Lennox OHR23-105, OHR23-120, OHR23-140, OHR23-154 Installation Instructions Manual

®
INSTALLATION
2004 Lennox Industries Inc.
Dallas, Texas, USA
WARNING
This product contain fiberglass wool.
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
INSTRUCTIONS
OHR23 Series Units
OIL UNITS
504,628M 38152A061 06/04 Supersedes 4/02
Table of Contents
Elite Series Oil Furnace 1. . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping and Packing List 1. . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
OHR23 Unit Parts Arrangement 3. . . . . . . . . . . . . . . . . . .
Oil Burner Parts Arrangement 3. . . . . . . . . . . . . . . . . . . . .
Requirements 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Supply & Return Air Plenums 5. . . . . . . . . . . . . . . . . . . . .
Optional Filter Kit 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Initial Unit Adjustments 6. . . . . . . . . . . . . . . . . . . . . . . . . .
Venting 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Combustion and Ventilation Air 8. . . . . . . . . . . . . . . . . . . .
Flue Connections 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Oil Supply Lines Sizing 12. . . . . . . . . . . . . . . . . . . . . . . . .
Oil Supply Line & Filter Connections 13. . . . . . . . . . . . . .
Leak Check 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Wiring 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Start−Up & Adjustments 15. . . . . . . . . . . . . . . . . . . . .
Service 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up & Performance Checklist 17. . . . . . . . . . . . . . . .
Troubleshooting 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
Litho U.S.A.
Elite® Series Oil Furnace
These instructions are intended as a general guide and do not supersede local codes in any way. Only qualified tech­nicians can install and service the Lennox Elite® Series OHR23 oil furnaces. In Canada, refer to CSA B139 for rec­ommended installation procedures. Consult authorities who have jurisdiction before installation.
WARNING
Installation and service must be performed by a qualified installer or service agency.
06/04 504,628M
Page 1
Shipping & Packing List
1− Assembled oil furnace
1− Draft control Check the components for shipping damage. If you find any damage, immediately contact the last carrier.
CAUTION
Never burn garbage or paper in the heating system. Never leave papers near or around the unit.
Do not store or use gasoline or other flammable va­pors and liquids in the vicinity of this or any other appliance.
When venting this appliance, keep vent terminal free of snow, ice and debris.
*2P0604* *P504628M*
OHR23 Unit Dimensions − Inches (mm)
OHR23Q3-
OHR23Q5-
Model No. A B C D E F G H
OHR23Q3-
105/120
OHR23Q5-
140/154
in. 20-1/2 20-1/2 18 18 18 18 3 10-1/4
mm 521 521 457 457 457 457 76 260
in. 23-1/2 23-1/2 21 21 21 21 4-3/4 11- 3/ 8
mm 597 597 533 533 533 533 121 289
53 (1346)
4 KNOCKOUTS
(For Suspending)
TOP VIEW
14-1/2
3-1/2
(89)
(368)
AIR
F A
FLOW
F
RETURN
E
AIR
OPENING
TOP VIEW
A
A
8
(203)
C
SUPPLY
D
AIR
OPENING
END VIEW FLUE OUTLET
(4) SPACER LEGS
3/4
(19)
HEAT EX­CHANGER CLEAN OUT PORTS (3)
1
(25)
BURNER
HORIZONTAL POSITION
OPTIONAL DOWNFLOW COMBUSTIBLE FLOOR BASE
B
3/4
(19)
FRONT OF FURNACE
FLUE OUTLET
59 (1499)
G
32-1/2 (826)
H
SIDE VIEW
RETURN
AIR
3/4
(19)
E B
RETURN
AIR
SUPPLY AIR DUCT (Not Furnished)
AIR
FLOW
32-1/2
(826)
59
(1499)
HEAT
EXCHANGER
CLEAN OUT
PORTS (3)
BURNER
3/4
8
(203)
SUPPLY AIR OPENING
(19)
DC
SUPPLY AIR OPENING
SIDE VIEW FRONT VIEW
DOWNFLOW POSITION
105/120
16-1/4(413)
H
140/154
20-1/4(514)
FLUE OUTLET
105/120
16-1/4(413)
140/154
20-1/4(514)
BURNER
Additive Base Raises Furnace
3/4 in. (19 mm) Inch above Floor Level
OPTIONAL DOWNFLOW ADDITIVE BASE
COMBUSTIBLE FLOOR
Page 2
OHR23 Unit Parts Arrangement
BECKETT
AFII BURNER
CLEAN−OUT PORT
CLEAN−OUT PORT
WITH FAN CONTROL BOARD
FLUE OPENING
HEAT EXCHANGER
INDOOR BLOWER
CONTROL BOX
OHR23 Oil Burner Parts Arrangement
RETAINING
CLIP
HEAD SCREW
HEAD
INSULATOR
FLANGE
GASKET
AIR TUBE
ASSY FOR
FB HEADS
1/4" HEX
FB−HEAD
NOZZLE
ADAPTER
NOZZLE LINE
ELECTRODE HEAD
ASSY.
FLANGE
ELECTRODE
ASSY
AIR TUBE SCREWS
PEDESTAL
PRE−MOUNTED OIL−DELAY
Figure 1
ELECTRONIC IGNITION
TRANSFORMER
REAR ACCESS
DOOR ASSY
MAIN
HOUSING
ASSY
ESCUTCHEON
PLATE
CONNECTOR
TUBE
FUEL PUMP
COUPLING
VALV E
Figure 2
REAR ACCESS
DOOR GASKET
SPLINED
NUT
IGNITOR
MOTOR
PRIMARY
CONTROL
BLOWER
WHEEL
4X4
BOX
0
3 4 5
6 7 8
AIR ADJ. DIAL
INLET
AIR SCOOP
Page 3
Requirements
Installation of Lennox oil−fired furnaces must conform with the National Fire Protection Association Standard for the Installation of Oil Burning Equipment, NFPA No. 31, the National Electrical Code, ANSI/NFPA No.70 (in the U.S.A.), CSA Standard CAN/CSA−B139 (in Canada), Installation Code for Oil Burning Equipment, the Canadian Electrical Code Part1, CSA 22.1 (Canada), the recom­mendations of the National Environmental Systems Con­tractors Association and any state or provincial laws or lo­cal ordinances. Authorities having jurisdiction should be consulted before installation. Such applicable regulations or requirements take precedence over general instructions in this manual.
Chimneys and chimney connectors must be of the type and construction outlined in section 160 of NFPA No. 31.
Air for combustion and ventilation must conform to stan­dards outlined in section 140 of NFPA No. 31 or, in Cana­da, CSA Standard B139. When installing OHR23 units in confined spaces such as utility rooms, two combustion air openings are required. Dimensions of combustion air openings are shown in table 1. One opening shall be below burner level and the other opening shall be no more than 6 inches from the room’s ceiling.
Combustion air openings should provide a minimum free area one-half square inch per 1,000 Btu per hour input. This combustion air should be brought into the area con­taining the furnace below the level of the furnace burner.
IMPORTANT
An opening to the outside for combustion air is strongly recommended, especially in new homes. Refer to table 1 or the unit rating plate for specific combustion air opening dimensions.
Table 1
Combustion Air Opening Dimensions
Model No. (2 openings required)
OHR23−105/120 10" X 20"
OHR23−140/154 11" X 22"
This unit is approved for clearances to combustible materi­al as listed unit rating plate and in tables 2 or 3. Unit service and accessibility clearances take precedence over fire protection clearances.
Table 2
Horizontal Installation Clearances
Clearances Inches (mm)
Top of Cabinet 3 (76) *Bottom and Rear of Cabinet 1 (25) Front of Cabinet 24 (610) Service Clearance (Front) 24 (610) End of Supply Plenum 0 (0) Supply Air Opening 0 (0) Return Air Opening 0 (0) Above Horizontal Warm Air Duct
within 3 ft. (914mm) of Furnace Flue Pipe Horizontal 7 (178) Flue Pipe Vertical 7 (178)
*NOTE−When furnace is installed on combustible floor, 1 " (25 mm) spacer legs must be installed to elevate unit off of mounting surface.
0 (0)
Table 3
Downflow Installation Clearances
Clearances Inches (mm)
Bottom of Plenum and Ductwork 1 (25) Plenum Sides 1 (25) Side of Cabinet 1 (25) Rear of Cabinet 1 (25) Front of Cabinet 16 (406) Service Clearance (Front) 24 (610) Flue Pipe Horizontal 1 (25) Flue Pipe Vertical 7 (178) Return Air Opening 0 (0) *Floor *Combustible
*NOTE−Clearance for installation on combustible floor if op­tional additive base is installed between the furnace and combustible floor. Not required in add−on coiling applications.
NOTE − Downflow Application Only  For installation on combustible floors, appliance shall not be installed directly on carpeting, tile or other combustible material other than wood flooring. When installed on wood flooring, the addi­tive base must be used. See Unit Dimension illustration.
NOTE − Unit must be adjusted to obtain a temperature rise within the range listed in table 7 (see Page 15).
When used in conjunction with a evaporator coil, the fur­nace shall be installed in parallel with, or on the upstream side of the evaporator coil. In a parallel flow arrangement, the dampers, or other measures used to control flow of air flow, shall be adequate to prevent chilled air from entering the furnace. If the furnace is manually operated, it must be equipped with means to prevent operation of either unit un­less dampers are in the full-heat or full-cool position.
Page 4
When installed, furnace must be electrically grounded in accordance with local codes or, in the absence of local codes, with the current National Electric Code, ANSI/ NFPA No. 70, if an external electrical source is utilized.
Field wiring connection with unit must meet or exceed specifications of type T wire and withstand a 63F (17C) temperature rise.
Installation
When installed, OHR23 furnaces must be level. If the fur­nace is not level, place fireproof wedges or shims between the low side of the furnace and floor. Make sure the weight of the furnace is evenly distributed on all four corners. Strain on sides of the cabinet causing cracking and pop­ping noises may occur if weight of furnace is not evenly dis­tributed.
Set the unit in desired location keeping in mind the clear­ances list in tables 2 and 3. Also keep in mind oil supply connections, electrical supply, flue connections and suffi­cient clearance for installing and servicing unit.
OHR23 series units may be installed in a crawl space un­der a house, utility room or in a wide variety of suspended applications.
Horizontal Application
The OHR23 furnace is shipped from the factory in the hori­zontal left hand air discharge application. Air flow may be reversed to right side discharge or unit may be used as downflow.
Reversing Airflow for Right Hand Discharge
1. Rotate the furnace 180so that when facing the front, the warm discharge is to the right.
2. Remove the nuts in the bracket that hold the burner to the furnace front. Rotate the burner and burner mount­ing plate 180 and reinstall the nuts.
3. Remove the screws that hold the limit control in place. Use the provided knockout hole to relocate the limit control to the top side of the front panel.
Installation on Non−Combustible Material
Set the furnace on non-combustible material (such as con­crete blocks, bricks or angle iron). Install spacer legs, pro­vided with unit, by using the cabinet screws from each cor­ner of the unit. Use a level to check level of furnace in at least two directions. Use shims or non-combustible materi­al. A minimum clearance of 1" must be maintained be­tween bottom of furnace and combustible material.
Suspended Installation
To suspend furnace, remove knockouts in top of panel at warm air discharge and at blower panel (Refer to unit di­mensions). Use 3/8" rods cut to desired length. Use one flat washer and two nuts for each rod. One nut and the washer on the inside of unit and the other nut on the outside of unit (the locking nut). Level the unit by adjusting the nuts on the inside of unit. See figure 3 to suspend unit.
Hanger Rod Installation
rod
nut
blower compartment
top of furnace
washer
nut
division panel
Figure 3
Downflow Application
When installing the OHR23 in a downflow position and on combustible flooring, a combustible floor base must be used. See Unit Dimension illustration.
1. Rotate the furnace so that return is on top and supply is on bottom. Refer to table 3 for clearances to com­bustible flooring.
2. Remove the nuts in the bracket that hold the burner to the furnace front. Rotate the burner and burner mount­ing plate 90 and reinstall the nuts.
3. It is also recommended that the upper rear screw hold­ing the blower housing to the blower deck be removed before installation in a closet. Removing this screw al­lows for easy service and removal of the blower as­sembly in a closet installation.
Supply & Return Air Plenums
NOTE − Following these suggestions when installing sup­ply and return air plenums.
1. Use sealing strips of fiberglass.
2. In all cases, the plenum should be secured to furnace or evaporator cabinet with sheet metal screws.
3. Both supply and return air plenums shall be square and least 18" long. They should be the same dimen­sion as the furnace opening.
4. If unit is installed in a confined space such as a utility room where there is no complete return air duct sys­tem, a return air connection should be run (the same size as the return air opening) to a location outside the room containing the furnace.
5. Install supply and return air ducts as desired.
Optional Filter Kit
An Optional filter kit is available for OHR23 units. Kit 35K05 is used with OHR23−105/120 units, and kit 35K06 is used with OHR23−140/154 units. All kits include the following:
2 filters 3 rods 7 screws 1 rack assembly 1 panel
Page 5
OHR23−140/154 Filter Rack Installation
1. Slide filter rack over return duct flanges.
2. Using a scriber through the filter rack mounting holes, mark seven mounting hole locations in the return end of the cabinet. See figure 4.
3. Remove filter rack and drill 1/8" diameter holes at the marked positions.
4. Place filter rack in position again and secure it to the cabinet using the sheet metal screws provided. Clear­ance for the screw driver is provided in outside holes of rack and in filter support angles.
5. Bend the ends of filter rods and hook ends through holes provided in top and bottom filter support angles.
6. Slide filter between the support angles and the plenum side for the filter rack. The filter rods hold the filter in place.
OHR23 105/120 Optional Filter Kit
FILTER RACK (FURNISHED)
22 (559)
14 (356)
RETURN AIR DUCT (NOT FUR­NISHED BY LENNOX)
Oil vacuum gaugeBeckett T−500 gaugeKnowledge of proper test equipment operation
CAUTION
Improper nozzle and/or air adjustment of this unit may result in sooting problems. Refer to the follow­ing set-up section for correct adjustment proce­dures.
Adjusting the Nozzle
Proper adjustment of the nozzle assembly is critical be­cause alignment may have changed during shipping. Be­fore the furnace and oil lines are installed, the nozzle as­sembly must be checked. This may easily be done by removing the entire burner assembly (not just the nozzle) from the furnace. The lower firing nozzle is factory installed. This should be verified by the installer. Inspect the spark transformer leads also to ensure they are still at­tached to the electrodes.
The burner assembly is attached to the vestibule panel by three nuts. Slots are provided in the mounting flange for re­moving the burner assembly from the vestibule. By loosen­ing the nuts and by turning the whole burner assembly counterclockwise (figure 5), the entire burner assembly will come out of the furnace. There is adequate wire to re­move the burner without disconnecting wires. Once re­moved, just turn the burner around in the vest panel area.
FILTER
(FUR-
NISHED)
OPENING
IN UNIT
(EITHER SIDE)
Figure 4
Initial Unit Adjustments
Neither the nozzle setting nor the air adjustments are fac­tory set. The furnace is fire−tested and the limit control is checked to make sure it functions properly; no factory set­tings are made. During installation, the furnace must be set up. The installing dealer/contractor must have and use proper test equipment in order to correctly set up the oil fur­nace. Proper testing equipment is required to ensure cor­rect operation of the unit. The use of test equipment is now more critical than ever due to tighter tolerances needed to keep the furnace operating efficiently. Among the test equipment for an oil furnace, the proper combustion test kit should contain the following:
Draft gaugeCO
or O2 analyzer
2
Smoke testerPressure gaugeHigh temperature thermometer
OHR23 Series Burner Removal
LOOSEN THREE NUTS WHICH AT­TACH BURNER TO VEST PANEL.
ROTATE BURNER COUNTERCLOCKWISE ON SLOTS THEN PULL TOWARD YOU.
Figure 5
To correctly adjust the nozzle, use a Beckett #T−500 gauge.
Insert the small end of the gauge into the end of the cone and measure from the flat of the end cone to the tip of the nozzle. When nozzle depth is correct, the tip of the nozzle should just touch the end of the gauge. Refer to the illustra­tion sheet provided with the gauge. Note that the scale side of the gauge is not used for this purpose. Make corrections by sliding the nozzle assembly forward or backward within the blast tube (figure 6). At the same time, check the nozzle alignment.
Page 6
To check nozzle alignment, again insert the small end into the end cone and measure the nozzle and electrode align­ment against the center lines marked on the gauge (again refer to enclosed illustration sheet). If the nozzle is not cen­tered, but found to be too far left or right, a new nozzle as­sembly will need to be ordered. Do not attempt to adjust by bending the 90 degree elbow in the oil line.
Beckett Oil Burner Nozzle Adjustment
BURNER MUST BE REMOVED FROM FURNACE FOR THIS PROCEDURE.
GAUGE
2
TO ADJUST NOZZLE:
1−LOOSEN SCREW.
2−SLIDE ENTIRE NOZZLE/ELECTRODE ASSEMBLY BACK AND FORTH UNTIL NOZZLE JUST TOUCHES GAUGE.
1
Figure 6
Venting
WARNING
The barometric damper shall be in the same atmo­spheric pressure zone as the combustion air inlet to the furnace. Deviation from this practice will cause improper burner operation and may result in a fire hazard.
This furnace is certified for use with type L" vent. B" vent must not be used with oil furnaces.
Prior to installation of unit, make a thorough inspection of the chimney to determine whether repairs are necessary. Make sure the chimney is properly constructed and sized according to the requirements of the National Fire Protec­tion Association. The smallest dimensions of the chimney should be at least equal to the diameter of the furnace vent connector. Make sure the chimney will produce a steady draft sufficient to remove all the products of combustion from the furnace. A draft of at least .04" w.c. (9.9 Pa) is re­quired during burner operation.
1. Local building codes may have more stringent installa­tion requirements and should be consulted before installation of unit.
2. The vent connector should be as short as possible to do the job.
3. The vent connector should not be smaller than the out­let diameter of the vent outlet of the furnace.
4. Pipe should be at least 24 gauge galvanized.
5. Single wall vent pipe should not run outside or through any unconditioned space.
6. Chimney should extend 3 feet (0.9 m) above highest point where the vent passes through the roof, and 2 feet (0.6 m) higher than any portion of a building within a horizontal distance of 10 feet (3 m).
7. The vent must not pass through a floor or ceiling. Clear­ances to single wall vent pipe should be no less than 6" (152 mm); more if local codes require it.
8. The vent may pass through a wall where provisions have been made for a thimble as specified in the Standards of the National Board of Fire Underwriters. See figure 7.
Wall Thimble
THIMBLE
CAUTION
Do not store combustible materials near the furnace or supply air ducts. The material (such as paint, mo­tor oil, gasoline, paint thinner, etc.) may ignite by spontaneous combustion creating a fire hazard.
NOTE − Oil burning equipment may be vented into an ap­proved masonry chimney or type L vent. (Type L vent is similar in construction to type B gas vent except it carries a higher temperature rating and is constructed with an inner liner of stainless steel rather than aluminum).
Page 7
COMBUSTIBLE
WALL
VENT PIPE
Figure 7
9. The vent pipe should slope upward toward the chim­ney on horizontal run at least 1/4 inch (6 mm) to the foot (0.3 m) and should be supported by something other than the furnace, such as isolation hangers. See figure 8.
BAROMETRIC
CONTROL* (IN EITHER LOCATION)
HORIZONTAL
APPLICATION
SHOWN
Masonry Chimney
LINER
CLEAN OUT
MASONRY CHIMNEY
BAROMETRIC
CONTROL* (IN EITHER LOCATION)
HORIZONTAL
APPLICATION
SHOWN
Factory-Built Chimney
FACTORY BUILT CHIMNEY
DRAIN FOR CONDENSATE
CLEAN OUT
*BAROMETRIC CONTROL MAY BE INSTALLED IN EITHER VERTICAL OR HORIZON­TAL SECTION OF FLUE PIPE WITHIN 18" OF FLUE OUTLET OF FURNACE.
Figure 8
10. Extend the vent pipe into the chimney so that it is flush with the inside of the vent liner. Seal the joint between the pipe and the liner.
11. The furnace shall be connected to a factory built chim­ney or vent complying with a recognized standard, or masonry or concrete chimney lined with a lining mate­rial acceptable to the author ity having jurisdiction.
12. When two or more appliances vent into a common vent, the area of the common vent should not be less than the area of the largest vent or vent connection plus 50% of the areas of the additional vent or vent connection. Chimney must be able to sufficiently vent all appliances operating at the same time.
13. The vent pipe shall not be connected to a chimney vent serving a solid fuel appliance or any mechanical draft system.
14. All unused chimney openings should be closed.
15. All vent pipe run through unconditioned areas or out­side shall be constructed of factory built chimney sec­tions. See figure 9.
16. Where condensation of vent gas is apparent, the vent should be repaired or replaced. Accumulation of con­densation in the vent is unacceptable.
17. Vent connectors serving this appliance shall not be connected into any portion of mechanical draft sys­tems operating under positive pressure.
18. Keep the area around the vent terminal free of snow, ice and debris.
*BAROMETRIC CONTROL MAY BE INSTALLED IN EITHER VERTICAL OR HORI­ZONTAL SECTION OF FLUE PIPE WITHIN 18" OF FLUE OUTLET OF FURNACE.
Figure 9
Combustion and Ventilation Air (Confined and Unconfined Spaces)
Homes designed with energy conservation in mind use air-tight construction practices. Therefore, it is necessary to bring in outside air for combustion. Consideration must also be given to the use of exhaust fans, appliance vents, chimneys and fireplaces that force out air which might have otherwise been used for combustion. Unless outside air is brought into the home for combustion, negative pres­sure (pressure outside is greater than inside pressure) will build to the point that a downdraft can occur in the furnace vent pipe or chimney. Combustion gases entering the liv­ing space create a potentially dangerous situation.
NOTE − The importance of the previous paragraph can­not be overstated. Users may inadvertently block fresh air intakes after installation.
In the absence of local codes concerning air for combus­tion and ventilation, the following section outlines guide­lines and recommends procedures for operating oil fur­naces in a manner that ensures efficient and safe operation. Special consideration must be given to combus­tion air needs as well as requirements for exhaust vents and oil piping.
Combustion Air Requirements
All oil-fired appliances require air to be used for the com­bustion process. If sufficient amounts of combustion air are not available, the furnace or other appliance will oper­ate in an inefficient and unsafe manner. Enough air must be provided to meet the needs of all fuel-burning ap­pliances, as well as appliances such as exhaust fans which force air out of the home.
Page 8
Loading...
+ 16 hidden pages