Lennox XP19, Signature XP19-024, Signature XP19-036, Signature XP19-048, Signature XP19-060 Installation Instructions Manual

INSTALLATION
E2009 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
CAUTION
INSTRUCTIONS
Dave Lennox Signature Collection XP19 Series Units
HEAT PUMPS
505,331M 06/09 Supersedes 05/09
Table of Contents
Shipping and Packing List 1. . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
XP19 Heat Pumps 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Information 2. . . . . . . . . . . . . . . . . . . . . . . . . . .
Recovering Refrigerant from Existing System 4. . . . .
Removing Existing Outdoor Unit 5. . . . . . . . . . . . . . . . .
Positioning New Outdoor Unit 5. . . . . . . . . . . . . . . . . . .
Removing Panels 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
New or Replacement Line Set 8. . . . . . . . . . . . . . . . . . .
Brazing Connections 9. . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing Indoor Unit Metering Device 10. . . . . . . . . . .
Flushing the System 11. . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing New Indoor Unit Metering Device 12. . . . . . . .
Testing for Leaks 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evacuating the System 14. . . . . . . . . . . . . . . . . . . . . . . . .
Servicing Unit Delivered Void of Charge 15. . . . . . . . . .
Electrical Connections 16. . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up and Charging Procedures 16. . . . . . . . . . . . . . .
System Operations 21. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Lennox System Operation Monitor (LSOM) 21. . . . . . .
Defrost System 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Two−Stage Compressor Check−out 30. . . . . . . . . . . . . . .
Homeowner Information 30. . . . . . . . . . . . . . . . . . . . . . . .
Field Operational Checklist 32. . . . . . . . . . . . . . . . . . . . .
Start−up and Performance Checklist 32. . . . . . . . . . . . . .
Shipping and Packing List1
®
Litho U.S.A.
IMPORTANT
This unit must be matched with an indoor coil as specified in Lennox’ Engineering Handbook. Coils previously charged with HCFC−22 must be flushed.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs AND HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
06/09 505,331M
*2P0609* *P505331M*
Check the unit for shipping damage and listed times below are intact. If damaged, or if parts are missing, immediately contact the last shipping carrier.
1  Assembled outdoor unit. 1  Bag assembly which contains the followings:
1  Bushing (for low voltage wiring 2  Isolation grommets for liquid and suction lines
ISOLATION GROMMETS (2)
Figure 1. Bag Assembly (Parts)
Page 1
BUSHING (1)
Unit Dimensions −− Inches (mm)2
UNIT SUPPORT
FEET
16−7/8
(429)
8−3/4 (222)
3−1/8
(79)
39−1/2 (1003)
DISCHARGE AIR
SIDE VIEW
30−3/4
(781)
SUCTION LINE INLET
LIQUID LINE INLET
26−7/8
(683)
3−3/4 (95)
4−5/8 (117)
ELECTRICAL
INLETS
37 (940) [−024, −036]
47 (1194) [−048, −060]
18−1/2
(470)
CONTACTOR
DEFROST CONTROL
SYSTEM
OPERATION
MONITOR
VAPOR VALVE
AND GAUGE
PORT
DISCHARGE
LINE
REVERSING
VALV E
VAPOR LINE
FILTER DRIER
4−1/2 (114)
8 (203)
1 (25)
35−1/2
(902)
ACCESS VIEW
OUTDOOR FAN
RUN CAPACITOR
TWO−STAGE COMPRESSOR
COMPRESSOR TERMINAL PLUG
LOW PRESSURE SWITCH
HIGH PRESSURE SWITCH
BASE
WARNING
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
505331M 06/09
XP19 PARTS ARRANGEMENT
XP19 Heat Pumps3
The XP19 Heat Pumps, which will also be referred to in this instruction as the outdoor unit, uses HFC−410A refrigerant. This outdoor unit must be installed with a matching indoor unit and line set as outlined in the Lennox XP19 Engineering Handbook.
This outdoor unit is designed for use in systems that use check thermal expansion valve (CTXV) refrigerant metering devices.
General Information4
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.
When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. Table 1 shows torque values for fasteners.
Page 2
Table 1. Torque Requirements
Parts Recommended Torque
Service valve cap 8 ft.− lb. 11 NM
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 NM
USING MANIFOLD GAUGE SETS
When checking the system charge, only use a manifold gauge set that features low loss anti−blow back fittings. See Figure 3 for a typical manifold gauge connection setup.
Manifold gauge sets used with HFC−410A refrigerant systems must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 − 800 on the high side and a low side of 30" vacuum to 250 psi with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psi of pressure with a 4000 psi burst rating.
OPERATING SERVICE VALVES
The liquid and vapor line service valves are used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging.
Each valve is equipped with a service port which has a factory−installed valve stem.
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9 ft−lbs for small valves, to 25 ft−lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
1/12 TURN
12
1
2
3
4
7
5
6
9
10
8
11
1/6 TURN
12
1
2
3
4
7
5
6
11
10
9
8
Figure 2. Cap Tightening Distances
IMPORTANT
To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.
To Access Angle−Type Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and tighten as follows:
D With Torque Wrench: Finger tighten and then
tighten per Table 1.
D Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/6 turn clockwise as illustrated in Figure 2.
To Open and Close Angle−Type Service Valve:
A valve stem cap protects the valve stem from contamination and assures a leak−free seal.
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid-line valve sizes and 5/16" for vapor-line valve sizes) to back the stem out counterclockwise as far as it will go.
CHECK
EXPANSION VALVE
LOW
PRESSURE
GAUGE MANIFOLD
PRESSURE
TO HFC−410 A DRUM
HIGH
LIQUID LINE VALV E
Figure 3. Typical Manifold Gauge Connection Setup
BI−FLOW FILTER / DRIER
MUFFLER
LIQUID
SERVICE
PORT
DISTRIBUTOR
OUTDOOR
COIL
COMPRESSOR
Page 3
HEAT PUMP
REVERSING VALVE
VAPOR
SERVICE
PORT
NOTE − Arrows indicate direction of refrigerant flow.
VAPOR LINE VALV E
CHECK EXPANSION VALVE
INDOOR
COIL
XP19 SERIES
3. Replace the stem cap and tighten as follows:
D With Torque Wrench: Tighten finger tight and then
tighten per Table 1.
D Without Torque Wrench: Finger tighten and use an
appropriately sized wrenched to turn an additional 1/12 turn clockwise as illustrated in Figure 2.
SERVICE PORT
CORE
VALVE STEM
FRONT-SEATED
TO INDOOR
UNIT
TO OUTDOOR UNIT
SERVICE PORT
CAP
SERVICE PORT
(VALVE STEM SHOWN CLOSED) INSERT HEX WRENCH HERE
STEM CAP
CLOSED TO BOTH INDOOR
AND OUTDOOR UNITS
Figure 4. Angle−Type Service Valve
(Font−Seated Closed)
NOTE  A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
NOTE  To prevent stripping of the cap, the wrench should be appropriately sized and fit snugly over the cap before tightening the cap.
SERVICE PORT CAP
SERVICE PORT
CORE
OPEN TO BOTH
INDOOR AND
OUTDOOR UNITS
TO INDOOR
UNIT
TO OUTDOOR UNIT
STEM CAP
SERVICE PORT
(VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE
Figure 5. Angle−Type Service Valve
(Back−Seated Opened)
To Access Ball−Type Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and tighten as follows:
D With Torque Wrench: Finger tighten and then
tighten per Table 1.
D Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/6 turn clockwise as illustrated in Figure 2.
OPEN TO LINE SET WHEN VALVE IS CLOSED, TO BOTH LINE SET AND UNIT WHEN VALVE IS OPEN.
TO OPEN ROTATE STEM COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT
CORE
SERVICE PORT CAP
TO OUTDOOR UNIT
TO INDOOR UNIT
BALL (SHOWN CLOSED)
STEM CAP
VALV E STEM
Figure 6. Ball−Type Service Valve
To Open and Close Ball−Type Service Valve:
A valve stem cap protects the valve stem from contamination and assures a leak−free seal.
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrenched to open. To open valve, roate stem counterclockwise 90°. To close rotate stem clockwise 90°.
3. Replace the stem cap and tighten as follows:
D With Torque Wrench: Finger tighten and then
tighten per Table 1.
D Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/12 turn clockwise as illustrated in Figure 2.
NOTE  A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
Recovering Refrigerant from Existing System5
Remove existing HCFC−22 refrigerant using one of the following procedures:
METHOD 1:
If the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational and you plan to use the existing HCFC−22 to flush the system.
NOTE  Use recovery machine instructions for specific setup requirements.
1. Disconnect all power to the existing outdoor unit.
2. Connect to the existing unit a gauge set, clean recovery cylinder and a recovery machine. Use the instructions provided with the recovery machine on how to setup the connections.
505331M 06/09
Page 4
3. Remove all HCFC−22 refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.
RECOVERY MACHINE
CLEAN RECOVERY CYLINDER
MANIFOLD GAUGES
OUTDOOR UNIT
Figure 7. Typical Refrigerant Recovery
(Method 1)
NOTE  Use recovery machine instructions for specific setup requirements.
METHOD 2:
Use this method if the existing outdoor unit is equipped with manual shut−off valves, and plan on using new HCFC−22 refrigerant to flush the system.
IMPORTANT: Some system configurations may contain higher than normal refrigerant charge due to either large internal coil volumes, and/or long line sets. The following conditions may cause the compressor to stop functioning:
The following devices could prevent full system charge recovery into the outdoor unit:
S Outdoor unit’s high or low−pressure switches (if
applicable) when tripped can cycled the compressor OFF.
S Compressor can stop pumping due to tripped internal
pressure relief valve.
S Compressor has internal vacuum protection that is
designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed to go into a vacuum. Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seals).
Once the compressor can not pump down to a lower pressure due to one of the above system conditions, shut off the suction valve. Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.
Perform the following task:
1. Start the existing HCFC−22 system in the cooling mode and close the liquid line valve.
2. Pump as much of the existing HCFC−22 refrigerant with the compressor back into the outdoor unit until you have reached the limitations of the outdoor system. Turn the outdoor unit main power OFF and use a recovery machine to remove the remaining refrigerant in the system.
NOTE  It may be necessary to bypass the low pressure switches if equipped to ensure complete refrigerant evacuation.
3. When the low side system pressures reach 0 psig, close the suction line valve.
4. Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.
Removing Existing Outdoor Unit6
Perform the following task at the existing outdoor unit:
S Disconnect line set at the service valves. S Disconnect electrical service at the disconnect switch. S Remove old outdoor unit.
Positioning New Outdoor Unit7
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
See Unit Dimensions on page 3 for sizing mounting slab, platforms or supports. Refer to Figure 8 for mandatory installation clearance requirements.
CONTROL PANEL ACCESS LOCATION
SEE NOTES BELOW THIS FIGURE FOR FURTHER DETAILS.
Figure 8. Installation Clearances
NOTES:
S Service clearance of 30 in. (762 mm) must be
maintained on one of the sides adjacent to the control box.
S Clearance to one of the other three sides must be 36
in. (914 mm)
S Clearance to one of the remaining two sides may be
12 in. (305 mm) and the final side may be 6 in. (152
.
mm)
S 48 in. (1219 mm) clearance required on top of unit. S A clearance of 24 in. (610 mm) must be maintained
between two units.
.
Page 5
XP19 SERIES
POSITIONING CONSIDERATIONS
INSTALL UNIT AWAY
FROM WINDOWS
TWO 90° ELBOWS INSTALLED
IN LINE SET WILL REDUCE
LINE SET VIBRATION.
Figure 9. Outside Unit Placement
Consider the following when positioning the unit:
S Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line.
S When possible, do not install the unit directly outside
a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in Figure 9.
PLACING UNIT ON SLAB
When installing unit at grade level, the top of the slab should be high enough above grade so that water from higher ground will not collect around the unit. The slab should have a slope tolerance as described in Figure 10.
NOTE  If necessary for stability, anchor unit to slab as described in Stabilizing Unit on Uneven Surfaces on page
7.
ELEVATING THE UNIT
This unit is outfitted with elongated support feet as illustrated in Figure 11 which uses a similar method for elevating the unit.
BASE
LEG DETAIL
2" (50.8MM) SCH 40 FEMALE THREADED ADAPTER
Figure 11. Elevated Slab Mounting using Feet
Extenders
If additional elevation is necessary, raise the unit by extending the length of the unit support feet. This may be achieved by using a 2" SCH 40 female threaded adapter.
The specified coupling will fit snuggly into the recessed portion of the feet. Use additional 2" SCH 40 male threaded adaptors which can be threaded into the female threaded adaptors to make additional adjustments to the level of the unit.
NOTE  Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend further, consider a different type of field−fabricated framework that is sturdy enough for greater heights.
INSTALL UNIT LEVEL OR, IF ON A SLOPE, MAINTAIN SLOPE TOLERANCE OF 2 DEGREES (OR 2 INCHES PER 5 FEET [50 MM PER 1.5 M]) AWAY FROM BUILDING STRUCTURE.
STRUCTURE
GROUND LEVEL
Figure 10. Slab Mounting at Ground Level
505331M 06/09
BUILDING
MOUNTING SLAB
Removing and Installing Panels8
CAUTION
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and battered.
Page 6
WARNING
Unit must be grounded in accordance with national and local codes. Electric Shock Hazard. Can cause injury or death.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
IMPORTANT! DO NOT ALLOW PANELS TO HANG ON UNIT BY TOP TAB. TAB IS FOR ALIGNMENT AND NOT DESIGNED TO SUPPORT WEIGHT OF PANEL.
PANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TO EXIT (OR ENTER) TOP SLOT FOR REMOVING (OR INSTALLING) PANEL.
SCREW HOLES
LIP
ACCESS PANEL
Removal and reinstallation of the access panel is illustrated in Figure 12.
REMOVE 4 SCREWS TO REMOVE PANEL FOR ACCESSING COMPRESSOR AND CONTROLS.
INSTALL BY POSITIONING PANEL WITH HOLES ALIGNED; INSTALL SCREWS AND TIGHTEN.
Figure 12. Access Panel
LOUVERED PANELS
Remove the louvered panels as follows:
1. Remove two screws, allowing the panel to swing open slightly.
2. Hold the panel firmly throughout this procedure. Rotate bottom corner of panel away from hinged corner post until lower three tabs clear the slots as illustrated in Figure 13, detail B.
3. Move panel down until lip of upper tab clears the top slot in corner post as illustrated in Figure 13, detail A.
Position and Install PanelPosition the panel almost parallel with the unit as illustrated in Figure 14, detail D with the screw side as close to the unit as possible. Then, in a continuous motion:
S Slightly rotate and guide the lip of top tab inward as
illustrated in Figure 13, details A and C; then upward into the top slot of the hinge corner post.
S Rotate panel to vertical to fully engage all tabs. S Holding the panel’s hinged side firmly in place, close
the right−hand side of the panel, aligning the screw holes.
When panel is correctly positioned and aligned, insert the screws and tighten.
Detail A
Detail B
Detail C
ROTATE IN THIS DIRECTION; THEN DOWN TO REMOVE PANEL
Figure 13. Removing/Installing Louvered Panels
(Detail A, B and C)
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL WITH THE UNIT AS POSSIBLE) WHILE INSTALLING PANEL.
ANGLE MAY BE TOO EXTREME
PREFERRED ANGLE FOR INSTALLATION
HOLD DOOR FIRMLY ALONG
THE HINGED SIDE TO MAINTAIN
FULLY−ENGAGED TABS
Detail D
Figure 14. Removing/Installing Louvered Panels
(Detail D)
STABILIZING UNIT ON UNEVEN SURFACES
With unit positioned at installation site, remove two side louvered panels to expose the unit base pan. Install the brackets as illustrated in Figure 15 using conventional
practices; replace the panels after installation is complete.
Page 7
XP19 SERIES
IMPORTANT
Unit Stabilizer Bracket Use (field−provided):
Always use stabilizers when unit is raised above the factory height. (Elevated units could become unstable in gusty wind conditions).
Stabilizers may be used on factory height units when mounted on unstable an uneven surface.
To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors commonly available in the marketplace.
Slab Side Mounting
REFRIGERANT LINE SET
Field refrigerant piping consists of liquid and suction lines from the outdoor unit (braze connections) to the indoor unit coil (flare or sweat connections). Use Lennox L15 (sweat, non−flare) series line set, or use field−fabricated refrigerant lines as listed in Table 2.
Table 2. Refrigerant Line Set
Field Connections Recommended Line Set
Model
−024
−036
−048
−060
Liquid
Line
3/8". (10 mm)
3/8". (10 mm)
Suction
Line
7/8" (22 mm)
1−1/8". (29 mm)
Liquid
Line
3/8" (10 mm)
3/8" (10 mm)
Suction
Line
7/8" (22 mm)
1−1/8" (29 mm)
L15 Line Set
L15−65 15 ft. − 50 ft. (4.6 m − 15 m)
Field Fabricated
#10 1/2" LONG SELF−
DRILLING SHEET
METAL SCREWS
STABILIZING
BRACKET (18 GAUGE
METAL − 2" WIDTH;
HEIGHT AS REQ’D)
#10 1−1/4" LONG
HEX HD SCREW
AND FLATWASHER
CONCRETE SLAB − USE PLASTIC PLASTIC ANCHOR (HOLE DRILL 1/4")PLASTIC SLAB − NO PLASTIC ANCHOR (HOLE DRILL 1/8")
COIL
BASE PAN
CORNER POST
Deck Top Mounting
STABILIZING BRACKET (18 GAUGE METAL − 2" WIDTH; HEIGHT AS REQ’D); BEND TO FORM RIGHT ANGLE
FOR EXTRA
ONE BRACKET PER SIDE (MIN.); FOR EXTRA STABILITY, 2 BRACKETS PER SIDE, 2" FROM EACH CORNER.
STABILITY
MINIMUM 1 PER SIDE
Figure 15. Installing Stabilizer Brackets
New or Replacement Line Set9
This section provides information on installation or replacement of existing line set. If line set are not being installed then proceed to Brazing Connections on page 12.
If refrigerant lines are routed through a wall, seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds. Also, consider the following when placing and installing a high−efficiency air conditioner.
NOTE  When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fabrication Guidelines, or contact Lennox Technical Support Product Applications for assistance. To obtain the correct information from Lennox, be sure to communicate the following points:
S Model (XP19) and size of unit (e.g. −060). S Line set diameters for the unit being installed as listed
in Table 2 and total length of installation.
S Number of elbows and if there is a rise or drop of the
piping.
MATCHING WITH NEW OR EXISTING INDOOR COIL AND LINE SET
The RFC1−metering line consisted of a small bore copper line that ran from condenser to evaporator coil. Refrigerant was metered into the evaporator by utilizing temperature/pressure evaporation effects on refrigerant in the small RFC line. The length and bore of the RFC line corresponded to the size of cooling unit.
If the XP19 is being used with either a new or existing indoor coil which is equipped with a liquid line which served as a metering device (RFCI), the liquid line must be replaced prior to the installation of the XP19 unit. Typically a liquid line used to meter flow is 1/4" in diameter and copper.
INSTALLING LINE SET Line Set Isolation  This reference illustrates
procedures, which ensure proper refrigerant line set isolation:
S Installation of line set on horizontal runs is
illustrated in Figure 16.
S Installation of line set on vertical runs is illustrated in
Figure 17.
S Installation of a transition from horizontal to
vertical is illustrated in Figure 18.
505331M 06/09
Page 8
TO HANG LINE SET FROM JOIST OR RAFTER, USE EITHER METAL STRAPPING MATERIAL OR ANCHORED HEAVY NYLON WIRE TIES.
STRAPPING MATERIAL
(AROUND SUCTION
LINE ONLY)
FLOOR JOIST OR
ROOF RAFTER
TAPE OR WIRE TIE
8 FEET
FLOOR JOIST OR
ROOF RAFTER
METAL
SLEEVE
WIRE TIE (AROUND SUCTION LINE ONLY)
TAPE OR
8 FEET
STRAP THE SUCTION LINE TO THE JOIST OR RAFTER AT 8 FEET INTERVALS THEN STRAP THE LIQUID LINE TO THE SUCTION LINE.
WIRE TIE
AUTOMOTIVE
STRAP LIQUID LINE TO SUCTION LINE
LIQUID LINE
SUCTION LINE − WRAPPED IN ARMAFLEX
ANCHORED HEAVY NYLON WIRE TIE OR AUTOMOTIVE MUFFLER-TYPE HANGER
WALL STUD
METAL SLEEVE
MUFFLER-TYPE HANGER
Figure 18. Refrigerant Line Set: Transition from
Vertical to Horizontal
Figure 16. Refrigerant Line Set: Installing
Horizontal Runs
IMPORTANT - REFRIGERANT LINES
OUTSIDE WALL
WOOD BLOCK
BETWEEN STUDS
NOTE − SIMILAR INSTALLATION PRACTICES SHOULD BE USED IF LINE SET IS TO BE INSTALLED ON EXTERIOR OF OUTSIDE WALL.
SUCTION LINE
WRAPPED WITH
ARMAFLEX
OUTSIDE
PVC
PIPE
MUST NOT CONTACT WALL.
LIQUID LINE
WALL
CAULK
FIBERGLASS
INSULATION
SUCTION LINE
SLEEVE
IMPORTANT! REFRIGERANT LINES MUST NOT CONTACT STRUCTURE.
LIQUID LINE
WIRE TIE
INSIDE WALL
STRAP
SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
Brazing Connections10
Use the following procedure to braze the line set to the new air conditioner unit. Figure 19 is provided as a general guide for preparing to braze the line set to the air conditioner unit.
WARNING
Polyol ester (POE) oils used with HFC−410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
WARNING
Danger of fire. Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubing being pressurized. Application of a brazing torch while pressurized may result in ignition of the refrigerant and oil mixture − check the high and low pressures before unbrazing.
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
Figure 17. Refrigerant Line Set: Installing Vertical
Runs (New Construction Shown)
1. Cut ends of the refrigerant lines square (free from nicks or dents). Debur the ends. The pipe must remain round, do not pinch end of the line.
Page 9
XP19 SERIES
1
2
3
CUT AND DEBUR
7
INSTALL CORE ONLY FOR
BOTH SERVICE PORTS after they
have coolED.
INDOOR UNIT
6
BRAZE LINE SET
REMOVE CAP AND CORE FROM
BOTH LIQUID AND SUCTION
SERVICE PORTS
SERVICE PORT MUST BE
OPEN TO ALLOW EXIT POINT FOR NITROGEN
SUCTION LINE
LIQUID LINE
Figure 19. Brazing Connections
2. Remove service cap and core from both the suction and liquid line service ports.
3. Connect gauge low pressure side to liquid line service valve.
4. To protect components during brazing, wrap a wet cloth around the liquid line service valve body and copper tube stub and use another wet cloth underneath the valve body to protect the base paint. Also, shield the light maroon R−410A sticker.
5. Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid line service valve and out of the valve stem port connection on the suction service valve.
ATTACH
GAUGES
SERVICE
5
VALVE
SERVICE
VALVE
outdoor
UNIT
FLOW NITROGEN
NITROGEN
4
WRAP
SERVICE
VALV E
Removing Indoor Unit Metering Device11
Remove the existing HCFC−22 refrigerant flow control orifice or thermal expansion valve from the indoor coil. The existing indoor unit HCFC−22 metering device is not approved for use with HFC−410A refrigerant and may prevent proper flushing.
REPLACEMENT PARTS
If replacement parts are necessary for the indoor unit, order kit 69J46. The kit includes:
LIQUID LINE ORIFICE HOUSINGS (10)
TEFLON RINGS (20)
BRASS NUTS (10)
PISTON RETAINER
STRAINER
NOTE  The RFCIV or TXV metering device at the indoor unit will allow low pressure nitrogen to flow through the system.)
6. Braze the liquid line to the liquid line service valve. Turn off nitrogen flow. Repeat procedure starting at paragraph 4 for brazing the suction line to the suction service valve.
7. After all connections have been brazed, disconnect manifold gauge set the from service ports, cool down piping with wet rag and remove all wrappings. Do not reinstall cores until after evacuation procedures. Reinstall service caps if desired to close off refrigerant ports.
505331M 06/09
Page 10
COPPER TUBE
LIQUID LINE ASSEMBLIES
(INCLUDES STRAINER) (10)
LIQUID LINE
ASSEMBLY
Figure 20. 69J46 Kit Components
TYPICAL FIXED ORIFICE REMOVAL PROCEDURE
1. On fully cased coils, remove the coil access and plumbing panels.
2. Remove any shipping clamps holding the liquid line and distributor assembly.
3. Using two wrenches, disconnect liquid line from liquid line orifice housing. Take care not to twist or damage distributor tubes during this process.
4. Remove and discard fixed orifice, valve stem assembly if present and Teflon washer as illustrated in Figure 21.
5. Use a field−provided fitting to temporary reconnect the liquid line to the indoor unit’s liquid line orifice housing.
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
TEFLON RING
(Uncased Coil Shown)
FIXED ORIFICE
BRASS NUT
7. Remove and discard TXV and the two Teflon rings.
8. Use a field−provided fitting to temporary reconnect the liquid line to the indoor unit’s liquid line orifice housing.
Flushing the System12
IMPORTANT
The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant that previously charged the system. Check the charge in the flushing cylinder before proceeding.
DISTRIBUTOR
ASSEMBLY
REMOVE AND
DISCARD
WHITE TEFLON SEAL
(IF PRESENT)
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
Figure 21. Typical Fixed Orifice Removal
TYPICAL TXV REMOVAL PROCEDURE
(Uncased Coil Shown)
TWO PIECE
PATCH PLATE
(UNCASED COIL
ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE
FITTING
LIQUID LINE
ORIFICE HOUSING
EQUALIZER LINE
SENSING BULB
STUB END
TXV
TEFLON RING
LIQUID LINE ASSEMBLY
WITH BRASS NUT
SUCTION
LINE
TEFLON
RING
SENSING
LINE
LIQUID
LINE
Figure 22. Typical TXV Removal
1. On fully cased coils, remove the coil access and plumbing panels.
2. Remove any shipping clamps holding the liquid line and distributor assembly.
3. Disconnect the equalizer line from the TXV equalizer line fitting on the suction line.
4. Remove the suction line sensing bulb.
5. Disconnect the liquid line from the TXV at the liquid line assembly.
6. Disconnect the TXV from the liquid line orifice housing. Take care not to twist or damage distributor tubes during this process.
IMPORTANT
If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC−410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity. Failure to properly flush the system per the instructions below will void the warranty.
IMPORTANT
The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.
INVERTED HCFC−22 CYLINDER CONTAINS CLEAN HCFC−22 TO BE USED FOR FLUSHING.
SUCTION LINE
SERVICE VALVE
EXISTING
INDOOR
UNIT
LIQUID LINE SERVICE VALVE
RECOVERY
CYLINDER
SUCTION
LIQUID
NOTE − THE INVERTED HCFC−22 CYLINDER MUST CONTAIN AT LEAST THE SAME AMOUNT OF REFRIGERANT AS WAS RECOVERED FROM THE EXISTING SYSTEM.
NEW
OUTDOOR
UNIT
OPENED
RECOVERY MACHINE
Figure 23. Typical Flushing Connection
GAUGE
MANIFOLD
LOW
PRESSURE
TANK RETURN
INLET
DISCHARGE
HIGH
PRESSURE
CLOSED
Page 11
XP19 SERIES
CAUTION
This procedure should not be performed on systems which contain contaminants (Example: compressor burn out).
If the original system used:
S HCFC−22 refrigerant, then flush the system using the
procedure provided in this section.
9
10
8
11
1/8 TURN
10
8
11
12
7
6
12
1
2
3
9
4
7
5
6
1/2 TURN
1
2
3
4
5
S HFC−410A refrigerant, then proceed to Installing New
Refrigerant Metering Device.
REQUIRED EQUIPMENT
Equipment required to flush the existing line set and indoor unit coil:
S Two clean HCFC−22 recovery bottles,
S Oilless recovery machine with pump-down feature,
S Two gauge sets (one for HCFC−22; one for
HFC−410A).
FLUSHING PROCEDURE
1. Connect the following:
S HCFC−22 cylinder with clean refrigerant to the
suction service valve,
S HCFC−22 gauge set to the liquid line valve,
S Recovery machine with an empty recovery tank to
the gauge set.
2. Set the recovery machine for liquid recovery and start the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor unit coil.
Figure 24. Tightening Distance
TYPICAL CTXV INSTALLATION PROCEDURE
The CTXV unit can be installed internal or external to the indoor coil. In applications where an uncased coil is being installed in a field−provided plenum, install the CTXV in a manner that will provide access for field servicing of the CTXV. Refer to Figure 25 for reference during installation of CTXV unit.
TWO PIECE
PATCH PLATE
(UNCASED COIL
ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
(Uncased Coil Shown)
LIQUID LINE
ORIFICE
HOUSING
EQUALIZER LINE
STUB END
TEFLON RING
LIQUID LINE ASSEMBLY
WITH BRASS NUT
CTXV
TEFLON
RING
SENSING
LINE
3. Invert the cylinder of clean HCFC−22 and open its valve to allow liquid refrigerant to flow into the system through the suction line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine.
4. After all of the liquid refrigerant has been recovered, switch the recovery machine to suction recovery so that all of the HCFC−22 suction is recovered. Allow the recovery machine to pull a vacuum on the system.
5. Close the valve on the inverted HCFC−22 drum and the gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
Installing New Indoor Metering Device13
XP19 units use CTXV for metering refrigerant only. This section provides instructions on installing CTXV refrigerant metering device.
505331M 06/09
Page 12
MALE EQUALIZER LINE FITTING (SEE FIGURE 27 FOR FURTHER DETAILS)
SENSING BULB INSULATION IS REQUIRED IF MOUNTED EXTERNAL TO THE COIL CASING. SEE FIGURE 26 FOR BULB POSITIONING.
SUCTION LINE
LIQUID
LINE
Figure 25. Typical TXV Installation
1. Remove the field−provided fitting that temporary reconnected the liquid line to the indoor unit’s distributor assembly.
2. Install one of the provided Teflon rings around the stubbed end of the CTXV and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil.
3. Attach the stubbed end of the CTXV to the liquid line orifice housing. Finger tighten and use an appropriately
sized wrench to turn an additional 1/2 turn clockwise as illustrated in Figure 24, or 20 ft−lb.
4. Place the remaining Teflon washer around the other end of the CTXV. Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant oil.
5. Attach the liquid line assembly to the CTXV. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in Figure 24, or 20 ft−lb.
6. Attach the suction line sensing bulb in the proper orientation as illustrated in Figure 26 using the clamp and screws provided.
NOTE  Insulating the sensing bulb once installed may be required when the bulb location is external to the coil casing.
SUCTION LINE
BULB
12
ON LINES SMALLER THAN 7/8", MOUNT SENSING BULB AT EITHER THE 3 OR 9 O’CLOCK POSITION.
BULB
IMPORTANT
When removing the flare nut, ensure that the copper flare seal bonnet is removed.
8. Connect the equalizer line from the TXV to the equalizer suction port on the suction line. Finger tighten the flare nut plus 1/8 turn (7 ft−lbs) as illustrated in Figure 24.
NOTE  To prevent any possibility of water damage, properly insulate all parts of the TXV assembly that may sweat due to temperature differences between the valve and its surrounding ambient temperatures.
See the XP19 Engineering Handbook for approved CTXV kit match−ups and application information.
The reference CTXV kits include: 1  CTXV 2  Teflon rings 1  1 1/4" wide copper mounting strap for sensing bulb 2  #10 hex head bolts and nuts for securing sensing bulb
SUCTION LINE
12
BULB
NOTE − NEVER MOUNT ON BOTTOM OF LINE.
ON 7/8" AND LARGER LINES, MOUNT SENSING BULB AT EITHER THE 4 OR 8 O’CLOCK POSITION. NEVER MOUNT ON BOTTOM OF LINE.
BULB
Figure 26. TXV Sensing Bulb Installation
7. Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the suction line as illustrated in Figure 27.
FLARE SEAL
CAP
OR
MALE BRASS EQUALIZER
FLARE NUT
COPPER
FLARE SEAL
BONNET
LINE FITTING
SUCTION LINE
Figure 27. Copper Flare Seal Bonnet Removal
CTXV (1)
HEX HEAD BOLTS
AND NUTS (2)
TEFLON RINGS (2)
COPPER
MOUNTING
STRAP (1)
Figure 28. CTXV Kit Components
Testing for Leaks14
After the line set has been connected to the indoor unit and air conditioner, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks:
IMPORTANT
Leak detector must be capable of sensing HFC refrigerant.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
Page 13
XP19 SERIES
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
Evacuating the System15
Evacuating the system of non−condensables is critical for proper operation of the unit. Non−condensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Non−condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts.
WARNING
Fire, Explosion and Personal Safety Hazard.
Failure to follow this warning could result in damage, personal injury or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause damage by fire and/ or an explosion, that could result in personal injury or death.
1. Connect an HFC−410A manifold gauge set high pressure hose to the suction valve service port.
(Normally, the high pressure hose is connected to the liquid line port; however, connecting it to the suction port better protects the manifold gauge set from high pressure damage.)
2. With both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of the manifold gauge set. Open the valve on the HFC−410A cylinder (suction only).
3. Open the high pressure side of the manifold to allow HFC−410A into the line set and indoor unit. Weigh in a trace amount of HFC−410A. [A trace amount is a
maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the
HFC−410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC−410A cylinder.
4. Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.
5. Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit.
6. After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector.
7. After leak testing disconnect gauges from service ports.
WARNING
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
IMPORTANT
NOTE  Remove cores from service valves if not already done.
1. Connect manifold gauge set to the service valve ports as follows:
S low pressure gauge to suction line service valve S high pressure gauge to liquid line service valve
2. Connect micron gauge.
3. Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set.
4. Open both manifold valves and start the vacuum pump.
5. Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
NOTE  During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in sure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE  The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
6. When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a dry nitrogen
505331M 06/09
Page 14
cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves.
7. Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the dry nitrogen from the line set and indoor unit.
8. Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing the manifold gauge valves.
9. When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an upright cylinder of HFC−410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit.
10. Perform the following:
A Close manifold gauge valves. B Shut off HFC−410A cylinder. C Reinstall service valve cores by removing
manifold hose form service valve. Quickly install core with core tool while maintaining a positive system pressure.
D Replace the stem caps and secure finger tight,
then tighten an additional one−sixth (1/6) of a turn as illustrated in Figure 2.
Servicing Units Delivered Void of Charge16
If the outdoor unit is void of refrigerant, clean the system using the procedure described below.
1. Use nitrogen to pressurize the system and check for leaks. Repair all leaks.
2. Evacuate the system to remove as much of the moisture as possible.
3. Use nitrogen to break the vacuum and install a new filter drier in the system.
4. Evacuate the system again. Then, weigh the appropriate amount of HFC−410A refrigerant as listed on unit nameplate into the system.
5. Monitor the system to determine the amount of moisture remaining in the oil. It may be necessary to replace the filter drier several times to achieve the required dryness level. If system dryness is not
verified, the compressor will fail in the future.
Figure 29. XP19 Wiring
Page 15
BLUE WIRE
Y2 OUT
DEFROST BOARD DETAIL
SHIPPED AS SHOWN ABOVE WITH TERMINAL CRIMPED TO BLUE WIRE; USE TERMINAL OR CUT OFF TERMINAL AND SPLICE BLUE
WIRE WITH Y2 WIRE TO INDOOR UNIT.
WITH CRIMPED
TERMINAL
XP19 SERIES
Electrical Connections17
WARNING
Electric shock hazard. Can cause injury or death.
Line voltage is present at all components on units with single−pole contactors, even when unit is not in operation!
Unit may have multiple power supplies. Disconnect all remote electric power supplies before opening access panel.
Unit must be grounded in accordance with national and local codes.
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
230VAC SUPPLY VOLTAGE
The XP19 outdoor unit is rated for 230VAC applications only. A hard-start kit is required for applications where the supply voltage is less than 230VAC.
24VAC TRANSFORMER
Use the transformer provided with the furnace or coil blower for low-voltage control power (24VAC − 40 VA minimum)
NOTE  The addition of accessories to the system could exceed the 40 VA power requirement of the factory-provided transformer. Measure the system’s current and voltage after installation is complete to determine transformer loading. If loading exceeds the factory-provided transformer capacity, a larger field-provided transformer will need to be installed in the system.
WIRING CONNECTIONS
1. Install line voltage power supply to unit from a properly sized disconnect switch.
2. Ground unit at unit disconnect switch or to an earth ground.
NOTE  Connect conduit to the unit using a proper conduit fitting. Units are approved for use only with copper conductors. A complete unit wiring diagram is located on the back side of the unit’s access panel.
NOTE  For proper voltages, select thermostat wire gauge per the following chart:
Table 3. Wire Run Length
Wire Run Length AWG # Insulation Type
less than 100’ (30m) 18
more than 100’ (30m) 16
3. Install room thermostat (ordered separately) on an inside wall approximately in the center of the area and 5 feet (1.5 m) from the floor. Do not install on an outside wall or where sunlight, drafts or vibrations affect it.
4. Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit as illustrated in Figure 29.
THERMOSTAT SECOND−STAGE COOLING CONNECTIONS
The Lennox System Operation Monitor (LSOM) requires a twos−stage room thermostat to operating properly.
color−coded, temperature rating 35ºC minimum
S Y2 Room Thermostat Wire  Connect the Y2 room
thermostat wire from the outdoor unit to the Y2 input on the DCB.
S L Terminal Wiring  Connect L terminal of the room
thermostat to the L (brown) field wire connection.
S Y2 DC Solenoid Connector (DC SOL)  The two−pin
DC solenoid connector is connected at the factory to the compressor second−state solenoid connector. No field connections are required for this component.
NOTE  Wiring the module incorrectly will cause false LED codes. Table 14 describes LED operation when the module is incorrectly wired and the action required to correct the problem.
Start−Up and Charging Procedures18
IMPORTANT
If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start−up to prevent compressor damage as a result of slugging.
1. Rotate fan to check for binding.
2. Inspect all factory− and field−installed wiring for loose connections.
3. After evacuation is complete, open both the liquid and vapor line service valves to release the refrigerant charge contained in outdoor unit into the system.
4. Replace the stem caps and tighten to the value listed in Table 1.
5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit’s nameplate. If not, do not start the equipment until you have consulted with the power company and the voltage condition has been corrected.
6. Set the thermostat for a cooling demand. Turn on power to the indoor indoor unit and close the outdoor unit disconnect switch to start the unit.
7. Recheck voltage while the unit is running. Power must be within range shown on the nameplate.
505331M 06/09
Page 16
8. Check system for sufficient refrigerate by using the procedures listed under Testing and Charging System.
TESTING AND CHARGING SYSTEM
This system uses HFC−410A refrigerant which operates at much higher pressures than HCFC−22. The pre−installed liquid line filter drier is approved for use with HFC−410A only. Do not replace it with components designed for use with HCFC−22. This unit is NOT approved for use with coils which use capillary tubes as a refrigerant metering device.
SETTING UP TO CHECK CHARGE
1. Close manifold gauge set valves. Connect the center manifold hose to an upright cylinder of HFC−410A.
2. Connect the manifold gauge set to the unit’s service ports as illustrated in Figure 3.
D low pressure gauge to vapor service port D high pressure gauge to liquid service port
COOLING MODE INDOOR AIRFLOW CHECK
Check airflow using the Delta−T (
DT) process using the
illustration in Figure 30.
HEATING MODE INDOOR AIRFLOW CHECK
Blower airflow (CFM) may be calculated by energizing electric heat and measuring:
Temp. of air entering indoor coil ºF
A
Wet−bulb ºF
53º
DRY
BULB
80 24 24 24 23 23 22 22 22 20 19 18 17 16 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13 74 21 21 21 20 19 19 18 17 16 16 15 14 13 12
Dry−bulb
72 20 20 19 18 17 17 16 15 15 14 13 12 11 10
70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
57 58 59 60 61 62 63 64 65 66 67 68 69 70
T
C
Drop
19º
All temperatures are
expressed in ºF
DT
air flowair flow
INDOOR COIL
B
A
72º
B
64º
WET
BULB
DRY
BULB
S Temperature rise between the return air and supply air
temperatures at the indoor coil blower unit,
S Measuring voltage supplied to the unit,
S Measuring amperage being drawn by the heat unit(s).
Then, apply the measurements taken in following formula to determine CFM:
CFM =
CALCULATING CHARGE
If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit. To calculate the total refrigerant charge:
Amount
specified
on
nameplate
1. Determine the desired DTMeasure entering air temperature using dry bulb (A) and wet bulb (B). DT is the intersecting value of A and B in the Table (see triangle).
2. Find temperature drop across coilMeasure the coil’s dry bulb entering and leaving air temperatures (A and C). Temperature Drop Formula: (T
3. Determine if fan needs adjustmentIf the difference between the measured T justment is needed. See examples: Assume DT = 15 and A temp. = 72º, these C temperatures would necessitate stated actions:
Cº T
Drop
53º 19 15 = 4 Increase the airflow 58º 14 15 = −1 (within +3º range) no change 62º 10 15 = −5 Decrease the airflow
4. Adjust the fan speedSee indoor unit instructions to in-
crease/decrease fan speed.
Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and DT are within +3º.
Amps x Volts x 3.41
1.08 x Temperature rise (F)
Additional charge
Adjust amount. for
variation in line set
length listed on Table
in Figure 31.
specified per
indoor unit
match−up listed in
Tables 4 through
+ + =
) = A minus C.
Drop
and the desired DT (T
Drop
DT = ºF ACTION
DT) is within +3º, no ad-
Drop
7.
charge
Total
Figure 30. Checking Indoor Airflow over Evaporator Coil using Delta−T Chart
Page 17
XP19 SERIES
WEIGH IN
Refrigerant Charge per Line Set Length
Liquid Line
Set Diameter
3/8" (9.5 mm)
NOTE − *If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
SUBCOOLING
Ounces per 5 feet (g per 1.5 m)
adjust from 15 feet (4.6 m) line set*
3 ounce per 5’ (85 g per 1.5 m)
1 Check the airflow as illustrated in Figure 30 to be sure the indoor airflow is as required.
(Make any air flow adjustments before continuing with the following procedure.)
2 Measure outdoor ambient temperature; determine whether to use cooling mode or
heating mode to check charge.
3 Connect gauge set. 4 Check liquid and vapor line pressures. Compare pressures with either cooling or heating
mode normal operating pressures in Table 8 (second stage − high capacity).
USE COOLING
MODE
60ºF (15º)
USE HEATING
MODE
NOTE − The reference table is a general guide. Expect minor pressure variations. Significant
differences may mean improper charge or other system problem.)
5 Set thermostat for heat/cool demand, depending on mode being used:
Using cooling modeWhen the outdoor ambient temperature is 60°F (15°C) and above. Target subcooling values (second stage − high capacity) in Table 8 are based on 70 to 80°F (21−27°C) indoor return air temperature; if necessary, operate heating to reach that temperature range; then set thermostat to cooling mode setpoint to 68ºF (20ºC) which should call for second stage (high capacity) cooling. When pressures have stabilized, continue with step 6.
Figure 31. Using Weigh In Method
1. Check Liquid and suction line pressures
2. Compare unit pressures with Table 8, Normal Operating Pressures.
3. Conduct leak check; evacuate as previously outlined.
4. Weigh in the unit nameplate charge plus any charge required for line set differences over feet.
This nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.
SATº LIQº – SCº =
Using heating modeWhen the outdoor ambient temperature is below 60°F (15°C). Target
subcooling values (second stage − high capacity) in Table 8 are based on 65−75°F (18−24°C) indoor return air temperature; if necessary, operate cooling to reach that temperature range; then set thermostat to heating mode setpoint to 77ºF (25ºC) which should call for second stage (high capacity) heating. When pressures have stabilized, continue with step 6.
6 Read the liquid line temperature; record in the LIQº space. 7 Read the liquid line pressure; then find its corresponding temperature in the temperature/
pressure chart listed in Table 9 and record it in the SATº space. 8 Subtract LIQº temp. from SATº temp. to determine subcooling; record it in SCº space. 9 Compare SCº results with tables below, being sure to note any additional charge for line set
and/or match−up.
10 If subcooling value is greater than shown in Tables 4 through 7 for the applicable unit, remove
refrigerant; if less than shown, add refrigerant. 11 If refrigerant is added or removed, repeat steps 4 through 10 to verify charge.
Figure 32. Using Subcooling Method  Second Stage (High Capacity)
505331M 06/09
Page 18
** Amount of charge required in additional to charge shown on unit nameplate. Remember to consider line set length difference.
Table 4  XP19−024
INDOOR HEAT MATCH−UP PUMP
C33−31 12 7 0 1 C33–38 SN# before SN#6007K 31 7 0 6 C33–38 SN#6007K and after 10 8 0 6 CBX27UH−030−230 10 6 0 6 CB30U−31 12 7 0 1 CB30U−41 10 6 0 6 CB31MV−41 10 6 0 6 CBX32M−030−230 12 7 0 1 CBX32M−036−230 10 6 0 6 CBX32MV−024/030−230 12 8 0 0 CBX32MV−036−230 10 6 0 6 CBX40UHV−024, −030 12 8 0 0 CBX40UHV−036 10 6 0 6 CH33−44/48, −48C 8 7 1 0 CR33−48 6 6 1 3 CR33−50/60 8 6 1 0 CR33−60 8 6 1 0 CX34−31 12 7 0 1 CX34−38 SN# before SN#6007K 31 7 0 6 CX34−38 SN#6007K and after 10 8 0 6
TargetSubcooling
HeatingCooling
5ºF)(+1ºF)
(+
**Add
charge
lb oz
Table 5  XP19−036
INDOOR HEAT MATCH−UP PUMP
C33−38 SN# before SN#6007K 31 7 0 0 C33−38 SN#6007K and after 10 8 0 0 C33−44, −48 14 6 0 7 C33−49 6 6 1 5 C33−50/60C 12 5 0 13 C33−60D 8 5 0 15 C33−62D 6 6 1 5 CH23−51 14 6 0 5 CH23−65 12 5 0 13 CBX27UH−036−230 14 6 0 7 CBX27UH−042−230 6 6 1 5 CB29M−51 6 6 1 5 CB30M−41, −46 14 6 0 7 CB30M−51 6 6 1 5 CB30U−51 6 6 1 5 CB31MV−41 14 6 0 7 CB31MV−51 6 6 1 5 CBX32M−036−230 14 6 0 7 CBX32M−042−230 14 6 0 7 CBX32M−048−230 6 6 1 5 CBX32MV−036−230 14 6 0 5 CBX32MV−048−230 6 6 1 5 CBX40UHV−036 14 6 0 5 CBX40UHV−042, −048 6 6 1 5 CH33−44/48B 12 5 0 13 CH33−48 12 5 0 13 CR33−48 30 5 0 0 CR33−50/60, −60 15 4 1 5
TargetSubcooling
HeatingCooling
5ºF)(+1ºF)
(+
**Add
charge
lb oz
Table 8  XP19−036 (Continued)
INDOOR HEAT MATCH−UP PUMP
CX34−48 SN# before SN#6007K 31 7 0 0 CX34−48 SN#6007K and after 10 8 0 0 CX34−44/48 30 5 0 0 CX34−49 6 6 1 5 CX34−50/60C 12 5 0 13 CX34−60D 8 5 0 15 CX34−62D 6 6 1 5
TargetSubcooling
HeatingCooling
5ºF)(+1ºF)
(+
**Add
charge
Table 6  XP19−048
INDOOR HEAT MATCH−UP PUMP
C33−49 13 5 0 5 C33−60D 20 4 0 0 C33−62C, −62D 12 5 0 8 CBX27UH−048−230 13 5 0 5 CBX27UH−060−230 13 5 0 5 CB30M−51, −65 13 5 0 5 CB30U−51, −65 13 5 0 5 CB31MV−51, −65 13 5 0 5 CBX32M−048−230 13 5 0 5 CBX32M−060−230 13 5 0 5 CBX32MV−048−230 13 5 0 5 CBX32MV−060−230 13 6 0 5 CBX32MV−068−230 10 6 0 13 CBX40UHV−048 13 5 0 5 CBX40UHV−060 13 6 0 5 CH23−68 12 7 0 13 CH33−50/60C 20 7 0 5 CH33−62D 13 5 0 5 CR33−50/60. −60 20 4 0 5 CX34−49 13 5 0 5 CX34−60D 20 4 0 0 CX34−62C, −62D 12 5 0 8
TargetSubcooling
HeatingCooling
5ºF)(+1ºF)
(+
**Add
charge
lb oz
Table 7  XP19−060
INDOOR HEAT MATCH−UP PUMP
C33−49 16 5 1 0 C33−60D 24 5 0 0 C33−62C, −62D 13 5 0 11 CBX27UH−060−230 16 5 1 0 CB30M−51, −65 16 5 1 0 CB30U−41, −65 16 5 1 0 CB31MV−51, −65 16 5 1 0 CBX32M−048−230 16 5 1 0 CBX32M−060−230 16 5 1 0 CBX32MV−048−230 16 5 1 0 CBX32MV−060−230 16 6 1 0 CBX32MV−068−230 14 4 1 0 CBX40UHV−048 16 5 1 0 CBX40UHV−060 16 6 1 0 CH23−68 14 4 1 0 CH33−62D 18 4 1 0 CR33−50/60, −60 24 5 0 0 CX34−49 16 5 1 0 CX34−60D 24 5 0 0 CX34−62C, −62D 13 5 0 11
TargetSubcooling
HeatingCooling
5ºF)(+1ºF)
(+
**Add
charge
lb oz
Page 19
XP19 SERIES
Table 8. Normal Operating Pressure − Liquid +10 and Vapor
+
5 PSIG*
IMPORTANT
Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system.
XP19−024 XP19−036 XP19−048 XP19−060
5F (5C)**
40 (4.4) 314 100 316 99 350 98 365 96
50 (10) 334 120 334 11 7 367 111 388 112
20 (−7.0) 304 68 294 64 314 60 346 60
30 (−1.0) 323 82 313 77 331 72 362 72
40 (4.4) 342 98 329 89 358 85 382 85
50 (10) 364 11 6 344 109 384 107 409 106
65 (18.3) 226 152 230 148 210 136 234 135
75 (23.9) 262 151 267 150 242 138 274 137
85 (29.4) 304 152 309 153 286 140 314 142
95 (35.0) 351 155 355 155 328 142 361 147
105 (40.6) 400 158 404 157 374 144 413 147
115 (49.0) 454 161 460 159 426 146 470 149
65 (18.3) 228 146 236 144 227 11 4 237 131
75 (23.9) 267 148 275 145 265 123 276 133
85 (29.4) 309 149 318 148 306 132 320 135
95 (35.0) 358 151 365 150 348 138 369 138
105 (40.6) 410 152 416 153 397 141 423 140
115 (49.0) 465 154 473 155 453 143 482 144
Liq Vap Liq Vap Liq Vap Liq Vap
First Stage (Low Capacity)
Second Stage (High Capacity)
First Stage (Low Capacity)
Second Stage (High Capacity)
Table 9
. HFC−410A Temperature (°F) − Pressure (Psig)
°F Psig °F Psig °F Psig °F Psig
32 100.8 63 178.5 94 290.8 125 445.9 33 102.9 64 181.6 95 295.1 126 451.8
34 105.0 65 184.3 96 299.4 127 457.6
35 107.1 66 187.7 97 303.8 128 463.5
36 109.2 67 190.9 98 308.2 129 469.5
37 111.4 68 194.1 99 312.7 130 475.6
38 113.6 69 197.3 100 317.2 131 481.6
39 115.8 70 200.6 101 321.8 132 487.8
40 118.0 71 203.9 102 326.4 133 494.0
41 120.3 72 207.2 103 331.0 134 500.2
42 122.6 73 210.6 104 335.7 135 506.5
43 125.0 74 214.0 105 340.5 136 512.9
44 127.3 75 217.4 106 345.3 137 519.3
45 129.7 76 220.9 107 350.1 138 525.8
46 132.2 77 224.4 108 355.0 139 532.4
47 134.6 78 228.0 109 360.0 140 539.0
48 137.1 79 231.6 110 365.0 141 545.6
49 139.6 80 235.3 111 370.0 142 552.3
50 142.2 81 239.0 112 375.1 143 559.1
51 144.8 82 242.7 113 380.2 144 565.9
52 147.4 83 246.5 114 385.4 145 572.8
53 150.1 84 250.3 115 390.7 146 579.8
54 152.8 85 254.1 116 396.0 147 586.8
55 155.5 86 258.0 117 401.3 148 593.8
56 158.2 87 262.0 118 406.7 149 601.0
57 161.0 88 266.0 119 412.2 150 608.1
58 163.9 89 270.0 120 417.7 151 615.4
59 166.7 90 274.1 121 423.2 152 622.7
60 169.6 91 278.2 122 428.8 153 630.1
61 172.6 92 282.3 123 434.5 154 637.5
62 175.4 93 286.5 124 440.2 155 645.0
INSTALLING SERVICE VALVE CAPS
Disconnect gauge set and re−install all service valve caps.
OUTDOOR UNIT
SERVICE VALVE
INSTALL CAPS
*These are most−popular−match−up pressures. Indoor match up, indoor air quality, and indoor load cause pressures to vary.
**Temperature of the air entering the outside coil.
505331M 06/09
Figure 33. Installing Service Valve Port Caps
Page 20
System Operations19
The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continuously.
THERMOSTAT OPERATION
Some indoor thermostats incorporate isolating contacts and an emergency heat function (which includes an amber indicating light). The thermostat is not included with the unit and must be purchased separately.
EMERGENCY HEAT (AMBER LIGHT)
An emergency heat function is designed into some room thermostats. This feature is applicable when isolation of the outdoor unit is required, or when auxiliary electric heat is staged by outdoor thermostats. When the room thermostat is placed in the emergency heat position, the outdoor unit control circuit is isolated from power and field-provided relays bypass the outdoor thermostats. An amber indicating light simultaneously comes on to remind the homeowner that the unit is operating in the emergency heat mode.
Emergency heat is usually used during an outdoor unit shutdown, but it should also be used following a power outage if power has been off for over an hour and the outdoor temperature is below 50°F (10°C). The system should be left in the emergency heat mode at least six hours to allow the crankcase heater sufficient time to prevent compressor slugging.
FILTER DRIER
The unit is equipped with a large−capacity biflow filter drier which keeps the system clean and dry. If replacement is necessary, order another of like design and capacity.
Lennox System Operation Monitor (LSOM) (100034−1)20
The diagnostic indicator detects the most common fault conditions in the air conditioning system. When an abnormal condition is detected, the module communicates the specific condition through its ALERT and TRIP lights. The module is capable of detecting both mechanical and electrical system problems.
IMPORTANT
This monitor does not provide safety protection. The is a monitoring device only and cannot control or shut down other devices.
LSOMLED FUNCTIONS
The LSOM LED functions are described as follows:
Table 10. LED Functions
Label LED
Color
Power Green Indicates voltage within the range of
Alert Yellow Communicates an abnormal system
Trip Red Indicates there is a demand signal
Refer to Table 12 for the complete explanation of troubleshooting codes.
RESETTING ALERT CODES
Alert codes can be reset manually or automatically:
Manual Reset
Cycle the 24VAC power to LSOM off and on. After power up, existing code will display for 60 seconds and then clear. Manual reset can be achieve by any of the following methods:
S Disconnecting R wire from the LSOM’s R terminal. S Turning the indoor unit off an on again
Automatic Reset
After an alert is detected, the LSOM continues to monitor the compressor and system. When/if conditions return to normal, the alert code is turned off automatically.
Function
19−28VAC is present at the system monitor power connection.
condition through a unique flash code. The alert LED flashes a number of times consecutively; then pauses; then repeats the process. This consecutive flashing correlates to a particular abnormal condition.
from the thermostat but no current to the compressor is detected by the module.
Page 21
XP19 SERIES
Status LED Condition
Table 11. LSOM Module LED Troubleshooting Codes
Mis−wired Module Indication
Status LED Troubleshooting Information
Green LED ON Module not powering up.
Green LED Intermittent
Red LED ON
Module powers up only when compressor runs.
LED is on but system and compressor check OK.
Red and Yellow LED Simultaneous flashing.
Table 12. LSOM System LED Troubleshooting Codes
Status LED Condition
Red LED ON
Yellow Flash Code 1
Yellow Flash Code 2
Yellow Flash Code 3
Status LED Description Status LED Troubleshooting Information
Thermostat demand signal Y1 is present, but compressor not running
Long Run Time − Compressor is running extremely long run cycles.
System Pressure Trip − Discharge or suction pressure out of limits or compressor overloaded
Short Cycling − Compressor is running only briefly
Determine/verify that both R and C module terminals are connected and voltage is present at both terminals.
Determine if R and Y terminals are wired in reverse. Verify module’s R and C terminals have a constant source.
1
Verify Y terminal is connected to 24VAC at contactor coil.
2
Verify voltage at contactor coil falls below 0.5VAC when off.
3
Verify 24VAC is present across Y and C when thermostat demand signal is present; if not present, R and C wires are reversed.
Indicates that the control circuit voltage is too low for operation. Verify R and C terminals are supplied with 19−28VAC.
1
Compressor protector is open.
S Check for high head pressure S Check compressor supply voltage
2
Outdoor unit power disconnect is open.
3
Compressor circuit breaker or fuse(s) is open.
4
Broken wire or connector is not making contact.
5
Low or high pressure switch open if present in the system.
6
Compressor contactor has failed to close.
1
Low refrigerant charge.
2
Evaporator blower is not running.
S Check blower relay coil and contacts S Check blower motor capacitor S Check blower motor for failure or blockage S Check evaporator blower wiring and connectors S Check indoor blower control board S Check thermostat wiring for open circuit
3
Evaporator coil is frozen.
S Check for low suction pressure S Check for excessively low thermostat setting S Check evaporator airflow (coil blockages or return air filter) S Check ductwork or registers for blockage.
4
Faulty metering device.
S Check TXV bulb installation (size, location and contact) S Check if TXV/fixed orifice is stuck closed or defective
5
Condenser coil is dirty
6
Liquid line restriction (filter drier blocked if present)
7
Thermostat is malfunctioning
.
.
.
S Check thermostat sub−base or wiring for short circuit S Check thermostat installation (location and level)
1
High head pressure.
S Check high pressure switch if present in system S Check if system is overcharged with refrigerant S Check for non−condensable in system
2
Condenser coil poor air circulation (dirty, blocked, damaged).
3
Condenser fan is not running.
S Check fan capacitor S Check fan wiring and connectors S Check fan motor for failure or blockage
4
Return air duct has substantial leakage.
1
Thermostat demand signal is intermittent.
2
Time delay relay or control board is defective.
3
If high pressure switch is present, see Flash Code 2 information.
505331M 06/09
Page 22
Status LED Condition
Yellow Flash Code 4 Locked Rotor
Yellow Flash Code 5 Open Circuit
Yellow Flash Code 6
Yellow Flash Code 7
Yellow Flash Code 8
Yellow Flash Code 9
Open Start Circuit − Current
only in run circuit
Open Run Circuit − Current only in start circuit
Welded Contactor − Compressor always runs
Low Voltage − Control circuit <17VAC
Status LED Troubleshooting InformationStatus LED Description
1
Run capacitor has failed.
2
Low line voltage (contact utility if voltage at disconnect is low).
S Check wiring connections
3
Excessive liquid refrigerant in the compressor.
4
Compressor bearings are seized.
1
Outdoor unit power disconnect is open.
2
Unit circuit breaker or fuse(s) is open.
3
Unit contactor has failed to close.
S Check compressor contactor wiring and connectors S Check for compressor contactor failure (burned, pitted or open) S Check wiring and connectors between supply and compressor S Check for low pilot voltage at compressor contactor coil
4
High pressure switch is open and requires manual reset.
5
Open circuit in compressor supply wiring or connections.
6
Unusually long compressor protector reset time due to extreme ambient tempera­ture.
7
Compressor windings are damaged.
S Check compressor motor winding resistance
1
Run capacitor has failed.
2
Open circuit in compressor start wiring or connections.
S Check wiring and connectors between supply and the compressor S terminal
3
Compressor start winding is damaged.
S Check compressor motor winding resistance
1
Open circuit in compressor start wiring or connections.
S Check wiring and connectors between supply and the compressor R terminal
2
Compressor start winding is damaged.
S Check compressor motor winding resistance
1
Compressor contactor failed to open.
2
Thermostat demand signal not connected to module.
1
Control circuit transformer is overloaded.
2
Low line voltage (contact utility if voltage at disconnect is low).
S Check wiring connections
NOTE − Last code will display for 1 minute when power is cycled to module. Power must be on to module for a minimum of 1 minute for code to clear. NOTE − Upon Y2 signal detection and after 5 seconds, the LSOM module will send 24 VAC to the solenoid. Once the solenoid is fully energized, the LSOM
module reduces voltage to between 4 to 18 VDC . Every 15 minutes the solenoid voltage will be increase to 24 volts for a few seconds to ensure solenoid valve is engaged until Y2 signal is no longer present.
Page 23
XP19 SERIES
Defrost System21
DEFROST SYSTEM DESCRIPTION
The defrost control board (DCB) measures differential temperatures to detect when the system is performing poorly because of ice build−up on the outdoor coil. The controller self−calibrates when the defrost system starts and after each system defrost cycle. The DCB components are illustrated on page 22.
The DCB monitors ambient temperature, outdoor coil temperature, and total run time to determine when a defrost cycle is required. The coil temperature probe is designed with a spring clip to allow mounting to the outside coil tubing. The location of the coil sensor is important for proper defrost operation.
NOTE  The DCB accurately measures the performance of the system as frost accumulates on the outdoor coil. This typically will translate into longer running time between defrost cycles as more frost accumulates on the outdoor coil before the board initiates defrost cycles.
DIAGNOSTIC LEDS
The state (Off, On, Flashing) of two LEDs on the DCB (DS1 [Red] and DS2 [Green]) indicate diagnostics conditions that are described in Table 15.
DCB PRESSURE SWITCH CONNECTIONS
The unit’s automatic reset pressure switches (LO PS − S87 and HI PS − S4) are factory−wired into the DCB on the LO−PS and HI−PS terminals, respectively.
Low Pressure Switch (LO−PS) When the low pressure switch trips, the DCB will cycle off the compressor, and the strike counter in the board will count one strike. The low pressure switch is ignored under the following conditions:
S during the defrost cycle and 90 seconds after the
termination of defrost
S when the average ambient sensor temperature is
below 15° F (−9°C)
S for 90 seconds following the start up of the compressor S during TEST mode
High Pressure Switch (HI−PS)When the high pressure switch trips, the DCB will cycle off the compressor, and the strike counter in the board will count one strike.
DCB PRESSURE SWITCH EVENT SETTINGS
The following pressures are the auto reset event values for low and high pressure thresholds:
High Pressure (auto reset) − trip at 590 psig; reset at 418. Low Pressure (auto reset) − trip at 25 psig; reset at 40.
FIVE−STRIKE LOCKOUT SAFETY FUNCTION
The five−strike lockout safety function is designed to protect the unit’s compressor from damage. The DCB looks for 24VAC on it’s Y1 terminal. When the Y1 input is see 24VAC, then internal control logic of the DCB will do the following:
S Count any HI−PS and LO−PS pressure switch trips
(open and close). Individual HI−PS and LO−PS trips
are added together for the total number of trips counted by the DCB.
S Up to four pressure switch trips are allowed in a single
thermostat demand without locking out the DCB. If the thermostat demand satisfies before a fifth pressure switch trip, the DCB will reset the five−strike counter to zero.
S If either pressure switch opens for a fifth time during
the current Y1 input state, the DCB will enter a lockout condition.
The system will require servicing to determine the cause of the pressure switch condition. Once the condition has been rectified, use the following procedure to reset the DCB.
Low Ambient Thermostat Pins − P3 provides selecting of the Y2 compressor lock−in temperature.
DEFROST SYSTEM SENSORS
Sensors connect to the DCB through a field-replaceable harness assembly that plugs into the board. Through the sensors, the DCB detects outdoor ambient, coil, and discharge temperature fault conditions. As the detected temperature changes, the resistance across the sensor changes. Figure 34 shows how the resistance varies as the temperature changes for both type of sensors. Sensor resistance values can be checked by ohming across pins shown in Table 34.
Ambient and Coil Sensor
100
TEMPERATURE (ºF)
300
280
260
240
220
200
180
160
TEMPERATURE (ºF)
140
120
100
5750
90
80
70
60
50
40
30
20
10
7450
9275
11775
15425
19975
26200
34375
46275
62700
0
10000 30000 50000 70000 90000
200
225
250
275
325
375
425
500
600
700
825
1000
1000 2000 50004000 60003000
RESISTANCE (OHMS)
Discharge Sensor
1175
1400
1700
2025
2500
3000
3750
RESISTANCE (OHMS)
4650
85300
5825
Figure 34. Temperature/Resistance Chart
505331M 06/09
Page 24
Table 13. Sensor Temperature / Resistance Range
Temperature
Sensor
Outdoor (Ambient)
Coil −35 (−37) to 120
Discharge (if applicable)
NOTE Sensor resistance decreases as sensed temperature increases (see Figure 34).
Range °F (°C)
−35 (−37) to 120 (48)
(48)
24 (−4) to 350 (176)
Resistance values range (ohms)
280,000 to 3750 3 and 4
280,000 to 3750 5 and 6
41,000 to 103 1 and 2
Pins/Wire Color
(Black)
(Brown)
(Yellow)
NOTE  When checking the ohms across a sensor, be aware that a sensor showing a resistance value that is not within the range shown in Table 13, may be performing as designed. However, if a shorted or open circuit is detected, then the sensor may be faulty and the sensor harness will need to be replaced.
Defrost Coil Sensor (RT21)  This sensor (shown in Figure 35, Detail A) considers outdoor temperatures below
−35°F (−37°C) or above 120°F (48°C) as a fault. If the defrost coil sensor is detected as being open, shorted or out of the temperature range of the sensor, the board will not perform demand or time/temperature defrost operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault condition.
Discharge Line Sensor (RT28)  If this sensor exceeds a temperature of 300°F (148°C) during compressor operation, the board will de−energize the compressor contactor output (and the defrost output, if active). The compressor will remain off until the discharge temperature has dropped below 225°F (107°C) and the 5-minute anti−short cycle delay has been satisfied. This sensor has two fault and lockout codes:
DETAIL B
WIRE TIE
1. If the board recognizes five high discharge line temperature faults during a single (Y1) compressor demand, it reverts to a lockout mode and displays the appropriate code. This code detects shorted sensor or high discharge temperatures. Code on board is Discharge Line Temperature Fault and Lockout.
2. If the board recognizes five temperature sensor range faults during a single (Y1) compressor demand, it reverts to a lockout mode and displays the appropriate code. The board detects open sensor or out-of-temperature sensor range. This fault is detected by allowing the unit to run for 90 seconds before checking sensor resistance. If the sensor resistance is not within range after 90 seconds, the board will count one fault. After five faults, the board will lockout. Code on board is Discharge Sensor Fault and Lockout.
The discharge line sensor (see Figure 35), which covers a range of 150°F (65°C) to 350°F (176°C), is designed to mount on a ½" refrigerant discharge line.
Ambient Sensor (RT13)  The ambient sensor (shown in Figure 35, Detail B) considers outdoor temperatures below −35°F (−37°C) or above 120°F (48°C) as a fault. If the ambient sensor is detected as being open, shorted or out of the temperature range of the sensor, the board will not perform demand defrost operation. The board will revert to time/temperature defrost operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault condition.
NOTE  Within a single room thermostat demand, if 5−strikes occur, the board will lockout the unit. DCB 24 volt power R must be cycled OFF or the TEST pins on board must be shorted between 1 to 2 seconds to reset the board.
MODELS −024 AND −036
MODELS −048 AND −060
24 TUBES
UP
SLEEVE
AMBIENT SENSOR − EXTEND TIP OF
PLASTIC SENSOR JUST OUTSIDE OF PLASTIC SLEEVE. PLACE AMBIENT SENSOR AND WIRE FROM DCB INSIDE OF PLASTIC SLEEVE AND ROUTE THROUGH GAP BETWEEN CORNER POST AND COIL SUPPORT AS SHOWN. SECURE WITH WIRE TIE.
DISCHARGE LINE
SENSOR
COIL SENSOR − CLIP COIL TEMPERATURE SENSOR FROM THE DCB ON THE RETURN BEND SHOWN ON MODELS AS FOLLOWS:
Figure 35. Sensor Locations
Page 25
12 TUBES UP
DETAIL A
XP19 SERIES
Second−Stage Operation  If the board receives a call for second−stage compressor operation Y2 in heating or cooling mode and the first-stage compressor output is active, the second-stage compressor solenoid output will be energized by the LSOM.
NOTE  Figure 29 illustrates the correct Y2 field wiring configuration.
NOTE  The LSOM has a five second delay between Y2 being powered and the solenoid energizing.
If first-stage compressor output is active in heating mode and the outdoor ambient temperature is below the selected compressor lock−in temperature, the second-stage compressor solenoid output will be energized without the Y2 room thermostat input.
If the jumper is not connected to one of the temperature selection pins on P3 (40, 45, 50, 55°F), the default lock−in temperature of 40°F (4.5°C) will be used.
The board de−energizes the second-stage compressor solenoid output immediately when the Y2 signal is removed or the outdoor ambient temperature is 5°F above the selected compressor lock−in temperature, or the first-stage compressor output is de−energized for any reason.
Defrost Temperature Termination Jumper Pins  The DCB selections are: 50, 70, 90, and 100°F (10, 21, 32 and 38°C). The jumper termination pin is factory set at 50°F (10°C). If the temperature jumper is not installed, the default termination temperature is 90°F (32°C).
DELAY MODE
The DCB has a field−selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. When a jumper is installed on the DELAY pins, the compressor will be cycled off for 30 seconds going in and out of the defrost mode. Units are shipped with jumper installed on DELAY pins.
NOTE  The 30 second off cycle is NOT functional when jumpering the TEST pins.
OPERATIONAL DESCRIPTION
The defrost control board has three basic operational modes: normal, calibration, and defrost.
Normal Mode  The demand DCB monitors the O line, to determine the system operating mode (heat/cool), outdoor ambient temperature, coil temperature (outdoor coil) and compressor run time to determine when a defrost cycle is required.
Calibration Mode  The board is considered uncalibrated when power is applied to the board, after cool mode operation, or if the coil temperature exceeds the termination temperature when it is in heat mode.
Calibration of the board occurs after a defrost cycle to ensure that there is no ice on the coil. During calibration, the temperature of both the coil and the ambient sensor are measured to establish the temperature differential which is required to allow a defrost cycle.
Defrost Mode  The following paragraphs provide a detailed description of the defrost system operation.
DETAILED DEFROST SYSTEM OPERATION Defrost Cycles  The demand defrost control board
initiates a defrost cycle based on either frost detection or time.
S Frost Detection  If the compressor runs longer than
30 minutes and the actual difference between the clear coil and frosted coil temperatures exceeds the maximum difference allowed by the control, a defrost cycle will be initiated.
IMPORTANT − The demand defrost control board will allow a greater accumulation of frost and will initiate fewer defrost cycles than a time/temperature defrost system.
S Time  If six hours of heating mode compressor run
time has elapsed since the last defrost cycle while the coil temperature remains below 35°F (2°C), the demand defrost control will initiate a defrost cycle.
Actuation of Defrost Cycle  The defrost cycle starts when the following occurs:
S Reversing valve is de−energized S Y1 circuit is energized S Coil temperature is below 35°F (2°C), S DCB starts logging the compressor run time.
Calibration success depends on stable system temperatures during the 20−minute calibration period. If the board fails to calibrate, another defrost cycle will be initiated after 45 minutes of heating mode compressor run time. Once the DCB is calibrated, it initiates a demand defrost cycle when the difference between the clear coil and frosted coil temperatures exceeds the maximum difference allowed by the control OR after 6 hours of heating mode compressor run time has been logged since the last defrost cycle.
NOTE − If ambient or coil fault is detected, the board will not execute the TEST mode.
Termination  The defrost cycle ends when the coil temperature exceeds the termination temperature or after 14 minutes of defrost operation. If the defrost is terminated by the 14−minute timer, another defrost cycle will be initiated after 30 minutes of run time.
Test Mode  When Y1 is energized and 24V power is being applied to the board, a test cycle can be initiated by placing the termination temperature jumper across the TEST pins for 2 to 5 seconds. If the jumper remains across the TEST pins longer than 5 seconds, the control will ignore the test pins and revert to normal operation. The jumper will initiate one cycle per test.
NOTE  Coil sensor temperature must be below 35ºF before the DCB will initiate a TEST defrost
Each test pin shorting will result in one test event. For each TEST the jumper must be removed for at least 1 second and reapplied. Refer to flow chart (Figure 36) for TEST operation.
NOTE  The Y1 input must be active (ON) and the O room thermostat terminal into board must be inactive.
505331M 06/09
Page 26
JUMPER
TEST
Placing the jumper on the test pins allows the technician to:
S Clear short cycle lockout S Clear five−strike fault lockout S Cycle the unit in and out of defrost mode S Place the unit in defrost mode to clear the coil
When Y1 is energized and 24V power is being applied to the Demand Defrost Control, a test cycle can be initiated by placing a jumper on the Demand Defrost Control’s TEST pins for 2 to 5 seconds. If the jumper remains on the TEST pins for longer than five seconds, the Demand Defrost Control will ignore the jumpered TEST pins and revert to normal operation.
The control will initiate one test event each time a jumper is placed on the TEST pins. For each TEST the jumper must be removed for at least one second and then reapplied.
Y1 Active
DEMAND DEFROST CONTROL (UPPER LEFT−HAND CORNER)
Place a jumper on TEST pins for
longer than one second but less than two seconds.
Clears any short cycle lockout and five strike fault lockout function, if applicable. No other functions will be executed and unit will continue in the mode it was operating.
If in COOLING Mode
No further test mode operation will be executed until the jumper is removed from the TEST pins and reapplied.
Place a jumper on TEST pins for
more than two seconds.
Clears any short cycle lockout and five strike fault lockout function, if applicable.
ACTIVE
O Line Status
If in DEFROST Mode
The unit will terminate defrost and enter HEAT MODE uncalibrated with defrost timer set for 30 minute test.
INACTIVE
If in HEATING Mode
If no ambient or coil sensor ault exist, unit will go into DEFROST MODE.
If ambient or coil faults exist (open or shorted), unit will remain in HEAT MODE.
NOTE  Placing a jumper on the TEST pins will not bring the unit out of inactive mode. The only way manually activate the heat pump from an inactive mode is to cycle the 24VAC power to the Demand Defrost Control.
If jumper on TEST pins remains in place for more than five seconds.
The unit will return to HEAT MODE uncalibrated with defrost timer set for 30 minutes.
Figure 36. Test Mode
Page 27
If jumper on TEST pins is removed before a maximum of five seconds.
The unit will remain in DEFROST MODE until termination on time or temperature.
XP19 SERIES
DEMAND DEFROST CONTROL BOARD  A10822
NOTE  Component locations may vary by board manufacturer.
P3
P1
TEST PINS
DEFROST
TERMINATION
PIN SETTINGS
P4
DS1 AND DS2
P5
REVERSING
VALV E
PRESSURE
SWITCH
CIRCUIT
CONNECTIONS
P6
RL
C
W OUT
R
P2  24V TERMINAL STRIP
CONNECTIONS
W IN
O
Y1
DIAGNOSTIC LEDs
Diagnostic LED descriptions are listed in Table 15.
Table 14. Demand Defrost Control  A108
Inputs/Outputs and Jumper Settings
ID Description
O OUT 24VAC output connection for reversing valve.
LO−PS Connection for low−pressure switch
W−OUT
Y1
H1−PS Connection for high−pressure switch.
FAN
50
P1
P2
P3 Not used.
P4
P5 For factory test.
P6
70
90
100
RL
C 24VAC system common
W Out
R 24VAC system power input
W In
O
Y1
Six position square pin header. P4 provides connections for the temperature sensors.
COIL
(BROWN)
AMB
(BLACK)
DIS
(YELLOW)
24VAC output for second−stage (gas heat) furnace connection
24VAC common output, switched to enable compressor contactor.
240 VAC line voltage connection for condenser fan.
Defrost Termination Settings: Seven position square pin header. The defrost termination temperature is measured by the defrost coil sensor. The jumper termination pin is factory set at 50°F (10°C). If the temperature jumper is not installed, the default termination
temperature is 90°F (32°C).
24VAC output for external K229 relay to control blower operation during defrost, heat pump inactive mode, and a call for second−stage (gas heat) furnace operations.
24VAC output to furnace control to begin furnace heating operation.
24VAC thermostat input for second stage (gas heat) furnace operation
24VAC thermostat input for reversing valve operation
24VAC thermostat input for first−stage compressor operation
(PIN 1) Ground connection for outdoor coil temperature sensor.
(PIN 2) Connection for outdoor coil temperature sensor.
(PIN 3) Ground connection for outdoor ambient temperature sensor.
(PIN 4) Connection for outdoor ambient temperature sensor.
(PIN 5 and PIN 6) Harness resistor fault  10K resistor. 10K resistor built into wiring harness connected to the DIS connector.
Eight−position header. Provides connections for the factory test.
505331M 06/09
Page 28
DCB DIAGNOSTICS
See Table 15 to determine DCB operational conditions and to diagnose cause and solution to problems.
Table 15. Defrost Control Board Diagnostic LEDs
DS2 Green
OFF OFF Power problem No power (24V) to board terminals R
Simultaneous SLOW Flash
Alternating SLOW Flash
Simultaneous FAST Flash
Alternating FAST Flash
ON ON Circuit Board Failure Indicates that board has internal component failure. Cycle 24 volt power to board. If code does
DS1 Red
Condition/Code Possible Cause(s) Solution
1
Check control transformer power (24V).
and C or board failure.
Normal operation Unit operating normally or in standby
5−minute anti−short cycle delay
Ambient Sensor Problem Sensor being detected open or shorted or out of temperature range. Board will revert to time/
Coil Sensor Problem Sensor being detected open or shorted or out of temperature range. Board will not perform
mode.
Initial power up, safety trip, end of room thermostat demand.
temperature defrost operation. (System will still heat or cool).
demand or time/temperature defrost operation. (System will still heat or cool).
not clear, replace board.
2
If power is available to board and LED(s) do not light, replace board.
None required.
None required (Jumper TEST pins to override)
FAULT and LOCKOUT CODES (Each fault adds 1 strike to that code’s counter; 5 strikes per code = LOCKOUT)
OFF SLOW
OFF ON
SLOW Flash
ON OFF
Flash
OFF High Pressure Fault
Low Pressure Fault
Low Pressure Discharge
Sensor Lockout
High Pressure Discharge
Sensor Lockout
1
Restricted air flow over indoor or out­door coil.
2
Improper refrigerant charge in sys­tem.
3
Improper metering device installed or incorrect operation of metering de­vice.
4
Incorrect or improper sensor location or connection to system.
1
Remove any blockages or restrictions from coils and/or fans. Check indoor and outdoor fan motor for proper current draws.
2
Check system charge using approach and subcool­ing temperatures.
3
Check system operating pressures and compare to unit charging charts.
4
Make sure all pressure switches and sensors have secure connections to system to prevent refrigerant leaks or errors in pressure and temperature mea­surements.
SLOW Flash
FAST Flash
OFF Fast
Fast Flash
ON Discharge Line Temperature
ON
Fault
Discharge Line Temperature Discharge
Sensor Lockout
Flash
OFF
Discharge Sensor Fault The board detects open sensor or out of temperature sensor range. This fault is detected by
Discharge Sensor
Discharge Sensor Lockout
This code detects shorted sensor or high discharge temperatures. If the discharge line temperature exceeds a temperature of 300ºF (148ºC) during compressor operation, the board will de−energize the compressor contactor output (and the defrost output if active). The compressor will remain off until the discharge temperature has dropped below 225ºF (107ºC).
allowing the unit to run for 90 seconds before checking sensor resistance. If the sensor resist­ance is not within range after 90 seconds, the board will count one fault. After 5 faults, the board will lockout.
Maintenance23
WARNING
Electric shock hazard. Can cause inju­ry or death. Before attempting to per­form any service or maintenance, turn the electrical power to unit OFF at dis­connect switch(es). Unit may have multiple power supplies.
Before the start of each heating and cooling season, the following service checks should be performed by a qualified service technician. First, turn off electrical power to the unit prior to performing unit maintenance.
S Inspect and clean the outdoor and indoor coils. The
outdoor coil may be flushed with a water hose.
NOTE  It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are corrosive or which block airflow across the coil (e.g., pet urine, cottonwood seeds, etc.)
S Visually inspect the refrigerant lines and coils for leaks. S Check wiring for loose connections. S Check voltage at the indoor and outdoor units (with
units operating).
S Check the amperage draw at the outdoor fan motor,
compressor, and indoor blower motor. Values should be compared with those given on unit nameplate.
S Check, clean (or replace) indoor unit filters. S Check the refrigerant charge and gauge the system
pressures.
S Check the condensate drain line for free and
unobstructed flow; clean, if necessary.
Page 29
XP19 SERIES
S Outdoor unit fan motor is prelubricated and sealed. No
further lubrication is needed.
NOTE  If owner reports insufficient cooling, the unit should be gauged and refrigerant charge checked. Refer to section on refrigerant charging in this instruction.
Two−Stage Modulation Compressors24
IMPORTANT
Use this check-out procedure to verify part- and full-load capacity operation of two-stage modulation compressors.
TOOLS REQUIRED
S Refrigeration gauge set S Digital volt/amp meter S Electronic temperature thermometer S On-off toggle switch
PROCEDURE
1. Turn main power OFF to outdoor unit.
2. Adjust room thermostat set point 5ºF above (heating operation) or 5ºF below (cooling operation) the room temperature.
3. Remove control access panel. Install refrigeration gauges on unit. Attach the amp meter to the common (black wire) wire of the compressor harness. Attach thermometer to discharge line as close as possible to the compressor.
4. Turn toggle switch OFF. Install switch in series with Y2 wire from room thermostat (see note ** in the Field Operational Checklist on page 26).
5. Cycle main power ON.
6. Allow pressures and temperatures to stabilize before taking any measured reading (may take up to 10 minutes).
7. Record all of the readings for the Y1 demand.
8. Close switch to energize Y2 demand. Verify power is going to compressor solenoid (see note ** in the Field Operational Checklist on page 26).
9. Allow pressures and temperatures to stabilize before taking any measured reading (this may take up to 10 minutes).
10. Record all of the readings with the Y1 and Y2 demand.
11. If temperatures and pressures change in the direction noted in chart, the compressor is properly modulating from low to high capacity. (If no amperage, pressures or temperature readings change when this test is
performed, the compressor is not modulating between low and high capacity and replacement is necessary).
12. After testing is complete, return unit to original set up.
Homeowner Information − Maintenance25
In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level.
1. Air Filter  Ask your Lennox dealer to show you
where your indoor unit’s filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed.
2. Disposable Filter  Disposable filters should be
replaced with a filter of the same type and size.
NOTE − If you are unsure about the filter required for your system, call your Lennox dealer for assistance.
IMPORTANT
Turn off electrical power to the unit at the disconnect switch before performing any maintenance. The unit may have multiple power supplies.
3. Reusable Filter  Many indoor units are equipped
with reusable foam filters. Clean foam filters with a mild soap and water solution; rinse thoroughly; allow filter to dry completely before returning it to the unit or grille.
NOTE The filter and all access panels must be in place any time the unit is in operation.
4. Electronic Air Cleaner  Some systems are
equipped with an electronic air cleaner, designed to remove airborne particles from the air passing through the cleaner. If your system is so equipped, ask your dealer for maintenance instructions.
5. Indoor Unit  The indoor unit’s evaporator coil is
equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.)
IMPORTANT
Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soakers, waste water, etc.) will corrode the surface of steel and aluminum parts and diminish perfor­mance and longevity of the unit.
6. Outdoor Unit  Make sure no obstructions restrict
airflow to the outdoor unit. Leaves, trash or shrubs crowding the unit cause the outdoor unit to work harder and use more energy. Keep shrubbery trimmed away from the unit and periodically check for debris which collects around the unit.
505331M 06/09
Page 30
When removing debris from around the unit, be aware of metal edges on parts and screws. Although special care has been taken to keep exposed edges to a minimum, physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury.
Cleaning of the outdoor unit’s coil should be performed by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your heat pump system.
HEAT PUMP OPERATION
Your new Lennox heat pump has several characteristics that you should be aware of:
S Heat pumps satisfy heating demand by delivering
large amounts of warm air into the living space. This is quite different from gas- or oil-fired furnaces or an electric furnace which deliver lower volumes of considerably hotter air to heat the space.
S Do not be alarmed if you notice frost on the outdoor coil
in the winter months. Frost develops on the outdoor coil during the heating cycle when temperatures are below 45°F (7°C). An electronic control activates a defrost cycle lasting 5 to 15 minutes at preset intervals to clear the outdoor coil of the frost.
S During the defrost cycle, you may notice steam rising
from the outdoor unit. This is a normal occurrence. The thermostat may engage auxiliary heat during the defrost cycle to satisfy a heating demand; however, the unit will return to normal operation at the conclusion of the defrost cycle.
EXTENDED POWER OUTAGE
The heat pump is equipped with a compressor crankcase heater which protects the compressor from refrigerant slugging during cold weather operation.
If power to your unit has been interrupted for several hours or more, set the room thermostat selector to the EMERGENCY HEAT setting to obtain temporary heat without the risk of serious damage to the heat pump.
In EMERGENCY HEAT mode, all heating demand is satisfied by auxiliary heat; heat pump operation is locked out. After a six-hour compressor crankcase warm-up period, the thermostat can be switched to the HEAT setting and normal heat pump operation may resume.
THERMOSTAT OPERATION
Though your thermostat may vary somewhat from the description below, its operation will be similar.
Temperature Setting Levers
Most heat pump thermostats have two temperature selector levers: one for heating and one for cooling. Set the levers or dials to the desired temperature setpoints for both heating and cooling. Avoid frequent temperature adjustment; turning the unit off and back on before pressures equalize puts stress on the unit compressor.
Fan Switch
In AUTO or INT (intermittent) mode, the blower operates only when the thermostat calls for heating or cooling. This mode is generally preferred when humidity control is a priority. The ON or CONT mode provides continuous indoor blower operation, regardless of whether the compressor or auxiliary heat are operating. This mode is required when constant air circulation or filtering is desired.
System Switch
Set the system switch for heating, cooling or auto operation. The auto mode allows the heat pump to automatically switch from heating mode to cooling mode to maintain predetermined comfort settings. Many heat pump thermostats are also equipped with an emergency heat mode which locks out heat pump operation and provides temporary heat supplied by the auxiliary heat.
Indicating Light
Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the emergency heat mode.
Temperature Indicator
The temperature indicator displays the actual room temperature.
PROGRAMMABLE THERMOSTATS
Your Lennox system may be controlled by a programmable thermostat. These thermostats provide the added feature of programmable time-of-day setpoints for both heating and cooling. Refer to the user’s information manual provided with your particular thermostat for operation details.
PRESERVICE CHECK
If your system fails to operate, check the following before calling for service:
S Check to see that all electrical disconnect switches are
ON.
S Make sure the room thermostat Temperature Selector
and System Switch (Heat, Cool, Auto) are properly set.
S Check for any blown fuses or tripped circuit breakers. S Make sure unit access panels are in place. S Make sure air filter is clean. S If service is needed, locate and write down the unit
model number and have it handy before calling.
OPTIONAL ACCESSORIES
Optional accessories for the XP19 include the following (see the XP19 Engineering Handbook for more details):
S Timed-off control S Low ambient kit S Top cap snow cover S Snow Guard (X8782) S Snow Shield Kit (44W14)
Page 31
XP19 SERIES
XP19 Field Operational Checklist26
Cooling*** Heating***
Unit Readings
Compressor
Voltage Same Same
Amperage Higher Higher
Condenser Fan motor
Amperage Same or Higher Same or Higher
Temperature
Ambient Same Same
Outdoor Coil Discharge Air Higher Lower
Compressor Discharge Line Higher Higher
Indoor Return Air Same Same
Indoor Coil Discharge Air Lower Higher
Pressures
Suction (Vapor) Lower Down
Liquid Higher Higher
Note − Heat pump may have a low ambient control or DCB that locks in second stage below its set point. It may be necessary to remove a wire from
the control when performing this check out. ** On the XP19 units, the Lennox System Operational Module controls the 2nd stage solenoid coil in compressor. *** Cooling Mode Operation − Block outdoor coil to maintain a minimum of 375 psig during testing.
Heating Mode Operation − Block indoor coil to maintain a minimum of 375 psig during testing.
Y1 − 1st-
Stage
Expected results
during Y2 demand
(Toggle switch On)
Y2 − 2nd-
Stage
Y1 − 1st-
Stage
Expected results
during Y2 demand
(Toggle switch On)
Y2 − 2nd-
Stage
XP19 Start−Up and Performance Checklist27
Customer Address Indoor Unit Model Serial Outdoor Unit Model Serial Notes:
START−UP CHECKS
Refrigerant Type: Rated Load Amps Actual Amps Rated Volts Actual Volts Condenser Fan Full Load Amps Actual Amps:
COOLING MODE
Vapor Pressure: Liquid Pressure: Supply Air Temperature: Ambient Temperature: Return Air Temperature:
HEATING MODE
Vapor Pressure: Liquid Pressure: Supply Air Temperature: Ambient Temperature: Return Air Temperature: System Refrigerant Charge (Refer to manufacturer’s information on unit or installation instructions for required subcooling and approach
temperatures.) Subcooling: A
Saturated Condensing Temperature (A)
minus Liquid Line Temperature (B)
Approach: A
Liquid Line Temperature (A)
minus Outdoor Air Temperature (B)
Indoor Coil Temp. Drop (18 to 22°F) A
Return Air Temperature (A)
minus Supply Air Temperature (B)
B
B
B
SUBCOOLING
=
APPROACH
=
COIL TEMP DROP
=
505331M 06/09
Page 32
Loading...