SL280UHNVseries units are 80% effi ciency gas furnac-
es used for upfl ow or horizontal applications only, man-
ufactured with Lennox Duralok heat exchangers formed
of aluminized steel. SL280UHNV units are available in
heating capacities of 40,000 to 100,000 Btuh and cooling
applications up to 5 tons. Refer to Engineering Handbook
for proper sizing.
Units are approved for installations up 4500 ft and factory equipped for use with natural gas only. SL280UHNV
model units are equipped with the iComfort® enabled
SureLight® two-stage variable speed integrated control.
SL280UHNV unit meets the California Nitrogen Oxides
(NOx) Standards and California Seasonal Effi ciency re-
quirements. All units use a redundant gas valve to assure
safety shut-off as required by C.S.A.
All specifi cations in this manual are subject to change.
Procedures outlined in this manual are presented as a
recommendation only and do not supersede or replace local or state codes. In the absence of local or state codes,
the guidelines and procedures outlined in this manual (except where noted) are recommendations only and do not
constitute code.
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal
injury or loss of life. Installation and service must be
performed by a licensed professional HVAC installer or
equivalent, service agency, or the gas supplier.
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and wear gloves and
protective clothing.
NOTE - Filters and provisions for mounting are not furnished and must be fi eld provided.
1
Annual Fuel Utilization Effi ciency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
Model No.SL280UH060NV36ASL280UH080NV48B
1
AFUE80%80%
Input - Btuh60,00080,000
Output - Btuh48,00064,000
3.43.4
Natural Gas Only
Input - Btuh39,00052,000
Output - Btuh31,00041,000
1.51.5
Natural Gas Only
Cooling1.01.0
Gas pipe size IPS1/21/2
Motor output - hp1/2 1.0
SPECIFICATIONS
Gas
Heating
Performance
High
Fire
Temperature rise range - °F30 - 6030 - 60
Gas Manifold Pressure (in. w.g.)
Low
Fire
Temperature rise range - °F20 - 5025 - 50
Gas Manifold Pressure (in. w.g.)
High static - in. w.g.Heating0.80.8
Connections
Flue connection − in. round44
in.
Indoor
Wheel nominal diameter x width - in.11-1/2 X 1011-1/2 X 10
NOTE - Filters and provisions for mounting are not furnished and must be fi eld provided.
1
Annual Fuel Utilization Effi ciency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
Model No.SL280UH080NV60CSL280UH100NV60C
1
AFUE80%80%
Input - Btuh80,000100,000
Output - Btuh64,00080,000
3.43.4
Natural Gas Only
Input - Btuh52,00065,000
Output - Btuh41,00052,000
1.51.5
Natural Gas Only
Cooling1.01.0
Gas pipe size IPS1/21/2
Motor output - hp1.01.0
Page 2
Combustion Air Inducer
A
Gas Valve
Air Intake Pipe
Heat Exchanger
ccess Panel
Inner Access
Panel
(includes two-stage integrated control,
transformer and circuit breaker)
FIGURE 1
Control Box
Blower Assembly
Page 3
I-Unit Components
SL280UHNV unit components are shown in Figure 1. The
gas valve, combustion air inducer and burners can be accessed by removing the access panel. Electrical components are in the control box (Figure 2) found in the blower
section.
SL280UHNV units are factory equipped with a bottom return air panel in place. The panel is designed to be fi eld
removed as required for bottom air return. Markings are
provided for side return air and may be cut out in the fi eld.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic components.
Take precautions during furnace installation and service
to protect the furnace’s electronic controls. Precautions
will help to avoid control exposure to electrostatic
discharge by putting the furnace, the control and the
technician at the same electrostatic potential. Neutralize
electrostatic charge by touching hand and all tools on an
unpainted unit surface, such as the gas valve or blower
deck, before performing any service procedure.
A- Control Box
1. Control Transformer (T1)
A transformer located in the control box provides power tothe low voltage section of the unit. Transformers on
allmodels are rated 40VA with a 120V primary and a 24V
secondary.
2. Door Interlock Switch (S51)
A door interlock switch rated 14A at 125VAC is wired in series with line voltage. When the inner blower access panel
is removed the unit will shut down.
CONTROL BOX
Transformer
Circuit Breaker
Interlock Switch
®
SureLight
FIGURE 2
3. Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box.
The switch provides overcurrent protection to the transformer (T1). The breaker is rated 3A at 32V. If the current
exceeds this limit the breaker will trip and all unit operation will shutdown. The breaker can be manually reset by
pressing the button on the face. See Figure 3
Integrated Control
CIRCUIT BREAKER CB8
PRESS TO RESET
FIGURE 3
WARNING
Shock hazard. Disconnect power before
servicing. Integrated control is not fi eld
repairable. If control is inoperable, simply
replace entire control. Can cause injury or
death. Unsafe operation will resul if repair
is attempted.
4. Integrated Control (A92)
Units are equipped with the icomfort enabled SureLight
® two-stage, variable speed integrated control. This control is used with the icomfort Wi-Fi® thermostat as part
of a communicating comfort system. The control can also
operate with a non-communicating conventional single or
two-stage thermostat. The system consists of a ignition
/ blower control (Figure 4 and Figure 5) with control pin
designations in Table 1, Table 2 and Table 3 and ignitor
(Figure 13). The control and ignitor work in combination
to ensure furnace ignition and ignitor durability. The control provides gas ignition, safety checks and indoor blower
control with two-stage gas heating.
The furnace combustion air inducer, gas valve and indoor
blower are controlled in response to various system inputs
such as thermostat signal, pressure and limit switch signal
and fl ame signal. The control features a seven-segment
LED display, indicating furnace status (including indoor
blower) and error codes. The LED fl ashes in single dig-
its. For example using Table 5 under LIMIT CODE, an “E”
followed by “2” followed by “5” followed by “0”, the limit
switch circuit is open. The control also has two unpowered
(dry) 1/4” contacts for a humidifi er and a 120 volt accesso-
ry terminal. Both rated at (1) one amp each.
Electronic Ignition
At the beginning of the heat cycle the integrated control
monitors the fi rst stage and second stage combustion air
inducer prove switch. The control will not begin the heating
cycle if the fi rst stage prove switch is closed (by-passed).
Likewise the integrated control will not begin the second
stage heating cycle if the second stage prove switch is
closed, and will remain in fi rst stage heat. However, if the
second stage prove switch closes during the fi rst stage
heat pre-purge, the control will allow second stage heat.
Once the fi rst stage prove switch is determined to be open,
the combustion air inducer is energized on low (fi rst stage)
heat speed. When the differential in the prove switch is
great enough, the prove switch closes and a 15-second
pre-purge begins.
Page 4
NOTE - During abnormal conditions such as low supply
voltage or low outdoor temperatures and the low fi re pres-
sure switch does not close, the combustion air inducer will
switch to high fi re. After a 15 second pre-purge the high fi re pressure switch will close and the unit will begin operation on high fi re. After 10 to 20 seconds of high fi re
operation the unit will switch to low fi re.
After the 15-second pre-purge period, the SureLight ignitor warms up for 20 seconds after which the gas valve
opens for a 4-second trial for ignition. The ignitor energizes during the trial until fl ame is sensed. If ignition is
not proved during the 4-second period, the control will try
four more times with an inter purge and warm-up time between trials of 35 seconds. After a total of fi ve trials for
ignition (including the initial trial), the control goes into
Watchguard-Flame Failure mode. After a 60-minute reset
period, the control will begin the ignition sequence again.
Two Stage Operation / Thermostat Selection DIP
Switch
The control can be utilized in two modes: SINGLE-STAGE
thermostat or TWO-STAGE thermostat. The thermostat
selection is made using a DIP switch and must be positioned for the particular application. DIP switch 1, labeled
T”STAT HEAT STAGE is factory-set in the OFF position for
use with a two-stage thermostat. Move the DIP switch to
ON for use with a single stage thermostat.
While in the single-stage thermostat mode, the burners
will always fi re on fi rst-stage heat. The combustion air in-
ducer will operate on low speed and indoor blower will
operate on low heat speed. The unit will switch to second
stage heat after a “recognition period”. DIP switch 2, labeled SECOND STAGE DELAY, is factory set in the OFF
position for a 7 minute recognition period. The switch can
be moved to the ON position for a 12 minute recognition
period, after which time the unit will switch to secondstage
heat.
While in the two-stage thermostat mode (two DIP switch
setting) the burners will fi re on fi rst-stage heat. The com-
bustion air inducer will operate on low speed and indoor
blower will operate on low heat speed. The unit will switch
to second-stage heat on call from the indoor thermostat.
If there is a simultaneous call for fi rst and second stage
heat, the unit will fi re an fi rst stage heat and switch to sec-
ond stage heat after 30 seconds of operation. See Sequence of Operation fl ow charts in the back of this manual
for more detail.
TABLE 1
SureLight® Control 5 Pin Terminal Designation
PIN#Function
1Ignitor
2Combustion Air Inducer High
Speed
3Combustion Air Inducer Low
Speed
4Combustuion Air Inducer
Neutral
5Ignitor Neutral
TABLE 2
SureLight® Control 12 Pin Terminal Designation
PIN#Function
1Gas Valve High Fire
2Second Stage Prove Switch
3Rollout In
4Ground
524V Hot
6Primary Limit In
7Gas Valve Low Stage
8Gas Valve Common
924V Neutral
10Ground
11Rollout Switch Out
121st Stage Prove Switch
TABLE 3
SureLight® Control 6 Pin Terminal Designation
PIN#Function
1Data Input From Motor
2Common
3Not Used
4Data Output To Motor
55 Volt Bias Supply
6
Not Used
Page 5
HUM
LINE 1
7 SEGMENT LED
FLAME SENSE
DIAGNOSTIC
PUSH BUTTON
DIP SWITCHES
ACC
HS/ CAI
INDOOR
BLOWER
CONNECTOR
NEUTRAL
OUTDOOR AIR
SENSOR
TERMINALS
DISCHARGE AIR
SENSOR
TERMINALS
TB83
COMMUNICATING
OUTDOOR
EQUIPMENT
I + I -CRI + I -
TB84
COMMUNICATING
INDOOR
THERMOSTAT
R
RS-BUS LINK (TB82, future use)
I+ = DATA HIGH CONNECTION
I - = DATA LOW CONNECTION
RS-BUS OUTDOOR (TB83)
R = 24VAC
I + = DATA HIGH CONNECTION
I - = DATA LOW CONNECTION
C = 24VAXC COMMON
RS-BUS INDOOR (TB84)
R = 24VAC
I + = DATA HIGH CONNECTION
I - = DATA LOW CONNECTION
C = 24VAXC COMMON
1/4” QUICK CONNECT TERMINALS
HUM = UNPOWERED NORMALLY OPEN (DRY) CONTACTS
XMFR = 120 VAC OUTPUT TO TRANSFORMER
LI = 120 VAC INPUT TO CONTROL
ACC = 120 VAC OUTPUT TO OPTIONAL ACCESSORY
NEUTRALS = 120 VAC NEUTRAL
C
W1 W2 GY2Y1
NON-COMMUNICATINGNG
24V TERMINALS
12 PIN LOW
VOLTAGE
CONNECTOR
W915 Y1 TO Y2
2 STAGE COMPR
W951 R TO O
HEAT PUMP
W914 R TO DS
DEHUM OR
CC
RDHLODS
HARMONY
THERMOSTAT CONNECTIONS (TB1)
DS = DEHUMIDIFICATION SIGNAL
W2 = HEAT DEMAND FROM 2ND STAGE T/STAT
W1 = HEAT DEMAND FROM 1ST STAGE T/STAT
R = CLASS 2 VOLTAGE TO THERMOSTAT
G = MANUAL FAN FROM T'STAT
C = THERMOSTAT SIGNAL GROUND CONNECTED TO
TRANSFORMER GRD (TR) & CHASIS GROUND (GRD)
Y1 = THERMOSTAT 1ST STAGE COOL SIGNAL
Y2 = THERMOSTAT 2ND STAGE COOL SIGNAL
O = THERMOSTAT SIGNAL TO HEAT PUMP
DH = DEHUMIDIFICATION OUTPUT COMMUNICATING
L = USE ONLY WITH A COMMUNICATING THERMOSTAT
AND A NON-COMMUNICATING OUTDOOR UNIT
REVERSING VALVE
THERMOSTAT ONLY
FIGURE 4
Page 6
THERMOSTAT SELECTION
1
2
*
TWO STAGE
THERMOSTAT
1−STAGE
THERMOSTAT
(TIMED STAGING)
−SEE SW #2
HEATING BLOWER−OFF DELAY
*
90 SECOND
HTG BLOWER
OFF DELAY
60 SECOND
HTG BLOWER
OFF DELAY
120 SECOND
HTG BLOWER
OFF DELAY
180 SECOND
HTG BLOWER
OFF DELAY
−BLOWER ON DELAY − 30 SEC. FIXED
3
ON
1
2
3
ON
1
2
3
ON
1
2
3
ON
1
2
3
ON
1
2
3
ON
HEATING MODE BLOWER SPEED
9
+ 24%
+ 18%
+ 12%
INCREASE AIR HTG CFM
+ 6%
*
FACTORY
DEFAULT
− 6%
− 12%
DECREASE AIR HTG CFM
− 18%
ON
9
ON
9
ON
9
ON
9
ON
9
ON
9
ON
9
ON
INTEGRATED CONTROL CONFIGURATION GUIDE
2ND STAGE HEAT ON DELAY
1
2
3
4
5
7 MIN
DELAY
12 MIN
DELAY
FLAME
SENSE
123456
ON
S4S3
911
10
ON
OUTDOOR
SENSOR
DISCHARGE
AIR SENSOR
I+ I
ON
1
ON
DIAGNOSTIC
PUSH BUTTON
13
14
12
*
UPSTAGE
4
5
6
7
8
4
5
6
7
8
4
5
6
7
8
4
5
6
7
8
4
5
6
7
8
4
5
6
7
8
11
13
10
15
12
14
UPSTAGE
6
7
2
3
4
5
6
7
HUM
S1
7
8
15
CLG BLOWER SPEED ADJUSTMENT
*
DEFAULT
8
8
ACC
−
11
13
10
12
15
14
R
11
13
10
10
10
10
10
10
15
12
14
11
13
12
15
14
11
13
12
15
14
11
13
15
12
14
11
13
12
15
14
11
13
12
15
14
I+ I−CRI+ I−
OUTDOOR EQUIPMENT
1−STG COMPRESSOR
W915
2 STAGE
COMPR
DO NOT CUT
2−STG COMPRESSOR
W915
2 STAGE
COMPR
CUT LINK
2−STAGE
COMPRESSOR LINK
(JUMPERS Y1 to Y2)
W915
INDOOR EQUIPMENT
1
C
W1W2GY2
W2
W1
ON−BOARD LINK
OPTION SELECTION
A/C UNIT
W951
HEAT
PUMP
DO NOT CUT
HEAT PUMP UNIT
W951
HEAT
PUMP
CUT LINK
HEAT PUMP LINK
(JUMPERS R to O)
W951
G
Y2
1
ON
ON
+ 10%
ON
− 10%
L1
DIAGNOSTIC
LED
SureLight
Y1 C CDH L O DSR
C
C
Y1
1
2
3
4
5
6
7
1
2
3
4
5
6
7
1
2
3
4
5
6
7
HSI/CAI
1
J3
®
R
NO HARMONY ZONING
NO SIGNATURESTAT
W/ DS CONNECTION
5
N
IGN
CAI1
CAI2
P79
14
3
110
4 7
3
12
CUT FOR
OPTION
SELECTION
W915
2 STAGE
COMPR
W951
HEAT
PUMP
W914
DEHUM
HARMONY
L
DH
OR
DO NOT CUT
W914
DEHUM
or
HARMONY
HARMONY ZONING
OR
SIGNATURESTAT W/
DS CONNECTION
CUT LINK
1
W914
DEHUM
or
HARMONY
DEHUMIDIFICATION−
HARMONY LINK
(JUMPERS R to DS)
W914
8
8
8
N
NEUTRALS
6
J2
CONTINUOUS FAN MODE BLOWER SPEED
MEDIUM−LOW
*
SPEED
(38%)
MEDIUM−HIGH
SPEED
(70%)
LOW
SPEED
(28%)
HIGH
SPEED
(100%)
9
11
13
10
12
ON
9
ON
9
ON
9
ON
14
11
10
12
14
11
10
12
14
11
10
12
14
COOLING MODE BLOWER SPEED
1
2
3
4
5
*
HIGH
SPEED
MEDIUM−HIGH
SPEED
MEDIUM−LOW
SPEED
LOW
SPEED
COOLING MODE BLOWER RAMPING
*
OPTION A
OFF−50%−82%−
100%−50%−OFF
OPTION B
OFF−82%−100%−OFF
OPTION C
OFF−100%−100%−OFF
OPTION D
OFF−100%−OFF
−CUT ON−BOARD LINK (SOLDER TRACE) COMPLETELY THROUGH
1
BOTH LAYERS ON THE CONTROL BOARD
−LINKS CUT IN ERROR −INSTALL A JUMPER ON THE APPROPRIATE
TERMINALS ON THE TERMINAL STRIP
−PROTECTIVE PLASTIC FILM ON DIP SWITCHES MAY BE
REMOVED FOR EASE IN SETTING OF DIP SW.
ON
1
ON
1
ON
1
ON
9
ON
9
ON
9
ON
9
ON
* FACTORY DEFAULT
6
7
2
3
4
5
6
7
2
3
4
5
6
7
2
3
4
5
6
7
11
13
10
12
14
11
13
10
12
14
11
13
10
12
14
11
13
10
12
14
15
15
15
15
8
8
8
8
15
15
15
15
FIGURE 5
Page 7
TABLE 4
Integrated Control Diagnostic Modes
DispalyAction (when button released)
No change (idle)*Remain in idle mode
Solid “E”Enter diagnostic recall mode
Solid “D”Discharge Air Installed
Solid “F”Enter fl ame signal mode
Solid “P” (variable speed only)Program unit capacity/size (Unit Code)
Two horizontal bars =Soft disable
* No change implies the display will continue to show whatever is currently being displayed for normal operation (blinking decimal, active error code,
heat state, etc..)
Diagnostic LED (Figure 5)
The seven-segment diagnostic LED displays operating
status, target airfl ow, error codes and other information.
The table beginning on Page 9 lists diagnostic LED codes.
Diagnostic Push Button (Figure 5)
The diagnostic push button is located adjacent to the seven-segment diagnostic LED. This button is used to enable
the Error Code Recall “E” mode and the Flame Signal
“F” mode. Press the button and hold it to cycle through a
menu of options. Every fi ve seconds a new menu item will
be displayed. When the button is released, the displayed
item will be selected. Once all items in the menu have
been displayed, the menu resumes from the beginning
until the button is released.
Error Code Recall Mode
Select ”E” from the menu to access the most recent 10
error codes. Select “c” from the Error Code Recall menu
to clear all error codes. Button must be pressed a second
time while “c” is fl ashing to confi rm command to delete
codes. Press the button until a solid “≡” is displayed to exit
the Error Code Recall mode.
Flame Signal Mode
Select ”F” from the menu to access the fl ame signal mode.
The integrated control will display the fl ame current on 7
segment LED in in micro amps (uA).
• Flame signal mode is exited after any of the following: Power is reset
• Pressing and holding push button until 3 horizontal
lines “≡” are displayed
• 10 minutes after entering the fl ame sense mode.
Program Unit Capacity/Size Mode
After the “P” is selected (by releasing the push button)
the integrated control will start fl ashing the “P” on display
for 90 seconds. If push button is pressed again and held
during that time, the control will start to display characters
corresponding to different variable speed furnace models
for 3 seconds each. While the wanted character-model is
displayed push button has to be released. Selected option
will fl ash display for 10 seconds and during that time push
button has to be pressed and held for 5 seconds. Once
control accepts new setting it will store data in non-volatile
memory and reset itself. If 10 seconds expires or push
button is held less than 5 seconds, control will exit fi eld
test mode and go into idle without changing programming
the unit size.
Soft Disable
Soft disabling is when thermostat fi nds a device on the
BUS that it does not recognize and the thermostat sends
a the device a message to be in soft disabling mode until
properly confi gured. Two horizontal bars will display.
Steps to follow if the damper control module is displaying
the soft disable code.
1 - Confi rm proper wiring between all devices
(thermostat, damper control module, indoor and
outdoor).
2 - Cycle power to the control that is displaying the soft
disable code.
3 - Put the room thermostat through set up.
4 - Go to setup / system devices / thermostat / edit
/ then push reset.
5 - Go to setup / system devices / thermostat / edit /
then push resetAll.
Page 8
TABLE 5
Integrated Diagnostic Codes/Status of Equipment
CodeDiagnostic Codes/Status of EquipmentAction Required to Clear and Recover
.Idle mode (Decimal blinks at 1 Hertz -- 0.5
second ON, 0.5 second OFF).
ACubic feet per minute (cfm) setting for
indoor blower (1 second ON, 0.5 second
OFF) / cfm setting for current mode
displayed.
second OFF) / % of input rate displayed
/ Pause / cfm setting / Pause / Repeat
codes.
HGas Heat Stage (1 second ON, 0.5 second
OFF) / 1 or 2 displayed / Pause / cfm
setting displayed / Pause / Repeat codes.
Blinking during ignition.
dFDefrost mode.
UDischarge Air Temperature
E105Device communication problem - No other
devices on RS BUS (Communication
system).
E110Low line voltage.Line Voltage Low (Voltage lower than nameplate rating). Check power line
E111Low line voltage.Reverse line power voltage wiring. System resumes normal operation 5
E112Ground not detectedSystem shuts down. Provide proper earth ground. System resumes normal
E113High line voltage.Line Voltage High (Voltage higher than nameplate rating). Provide power
E114Line voltage frequency out-of-range.No 60 Hertz Power. Check voltage and line power frequency. Correct
E115Low 24V - Control will restart if the error
recovers.
E116High 24V.24 Volt Power High (Range is 18 to 30 volts). Check and correct voltage.
E117Poor ground detected (Warning only)Provide proper grounding for unit. Check for proper earth ground to the
E120Unresponsive device. Communication
only.
Equipment is unable to communicate. Indicates numerous message
errors. In most cases errors are related to electrical noise. Make sure
high voltage power is separated from RSBus. Check for miswired and/or
loose connections between the stat, indoor unit and outdoor unit. Check
for a high voltage source of noise close to the system. Fault clears after
communication is restored.
voltage and correct. Alarm clears 5 seconds after fault recovered.
seconds after fault recovered.
operation 5 seconds after fault recovered.
voltage within proper range. System resumes normal operation 5 seconds
after fault recovered.
voltage and frequency problems. System resumes normal operation 5
seconds after fault recovered.
24-Volt Power Low (Range is 18 to 30 volts). Check and correct voltage.
Check for additional power-robbing equipment connected to system. May
require installation of larger VA transformer to be installed in furnace / air
handler. Clears after fault recovered.
Check for proper line voltage (120V, 240V, etc.) to equipment. Clears when
control senses proper voltage.
system. Warning only will clear 30 seconds after fault recovered.
Usually caused by delay in outdoor unit responding to indoor unit poling.
Recycle power. Check all wiring connections. Cleared after unresponsive
device responds to any inquiry.
Page 9
TABLE 5 Continued
Code
E124Active communicating thermostat signal
Diagnostic Codes/Status of EquipmentAction Required to Clear and Recover
Equipment lost communication with the thermostat. Check
missing for more than 3 minutes.
four wiring connections, ohm wires and cycle power at the
thermostat. Alert stops all services and waits for heartbeat
message from thermostat (subnet controller). Cleared after
valid thermostat (subnet controller) message is received.
E125Control failed self-check, internal error,
failed hardware. Will restart if error recovers. Integrated control not communicating.
Hardware problem on the control. Cycle power on control.
Replace if problem prevents service and is persistent. Criti-
cal alert. Cleared 300 seconds after fault recovered.
Covers hardware errors (fl ame sense cir-
cuit faults, pin shorts, etc.).
E126Control internal communication problem.Hardware problem on the control. Cycle power on con-
trol. Replace if problem prevents service and is persistent.
Cleared 300 seconds after fault recovered.
E131Corrupted control parameters (Verify con-
fi guration of system). Communicating only.
Reconfi gure the system. Replace control if heating or cool-
ing is not available. Only applicable in the communicating
mode, not in startup. Exit from Commissioning and Execute
‘Set Factory Default mode Control will still operate on default
parameter settings
E180Outdoor air temperature sensor failure.
Only shown if shorted or out-ofrange.
Compare outdoor sensor resistance to temperature/ resis-
tance charts in unit installation instructions. Replace sensor
pack if necessary. At beginning of (any) confi guration, furnace
or air handler control will sense outdoor air and discharge
air temperature sensor(s). If detected (reading in range),
appropriate feature will be set as ‘installed’ and that could
be seen in ‘About’ screen. In normal operation after control
recognizes sensors, alarm will be sent if valid temperature
reading is lost. To get rid of setting and alarm, redo confi gu-
ration and make sure that temperature sensor is marked as
‘not installed’ in Indoor Unit ‘About’ screen. When Indoor unit
control is replaced, thermostat will ‘tell’ new control if tem-
perature sensor is in system or not. Clears 30 seconds after
fault recovered.
E200Hard lockout - Rollout circuit open or pre-
viously open.
E201Indoor blower communication failure - Un-
able to communicate with blower motor.
Correct cause of rollout trip, or replace fl ame rollout switch.
Test furnace operation. Cleared after fault recovered.
Indoor blower communication failure (including power out-
age). Lost communication with indoor blower motor. Possible
causes: motor not powered, loose wiring. Problem may be
on control or motor side. Cleared after fault recovered.
E202Indoor blower motor mis-match - Indoor
motor horsepower does not match unit capacity.
Incorrect appliance capacity code selected. Check for proper
confi guring under: Unit Size Codes for Furnace/Air Handler
on confi guration guide or in installation instructions. Cleared
after the correct match is detected following a reset. (Re-
move thermostat from system while applying power and re-
programming.)
E203Appliance capacity / size is NOT pro-
grammed. Invalid unit codes refer to confi guration fl ow chart.
No appliance capacity code selected. Check for proper con-
fi guring under: Unit Size Codes for Furnace on confi guration
guide or in installation instructions. Critical Alert. Cleared af-
ter valid unit code is read following a reset. (Remove thermo-
stat from system while applying power and reprogramming.)
E204Gas valve mis-wired.Check gas valve operation and wiring. Clears when repaired.
E205Gas valve control relay contact shorted.Check wiring on control and gas valve. If wiring is correct,
replace control.
Page 10
TABLE 5 Continued
CodeDiagnostic Codes/Status of EquipmentAction Required to Clear and Recover
E206Gas valve second-stage relay failureFurnace will operate on 1st stage for remainder of the
heating demand. Will clear after fault recovered. If unable to operate 2nd stage, replace control.
E207Hot surface ignitor sensed open.Measure resistance of hot surface ignitor. Replace if
open or not within specifi ed range found in IOM. Re-
sumes normal operation after fault is cleared.
closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for
correct operation and restriction. Resumes normal operation after fault is cleared
E224Low pressure switch failed closed.Check operation of low pressure switch to see if it is
stuck closed on heat call longer than 150 seconds. Measure operating pressure (inches w.c.). Inspect vent and
combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.
E225High pressure switch failed open.Check pressure (inches w.c.) of high pressure switch
closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for
correct operation and restriction. Resumes normal operation after fault is cleared.
E226High pressure switch failed closedCheck operation of high pressure switch closing on heat
call. Measure operating pressure (inches w.c.). Inspect
vent and combustion air inducer for correct operation
and restriction. Resumes normal operation after fault is
cleared.
E227Low pressure switch open during trial for ignition
or run mode.
E228Combustion air inducer calibration failureUnable to perform pressure switch calibration. Check
E229Ignition on high fi reIFC switched to high fi re ignition because low fi re pres-
E240Low fl ame current - Run mode.Check micro-amperes of fl ame sensor using control
E241Flame sensed out of sequence - Flame still pres-
ent.
E250Limit switch circuit open.Check for proper fi ring rate on furnace. Ensure there is
E252Discharge air temperature too high (gas heat only). Check temperature rise, air fl ow and input rate. Cleared
E270Soft lockout - Exceeded maximum number of re-
tries. No fl ame current sensed.
Check pressure (inches w.c.) of low pressure switch
closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for
correct operation and restriction. Resumes normal operation after fault is cleared.
vent system and pressure switch wiring connections.
Resumes normal operation after fault is cleared.
sure switch did not close in allowed time. No action is
needed.
diagnostics or fi eld-installed mode. Clean or replace
sensor. Measure voltage of neutral to ground to ensure
good unit ground. Alert clears after current heat call has
been completed.
Shut off gas. Check for gas valve leak. Replace, if necessary. Alert clears when fault is recovered.
no blockage in heater. Check for proper air fl ow. If limit
not closed within 3 minutes, unit will go into 1-hour soft
lockout. Resumes normal operation after fault is cleared.
when heat call is fi nished.
Check for proper gas fl ow. Ensure that ignitor is lighting
burner. Check fl ame sensor current. Clears when heat
call fi nishes successfully.
Page 11
TABLE 5 Continued
CodeDiagnostic Codes/Status of EquipmentAction Required to Clear and Recover
E271Soft lockout - Exceeded maximum number of re-
tries. Last retry failed due to the pressure switch
opening.
E272Soft lockout - Exceeded maximum number of re-
cycles. Last recycle due to the pressure switch
opening.
E273Soft lockout - Exceeded maximum number of re-
cycles. Last recycle due to fl ame failure.
E274Soft lockout - Exceeded maximum number of re-
cycles. Last recycle failed due to the limit circuit
opening or limit remained open longer than 3 minutes
E275Soft lockout - Flame sensed out of sequence.
Flame signal is gone.
E276Watchguard calibration failure.Unable to perform pressure switch calibration. Check vent
E290Ignitor circuit fault - Failed ignitor or triggering cir-
cuitry.
E291Heat air fl ow restricted below the minimum.Check for dirty fi lter and air fl ow restriction. Check blower
E292Indoor blower motor unable to start due to ob-
structed wheel, seized
bearings.
E294Combustion air inducer over current.Check combustion blower bearings, wiring and amps. Re-
E295Indoor blower motor temperature is too high.Indoor blower motor over temperature (motor tripped on
E310Discharge error temperature sensor failure. Only
shown if shorted or
out of range.
E311Heat rate reduced to match indoor blower air fl ow. Warning Only. Furnace blower in cutback mode due to
Check pressure (inches w.c.) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.).
Inspect vent and combustion air inducer for correct operation and restriction. Clears when heat call fi nishes suc-
cessfully.
Check operation of low pressure switch to see if it is stuck
closed on heat call. Check pressure (inches w.c.) of high
pressure switch closing on heat call. Measure operating
pressure (inches w.c.). Inspect vent and combustion air
inducer for correct operation and restriction. Clears when
heat call fi nishes successfully.
Check micro-amperes of fl ame sensor using control diag-
nostics or fi eld-installed mode. Clean or replace sensor.
Measure voltage of neutral to ground to ensure good unit
ground. Clears when heat call fi nishes successfully.
Shut down system. 1-hour soft lockout. Check fi ring rate
and air fl ow. Check for blockage. Clears when heat call fi nishes successfully.
Shut off gas. Check for gas valve leak. 1-hour soft lockout.
Clears when fl ame has been proven stable.
system and pressure switch wiring connections. 1-hour soft
lockout. Clears when calibration has fi nished successfully.
Measure resistance of hot surface ignitor. Replace if open
or not within specifi cations. 1-hour soft lockout. Clears
when fl ame has been proven stable.
Indoor blower motor unable to start (seized bearing, stuck
wheel, etc.). Replace motor or wheel if assembly does not
operate or meet performance standards. 1-hour soft lockout. Clears after circulator successfully starts.
place if does not operate or does not meet performance
standards. Clears after inducer current is sensed to be inrange after the ignition following the soft lockout or reset.
internal protector). Check motor bearings and amps. Replace if necessary. Cleared after blower demand is satisfi ed.
Compare outdoor sensor resistance to temperature/ resistance charts in installation instructions. Replace sensor
if necessary. Cleared in Communicating mode: 30 seconds after fault recovered. In Non- Communicating mode:
Cleared after the current heat call is completed.
restricted airfl ow. Reduce fi ring rate every 60 seconds to
match available CFM. Check fi lter and duct system. To
clear, replace fi lter if needed or repair/ add duct. 2-stage
controls will reduce fi ring rate to 1st stage. Clears when
heat call fi nishes successfully.
Page 12
TABLE 5 Continued
CodeDiagnostic Codes/Status of EquipmentAction Required to Clear and Recover
E312Restricted air fl ow in cooling or continu-
ous fan mode is lower than cfm setting.
E313Indoor or outdoor unit capacity mismatch.
Communication only.
E331Global network connection - Communica-
tion link problem.
E334Relay “Y1” stuck on interated control.Replace integrated control.
E347No 24 Volt output on Y1 of ”integrated
control” with non communicating outdoor
unit.
E348No 24 Volt output on Y2 of ”integrated
control” with non?communicating outdoor
unit.
E349No 24 Volts between R & O on ”integrated
control” with non communicating outdoor
unit (Dual fuel module required for heat
pump application
E370Interlock switch sensed open for 2 min-
utes.
E400LSOM - Compressor internal overload
tripped.
E401LSOM Compressor long run cycle or low
system pressure.
E402LSOM - Outdoor unit system pressure
trip.
E403LSOM - Compressor short-cycling. .(Run-
ning less than 4 minutes). Outdoor unit
pressure trip
E404LSOM - Compressor rotor locked. Com-
pressor short-cycling. (Running less than
4 minutes).
E405LSOM - Compressor open circuit.Compressor circuit open (due to power disconnection, open fuse,
Warning Only. Restricted airfl ow - Indoor blower is running at a re-
duced CFM (Cutback Mode - The variable speed motor has pre-set
speed and torque limiters to protect the motor from damage caused
by operating outside of design parameters (0 to 0.8” W.C.. total external static pressure). Check fi lter and duct system. To clear, re-
place fi lter if needed or repair/add duct. Cleared after the current
service demand is satisfi ed.
Incorrect indoor/outdoor capacity code selected. Check for proper
confi guring in installation instructions. Alarm is just a warning. The
system will operate, but might not meet effi ciency and capacity pa-
rameters. Alarm will clear when commissioning is exited. Cleared
after commissioning is complete.
For Future Use.
Operation stopped. Y1 relay / Stage 1 failed. (Pilot relay contacts
did not close or the relay coil did not energize; no input back to IFC
chip). Critical Alert. Cleared after reset and Y1 input sensed.
Y2 relay / Stage 2 failed. (Pilot relay contacts did not close or the
relay coil did not energize; no input back to IFC chip). Critical Alert.
Cleared after reset and Y1 input sensed.
Confi guration link R to O needs to be restored. Replace link or hard-
wire. Applicable in non communicating mode. Critical Alert.
Control sees the loss of 24VAC for 2 minutes.Terminate all services
and wait for interlock switch to close. The alarm will clear when
24VAC is continuously sensed on DS terminal for a minimum of 10
seconds or on a power reset.
Thermostat demand Y1 is present; but, compressor is not running.
Check power to outdoor unit. Clears the error after current is sensed
in both RUN and START sensors for at least 2 seconds, or after
service is removed, or after power reset.
Compressor ran more than 18 hours to satisfy a single thermostat
demand. Critical Alert. Clears the error after 30 consecutive normal
run cycles or power reset. Also monitors low pressure switch trips.
Discharge or suction pressure out-of-limits, or compressor overloaded. Clears the error after 4 consecutive normal compressor run
cycles.
Compressor runs less than 3 minutes to satisfy a thermostat demand. Clears the error after 4 consecutive normal run cycles or
power reset.
Compressor rotor locked up due to run capacitor short, bearings
are seized, excessive liquid refrigerant, etc. Clears the error after 4
consecutive normal run cycles or after power reset.
etc.) Clears the error after 1 normalcompressor run cycle.
Page 13
TABLE 5 Continued
CodeDiagnostic Codes/Status of EquipmentAction Required to Clear and Recover
E406LSOM - Compressor open start circuit.Required amount of current is not passing through Start cur-
rent transformer. Clears the error after current is sensed in
START sensor, or after power reset.
E407LSOM - Compressor open run circuit.Required amount of current is not passing through Run current
transformer. Clears the error after current is sensed in RUN
sensor, or 1 normal compressor run cycle, or after power reset.
E408LSOM - Compressor contactor is welded.Compressor runs continuously. Clears the error after 1 normal
compressor run cycle or after power reset.
E409LSOM - Compressor low voltage.Secondary voltage is below 18VAC. After 10 minutes, oper-
ation is discontinued. Clears the code after voltage is higher
than 20 VAC for 2 seconds or after power reset.
DIP Switch Settings
NOTE - All icomfort settings are set at the icomfort Wi-Fi
®
thermostat. See icomfort installation instruction. In icomfort communication system all DIP switch and clippable
link settings are ignored. For conventional thermostats
proceed with DIP switch and clippable link settings as outlined in the following.
Heating Operation DIP Switch Settings
Switch 1 -- Thermostat Selection -- This unit may be
used with either a single-stage or two-stage thermostat.
The thermostat selection is made using a DIP switch
which must be properly positioned for the particular application. The DIP switch is factory-positioned for use with a
twostage thermostat. If a single-stage thermostat is to be
used, the DIP switch must be repositioned.
a. Select “OFF” for two-stage heating operation controlled by a
two-stage heating thermostat (factory setting);
b. Select “ON” for two-stage heating operation controlled by
a single-stage heating thermostat. This setting provides a
timed delay before second-stage heat is initiated.
Switch 2 -- Second Stage Delay (Used with SingleStage Thermostat Only) -- This switch is used to deter-
mine the second stage on delay when a single-stage thermostat is being used. The switch is factory-set in the OFF
position, which provides a 7-minute delay before secondstage heat is initiated. If the switch is toggled to the ON
position, it will provide a 12-minute delay before secondstage heat is initiated. This switch is only activated when
the thermostat selector jumper is positioned for SINGLEstage thermostat use.
Switches 3 and 4 -- Blower-Off Delay -- The blower-on
delay of 30 seconds is not adjustable. The blower-off delay (time that the blower operates after the heating demand has been satisfi ed) can be adjusted by moving
switches 3 and 4 on the integrated control. The unit is
shipped from the factory with a blower-off delay of 90 seconds. The blower off delay affects comfort and is adjustable to atisfy individual applicationsAdjust the blower off
delay to achieve a supply air temperature between 90°
and 110°F at the exact moment that the blower is de-energized. Longer off delay settings provide lower supply air
temperatures; shorter settings provide higher supply air
temperatures. Table 6 provides the blower off timings that
will result from different switch settings.
TABLE 6
Blower Off Delay Switch Settings
Blower Off Delay
Seconds
60OnOff
90 (factory)OffOff
120OffOn
180OnOn
Switch 3Switch 4
Indoor Blower Operation DIP Switch Settings
Switches 5 and 6 -- Cooling Mode Blower Speed -- The
unit is shipped from the factory with the dip switches positioned for high speed (4) indoor blower motor operation
during the cooling mode. Table 7 provides the cooling
mode blower speeds that will result from different switch
settings. Switches 5 and 6 set the blower cfm for secondstage cool. The integrated control automatically ramps
down to 70% of the second-stage cfm for fi rst-stage cfm.
Refer to tables for corresponding cfm values.
TABLE 7
Cooling Mode Blower Speeds
SpeedSwitch 5Switch 6
LowOnOn
Medium LowOffOn
Medium HighOnOff
High (factory)OffOff
. Switches 7 and 8 -- Cooling Blower Speed Adjust-
ment
-- The unit is shipped from the factory with the dip switches
positioned for NORMAL (no) adjustment. The dip switches
may be positioned to adjust the blower speed by +10% or
-10% to better suit the application. Table 8 below provides
blower speed adjustments that will result from different
switch settings. Refer to tables for corresponding cfm values.
Page 14
TABLE 8
Cooling Blower Speed Adjustment
AdjustmentSwitch 7Switch 8
+10% (approx)OnOff
Factory DefaultOffOff
-10% (approx)OffOff
Ramping Option C
• Motor runs at 100% until demand is satisfi ed.
• Once demand is met, motor runs at 100% for 45 sec-
onds then ramps down to stop.
OFF
100% CFM
COMPRESSOR
DEMAND
100% CFM
45 SEC.
OFF
Switches 9 and 10 -- Cooling Mode Blower Speed
Ramping -- Blower speed ramping may be used to en-
hance dehumidifi cation performance. The switches are
factory set at option A which has the greatest effect on dehumidifi cation performance. Table 9 provides the cooling
mode blower speed ramping options that will result from
different switch settings. The cooling mode blower speed
ramping options are detailed below.
TABLE 9
Cooling Mode Blower Speed Ramping
RampingSwitch 9Switch 10
A (Factory)OffOff
BOffOn
COnOff
DOnOn
Ramping Option A (Factory Selection)
• Motor runs at 50% for 30 seconds.
• Motor then runs at 82% for approximately 7-1/2 minutes.
• If demand has not been satisfi ed after 7-1/2 minutes,
motor runs at 100% until demand is satisfi ed.
• Once demand is met, motor runs at 50% for 30 seconds then ramps down to stop.
OFF
1/2 MIN
50% CFM
7 1/2 MIN
82% CFM
COMPRESSOR DEMAND
100%
CFM
1/2 MIN
50% CFM
OFF
Ramping Option D
• Motor runs at 100% until demand is satisfi ed.
• Once demand is met, motor ramps down to stop.
100% CFM
COMPRESSOR
DEMAND
OFFOFF
Switches 11, 12 and 13 -- Heating Mode Blower Speed
The switches are factory set to the OFF position which
provides factory default heat speed. Refer to Table 10 for
switches 11, 12 and 13 that provided the corresponding
increases or decrease to both high and low heat demand.
TABLE 10
Heating Mode Blower Speeds
Heat SpeedSwitch 11Switch 12Switch 13
Increase 24%OnOnOn
Increase 18%OnOnOff
Increase 12%OnOffOn
Increae 6%On OffOff
Factory
OffOffOff
Default
Decrease 6%OffOffOn
Decrease
OffOnOff
12%
Decrease
OffOnOn
18%
Switches 14 and 15 -- Continuous Blower Speed --
Table 11 provides continuous blower speed adjustments
that will result from different switch settings.
Ramping Option B
• Motor runs at 82% for approximately 7-1/2 minutes. If
demand has not been satisfi ed after 7-1/2 minutes,mo-
tor runs at 100% until demand is satisfi ed.
• Once demand is met, motor ramps down to stop.
OFF
7 1/2 MIN
82%CFM
COMPRESSOR DEMAND
100% CFM
OFF
Page 15
TABLE 11
Continuous Blower Speed
Coninuous Blower SpeedSwitch 14Switch 15
28% of High Cool SpeedOffOn
38% of High Cool Speed
(Factory)
70% of High Cool SpeedOnOff
100% of High Cool SpeedOnOn
OffOff
Loading...
+ 35 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.