230VAC power cord available separately (part number
91X44).
Check equipment for shipping damage. If damage is found,
immediately contact last carrier.
Models
Table 1. Unit Catalog Numbers
ModelCatalog Number
PCO3S-14-16Y8905
PCO3S-16-16Y8904
PCO3S-20-16Y8903
The iComfort S30 Ultra Smart Thermostat will require
rmware version 3.4 or higher to take advantage of all of
the PureAir S features.
New features included are:
• 4-wire connection to Lennox communicating indoor
unit control
• Using sensors to:
> Automatically detect dirty air lter
> Display air lter life percentage
> Monitor UVA lamp operational state (On or Off).
> Display UVA lamp life percentage
IMPORTANT
Oil on metal ducts may cause odors.
Use a mild soap and water solution to remove oils from
transitions and duct surfaces prior to installation.
IMPORTANT
Do not use any form of silicone sealant.
Use of silicone-based products will reduce the
effectiveness of, or damage the titanium dioxide coatings
on the PCO cartridge.
IMPORTANT
Route power cord away from trafc areas where the cord
may become a safety hazard.
Application
The PureAir S air purication system uses photocatalytic
oxidation (PCO) technology to reduce levels of airborne
volatile organic compounds, cooking odors, common
household odors, airborne dust particles, mold spores and
pollen. Each unit may be connected to either 120VAC or
230VAC power supply.
Lab tests conrm a 50% reduction in total volatile organic
compounds (TVOC) within the rst 24 hours of initial
operation of the PureAir S air purication system. It may
take up to 48 hours after initial system start-up to reduce
the airborne chemicals that have built up in a home over a
long period of time.
For peak performance, unit should be installed in homes
with TVOC levels that are less than 1000 micro-gram /
cubic meter. Home source removal and ventilation may be
required to lower total volatile organic compounds to this
level.
The Healthy Climate® Carbon Clean 16® Filter combines
industry-leading MERV 16 ltration and carbon-coated ber
matrix.
For full feature benets, the PureAir S must be used with
an S30 Ultra Smart Thermostat and communicating indoor
unit.
IMPORTANT
UVA lamp life is shortened when lamp is turned off and on.
Power to unit must remain on at all times.
Do not interlock lamp operation with air handler blower
operation.
CAUTION
Ultraviolet (UVA) radiation risk.
Prolonged exposure may cause skin or eye damage.
Avoid prolonged (weeks) exposure to skin or eyes.
WARNING
Risk of carbon monoxide poisoning.
Can cause injury or death.
Do not operate system unless access panel is in place
and properly secured. Operation of this equipment without
the access panel in place may cause exhaust fumes to be
drawn into occupied spaces.
*Not recommended. Excessive system pressure drop can damage
HVAC system and reduce performance.
Flow Rate
(CFM)
4000.050.040.03
6000.070.070.06
28000.110.110.08
312000.200.200.15
41600*0.310.22
52000**0.31
PCO3S-14-16 PCO3S-16-16PCO3S-20-16
Pressure Drop (in. w.g.)
IMPORTANT
Do not wash UVA Lampholder / PCO cartridge. Soap and
water will destroy the titanium dioxide catalyst that coats
the cartridge surface.
IMPORTANT
Possible odor emissions. Chemical reactions may
cause temporary odors after initial start-up or after lamp
replacement. Odor may also be present after paint,
cleaning solutions or hobby materials have been used in
the conditioned space.
Some occupants may experience irritation or discomfort
during this period. If the irritation or discomfort lasts longer
than 48 hours, the homeowner should be advised to
contact a Lennox dealer.
IMPORTANT
The cabinet should be installed so that the UVA lamp will
be in the horizontal position.
IMPORTANT
This system is NOT intended to be used for removal of
active mold growth or continuous sources of high levels of
chemicals in the air.
For existing mold growth, the mold must be properly
removed PRIOR to installation of the PureAir S air
purication system.
IMPORTANT
Unpacking required.
Remove all protective packing material from the UVA
lamp (taped to the cabinet) and the titanium dioxide PCO
cartridge.
Packing material should be disposed of properly.
IMPORTANT
Healthy Climate® Carbon Clean 16® Filter cannot tolerate
direct exposure to UVA light.
Filter is protected by PCO cartridge shield.
IMPORTANT
This appliance is intended for return air duct installation
only.
Improper installation may damage PureAir S air purication
system, HVAC system, or other equipment and may also
void warranty.
5
Page 6
Installation Examples
UPFLOW FURNACE/AIR HANDLER
UPFLOW FURNACE
(Bottom Return Air)
SUPPLY
DUCT
RETURN
DUCT
DOWNFLOW FURNACE/AIR HANDLER
RETURN
DUCT
PCO3S
PCO3S
(Side Return Air − up to 4 ton)
RETURN
DUCT
PCO3S
UPFLOW FURNACE
(Option 1 − Side Return Air − 5 ton)
(With Optional RAB Return Air Base)
SUPPLY
DUCT
SUPPLY
DUCT
RETURN
DUCT
SUPPLY
DUCT
HORIZONTAL FURNACE/AIR HANDLER
DUCT TRANSIITON
SUPPLY DUCT
(Field Furnished)
FURNACE OR
AIR HANDLER
NOTE: Lennox badge can be rotated 180 degrees
for this application.
PCO3S
RETURN DUCT
OPTIONAL
RAB RETURN
AIR BASE
PCO3S
NOTE: Lennox badge can be rotated 180 degrees
for this application.
UPFLOW FURNACE
(Option 2 − Side Return Air − 5 ton)
(Modified Return Air Opening)
Figure 3. Installation Examples
6
Page 7
UniqUe fielD-sUpplieD installation items
Allow Approximately
30” (76cm) of Clearance
The following items are recommended to have on-hand for
installation of the unit.
• Cotton gloves and cloth (to remove nger prints from
UVA lamp)
• Aluminum foil tape or water-based mastic (NOT silicone) to be applied as a sealant.
Installation
selecting location
The unit must be installed in the return air duct upstream of
the supply blower. Allow a 30” (76cm) service clearance in
front of the access panel as shown in gure 4. The air lter
and UVA Lampholder / PCO cartridge must be removable.
5. Use eld-provided aluminum foil tape or water-based
mastic to seal all joints between the cabinet, air handler
and duct.
6. In high humidity applications, wrap cabinet with eld-
provided 2” (50mm) foil-faced insulation (foil on the
outside) to prevent condensation.
installing UVa lamp
Use cotton gloves or a cotton cloth to protect the lamp and
your hands during unpacking and installation.
1. Remove cabinet access panel.
2. The UVA Lampholder / PCO cartridge is shipped in a
protective packaging. Packaging must be removed
prior to installation. Take care to prevent damage while
removing from packaging.
3. Locate the UVA lamp box, which is taped to the inside of
cabinet and carefully remove. Set UVA lamp box aside
while preparing cabinet for UVA lamp installation.
5. Disconnect the lampholder cable assembly from the
UVA lamp ballast connector.
6. Carefully remove lamp from UVA lamp box and secure
the UVA lamp electrical connector to the UVA lamp by
sliding the UVA lamp pins into the slot. Proper connection
will make a snapping sound.
Figure 4. Service Clearance
installing cabinet
The cabinet may either be installed on a level installation
deck or platform adjacent to the air handler or it may be
suspended from the rafters using metal strapping. If straps
are used, take care when attaching straps to the cabinet.
Ensure fasteners do not interfere with internal components
of the cabinet. The air lter and UVA Lampholder / PCO
cartridge must be able to slide freely into the cabinet.
1. Locate and remove the UVA Lampholder / PCO cartridge
from the cabinet.
NOTE: Oil on metal surfaces may cause odors. Use mild
soap and water solution to wash all new duct and
transition surfaces.
2. Use the air ow directional label on the inside of the UVA
Lampholder / PCO cartridge to orient the unit.
3. Properly position the cabinet next to the return air
opening of the air handling unit. Use sheet metal screws
1” (25mm) maximum length, rivets or other appropriate
fasteners to secure cabinet to the return air side of the
air handling unit.
4. Use eld-provided sheet metal screws 1” (25mm)
maximum length to fasten the return air duct to the other
side of the cabinet. Attachment holes are provided in
housing.
DEPRESS RED BUTTON
ONLY TO RELEASE UVA
LAMP FROM SOCKET.
Figure 5. Releasing UVA Lamp from Socket
7. Slide the UVA lamp into UVA Lampholder / PCO
cartridge. Verify that the UVA lamp is secure to the one
metal UVA lamp clamp located mid-way on the UVA
lamp reector.
METAL UVA LAMP
CLAMP
UVA LAMP REFLECTOR
Figure 6. UVA Lamp Metal Clamp
7
Page 8
8. Rotate the hinged control panel assembly out.
ROTATE OUT THE
CONTROL PANEL
ASSEMBLY
BRASS FINGER
NUTS
A
IRFLOW
INDICATOR
WING
NUTS
BALLAST FOUR PIN
FEMALE CONNECTOR
LAMPHOLDER
ASSEMBLY
(Y6622)
Figure 7. Rotate Out Control Panel Assembly
9. Thread the UVA Lampholder / PCO cartridge two posts
through the UVA lamp connector’s two holes.
10. Fasten the lamp socket to the UVA Lampholder / PCO
cartridge using the two-brass nger nuts located in the
literature bag.
NOTE: There is an arrow on the front of the component
indicating the correct way to install it.
3. Connect UVA lamp 4-pin male connector to ballast
female 4-pin connector.
Figure 9. Ballast 4-Pin Female Connector
4. Rotate hinged control panel assembly back into the
cabinet. Make sure no wiring is being pinched.
installing air filter
Use the following procedure to install the air lter.
1. Slide the Healthy Climate® Carbon Clean 16® Filter into
the rails on the air inlet side of the cabinet. Verify proper
airow direction.
2. Securely fasten the access panel.
3. Plug one end of the provided power cord into the
receptacle on the cabinet and the other end into a power
receptacle.
4. Look through the view port in the access panel to check
that the UVA lamp is illuminated.
NOTE: On initial start-up, the UVA lamp may not reach full
illumination for several minutes.
Figure 8. Brass Finger and Wing Nuts
installing UVa lampholDer
Use the following procedure to install the UVA Lampholder
/ PCO cartridge.
1. While aligning, slide the UVA Lampholder / PCO
cartridge into case rails and align with rear mounting
bracket.
2. Secure the UVA Lampholder / PCO cartridge to the two
frame screw posts using the provided wing nuts (2).
Figure 10. Communicating and Low Voltage Connections
commUnication Wiring
Communicating systems requires four thermostat wires
between the PureAir S and the Lennox Communicating
Indoor Control. When a thermostat cable with more
than four wires is used, the extra wires must be properly
connected to avoid electrical noise. The wires must not be
left disconnected. See “Figure 10. Communicating and Low
Voltage Connections”.
• Use wire nuts to bundle the unused wires at each end of
the cable. A single wire should then be connected to the
indoor unit end of the wire bundle and attached to the “C”
terminals.
• Keep all communication wiring as far away from the
house electrical wiring and large electrical appliances as
possible. Recommended minimal distance is 15 feet (5
meters).
commUnication Wiring roUting
Communication wiring to the indoor unit is routed through
the opening in the top of the cabinet as illustrated below.
Route communication wiring through
grommet to indoor unit
pUreairS internal factory Wiring
The should be wired in accordance with national and local
codes.
iComfort Communicating
PCO Control
Figure 11. Routing of Communication Wiring
Figure 12. PCO Wiring Schematic
9
Page 10
Communicating Control Functions
14-16
Jumper Setting
16-16
20-16
Jumper
pco moDel (h2) JUmpers
A series of jumpers is used to select which size pure air the
control is installed.
Jumper selections are:
• Position 1 (pins 1 and 2 shorted): 14-16 (nominal airow
= 1400cfm)
• Position 2 (pins 2 and 3 shorted): 16-16 (nominal airow
= 1600cfm)
• Position 3 (pins 3 and 4 shorted): 20-16 (nominal airow
= 2000cfm)
NOTE: The correct size selection should already be set
from the factory.
Jumper Setting
Jumper Setting
Figure 13. Model Jumper Selection
change lamp reset (sW1)
After bulb replacement, press and hold for three seconds
SW1 - Change Lamp button. This resets the system.
A LED will start to ash after three seconds to indicate the
reset was successful.
change filter reset (sW2)
After air lter replacement, press and hold for three seconds
SW2 - Change Filter. This resets the system.
A LED will start to ash after three seconds to indicate the
reset was successful.
Figure 14. PureAir S Communicating Control
control manUal reset
When pressing both the SW1 and SW2 switches at the
same time for ten seconds will reset the control to factory
default.
Control can also be reset by using the S30 thermostat. Go
to menu > settings > advanced settings > view dealer
control center > equipment > reset > reset HVAC
equipment.
Lennox S30 Thermostat Setup
system setUp (commissioning)
During the initial or rerunning the commissioning of the
system using the iComfort S30 Ultra Smart thermostat, the
system will auto-detect the presence of the PureAirS unit.
Follow the instructions provided with the thermostat for the
system commissioning process. If the PureAir S component
is successfully detected, it will appear on the found
equipment screen.
welcome to iComfort
10
system
Smart Hub
Air Handler
CBX40UHV-060; 1
equipment found
non-communicating
+/-
equipment
Heat Pump
XP25-060-230
Thermostat
104553-01
previouscontinue
PureAir
PCO3S16-16
Mag-Mount
1045498-01
Figure 15. Equipment Found
Page 11
reminDers
disabled
Please verify or modify reminder settings.
done
PureAir maintenance
calendar time
sensor-based
run-time
aDDing pUreairS to existing system
Default setting is sensor-based. Additional options are
calendar time, run-time or disabled. On the reminder screen,
select PureAirS maintenance to change the option.
Once the PureAir S accessory has been installed and
system powered up, go to the thermostat. From the
thermostat to go to menu > settings > advanced settings
> view dealer control center > equipment and select reset. From the reset list, select re-congure system. This
will tell the system to reboot and search for new equipment
attached to the system.
Follow the commissioning screens to the equipment
found screen, verify that the PureAir S accessory has
been detected and added to the system (see “Figure 15.
Equipment Found” on page 10).
NOTE: The Lennox S30 thermostat must have rmware
version 3.4 or later for compatibility with Lennox
Pure Air S Air Purication System.
Figure 16. PureAir S Maintenance Setting
Dealer Control Center
The Dealer Control Center menu provides access for the installer or service technician to perform various functions.
Advance equipment congurations, notications, tests, diagnostics, installation reports and general information about the
system. Go to menu > settings > advanced settings > view dealer control center.
<
“Previous Screen
<
Name”
Use to make changes to equipment settings and add or remove
non-communicating equipment or accessories. In addition the reset all
equipment option is available. This will allow the installer to reset all
To navigate back to the dealer control center,
touch on the Dave Lennox icon when available
on the top left-hand side of the screen.
To navigate back to the previous screen, touch
on the left arrow when available.
system notifications
equipment and reconfigure.
Use to display
Use to run test on
system components
notifications
tests
diagnostics
Use to run
diagnostics on
system components
dealer
control center
equipment
exit
Exit to Home
screen.
Figure 17. Dealer Control Center
installation
report
information
Used to display installation results.
NOTE: This report is not available until after
exiting the dealer control center following the
commissioning procedure. Exit and return to
the dealer control center to view the installation
report.
Use to display
system information
11
Page 12
pUreairS eqUipment parameters
The following is a complete list of all possible parameters listed under System. Parameters actually available are dependent
on the Lennox communicating equipment type detected and non-communicating equipment added.
From the Dealer Control Center Screen, go to equipment > PureAir. There you will nd the applicable parameter settings
for PureAir S.
Table 1. PureAir S Parameters
ParameterDescription
EquipmentPureAir Filter
Default: ON. Options are either ON or OFF. Alarms 503 and 504 will not be displayed when this parameter is set to OFF.
The diagnostics screen on the thermostat will continue to show values for both lter life and UV lamp life regardless of
the value of this parameter.
Dirty Filter and UV
Life Detection
Max Air Filtered
between Tests
UV lamp operation
detection
Filter LifeProvides percentage of remaining lter life. This is for display purposes only and cannot be changed.
Last replacement
date for lter
Purier life
Last replacement date
for purier insert
• reset PureAir S will reset all PureAir S parameters back to factory defaults.
• reset purier insert will reset it to 100%. This is usually accomplished after the UVA Lamp / PCO cartridge insert has been replaced.
• reset lter will reset it to 100%. This is usually accomplished after the air lter has been replaced.
This parameter turns on and off the lter life and UV lamp life reporting. When set to off, the control will continue to
calculate the remaining lter life through continuous sampling, but will not use lter tests to determine lter life. The
control will:
• Perform a lter calibration upon indication of a lter change regardless of the value of this parameter.
• Perform a UV lamp calibration upon indication of a lamp change regardless of the value of this parameter.
• Will calculate UV lamp life remaining regardless of the value of this parameter.
Default is 100%, Range is 50% to 100% Changes can be made in increments of 10%.
This parameter modies the amount of air that is allowed to pass through the lter after a valid % life determination
before a lter test is initiated.
This parameter is expressed as a percentage of the cubic feet of air that would pass through the lter if the fan operated
at continuous fan CFM for 30 days.
Default: ON. Options are either ON or OFF.
Date last lter reset was accomplished. This is for display purposes only and cannot be changed
Provides percentage of remaining purier life. This is for display purposes only and cannot be changed
NOTE: Purier life is referring to the UVA Lamp / PCO cartridge insert.
Date last purier insert reset was accomplished. This is for display purposes only and cannot be changed
notifications (alert coDes)
The thermostat’s notication screens provide information
on active notications and previously cleared notications.
When selecting either a cleared or active notication a brief
description and alert code will be displayed. Notications are
categorized by system, indoor unit (air handler or furnace),
outdoor unit (air conditioner or heat pump), zoning control (if
installed) and thermostat.
testsanD Diagnostics fUnction
There are no installer tests or diagnostic features available
for the PureAir S accessory.
installation report
PureAir S accessory information includes equipment name,
model number, serial number and rmware version.
In addition, when selecting PureAir S, lter life, last
replacement date for lter and purier life and last
replacement date for purier information is available.
3/15/2017
3/15/2017
Overview
System
Air Conditioner
Furnace
PureAir
installation report
filter life100%
last replacement date for filter
purifier life100%
last replacement date for purifier3/15/2017
Figure 18. Installation Report
Alert Codes
soft Disable
Soft disabling is when the thermostat nds an unknown
control on the system communication bus. The thermostat
sends the unknown control a message to go into soft
12
Page 13
disable mode until the component is properly congured
or removed.
The thermostat will not show any code for a soft disabled
control. When soft disabling occurs only the control that
has been disabled will display the blinking LED status.
Refer to the device’s installation and setup guide for
further guidance.
Conrm proper wiring between all devices such as
thermostat, PureAirS and Smart Hub.
Cycle power to the PureAir S.
1. Go to the menu > settings > advanced settings
> view dealer control center. Touch proceed to
continue.
2. Select equipment.
3. Touch reset.
alert coDe types
To expand a specication notication to access a more
detail description of the alert code, press the down arrow
to expand the description.
Critical alerts are displayed on Home (user) screen, in the
Homeowner alert button, and in the Installer alert button.
Critical means that a service call is needed to get the
system running.
Minor and Moderate alerts are found only in the Installer
alert button.
What does minor and moderate mean?
• Minor is information only, helps Lennox interpret
test results, understand complicated behavior.
• Moderate means that the system will likely recover
on its own, no action necessary.
• Communication System: When communication
controls are operating in a communication system,
all jumper and link setting on controls are ignored.
Jumpers and link setting are treated as defaults and
would only be active if the system was converted to
a non-communicating system.
Table 4. PureAir S Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found
only under the notication menu.
Alert
Code
105Moderate
120Moderate
124Critical
125Critical
Priority
Condition
Actual
Displayed
Alert Text
Communication
Problem
Unresponsive
DEVICE2.
Active Subnet
Controller
Missing
Control
Hardware
Problem
Component or System Operational State and Troubleshooting TipHow to clear alert code
A system component has lost communication with the system. System
component (device) is unable to communicate.
This may indicate the existence of other active alert codes.
TIPS:
• In most cases errors are related to electrical noise. Verify that high voltage
power is separated from the low voltage communication wires.
• Check for incorrectly wired or loose connections between system
components (devices).
• Check for a high voltage source of noise close to the system.
There is a delay in the system component responding to the system.
TIPS:
• Typically this alert code does not cause any operational issues and will
clear on its own.
• Usually caused by a delay in the outdoor unit responding to the
thermostat.
• Check all wiring connections.
The thermostat has lost communication with a system component for more
than three minutes.
This alert code stops all associated system operations and waits for a
heartbeat message from the system component that is not communicating.
TIPS:
• Check the wiring connections.
> Ohm wires.
> Cycle power.
> Check voltage at component.
There is a hardware problem with a system component control.
TIPS:
• PCO3 jumper selector is missing.
• Replace the PCO3S control if the problem prevents operation and is
persistent.
Automatically clears
when the system detects
the issue no longer
exists.
Automatically clears after
an unresponsive system
component (device)
responds to any inquiry.
Automatically clears
after communication
is re-established with
applicable system
component (device).
Automatically clears ve
minutes after the issue
no longer exists.
13
Page 14
Table 4. PureAir S Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found
only under the notication menu.
Alert
Code
131Critical
132Critical
500
501
502CriticalUVA Lamp Off
504CriticalFilter Life at 0%
505Moderate
506Critical
Priority
Condition
Minor
(Escalated
to Critical
after alarm
persists for
15 minutes)
Minor
(Escalated
to Critical
after alarm
persists for
15 minutes)
Actual
Displayed
Alert Text
Corrupted
Control
Parameters
Failed Flash
CRC Check
Diff Press
Sensor Fault
UVA Sensor
Fault
PureAir Model
Selection
Changed
UVA Lamp Life
at 0%
Component or System Operational State and Troubleshooting TipHow to clear alert code
System component control parameters are corrupted.
TIPS:
• Go to menu > advance settings > view dealer control center >
equipment and press reset all equipment. This will allow the system to
auto-detect the PCO3S control.
• Replace the PCO3S control.
PCO3S control software is corrupted.
TIPS:
• Recycle power.
• If failure re-occurs, replace the system component control.
Pressure sensor reports a fault for more than ve minutes, or does not
respond for more ve 5 minutes. Device will not perform any pressure
reading calculations until fault is recovered. Remaining lter life display will
indicate “-“ while fault exists.
TIPS:
• Verify connection of pressure sensor lines to PCO3S control.
• Replace pressure sensor.
UVA sensor reports a fault for more than ve minutes or UV sensor does not
respond for more than ve minutes.
Device will not perform any UV lamp life remaining calculations until fault has
recovered. Life remaining display shall indicate “-“ while fault exists.
TIPS:
• Verify that the wiring connections between the UV sensor control and main
PCO3S control are good.
• Replace UVA sensor control.
The light is determined to be off when the last three last light intensities
measurements are below the set threshold.
TIPS:
• Verify UVA light is installed correctly.
• Replace UVA light.
Filter life at 0%.
TIPS:
Replace air ler and reset. Go to menu > settings > advanced settings >
viewdealer control center > equipment > PureAir S and select reset lter
at bottom of the screen.
Model selection jumper has changed positions while system was running.
TIPS:
Repositioned jumper back to original jumper position and cycle power to the
PCO3S and S30 system.
UV Lamp Life at 0%.
TIPS:
Replace UVA lamp and reset. Go to menu > settings > advanced settings >
view dealer control center > equipment > PureAir S and select reset puri-
er at bottom of the screen.
Will automatically clear
when system component
(device) passes memory
self-test or system
component control is
replaced.
Manual system power
reset is required to
recover from this alert
code.
Automatically clears 30
seconds after fault is
recovered.
Automatically clears 30
seconds after fault is
recovered.
Light is determined on
after single set of ve
samples are above the
set threshold.
Replace air lter and
reset to 100%.
Correct issue and cycle
power to system.
Replace UVA lamp and
reset to 100%.
Operation
1. Check to ensure that access panel is securely in place.
2. Lamp should remain illuminated continuously except
during service and maintenance.
3. For optimal odor control, air handler blower should
remain on CONTINUOUSLY (thermostat fan setting in
ON position, rather than AUTO).
NOTE: If air handler does not provide a continuous low
blower speed option, an additional blower relay
should be installed. Use Lennox part number
45H03. Contact the Lennox Application Department
at 1-800-453-6669 for wiring information.
NOTE: Continuous fan operation may result in higher
humidity. If humidity levels are uncomfortably high,
fan setting should be switched to AUTO during
cooling operation.
14
Page 15
Filter, UVA Lampholder / PCO Cartridge and
UVA Lamp Replacement
remoVinganD installing UVa lamp, lampholDeranD
air filter
IMPORTANT
Hg -- UVA Lamp contain mercury.
Manage in accord with disposal laws.
Refer to www.lamprecycle.org or call 1-800-9LENNOX.
The Healthy Climate® Carbon Clean 16® Filter, UVA
Lampholder / PCO cartridge and UVA lamp require annual
replacement. More frequent lter replacement may be
required in applications with heavier dust or dirt loads or if
you notice a reduction in odor-removal efciency. An annual
maintenance kit is available.
Annual Maintenance Kits
The annual maintenance kits include the following:
• Healthy Climate® Carbon Clean 16® Filter (1)
• PCO cartridge (1)
• UVA lamp (1)
Order using the following kit catalog numbers:
Table 5. Maintenance Kits
Part
Description
Annual
Maintenance
Kit
PCO3S-14-16PCO3S-16-16PCO3S-20-16
Y6616Y6612Y6608
Replacement Parts
Replacement parts are available through Lennox, see
“Figure 1. Parts Identication” on page 3 for parts
arrangement. Part description and catalog numbers are as
follows:
Table 6. Repair Parts
Part Description
HC Carbon Clean
16 Filter
UVA LampX8794
PCO cartridge
insert (Purier)
Lampholder
Assembly
Power Cord
(120VAC)
Power Cord
(230VAC)
Electrical Socket75X77
BallastY6620
Probe Repair Kit16X0116X0216X01
Sensor Repair Kit16X03
PCO3S-14-16 PCO3S-16-16PCO3S-20-16
Y6606Y6605Y6604
Y6621Y6607
Catalog Numbers
Catalog Numbers
Y6622
49M48
91X44
IMPORTANT
If the system has been operated for a period of time
without the UVA lamp being illuminated, an odor may
occur when lamp is illuminated. This odor is considered
typical and should dissipate within 12 hours of full
operation. If the odor does not subside after 48 hours
of operation, instruct the homeowner to unplug the unit
and contact a Lennox dealer.
CAUTION
Personal Burn Hazard.
UVA lamp is very hot when illuminated.
Allow lamp to cool for 10 minutes before removing lamp
from socket.
Injury may result from contact with hot UVA lamp.
1. Remove power cord from 120VAC or 230VAC receptacle.
6. Disconnect UVA lamp electrical connector from ballast.
7. Remove both fasteners securing the UVA Lampholder /
PCO cartridge from the chassis.
8. Slide out the UVA Lampholder / PCO cartridge from the
chassis.
9. Remove both brass nger nuts that secure the UVA
lamp elector connector to the UVA Lampholder / PCO
cartridge.
10. Slide out UVA lamp from UVA Lampholder / PCO
cartridge insert.
11. Push the red button on UVA lamp electrical connector
and gently slide off connector from UVA lamp (do not
dispose of UVA lamp electrical connector).
12. Properly dispose of UVA lamp and air lter.
13. Reinstall in reverse order starting.
15
Page 16
proper clean-Upof broken UVa lamp
START
Look through the access panel
viewing port to check lamp.
Is there power to the
PCO?
Is the lamp on?NO
Check PCO power cord for
damage and AC outlet for
power. Check breaker
panel. Repair electrical
problem and plug−in power
cord.
Is the lamp on?
Unplug power cord to
the PCO cabinet.
YES
Check lamp
electrical
connectors. Also check
electrical wiring from ballast
to lamp connector.
Any issues?
Plug power cord back
to the PCO cabinet.
N
O
Repair Issues
Is the lamp on?
Check ballast voltages (see
table below) on red and blue
wires at 4−pin connector.
Replace any burned out or
damaged components.
NO
Is the lamp on?
NO
Continue with
maintenance per unit
installation instruction.
YES
YES
YES
NO
Is PCO power cord plugged
into AC outlet? If not, plug
PCO cord into AC Outlet.
Is the lamp on?
NO
YES
NO
YES
YES
If UVA lamp is broken, it must be disposed of properly.
• Wear protective gloves, eye wear and mask.
Troubleshooting Flow Chart
• Sweep broken glass and debris into a plastic bag and
seal before disposal in accordance with instructions
provided by local waste management ofce.
• Do not use a vacuum cleaner. Do not incinerate.
BALLAST
INPUT/OUTPUTWIRE/TERM COLORNORMAL READING (VAC)
OUTPUT
RED>60
RED>60
BLUE>200
BLUE>200
Figure 19. Troubleshooting Flowchart
SERVICE ACTION (See “Figure 12. PCO
Wiring Schematic” on page 9.)
Replace ballast if less than 60VAC.
Replace ballast if less than 200VAC.
16
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.