Lennox SL280UHNV, SL280UH060NV36A, SL280UH080NV48B Series Manual

Page 1
UNIT INFORMATION
UNIT INFORMATION
Corp 1601-L8
Service Literature
ICOMFORT®-ENABLED SL280UHNV SERIES UNITS
SL280UHNVseries units are 80% effi ciency gas furnac- es used for upfl ow or horizontal applications only, man- ufactured with Lennox Duralok heat exchangers formed of aluminized steel. SL280UHNV units are available in heating capacities of 40,000 to 100,000 Btuh and cooling applications up to 5 tons. Refer to Engineering Handbook for proper sizing.
Units are approved for installations up 4500 ft and facto­ry equipped for use with natural gas only. SL280UHNV model units are equipped with the iComfort® enabled SureLight® two-stage variable speed integrated control. SL280UHNV unit meets the California Nitrogen Oxides (NOx) Standards and California Seasonal Effi ciency re- quirements. All units use a redundant gas valve to assure safety shut-off as required by C.S.A.
All specifi cations in this manual are subject to change. Procedures outlined in this manual are presented as a recommendation only and do not supersede or replace lo­cal or state codes. In the absence of local or state codes, the guidelines and procedures outlined in this manual (ex­cept where noted) are recommendations only and do not constitute code.
SL280UHNV
Contents
I-Unit Components..........................................................4
Blower Data ..................................................................16
II-Placement and Installation ........................................ 31
III-Start-Up .................................................................... 31
IV-Heating System Service Checks ..............................32
V-Typical Operating Characteristics .............................34
VI-Maintenance ............................................................35
VII- Wiring and Sequence of Operation ........................38
VIII- Field Wiring With Conventional Thermostat ..........42
IX- Program Unit Capacity Size Modes ........................46
X- Troubleshooting ....................................................... 47
Page 1
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
©2017 Lennox Industries, Inc.
Page 2
SPECIFICATIONS
Gas Heating Performance
High Fire
Temperature rise range - °F 30 - 60 30 - 60
Gas Manifold Pressure (in. w.g.)
Low Fire
Temperature rise range - °F 20 - 50 20 - 50
Gas Manifold Pressure (in. w.g.)
High static - in. w.g. Heating 0.8 0.8
Connections
Flue connection in. round 4 4
in.
Indoor
Wheel nominal diameter x width - in. 10 X 8 11-1/2 X 9
Blower
Tons of add-on cooling 2 - 3 2.5 - 4
Air Volume Range - cfm 606 - 1345 679 - 2002
Electrical Data Voltage 120 volts - 60 hertz - 1 phase
Blower motor full load amps 7.7 12.8
Maximum overcurrent protection 15 20
Shipping Data lbs. - 1 package 112 138
NOTE - Filters and provisions for mounting are not furnished and must be fi eld provided.
1
Annual Fuel Utilization Effi ciency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
Model No. SL280UH060NV36A SL280UH080NV48B
1
AFUE 80% 80%
Input - Btuh 60,000 80,000
Output - Btuh 48,000 64,000
3.4 3.4
Natural Gas Only
Input - Btuh 39,000 52,000
Output - Btuh 31,000 41,000
1.5 1.5
Natural Gas Only
Cooling 1.0 1.0
Gas pipe size IPS 1/2 1/2
Motor output - hp 1/2 1.0
SPECIFICATIONS
Gas Heating Performance
High Fire
Temperature rise range - °F 30 - 60 30 - 60
Gas Manifold Pressure (in. w.g.)
Low Fire
Temperature rise range - °F 20 - 50 25 - 50
Gas Manifold Pressure (in. w.g.)
High static - in. w.g. Heating 0.8 0.8
Connections
Flue connection in. round 4 4
in.
Indoor
Wheel nominal diameter x width - in. 11-1/2 X 10 11-1/2 X 10
Blower
Tons of add-on cooling 3 - 5 3 - 5
Air Volume Range - cfm 826 - 2305 812 - 2125
Electrical Data Voltage 120 volts - 60 hertz - 1 phase
Blower motor full load amps 12.8 12.8
Maximum overcurrent protection 20 20
Shipping Data lbs. - 1 package 157 161
NOTE - Filters and provisions for mounting are not furnished and must be fi eld provided.
1
Annual Fuel Utilization Effi ciency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
Model No. SL280UH080NV60C SL280UH100NV60C
1
AFUE 80% 80%
Input - Btuh 80,000 100,000
Output - Btuh 64,000 80,000
3.4 3.4
Natural Gas Only
Input - Btuh 52,000 65,000
Output - Btuh 41,000 52,000
1.5 1.5
Natural Gas Only
Cooling 1.0 1.0
Gas pipe size IPS 1/2 1/2
Motor output - hp 1.0 1.0
Page 2
Page 3
Combustion Air Inducer
A
Gas Valve
Air Intake Pipe
Heat Exchanger
ccess Panel
Inner Access
Panel
(includes two-stage integrated control,
transformer and circuit breaker)
FIGURE 1
Control Box
Blower Assembly
Page 3
Page 4
I-Unit Components
SL280UHNV unit components are shown in Figure 1. The gas valve, combustion air inducer and burners can be ac­cessed by removing the access panel. Electrical compo­nents are in the control box (Figure 2) found in the blower section.
SL280UHNV units are factory equipped with a bottom re­turn air panel in place. The panel is designed to be fi eld removed as required for bottom air return. Markings are provided for side return air and may be cut out in the fi eld.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic components. Take precautions during furnace installation and service to protect the furnace’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the furnace, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touching hand and all tools on an unpainted unit surface, such as the gas valve or blower deck, before performing any service procedure.
A- Control Box
1. Control Transformer (T1)
A transformer located in the control box provides pow­er tothe low voltage section of the unit. Transformers on allmodels are rated 40VA with a 120V primary and a 24V
secondary.
2. Door Interlock Switch (S51)
A door interlock switch rated 14A at 125VAC is wired in se­ries with line voltage. When the inner blower access panel
is removed the unit will shut down.
CONTROL BOX
Transformer
Circuit Breaker
Interlock Switch
®
SureLight
FIGURE 2
3. Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box. The switch provides overcurrent protection to the trans­former (T1). The breaker is rated 3A at 32V. If the current exceeds this limit the breaker will trip and all unit opera­tion will shutdown. The breaker can be manually reset by pressing the button on the face. See Figure 3
Integrated Control
CIRCUIT BREAKER CB8
PRESS TO RESET
FIGURE 3
WARNING
Shock hazard. Disconnect power before servicing. Integrated control is not fi eld repairable. If control is inoperable, simply replace entire control. Can cause injury or death. Unsafe operation will resul if repair is attempted.
4. Integrated Control (A92)
Units are equipped with the icomfort enabled SureLight ® two-stage, variable speed integrated control. This con­trol is used with the icomfort Wi-Fi® thermostat as part of a communicating comfort system. The control can also operate with a non-communicating conventional single or two-stage thermostat. The system consists of a ignition / blower control (Figure 4 and Figure 5) with control pin designations in Table 1, Table 2 and Table 3 and ignitor (Figure 13). The control and ignitor work in combination to ensure furnace ignition and ignitor durability. The con­trol provides gas ignition, safety checks and indoor blower control with two-stage gas heating.
The furnace combustion air inducer, gas valve and indoor blower are controlled in response to various system inputs such as thermostat signal, pressure and limit switch signal and fl ame signal. The control features a seven-segment LED display, indicating furnace status (including indoor blower) and error codes. The LED fl ashes in single dig- its. For example using Table 5 under LIMIT CODE, an “E” followed by “2” followed by “5” followed by “0”, the limit switch circuit is open. The control also has two unpowered (dry) 1/4” contacts for a humidifi er and a 120 volt accesso- ry terminal. Both rated at (1) one amp each.
Electronic Ignition
At the beginning of the heat cycle the integrated control monitors the fi rst stage and second stage combustion air inducer prove switch. The control will not begin the heating cycle if the fi rst stage prove switch is closed (by-passed). Likewise the integrated control will not begin the second stage heating cycle if the second stage prove switch is closed, and will remain in fi rst stage heat. However, if the second stage prove switch closes during the fi rst stage heat pre-purge, the control will allow second stage heat.
Once the fi rst stage prove switch is determined to be open, the combustion air inducer is energized on low (fi rst stage) heat speed. When the differential in the prove switch is great enough, the prove switch closes and a 15-second pre-purge begins.
Page 4
Page 5
NOTE - During abnormal conditions such as low supply voltage or low outdoor temperatures and the low fi re pres- sure switch does not close, the combustion air inducer will switch to high fi re. After a 15 second pre-purge the high re pressure switch will close and the unit will begin op­eration on high fi re. After 10 to 20 seconds of high fi re operation the unit will switch to low fi re.
After the 15-second pre-purge period, the SureLight ig­nitor warms up for 20 seconds after which the gas valve opens for a 4-second trial for ignition. The ignitor ener­gizes during the trial until fl ame is sensed. If ignition is not proved during the 4-second period, the control will try four more times with an inter purge and warm-up time be­tween trials of 35 seconds. After a total of fi ve trials for ignition (including the initial trial), the control goes into Watchguard-Flame Failure mode. After a 60-minute reset period, the control will begin the ignition sequence again.
Two Stage Operation / Thermostat Selection DIP Switch
The control can be utilized in two modes: SINGLE-STAGE thermostat or TWO-STAGE thermostat. The thermostat selection is made using a DIP switch and must be posi­tioned for the particular application. DIP switch 1, labeled T”STAT HEAT STAGE is factory-set in the OFF position for use with a two-stage thermostat. Move the DIP switch to ON for use with a single stage thermostat.
While in the single-stage thermostat mode, the burners will always fi re on fi rst-stage heat. The combustion air in- ducer will operate on low speed and indoor blower will operate on low heat speed. The unit will switch to second stage heat after a “recognition period”. DIP switch 2, la­beled SECOND STAGE DELAY, is factory set in the OFF position for a 7 minute recognition period. The switch can be moved to the ON position for a 12 minute recognition period, after which time the unit will switch to secondstage heat.
While in the two-stage thermostat mode (two DIP switch setting) the burners will fi re on fi rst-stage heat. The com- bustion air inducer will operate on low speed and indoor blower will operate on low heat speed. The unit will switch to second-stage heat on call from the indoor thermostat. If there is a simultaneous call for fi rst and second stage heat, the unit will fi re an fi rst stage heat and switch to sec- ond stage heat after 30 seconds of operation. See Se­quence of Operation fl ow charts in the back of this manual for more detail.
TABLE 1
SureLight® Control 5 Pin Terminal Designation
PIN# Function
1 Ignitor
2 Combustion Air Inducer High
Speed
3 Combustion Air Inducer Low
Speed
4 Combustuion Air Inducer
Neutral
5 Ignitor Neutral
TABLE 2
SureLight® Control 12 Pin Terminal Designation
PIN# Function
1 Gas Valve High Fire
2 Second Stage Prove Switch
3 Rollout In
4 Ground
5 24V Hot
6 Primary Limit In
7 Gas Valve Low Stage
8 Gas Valve Common
9 24V Neutral
10 Ground
11 Rollout Switch Out
12 1st Stage Prove Switch
TABLE 3
SureLight® Control 6 Pin Terminal Designation
PIN# Function
1 Data Input From Motor
2 Common
3 Not Used
4 Data Output To Motor
5 5 Volt Bias Supply
6
Not Used
Page 5
Page 6
HUM
LINE 1
7 SEGMENT LED
FLAME SENSE
DIAGNOSTIC
PUSH BUTTON
DIP SWITCHES
ACC
HS/ CAI
INDOOR
BLOWER
CONNECTOR
NEUTRAL
OUTDOOR AIR
SENSOR
TERMINALS
DISCHARGE AIR
SENSOR
TERMINALS
TB83
COMMUNICATING
OUTDOOR
EQUIPMENT
I + I -CRI + I -
TB84
COMMUNICATING
INDOOR
THERMOSTAT
R
RS-BUS LINK (TB82, future use)
I+ = DATA HIGH CONNECTION I - = DATA LOW CONNECTION
RS-BUS OUTDOOR (TB83)
R = 24VAC I + = DATA HIGH CONNECTION I - = DATA LOW CONNECTION C = 24VAXC COMMON
RS-BUS INDOOR (TB84)
R = 24VAC I + = DATA HIGH CONNECTION I - = DATA LOW CONNECTION C = 24VAXC COMMON
1/4” QUICK CONNECT TERMINALS
HUM = UNPOWERED NORMALLY OPEN (DRY) CONTACTS
XMFR = 120 VAC OUTPUT TO TRANSFORMER
LI = 120 VAC INPUT TO CONTROL
ACC = 120 VAC OUTPUT TO OPTIONAL ACCESSORY
NEUTRALS = 120 VAC NEUTRAL
C
W1 W2 GY2Y1
NON-COMMUNICATINGNG
24V TERMINALS
12 PIN LOW
VOLTAGE
CONNECTOR
W915 Y1 TO Y2
2 STAGE COMPR
W951 R TO O HEAT PUMP
W914 R TO DS
DEHUM OR
CC
RDHLODS
HARMONY
THERMOSTAT CONNECTIONS (TB1)
DS = DEHUMIDIFICATION SIGNAL W2 = HEAT DEMAND FROM 2ND STAGE T/STAT W1 = HEAT DEMAND FROM 1ST STAGE T/STAT
R = CLASS 2 VOLTAGE TO THERMOSTAT
G = MANUAL FAN FROM T'STAT
C = THERMOSTAT SIGNAL GROUND CONNECTED TO TRANSFORMER GRD (TR) & CHASIS GROUND (GRD)
Y1 = THERMOSTAT 1ST STAGE COOL SIGNAL
Y2 = THERMOSTAT 2ND STAGE COOL SIGNAL
O = THERMOSTAT SIGNAL TO HEAT PUMP
DH = DEHUMIDIFICATION OUTPUT COMMUNICATING
L = USE ONLY WITH A COMMUNICATING THERMOSTAT
AND A NON-COMMUNICATING OUTDOOR UNIT
REVERSING VALVE
THERMOSTAT ONLY
FIGURE 4
Page 6
Page 7
THERMOSTAT SELECTION
1
2
*
TWO STAGE
THERMOSTAT
1−STAGE
THERMOSTAT
(TIMED STAGING)
−SEE SW #2
HEATING BLOWER−OFF DELAY
*
90 SECOND
HTG BLOWER
OFF DELAY
60 SECOND
HTG BLOWER
OFF DELAY
120 SECOND
HTG BLOWER
OFF DELAY
180 SECOND
HTG BLOWER
OFF DELAY
−BLOWER ON DELAY − 30 SEC. FIXED
3
ON
1
2
3
ON
1
2
3
ON
1
2
3
ON
1
2
3
ON
1
2
3
ON
HEATING MODE BLOWER SPEED
9
+ 24%
+ 18%
+ 12%
INCREASE AIR HTG CFM
+ 6%
*
FACTORY
DEFAULT
− 6%
− 12%
DECREASE AIR HTG CFM
− 18%
ON
9
ON
9
ON
9
ON
9
ON
9
ON
9
ON
9
ON
INTEGRATED CONTROL CONFIGURATION GUIDE
2ND STAGE HEAT ON DELAY
1
2
3
4
5
7 MIN
DELAY
12 MIN
DELAY
FLAME SENSE
123456
ON
S4S3
911
10
ON
OUTDOOR
SENSOR
DISCHARGE
AIR SENSOR
I+ I
ON
1
ON
DIAGNOSTIC
PUSH BUTTON
13
14
12
*
UPSTAGE
4
5
6
7
8
4
5
6
7
8
4
5
6
7
8
4
5
6
7
8
4
5
6
7
8
4
5
6
7
8
11
13
10
15
12
14
UPSTAGE
6
7
2
3
4
5
6
7
HUM
S1
7
8
15
CLG BLOWER SPEED ADJUSTMENT
*
DEFAULT
8
8
ACC
11
13
10
12
15
14
R
11
13
10
10
10
10
10
10
15
12
14
11
13
12
15
14
11
13
12
15
14
11
13
15
12
14
11
13
12
15
14
11
13
12
15
14
I+ I−CRI+ I−
OUTDOOR EQUIPMENT
1−STG COMPRESSOR
W915
2 STAGE
COMPR
DO NOT CUT
2−STG COMPRESSOR
W915
2 STAGE
COMPR
CUT LINK
2−STAGE
COMPRESSOR LINK
(JUMPERS Y1 to Y2)
W915
INDOOR EQUIPMENT
1
C
W1W2GY2
W2
W1
ON−BOARD LINK
OPTION SELECTION
A/C UNIT
W951
HEAT PUMP
DO NOT CUT
HEAT PUMP UNIT
W951
HEAT PUMP
CUT LINK
HEAT PUMP LINK
(JUMPERS R to O)
W951
G
Y2
1
ON
ON
+ 10%
ON
− 10%
L1
DIAGNOSTIC
LED
SureLight
Y1 C C DH L O DSR
C
C
Y1
1
2
3
4
5
6
7
1
2
3
4
5
6
7
1
2
3
4
5
6
7
HSI/CAI
1
J3
®
R
NO HARMONY ZONING
NO SIGNATURESTAT W/ DS CONNECTION
5
N
IGN
CAI1
CAI2
P79
14
3
110
4 7
3
12
CUT FOR
OPTION
SELECTION
W915
2 STAGE
COMPR
W951 HEAT
PUMP
W914
DEHUM
HARMONY
L
DH
OR
DO NOT CUT
W914
DEHUM
or
HARMONY
HARMONY ZONING
OR
SIGNATURESTAT W/
DS CONNECTION
CUT LINK
1
W914
DEHUM
or
HARMONY
DEHUMIDIFICATION−
HARMONY LINK
(JUMPERS R to DS)
W914
8
8
8
N
NEUTRALS
6
J2
CONTINUOUS FAN MODE BLOWER SPEED
MEDIUM−LOW
*
SPEED (38%)
MEDIUM−HIGH
SPEED
(70%)
LOW
SPEED
(28%)
HIGH SPEED (100%)
9
11
13
10
12
ON
9
ON
9
ON
9
ON
14
11
10
12
14
11
10
12
14
11
10
12
14
COOLING MODE BLOWER SPEED
1
2
3
4
5
*
HIGH
SPEED
MEDIUM−HIGH
SPEED
MEDIUM−LOW
SPEED
LOW
SPEED
COOLING MODE BLOWER RAMPING
*
OPTION A
OFF−50%−82%−
100%−50%−OFF
OPTION B
OFF−82%−100%−OFF
OPTION C
OFF−100%−100%−OFF
OPTION D
OFF−100%−OFF
−CUT ON−BOARD LINK (SOLDER TRACE) COMPLETELY THROUGH
1
BOTH LAYERS ON THE CONTROL BOARD
−LINKS CUT IN ERROR −INSTALL A JUMPER ON THE APPROPRIATE
TERMINALS ON THE TERMINAL STRIP
−PROTECTIVE PLASTIC FILM ON DIP SWITCHES MAY BE
REMOVED FOR EASE IN SETTING OF DIP SW.
ON
1
ON
1
ON
1
ON
9
ON
9
ON
9
ON
9
ON
* FACTORY DEFAULT
6
7
2
3
4
5
6
7
2
3
4
5
6
7
2
3
4
5
6
7
11
13
10
12
14
11
13
10
12
14
11
13
10
12
14
11
13
10
12
14
15
15
15
15
8
8
8
8
15
15
15
15
FIGURE 5
Page 7
Page 8
TABLE 4
Integrated Control Diagnostic Modes
Dispaly Action (when button released)
No change (idle)* Remain in idle mode
Solid “E” Enter diagnostic recall mode
Solid “D” Discharge Air Installed
Solid “F” Enter fl ame signal mode
Solid “P” (variable speed only) Program unit capacity/size (Unit Code)
Two horizontal bars = Soft disable
* No change implies the display will continue to show whatever is currently being displayed for normal operation (blinking decimal, active error code, heat state, etc..)
Diagnostic LED (Figure 5)
The seven-segment diagnostic LED displays operating status, target airfl ow, error codes and other information. The table beginning on Page 9 lists diagnostic LED codes.
Diagnostic Push Button (Figure 5)
The diagnostic push button is located adjacent to the sev­en-segment diagnostic LED. This button is used to enable the Error Code Recall “E” mode and the Flame Signal “F” mode. Press the button and hold it to cycle through a menu of options. Every fi ve seconds a new menu item will be displayed. When the button is released, the displayed item will be selected. Once all items in the menu have been displayed, the menu resumes from the beginning until the button is released.
Error Code Recall Mode
Select ”E” from the menu to access the most recent 10 error codes. Select “c” from the Error Code Recall menu to clear all error codes. Button must be pressed a second time while “c” is fl ashing to confi rm command to delete codes. Press the button until a solid “” is displayed to exit the Error Code Recall mode.
Flame Signal Mode
Select ”F” from the menu to access the fl ame signal mode. The integrated control will display the fl ame current on 7 segment LED in in micro amps (uA).
Flame signal mode is exited after any of the follow­ing: Power is reset
Pressing and holding push button until 3 horizontal lines “” are displayed
10 minutes after entering the fl ame sense mode.
Program Unit Capacity/Size Mode
After the “P” is selected (by releasing the push button) the integrated control will start fl ashing the “P” on display for 90 seconds. If push button is pressed again and held during that time, the control will start to display characters corresponding to different variable speed furnace models for 3 seconds each. While the wanted character-model is displayed push button has to be released. Selected option will fl ash display for 10 seconds and during that time push button has to be pressed and held for 5 seconds. Once control accepts new setting it will store data in non-volatile memory and reset itself. If 10 seconds expires or push button is held less than 5 seconds, control will exit fi eld test mode and go into idle without changing programming the unit size.
Soft Disable
Soft disabling is when thermostat fi nds a device on the BUS that it does not recognize and the thermostat sends a the device a message to be in soft disabling mode until properly confi gured. Two horizontal bars will display.
Steps to follow if the damper control module is displaying the soft disable code.
1 - Confi rm proper wiring between all devices
(thermostat, damper control module, indoor and outdoor).
2 - Cycle power to the control that is displaying the soft
disable code.
3 - Put the room thermostat through set up.
4 - Go to setup / system devices / thermostat / edit
/ then push reset.
5 - Go to setup / system devices / thermostat / edit /
then push resetAll.
Page 8
Page 9
TABLE 5
Integrated Diagnostic Codes/Status of Equipment
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
. Idle mode (Decimal blinks at 1 Hertz -- 0.5
second ON, 0.5 second OFF).
A Cubic feet per minute (cfm) setting for
indoor blower (1 second ON, 0.5 second OFF) / cfm setting for current mode displayed.
C Cooling stage (1 second ON, 0.5 second
OFF) / 1 or 2 displayed / Pause / cfm setting displayed / Pause / Repeat codes).
d Dehumidifi cation mode (1 second ON) /
1 second OFF) / cfm setting displayed / Pause / Repeat Codes).
h Heat pump stage (1 second ON, 0.5
second OFF) / % of input rate displayed / Pause / cfm setting / Pause / Repeat codes.
H Gas Heat Stage (1 second ON, 0.5 second
OFF) / 1 or 2 displayed / Pause / cfm setting displayed / Pause / Repeat codes. Blinking during ignition.
dF Defrost mode.
U Discharge Air Temperature
E105 Device communication problem - No other
devices on RS BUS (Communication system).
E110 Low line voltage. Line Voltage Low (Voltage lower than nameplate rating). Check power line
E111 Low line voltage. Reverse line power voltage wiring. System resumes normal operation 5
E112 Ground not detected System shuts down. Provide proper earth ground. System resumes normal
E113 High line voltage. Line Voltage High (Voltage higher than nameplate rating). Provide power
E114 Line voltage frequency out-of-range. No 60 Hertz Power. Check voltage and line power frequency. Correct
E115 Low 24V - Control will restart if the error
recovers.
E116 High 24V. 24 Volt Power High (Range is 18 to 30 volts). Check and correct voltage.
E117 Poor ground detected (Warning only) Provide proper grounding for unit. Check for proper earth ground to the
E120 Unresponsive device. Communication
only.
Equipment is unable to communicate. Indicates numerous message errors. In most cases errors are related to electrical noise. Make sure high voltage power is separated from RSBus. Check for miswired and/or loose connections between the stat, indoor unit and outdoor unit. Check for a high voltage source of noise close to the system. Fault clears after communication is restored.
voltage and correct. Alarm clears 5 seconds after fault recovered.
seconds after fault recovered.
operation 5 seconds after fault recovered.
voltage within proper range. System resumes normal operation 5 seconds after fault recovered.
voltage and frequency problems. System resumes normal operation 5 seconds after fault recovered.
24-Volt Power Low (Range is 18 to 30 volts). Check and correct voltage. Check for additional power-robbing equipment connected to system. May require installation of larger VA transformer to be installed in furnace / air handler. Clears after fault recovered.
Check for proper line voltage (120V, 240V, etc.) to equipment. Clears when control senses proper voltage.
system. Warning only will clear 30 seconds after fault recovered.
Usually caused by delay in outdoor unit responding to indoor unit poling. Recycle power. Check all wiring connections. Cleared after unresponsive device responds to any inquiry.
Page 9
Page 10
TABLE 5 Continued
Code
E124 Active communicating thermostat signal
Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
Equipment lost communication with the thermostat. Check
missing for more than 3 minutes.
four wiring connections, ohm wires and cycle power at the thermostat. Alert stops all services and waits for heartbeat message from thermostat (subnet controller). Cleared after valid thermostat (subnet controller) message is received.
E125 Control failed self-check, internal error,
failed hardware. Will restart if error recov­ers. Integrated control not communicating.
Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Criti-
cal alert. Cleared 300 seconds after fault recovered. Covers hardware errors (fl ame sense cir- cuit faults, pin shorts, etc.).
E126 Control internal communication problem. Hardware problem on the control. Cycle power on con-
trol. Replace if problem prevents service and is persistent.
Cleared 300 seconds after fault recovered.
E131 Corrupted control parameters (Verify con-
guration of system). Communicating only.
Reconfi gure the system. Replace control if heating or cool-
ing is not available. Only applicable in the communicating
mode, not in startup. Exit from Commissioning and Execute
‘Set Factory Default mode Control will still operate on default
parameter settings
E180 Outdoor air temperature sensor failure.
Only shown if shorted or out-ofrange.
Compare outdoor sensor resistance to temperature/ resis-
tance charts in unit installation instructions. Replace sensor
pack if necessary. At beginning of (any) confi guration, furnace
or air handler control will sense outdoor air and discharge
air temperature sensor(s). If detected (reading in range),
appropriate feature will be set as ‘installed’ and that could
be seen in ‘About’ screen. In normal operation after control
recognizes sensors, alarm will be sent if valid temperature
reading is lost. To get rid of setting and alarm, redo confi gu-
ration and make sure that temperature sensor is marked as
‘not installed’ in Indoor Unit ‘About’ screen. When Indoor unit
control is replaced, thermostat will ‘tell’ new control if tem-
perature sensor is in system or not. Clears 30 seconds after
fault recovered.
E200 Hard lockout - Rollout circuit open or pre-
viously open.
E201 Indoor blower communication failure - Un-
able to communicate with blower motor.
Correct cause of rollout trip, or replace fl ame rollout switch.
Test furnace operation. Cleared after fault recovered.
Indoor blower communication failure (including power out-
age). Lost communication with indoor blower motor. Possible
causes: motor not powered, loose wiring. Problem may be
on control or motor side. Cleared after fault recovered.
E202 Indoor blower motor mis-match - Indoor
motor horsepower does not match unit ca­pacity.
Incorrect appliance capacity code selected. Check for proper
confi guring under: Unit Size Codes for Furnace/Air Handler
on confi guration guide or in installation instructions. Cleared
after the correct match is detected following a reset. (Re-
move thermostat from system while applying power and re-
programming.)
E203 Appliance capacity / size is NOT pro-
grammed. Invalid unit codes refer to con­ guration fl ow chart.
No appliance capacity code selected. Check for proper con-
guring under: Unit Size Codes for Furnace on confi guration
guide or in installation instructions. Critical Alert. Cleared af-
ter valid unit code is read following a reset. (Remove thermo-
stat from system while applying power and reprogramming.)
E204 Gas valve mis-wired. Check gas valve operation and wiring. Clears when repaired.
E205 Gas valve control relay contact shorted. Check wiring on control and gas valve. If wiring is correct,
replace control.
Page 10
Page 11
TABLE 5 Continued
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E206 Gas valve second-stage relay failure Furnace will operate on 1st stage for remainder of the
heating demand. Will clear after fault recovered. If un­able to operate 2nd stage, replace control.
E207 Hot surface ignitor sensed open. Measure resistance of hot surface ignitor. Replace if
open or not within specifi ed range found in IOM. Re- sumes normal operation after fault is cleared.
E223 Low pressure switch failed open. Check pressure (inches w.c.) of low pressure switch
closing on heat call. Measure operating pressure (inch­es w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal op­eration after fault is cleared
E224 Low pressure switch failed closed. Check operation of low pressure switch to see if it is
stuck closed on heat call longer than 150 seconds. Mea­sure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restric­tion. Resumes normal operation after fault is cleared.
E225 High pressure switch failed open. Check pressure (inches w.c.) of high pressure switch
closing on heat call. Measure operating pressure (inch­es w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal op­eration after fault is cleared.
E226 High pressure switch failed closed Check operation of high pressure switch closing on heat
call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.
E227 Low pressure switch open during trial for ignition
or run mode.
E228 Combustion air inducer calibration failure Unable to perform pressure switch calibration. Check
E229 Ignition on high fi re IFC switched to high fi re ignition because low fi re pres-
E240 Low fl ame current - Run mode. Check micro-amperes of fl ame sensor using control
E241 Flame sensed out of sequence - Flame still pres-
ent.
E250 Limit switch circuit open. Check for proper fi ring rate on furnace. Ensure there is
E252 Discharge air temperature too high (gas heat only). Check temperature rise, air fl ow and input rate. Cleared
E270 Soft lockout - Exceeded maximum number of re-
tries. No fl ame current sensed.
Check pressure (inches w.c.) of low pressure switch closing on heat call. Measure operating pressure (inch­es w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal op­eration after fault is cleared.
vent system and pressure switch wiring connections. Resumes normal operation after fault is cleared.
sure switch did not close in allowed time. No action is needed.
diagnostics or fi eld-installed mode. Clean or replace sensor. Measure voltage of neutral to ground to ensure good unit ground. Alert clears after current heat call has been completed.
Shut off gas. Check for gas valve leak. Replace, if nec­essary. Alert clears when fault is recovered.
no blockage in heater. Check for proper air fl ow. If limit not closed within 3 minutes, unit will go into 1-hour soft lockout. Resumes normal operation after fault is cleared.
when heat call is fi nished.
Check for proper gas fl ow. Ensure that ignitor is lighting burner. Check fl ame sensor current. Clears when heat call fi nishes successfully.
Page 11
Page 12
TABLE 5 Continued
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E271 Soft lockout - Exceeded maximum number of re-
tries. Last retry failed due to the pressure switch opening.
E272 Soft lockout - Exceeded maximum number of re-
cycles. Last recycle due to the pressure switch opening.
E273 Soft lockout - Exceeded maximum number of re-
cycles. Last recycle due to fl ame failure.
E274 Soft lockout - Exceeded maximum number of re-
cycles. Last recycle failed due to the limit circuit opening or limit remained open longer than 3 min­utes
E275 Soft lockout - Flame sensed out of sequence.
Flame signal is gone.
E276 Watchguard calibration failure. Unable to perform pressure switch calibration. Check vent
E290 Ignitor circuit fault - Failed ignitor or triggering cir-
cuitry.
E291 Heat air fl ow restricted below the minimum. Check for dirty fi lter and air fl ow restriction. Check blower
E292 Indoor blower motor unable to start due to ob-
structed wheel, seized bearings.
E294 Combustion air inducer over current. Check combustion blower bearings, wiring and amps. Re-
E295 Indoor blower motor temperature is too high. Indoor blower motor over temperature (motor tripped on
E310 Discharge error temperature sensor failure. Only
shown if shorted or out of range.
E311 Heat rate reduced to match indoor blower air fl ow. Warning Only. Furnace blower in cutback mode due to
Check pressure (inches w.c.) of low pressure switch clos­ing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct oper­ation and restriction. Clears when heat call fi nishes suc- cessfully.
Check operation of low pressure switch to see if it is stuck closed on heat call. Check pressure (inches w.c.) of high pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Clears when heat call fi nishes successfully.
Check micro-amperes of fl ame sensor using control diag- nostics or fi eld-installed mode. Clean or replace sensor. Measure voltage of neutral to ground to ensure good unit ground. Clears when heat call fi nishes successfully.
Shut down system. 1-hour soft lockout. Check fi ring rate and air fl ow. Check for blockage. Clears when heat call nishes successfully.
Shut off gas. Check for gas valve leak. 1-hour soft lockout. Clears when fl ame has been proven stable.
system and pressure switch wiring connections. 1-hour soft lockout. Clears when calibration has fi nished successfully.
Measure resistance of hot surface ignitor. Replace if open or not within specifi cations. 1-hour soft lockout. Clears when fl ame has been proven stable.
performance. 1-hour soft lockout. Cleared when heat call nishes successfully.
Indoor blower motor unable to start (seized bearing, stuck wheel, etc.). Replace motor or wheel if assembly does not operate or meet performance standards. 1-hour soft lock­out. Clears after circulator successfully starts.
place if does not operate or does not meet performance standards. Clears after inducer current is sensed to be in­range after the ignition following the soft lockout or reset.
internal protector). Check motor bearings and amps. Re­place if necessary. Cleared after blower demand is satis­ ed.
Compare outdoor sensor resistance to temperature/ re­sistance charts in installation instructions. Replace sensor if necessary. Cleared in Communicating mode: 30 sec­onds after fault recovered. In Non- Communicating mode: Cleared after the current heat call is completed.
restricted airfl ow. Reduce fi ring rate every 60 seconds to match available CFM. Check fi lter and duct system. To clear, replace fi lter if needed or repair/ add duct. 2-stage controls will reduce fi ring rate to 1st stage. Clears when heat call fi nishes successfully.
Page 12
Page 13
TABLE 5 Continued
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E312 Restricted air fl ow in cooling or continu-
ous fan mode is lower than cfm setting.
E313 Indoor or outdoor unit capacity mismatch.
Communication only.
E331 Global network connection - Communica-
tion link problem.
E334 Relay “Y1” stuck on interated control. Replace integrated control.
E347 No 24 Volt output on Y1 of ”integrated
control” with non communicating outdoor unit.
E348 No 24 Volt output on Y2 of ”integrated
control” with non?communicating outdoor unit.
E349 No 24 Volts between R & O on ”integrated
control” with non communicating outdoor unit (Dual fuel module required for heat pump application
E370 Interlock switch sensed open for 2 min-
utes.
E400 LSOM - Compressor internal overload
tripped.
E401 LSOM Compressor long run cycle or low
system pressure.
E402 LSOM - Outdoor unit system pressure
trip.
E403 LSOM - Compressor short-cycling. .(Run-
ning less than 4 minutes). Outdoor unit pressure trip
E404 LSOM - Compressor rotor locked. Com-
pressor short-cycling. (Running less than 4 minutes).
E405 LSOM - Compressor open circuit. Compressor circuit open (due to power disconnection, open fuse,
Warning Only. Restricted airfl ow - Indoor blower is running at a re- duced CFM (Cutback Mode - The variable speed motor has pre-set speed and torque limiters to protect the motor from damage caused by operating outside of design parameters (0 to 0.8” W.C.. total ex­ternal static pressure). Check fi lter and duct system. To clear, re- place fi lter if needed or repair/add duct. Cleared after the current service demand is satisfi ed.
Incorrect indoor/outdoor capacity code selected. Check for proper confi guring in installation instructions. Alarm is just a warning. The system will operate, but might not meet effi ciency and capacity pa- rameters. Alarm will clear when commissioning is exited. Cleared after commissioning is complete.
For Future Use.
Operation stopped. Y1 relay / Stage 1 failed. (Pilot relay contacts did not close or the relay coil did not energize; no input back to IFC chip). Critical Alert. Cleared after reset and Y1 input sensed.
Y2 relay / Stage 2 failed. (Pilot relay contacts did not close or the relay coil did not energize; no input back to IFC chip). Critical Alert. Cleared after reset and Y1 input sensed.
Confi guration link R to O needs to be restored. Replace link or hard- wire. Applicable in non communicating mode. Critical Alert.
Control sees the loss of 24VAC for 2 minutes.Terminate all services and wait for interlock switch to close. The alarm will clear when 24VAC is continuously sensed on DS terminal for a minimum of 10 seconds or on a power reset.
Thermostat demand Y1 is present; but, compressor is not running. Check power to outdoor unit. Clears the error after current is sensed in both RUN and START sensors for at least 2 seconds, or after service is removed, or after power reset.
Compressor ran more than 18 hours to satisfy a single thermostat demand. Critical Alert. Clears the error after 30 consecutive normal run cycles or power reset. Also monitors low pressure switch trips.
Discharge or suction pressure out-of-limits, or compressor over­loaded. Clears the error after 4 consecutive normal compressor run cycles.
Compressor runs less than 3 minutes to satisfy a thermostat de­mand. Clears the error after 4 consecutive normal run cycles or power reset.
Compressor rotor locked up due to run capacitor short, bearings are seized, excessive liquid refrigerant, etc. Clears the error after 4 consecutive normal run cycles or after power reset.
etc.) Clears the error after 1 normalcompressor run cycle.
Page 13
Page 14
TABLE 5 Continued
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E406 LSOM - Compressor open start circuit. Required amount of current is not passing through Start cur-
rent transformer. Clears the error after current is sensed in START sensor, or after power reset.
E407 LSOM - Compressor open run circuit. Required amount of current is not passing through Run current
transformer. Clears the error after current is sensed in RUN sensor, or 1 normal compressor run cycle, or after power reset.
E408 LSOM - Compressor contactor is welded. Compressor runs continuously. Clears the error after 1 normal
compressor run cycle or after power reset.
E409 LSOM - Compressor low voltage. Secondary voltage is below 18VAC. After 10 minutes, oper-
ation is discontinued. Clears the code after voltage is higher than 20 VAC for 2 seconds or after power reset.
DIP Switch Settings
NOTE - All icomfort settings are set at the icomfort Wi-Fi
®
thermostat. See icomfort installation instruction. In icom­fort communication system all DIP switch and clippable link settings are ignored. For conventional thermostats proceed with DIP switch and clippable link settings as out­lined in the following.
Heating Operation DIP Switch Settings Switch 1 -- Thermostat Selection -- This unit may be
used with either a single-stage or two-stage thermostat. The thermostat selection is made using a DIP switch which must be properly positioned for the particular appli­cation. The DIP switch is factory-positioned for use with a twostage thermostat. If a single-stage thermostat is to be used, the DIP switch must be repositioned.
a. Select “OFF” for two-stage heating operation controlled by a
two-stage heating thermostat (factory setting);
b. Select “ON” for two-stage heating operation controlled by
a single-stage heating thermostat. This setting provides a timed delay before second-stage heat is initiated.
Switch 2 -- Second Stage Delay (Used with Single­Stage Thermostat Only) -- This switch is used to deter-
mine the second stage on delay when a single-stage ther­mostat is being used. The switch is factory-set in the OFF position, which provides a 7-minute delay before second­stage heat is initiated. If the switch is toggled to the ON position, it will provide a 12-minute delay before second­stage heat is initiated. This switch is only activated when the thermostat selector jumper is positioned for SINGLE­stage thermostat use.
Switches 3 and 4 -- Blower-Off Delay -- The blower-on
delay of 30 seconds is not adjustable. The blower-off de­lay (time that the blower operates after the heating de­mand has been satisfi ed) can be adjusted by moving switches 3 and 4 on the integrated control. The unit is shipped from the factory with a blower-off delay of 90 sec­onds. The blower off delay affects comfort and is adjust­able to atisfy individual applicationsAdjust the blower off delay to achieve a supply air temperature between 90° and 110°F at the exact moment that the blower is de-en­ergized. Longer off delay settings provide lower supply air temperatures; shorter settings provide higher supply air temperatures. Table 6 provides the blower off timings that will result from different switch settings.
TABLE 6
Blower Off Delay Switch Settings
Blower Off Delay
Seconds
60 On Off
90 (factory) Off Off
120 Off On
180 On On
Switch 3 Switch 4
Indoor Blower Operation DIP Switch Settings Switches 5 and 6 -- Cooling Mode Blower Speed -- The
unit is shipped from the factory with the dip switches po­sitioned for high speed (4) indoor blower motor operation during the cooling mode. Table 7 provides the cooling mode blower speeds that will result from different switch settings. Switches 5 and 6 set the blower cfm for second­stage cool. The integrated control automatically ramps down to 70% of the second-stage cfm for fi rst-stage cfm. Refer to tables for corresponding cfm values.
TABLE 7
Cooling Mode Blower Speeds
Speed Switch 5 Switch 6
Low On On
Medium Low Off On
Medium High On Off
High (factory) Off Off
. Switches 7 and 8 -- Cooling Blower Speed Adjust-
ment
-- The unit is shipped from the factory with the dip switches positioned for NORMAL (no) adjustment. The dip switches may be positioned to adjust the blower speed by +10% or
-10% to better suit the application. Table 8 below provides blower speed adjustments that will result from different switch settings. Refer to tables for corresponding cfm val­ues.
Page 14
Page 15
TABLE 8
Cooling Blower Speed Adjustment
Adjustment Switch 7 Switch 8
+10% (approx) On Off
Factory Default Off Off
-10% (approx) Off Off
Ramping Option C
• Motor runs at 100% until demand is satisfi ed.
• Once demand is met, motor runs at 100% for 45 sec-
onds then ramps down to stop.
OFF
100% CFM
COMPRESSOR
DEMAND
100% CFM
45 SEC.
OFF
Switches 9 and 10 -- Cooling Mode Blower Speed Ramping -- Blower speed ramping may be used to en-
hance dehumidifi cation performance. The switches are factory set at option A which has the greatest effect on de­humidifi cation performance. Table 9 provides the cooling mode blower speed ramping options that will result from different switch settings. The cooling mode blower speed ramping options are detailed below.
TABLE 9
Cooling Mode Blower Speed Ramping
Ramping Switch 9 Switch 10
A (Factory) Off Off
BOffOn
COnOff
DOnOn
Ramping Option A (Factory Selection)
Motor runs at 50% for 30 seconds.
• Motor then runs at 82% for approximately 7-1/2 min­utes.
• If demand has not been satisfi ed after 7-1/2 minutes, motor runs at 100% until demand is satisfi ed.
• Once demand is met, motor runs at 50% for 30 sec­onds then ramps down to stop.
OFF
1/2 MIN 50% CFM
7 1/2 MIN 82% CFM
COMPRESSOR DEMAND
100% CFM
1/2 MIN 50% CFM
OFF
Ramping Option D
Motor runs at 100% until demand is satisfi ed.
• Once demand is met, motor ramps down to stop.
100% CFM
COMPRESSOR
DEMAND
OFFOFF
Switches 11, 12 and 13 -- Heating Mode Blower Speed
The switches are factory set to the OFF position which provides factory default heat speed. Refer to Table 10 for switches 11, 12 and 13 that provided the corresponding increases or decrease to both high and low heat demand.
TABLE 10
Heating Mode Blower Speeds
Heat Speed Switch 11 Switch 12 Switch 13
Increase 24% On On On
Increase 18% On On Off
Increase 12% On Off On
Increae 6% On Off Off
Factory
Off Off Off
Default
Decrease 6% Off Off On
Decrease
Off On Off
12%
Decrease
Off On On
18%
Switches 14 and 15 -- Continuous Blower Speed --
Table 11 provides continuous blower speed adjustments that will result from different switch settings.
Ramping Option B
Motor runs at 82% for approximately 7-1/2 minutes. If
demand has not been satisfi ed after 7-1/2 minutes,mo- tor runs at 100% until demand is satisfi ed.
• Once demand is met, motor ramps down to stop.
OFF
7 1/2 MIN
82%CFM
COMPRESSOR DEMAND
100% CFM
OFF
Page 15
TABLE 11
Continuous Blower Speed
Coninuous Blower Speed Switch 14 Switch 15
28% of High Cool Speed Off On
38% of High Cool Speed
(Factory)
70% of High Cool Speed On Off
100% of High Cool Speed On On
Off Off
Page 16
BLOWER DATA
SL280UH060NV36A BLOWER PERFORMANCE (less fi lter) BOTTOM RETURN AIR 0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
+24% 1030 1140
+18% 965 1075
+12% 925 1020
+6% 870 965
Factory Default 825 915
–6% 775 865
–12% 735 810
–18% 685 760
1
Cooling Speed
DIP Switch
Settings
Low Medium-Low Medium-High
+ 595 715 815 920 845 1015 1175 1340
Factory Default 565 680 735 840 790 945 1070 1215
510 610 695 780 715 845 980 1120
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
COOLING
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
2
High Low Medium-Low Medium-High
2
High
SL280UH060NV36A BLOWER PERFORMANCE (less fi lter) SINGLE SIDE RETURN AIR 0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
Settings
+24% 985 1100
+18% 950 1050
+12% 875 1000
+6% 850 935
Factory Default 800 890
–6% 750 840
–12% 700 790
–18% 680 740
COOLING
1
Cooling Speed
DIP Switch
Settings
Low Medium-Low Medium-High
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
2
High Low Medium-Low Medium-High
2
High
+ 575 700 800 890 835 990 1145 1300
Factory Default 535 630 745 825 760 890 1020 1185
475 580 645 750 690 820 950 1055
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specifi c DIP Switch Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 250 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 250 cfm.
Page 16
Page 17
BLOWER DATA
SL280UH080NV48B BLOWER PERFORMANCE (less fi lter) BOTTOM RETURN AIR 0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
+24% 1350 1500
+18% 1270 1420
+12% 1200 1340
+6% 1130 1270
Factory Default 1060 1190
–6% 970 1130
–12% 880 1025
–18% 845 950
1
Cooling Speed
DIP Switch
Settings
Low Medium-Low Medium-High
+ 640 870 1030 1200 1020 1310 1535 1750
Factory Default 590 770 925 1100 935 1200 1400 1600
545 635 750 960 815 1080 1260 1430
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
COOLING
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
2
High Low Medium-Low Medium-High
2
High
SL280UH080NV48B BLOWER PERFORMANCE (less fi lter) SINGLE SIDE RETURN AIR 0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
Settings
+24% 1245 1385
+18% 1180 1320
+12% 1130 1245
+6% 1045 1185
Factory Default 1095 1120
–6% 1020 1050
–12% 825 975
–18% 840 865
COOLING
1
Cooling Speed
DIP Switch
Settings
Low Medium-Low Medium-High
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
2
High Low Medium-Low Medium-High
2
High
+ 600 810 995 1165 995 1265 1490 1680
Factory Default 560 705 855 1050 905 1140 1350 1525
540 585 750 910 735 1010 1200 1365
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specifi c DIP Switch Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 380 cfm. Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 380 cfm.
Page 17
Page 18
BLOWER DATA
SL280UH080NV48B BLOWER PERFORMANCE (less fi lter) SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE 0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
+24% 1300 1445
+18% 1230 1355
+12% 1145 1300
+6% 1215 1225
Factory Default 1015 1150
–6% 1050 1070
–12% 860 1000
–18% 750 935
1
Cooling Speed
DIP Switch
Settings
Low Medium-Low Medium-High
+ 625 835 1000 1190 1000 1280 1500 1715
Factory Default 590 760 910 1070 910 1180 1360 1560
540 655 800 940 760 1040 1230 1380
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
COOLING
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
2
High Low Medium-Low Medium-High
2
High
SL280UH080NV60C BLOWER PERFORMANCE (less fi lter) BOTTOM RETURN AIR, RETURN AIR FROM BOTH SIDES OR RETURN AIR FROM BOTTOM AND ONE SIDE 0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
Settings
+24% 1375 1530
+18% 1330 1450
+12% 1260 1390
+6% 1185 1315
Factory Default 1130 1235
–6% 1050 1165
–12% 980 1090
–18% 940 1020
COOLING
1
Cooling Speed
DIP Switch
Settings
Low Medium-Low Medium-High
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
2
High Low Medium-Low Medium-High
+ 1080 1235 1410 1655 1540 1745 2000 2300
Factory Default 975 1125 1290 1500 1390 1595 1815 2130
880 1010 1165 1360 1265 1440 1630 1930
2
High
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specifi c DIP Switch Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 380 cfm. Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 380 cfm for 08048B and 450cfm for 08060C
Page 18
Page 19
BLOWER DATA
SL280UH080NV60C BLOWER PERFORMANCE (less fi lter)
Single Side Return Air - Air volumes in bold require Optional Return Air base and fi eld fabricated transition to accommodate 20 x
25 x 1 in. air fi lter in order to maintain proper air velocity. 0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
+24% 1350 1485
+18% 1280 1420
+12% 1220 1345
+6% 1155 1270
Factory Default 1100 1200
–6% 1020 1135
–12% 965 1070
–18% 870 980
1
Cooling Speed
DIP Switch
Settings
Low Medium-Low Medium-High
+ 1050 1180 1350 1570 1500 1700 1915 2240
Factory Default 960 1080 1225 1420 1370 1540 1760 2035
845 950 1110 1290 1235 1390 1570 1840
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
COOLING
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
2
High Low Medium-Low Medium-High
2
High
Page 19
Page 20
BLOWER DATA
SL280UH100NV60C BLOWER PERFORMANCE (less fi lter) BOTTOM RETURN AIR, RETURN AIR FROM BOTH SIDES OR RETURN AIR FROM BOTTOM AND ONE SIDE 0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
+24% 1745 1930
+18% 1670 1825
+12% 1580 1740
+6% 1500 1655
Factory Default 1425 1565
–6% 1310 1470
–12% 1260 1390
–18% 1190 1300
1
Cooling Speed
DIP Switch
Settings
Low Medium-Low Medium-High
+ 1200 1250 1380 1585 1710 1790 1950 2270
Factory Default 1075 1150 1275 1460 1570 1610 1785 2065
1010 1050 1150 1320 1410 1480 1625 1880
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
COOLING
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
2
High Low Medium-Low Medium-High
2
High
SL280UH100NV60C BLOWER PERFORMANCE (less fi lter)
Single Side Return Air - Air volumes in bold require Optional Return Air base and fi eld fabricated transition to accommodate 20 x
25 x 1 in. air fi lter in order to maintain proper air velocity. 0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
Settings
+24% 1600 1785
+18% 1530 1685
+12% 1440 1600
+6% 1370 1515
Factory Default 1290 1415
–6% 1260 1390
–12% 1175 1290
–18% 1065 1190
COOLING
1
Cooling Speed
DIP Switch
Settings
Low Medium-Low Medium-High
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
2
High Low Medium-Low Medium-High
2
High
+ 1140 1180 1300 1480 1615 1695 1865 2160
Factory Default 1040 1060 1190 1365 1460 1530 1690 1960
930 970 1070 1240 1325 1380 1520 1760
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specifi c DIP Switch Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 450 cfm. Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 450 cfm.
Page 20
Page 21
On-Board Links
Note: In icomfort systems with a conventional outdoor unit (non-communicating), the on-board clippable links must be set to properly confi gure the system.
damage. Refer to Table 12 for operation sequence in ap­plications including SL280UHNV, a thermostat which fea­tures humidity control and a single-speed outdoor unit. Ta­ble 13 gives the operation sequence in applications with a two-speed outdoor unit.
WARNING
Carefully review all confi guration information provided. Failure to properly set DIP switches, jumpers and on­board links can result in improper operation!
On-Board Link W914 Dehum or Harmony (R to DS)
On-board link W914, is a clippable connection between terminals R and DS on the integrated control. W914 must be cut when the furnace is installed with either the Harmo­ny III zone control or a thermostat which features humidity control. If the link is left intact the PMW signal from the Harmony III control will be blocked and also lead to control
On-Board Link W951 Heat Pump (R to O)
On-board link W951 is a clippable connection between terminals R and O on the integrated control. W951 must be cut when the furnace is installed in applications which include a heat pump unit and a thermostat which features dual fuel use. If the link is left intact, terminal “O” will re­main energized eliminating the HEAT MODE in the heat pump.
On-Board Link W915 2 Stage Compr (Y1 to Y2)
On-board link W915 is a clippable connection between terminals Y1 and Y2 on the integrated control. W915 must be cut if two-stage cooling will be used. If the Y1 to Y2 link is not cut the outdoor unit will operate in second-stage cooling only.
TABLE 12
OPERATING SEQUENCE
SL280UHV, Non-Communicating Thermostat with Humidity Control Feature and Single-Speed Outdoor Unit
OPERATING SEQUENCE SYSTEM DEMAND SYSTEM RESPONSE
System
Condition
NO CALL FOR DEHUMIDIFICATION
Normal Operation 1 On On On Acceptable
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation 1 On On On Acceptable
Dehumidifi cation
call
PRECISION MODE (operates independent of a Y1 demand)
Normal Operation 1 On On On Acceptable
Dehumidifi cation
Call
Dehumidifi cation
Call Only
Dave Lennox ComfortSense® 7500 thermostat to use for this application - Y2081 4 heat / 2 cool *Dehumidifi cation blower speed is 70% of COOL speed for all units . **In Precision mode, ComfortSense® 7000 thermostat will maintain room temperature up to 2 °F (1.2°C) cooler than room setting.
Step
2 On On On Demand 0 VAC High 70%*
2 On On On Demand 0 VAC High 70%*
1 On On On Demand 0 VAC High 70%*
Jumpers at indoor unit with a single stage outdoor unit. With Condensing unit - Cut W914 (R to DS) on SureLight® control With Heat Pump - Cut W914 (R to DS) & W951 (R to O) on SureLight® control
Thermostat Demand Relative Humidity
Y1 O G W1 Status D
24
VAC
24
VAC
24
VAC
Compre
ssor
High 100%
High 100%
High 100%
Blower
CFM
(cool)
Comments
Compressor and indoor blower follow thermostat demand
ComfortSense® 7500
thermostat energizes Y1 and de-energizes
D on a call for de-
humidifi cation
Dehumidifi cation
mode begins when
humidity is greater
than set point
ComfortSense® 7500 thermostat will try to maintain room humidity setpoint by
allowing the room space to maintain
a cooler room
thermostat setpoint**
Page 21
Page 22
TABLE 13
OPERATING SEQUENCE
SL280UHV, Non-Communicating Thermostat with Humidity Control Feature and Two-Speed Outdoor Unit
OPERATING
SEQUENCE
System
Condition
Step
NO CALL FOR DEHUMIDIFICATION
Normal Operation
Y1
Normal Operation
Y2
1 On On On Acceptable
2 On On On On Acceptable
ROOM THERMOSTAT CALLS FOR FIRST STAGE COOLING
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation 1 On On On Acceptable
Dehumidifi cation
call
2 On On On On Demand
PRECISION MODE (operates independent of a Y1 demand)
Normal Operation 1 On On On Acceptable
Dehumidifi cation
Call
Dehumidifi cation
Call Only
2 On On On On Demand
1 On On On On Demand
ROOM THERMOSTAT CALLS FOR FIRST AND SECOND STAGE COOLING
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation 1 On On On On Acceptable
Dehumidifi cation
Call
2 On On On On Demand
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Operation 1 On On On Acceptable
Dehumidifi cation
Call
Dehumidifi cation
Call ONLY
2 On On On On Demand
1 On On On On Demand
Jumpers at indoor unit with a two stage outdoor unit
Cut factory jumper from Y1 to Y2 or cut W915 (Y1 to Y2)
With Condensing unit - Cut W914 (R to DS) on SureLight® control
With Heat Pump - Cut W914 (R to DS) & W951 (R to O) on SureLight® control
Dave Lennox ComfortSense® 7500 thermostat to use for this application - Y2081 4 heat / 2 cool *Normal operation fi rst stage cooling blower speed is 70% COOL speed. **Dehumidifi cation blower speed is, reduced to 70% of COOL. ***In Precision mode, ComfortSense® 7000 thermostat will maintain room temperature up to 2 °F (1.2°C) cooler than room setting.
SYSTEM DEMAND SYSTEM RESPONSE
Thermostat Demand Relative Humidity
Y1 Y2 O G W1 W2 Status D
24
VAC
24
VAC
24
VAC
0
VAC
24
VAC
0
VAC
0
VAC
24
VAC
0
VAC
24
VAC
0
VAC
0
VAC
Compre
ssor
Low 70%*
High 100%
Low 70%*
High 70%**
Low 70%*
High 70%**
High 70%**
High 100%
High 70%**
Low 70%*
High 70%**
High 70%**
Blower
CFM
(cool)
Comments
Compressor and indoor blower follow thermostat demand
ComfortSense® 7500 thermostat energizes Y1 and de-energizes D on a call for de-humidifi cation
Dehumidifi cation mode begins when humidity is greater than set point
ComfortSense® 7500 thermostat will try to maintain room humidity setpoint by allowing the room space to maintain a cooler room thermostat setpoint**
ComfortSense® 7500 thermostat energizes Y2 and de-energizes D on a call for de-humidifi cation
Dehumidifi cation mode begins when humidity is greater than set point
ComfortSense® 7500 thermostat will try to maintain room humidity setpoint by allowing the room space to maintain a cooler room thermostat setpoint***
Page 22
Page 23
B- Indoor Blower Motor
Power Choke
(4 and 5 Ton Only)
To Remove Blower From Unit: Remove access panels,
Control box, Bolts and Wiring Jackplugs.
Blower Motor
(B3)
Then Slide Out Front of Unit.
FIGURE 6
WARNING
During blower operation, the ECM motor emits energy that may interfere with pacemaker operation. Interference is reduced by both the sheet metal cabinet and distance.
During blower operation, the ECM motor emits energy that may interfere with pacemaker operation. Interference is reduced by both the sheet metal cabinet and distance. The motor communicates with the integrated control via a 2-way serial connection. The motor receives all nec­essary functional parameters from the integrated control and does not rely on a factory program like traditional vari­able speed motors. SL280UHNV units use a three-phase, electronically controlled D.C. brushless motor (controller converts single phase a.c. to three phase D.C.), with a permanent-magnettype rotor (Figure 7). Because this mo­tor has a permanent magnet rotor it does not need brush­es like conventional D.C. motors.
The stator windings are split into three poles which are electrically connected to the controller. This arrangement allows motor windings to turn on and off in sequence by the controller.
IMPORTANT
Earlier ECM motors used on other Lennox furnace models are not interchangeable with motors used on the SL280UH furnace line.
A solid-state controller is permanently attached to the mo­tor. The controller is primarily an A.C. to D.C. converter. Converted D.C. power is used to drive the motor. The con­troller contains a microprocessor which monitors varying conditions inside the motor (such as motor workload).
BLOWER MOTOR COMPONENTS
STATOR
(WINDINGS)
BEARING
ROTOR
FIGURE 7
The controller uses sensing devices to sense what posi­tion the rotor is in at any given time. By sensing the posi­tion of the rotor and then switching the motor windings on and off in sequence, the rotor shaft turns the blower.
All SL280UHNV blower motors use single phase power. An external run capacitor is not used. The motor uses per­manently lubricated ball-type bearings.
Internal Operation
The motor is controlled via serial communication between the integrated control on the furnace and the controller attached to the motor shell. The messages sent back and forth between the two controls serve to communicate rota­tional direction, demand, motor size, current draw, torque, and rpm, among other variables.
Motor rpm is continually adjusted internally to maintain constant static pressure against the blower wheel. The controller monitors the static work load on the motor and motor ampdraw to determine the amount of rpm adjust­ment. Blower rpm may be adjusted any amount in order to maintain a constant cfm as shown in Blower Ratings Ta­bles. The cfm remains relatively stable over a broad range of static pressure. Since the blower constantly adjusts rpm to maintain a specifi ed cfm, motor rpm is not rated. Hence, the terms “cool speed”, “heat speed ” or “speed tap” in this manual, on the unit wiring diagram and on blower B3, refer to blower cfm regardless of motor rpm.
Initial Power Up
When line voltage is applied to B3, there will be a large inrush of power lasting less than 1/4 second. This inrush charges a bank of DC fi lter capacitors inside the controller. If the disconnect switch is bounced when the disconnect is closed, the disconnect contacts may become welded. Try not to bounce the disconnect switch when applying power to the unit.
Page 23
Page 24
Motor Start-Up
When B3 begins start-up, the motor gently vibrates back and forth for a moment. This is normal. During this time the electronic controller is determining the exact position of the rotor. Once the motor begins turning, the controller slowly eases the motor up to speed (this is called “soft­start”). The motor may take as long as 10-15 seconds to reach full speed. If the motor does not reach 200 rpm within 13 seconds, the motor shuts down. Then the motor will immediately attempt a restart. The shutdown feature provides protection in case of a frozen bearing or blocked blower wheel. The motor may attempt to start eight times. If the motor does not start after the eighth try, the control­ler locks out. Reset controller by momentarily turning off power to unit.
The DC fi lter capacitors inside the controller are connect- ed electrically to the motor supply wires. The capacitors take approximately 5 minutes to discharge when the dis­connect is opened. For this reason it is necessary to wait at least 5 minutes after turning off power to the unit before attempting to service motor.
DANGER
Disconnect power from unit and wait at least ve minutes to allow capacitors to discharge before attempting to service motor. Failure to wait may cause personal injury or death.
Troubleshooting Motor Operation
To verify motor operation see steps below and Figure 8 and Figure 9.
1 - Remove J48 (5 pin power plug) from P48 on the
motor.
2 - With the power on at the furnace and door switch
depressed, use a test meter to verify 120V between
pins 4 and 5 on J48. 3 - Reconnect J48 to P48 on the motor. 4 - Remove J49 (4 pin low voltage connector) from P49
on the motor. 5 - Using test jumpers, apply 24V to pins 3 and 4 on
P49 on the motor.
Note: Do not apply 24V to pins 2 and 4 on P49. Doing so will cause permanent damage to the motor.
6 - 6- Motor should run at 75%. 7 - Test is complete. Remove jumpers and reconnect
plugs.
Another option is to use the TECMate PRO motor tester with the 16 to 4 pin adaptor. The use of the TECMate PRO isolates the motor from the integrated control. Follow the instructions provided with the kit. If the motor runs do not replace.
Power Choke (L13)
A choke coil is used on SL280UHNV 4 and 5 ton units equipped with 1 hp motors. The choke is located on the blower housing and is used to suppress transient current spikes.
Page 24
Page 25
BLOWER B3 HARNESS CONNECTORS
P48 5 Pin
SHAFT
BLOWER B3 HARNESS CONNECTORS
P48 5 Pin
P49 4 Pin
SHAFT
MOTOR with INTEGRATED
CONTROLLER
J48 5 Pin
J49 4 Pin
J49 4 Pin Control Connector
J48 5 Pin Line Voltage Connector
P49 4 Pin
MOTOR with INTEGRATED
CONTROLLER
P48 5 Pin
P49 4 Pin
1
2
3
4
5
120v
0
J48 Connector
240v
FIGURE 8
J48 Connector
installed on motor
P49 4 Pin
24v Transformer
J49 Connector
FIGURE 9
Page 25
Page 26
Troubleshooting Motor Windings
Ensure that motor windings are not damaged by perform­ing the following tests:
NOTE - If your ohm meter is not an auto-ranging type, set it to the highest ohm scale (100k ohms or greater) before performing tests.
TABLE 14
Ohm Meter Range
Scale Measurement Range
In Words ohms
2M two megohm - two
million ohms
200k two hundred kilohm
- two hundred
thousand ohms
20k twenty kilohm --
twenty thousand
ohms
2k two kilohm -- two
thousand ohms
200 two hundred ohm 0 - 200
0 - 2,000,000
0 - 200,000
0-20,000
0 - 2,000
TEST A
Measure the resistance between each of the three motor leads (3-pin plug) and the unpainted part of the end shield.
If the winding resistance to ground is <100k ohms, re­place the motor and control module. If the resistance to ground is >100k, the motor windings are fi ne. Pro- ceed to Test B.
Test A
FIGURE 11
TEST B
Use an ohmmeter to measure the motor phase-to-phase resistance by checking these combinations of the the 3-pin motor plug. For the purpose of this test, start at either end of the connector as lead 1.
1 - The lead-to-lead resistance across any two leads
should be less than 20 ohms.
2 - Each lead-to-lead resistance should be the same.
If the measured resistance is greater than 20 ohms, re­place the motor and control module.
FIGURE 10
Test B
FIGURE 12
Page 26
Page 27
C- Heating Components
1. Ignitor
The SureLight® ignitor is made of durable silicon nitride. Ignitor longevity is enhanced by controlling voltage to the ignitor. The integrated control provides a regulated 120 volts to the ignitor for a consistent ignition and long ignitor life. Ohm value should be 39 to 70. See Figure 13 for ignit­or location and Figure 14 for ignitor check out.
NOTE - The SL280UHNV furnace contains electronic components that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.
2. Flame Sensor
A fl ame sensor is located on the top of the air gas ple- num. See Figure 13. The sensor can be removed for ser­vice without removing the the burner. During operation, ame is sensed by current passed through the fl ame and sensing electrode. The SureLight control allows the gas valve to remain open as long as fl ame signal is sensed. To check fl ame sense signal use the push-button found on the integrated control and go to Field Test Mode. The menu will display the fl ame signal. See Table 15 for fl ame signal.
TABLE 15
Flame Signal in Microamps
Normal Low Drop Out
2.6 or greater 2.5 or less 1.1
3. Gas Valve
The valve (Figure 16) is internally redundant to assure safety shut-off. If the gas valve must be replaced, the same type valve must be used.
24VAC terminals and gas control knob are located on the valve. A wire harness connects the terminals from the gas valve to the electronic ignition control. 24V applied to the terminals energizes the valve. Inlet and outlet pressure taps are located on the valve. A regulator adjustment screw is located on the valve.
4. Thermal Switch
The auto-reset switch is located on the front of the intake air elbow. The switch will safely shut the unit down if ex­cessive temperatures are detected. See Figure 13. When the switch senses excessive temperature, the circuit breaks and the ignition control immediately stops ignition and closes the gas valve.
5. Burner and Orifi ce
Burners are factory set and require no adjustment. Always operate the unit with air gas plenum in place. The burn­er has one orifi ce located between the gas valve and the air intake assembly (Figure 13). To check or replace the orifi ce remove the intake air screen, coupling and intake air elbow.Using a 5/8” socket, go through the elbow and unscrew the gas orifi ce. The burner uses an orifi ce (see Table 16) that is precisely matched to the burner input. The burner can be removed for service. If burner has been removed, it is critical to replace all gaskets.
TABLE 16
Gas Orifi ces
Unit Input Orifi ce Size (0 - 4500 ft)
060 0.0595
080 0.0689
100 0.0810
6. Primary Limit Control (S10)
The primary limit (S10) is located in the heating vestibule panel. When excess heat is sensed in the heat exchanger, the limit will open. If the limit is open, the furnace control energizes the supply air blower and closes the gas valve. The limit automatically resets when unit temperature re­turns to normal. The switch must reset within three min­utes or the SureLight control will go into Watch guard for one hour. The switch is factory set and cannot be adjust­ed. The switch may have a different set point for each unit model number. See Lennox Repair Parts Handbook if limit switch must be replaced.
Page 27
Page 28
Gas Valve
Orifice Housing
Gas Orifice
Air Orifice
HEATING COMPONENTS
Air Gas Plenum
Sensor
Ignitor
Burner
Gasket
Intake Air Screen
Intake Air
Elbow
FIGURE 13
Thermal
Switch
(location)
Page 28
Page 29
Tes t 1
Remove 5-pin plug from control
Check ohms reading across terminals 1and 5
Ohm value should be between 39 - 70.
Meter
(set to ohms)
Seperate the 2-pin jack plug near the manifold
and check resistance of the ignitor. If the reading
is correct, then then there is a problem with the
wiring between the jack plug and control. If the
reading is not correct the issue is the ignitor.
Tes t 2
.
SL280UHNV Ignitor Check Out
(exploded view for clarity)
Integrated control detail
Meter
(set to ohms)
Insert meter probes into the terminals 1 and 5. (Use small
diameter probes in order to not damage plug). Check
voltage during 20 second warm up period. Voltage should
read 120 volts +
check for correct supply voltage to furnace.
10%. If voltage is above these values,
Tes t 3
Meter
(set to AC volts)
Integrated control detail
Integrated control detail
FIGURE 14
Page 29
Page 30
7. Combustion Air Inducer (B6)
All SL280UHNV units use a two-stage combustion air in­ducer to move air through the burners and heat exchang­er during heating operation. The blower uses a 120VAC motor. The motor operates during all heating operation and is controlled by integrated control control A92. The in­ducer also operates for 15 seconds before burner ignition (prepurge) and for 5 seconds after the gas valve closes (postpurge). The inducer operates on low speed during rststage heat, then switches to high speed for second stage heat.
8. Combustion Air Inducer Prove Switch (S18)
SL280UHNV series units are equipped with a single com­bustion air proving switch (fi rst and second stage) located near the gas valve. See Figure 15. The switch is a sin­gle-pole single-throw proving switch electrically connect­ed to the integrated control. The purpose of the switch is to prevent burner operation if the combustion air inducer is not operating or if the fl ue becomes obstructed.
On heat demand (fi rst or second stage) the switch senses that the combustion air inducer is operating. It closes a circuit to the integrated control when pressure inside the combustion air inducer decreases to a certain set point. The set point is 0.20” for low heat and high heat and the same for all SL280UHNV models. The pressure sensed by the switch is negative relative to atmospheric pres­sure. If the fl ue becomes obstructed during operation, the switch senses a loss of pressure difference and opens the circuit to the furnace control and gas valve.
COMBUSTION AIR PRESSURE SWITCH
NOTE - The switch is factory set and is not fi eld adjust- able. It is a safety shut-down control in the furnace and must not be by-passed for any reason. If switch is closed or bypassed, the control will not initiate ignition at start up.
II-Placement and Installation
Make sure unit is installed in accordance with installation instructions and applicable codes.
III-Start-Up A-Preliminary and Seasonal Checks
1 - Inspect electrical wiring, both fi eld and factory
installed for loose connections. Tighten as required.
2 - Check voltage at disconnect switch. Voltage must
be within range listed on the nameplate. If not,
consult the power company and have voltage
condition corrected before starting unit.
B-Heating Start-Up
WARNING
Shock and burn hazard. SL280UHNV units are equipped with a hot surface
ignition system. Do not attempt to light manually.
1 - STOP! Read the safety information at the beginning
of this section. 2 - 2 - Set the thermostat to the lowest setting. 3 - Turn off all electrical power to the unit. 4 - This furnace is equipped with an ignition device
which automatically lights the burners. Do not try to
light the burners by hand. 5 - Remove the access panel. 6 - Turn switch on gas valve to OFF. Do not force. See
gure 16. 7 - Wait fi ve minutes to clear out any gas. If you then
smell gas, STOP! Immediately call your gas supplier
from a neighbor’s phone. Follow the gas supplier’s
instructions. If you do not smell gas go to next step.
Positive +
to air intake pipe
FIGURE 15
Negative -
to air intake
elbow
Page 30
Page 31
MANIFOLD PRESSURE ADJUSTMENT (TURN CCW TO INCREASE PRESSURE)
NEGATIVE AIR
PRESSURE PORT
GAS VALVE
POSITIVE AIR
PRESSURE PORT
10 - Is pressure switch closed? Obstructed fl ue will
cause unit to shut off at pressure switch. Check fl ue
and outlet for blockages. 11 - Are fl ame rollout switches tripped? If fl ame rollout
switches are tripped, call the service technician for
inspection.
C-Safety or Emergency Shutdown
Turn off unit power. Close manual and main gas valves.
D-Extended Period Shutdown
INLET
SUPPLY
PRESSURE
TAP
GAS VALVE SHOWN IN THE ON POSITION
OUTLET
MANIFOLD
PRESSURE TAP
FIGURE 16
8 - Move switch on gas valve to ON. Do not force. See
Figure 16. 9 - Replace the access panel. 10 - Turn on all electrical power to to the unit. 11 - Set the thermostat to desired setting.
NOTE - When unit is initially started, steps 1 through 11 may need to be repeated to purge air from gas line.
Turning Off Gas To Unit
1 - Set thermostat to lowest setting. 2 - Turn off all electrical power to unit if service is to be
performed. 3 - Remove access panel. 4 - Move switch on valve to OFF. Do not force. 5 - Replace access panel.
Failure To Operate
If the unit fails to operate, check the following:
1 - Is the thermostat calling for heat? 2 - Are access panels securely in place? 3 - Is the main disconnect switch closed? 4 - Is there a blown fuse or tripped circuit breaker? 5 - Is the fi lter dirty or plugged? Dirty or plugged fi lters
will cause the limit control to shut the unit off. 6 - Is gas turned on at the meter? 7 - Is the manual main shut-off valve open? 8 - Is the internal manual shut-off valve open? 9 - Is the unit ignition system in lock out? If the unit locks
out again, call the service technician to inspect the
unit for blockages.
Turn off thermostat or set to “UNOCCUPIED” mode. Close all gas valves (both internal and external to unit) to guar­antee no gas leak into combustion chamber. Turn off pow­er to unit. All access panels and covers must be in place and secured.
IV-Heating System Service Checks A-CSA Certifi cation
All units are CSA design certifi ed without modifi cations. Refer to the SL280UHNV Installation Instruction.
B-Gas Piping
CAUTION
If a fl exible gas connector is required or allowed by the authority that has jurisdiction, black iron pipe shall be installed at the gas valve and extend outside the furnace cabinet.
WARNING
Do not over torque (800 in-lbs) or under torque (350 in­lbs) when attaching the gas piping to the gas valve.
Gas supply piping should not allow more than 0.5”W.C. drop in pressure between gas meter and unit. Supply gas pipe must not be smaller than unit gas connection.
Compounds used on gas piping threaded joints should be resistant to action of liquefi ed petroleum gases.
C-Testing Gas Piping
IMPORTANT
In case emergency shutdown is required, turn off the main shut-off valve and disconnect the main power to unit. These controls should be properly labeled by the installer.
Page 31
Page 32
When pressure testing gas lines, the gas valve must be
E
disconnected and isolated. Gas valves can be damaged if subjected to more than 0.5 psig (14” W.C.). See Figure 17. If the pressure is greater than 0.5psig (14”W.C.), use the manual shut-off valve before pressure testing to isolate furnace from gas supply.
MANUAL MAIN
SHUT-OFF VALVE
WILL NOT HOLD
NORMAL TEST
PRESSURE
1/8 NPT PLUG
CAP
ISOLATE
GAS VALVE
FURNAC
FIGURE 17
When checking piping connections for gas leaks, use preferred means. Kitchen detergents can cause harmful corrosion on various metals used in gas piping. Use of a specialty Gas Leak Detector is strongly recommended. It is available through Lennox under part number 31B2001. See Corp. 8411-L10, for further details.
Do not use matches, candles, fl ame or any other source of ignition to check for gas leaks.
D-Testing Gas Supply Pressure
A port on the inlet side of the gas valve provides access to the supply pressure tap. See fi gure 16. Loosen the screw and connect a manometer to measure supply pressure. The minimum supply line is 4.5” w.c. And the maximum supply line is 13.0” w.c. Tighten screw after measure­ments have been taken.
IMPORTANT
For safety, connect a shut-off valve between the manometer and the gas tap to permit shut off of gas pressure to the manometer.
E-Rate Check Manifold Pressure Measurement
TABLE 17
Unit High Fire Low Fire
060
3.2 - 3.6 in wc 1.3 - 1.7 in wc080
100
F- Proper Combustion
Furnace should operate minimum 15 minutes with correct gas fl ow rate before checking combustion. Take combus- tion sample beyond the fl ue outlet. Table 18 shows ac- ceptable combustion for ALL SL280UHNV models. The maximum carbon monoxide reading should not exceed 100 ppm.
TABLE 18
Firing Rate CO2% For Natural
High Fire
6.0 - 7.5
Low Fire
G- Proper Gas Flow (Approximate)
Furnace should operate at least 5 minutes before check-
ing gas fl ow. Determine time in seconds for two revolu-
tions of gas through the meter. (Two revolutions assures a
more accurate time.) Divide by two and compare to time
in Table 19 below.
NOTE- To obtain accurate reading, shut off all other gas appliances connected to meter.
TABLE 19
GAS METER CLOCKING CHART
Seconds for One Revolution
SL280N Unit
Natural
1 cu ft Dial 2 cu ft Dial
060 60 120
080 45 90
100 36 72
Natural-1000 btu/cu ft
To correctly measure manifold pressure, follow the steps below:
1 - Remove the threaded plug from the outlet side of
the gas valve and install a fi eld-provided barbed tting. Connect measuring device “+” connection to barbed fi tting to measure manifold pressure.
2 - Start unit on low heat and allow 15 minutes for unit
to reach steady state. 3 - After allowing unit to stabilize for 15 minutes, record
manifold pressure and compare to value given in
Table 17 4 - Repeat on high heat. 5 - Shut unit off and remove manometer as soon as
an accurate reading has been obtained. Take care
to remove barbed fi tting and replace threaded plug. 6 - Start unit and perform leak check. Seal leaks if
found.
Page 32
Page 33
V-Typical Operating Characteristics
C-External Static Pressure
A-Blower Operation and Adjustment
1 - Blower operation is dependent on thermostat control
system.
2 - Generally, blower operation is set at thermostat
subbase fan switch. With fan switch in ON position,
blower operates continuously. With fan switch in
AUTO position, blower cycles with demand or runs
continuously while heating or cooling circuit cycles. 3 - Depending on the type of indoor thermostat, blower
and entire unit will be off when the system switch is
in OFF position.
B-Temperature Rise Figure 18
Temperature rise for SL280UHNV units depends on unit input, blower speed, blower horsepower and static pres­sure as marked on the unit rating plate. The blower speed must be set for unit operation within the range of “TEMP. RISE °F” listed on the unit rating plate.
TEMPERATURE RISE
Supply Duct Temperature ________
Return Duct Temperature _ _____
Temperature Rise = ________
1 - Tap locations shown in Figure 19. 2 - Punch a 1/4” diameter hole in supply and return
air plenums. Insert manometer hose fl ush with inside edge of hole or insulation. Seal around the hose with permagum. Connect the zero end of the manometer to the discharge (supply) side of the system. On ducted systems, connect the other end of manometer to the return duct as above.
3 - With only the blower motor running and the
evaporator coil dry, observe the manometer reading. Adjust blower motor speed to deliver the air desired according to the job requirements. For heating speed external static pressure drop must not be more than 0.5” W.C. For cooling speed external static pressure drop must not be more than
0.8” W.C.
4 - Seal the hole when the check is complete.
EXTERNAL STATIC PRESSURE
Supply Duct Static ________
Return Duct Static + _____
Total Duct Static = ________ (dry coil)
Supply Air
Return Air
FIGURE 18
Supply Air
Return Air
FIGURE 19
or
-+
Page 33
Page 34
VI-Maintenance Annual Furnace Maintenance
At the beginning of each heating season, and to comply with the Lennox Limited Warranty, your system should be checked by a licensed professional technician (or equiva­lent) as follows:
WARNING
Disconnect power before servicing unit..
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
1 - Check wiring for loose connections, voltage at
indoor unit and amperage of indoor motor.
2 - Check the condition of the belt and shaft bearings
if applicable. 3 - Inspect all gas pipe and connections for leaks. 4 - Check the cleanliness of fi lters and change if
necessary (monthly).
IMPORTANT
If a higheffi ciency fi lter is being installed as part of this system to ensure better indoor air quality, the fi lter must be properly sized. Higheffi ciency fi lters have a higher static pressure drop than standardeffi ciency glass/foam lters. If the pressure drop is too great, system capacity and performance may be reduced. The pressure drop may also cause the limit to trip more frequently during the winter and the indoor coil to freeze in the summer, resulting in an increase in the number of service calls.
Before using any fi lter with this system, check the specifi cations provided by the fi lter manufacturer against the data given in the appropriate Lennox Product Specifi cations bulletin. Additional information is provided in Service and Application Note ACC002
(August 2000).
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.
5 - Check the condition and cleanliness of burners and
heat exchanger and clean if necessary. 6 - Check the cleanliness of blower assembly and
clean the housing, blower wheel and blower motor
if necessary. The blower motors are prelubricated
for extended bearing life. No further lubrication is
needed.
7 - Inspect the combustion air inducer and clean if
necessary.
8 - Evaluate the heat exchanger integrity by inspecting
the heat exchanger per the AHRI heat exchanger inspection procedure. This procedure can be viewed at www.ahrinet.org
9 - Ensure suffi cient combustion air is available to the
furnace. Fresh air grilles and louvers (on the unit and in the room where the furnace is installed) must be properly sized, open and unobstructed to provide combustion air.
10 - Inspect the furnace venting system to make sure
it is in place, structurally sound, and without holes, corrosion, or blockage. Vent system must be free and clear of obstructions and must slope upward away from the furnace. Vent system should be installed per the National Fuel Gas Code
11 - Inspect the furnace return air duct connection to
ensure the duct is sealed to the furnace. Check for air leaks on supply and return ducts and seal where necessary.
12 - Check the condition of the furnace cabinet insulation
and repair if necessary.
13 - Perform a complete combustion analysis during the
furnace inspection to ensure proper combustion and operation. Consult Service Literature for proper combustion values.
14 - Verify operation of CO detectors and replace
batteries as required.
Perform a general system test. Turn on the furnace to check operating functions such as the start-up and shut­off operation.
1 - Check the operation of the ignition system, inspect
and clean fl ame sensor. Check microamps before and after. Check controls and safety devices (gas valve, fl ame sensor, temperature limits). Consult Service Manual for proper operating range. Thermal Limits should be checked by restricting airfl ow and not disconnecting the indoor blower. For additional details, please see Service and Application Note H049.
2 - Verify that system total static pressure and airfl ow
settings are within specifi c operating parameters.
3 - Clock gas meter to ensure that the unit is operating
at the specifi ed fi ring rate. Check the supply pressure and the manifold pressure. On two-stage gas furnaces check the manifold pressure on high re and low fi re. If manifold pressure adjustment is necessary, consult the Service Literature for unit specifi c information on adjusting gas pressure. Not all gas valves are adjustable. Verify correct temperature rise.
Page 34
Page 35
A-Heat Exchanger and Burners Figure 20 Cleaning the Heat Exchanger and Burners
NOTE - Use papers or protective covering in front of the furnace during cleaning.
1 - Turn off both electrical and gas power supplies to
furnace.
2 - Remove fl ue pipe and top cap (some applications
top cap can remain) from the unit. 3 - Label the wires from gas valve, thermal switch,
primary limit switch and make-up box then
disconnect them. 4 - Remove the screws that secure the combustion air
inducer to the collector box. 5 - Disconnect gas supply piping. Remove the screw
securing the air fuel plenum and remove along with
the air inake assembly as one component. 6 - Remove screws from both sides, top and bottom of
vestibule panel. 7 - Remove heat exchanger. It may be necessary
to spread cabinet side to allow more room. If so,
remove fi ve screws from the left side or right side of
cabinet. See Figure 21. 8 - Back wash using steam. Begin from the burner
opening on each tube. Steam must not exceed
275°F. 9 - To clean burner and intake debris screen, run a
vacuum cleaner over the face of burners. Visually
inspect inside the burner. Remove any blockage.
Figure 20 shows burner detail. Replace gasket
between burner plate and air fuel plenum then re-
install burner plate.
10 - To clean the combustion air inducer visually inspect
and using a wire brush clean where necessary. Use compressed air to clean off debris and any rust.
11 - Reinstall heat exchanger in vestibule. (Replace the
ve screws in the cabinet from step 7 if removed).
12 - Reinstall the air fuel plenum and air intake
assembly. Make note of the numbered sequence when re-installing the air fuel plenum. Follow the sequence as shown in Figure 20. Torque screws to a maximum of 100 + 5 in - lbs. and a minimum 60 in - lbs.
13 - Re-install the combustion air inducer assembly.
Make note to re-install all screws. Failure to replace all screws may cause leaks. Reconnect all wires.
14 - Reconnect top cap and vent pipe to combustion air
inducer outlet. 15 - Reconnect gas supply piping. 16 - Turn on power and gas supply to unit. 17 - Set thermostat and check for proper operation. 18 - Check all piping connections, factory and fi eld, for
gas leaks. Use a leak detecting solution or other
preferred means.
CAUTION
Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly after leak test has been completed. Do not use matches, candles, fl ame or other sources of ignition to check for gas leaks.
19 - If a leak is detected, shut gas and electricity off and
repair leak. 20 - Repeat steps 18 and 19 until no leaks are detected. 21 - Replace access panel
Page 35
Page 36
Air Fuel Plenum
Heat Exchanger and Burner Assembly Removal
* Re-install screws per the numbered sequence shown
Heat Exchanger
Gasket
Burner
Gasket
Debri Screen
Remove 5 screws if necessary
(cabinet for reference only)
Gas Valve
Air Intake Assembly
*Air Fuel Plenum
FIGURE 20
1
2
3
4
Gasket (replace)
FIGURE 21
5
Page 36
Page 37
VII- Wiring and Sequence of Operation
When there is a call for heat, the iComfort® enabled in­tegrated control runs a self check. The control checks for S10 primary limit and S47 rollout switch normally closed contacts. The control also checks for S102 high heat and S128 low heat prove switch normally open contacts. Once self check is complete and all safety switches are opera­tional, heat call can continue.
NOTE - The ignition control thermostat selection DIP switch is factory-set in the “TWO-STAGE” position.
Page 37
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be properly grounded in accordance with national and local codes.
WARNING
Fire Hazard. Use of aluminum wire with this product may result in a fi re, causing property damage, severe injury or death. Use copper wire only with this product.
Page 38
CAUTION
Failure to use properly sized wiring and circuit breaker may result in property damage. Size wiring and circuit breaker(s) per Product Specifi cations bulletin (EHB) and unit rating plate.
Applications Using a Two-Stage Thermostat
A - Heating Sequence -- Integrated Control Thermo­stat Selection DIP Switch 1 OFF in “Two-Stage” Posi­tion (Factory Setting)
1 - On a call for heat, thermostat fi rst-stage contacts
close sending a signal to the integrated control. The integrated control runs a self-diagnostic program and checks high temperature limit for normally closed contacts and pressure switch for normally open contacts. The combustion air inducer is energized at low speed.
2 - Once the control receives a signal that the pressure
switch has closed, the combustion air inducer begins a 15-second pre-purge in low speed.
3 - After the pre-purge is complete, a 20-second initial
ignitor warm-up period begins. The combustion air inducer continues to operate at low speed.
4 - After the 20-second warm-up period has ended,
the gas valve is energized on low fi re and ignition occurs. At the same time, the control module sends a signal to begin an indoor blower 30-second ON­delay. When the delay ends, the indoor blower motor is energized on the low fi re heating speed, the HUM contacts close energizing the humidifi er and 120V ACC terminal is energized. The furnace will continue this operation as long as the thermostat has a fi rst-stage heating demand.
NOTE - If the indoor thermostat is set on CONTINUOUS FAN ON mode, the furnace will light on high fi re (second-stage) for 60 seconds to improve heat exchanger warm up. After 60 second warm-up period, furnace will switch to low fi re (fi rst- stage).
5 - If second-stage heat is required, the thermostat
second- stage heat contacts close and send a signal to the integrated control. The integrated control initiates a 30-second second-stage recognition delay.
6 - At the end of the recognition delay, the integrated
control energizes the combustion air inducer at high speed. The gas valve is energized on high fi re and the indoor blower motor is energized for operation at the high fi re heating speed.
7 - When the demand for high fi re heat is satisfi ed, the
combustion air inducer is switched to the low-fi re heating speed and the gas valve reduces to low re. The low-fi re gas valve continues operation. The indoor blower motor is switched to the low-fi re heating speed.
8 - When the thermostat demand for low-fi re heat is
satisfi ed, the gas valve is de-energized and the
eld-selected indoor blower off delay begins. The
combustion air inducer begins a 5-second post-
purge period. 9 - When the combustion air post-purge period is
complete, the inducer, the HUM contacts as well
as the 120V ACC terminals are de-energized. The
indoor blower is de-energized at the end of the off
delay.
Applications Using A Single-Stage Thermostat
B - Heating Sequence -- Integrated Control Thermostat Selection DIP Switch 1 ON in “Single-Stage” Position
NOTE - In these applications, two-stage heat will be initi­ated by the integrated control if heating demand has not been satisfi ed after the fi eld adjustable period (7 or 12 minutes).
1 - On a call for heat, thermostat fi rst-stage contacts
close sending a signal to the integrated control. The integrated control runs a self-diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts. The combustion air inducer is energized at low speed.
2 - Once the control receives a signal that the pressure
switch has closed, the combustion air inducer
begins a 15-second pre-purge in low speed. 3 - After the pre-purge is complete, a 20-second initial
ignitor warm-up period begins. The combustion air
inducer continues to operate at low speed. 4 - After the 20-second warm-up period has ended,
the gas valve is energized on low fi re (fi rst stage)
and ignition occurs. At the same time, the control
module sends a signal to begin an indoor blower
30-second ON-delay. When the delay ends, the
indoor blower motor is energized on the low fi re
heating speed and the HUM contacts are energized.
The integrated control also initiates a second-stage
on delay (factory-set at 7 minutes; adjustable to 12
minutes). 5 - If the heating demand continues beyond the
secondstage on delay, the integrated control
energizes the combustion air inducer at high speed.
The gas valve is energized on high fi re and the
indoor blower motor is energized for operation at
the high fi re heating speed. 6 - When the thermostat heating demand is satisfi ed,
the combustion air inducer begins a 5-second low
speed post-purge. The fi eld-selected indoor blower
off delay begins. The indoor blower operates at the
low-fi re heating speed. 7 - When the combustion air post-purge period is
complete, the inducer, the HUM contacts as well
as the 120V ACC terminals are de-energized. The
indoor blower is de-energized at the end of the off
delay.
Page 38
Page 39
iComfort® Thermostat with a
Non-Communicating Outdoor Unit
iComforti® Thermostat with an iComfort
ENABLED Outdoor Unit
®
iComforti® Thermostat iComfort
®
-Enabled Indoor Furnace
Non-Communicating Outdoor Air Conditioner
®
iComfort
ENABLED
OPTIONAL
DISCHARGE
AIR SENSOR
®
iComfort
TWO-STAGE OPERATION
ENABLED
THERMOSTAT
CLIP ON-BOARD LINK W915 (Y1 TO Y2) FOR
FURNACE
NON-COMMUNICATING
OUTDOOR AIR
CONDITIONING UNIT -
1 OR 2 STAGE
OPTIONAL
OUTDOOR
AIR SENSOR
icomfort® Thermostat iComfort iComfort
DISCHARGE
AIR SENSOR
OPTIONAL OUTDOOR
AIR SENSOR
® ®
OPTIONAL
iComfort
THERMOSTAT
Enabled Indoor Furnace Enabled Outdoor Air Conditioner or Heat Pump
®
iComfort ENABLED FURNACE
®
®
iComfort
OUTDOOR AIR CONDITIONING
OR HEAT PUMP UNIT
- ENABLED
Outdoor Unit
Communicating systems using the iComfort®thermostat require four thermostat wires between the thermostat and the furnace/air handler control and four wires between the outdoor unit and the furnace/air handler control. When a thermostat cable with more than four wires is used, the extra wires must be properly connected to avoid electrical noise. The wires must not be left disconnected.
Use wire nuts to bundle the four unused wires at each end of the cable. A single wire should then be connected to the indoor unit end of the wire bundle and attached to the “C” terminals as shown below.
Indoor Unit Controller
iComfort
Single wire
Single wire to terminal C
Unused wires
to terminal C
Unused wires
®
thermostat
Page 39
Page 40
Optional Accessories for use with any iComfort Touch
®
System
NOTE: iComfort® THERMOSTAT SENSES HUMIDITY & CONTROLS HUM CONTACTS TO CYCLE HUMIDIFIER BASED ON DEMAND. NO OTHER CONTROL OR HUMIDISTAT REQUIRED.
OPTIONAL OUTDOOR AIR SENSOR FOR USE WITH HUMIDIFIER (IF NOT ALREADY IN THE SYSTEM FOR OTHER FUNCTIONS. BUILT INTO ALL icomfort® by Lennox® OUTDOOR UNITS).
iComfort®ENABLED
Discharge Air
Sensor (Required
for even heat)
iComfort
THERMOSTAT
FURNACE
®
RSBus
Maximum total
nections on the RSBus is limited to 1500ft.
Wire gauge of RSBus wire is 18.
®
icomfort
DOOR AIR CONDITIONING
OR HEAT PUMP UNIT
ENABLED
icomfort
FURNACE
(POWER COMPANY INTERRUPTION SYSTEMS ARE WIRED SAME AS OVERFLOW SWITCH)
NOTE: 24V UV LIGHT APPLICATIONS
In an iComfort® by Lennox® system, neither furnace nor air handler former will have adequate VA to power 24V UV light applications. An additional transformer for UV light applications is required.
HVAC EQUIPMENT
iComfort
THERMOSTAT
DEHUMIDIFIER CONTROL
Rf WGh
HVAC EQUIP
Cf Gs
DH
120V CONNECTIONS
“HUM” CONTACT IS CLOSED ANYTIME HUMIDITY DEMAND IS PRESENT
24V HUMIDIFIER CONNECTIONS
THERMOSTAT
CONVENTIONAL
CATING SYSTEM
COMMUNICATING SYSTEM
*24V IN jumper not used in non­communicating configuration
*24V IN JUMPER
iComfort® ENABLED FURNACE
®
HEPA BYPASS FILTER X2680 HEPA INTERLOCK KIT
PASS INDOOR BLOWER MOTOR COMMON WIRE
ENABLED
FURNACE
THROUGH CURRENT LOOP.
SEE HEPA INTERLOCK KIT
TAILS
icomfort
LVCS VENTILATION CONTROL SYSTEM
SEE LVCS VENTILATION INSTRUCTIONS FOR DAMPER & SENSOR WIRING
ENABLED
FURNACE
icomfort
Page 40
STANDARD 1 OR 2
STAGE AC OR HP UNIT
2 STAGE FURNACE
CUT R-DS W914
NON-COMMUNICATING SYSTEM WIRING
DS
COMMUNICATING SYSTEM WIRING
R
Page 41
VIII- Field Wiring With Conventional Thermostat
DIP Switch Settings and On-Board Links
Thermostat
DIP Switch 1
Thermostat
On Board Links Must Be Cut To Select
Heating
Stages
1 Heat / 1 Cool
ON
NOTE - Use DIP switch 2 to set second-stage heat ON delay. OFF-7 minutes.
DO NOT CUT ANY ON-BOARD LINKS
ON-12 minutes.
System Options
Wiring Connections
S1
T'STAT
FURNACE
TERM. STRIP
OUTDOOR
UNIT
*
1 Heat / 2 Cool
NOTE - Use DIP switch 2 to set second-stage heat ON delay. OFF-7 minutes. ON-12 minutes.
1 Heat / 2 Cool with t'stat with humidity control
NOTE - Use DIP switch 2 to set second-stage heat ON delay. OFF-7 minutes. ON-12 minutes.
ON
ON
CUT ON-BOARD LINK
W915
2 STAGE
COMPR
CUT ON-BOARD LINK
W915
2 STAGE
COMPR
CUT ON-BOARD LINK
W914
DEHUM
OR
HARMONY
S1
T'STAT
S1
T'STAT
FURNACE
TERM. STRIP
FURNACE
TERM. STRIP
*
o
OUTDOOR
UNIT
OUTDOOR
UNIT
*
* Not required on all units.
Page 41
Page 42
DIP Switch 1
Thermostat
Thermostat
Heating
Stages
2 Heat / 2 Cool OFF
Field Wiring With Conventional Thermostat (Continued)
DIP Switch Settings and On-Board Links
On Board Links Must Be Cut To Select
System Options
S1
CUT ON-BOARD LINK
W915
2 STAGE
COMPR
T'STAT
Wiring Connections
FURNACE
TERM. STRIP
OUTDOOR
*
UNIT
2 Heat / 2 Cool with t'stat with humidity control
2 Heat / 1 Cool with t'stat with humidity control
OFF
OFF
CUT ON-BOARD LINK
W915
2 STAGE
COMPR
CUT ON-BOARD LINK
W914
DEHUM
OR
HARMONY
CUT ON-BOARD LINK
W914
DEHUM
OR
HARMONY
S1
T'STAT
S1
T'STAT
FURNACE
TERM. STRIP
o
FURNACE
TERM. STRIP
o
OUTDOOR
UNIT
*
OUTDOOR
UNIT
*
2 Heat / 1 Cool OFF
* Not required on all units.
DO NOT CUT ANY ON-BOARD LINKS
Page 42
S1
T'STAT
FURNACE
TERM. STRIP
OUTDOOR
UNIT
*
Page 43
Thermostat
Dual Fuel Single Stage Heat Pump
ComfortSense thermostat w/
Field Wiring With Conventional Thermostat (Continued)
DIP Switch Settings and On-Board Links
DIP Switch 1
Thermostat
Heating
Stages
OFF
On Board Links Must Be Cut To Select
System Options
CUT ON-BOARD LINK
W951 HEAT
PUMP
Wiring Connections
T'STAT
H
FURNACE
TERM. STRIP
HEAT PUMP
67M41*
bilities Capable of 2 stage gas heat control
Dual Fuel Two Stage Heat Pump
ComfortSense thermostat w/
bilities Capable of 2 stage gas heat control
OFF
CUT ON-BOARD LINK
W915
2 STAGE
COMPR
CUT ON-BOARD LINK
W951 HEAT PUMP
L
Y2
D
B
T
T
T'STAT
H
L
Y2
D
B
Y2
FURNACE
TERM. STRIP
67M41*
L
Y
outdoor
sensor
HEAT PUMP
L
Y2
out blue
T
T
outdoor sensor
* Connect W1 to W1 ONLY if using defrost tempering kit 67M41
NOTE - Do NOT make a wire connection between the room thermostat L terminal and the L terminal of the furnace integrated control.
Page 43
Page 44
Thermostat
Dual Fuel Single Stage Heat Pump
ComfortSense thermostat w/
Field Wiring With Conventional Thermostat (Continued)
DIP Switch Settings and On-Board Links
DIP Switch 1
Thermostat
Heating
Stages
OFF
On Board Links Must Be Cut To Select
System Options
CUT ON-BOARD LINK
W951 HEAT
PUMP
Wiring Connections
T'STAT
H
FURNACE
TERM. STRIP
HEAT PUMP
67M41*
bilities Capable of 2 stage gas heat
midification control
Dual Fuel Two Stage Heat Pump
ComfortSense thermostat w/
bilities Capable of 2 stage gas heat
midification
OFF
CUT ON-BOARD LINK
W914
DEHUM
OR
HARMONY
CUT ON-BOARD LINK
W915
2 STAGE
COMPR
CUT ON-BOARD LINK
W951 HEAT
PUMP
CUT ON-BOARD LINK
W914
DEHUM
OR
HARMONY
L
Y2
D
B
T
T
T'STAT
H
L
Y2
D
B
Y2
FURNACE
TERM. STRIP
Y2
67M41*
L
Y
outdoor
sensor
HEAT PUMP
L
Y2
out blue
T
T
outdoor
sensor
* Connect W1 to W1 ONLY if using defrost tempering kit 67M41
NOTE - Do NOT make a wire connection between the room thermostat L terminal and the L terminal of the furnace integrated control.
Page 44
Page 45
IX- Program Unit Capacity Size Modes
Power-Up - Number displayed represents by integrated control unit size code (furnace model and capacity). If three horizontal bars are displayed followed by continuous E203, furnace control does not recognize unit size code. Configure per the following:
Yes
To enter Program Unit Capacity/Size: push and hold button next to 7-segment LED display until solid “P” symbol appears. Release button.
IMPORTANT: Field replacement controls may need to be manually configured to validate furnace unit size code.
_
Furnace control in IDLE mode
No heating, cooling or indoor fan
operation)
No
UNIT SIZE
CODE
A
C
d
E
Turn room thermostat to OFF
FURNACE MODEL
SL280UH060NV36A
SL280UH080NV48B
SL280UH080NV60C
SL280UH100NV60C
Solid P starts blinking on 7-Segment LED
Push and hold button. Integrated control will display unit size code number for each furnace model for three seconds.
P
FINISHED
When the correct unit size code is displayed, release button. Selected code will flash for 10-second period. During that period, press and hold push button for 5 seconds. Integrated control will store code in memory and will automatically exit Program Unit Capacity/Size Mode and reset. (If second period expires or push button is held less than five seconds, control will automatically exit Program Capacity/Size Mode and go into IDLE mode without storing unit size code. If this happens, programming function must be repeated).
. If
Verify that the selected unit size code is correct and stored in non-volatile memory by cycling the 24 volt power to the furnace control. (At 24 volt power-up of the furnace control, the 7-segment LED will display a unit size code three horizontal bars display, board does not recognize unit size code function must be repeated)
. Programming
Page 45
Page 46
X- Troubleshooting Heating Sequence of Operation
CALL FOR FIRST-STAGE HEAT
1
CALL FOR
1ST STAGE HEAT
(LOW FIRE)
HIGH
LIMIT SWITCH
ROLLOUT
PRESSURE
INDUCER ON
LOW SPEED
PRESSURE SWITCH CLOSED WITHIN 120
SECONDS?
PRE−PURGE
(15 SECONDS)
H.S.I. ON
(20 SECONDS)
1ST STAGE GAS
VALVE ENERGIZED
IGNITION TRIAL
BEGINS (H.S.I. ON)
CLOSED?
YES
CIRCUITS
CLOSED?
YES
LOW
SWITCH
OPEN?
YES
LOW
YES
NO
NO
NO
3
HEAT FAN ON DELAY
TIMER STARTED
INDOOR BLOWER OFF AFTER
HEAT FAN OFF DELAY
(LOW HEAT SPEED)
ERROR
CODE
FLASHES
DE−ENERGIZE
GAS VALVE
ERROR CODE
FLASHES (AFTER
5 SECONDS)
LOW PRESSURE SWITCH OPENS
NO
INDOOR BLOWER
ON(LOW HEAT
SPEED)
HIGH
PRESSURE
SWITCH
OPEN
BEFORE
INDUCER WAS
TURNED ON?
INDUCER ON
(HIGH SPEED)
INDOOR BLOWER
ON (LOW HEAT
SPEED)
INTERPURGE
(15 SECONDS)
YES
YES
NO
LIMIT
SWITCH
CLOSED WITHIN 3
MINUTES?
ERROR
CODE
FLASHES
INDUCER TO
HIGH SPEED−
ERROR CODE
FLASHES
NO
AFTER HEAT FAN
NO
OFF DELAY (LOW
ROLLOUT
CIRCUIT
CLOSES
NO
INDOOR BLOWER OFF AFTER HEAT OFF DELAY
HARD LOCKOUT − ERROR CODE FLASHES
LOW & HIGH
PRESSURE SWITCH
CLOSED WITHIN 30
SECONDS?
NO
INDOOR
BLOWER OFF
HEAT SPEED)
INDUCER OFF
AFTER POST
PURGE
YES
WATCHGUARD − ERROR CODE FLASHES
YES
2
NO
YES
INDUCER OFF−
WAIT 5 MINUTES ERROR CODE
FLASHES
1
NO
CALL
FOR HEAT
ENDS?
YES
INDOOR
INDOOR
BLOWER
BLOWER
ON?
ON?
YES
INDOOR
BLOWER
OFF AFTER
HEAT FAN
OFF DELAY
1
NO
FLAME
SENSED WITHIN
4 SECONDS?
YES
H.S.I. OFF
INDOOR
BLOWER ON 30 SEC.
(LOW HEAT SPEED)
2
CALL FOR HEAT SATISFIED
NO
GAS VALVE
DE−ENERGIZED
H.S.I. OFF
1
WATCHGUARD LOCKOUT AUTOMATICALLY RESETS AFTER ONE HOUR
HARD LOCKOUT REQUIRES THERMOSTAT RESET OR CYCLING OF POWER TO RESET THE LOCKOUT.
2
IN CASE HIGH SPEED INDUCER IS RUNNING AT THE TIME THE GAS VALVE GETS ENERGIZED,
3
2ND STAGE GAS VALVE IS ENERGIZED INSTEAD OF 1ST STAGE. 20 SECONDS AFTER FLAME IS SENSED, INDUCER SWITCHES TO LOW SPEED, AND GAS VALVE SWITCHES TO 1ST STAGE.
5TH
UNSUCCESSFUL
TRIAL?
Page 46
YES
POSTPURGE (5 SECONDS)
INDUCER
OFF
WATCHGUARD − ERROR CODE FLASHES
1
Page 47
Heating Sequence of Operation (Continued)
CALL FOR SECOND-STAGE HEAT
2
2 STAGE THERMOSTAT
RECOGNITION DELAY
ONLY FOR 1ST REQUEST FOR
2ND STAGE HEAT
CALL FOR 2ND STAGE HEAT
(30 SECONDS)
EXPIRED?
(HIGH FIRE)
YES
INDUCER SWITCHED
TO HIGH SPEED
HIGH
PRESSURE SWITCH
CLOSED WITHIN 10
SECONDS?
YES
2ND STAGE GAS VALVE
ENERGIZED
INDOOR BLOWER ENERGIZED
ON HIGH HEAT SPEED
1
SINGLE STAGE
THERMOSTAT
2ND STAGE
ON DELAY
EXPIRED?
YES
2
INDUCER SWITCHED
NO
TO LOW SPEED
5 MINUTE DELAY
(ERROR CODE FLASHES)
3
3
CALL FOR HEAT SATISFIED
1
SYSTEM WILL ALWAYS LIGHT ON LOW FIIRE, EVEN IF 2ND STAGE HEAT IS IN PLACE.
WHEN USED WITH A SINGLE STAGE THERMOSTAT, SET SW1 TO THE ON POSITION IN DIP SWITCH S4.
2
3
IF THE HIGH FIRE PRESSURE SWITCH DOES NOT CLOSE WITHIN 5 ATTEMPTS, THE SYSTEM WILL OPERATE AT LOW FIRE FOR THE REMAINDER OF THE CALL FOR HEAT REQUEST.
Page 47
Page 48
Heating Sequence of Operation (Continued)
CALL FOR HEAT SATISFIED
FIRST-STAGE HEAT SECOND-STAGE HEAT
2 3
2ND STAGE HEAT
INDUCER SPEED SWITCHED
NO
2ND STAGE
CALL FOR HEAT
SATISFIED?
YES
DE−ENERGIZE 2ND STAGE
GAS VALVE
TO LOW SPEED
RUN MODE: 1ST OR 2ND STAGE CALL FOR HEAT.
ALL INPUTS MONITORED (LIMIT, PRESSURE, CALL FOR HEAT/COOL, FLAME LEVEL)
INDOOR BLOWER SWITCHED
TO LOW HEAT SPEED
1ST STAGE HEAT
1ST STAGE
CALL FOR HEAT
SATISFIED?
GAS VALVE
DE−ENERGIZED
INDUCER OFF AFTER
5 SECOND POST PURGE
INDOOR BLOWER OFF
AFTER FIELD SELECTABLE
OFF DELAY
NO
YES
1
Page 48
Page 49
Cooling Sequence of Operation
CALL FOR COOLING
1
1ST STAGE COOLING
REQUEST RECEIVED
WAIT FOR COMPRESSOR TIMED
OFF DELAY TO EXPIRE
ENERGIZE 1ST STAGE COOLING CONTACTOR (COMPRESSOR & FAN)
INDOOR BLOWER 2 SECOND ON DELAY
ENERGIZE INDOOR BLOWER
(LOW COOLING MODE)
2ND STAGE
COOLING
REQUEST?
YES
ENERGIZE 2ND STAGE COOLING CONTACTOR (COMPRESSOR & FAN)
2ND STAGE
COOLING REQUEST
STILL ACTIVE?
1
2
MAINTAIN INDOOR
BLOWER
(LOW COOLING MODE)
1
NO
YES
ENERGIZE INDOOR BLOWER
(HIGH COOLING MODE)
MAINTAIN INDOOR BLOWER
YES
YES
YES
1ST STAGE
COOLING REQUEST
STILL ACTIVE?
2
(HIGH COOLING MODE)
NO
NO
DE−ENERGIZE 2ND
STAGE COOLING
CONTACTOR
(COMPRESSOR & FAN)
1ST STAGE
COOLING REQUEST
STILL ACTIVE?
NO
DE−ENERGIZE 1ST
STAGE COOLING
CONTACTOR
(COMPRESSOR & FAN)
DE−ENERGIZE INDOOR
BLOWER
1
YES
2
ENERGIZE AND MAINTAIN
INDOOR BLOWER AT
(LOW COOLING MODE)
1
CONTROL WILL NOT RESPOND TO A 2ND STAGE COOLING REQUEST UNLESS A 1ST STAGE COOLING REQUEST IS ACTIVE.
INDOOR BLOWER LOW COOLING MODE AND HIGH COOLING MODE HAVE SPECIFIC ON, OFF
2
AND SPEED RAMPING PROFILES. THE SPECIFIC PROFILE IS SELECTED USING THE
DIP SWITCHES ON THE CONROL.
Page 49
Page 50
Continuous Fan Sequence of Operation
CALL FOR FAN
1
CALL FOR FAN
INDOOR BLOWER ON
CONTINUOUS FAN
SPEED
CALL FOR FAN
REMOVED?
YES
REQUEST
FOR COOLING
RECEIVED?
NO
REQUEST
FOR HEAT
RECEIVED?
NO
DE-ENERGIZE INDOOR
BLOWER
1
NO
YES
YES
MAINTAIN INDOOR
BLOWER AT
CONTINUOUS FAN
MAINTAIN INDOOR
BLOWER AT
CONTINUOUS FAN
INDOOR BLOWER OFF
GO TO CALL FOR COOLING
4
1
GO TO CALL FOR 1ST STAGE HEAT
Page 50
Loading...