This SL18XP1 outdoor heat pump with all-aluminum coil
is designed for use with HFC-410A refrigerant only. This
unit must be installed with an approved indoor air handler
or coil. See the Lennox SL18XP1 Product Specifications
bulletin (EHB) for matching indoor components.
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
NOTICE !
For more in-depth information, consult the Installa
tion and Service Procedures manual, available as
Corp.1406-L10 on LennoxPROS.com or through the
Technical Support department at 800-453-6669.
INSTRUCTIONS
Dave Lennox Signature
Collection SL18XP1 System
HEAT PUMPS
507468-01
7/2018
WARNING
Improper installation, adjustment, alteration, service or
maintenance can cause property damage, personal inju
ry or loss of life.
Installation and service must be performed by a licensed
professional installer (or equivalent) or service agency.
CAUTION
Before attempting to perform any service or mainte
nance, turn the electrical power to unit OFF at discon
nect switch.
®
STEP 1 -- SETTING THE UNIT -- Clearances
NOTES:
See NOTES
See
NOTES
See NOTES
NOTICE: Specific applications may require adjustment of the listed installation clearances to provide protection for
the unit from physical damage or to avoid conditions which limit operating efficiency. (Example: Clearances may
have to be increased to prevent snow or ice from falling on the top of the unit. Additional clearances may also be
required to prevent air recirculation when the unit is installed under a deck or in another tight space.)
See
NOTES
Control
Box
Service clearance of 30 in. must be maintained on one of the sides
adjacent to the control box.
Clearance to one of the other three sides must be 36 in.
Clearance to one of the remaining two sides may be 12 in. and the
final side may be 6 in.
A clearance of 24 in. must be maintained between two units.
48 in. clearance required on top of unit.
FIGURE 1
Page 1
Page 2
STEP 1 -- SETTING THE UNIT (Continued) -- Unit Dimensions/Placement
UNIT DIMENSIONS - INCHES (MM)
39-1/2
(1003)
DISCHARGE AIR
ELECTRICAL INLETS
37 (940) [-024 AND -030]
41 (1041) [-036 AND -042]
47 (1194) [-048 AND -060]
VAPOR LINE
INLET
LIQUID LINE
INLET
4-7/16
18-1/2
(470)
(113)
8 (203)
1 (25)
SIDE VIEWACCESS VIEW
UNIT SUPPORT
FEET
35-1/2
(902)
16-7/8
(429)
8-3/4
(222)
3-1/8
(79)
30-3/4
(781)
BASE WITH ELONGATED LEGS
26-7/8
(683)
3-3/4 (95)
4-5/8
(117)
Page 2
Page 3
STEP 1 -- SETTING THE UNIT (Continued)
-- Unit Placement
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and wear gloves and
protective clothing.
WARNING
To prevent personal injury, as well as damage to panels,
unit or structure, observe the following:
While installing or servicing this unit, carefully stow all
removed panels so that the panels will not cause injury
to personnel, objects or nearby structures. Also, take
care to store panels where they will not be subject to
damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any
weather conditions (especially wind) that may cause
panels to be blown around and damaged.
NOTICE !
Roof Damage!
This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil, causing the
rubber to degrade. Failure to follow this notice
could result in damage to roof surface.
IMPORTANT !
Exhaust vents from dryers, water heaters and
furnaces should be directed away from the outdoor
unit. Prolonged exposure to exhaust gases and the
chemicals contained within them may cause
condensation to form on the steel cabinet and other
metal components of the outdoor unit. This will
diminish unit performance and longevity.
SLAB MOUNTING
Install unit level or, if on a slope, maintain slope tolerance of 2
degrees (or 2 inches per 5 feet [50 mm per 1.5 m]) away from
building structure.
BUILDING
STRUCTURE
DISCHARGE AIR
MOUNTING
SLAB
GROUND LEVEL
FIGURE 3
ELEVATED SLAB MOUNTING USING FEET
EXTENDERS
Use additional 2” SCH 40 male threaded adapters which can be
threaded into the female threaded adapters to make additional
adjustments to the level of the unit.
2” (50.8MM) SCH 40
FEMALE THREADED
ADAPTER
2” (50.8MM) SCH 40
MALE THREADED
ADAPTER
PLACEMENT
INSTALL UNIT AWAY
FROM WINDOWS
TWO 90 ELBOWS INSTALLED IN LINE SET
WILL REDUCE LINE SET VIBRATION
FIGURE 2
BASE
LEG DETAIL
FIGURE 4
IMPORTANT !
This model is designed for use in check / expansion
valve systems only. An indoor expansion valve ap
proved for use with HFC-410A refrigerant must be
ordered separately and installed prior to operating
the system.
Page 3
SL18XP1 SERIES
Page 4
STEP 1 -- SETTING THE UNIT (Continued) -- Unit Placement
STABILIZING UNIT ON UNEVEN SURFACES
SLAB MOUNTING
#10 X 1/2” LONG SELF-DRILLING
SHEET METAL SCREWS
STABILIZING BRACKET
(18 GAUGE METAL — 2” WIDTH;
HEIGHT AS REQUIRED)
COIL
BASE PAN
Always use stabilizers when unit is
raised above the factory height.
(Elevated units could become unsta
#10 X 1-1/4” LONG HEX HD SCREW
Concrete slab — use two plastic anchors
(hole drill 1/4”)
AND FLAT WASHER
CORNER POST
ble in gusty wind conditions.)
Stabilizers may be used on any unit
installed on unstable and uneven
surfaces.
DECK TOP MOUNTING
Stabilizing bracket (18 gauge metal — 2” [50.8mm] width; height as required); bend to form
right angle as shown below.
MINIMUM ONE
PER SIDE
!
IMPORTANT !
Unit Stabilizer Bracket
(field-provided):
SAME FASTENERS AS
SLAB SIDE MOUNTING.
Install one bracket per side (minimum). For extra stability, install
two brackets per side, two inches (51mm) from each corner.
WIND BARRIER
Install the unit a minimum of six inches (152 mm)
above the roof surface to avoid ice build-up around
the unit. Locate the unit above a load-bearing wall
or area of the roof that can adequately support the
unit. Consult local codes for rooftop applications.
If coil must be installed facing prevailing winter
winds, a wind barrier should be constructed. Size
barrier at least the same height and width as out
door unit. Install barrier 24 inches (610 mm) from
the sides of the unit in the direction of prevailing
winds.
FOR EXTRA
STABILITY
INLET AIR
PREVAILING WINTER
WINDS
WIND BARRIER
INLET AIR
24”
(610)
INLET AIR
FIGURE 5
Page 4
Page 5
STEP 2 -- ELECTRICAL -- Circuit Sizing
and Wire Routing
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current
Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air han
dler for low‐voltage control power (24VAC - 40 VA mini
mum).
ELECTROSTATIC
DISCHARGE
(ESD)
Precautions and
Procedures
CAUTION
Electrostatic discharge can affect
electronic components. Take care
during unit installation and service to
protect the unit's electronic controls.
Precautions will help to avoid control
exposure to electrostatic discharge by
putting the unit, the control and the
technician at the same electrostatic
potential. Touch hand and all tools on an
unpainted unit surface before
performing any service procedure to
neutralize electrostatic charge.
WARNING
Electric Shock Hazard. Can cause injury
or death. Unit must be grounded in
accordance with national and local
codes.
Line voltage is present at all components
when unit is not in operation on units with
single‐pole contactors. Disconnect all
remote electric power supplies before
opening access panel. Unit may have
multiple power supplies.
IMPORTANT !
If unit is equipped with a crankcase heater, it should
be energized 24 hours before unit start-up to pre
vent compressor damage as a result of slugging.
1. Size Circuit and Install Disconnect: Refer to the unit
nameplate for minimum circuit ampacity, and maxi
mum fuse or circuit breaker size (HACR per NEC).
Install power wiring and properly sized disconnect
switch.
NOTE — Units are approved for use only with copper
conductors. Ground unit at disconnect switch or connect
to an earth ground.
separately) on an inside wall in the center of the condi
tioned area and 5 feet (1.5m) from the floor. The ther
mostat should not be installed on an outside wall or
where it can be affected by sunlight or drafts.
NOTE — 24VAC, Class II circuit connections are made in
the control box.
Page 5
SL18XP1 SERIES
Page 6
A. ROUTE CONTROL WIRES — NON-COMMUNICATING
Install low voltage control wiring from outdoor to indoor unit and from
thermostat to indoor unit. All low voltage wiring must enter unit through
provided field-installed busing installed in electrical inlet.
Run 24VAC control wires through hole with grommet.
Make 24VAC control wire connections to heat pump control (A175).
NOTE — Do not bundle any excess 24VAC control wires inside control box.
NOTE — Wire tie provides low voltage wire strain relief and maintains
B
separation of field-installed low and high voltage circuits.
NOTE — For proper voltages, select control wires gauge per table below.
WIRE RUN LENGTHAWG# INSULATION TYPE
LESS THAN 100' (30 METERS) 18 TEMPERATURE RATING
MORE THAN 100' (30 METERS) 16 35ºC MINIMUM.
B. ROUTE CONTROL WIRES — COMMUNICATING
A
Maximum length of wiring (18 gauge) for all connections on the RSBus is 1500 feet (457 meters). Wires should be color-coded, with a temperature
rating of 95ºF (35ºC) minimum, and solid-core (Class II Rated Wiring). All low voltage wiring must enter unit through provided field-installed bushing
installed in electrical inlet.
Communicating systems using the iComfort®-enabled thermostat require four thermostat wires between the thermostat and the furnace/air han
dler control and four wires between the outdoor unit and the furnace/air handler control. When a thermostat cable with more than four wires is used,
the extra wires must be properly connected to avoid electrical noise (see illustration below).
Use a wire nut to bundle the four unused wires at each end of the cable. Each bundle should also include an additional wire that should be connected
on each end to the C terminal as shown in the figure below.
iComfort®-enabled
iComfort®-enabled
Indoor Unit
Outdoor Unit
HOLE
CONTROL
(A175)
Single Wire To C
iComfort®-enabled
Terminal
Single Wire To C
Terminal
Unused Wires
Unused Wires
ROUTE HIGH VOLTAGE AND GROUND WIRES
Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring. To facilitate a conduit, a
cutout is located in the bottom of the control box. Connect conduit to the control box using a proper conduit fitting.
WATERTIGHT
CONDUIT FITTING
WATERTIGHT
FLEXIBLE CONDUIT
TO SERVICE
DISCONNECT BOX
GROUND LUG*
CONTACTOR
ELECTRICAL INLET (CONTROL WIRING —
LOW VOLTAGE). USE BUSHING
PROVIDED IN BAG ASSEMBLY HERE.
CONTROL BOX
ELECTRICAL
INLET (HIGH
VOLTAGE)
WIRING ENTRY
POINTS
* Attach field-provided
green ground wire to
provided ground lug.
NOTE - Grounding wire
must be a single, contin
uous wire run from unit
ground lug to earth
ground. DO NOT splice
wire.
ACCESS VIEW
thermostat
FIGURE 6
Page 6
Page 7
STEP 2 -- ELECTRICAL (Continued) -- Outdoor Control (A175) Jumpers and Terminals
J4 - COMPRESSOR
SHIFT DELAY
30
SECOND DELAY
(DEFAULT)
0
SECOND DELAY
30
J2 - SECOND-STAGE
LOCK-IN
TEMPERATURE
(TWO-STAGE HEAT PUMP ONLY)
55
DEGREE
TARGET
50
DEGREE
TARGET
45
DEGREE
TARGET
40
DEGREE
TARGET (DEFAULT)
55
50
45
55
50
45
55
50
45
55
50
45
40
7-SEGMENT DISPLAY
PUSH BUTTON
J3 - DEFROST AUTO
(HEAT PUMP ONLY)
JUMPER ON PINS 1 AND 2
DEFROST AUTO ENABLED
DEFROST AUTO DISABLED (DEFAULT)
JUMPER ON PINS 2 AND 3
ON
OFF
J1 - DEFROST TERMINATION
0
SECOND-STAGE LOCK-IN
40
40
TEMPERATURE
TEMPERATURE
MAX
TARGET
90
MAX
90
DEGREE
TARGET
90
70
DEGREE
TARGET
MAX
MAX
(HEAT PUMP ONLY)
70
50
(DEFAULT WHEN JUMPER IS
REMOVED OR MISSING)
70
50
DEGREE
TARGET
(DEFAULT)
90
70
50
90
90
70
50
MAX
50
MAX
90
70
50
DS TO R LINK - EDA
APPLICATION
(TWO-STAGE UNIT ONLY)
40
NOTE - LINK NOT APPLICABLE TO SINGLE-STAGE
UNIT. CUTTING LINK WILL HAVE NO AFFECT ON
OPERATION OF SINGLE-STAGE UNITS.
CUT FOR HUMIDITROL® - ENHANCED
DEHUMIFICATION ACCESSORY (EDA)
APPLICATIONS.
J1 - DEFROST TERMINATION TEMPERATURE
1. The J1 jumper is factory set to 50°F (10°C). This jumper can also be set to 70°F, 90°F, 100°For MAX
(21°C, 32°C, 38°C and MAX). If a jumper is not present on J1, the default termination temperature is MAX.
NOTE Colder climates could require a higher defrost termination temperature setting to maintain a clear coil.
2. If the J1 jumper is set to MAX, defrost will run maximum defrost sequence.
J3 - DEFROST AUTO
1. Defrost Auto can be set to either ON or OFF. Factory default setting is OFF. Note: If the jumper is miss
ing the default is OFF.
2. Defrost Auto is set to OFF - Defrost will run and terminate based on J1 setting.
3. Defrost Auto is set to ON - Defrost termination setting may differ from the actual J1 jumper setting. The
actual defrost termination will be determined based on the following rules:
A.. The first defrost after the unit is powered up, or the first defrost after cooling call will terminate based
on the J1 setting.
B.. The control accumulates heating runtime between defrost cycles:
Heating time between defrost is less than 50 minutes - The defrost termination temperature
will be increased for the next defrost cycle based on current termination setting. If current ter
mination setting is <70°F then the next defrost termination will be 90°F. If J1 is set at >70°F orMAX the next defrost termination will be MAX.
Heating time between defrosts is longer than 1 hour for 2 consecutive heating cycles
- The defrost termination will be decreased for the next defrost cycle. If the termination is set
at 50°F, 70°F, or 90°F, then defrost termination will follow the J1 jumper setting. If the J1 is set
to MAX, then the next defrost termination will be 90°F.
C.. If J1 is set to MAX, the system will always run at MAX when accumulated compressor OFF time
is longer than 30 minutes and ambient temperature is less than 35°F.
D.. When the ambient sensor temperature is higher than 40°F, and J1 is set to MAX, defrost termina
tion will be 90°F. If J1 is to 50°F, 70°F, 90°F or 100°F , defrost termination will follow the J1 setting.
FIGURE 7
Page 7
SL18XP1 SERIES
Page 8
STEP 2 -- ELECTRICAL (Continued) -- Field Control Wiring
The following two illustrations provide examples of control wiring connections when using a non-communicating thermostat.
For examples of control wiring in complete- or partial-communicating systems, see the iComfort®-enabled thermostat
Quick Start Guide which is provided with the thermostat.
Single−Stage
Heat Pump Control
2
W
L
Y2
Y1
O
DS
C
i−
i+
R
Air Hander Control
DS
O
5
6
L
H
DH
R
C
Y1
Y2
G
W3
3
W2
W1
ComfortSense[ 7000 Thermostats
Catalog # Y0349 or Y2081
R
On−board link
G
W2
W1
O
L
H
D
B
Y2
Y1
Low voltage thermostat
wiring
Flat metal jumper
1
C
4
T
T
1. Thermostat T terminals are used for outdoor sensor input. Sensor provides input for thermostat's outdoor
temperature display (optional).
2. R to L connection is required for this model only when used with the ComfortSense
®
7000 thermostat - (catalog
number Y0349). Resistor Kit (catalog number 47W97) is required and must be ordered separately.
3. Air handler control ships from factory with metal jumpers installed across W1, W2 and W3. For single-stage electric
heat, do not remove factory-installed metal jumper.
4. Air handler control ships from factory with metal jumpers installed across W1, W2 and W3. For two-stage electric
heat, remove factory-installed metal jumper between W1 and W2. Then, connect thermostat wire between the air
handler control's W2 and the thermostat's W2 terminal.
5. Cut on-board link (clippable wire) from R-O HEAT PUMP for heat pump applications.
6. Cut on-board link (clippable wire) DS-R for Humiditrol
®
or Harmony III applications. This will slow the indoor blower
motor to the lowest speed setting. See air handler installation instruction or product specification bulletin for lowest
fan speed information.
FIGURE 8
Page 8
Page 9
Single−Stage
Heat Pump Control
W
L
Y2
Y1
O
DS
Furnace Control
DS
O
4
L
H
DH
R
ComfortSense[ 7000 Thermostats
Catalog # Y0349 or Y2081
R
3
G
W2
W1
O
L
H
On−board link
Low voltage thermostat
wiring
2
C
i−
C
Y1
Y2
G
i+
R
W2
Y2
Y1
C
D
B
1
T
W1
T
1. Thermostat T terminals are used for outdoor sensor input. Sensor provides input for thermostat's outdoor tempera
ture display (optional).
2. R to L connection is required for this model only when used with the ComfortSense
®
7000 thermostat - (catalog
number Y0349). Resistor Kit (catalog number 47W97) is required and must be ordered separately.
3. Cut on-board link W951 (clippable wire) from R-O HEAT PUMP for heat pump applications.
4. Cut on−board link (clippable wire) DS−R for Humiditrol
®
or Harmony III applications. This will slow the indoor
blower motor to the lowest speed setting. See furnace installation instruction or product specification bulletin for
lowest fan speed information.
NOTE - To use furnace to temper air during defrost, wire optional temper kit (67M41) between the W terminal of the heat
pump control (A175) and the W1 terminal on the furnace control. The temper kit cycles the furnace on and off during the
defrost cycle. It also protects the heat pump compressor from high pressures during defrost.
FIGURE 9
Page 9
SL18XP1 SERIES
Page 10
STEP 3 -- REFRIGERANT PIPING —
Flushing Existing Line Set & Indoor Coil
Flush the existing line set per the following instruc
tions. For more information, refer to the Installation
and Service Procedures manual available on
LennoxPROS.com. CAUTION - DO NOT attempt to
flush and re-use existing line sets or indoor coil
when the system containscontaminants (i.e., com
pressor burn out).
NOTE - When installing refrigerant lines longer than 50
feet, refer to the Refrigerant Piping Design and Fabrication
Guidelines manual available on LennoxPROS.com (Corp.
9351-L9), or contact the Technical Support Department
Product Application group for assistance.
NOTE - For new or replacement line set installation refer to
Service and Application Note - Corp 9112-L4 (C-91-4).
TABLE 1
REFRIGERANT LINE SET — INCHES (MM)
Model
-024 and
-030
-036, -042
and -048
Liquid
Line
3/8” (10)3/4” (19)
3/8” (10)7/8” (22)
Vapor
Line
L15 line set sizes are depen
dent on matching system com
ponents. See SL18XP1 Engi
neering Handbook to determine
correct line set sizes.
L15
Line Sets
Feet (Meters)
WARNING
When using a high pressure gas such as
nitrogen to pressurize a refrigeration or air
conditioning system, use a regulator that
can control the pressure down to 1 or 2
psig (6.9 to 13.8 kPa).
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant
must be used and recovered responsibly.
Failure to follow this warning may result in personal injury
or death.
WARNING
Fire, Explosion and Personal Safety Haz
ard. Failure to follow this warning could re
sult in damage, personal injury or death.
Never use oxygen to pressurize or purge
refrigeration lines. Oxygen, when exposed
to a spark or open flame, can cause fire
and/or an explosion, that could result in
property damage, personal injury or death.
-0603/8” (10)
NOTE — Some applications may require a field-provided 7/8” to
1-1/8” adapter.
1-1/8”
(29)
Field-Fabricated
IMPORTANT !
If this unit is being matched with an approved line
set or indoor unit coil that was previously charged
with mineral oil, or if it is being matched with a coil
which was manufactured before January of 1999,
the coil and line set must be flushed prior to installa
tion. Take care to empty all existing traps. Polyol es
ter (POE) oils are used in Lennox units charged with
HFC-410A refrigerant. Residual mineral oil can act
as an insulator, preventing proper heat transfer. It
can also clog the expansion device and reduce sys
tem performance and capacity.
Failure to properly flush the system per this instruc
tion and the detailed Installation and Service Proce
dures manual will void the warranty.
WARNING
Polyol ester (POE) oils used with HFC-410A
refrigerant absorb moisture very quickly. It is very
important that the refrigerant system be kept closed
as much as possible. DO NOT remove line set caps
or service valve stub caps until you are ready to make
connections.
IMPORTANT !
Some scroll compressors have an internal vacuum
protection devices that will unload scrolls when
suction pressure goes below 20 psig. A hissing
sound will be heard when the compressor is run
ning unloaded. The protection device will reset
when pressure in system rises above 40 psig. This
is normal operation. DO NOT replace compressor.
1. On fully cased coils, remove the coil access and plumbing panels.
2. Remove any shipping clamps from the liquid line and distributor as
sembly.
3. Using two wrenches, disconnect liquid line from liquid line orifice hous
ing. Take care not to twist or damage distributor tubes during this pro
cess.
4. Remove and discard fixed orifice, valve stem assembly (if present)
and Teflon® washer as illustrated above.
5. Use a field-provided fitting to temporarily reconnect the liquid line to the
indoor unit's liquid line orifice housing.
(UNCASED COIL SHOWN)
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
TEFLON® RING
FIXED ORIFICE
REMOVE AND DISCARD
WHITE TEFLON
(IF PRESENT)
®
SEAL
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
REMOVAL PROCEDURE
OR
BRASS NUT
1B
TWO-PIECE PATCH PLATE
(UNCASED COIL ONLY)
CONNECT GAUGES AND EQUIPMENT FOR
FLUSHING PROCEDURE
2
CYLINDER CONTAINING
CLEAN HCFC-22* TO BE
USED FOR FLUSHING
(Positioned to deliver liquid
A
refrigerant)
1
VAPOR LINE
SERVICE VALVE
EXISTING
INDOOR
UNIT
LIQUID LINE SERVICE
VALV E
RECOVERY
CYLINDER
VAPOR
LIQUID
OUTDOOR
B
NEW
UNIT
OPENED
C
D
RECOVERY MACHINE
A. HCFC-22 cylinder with clean refrigerant* (positioned to deliver liquid
refrigerant) to the vapor service valve.
B. HCFC-22 gauge set (low side) to the liquid line valve.
C. HCFC-22 gauge set center port to inlet on the recovery machine with an
empty recovery tank connected to the gauge set.
D. Connect recovery tank to recovery machine per machine instructions.
1. On fully cased coils, remove the coil access and plumbing panels.
2. Remove any shipping clamps from the liquid line and distributor
assembly.
3. Disconnect the equalizer line from the expansion valve equalizer
line fitting on the vapor line.
4. Remove the vapor line sensing bulb.
5. Disconnect the liquid line from the expansion valve at the liquid line
assembly.
6. Disconnect the expansion valve from the liquid line orifice housing.
Take care not to twist or damage distributor tubes during this
process.
7. Remove and discard expansion valve and the two Teflon® rings.
8. Use a field-provided fitting to temporarily reconnect the liquid line to
the indoor unit's liquid line orifice housing.
FLUSHING LINE SET
The line set and indoor unit coil must be flushed with at least the same
3
amount of clean refrigerant* that previously charged the system.
Check the charge in the flushing cylinder before proceeding.
1. Set the recovery machine for liquid recovery and start the recovery
machine. Open the gauge set valves to allow the recovery
machine to pull a vacuum on the existing system line set and indoor
unit coil.
2. Position the cylinder of clean HCFC-22* for delivery of liquid
refrigerant and open its valve to allow liquid refrigerant to flow into
the system through the vapor line valve. Allow the refrigerant to
pass from the cylinder and through the line set and the indoor unit
coil before it enters the recovery machine.
3. After all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the HCFC-22
vapor is recovered. Allow the recovery machine to pull the system
down to 0.
4. Close the valve on the inverted HCFC-22 cylinder and the gauge
set valves. Pump the remaining refrigerant out of the recovery
machine and turn the machine off.
®
LINE
LIQUID
LINE
*IMPORTANT - Clean refrigerant is any refrigerant in a system that has not had compressor burn out. If the system
has experienced burn out, it is recommended that the existing line set and indoor coil be replaced.
ends of the refrigerant lines square (free from nicks or
dents) and debur the ends. The pipe must remain
round. Do not crimp end of the line.
CUT AND DEBUR
LINE SET SIZE MATCHES
SERVICE VALVE CONNECTION
SERVICE VALVE
COPPER TUBE
REDUCER
CONNECTION
STUB
REFRIGERANT LINE
LINE SET SIZE IS SMALLER
THAN CONNECTION
CAP AND CORE REMOVAL
Remove service cap and core from both the vapor
2
and liquid line service ports.
SERVICE PORT CAP
SERVICE PORT
CORE
LIQUID LINE SERVICE VALVE
SERVICE PORT
CORE
SERVICE
PORT CAP
VAPOR LINE
DO NOT CRIMP SERVICE VALVE
CONNECTOR WHEN PIPE IS
SMALLER THAN CONNECTION
SERVICE VALVE
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING
LIQUID AND VAPOR LINE SERVICE VALVES
3
AConnect gauge set low pressure side to liquid line service valve (service port).
BConnect gauge set center port to bottle of nitrogen with regulator.
CWith valve core removed from the vapor line service port, nitrogen flow will have an exit point.
HIGHLOW
ATTACH
GAUGES
VAPOR LINE SERVICE PORT MUST BE OPEN
AND SERVICE PORT CORE REMOVED TO AL
LOW EXIT POINT FOR NITROGEN FLOW
VAPOR LINE
INDOOR
UNIT
LIQUID LINE
C
LIQUID LINE SERVICE
VAPOR LINE
SERVICE
VALV E
VALV E
A
B
OUTDOOR
UNIT
NITROGEN
FIGURE 11
Page 12
Page 13
CAUTION
Brazing alloys and flux contain materials which are
hazardous to your health.
Avoid breathing vapors or fumes from brazing
operations. Perform operations only in well-ventilated
areas.
Wear gloves and protective goggles or face shield to
protect against burns.
Wash hands with soap and water after handling brazing
alloys and flux.
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap water-saturated cloths around service valve bodies and copper tube stubs. Use
4
additional water-saturated cloths under the valve body to protect the base paint.
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration
5
gauge set into the valve stem port connection on the liquid service
valve and out of the vapor valve stem port. See steps 3A, 3B and 3C
on previous page and below for manifold gauge setup.
BRAZE LINE SET
Cloths must remain water-saturated throughout the brazing and
6
cool-down process.
A. Braze liquid line to liquid line service valve.
B. Braze vapor line to vapor service valve.
FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE
may result if you do not wrap a water-saturated cloth around
both liquid and vapor line service valve bodies and copper
tube stub while brazing the line set! The braze, when
complete, must be quenched with water to absorb any
residual heat.
Do not open service valves until refrigerant lines and
indoor coil have been leak-tested and evacuated. Refer
to Installation and Service Procedures manual found on
DAVENET.
WARNING
Danger of fire. Bleeding the refrigerant
charge from only the high side may result
in pressurization of the low side shell and
suction tubing. Application of a brazing
torch to a pressurized system may result
in ignition of the refrigerant and oil
mixture. Check the high and low
pressures before applying heat.
WARNING
VAPOR LINE
WATER-SATURATED CLOTHS
IMPORTANT !
Allow braze joint to cool. Apply additional
water-saturated cloths to help cool brazed
joints. Do not remove water-saturated cloths
until piping has cooled. Temperatures above
250ºF will damage valve seals.
LIQUID LINE
6B
6A
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
VAPOR LINE SERVICE PORT
MUST BE OPEN AND SERVICE
PORT CORE REMOVED TO AL
LOW EXIT POINT FOR NITRO
GEN FLOW
PREPARATION FOR NEXT STEP
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water-saturated cloths to both
7
services valves to cool piping. Once piping is cool, remove all water-saturated cloths.
WATER SATURATED
FIGURE 12
Page 13
CLOTHS
SL18XP1 SERIES
Page 14
STEP 6 -- INSTALLING INDOOR EXPANSION VALVE
THIS OUTDOOR UNIT IS DESIGNED FOR USE IN SYSTEMS THAT USE A CHECK EXPANSION VALVE METERING DEVICE. SEE THE LENNOX SL18XP1
PRODUCT SPECIFICATION BULLETIN (EHB) FOR APPROVED EXPANSION VALVE KITS AND APPLICATION INFORMATION.
THE EXPANSION VALVE UNIT CAN BE INSTALLED INTERNAL OR
EXTERNAL TO THE INDOOR COIL. IN APPLICATIONS WHERE AN
TWO PIECE
PATCH PLATE
(UNCASED
COIL ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE
FITTING (SEE
EQUALIZER LINE
INSTALLATION FOR
FURTHER DETAILS)
SENSING BULB INSULATION IS REQUIRED
IF MOUNTED EXTERNAL TO THE COIL
CASING. SEE SENSING BULB
INSTALLATION FOR BULB POSITIONING.
(Uncased Coil Shown)
LIQUID LINE
ORIFICE
HOUSING
STUB
END
TEFLON
RING
EQUALIZER
LINE
EXPANSION
VALV E
®
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
VAPOR
LINE
UNCASED COIL IS BEING INSTALLED IN A FIELD-PROVIDED
PLENUM, INSTALL THE CHECK EXPANSION VALVE IN A MANNER
WHICH PROVIDES ACCESS FOR FIELD SERVICING OF THE
EXPANSION VALVE. REFER TO BELOW ILLUSTRATION FOR
REFERENCE DURING INSTALLATION OF EXPANSION VALVE
UNIT.
®
TEFLON
RING
A. REMOVE THE FIELD-PROVIDED FITTING THAT TEMPORARILY RECON
NECTED THE LIQUID LINE TO THE INDOOR UNIT'S DISTRIBUTOR ASSEM
SENSING
LINE
LIQUID LINE
BLY.
B. INSTALL ONE OF THE PROVIDED TEFLON
STUBBED END OF THE EXPANSION VALVE AND LIGHTLY LUBRICATE THE
CONNECTOR THREADS AND EXPOSE SURFACE OF THE TEFLON
WITH REFRIGERANT OIL.
C. ATTACH THE STUBBED END OF THE EXPANSION VALVE TO THE LIQUID
LINE ORIFICE HOUSING. FINGER TIGHTEN AND USE AN APPROPRIATE
LY SIZED WRENCH TO TURN AN ADDITIONAL 1/2 TURN CLOCKWISE AS
ILLUSTRATED IN THE FIGURE ABOVE, OR 20 FT-LB.
D. PLACE THE REMAINING TEFLON
OF THE EXPANSION VALVE. LIGHTLY LUBRICATE CONNECTOR
THREADS AND EXPOSE SURFACE OF THE TEFLON
ERANT OIL.
E. ATTACH THE LIQUID LINE ASSEMBLY TO THE EXPANSION VALVE. FIN
GER TIGHTEN AND USE AN APPROPRIATELY SIZED WRENCH TO TURN
AN ADDITIONAL 1/2 TURN CLOCKWISE AS ILLUSTRATED IN THE FIGURE
ABOVE OR 20 FT-LB.
9 O'CLOCK TO
3 O'CLOCK
BULB
12
®
BULB
9
WASHER AROUND THE OTHER END
12
11
10
8
7
®
RINGS AROUND THE
ON LINES SMALLER THAN
7/8”, MOUNT SENSING
BULB BETWEEN THE 9 AND
3 O'CLOCK POSITIONS.
1
2
4
5
6
®
RING WITH REFRIG
3
1/2 TURN
®
RING
SENSING BULB INSTALLATION
A. ATTACH THE VAPOR LINE SENSING BULB IN THE PROPER
ORIENTATION AS ILLUSTRATED TO THE RIGHT USING THE
CLAMP AND SCREWS PROVIDED.
NOTE - CONFIRM PROPER THERMAL CONTACT BETWEEN
VAPOR LINE AND CHECK EXPANSION BULB BEFORE INSU
LATING THE SENSING BULB ONCE INSTALLED.
B. CONNECT THE EQUALIZER LINE
FROM THE EXPANSION VALVE TO
THE EQUALIZER VAPOR PORT ON
THE VAPOR LINE. FINGER
TIGHTEN THE FLARE NUT PLUS
1/8 TURN (7 FT-LBS) AS ILLUS
TRATED BELOW.
10
9
11
12
8
7
6
EQUALIZER LINE INSTALLATION
REMOVE AND DISCARD EITHER THE FLARE SEAL CAP OR FLARE
NUT WITH COPPER FLARE SEAL BONNET FROM THE EQUALIZER
LINE PORT ON THE VAPOR LINE AS ILLUSTRATED IN THE FIGURE
TO THE RIGHT.
1/8 TURN
1
2
3
4
5
VAPOR LINE
FLARE SEAL CAP
FIGURE 13
BULB
ON 7/8” AND LARGER LINES,
MOUNT SENSING BULB AT
EITHER THE 4 OR 8 O'CLOCK
POSITION. NEVER MOUNT
12
BULB
OR
THE SENSING BULB ON
BOTTOM OF LINE.
NOTE - NEVER MOUNT
THE SENSING BULB ON
BOTTOM OF LINE.
FLARE NUT
COPPER FLARE
SEAL BONNET
MALE BRASS EQUALIZER
LINE FITTING
VAPOR LINE
Page 14
Page 15
STEP 7 -- LEAK TEST
HIGHLOW
MANIFOLD GAUGE SET
OUTDOOR UNIT
B
TO VAPOR
SERVICE VALVE
NOTE - Position
canister to deliver
liquid refrigerant.
NITROGEN
CONNECT GAUGE SET
AConnect the high pressure hose of an HFC-410A manifold gauge set to the vapor valve service port.
1
2
NOTE — Normally, the high pressure hose is connected to the liquid line port. However, connecting it
to the vapor port better protects the manifold gauge set from high pressure damage.
BWith both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of
the manifold gauge set.
NOTE — Later in the procedure, the HFC-410A container will be replaced by the nitrogen container.
TEST FOR LEAKS
After the line set has been connected to the indoor and outdoor units, check the line set connections
and indoor unit for leaks. Use the following procedure to test for leaks:
AWith both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of
the manifold gauge set. Open the valve on the HFC-410A cylinder (vapor only).
BOpen the high pressure side of the manifold to allow HFC-410A into the line set and indoor unit.
Weigh in a trace amount of HFC-410A. [A trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure.] Close the valve on the HFC-410A cylinder and the valve on
the high pressure side of the manifold gauge set. Disconnect the HFC-410A cylinder.
CConnect a cylinder of nitrogen with a pressure regulating valve to the center port of the manifold
gauge set.
DAdjust nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge
set in order to pressurize the line set and the indoor unit.
EAfter a few minutes, open one of the service valve ports and verify that the refrigerant added to the
system earlier is measurable with a leak detector.
FAfter leak testing, disconnect gauges from service ports.
HFC-410A
A
FIGURE 14
Page 15
SL18XP1 SERIES
Page 16
STEP 8 -- EVACUATION
Evacuating the system of non-condensables is critical for proper operation of the unit. Non-condensables are defined as any
gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Noncondensables and water suction combine with refrigerant to produce substances that corrode copper piping and com
pressor parts.
WARNING
Danger of Equipment Damage. Avoid deep vacuum system operation. Do not use the system compressor to
evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by
deep vacuum system operation will void warranty.
MANIFOLD
LOW
GAUGE SET
HIGH
LINE SET AND INDOOR COIL
CONNECT GAUGE SET
NOTE — Remove cores from service valves (if not al
ready done).
AConnect low side of manifold gauge set
with 1/4 SAE in-line tee to vapor line
service valve
BConnect high side of manifold gauge
set to liquid line service valve
CConnect micron gauge available
connector on the 1/4 SAE in-line tee.
DConnect the vacuum pump (with
vacuum gauge) to the center port of the
manifold gauge set. The center port line
will be used later for both the HFC-410A
and nitrogen containers.
NITROGEN
OUTDOOR
UNIT
A
A34000 1/4 SAE TEE WITH
SWIVEL COUPLER
500
C
MICRON
GAUGE
TO VAPOR
SERVICE VALVE
HFC-410A
(INVERTED)
VACUUM PUMP
B
FIGURE 15
EVACUATE LINE SET AND INDOOR COIL
The unit is shipped with a factory refrigerant charge. The
liquid and vapor line valves were closed after final testing
at the factory. Do not operate these valves until the line set
and indoor coil have been evacuated and leak checked, or
the charge is lost.
NOTE - Do not use any portion of the factory charge for
purging or leak testing. The factory charge is for filling the
system only after a complete evacuation and leak check
has been performed.
Line set and indoor coil should be evacuated using the rec
ommended deep vacuum method of 500 microns. If deep
vacuum equipment is not available, the alternate triple
evacuation method may be used by following the specified
procedure.
TO LIQUID LINE
SERVICE VALVE
D
RECOMMEND
MINIMUM 3/8” HOSE
If vacuum must be interrupted during the evacuation pro
cedure, always break vacuum with dry nitrogen.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump cap
able of pulling a vacuum to 500 microns and a vacuum
gauge capable of accurately measuring this vacuum level.
The deep vacuum method is the most positive way of as
suring a system is free of air and water.
Watch the vacuum gauge as the system is pulling down.
The response of the gauge is an indicator of the condition
of the system (refer to figure 15).
With no leaks in the system, allow the vacuum pump to run
for 30 minutes minimum at the deep vacuum level.
Page 16
Page 17
Deep Vacuum Gauge Response and
System Conditions
FIGURE 16
Triple Evacuation Method
The triple evacuation method should only be used when
system does not contain any water in liquid form and vacu
um pump is only capable of pulling down to 28 inches of
mercury (711mm Hg). Refer to figure 17 and proceed as
follows:
Triple Evacuation Sequence
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
4. Close nitrogen valve and allow system to stand for one
hour. During this time, dry nitrogen will diffuse
throughout the system, absorbing moisture.
5. Repeat this procedure as indicated in figure 17.
6. After the final evacuate sequence, confirm there are
no leaks in the system. If a leak is found, repeat the en
tire process after repair is made.
7. Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not
rise above 500 microns (29.9 inches of mercury) within
a 20*minute period after shutting off the vacuum
pump and closing the manifold gauge valves.
8. Disconnect the manifold hose from the vacuum pump
and connect it to an inverted cylinder of HFC*410A
positioned to deliver liquid refrigerant. Open the mani
fold gauge valve 1 to 2 psig in order to release the va
cuum in the line set and indoor unit.
9. Perform the following:
Close manifold gauge valves.
Shut off HFC*410A cylinder.
Slowly open the service valves.
Refer to the charging sticker on the unit to com
plete the outdoor unit installation.
Charging
The SL18XP1 unit is factory-charged with enough
HFC-410A refrigerant to accommodate a 15-foot length of
refrigerant piping. Charge should be checked and adjusted
using the tables provided on the charging procedure stick
er on the unit access panel. Detailed information is given in
the SL18XP1 Installation and Service Procedures manual,
which is available on DaveNet.
Heat Pump Control -- Defrost Operation
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
CHECK FOR TIGHT, DRY SYSTEM (IF IT HOLDS DEEP VACUUM)
CHARGE SYSTEM
FIGURE 17
1. Pull system down to 28 inches of mercury (711mm Hg)
and allow pump to continue operating for an additional
15 minutes.
2. Close manifold valves or valve at vacuum pump and
shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system
and fill with nitrogen until system pressure is 2 psig.
A full description of the heat pump control can be found in
the detailed installation and service procedure manual
available on DaveNet. The defrost termination pins (E47)
must be set on the heat pump control prior to starting the
system to ensure proper defrost operation.
The heat pump control (A175) measures differential tem
peratures to detect when the system is performing poorly
because of frost build-up on the outdoor coil. The heat
pump control self-calibrates when the defrost system
starts and after each system defrost cycle. The heat pump
control monitors ambient temperature, outdoor coil tem
perature, and total run-time to determine when a defrost
cycle is required. The coil temperature sensor is designed
with a spring clip to allow mounting to the outside coil tub
ing. The location of the coil sensor is important for proper
defrost operation.
NOTE - The heat pump control accurately measures the
performance of the system as frost accumulates on the
outdoor coil. This typically will translate into longer running
time between defrost cycles as more frost accumulates on
the outdoor coil before the heat pump control initiates de
frost cycles.
Page 17
SL18XP1 SERIES
Page 18
Homeowner Information
CAUTION
Before attempting to perform any service or mainte
nance, turn the electrical power to unit OFF at discon
nect switch.
In order to ensure peak performance, your system must be
properly maintained. Clogged filters and blocked airflow
prevent your unit from operating at its most efficient level.
The system should be inspected and serviced before each
cooling and heating season by a licensed professional
HVAC service technician (or equivalent).
Heat Pump Operation
Your new Lennox heat pump has several characteristics
that you should be aware of:
Heat pumps satisfy heating demand by delivering large
amounts of warm air into the living space. This is quite
different from gas‐ or oil‐fired furnaces or an electric fur
nace which deliver lower volumes of considerably hotter
air to heat the space.
Do not be alarmed if you notice frost on the outdoor coil
in the winter months. Frost develops on the outdoor coil
during the heating cycle when temperatures are below
45°F (7°C). An electronic control activates a defrost
cycle lasting 5 to 15 minutes at preset intervals to clear
the outdoor coil of the frost.
During the defrost cycle, you may notice steam rising
from the outdoor unit. This is a normal occurrence. The
thermostat may engage auxiliary heat during the defrost
cycle to satisfy a heating demand; however, the unit will
return to normal operation at the conclusion of the de
frost cycle.
Homeowner Maintenance
The following maintenance may be performed by the
homeowner.
Contact a licensed professional HVAC technician to
schedule inspection and maintenance appointments for
your equipment before each heating and cooling sea
son.
Check the indoor unit filter each month and replace the
filter, if necessary.
Have your Lennox dealer show you where your indoor
unit filter is located. It will be either at the indoor unit (in
stalled internal or external to the cabinet) or behind a re
turn air grille in the wall or ceiling. Check the filter monthly
and clean or replace it as needed.
Disposable filters should be replaced with a filter of the
same type and size.
Check the indoor unit drain line for obstructions monthly.
The indoor coil is equipped with a drain pan to collect
condensate formed as your system removes humidity
from the inside air. Have your dealer show you the loca
tion of the drain line and how to check for obstructions.
(This would also apply to an auxiliary drain, if installed.)
Check the area around the outdoor unit monthly and re
move any obstructions that may restrict airflow to the
outdoor unit. This would include grass clippings, leaves,
or papers that may have settled around the unit.
Trim shrubbery away from the unit and periodically
check for debris which collects around the unit.
During the winter months, keep the snow level below the
louvered panels.
NOTE - The filter and all access panels must be in place
any time the unit is in operation. If you are unsure about the
filter required for your system, call your Lennox dealer for
assistance.
IMPORTANT !
Sprinklers and soaker hoses should not be installed
where they could cause prolonged exposure to the
outdoor unit by treated water. Prolonged exposure
of the unit to treated water (i.e., sprinkler systems,
soakers, waste water, etc.) will corrode the surface
of steel and aluminum parts, diminish performance
and affect longevity of the unit.
Thermostat Operation
See the thermostat homeowner manual for instructions on
how to operate your thermostat.
Pre-Service Check
If your system fails to operate, check the following before
calling for service:
Verify room thermostat settings are correct.
Verify that all electrical disconnect switches are ON.
Check for any blown fuses or tripped circuit breakers.
Verify unit access panels are in place.
Verify air filter is clean.
If service is needed, locate and write down the unit model
number and have it handy before calling.
Extended Power Outage
The heat pump is equipped with a compressor crankcase
heater which protects the compressor during cold weather
operation.
If power to your unit has been interrupted for several hours
or more, set the room thermostat selector to the EMER
GENCY HEAT setting to obtain temporary heat without the
risk of serious damage to the heat pump.
In EMERGENCY HEAT mode, all heating demand is satis
fied by auxiliary heat; heat pump operation is locked out.
After a six‐hour compressor crankcase warm‐up period,
the thermostat can be switched to the HEAT setting and
normal heat pump operation may resume.
Professional Maintenance
Your heating and air conditioning system should be inspec
ted and maintained twice each year (before the start of the
cooling and heating seasons) by a licensed professional
HVAC technician. You can expect the technician to check
the following items. These checks may only be conduc
ted by a licensed professional HVAC technician.
Outdoor Unit
1. Inspect component wiring for loose, worn or damaged
connections. Also check for any rubbing or pinching of
wires. Confirm proper voltage plus amperage of out
door unit.
Page 18
Page 19
2. Check the cleanliness of outdoor fan and blade condi
tion (cracks) and clean or replace them, if necessary.
3. Inspect base pan drains for debris and clean as neces
sary.
4. Inspect the condition of refrigerant piping and confirm
that pipes are not rubbing copper-to-copper. Also,
check the condition of the insulation on the refrigerant
lines. Repair, correct, or replace as necessary.
5. Test capacitor. Replace as necessary.
6. Inspect contactor contacts for pitting or burn marks.
Replace as necessary.
7. Check outdoor fan motor for worn bearings/bushings.
Replace as necessary.
2. Inspect and clean or replace air filters in indoor unit.
3. Check the cleanliness of indoor blower and clean
blower, if necessary.
4. Inspect the indoor coil drain pans and condensate
drains for rust, debris, obstructions, leaks or cracks.
Pour water in pans to confirm proper drainage from the
pan through to the outlet of the pipe. Clean or replace
as necessary.
5. Inspect and clean indoor coil, if necessary.
6. Inspect the condition of the refrigerant lines and con
firm that pipes are not rubbing copper-to-copper. Also,
ensure that refrigerant pipes are not being affected by
indoor air contamination. Check condition of insulation
on the refrigerant lines. Repair, correct, or replace as
necessary.
8. Inspect and clean outdoor coils, if necessary and note
any damage to coils or signs of leakage.
NOTICE !
Failure to follow instructions will cause damage to
the unit.
This unit is equipped with an aluminum coil. Alu
minum coils may be damaged by exposure to solu
tions with a pH below 5 or above 9. The aluminum
coil should be cleaned using potable water at a
moderate pressure (less than 50psi). If the coil can
not be cleaned using water alone, Lennox recom
mends use of a coil cleaner with a pH in the range of
5 to 9. The coil must be rinsed thoroughly after
cleaning.
In coastal areas, the coil should be cleaned with
potable water several times per year to avoid corro
sive buildup (salt).
Indoor Unit (Air Handler or Furnace)
1. Inspect component wiring for loose, worn or damaged
connections. Confirm proper voltage plus amperage
of indoor unit.
7. Inspect the duct system for leaks or other problems.
Repair or replace as necessary.
8. Check for bearing/bushing wear on indoor blower mo
tor. Replace as necessary.
9. If your heat pump is matched with a gas- or oil-fired fur
nace for auxiliary heating, indoor unit service will also
include inspection and cleaning of the burners, and a
full inspection of the gas valve, heat exchanger and
flue (exhaust) system.
General System Test with System Operating
1. Your technician should perform a general system test.
He will turn on the air conditioner to check operating
functions such as the startup and shutoff operation.
He will also check for unusual noises or odors, and
measure indoor/outdoor temperatures and system
pressures as needed. He will check the refrigerant
charge per the charging sticker information on the out
door unit.
2. Verify that system total static pressure and airflow set
tings are within specific operating parameters.
3. Verify correct temperature drop across indoor coil.
Page 19
SL18XP1 SERIES
Page 20
IMPORTANT
This performance check is ONLY valid on systems that have clean indoor and outdoor coils, proper airflow over coils,
and correct system refrigerant charge. All components in the system must be functioning properly to correctly perform
compressor operational check. (Accurate measurements are critical to this test as indoor system loading and outdoor
ambient can affect variations between low and high capacity readings).
SL18XP1 Start-Up and Performance Checklist
Customer Address
Indoor Unit ModelSerial
Outdoor Unit ModelSerial
Solar Module Mfg and ModelSerial
Notes:
START-UP CHECKS
Refrigerant Type:
Rated Load AmpsActual AmpsRated VoltsActual Volts
Condenser Fan Full Load AmpsActual Amps:
COOLING MODE
Vapor Pressure: Liquid Pressure:
Supply Air Temperature:Ambient Temperature:Return Air Temperature:
HEATING MODE
Vapor Pressure: Liquid Pressure:
Supply Air Temperature:Ambient Temperature:Return Air Temperature:
System Refrigerant Charge (Refer to manufacturer's information on unit or installation instructions for required
subcooling and approach temperatures.)
Subcooling:
Saturated Condensing Temperature (A)
minus Liquid Line Temperature (B)
Approach:
Liquid Line Temperature (A)
minus Outdoor Air Temperature (B)
Indoor Coil Temp. Drop (18 to 22°F)
Return Air Temperature (A)
minus Supply Air Temperature (B)
A—B=SUBCOOLING
A—B=APPROACH
A—B= COIL TEMP DROP
Page 20
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.