Lennox SignatureStat 81M26, SignatureSu0001tat 81M27, SignatureSu0001tat 81M28 Programming And Application Manual

Page 1
Page 1
E2007 Lennox Industries Inc.
Dallas, Texas, USA
Table of Contents
SignatureStatt Thermostat 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Date Code & Serial Number 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Features 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Home Screen & Main Menu 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Programming the Thermostat 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heating and Cooling Cycles 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Humidification 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dew Point Control 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dehumidification 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Humiditrol® Accessory 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Changing Time of Day / Day of Week 11. . . . . . . . . . . . . . . . . . . . . . . .
Cycling the Fan 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
User Settings and Options 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Change Temperature Settings 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting Vacation Mode 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installer Settings 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remote Outdoor Sensor 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Lights 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Memory Protection 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EPA ENERGYSTAR® Recommended Setpoints 21. . . . . . . . . . . . . . .
Resetting Program to Factory Conditions 21. . . . . . . . . . . . . . . . . . . . .
Thermostat−specific Information 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Flow Diagrams 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Diagrams 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PROGRAMMING AND APPLICATION GUIDE
SignatureStatt Thermostat
CONTROLS
505,232M 06/07 Supersedes 2/07
81M26 shown
NOTE − This thermostat is equipped with automatic compressor protection to prevent potential damage due to short cycling or extended power out­ages. The short cycle protection provides a 5−minute delay between heat­ing or cooling cycles to prevent the compressor from being damaged.
Shipping and Packing List
1 − SignatureStatt thermostat 1 − Outdoor temperature sensor
Litho U.S.A.
Page 2
505232 06/07
Page 2
WARNING
Always turn off power at the main power source by unscrewing fuse or switching circuit breaker to the OFF position before instal­ling, removing, or cleaning this thermostat.
WARNING
All wiring must conform to local and national building and electri­cal codes and ordinances.
WARNING
Do not switch system to cool if the temperature is below 45°F (7°C). This can damage the cooling system and may cause personal inju­ry.
CAUTION
This is a 24VAC low−voltage thermostat. Do not install on voltages higher than 30VAC.
Do not short (jumper) across terminals on the gas valve or at the system control to test installation. This will damage the thermostat and void the warranty.
IMPORTANT
Commercial use of the SignatureStatt thermostat can only be with approved split-system matches, and which meets the following installation criteria:
S installation uses 18 GAUGE thermostat wire or larger, S thermostat wire run length DOES NOT EXCEED 300’ (91m), S load from any thermostat connection is LESS THAN 1 AMP.
Connect outdoor sensor (if used) to the thermostat using separate twisted-pair cable, 22 awg min., 300’ (91m) max., Lennox cat. no. 84X49 (1000’ roll) or X3790 (500’ roll).
If used with Harmony II® Zone Control System, consult Application Note H−04−5.
IMPORTANT
Read this manual before programming this thermostat.
Use this thermostat only as described in this manual.
SignatureStat t Thermostat
The fully programmable SignatureStatt thermostat offers all of the fea­tures of a high−performance thermostat. It also offers enhanced capabilities which include humidification measurement and control, dew point adjust­ment control, dehumidification measurement and control, Humiditrol® ca­pability, and equipment maintenance reminders.
The 24VAC thermostat also features worry−free memory storage and a menu−driven display.
This document supports the following products:
S 81M26 − 1 stage heat / 1 stage cool, conventional or heat pump (When
configured for a single−stage heat pump, no auxiliary backup heat is supported.)
Page 3
SignatureStat t Thermostat
Page 3
S 81M27 − 2 stage heat / 2 stage cool, conventional S 81M28 − 2 stage heat / 2 stage cool, heat pump (Provides 2 stages of
heat pump cooling and one stage of heat pump heating. A second− stage of auxiliary backup heat is also provided.)
S 46M98 − Outdoor temperature sensor (included with thermostat)
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before instal­lation.
Check equipment for shipping damage. If you find any damage, immediate­ly contact the last carrier.
Date Code & Serial Number
The date code and serial number are on the back of the SignatureStatt thermostat (shown in figure 1). Date code identifies when the thermostat was manufactured; serial number uniquely identifies each thermostat for tracking purposes.
Figure 1. Date Code and Serial Number
DATE CODE (0411)
SERIAL NUMBER (02634)
(BACK OF
SignatureStat t
THERMOSTAT)
Features
Outdoor Temperature Sensor
The outdoor sensor is provided as a standard component of each Signatu­reStatt thermostat. In addition to measuring and displaying outdoor tem-
perature, the outdoor sensor provides dew point adjustment and control for all models. It can also be used with the multistage heat pump thermostat (81M28) to provide optimal heating equipment operation via programmable balance points.
NOTE − Outdoor sensor must use twisted pair wiring (Lennox Cat, No. 84X49 [1000’] or X3790 [500’]).
When an outdoor sensor is connected, the temperature is displayed on the LCD at the right hand side. For exam­ple, the display will show OUTSIDE 90" if the outdoor temperature is mea­sured to be 90°F.
NOTE − For proper operation of Humiditrol
®
applications, the outdoor sen-
sor MUST be installed.
L" Input
"L" input from the equipment is used to notify the user if the equipment fails. The "L" terminal is connected to common through a resistor, LED, and volt­age regulator. The CHECK LED is illuminated when 24 VAC is applied to the L terminal. Nothing is displayed on the user interface screen.
Compressor Short Cycle Protection
A 5−minute compressor short cycle protection timer begins when a com­pressor output is de−energized.
MONDAY 3:29 PM
AUTO
FAN AUTO
SET AT 78
OUTSIDE 90
27%RH
HOLD TEMP MENU
78
ºF
Page 4
505232 06/07
Page 4
Home Screen and Main Menu
The home screen displays the present time, indoor temperature, indoor rel­ative humidity, and outdoor temperature (if the outdoor sensor is installed). To access the main menu screen, press the menu button on the home screen (see figure 2).
MENU BUTTON
Figure 2. Home/Main Menu Screen
UP/DOWN BUTTONS
Main menu options
The main menu includes eight options, displaying four options at a time. Press the DOWN arrow button to see the remaining options (see figure 3).
Press SELECT to choose the option you wish to program. All menus will time out" after 20 seconds; therefore, the previous menu will be displayed if you fail to select an option within 20 seconds.
MAIN MENU PROGRAM HEAT / COOL HUMIDIFY DEHUMIDIFY
HOME SELECT
MAIN MENU DAY / TIME FAN USER SETTINGS INSTALLER SETTINGS
HOME SELECT
Figure 3. Main Menu
Programming the Thermostat
Program the thermostat by choosing an event. An event is the beginning of a programming period. The default number of events per day is four. The thermostat may be programmed for two or four events per day. The names for the events are: WAKE, MORN, EVE, and NIGHT. The time for an event is selected based on when you want the event to occur. Four events are common for working households.
Programming may be performed in groups of days or individual days, as follows:
MON TO SUN − allows every day to be set the same.
MON TO FRI − allows for weekday programming.
SAT TO SUN − allows for weekend days to be adjusted separately.
MONDAY through SUNDAY − allows individual days of the week to be programmed separately.
NOTE − After using one of the groups of days described above, the program does allow you to subsequently change individual days to suit your needs.
Page 5
SignatureStat t Thermostat
Page 5
Programming for Full Week or Work Week
The programming process for MON TO SUN, MON TO FRI, and SAT TO SUN is identical.
Full WeekThe least complex program is the full week MON TO SUN" program, wherein the events for every day of the week are the same. If this is chosen, follow steps 1 through 6, below, setting time and temperature for each event. One time through all the events completes the programming process.
Work WeekNext in complexity to the full week program is the work week program wherein the events are set for a typical work week (MON TO FRI) and different events are set for the weekend (SAT TO SUN). If MON TO FRI is chosen, follow steps 1 through 6, below, setting time and temperature for each event. Then repeat the same process for SAT TO SUN to complete the programming process.
1. From the home screen, press MENU. Use the Up or Down button to highlight PROGRAM. Press Select.
2. Select the appropriate time span from the program days list. For this example, choose the MON TO SUN program days and press Select.
3. Use Up/Down buttons to select the event to program. The unit can be set for two or four events per day. After choosing an event to program, press select. See User Settings" for Events Per Day selection.
4. The time for the first event should be highlighted. Use the UP or DOWN button to change the time.
Press SET TIME.
5. The heating setpoint for the first event is highlighted. Use the UP or DOWN button to change the desired temperature. Press SET HEAT.
6. The cooling setpoint for the first event will be highlighted. Use the UP or DOWN button to change the desired temperature. Press SET COOL. The next event, e.g. MORN will then be highlighted. Continue programming until all event times and heat/cool settings are set as desired.
Programming Day-by-Day
Individual day programming, MONDAY through SUNDAY, is done similar to full week or work week. However, with this mode, a down arrow" ap­pears next to the SELECT. Using the down button, an additional option is available, COPY. After programming events for a selected day, for example MONDAY, you can select COPY. Another screen with the remaining days of the week appears. Use the up/down arrow buttons to scroll to another day, for example, THURSDAY, and press YES/NO. YES will appear next to THURSDAY. (Another press of the YES/NO button clears the YES" dis­play [toggles back to NO]). Do this for each day to which you want to copy the individual day’s program.
SELECT PROGRAM DAYS
MON TO SUN MON TO FRI SAT TO SUN MONDAY
MAIN MENU SELECT
MON−SUN PROGRAM
HEAT COOL WAKE 6:30 AM 70 78 MORN 8:30 AM 62 85 EVE 4:30 PM 70 78 NIGHT 10:30 PM 62 82
MAIN MENU SELECT
MON−SUN PROGRAM
HEAT COOL WAKE 6:30 AM 70 78 MORN 8:30 AM 62 85 EVE 4:30 PM 70 78 NIGHT 10:30 PM 62 82
BACK SET TIME
MON−SUN PROGRAM
HEAT COOL WAKE 6:30 AM 70 78 MORN 8:30 AM 62 85 EVE 4:30 PM 70 78 NIGHT 10:30 PM 62 82
BACK SET HEAT
Page 6
505232 06/07
Page 6
Heating and Cooling Cycles
NOTE − AUTO CHANGEOVER will appear in the HEAT/COOL menu only if enabled via Installer Settings."
GO TO: MENU > INSTALLER SETTINGS > AUTO CHANGEOVER > ENABLE [SELECT]
1. From the home screen press MENU. Use the UP or DOWN buttons to highlight HEAT/COOL. Press SELECT.
2. Use the UP or DOWN buttons to highlight HEAT, COOL, or AUTO CHANGEOVER. Press SELECT. Pressing SELECT will turn on or off the selected cycle.
You do not have to turn off HEAT to turn on COOL. When HEAT or COOL or AUTO CHANGEOVER is turned on, all others are automatically shut off. After pressing SELECT, the home screen will automatically appear.
Determining if Heating or Cooling is ON
The thermostat display indicates the operating mode, HEAT, COOL, or AUTO. When the indoor temperature decreases or increases, the HEAT­ING or COOLING cycle will turn on based on the displayed mode. When the HVAC system is on, LEDs along the bottom of the thermostat housing will turn on.
Humidification
Humidification is provided only when the thermostat is in heat mode. The
humidification signal (H terminal) to the humidifier is off when the thermo­stat is in the COOL mode.
The H terminal controls humidification. When the thermostat is powered, the H terminal is normally inactive (open circuit) in any mode (HEAT, COOL, OFF). When a humidification demand is present, H terminal and G terminal are energized (24V).
Also while humidification is occurring, a small water drop icon with a +" symbol inside (shown in margin) is displayed on the screen.
The default humidification setpoint is 45% Relative Humidity (RH). The de­fault mode for humidification is OFF and needs to be activated during instal­lation.
Humidification Modes
In BASIC mode, humidification occurs if these conditions are met and sig­nals are present at specific terminals:
S humidification mode has been enabled, and S the unit is in HEAT mode, and S humidification demand exists (24V present at H), and S heat demand exists (W energized [for gas heat, W may be energized
with G de−energized]).
In PRECISION mode, humidification occurs (with or without a heat de­mand) when:
S humidification has been enabled, and S the unit is in HEAT mode, and S humidification demand exists (24V present at H).
NOTE − The D terminal is inactive (reverse logic, the terminal is powered) during humidification. For complete terminal descriptions, see tables 3, 5, and 7, on pp 22 and 23.
MAIN MENU
PROGRAM HEAT / COOL HUMIDIFY DEHUMIDIFY
HOME SELECT
HEAT / COOL SETTINGS OFF HEAT COOL AUTO CHANGEOVER
MAIN MENU SELECT
+
Page 7
SignatureStat t Thermostat
Page 7
Adjust Humidification Level
1. NOTE − Basic or precision mode must be turned on before you can adjust the humidification level on the thermostat. From the home
screen press MENU.
2. Use UP/DOWN buttons to high­light HUMIDIFY. Then press SE­LECT to choose MODE.
3. By default, humidification is OFF; turn on by selecting BASIC or PRECISION for humidification mode (modes are described above).
4. The HUMIDIFY MENU appears. The mode, shown as BAS (basic) is displayed on the right−hand side of the screen.
5. Use the UP/DOWN button to highlight HUMIDIFY; press SE­LECT.
6. In the HUMIDIFY CONTROL screen, use the UP/DOWN but­tons to adjust the desired relative humidity. At the desired level, press SELECT.
The humidification adjustment control may be adjusted in 1 percent increments; dew point range. Setting limits: Min. 15%, Max. 45%. De­fault setting: 45%.
Humidifier Maintenance Interval
The humidifier maintenance interval is a fixed (cannot be changed), 6−month interval that is measured when the thermostat H terminal is active. The HUMIDIFIER MAINTENANCE screen will be displayed after the H ter­minal has been active for a total elapsed time of 6 months (or 4,368 hours).
For example, if the interval timer started 2 days ago, the H terminal was ac­tive for 3 hours yesterday and 4 hours today; so far the H terminal has been active for 7 hours. Another 4,361 hours, during which the H terminal is ac­tive, must elapse before the HUMIDIFIER MAINTENANCE screen is dis­played.
When the interval has expired, the screen will appear as shown to the right. Press DELAY to be reminded lat­er or RESET to reset the interval. The delay lasts for two hours.
Humidification Sensor Fault
If the reading from the humidification sensor is out of range, then the H ter­minal becomes inactive, the D terminal goes to 24V, and the humidification reading display is blank. The out-of-range signal is an open or short circuit on the humidification sensor.
MAIN MENU
PROGRAM HEAT / COOL HUMIDIFY DEHUMIDIFY
HOME SELECT
HUMIDIFY MENU
MODE OFF HUMIDIFY 44%
MAIN MENU SELECT
HUMIDIFY MODE
OFF BASIC PRECISION BASIC/DP
HUM MENU SELECT
HUMIDIFY MENU
MODE BAS HUMIDIFY 45%
MAIN MENU SELECT
HUMIDIFY MENU
MODE BAS HUMIDIFY 45%
MAIN MENU SELECT
HUMIDIFY
CONTROL
HUM MENU SELECT
%
44
HUMIDIFIER
MAINTENANCE
LENNOX, INC.
1−800−9LENNOX
DELAY RESET
Page 8
505232 06/07
Page 8
Dew Point Control
NOTE − Dew point control is only available when an outdoor sensor is at­tached.
Select ADJ from the HUMIDIFY MENU. Dew point adjustment will change the humidification setpoint based on the outdoor temperature and a user− defined dew point adjustment setting.
NOTE − In dew point adjustment mode, the humidification setpoint has no effect whatsoever on unit operation. Only the user−defined dew point ad­justment setting affects operation per the following:
Formula:
RH
setpoint
=
Outdoor Temp
2
+ 25 +
RH
user dew point adjustment
Where: RH
user dew point adjustment
cannot exceed +/−15% and
RH
setpoint
minimum is 15% and cannot exceed 45%.
Turn on and Adjust Dew Point Control
The dew point adjustment control may be adjusted in 1 percent increments; relative humidity range. To locate the DEW POINT ADJ CONTROL screen:
1. From the home screen press MENU. From the main menu screen select HUMIDIFY. Press SELECT.
2. Use the up or down button to high­light MODE. Press SELECT.
3. To turn on the dew point control in either basic or precision mode, use the up or down button to high­light BASIC/DP or PRECISION/ DP. Press SELECT to choose the mode you want to set.
4. The HUMIDIFY MENU screen re­appears, this time with an addi­tional option, DEW POINT ADJ.
5. Use the UP/DOWN button to highlight DEW POINT ADJ; press SELECT. Limits: Min. −15%, Max. +15%. Default setting: 0%.
6. In the DEW POINT ADJ CON­TROL screen, use UP/DOWN buttons to adjust desired dew point limit. When you reach the desired level, press SELECT.
Dehumidification
Dehumidification is provided only when the thermostat is in cool mode. The dehumidification signal (D terminal) is used to reduce the speed of the in­door blower during dehumidification. It does this by de−energizing the D ter­minal (terminal is an open circuit). Otherwise, the D terminal is activated with 24VAC. This is always the case when the thermostat is in HEAT or OFF mode.
The D terminal controls dehumidification. When the thermostat is powered, the D terminal is always active (24V present) in HEAT and OFF modes and is also active in the COOL mode EXCEPT when there is a call for dehumidi­fication. When a dehumidification demand is present, the D terminal is de− energized (open circuit), and the Y1 terminal becomes activated with 24VAC. Y2 (if available) also becomes activated with 24VAC.
The default mode for dehumidification is OFF and needs to be activated during installation. When dehumidification is occurring, a small teardrop icon with a −" symbol inside (shown in margin) is displayed on the screen.
MAIN MENU
PROGRAM HEAT / COOL HUMIDIFY DEHUMIDIFY
HOME SELECT
HUMIDIFY MENU
MODE OFF HUMIDIFY 44%
MAIN MENU SELECT
HUMIDIFY MODE
BASIC PRECISION BASIC/DP PRECISION/DP
HUM MENU SELECT
HUMIDIFY MENU
MODE BAS/DP DEW POINT ADJ 10%
MAIN MENU SELECT
HUMIDIFY MENU
MODE BAS/DP DEW POINT ADJ 0%
MAIN MENU SELECT
DEW POINT ADJ
CONTROL
HUM MENU SELECT
%
10
Page 9
SignatureStat t Thermostat
Page 9
Dehumidification Modes
In BASIC mode, dehumidification occurs if these conditions are met and
signals are present at specific terminals:
S dehumidification has been enabled, and S the unit is in COOL mode, and S cooling demand exists (Y1 energized), and S dehumidification demand exists.
In PRECISION mode, dehumidification occurs if these conditions are met:
S dehumidification has been enabled, and S the unit is in COOL mode, and S dehumidification demand exists , and S the room temperature is no lower than 2°F below the setpoint. S (If in Auto Changeover Mode) there has been at least one sensible
cooling call made prior to the dehumidification demand.
NOTE − The H terminal is inactive (open circuit) during dehumidification.
DEHUMIDIFY MODE Screen
NOTE − Basic or Precision mode must be turned on before you can adjust the dehumidification level on the thermostat.
DEHUMIDIFY CONTROL may be adjusted in 1 percent increments; rela­tive humidity range. To locate and adjust the DEHUMIDIFY CONTROL:
1. From the home screen press
MENU. Use the UP or DOWN button to highlight DEHUMIDIFY. Press SELECT for the DEHU­MIDIFY MENU.
2. From the DEHUMIDIFY MENU,
press SELECT again to choose MODE.
3. The default setting for dehumidifi-
cation is OFF. To turn on basic de­humidification mode, select BA­SIC. To turn on precision dehumidification mode, select PRECISION.
4. If you selected BASIC in the pre-
vious step, BAS is displayed on the right−hand side of the screen.
5. Use the UP/DOWN button to
highlight DEHUMIDIFY; press SELECT. Setting limits: Min. 45%, Max. 60%. Default setting: 50%.
6. In the DEHUMIDIFY CONTROL
screen, use the UP/DOWN but­tons to adjust for the desired hu­midification level; press SELECT.
MAIN MENU PROGRAM HEAT / COOL HUMIDIFY DEHUMIDIFY
HOME SELECT
DEHUMIDIFY MENU
MODE OFF DEHUMIDIFY 50%
MAIN MENU SELECT
DEHUMIDIFY MODE
OFF BASIC PRECISION
HUM MENU SELECT
DEHUMIDIFY MENU MODE BAS DEHUMIDIFY 50%
MAIN MENU SELECT
DEHUMIDIFY MENU
MODE BAS DEHUMIDIFY 50%
MAIN MENU SELECT
DEHUMIDIFY CONTROL
DEHUM MENU SELECT
%
50
Page 10
505232 06/07
Page 10
Humiditrol
®
Accessory
If a Humiditrol
®
accessory is present in the equipment at hand, then the
SignatureStatt thermostat must be configured to properly operate the Hu- miditrol® accessory as follows (see Figure 6 for the Humiditrol operation flowchart):
1. From the Home screen, press MENU. Then select INSTALLER SET­TINGS. Select HUMIDITROL, then select ENABLE. Verify that the HUMIDITROL ON is displayed in the INSTALLER SETTINGS menu.
2. Select MAIN MENU. Then select DEHUMIDIFY. Select MODE, then select HUMIDITROL. The SignatureStatt thermostat is now config­ured to operate the Humiditrol® accessory.
NOTE − Humiditrol® operation requires use of an outdoor sensor. If sensor is not connected and Humiditrol® is enabled, OUTSIDE ERR" is displayed on the main screen.
SignatureStatt thermostat operation with Humiditrol
®
enabled
Cooling onlyDehumidification will only occur if a dehumidification de-
mand is present, a cooling demand is not present, outdoor temperature is less than 95ºF, and the indoor temperature is not cooler than:
Heating setpoint + 2ºF (IF the difference between cooling and heating setpoints is greater than the deadband)
Cooling setpoint – deadband + 2ºF (IF the difference between cooling and heating setpoints is less than the deadband)
In this case, the 24 VAC is removed from the D" terminal and the Y2" ter­minal (if available) becomes activated with 24VAC. This will cycle the in­door variable speed motor to the dehumidification speed and cycle Y2 On" to the outdoor unit Cooling calls have priority over Humiditrol® calls.
Heating onlyThermostat will cycle heating On" and Off  to maintain heating setpoint. Dehumidification functions are disabled.
Calculating maximum allowable overcooling in cooling-only mode START
Maximum allowable over­cooling is equal to the cooling setpoint minus the deadband plus 2ºF
NO
Is the
cooling setpoint
minus heating setpoint greater than the
deadband
?
YES
Maximum allowable over­cooling is equal to the heating setpoint plus 2ºF
Values below were calculated following this flow diagram
"2" in calculations below is for over­cool," up to 2°F above heating setpoint.
Heating Only Set­point
Cooling Only Set­point
Deadband Set­ting (Range 3 to 8°F)
Maximum Allowable Overcool­ing:
75 °F 75 °F 4 °F 75 – 4 + 2 = 73°F (difference is
less than deadband setting)
80 °F 77 °F 5 °F 77 – 5 + 2 = 74°F (difference is
less than deadband setting)
74 °F 79 °F 6 °F 79 – 6 + 2 = 75°F (difference is
less than deadband setting)
70 °F 79 °F 6 °F 70 + 2 = 72°F (79 –70 = 9 > 6
therefore use heating setpoint)
AutochangeoverDehumidification will only occur if a dehumidification
demand is present, a cooling demand is not present, outdoor temperature is less than 95°F, and the indoor temperature is not cooler than 2ºF above heating setpoint.
In this case, the 24 VAC is removed from the D" terminal and the Y2" termi­nal (if available) becomes activated with 24VAC. This will cycle the indoor variable speed motor to the dehumidification speed and cycle Y2 On" to the outdoor unit. Cooling calls have priority over Humiditrol® calls. Humidi­trol® mode is allowed to overcool up to 2°F above the heating setpoint.
Note: If the last thermostat demand was a heating demand, the thermostat does not require a cooling demand before Humiditrol® operation.
Page 11
SignatureStat t Thermostat
Page 11
Other Humiditrol® Accessory Notes:
If the outdoor sensor is disconnected while Humiditrol® is enabled, thermo­stat will not allow operation in dehumidification mode.
Set point range: 45 to 60% Relative Humidity (RH). Factory default − 50%.
Relative Humidity controls to within 2% on either side of RH set point.
When the D" terminal is activated with 24VAC,.dehumidification is inac­tive.
Basic, Precision and Humiditrol
®
modes are deactivated by default from
the factory.
When HOLD" modes (Temporary, Vacation) are activated, and Auto­changeover is enabled, there is insignificant opportunity for dehumidifica­tion because cooling and heating use the same temperature setpoint.
As a precaution, regardless of how low the heating setpoint has been set, Humiditrol® dehumidification is inhibited below 65ºF indoor temperature.
Changing Time of Day / Day of Week
The time of day must be entered via the menu. This information appears on the top line of the home screen.
1. From the home screen press MENU. Use the UP or DOWN button to highlight DAY/TIME. Press SELECT.
2. Use the UP or DOWN button to highlight DAY, HOUR, or MIN­UTES. Press SET.
3. Use the UP or DOWN button to scroll through the days of the week, hours, or minutes. Press SET to select desired value. Press FINISHED when complete (see diagram).
Cycling the Fan
Fan Settings
1. From the home screen press MENU. Use the UP or DOWN buttons until FAN is highlighted. Press SELECT.
2. Use the UP or DOWN buttons to highlight FAN SETTINGS. Press SELECT.
3. Three fan setting choices are available:
ON will turn the indoor blower on continuously.
AUTO will turn the indoor blower on only when there is a call for heating or cooling.
INTERMITTENT will turn the indoor blower on for a set period of time for a given interval. Highlight the choice you desire and press SELECT.
Intermittent fan default ON time is 5 minutes; Default OFF time is 20 minutes. This function allows users to cycle the indoor blower for a selectable number of minutes per hour during periods of inactivity of heating/cooling system. ON time can be set from 1 to 20 minutes in 1−minute steps; OFF time can be set from 10 to 40 minutes in 1−minute steps.
If the HVAC system runs for a longer period than the ON cycle, the OFF cycle will start counting over again when the system shuts off (see diagram).
MAIN MENU
DAY / TIME FAN USER SETTINGS INSTALLER SETTINGS
HOME SELECT
MAIN MENU DAY FRIDAY HOUR 12 PM MINUTES 06
HOME SET
MAIN MENU DAY FRIDAY HOUR 12 PM MINUTES 06
FINISHED SET
MAIN MENU
DAY / TIME FAN USER SETTINGS INSTALLER SETTINGS
HOME SELECT
FAN MENU FAN SETTINGS FAN PROGRAM
HOME SELECT
FAN SETTINGS ON AUTO INTERMITTENT
MAIN MENU SELECT
INTERMITTENT FAN
ON TIME 5 MIN OFF TIME 20 MIN
FAN MENU SELECT
Page 12
505232 06/07
Page 12
Fan Program
This function allows the user to select whether the indoor blower operates in ON or AUTO modes during each programmed event period. For example, the indoor blower could be programmed to run in AUTO mode during the WAKE and MORN event periods and run in ON mode during the EVE and NIGHT event periods. The indoor blower may be set to run continuously during the occupied times to improve indoor air quality.
1. From the home screen press MENU. Use the UP or DOWN buttons until FAN is highlighted. Press SELECT.
2. Use the UP or DOWN buttons to highlight FAN PROGRAM. Press SELECT.
3. Use the UP or DOWN buttons to highlight the days or day you want to program. You can choose MON to SUN, MON to FRI, SAT to SUN, or individual days of the week. Press SELECT.
4. Use the UP or DOWN buttons to highlight the event you want to program.
5. Press SELECT. ON/AUTO is highlighted. Use the UP or DOWN buttons to highlight the ON or AUTO. Press SELECT. Press SET to select desired val­ue. Press FINISHED when com­plete.
MAIN MENU
DAY / TIME FAN USER SETTINGS INSTALLER SETTINGS
HOME SELECT
FAN MENU FAN SETTINGS FAN PROGRAM
HOME SELECT
SELECT PROGRAM DAYS
MON TO SUN MON TO FRI SAT TO SUN MONDAY
MAIN MENU SELECT
MON−SUN PROGRAM
FAN WAKE 6:30 AM AUTO MORN 8:30 AM AUTO EVE 4:30 PM AUTO NIGHT 10:30 PM AUTO
MAIN MENU SELECT
MON−SUN PROGRAM
FAN WAKE 6:30 AM AUTO MORN 8:30 AM AUTO EVE 4:30 PM AUTO NIGHT 10:30 PM AUTO
MAIN MENU SELECT
MON−SUN PROGRAM
FAN WAKE 6:30 AM AUTO MORN 8:30 AM AUTO EVE 4:30 PM AUTO NIGHT 10:30 PM AUTO
MAIN MENU SELECT
MON−SUN PROGRAM
FAN WAKE 6:30 AM ON MORN 8:30 AM AUTO EVE 4:30 PM AUTO NIGHT 10:30 PM AUTO
MAIN MENU SELECT
Page 13
SignatureStat t Thermostat
Page 13
User Settings and Options
User settings allow you to personalize your thermostat and change the way information is displayed on the home screen, and it helps to optimize the HVAC system to your comfort level.
1. From the home screen press MENU. Use the UP or DOWN buttons until USER SETTINGS is highlighted. Press SELECT.
2. Choose the setting you would like to change by pressing the UP or DOWN button to highlight the de­sired selection; then press SE­LECT. The first four settings may be set as follows:
ºF or ºC settingYou can choose to display the temperature in either Fahrenheit (F) or Celsius (C).
Press the UP or DOWN button to select the temperature display that you want, then press SE­LECT.
12 or 24 hour settingYou can choose to display the time in 12−hour format (default) or 24−hour format (international option).
Press the UP or DOWN button to select the time display that you want, then press SELECT.
SHOW SET TEMP settingEach event has a setpoint temperature, and the default is to display the setpoint on the HOME screen. Choose whether to display this value or not.
Press the UP or DOWN button to select whether you want the set­point temperature displayed or not, then press SELECT.
EVENTS/DAY settingThis screen allows users to select the num­ber of events per day. The default number of events per day is 4 (WAKE, MORN, EVE, and NIGHT); the alternate setting is two events (WAKE and NIGHT).
Press the UP or DOWN button to select the number of events you want for the day, then press SE­LECT.
3. Differential and delay settings de­termine when a first− or second­stage demand exists and desired delay time before the second stage operation can begin.
4. Choose one of the differential or relay settings from the User Set­tings menu. The screen changes to the differential settings menu. 1ST STAGE DIFFerential is used in all thermostats.
MAIN MENU
DAY / TIME FAN USER SETTINGS INSTALLER SETTINGS
HOME SELECT
USER SETTINGS Y F OR C F° 12 OR 24 HR 12 SHOW SET TEMP 78°F EVENTS/DAY 4
MAIN MENU SELECT
B
TEMPERATURE
ºF
ºC
USER MENU SELECT
CLOCK
12 HOUR 24 HOUR
USER MENU SELECT
DISPLAY SETPOINT
TEMPERATURE
NO
YES
USER MENU SELECT
BB B B B
0 6 12 18 24
SELECT
EVENTS/DAY 4
USER MENU SELECT
USER SETTINGS Y 1ST STAGE DIFF 1.0°F 2ND STAGE DIFF 2.0°F 2ND STAGE DELAY 20
COOLING LIMIT 45°F
MAIN MENU SELECT
B
DIFFERENTIAL SETTINGS
1ST STAGE DIFF 1°F 2ND STAGE DIFF 2°F 2ND STAGE DELAY 20
MAIN MENU SELECT
Page 14
505232 06/07
Page 14
The default is 1.0°F but can be programmed between 0.5° and 3.0°F in 0.5°F increments. See figure 4 for first−stage heating and cooling operations.
Figure 4. First−Stage Differential Settings
0°C
100°C
1st-stage ON
Setpoint + 0.5°F
No action
Setpoint
1st-stage OFFNo action
0°C 100°C
1st-stage ON
No action
Setpoint
1st-stage OFF
No action
Setpoint + 1st-stage diff
− 0.5°F
Setpoint
− 0.5°F
Setpoint
− 1st-stage diff + 0.5°F
HEATING MODE
COOLING MODE
2ND STAGE DIFFerential (multistage models only). The low limit
(and default) is 2.0°F but can be programmed up to 8.0°F in 0.5°F in­crements. See figure 5 for second−stage operation heating and cool­ing modes.
NOTE − On the 81M28 thermostat, the second−stage operation can be LOCKED OUT using the balance point settings. This second− stage lockout will OVERRIDE the operation shown in figure 5.
Figure 5. Second−Stage Differential Settings
0°C
100°C
Setpoint
− 1st stage diff
− 2nd stage diff + 0.5°F
2nd-stage ON
Setpoint + 0.5°F
1st-stage OFFIf 2nd-stage
timer expires,
then turn on
2nd-stage
Setpoint
2nd-stage OFF
Setpoint
−1st-stage diff + 0.5°F
1st-stage ON & reset 2nd-stage timer
Setpoint
− 0.5°F
No action No action
No action No action
0°C
100°C
Setpoint + 1st-stage diff + 2nd-stage diff
− 0.5°F
2nd-stage ON
Setpoint
− 0.5°F
1st-stage OFF If 2nd-stage
timer expires,
then turn on
2nd-stage
Setpoint
2nd-stage OFF
Setpoint + 1st-stage diff
− 0.5°F
1st-stage ON & re­set 2nd-stage timer
Setpoint + 0.5°F
No action No action
No actionNo action
COOLING MODE
HEATING MODE
2ND STAGE DELAY timer (multistage models only). Default delay is
20 minutes but can be programmed from 5 to 40 minutes in 5−minute increments. If first stage fails to advance the ambient temperature to­ward the setpoint by 1.0°F in the programmed delay time, then the second stage is activated (see figure 5).
Page 15
SignatureStat t Thermostat
Page 15
5. Heating and cooling limits help prevent user−settings to extreme temperatures. The homeowner can limit the maximum setting for the heating and cooling modes, thus helping to conserve energy and costs. Press the UP or DOWN button to select the high­est or lowest temperature for heating or cooling, then press SE­LECT. Programmed setpoints will be changed if they are higher (heating) or lower (cooling) than the minimum allowed setpoint. A warning screen appears before programmed setpoints change. COOLING LIMITThe default is 45°F. The minimum cooling set­point can be programmed from 45° to 90°F in 1.0°F increments. HEATING LIMITThe default is 90°F. The maximum heating set­point can be programmed from 45° to 90°F in 1.0°F increments.
6. Security settings are available to prevent tampering with the pro­gram and the user’s desired set­tings. Two levels of security are available; the default security set­ting is OFF.
ALLOW TEMPERATUREthis level permits temporary changes to temperature only while disal­lowing change to other program­ming.
RESTRICT ALLthis disallows any changes to System, Fan, Pro- gram, or setpoint. If security is activated, a screen pops up into which a 4−digit user security code is to be entered before any change is per­mitted.
Entering Security CodeSecu­rity is enabled after you enter a user−selectable 4−digit, numeric security code at the SECURITY SETTINGS screen.
Security remains enabled until the same security code is entered some time later, when changes to other settings are attempted. After the security code is entered, complete access to all features and functions is provided. To enable security again, re−enter a security code via the SECURITY SETTINGS screen.
A From the home screen press MENU. B Use the UP or DOWN button to highlight USER SETTINGS.
Press SELECT.
C Use the UP or DOWN button to highlight SECURITY. Press SE-
LECT.
D Use the UP or DOWN button to highlight select ALLOW TEM-
PERATURE or RESTRICT ALL. Press SELECT.
NOTE − Choosing ALLOW TEMPERATURE places the security code on all programming except the temperature. Other users can still change the temperature up or down. Such changes remain effec­tive until the time of the next programmed event. RESTRICT ALL pre­vents any change without first entering the security code.
E Use the UP/DOWN buttons to select the first digit for the code,
then press SELECT.
F After you choose the first value, the second digit is highlighted.
Repeat for all four digits.
G When the correct code is in, press a final SELECT. Future pro-
gramming changes will now require the code to be entered be­fore changes can be made.
USER SETTINGS Y
2ND STAGE DELAY 20 COOLING LIMIT 45°F
HEATING LIMIT 90°F
SECURITY OFF
MAIN MENU SELECT
B
WARNING: CHANGING MIN/MAX VALUE WILL CHANGE PROGRAMMED TEMPERATURE SETTINGS. CONTINUE:
NO YES
SET COOLING LIMIT
LOWEST COOLING
SETTING ALLOWED
45°F
USER MENU SELECT
SET HEATING LIMIT
HIGHEST HEATING
SETTING ALLOWED
90°F
USER MENU SELECT
USER SETTINGS Y 2ND STAGE DELAY 20 COOLING LIMIT 45°F HEATING LIMIT 90°F SECURITY OFF
MAIN MENU SELECT
SECURITY
ALLOW TEMPERATURE RESTRICT ALL
USER MENU SELECT
ENTER SECURITY CODE
FOR USER SETTINGS
0 0 0 0
USER MENU SELECT
Page 16
505232 06/07
Page 16
IMPORTANT
Stress to the homeowner the importance of remembering the Secu­rity Code  if code is forgotten or misplaced, the universal code 4199" can be used. If the thermostat is reset, all schedules are erased and full reprogramming is required.
After the security code is set, when any button on the thermostat is pushed, a screen appears that requires the security code to be en­tered. After the correct security code is entered, security is turned off. After revisions are made to the settings, the user must reenter the code to reestablish security
Change Temperature Settings
NOTE − If auto changeover is enabled at the time a temperature hold is invoked, the thermostat MAY CHANGE OVER from heating to cooling and vice versa, to maintain the temperature hold setpoint. The auto changeover deadband is still used to determine whether changeover occurs. This applies to all of the following hold modes.
Brief Temperature Change
1. From the home screen, press the UP or DOWN button. Press the UP/DOWN buttons to adjust to the desired temperature.
2. This setting will hold for 3 hours or until the next programmmed event begins, whichever time period is shorter.
3. After pressing SET TEMP or after 5 seconds, the home screen indicates new setpoint and duration. RESUME PROGRAM cancels a temporary setpoint change and returns to programmed setting.
Hold Settings Menu
Make permanent, temporary, or vaca­tion changes through the HOLD SET­TINGS menu. To access the menu, press HOLD TEMP from home screen.
Change Temperature Permanently
In the permanent change mode, the setpoint is maintained indefinitely. The thermostat must not be in OFF mode to enter this mode. To resume pro­grammed operation press the RESUME PROGRAM button from the main screen.
1. From the home screen, press the HOLD TEMP button Then select PERMANENT HOLD.
2. Use the UP or DOWN button to set the temperature to the desired level. Press SET TEMP.
3. The home screen will now indicate a PERMANENT HOLD. RESUME PROGRAM will cancel a permanent hold and return to the programmed temperature setting.
Change Temperature Temporarily
The setpoint and temperature are held for up to 24 hours.
1. From the home screen, press the HOLD TEMP button Then select TEMPORARY HOLD.
SET AT
↑ ↓
UNTIL 4:00 PM
HOME SET TEMP
70
°F
SET AT
↑ ↓
UNTIL 5:00 PM
HOME SET TEMP
78
°F
SET AT 78 UNTIL 5:00 PM
AUTO
FAN INT
27%RH OUTSIDE 95
RESUME
PROGRAM MENU
70
ºF
HOLD SETTINGS PERMANENT HOLD TEMPORARY HOLD VACATION HOLD
HOME SELECT
PERMANENTLY AT
↑ ↓
HOLD MENU SET TEMP
75
°F
PERMANENTLY SET AT 75
AUTO
FAN INT
27%RH OUTSIDE 95
RESUME
PROGRAM MENU
70
ºF
Page 17
SignatureStat t Thermostat
Page 17
2. The temperature should be high­lighted. Press the UP or DOWN button to adjust the temperature. Press SET TEMP.
3. The time should be highlighted. Press the UP or DOWN button to adjust the time. Press SET TIME.
4. The home screen will now indi­cate a TEMPORARY HOLD until the desired time. RESUME PROGRAM will cancel the tem­porary hold and return to the programmed temperature set­ting.
Setting Vacation Mode
The setpoint and temperature are held to up to 45 days.
1. From the home screen, press the HOLD TEMP button Then select VACATION HOLD.
2. The temperature should be high­lighted. Use the UP or DOWN button to change to the desired temperature. Press SET TEMP.
3. The number of days should be blinking. Use the UP or DOWN button to set the length of your vacation. Press SET DAY.
4. The home screen will now indi­cate the VACATION settings. RESUME PROGRAM will cancel the vacation settings and return to the programmed temperature setting.
Installer Settings
The INSTALLER SETTINGS are programmed during the initial installation and are selected based on the type of equipment used in the application. This feature should be set only by a certified HVAC technician. Incorrect use of these settings could result in higher energy costs and may even damage the HVAC equipment.
1. From the home screen press MENU. Use UP/DOWN buttons to highlight INSTALLER SET­TINGS. Press SELECT.
2. The INSTALLER SETTINGS screen appears. Use the UP/ DOWN buttons to scroll to all the installer settings.
NOTE − DEADBAND setting will not appear if AUTO CHANGE­OVER is disabled. BALANCE POINT settings appears only on 81M28 units only and require that an outdoor temperature sensor be installed.
3. Select SYSTEM SETUP. The resulting screen depends on which system and thermostat are being installed and are described as fol­lows:
SYSTEM SETUPUse the 81M26 thermostat’s system set­up screen to choose the system component that the thermostat will control. Use UP/DOWN but­tons for desired selection; press SELECT.
TEMPORARILY AT
↑ ↓
UNTIL 4:00 PM
HOME SET TEMP
70
°F
75
TEMPORARILY SET AT
↑ ↓
UNTIL 10:00 PM
HOME SET TEMP
°F
SET AT 72 UNTIL 10:00 PM
AUTO
FAN INT
27%RH OUTSIDE 95
RESUME
PROGRAM MENU
70
ºF
VACATION SETTING
↑ ↓
FOR 2 DAYS
HOME SET DAY
70
°F
VACATION SETTING
↑ ↓
FOR 45 DAYS
HOME SET DAY
78
°F
SET AT 78 FOR 45 DAYS
AUTO
FAN INT
27%RH OUTSIDE 95
RESUME
PROGRAM MENU
70
ºF
MAIN MENU
DAY / TIME FAN USER SETTINGS INSTALLER SETTINGS
HOME SELECT
INSTALLER SETTINGS Y SYSTEM SETUP GAS RESIDUAL COOL 120 LOW BALANCE 28°F HIGH BALANCE 28°F
AUTO CHANGEOVER ON EER ON DEADBAND 4.0°F HUMIDITROL OFF
SECURITY OFF CONTACT INFO SERVICE INT REMINDER CLNDR
TEMP OFFSET 0.0°F
MAIN MENU SELECT
B
SYSTEM SETUP
FURNACE HEAT PUMP
INSTALL MENU SELECT
Page 18
505232 06/07
Page 18
NOTE − In addition to non−heat pump single-stage applications, the 81M26 thermostat supports a single-stage heat pump with NO auxil­iary heat source.
1ST STAGE HEATINGUse the 81M27 thermostat’s 1st stage heating screen to choose gas/oil or electric first−stage heating.
Use UP/DOWN buttons for desired selection; press SELECT.
AUXILIARY HEATUse the 81M28 thermostat’s auxiliary heat screen. Use UP/DOWN but­tons for desired selection; press SELECT.
If using an electric furnace, select STANDARD − COMP = ON; if using a gas furnace (dual fuel), use ADD ON − COMP = OFF).
4. BALANCE POINTSBalance point settings are only available on the 81M28 thermostat. This screen appears only when optional out- door sensor 46M98 is connected to the thermostat.
When sensor is used with the 81M28, you can set the lower and upper temperatures to disable or enable second stage heat.
Use the UP/DOWN buttons to select either LOW or HIGH BALANCE. Press SELECT. Now use the UP/DOWN buttons to adjust the balance point temperature. Setting range: −20F to +75F.
NOTE − High Balance cannot be set lower than the LOW setting; Low Balance cannot be set higher than the HIGH setting.
5. RESIDUAL COOLTo ensure greatest cooling efficiency, the indoor blower can be programmed to run after a cooling demand has been
met by adjusting the residual cool setting. This is the amount of time that the indoor blower will run after a call for cooling has been satis­fied. This ensures that any residual cool air will be pushed out of the ductwork and into the living area. Residual cool may interfere with proper system operation, especially in humid climates.
Set residual cool to run for 30, 60, 90, or 120 seconds after the com­pressor has shut off (default: OFF).
6. AUTO CHANGEOVER / AUTOCHANGE DEADBANDWhen
AUTO CHANGEOVER (default − DISABLED) is turned ON, the ther­mostat will switch automatically between heating and cooling to main­tain the optimal temperature in the home.
From the INSTALLER SET­TINGS menu, select AUTO CHANGEOVER, then select EN­ABLE.
The minimum allowable difference between the heating and cooling setpoints is the auto changeover deadband (default − 4.0 degrees). DEADBAND appears only when auto changeover is ENABLED as described above. The deadband may be adjusted from 3.0 to 8.0 de­grees in 0.5 degree increments.
From the INSTALLER SET­TINGS menu select DEAD­BAND. Use the UP and DOWN arrows to adjust.
With default settings as described, the thermostat is essentially shipped as a HEAT/COOL thermostat).
HEATING/1ST STAGE HEATING
GAS / OIL
ELECTRIC
INSTALL MENU SELECT
AUXILIARY HEAT
STANDARD − COMP = ON ADD ON − COMP. = OFF
BACK SELECT
BALANCE POINTS
LOW BALANCE 45 °F HIGH BALANCE 75 °F
INSTALL MENU SELECT
RESIDUAL COOL
SECONDS DELAY
OFF
INSTALL MENU SELECT
AUTO CHANGEOVER
DISABLE
ENABLE
INSTALL MENU SELECT
AUTOCHANGE DEADBAND
4ºF
INSTALL MENU SELECT
Page 19
SignatureStat t Thermostat
Page 19
7. ENERGY EFFICIENT RECOVERYWith energy efficient recovery
enabled, the recovery will start before the programmed time. When disabled, the control will start a recovery at the programmed time. The control assumes a heating capacity of 6°F per hour and a cooling ca­pacity of 4°F per hour. The control then turns on before the pro­grammed time by determining the difference between the actual tem­perature and the recovered setpoint.
The control then calculates how much in advance the low−cost first stage will operate to be at the setpoint at the programmed time. The second stage is locked" out until 20 minutes before the programmed time.
The energy efficient recovery de­fault setting is on (ENABLE). To turn it off, use UP/DOWN buttons to highlight DISABLE; press SE­LECT.
NOTE − When the EER causes the equipment to be activated ahead of the programmed event time, EER will be displayed on the home screen in the place of the outdoor temperature.
8. HUMIDITROL If a Humiditrol
®
accessory is present in the equip-
ment at hand, then the SignatureStatt thermostat must be config- ured to properly operate the accessory. An outdoor sensor is re- quired when using Humiditrol. Configure the thermostat as follows (see Figure 6 for the Humiditrol operation flowchart):
From the Home screen, press MENU. Select INSTALLER SET­TINGS, then HUMIDITROL, then ENABLE. Verify that the HUMIDI­TROL ON is displayed in the IN­STALLER SETTINGS menu.
From Home screen, press MENU, then DEHUMIDIFY, then MODE, then HUMIDITROL. The thermostat is now configured to operate the accessory.
9. SECURITY CODEA security code prevents changes to the IN-
STALLER settings. The default security code setting is OFF. This lev­el of security restricts access to the installer menus. All other thermo­stat and user settings are available. When SECURITY is selected, a screen appears for entering a four−digit installer security code.
If the installer settings security code is forgotten or misplaced for some reason, the universal code "0801" can be used.
10. CONTACT INFORMATIONThis will provide information to the
homeowner regarding who and when to contact in case of trouble, or for routine service. Contact information is displayed in the event of a service maintenance interval (such as an elapsed system monitor timer). You can program two full lines of character information via the user interface. The top line can contain up to 20 characters, and the bottom line can contain up to 14 characters.
At the contact screen, push the EDIT button then the UP/DOWN buttons to choose correct contact information. Push NEXT to ad­vance to next character. When finished with the first line, press ACCEPT. The cursor advances to the next line.
Continue choosing contact information, then push ACCEPT to finish.
ENERGY EFFICIENT
RECOVERY
DISABLE
ENABLE
INSTALL MENU SELECT
INSTALLER SETTINGS Y AUTO CHANGEOVER ON EER ON DEADBAND 4.0°F HUMIDITROL OFF
MAIN MENU SELECT
B
HUMIDITROL
DISABLE
ENABLE
INSTALL MENU SELECT
ENTER SECURITY CODE
FOR INSTALLER
SETTINGS
0 0 0 0
INSTALL MENU SELECT
CONTACT INFORMATION
M
BACK EDIT
CONTACT INFORMATION
MY HVAC COMPANY
1−800−123−456
ACCEPT NEXT
Page 20
505232 06/07
Page 20
11. SERVICE INTThese settings
establish criteria for service mes­sages and alert the homeowner when filters or cooling/heating system need servicing. This mon­itor counts the run time hours or calendar days of operation of the indoor blower. When the pro­grammed time is reached, a mes­sage will appear on the HOME screen (message programmable via the CONTACT INFORMA­TION screen).
The service interval setting can be adjusted for intervals from 20 to 980 hours (in 20-hour increments), and to reset the timer and warning message. The OFF setting disables the CHANGE FILTER warning.
Two choices are available on this menu: the Service Monitor and the Filter Monitor. Both can be set based on the HVAC system run time or the calendar. (See Re­minder Interval.)
Choose a MONITOR: COOL, HEAT (SYSTEM on 81M28), or FILTER. Press SELECT. The Checkup Interval screen appears.
Use the UP or DOWN button to adjust the number of hours or days for the service interval. Press SELECT when you reach the desired num­ber.
12. REMINDERThe reminder period can be set for either HVAC sys-
tem run-time (hours) or based on the calendar (days).
If RUN TIME is chosen, the ser­vice reminder will be set in hours and displayed on the INSTALLER SETTINGS menu as RUN.
After indoor blower has operated for selected number of hours, a Ser­vice Reminder alerts homeowner that it is time to service system or filter.
If CALENDAR TIME is chosen, the service reminders will be set in days and displayed on the INSTALLER SETTINGS menu as CLNDR. After the selected number of days has passed, a Service Reminder will be displayed to alert the homeowner that it is time to service the system or filter.
13. TEMP OFFSETThis feature adds or subtracts the amount of the
setting to/from the detected room temperature.
For example, if actual room tem­perature is 75ºF and the offset were set at −1.0ºF, the thermo­stat’s display would show 74ºF.
The temperature offset is programmable from −3 to +3°F, and the de­fault offset is zero.
Remote Outdoor Sensor
The remote outdoor sensor (46M98) can be used to aid in the comfort of the home or simply as a sensing device for outdoor conditions.
In most applications, the SignatureStatt thermostat will have a display of the temperature sensed by the remote outdoor sensor. With the heat pump system, the remote outdoor sensor can help determine when to turn on the second stage of heating for optimal comfort.
When the outdoor sensor is connected, the temperature displays on the right−hand side of the screen. For example, the display will show OUT­SIDE 77°F" if the outdoor temperature is 77°F.
SERVICE MONITOR MENU
COOL MONITOR 980 HEAT MONITOR 980 FILTER MONITOR 980
INSTALL MENU SELECT
COOLING SYSTEM CHECK−UP
HEATING SYSTEM CHECK−UP
FILTER REPLACEMENT
INTERVAL 600 HRS
SERVICE MENU SELECT
SERVICE MONITOR MENU
SERVICE MONITOR 180 FILTER MONITOR 120
INSTALL MENU SELECT
SYSTEM CHECK−UP
INTERVAL
90 DAYS
SERVICE MENU SELECT
REMINDER PERIOD
RUN TIME CALENDAR TIME
INSTALL MENU SELECT
TEMPERATURE OFFSET
−1.0 ºF
INSTALL MENU SELECT
Page 21
SignatureStat t Thermostat
Page 21
Installing Remote Outdoor Sensor
Install the remote outdoor sensor on a northern wall of the home, away from direct sunlight or other heat sources that may affect its sensitivity.
IMPORTANT
The outdoor sensor must be connected with twisted pair wire (84X49 [1000’ roll] or X3790 [500’ roll]). For operating a system with a Humiditrol® accessory, the remote sensor MUST be installed.
Display Lights
The display lights indicate HVAC system operation.
S HEAT or COOL light will be illuminated with a call for heating or cooling
(81M26 and 81M27 models).
S AUX light indicates the second stage of heating − W2 is active (81M28
model only).
S EMER light indicates that the emergency heat is enabled in HEAT/
COOL menu, regardless of heat demand (81M28 model only). Emer­gency heat is activated via the E/W1 terminal.
S CHECK light comes on when a 24V signal is present on the L" termi-
nal. This indicates that the equipment requires service by a qualified technician (all models).
Memory Protection
The thermostat stores all the information concerning its programming (state, mode, program information, last temperature measured) in a non­volatile memory.
This function avoids the loss of the state of the thermostat when a power− down occurs. The only thing that might be lost is the time. A super−cap pro­vides 2 hours of power reserve (for power outages). When a power down occurs (due to a power outage) the thermostat is able to switch off all relays. The O and B relay will maintain their last state.
EPA ENERGYSTAR® Recommended Setpoints
EPA ENERGYSTAR® recommended setpoints for heating and cooling can help the household save energy.
The following time and temperatures are preprogrammed into the control to conform to Energy Star requirements.
Table 1. ENERGYSTAR
®
Setpoints
Time Winter Heating Summer Cooling
Morning 70°F (21°C) 78°F (25°C)
Day 62°F (17°C) 85°F (29°C)
Evening 70°F (21C) 78°F (25°C)
Night 62°F (17°C) 82°F (28°C)
NOTE − Humidification and dehumidification are not part of the ENERGYS­TAR® program. A higher utility bill may occur when not using the setpoints in table 1.
Resetting Program to Factory Conditions
To reset the SignatureStatt thermostat to factory conditions, press the UP button and the LEFT button at the same time. Hold for 8 seconds. The time of day will display 12:00 indicating a reset has occurred or until LENNOX  or the software version is shown on LCD.
NOTE − This will erase all programming and return the thermostat to the fac­tory conditions, including the installer settings. Use this only as a last resort.
Page 22
505232 06/07
Page 22
Thermostat−Specific Information
81M261 Stage Heat / 1 Stage Cool, Heat Pump without Auxiliary Heat, or Non−Heat Pump
Table 2. 81M26 LED Indicators
COOL Cooling mode (Y is active)
CHECK 24V signal is present on the L" terminal
HEAT Heating mode (W is active)
Fan AutoWhen COOLING, the indoor blower will cycle with calls for
cooling. When HEATING, and with the thermostat set for gas/oil, the indoor blower (G) does not cycle with a call for Heat. The independent fan control in the flue will cycle the indoor blower as necessary.
GO TO: MENU > INSTALLER SETTINGS > SYSTEM SETUP > FURNACE > GAS/OIL
When in electric heat, the indoor blower (G) cycles with the call for heat.
GO TO: MENU > INSTALLER SETTINGS > SYSTEM SETUP > FURNACE > ELECTRIC
When the single stage heat pump is activated, the indoor blower cycles with every call of heating and cooling.
GO TO: MENU > INSTALLER SETTINGS > SYSTEM SETUP > HEAT PUMP
Fan ONThe indoor blower is ON continuously regardless of whether
the heating or cooling equipment is running.
Table 3. 81M26 Terminal Designations
R 24 Vac power input
C 24 Vac common
Y1 Energized on call for COOL
E/W1 Energized on call for HEAT
G Energized on call for FAN
H Energized on a call for humidification
D De−energized on a call for dehumidification (reverse logic)
O COOL active (always energized when the stat is in COOL mode,
default value is OFF)
B HEAT active (always energized when the stat is in HEAT mode,
default value is ON)
L Illuminates CHECK LED when energized with 24VAC
NOTE − High−temperature PEPI disables W1 when ambient temperature exceeds 95°F.
Thermostat Off" ModeIn this mode, the heating and cooling and
H/D terminals are inactive. The O or B terminal is active. This is determined by the last state of O/B. For example, if the mode goes from heat (B active) to off, then B will be active in the off mode. Default on power−up is B active. The G terminal may be active if FAN ON is selected from the menu.
Page 23
SignatureStat t Thermostat
Page 23
81M272 Stage Heat & Cool, Non−Heat Pump
Table 4. 81M27 LED Indicators
COOL Cooling mode (Y is active)
CHECK 24V signal is present on the L" terminal
HEAT Heating mode (W1 is active)
Table 5. 81M27 Terminal Designations
R 24 Vac power input from HVAC system
C 24 Vac common
Y1 Energized on call for 1st stage COOL
Y2 Energized on call for 2nd stage COOL
E/W1 Energized on for 1st stage HEAT
W2 Energized on for 2nd stage HEAT
G Energized on call for FAN
H Energized on a call for humidification
D De−energized on a call for dehumidification (reverse logic)
O COOL active (always energized when the stat is in COOL mode,
default value is OFF)
B HEAT active (always energized when the stat is in HEAT mode,
default value is ON)
L Illuminates CHECK LED when energized with 24VAC
NOTE − High−temperature PEPI disables W1 ands W2 when ambient tem­perature exceeds 95F.
Fan AutoIn COOLING, the indoor blower cycles with calls for cooling.
In HEAT, and with the thermostat set for gas/oil, the indoor blower (G) does not cycle with a call for heat. The independent fan control in the flue will cycle the indoor blower as necessary.
GO TO: MENU > INSTALLER SETTINGS > SYSTEM SETUP > GAS/OIL
When in electric heat, the indoor blower (G) cycles with the call for heat.
GO TO: MENU > INSTALLER SETTINGS > SYSTEM SETUP > ELECTRIC
Fan ONThe indoor blower is ON continuously regardless of whether
the heating or cooling equipment is running.
Thermostat Off" ModeIn this mode, the heating and cooling and
H/D terminals are inactive. The O or B terminal is active. This is determined by the last state of O/B. For example, if the mode goes from heat (B active) to off, then B will be active in the off mode. Default on power−up is B active. The G terminal may be active if FAN ON is selected from the menu.
81M282 Stage Heat & Cool Heat Pump
Table 6. 81M28 LED Indicators
AUX W2 is active.
CHECK 24V signal is present on the L" terminal
EMER Emergency heat is enabled in menu.
Table 7. 81M28 Terminal Designations
R 24 Vac power input from HVAC system
C 24 Vac common
Y1 Energized on for 1st stage HEAT or COOL (heat pump com-
pressor control)
Y2 Energized on call for 2nd stage COOL
E/W1* Energized on call for emergency heat
W2* Energized on for 2nd stage HEAT
G Energized on call for FAN
H Energized on a call for humidification
D De−energized on a call for dehumidification (reverse logic)
O COOL active (always energized when the stat is in COOL
mode, default value is OFF)
B HEAT active (always energized when the stat is in HEAT
mode, default value is ON)
L Illuminates CHECK LED when energized with 24VAC
* Factory-installed jumper between E/W1 and W2.
Page 24
505232 06/07
Page 24
NOTE − High−temperature PEPI disables W2, E and Y1 (in heat mode only) when ambient temperature exceeds 95F.
Table 8. 81M28 Output Characteristics
(with electric heat backup and no outdoor sensor)
Mode Outputs Activated
First−stage heat pump − cool Y1, G, O
Second−stage heat pump − cool Y1, G, O, Y2
First−stage heat pump − heat Y1, G, B
Second−stage heat pump − heat (Combina­tion of heat pump and electric backup heat)
Y1, G, B, W2
First−stage emergency heat E/W1, G, B
Second−stage emergency heat E/W1, G, B, W2
81M28 Output Characteristics (with electric or gas (dual fuel) heat backup and outdoor sensor)
The above output characteristics become restricted when high and low bal­ance points are used.
1. Balance points are used only when the outdoor temperature sensor (46M98) is attached to the unit.
2. When the thermostat is in heat mode and a heat demand exists, if the temperature measured by outdoor sensor is below the low balance point, the heat pump is turned off and only the electric (or gas) heat can cycle.
3. When the thermostat is in heat mode and a heat demand exists, if the temperature measured by outdoor sensor is above the high balance point, the electric (or gas) heat is turned off and only the heat pump can cycle.
4. When the thermostat is in heat mode and a heat demand exists, if the temperature measured by outdoor sensor is between the high and low balance points, both the heat pump and electric (or gas) heat and can cycle.
5. Emergency heat is enabled whenever it is selected by the user (and a heat demand exists) and is NOT restricted by the balance points.
NOTE − See figure 7 for a detailed flowchart of Dual Fuel operation.
Page 25
SignatureStat t Thermostat
Page 25
Fan AutoIn COOLING, the indoor blower cycles with calls for Cooling.
In HEAT, and with the thermostat set for standard, the indoor blower (G) cycles with a call for first stage of heating. Note the indoor blower and com­pressor stay on when the second stage of heating activates.
GO TO: MENU > INSTALLER SETTINGS > SYSTEM SETUP > STANDARD−COMP=ON
When in add−on heat, the indoor blower (G) again cycles with the call for first stage heat. Note that the compressor turns off (comp=off) when the second stage of heat activates, but the indoor blower remains on.
GO TO: MENU > INSTALLER SETTINGS > SYSTEM SETUP > ADD ON−COMP=OFF
Fan ONThe indoor blower is ON continuously regardless of whether
the heating or cooling equipment is running.
Thermostat Off" ModeIn this mode, the heating and cooling and
H/D terminals are inactive. The O or B terminal is active. This is determined by the last state of O/B. For example, if the mode goes from Heat (B active) to Off, then B will be active in the Off mode. Default on power−up is B active. The G terminal may be active if FAN ON is selected from the menu.
System SetupDefault setting is STD (STANDARD−COMP=ON). The
auxiliary heat may be configured for standard or ADD on. Standard means the auxiliary stage supplements the compressor stage (the compressor and auxiliary are on at the same time). Add−on (ADD ON−COMP=OFF) means that the compressor turns off before the auxiliary turns on. When the auxiliary turns off, the compressor may turn on again.
Low Balance PointDefault setting is 25°F. This option will only be
available if an outdoor sensor is installed. If the outside temperature is be­low the programmed low balance point, then the compressor stage opera­tion is disallowed. This protects the compressor from operation and dam­age in cold outdoor temperatures. Also, if the heat pump is not effective at a low outdoor temperature, then it is more comfortable and efficient to go di­rectly to the second stage. The options are from −20°F to the high balance point temperature in 1.0°F steps.
High Balance PointDefault setting is 50°F. This option is only avail-
able if an outdoor sensor is installed. If the outside temperature is above the high balance point, then the auxiliary heat stage is disallowed. This pre­vents the expensive auxiliary heat stage from operating, and makes the low
cost heat pump satisfy the call. Both the compressor and auxiliary heat may not be disabled at the same time by the low and high balance points.
SignatureStatt Humiditrol® Logic Diagram
RUN EQUIPMENT
IN NORMAL
HEATING MODE
RUN EQUIPMENT
IN NORMAL
COOLING MODE
DEACTIVATE
ALL
EQUIPMENT
81M SignatureStatt Equipment Operation with Humiditrol® Enabled
NO
IS THERE A
HEATING
DEMAND?
start
IS THERE A
COOLING
DEMAND?YES
IS THERE A
DEHUMIDIFICATION
DEMAND?
YES
NO
NO
YES
IS
COOLSET – HEATSET
> DBND
?
IS INTEMP >
COOLSET – DBND
+2ºF
?
IS INTEMP >
2ºF ABOVE
HEATSET
?
run
Humiditrol
®
LEGEND:
COOLSET = COOLING SETPOINT DBND = DEADBAND HEATSET = HEATING SETPOINT INTEMP = INDOOR TEMPERATURE
YES
NO
IMPORTANT!
HUMIDITROL® IS NOT ALLOWED TO RUN IF:
S OUTDOOR
TEMPERATURE IS GREATER THAN 95ºF OR,
S INDOOR
TEMPERATURE IS LESS THAN 65ºF.
NO
YES
YES
NO
Figure 6
Page 26
505232 06/07
Page 26
Figure 7 shows a Dual Fuel Flowchart for 81M28 Thermostat.
Figure 7
Dual Fuel Flowchart for 81M28 Thermostat
Abbreviations: aux = auxiliary comp = compressor LBP = Low Balance Point temp = temperature tstat = thermostat
Gas heat lock­out (when set for aux heat = add (comp = off))
De−energize
Y1 & G
Energize
W2
Heat pump lockout (when set for aux heat = add (comp = off))
NO
YES
Outdoor
temp above
LBP
?
De−energize
W2
Energize
Y1, B & G
YES
NO
YES
NO
De−energize
W2
2nd stage
heat demand
?
Indoor
tstat heat
demand
?
2nd stage
heat demand
?
Indoor
tstat heat
demand
?
2nd stage
heat demand
?
Indoor
tstat heat
demand
?
De−energize
Y1
Outdoor
temp above
LBP
?
YES
NO
NO
YES YES
NO
NO
YES
YES
NO
Wiring DiagramsThermostat wiring connections with various units,
including dual fuel, zone control, and applications that include the Humidi­trol® accessory. See figures 8 and 9.
Figure 8
Typical Condensing Unit/Humiditrol
®
Accessory
Wiring Diagram
RED
YEL
BLU
BLK
BRN
SignatureStat
t
THERMOSTAT
INDOOR UNIT
OUTDOOR UNIT
TWISTED PAIR
PUR
OUTDOOR SENSOR (46M98)
BLK
Y1Y2 JUMPER − IN FOR SINGLE− STAGE COOLING; REMOVED FOR 2−STAGE COOLING
RED
BLK
PUR
EDA UNIT
FAN RELAY
NOTES − /1\ NOT REQUIRED FOR APPLICATIONS WITHOUT LSOM /2\ NOT REQUIRED WITH SINGLE-SPEED OUTDOOR FAN) /3\ NOT REQUIRED FOR SINGLE STAGE /4\ ON 81M28 MODEL, E/W1 AND W2 TERMINALS MUST BE JUMPERED
TOGETHER FOR MOST APPLICATIONS
Page 27
SignatureStat t Thermostat
Page 27
Figure 9
Wiring Diagrams
Page 28
Loading...