These instructions are intended as a general guide and do
not supersede local codes in any way. Only qualified technicians can install and service the Lennox Elite
OF23 oil furnaces. In Canada, refer to CSA B139 for recommended installation procedures. Consult authorities
who have jurisdiction before installation.
Litho U.S.A.
®
Series
WARNING
Improper installation, adjustment, alteration, service, or maintenance can cause injury or property
damage. Refer to this manual. For assistance or
additional information, consult a qualified installer
or service agency.
CAUTION
When venting this appliance, keep vent terminal free
of snow, ice and debris.
01/04
*2P0104*
CAUTION
Never burn garbage or paper in the heating system.
Never leave papers near or around the unit.
Shipping & Packing List
1− Assembled oil furnace
1− Barometric draft control
1− Side exhaust pipe collar (front flue units only)
1− Direct intake collar (AFII burner units only)
Check the components for shipping damage. If you find any
damage, immediately contact the last carrier.
504,627M
Page 1
*P504627M*
Page 2
OF23 Unit Dimensions − Inches (mm)
1-1/2
(38)
FLUE CONNECTION
OF23Q3/4-105/120R,
OF23Q5-140/154R
OF23Q5−175/210R
C
3/4
(19)
RETURN
E
OPENING
3/4
(19)
AIRFLOW
3/4
(19)
3-1/4
(83)
E
AIR
3/4
(19)
TOP VIEW
C
AIRFLOW
FLUE CONNECTION
OF23Q3/4-105/140 &
OF23Q5-140/154
(On Heat Exchanger)
ELECTRICAL INLETS
(Right Side Only)
FG
SUPPLY
AIR
OPENING
TOP FLUE
OUTLET
SIDE
FLUE OUTLET
CENTERING HOLE
(Field Fabricate
Either Side)
OPT. OUTDOOR
COMBUSTION
AIR INLET
CENTERING HOLE
(Field Fabricate
Right Side only)
A
B
1
(25)
Model No.
OIL PIPING INLET
(Both Sides)
SIDE VIEWFRONT VIEW
1 (25)
6-1/2
(165)
ABCDE x F (Supply)E x G (Return)
in.mmin.mmin.mmin.mmin.mmin.mm
OF23Q3/4-105/12019-1/2 495937940 52−1/2 13342768618 x 21457 x 53318 x 16457 x 406
OF23Q3/4-105/120R 19-1/249537940 52−1/2 1334 2768618 x 21457 x 53318 x 16457 x 406
OF23Q5-140/15422-1/2 57237940 52−1/2 13342768621 x 21533 x 53321 x 16533 x 406
OF23Q5-140/154R22-1/257237940 52−1/2 13342768621 x 21533 x 53321 x 16533 x 406
OF23Q5-175/210R2461039−1/4 9975513972973722−1/2 x 23−1/8572 x 58722−1/2 x 16−1/2572 x 419
OF23 Start−Up & Performance Check List
Job Name
Job Location
Installer
Unit Model No.
HEATING SECTION
Electrical Connections Tight?
Supply Voltage
Blower Motor Amps
Blower Motor H.P.
Blower Motor Lubrication O.K.?
Piping Connections Tight?
Burner Model No.
All Valves Open?
Serial Number
Oil Pump Pressure [recommended minimum 140 psi]
Job No.
City
City
Serial No.
Date
State
State
Serviceman
PROPER DRAFT
Draft Reading (recommended .03−.04 inches w.c.)
% CO2 (recommended 12%)
Flue Connections Tight?
Fan Control Setting (maximum 130_ F)
(55_C)
Temperature RiseFan Control Cutout
Filter Clean & Secure?
Vent Clear?
THERMOSTAT
Calibrated?Heat Anticipator Properly Set?Level?
Page 2
Page 3
OF23 Unit Parts Arrangement
flue opening
clean-out port
limit switch
control box
with fan control
board
observation port
filter
indoor blower
heat exchanger
BeckettR AFII Burner
(Shown)
OF23 Oil AFII Burner Parts Arrangement
RETAINING
CLIP
HEAD SCREW
HEAD
INSULATOR
ADAPTER
FLANGE
GASKET
AIR TUBE
ASSY FOR
FB HEADS
1/4" HEX
FB−HEAD
NOZZLE
NOZZLE LINE
ELECTRODE HEAD
ASSY.
FLANGE
ELECTRODE
ASSY
AIR TUBE
SCREWS
PEDESTAL
PREMOUNTED OIL−DELAY VALVE
Figure 1
ELECTRONIC IGNITION
TRANSFORMER
REAR ACCESS
DOOR GASKET
REAR ACCESS
DOOR ASSY
MAIN
HOUSING
ASSY
SPLINED
NUT
ESCUTCHEON
PLATE
CONNECTOR
TUBE
FUEL PUMP
COUPLING
clean−out
port
IGNITOR
MOTOR
PRIMARY
CONTROL
BLOWER
WHEEL
4X4
BOX
0
3
4
5
6
7
8
AIR
ADJ.
DIAL
INLET
AIR SCOOP
Figure 2
Page 3
Page 4
Requirements
Table 1
Combustion Air Opening Dimensions
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during
installation, maintenance, or repair will expose you
to fiberglass wool dust. Breathing this may cause
lung cancer. (Fiberglass wool is known to the State
of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin,
and eye irritation.
To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address shown below, or contact your
supervisor.
Lennox Industries Inc.
P.O. Box 799900
Dallas, TX 75379−9900
Installation of Lennox oil−fired furnaces must conform with
the National Fire Protection Association Standard for the
Installation of Oil Burning Equipment, NFPA No. 31, the
National Electrical Code, ANSI/NFPA No.70 (in the
U.S.A.), CSA Standard CAN/CSA−B139 (in Canada),
Installation Code for Oil Burning Equipment, the Canadian
Electrical Code Part1, CSA 22.1 (Canada), the recommendations of the National Environmental Systems Contractors Association and any state or provincial laws or local ordinances. Authorities having jurisdiction should be
consulted before installation. Such applicable regulations
or requirements take precedence over general instructions
in this manual.
Chimneys and chimney connectors must be of the type and
construction outlined in section 160 of NFPA No. 31.
Air for combustion and ventilation must conform to standards outlined in section 140 of NFPA No. 31 or, in Canada,
CSA Standard B139. When installing OF23 units in confined spaces such as utility rooms, two combustion air
openings are required. Dimensions of combustion air
openings are shown in table 1. One opening shall be below
burner level and the other opening shall be no more than 6"
(152 mm) from the room’s ceiling.
The combustion air opening should provide a minimum free
area one-half square inch per 1,000 Btu per hour input. This
combustion air should be brought into the area containing the
furnace below the level of the furnace burner.
IMPORTANT
An opening to the outside for combustion air is
strongly recommended, especially in new homes.
Refer to table 1 or the unit plate for specific combustion air opening dimensions.
Model No.
O23−105/120
O23−105R/120R
O23−140/154
O23−140R/154R
O23−175R/210R
O23−175R/210R
This unit is approved for use on combustible flooring and for
clearances to combustible material as listed on unit rating
plate and in table 2. Unit service and accessibility clearances
take precedence over fire protection clearances.
Combustion Air Opening
Dimensions (2 required)
10" X 20" (254 mm X 508 mm)
11" X 22" (279 mm X 559 mm)
20" X 40" (508 mm X 1016 mm)
Table 2
Installation Clearances
Clearances
top of plenum and duct2 (51)
plenum sides3 (76)
sides*6 (152)
rear24 (610)
front4 (102)
flue pipe measured vertical**
(measured from above)
NOTE−Service access clearance must be maintained.
*Clearance to allow inspection of furnace and flue connector
shall be provided. 24" (610 mm) at rear and on one side of furnace should
be allowed for cleaning and service of the blower.
**Minimum clearance shown for flue pipe may be reduced by using special
protection as provided by local building codes and the National Fire
Protection Association Standards and CSA 189.
NOTE − When service clearances are greater than fire
protection clearances, service clearances take precedence.
Unit must be adjusted to obtain a temperature rise within
the range listed in table 3 in the Start-Up section of this
manual.
When installed, furnace must be electrically grounded in
accordance with local codes or, in the absence of local
codes, with the current National Electric Code, ANSI/NFPA
No. 70, or Canadian Electric Code (CEC) if an external
electrical source is utilized.
Field wiring connection with unit must meet or exceed
specifications of type T wire and withstand a 63_F (17_C)
temperature rise.
All Unit Sizes
inches (mm)
9 (229)
Page 4
Page 5
Locate & Level the Unit
The compact design of this furnace makes it ideal for a
basement or utility room installation. Choose a central
location for the furnace so that supply air ducts approximately the same length. This will allow each room to receive the proper amount of heat. The furnace should be
placed so that the flue connection to the chimney will be of
minimum length and have a minimum number of elbows.
1− Set the unit in desired location keeping in mind the
clearances listed in table 2. Also keep in mind oil supply connections, electrical supply, flue connections
and sufficient clearance for installing and servicing
unit.
2− Level the unit from side to side and from front to rear. If
the furnace is not level, place fireproof wedges or
shims between the low side of the furnace and the
floor. Make sure the weight of the furnace is distributed
evenly on all four corners. Strain on sides of cabinet
causing cracking and popping noises may occur if
weight of furnace is not evenly distributed.
Unit Adjustments
Neither the nozzle setting nor the air adjustments are factory set. The furnace is fire tested and the limit control is
checked to make sure it functions properly; no factory settings are made. During installation, the furnace must be
set up." The installing dealer/contractor must have and
use proper test equipment in order to correctly set up the oil
furnace. Proper testing equipment is required to ensure
correct operation of the unit. The use of test equipment is
now more critical than ever due to tighter tolerances needed to keep the furnace operating efficiently.
Among the test equipment for an oil furnace, the proper
combustion test kit should contain the following:
D Draft gauge
D CO
or O2 Analyzer
2
D Smoke tester
D Pressure gauge
D High temperature thermometer
D Oil vacuum gauge
D Beckett T−500 gauge
D Knowledge of proper test equipment operation
CAUTION
Improper nozzle and/or air adjustment of this unit
may result in sooting problems. Refer to the following section for correct adjustment procedures.
Nozzle Adjustment
Proper adjustment of the nozzle assembly is critical because
alignment may have changed during shipping. Before the furnace and oil lines are installed, the nozzle assembly must be
checked. This may easily be done by removing the entire
burner assembly (not just the nozzle) from the furnace. The
lower firing nozzle is factory installed. This should be verified
by the installer. Inspect the spark transformer leads also to
ensure they are still attached to the electrodes. Note that
OF23−105/120 and OF23−140/154 series units use the
Beckett AFII burner. OF23−175/210R series units use the
Beckett AFG burner.
The burner assembly is attached to the vestibule panel by
three nuts. Slots are provided in the mounting flange for removing the burner assembly from the vestibule. By loosening the nuts and by turning the whole burner assembly counterclockwise (figure 3), the entire burner assembly will come
out of the furnace. There is adequate wire to remove the
burner without disconnecting wires. Once removed, just turn
the burner around in the vest panel area.
OF23 Series Burner Removal
First, loosen three nuts which
attach burner to vest panel.
Next, rotate burner counter-
clockwise on slots then pull
toward you.
Figure 3
To correctly adjust the nozzle, use a Beckett #T−500 gauge.
Insert the small end of the gauge into the end of the cone
and measure from the flat of the end cone to the tip of the
nozzle. When nozzle depth is correct, the tip of the nozzle
should just touch the end of the gauge. Refer to the illustration sheet provided with the gauge. Note that the scale side
of the gauge is not used for this purpose. Corrections are
made by sliding the entire nozzle assembly forward or
backward within the blast tube (figure 4). At the same time,
nozzle alignment must be checked.
To check nozzle alignment, again insert the small end of
gauge into the end cone and measure the nozzle and
electrode alignment against the center lines marked on
the gauge (again refer to enclosed illustration sheet). If
the nozzle is not centered, but found to be too far left or
right, a new nozzle assembly will need to be ordered. Do
not attempt to adjust by bending the 90 degree elbow in
the oil line.
Page 5
Page 6
Beckett Oil Burner Nozzle Adjustment
Burner must be removed from
furnace for this procedure.
gauge
To Adjust Nozzle
1−Loosen screw.
2−Slide entire nozzle/electrode assembly back and forth until
nozzle just touches gauge.
2
1
Figure 4
Venting
WARNING
Combustion air openings in front of the furnace must
be kept free of obstructions. Any obstruction will
cause improper burner operation and may result in
a fire hazard.
WARNING
The barometric damper shall be in the same atmospheric pressure zone as the combustion air inlet to
the furnace. Deviation from this practice will cause
improper burner operation and may result in a fire
hazard.
Prior to installation of unit, make a thorough inspection of the
chimney to determine whether repairs are necessary. Make
sure the chimney is properly constructed and sized according to the requirements of the National Fire Protection Association. The smallest dimensions of the chimney should be
at least equal to the diameter of the furnace vent connector.
Make sure the chimney will produce a steady draft sufficient
to remove all the products of combustion from the furnace. A
draft of at least .04" w.c. (9.9 Pa) is required during burner
operation.
1 − Local building codes may have more stringent installa-
tion requirements and should be consulted before
installation of unit.
2 − The vent connector should be as short as possible to
do the job.
3 − The vent connector should not be smaller than the out-
let diameter of the vent outlet of the furnace.
4 − Pipe should be at least 24 gauge galvanized.
5 − Single wall vent pipe should not run outside or through
any unconditioned space.
6 − Chimney should extend 3 feet (0.9 m) above highest
point where the vent passes through the roof, and 2
feet (0.6 m) higher than any portion of a building within
a horizontal distance of 10 feet (3 m).
7 − The vent must not pass through a floor or ceiling.
Clearances to single wall vent pipe should be no less
than 6" (152 mm); more if local codes require it.
8 − The vent may pass through a wall where provisions
have been made for a thimble as specified in the Standards of the National Board of Fire Underwriters. See figure 5.
Wall Thimble
CAUTION
Do not store combustible materials near the furnace
or supply air ducts. The material (such as paint, motor oil, gasoline, paint thinner, etc.) may ignite by
spontaneous combustion creating a fire hazard.
WARNING
This furnace is certified for use with type L" vent.
B" vent must not be used with oil furnaces.
NOTE − Oil burning equipment may be vented into an approved masonry chimney or type L vent. (Type L vent is
similar in construction to type B gas vent except it carries a
higher temperature rating and is constructed with an inner
liner of stainless steel rather than aluminum).
thimble
combustible
wall
vent pipe
Figure 5
9 − The vent pipe should slope upward toward the chim-
ney on horizontal run at least 1/4 inch (6 mm) to the
foot (0.3 m) and should be supported by something
other than the furnace, such as isolation hangers. See
figure 6.
Page 6
Page 7
Front Flue / Masonry Chimney
barometric
control*
(in either location)
Rear Flue / Masonry Chimney
barometric
control*
(in either location)
clean out
liner
clean out
masonry
chimney
liner
clean out
15− All vent pipe run through unconditioned areas or out-
side shall be constructed of factory built chimney sections. See figure 7.
16− Where condensation of vent gas is apparent, the vent
should be repaired or replaced. Accumulation of condensation in the vent is unacceptable.
17− Vent connectors serving this appliance shall not be
connected into any portion of mechanical draft systems operating under positive pressure.
18− Keep the area around the vent terminal free of snow,
ice and debris.
NOTE − If vent pipe needs to exit from side of cabinet,
use the pilot hole (located on either side of the unit) to
cut a 6" (152 mm) round hole. Attach finishing plate
(provided) with four sheet metal screws to cover rough
edges.
Front Flue / Factory−Built Chimney
barometric
control*
(in either location)
factory
built
chimney
clean out
*Barometric control may be installed in either vertical or horizontal section of flue pipe within 18" of flue outlet of furnace.
masonry
chimney
Figure 6
10− Extend the vent pipe into the chimney so that it is flush
with the inside of the vent liner. Seal the joint between
the pipe and the liner.
11− The furnace shall be connected to a factory built chim-
ney or vent complying with a recognized standard, or
masonry or concrete chimney lined with a lining material acceptable to the authority having jurisdiction.
12− When two or more appliances vent into a common
vent, the area of the common vent should not be less
than the area of the largest vent or vent connection
plus 50% of the area of the additional vent or vent connection. Chimney must be able to sufficiently vent all
appliances operating at the same time.
13− The vent pipe shall not be connected to a chimney
vent serving a solid fuel appliance or any mechanical
draft system.
14− All unused chimney openings should be closed.
drain for
condensate
Rear Flue / Factory−Built Chimney
barometric
control*
(in either location)
*Barometric control may be installed in either vertical or horizontal section of flue pipe within 18" of flue outlet of furnace.
factory
built
chimney
drain for
condensate
Figure 7
Page 7
Page 8
Combustion and Ventilation Air
(Confined and Unconfined Spaces)
In the past, there was no problem in bringing in sufficient
amounts of outdoor air for combustion −− infiltration provided all the air that was needed and then some. In today’s
homes built with energy conservation in mind, tight
construction practices make it necessary to bring in air
from outside for combustion. Consideration must also be
given to the use of exhaust fans, appliance vents, chimneys and fireplaces because they force additional air that
could be used for combustion out of the house. Unless outside air is brought into the home for combustion, negative
pressure (pressure outside is greater than inside pressure)
will build to the point that a down draft can occur in the furnace vent pipe or chimney. Combustion gases enter the living space creating a potentially dangerous situation.
The importance of the previous paragraph cannot be overstated. Users may inadvertently block fresh air intakes after
installation.
In the absence of local codes concerning air for combustion and ventilation, the following section outlines guidelines and recommends procedures for operating oil furnaces in a manner that ensures efficient and safe
operation. Special consideration must be given to combustion air needs as well as requirements for exhaust vents
and oil piping.
Combustion Air Requirements
CAUTION
Insufficient combustion air can cause headaches,
nausea, dizziness or asphyxiation. It will also cause
excess water in the heat exchanger resulting in rusting and premature heat exchanger failure. It can also
cause property damage.
All oil-fired appliances require air to be used for the combustion process. If sufficient amounts of combustion air are
not available, the furnace or other appliance will operate in
an inefficient and unsafe manner. Enough air must be provided to meet the needs of all fuel-burning appliances, as
well as appliances such as exhaust fans which force air out
of the home. When fireplaces, exhaust fans, or clothes dryers are used at the same time as the furnace, much more
air is required to ensure proper combustion and to prevent
a down-draft situation. Insufficient amounts of air also
cause incomplete combustion which can result in sooting.
Requirements for providing air for combustion and ventilation depend largely on whether the furnace is installed in an
unconfined or confined space.
space. This space also includes adjacent rooms which are
not separated by a door. Though an area may appear to be
unconfined, it might be necessary to bring in outdoor air for
combustion if the structure does not provide enough air by
infiltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around
the windows and doors, follow the procedures outlined for
using air from the outside for combustion and ventilation.
Confined Space
A confined space is an area with volume less than 50 cubic
feet (1.4 cubic meters) per 1,000 Btu (293 W) per hour of
the combined input rating of all appliances installed in that
space. This definition includes furnace closets or small
equipment rooms.
When the furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space containing the furnace, the return air must be handled by ducts
which are sealed to the furnace casing and which terminate
outside the space containing the furnace. This is especially
important when the furnace is mounted on a platform in a
confined space such as a closet or small equipment room.
Even a small leak around the base of the unit at the platform
or at the return air duct connection can cause a potentially
dangerous negative pressure condition. Air for combustion
and ventilation can be brought into the confined space either from inside the building or from outside.
Air from an Adjacent Space
If the confined space housing the furnace adjoins space
categorized as unconfined, air can be brought in by providing two permanent openings between the two spaces.
Each opening must have a minimum free area of 1 square
inch
(6.4 square centimeters) per 1,000 Btu (293 W) per
hour of the total input rating of all fuel-fired equipment in the
confined space. Each opening must be at least 100 square
inches (614.5 square centimeters). One opening shall be
within 12" (305 mm) of the top of the enclosure and one
opening within 12" (305 mm) of the bottom (See figure 8).
Equipment In Confined Space
All Air From Inside
Chimney or
t
Oil Ven
Oil
Furnace
Water
Heater
Openings
(To Adjacent Room)
Unconfined Space
An unconfined space is an area such as a basement or
large equipment room with a volume greater than 50 cubic
feet (1.4 cubic meters) per 1,000 Btu (293 W) per hour of
the combined input rating of all appliances installed in that
Page 8
NOTE−Each opening shall have a free area of at least 1 square inch
(6.4 square centimeters) per 1,000 Btu (293 W) per hour of the total
input rating of all equipment in the enclosure, but not less than 100
square inches
(614.5 square centimeters).
Figure 8
Page 9
Air from Outside
If air from outside is brought in for combustion and ventilation, the confined space shall be provided with two permanent openings. One opening shall be within 12" (305 mm)
of the top of the enclosure and one within 12" (305 mm) of
the bottom. These openings must communicate directly or
by ducts with the outdoors or spaces (crawl or attic) that
freely communicate with the outdoors or indirectly through
vertical ducts. Each opening shall have a minimum free
area of 1 square inch (6.4 square centimeters) per 4,000
Btu (1172 W) per hour of total input rating of all equipment
in the enclosure (See figures 9 and 10). When communicating with the outdoors through horizontal ducts, each
opening shall have a minimum free area of 1 square inch
(6.4 square centimeters) per 2,000 Btu (586 W) per total input rating of all equipment in the enclosure (See figure 11).
Equipment In Confined Space
(Inlet Air from Crawl Space and Outlet Air to
Chimney or
Oil Vent
Oil
Furnace
Ventilation
Louvers
(For unheated
crawl space)
NOTE−The inlet and outlet air openings shall each have a free area of
at least one square inch (6.4 square centimeters) per 4,000 Btu (1172
W) per hour of the total input rating of all equipment in the enclosure.
All Air From Outside
Ventilated Attic)
Ventilation Louvers
(Each End Of Attic)
Outlet
r
Ai
Water
Heater
Inlet
Air
Equipment In Confined Space
All Air From Outside
Chimney
Or Oil
Vent
Oil
Furnace
NOTE−Each air duct opening shall have a free area of at least one
square inch (6.4 square centimeters) per 2,000 Btu (586 W) per hour
of the total input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings
communicate directly with the outdoors, each opening shall have a
free area of at least one square inch (6.4 square centimeters) per
4,000 Btu (1172 W) per hour of the total input rating of all other equipment in the enclosure.
Water
Heate
r
Outlet Air
Inlet Air
Figure 11
When ducts are used, they shall be of the same cross−sectional area as the free area of the openings to which they
connect. The minimum dimension of rectangular air ducts
shall be no less than 3" (76 mm). In calculating free area,
the blocking effect of louvers, grilles, or screens must be
considered. If the design and free area of protective covering is not known for calculating the size opening required, it
may be assumed that wood louvers will have 20 to 25 percent free area and metal louvers and grilles will have 60 to
75 percent free area. Louvers and grilles must be fixed in
the open position or interlocked with the equipment so that
they are opened automatically during equipment operation.
Figure 9
Equipment In Confined Space
All Air From Outside
(All Air Through Ventilated Attic)
Chimney
or Oil
Vent
Outlet
Air
Oil
Furnace
NOTE−The inlet and outlet air openings shall each have a free area of at
least one square inch (6.4 square centimeters) per 4,000 Btu (1172 W)
per hour of the total input rating of all equipment in the enclosure.
Ventilation Louvers
(Each End Of Attic)
Figure 10
Inlet Air
(Ends 12"
Above Bottom)
Water
r
Heate
CAUTION
Combustion air openings in the front of the furnace
must be kept free of obstructions. Any obstruction
will cause improper burner operation and may result
in a fire hazard or injury.
CAUTION
The barometric control shall be in the same atmospheric pressure zone as the combustion air inlet to
the furnace. Deviation from this practice will cause
improper burner operation and may result in a fire
hazard or injury.
Direct Connection of Outdoor Air for Combustion
The Beckett AFII burner was designed to allow for direct air
intake piping (4" [102 mm]). The maximum equivalent
length of pipe is 70 feet (21.3 m). A 90_ elbow equals 6 feet
(1.8 m). The enclosed intake pipe ring may be used to facilitate direct air intake to the burner through the right side of
the cabinet. The AFG burner requires a special kit for direct
air intake. Refer to kit instructions.
Page 9
Page 10
To convert the AFII burner from confined space to outside
combustion air, remove the three screws which attach the
inlet air scoop to the burner and insert 4" (102 mm) direct air
intake piping.
The use of a barometric relief placed in the intake pipe is
recommended when outdoor combustion air is directly
connected to the burner. This will allow confined space air
to be used as combustion air in the event that the opening
to the outdoor air becomes blocked. Use a barometric relief
in the intake to reduce the chance of sooting.
CAUTION
DO NOT USE a barometric draft relief in exhaust vent
pipe if outdoor combustion air is connected directly
to the burner.
Removal of Unit from Common Venting System
In the event that an existing furnace is removed from a
venting system commonly run with separate appliances,
the venting system is likely to be too large to properly vent
the remaining attached appliances. The following test
should be conducted while each appliance is in operation
and the other appliances not in operation remain connected to the common venting system. If venting system
has been installed improperly, the system must be corrected as outlined in the previous section.
1 − Seal any unused openings in the common venting
system.
2 − Visually inspect venting system for proper size and
horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion or other deficiencies
which could cause an unsafe condition.
3 − Insofar as is practical, close all building doors and win-
dows and all doors between the space in which the appliances remaining connected to the common venting
system are located and other spaces of the building.
Turn on clothes dryers and any appliances not connected to the common venting system. Turn on any
exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not
operate a summer exhaust fan. Close fireplace dampers.
4 − Following the lighting instruction on the unit, place the
appliance being inspected in operation. Adjust thermostat so appliance will operate continuously.
5 − Test for spillage using a draft gauge.
6 − After it has been determined that each appliance re-
maining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers and
any other fuel burning appliance to its previous condition of use.
7− If improper venting is observed during any of the
above tests, the common venting system must be corrected.
Horizontal Venting
The OF23 is approved for horizontal venting with the following mechanical vent systems:
Tjernlund (sideshot) #SS1C (Cat. #35E08) or Field Controls #SWG−5 (Cat. #35P08) with the CK−61 (Cat. #18N28)
control kit. Refer to the manufacturers’ installation instructions for proper installation procedures and service parts
information.
The barometric draft control must be installed within 18
inches of the furnace flue outlet. See figure 12 for barometric draft control location.
Do not common vent with any other appliance when using
sidewall vent system.
The maximum equivalent length of pipe is 70 equivalent
feet. A 90_ elbow equals 6 ft. Minimum length is 15 equiva-
lent feet. Calculate the equivalent vent pipe footage from
the furnace to the mechanical vent system (Tjernlund or
Field Controls) by adding the straight vent pipe length and
the equivalent elbow lengths together.
Front Flue / Horizontal Venting
barometric
control*
control for
horizontal
venting
Rear Flue / Horizontal Venting
barometric
control*
horizontal
venting
control
*Barometric control must be installed in the horizontal venting
system and located within 18" of flue outlet of furnace.
Figure 12
Page 10
Page 11
Flue Connections
IMPORTANT
When flue pipe is installed at less than minimum
clearance listed in table 2, radiation shields must be
installed. See 13.
Radiation Shield Installation
combustible
material
unit
cabinet
noncombustible
spacers
A
see note 2
OF23 unit
(top)
radiation
shields
A
radiation shields
(see note 1)
flue
pipe
1" (25 mm)
min
12" (305 mm)
min
7" (178 mm)
min
B
see note 3
vent connector, plus 50% of the area of any additional flues
or vent connectors. Install the barometric draft control (provided) and flue pipe according to instructions packed with
control.
Inspect flue pipe annually. Clean soot or ash from flue pipe,
if necessary. If pipe is rusted, replace.
Install draft control at least 12 inches beyond the furnace. If
there is no space to install the draft control in the flue pipe it
may be installed in the vent above the flue pipe. Follow the
instructions packed with the draft control.
Alternate Side Flue Connections
The vent pipe may exit the top or sides of the cabinet. A
hole is provided in the top cap for top exit. For side exit, locate the center hole punched in the side of the cabinet. See
unit dimensions on page 2. Using it as the center point, cut
a 6 inch (152 mm) round hole in the cabinet’s side. Using it
as the center point, cut a 6 inch (152 mm) round hole in the
cabinet’s side. Install the barometric draft control within 18
inches of the furnace flue outlet. Attach the provided finishing plate to cover rough edges.
Supply & Return Air Plenums
Secure return air plenum to unit using sheet metal screws.
NOTE − The following are suggested procedures that
should be followed when installing the supply air plenum.
1− Use sealing strips of fiberglass.
2− In all cases, the plenum should be secured to furnace
or evaporator cabinet with sheet metal screws.
3− Install supply and return air ducts as desired.
of23 unit
(front)
NOTE 1−Radiation shields must be constructed of 24 gauge sheet
metal minimum.
NOTE 2−Radiation shields required when A is less than 9" (229 mm).
NOTE 3−Radiation shields should extend from the top of the unit to
the top of the flue pipe.
Figure 13
For front flue models, the enclosed exhaust pipe ring may
be used for pipe to exit the left or right side of cabinet. Center line marks are provided in cabinet.
Use 24 gauge or heavier galvanized smoke pipe and fittings to connect furnace to vent. Connect flue pipe to chimney using the least number of elbows and angles possible.
Flue pipe or vent connector must be inserted into but not
beyond the outside wall of the chimney flue. No reduction in
diameter of flue pipe is acceptable. It is best to have flue
pipe as short and direct as possible. Where two or more appliances vent into a common flue, the area of the common
flue should be at least equal to the area of the largest flue or
Oil Supply Lines Sizing
Ensure that the restrictions of the piping system, plus any
lift involved, do not exceed the capability of the oil pump.
Use the following guidelines when determining whether to
use a single−or two−stage oil pump.
One−Pipe System
When using a one−pipe system with the oil tank above the
burner and a vacuum of 6" (152 mm) Hg or less, a single−
stage fuel pump with a supply line and no return line should
be adequate. See figure 14. Manual bleeding of the fuel
pump is required on initial start up. Failure to bleed air from
the oil pump could result in an air lock/oil starvation condition.
NOTE − As an extra precaution, cycle heating on and off ten
times after bleeding air from the oil pump. This will eliminate air in the gun assembly.
To determine the length of the run for piping, refer to table 2
.
Page 11
Page 12
air vent
fill
pipe
Oil Piping
One-Pipe System
pump
fuel
Aux
Filter
Use continuous lengths of heavy wall copper tubing or
steel pipe for oil supply pipe. Install oil supply pipe under
floor or near walls to protect it from damage. Avoid running
pipes along joists or reverberating surfaces. Always use
flare fittings. All fittings must be accessible. Do not use
compression fittings.
Oil
Tank
Shut−off
Valve
8 ft (2.4 m)
Maximum
One Pipe Lift
Figure 14
Table 2
One−Pipe Oil Sizing
Line Length
Pipe Diameter (OD Tubing)
0−50’ (15 m)3/8" (10 mm)
51−100’ (15 m)1/2" (12 mm)
Two−Pipe System
When using a two−pipe system with the oil tank below the
level of the burner, a single−stage fuel pump should be used
in lift conditions of up to 10 feet (3 m) and/or a vacuum of
10" (254 mm) Hg or less. See figure 15. Use a two−stage
fuel pump when lift exceeds 10 feet (3 m) and/or a vacuum
of 10" (254 mm) Hg to 15" (381 mm) Hg.
Both conditions require that you use of a two−pipe system,
which consists of a return line that purges the fuel pump of
air by returning it to the tank. To determine the run and lift for
piping, refer to table 3 .
Oil Piping
Two-pipe System
Air Vent
Fill
Pipe
Return
pipe
Oil
Tank
3"−4"
(76 mm −102 mm)
Return
pipe
outside tank fuel pump above bottom of tank
R
fuel
pump
Aux
Filter
Inlet
H
Figure 15
IMPORTANT
Both oil supply and return pipes must be submerged
in oil in the supply tank.
Table 3
Two−Pipe Maximum Pipe Length (H + R)
3450 RPM − 3 GPH (11.4 LPH)
Lift H"
0’
(0.0 m)
2’
(0.6 m)
4’
(1.2m)
6’
(1.8m)
8’
(2.4m)
10’
(3.0m)
12’
(3.7m)
14’
(4.3m)
16’
(4.9m)
18’
(5.5m)
3/8" (10 mm) OD
Tubing
Single
Stage
84’
(25.6 m)
73’
(22.3 m)
63’
(19.2 m)
52’
(15.8 m)
42’
(12.8 m)
31’
(9.4 m)
21’
(6.4 m)
−−−
−−−
Two
Stage
93’
(28.3 m)
85’
(25.9 m)
77’
(23.5 m)
69’
(21.0 m)
60’
(18.3 m)
52’
(15.9 m)
44’
(13.4 m)
36’
(11.0 m)
27’
(8.2 m)
−−−−−−−−−
Oil Supply Line & Filter Connections
One−Pipe Systems
CAUTION
Do not install the bypass plug into the pump on one−
pipe systems.
The burner is shipped with fuel pump set for one−pipe operation. For one−pipe systems, the oil supply pipe is connected to the inlet tap on the pump. A one−pipe system
should only be used where there is gravity oil flow to the
pump and the pipe is not run at any point above the oil level
in the tank.
1/2" (12 mm) OD
Tubing
Single
Stage
100’
(30.5 m)
100’
(30.5 m)
100’
(30.5 m)
100’
(30.5 m)
100’
(30.5 m)
100’
(30.5 m)
83’
(25.3 m)
41’
(12.5 m)
−−−
Two
Stage
100’
(30.5 m)
100’
(30.5 m)
100’
(30.5 m)
100’
(30.5 m)
100’
(30.5 m)
100’
(30.5 m)
100’
(30.5 m)
100’
(30.5 m)
100’
(30.5 m)
(23.2 m)
76’
Page 12
Page 13
1 − Connect the inlet pipe to the pump inlet. Start the burner.
2 − Arrange the primary burner control for continuous op-
eration during purging. See figure 14.
3 − Turn the bleed valve one turn counterclockwise.
4 − Bleed the unit until all air bubbles disappear.
NOTE − Hurried bleeding will prevent the unit from operating properly.
Table 4
Oil Filters (All Models)
Oil Filters
10 micron filter (no mounting bracket)81P89
10 micron filter (mounting bracket)53P92
10 micron replacement cartridge for filter, 45 gph53P93
Cat.
Number
5 − Tighten the bleed valve securely.
Two−Pipe Systems
If the installation requires a two−pipe operation, install the
bypass plug included in the bag which is attached to the
pump. To convert the pump, install the bypass plug according to the provided pump instructions. Notice in the two-pipe
system the return pipe must terminate in the tank 3" (76 mm)
to 4" (102 mm) above the supply inlet. Ensure the return pipe
terminates at the correct measurement or air may escape
into the system. This could result in loss of prime.
NOTE− If using an outside tank in cold climates a number
one fuel or an oil treatment is strongly recommended.
1 − Remove 1/4" plug from return port.
2 − Insert bypass plug and tighten it. See figure 15.
3 − Attach the return and inlet pipes. Start the burner. Air
bleeding is automatic.
NOTE − If a faster bleed is necessary, open the bleed
valve.
4 − The return pipe must terminate 3" to 4" above the sup-
ply pipe inlet. See figure 15.
NOTE − If the return pipe does not terminate where it
should, air may enter the system, and prime may be
lost.
An oil filter is required for all models. Install filter inside
the building between the tank shut-off valve and the burner.
Locate filter close to burner for easy maintenance. Table 4
lists the filters for the OF23 furnace.
Consult the burner manufacturer’s instructions that are included with the unit for further details concerning oil supply
pipe connections.
Filter restriction indicator gauge53P90
Leak Check
After oil piping is completed, carefully check all piping connections (factory and field) for oil leaks.
Oil Line Heater (Optional)
A heater for the oil pipe is available for applications that are
located in cold climates. The heater warms the oil pipe to
assist the initial start−up.
Electrical Wiring
All wiring must conform to the National Electric Code
(NEC), or Canadian Electric Code (CEC) and any local
codes. Refer to figure 16 for terminal designations on fan
control board.
1− Refer to appliance rating plate for proper fuse size.
2− Install room thermostat and make wire connections to
the fan control board. Avoid installing thermostat on an
outside wall or where it can be affected by radiant heat.
Set the adjustable heat anticipator on thermostat according to the wiring diagram sticker provided on unit.
3− Install a separate fused disconnect switch near unit so
power can be shut off for servicing.
4− Complete line voltage wiring from disconnect switch
near unit to make-up box.
NOTE − An equipment ground screw is provided. Refer
to unit wiring diagram and figure 16 for OF23 series
units. Ground unit using a suitable ground wire.
5− Any accessory rated up to 1 amp can be connected to
the accessory terminal. The accessory terminal is energized when the blower is in operation.
Page 13
Page 14
Fan Control Board
thermostat
terminal strip
Figure 16
Typical OF23 Wiring Diagram
Figure 17
Page 14
Page 15
Typical OF23 Wiring Diagram
Figure 18
Page 15
Page 16
Start−Up & Adjustment
Before starting unit, make sure the oil tank is adequately
filled with clean No. 1 or No. 2 furnace oil.
NOTE − Water, rust or other contaminants in oil supply system will cause malfunction and failure of the internal parts
of the fuel unit.
readings, subtract the readings. The difference in temperatures in the supply and return air plenums should approximate the temperatures listed in table 5 and the appliance
rating plate. If not, adjust the blower motor pulley to adjust
the blower speed.
Table 5
OF23
Unit
nozzle size,
spray, angle, &
pattern
input
rating
BTU/HR
output
rating
BTU/HR
headtemp
rise F°
CAUTION
Never burn garbage or paper in the heating system.
Never leave papers near or around the unit.
CAUTION
Blower access door must be in place before start-up.
1− Set thermostat for heating demand and turn on electri-
cal supply to unit.
2− Check initial air adjustment. All units are equipped with
an air adjustment dial on the right side of the burner.
See burner parts arrangement illustration.
3− Turn unit on. Place a can or container under the bleed
port located on the fuel pump. Loosen nut on bleed
port to release air and oil mixture from fuel line. Allow
mixture to escape until a steady stream of oil is emitted
from the port. Drain at least 1/2 pint of oil from the
pump. Retighten nut on bleed port.
NOTE − A two−line fuel system will normally bleed itself
by forcing air back to the tank through the return line.
This type of bleeding procedure is not necessary.
4− If burner fails to start, push reset button on primary
safety control and the burner motor reset button once.
See part arrangement illustration.
CAUTION
Do not push the reset button on the primary control
more than one time.
−105.65GPH- .80° B105,00085,000FB360
−105R.65GPH- .80° B105,00085,000FB365
−120*.75GPH-.80° B119,00097,000FB370
−120R*.75GPH−.80° B119,00097,000FB370
−140.85GPH- .80° B140,000113,000FB660
−140R.85GPH− .80° B140,000113,000FB665
−154*1.00GPH- .80° B154,000 125,000FB660
−154R*1.00GPH- .80° B154,000 125,000FB670
−1751.10GPH- .80° B175,000142,000FB670
−210R1.25GPH- .80° B210,000 166,000FB670
*Nozzle must be field provided for field conversion to higher
heating input.
Oil burner pump pressure is 140 psi for each unit.
C − Limit Control
Limit Control Do not adjust from factory setting.
D − Fan Control
The fan on time of 30 seconds is not adjustable. Fan off
time (time that the blower operates after the heat demand
has been satisfied) can be adjusted by moving the delay
switches on the fan control board. Fan off time will affect
comfort and is adjustable to satisfy individual applications.
See figure 19. Set the heat fan off delay switches to either
60, 90, 120, or 150 seconds. The factory setting is 90 seconds.
Delay Off Switch Settings
5− If burner fails to light again, refer to the troubleshooting
section in this manual.
A − Fuel Pump Pressure Adjustment
Measure fuel pump pressure with unit off. Attach pressure
gauge to pump outlet. Turn unit on and check pressure and
compare to table 3. Adjust if necessary.
B − Temperature Rise Adjustment
To measure temperature rise, place plenum thermometers
in warm air and return air plenums. Locate thermometer in
warm air plenum where thermometer will not see" the heat
exchanger to prevent it from picking up radiant heat. Set
thermostat to its highest setting to start unit. After plenum
thermometers have reached their highest and steadiest
Page 16
120 sec90 sec60 sec
150 sec
Figure 19
E − Burner Adjustment
The following instructions are essential to the proper operation of OF23 series oil furnaces. To prevent sooting,
these instructions must be followed in sequence:
1 − Draft
This test should be taken at the breach between the outlet
of the vent connector and the barometric draft control. Generally a 1/4" hole will need to be drilled for the draft gauge to
be inserted into the vent connector.
Page 17
A minimum of 0.03 draft must be established without the
burner in operation. With the burner in operation, the draft
should be 0.04 to 0.05. This is VERY critical to the flame
retention head burners.
the room air temperature from the stack temperature. This
will give you the net stack temperature. Use the efficiency
charts provided in most CO
analyzers to determine fur-
2
nace efficiency.
Oil furnace installations also require careful inspection to
make sure the chimney is in good shape and can accommodate the products of combustion. The temperature in
the unconditioned space will also affect the draft if long vent
connectors are allowed to get too cold.
2 − Overfire Draft
This test should be taken with the burner in operation. Remove the screw from the center of the inspection door. Insert your draft gauge into the hole.
A reading of the overfire draft should be 0.02 less than the
reading found in the vent connector. If a positive reading is
seen at this point, the combustion fan is pumping too much
air into the heat exchanger. Make the necessary adjustments at the air adjustment dial.
3 − Smoke Test
The smoke test should be taken at the hole drilled in step 1.
Using a smoke test gun adjust the air inlet shutter so that
you will have just a trace of smoke. Somewhere between 0
and #1 smoke. This is the starting point. Do not stop here.
4 − CO
Test
2
Again, take the sample at the vent pipe. With the unit firing
at a trace of smoke, take a sample of the CO
.
2
From the results of this test, a window of operation" will be
determined. This window of operation establishes some
tolerance. The tolerance the installer builds in provides
room within the set-up for those things which might affect
combustion. Those things which might affect combustion
can then do so without causing the unit to start sooting/
smoking. Things which might affect combustion include a
nozzle going bad, draft that changes during different climatic conditions, dirty oil, dirt obstructing the air inlet, etc.
To build in a window of operation," set up the burner to be
2% less in CO
CO
, adjust the air inlet shutter to increase the air and drop
2
the CO
to 10%.
2
. For example, if you find a reading of 12%
2
5 − Retest the Smoke
With a drop in the CO
and increase in the air you should
2
see that the smoke has returned to 0.
6 − Retest the Overfire Draft
This test serves to confirm that you have not increased the
air too much. Again you do not want a positive pressure at
the test port. It should still be 0.02 less than the draft pressure reading taken at the breach. You may need to
increase the stack draft by adjusting the barometric draft
control.
7 − Stack Temperature
Take a stack temperature reading in the vent pipe. Subtract
Service
A − Servicing Filter
NOTE − Under no circumstances should the access panels
to the blower compartment be left off or left partially open.
1− Throw-Away Type Filters Filters should be checked
monthly and replaced when necessary to assure proper furnace operation. Replace filters with like kind and
size filters.
2− Reusable Type Filters Filters should be checked
monthly and cleaned when necessary to assure proper furnace operation. Use warm water and a mild detergent. Replace filter when dry. Permanent filters
supplied with OF23 furnaces do not require oiling after
cleaning. Examine filter label for any for special instructions that may apply.
B − Blower
Blower motor is pre-lubricated and sealed for extended operation. No further lubrication is required. Disconnect power to unit before cleaning blower wheel for debris.
C − Flue Pipe Inspection
The flue pipe should be inspected annually by a qualified
service technician. Remove and clean any soot or ash
found in the flue pipe. Inspect pipe for holes or rusted
areas. If replacement is necessary, replace with the same
size and type as required by code. Inspect the flue draft
control device and replace if found defective.
D − Cleaning Heat Exchanger
1− Remove the vent pipe from the furnace.
2− Remove the locking screws and the caps from the
clean out tubes. Remove flue access elbow.
3− Using a long spiral wire brush, sweep down the outer
drum of the heat exchanger. Then using the hose attachment, vacuum out loose debris.
4− Remove the locking screw and cap from the observa-
tion tube and with the spiral wire brush, reach upward
toward the rear of the heat exchanger to clean out the
crossover tube.
CAUTION
Do not attempt to clean the combustion chamber. It
can be easily damaged.
5− Replace the clean out caps and flue access elbow.
Make sure locking screws are secure.
6− Brush out and vacuum the vent outlet area of the outer
drum and replace vent pipe.
7− Clean around burner, blower deck and vestibule area.
NOTE − A heat exchanger clean-out kit ABRSH380
(35K09) is available from Lennox.
Page 17
Page 18
Troubleshooting
Burner failure or improper operation can result from a number of different causes.
Often the cause can be pinpointed by observing the different types of failure or by the process of elimination. The fol-
Troubleshooting: Fan Board Operating Sequence
ActionSystem Response
lowing troubleshooting charts list some failures, causes
and a sequence of steps to isolate the point of failure.
Check the simplest and most obvious items before progressing to other items.
Thermostat calls for heat.
(W terminal is energized.)
Thermostat ends call for heat.
(W terminal is de−energized.)
Burner fails to light.Oil primary control locks out within lockout timing (timing depends on oil primary control).
Established flame fails.Burner motor is de−energized and oil primary control goes into recycle mode.
Thermostat begins call for cool.
(G and Y terminals are energized.)
Thermostat ends call for cool.
(G and Y terminals are de−energized.)
Thermostat begins call for fan.
(G terminal is energized.)
Thermostat ends call for fan.
(G terminal is de−energized.)
ST9103A closes oil primary control T−T connections.
Ignition system and oil primary control start the furnace. Oil flows as long as oil primary
control senses flame.
Burner motor is energized and heat fan on delay timing begins. When timing is complete,
the circulating fan is energized at heat speed and warm air is delivered to the controlled
space.
Oil primary control is de−energized, terminating the burner cycle.
Heat fan off delay timing begins. When timing is complete, the circulating fan is de−energized.
ST9103A returns to standby mode (oil primary control and circulating fan are off).
Burner motor is de−energized.
If heat fan has started, it continues through the selected delay off period.
If selected heat fan off delay is longer than the recycle delay timing, the heat fan continues to run through the next trial for ignition.
Circulating fan is energized at the cool speed.
Cooling compressor turns on immediately.
Circulating fan and cooling compressor turn off immediately.
Circulating fan is energized immediately at cool speed.
ST9103A may be factory−configured to operate heat speed in this mode.
Circulating fan is de−energized.
Limit switch string opens.Oil primary control shut off the burner.
Limit switch string closes.ST9103A begins heat fan off delay sequence.
Continuous circulating fan is connected.
(Optional connectors are available for separate circulating fan speed tap.)
Electronic air cleaner is connected.
(Optional connectors are available for 120 Vac electronic air cleaner.)
Humidity control is connected.
(Optional connectors are available for 120 Vac humidifier.)
Circulating fan is energized immediately at heat speed.
ST9103A opens oil primary control T−T connections.
Circulating fan runs as long as limit string stays open.
If there is a call for cooling or fan, the circulating fan switches from heat speed to cool
speed.
Circulating fan turns off after the selected heat fan off delay timing.
ST9103A closes oil primary control T−T connections.
Oil primary control is energized, initiating burner light off.
Circulating fan is energized at low speed when there is no call for heat, cool or fan.
If fan operation is required by a call for heat, cool, or fan, the ST9103A switches off the
continuous fan speed tap before energizing the other fan speed.
Electronic air cleaner (EAC) connections are energized when the heat or cool speed of
the circulating fan is energized. EAC connections are not energized when the optional
continuous fan terminal is energized.
Humidifier connections are energized when the burner motor is energized.
Page 18
Page 19
Troubleshooting: Burner fails to start.
y
yy
Check f
t
Thermostat
ostatteasopay
fault is in the thermostat circuit
the burner starts, fault is in the
Pri
ili
l
indicat
black
hite leads to th
p
blower wheel by hand. If seized,
power to the motor and burner
SourceProcedureCausesCorrection
Thermostat in OFF or COOLSwitch to HEAT.
ThermostatCheck thermostat settings.
Check burner motor, primary
Safety Overloads
Power
CAD Cell
Primary Control
Burner
safety control, & auxiliary limit
switch.
urnace disconnec
switch & main disconnect.
Touch jumper wire across thermostat terminals on primary
control. If burner starts, then
Disconnect the flame detector
wires at the primary control. If
detector circuit.
Place trouble light between the
black and white leads. No light
es that no power is going
to the control.
Place trouble light between the
orange and white leads. No light
indicates faulty control.
Place the trouble light between
the black and white leads to the
burner motor. No light indicates
that no power is getting to the
motor.
Place trouble light between the
and w
blower motor. Light indicates
ower to the motor and burner
fault.
Thermostat is set too low
Burner motor overload trippedPush reset button pump motor.
Primary control tripped on safety
Auxiliary limit switch tripped on
safety
Open switchClose switch.
Blown fuse or tripped circuit
breaker
Broken or loose thermostat
wires
Loose thermostat screw connection
Dirty thermostat contactsClean contacts.
.
Thermostat not levelLevel thermostat.
Faulty thermostatReplace thermostat.
Flame detector leads are
shorted
Flame detector exposed to lightSeal off false source of light.
short circuit in the flame detector
mary or aux
switch is open
Open circuit between disconnect switch and limit control
Low line voltage or power failure
Defective internal control circuitReplace the control.
Blown fuseReplace the fuse.
Binding burner blower wheel
e
Sized fuel pump
Defective burner motorReplace the motor.
ary contro
Turn thermostat to higher temperature.
Reset primary control.
Reset auxiliary limit.
Replace fuse or reset circuit
breaker.
Repair or replace wires.
Tighten connection.
Separate leads.
Replace detector.
Check adjustment. Set the
maximum setting.
Jumper terminals; if burner
starts, switch is faulty, replace
control.
Trace wiring and repair or replace it.
Call the power company.
Turn off power and rotate the
blower wheel by hand. If seized,
free the wheel or replace the
fuel pump.
Page 19
Page 20
Troubleshooting: Burner starts, but no flame is established.
Otes&Oe
Start the b
ilk
Air leak i
pggpp
pray (g
serve the oil spray (gun assem
spectteoeopugged
t
Cl
gap
the gap to 5/32 inches and cor-
g
to transformer primary
pp
ing or excessive drag
SourceProcedureCausesCorrection
Oil Supply
Oil Filters & Oil Line
Oil Pump
Check tank gauge or use dip
stick.
Coat dip stick with litmus paste
and insert into bottom of tank.
Listen for pump whine.Tank shut−off valve closedOpen valve.
Listen for pump whine.
Open bleed valve or gauge port.
urner. No oil or m
oil indicates loss or prime.
Install pressure gauge on pump
and read pressure. Should not
be less than 140 psi.
No oil in tankFill tank.
Water in oil tank
Oil line filter is pluggedReplace filter cartridges.
Kinks or restriction in oil lineRepair or replace oil line.
Plugged fuel pump strainerClean strainer or replace pump.
y
Pump is partially or completely
frozen. No pressure and the
motor locks out on overload.
Coupling disengaged or broken
− no pressure
Fuel pressure too lowAdjust to 100 psi.
n oil supply line
If water depth exceeds 1 inch,
pump or drain water.
Locate and correct leak.
Tighten all connections.
Replace pump.
Re−engage or replace coupling.
Nozzle
Ignition Electrodes
Ignition
Transformer
Burner Motor
Disconnect ignition leads. Observe the oil s
bly must be removed from unit).
Inspect the nozzle for plugged
orifice or carbon build−up around
orifice.
Remove gun assembly and inspect electrodes and leads.
Connect ignition leads to the
transformer. Start burner and observe spark. Check line voltage
Motor does not come up to
speed and trips out on overload.
Turn off power and rotate blower
wheel by hand to check for bind-
un assem-
.
.
Nozzle orifice plugged
Nozzle strainer plugged
Poor or off center spray
Fouled or shorted electrodes
Dirty electrodes and leads
Eroded electrode tips
Improper electrode gap spacing
Improper position of electrode
tips
Bad buss bar connectionRetension and realign.
Cracked or chipped insulatorsReplace electrode.
Cracked or burned lead insulators
Low line voltage
Burned out transformer windings.
No spark or weak spark
Low line voltage
Pump or blower overloading
motor
Faulty motorReplace motor.
Replace nozzle with the same
size, spray angle, and spray
ype.
ean electrode leads.
Clean electrode tips and reset
the
rectly position tips.
Replace electrode leads.
Check voltage at power source.
Correct cause of voltage drop
or call the power company.
Replace the transformer.
Properly ground the transformer
case.
Check voltage at power source.
Correct cause of voltage drop
or the call power company.
Correct cause of overloading.
to 5/32 inches and cor-
Page 20
Page 21
Troubleshooting: Burner starts and fires, but lock out on safety.
due to poor
,
If fire is good
fault may be
p
After burner
,
If fire is good
Fl
detector termi-
in the fuel sys
SourceProcedureCausesCorrection
Unbalanced fireReplace nozzle
Reduce combustion air − check
combustion.
Increase combustion air − check
combustion.
Adjust barometric damper for
correct draft.
Correct draft or remove restriction.
Replace cad cell.
Secure connections or replace
cad cell holder and wire leads.
Poor Fire
Flame Detector
Primary Control
After burner
fires, immediately jumper
across flame
detector terminals at the primary control.
If burner continues to run,
this may be
fire. Inspect
fire.
If fire is good
fault is in the
flame detector.
Check detector circuit.
If burner locks
out on safety,
fault is in the
primary control.
,
Too much air − −lean short fire
Too little air − − long dirty fire
Excessive draft
Too little draft or restriction
Dirty cad cell faceClean cad cell face.
Faulty cad cell − exceeds 15000
hms
Loose or defective cad cell
wires
Primary control circuit defectiveReplace primary control.
Troubleshooting: Burner Starts and Fires, but Loses Flame and Lock Out on Safety
SourceProcedureCausesCorrection
Unbalanced fireReplace nozzle
Poor Fire
ame Detector
Oil Supply
After burner
fires, immediately jumper
across flame
detector terminals at the primary control.
Listen for pump whine
If burner continues to run
(does not lock
out of safety),
due to poor
fire. Inspect
fire.
If fire is good
fault is in the
flame detector.
Check detector circuit.
If burner loses
flame (does
not lock out on
safety), fault is
in the fuel system.
,
Too much air − − lean short fire
Too little air − − long dirty fire
Excessive draft
Too little draft or restriction
Dirty CAD cell faceClean CAD cell face.
Faulty CAD cell − − exceeds
15000 hp
Loose or defective cad cell
wires
Pump loses prime − air slugPrime pump at bleed port
Pump loses prime − air leak in
supply line
Water slug in lineCheck oil tank for water (over 1
Partially plugged nozzle or
nozzle strainer
Restriction in oil lineClear restriction.
Plugged fuel pump strainerClean strainer or replace pump.
Cold oil − outdoor tankChange to number 1 oil.
Reduce combustion air − check
combustion.
Increase combustion air − check
combustion.
Adjust barometric damper for
correct draft.
Correct draft or remove restriction.
Replace CAD cell.
Secure connections or replace
cad cell holder and wire leads.
Check supply line for loose connections and tighten fittings.
inch) pump or drain out water.
Replace nozzle.
Page 21
Page 22
Troubleshooting: Burner starts and fires, but short cycles (too little heat)
Thermostat
Check thermostat
(
Limit Control
control (black & white leads). If
P
If burner turns
Thermostat
the th
t
scoect
circuit.
wires at the pri
SourceProcedureCausesCorrection
Heat anticipator set too lowCorrect heat anticipator setting.
ThermostatCheck thermostat.
Connect voltmeter between line
voltage connections to primary
Limit Control
ower
control
burner cycles due to power interruption, it is cycling on limit.
If voltage fluctuates, fault is in the
power source. Recheck voltage
at the power source.
black & white leads). If
.
Vibration at thermostatCorrect source of vibration.
Thermostat in the path of a
warm air draft
Dirty furnace air filtersClean or replace filter.
Burner running too slow
Blower motor seized or burned
out
Blower bearings seizedReplace bearings and shaft.
Blower wheel dirtyClean blower wheel.
Blower wheel in backwardReverse blower wheel.
Wrong motor rotation
Restrictions in return or supply
air system
Adjustable limit control set too
low
Loose wiring connectionLocate and secure connection.
Low or fluctuating line voltageCall power company.
Shield thermostat from draft or
relocate.
Increase blower speed to maintain proper temp. rise.
Replace motor.
Replace with properly rotating
wheel.
Correct cause of restriction.
Reset limit to maximum stop
setting.
Troubleshooting: Burner runs continuously (too much heat).
SourceProcedureCausesCorrection
Thermostat
Primary control
Disconnect
thermostat
mary control.
If burner turns
off, fault is in
ermosta
circuit.
-
-
If burner does
not turn off,
fault is in the
primary control.
Shorted or welded thermostat
contacts
Stuck thermostat bimetal
Thermostat not levelLevel thermostat.
Shorted thermostat wiresRepair short or replace wires.
Thermostat out of calibrationReplace thermostat.
Thermostat in cold draft
Defective primary control
Repair or replace the thermostat.
Clear obstruction or replace
thermostat.
Correct draft or relocate the
thermostat.
Replace the defective primary
control.
Page 22
Page 23
Troubleshooting: Burner runs continuously (too little heat).
L
CO
l
Dirt
g
Check b
reading more
CO2, stack tem
High stack tem
550 F Net.
Oil P
Inspect fire and check
SourceProcedureCausesCorrection
Too much combustion airReduce combustion air.
Combustion
ressure
urner
combustion for
CO2, stack temperature, and
smoke
Inspect fire and check
oil pressure.
Air leaks into heat exchanger
ow
2
than 10%.
ess
around inspection door, etc.
Excessive draft
Incorrect burner head adjustment
y or plugged heat exchanger
High smoke
readin
more
Insufficient draftIncrease draft.
than a trace.Incorrect burner head adjust-
ment
Too little combustion airIncrease combustion air.
Too little blower air
Blower belt too loose (if
High stack temperature is
more than
_F Net.
550
equipped)
Dirty or plugged heat exchanger Clean heat exchanger.
Dirty blower wheelClean blower wheel.
Dirty furnace air filtersClean or replace filter.
Restricted or closed registers or
dampers
Partially plugged or defective
nozzle
Oil pressure is too low: less
than 100 psi.
Correct cause of air leak.
Adjust barometric draft control for correct draft.
Correct burner head setting.
Clean heat exchanger.
Readjust burner.
Correct burner setting.
Increase blower speed to
maintain proper temp. rise.
Tighten blower belt.
Readjust registers or dampers.
Replace nozzle.
Increase oil pressure top
100psi.
Page 23
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.