Lennox Signature XP21 Installation And Service Procedure

Page 1
2012 Lennox Industries Inc.
Corp. 1031−L7
Revised August 17, 2012
XP21
INSTALLATION AND SERVICE
PROCEDURE
Dave Lennox Signature
®
Collection XP21 Series Units
NOTICE
A thermostat is not included and must be ordered separately.
The Lennox icomfort thermostat must be used in
communicating applications.
In non−communicating applications, the Lennox
ComfortSense
®
7000 thermostat may be used, as well
as other non−communicating thermostats.
In all cases, setup is critical to ensure proper system operation.
Field wiring examples for non−communicating applications begin on page 22.
See the icomfort thermostat Quick Start Guide for communicating and partial communicating field wiring connections.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs AND HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
TABLE OF CONTENTS
I. OVERVIEW
Model Number Identification 2. . . . . . . . . . . . . . . . . . . .
Typical Serial Number Identification 2. . . . . . . . . . . . . .
Specifications 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Data 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Typical Unit Parts Arrangement 5. . . . . . . . . . . . . . . . .
Operating Gauge Set 6. . . . . . . . . . . . . . . . . . . . . . . . . .
General 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
II. INSTALLATION
Unit Placement 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing and Installing Panels 11. . . . . . . . . . . . . . . . .
New or Replacement Line Set 12. . . . . . . . . . . . . . . . . .
Brazing Connections 14. . . . . . . . . . . . . . . . . . . . . . . . . . .
Flushing the System 17. . . . . . . . . . . . . . . . . . . . . . . . . . .
Leak Testing the System 19. . . . . . . . . . . . . . . . . . . . . . .
Evacuating the System 19. . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Field Control Wiring 24. . . . . . . . . . . . . . . . . . . . . . . . . . .
Servicing Unit Delivered Void of Charge 26. . . . . . . . . .
Unit Start−Up 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Refrigerant 26. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Air Handler / Indoor Coil Match ups and Targeted
Subcooling Values 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating and Temperature Pressures 30. . . . . . . . . .
III. SYSTEM OPERATION AND SERVICE
OUTDOOR CONTROL − PART NUMBER 101796−XX
Heat Pump Control (A175) Jumpers and Terminals 31
System Status, Fault and Lockout LED Codes 33. . . .
Component Field Configuration and
Troubleshooting 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
OUTDOOR CONTROL − PART NUMBER 103369−XX
Jumpers and Links 47. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring Unit 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7−Segment Alert and System Status Codes 51. . . . . . .
Reconfiguring Outdoor Control using icomfort
Thermostat 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
APPLICABLE TO ALL VERSIONS
Compressor Information and Testing 57. . . . . . . . . . . . .
System Overview 61. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Defrost System 61. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 67. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SunSource
®
Home Energy System 67. . . . . . . . . . . . . .
Checklists 68. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Wiring Diagrams 69. . . . . . . . . . . . . . . . . . . . . . . . . .
Factory Wiring Diagrams 72. . . . . . . . . . . . . . . . . . . . . . .
Unit Sequence of Operations 75. . . . . . . . . . . . . . . . . . .
Page 2
XP21
I. OVERVIEW
Model Number identification
P 21 XXX
Unit Type
P = Heat Pump
Series
Nominal Cooling Capacity
024 = 2 tons 036 = 3 tons 048 = 4 tons 060 = 5 tons
Minor Revision Number
230
Voltage
230 = 208/230V−1ph−60hz
Refrigerant Type
X = R−410A
X
02
Typical Serial Number Identification
8 09 C
Year Code
08 = 2008 09 = 2009 10 = 2010
Month Code
A = January B = February C = March
05716
5 (or 6) Digit Unique Number
Location Code
19 = Saltillo, Mexico
58 = Marshalltown, IA
5
Specifications
Model Number
Unit Outdoor Fan
Sound Rating Number
(dB)
1
Factory Refrigerant
Charge
2
Number of Blades Diameter − inches.
XP21−024−230−01, −02, −03, −04, −05 67 11 lbs. 0 oz. 5 26.1
Model Number
Unit Outdoor Fan
Sound Rating Number
(dB)
1
Factory Refrigerant
Charge
2
Number of Blades Diameter − inches.
XP21−036−230−01, −02, −03, −04 72 11 lbs. 0 oz. 5 26.1
Model Number
Sound Rating Number
(dB)
1
Factory Refrigerant
Charge
2
Number of Blades Diameter − inches.
XP21−048−230−01, −02, −03 73 14 lbs. 0 oz. 5 26.1
XP21−048−230−04 73 13 lbs. 0 oz. 5 26.1
Model Number
Sound Rating Number
(dB)
1
Factory Refrigerant
Charge
2
Number of Blades Diameter − inches.
XP21−060−230−01, −02, −03 73 14 lbs. 4 oz. 5 26.1
XP21−060−230−04 73 13 lbs. 2 oz. 5 26.1
1
Tested according to AHRI Standard 270−2008 test conditions.
2
Refrigerant charge sufficient for 15 feet length of refrigerant lines.
Page 3
XP21
Electrical Data
208/230V−60 Hz−1 Ph
Model Number
Unit Compressor Condenser Fan
Maximum
Over−
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
2
Rated Load
Amps (RLA)
Locked
Rotor Amps (LRA)
Motor HP
Nominal
RPM 1−Stage
Nominal
RPM 2−Stage
Full Load
Amps (FLA)
XP21−024−230−01,
−02, −03, −04, −05
25 14.9 10.3 51.0 1/3 430 500 2.0
XP21−024−230−05 25 16.6 11.7 58.0 1/3 430 500 2.0
208/230V−60 Hz−1 Ph
Model Number
Unit Compressor Condenser Fan
Maximum
Over−
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
2
Rated Load
Amps (RLA)
Locked
Rotor Amps (LRA)
Motor HP
Nominal
RPM 1−Stage
Nominal
RPM 2−Stage
Full Load
Amps (FLA)
XP21−036−230−01,
−02, −03
35 22.9 16.7 82.0 1/3 525 600 2.0
XP21−036−230−04 35 21.1 15.3 83.0 1/3 525 600 2.0
208/230V−60 Hz−1 Ph
Model Number
Unit Compressor Condenser Fan
Maximum
Over−
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
2
Rated Load
Amps (RLA)
Locked
Rotor Amps (LRA)
Motor HP
Nominal
RPM 1−Stage
Nominal
RPM 2−Stage
Full Load
Amps (FLA)
XP21−048−230−01,
−02, −03
45 28.5 21.2 96.0 1/3 600 675 2.0
XP21−048−230−04 45 28.5 21.2 104.0 1/3 600 675 2.0
208/230V−60 Hz−1 Ph
Model Number
Unit Compressor Condenser Fan
Maximum
Over−
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
2
Rated Load
Amps (RLA)
Locked
Rotor Amps (LRA)
Motor HP
Nominal
RPM 1−Stage
Nominal
RPM 2−Stage
Full Load
Amps (FLA)
XP21−060−230−01 50 34.1 25.7 118.0 1/3 625 700 2.0
XP21−060−230−02,
−03
50 30.9 23.1 118.0 1/3 625 700 2.0
XP21−060−230−04 60 38.0 28.8 153.0 1/3 625 700 2.0
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Page 4
XP21
Unit Dimensions −− Inches (mm)
39−1/2 (1003)
1 (25)
LIQUID LINE INLET
SIDE VIEW
ACCESS VIEW
DISCHARGE AIR
4−5/8 (117)
BASE WITH ELONGATED LEGS
16−7/8
(429)
8−3/4 (222)
26−7/8
(683)
3−3/4 (95)
30−3/4
(781)
3−1/8
(79)
SUCTION LINE INLET
UNIT SUPPORT
FEET
35−1/2
(902)
18−1/2
(470)
8 (203)
4−1/2 (114)
ELECTRICAL INLET (HIGH VOLTAGE)
37 (940) (−024 AND −036)
SOLAR MODULE WIRING
ELECTRICAL INLET (CONTROL WIRING − LOW VOLTAGE)
47 (1194) (−048 AND −060)
Page 5
XP21
Typical Unit Parts Arrangement
GROUND LUGS
HIGH VOLTAGE FIELD
CONNECTIONS
CONTACTOR−1POLE
(K1−1)
HEAT PUMP CONTROL (A175)
CAPACITOR (C12)
FAN MOTOR CONTROL (A177)  PULSE−WIDTH
MODULATION (PWM) (ONLY ON UNITS WITH MAIN
CONTROL 101796−XX)
WIRE TIE
RT13 OUTDOOR
AMBIENT
TEMPERATURE
SENSOR
VAPOR VALVE
AND GAUGE
PORT
REVERSING
VALV E
LIQUID LINE BI−FLOW
FILTER DRIER
HIGH PRESSURE
SWITCH (S4)
LIQUID VALVE AND
GAUGE PORT
TRUE SUCTION LINE
PORT
LOW PRESSURE
SWITCH (S87)
CRANKCASE HEATER THERMOSTAT (S40)
HR1 CRANKCASE HEATER
COMPRESSOR
MUFFLER
DISCHARGE LINE
CHECK
EXPANSION VALVE
DISCHARGE LINE
TEMPERATURE SENSOR
(RT28)
COIL TEMPERATURE SENSOR (RT21) − ON
RETURN BEND, 12 TUBES UP FROM
BOTTOM (11.50’ UP)
XP21−024 AND −036
XP21−048 AND −060
COIL TEMPERATURE
SENSOR (RT21) − ON
RETURN BEND, 24
TUBES UP FROM
BOTTOM (23.50’ UP)
FAN MOTOR SURGE PROTECTION (ONLY
ON XP21−XXX−230−01 BUILD. STARTING
WITH BUILD −02, SURGE PROTECTION
BUILT INTO FAN MOTOR)
Figure 1. Plumbing, Switches and Sensor Components
Page 6
XP21
IMPORTANT
This unit must be matched with an indoor coil as specified in Lennox’ Engineering Handbook. Coils previously charged with HCFC−22 must be flushed.
WARNING
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working nearby these areas during installation or while servicing this equipment.
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
Operating Gauge Set
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.
TORQUE REQUIREMENTS
When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. Table 1 lists torque values for fasteners.
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9 ft−lbs for small valves, to 25 ft−lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
See the Lennox Service and Application Notes #C−08−1 for further details and information.
IMPORTANT
To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.
Table 1. Torque Requirements
Parts Recommended Torque
Service valve cap 8 ft.− lb. 11 NM
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 NM
USING MANIFOLD GAUGE SET
When checking the system charge, only use a manifold gauge set that features low loss anti−blow back fittings.
Manifold gauge set used with HFC−410A refrigerant sys­tems must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 − 800 psig on the high side and a low side of 30" vacuum to 250 psig with dampened speed to 500 psi. Gauge hoses must be rated for use at or up to 800 psig of pressure with a 4000 psig burst rating.
OPERATING SERVICE VALVES
The liquid and vapor line service valves are used for re­moving refrigerant, flushing, leak testing, evacuating, checking charge and charging.
Each valve is equipped with a service port which has a fac­tory−installed valve stem. Figure 2 provides information on how to access and operating both angle and ball service valves.
General
The XP21 is a high efficiency residential split−system heat pump unit, which features a two−stage scroll compressor and HFC−410A refrigerant. Units are available in 2, 3, 4 and 5−ton sizes. The series is designed for use with an expan­sion valve only (approved for use with HFC−410A) in the indoor unit.
Page 7
XP21
(VALVE STEM SHOWN CLOSED) INSERT HEX WRENCH HERE
SERVICE PORT CORE
SERVICE PORT CAP
ANGLE−TYPE SERVICE VALVE
(FRONT−SEATED CLOSED)
TO OUTDOOR UNIT
STEM CAP
(VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE
TO INDOOR
UNIT
ANGLE−TYPE SERVICE VALVE
(BACK−SEATED OPENED)
BALL (SHOWN CLOSED)
SERVICE PORT
CORE
TO INDOOR UNIT
TO OUTDOOR
UNIT
TO OPEN ROTATE STEM COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT
CAP
STEM CAP
VALV E STEM
SERVICE VALVES
ANGLE AND BALL
Operating Angle Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16" for vapor line valve sizes) to back the stem out counterclockwise as far as it will go.
Operating Ball Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrenched to open. To open valve, rotate stem counterclockwise 90°. To close, rotate stem clockwise 90°.
1
2
3
4
5
6
7
8
9
10
11
12
1/12 TURN
To Access Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge set to service port.
3. When testing is completed, replace service port cap and tighten as follows:
With torque wrench: Finger tighten and
torque cap per table 1.
Without torque wrench: Finger tighten and
use an appropriately sized wrench to turn an additional 1/6 turn clockwise.
1
2
3
4
5
6
7
8
9
10
11
12
1/6 TURN
WHEN SERVICE VALV E IS CLOSED, THE SERVICE PORT IS OPEN
TO THE LINE SET AND INDOOR UNIT.
When service valve is OPEN, the service port is open to linE set, indoor and outdoor unit.
Reinstall Stem Cap:
Stem cap protects the valve stem from damage and serves as the primary seal. Replace the stem cap and tighten as follows:
With Torque Wrench: Finger tighten and then
torque cap per table 1.
Without Torque Wrench: Finger tighten and
use an appropriately sized wrench to turn an additional 1/12 turn clockwise.
NOTE  A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
Figure 2. Angle and Ball Service Valves
Page 8
XP21
II. INSTALLATION
Unit Placement
CAUTION
In order to avoid injury, take proper precaution when lift­ing heavy objects.
See Unit Dimensions on page 3 for sizing mounting slab, platforms or supports. Refer to figure 3 for mandatory installation clearance requirements.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line.
When possible, do not install the unit directly outside
a window. Glass has a very high level of sound trans­mission. For proper placement of unit in relation to a window see the provided illustration in figure 5, detail A.
PLACING UNIT ON SLAB
When installing unit at grade level, the top of the slab should be high enough above grade so that water from higher ground will not collect around the unit. The slab should have a slope tolerance as described in figure 5, de­tail B.
NOTE  If necessary for stability, anchor unit to slab as de­scribed in figure 5, detail D.
ELEVATING THE UNIT
Units are outfitted with elongated support feet as illustrated in figure 5, detail C.
If additional elevation is necessary, raise the unit by ex­tending the height of the unit support feet. This may be achieved by using a 2−inch (50.8mm) Schedule 40 female threaded adapter.
The specified coupling will fit snuggly into the recessed portion of the feet. Use additional 2−inch (50.8mm) Sched­ule 40 male threaded adaptors which can be threaded into the female threaded adaptors to make additional adjust­ments to the level of the unit.
NOTE  Keep the height of extenders short enough to en­sure a sturdy installation. If it is necessary to extend further, consider a different type of field−fabricated frame­work that is sturdy enough for greater heights.
CONTROL PANEL
ACCESS
LOCATION
6 (152)
36 (914)
12 (305)
30 (762)
LINE SET CONNECTIONS
24 (610)
LINE SET
CONNECTIONS
ACCESS PANEL
REAR VIEW OF UNIT
48 (1219)
MINIMUM CLEARANCE BETWEEN
TWO UNITS
CLEARANCE ON ALL SIDES  INCHES (MILLIMETERS)
ACCESS PANEL
MINIMUM CLEARANCE
ABOVE UNIT
NOTES:
CLEARANCE TO ONE OF THE
OTHER THREE SIDES MUST BE 36 INCHES (914MM).
CLEARANCE TO ONE OF THE
REMAINING TWO SIDES MAY BE 12 INCHES (305MM) AND THE FINAL SIDE MAY BE 6 INCHES (152MM).
Figure 3. Installation Clearances
Page 9
XP21
STABILIZING UNIT ON UNEVEN SURFACES
IMPORTANT
Unit Stabilizer Bracket Use (field−provided):
Always use stabilizers when unit is raised above the factory height. (Elevated units could become unstable in gusty wind conditions).
Stabilizers may be used on factory height units when mounted on unstable an uneven surface.
1. Remove two side louvered panels to expose the unit base.
2. Install the brackets as illustrated in figure 5, detail D us­ing conventional practices.
3. Replace the panels after installation is complete.
ROOF MOUNTING
NOTICE
Roof Damage! This system contains both refrigerant and oil. Some
rubber roofing material may absorbed oil and cause the rubber to swell when it comes into contact with oil. The rubber will then bubble and could cause leaks. Protect the roof surface to avoid exposure to refrigerant and oil during service and installation. Failure to follow this notice could result in damage to roof surface.
Install the unit a minimum of six inches (152 mm) above the roof surface to avoid ice build−up around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications.
If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be constructed. Size barrier at least the same height and width as outdoor unit. Mount bar­rier 24 inches (610 mm) from the sides of the unit in the direction of prevailing winds.
24"
(610)
WIND BARRIER
PREVAILING WINTER
WINDS
INLET AIR
INLET AIR
INLET AIR
Figure 4. Rooftop Application and Wind Barrier
Page 10
XP21
LEG DETAIL
BASE
2" (50.8MM) SCH 40
FEMALE THREADED
ADAPTER
ONE BRACKET PER SIDE (MIN.); FOR EXTRA STABILITY, TWO BRACKETS PER SIDE, 2" (50.8MM) FROM EACH CORNER.
CONCRETE SLAB  USE TWO PLASTIC ANCHORS (HOLE DRILL 1/4")
COIL
BASE PAN
CORNER POST
STABILIZING BRACKET (18 GAUGE
METAL  2" WIDTH; HEIGHT AS
REQUIRED)
Slab Side Mounting
#10 1/2" LONG SELF−DRILLING
SHEET METAL SCREWS
#10 1−1/4" LONG HEX HD SCREW
AND FLAT WASHER
MINIMUM ONE
PER SIDE
STABILIZING BRACKET (18 GAUGE METAL  2" (50.8MM) WIDTH; HEIGHT AS REQUIRED); BEND TO FORM RIGHT ANGLE
FOR EXTRA
STABILITY
Deck Top Mounting
Elevated Slab Mounting using Feet
Extenders
Stabilizing Unit on Uneven Surfaces
WOOD OR PLASTIC SLAB  NO PLASTIC ANCHOR
(HOLE DRILL 1/8")
INSTALL UNIT LEVEL OR, IF ON A SLOPE, MAINTAIN SLOPE TOLERANCE OF 2 DEGREES (OR 2 INCHES PER 5 FEET [50 MM PER 1.5 M]) AWAY FROM BUILDING STRUCTURE.
MOUNTING SLAB
BUILDING
STRUCTURE
GROUND LEVEL
Outside Unit Placement
Slab Mounting at Ground Level
SAME FASTENERS AS SLAB SIDE MOUNTING.
IMPORTANT  To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors commonly available in the marketplace.
DETAIL A
DETAIL B
DETAIL C
DETAIL D
2" (50.8MM) SCH 40
MALE THREADED
ADAPTER
USE ADDITIONAL 2" SCH 40 MALE THREADED ADAPT­ERS WHICH CAN BE THREADED INTO THE FEMALE THREADED ADAPTERS TO MAKE ADDITIONAL AD­JUSTMENTS TO THE LEVEL OF THE UNIT.
TWO 90° ELBOWS INSTALLED IN LINE SET WILL
REDUCE LINE SET VIBRATION.
INSTALL UNIT AWAY FROM WINDOWS
Figure 5. Placement and Slab Mounting
Page 11
XP21
Removing and Installing Panels
REMOVE 4 SCREWS TO REMOVE PANEL FOR ACCESSING COMPRESSOR AND CONTROLS.
POSITION PANEL WITH HOLES ALIGNED; INSTALL SCREWS AND TIGHTEN.
ACCESS PANEL REMOVAL
REMOVAL AND RE−INSTALLATION OF THE ACCESS PANEL IS AS ILLUSTRATED.
Detail A
Detail B
ROTATE IN THIS DIRECTION; THEN
DOWN TO REMOVE PANEL
SCREW
HOLES
LIP
PANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TO EXIT (OR ENTER) TOP SLOT FOR REMOVING (OR INSTALLING) PANEL.
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL WITH THE UNIT AS POSSIBLE) WHILE INSTALLING PANEL.
PREFERRED ANGLE FOR INSTALLATION
Detail D
ANGLE MAY BE TOO EXTREME
HOLD DOOR FIRMLY ALONG
THE HINGED SIDE TO MAINTAIN
FULLY−ENGAGED TABS
LOUVERED PANEL REMOVAL
REMOVE THE LOUVERED PANELS AS FOLLOWS:
1. REMOVE TWO SCREWS, ALLOWING THE PANEL TO SWING OPEN SLIGHTLY.
2. HOLD THE PANEL FIRMLY THROUGHOUT THIS PROCEDURE ROTATE BOTTOM
CORNER OF PANEL AWAY FROM HINGED CORNER POST UNTIL LOWER THREE TABS CLEAR THE SLOTS AS ILLUSTRATED IN DETAIL B.
3. MOVE PANEL DOWN UNTIL LIP OF UPPER TAB CLEARS THE TOP SLOT IN CORNER
POST AS ILLUSTRATED IN DETAIL A.
LOUVERED PANEL INSTALLATION
POSITION THE PANEL ALMOST PARALLEL WITH THE UNIT AS ILLUSTRATED IN DETAIL D WITH THE SCREW SIDE AS CLOSE TO THE UNIT AS POSSIBLE. THEN, IN A CONTINUOUS MOTION:
1. SLIGHTLY ROTATE AND GUIDE THE LIP OF TOP TAB INWARD AS ILLUSTRATED IN DETAIL A AND C; THEN UPWARD INTO THE TOP SLOT OF THE HINGE CORNER POST.
2. ROTATE PANEL TO VERTICAL TO FULLY ENGAGE ALL TABS.
3. HOLDING THE PANEL’S HINGED SIDE FIRMLY IN PLACE, CLOSE THE RIGHT−HAND SIDE OF THE PANEL, ALIGNING THE SCREW HOLES.
4. WHEN PANEL IS CORRECTLY POSITIONED AND ALIGNED, INSERT THE SCREWS AND TIGHTEN.
PANELS
ACCESS AND LOUVERED
IMPORTANT  Do not allow panels to hang on unit by top tab.
Tab is for alignment and not designed to support weight of panel.
IMPORTANT  To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors commonly available in the marketplace.
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and battered.
WARNING
Detail C
Figure 6. Removing and Installing Panels
Page 12
XP21
New or Replacement Line Set
REFRIGERANT LINE SET
This section provides information on installation or replace­ment of existing line set. If new or replacement line set is not being installed then proceed to Brazing Connections on page 14.
IMPORTANT
Lennox highly recommends changing line set when converting the existing system from HCFC−22 to HFC−410A. If that is not possible and the line set is the proper size as reference in table 2, use the procedure outlined under Flushing the System on page 17.
If refrigerant lines are routed through a wall, then seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrig­erant lines will not create unnecessary vibration and subsequent sounds. See figure 7 for recommended instal­lation practices. Also, consider the following when placing and installing a high−efficiency outdoor unit.
Liquid lines that meter the refrigerant, such as RFC1 liquid lines, must not be used in this application. Existing line set of proper size as listed in table 2 may be reused. If system was previously charged with HCFC−22 refrigerant, then ex­isting line set must be flushed (see Flushing the System on page 17).
Field refrigerant piping consists of liquid and vapor lines from the outdoor unit to the indoor unit coil (braze connec­tions). Use Lennox L15 (sweat, non−flare) series line set, or field−fabricated refrigerant line sizes as listed in table 2.
Table 2. Refrigerant Line Set
Models Liquid
Line
Vapor/ Suction Line
L15 Line Set
−024, −036 and−048
3/8 (10) 7/8 (22) L15 line set sizes are
dependent on unit match up. See XP21 Engineering Handbook to determine correct line set sizes.
−060 3/8 (10) 1−1/8 (29) Field Fabricated
NOTE  Some applications may required a field−provided 7/8" to 1−1/8" adapter.
NOTE  When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fab­rication Guidelines, or contact Lennox Technical Support
Product Applications for assistance. To obtain the correct information from Lennox, be sure to communicate the fol­lowing points:
Model (XP21) and size of unit (e.g. −036). Line set diameters for the unit being installed as listed
in table 2 and total length of installation.
Number of elbows vertical rise or drop in the piping.
IMPORTANT
Mineral oils are not compatible with HFC−410A. If oil must
be added, it must be a Polyol ester oil.
The compressor is charged with sufficient Polyol ester oil for line set lengths up to 50 feet. Recommend adding oil to system based on the amount of refrigerant charge in the system. No need to add oil in system with 20 pounds of re­frigerant or less. For systems over 20 pounds − add one ounce of every five pounds of refrigerant.
Recommended topping−off POE oils are Mobil EAL ARC­TIC 22 CC or ICI EMKARATE RL32CF.
WARNING
Danger of fire. Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubing being pressurized. Application of a brazing torch while pressurized may result in ignition of the refrigerant and oil mixture − check the high and low pressures before unbrazing.
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
CAUTION
Brazing alloys and flux contain materials which are hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. Perform operations only in well ventilated areas.
Wear gloves and protective goggles or face shield to protect against burns.
Wash hands with soap and water after handling brazing alloys and flux.
Page 13
XP21
ANCHORED HEAVY NYLON WIRE TIE OR AUTOMOTIVE
MUFFLER-TYPE HANGER
STRAP LIQUID LINE TO VAPOR LINE
WALL STUD
LIQUID LINE
NON−CORROSIVE
METAL SLEEVE
VAPOR LINE − WRAPPED IN ARMAFLEX
AUTOMOTIVE
MUFFLER-TYPE HANGER
REFRIGERANT LINE SET  TRANSITION
FROM VERTICAL TO HORIZONTAL
LINE SET ISOLATION  THE FOLLOWING ILLUSTRATIONS ARE EXAM-
PLES OF PROPER REFRIGERANT LINE SET ISOLATION:
STRAPPING
MATERIAL (AROUND
VAPOR LINE ONLY)
TAPE OR WIRE TIE
WIRE TIE (AROUND VAPOR LINE ONLY)
FLOOR JOIST OR
ROOF RAFTER
TAPE OR WIRE TIE
TO HANG LINE SET FROM JOIST OR RAFTER, USE EITHER METAL STRAPPING MATERIAL OR ANCHORED HEAVY NYLON WIRE TIES.
8 FEET (2.43 METERS)
STRAP THE VAPOR LINE TO THE JOIST OR RAFTER AT 8 FEET (2.43 METERS) INTERVALS THEN STRAP THE LIQUID LINE TO THE VAPOR LINE.
FLOOR JOIST OR
ROOF RAFTER
REFRIGERANT LINE SET  INSTALLING
HORIZONTAL RUNS
NOTE  SIMILAR INSTALLATION PRACTICES SHOULD BE USED IF
LINE SET IS TO BE INSTALLED ON EXTERIOR OF OUTSIDE WALL.
PVC
PIPE
FIBERGLASS
INSULATION
CAULK
OUTSIDE
WALL
VAPOR LINE WRAPPED
WITH ARMAFLEX
LIQUID LINE
OUTSIDE WALL
LIQUID LINE
VAPOR LINE
WOOD BLOCK
BETWEEN STUDS
STRAP
WOOD BLOCK
STRAP
SLEEVE
WIRE TIE
WIRE TIE
WIRE TIE
INSIDE WALL
REFRIGERANT LINE SET  INSTALLING
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)
INSTALLATION
LINE SET
NOTE  INSULATE LIQUID LINE WHEN IT IS ROUTED THROUGH AREAS WHERE THE SURROUNDING AMBIENT TEMPERATURE COULD BECOME HIGHER THAN THE TEMPERATURE OF THE LIQUID LINE OR WHEN PRESSURE DROP IS EQUAL TO OR GREATER THAN 20 PSIG.
NON−CORROSIVE METAL SLEEVE
IMPORTANT  Refrigerant lines must not contact structure.
NON−CORROSIVE METAL SLEEVE
8 FEET (2.43 METERS)
IMPORTANT  Refrigerant lines must not contact wall
WARNING  Polyol ester (POE) oils used with HFC−410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
Figure 7. Line Set Installation
Page 14
XP21
Brazing Connections
Use the procedures outline in figures 8 and 9 for brazing line set connections to service valves.
WARNING
Danger of fire. Bleeding the refrigerant charge from only the high side may result in pressurization of the low side shell and suction tubing. Application of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture
− Check the high and low pressures before applying heat.
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
CAUTION
Brazing alloys and flux contain materials which are hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. Perform operations only in well−ventilated areas.
Wear gloves and protective goggles or face shield to protect against burns.
Wash hands with soap and water after handling brazing alloys and flux.
IMPORTANT
Connect gauge set low pressure side to vapor line service valve and repeat procedure starting at paragraph 4 for brazing the liquid line to service port valve.
IMPORTANT
Allow braze joint to cool before removing the wet rag from the service valve. Temperatures above 250ºF can damage valve seals.
IMPORTANT
Use silver alloy brazing rods with 5% minimum silver alloy for copper−to−copper brazing. Use 45% minimum alloy for copper−to−brass and copper−to−steel brazing.
WARNING
Fire, Explosion and Personal Safety Hazard.
Failure to follow this warning could result in damage, personal injury or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause fire and/or an ex­plosion, that could result in property damage, personal injury or death.
Page 15
XP21
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION LINE SERVICE VALVES
OUTDOOR
UNIT
LIQUID LINE
SUCTION LINE
LIQUID LINE SERVICE
VALV E
SUCTION LINE
SERVICE VALVE
ATTACH
GAUGES
INDOOR
UNIT
SUCTION SERVICE PORT MUST BE OPEN AND
SERVICE PORT CORE REMOVED TO ALLOW
EXIT POINT FOR NITROGEN FLOW
A Connect gauge set low pressure side to liquid line
service valve (service port).
B Connect gauge set center port to bottle of nitrogen
with regulator.
C With valve core removed from the suction line service
port, nitrogen flow will have an exit point.
NITROGEN
HIGH
LOW
B
A
C
PIPING PANEL REMOVAL AND PREPARING LINE SET
CAP AND CORE REMOVAL
Remove piping panel for easier access to service valves. Cut ends of the refrigerant lines square (free from nicks or dents) and debur the ends. The pipe must remain round. Do not crimp end of the line.
Remove service cap and core from both the suction and liquid line service ports.
1
2
LIQUID LINE SERVICE VALVE
SERVICE PORT CORE
SERVICE PORT CAP
SERVICE PORT CORE
SERVICE PORT CAP
CUT AND DEBUR
LINE SET SIZE MATCHES
SERVICE VALVE CONNECTION
COPPER TUBE
STUB
SERVICE VALVE CONNECTION
REFRIGERANT LINE
DO NOT CRIMP SERVICE
VALVE CONNECTOR WHEN
PIPE IS SMALLER THAN
CONNECTION
REDUCER
3
SUCTION LINE SERVICE
VALV E
LINE SET SIZE IS SMALLER
THAN CONNECTION
Figure 8. Brazing Procedures
Page 16
XP21
BRAZE LINE SET
Water saturated cloths must remain water saturated throughout the brazing and cool−down process.
6
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water saturated cloths to both services valves to cool piping. Once piping is cool, remove all water saturated cloths. Refer to the unit installation instructions for the next step in preparing the unit.
PREPARATION FOR NEXT STEP
7
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap water saturated cloths around service valve bodies and copper tube stubs. Use additional water saturated cloths underneath the valve body to protect the base paint.
4
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and out of the suction / vapor valve stem port. See steps 3A,
3B and 3C on previous page and below for manifold gauge setup.
5
SUCTION / VAPOR LINE
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
WARNING
1. FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE will result if you do not wrap a water
saturated cloth around both liquid and suction line service valve bodies and copper tube stub while brazing in the line set! The braze, when complete, must be quenched with water to absorb any residual heat.
2. Do not open service valves until refrigerant lines and indoor coil have been leak−tested and evacuated. Refer to procedures provided in this supplement.
LIQUID LINE
WATER SATURATED
CLOTHS
WATER SATURATED CLOTHS
A Braze liquid line to liquid line service valve.
B Braze suction / vapor line to suction / vapor service
valve.
6A
6B
SUCTION / VAPOR SERVICE PORT
MUST BE OPEN AND SERVICE PORT
CORE REMOVED TO ALLOW EXIT
POINT FOR NITROGEN FLOW
IMPORTANT  Allow braze joint to cool. Apply
additional water saturated cloths to help cool brazed joints. Do not remove water saturated cloths until piping has cooled. Temperatures above 250ºF will damage valve seals.
Figure 9. Brazing Procedures (Continued)
Page 17
XP21
Flushing the System
SENSING
LINE
TEFLON® RING
FIXED ORIFICE
BRASS NUT
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
LIQUID LINE ORIFICE HOUSING
DISTRIBUTOR TUBES
DISTRIBUTOR
ASSEMBLY
REMOVE AND DISCARD
WHITE TEFLON
®
SEAL
(IF PRESENT)
A ON FULLY CASED COILS, REMOVE THE COIL ACCESS AND PLUMBING
PANELS.
B REMOVE ANY SHIPPING CLAMPS HOLDING THE LIQUID LINE AND DIS-
TRIBUTOR ASSEMBLY.
C USING TWO WRENCHES, DISCONNECT LIQUID LINE FROM LIQUID LINE
ORIFICE HOUSING. TAKE CARE NOT TO TWIST OR DAMAGE DISTRIBU­TOR TUBES DURING THIS PROCESS.
D REMOVE AND DISCARD FIXED ORIFICE, VALVE STEM ASSEMBLY IF
PRESENT AND TEFLON
®
WASHER AS ILLUSTRATED ABOVE.
E USE A FIELD−PROVIDED FITTING TO TEMPORARY RECONNECT THE
LIQUID LINE TO THE INDOOR UNIT’S LIQUID LINE ORIFICE HOUSING.
TYPICAL EXISTING FIXED ORIFICE REMOVAL PROCEDURE (UNCASED COIL SHOWN)
TYPICAL EXISTING EXPANSION VALVE REMOVAL PROCEDURE (UNCASED COIL SHOWN)
TWO PIECE PATCH PLATE
(UNCASED COIL ONLY)
VAPOR
LINE
DISTRIBUTOR
ASSEMBLY
DISTRIBUTOR
TUBES
LIQUID
LINE
MALE EQUALIZER
LINE FITTING
EQUALIZER LINE
CHECK
EXPANSION
VALV E
TEFLON
®
RING
STUB END
TEFLON
®
RING
SENSING BULB
LIQUID LINE
ORIFICE
HOUSING
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
A ON FULLY CASED COILS, REMOVE THE COIL ACCESS AND PLUMBING
PANELS.
B REMOVE ANY SHIPPING CLAMPS HOLDING THE LIQUID LINE AND DIS-
TRIBUTOR ASSEMBLY.
C DISCONNECT THE EQUALIZER LINE FROM THE CHECK EXPANSION
VALVE EQUALIZER LINE FITTING ON THE VAPOR LINE.
D REMOVE THE VAPOR LINE SENSING BULB.
E DISCONNECT THE LIQUID LINE FROM THE CHECK EXPANSION VALVE
AT THE LIQUID LINE ASSEMBLY.
F DISCONNECT THE CHECK EXPANSION VALVE FROM THE LIQUID LINE
ORIFICE HOUSING. TAKE CARE NOT TO TWIST OR DAMAGE DISTRIBU­TOR TUBES DURING THIS PROCESS.
G REMOVE AND DISCARD CHECK EXPANSION VALVE AND THE TWO TEF-
LON
®
RINGS.
H USE A FIELD−PROVIDED FITTING TO TEMPORARY RECONNECT THE
LIQUID LINE TO THE INDOOR UNIT’S LIQUID LINE ORIFICE HOUSING.
LOW
HIGH
EXISTING
INDOOR
UNIT
GAUGE
MANIFOLD
INV ERTED HCFC−22 CYLINDER CONTAINS CLE AN HCFC−22 TO BE USED FOR FLUSHING.
LIQUID LINE SERVICE
VALV E
INLET
DISCHARGE
TANK RETURN
CLOSED
OPENED
RECOVERY
CYLINDER
RECOVERY MACHINE
NEW
OUTDOOR
UNIT
VAPOR LINE
SERVICE VALVE
VAPOR
LIQUID
1
A INVERTED HCFC−22 CYLINDER WITH CLEAN REFRIGERANT TO THE
VAPOR SERVICE VALVE.
B HCFC−22 GAUGE SET (LOW SIDE) TO THE LIQUID LINE VALVE.
C HCFC−22 GAUGE SET CENTER PORT TO INLET ON THE RECOVERY
MACHINE WITH AN EMPTY RECOVERY TANK TO THE GAUGE SET.
D CONNECT RECOVERY TANK TO RECOVERY MACHINES PER MACHINE
INSTRUCTIONS.
CONNECT GAUGES AND EQUIPMENT FOR FLUSHING PROCEDURE
A
B
C
D
B
OR
FLUSHING LINE SET
A SET THE RECOVERY MACHINE FOR LIQUID RECOVERY AND
START THE RECOVERY MACHINE. OPEN THE GAUGE SET VALVES TO ALLOW THE RECOVERY MACHINE TO PULL A VACU­UM ON THE EXISTING SYSTEM LINE SET AND INDOOR UNIT COIL.
B INVERT THE CYLINDER OF CLEAN HCFC−22 AND OPEN ITS VALVE
TO ALLOW LIQUID REFRIGERANT TO FLOW INTO THE SYSTEM THROUGH THE VAPOR LINE VALVE. ALLOW THE REFRIGERANT TO PASS FROM THE CYLINDER AND THROUGH THE LINE SET AND THE INDOOR UNIT COIL BEFORE IT ENTERS THE RECOVERY MACHINE.
C AFTER ALL OF THE LIQUID REFRIGERANT HAS BEEN RECOV-
ERED, SWITCH THE RECOVERY MACHINE TO VAPOR RECOVERY SO THAT ALL OF THE HCFC−22 VAPOR IS RECOVERED. ALLOW THE RECOVERY MACHINE TO PULL DOWN TO 0 THE SYSTEM.
D CLOSE THE VALVE ON THE INVERTED HCFC−22 DRUM AND THE
GAUGE SET VALVES. PUMP THE REMAINING REFRIGERANT OUT OF THE RECOVERY MACHINE AND TURN THE MACHINE OFF.
THE LINE SET AND INDOOR UNIT COIL MUST BE FLUSHED WITH AT LEAST THE SAME AMOUNT OF CLEAN REFRIGERANT THAT PRE­VIOUSLY CHARGED THE SYSTEM. CHECK THE CHARGE IN THE FLUSHING CYLINDER BEFORE PROCEEDING.
LINE SET AND INDOOR COIL (1 OF 2)
1A
2
3
CAUTION This procedure should not be performed on sys-
tems which contain contaminants (Example compressor burn out.
1B
Page 18
XP21
A ATTACH THE VAPOR LINE SENSING BULB IN THE PROPER
ORIENTATION AS ILLUSTRATED TO THE RIGHT USING THE CLAMP AND SCREWS PROVIDED.
NOTE  CONFIRM PROPER THERMAL CONTACT BETWEEN VA­POR LINE AND CHECK EXPANSION BULB BEFORE INSULATING THE SENSING BULB ONCE INSTALLED.
B CONNECT THE EQUALIZER LINE
FROM THE CHECK EXPANSION VALVE TO THE EQUALIZER VAPOR PORT ON THE VAPOR LINE. FIN­GER TIGHTEN THE FLARE NUT PLUS 1/8 TURN (7 FT−LBS) AS IL­LUSTRATED BELOW.
THE CHECK EXPANSION VALVE UNIT CAN BE INSTALLED INTERNAL OR EXTERNAL TO THE INDOOR COIL. IN APPLICATIONS WHERE AN UNCASED COIL IS BEING INSTALLED IN A FIELD−PROVIDED PLENUM, INSTALL THE CHECK EXPANSION VALVE IN A MANNER THAT WILL PROVIDE ACCESS FOR FIELD SERVICING OF THE CHECK EXPANSION VALVE. REFER TO BELOW ILLUSTRATION FOR REFERENCE DURING INSTALLATION OF CHECK EXPANSION VALVE UNIT.
TYPICAL NEW CHECK EXPANSION VALVE INSTALLATION PROCEDURE
TWO PIECE
PATCH PLATE
(UNCASED
COIL ONLY)
VAPOR
LINE
LIQUID LINE
ORIFICE
HOUSING
DISTRIBUTOR
TUBES
LIQUID LINE
MALE EQUALIZER LINE
FITTING (SEE
EQUALIZER LINE INSTALLATION FOR FURTHER DETAILS)
SENSING
LINE
EQUALIZER LINE
CHECK
EXPANSION
VALV E
TEFLON
®
RING
(Uncased Coil Shown)
SENSING BULB INSULATION IS REQUIRED IF MOUNTED EXTERNAL TO THE COIL CASING. SENSING BULB INSTALLATION FOR BULB POSITIONING.
STUB
END
TEFLON
®
RING
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
DISTRIBUTOR
ASSEMBLY
THIS OUTDOOR UNIT IS DESIGNED FOR USE IN SYSTEMS THAT USE CHECK EXPANSION VALVE METERING DEVICE. SEE THE LENNOX XP21 ENGI- NEERING HANDBOOK FOR APPROVED CHECK EXPANSION VALVE KIT MATCH−UPS AND APPLICATION INFORMATION.
A REMOVE THE FIELD−PROVIDED FITTING THAT TEMPORARY RECON-
NECTED THE LIQUID LINE TO THE INDOOR UNIT’S DISTRIBUTOR AS­SEMBLY.
B INSTALL ONE OF THE PROVIDED TEFLON
®
RINGS AROUND THE STUBBED END OF THE CHECK EXPANSION VALVE AND LIGHTLY LUBRI­CATE THE CONNECTOR THREADS AND EXPOSE SURFACE OF THE TEF­LON
®
RING WITH REFRIGERANT OIL.
C ATTACH THE STUBBED END OF THE CHECK EXPANSION VALVE TO THE
LIQUID LINE ORIFICE HOUSING. FINGER TIGHTEN AND USE AN APPRO­PRIATELY SIZED WRENCH TO TURN AN ADDITIONAL 1/2 TURN CLOCK­WISE AS ILLUSTRATED IN THE FIGURE ABOVE, OR 20 FT−LB.
D PLACE THE REMAINING TEFLON
®
WASHER AROUND THE OTHER END OF THE CHECK EXPANSION VALVE. LIGHTLY LUBRICATE CONNECTOR THREADS AND EXPOSE SURFACE OF THE TEFLON
®
RING WITH RE-
FRIGERANT OIL.
E ATTACH THE LIQUID LINE ASSEMBLY TO THE CHECK EXPANSION VALVE.
FINGER TIGHTEN AND USE AN APPROPRIATELY SIZED WRENCH TO TURN AN ADDITIONAL 1/2 TURN CLOCKWISE AS ILLUSTRATED IN THE FIGURE ABOVE OR 20 FT−LB.
ON 7/8" AND LARGER LINES, MOUNT SENSING BULB AT EITHER THE 4 OR 8 O’CLOCK POSITION. NEVER MOUNT ON BOTTOM OF LINE.
12
ON LINES SMALLER THAN 7/8", MOUNT SENSING BULB AT EITHER THE 3 OR 9 O’CLOCK POSITION.
12
BULB
VAPOR LINE
VAPOR LINE
NOTE  NEVER MOUNT ON BOTTOM OF LINE.
BULB
BULB
BULB
VAPOR LINE
FLARE NUT
COPPER FLARE SEAL BONNET
MALE BRASS EQUALIZER LINE FITTING
FLARE SEAL CAP
OR
1
2
3
4
5
6
7
8
9
10
11
12
1/2 TURN
SENSING BULB INSTALLATION
EQUALIZER LINE INSTALLATION
1
2
3
4
5
6
7
8
9
10
11
12
1/8 TURN
FLUSHING LINE SET AND INDOOR COIL (2 OF 2)
4
A REMOVE AND DISCARD EITHER THE FLARE SEAL CAP OR
FLARE NUT WITH COPPER FLARE SEAL BONNET FROM THE EQUALIZER LINE PORT ON THE VAPOR LINE AS ILLUS­TRATED IN THE FIGURE TO THE RIGHT.
B REMOVE AND DISCARD EITHER THE FLARE SEAL CAP OR
FLARE NUT WITH COPPER FLARE SEAL BONNET FROM THE EQUALIZER LINE PORT ON THE VAPOR LINE AS ILLUS­TRATED IN THE FIGURE TO THE RIGHT.
Page 19
XP21
INSTALLING ISOLATION GROMMETS
Locate the isolation grommets (provided). Slide grommets onto vapor and liquid lines. Insert grommets into piping panel to isolate refrigerant lines from sheet metal edges.
TWO ISOLATION GROMMETS ARE PROVIDE FOR THE LIQUID AND SUCTION LINE PIPE PANEL PASS THROUGH.
LIQUID LINE
SUCTION LINE
REAR VIEW OF UNIT EXTERIOR
PIPING PANEL
Figure 10. Isolation Grommets
IMPORTANT
The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.
IMPORTANT
If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC−410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity. Failure to properly flush the system per the instructions below will void the warranty.
Leak Testing the System
IMPORTANT
Leak detector must be capable of sensing HFC refrigerant.
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
WARNING
Fire, Explosion and Personal Safety Hazard.
Failure to follow this warning could result in damage, personal injury or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause damage by fire and/ or an explosion, that could result in personal injury or death.
Page 20
XP21
TO VAPOR
SERVICE VALVE
HFC−410A
MANIFOLD GAUGE SET
OUTDOOR UNIT
HIGH
LOW
NITROGEN
NOTE  NORMALLY, THE HIGH PRESSURE HOSE IS CONNECTED TO THE LIQUID LINE PORT. HOWEVER, CONNECTING IT TO THE VAPOR PORT BETTER PROTECTS THE MANIFOLD GAUGE SET FROM HIGH PRESSURE DAMAGE.
A WITH BOTH MANIFOLD VALVES CLOSED, CONNECT THE CYLINDER OF HFC−410A REFRIGERANT TO THE CENTER PORT OF THE
MANIFOLD GAUGE SET. OPEN THE VALVE ON THE HFC−410A CYLINDER (VAPOR ONLY).
B OPEN THE HIGH PRESSURE SIDE OF THE MANIFOLD TO ALLOW HFC−410A INTO THE LINE SET AND INDOOR UNIT. WEIGH IN A TRACE
AMOUNT OF HFC−410A. [A TRACE AMOUNT IS A MAXIMUM OF TWO OUNCES (57 G) REFRIGERANT OR THREE POUNDS (31 KPA) PRESSURE]. CLOSE THE VALVE ON THE HFC−410A CYLINDER AND THE VALVE ON THE HIGH PRESSURE SIDE OF THE MANIFOLD GAUGE SET. DISCONNECT THE HFC−410A CYLINDER.
C CONNECT A CYLINDER OF DRY NITROGEN WITH A PRESSURE REGULATING VALVE TO THE CENTER PORT OF THE MANIFOLD
GAUGE SET.
D ADJUST DRY NITROGEN PRESSURE TO 150 PSIG (1034 KPA). OPEN THE VALVE ON THE HIGH SIDE OF THE MANIFOLD GAUGE SET IN
ORDER TO PRESSURIZE THE LINE SET AND THE INDOOR UNIT.
E AFTER A FEW MINUTES, OPEN ONE OF THE SERVICE VALVE PORTS AND VERIFY THAT THE REFRIGERANT ADDED TO THE SYSTEM
EARLIER IS MEASURABLE WITH A LEAK DETECTOR.
F AFTER LEAK TESTING DISCONNECT GAUGES FROM SERVICE PORTS.
LINE SET AND INDOOR COIL
AFTER THE LINE SET HAS BEEN CONNECTED TO THE INDOOR AND OUTDOOR UNITS, CHECK THE LINE SET CON­NECTIONS AND INDOOR UNIT FOR LEAKS. USE THE FOLLOWING PROCEDURE TO TEST FOR LEAKS:
LEAK TEST
A CONNECT AN HFC−410A MANIFOLD GAUGE SET
HIGH PRESSURE HOSE TO THE VAPOR VALVE SERVICE PORT.
B WITH BOTH MANIFOLD VALVES CLOSED, CONNECT
THE CYLINDER OF HFC−410A REFRIGERANT TO THE CENTER PORT OF THE MANIFOLD GAUGE SET.
1
CONNECT GAUGE SET
2
TEST FOR LEAKS
A
B
NOTE  LATER IN THE PROCEDURE, THE HFC−410A CONTAINER WILL BE REPLACED BY THE NITROGEN CONTAINER.
Figure 11. System Leak Test
Page 21
XP21
Evacuating the System
A OPEN BOTH MANIFOLD VALVES AND START THE VACUUM PUMP. B EVACUATE THE LINE SET AND INDOOR UNIT TO AN ABSOLUTE PRESSURE OF 23,000 MICRONS (29.01 INCHES OF MERCURY).
NOTE  DURING THE EARLY STAGES OF EVACUATION, IT IS DESIRABLE TO CLOSE THE MANIFOLD GAUGE VALVE AT LEAST ONCE. A RAPID RISE IN PRESSURE INDICATES A RELATIVELY LARGE LEAK. IF THIS OCCURS, REPEAT THE LEAK TESTING PROCEDURE.
NOTE  THE TERM ABSOLUTE PRESSURE MEANS THE TOTAL ACTUAL PRESSURE WITHIN A GIVEN VOLUME OR SYSTEM, ABOVE THE ABSO-
LUTE ZERO OF PRESSURE. ABSOLUTE PRESSURE IN A VACUUM IS EQUAL TO ATMOSPHERIC PRESSURE MINUS VACUUM PRESSURE.
C WHEN THE ABSOLUTE PRESSURE REACHES 23,000 MICRONS (29.01 INCHES OF MERCURY), CLOSE THE MANIFOLD GAUGE VALVES, TURN
OFF THE VACUUM PUMP AND DISCONNECT THE MANIFOLD GAUGE CENTER PORT HOSE FROM VACUUM PUMP. ATTACH THE MANIFOLD CENTER PORT HOSE TO A DRY NITROGEN CYLINDER WITH PRESSURE REGULATOR SET TO 150 PSIG (1034 KPA) AND PURGE THE HOSE. OPEN THE MANIFOLD GAUGE VALVES TO BREAK THE VACUUM IN THE LINE SET AND INDOOR UNIT. CLOSE THE MANIFOLD GAUGE VALVES.
D SHUT OFF THE DRY NITROGEN CYLINDER AND REMOVE THE MANIFOLD GAUGE HOSE FROM THE CYLINDER. OPEN THE MANIFOLD
GAUGE VALVES TO RELEASE THE DRY NITROGEN FROM THE LINE SET AND INDOOR UNIT.
E RECONNECT THE MANIFOLD GAUGE TO THE VACUUM PUMP, TURN THE PUMP ON, AND CONTINUE TO EVACUATE THE LINE SET AND IN-
DOOR UNIT UNTIL THE ABSOLUTE PRESSURE DOES NOT RISE ABOVE 500 MICRONS (29.9 INCHES OF MERCURY) WITHIN A 20−MINUTE PERIOD AFTER SHUTTING OFF THE VACUUM PUMP AND CLOSING THE MANIFOLD GAUGE VALVES.
F WHEN THE ABSOLUTE PRESSURE REQUIREMENT ABOVE HAS BEEN MET, DISCONNECT THE MANIFOLD HOSE FROM THE VACUUM PUMP
AND CONNECT IT TO AN UPRIGHT CYLINDER OF HFC−410A REFRIGERANT. OPEN THE MANIFOLD GAUGE VALVE 1 TO 2 PSIG IN ORDER TO RELEASE THE VACUUM IN THE LINE SET AND INDOOR UNIT.
G PERFORM THE FOLLOWING:
OUTDOOR
UNIT
TO VAPOR
SERVICE VALVE
TO LIQUID LINE SERVICE VALVE
MICRON
GAUGE
VACUUM PUMP
A34000 1/4 SAE TEE WITH SWIVEL COUPLER
500
MANIFOLD
GAUGE SET
HFC−410A
RECOMMEND
MINIMUM 3/8" HOSE
A CONNECT LOW SIDE OF MANIFOLD
GAUGE SET WITH 1/4 SAE IN−LINE TEE TO VAPOR LINE SERVICE VALVE
B CONNECT HIGH SIDE OF MANIFOLD
GAUGE SET TO LIQUID LINE SERVICE VALV E
C CONNECT MICRON GAUGE AVAILABLE
CONNECTOR ON THE 1/4 SAE IN−LINE TEE.
D CONNECT THE VACUUM PUMP (WITH
VACUUM GAUGE) TO THE CENTER PORT OF THE MANIFOLD GAUGE SET. THE CENTER PORT LINE WILL BE USED LATER FOR BOTH THE HFC−410A AND NITROGEN CONTAINERS.
HIGH
LOW
1
2
3
4
5
6
7
8
9
10
11
12
1/6 TURN
NITROGEN
1
CONNECT GAUGE SET
A
B
C
D
2
EVACUATE THE SYSTEM
CLOSE MANIFOLD GAUGE VALVES.
SHUT OFF HFC−410A CYLINDER.
REINSTALL SERVICE VALVE CORES BY REMOVING MANIFOLD HOSE FROM SERVICE VALVE. QUICKLY
INSTALL CORES WITH CORE TOOL WHILE MAINTAINING A POSITIVE SYSTEM PRESSURE.
REPLACE THE STEM CAPS AND SECURE FINGER TIGHT, THEN TIGHTEN AN ADDITIONAL ONE−SIXTH
(1/6) OF A TURN AS ILLUSTRATED.
LINE SET AND INDOOR COIL
NOTE  REMOVE CORES FROM SERVICE VALVES (IF
NOT ALREADY DONE).
Figure 12. Evacuating System
Page 22
XP21
IMPORTANT
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns.
WARNING
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
Evacuating the system of non−condensables is critical for
proper operation of the unit. Non−condensables are de-
fined as any gas that will not condense under temperatures and pressures present during operation of an air condition­ing system. Non−condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts.
Electrical
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air han­dler for low-voltage control power (24VAC − 40 VA minimum)
REFER TO THE UNIT NAMEPLATE FOR MINIMUM CIRCUIT AMPACITY, AND MAXIMUM FUSE OR CIRCUIT BREAKER (HACR PER NEC). INSTALL POWER WIRING AND PROPERLY SIZED DISCONNECT SWITCH.
NOTE  UNITS ARE APPROVED FOR USE ONLY WITH COPPER CONDUCTORS. GROUND UNIT AT DISCONNECT SWITCH OR TO AN EARTH GROUND.
SIZE CIRCUIT AND INSTALL DISCONNECT SWITCH
1
NOTE  24VAC, CLASS II CIRCUIT CONNECTIONS ARE MADE IN THE
CONTROL BOX.
INSTALL ROOM THERMOSTAT (ORDERED SEPARATELY) ON AN INSIDE WALL APPROXIMATELY IN THE CENTER OF THE CONDITIONED AREA AND 5 FEET (1.5M) FROM THE FLOOR. IT SHOULD NOT BE INSTALLED ON AN OUTSIDE WALL OR WHERE IT CAN BE AFFECTED BY SUNLIGHT OR DRAFTS.
THERMOSTAT
5 FEET
(1.5M)
INSTALL THERMOSTAT
2
SERVICE
DISCONNECT
SWITCH
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
CAUTION
ELECTROSTATIC DISCHARGE
(ESD)
Precautions and Procedures
Electrostatic discharge can affect electronic components. Take precautions during unit installation and service to protect the unit’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touching hand and all tools on an unpainted unit surface before performing any service procedure
Page 23
XP21
NOTE  FOR PROPER VOLTAGES, SELECT CONTROL WIRES GAUGE PER TABLE BELOW.
WIRE RUN LENGTH AWG# INSULATION TYPE
LESS THAN 100’ (30 METERS) 18 TEMPERATURE RATING
MORE THAN 100’ (30 METERS) 16 35ºC MINIMUM.
NOTE  WIRE TIE PROVIDES LOW VOLTAGE WIRE STRAIN RELIEF AND TO MAINTAIN SEPARATION OF FIELD INSTALLED LOW AND HIGH VOLTAGE CIRCUITS.
NOTE  DO NOT BUNDLE ANY EXCESS 24VAC CONTROL WIRES INSIDE CON­TROL BOX.
A. ROUTE CONTROL WIRES  NON−COMMUNICATING
A
B
HEAT PUMP
CONTROL (A175)
CONTROL BOX
HOLE
INSTALL LOW VOLTAGE CONTROL WIRING FROM OUTDOOR TO INDOOR UNIT AND FROM THERMOSTAT TO INDOOR UNIT AS ILLUSTRATED.
3
A RUN 24VAC CONTROL WIRES THROUGH HOLE WITH GROMMET.
B MAKE 24VAC CONTROL WIRE CONNECTIONS TO HEAT PUMP
CONTROL (A175) .
B. ROUTE CONTROL WIRES  COMMUNICATING
MAXIMUM LENGTH OF WIRING (18 GAUGE) FOR ALL CONNECTIONS ON THE RSBUS IS LIMITED TO 1500 FEET (457 METERS). COLOR−CODED, TEMPERATURE RATING 95
º
F (35ºC) MINIMUM, SOLID CORE. (CLASS II RATED WIRING)
ANY EXCESS HIGH VOLTAGE FIELD WIRING SHOULD BE TRIMMED AND SECURED AWAY FROM ANY LOW VOLTAGE FIELD WIRING. TO FACILITATE A CONDUIT, A CUTOUT IS LOCATED IN THE BOTTOM OF THE CONTROL BOX. CONNECT CONDUIT TO THE CONTROL BOX USING A PROPER CONDUIT FITTING.
ROUTE HIGH VOLTAGE AND GROUND WIRES
CONTROL BOX
PIPING PANEL
HIGH VOLTAGE
CONDUIT HOLE
GROUND LUG
CONTACTOR
WATERTIGHT
CONDUIT
FITTING
WATERTIGHT
FLEXIBLE CONDUIT
TO AC DISCONNECT
BOX
ACCESS VIEW
ELECTRICAL INLET
(HIGH VOLTAGE)
WIRING ENTRY POINTS
ELECTRICAL INLET (CONTROL WIRING  LOW VOLTAGE). USE BUSHING PROVIDED IN BAG ASSEMBLY HERE.
4
Page 24
XP21
Field Control Wiring
The following two illustrations provide examples on how to install control wiring using a non−communicating thermostat. For examples of how to install control wiring in complete or partial communicating systems, see the icomfort thermostat Quick Start Guide which is provided with the thermostat.
Y1
O
R
W1
G
D
R
Y1
L
C
C
ComfortSense[ 7000 Thermostats
Catalog # Y0349 or Y2081
B
Y2
Y2
W
O
DS
L
T
T
W2
H
W3
H
O
C
L
Y2
DS
DH
G
R
Y1
W2
W1
1
2
5
6
8
7
Onboard link
Low voltage thermosta
t
wiring
Flat metal jumper
3
4
Air Handler Control
XP21 Two−Stage
Heat Pump Control
1. Thermostat T terminals are used for outdoor sensor input. Use for thermostat’s outdoor temperature display (optional).
2. R to L connection is required for this model when using the ComfortSense
®
7000 − catalog number Y0349 only. Resistor Kit (catalog number
47W97) required and ordered separately.
3. Air handler control ships from factory with metal jumpers installed across W1, W2 and W3. For one−stage electric heat, do not remove factory
installed metal jumpers.
4. Air handler control ships from factory with metal jumpers installed across W1, W2 and W3. For two−stage electric heat, remove factory installed metal jumper between W1 to W2. Then connect thermostat wire between the air handler control’s W2 and the thermostat’s W2 terminal.
5. Cut on−board link (clippable wire) from R−O HEAT PUMP for heat pump applications.
6. Cut on−board link (clippable wire) from Y1−Y2 2 STAGE COMPR for two−stage compressor and two−speed fan operation.
7. Cut loop jumper (clippable wire) Short DS to R for Humiditrol
®
applications. This will slow the outdoor unit’s fan speed to a specific RPM. A wire
must be installed between the DS terminals on the air handler and outdoor unit controls. See table 17 for fan speed based on unit capacity.
8. Cut on−board link (clippable wire) DS−R for Humiditrol
®
or Harmony III applications. This will slow the indoor blower motor to the lowest speed
setting. See air handler installation instruction or engineering handbook for lowest fan speed information.
Figure 13. ComfortSense® 7000 Series Thermostat  Air Hander/Two−Stage Heat Pump
Page 25
XP21
Y1
O
R
W1
G
D
R
Y1
L
C
C
Furnace Control
ComfortSense[ 7000 Thermostats
Catalog # Y0349 or Y2081
XP21 TwoStage
Heat Pump Control
B
Y2
Y2
W
O
DS
L
T
T
W2
H
W3
H
O
C
L
Y2
DS
DH
G
R
Y1
W2
W1
1
2
3
4
6
5
Onboard link
Low voltage thermostat wiring
1. Thermostat T terminals are used for outdoor sensor input. Use for thermostat’s outdoor temperature display (optional).
2. R to L connection is required for this model when using the ComfortSense
®
7000 − catalog number Y0349 only. Resistor Kit (catalog number
47W97) required and ordered separately.
3. Cut on−board link W951 (clippable wire) from R−O HEAT PUMP for heat pump applications.
4. Cut on−board link W915 (clippable wire) for two−stage operation.
5. Cut loop jumper (clippable wire) Short DS to R for Humiditrol
®
applications. This will slow the outdoor unit’s fan speed to a specific RPM. A wire
must be installed between the DS terminals on the furnace and outdoor unit controls. See table 17 for fan speed based on unit capacity.
6. Cut onboard link (clippable wire) DSR for Humiditrol
®
or Harmony III applications. This will slow the indoor blower motor to the lowest speed
setting. See furnace installation instruction or engineering handbook for lowest fan speed information.
NOTE − For defrost temper with furnace, the optional 67M41 temper kit would be wired between W of from the heat pump control (A175) to the W1 of the furnace control The kit allows for the furnace to cycle on and off during a defrost. It protects the compressor from high refrigeration pressures during defrost.
Figure 14. ComfortSense® 7000 Series Thermostat  Furnace/Two−Stage Heat Pump
Loading...
+ 56 hidden pages