This SL18XC1 outdoor air conditioner with all-aluminum
coil is designed for use with HFC-410A refrigerant only.
This unit must be installed with an approved indoor air han
dler or coil. See the Lennox SL18XC1 Product Specifica
tions bulletin (EHB) for approved indoor component match
ups.
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
NOTICE !
For more in-depth information, consult the Installa
tion and Service Procedures manual, available as
Corp. 1405-L10 on DaveNet or through the Technical
Support department at 800-453-6669.
INSTRUCTIONS
Dave Lennox Signature
Collection SL18XC1 System
AIR CONDITIONERS
507353-01
7/2018
WARNING
Improper installation, adjustment, alteration, service or
maintenance can cause property damage, personal inju
ry or loss of life.
Installation and service must be performed by a licensed
professional installer (or equivalent) or service agency.
CAUTION
Before attempting to perform any service or mainte
nance, turn the electrical power to unit OFF at discon
nect switch.
®
STEP 1 -- SETTING THE UNIT -- Clearances
CLEARANCE ON ALL SIDES — INCHES (MILLIMETERS)
6 (152)
CONTROL
PANEL ACCESS
LOCATION
24
(610)
30 (762)
12 (305)
36 (914)
MINIMUM CLEARANCE BETWEEN TWO UNITS
NOTES:
S Clearance to access panel must be 30
inches (762mm).
S Clearance to one of the other three
sides must be 36 inches (914mm).
S Clearance to one of the remaining two
sides may be 12 inches (305mm) and
the final side may be 6 inches
(152mm).
ACCESS PANEL
LINE SET
CONNECTIONS
MINIMUM CLEARANCE
ABOVE UNIT
48 (1219)
REAR VIEW OF UNIT
FIGURE 1
Page 1
Page 2
STEP 1 -- SETTING THE UNIT (Continued) -- Dimensions / Placement
UNIT DIMENSIONS - INCHES (MM)
39.40”
(1003)
DISCHARGE AIR
ELECTRICAL INLETS
[-030 THROUGH -042]
SUCTION LINE
INLET
LIQUID
LINE
INLET
41 (1040)
[-024, -048, -060]
47 (1194)
18.60”
(470)
8.00” (203)
35.50”
(902)
SIDE VIEW
UNIT SUPPORT
FEET
3-1/8
16-7/8
(429)
8-3/4
(222)
(79)
WARNING
To prevent personal injury, as well as damage to panels,
unit or structure, observe the following:
While installing or servicing this unit, carefully stow all
removed panels so that the panels will not cause injury
to personnel, objects or nearby structures. Also, take
care to store panels where they will not be subject to
damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any
weather conditions (especially wind) that may cause
panels to be blown around and damaged.
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and use protective
clothing.
30-3/4
(781)
1 (25)
26-7/8
(683)
3-3/4 (95)
4-5/8
(117)
ACCESS VIEW
BASE WITH
ELONGATED LEGS
NOTICE !
Roof Damage!
This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil, causing the
rubber to degrade. Failure to follow this notice
could result in damage to roof surface.
IMPORTANT !
Exhaust vents from dryers, water heaters and
furnaces should be directed away from the outdoor
unit. Prolonged exposure to exhaust gases and the
chemicals contained within them may cause
condensation to form on the steel cabinet and other
metal components of the outdoor unit. This will
diminish unit performance and longevity.
Page 2
Page 3
PLACEMENT
INSTALL UNIT AWAY
FROM WINDOWS
TWO 90_ ELBOWS INSTALLED IN LINE SET
WILL REDUCE LINE SET VIBRATION
FIGURE 2
SLAB MOUNTING
Install unit level or, if on a slope, maintain slope tolerance of 2
degrees (or 2 inches per 5 feet [50 mm per 1.5 m]) away from
building structure.
BUILDING
STRUCTURE
DISCHARGE AIR
STABILIZING UNIT ON UNEVEN SURFACES
Slab Mounting
#10 X 1/2” LONG
SELF-DRILLING
SHEET METAL
SCREWS
STABILIZING BRACKET
(18 GAUGE METAL — 2”
WIDTH; HEIGHT AS
REQUIRED)
#10 X 1-1/4” LONG
HEX HD SCREW AND
FLAT WASHER
Concrete slab — use two
plastic anchors (hole drill 1/4”)
CORNER POST
Deck Top Mounting
Stabilizing bracket - 18 gauge metal.
2” (50.8mm) width; height as required.
Bent to form right angle as shown.
SAME FASTENERS AS
SLAB SIDE MOUNTING.
COIL
BASE PAN
MOUNTING
SLAB
GROUND LEVEL
FIGURE 3
ELEVATED SLAB MOUNTING USING FEET
EXTENDERS
2” (50.8MM) SCH 40
FEMALE THREADED
ADAPTER
2” (50.8MM)
SCH 40 MALE
THREADED
ADAPTER
LEG DETAIL
Use additional 2” SCH 40 male
threaded adapters which can
be threaded into the female
threaded adapters to make
additional adjustments to the
level of the unit.
BASE
FIGURE 4
MINIMUM ONE
PER SIDE
FOR EXTRA
STABILITY
Install one bracket per side (minimum). For extra stability, install
two brackets per side, two inches (51mm) from each corner.
IMPORTANT !
Unit Stabilizer Bracket (field-provided):
Always use stabilizers when unit is raised above
the factory height.
(Elevated units could become unstable in gusty
wind conditions.)
Stabilizers may be used on any unit installed on
unstable and uneven surfaces.
FIGURE 5
STEP 2 -- ELECTRICAL -- Circuit Sizing
and Wire Routing
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current
Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
Page 3
SL18XC1 SERIES
Page 4
24VAC TRANSFORMER
Use the transformer provided with the furnace or air han
dler for low‐voltage control power (24VAC - 40 VA mini
mum).
WARNING
Electric Shock Hazard. Can cause injury
or death. Unit must be grounded in
accordance with national and local
codes.
Line voltage is present at all components
when unit is not in operation on units with
single‐pole contactors. Disconnect all
remote electric power supplies before
opening access panel. Unit may have
multiple power supplies.
IMPORTANT !
If unit is equipped with a crankcase heater, it should
be energized 24 hours before unit start-up to pre
vent compressor damage as a result of slugging.
1. Size Circuit and Install Disconnect: Refer to unit
nameplate for minimum circuit ampacity, and maximum
fuse or circuit breaker size (HACR per NEC). Install pow
er wiring and properly sized disconnect switch.
NOTE — Units are approved for use only with cop
per conductors. Ground unit at disconnect switch or
connect to an earth ground.
separately) on an inside wall in the center of the condi
tioned area and 5 feet (1.5m) from the floor. The ther
mostat should not be installed on an outside wall or
where it can be affected by sunlight or drafts.
NOTE — 24VAC, Class II circuit connections are
made in the control box.
CAUTION
Electrostatic discharge can affect
electronic components. Take care
during unit installation and service to
protect the unit's electronic controls.
ELECTROSTATIC
DISCHARGE
(ESD)
Precautions and
Procedures
Precautions will help to avoid control
exposure to electrostatic discharge by
putting the unit, the control and the
technician at the same electrostatic
potential. Touch hand and all tools on an
unpainted unit surface before
performing any service procedure to
neutralize electrostatic charge.
A. ROUTE CONTROL WIRES — NON-COMMUNICATING
Install low voltage control wiring from outdoor to indoor unit and from
thermostat to indoor unit. All low voltage wiring must enter unit through
provided field-installed busing installed in electrical inlet.
Run 24VAC control wires through hole with grommet.
Make 24VAC control wire connections to heat pump control (A175).
NOTE — Do not bundle any excess 24VAC control wires inside control box.
NOTE — Wire tie provides low voltage wire strain relief and maintains
separation of field-installed low and high voltage circuits.
NOTE — For proper voltages, select control wires gauge per table below.
WIRE RUN LENGTHAWG# INSULATION TYPE
LESS THAN 100' (30 METERS) 18 TEMPERATURE RATING
MORE THAN 100' (30 METERS) 16 35ºC MINIMUM.
B
A
HOLE
CONTROL
(A175)
B. ROUTE CONTROL WIRES — COMMUNICATING
Maximum length of wiring (18 gauge) for all connections on the RSBus is 1500 feet (457 meters). Wires should be color-coded, with a temperature rating
of 95ºF (35ºC) minimum, and solid-core (Class II Rated Wiring). All low voltage wiring must enter unit through provided field-installed busing installed
in electrical inlet.
Communicating systems using the iComfortt-enabled thermostat require four thermostat wires between the thermostat and the furnace/air handler
control and four wires between the outdoor unit and the furnace/air handler control. When a thermostat cable with more than four wires is used, the extra
wires must be properly connected to avoid electrical noise (see illustration below).
Use a wire nut to bundle the four unused wires at each end of the cable. Each bundle should also include an additional wire that should be connected
on each end to the C terminal as shown in figure 7.
iComfortt-enabled
Outdoor Unit
Single Wire To
C Terminal
iComfortt-enabled
Indoor Unit
Single Wire To
C Terminal
iComfortt-enabled
thermostat
Unused Wires
Unused Wires
FIGURE 6
Page 4
Page 5
B. ROUTE HIGH VOLTAGE AND GROUND WIRES
Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring. To facilitate a conduit, a
cutout is located in the bottom of the control box. Connect conduit to the control box using a proper conduit fitting.
WATERTIGHT
CONDUIT FITTING
GROUND LUG*
CONTROL BOX
ACCESS VIEW
* Attach field-provided
WATERTIGHT
FLEXIBLE CONDUIT
CONTACTOR
ELECTRICAL
INLET (HIGH
VOLTAGE)
WIRING ENTRY
POINTS
green ground wire to
provided ground lug.
NOTE - Grounding wire
must be a single, contin
uous wire run from unit
ground lug to earth
ground. DO NOT splice
TO SERVICE
DISCONNECT BOX
ELECTRICAL INLET (CONTROL WIRING —
LOW VOLTAGE). USE BUSHING
PROVIDED IN BAG ASSEMBLY HERE.
wire.
FIGURE 7
STEP 2 -- ELECTRICAL (Continued) -- Outdoor Control (A175) Jumpers and Terminals
J4 - COMPRESSOR
SHIFT DELAY
30
SECOND DELAY
(DEFAULT)
0
SECOND DELAY
30
J2 - SECOND-STAGE
LOCK-IN
TEMPERATURE
(TWO-STAGE HEAT PUMP ONLY)
55
DEGREE
TARGET
50
DEGREE
TARGET
45
DEGREE
TARGET
40
DEGREE
TARGET (DEFAULT)
55
50
45
55
50
45
55
50
45
55
50
45
40
7-SEGMENT DISPLAY
PUSH BUTTON
J3 - DEFROST AUTO
(HEAT PUMP ONLY)
JUMPER ON PINS 1 AND 2
DEFROST AUTO ENABLED
JUMPER ON PINS 2 AND 3
DEFROST AUTO DISABLED (DEFAULT)
ON
OFF
J1 - DEFROST TERMINATION
0
SECOND-STAGE LOCK-IN
40
40
TEMPERATURE
TEMPERATURE
MAX
TARGET
90
MAX
90
DEGREE
TARGET
90
70
DEGREE
TARGET
MAX
MAX
DS TO R LINK - EDA
(HEAT PUMP ONLY)
70
50
(DEFAULT WHEN JUMPER IS
REMOVED OR MISSING)
70
50
70
DEGREE
TARGET
(DEFAULT)
90
70
50
MAX
90
90
70
50
MAX
90
70
50
APPLICATION
(TWO-STAGE UNIT ONLY)
40
NOTE - LINK NOT APPLICABLE TO SINGLE-STAGE
UNIT. CUTTING LINK WILL HAVE NO AFFECT ON
OPERATION OF SINGLE-STAGE UNITS
.
CUT FOR HUMIDITROL® - ENHANCED
DEHUMIFICATION ACCESSORY (EDA)
APPLICATIONS.
FIGURE 8
Page 5
SL18XC1 SERIES
Page 6
STEP 2 -- ELECTRICAL (Continued) -- Field Control Wiring
The following two illustrations provide examples of control wiring connections when using a non-communicating thermostat.
For examples of control wiring in complete or partial communicating systems, see the iComfortt-enabled thermostat
Quick Start Guide which is provided with the thermostat.
On−board link
Low voltage thermostat wiring
Flat metal jumper
1. Thermostat T terminals are used for outdoor
sensor input. Use for thermostat's outdoor
temperature display (optional).
2. R to L connection is required for this model only
when used with the ComfortSense
thermostat- (catalog number Y0349). Resistor Kit
(catalog number 47W97) required and ordered
separately.
3. Air handler control ships from factory with metal
jumpers (links) installed across W1, W2 and W3.
For single-stage electric heat, do not remove
factory-installed metal link.
4. Air handler control ships from factory with metal
jumpers installed across W1, W2 and W3. For
two-stage electric heat, cut factory-installed metal
link between W1 and W2. Then, connect
thermostat wire between the air handler control's
W2 and the thermostat's W2 terminal.
5. Cut on-board link (clippable wire) DS-R for
Humiditrol
slow the indoor blower motor to the lowest speed
setting. See air handler installation instruction or
product specifications bulletin for lowest fan speed
information.
®
or Harmony IIIt applications. This will
®
7000
Single−Stage
Air Conditioner Control
W
L
Y2
Y1
O
DS
2
C
i−
i+
R
FIGURE 9
Air Handler Control
DS
O
5
L
H
DH
R
C
Y1
Y2
G
W3
W2
3
W1
ComfortSense[ 7000 Thermostats
Catalog # Y0349 or Y2081
R
G
W2
W1
O
L
H
D
B
Y2
Y1
1
C
4
T
T
On−board link
Low voltage thermostat wiring
Flat metal jumper
1. Thermostat T terminals are used for outdoor sen
sor input. Sensor provides input for thermostat's
outdoor temperature display (optional).
2. R to L connection is required for this model only
when used with the ComfortSense
mostat - (catalog number Y0349). Resistor Kit
(catalog number 47W97) is required and must be
ordered separately.
3. Cut on-board link (clippable wire) DS-R for Humi
®
ditrol
or Harmony IIIt applications. This will slow
the indoor blower motor to the lowest speed set
ting. See furnace installation instruction or prod
uct specification bulletin for lowest fan speed in
formation.
®
7000 ther
Single−Stage
Air Conditioner Control
W
L
Y2
Y1
O
DS
2
C
i−
i+
R
Furnace Control
DS
O
L
3
H
DH
R
C
Y1
Y2
G
W2
W1
ComfortSense[ 7000 Thermostats
Catalog # Y0349 or Y2081
R
G
W2
W1
O
L
H
D
B
Y2
Y1
1
C
T
T
Cut on-board link (W914) (clippable wire) from DS to R for dehumidification (Optional).
FIGURE 10
Page 6
Page 7
STEP 3 -- REFRIGERANT PIPING —
Flushing Existing Line Set & Indoor Coil
Flush the existing line set per the following instruc
tions. For more information, refer to the Installation
and Service Procedures manual available on Dav
eNet. CAUTION - DO NOT attempt to flush and re-use
existing line sets or indoor coil when the system con
tainscontaminants (i.e., compressor burn out).
NOTE - When installing refrigerant lines longer than 50
feet, refer to the Refrigerant Piping Design and Fabrication
Guidelines manual available on DaveNet (Corp. 9351-L9),
or contact the Technical Support Department Product Ap
plication group for assistance.
NOTE - For new or replacement line set installation, refer
to Service and Application Note - Corp. 9112-L4 (C-91-4).
TABLE 1
REFRIGERANT LINE SET — INCHES (MM)
Field
Model
Size
-024
-030
-036
-042
-048
-060
NOTE — Some applications may require a field-provided 7/8” to
1-1/8” adapter
Connections
Liquid
Line
3/8“
(10)
3/8“
(10)
3/8“
(10)
3/8“
(10)
Suction
Line
3/4“
(19)
7/8“
(22)
7/8“
(22)
1-1/8“.
(29)
Recommended Line Set
Liquid
Line
3/8“
(10)
3/8“
(10)
3/8“
(10)
3/8“
(10)
Suction
Line
3/4“
(19)
7/8“
(22)
7/8“
(22)
1-1/8“
(29)
L15
Line Sets
Feet (Meters)
L15-41
15 - 50' (5 - 15)
L15-65
15 - 50' (5 - 15)
Field Fabricated
IMPORTANT !
If this unit is being matched with an approved line
set or indoor unit coil that was previously charged
with mineral oil, or if it is being matched with a coil
which was manufactured before January of 1999,
the coil and line set must be flushed prior to installa
tion. Take care to empty all existing traps. Polyol es
ter (POE) oils are used in Lennox units charged with
HFC-410A refrigerant. Residual mineral oil can act
as an insulator, preventing proper heat transfer. It
can also clog the expansion device and reduce sys
tem performance and capacity.
Failure to properly flush the system per this instruc
tion and the detailed Installation and Service Proce
dures manual will void the warranty.
WARNING
When using a high pressure gas such as
nitrogen to pressurize a refrigeration or air
conditioning system, use a regulator that
can control the pressure down to 1 or 2
psig (6.9 to 13.8 kPa).
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant
must be used and recovered responsibly.
Failure to follow this warning may result in personal injury
or death.
WARNING
Fire, Explosion and Personal Safety Haz
ard. Failure to follow this warning could re
sult in damage, personal injury or death.
Never use oxygen to pressurize or purge
refrigeration lines. Oxygen, when exposed
to a spark or open flame, can cause fire
and/or an explosion, that could result in
property damage, personal injury or death.
WARNING
Polyol ester (POE) oils used with HFC-410A
refrigerant absorb moisture very quickly. It is very
important that the refrigerant system be kept closed
as much as possible. DO NOT remove line set caps
or service valve stub caps until you are ready to make
connections.
IMPORTANT !
Some scroll compressors have an internal vacuum
protector that will unload scrolls when suction pres
sure goes below 20 psig. A hissing sound will be
heard when the compressor is running unloaded.
Protector will reset when low pressure in system is
raised above 40 psig. DO NOT REPLACE COM
PRESSOR.
1. On fully cased coils, remove the coil access and plumbing panels.
2. Remove any shipping clamps from the liquid line and distributor as
sembly.
3. Using two wrenches, disconnect liquid line from liquid line orifice hous
ing. Take care not to twist or damage distributor tubes during this pro
cess.
4. Remove and discard fixed orifice, valve stem assembly (if present)
and Teflon® washer as illustrated above.
5. Use a field-provided fitting to temporarily reconnect the liquid line to the
indoor unit's liquid line orifice housing.
(UNCASED COIL SHOWN)
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
TEFLON® RING
FIXED ORIFICE
REMOVE AND DISCARD
WHITE TEFLON
(IF PRESENT)
®
SEAL
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
REMOVAL PROCEDURE
OR
BRASS NUT
1B
TWO-PIECE PATCH PLATE
CONNECT GAUGES AND EQUIPMENT FOR
FLUSHING PROCEDURE
2
CYLINDER CONTAINING
CLEAN HCFC-22* TO BE
USED FOR FLUSHING
(Positioned to deliver liquid
A
refrigerant)
1
VAPOR LINE
SERVICE VALVE
EXISTING
INDOOR
UNIT
LIQUID LINE SERVICE
VALV E
RECOVERY
CYLINDER
VAPOR
LIQUID
OUTDOOR
B
NEW
UNIT
OPENED
C
D
RECOVERY MACHINE
A. HCFC-22 cylinder with clean refrigerant* (positioned to deliver liquid
refrigerant) to the vapor service valve.
B. HCFC-22 gauge set (low side) to the liquid line valve.
C. HCFC-22 gauge set center port to inlet on the recovery machine with an
empty recovery tank connected to the gauge set.
D. Connect recovery tank to recovery machine per machine instructions.
1. On fully cased coils, remove the coil access and plumbing panels.
2. Remove any shipping clamps from the liquid line and distributor
assembly.
3. Disconnect the equalizer line from the expansion valve equalizer
line fitting on the vapor line.
4. Remove the vapor line sensing bulb.
5. Disconnect the liquid line from the expansion valve at the liquid line
assembly.
6. Disconnect the expansion valve from the liquid line orifice housing.
Take care not to twist or damage distributor tubes during this
process.
7. Remove and discard expansion valve and the two Teflon® rings.
8. Use a field-provided fitting to temporarily reconnect the liquid line to
the indoor unit's liquid line orifice housing.
LIQUID LINE
SENSING BULB
FLUSHING LINE SET
The line set and indoor unit coil must be flushed with at least the same
3
amount of clean refrigerant* that previously charged the system.
Check the charge in the flushing cylinder before proceeding.
1. Set the recovery machine for liquid recovery and start the recovery
machine. Open the gauge set valves to allow the recovery
machine to pull a vacuum on the existing system line set and indoor
unit coil.
B
2. Position the cylinder of clean HCFC-22* for delivery of liquid
refrigerant and open its valve to allow liquid refrigerant to flow into
the system through the vapor line valve. Allow the refrigerant to
pass from the cylinder and through the line set and the indoor unit
coil before it enters the recovery machine.
3. After all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the HCFC-22
vapor is recovered. Allow the recovery machine to pull the system
down to 0.
4. Close the valve on the inverted HCFC-22 cylinder and the gauge
set valves. Pump the remaining refrigerant out of the recovery
machine and turn the machine off.
RING
®
SENSING
LINE
LIQUID
LINE
*IMPORTANT - Clean refrigerant is any refrigerant in a system that has not had compressor burn out. If the system
has experienced burn out, it is recommended that the existing line set and indoor coil be replaced.
ends of the refrigerant lines square (free from nicks or
dents) and debur the ends. The pipe must remain
round. Do not crimp the end of the line.
CUT AND DEBUR
LINE SET SIZE MATCHES
SERVICE VALVE CONNECTION
SERVICE VALVE
COPPER TUBE
REDUCER
CONNECTION
STUB
REFRIGERANT LINE
LINE SET SIZE IS SMALLER
THAN CONNECTION
CAP AND CORE REMOVAL
Remove service cap and core from both the suction
2
and liquid line service ports.
SERVICE PORT CAP
SERVICE PORT
CORE
LIQUID LINE SERVICE VALVE
SERVICE PORT
CORE
SERVICE
PORT CAP
SUCTION LINE
DO NOT CRIMP SERVICE VALVE
CONNECTOR WHEN PIPE IS
SMALLER THAN CONNECTION
SERVICE VALVE
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING
LIQUID AND SUCTION LINE SERVICE VALVES
3
AConnect gauge set low pressure side to liquid line service valve (service port).
BConnect gauge set center port to bottle of nitrogen with regulator.
CWith valve core removed from the suction line service port, nitrogen flow will have an exit point.
HIGHLOW
ATTACH
GAUGES
SUCTION LINE SERVICE PORT MUST BE OPEN
AND SERVICE PORT CORE REMOVED TO
ALLOW EXIT POINT FOR NITROGEN FLOW
SUCTION LINE
INDOOR
UNIT
LIQUID LINE
C
LIQUID LINE SERVICE
SUCTION
LINE
SERVICE
VALV E
VALV E
A
B
OUTDOOR
UNIT
NITROGEN
FIGURE 12
Page 9
SL18XC1 SERIES
Page 10
CAUTION
Brazing alloys and flux contain materials which are
hazardous to your health.
Avoid breathing vapors or fumes from brazing
operations. Perform operations only in well-ventilated
areas.
Wear gloves and protective goggles or face shield to
protect against burns.
Wash hands with soap and water after handling brazing
alloys and flux.
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap water-saturated cloths around service valve bodies and copper tube stubs. Use
4
additional water-saturated cloths under the valve body to protect the base paint.
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration
5
gauge set into the valve stem port connection on the liquid service
valve and out of the suction valve stem port. See steps 3A, 3B and
3C on previous page and below for manifold gauge setup.
BRAZE LINE SET
Cloths must remain water-saturated throughout the brazing and
6
cool-down process.
A. Braze liquid line to liquid line service valve.
B. Braze suction line to suction service valve.
FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE
may result if you do not wrap a water-saturated cloth around
both liquid and suction line service valve bodies and copper
tube stub while brazing the line set! The braze, when
complete, must be quenched with water to absorb any
residual heat.
Do not open service valves until refrigerant lines and
indoor coil have been leak-tested and evacuated. Refer
to Installation and Service Procedures manual found on
DAVENET.
WARNING
Danger of fire. Bleeding the refrigerant
charge from only the high side may result
in pressurization of the low side shell and
suction tubing. Application of a brazing
torch to a pressurized system may result
in ignition of the refrigerant and oil
mixture. Check the high and low
pressures before applying heat.
WARNING
SUCTION LINE
WATER-SATURATED CLOTHS
IMPORTANT !
Allow braze joint to cool. Apply additional
water-saturated cloths to help cool brazed
joints. Do not remove water-saturated cloths
until piping has cooled. Temperatures above
250ºF will damage valve seals.
LIQUID LINE
6B
6A
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
SUCTION SERVICE PORT MUST
BE OPEN AND SERVICE PORT
CORE REMOVED TO ALLOW
EXIT POINT FOR NITROGEN
FLOW
PREPARATION FOR NEXT STEP
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water-saturated cloths to both service
7
valves to cool piping. Once piping is cool, remove all water-saturated cloths.
WATER-SATURATED
FIGURE 13
Page 10
CLOTHS
Page 11
STEP 6 -- INSTALLING INDOOR EXPANSION VALVE
THIS OUTDOOR UNIT IS DESIGNED FOR USE IN SYSTEMS THAT USE A CHECK EXPANSION VALVE METERING DEVICE. SEE THE LENNOX SL18XC1
PRODUCT SPECIFICATION BULLETIN (EHB) FOR APPROVED EXPANSION VALVE KIT MATCH-UPS AND APPLICATION INFORMATION.
THE EXPANSION VALVE UNIT CAN BE INSTALLED INTERNAL OR
EXTERNAL TO THE INDOOR COIL. IN APPLICATIONS WHERE AN
TWO PIECE
PATCH PLATE
(UNCASED
COIL ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE
FITTING (SEE
EQUALIZER LINE
INSTALLATION FOR
FURTHER DETAILS)
SENSING BULB INSULATION IS REQUIRED
IF MOUNTED EXTERNAL TO THE COIL
CASING. SEE SENSING BULB
INSTALLATION FOR BULB POSITIONING.
(Uncased Coil Shown)
LIQUID LINE
ORIFICE
HOUSING
STUB
END
TEFLON
RING
EQUALIZER
LINE
EXPANSION
VALV E
®
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
VAPOR
LINE
UNCASED COIL IS BEING INSTALLED IN A FIELD-PROVIDED
PLENUM, INSTALL THE CHECK EXPANSION VALVE IN A MANNER
WHICH PROVIDES ACCESS FOR FIELD SERVICING OF THE
EXPANSION VALVE. REFER TO BELOW ILLUSTRATION FOR
REFERENCE DURING INSTALLATION OF EXPANSION VALVE
UNIT.
®
TEFLON
RING
1. REMOVE THE FIELD-PROVIDED FITTING THAT TEMPORARILY RECON
NECTED THE LIQUID LINE TO THE INDOOR UNIT'S DISTRIBUTOR ASSEM
SENSING
LINE
LIQUID LINE
BLY.
2. INSTALL ONE OF THE PROVIDED TEFLON
STUBBED END OF THE EXPANSION VALVE AND LIGHTLY LUBRICATE THE
CONNECTOR THREADS AND EXPOSE SURFACE OF THE TEFLON
WITH REFRIGERANT OIL.
3. ATTACH THE STUBBED END OF THE EXPANSION VALVE TO THE LIQUID
LINE ORIFICE HOUSING. FINGER TIGHTEN AND USE AN APPROPRIATE
LY SIZED WRENCH TO TURN AN ADDITIONAL 1/2 TURN CLOCKWISE AS
ILLUSTRATED IN THE FIGURE ABOVE, OR 20 FT-LB.
4. PLACE THE REMAINING TEFLON
OF THE EXPANSION VALVE. LIGHTLY LUBRICATE CONNECTOR
THREADS AND EXPOSE SURFACE OF THE TEFLON
ERANT OIL.
5. ATTACH THE LIQUID LINE ASSEMBLY TO THE EXPANSION VALVE. FIN
GER TIGHTEN AND USE AN APPROPRIATELY SIZED WRENCH TO TURN
AN ADDITIONAL 1/2 TURN CLOCKWISE AS ILLUSTRATED IN THE FIGURE
ABOVE OR 20 FT-LB.
9 O'CLOCK TO
3 O'CLOCK
BULB
12
®
BULB
9
WASHER AROUND THE OTHER END
12
11
1
10
8
7
®
RINGS AROUND THE
®
RING WITH REFRIG
ON LINES SMALLER THAN
7/8”, MOUNT SENSING
BULB BETWEEN THE 9 AND
3 O'CLOCK POSITIONS.
4
5
6
2
3
1/2 TURN
®
RING
SENSING BULB INSTALLATION
A.ATTACH THE SUCTION LINE SENSING BULB IN THE PROPER
ORIENTATION AS ILLUSTRATED TO THE RIGHT USING THE
CLAMP AND SCREWS PROVIDED.
NOTE - CONFIRM PROPER THERMAL CONTACT BETWEEN
SUCTION LINE AND CHECK EXPANSION BULB BEFORE IN
SULATING THE SENSING BULB ONCE INSTALLED.
B.CONNECT THE EQUALIZER LINE
FROM THE EXPANSION VALVE TO
THE EQUALIZER VAPOR PORT ON
THE SUCTION LINE. FINGER
TIGHTEN THE FLARE NUT PLUS
1/8 TURN (7 FT-LBS) AS ILLUS
TRATED BELOW.
9
10
11
12
1
8
7
EQUALIZER LINE INSTALLATION
REMOVE AND DISCARD EITHER THE FLARE SEAL CAP OR FLARE
NUT WITH COPPER FLARE SEAL BONNET FROM THE EQUALIZER
LINE PORT ON THE SUCTION LINE AS ILLUSTRATED IN THE FIGURE
TO THE RIGHT.
5
6
1/8 TURN
2
FLARE SEAL CAP
3
4
FIGURE 14
VAPOR LINE
BULB
ON 7/8” AND LARGER LINES,
MOUNT SENSING BULB AT
EITHER THE 4 OR 8 O'CLOCK
POSITION. NEVER MOUNT
12
BULB
OR
THE SENSING BULB ON
BOTTOM OF LINE.
NOTE - NEVER MOUNT
THE SENSING BULB ON
BOTTOM OF LINE.
FLARE NUT
COPPER FLARE
SEAL BONNET
MALE BRASS EQUALIZER
LINE FITTING
SUCTION LINE
Page 11
SL18XC1 SERIES
Page 12
STEP 7 -- LEAK TEST
HIGHLOW
MANIFOLD GAUGE SET
OUTDOOR UNIT
B
TO SUCTION
SERVICE VALVE
NOTE - Position
canister to deliver
liquid refrigerant.
NITROGEN
CONNECT GAUGE SET
AConnect the high pressure hose of an HFC-410A manifold gauge set to the suction valve service port.
1
2
NOTE — Normally, the high pressure hose is connected to the liquid line port. However, connecting it
to the suction port better protects the manifold gauge set from high pressure damage.
BWith both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of
the manifold gauge set.
NOTE — Later in the procedure, the HFC-410A container will be replaced by the nitrogen container.
TEST FOR LEAKS
After the line set has been connected to the indoor and outdoor units, check the line set connections
and indoor unit for leaks. Use the following procedure to test for leaks:
AWith both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of
the manifold gauge set. Open the valve on the HFC-410A cylinder (vapor only).
BOpen the high pressure side of the manifold to allow HFC-410A into the line set and indoor unit.
Weigh in a trace amount of HFC-410A. [A trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure.] Close the valve on the HFC-410A cylinder and the valve on
the high pressure side of the manifold gauge set. Disconnect the HFC-410A cylinder.
CConnect a cylinder of nitrogen with a pressure regulating valve to the center port of the manifold
gauge set.
DAdjust nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge
set in order to pressurize the line set and the indoor unit.
EAfter a few minutes, open one of the service valve ports and verify that the refrigerant added to the
system earlier is measurable with a leak detector.
FAfter leak testing, disconnect gauges from service ports.
HFC-410A
A
FIGURE 15
Page 12
Page 13
STEP 8 -- EVACUATION
Evacuating the system of non-condensables is critical for proper operation of the unit. Non-condensables are defined as any
gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Noncondensables and water suction combine with refrigerant to produce substances that corrode copper piping and compres
sor parts.
WARNING
Danger of Equipment Damage. Avoid deep vacuum system operation. Do not use the system compressor to
evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by
deep vacuum system operation will void warranty.
MANIFOLD
LOW
GAUGE SET
HIGH
LINE SET AND INDOOR COIL
CONNECT GAUGE SET
NOTE — Remove cores from service valves
(if not already done).
AConnect low side of manifold gauge set
with 1/4 SAE in-line tee to suction line
service valve
BConnect high side of manifold gauge
set to liquid line service valve
CConnect micron gauge available
connector on the 1/4 SAE in-line tee.
DConnect the vacuum pump (with
vacuum gauge) to the center port of the
manifold gauge set. The center port line
will be used later for both the HFC-410A
and nitrogen containers.
NITROGEN
OUTDOOR
UNIT
A
A34000 1/4 SAE TEE WITH
SWIVEL COUPLER
500
C
MICRON
GAUGE
TO SUCTION
SERVICE VALVE
HFC-410A
VACUUM PUMP
B
FIGURE 16
EVACUATE LINE SET AND INDOOR COIL
The unit is shipped with a factory refrigerant charge. The
liquid and suction line valves were closed after final testing
at the factory. Do not operate these valves until the line set
and indoor coil have been evacuated and leak checked, or
the charge is lost.
NOTE - Do not use any portion of the factory charge for
purging or leak testing. The factory charge is for filling the
system only after a complete evacuation and leak check
has been performed.
Line set and indoor coil should be evacuated using the rec
ommended deep vacuum method of 500 microns. If deep
vacuum equipment is not available, the alternate triple
evacuation method may be used by following the specified
procedure.
TO LIQUID LINE
SERVICE VALVE
D
RECOMMEND
MINIMUM 3/8” HOSE
If vacuum must be interrupted during the evacuation pro
cedure, always break vacuum with dry nitrogen.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capa
ble of pulling a vacuum to 500 microns and a vacuum
gauge capable of accurately measuring this vacuum level.
The deep vacuum method is the most positive way of as
suring a system is free of air and water.
Watch the vacuum gauge as the system is pulling down.
The response of the gauge is an indicator of the condition
of the system (refer to figure 17).
With no leaks in the system, allow the vacuum pump to run
for 30 minutes minimum at the deep vacuum level.
Page 13
SL18XC1 SERIES
Page 14
Deep Vacuum Gauge Response and
System Conditions
FIGURE 17
Triple Evacuation Method
The triple evacuation method should only be used when
system does not contain any water in liquid form and vacu
um pump is only capable of pulling down to 28 inches of
mercury (711mm Hg). Refer to figure 18 and proceed as
follows:
Triple Evacuation Sequence
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
6. After the final evacuation sequence, confirm there are
no leaks in the system. If a leak is found, repeat the en
tire process after repair is made.
7. Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not
rise above 500 microns (29.9 inches of mercury) within
a 20-minute period after shutting off the vacuum pump
and closing the manifold gauge valves.
8. Disconnect the manifold hose from the vacuum pump
and connect it to an inverted cylinder of HFC*410A
positioned to deliver liquid refrigerant. Open the mani
fold gauge valve 1 to 2 psig in order to release the vac
uum in the line set and indoor unit.
9. Perform the following:
SClose manifold gauge valves.
SShut off HFC*410A cylinder.
SSlowly open the service valves.
SRefer to the charging sticker on the unit to com
plete the outdoor unit installation.
Charging
The SL18XC1 unit is factory-charged with enough
HFC-410A refrigerant to accommodate a 15-foot length of
refrigerant piping. Charge should be checked and adjusted
using the tables provided on the charging procedure stick
er on the unit access panel. Detailed information is given in
the SL18XC1 Installation and Service Procedures manual,
which is available on LennoxPROS.com.
WAIT
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
CHECK FOR TIGHT, DRY SYSTEM (IF IT HOLDS DEEP VACUUM)
CHARGE SYSTEM
FIGURE 18
1. Pull system down to 28 inches of mercury (711mm Hg)
and allow pump to continue operating for an additional
15 minutes.
2. Close manifold valves or valve at vacuum pump and
shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system
and fill with nitrogen until system pressure is 2 psig.
4. Close nitrogen valve and allow system to stand for one
hour. During this time, dry nitrogen will diffuse through
out the system absorbing moisture.
5. Repeat this procedure as indicated in figure 18.
Homeowner Information
CAUTION
Before attempting to perform any service or mainte
nance, turn the electrical power to unit OFF at discon
nect switch.
In order to ensure peak performance, your system must be
properly maintained. Clogged filters and blocked airflow
prevent your unit from operating at its most efficient level.
Homeowner Maintenance
The following maintenance may be performed by the
homeowner.
S Contact a licensed professional HVAC technician to
schedule a yearly inspection and maintenance appoint
ment for your equipment.
S Check the indoor unit filter each month and replace the
filter, if necessary.
Have your Lennox dealer show you where your indoor
unit filter is located. It will be either at the indoor unit (in
stalled internal or external to the cabinet) or behind a re
turn air grille in the wall or ceiling. Check the filter monthly
and clean or replace it as needed.
Disposable filters should be replaced with a filter of the
same type and size.
S Check the indoor unit drain line for obstructions monthly
during the cooling season.
The indoor evaporator coil is equipped with a drain pan
Page 14
Page 15
to collect condensate formed as your system removes
humidity from the inside air. Have your dealer show you
the location of the drain line and how to check for ob
structions. (This would also apply to an auxiliary drain,
if installed.)
S Check the area around the outdoor unit monthly and re
move any obstructions that may restrict airflow to the
outdoor unit. This would include grass clippings, leaves,
or papers that may have settled around the unit.
S Trim shrubbery away from the unit and periodically
check for debris which collects around the unit.
S During the winter months, keep the snow level below the
louvered panels.
NOTE- The filter and all access panels must be in place
any time the unit is in operation. If you are unsure about the
filter required for your system, call your Lennox dealer for
assistance.
IMPORTANT !
Sprinklers and soaker hoses should not be installed
where they could cause prolonged exposure to the
outdoor unit by treated water. Prolonged exposure
of the unit to treated water (i.e., sprinkler systems,
soakers, waste water, etc.) will corrode the surface
of steel and aluminum parts, diminish performance
and affect longevity of the unit.
Thermostat Operation
See the ComfortSense® 7000 or iComfort®-enabled ther
mostat homeowner manual for instructions on how to op
erate your thermostat.
Pre-Service Check
If your system fails to operate, check the following before
calling for service:
SVerify room thermostat settings are correct.
SVerify that all electrical disconnect switches are ON.
SCheck for any blown fuses or tripped circuit breakers.
SVerify unit access panels are in place.
SVerify air filter is clean.
SIf service is needed, locate and write down the unit
model number and have it handy before calling.
Professional Maintenance
Your heating and air conditioning system should be in
spected and maintained yearly (before the start of the cool
ing and heating seasons) by a licensed professional HVAC
technician. You can expect the technician to check the fol
lowing items. These checks may only be conducted by
a licensed professional HVAC technician.
Outdoor Unit
1. Inspect component wiring for loose, worn or damaged
connections. Also check for any rubbing or pinching of
wires. Confirm proper voltage plus amperage of outdoor
unit.
2. Check the cleanliness of outdoor fan and blade as
semblies. Check condition of fan blades (cracks).
Clean or replace them, if necessary.
3. Inspect base pan drains for debris and clean as neces
sary.
4. Inspect the condition of refrigerant piping and confirm
that pipes are not rubbing copper-to-copper. Also,
check the condition of the insulation on the refrigerant
lines. Repair, correct, or replace as necessary.
5. Test capacitor. Replace as necessary.
6. Inspect contactor contacts for pitting or burn marks.
Replace as necessary.
7. Check outdoor fan motor for worn bearings/bushings.
Replace as necessary.
8. Inspect and clean outdoor coils, if necessary and note
any damage to coils or signs of leakage.
NOTICE !
Failure to follow instructions will cause damage to
the unit.
This unit is equipped with an aluminum coil. Alu
minum coils may be damaged by exposure to solu
tions with a pH below 5 or above 9. The aluminum
coil should be cleaned using potable water at a
moderate pressure (less than 50psi). If the coil can
not be cleaned using water alone, Lennox recom
mends use of a coil cleaner with a pH in the range of
5 to 9. The coil must be rinsed thoroughly after
cleaning.
In coastal areas, the coil should be cleaned with
potable water several times per year to avoid corro
sive buildup (salt).
Indoor Unit (Air Handler or Furnace)
1. Inspect component wiring for loose, worn or damaged
connections. Confirm proper voltage plus amperage
indoor unit.
2. Inspect and clean or replace air filters in indoor unit.
3. Check the cleanliness of indoor blower and clean
blower, if necessary.
4. Inspect the evaporator coil (Indoor) drain pans and
condensate drains for rust, debris, obstructions, leaks
or cracks. Pour water in pans to confirm proper
drainage from the pan through to the outlet of the pipe.
Clean or replace as necessary.
5. Inspect and clean evaporator (indoor) coil, if necessary.
6. Inspect the condition of the refrigerant lines and con
firm that pipes are not rubbing copper-to-copper. Also,
ensure that refrigerant pipes are not being affected by
indoor air contamination. Check condition of insulation
on the refrigerant lines. Repair, correct, or replace as
necessary.
7. Inspect the duct system for leaks or other problems.
Repair or replace as necessary.
8. Check for bearing/bushing wear on indoor blower mo
tor. Replace as necessary.
9. Indoor unit inspections of gas- or oil-fired furnaces will
also include inspection and cleaning of the burners,
and a full inspection of the gas valve, heat exchanger
and flue (exhaust) system.
General System Test with System Operating
1. Your technician should perform a general system test.
He will turn on the air conditioner to check operating
functions such as the startup and shutoff operation.
He will also check for unusual noises or odors, and
measure indoor/outdoor temperatures and system
pressures as needed.
Page 15
SL18XC1 SERIES
Page 16
2. The technician will check the refrigerant charge per
the charging sticker information on the outdoor unit.
3. Verify that system total static pressure and airflow set
tings are within specific operating parameters.
4. Verify correct temperature drop across indoor coil.
IMPORTANT
This performance check is ONLY valid on systems that have clean indoor and outdoor coils, proper airflow over coils,
and correct system refrigerant charge. All components in the system must be functioning properly to correctly perform
compressor operational check. (Accurate measurements are critical to this test as indoor system loading and outdoor
ambient can affect variations between low and high capacity readings).
SL18XC1 Start-Up and Performance Checklist
Customer Address
Indoor Unit ModelSerial
Outdoor Unit ModelSerial
Solar Module Mfg and ModelSerial
Notes:
START-UP CHECKS
Refrigerant Type:
Rated Load AmpsActual AmpsRated VoltsActual Volts
Condenser Fan Full Load AmpsActual Amps:
COOLING MODE
Vapor Pressure: Liquid Pressure:
Supply Air Temperature:Ambient Temperature:Return Air Temperature:
HEATING MODE
Vapor Pressure: Liquid Pressure:
Supply Air Temperature:Ambient Temperature:Return Air Temperature:
System Refrigerant Charge (Refer to manufacturer's information on unit or installation instructions for required
subcooling and approach temperatures.)
Subcooling:
Saturated Condensing Temperature (A)
minus Liquid Line Temperature (B)
Approach:
Liquid Line Temperature (A)
minus Outdoor Air Temperature (B)
Indoor Coil Temp. Drop (18 to 22°F)
minus Supply Air Temperature (B)
A—B=SUBCOOLING
A—B=APPROACH
A—B= COIL TEMP DROPReturn Air Temperature (A)
Page 16
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.