be careful when you handle this equipment.
®
Litho U.S.A.
AIR FLOWAIR FLOW
HORIZONTAL LEFTHORIZONTAL RIGHT
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal injury or loss of life. Installation and service must
be performed by a licensed professional installer (or
equivalent), service agency or the gas supplier.
NOTE − 60C and 60D units that require air volumes over 1800 cfm
(850 L/s) must have one of the following:
1. Return air from single side transition will accommodate 20 x 25 x1 in.
(508 x 635 x 25) cleanable air filter. (Required to maintain proper air
velocity)
2. Single side return air with optional RAB Return
Air Base.
3. Return air from bottom and one side.
4. Return air from both sides.
5. Return air from bottom.
See blower performance tables for additional information
2
Flue outlet may be horizontal but furnace must be
vented vertically
3
Optional external side return air filter kit cannot be used
with the optional RAB Return Air Base.
FLUE OUTLET
D
(Top)
3
OPTIONAL
EXTERNAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
3−1/8 (79)
SUPPLY AIR
OPENING
23−3/4
(603)
25
(635)
TOP VIEW
3/4
(19)
A
B
AIR FLOW
C
1
Bottom Return
Air Opening
FRONT VIEW
9/16 (14)
3
OPTIONAL
EXTERNAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
14−3/4
(375)
16
(406)
5/8
(16)
3/4
(19)
9−1/8 (232) Right
8−5/8 (219) Left
33
(838)
5−3/8 (137) Right
2−3/4 (70) Left
1−1/2 (38)
Front Panel
3 (76) Right
7 (178) Left
3−1/4
(83)
3−1/4 (83)
2
FLUE OUTLET
(Either Side)
GAS PIPING INLET
(Either Side)
ELECTRICAL INLET
(Either Side)
(584)
1
Side Return
Air Opening
(Either Side)
23−1/2
(597)
1
Bottom Return
SIDE VIEW
23
27−3/4
(705)
19−7/16
(494)
1−15/16 (49)
14
(356)
9/16
(14)
1−1/2
(38)
Model No.
SL280UH070V36A14−1/236813−3/8340133304−3/4121
SL280UH090V36B
SL280UH090V48B
SL280UH090V60C
SL280UH110V60C
SL280UH135V60D24−1/262223−3/8546235849−3/4248
17−1/244616−3/8416164066−1/4159
ABCD
in.mm,in.mmin.mmin.mm
2153319−7/850419 1/24958203
Page 2
Parts Arrangement
COMBUSTION AIR INDUCER
COMBUSTION AIR INDUCER
PRESSURE SWITCH
HEAT EXCHANGER
ROLLOUT SWITCH
BURNER BOX
INNER BLOWER
ACCESS PANEL
GAS VALVE
ACCESS PANEL
SIGHT GLASS
CABINET
CONTROL BOX
(Includes two−stage integrated control,
transformer and circuit breaker)
FIGURE 1
Page 3
BLOWER
ASSEMBLY
SL280UHV Gas Furnace
The SL280UHV gas furnace is equipped with a two−stage,
variable speed integrated control. the control is compatible with:
Communicating thermostats − icomfort Touch
Non−comunicating thermostats − ComfortSense or other
conventional thermostats.
Control systems − Harmony III Zone Control System
(non−communicating).
Each SL280UHV unit is shipped ready for installation in
the upflow or horizontal position (left or right). The furnace
is shipped with the bottom panel in place. The bottom panel must be removed if the unit is to be installed in a horizontal application. The panel may also be removed in upflow
applications.
®
.
Shipping and Packing List
Package 1 of 1 contains
1 − Assembled SL280UHV unit
1 − Bag assembly containing the following:
The following items may be ordered separately:
1 − Thermostat
1 − Suspension Kit (for horizontal installations)
1 − Propane/LP changeover kit
1 − Return air base
1 − High altitude kit
1 − Side filter kit
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
Safety Information
DANGER
Danger of explosion.
There are circumstances in which odorant used with
LP/propane gas can lose its scent. In case of a leak,
LP/propane gas will settle close to the floor and may
be difficult to smell. An LP/propane leak detector
should be installed in all LP applications.
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal injury or loss of life. Installation and service must
be performed by a licensed professional installer (or
equivalent), service agency or the gas supplier.
CAUTION
As with any mechanical equipment, personal injury
can result from contact with sharp sheet metal
edges. Be careful when you handle this equipment.
Certifications
SL280UHV units are CSA International certified to ANSI
Z21.47.
In the USA, installation of gas furnaces must conform with
local building codes. In the absence of local codes, units
must be installed according to the current National Fuel
Gas Code (ANSI-Z223.1). The National Fuel Gas Code is
available from the following address:
American National Standards Institute, Inc.
11 West 42nd Street
New York, NY 10036
Clearances
Adequate clearance must be made around the air openings into the vestibule area. In order to ensure proper unit
operation, combustion and ventilation air supply must be
provided according to the current National Fuel Gas Code.
Vent installations must be consistent with the venting
tables (in this instruction) and applicable provisions of local
building codes.
This furnace is CSA International certified for installation
clearances to combustible material as listed on the unit
nameplate and in the tables in figures 7 and 11. Accessibility
and service clearances must take precedence over fire
protection clearances.
NOTE − For installation on combustible floors, the furnace
shall not be installed directly on carpeting, tile, or other
combustible material other than wood flooring.
Installed Locations
For installation in a residential garage, the furnace must
be installed so that the burner(s) and the ignition source
are located no less than 18 inches (457 mm) above the
floor. The furnace must be located or protected to avoid
physical damage by vehicles. When a furnace is installed
in a public garage, hangar, or other building that has a hazardous atmosphere, the furnace must be installed according to recommended good practice requirements and current National Fuel Gas Code.
Page 4
Temperature Rise
NOTE − Furnace must be adjusted to obtain a temperature
rise(high and low fire) within the range(s) specified on the unit
nameplate. Failure to do so may cause erratic limit operation
and may result in premature heat exchanger failure.
This SL280UHV furnace must be installed so that its electrical components are protected from water.
Installed in Combination with a Cooling Coil
When this furnace is used with cooling units, it shall be
installed in parallel with, or on the upstream side of, cooling
units to avoid condensation in the heating compartment.
See figure 1. With a parallel flow arrangement, a damper (or
other means to control the flow of air) must adequately prevent chilled air from entering the furnace. If the damper is
manually operated, it must be equipped to prevent operation
of either the heating or the cooling unit, unless it is in the full
HEAT or COOL setting. See figure 1.
Heating Unit Installed Parallell to Air Handler Unit
Dampers
(open during heating operation only)
Gas Unit
Air Handler Unit
Dampers
(open during cooling operation only)
Heating Unit Installed Upstream of Cooling Unit
Gas Unit
Evaporator
FIGURE 1
When installed, this furnace must be electrically grounded
according to local codes. In addition, in the United States,
installation must conform with the current National Electric Code, ANSI/NFPA No. 70. The National Electric Code
(ANSI/NFPA No. 70) is available from the following address:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
NOTE − This furnace is designed for a minimum continuous return air temperature of 60°F (16°C) or an intermittent operation down to 55°F (13°C) dry bulb for cases
where a night setback thermostat is used. Return air temperature must not exceed 85°F (29°C) dry bulb.
The SL280UHV furnace may be installed in alcoves, closets, attics, basements, garages, and utility rooms in the upflow or horizontal position.
This furnace is not designed for installation in mobile
homes, recreational vehicles, or outdoors.
Never use an open flame to test for gas leaks. Check all
connections using a commercially available soap solution
made specifically for leak detection.
Use of Furnace as Construction Heater
Lennox does not recommend the use of SL280UHV units
as a construction heater during any phase of construction.
Very low return air temperatures, harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit.
SL280UHV units may be used for heating of buildings or
structures under construction, if the following conditions
are met:
The vent system must be permanently installed per
these installation instructions.
A room thermostat must control the furnace. The use of
fixed jumpers that will provide continuous heating is not
allowed.
The return air duct must be provided and sealed to the
furnace.
Return air temperature range between 60°F (16°C) and
80°F (27°C) must be maintained.
Air filters must be installed in the system and must be
maintained during construction.
Air filters must be replaced upon construction comple-
tion.
The input rate and temperature rise must be set per the
furnace rating plate.
One hundred percent (100%) outdoor air must be pro-
vided for combustion air requirements during construction. Temporary ducting may supply outdoor air to the
furnace. Do not connect duct directly to the furnace.
Size the temporary duct following these instructions in
section for Combustion, Dilution and Ventilation Air in a
confined space with air from outside.
The furnace heat exchanger, components, duct system,
air filters and evaporator coils must be thoroughly
cleaned following final construction clean−up.
All furnace operating conditions (including ignition, in-
put rate, temperature rise and venting) must be verified
according to these installation instructions.
General
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
In addition to the requirements outlined previously, the following general recommendations must be considered
when installing a SL280UHV furnace:
Page 5
Place the furnace as close to the center of the air dis-
tribution system as possible. The furnace should also be
located close to the chimney or vent termination point.
Do not install the furnace where drafts might blow direct-
ly into it. This could cause improper combustion and unsafe operation.
Do not block the furnace combustion air openings with
clothing, boxes, doors, etc. Air is needed for proper
combustion and safe unit operation.
When the furnace is installed in an attic or other insu-
lated space, keep insulation away from the furnace.
NOTE − The Commonwealth of Massachusetts stipulates these additional requirements:
D Gas furnaces shall be installed by a licensed plumb-
er or fitter only.
D The gas cock must be T handle" type.
D When a furnace is installed in an attic, the passage-
way to and service area surrounding the equipment
shall be floored.
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during
installation, maintenance, or repair will expose you
to fiberglass wool. Breathing this may cause lung
cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin,
and eye irritation.
To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address shown below, or contact your
supervisor.
Lennox Industries Inc.
P.O. Box 799900
Dallas, TX 75379−9900
Combustion, Dilution & Ventilation Air
In the past, there was no problem in bringing in sufficient outdoor air for combustion. Infiltration provided all the air that
was needed. In today’s homes, tight construction practices
make it necessary to bring in air from outside for combustion. Take into account that exhaust fans, appliance vents,
chimneys, and fireplaces force additional air that could be
used for combustion out of the house. Unless outside air is
brought into the house for combustion, negative pressure
(outside pressure is greater than inside pressure) will build
to the point that a downdraft can occur in the furnace vent
pipe or chimney. As a result, combustion gases enter the living space creating a potentially dangerous situation.
In the absence of local codes concerning air for combustion and ventilation, use the guidelines and procedures in
this section to install SL280UHV furnaces to ensure efficient and safe operation. You must consider combustion air
needs and requirements for exhaust vents and gas piping.
A portion of this information has been reprinted with permission from the National Fuel Gas Code (ANSI-Z223.1).
This reprinted material is not the complete and official position of the ANSI on the referenced subject, which is represented only by the standard in its entirety.
CAUTION
Do not install the furnace in a corrosive or contaminated atmosphere. Meet all combustion and ventilation air requirements, as well as all local codes.
CAUTION
Insufficient combustion air can cause headaches,
nausea, dizziness or asphyxiation. It will also cause
excess water in the heat exchanger resulting in rusting and premature heat exchanger failure. Excessive
exposure to contaminated combustion air will result
in safety and performance related problems. Avoid
exposure to the following substances in the combustion air supply:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine base swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
All gas-fired appliances require air for the combustion process. If sufficient combustion air is not available, the furnace or other appliances will operate inefficiently and unsafely. Enough air must be provided to meet the needs of all
fuel-burning appliances and appliances such as exhaust
fans which force air out of the house. When fireplaces, exhaust fans, or clothes dryers are used at the same time as
the furnace, much more air is necessary to ensure proper
combustion and to prevent a downdraft. Insufficient air
causes incomplete combustion which can result in carbon
monoxide.
In addition to providing combustion air, fresh outdoor air
dilutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace
components.
The requirements for providing air for combustion and ventilation depend largely on whether the furnace is installed in
an unconfined or a confined space.
Page 6
Unconfined Space
An unconfined space is an area such as a basement or
large equipment room with a volume greater than 50 cubic
feet (1.42 m
3
) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space.
This space also includes adjacent rooms which are not
separated by a door. Though an area may appear to be unconfined, it might be necessary to bring in outdoor air for
combustion if the structure does not provide enough air by
infiltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around
the windows and doors, follow the procedures in the air
from outside section.
Confined Space
A confined space is an area with a volume less than 50 cubic feet (1.42 m
3
) per 1,000 Btu (.29 kW) per hour of the
combined input rating of all appliances installed in that
space. This definition includes furnace closets or small
equipment rooms.
When the furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space containing the furnace, the return air must be handled by ducts
which are sealed to the furnace casing and which terminate
outside the space containing the furnace. This is especially
important when the furnace is mounted on a platform in a
confined space such as a closet or small equipment room.
Even a small leak around the base of the unit at the platform
or at the return air duct connection can cause a potentially
dangerous negative pressure condition. Air for combustion
and ventilation can be brought into the confined space either
from inside the building or from outside.
EQUIPMENT IN CONFINED
CHIMNEY
OR GAS
VENT
FURNACE
SPACE ALL AIR FROM INSIDE
WATER
HEATER
OPENINGS
(To Adjacent
Room)
Air from Inside
If the confined space that houses the furnace adjoins a
space categorized as unconfined, air can be brought in by
providing two permanent openings between the two
spaces. Each opening must have a minimum free area of 1
square inch (645 mm
2
) per 1,000 Btu (.29 kW) per hour of
total input rating of all gas−fired equipment in the confined
space. Each opening must be at least 100 square inches
(64516 mm
2
). One opening shall be within 12 inches (305
mm) of the top of the enclosure and one opening within 12
inches (305 mm) of the bottom. See figure 2.
Air from Outside
If air from outside is brought in for combustion and ventilation, the confined space must have two permanent openings. One opening shall be within 12 inches (305 mm) of the
top of the enclosure and one opening within 12 inches (305
mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly
through vertical ducts. Each opening shall have a minimum
free area of 1 square inch (645 mm
2
) per 4,000 Btu (1.17
kW) per hour of total input rating of all equipment in the enclosure. See figures 3 and 4. When communicating with
the outdoors through horizontal ducts, each opening shall
have a minimum free area of 1 square inch (645 mm
2
) per
2,000 Btu (.56 kW) per total input rating of all equipment in
the enclosure. See figure 5.
When ducts are used, they shall be of the same cross−sectional area as the free area of the openings to which they
connect. The minimum dimension of rectangular air ducts
shall be no less than 3 inches (75 mm). In calculating free
area, the blocking effect of louvers, grilles, or screens must
be considered. If the design and free area of protective covering is not known for calculating the size opening required,
it may be assumed that wood louvers will have 20 to 25 percent free area and metal louvers and grilles will have 60 to
75 percent free area. Louvers and grilles must be fixed in the
open position or interlocked with the equipment so that they
are opened automatically during equipment operation.
AIR FLOW
NOTE − Each opening shall have a free area of at least one square
inch (645 mm
ing of all equipment in the enclosure, but not less than 100 square
inches (64516 mm
2
) per 1,000 Btu (.29 kW) per hour of the total input rat-
2
).
FIGURE 2
Page 7
CHIMNEY OR
GAS VENT
FURNACE
(Inlet Air from Crawlspace and Outlet Air to Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
OUTLET
AIR
WATER
HEATER
VENTILATION
LOUVERS
(For unheated crawl space)
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (645
2
mm
) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equipment in the enclosure.
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
CHIMNEY
OR GAS
VENT
FURNACE
NOTE−The inlet and outlet air openings shall each have a
free area of at least one square inch (645 mm
(All Air Through Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
OUTLET
AIR
above bottom)
AIR FLOW
2
INLET AIR
(Ends 12 in.
WATER
HEATER
) per 4,000
Btu (1.17 kW) per hour of the total input rating of all equipment in the enclosure.
AIR FLOW
FIGURE 3
INLET
AIR
EQUIPMENT IN
CONFINED SPACE
ALL AIR FROM
CHIMNEY
OR GAS
VENT
FURNACE
AIR FLOW
NOTE − Each air duct opening shall have a free area of at least
one square inch (645 mm
2
) per 2,000 Btu (.59 kW) per hour of
WATER
HEATER
OUTSIDE
OUTLET AIR
INLET AIR
the total input rating of all equipment in the enclosure. If the
equipment room is located against an outside wall and the air
openings communicate directly with the outdoors, each opening shall have a free area of at least one square inch (645 mm
per 4,000 Btu (1.17 kW) per hour of the total input rating of all
other equipment in the enclosure.
2
)
FIGURE 4
FIGURE 5
Page 8
Setting Equipment
WARNING
Do not install the furnace on its front or its back. Do
not connect the return air ducts to the back of the furnace. Doing so will adversely affect the operation of
the safety control devices, which could result in personal injury or death.
The SL280UHV gas furnace can be installed as shipped
in either the upflow position or the horizontal position.
Select a location that allows for the required clearances
that are listed on the unit nameplate. Also consider gas
supply connections, electrical supply, vent connection,
and installation and service clearances [24 inches (610
mm) at unit front]. The unit must be level.
NOTE − Units with 1/2 hp blower motors are equipped with
three flexible legs and one rigid leg. See figure 6. The rigid
leg is equipped with a shipping bolt and a flat white plastic
washer (rather than the rubber mounting grommet used
with a flexible mounting leg). The bolt and washer must
be removed before the furnace is placed into operation. After the bolt and washer have been removed, the rig-
id leg will not touch the blower housing.
SL280UHV07036A and
SL280UHV09036B WITH 1/2 HP
BLOWER MOTOR
RIGID LEG
remove shipping bolt and washer
FIGURE 6
Upflow Applications
Allow for clearances to combustible materials as indicated
on the unit nameplate. Minimum clearances for closet or alcove installations are shown in figure 7.
Upflow Application Installation Clearances
Top
Left Side
AIR FLOW
Bottom
Type of Vent
Connector
Top1 in. (25 mm)1 in. (25 mm)
*Front2−1/4 in. (57 mm)**2−1/4 in. (57 mm)
Back00
Sides0†0
Vent6 in. (152 mm)1 in. (25 mm)
Floor0‡0‡
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
** 3−1/4 in. if single wall vent pipe is used.
‡For installation on a combustible floor, do not install the furnace
directly on carpeting, tile or other combustible materials other
than wood flooring.
†Left side requires 3 inches if a single wall vent is used on 14−1/2
inch cabinets, or 2 in. if a single wall vent is used on 17−1/2 in. cabinets.
Type CType B1
Right Side
FIGURE 7
Page 9
Return Air −− Upflow Applications
Return air can be brought in through the bottom or either
side of the furnace installed in an upflow application. If the
furnace is installed on a platform with bottom return, make
an airtight seal between the bottom of the furnace and the
platform to ensure that the furnace operates properly and
safely. The furnace is equipped with a removable bottom
panel to facilitate installation.
Markings are provided on both sides of the furnace cabinet
for installations that require side return air. Cut the furnace
cabinet at the maximum dimensions shown on page 2.
NOTE −
cfm (850 L/s) must have one of the following:
1 − Return air from single side with transition which will
2 − Return air from single side with optional RAB Return
3 − Return air from bottom and
4 − Return air from both sides.
5 − Return air from bottom.
60C and 60D units that require air volumes over 1800
accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter. (Required to maintain proper air velocity.)
See figure 8.
Air Base. See figure 9.
one side.
Refer to Engineering Handbook for additional information.
Single Side Return Air
(with transition and filter)
20” X 25” X 1”
(508mm X635mm X 25mm)
Cleanable Filter
Return Air
Plenum
AIR FLOW
Transition
FIGURE 8
Optional Return Air Base
(Upflow Applications Only −− For use with A, B, C and D cabinets)
FURNACE
FRONT
IF BASE
IS USED
WITHOUT
INDOOR AIR
AIR FLOW
14−1/2” (368) A Width (65W75)
17−1/2” (446) B Width (50W98)
21”− (533) C Width (50W99)
24−1/2”− (622) D Width (51W00)
NOTE− Optional Side Return Air Filter Kits are not for use with Optional Return Air Base.
1
Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.
OPTIONAL
RETURN AIR BASE
IAQ CABINET,
A SINGLE
RETURN AIR
PLENUM
MUST
COVER BOTH
UNIT AND
RETURN
AIR BASE
OPENINGS
3−1/4
(83)
7−1/4
(184)
1
23 (584)
Overall
(Maximum)
1
Unit side return air
Opening
5−5/8
(143)
SIDE RETURN
AIR OPENINGS
(Either Side)
26−7/8
(683)
SIDE VIEW
23
(584)
1
Minimum
11 (279)
2
Maximum
14 (356)
1
22−7/16
(570)
Overall
(Maximum)
3/4
(19)
Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm).
The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.
Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air
opening. The size of the opening must not extend beyond the markings on the furnace cabinet.
2
To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.
FIGURE 9
Page 10
Removing the Bottom Panel
Hori
Remove the two screws that secure the bottom cap to the
furnace. Pivot the bottom cap down to release the bottom
panel. Once the bottom panel has been removed, reinstall
the bottom cap. See figure 10.
Removing the Bottom Panel
Horizontal Applications
The SL280UHV furnace can be installed in horizontal applications. Order kit number 51W10 (or use equivalent)
from Lennox.
Allow for clearances to combustible materials as indicated
on the unit nameplate. Minimum clearances for closet or alcove installations are shown in figure 11.
This furnace may be installed in either an attic or a crawlspace. Either suspend the furnace from roof rafters or
floor joists, as shown in figure 12, or install the furnace on a
platform, as shown in figure 13.
Typical Horizontal Application
Unit Suspended in Attic or Crawlspace
Bracket
Metal Strap
Screw
Bottom Cap
Bottom Panel
FIGURE 10
zontal Application
Installation Clearances
Left
End
Vent Connector
Type
Top00
*Front2−1/4 in. (57 mm)**2−14 in. (57 mm)
Back00
Ends2 in. (51 mm)2 in. (51 mm)
Vent6 in. (152 mm)1 in. (25 mm)
Floor0‡0‡
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
** 3−1/4 in. if single wall vent pipe is used.
‡For installations on a combustible floor, do not install the furnace
directly on carpeting, tile or other combustible materials other
than wood flooring.
Top
Right
AIR FLOW
End
Bottom
Type CType B1
FIGURE 11
Bottom Cap
3/16 inch
Air Flow
FIGURE 12
NOTE − Heavy−gauge perforated sheet metal straps may
be used to suspend the unit from roof rafters or ceiling
joists. When straps are used to suspend the unit in this
way, support must be provided for both the ends. The
straps must not interfere with the plenum or exhaust piping installation. Cooling coils and supply and return air
plenums must be supported separately.
NOTE − When the furnace is installed on a platform in a
crawlspace, it must be elevated enough to avoid water
damage and to allow the evaporator coil to drain.
Return Air −− Horizontal Applications
Return air must be brought in through the end of a furnace
installed in a horizontal application. The furnace is
equipped with a removable bottom panel to facilitate
installation. See figure 10.
Page 11
Horizontal Application
Unit Installed on Platform
Line contact is permissible
See the unit nameplate for
clearances.
GAS
ENTRY
SERVICE PLATFORM
VENT
PIPE
FIGURE 13
WARNING
Improper installation of the furnace can result in personal injury or death. Combustion and flue products
must never be allowed to enter the return air system
or the living space. Use screws and joint tape to seal
the return air system to the furnace.
In platform installations with bottom return air, the
furnace should be sealed airtight to the return air plenum. A door must never be used as a portion of the
return air duct system. The base must provide a
stable support and an airtight seal to the furnace. Allow absolutely no sagging, cracks, gaps, etc.
The return and supply air duct systems must never
be connected to or from other heating devices such
as a fireplace or stove, etc. Fire, explosion, carbon
monoxide poisoning, personal injury and/or property damage could result.
WARNING
The inner blower panel must be securely in place
when the blower and burners are operating. Gas
fumes, which could contain carbon monoxide, can
be drawn into living space resulting in personal injury or death.
Filters
This unit is not equipped with a filter or rack. A field−provided high−velocity filter is required for the unit to operate
properly. Table 1 lists recommended filter sizes.
A filter must be in place any time the unit is operating.
TABLE 1
Furnace
Cabinet Width
14−1/2"16 X 25 X 1 (1)14 X 25 X 1 (1)
17−1/2"16 X 25 X 1 (1)16 X 25 X 1 (1)
21"16 X 25 X 1 (1)20 X 25 X 1 (1)
24−1/2"16 X 25 X 1 (2)24 X 25 X 1 (1)
Side ReturnBottom Return
Filter Size
Duct System
Use industry-approved standards (such as those published by Air Conditioning Contractors of America or American Society of Heating, Refrigerating and Air Conditioning
Engineers) to size and install the supply and return air duct
system. This will result in a quiet and low-static system that
has uniform air distribution.
NOTE − Do not operate the furnace in the heating mode
with an external static pressure that exceeds 0.8 inches
w.c. Higher external static pressures may cause erratic limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a removable
access panel must be installed in the supply air duct. The
access panel should be large enough to permit inspection
(either by smoke or reflected light) of the heat exchanger
for leaks after the furnace is installed. The furnace access
panel must always be in place when the furnace is operating and it must not allow leaks into the supply air duct system.
Return Air Plenum
NOTE − Return air must not be drawn from a room
where this furnace, or any other gas−fueled appliance
(i.e., water heater), or carbon monoxide− producing device (i.e., wood fireplace) is installed.
When return air is drawn from a room, a negative pressure is created in the room. If a gas appliance is operating
in a room with negative pressure, the flue products can
be pulled back down the vent pipe and into the room. This
reverse flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas. This
toxic gas might then be distributed throughout the house
by the furnace duct system.
In upflow applications, the return air can be brought in
through the bottom or either side of the furnace. If a furnace with bottom return air is installed on a platform, make
an airtight seal between the bottom of the furnace and the
platform to ensure that the unit operates properly and
safely. Use fiberglass sealing strips, caulking, or equivalent sealing method between the plenum and the furnace
cabinet to ensure a tight seal. If a filter is installed, size the
return air duct to fit the filter frame.
Page 12
Venting
A 4−inch diameter flue transition is factory-installed on the
combustion air inducer outlet of all models. Figure 15
shows the combustion air inducer as shipped from the
factory.
Mounting Screws Location
mounting screws
mounting screw
FIGURE 14
UPFlow Position
UPFLOW POSITION
Top Vent Discharge
flue
transition
pressure
switch
make−up
box
vent pipe
collector box
1 − Remove the four mounting screws (figure 14) which
secure the combustion air inducer / pressure switch
assembly to the orifice plate. Lift and rotate the assembly 90 degrees clockwise or counter clockwise to either
the 3 o’clock position or to 9 o’clock position and re−secure with four screws. Gasket should be left in place.
2 − Use tin snips to cut preferred opening on the cabinet
for repositioning the flue outlet. Use the cut out piece
as a cover plate to patch unused opening on cabinet.
UPFLOW POSITION
Left Side Vent Discharge
cover plate
pressure
switch
vent pipe
flue
transition
FLOW
AIR
Gas supply piping must be brought into the unit from the right
side in order to accommodate the flue pipe.
Remove make−up box assembly (2 screws) and cut wire tie to
free make−up box wires. Re−install make−up box on other side
of cabinet.
Re−secure make−up box wires, either pulling excess wires
through the blower compartment and securing with supplied
wire tie, or coil excess wire and secure to the gas manifold.
collector box
make−up
box
FIGURE 16
FLOW
AIR
FIGURE 15
IMPORTANT
The unit will not vent properly with the flue transition
pointed down in the 6 o’clock position.
The combustion air inducer may be rotated clockwise or counterclockwise by 90° to allow for top or
side vent discharge in all applications. When the unit
is installed, the flue transition must be in the 9
o’clock, 12 o’clock or 3 o’clock position.
If necessary reposition the combustion air inducer, pressure switch and or make up box as needed per the following steps and see figures 15 through 21.
Page 13
UPFLOW POSITION
Right Side Vent Discharge
collector box
pressure
switch
make−up
box
Pressure switch tubing may be too long. Cut to
fit , then re−attach to barbed fitting on pressure
switch. Tubing must not be allowed to sag.
cover plate
AIR
flue transition
FLOW
FIGURE 17
vent pipe
Horizontal Position
HORIZONTAL LEFT POSITION
Top Vent Discharge
vent pipe
flue
transition
cover plate
make−up box
Disconnect pressure switch hose from barbed fitting on the pres-
sure switch assembly. Remove pressure switch assembly (1
screw) and cut wire tie to free pressure switch wires. Re−install
pressure switch on the other side of orifice plate and re−connect
pressure switch hose.
Re−secure pressure switch wires by either pulling excess wires
through the blower compartment and securing with supplied wire
tie or coil excess wire and secure to the gas manifold.
pressure switch
AIR
FLOW
collector box
FIGURE 18
HORIZONTAL LEFT POSITION
Side Vent Discharge
HORIZONTAL RIGHT POSITION
Top Vent Discharge
vent pipe
flue transition
AIR
FLOW
Gas supply piping must be brought into the unit from the bottom
in order to accommodate the flue pipe.
Remove make−up box assembly (2 screws) and cut wire tie to
free make−up box wires. Re−install make−up box on other side
of cabinet.
Re−secure make−up box wires by either pulling excess wires
through the blower compartment and securing with supplied
wire tie, or coil excess wire and secure to the gas manifold.
pressure switch
cover plate
collector box
make−up box
FIGURE 20
pressure switch
AIR
FLOW
flue transition
make−up box
Disconnect pressure switch hose from barbed fitting on the
pressure switch assembly. Remove pressure switch assembly
(1 screw) and cut wire tie to free pressure switch wires. Re−
install pressure switch on the other side of orifice plate and re−
connect pressure switch hose.
Re−secure pressure switch wires by either pulling excess wires
through the blower compartment and securing with supplied
wire tie, or coil excess wire and secure to the gas manifold.
collector box
FIGURE 19
AIR
FLOW
HORIZONTAL RIGHT POSITION
Side Vent Discharge
pressure switch
flue transition
collector box
make up box
FIGURE 21
Page 14
The SL280UHV series units are classified as fan−assisted
Category I furnaces when vertically vented according to
the latest edition of National Fuel Gas Code (NFPA 54 /
ANSI Z223.1) in the USA. A fan−assisted Category I furnace is an appliance equipped with an integral mechanical
means to either draw or force combustion products through
the combustion chamber and/or heat exchanger. The
SL280UHV is not approved for use with horizontal venting..
NOTE − Use these instructions as a guide. They do not supersede local codes. This furnace must be vented according to all local codes these installation instructions, and the
provided venting tables in these instructions
The venting tables in this manual were extracted from the
National Fuel Gas Code (NFPA 54 / ANSI Z223.1) and are
provided as a guide for proper vent installation. Proper application, termination, construction and location of vents
must conform to local codes having jurisdiction. In the absence of local codes, the NFGC serves as the defining document.
Refer to the tables and the venting information contained in
these instructions to properly size and install the venting
system.
IMPORTANT
Once the venting system is installed, attach the Disconnected Vent" warning sticker to a visible area of
the plenum near the vent pipe. See figure 22. The
warning sticker is provided in the bag assembly. Order kit 66W04 for additional stickers.
Use self−drilling sheet metal screws or a mechanical fastener to firmly secure the vent pipe to the round collar of the
flue transition. If self−drilling screws are used to attach the
vent pipe, it is recommended that three be used. Drive one
self−drilling screw through the front and one through each
side of the vent pipe and collar. See figures 19, 21 and 22.
Install the first vent connector elbow at a minimum of six
inches (152 mm) from the furnace vent outlet. See figure
22.
Venting Using a Masonry Chimney
The following additional requirements apply when a lined
masonry chimney is used to vent this furnace.
Masonry chimneys used to vent Category I central furnaces must be either tile-lined or lined with a listed metal
lining system or dedicated gas vent. Unlined masonry
chimneys are prohibited. See figures 23 and 24 for common venting.
A chimney with one or more sides exposed to the outside of
the structure is considered to be an exterior chimney.
An exterior masonry chimney that is not tile−lined must be
lined with B1 vent or a listed insulated flexible metal vent.
An exterior tile−lined chimney that is sealed and capped
may be lined with a listed uninsulated flexible metal vent.
If the existing chimney will not accommodate a listed metal
liner, either the chimney must be rebuilt to accommodate
one of these liners or an alternate approved venting method must be found.
Insulation for the flexible vent pipe must be an encapsulated fiberglass sleeve recommended by the flexible vent
pipe manufacturer. See figure 23.
WARNING
Asphyxiation hazard. The exhaust vent for this furnace must be securely connected to the furnace flue
transition at all times.
VENT CONNECTION
VENT PIPE
(min. 6" length)
FLUE TRANSITION
COLLAR
FIGURE 22
“DISCONNECTED VENT”
WARNING
STICKER
Common Venting Using Metal−Lined Masonry Chimney
SEALED
MAX. LENGTH
−− SEE NOTE 1
5 ft. (1.5 m)
minimum
VENT CONNECTOR
4 in. (102 mm)
minimum
OTHER
APPLIANCE
NOTE 1 − Refer to the provided venting tables for installations. Refer
to the capacity requirements shown in the provided venting tables.
BELOW.
MIN. LENGTH −− AS
SHORT AS PRACTICAL
FURNACE
AIR FLOW
EXTERIOR
CHIMNEY WITH
METAL
LINER
PERMANENTLY
SEALED FIREPLACE
OPENING
FIGURE 23
Page 15
Common Venting Using Tile−Lined Interior Masonry Chimney and Combined Vent Connector
MINIMUM LENGTH = AS SHORT AS PRACTICAL.
FOR MAXIMUM LENGTH SEE NOTE TO LEFT
NOTE− Refer to provided venting tables
for installations.
OTHER
APPLIANCE
AIR FLOW
FIGURE 24
DO NOT insulate the space between the liner and the
chimney wall with puffed mica or any other loose granular insulating material
IMPORTANT
SINGLE appliance venting of a fan-assisted furnace
into a tile-lined masonry chimney (interior or outside
wall) is PROHIBITED. The chimney must first be lined
with either type B1 vent or an insulated single wall
flexible vent lining system which has been sized according to the provided venting tables and the vent
pipe manufacturer’s instructions.
A fan−assisted furnace may be commonly vented into an
existing lined masonry chimney if the following conditions
are met:
The chimney is currently serving at least one drafthood
equipped appliance
The vent connectors and chimney are sized according
to the provided venting tables.
If type B1 double-wall vent is used inside a chimney, no other appliance can be vented into the chimney. The outer wall
of type B1 vent pipe must not be exposed to flue products.
A type B1 vent or masonry chimney liner shall terminate
above the roof surface with a listed cap or a listed roof assembly according to the terms of their respective listings
and the vent manufacturer’s instructions.
When inspection reveals that an existing chimney is not
safe for the intended purpose, it shall be rebuilt to conform
to nationally recognized standards, lined or relined with
suitable materials, or replaced with a gas vent or chimney
suitable for venting SL280UHV series units. The chimney
passageway must be checked periodically to ensure that it
is clear and free of obstructions.
Do not install a manual damper, barometric draft regulator,
or flue restrictor between the furnace and the chimney.
INTERIOR TILE−LINED
MASONRY CHIMNEY
NOTE − the chimney must be properly
sized per provided venting tables or
lined with listed metal lining system.
VENT
CONNECTOR
FURNACE
PERMANENTLY
SEALED FIREPLACE
OPENING
Never connect a Category I appliance to a chimney that is
servicing a solid−fuel appliance. If a fireplace chimney flue
is used to vent this appliance, the fireplace opening must
be permanently sealed.
A type B or listed chimney lining system that passes
through an unused masonry chimney flue is not considered
to be exposed to the outdoors.
General Venting Requirements
Vent all SL280UHV furnaces according to these instructions:
1 − Vent diameter recommendations and maximum allow-
able piping runs are found in the provided venting
tables.
2 − In no case should the vent or vent connector diameter
be less than the diameter specified in the provided
venting tables.
3 − The minimum vent capacity determined by the sizing
tables must be less than the low fire input rating and the
maximum vent capacity must be greater than the high
fire input rating.
4 − Single appliance vents − If the vertical vent or tile-lined
chimney has a larger diameter or flow area than the
vent connector, use the vertical vent diameter to determine the minimum vent capacity and the vent
connector diameter to determine the maximum vent
capacity. The flow area of the vertical vent, however,
shall not exceed 7 times the flow area of the listed appliance categorized vent area, drafthood outlet area or
flue collar area unless designed according to approved
engineering methods.
5 − Multiple appliance vents − The flow area of the largest
section of vertical vent or chimney shall not exceed 7
times the smallest listed appliance categorized vent
area, drafthood outlet area or flue collar area unless designed according to approved engineering methods.
Page 16
6 − The entire length of single wall metal vent connector
shall be readily accessible for inspection, cleaning,
and replacement.
7 − Single appliance venting configurations with zero lat-
eral lengths (tables 3 and 4) are assumed to have no
elbows in the vent system. For all other vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for
example two 45° elbows equal one 90° elbow) beyond
two, the maximum capacity listed in the venting table
should be reduced by 10% (0.90 x maximum listed capacity).
8 − The common venting tables (5, 6, 7, and 8) were gen-
erated using a maximum horizontal vent connector
length of 1−1/2 feet (.46 m) for each inch (25 mm) of
connector diameter as follows:
TABLE 2
Connector Diameter
inches (mm)
3 (76)4−1/2 (1.37)
4 (102)6 (1.83)
5 (127)7−1/2 (2.29)
6 (152)9 (2.74)
7 (178)10−1/2 (3.20)
Maximum Horizontal
Connector Length feet (m)
9 − If the common vertical vent is offset, the maximum
common vent capacity listed in the common venting
tables should be reduced by 20%, the equivalent of two
90° elbows (0.80 x maximum common vent capacity).
The horizontal length of the offset shall not exceed
1-1/2 feet (.46 m) for each inch (25 mm) of common
vent diameter.
10 − The vent pipe should be as short as possible with the
least number of elbows and angles required to complete the job. Route the vent connector to the vent using the shortest possible route.
11 − A vent connector shall be supported without any dips
or sags and shall slope a minimum of 1/4 inch (6.4 mm)
per linear foot (305 mm) of connector, back toward the
appliance.
12 − Vent connectors shall be firmly attached to the furnace
flue collar by self−drilling screws or other approved
means, except vent connectors of listed type B vent
material which shall be assembled according to the
manufacturer’s instructions. Joints between sections
of single wall connector piping shall be fastened by
screws or other approved means.
13 − When the vent connector used for Category I ap-
pliances must be located in or pass through a crawlspace, attic or other areas which may be cold, that portion of the vent connector shall be constructed of listed
double-wall type B vent material or material having
equivalent insulation qualities.
14 − All venting pipe passing through floors, walls, and ceil-
ings must be installed with the listed clearance to combustible materials and be fire stopped according to local codes. In absence of local codes, refer to NFGC
(Z223.1).
15 − No portion of the venting system can extend into, or pass
through any circulation air duct or plenum.
16 − Vent connectors serving Category I appliances shall
not be connected to any portion of mechanical draft
systems operating under positive pressure such as
Category III or IV venting systems.
17 − If vent connectors are combined prior to entering the
common vent, the maximum common vent capacity
listed in the common venting tables must be reduced by
10%, the equivalent of one 90° elbow (0.90 x maximum
common vent capacity).
18 − The common vent diameter must always be at least as
large as the largest vent connector diameter.
19 − In no case, shall the vent connector be sized more than
two consecutive table size diameters over the size of
the draft hood outlet or flue collar outlet.
20 − Do not install a manual damper, barometric draft regu-
lator or flue restrictor between the furnace and the
chimney.
21 − When connecting this appliance to an existing dedi-
cated or common venting system, you must inspect the
venting system’s general condition and look for signs
of corrosion. The existing vent pipe size must conform
to these instructions and the provided venting tables. If
the existing venting system does not meet these requirements, it must be resized.
Page 17
TABLE 3
Capacity of Type B Double−Wall Vents with Type B Double−Wall Connectors
Serving a Single Category I Appliance
Vent and Connector Diameter − D (inches)
Height
H
(feet)
6
8
10
15
20
30
NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other
vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45°
elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maximum listed capacity).
Lateral
L
(feet)
0078015202510375
2135118972715732232
4214930943915350227
6254636914714959223
0084016502760415
21257161092517828263
52353321034217153255
8284939985116464247
0088017502950447
21261171182319426289
52357321134118752280
103051411045417667267
0094019103270502
21169151362022622339
52265301303921949330
102959401215120664315
153553481126119576301
0097020203490540
21075141491825020377
52171291433824247367
102864381335022962351
153458461245921773337
204852551166920684322
00100021303740587
2981131661428318432
52177281603627545421
102770371504826259405
153364441415724970389
205658531326623780374
30NRNR7311388214104346
3 Inch4 Inch5 Inch6 Inch
Appliance Input Rating in Thousands of Btu Per Hour
MINMAXMINMAXMINMAXMINMAX
Page 18
TABLE 4
Capacity of Type B Double−Wall Vents with Single−Wall Metal Connectors
Serving a Single Category I Appliance
Vent and Connector Diameter − D (inches)
Height
H
(feet)
6
8
10
15
20
30
NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other
vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45°
elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maximum listed capacity).
Lateral
L
(feet)
038775915185249126373
23951609685156123231
4NRNR7492102152146225
6NRNR838911 4147163220
037835816483273123412
239565910883176121261
5NRNR77102107168151252
8NRNR9095122161175243
037875717482293120444
239615911782193119287
5525676111105185148277
10NRNR97100132171188261
036935619080325116499
238695713680225115337
5516375128102216144326
10NRNR9511 6128201182308
15NRNRNRNR158186220290
035965420078346114537
237745614878248113375
5506873140100239141363
10NRNR93129125223177344
15NRNRNRNR155208216325
20NRNRNRNR186192254306
03499532117637211 0584
237805516476281109429
549747215798271136417
10NRNR91144122255171397
15NRNR115131151239208377
20NRNRNRNR181223246357
30NRNRNRNRNRNRNRNR
3 Inch4 Inch5 Inch6 Inch
Appliance Input Rating in Thousands of Btu Per Hour
MINMAXMINMAXMINMAXMINMAX
Page 19
Vent
Height
H
(feet)
6
8
10
15
20
30
TABLE 5
Vent Connector Capacity
Type B Double−Wall Vents with Type B Double−Wall Connectors
Serving Two or More Category I Appliances
Connector
Rise
R
(feet)
1223735664610658164
2234137754812160183
3244438814913262199
1224035724911464176
2234436805112866195
3244737875313967210
1224334784912365189
2234736865113667206
3245037925214669220
1215033894714264220
2225335964915366235
32455361025116368248
1215433994615762246
22257341054816764259
32360351105017666271
12062311134518160288
22164331184719062299
32266341234819864309
3 Inch4 Inch5 Inch6 Inch
MINMAXMINMAXMINMAXMINMAX
Vent and Connector Diameter − D (inches)
Appliance Input Rating in Thousands of Btu Per Hour
TABLE 6
Common Vent Capacity
Type B Double−Wall Vents with Type B Double−Wall Connectors
Appliance Input Rating in Thousands of Btu Per Hour
Common Vent Diameter − D (inches)
Page 20
TABLE 7
Vent Connector Capacity
Type B Double−Wall Vents with Single−Wall Metal Connectors
Serving Two or More Category I Appliances
Vent and Connector Diameter − D (inches)
Height
H
(feet)
6
8
10
15
20
30
NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other
vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45°
elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maximum listed capacity).
Lateral
L
(feet)
1NRNRNRNRNRNRNRNR
2NRNRNRNRNRNR168182
3NRNRNRNR121131175198
1NRNRNRNRNRNANRNR
2NRNRNRNR125126184193
3NRNRNRNR130138191208
1NRNRNRNR119121182186
2NRNR8485124134189203
3NRNR8991129144197217
1NRNR798711 6138177214
2NRNR8394121150185230
3NRNR87100127160193243
149567897115152175238
2525982103120163182252
3556287107125172190264
1476077110112175169278
2516281115117185177290
3546485119122193185300
3 Inch4 Inch5 Inch6 Inch
Appliance Input Rating in Thousands of Btu Per Hour
MINMAXMINMAXMINMAXMINMAX
TABLE 8
Common Vent Capacity
Type B Double−Wall Vents with Single−Wall Metal Connectors
Appliance Input Rating in Thousands of Btu Per Hour
Common Vent Diameter − D (inches)
Page 21
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a
venting system commonly run with separate gas appliances, the venting system is likely to be too large to
properly vent the remaining attached appliances.
Conduct the following test while each appliance is operating and the other appliances (which are not operating) remain connected to the common venting system. If the
venting system has been installed improperly, you must
correct the system as indicated in the general venting requirements section.
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being
placed into operation, while all other appliances
connected to the venting system are not in
operation:
1 − Seal any unused openings in the common venting sys-
tem.
2 − Inspect the venting system for proper size and horizontal
pitch. Determine that there is no blockage, restriction,
leakage, corrosion, or other deficiencies which could
cause an unsafe condition.
3 − Close all building doors and windows and all doors be-
tween the space in which the appliances remaining
connected to the common venting system are located
and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common
venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4 − Follow the lighting instructions. Turn on the appliance
that is being inspected. Adjust the thermostat so that
the appliance operates continuously.
5 − After the main burner has operated for 5 minutes, test
for leaks of flue gases at the draft hood relief opening.
Use the flame of a match or candle, or smoke from a
cigarette, cigar, or pipe.
6 − After determining that each appliance connected to the
common venting system is venting properly, (step 3)
return all doors, widows, exhaust fans, fireplace dampers, and any other gas−burning appliances to their previous mode of operation.
7 − If a venting problem is found during any of the preced-
ing tests, the common venting system must be modified to correct the problem.
Resize the common venting system to the minimum
vent pipe size determined by using the appropriate
tables in Appendix G. (These are in the current standards of the National Fuel Gas Code ANSI Z223.1.
Page 22
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.