EPA Wood-Burning Fireplace
P/N 850,038M REV. B 02/2007
MODEL
MONTEST
This installation manual will enable you to obtain a safe, efficient and dependable installation of your fireplace system. Please read and understand
these instructions before beginning your installation.
Do not alter or modify the fireplace or its components under any circumstances. Any modification or alteration of the fireplace system, including
but not limited to the fireplace, chimney components and accessories,
may void the warranty, listings and approvals of this system and could
result in an unsafe and potentially dangerous installation.
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNINGS
• Hot! Do not touch! The glass and
surfaces of this appliance will be hot
during operation and will retain heat
for a while after shutting off the appliance. Severe burns may result.
• Carefully supervise children in the
same room as appliance.
• If small children are present in the home, it
is recommended that this appliance be fitted
with a Firescreen kit. See Page 20 for ordering
information.
• The fireplace cannot be operated without a door.
Consult your dealer to select the correct door
model.
• Important! To assure proper alignment of glass
doors: Install this fireplace in a square and
plumb condition, using shims as necessary at
sides and/or bottom.
• Install the fireplace only as described in these
instructions.
PIMONTEST REV. 1
IMPORTANT! GENERAL SAFETY
PRE CAUT IONS . REA D AND
UNDERSTAND THESE SAFETY
RULES BEFORE YOUR FIRST FIRE.
WARNING
Never leave children unattended
when there is a fire burning in
the fireplace.
IMPORTANT
When burning wood, use SOLID
NATURAL DRY WELL-SEASONED
WOOD ONLY. Hardwoods are
recommended (soft woods tend
to burn very quickly).
• DO NOT burn treated wood,
charcoal, coal, trash, cardboard, driftwood, woods dipped
in tar, Christmas tree greens,
pitch, pine tar, creosote, chemical chimney cleaners, flame
colorants, polystyrene packaging, wood products with synthetic binders (i.e. plywood).
Plywood, lumber and other misc.
materials can produce abnormally high temperatures, sputtering and smoking fires and may
contain hazardous chemicals to
treat insects and fungus.
• Burning unapproved fuels can
produce excessive temperatures, beyond the design capabilities of the fireplace and may
produce excess sparks or may
contain hazardous chemicals.
Burning unapproved fuels can
result in a chimney fire, a house
fire, personal injury, death or
loss of property.
Never leave your fireplace unattended while it is burning.
WARNING
WARNING
To avoid the risk of damaging
fireplace materials and increasing the risk of fire, do not use the
fireplace to cook or warm food.
WARNING
NEVER use gasoline, gasolinetype lantern fuel, kerosene,
charcoal lighter fluid, naphtha,
engine oil or similar liquids to
start or “freshen up” a fire in this
fireplace. Keep any flammable
liquids a safe distance from the
fireplace at all times.
WARNING
The fireplace must be operated
with the doors fully opened or
fully closed. If the doors are
left partly opened, smoke may
be drawn into the room. Use
optional firescreen when doors
are fully opened.
WARNING
Use care when selecting window
treatments for windows located
near the fireplace. Avoid using
combustible flowing window
treatments such as curtains
on nearby windows that are of
sufficient length to be blown in
front of an open flame when the
window is opened.
Keep any combustible furniture,
materials or decorative pillows
at least 48" (1219 mm) from the
front fireplace opening.
WARNING
This fireplace has NOT been
tested with an unvented or vented
gas log set. To reduce risk of fire
or injury, do not install a gas log
set into this fireplace.
WARNING
Be careful adding wood fuel to the
fire or handling fireplace tools such
as shovels, tongs or pokers.
WARNING
Never modify or alter your fireplace system in any way. To do
so may create a potential fire
hazard and void the Limited
Warranty.
WARNING
The bottom refractory can be
cracked by excessive abuse such
as tossing heavy logs onto the
grate or gouging with fireplace
tools. Exercise caution when
adding wood to your fireplace.
WARNING
Neither the manufacturer nor the
seller warrants “smoke free”
operation nor are we responsible
for inadequate system draft
caused by mechanical systems,
general construction conditions,
inadequate chimney heights,
adverse wind conditions and/or
unusual environmental factors or
conditions beyond our control.
Always ensure that the air inlet to
the fireplace is free from debris
and any other obstructions that
can block the entrance of air.
The Montecito Estate™ must be
installed with an outside air kit,
which is included with fireplace.
WARNING
WARNING
2
CONGRATULATIONS!
In selecting this LENNOX wood-burning appliance you have chosen one of the finest
fireplaces available. The Montecito Estate™ is a clean burning EPA certified fireplace
that is designed to provide you dependable service as well as warmth and enjoyment
for many years to come.
Please carefully read and follow all of the instructions found in this manual. Please pay
special attention to the safety instructions provided in this manual. This information
will be useful to you now and in years to come, so keep the manual handy and refer to
it as needed.
The Montecito Estate wood-burning fireplace
is an energy efficient, heat circulating, closed
combustion fireplace. You will receive a lifetime
of comfort and enjoyment from your fireplace
provided it is installed, maintained and operated properly.
• Please read these instructions and retain
this manual for future reference.
• Before beginning the fireplace installation,
consult the local authorities to obtain your
building permit and check your local building
codes. Install the fireplace only as described
in these instructions and using only Lennox
Hearth Products components.
• The Montecito Estate is not intended for use
with a gas log set. Do not use a fireplace
insert or any other product with this fireplace
unless it is specified by Lennox for use
with this appliance. Failure to follow these
instructions will void the certification and the
warranty of the fireplace and may result in
an unsafe installation.
• These appliances are designed to provide
supplemental heat to the immediate area only.
Therefore, it is advisable to have an alternate
heat source when installed in a dwelling.
• These appliances are not approved for
Manufactured Home installations.
PARTS REQUIRED
Fireplace model: MONTEST
• 7” diameter chimney - Model Secure Temp
S-2100+, Nova Temp HT6000+, Secure
Temp GX (U.S. only) or ACBI manufactured
by Security Chimneys International only,
including:
- Chimney lengths
- Elbows (where necessary)
- Associated components as per these
installation instructions
• ..Decorative Doors - Required
....(Order Separately - See Page 20)
• Front Facade kit - Required
...(Order Separately - See Page 20)
• UZY5 Blower (included in the fireplace).
• VRUW Blower Speed Control (included)
• Outside air kit (Included w/Fireplace)
OPTIONAL EQUIPMENT
- AC Chimney Adaptor
(required if using AC Chimney)
- AC Chimney Outside Air Kit
- Gravity Venting System
- Rigid Firescreen
OPTIONAL EQUIPMENT
Additional Equipment (optional)
- Gravity Venting System
- TUBINOX chimney (or PROJET SS), 7”
diameter with adaptor for installation in a
masonry chimney.
OPERATING THE MONTECITO ESTATE
Fuel - USE SOLID NATURAL WOOD FUEL
ONLY. The Montecito Estate is designed to
work best when fueled with dry seasoned
natural wood only. Hardwoods are preferred
to softwoods since the energy content of
wood is relative to its density. Hardwoods will
result in a longer burning fire and less frequent
refueling. A moisture content of 15% to 20%
(seasoned) is recommended. Wood that has
been cut and split and let to dry under a cover
for a period of one year will usually meet that
criteria. Excessively wet wood will be difficult
to burn and will result in lower efficiency, increased creosoting and deposits on the glass
and in the chimney. Excessively dry wood will
burn well but will also have higher emissions
and shorter burning time.
Do not burn scrap or garbage, treated wood or
wood such as driftwood from the ocean which
has been exposed to salt or other chemicals.
Salt or chemicals can corrode the firebox and
chimney. Do not burn large amounts of paper,
cardboard, Christmas tree branches or building construction materials. Intense firing with
these materials may overheat the fireplace,
causing damage to the unit, a fire or even
possibly igniting a chimney fire if the chimney
is creosoted.
First Fires
Before using the fireplace make sure to remove the plastic wrapping and EPA label on
the door. Remove any glue residue left by the
label using mild soap.
Make sure the doors are properly adjusted,
thus avoiding color change to finish due to
overheating.
The first five or six fires should be small fires
of short duration (about 30 to 60 minutes).
This will help cure the refractory bricks. The
first fires may produce slight smoking and
some odor due to curing of the paint and steel
and the burning of any dust accumulated on
the fireplace which will burn off at this time. It
may set off a smoke alarm located in the same
room. For this reason the room should be well
ventilated for the first few fires.
HEAT OUTPUT
The Montecito Estate is the largest member of
the “Dave Lennox Signature Collection” of high
efficiency fireplaces. The heat generated from its
fire is more efficiently captured and distributed.
In spite of the large amount of heat that the
Montecito Estate can deliver, it should not replace
the main source of heat in your home. This
fireplace will bring extra warmth and ambiance
to your home by distributing its heat as describe
further in the manual.
3
Cl
o
se
d
C
losed
Ope
n
Ope
n
COMBUSTION CONTROLS
Primary Air & Air Boost Controls
There is no flue damper in the Montecito Estate™. As is common with air tight appliance,
the combustion air control sets the flow of air
entering the firebox. This allows for a more
precise control of the fire. The combustion air
control is located below the door on the left side.
The main source of air (primary air) entering
the firebox can be diminished by moving the
air combustion control from left to right. The
primary air is fully opened when the air control
is completely moved to the left. This air combustion control should be in the closed position
when the fireplace is not in operation. This will
minimize air leakage up the chimney.
The combustion air control should be opened
before opening the doors to minimize the possibility of back draft coming into the room (Figure
1-A) More details are available in Refueling For
Best Performance on Page 5.
Time Delayed Air Boost System
The time delayed air-boost system register is
located underneath the door handles. Placed
in the fully opened position, a timer with a
maximum duration of 2 hours is engaged. The
register gradually reduces the amount of air
injected, allowing for a better start of the fire,
whatever the conditions (See sections Building a Fire and Refueling For Best Performance for
proper sequence of operation). This allows
you to start the fire, set the primary air control
to the desired burn level and the fireplace will
automatically adjust itself to that level once the
fire is fully established (Figure 1-B).
Accelerated Combustion
The maximum heat output for the Montecito
Estate is achieved by burning with the door
closed and the combustion air opened and
pulled out. Through this method, the Montecito
Estate can produce up to 80,000 BTU of heat
per hour.
However, it will be necessary to reload with wood
every one or two hours. This is the least efficient
method of burning the Montecito Estate .
Use caution when firing with the combustion
air control wide open. Only burn cord wood in
this manner. Small dry pieces of softwood and
construction scraps will burn very intensely using this method and may damage the firebox.
Figure 1
Combustion Air
Register
(A)
Time Delay
Air-Boost Control
(T.D.A.B.)
Figure 2 -
Accelerated Combustion
Medium Combustion
This is the recommended mode of operating
the Montecito Estate and should be the one
normally used since it will deposit the least
amount of creosote on the glass and in the
chimney. The combustion air control must be
3/4 closed. The precise setting will depend on
(B)
many factors, including chimney length and the
moisture content of the wood.
For instance, a long chimney will necessitate
closing the damper more. To obtain the proper
combustion, close the damper completely, then
open it about 1/4” to 1/2”. Three medium size
pieces of cord wood-burning on a bed of hot
coals will generate an approximate heat output
will of 35,000 BTU per hour and the loading time
will be about every 3-4 hours. Softwoods may
be burned using this method but the combustion
time will be substantially reduced.
4
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Figure 3 - Medium Combustion
Slow Combustion
When the air combustion control is completely
closed, the fireplace is in a slow combustion
phase. If the hearth is hot enough, slow combustion will not extinguish the fire, but there
will be a noticeable change in the flame pattern.
The flames will be slow and may appear dirty
if the wood is too wet (moisture content of
20% and more).
The unit will burn best with 2-3 pieces of cord
wood spaced 1 to 2 inches apart and allowing
air to get under the fuel. Criss-crossing or arranging the fuel so that air can get underneath
will help the fire to get started easily. The unit
should be operated with the air control fully
open long enough to get the cord wood well
ignited.
REFUELING FOR BEST PERFORMANCE
As the fire burns, air goes up the chimney. This
air must be replaced through the outside air duct.
When operating the Montecito Estate, open a
nearby window temporarily to check if there is
adequate air supply replacement. Occasionally,
there may be a small amount of smoking upon
lighting the fire, until the chimney heats up but
this should not last. If the fireplace continues
to smoke it is probably for one of the following reasons:
Do not allow the wood to burn without flame,
since this will produce excessive creosote in
the unit. Creosote may accumulate on the glass
door. This method of burning should be used
only after operating the Montecito Estate™ with
the air control opened to produce a hot fire for
about an hour or at medium pace for at least
three (3) hours. Slow combustion can be used
at night in order to reduce the heat output and
to prolong the burn. The loading time will be
between 6-8 hours and at this combustion rate,
the level of BTU’s is at its lowest.
Figure 4 - Slow Combustion
Building a Fire
A) To start a fire, place several crumpled up
balls of newspaper in the firebox. Place small
dry pieces of kindling on top of the paper,
criss-crossing the kindling so that there are
air spaces in between. The kindling should
be placed at the center of the firebox so as
to allow for sufficient air circulation.
B) Adjust the primary air control and start the
time delayed air-boost system by pushing
the register towards the right. Light the
newspaper. Leave the doors partially opened
to facilitate the start-up.
C) Once kindling fire is well established, cord
wood can be added. You may set the primary
air control to the desire level (see Primary
Air Combustion Control and Air Boost Controls section for proper operation of the air
controls).
D) Set the primary control to the desired burn
level. The fireplace will automatically go to
that level after the fire is fully established
and the air boost is closed.
To reload the Montecito Estate at the end of a
combustion cycle, when no flame is visible and
there are only ashes left:
A) Completely open the air control level and
the T.D.A.B. (Time Delay Air Boost) level.
See Figure 1.
B) Open the doors about 1” and wait 5 seconds
until the air flow has stabilized. Then open
the doors completely, put the logs in and
close the doors.
C) Set the air control to the desired burn level.
The T.D.A.B will close by itself progressively.
To reload the Montecito Estate when the fireplace
is still hot with a few visible flames:
A) Open the air control completely. The T.D.A.B
can be set to a lower setting in order to
facilitate lighting.
B) Open the doors about 1” and wait 5 seconds
until the air flow has stabilized. Then open
the doors completely, put the logs in and
close the doors.
C) Set the air control to the desired burn
level.
Notes:
• For spectacular fire and optimization of the
fireplace efficiency, we recommend that the
wood load be placed as far back as possible.
• It may be necessary to turn off any blower(s)
in operation during the refueling process in
order to minimise smoking in the room. It
is recommended to wait 15 to 30 minutes
before turning the blower(s) back on to
ensure successful rekindling.
SMOKING –
CAUSES AND TROUBLESHOOTING
To reduce the likelihood of smoke coming
into the room when opening the door, set the
combustion air controls to the left (“Accelerated Combustion”) before opening the door.
Your fireplace has been designed and tested
to provide smoke free operation.
A. The doors are partially opened
When you open the doors, open them com
pletely.
B. Negative pressure in the house
C. Fans operating (e.g.: range hood)
These fans draw air out of the house and
may actually cause a negative pressure in the
house. Turn off all fans and open a nearby
window to determine if this is the cause of
the problem.
D. Wet wood
Wet or tarred wood will smoulder and smoke
instead of burn properly.
E. Dirty or blocked chimney
Check to make sure the chimney is clear and
clean.
F. Chimney not long enough
The minimum chimney height is 12 feet not
including the fireplace height. The chimney
must extend at least three (3) feet (915 mm)
above its point of contact with the roof and
at least two (2) feet (610 mm) higher than
any roof or wall within ten (10) feet (3 m)
of it. When installed with offsets, the minimum chimney height is 15 feet. Additional
height will increase draft and will decrease
the tendency to smoke.
G. Poor chimney draft
With no fire, there should be sufficient draft
to exhaust cigarette smoke introduced under
the baffle. Chimneys installed against an
outside wall without protection may generate back draft problems which will cause
start-up problems. To prevent this, open
a nearby window; roll up a piece of paper,
light it and hold it in the upper part of the
firebox to warm up the chimney. Wait until
the draft is sufficient, then start the fire.
-
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
5
IMPORTANT CAUTIONS
A. Do not block the hot air vents to the fire-
place as this will cause the fireplace to
overheat.
B. Never use gasoline, kerosene, charcoal
lighter fluid or similar liquids to start or
rekindle a fire in this fireplace. Keep all
such liquids well away from the fireplace
at all times.
C. Do not burn coal. The sulphur in coal will
corrode the firebox.
D. Do not burn driftwood which has been in the
ocean or salt water. The salt will corrode
the firebox and chimney.
E. Do not burn wood in the area in front of the
grate.
F. Do not abuse the unit by burning paper, or
cardboard or construction material such as
pressed wood, plywood or lumber. Wood
protectors, metallic paper, coal, plastic,
waste, sulphur and/or oil will damage the
fireplace.
G. Do not allow the wood to smoulder or burn
without flame, since this will produce
excessive creosote in the unit.
MAINTAINING YOUR MONTECITO
ESTATE
Creosote
When wood is burned slowly without a flame,
it produces tar and other organic vapors which
combine with expelled moisture to form a black
deposit called creosote which accumulates on
the flue lining. When ignited, this creosote
makes an extremely hot fire. If the creosote
accumulation is large, a creosote fire in the
chimney can damage the chimney and overheat the surrounding wood framing. Creosote
formation in a chimney can be minimized
by making sure there is always visible flame
burning, avoid smoldering fires and by proper
refueling techniques.
Chimney Maintenance
Regular chimney inspection and maintenance
combined with proper operation will prevent
chimney fires. Keep your chimney clean. Do
not allow more than 1/16” creosote build up
in your chimney. The amount of creosote will
depend on variables such as frequency of use
and type of fire. We recommend that you:
A. Initially inspect the chimney system weekly.
From this, you will learn how often it will be
necessary to clean your chimney.
B. Have your chimney cleaned by a qualified
chimney sweep. If you wish to clean it
yourself, we recommend using a stiff plastic
or non-metallic brush. If a metal brush is
used, its size should be slightly smaller than
the flue to avoid damaging the chimney. Do
not use a brush that will scratch the stainless
steel interior of the chimney.
C. Do not expect chemical cleaners to keep
your chimney clean. The rain cap can be
removed for inspection and/or cleaning of
the chimney.
Dealing With a Chimney Fire
Regular chimney maintenance and inspection
can prevent chimney fires. If you have a chimney
fire, follow these steps:
1.
IMPORTANT: Close the fireplace door and
the combustion air controls; this will stifle
the fire.
2. Alert your family of the possible danger.
3. If you require assistance, alert your fire
department.
4. If possible, use a dry chemical fire extin
guisher, baking soda or sand to control the
fire. Do not use water as it may cause a
dangerous steam explosion.
5. Ensure that sparks and hot embers com
ing out of the chimney are not igniting the
roof.
6. Do not use the fireplace again until your
chimney and fireplace have been inspected
by a qualified chimney sweep or a fire department inspector.
REFRACTORY REPLACEMENT
The intense heat of the fire will normally cause
hairline cracks in the refractory brick. These
cracks can be minimized by proper curing as
described in section First Fires. They will not
normally diminish the effectiveness of the
refractory brick. If large cracks develop, then
the refractory should be replaced. To replace
the refractory bricks, follow these steps:
6
5
Figure 5
DOOR FRAME FINISH CARE
Use a glass cleaner and a soft cloth to polish
the casing. Do not use abrasives such as steel
wool, steel pads or an abrasive polish for they
may scratch the frame’s finish.
DISPOSING OF ASHES
Remove ashes only when the fire is out and
the ashes are cold (24 to 48 hours after the
fire is out).
WARNING
When cleaning the fireplace,
the ashes should be placed in
a metal container with a tight
fitting lid. The closed container
-
of ashes should be placed on a
non-combustible floor or on the
ground outside the house, pend-
-
ing final disposal. If the ashes
are disposed of by burial in soil
or otherwise locally dispersed,
they should be retained in the
closed container until all cinders
have thoroughly cooled.
1. Remove the side refractory brackets (6)
2. Remove the front refractory bricks (3)
3. Remove the bottom refractory brick (4)
4. Remove the left side refractory bricks (5)
5. Remove the right side refractory bricks (2)
6. Remove the back refractory brick (1)
7. Remove the deflectors (7) above the tubes
(Can be removed without removing other bricks
for chimney cleaning)
To install the new refractory bricks, follow the
above steps in reverse.
7
1
4
2
6
3
6
DOOR INSTALLATION
The doors must be put in place only when the installation of the Montecito
Estate™ is completed. All you have to do is fit the male part of the hinge,
already on the door, to the female part, which is on the fireplace. To remove
the doors, simply pull them up from the hinges. The door adjustment
has been set at the factory. If the fit is still not perfect, you can adjust
the door using the hinge screws (See Figure 7-1)
Figure 6 -
Door Installation
1
2
Figure 7
GLASS CARE
Glass Replacement
The glass used for the Montecito Estate is a high temperature ceramic
glass (1,400° F). If the glass breaks or cracks, it must be replaced with
an identical ceramic glass. Tempered glass or ordinary glass will not
withstand the high temperatures of the Montecito Estate . Replacement
glass should be purchased from a Security Chimneys International dealer
(see “Replacement Parts” on Page 22).
DOOR ADJUSTMENT
The doors may need to be adjusted to be completely airtight. The gaskets’
air-tightness can be adjusted using the adjustment screw located on the
right side of the fireplace facade (An Allen key #1/8 – not supplied - will
be necessary for this adjustment) (see Figure 7-2).
Checking Door Seal
A one-inch strip of paper may be used to perform a test of the integrity
of the door seal. Close the door on the paper in at least eight points. It
is normal to feel only a slight amount of friction. The door gasket does
not need to be “tight” in all areas, since a small amount of leakage is not
hazardous or detrimental to the performance of your fireplace.
WARNINGS
• Use only a Lennox Hearth Products glass doors,
specifically designed for the Montecito Estate
fireplace.
• The fireplace cannot be operated without a door.
Consult your dealer to select the correct door
model.
• Important! To assure proper alignment of glass
doors: Install this fireplace in a square and
plumb condition, using shims as necessary at
sides and/or bottom.
Do not operate the unit with cracked or broken glass.
Glass Cleaning
The Montecito Estate is designed to keep the glass clean under normal
operating conditions. If the Montecito Estate is operated continuously
with the combustion air controls closed, the glass will tend to get dirty
unless the fuel, firebox and glass are maintained at hot temperatures (see
section Refueling For Best Performance). To clean the glass, there are a
number of specially designed cleaners to remove creosote. Your authorized
Lennox Dealer can recommend a suitable cleaner. Regular household
glass cleaners will not clean creosote. Do not use abrasives such as steel
pads, steel wool or oven cleaner as they will scratch the glass.
Gasket Replacement
Remove the doors from the unit (see section Door Installation) and lay
them on a clean nonabrasive surface. To replace the gasket, first remove
all of the old gasket and gasket cement. Make sure that the surface is
totally clean before applying new cement (a high temperature silicone
caulking rated at 500° F (260° C), is suitable) or adhesion problems may
result. Apply gasket cement to the gasket channel and install the new
gasket. This replacement part is available from your Lennox Dealer in
the following dimensions:
GasketPart #LengthQtyDimensions
Around the glass
On the door frame
Between the
doors
Table 1
PR-SR-1685C61-3/4”21” width
x 3/16” thick
PR-SR-1825I48-3/8”23/4” diameter
PR-SR-1823J17-5/8”25/8” diameter
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
7
FIREPLACE INSTALLATION
Locating The Montecito Estate™
The best location to install your fireplace is determined by considering
the location of windows, doors, and the traffic flow in the room where
the fireplace is located, allowing space in front of the unit for the hearth
extension and the mantel, and taking into consideration the location of
the hot air ducts (optional), outside air kit and chimney. If possible,
you should choose a location where the chimney will pass through the
house without cutting floor or roof joists (see fireplace dimensions on
Pages 8 & 9
).
Usually, no additional floor support is needed for the fireplace. The adequacy of the floor can be checked by first estimating the weight of the
fireplace system. Weights are given in the appendix. Next, measure the
area occupied by the fireplace. Note the floor construction and consult
your local building code to determine if additional support is needed.
Figure 9
Fireplace
Tile or Marble
Minimum 1”
Cement Board
2” x 4” Framing
The Montecito Estate may be installed directly on the floor or on a raised
base and a minimum of 80” measured from the base of the appliance to
the ceiling is required.
Facade Installation
Install the Facade per instructions provided in Facade Kit (ordered separately - see Page 20).
Hearth Extension Requirements
The Montecito Estate may be installed directly on a combustible floor;
however, the combustible floor in front of the fireplace must be covered
with one inch (1 in) of non-combustible support material (cement board,
cement block or other) before applying the finish material (tile, marble,
stone, etc). See Figure 8.
Hearth Extension Requirements
Area where
wood Mantel
can be
installed
24”
Framing, Facing And Mantel
The construction of the framing, facing, and mantel must be in accordance
with the standards and the following illustrations (Figures 10 & 11):
A. Frame the fireplace using 2” x 3” or heavier lumber.
B. WARNING: Combustible materials cannot be used in the space
directly above the fireplace, except for the studs above the facade that support the facing and mantel. This area must remain
empty for a height of 80” (2,032 mm) measured from the base
of the appliance.
C. Frame the fireplace with vertical studs at the sides of the fireplace run-
ning from floor to ceiling (see Figure 10). If combustible facing is to
be used, position the studs back, from the front edge of the fireplace
(a space that is the thickness of the facing material, so that the facing can be installed flush with the fireplace facing). Frame headers
between the vertical studs only as follows:
- Place 2” x 3” or 2” x 4” headers, only along the upper part of the
front, side and back faces (some codes may require a 2” x 6” on
an outside bearing wall). Do not put wood or any combustible
material within the area above the fireplace except on the front
facing.
- Place headers only as required to support the facing and man
tel.
D. WARNING: The fireplace must not be in contact with any insula-
tion or loose filling material. Cover the insulation with Drywall
panels around the fireplace.
-
56” Min.
COLD CLIMATE INSTALLATIONS
Climates where temperatures will fall below 32° F (0° C).
24”
Hearth
4”
46-5/16”
45 Deg.
16”
The heating performance of the appliance will vary depending upon the
level of insulation, house design, how the appliance is operated, etc.
If this fireplace is being installed in a cold climate, it is especially important
to seal all cracks around the fireplace and wherever cold air could enter
the room with noncombustible material. Also, the outside air inlet duct
should be wrapped with noncombustible insulation to minimize the
Non-Combustible Material
Figure 8
8
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
formation of condensation. Do not place insulation materials directly
against the chimney sections. We recommend that you use the insulated
wall radiation shield since it will maintain the home’s thermal barrier. AC
chimney is NOT recommended in cold climates.
7 Ft.
Min.
Attic
Radiation
Shield
Roof Support
Storm
Collar
Flashing
Drywall or
Any Rigid
Material
2” x 4”
1/2” Plywood
6’ 8”
Min.
Firestop
* Floor
Ceiling
Wall
* Floor
Ceiling
Wall
Fireplace
Optional
Insulation
In Outside
Walls Of
Chase
Solid
Continuous
Surface
Outside
Base
Insulation
(Thermal Barrier)
8'
Level
Header
B
A
F
7/8”
11-1/8”
16-1/4”
26-1/8”
1”
1-5/32”
26-1/4”
10-1/4”
41-3/4”
49-3/8”
46-1/4”
43-1/4”
37”
31”
15”
7”
4-1/4”
28-1/2”
5-5/8”
20-1/8”
28-1/2”
5-5/8”
10-3/8”
3”
OUTSIDE CHASE
G
C
Back Wall of Chase/Enclosure
Including Finising Materials if any
Rough Framing Face (Unfinished Shown)
* Zero Clearance
From Back
Spacer to Wall
CORNER
INSTALLATION
D
Insulated Chase Construction
29-1/2”
J
7’
Min.
B
Rough Framing Face
(unfinished shown)
FRAMING DIMENSIONS
Fireplace Opening Width
A46-3/8”1178 mm
B49-1/2”1257 mm
C42-3/4”1086 mm
D20-7/8”530 mm
E93-7/8”2384 mm
F47”1194 mm
G27-3/4”705 mm
J66-3/8”1686 mm
23-3/4”
E
Note: Floor
and wall
below the
2” x 3”
Min.
attic must
be insulated
using the
same
Plywood
insulation.
Notes
G
A
Due to Lennox' ongoing commitment to quality, all specifications,
ratings and dimensions are subject to change without notice.
All framing dimensions calculated for 1/2" dry wall at the fireplace
face. If sheathing the chase or finishing with other thickness materials,
calculations will need to be made.
* The fireplace must not be in contact with any insulation or loose
filling material. Cover the insulation with Drywall panels around
the fireplace.
* Total depth is 25 inches including the
back spacer minus 1/2 inch for drywall
to be flush with the facing.
• Must have the same firestopping
resistance as adjacent wall.
• Must have the same insulation as
adjacent ceiling.
The facade must be removable
once installed. The facade is
designed to overlap any facing
material installed on the front of
the fireplace. If thicker material
is installed, use the facade as a
template and make sure it can be
easily removed for servicing.
1. Combustible material must be installed flush
with the fireplace. It may not project in front
of and on the fireplace (i.e. the steel facade
of the fireplace) (Figure 14).
2. Non-combustible materials such as brick,
stone or ceramic tile may project in front of
and onto the fireplace facing (Figure 13).
Mantel & Facing
Mantel
56”
Rock Board
or Other
Noncombustible
Facing
Figure 13
Only non-combustible material
should be superposed or projecting over the front of the fireplace.
(Side View)
Drywall
2” X 3” Min.
Spacer
Fireplace Blower
The fireplace comes equipped with a heat activated blower. It is located in the bottom of the
fireplace, towards the back. It uses 120 V and
must be connected to the main electrical circuit
by a qualified electrician. For connection, use the
electrical box supplied with the unit located on
the bottom right corner of the fireplace.
If you wish to adjust the blower speed, the
variable speed control (VRUW) provided must
be installed in line with the wiring. Again, use
a qualified electrician for installation.
If the blower requires servicing,
1- Remove the doors and decorative facade.
2- Remove the screw located below the blower
motor that holds it to the back of fireplace.
3- Pull the blower out of the unit through the
square hole located in the front bottom right
corner.
MANTEL & FACING
The mantel must be installed at least 56”
(1143 mm) above the base of the fireplace
(Figure 13).
Fireplace Frame Section
(Top View)
3
5
3
7
10
1
2
6
1
2
1. Fireplace
2. Front of fireplace
3. Wood frame (2” x 3” min)
4. Drywall
5. Tiles
6. Rock board or other
7. Brick
Figure 12
HOT AIR DUCTING INSTALLATION
The Montecito Estate™ is approved for use with
a Gravity Kit:
50”
Min.
Gravity Kit
The gravity kit is designed for double hot air
outlets and includes:
(See Figure 16)
- 2 telescopic lengths 8” I.D.
- 2 90º elbows 8” I.D.
- 2 hot air outlet kits (grill and frames)
- 2 adaptors
4
Figure 14
Noncombustible Facing
Drywall
2” X 3” Min.
4
Spacer
See Gravity Kit Accessories on Page 20.
Only the blower available with the fireplace can
be used with the gravity kit.
For safe installation, the gravity kit must meet
the following requirements:
Minimum height* 68” (1,727 mm)
Maximum length See Figure 17
* The height of the louver must be measured
from the base of the Montecito Estate to the
middle point of the louver.
Figure 15
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Rain Cap
Grill
Figure 16
Frame
Flashing
Collar
Flashing
Attic
Radiation
Shield
Roof Support
Firestop
6-1/2” Min.
(to ceiling)
68” Min.
56” Min.
Non-Combustible
Flameproof
Facing
When installing the double outlet system, the hot air outlets can be
installed in the same room as the fireplace, or one or both of the outlets
can be installed in adjacent or upper rooms. Installing the ducts at different elevations will tend to exhaust more heat out of the higher outlet
(Figure 17).
WARNING: The outlet
grills should not be
installed facing up-
Outlet Grill
ward through a floor.
Danger of burns can
result if grills in floor
are stepped on.
10’ Max.
Outlet Grill
Maintain at least 6-1/2”
(160 mm) clearance from
the outlet grill framing to
a combustible ceiling,
side wall or mantel.
13” x 13”
10’ Max.
Figure 17
Figure 18
The duct system must be installed respecting the following:
1. Remove the plates closing up the 8” dia. holes on top of the fireplace.
Then, cut the insulation in order to obtain two 8” dia. openings. Fix
the adaptors on the fireplace openings by turning clockwise (Figure
16).
2. Maintain at least a 2” (50 mm) clearance between the ducts and any
combustible material; the required hole size is 13” x 13” (330 mm x
330 mm).
Exception #1: For the grills, the framing can be 10-3/4” x 10-
3/4” (275 mm x 275 mm) to provide the clearance as required
by the integral spacers on the double outlet duct system.
3. The maximum number of elbows in a run of duct is two.
4. Maintain at least 6-1/2” (160 mm) clearance from the outlet grill
framing to a combustible ceiling, side wall or mantel.
5. When traversing a combustible wall or floor, a firestop must be installed
at the wall or floor penetration. The hole size must be 13” x 13” (330
mm x 330 mm)
6. Do not connect the hot air ducts to a central heating system. Malfunc
tion of the heating system’s blower will cause the fireplace to overheat.
A furnace duct is only single wall and not double wall as is required
for the Montecito Estate™ hot air exhaust.
7. Use only Security Chimneys International grills and components as
described in this manual. Other grills or registers may be too restrictive and may overheat the fireplace or ceiling.
8. Do not use insulated flexible ducts as they will overheat.
9. Do not use tees or any other components than the ones specifically
listed here.
10. Never allow the ducting to pitch down as hot air will be trapped creating a fire hazard. Never route the ducting downwards.
11. The hot air outlet grills must be installed with the louvers pointing
downwards in order to prevent overheating adjacent ceilings.
-
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
11
OUTSIDE AIR KIT
It is mandatory to install an outside air connection to the Montecito
Estate™. The following components are required and are included with
the fireplace:
- Outside air kit
long)
- 4” Adaptor for fireplace connection
(includes 40 inch flex that goes up to ten (10) feet
Outside
Intake
OUTSIDE CONNECTION
Aluminum Tape
Plastic
Cover
Outside Air Installation
The outside air assembly may be installed according to the following
requirements:
A) Duct length should be kept to a minimum. The maximum length of a
4” interior diameter (100 mm) insulated flexible duct is 20 feet (6.1 m).
The duct can be extended to a maximum of 40 feet (12 m) using a 6”
interior diameter (150 mm) insulated flexible duct (See note below).
B) The air intake register must not be installed more than ten (10) feet
(3050 mm) above the base of the fireplace.
C) The fresh air must come from outside the house. The air intake must
not draw air from the attic, basement or garage.
D) The air intake should be installed where it is not likely to be blocked by
snow or exposed to extreme wind and away from automobile exhaust
fumes, gas meters and other vents.
E) The duct and register may be installed above or below floor level.
Make a 4-1/4” (110 mm) hole in the outside wall of the house at the chosen
location. From outside, place the outside air register in the hole (open
side down) and fasten the register to the wall with screws as shown (see
Figure 19
). Slip the pipe into the insulated sleeve. Place the insulated
pipe over the register tube and over the fireplace’s outside air connector
(see Figure 20). At each end, carefully pull back the insulation and plastic
cover exposing the flexible pipe. Using the aluminium tape provided,
wrap the tape around the joint between the flexible pipe and the air inlets.
Carefully push the insulation and plastic cover back over the pipe. Using
aluminium tape, fasten the plastic cover in place.
Screw
Opening
Facing
Down
Wall
Figure 19
Plastic
Cover
Insulation
Figure 20
Flexible Pipe
Insulation
Aluminum Tape
OUTSIDE AIR CONNECTION TO THE FIREPLACE
Fireplace
Connection
Aluminum Tape
Fireplace
Flexible Pipe
Aluminum Tape
NOTE: We recommend not to exceed 20 feet of 4” flexible pipe. If you
require a longer length we recommend that you use a 5” diameter flexible pipe for the complete run up to 30 feet and a 6” diameter pipe for a
run of up to 40 feet.
12
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
THE CHIMNEY SYSTEM
Chimney Installation Notes
1. If possible, install an interior chimney as it will provide better performance. In areas with continuous temperatures below 18°C (0°F),
the use of an exterior chimney increases the likelihood of operating
problems such as low draft, high rate of creosoting, and poor start-up
characteristics. Exterior chimneys are also prone to down-drafting
and flow reversal. Installations which are located on lower floors in
the house, such as in a basement, in combination with an outside
chimney, are especially prone to flow reversal.
2. The fireplace model MONTEST
may be installed only with Security
Chimneys International Ltd 7” dia. chimney systems model Secure
Temp™ S2100+ / Nova Temp™ HT6000 / Secure Temp GX (U.S. only)
or ACBI.
3. A chimney venting a fireplace shall not vent any other appliance.
4. The minimum chimney height is 12 feet (3.7 m) excluding the fireplace.
8. A rain cap must be installed on top of the chimney. Failure to install
a rain cap may cause corrosion problems.
9. Cut and frame square holes in all floors, ceilings, and roof that the
chimney will go through to provide a 2” (50 mm) clearance between
the chimney and any combustible materials. Do not fill this 2” space
with insulation or any other combustible material.
10. Portions of the chimney which may extend through accessible spaces
must be enclosed to avoid contact with combustible materials or
damage to the chimney.
11.When offsets are used, the pipe may not penetrate a ceiling or floor
unless it is running vertical (no 30° offsets).
two (2) feet Min.
5. All chimney installations must include at least one support in order to
be able to take any lateral load. The maximum chimney length that
can be supported by the fireplace is nine (9) feet (2.75 m) for Secure
Temp S2100+ / Nova Temp HT6000+ / Secure Temp GX and 26 feet
(8m) for ACBI chimney. In altitude, add 18” (450 mm) to the chimney
for every 2,000 feet (600 m) above sea level.
6. The chimney must extend at least three (3) feet (915 mm) above its
point of contact with the roof and at least two (2) feet (610 mm) higher
than any wall, roof or building within ten (10) feet (3 m) of it (Figure
21).
7. If the chimney extends higher than five (5) feet (1,500 mm) above
its point of contact with the roof, it must be secured using a roof
brace.
Figure 21
ten (10) feet
three (3) feet Min.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
13
CHIMNEY INSTALLATION INSTRUCTIONS
1. Cut and frame the holes in the ceiling, floor
and roof where the chimney will pass (see
Figure 22). Use a plumb bob to line up the
center of the holes. The sizes are indicated
in Table 2 for the floor and ceiling holes
and Table 3 (Page 15) for the roof holes.
S2100 / HT6000+
Solid Packed Pipe
Attic Radiation Shield
ACBI
Air Cooled Pipe
Attic Radiation
Shield
CHIMNEY MODELSQUARE HOLE
Secure Temp™ S2100+
Nova Temp™ HT6000+
Secure Temp GX
ACBI: Ceiling
(1” clearance)
Wall
Note: See Table 3 for Sloped Roof Framing
SIZE OPENING
15 in (380 mm)
15 in (380 mm)
17 in (432 mm)
Table 2 - Flat Roof Framing
Figure 22 - Roof Framing
From below, install a firestop in each ceiling/floor
separation through which the chimney will pass.
At the attic level, install an attic radiation shield
from above (Figures 23a & 23b).
2. For Secure Temp S2100+ / Nova Temp
HT6000+ / Secure Temp GX chimneys, place
the first chimney length on the fireplace.
To lock it in place, turn 1/4 of a turn clockwise. With the ACBI chimney, you must
use a starter section before installing the
first chimney length (Figure 24). Continue
installing chimney lengths making sure to
lock each length in place.
3. Every time the chimney passes through a ceil
ing or a wall, install the appropriate firestop.
When you reach the desired height, install the
roof support (Refer to instructions included
with the support). For an ACBI chimney use
an universal support AC10SU.
4. Put the roof flashing in place and seal the
joint between the roof and the flashing
with roofing pitch (see Figures 25 & 26).
For sloping roofs, place the flashing under
the upper shingles and on top of the lower
shingles. Nail the flashing to the roof, using
roofing nails.
5. Place the storm collar over the flashing, and
tighten it with the bolt supplied. Finally, seal
the joint between the storm collar and the
chimney, using silicone caulking.
6. Install the chimney cap.
Figure 23a
CHIMNEY INSTALLATION
MODEL ACBI
Optional Chimney
-
Outside Air Intake
Outside Combustion
Air Kit
Figure 24
Firestop
Radiation Shield
Figure 23b
Rain Cap
Collar
Flashing
Attic Radiation
Shield
Firestop
Universal Support
ACBI Starter Section
ACBI7SB
or
ACBI7SB30
Note: Outside air kits must be
installed for both fireplace and
ACBI chimney.
14
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
CHIMNEY MODEL ACBI
Chimney
Collar
Flashing
Figure 25
Figure 26
Roof Down Slope Hole Size
DEGREE OF SLOPESecure Temp™ S2100+
Nova Temp™ HT6000+
Secure Temp GX
Roof Pitch7”7”
0 *15” (380 mm)15” (380 mm)
2/1215-3/8” (390 mm)15-3/8” (390 mm)
4/1216-1/8” (410 mm)16-1/8” (410 mm)
6/1216-7/8” (430 mm)16-7/8” (430 mm)
8/1218-1/4” (465 mm)18-1/4” (465 mm)
10/1219-5/8” (500 mm)19-5/8” (500 mm)
12/1221-3/8” (545 mm)21-3/8” (545 mm)
ACBI
Table 3 * Cross Slope Hole Size
OFFSET CHIMNEY INSTALLATION
After reaching the location requiring the elbow, proceed as follows. The minimum chimney height
when using elbows is:
1. Install the first elbow; turn it in the required
direction. Fasten it to the chimney with
the three (3) 1/2” (12 mm) metal screws
provided with the elbow.
2. Install the necessary chimney lengths to
achieve the required offset. Lock the chimney
lengths together: it is recommended to use
three (3) 1/2” (12 mm) screws. If the offset
length is made of two (2) chimney lengths
or more, use an offset support halfway up
the offset. If penetrating a wall, install a wall
radiation shield (see Figures 29 & 30).
3. Use another elbow to turn the chimney
vertically. Secure the elbow, using three
(3) 1/2” (12 mm) screws (provided with the
elbow).
4. Use a plumb bob to line up the center of
the hole. Cut a hole for the chimney in the
ceiling/floor. Frame this hole as described
previously (refer to Chimney Installation
Instructions on Page 14).
5. From below, install a firestop (See Figure
23a).
6. A support (XST+ or XSO+) must be used on
the first 15’ section (5 m).
7. Continue with the regular installation.
ACBI Chimney
1. Install the first elbow. Turn it in the required
direction. To lock it in place, turn 1/8 of a
turn. Fasten the straps attached to the elbow
to the surrounding frame, using nails or
drywall screws (Figure 28).
2. Install the necessary chimney lengths to
achieve the required offset. Lock the chimney
lengths together. If penetrating a wall, use
a wall radiation shield.
3. Use another elbow to turn the chimney
vertically. Lock it to the chimney. Fasten
the straps attached to the elbow to the
surrounding framing using nails or drywall
screws.
4. Use a plumb bob to line up the center of the
hole. Cut a hole for the chimney in the ceiling.
Frame this hole as described previously.
5. From below, install a firestop (see Figure
23b).
6. Continue with the regular installation.
Note:
Must return to vertical before penetrating ceiling or floor.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
15
Offset Dimensions
B
Total Height
A
ChimneyElbow
GX
S2100+
HT6000+
7”
Canada
Chimney ElbowOffset &
15º
ACBI
7”
30º
Note: With the ACBI chimney, a starting length of 6” high must be used on top of the fireplace before installing.
One Length Between ElbowsTwo Lengths Between Elbows
5-1/2”
(140 mm)7”(178 mm)
32-1/4”
(819 mm)
10-1/2”
(267 mm)
30-1/8”
(765 mm)
5-3/4”
(146 mm)
29-1/2”
(749 mm)
12-1/2”
(318 mm)
26-1/4”
(667 mm)
17”
(432 mm)
24-5/8”
(625 mm)
38”
(965 mm)
13-1/2”
(343 mm)
35-3/8”
(899 mm)
7-1/4”
(184 mm)
34-3/4”
(883 mm)
15-1/2”
(394 mm)
32”
(813 mm)
21-1/4”
(540 mm)
28-7/8”
(733mm)
11-1/2”
(292 mm)
55-1/2”
(1410 mm)
22-1/2”
(543 mm)
51”
(1295 mm)
Horizontal Offset
10-1/4”
(260 mm)
(1143 mm)
21-1/2”
(546 mm)
43-1/2”
(1105 mm)
29-3/4”
(755 mm)
37-3/8”
(949 mm)
(375 mm)
(1702 mm)
(724 mm)
(1559 mm)
45”
14-3/4”
67”
28-1/2”
61-3/8”
12-1/4”
(311 mm)
51-1/4”
(1302 mm)
25”
(635 mm)
50-1/2”
(1383 mm)
34-11/32”
(872 mm)
42”
(1067 mm)
----
----
----
----
----
----
----
----
Two Lengths Between Elbows
13-1/4”
(337 mm)
54-3/4”
(1391 mm)
27”
(686 mm)
54-1/4”
(1378 mm)
37-5/32”
(949 mm)
44-3/4”
(1137 mm)
17-1/2”
(445 mm)
77-1/8”
(1959 mm)
33-3/4”
(857 mm)
70-1/2”
(1791 mm)
14-3/4”
(375 mm)
60”
(1524 mm)
30”
(762 mm)
60”
(1524 mm)
41-13/32”
(1052 mm)
49”
(1245 mm)
19”
(483 mm)
82-7/8”
(2105 mm)
36-3/4”
(933 mm)
75-5/8”
(1921 mm)
16-1/4”
(413 mm)
65-1/4”
(1657 mm)
33”
(838 mm)
65-3/4”
(1670 mm)
45-21/32”
(1160 mm)
59-9/32”
(1353 mm)
23-5/8”
(600 mm)
100-1/4”
(2318 mm)
45-3/4”
(1162 mm)
91-1/4”
(2318 mm)
19-1/2”
(495 mm)
75-1/2”
(1918 mm)
39”
(991 mm)
77-1/2”
(1969 mm)
54-1/8”
(1375 mm)
61-3/4”
(1568 mm)
26-3/4”
(679 mm)
111-1/8”
(2823 mm)
51-3/4”
(1314 mm)
101-5/8”
(2581 mm)
16
Figure 27
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
OFFSET CHIMNEY INSTALLATION
Figure 28
Straps
Support
Straps
Chimney ACBI
ACBI Starter Section
OFFSET CHIMNEY INSTALLATION WITH WALL PENETRATION
Rain Cap
Figure 29
Collar
Roof Support
Roof Flashing
Outside Wall
Offset Support
Framing
2” x 3”
Insulated Wall
Radiation Shield
Note: In cold areas it is recommended to
protect the chimney in a insulated chase.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
17
ANGLED WALL RADIATION SHIELD
(XRSMI30 and AC10RSMI30)
For roof support installation, refer to the instructions provided with the
support.
When traversing a combustible wall with the chimney at a 30º or 45º
angle, an angled firestop or wall radiation shield must be installed. Only
one is required.
Note: 45º angle for Canada only (XRSMI45).
In cold climate locations (climates where temperatures will fall below 32º
F / 0º C), we recommend that you use the insulated wall radiation shield
since it will maintain the home’s thermal barrier.
XRSMI30 and AC10RSMI30
(XRSMI45 - Canada Only)
Chimney Model (7” dia).AngleHole Size
Secure Temp™ S2100+
Nova Temp™ HT6000+
Secure Temp GX
Secure Temp S2100+
Nova Temp HT6000+
(US only)
ACBI30º
30º
45º
Canada only
15” x 38-1/4”
(380 mm x 972 mm)
15” x 25-7/8”
(380 mm x 657 mm)
17 x 42-1/2”
(432 mm x 1080 mm)
Table 5
Insulated Wall
Drywall
Universal Offset Support
This support is used to support the chimney above an offset. When
the chimney offset is used to traverse a wall this support may be used
on the wall to support the chimney. The maximum heights are given in
Table 6.
For offset support installation, refer to the instructions provided
with the support.
CHIMNEYMAXIMUM HEIGHT OF
SUPPORTED CHIMNEY
7” DiameterOffset SupportRoof Support
Secure Temp S2100+
Nova Temp HT6000+
Secure Temp GX
ACBI40 feet (12.19 m).50 feet (15.20 m).
16 feet (5.49 m).18 feet (6.1 m).
Table 6
CHIMNEY CHASE AND MULTIPLE TERMINATIONS
For the purpose of this manual, a chimney chase is considered a part of
the chimney system rather than part of a building. The termination must
be placed a minimum of 18” (460 mm) above the chase.
For installations where more than one chimney is located in the same
chase or within the same area, we suggest that their terminations be
separated by at least 16” (410 mm) horizontally, and 18” (460 mm) vertically. This separation is to prevent smoke migrating from one chimney
to another (see Figure 31).
Figure 30
Insulated Wall
Radiation Shield
CHIMNEY SUPPORT INSTALLATION
Universal Roof Support
This support has three possible uses:
1. For Secure Temp S2100+ / Nova Temp HT6000+ / Secure Temp GX, it
must be used on a roof to support the chimney.
2. It may be used on a floor, ceiling or roof above an offset to support
the chimney above the offset.
3. It may be used on a floor, ceiling or roof as a supplementary support
when the chimney height exceeds 15 feet (4.6 m).
Table 6 gives maximum height of supported chimney.
NOTE: For the ACBI chimney, a support section (ACBI7SL) must be used
every 30 feet (9m) or an universal support every 20 feet (6m) instead of
the universal roof support (ST).
18
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Figure 31
18” (460 mm)
16” (410 mm)
18” (460 mm)
16” (410 mm)
18” (460 mm)
INSTALLATION INSTRUCTIONS FOR MASONRY APPLICATION
Follow these steps:
WARNING: Before starting the installation, the masonry chimney
must be inspected by a qualified chimney sweep.
The following requirements must be respected:
1. The chimney must be absolutely clear of any soot residue or creosote.
Check for cracks, loose or missing bricks that could inhibit correct
installation of the liner.
2. The clearance to combustible must be a minimum of 1” between the
outside of the masonry and any wood framing or loose insulation.
3. The chimney must be built in accordance with the current building
code.
4. No other appliance can be connected to the same chimney.
5. The clearances to combustible for the BISTMA30 connectors are 2”
on the side and bottom and 16” at the top.
6. The connector parts are not necessary if the connection between the
insulated length and the stainless steel liner is done within the masonry
chimney.
Installation:
The chimney must be relined with a stainless steel liner model TUBINOX
or Projet SS of the same diameter as the outlet of the fireplace.
For connection at 30º angle, a special connector (BISTMA30) must be
used to connect the liner to the insulated chimney.
* IMPORTANT NOTE - The use of a 45º connector (BISTMA) is approved for use in Canada ONLY. Installations in the USA must use the
30º connector (BISTMA30).
1- Position the fireplace in its location. Temporarily install the S2100+
elbow on the top of the fireplace and, using a level, mark with an oval
the location where the flue liner will enter the masonry chimney.
2- In the middle of the oval, drill a hole in the masonry chimney at 30º.
3- Increase the size of the hole until a 30º TUBINOX liner elbow can be
easily slipped through.
4- Slide the liner down from the top of the masonry chimney until you
reach the hole level.
5- Slip through the hole a 30º liner elbow and connect it to the liner.
6- Add a small liner section to the liner elbow which will allow the liner to
extend at least 12” (measured at the top of the liner) from the masonry
chimney.
7- Seal the opening around the liner with high temperature refractory
cement.
8- The next steps must be done in the following order:
See typical installation illustrated below.
A. Select the S2100+ length that will fit between the elbow and the liner
so that it will slide at least 2” over the liner section (You may need to
cut the liner for a better fit).
B. Take that section and the BISTMA30 cover and slide it over the liner.
Make sure you have enough opening to be able to install the S2100+
elbow without difficulty.
C. Install the 30º elbow on the fireplace.
D. Slide the length section back down on the elbow and twist lock the
two together.
E. Pull the cover down over the length and install the insulation pad over
the liner; be careful to cover the liner completely.
F. Slide back the cover over the insulation and fix it in place using the 3
metal screws supplied.
Figure 32
6’ 8”
Insulation Pad &
Cover (BISTMA or
BISTMA3U)
* 30°
S2100+ / GX
Insulated Elbow
High-Temp.
Cement
3 Screws
1” Clearance
Firestop
TUBINOX or Projet
SS Stainless Steel
TUBINOX or Projet SS
Liner Must Slide at
Least 2” Inside Length
Insulated
Length
Masonry Chimney,
New or Existing
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
19
OPTIONAL INSTALLATION ACCESSORIES
CHIMNEY - PARTS AND COMPONENTS LISTS
Installation Accessories
DescriptionCat./Part No.
Facades (Required - Order Separately)
Montecito Estate™Facade Black, MEFBK
Montecito EstateFacade Brushed Nickel, MEFBN
Montecito EstateFacade Hammered Steel, MEFMC
H4850
H4851
H4852
Doors - (Required - Order Separately)
Montecito EstateDoors Black, MECBK
Montecito EstateDoors Brushed Nickel, MECBN
Montecito EstateDoors Hammered Steel, MECMC
H4853
H4854
H4855
Outside Air Kit(included with fireplace)
Outside Air Coupler To Connect Outside Air (UZI) To Fireplace,
UZIAD
Outside Air Ducting - includes 4” insulated flex x 10’ long, UZIUZI
UZIAD
Gravity Kit
Gravity kit: Complete double duct system includes: 2 elbows 90º,
• Top: Do not fill the space above the fireplace with any material (Except
the wood framing. See Figure 10)
• Chimney: 2” (50 mm), except for through ceiling application, ACBI
chimney, 1’’ (25 mm) clearance.
• Mantel: 56” (1422 mm) measured from the base of the fireplace.
22
NOTES
23
Lennox Hearth Products Wood Burning
Fireplaces, Stoves and Inserts 20 Year Limited Warranty
THE WARRANTY
Lennox Hea rth Products ("LHP") wa rrants the components of this wood b urning fact ory-built fireplace system, stov e or insert ma nufactured by LHP (LHP System) to be fr ee
from
defects in materia ls and wo rkmanship at the ti me of man ufacture.
REMEDY AND EXCLUSI ONS
The coverage of this Warra nty is limite d to all components of the fire place syste m, stove or insert manufact ured by LHP, with the exception of optional LH P tempered gl ass doors.
A separate limited warranty is available from LHP for option al glass doors manufact ured by LHP. Ceramic glass doors manufact ured by LHP are warranted against thermal breakage
only. LHP warran ts the components of this factory-built system manufactured by LHP (LHP System) to be free from defects in materials and workmanship at the time of manufacture.
(1) During the fir st five years of this Wa rranty, LHP will, at it s option and except for the components listed in subpara graphs (a) th rough (f), below, provide replac ement or repair
components of the LHP System manufactured by LHP, at n o charge, a nd will als o pay for re asonable l abor costs incurred in replacing or repairi ng such com ponents. I f repair
or re placement is not commercially practicable , LHP will, at its option, refun d the purchase p rice o f the LHP Firepl ace, S tove o r Inse rt and LHP Chimney Com ponents and
Accessories. With re spect to th e componen ts listed below, the remedies of t his paragr aph (1) are available only for the period of time indica ted. There after, however, until the
expiration of 20 years from date of ins tallation, LHP will, subject to the conditions of par agraph (3) below, provide repla cements or repair s for those components at 50% off the
then prevailing fa ctory lis t prices for those component s.
a. Cast iron, iron, or steel fuel grates a re consid ered consumable acc essories and therefore are n ot warran ted, with the excep tion of d efects in material or workma nship.
b. Fireplace scre ens, inte rior refractories, and side shields (metal or r efractory ) - two years from date of i nstallation.
c. Electrical component s, such as fan moto rs and bl owers - one year fr om date o f installation (lig ht bulbs are excluded).
d. Certain model fireplaces are supplied with standard glass doors which are warranted 90 days f rom the date of i nstallati on for defects i n m aterial and w orkmanshi p.
Replacement glass for firep laces utilizing tem pered gla ss will be supplied at no-ch arge during the ter ms of the 90 day li mited war ranty wit h the following exc eptions:
Accidental glass b reakage o r damage to the gla ss door f rame finishes incur red in tr ansit, handling or operation either be fore, dur ing or af ter installation.
e. Certain fireplaces, stoves and inserts are suppl ied with ceramic gl ass, whic h is warranted agai nst therm al breakage only fo r 2 years from date of installation.
LHP will assume no responsi bility for glass re placement labor costs.
f. Certain f ireplaces, stoves a nd insert s are supplied with catalysts, which a re warran ted for a period of six year s. Warranty coverage for ye ars three - six will be pro-
rated from time of installa tion.
g. Air tubes, baf fles and brick retainers - o ne year f rom date of install ation.
h. By-pass damper assembly (catalytic models only) - f ive years from date of insta llation.
(2) During the six th through t enth year of the Warran ty, LHP will , at its option, provid e replacement or repai r components at no-charge, except a s is provide d for the components
listed in subparag raph (a) through (e) above. This cove rage provides for p arts only and does not inclu de any labor.
(3) During the eleventh throug h the twentieth year of the Warranty, LHP will, at its option, provide replacement or repair components at 50% off the then prevaili ng factory list prices
for those componen ts. This coverage only provi des for t he purchase of repl acement o r repair components at discount and do es not in clude any labor.
This Warranty covers only parts, and in some instances labor (as provided in subparagraph (1) above). In no case shall LHP be responsible for materia ls, parts or construction which
were not ma nufactured or supplied by LHP or for the labor necessary to install, rep air, or remo ve such materials, part s or construc tion. All re placement or repair components wi ll
be shipped F.O.B. the neare st LHP factory.
QUALIFICATIONS TO THE WARRA NTY
The complete firep lace Warr anty outlined above is furth er subject to the f ollowing qualifications:
(1) The factory-built fireplace system, stove or insert manufactu red by LHP (LHP System) must be instal led in accordance with LHP installation instructions and local building codes.
The Warrant y on this LHP syste m manufactured by LHP covers only the compone nt parts manuf actured by LHP . The use of compon ents manufactured by others with this LHP
System could create seriou s safety hazards, may result in the denial of certification by recognize d national safety listing agencie s, and could be in violatio n of local building codes.
This Warranty does not cover any damages occurr ing from the use of any components not manufactured or supplied by LHP. Any modifications to the system or the retro-fitting
of any appliance t o the sys tem which alters th e functio n or performance of the appl iance will void thi s Warranty.
(2) The factory-b uilt fireplace system , stove or insert manuf actured by LHP (LHP Sys tem) is sub jected to normal use wi th fuels stated in the Ho me Owners Manual. Fact ory-built
fireplace system includes burning such natura l fireplace fuels as wood and
natural or propane gas. Fuel products with abnormal burning characteristics, including but not limited
to fuel such as driftwoo d, coal or plywood and wood products using a binder, may burn at exc essive temp eratures an d may cause damage to the fac tory-buil t fireplace or may
cause it to functi on improp erly; stoves and in serts are approved for burni ng dry se asoned wood only.
(3) Coverage of this Warranty is condition al upon use of an adequate fireplace grate on factory-built fireplaces only, when applicab le. Coverage of this warranty for stoves and inserts
is that these appl iances ar e operated without the use o f grates, irons or any other method to elevate the fire.
(4) LHP is not responsible for inadequate fir eplace, stov e or insert syste m draft caused by air condition ing, heating , mechanical systems, or gener al construction conditions which
may generate negat ive air p ressure in the room in which the appliance is i nstalled. Additionally LHP a ssumes no responsib ility for smoking condi tions cau sed by inadequate
chimney heights fr om adjoin ing trees or buildi ng, adver se wind conditions or unusua l environmental fac tors and conditions .
LIMITATION ON LIAB ILITY
It is expressly agreed and und erstood that LHP’s sole obligation and pu rchaser’s exclusiv e remedy under this Wa rranty, under any other warranty, expresse d or im plied,
otherwise, shall b e limited to replacement, re pair, or refund, as specifie d above.
In no event shall LHP be responsible for any incid ental or con sequentia l damages caused by defec ts in its prod ucts, whether such dama ge occurs or i s discovere d before or
after replacement or repair, and whether or not such damage is caused by LHP’s negligence. Some states do not allow the exclusion or limitation of incidental or consequent ial
damages, so the above limitatio n or exclusion may not a pply to you . The duration of any im plied warr anty with respect to th is LHP firepl ace is limi ted to the duration of t he
foregoing warranty . Some st ates do not allow l imitation s on how long an im plied war ranty lasts, so the above ma y not appl y to you.
INVESTIGATION OF C LAIMS AGA INST WARRANTY
LHP reserves the r ight to i nvestigate any and all claim s against this Warr anty and to decide upon meth od of settlement.
LHP IS NOT RESPONS IBLE FOR WORK DONE WITHOUT W RITTEN CO NSENT
LHP shall in no ev ent be re sponsible for any w arranty w ork done without fi rst obtai ning LHP’s written consent.
DEALERS HAVE NO AU THORITY T O ALTER THIS WARRAN TY
LHP’s employees an d dealers have no authority to make a ny warranties nor t o authori ze any remedies in addition to or inco nsistent with thos e stated above.
HOW TO REGISTER A CLAIM AGA INST WARRANTY
In order for any claim under this Warranty to be valid, LHP must be notified of the claimed defec t in writing to Lennox Hearth Products, attent ion Customer Servic e Department, 1110
West Taft Avenue, Orange , CA. 92865, as soon as reasona bly possible after the defe ct is discovered. Claims ag ainst this Warranty in writing should incl ude the date of installatio n,
and a description of the de fect.
OTHER RIGHTS
This Warranty give s you spe cific legal rights, and you may have other righ ts which vary from state to state.
The manufacturer reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your
local distributor for fireplace code information.