Lennox O23Q3-105, O23Q3-120, O23Q5-140, O23Q5-154, OHR23Q3-105 Unit Information

...
Page 1
Corp. 9535−L8
Service Literature
Revised 09/2003
O23 (Elite 80) series units are mid−efficiency upflow oil fur naces manufactured with Beckett oil burners. O23 units are available in heating capacities of 70,000 to 154,000 Btuh (20.5 to 45.1 kW) and cooling applications from 2 through 5 tons (7.0 through 17.6 kW). Refer to Engineering Hand book for proper sizing.
OHR23 (Elite 80) series units are mid−efficiency horizontal / downflow oil furnaces. The OF23 (Elite 80) series units are mid−efficiency loboy upflow oil furnaces, which come in front (OF23) or rear (OF23R) flue openings, both with Beckett oil burners. The OHR23 and OF23(R) units are available in heat ing capacities of 105,000 to 154,000 Btuh (30.8 to 45.1 kW) and cooling applications from 2 through 5 tons (7.0 through
17.6 kW). Refer to Engineering Handbook for proper siz ing.
The drum type heat exchanger comes with strategically placed ports allowing easy cleaning, while the oil burner can be removed for inspection and service. The mainte nance section gives a detailed description on how this is done.
O23/OHR23
OF23
Information contained in this manual is intended for use by experienced HVAC service technicians only. All specifica tions are subject to change. Procedures outlined in this manual are presented as a recommendation only and do not supersede or replace local or state codes.
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at discon nect switch(es). Unit may have multiple power supplies.
WARNING
Improper installation, adjustment, alteration, ser vice or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer or service agency.
O23 SHOWN
TABLE OF CONTENTS
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Indoor Blower Data 4. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts Arrangement 5. . . . . . . . . . . . . . . . . . . . . . . . . . . .
I Unit Components 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
II Placement and Installation 16. . . . . . . . . . . . . . . . . . . .
III Start Up 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IV Heating Systems Service Checks 22. . . . . . . . . . . . .
V Disassembling Burner 24. . . . . . . . . . . . . . . . . . . . . . . .
VI Typical Operating Characteristics 26. . . . . . . . . . . . . .
VII Maintenance 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VIII Wiring Diagrams 28. . . . . . . . . . . . . . . . . . . . . . . . . .
IX Troubleshooting 31. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page 1
1995 Lennox Industries Inc.
Litho U.S.A.
Page 2
SPECIFICATIONS − O23
Blower wheel nominal
Fil
Model Number O23Q270 O23Q3105/120 O23Q5140/154
InputBtuh (kW) low/high 70,000 (20.5) 105,000 / 120,000(30.8 / 35.2) 140,000 / 154,000(41.0 / 45.1)
Output Btuh (kW) low/high 57,000 (16.7) 85,000 / 97,000 (24.9 / 28.4) 113,000 / 125,000 (33.1 / 36.6)
*A.F.U.E. 83.8% 82.8% (105) / 82.5% (120) 82.5% (140) / 81.4% (154)
Nozzle Rating  gph (L/hr) and spray angle .50 (1.9)  80°hollow
Flue Size Diameterin. (mm) 6 (152) 6 (152) 6 (152)
Oil Burner Pump 1 Stage 1 Stage 1 Stage
Oil Burner Pump Pressure  psig (Pa) 100 (690) 140 (965) 140 (965)
Blower wheel nominal
diameter x width
Blower Motor Output  hp (W) 1/3 (249) 1/3 (249) 3/4 (560)
Nominal cooling that can be added
**Number and size of filtersin. (mm) (1) 16 x 25 x 1 (1) 16 x 25 x 1 (2) 16 x 25 x 1
Shipping weight  lbs. (kg) 1 package 225 (102) 225 (102) 275 (125)
Electrical characteristics 115 volts  60 hertz  1 phase
Two Stage Oil Pump 65A44
Oil Filter 81P89
*Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations. Isolated combustion system rating for nonweatherized furnaces. **Cleanable frame type filters. Furnished with unit in Side Filter Adaptor Kit for field installation external to the cabinet.
Requires return air from both sides of cabinet.Nozzle must be field provided for field conversion to higher heating input.
in. 10 x 6 10 x 8 12 x 9
mm 254 x 152 254 x 203 305 x 229
Tons 2 thru 2.5 2 thru 3.5 3 thru 5
kW 7.0 thru 8.8 7.0 thru 12.3 10.6 thru 17.6
Optional Accessories (Must Be Ordered Extra)
.65 (2.5)  80° (105 input) solid
.75 (2.8)  80°(120 input) solid
.85 (3.2)  80° (140 input) solid
1.00 (3.8)  80° (154 input) solid
SPECIFICATIONS − OHR23
Model Number OHR23Q3105/120 OHR23Q5140/154
InputBtuh (kW) low/high 105,000 / 120,000(30.8 / 35.2) 140,000 / 154,000(41.0 / 45.1)
OutputBtuh (kW) low/high 85,000 / 97,000 (24.9 / 28.4) 113,000 / 125,000 (33.1 / 36.6)
*A.F.U.E. (low/high) 81.8% / 81.3% 81.5% / 81.7%
Nozzle RatingU.S. gph (L/hr) and spray angle
Flue Size Diameterin. (mm) 6 (152) 6 (152)
Oil Burner Pump 1 Stage 1 Stage
Oil Burner Pump Pressure  psig (Pa) 140 (965) 140 (965)
Blower wheel nominal diameter x width  in. (mm) 10 x 10 (254 x 254) 12 x 9 (305 x 229)
Blower motor outputhp (W) 1/2 (373) 3/4 (560)
Nominal cooling that can be added
Shipping weightlbs. (kg) 1 package 225 (102) 265 (120)
Electrical characteristics 115 volts  60 hertz  1 phase
Two Stage Oil Pump 65A44
ter Kit
Downflo Additive Base 35K07 35K08
Horizontal Venting Kit 62J01
Burner Cover 84H26
Vestibule Cover Kit (full front cover) 37K28 37K29
Oil Filter 81P89
*Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations. Isolated combustion system rating for nonweatherized furnaces. Nozzle must be field provided for field conversion to higher heating input.
Catalog no. 35K01 35K06
No. & size of filtersin. (mm) (2) 101/4 x 201/2 x 1 (260 x 521 x 25) (2) 113/4 x 231/2 x 1 (298 x 597 x 25)
Tons 2 to 3 3 to 5
kW 7.0 to 10.6 10.6 to 17.6
Optional Accessories (Must Be Ordered Extra)
.65 (2.5)  8 0 (105 input) solid
.75 (2.8 )  80 (120 input) solid
.85(3.2) 8 0(140 input) solid
1.00 (3.8)  80 (154 input) solid
Page 2
Page 3
SPECIFICATIONS − OF23
Blower wheel nominal
External Static
External Static
External Static
Model Number
InputBtuh (kW) low/high 105,000 / 120,000(30.8 / 35.2) 140,000 / 154,000(41.0 / 45.1)
OutputBtuh (kW) low/high 85,000 / 97,000 (24.9 / 28.4) 113,000 / 125,000 (33.1 / 36.6)
*A.F.U.E. (low/high)
Nozzle Ratinggph (L/hr) and spray angle
Flue Size Diameterin. (mm) 6 (152) 6 (152)
Oil Burner Pump 1 Stage 1 Stage
Oil Burner Pump Pressure  psig (Pa) 140 (965) 140 (965)
Optional 2 Stage Fuel Pump 65A44
Blower wheel nominal
diameter x width
Blower Motor Outputhp (W) 1/3 (249) 3/4 (560)
Nominal cooling that can be addedTons (kW) 2 thru 3 (7.0 thru 10.6) 3 thru 5 (10.6 thru 17.6)
Number and size of filters
Shipping weightlbs. (kg) 1 package 255 (116) 290 (132)
Electrical Characteristics 115  60 hertz  1 phase
Optional Accessories (Must Be Ordered Extra)
Two Stage Oil Pump 65A44
Oil Filter 91P89
*Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations. Isolated combustion system rating for nonweatherized furnaces. Nozzle must be field provided for field conversion to higher heating input.
in. 10 x 8 12 x 9
mm 254 x 203 305 x 229
in. (1) 18 x 19 x 1 (1) 19 x 21 x 1
mm (1) 457 x 483 x 25 (1) 483 x 533 x 25
OF23Q3105/120
OF23Q3105/120R
82.4% / 81.5%
82.5% / 82.4% R Models
.65 (2.5)  80° (105 input)
.75 (2.8)  80° (120 input)
OF23Q5140/154
OF23Q5140/154R
81.8% / 81.5%
82.0% / 81.8% R Models
.85 (3.2)  80° (140 input)
1.00 (3.8)  80° (154 input)
BLOWER PERFORMANCE DATA − O23
O23Q270 BLOWER PERFORMANCE
External Static
Pressure
in.w.g. Pa cfm L/s cfm L/s cfm L/s
.20 50 1260 595 870 410 520 245
.30 75 1205 570 825 390 500 235
.40 100 1135 535 780 370 480 225
.50 125 1050 495 720 340 450 210
.60 150 960 455 660 310 410 195
NOTE  All air data is measured external to the unit with the air filter in place.
Air Volume at Various Blower Speeds
High Medium Low
O23Q5140/154 BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s cfm L/s cfm L/s
.20 50 1950 920 1620 765 1250 590
.30 75 1900 895 1590 750 1230 580
.40 100 1880 885 1560 735 1210 570
.50 125 1850 875 1540 725 1190 560
.60 150 1800 850 1490 705 1155 545
NOTE  All air data is measured external to the unit with the air filter in place.
O23Q3105/120 BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s cfm L/s cfm L/s
.20. 50 1350 635 1215 575 1080 510
.30 75 1280 605 1180 555 1060 500
.40 100 1210 570 1140 540 1040 490
.50 125 1180 444 1085 510 1000 470
.60 150 1100 520 1025 485 950 450
NOTE  All air data is measured external to the unit with the air filter in place.
Air Volume at Various Blower Speeds
High Medium Low
Air Volume at Various Blower Speeds
High Medium Low
Page 3
Page 4
BLOWER PERFORMANCE DATA − OHR23
External Static
External Static
External Static
External Static
External Static
External Static
OHR23Q3105/120 BLOWER PERFORMANCE
External Static
Pressure
in w.g. Pa cfm L/s cfm L/s cfm L/s
.20 50 1470 695 1360 640 1070 505
.30 75 1400 660 1300 615 1040 490
.40 100 1330 630 1230 580 1020 480
.50 125 1260 595 1160 545 980 460
.60 150 1180 555 1085 510 920 435
NOTE  All air data is measured external to the unit with air filter in place.
Air Volume at Various Speeds
High Medium Low
BLOWER PERFORMANCE DATA − OF23
FRONT FLUE MODELS
OF23Q3105/120 BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s cfm L/s cfm L/s
.20 50 1490 705 1370 645 1190 560
.30 75 1430 675 1345 635 1180 555
.40 100 1375 650 1280 605 1160 545
.50 125 1300 615 1230 580 1120 530
.60 150 1230 580 1160 545 1080 510
NOTE  All air data is measured external to the unit with the air filter in place.
Air Volume at Various Blower Speeds
High Medium Low
OHR23Q5140/154 BLOWER PERFORMANCE
External Static
Pressure
in w.g. Pa cfm L/s cfm L/s cfm L/s
.20 50 1950 920 1700 800 1340 630
.30 75 1920 905 1650 780 1300 615
.40 100 1900 895 1600 755 1270 600
.50 125 1870 880 1580 745 1220 575
.60 150 1780 840 1500 710 1170 550
NOTE  All air data is measured external to the unit with air filter in place.
Air Volume at Various Speeds
High Medium Low
OF23Q5140/154 BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s cfm L/s cfm L/s
.20 50 2110 995 1850 875 1500 710
.30 75 2035 960 1810 855 1480 700
.40 100 1970 930 1750 825 1450 685
.50 125 1950 920 1690 800 1420 670
.60 150 1880 885 1620 765 1375 650
NOTE  All air data is measured external to the unit with the air filter in place.
Air Volume at Various Blower Speeds
High Medium Low
OF23Q3105/120R BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s cfm L/s cfm L/s
.20 50 1470 695 1330 630 1150 545
.30 75 1410 665 1295 610 1140 540
.40 100 1340 630 1250 590 1125 530
.50 125 1280 605 1190 560 1080 510
.60 150 1205 670 1130 535 1030 485
NOTE  All air data is measured external to the unit with the air filter in place.
Air Volume at Various Blower Speeds
High Medium Low
REAR FLUE MODELS
OF23Q5140/154R BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s cfm L/s cfm L/s
.20 50 2010 950 1765 835 1380 650
.30 75 1960 925 1720 810 1350 635
.40 100 1900 895 1660 785 1330 630
.50 125 1880 885 1600 755 1295 610
.60 150 1800 850 1560 735 1230 580
NOTE  All air data is measured external to the unit with the air filter in place.
Page 4
Air Volume at Various Blower Speeds
High Medium Low
Page 5
O23 GENERAL PARTS ORIENTATION
HEAT EXCHANGER
CLEANOUT PORT
LIMIT SWITCH
CONTROL BOX
WITH FAN CONTROL
BECKETT
AFII BURNER
INDOOR BLOWER
VENT OPENING
CLEANOUT PORT
OBSERVATION PORT
COMBUSTION AIR INTAKE
BLOWER MOTOR
CAPACITOR
FIGURE 1
LIMIT SWITCH
BECKETT
AFII BURNER
COMBUSTION
AIR INTAKE
OBSERVATION
PORT
CLEANOUT
OHR23 GENERAL PARTS ORIENTATION
CLEANOUT PORT
HEAT EXCHANGER
PORT
VENT OPENING
CONTROL BOX
WITH FAN
CONTROL
BLOWER MOTOR
INDOOR BLOWER
FIGURE 2
Page 5
Page 6
OF23 GENERAL PARTS ORIENTATION
CLEANOUT
PORT
LIMIT SWITCH
CONTROL BOX
WITH FAN CONTROL
BECKETT
AFII BURNER
FRONT VENT
OPENING (OF23)
COMBUSTION
AIR INTAKE
FILTER
INDOOR BLOWER
REAR VENT
OPENING (OF23R)
HEAT EXCHANGER
CLEANOUT PORT
OBSERVATION PORT
FIGURE 3
NEUTRAL
TERMINALS
24VAC OUTPUT
TO BURNER
(HEAT DEMAND)
24VAC IN FROM
PRIMARY LIMIT
24VAC THERMOSTAT
DEMAND OUTPUT
BCC2 / BCC3 BLOWER CONTROL BOARD
120VAC LINE
VOLTAGE IN
THERMOSTAT TERMINAL STRIP TB1
(DETACHABLE ON EARLY −1 AND −2
MODELS ONLY)
COOLING
SPEED TAP
TERMINAL
TRANSFORMER
120VAC
COMMON
FROM TRANSFORMER
CONTINUOUS FAN
TERMINAL
BLOWER TIME
ADJUSTMENT
JUMPER
24VAC INPUT
HEATING SPEED
TAP TERMINAL
ACCESSORY
TERMINAL
To Remove Terminal Strip,
Grasp Ends of Block Between
Thumb and Forefinger. Push
Block Down and Out.
(Jack / Plug 94)
24VAC COMMON
FROM TRANSFORMER
FIGURE 4
Page 6
Page 7
I−UNIT COMPONENTS
General parts orientation for the O23, OHR23 and OF23 are shown in figures 1, 2 and 3 respectively. The O23 and OF23 control box, burner, limit switch and cleanout ports may be ac cessed by removing the front access panel, while the OHR23 components are exposed. The blower can be accessed in the O23 and OF23 by removing the blower access panel, while in the OHR23 units two 1/4" screws must be removed before the blower access panel can be removed.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic components. Take precautions during unit instal lation and service to protect the unit’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the control and the technician at the same electrostatic potential. Neutralize electro static charge by touching hand and all tools on an unpainted unit surface before performing any service procedure.
A−Blower Control Board
BCC2 Blower Control Board (Figure 4)
−1 and −2 units
All O23, OHR23 and OF23−1 and −2 oil units utilize the BCC2 (A15) blower control manufactured by Heatcraft. The BCC2 is a printed circuit board which controls the supply air blower and monitors the limit controls and oil burner operation. The control has a nonadjustable, factory preset fanon" timing. Fan off" timing is adjustable. The board is divided into two sec tions, 120 and 24VAC. Line voltage comes into the board on the 120VAC side. See figure 4. See table 1 for BCC2 terminal designations.
DANGER
Shock hazard. Avoid personal injury. Make sure to disconnect power before changing fan off" timing.
Blower Operation and Timing
Blower off" timing (time that the blower operates after the heat demand has been satisfied) is determined by the arrange ment of a jumper across pins on the BCC2 blower control board. See figure 4. To adjust fan off " timing, gently discon nect jumper and reposition across pins corresponding with new timing. Fan on" time is factory set at 45 seconds and is not adjustable.
NOTEIf fan off" time is set too low, residual heat in heat exchanger may cause primary limit S10 or auxilary limit S21 to trip resulting in frequent cycling of blower. If this occurs, adjust blower to longer time setting.
Figure 5 shows the various fan off" timings and how jumper should be positioned. Unit is shipped with a fac tory fan off" setting of 150 seconds. Fan off" time will affect comfort and efficiency and is adjustable to satisfy individual applications. The fan off" timing is initiated after a heating demand but not after a blower or cooling demand (that is, when indoor thermostat switch is changed from ON to AUTO and heating/cooling demand is not present, the blower stops immediately).
FANOFF TIME ADJUSTMENT
TIMING
JUMPER
270
150 90
To adjust fan−off timings:
Remove jumper from BCC2
and select one of the other pin com
binations to achieve the
desired time.
Leave jumper off to achieve
210
330 second fan−off timing.
TIMING PINS (seconds)
Fanoff timing is factory
set at 150 seconds
FIGURE 5
Thermostat Connection
Thermostat wires are connected to terminal strip TB1 found on the BCC2 control board. The terminal strip is c l early marked with the corresponding thermostat designation. The terminal strip (jack / plug 94) is simply removed by grasping the ends of the block and rotating down while pull ing away (see figure 4).
TABLE 1
BLOWER CONTROL A15 TERMINAL DESIGNATIONS
Term inal Type Function
W
R
Y
C
G
NEUTRAL 1/4" Spade 120VAC Neutral
L1 1/4" Spade 120VAC Line Voltage In
A 1/4" Spade
XFMRN 1/4" Spade 120VAC Transformer Common
CF 1/4" Spade
H 1/4" Spade
ACC 1/4" Spade
VALVE SENSE 3/16" Spade 24VAC Output To Burner
LIMIT 1/4" Spade
WI 1/4" Spade
24V 1/4" Spade
COM 1/4" Spade
Detachable Screw Strip
Detachable Screw Strip
Detachable Screw Strip
Detachable Screw Strip
Detachable Screw Strip
Heating Demand
24VAC to Thermostat
Cooling Demand
24VAC Common
To Indoor Thermostat
Blower Demand
Switched 120VAC
to Blower Cooling Tap
Switched 120VAC to
Continuous Blower Tap
Switched 120VAC to
Blower Heating Tap
Switched 120VAC to Accessory
(Electronic Air Cleaner,
Humidifier, Etc. 1 amp rating.)
24VAC In From Primary Limit.
Limit Open: Stops Burner and Turns
On Blower
Limit Closed: Allows Burner
Operation
24VAC Thermostat
Demand Output
24VAC Input
From Transformer
24VAC Common
From Transformer
Page 7
Page 8
BCC3 Blower Control Board (Figure 4)
−3 and −4 units
All O23, OHR23 and OF23−3 and −4 oil units utilize the BCC3 (A15) blower control manufactured by Heatcraft. The BCC3 is a printed circuit board which controls the supply air blower and monitors the limit controls and oil burner operation. The control has a nonadjustable, factory preset fanon" timing. Fan off" timing is adjustable. The board is divided into two sec tions, 120 and 24VAC. Line voltage comes into the board on the 120VAC side. See figure 4. See table 2 for BCC3 terminal designations.
DANGER
Shock hazard. Avoid personal injury. Make sure to disconnect power before changing fan off" timing.
Blower Operation and Timing
Blower off" timing (time that the blower operates after the heat demand has been satisfied) is determined by the arrange ment of a jumper across pins on the BCC3 blower control board. See figure 4. To adjust fan off " timing, gently discon nect jumper and reposition across pins corresponding with new timing. Fan on" time is factory set at 45 seconds and is not adjustable.
NOTEIf fan off" time is set too low, residual heat in heat exchanger may cause primary limit S10 or auxilary limit S21 to trip resulting in frequent cycling of blower. If this occurs, adjust blower to longer time setting.
Figure 5 shows the various fan off" timings and how jumper should be positioned. Unit is shipped with a fac tory fan off" setting of 150 seconds. Fan off" time will affect comfort and efficiency and is adjustable to satisfy individual applications. The fan off" timing is initiated after a heating demand but not after a blower or cooling demand (that is, when indoor thermostat switch is changed from ON to AUTO and heating/cooling demand is not present, the blower stops immediately).
FANOFF TIME ADJUSTMENT
TIMING
JUMPER
To adjust fan−off timings:
Remove jumper from BCC2
and select one of the other pin com
binations to achieve the
desired time.
Thermostat Connection
Thermostat wires are connected to terminal strip TB1 found on the BCC3 control board. The terminal strip is clea r ly marked with the corresponding thermostat designation. The terminal strip (jack / plug 94) is simply removed by grasping the ends of the block and rotating down while pull ing away (see figure 4).
TABLE 2
BLOWER CONTROL A15 TERMINAL DESIGNATIONS
Term inal Type Function
W
R
Y
C
G
NEUTRAL 1/4" Spade 120VAC Neutral
L1 1/4" Spade 120VAC Line Voltage In
A 1/4" Spade
XFMRN 1/4" Spade 120VAC Transformer Common
CF 1/4" Spade
H 1/4" Spade
ACC 1/4" Spade
VALVE SENSE 3/16" Spade 24VAC Output To Burner
LIMIT 1/4" Spade
WI 1/4" Spade
24V 1/4" Spade
COM 1/4" Spade
Detachable Screw Strip
Detachable Screw Strip
Detachable Screw Strip
Detachable Screw Strip
Detachable Screw Strip
Heating Demand
24VAC to Thermostat
Cooling Demand
24VAC Common
To Indoor Thermostat
Blower Demand
Switched 120VAC
to Blower Cooling Tap
Switched 120VAC to
Continuous Blower Tap
Switched 120VAC to
Blower Heating Tap
Switched 120VAC to Accessory
(Electronic Air Cleaner,
Humidifier, Etc. 4 amp rating.)
24VAC In From Primary Limit.
Limit Open: Stops Burner and Turns
On Blower
Limit Closed: Allows Burner
Operation
24VAC Thermostat
Demand Output
24VAC Input
From Transformer
24VAC Common
From Transformer
270
150 90
Leave jumper off to achieve
210
330 second fan−off timing.
TIMING PINS (seconds)
Fanoff timing is factory
set at 150 seconds
FIGURE 6
Page 8
Page 9
ST9103A Blower Control Board (Figure 8)
−5 units
All O23, OHR23 and OF23 −5 oil units utilize the ST9103A (A15) blower control manufactured by Honeywell. The ST9103A is a printed circuit board which controls the supply air blower and monitors the limit controls and oil burner opera tion. The control has a nonadjustable, factory preset fanon" timing. Fan off" timing is adjustable. See figure 8 and table 3 for ST9103A terminal designations
ST9103A Blower Control Board
120V
DANGER
Shock hazard. Avoid personal injury. Make sure to disconnect power before changing fan off" timing.
Blower Operation and Timing
The fan on time of 30 seconds is not adjustable. Fan off time (time that the blower operates after the heat demand has been satisfied) can be adjusted by moving the delay switches on the fan control board. Fan off time will affect comfort and is adjustable to satisfy individual applications. See figure 7. Set the heat fan off delay switches to either 60, 90, 120, or 150 seconds. The factory setting is 90 sec onds.
NOTEIf fan off" time is set too low, residual heat in heat exchanger may cause primary limit S10 or auilary limit S21 to trip resulting in frequent cycling of blower. If this occurs, adjust blower to longer time setting.
Thermostat Connection
Thermostat wires are connected directly to the terminlas on the ST9103A board. See figure 8.
Continuous Blower
If the ST9103A blower control board is wired for continuous blower, the blower will energized on low speed and remain energized when heat or cool demand is satisfied. Continuous blower will also energized when indoor thermostat is left in the OFF mode.
Fan Off Delay Switch Settings
ONON ON ON
120 sec90 sec60 sec
Figure 7
150 sec
fan off
delay switches
thermostat
terminal strip
Figure 8
TABLE 3
BLOWER CONTROL A15 TERMINAL DESIGNATIONS
J58 Pin # Function
1 Limit S10
2 L1 120V
3 T1 24V
4 L2 Common
5 Jumpered to Pin 4
6 T2 24V
7 Combustion Air Inducer
120V 8 Jumpered to Pin 7
9 Limit S21 (if used)
Thermostat Connections
G Blower Demand
W Heating Demand
R 24V
Y Cooling Demand
C Common
24 VAC CONNECTIONS
X 24V Transformer
C Common Transformer
120 VAC
S2 Line
S3 120V To Transformer
N, 2, 3, 4, 6, 7 Neutral
CONT Continuous Blower
COOL Cool Tap
HEAT Heat Tap
Page 9
Page 10
RETAINING
CLIP
HEAD
INSULATOR
−1THROUGH −4 UNIT OIL BURNER PARTS ARRANGEMENT
AIR TUBE SCREWS
HOLE PLUG
ELECTRONIC IGNITION
TRANSFORMER
MAIN
HOUSING
ASSY
ESCUTCHEON
PLATE
CONNECTOR
TUBE
AIR TUBE
ASSY FOR
FB HEADS
FB–HEAD
NOZZLE
ADAPTER
NOZZLE LINE
ELECTRODE HEAD
FLANGE
GASKET
ASSY.
FLANGE
ELECTRODE
ASSY
REAR ACCESS
DOOR GASKET
VIEW PORT
REAR ACCESS
DOOR ASSY
OIL PUMP
SPLINED
NUT
ELECTRONIC IGNITION
TRANSFORMER
BURNER
CONTROL
RESET
BUTTON
AIR
ADJUSTMENT
0
3 4 5
6 7 8
DIAL
COUPLING
COMBUSTION AIR
MOTOR
BLOWER
FIGURE 9
Page 10
WHEEL
INLET
AIR SCOOP
Page 11
−5 UNIT BURNER PARTS ARRANGEMENT
RETAINING
CLIP
HEAD
INSULATOR
AIR TUBE
ASSY FOR
FB HEADS
1/4" HEX
HEAD SCREW
FB−HEAD
NOZZLE
ADAPTER
ELECTRODE HEAD
FLANGE
GASKET
NOZZLE LINE
ASSY.
ELECTRODE
FLANGE
ASSY
AIR TUBE SCREWS
ELECTRONIC IGNITION
TRANSFORMER
ESCUTCHEON
CONNECTOR
PEDESTAL
PREMOUNTED PRE−PURGE VALVE
MAIN
HOUSING
ASSY
PLATE
TUBE
REAR ACCESS
DOOR ASSY
SPLINED
NUT
FUEL PUMP
COUPLING
REAR ACCESS
DOOR GASKET
MOTOR
IGNITOR
PRIMARY
CONTROL
BLOWER
WHEEL
4X4
BOX
0
3 4 5
6 7 8
AIR ADJ. DIAL
INLET
AIR SCOOP
FIGURE 10
Page 11
Page 12
TABLE 4
FURNACE / BURNER SPECIFICATIONS
Unit
70 35K74 AFII 85 3.0
105 35K75 AFII 85 4.0
120 35K75 AFII 85 4.5
140 35K76 AFII 150 6.0
154 35K76 AFII 150 6.5
*NOTE: The initial air dial setting is provided to get unit started. The air dial setting MUST be adjusted after startup to achieve proper combustion.
Lennox Burner
Part Number
Burner
Model
*Initial Air Dial Setting
Output
57,000 BTU
(16.7 kW)
84,000 BTU
(24.6 kW)
105,000 BTU
(30.8 kW)
112,000 BTU
(32.8 kW)
125,000 BTU
(36.6 kW)
Nozzle Size
(Delevan)
0.50 X 80A
0.65 X 80B
0.75 X 80B
0.85 X 80B
1.00 X 80B
Pump
Pressure
100 psig
(689.5 kPa)
140 psig
965.3 kPa)
140 psig
965.3 kPa)
140 psig
965.3 kPa)
140 psig
965.3 kPa)
Head
FB0
FB3
FB3
FB6
FB6
B−Burner (Figures 9 & 10)
The O23, OHR23, and OF23 oil furnaces use the Beckett AFII burner. The oil burner provides an atomized oil vapor mixed with the correct proportion of air when it is ignited in the com bustion chamber. Oil burner minimum and maximum ratings are listed on the unit nameplate. Proper air adjustment for these ratings is achieved through the air adjustment dial. Set air dial to the initial air dial setting (see table 4). After start up adjust air dial to achieve proper combustion. Remember to tighten set screw on air dial.
The AFII burner is available in five sizes with either a single or two stage pump. Table 4 identifies the burners used in Lennox units. Figures 9 and 10 show the typical layout of the burner assembly.
1−Combustion Air Blower / Pump Motor (B6)
The burner is activated by the primary control. A com bustion air blower is mounted on the motor shaft. The motor shaft also connects to the direct drive oil pump through a coupler. The burner motor turns both the com bustion air blower and the oil pump. The motor operates at 3500 RPM.
Burner motors are overload protected. In the event of excess motor temperature or current, the overload opens to de−energize the motor. The overload automat ically resets after temperature has returned to normal. Keep motor clean to prevent starting switch from sticking. All AFII motors are permanently lubricated. No further oiling is required.
2−Combustion Air Blower / Pump Fuse (F22)
(−140 and −154 CSA units only)
In the −140 and −154 Canadian units an in line fuse (F22) is used between the line voltage from the BCC2 blower con trol and the blower / pump motor. The fuse is rated at 300 volts and 15 amps.
3− Pump (−1 through −4 units)
The O23, OHR23, and OF23 oil furnaces use a single stage, 3450 RPM pump. A two stage pump is available as an option (catalog # 65A44). The oil burner is shipped from factory for use in a single line system. To convert the pump to a two line system, install the bypass plug pro vided in the attached bag according to the accompany ing instructions.
4− Pump (−5 units only)
The O23, OHR23 and OF23−5 units all utilize the Cleancut Fuel Unit manufactured by Becket. This pump uses a sole noid valve to control the piston cut−on cut−off operation instead of a cone valve and diaphram used by other con ventional pumps. The solenoid works with the R7184B Honeywell burner control to provide cut−on cut−off opera tion while the burner motor is at full speed.
At startup the pump shaft is brought to full speed before the solenoid is energized. At this time low pressure oil (approximatley 20−25 psi) from the gearset circulates around the pressure regulator piston which is closed and through the open solenoid valve. The solenoid valve re turns the oil to either the cover cavity (one pipe) or return line (two pipe). When the solenoid vavle is energized, it closes (and remains closed while energized) blocking the return path to the cover cavity and return line creating pres sure build up in the piston cavity. The piston opens and reg ulates pressure and delivers pressurized oil to the nozzle.
At shutdown the solenoid valve will de−energize and open before the pump shaft rotation stops. When the solenoid valve opens the oil by−passes the cover cavity and return line causing a pressure drop in the piston cavity. The piston closes blocking oil to the nozzle while the burner motor is running at full speed.
Page 12
Page 13
5−Burner Control (A3) & Transformer (T1)
−1 through −4 units
The burner control, along with the matching cad cell, proves flame and controls the burner. After the cad cell closes a circuit to the burner control, the burner control de−energizes the safe ty switch heater to allow the unit to operate normally. The burner control allows 45 seconds for the cad cell to close. If the cad cell remains open after the 45 second time frame, the burner control locks out. The burner control must be manually reset by depressing the red reset button on top of the burner control.
Transformer (T1) is part of the burner control. T1 provides 24VAC to the low voltage components in the unit and to the thermostat.
6−Burner Control (A3) −5 units
All O 23, OHR23 and OF23 −5 units are equipped with a burn er control R7184B manufactured by Honeywell. The burner control, along with the matching cad cell, proves flame and controls the burner. An LED on the control shows unit status. See table 5 for status codes. After the cad cell closes a circuit to the burner control, the burner control de−energizes the safe ty switch heater to allow the unit to operate normally. When there is a call for heat the control performs a 2 to 6 second delay safety check. Once this is established a 15 second pre− puge will follow. The valve then opens for a 15 second trial for ignition. If flame is not sensed during the 15 second trial, the control shuts down and must be manual re−set. After three consecutive lockouts the control goes into restricted lockout. Once flame is established after 10 seconds of run time, the ig niiton shuts off.
If flame is lost during the heat cycle the control will shut down the burner and begin a 60 second recycle delay. Af ter 60 seconds the control repeats the ignition process. If flame is lost three consecutive times during a single ther mostat demand the control goas into restricted lockout.
Reset button
If the control lockouts three consecutive times the control will go into restricted lockout. To reset control hold down the reset button for 30 seconds until the LED flashes twice.
At any time the burner motor is energized, press and hold the reset button to disable the buner. The burner will re main disabled as long as the reset button is held and return to operational once the button is released.
TABLE 5
LED STATUS
On Flame sensed
Off Flame not sensed
Flashing
(1/2 sec on1/2 sec off)
Flashing
(2 sec on 2 sec off)
Lockout /
Restricted Lockout
Recycle
7−Heat Shutoff Relay (K125)
−1 and −2 units only
Heat shutoff relay K125 is a SPST N.O. relay, with a 24V coil. K125 is located on the vestibule and wired in series with the burner. When secondary limit S21 or primary limit S10 open, the circuit breaks opening K125 contacts which in turn de−energizes the burner.
8−Cad Cell (R26)
Together the cad cell and the burner control prove flame. The cad cell senses the presence of burner light (less re sistance) to close a circuit to the burner control.
IMPORTANT−Burner should not be installed so it is ex posed to direct sunlight or electric bulb light. If the cell is exposed to light on start up, the burner will not oper ate.
O23, OHR23 & OF23 −5 Units Only
Resistance for the cad cell can be checked while the burn er is firing and after ignition is off. Press (1/2 second or less) and release the reset button. The LED will flash 1 to 4 times depending on the cad cell resistance. The cad cell resistance should read less than 1600 Ohms. See table 6.
O23, OHR23 & OF23 −5 UNITS
LED FLASHES RESISTANCE
1 0 − 400Ohms
2 400 − 800 Ohms
3 800 − 1600 Ohms
4
TABLE 6
1600 Ohms
Page 13
Page 14
9−Electronic Ignitor (A73)
The electronic ignitor provides the needed hot spark at the electrodes to ignite the fuel mixture. The ignitor is a solid state transformer . O23, OHR23 and OF23−1 through −4 units have 115V primary and 14,000V secondary wind ings. O23, OHR23 and OF23−5 units have 120V primary and 20,000V secondary windings. The center of the sec ondary winding is grounded. Each secondary terminal is 7000V to ground and the total voltage between the elec trodes is 14,000V.
NOTE−The leads for the solid state transformer are re placeable and are available in a kit form.
NOTE−When testing the solid state transformer, do not use a transformer tester designed for iron magnet trans formers. Damage to the tester may result.
Testing the Ignitor
WARNING
SHOCK HAZARD Do not touch ignitor or any metal touching ignitor when ignitor is energized. Can result in serious per sonal injury.
10−Gun Assembly
The gun assembly receives oil from the oil pump and feeds it to the nozzle. The nozzle converts liquid oil into a fog−like mist that is discharged through the flame retention head into the combustion chamber.
11−Flame Retention Heads
The stainless steel flame retention head (see figure 11) is used to swirl (cone) the foglike oil and air mixture as it enters the combustion chamber. Three different heads are used in the O23/OHR23/OF23. The firing rate dic tates which head is used. See table 4. The greater the FB number the larger the slots on the head. When com bustion takes place, the flame will be cylindrical com pact shaped as a result.
FLAME RETENTION HEAD
FB3 SHOWN
If the ignitor fails it will not produce a spark. Looking and listening for the arc is a simple way to check. The most sure way is to perform the screwdriver check. By placing the blade of an insulated screwdrivere across the ignitor termi nal leads will test for an arc. First, remove power from the burner and disconnect the oil supply from nozzle. The cad cell will not let the control energize the ignitor if the cad cell senses light. Therefore remove one lead of the cad cell from the burner control, or remove the cad cell all together (do not forget to put back when test is complete). Place the screwdriver blade across the terminals and slowly raise one end of the blade off the terminal while the other re mains in contact with the other terminal. There should be an arc from terminal to the blade up to 3/4" away. If not re place the ignitor. If an arc is present then place one end of the screwdriver on one terminal and the other end with the grounded baseplate. Raise the blade from the baseplate and draw an arc. Repeat with the other terminal. If the arc from the baseplate to one terminal is weaker than the arc from the baseplate to the other terminal, replace the ignitor.
FIGURE 11
C−Primary Limit Control (S10)
The primary limit on all O23, OHR23, and OF23 units, is located on the vestibule panel (see figures 1 through 3 for location and figure 12 for type). When excess heat is sensed in the heat exchanger, the limit will open. If the limit is tripped, the blower control deenergizes the thermostat, in turn shutting down the unit. The limit automatically re sets when unit temperature returns to normal. The switch is factory set and cannot be adjusted. The switch has a different setpoint for each unit model number (see table 7). The set point is printed on the face plate of the limit.
Page 14
Page 15
TABLE 7
PRIMARY LIMIT CONTROL (S10)
UNIT
ACTUATES
ON TEMP. RISE
O23Q2−70 210F (99C) 180F (82C)
O23Q3−105/120 220F (104C) 190F (88C)
O23Q5−140/154 210F (99C) 180F (82C)
OHR23Q3−105/120 240F (116C) 210F (99C)
OHR23Q5−140/154 190F (88C) 160F (71C)
OF23Q3−105/120
OF23Q3−105/120R
OF23Q5−140/154
OF23Q5−140/154R
SPADE CONNECTORS
240F (116C) 210F (99C)
210F (99C) 180F (82C)
LIMIT CONTROL (S10)
INSULATING COVER
ACTUATES
ON TEMP. FALL
LIMIT
1.Blower Motor (B3) and Capacitor (C4)
All O23, OHR23, and OF23 series units use single phase direct drive blower motors. All motors used are 115V perma nent split capacitor motors to ensure maximum efficiency. See SPECIFICATIONS tables for horsepower and motor nameplate for capacitor rating.The blower motor is con nected to the blower control board via the blower motor plug P43.
2.Secondary Limit Control (S21)
The secondary limit (S21) is used on the OHR23 series unit only. The N.C. limit is mounted on the side and toward the back of the blower housing. See figure 13 for location and fig ure 14 for type. When excess heat is sensed in the blower compartment, the limit will open. If the limit is tripped, the blow er control deenergizes the thermostat, inturn shutting down the unit. The limit automatically resets when unit tempera ture returns to normal. The switch opens at 150F + 5F (65.5C + 2.8C) on a temperature rise and resets at 140F + 5F (60.0C + 2.8C) on a temperature fall. The switch is factory set and cannot be adjusted. The set point is printed on the face plate of the limit.
FIGURE 12
D−Blower Compartment (Figure 13)
Blower motor (B3), capacitor (C4), and secondary limit con trol (S21) are located in the blower compartment. The blow er compartment can be accessed by removing the blower access panel.
BLOWER COMPARTMENT
(OHR23 SIDE VIEW SHOWN)
SECONDARY LIMIT
CONTROL (S21)
(OHR23 ONLY)
(BACK SIDE)
BLOWER
MOTOR
CAPACITOR
(C4)
SECONDARY LIMIT CONTROL (S21)
FIGURE 14
E−Optional Accessories
Optional accessories are available from Lennox for the O23, OHR23, and OF23 series units. Some accessories are in kit form which come with instructions.
1.Low Speed On − Off Switch (S68)
The low speed on  off switch is a kit (catalog # 67H91) which permits continuous low speed blower operation. The switch is a DPDT toggle switch.
FIGURE 13
BLOWER MOTOR
(B3)
2.Economizer Relay (K43)
The economizer relay (catalog # 65G40) is used to energize the economizer if used. The relay is a 120V coil, single pole contact which is energized by the accessory terminal of the blower control board.
Page 15
Page 16
II−PLACEMENT AND INSTALLATION
g
Make sure unit is installed in accordance with installation in structions and applicable codes.
A−Piping
The piping system and it’s components (oil filter, safety valves, shutoff valves, etc.) must be designed to provide clean, air free fuel to the burner.
An oil filter is required for all models. Use an oil filter of gener ous capacity for all installations. Install filter inside the building between the tank shut−off valve and the burner. Locate filter close to burner for easy servicing. The GAR−Ber 11BV−R or equivalent filter (with the below specifications) is recom mended.
Fill
Pipe
Air Vent
OIL PIPING
ONEPIPE SYSTEM
Fuel Unit
Oil
Tank
Shut−off
Valve
Aux
Filter
8 ft (2.4 m)
Maximum
One Pipe Lift
Maximum Firing Rate: 10GPH (38LPH)
Micron Removal: 10
Filtering Area: 500 in.2 (3225.8 cm2)
Working Pressure: 15 PSI (103.4 kPa)
Inlet/Outlet Dimension: 3/8" (9.5 mm) NPT
Flow Rate: 45GPH (171LPH)
Care must be taken to ensure the restriction of the piping sys tem, plus any lift involved, does not exceed the capabili ty of the oil pump. Each installation will be different. Use the following guide lines when determining to use a single or two stage pump.
When using a single pipe system with the fuel supply level with or above the burner (see figure 15) and a vacuum of 6" (152 mm) Hg or below, a single stage fuel unit with a supply line and no return line should be adequate. Manual bleeding of the fuel unit is required on initial start up. Failure to bleed air from the pump could result in an air lock/oil starvation condi tion.
NOTE−As an extra precaution, cycle heating on and off ten times after bleeding air from the pump. This will elim inate air in the gun assembly.
When using a two pipe system with the fuel supply level below the level of the burner (see figure 16) a single stage fuel unit should be used in lift conditions of up to 10 feet (3 m) and/or a vacuum of 10" (254 mm) Hg or be low. A two stage fuel unit should be used when lift ex ceeds 10 feet (3 m) and/or a vacuum of 10" (254 mm) Hg to 15" (381 mm) Hg. Both conditions require the use of a re turn line that purges the fuel unit of air by returning it to the fuel tank. Use table 8 when determining the run and lift for piping.
Before converting a onepipe system to a twopipe sys tem the pump must be converted to a twopipe system. To convert the pump, install the bypass plug according to the instructions. Notice in the twopipe system the re turn line must terminate 3" (76 mm) to 4" (102 mm) above the supply inlet. Failure to do this may introduce air into the system and could result in loss of prime.
NOTE−If using an outside tank in cold climates a number one fuel or an oil treatment is strongly recommended.
Page 16
FIGURE 15
OIL PIPING
TWOPIPE SYSTEM
Air Vent
Fill
Pipe
Return
Line
Oil
Tank
3"−4"
Return
Line
OUTSIDE TANK FUEL UNIT ABOVE BOTTOM OF TANK.
(76mm −102mm)
R
FIGURE 16
TABLE 8
Fuel Unit
Aux
Filter
Inlet
H
TWO−PIPE MAXIMUM LINE LENGTH (H + R)
3450 RPM − 3 GPH (11.4 LPH)
Lift H"
Figure 15
0’
(0.0 m)
2’
(0.6 m)
4’
(1.2m)
6’
(1.8m)
8’
(2.4m)
10’
(3.0m)
12’
(3.7m)
14’
(4.3m)
16’
(4.9m)
18’
(5.5m)
3/8" (10 mm) OD
Tubing
Single
Stage
84’
(25.6 m)
73’
(22.3 m)
63’
(19.2 m)
52’
(15.8 m)
42’
(12.8 m)
31’
(9.4 m)
21’
(6.4 m)
−−−
−−−
Two
Stage
93’
(28.3 m)
85’
(25.9 m)
77’
(23.5 m)
69’
(21.0 m)
60’
(18.3 m)
52’
(15.9 m)
44’
(13.4 m)
36’
(11.0 m)
27’
(8.2 m)
−−− −−− −−−
1/2" (12 mm) OD
Tubing
Single
Stage
Stage
100’
(30.5 m)
(30.5 m)
100’
(30.5 m)
(30.5 m)
100’
(30.5 m)
(30.5 m)
100’
(30.5 m)
(30.5 m)
100’
(30.5 m)
(30.5 m)
100’
(30.5 m)
(30.5 m)
83’
(25.3 m)
(30.5 m)
41’
(12.5 m)
−−−
(30.5 m)
(30.5 m)
(23.2 m)
Two
100’
100’
100’
100’
100’
100’
100’
100’
100’
76’
Page 17
B−Venting Considerations
2− The vent connector should be as short as possible to
do the job.
WARNING
Combustion air openings in front of the furnace must be kept free of obstructions. Any obstruction will cause improper burner operation and may re sult in a fire hazard or injury.
WARNING
The barometric shall be in the same atmospheric pressure zone as the combustion air inlet to the furnace. Deviation from this practice will cause im proper burner operation and may result in a fire hazard or injury.
CAUTION
Do not store combustible materials near the fur nace or supply air ducts. The material (such as paint, motor oil, gasoline, paint thinner, etc.) may ignite by spontaneous combustion creating a fire hazard.
3− The vent connector should not be smaller than the
outlet diameter of the vent outlet of the furnace.
4− Pipe should be at least 24 gauge galvanized.
5− Single wall vent pipe should not run outside or through
any unconditioned space.
6− Chimney should extend 3 feet (0.9 m) above the high
est point where the vent passes through the roof, and 2 feet (0.6 m) higher than any portion of a building within a horizontal distance of 10 feet (3 m).
7− The vent must not pass through a floor or ceiling. Clear
ances to single wall vent pipe should be no less than 6" (152 mm); more if local codes require it.
8− The vent may pass through a wall where provisions have
been made for a thimble as specified in the Standards of the National Board of Fire Underwriters. See figure 17.
9− The vent pipe should slope upward toward the chim
ney on horizontal run at least 1/4 inch (6 mm) to the foot (0.3 m) and should be supported by something other than the furnace, such as isolation hangers. See figure 18.
WARNING
This furnace is certified for use with type L" vent. B" vent must not be used with oil furnaces.
NOTE−Oil burning equipment may be vented into an ap proved masonry chimney or type L vent. (Type L vent is similar in construction to type B gas vent except it carries a higher temperature rating and is constructed with an inner liner of stainless steel rather than aluminum).
Prior to installation of unit, make a thorough inspection of the chimney to determine whether repairs are necessary. Make sure the chimney is properly constructed and sized accord ing to the requirements of the National Fire Protection Asso ciation. The smallest dimensions of the chimney should be at least equal to the diameter of the furnace vent connector. Make sure the chimney will produce a steady draft sufficient to remove all the products of combustion from the furnace. A draft of at least .04" w.c. (9.9 Pa) is required during burner operation.
1− Local building codes may have more stringent instal
lation requirements and should be consulted before installation of unit.
10− Extend the vent pipe into the chimney so that it is flush
with the inside of the vent liner. Seal the joint between the pipe and the liner.
11− The furnace shall be connected to a factory built
chimney or vent complying with a recognized stan dard, or masonry or concrete chimney lined with a lining material acceptable to the authority having jurisdiction.
WALL THIMBLE
THIMBLE
COMBUSTIBLE
WALL
VENT PIPE
FIGURE 17
Page 17
Page 18
BAROMETRIC
CONTROL* (IN EITHER LOCATION)
CLEANOUT
*Barometric control may be installed in either vertical or horizontal section of vent pipe within 18" (457 mm) of vent outlet of furnace.
LINER
CLEANOUT
MASONRY
CHIMNEY
FIGURE 18
12− When two or more appliances vent into a common vent,
the area of the common vent should not be less than the area of the largest vent or vent connection plus 50% of the areas of the additional vent or vent connection. Chim ney must be able to sufficiently vent all appliances oper ating at the same time.
13− The vent pipe shall not be connected to a chimney vent
serving a solid fuel appliance or any mechanical draft system.
14− All unused chimney openings should be closed.
15− All vent pipe run through unconditioned areas or outside
shall be constructed of factory built chimney sections. See figure 19.
16− Where condensation of vent gas is apparent, the vent
should be repaired or replaced. Accumulation of con densation in the vent is unacceptable.
FACTORY−BUILT CHIMNEY
MASONRY CHIMNEY
17− Vent connectors serving this appliance shall not be
connected into any portion of mechanical draft sys tems operating under positive pressure.
18− Keep the area around the vent terminal free of snow,
ice and debris.
NOTE−If vent pipe needs to exit from side of cabinet, use the cross hairs (located on either side of the unit) to cut a 6" (152 mm) round hole. Attach finishing plate (provided) with four sheet metal screws to cover rough edges.
Combustion and Ventilation Air (Confined and Unconfined Spaces)
Until recently, there was no problem in bringing in suffi cient amounts of outdoor air for combustion −− infiltration provided all the air that was needed and then some. In today’s homes built with energy conservation in mind, tight construction practices make it necessary to bring in air from outside for combustion. Consideration must also be given to the use of exhaust fans, appliance vents, chimneys and fireplaces because they force additional air that could be used for combustion out of the house. Unless outside air is brought into the home for combustion, negative pressure (pressure outside is greater than inside pres sure) will build to the point that a down draft can occur in the furnace vent pipe or chimney. Combustion gases e n ter the living space creating a potentially dangerous situa tion.
The importance of the previous paragraph cannot be overstated. Users may inadvertently block fresh air in takes after installation.
In the absence of local codes concerning air for combus tion and ventilation, the following section outlines guide lines and recommends procedures for operating oil fur naces in a manner that ensures efficient and safe operation. Special consideration must be given to com bustion air needs as well as requirements for exhaust vents and oil piping.
Combustion Air Requirements
BAROMETRIC
CONTROL* (IN EITHER LOCATION)
*Barometric control may be installed in either vertical or horizontal section of vent pipe within 18" (457 mm) of vent outlet of furnace.
FIGURE 19
FACTORY
BUILT
CHIMNEY
CAUTION
Insufficient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger result ing in rusting and premature heat exchanger fail ure. It can also cause property damage.
All oil−fired appliances require air to be used for the com bustion process. If sufficient amounts of combustion air are not available, the furnace or other appliance will operate in an inef ficient and unsafe manner. Enough air must be provided to meet the needs of all fuel−burning appliances, as well as ap pliances such as exhaust fans which force air out of the home. When fireplaces, exhaust fans, or clothes dryers are used at the same time as the furnace, much more air is required to ensure proper combustion and to prevent a down− draft situation. Insufficient amounts of air also cause in
Page 18
Page 19
comp l ete combustion which can result in sooting. Require ments for providing air for combustion and ventilation depend largely on whether the furnace is installed in an uncon fined or confined space.
Unconfined Space
CHIMNEY OR
OIL VENT
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM INSIDE
An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cu bic feet (1.4 cubic meters) per 1,000 Btu (293 W) per hour of the combined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be unconfined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the proce dures outlined for using air from the outside for combus tion and ventilation.
Confined Space
A confined space is an area with volume less than 50 cu bic feet (1.4 cubic meters) per 1,000 Btu (293 W) per hour of the combined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms.
When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space con taining the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on a platform in a con fined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the confined space either from inside the building or from outside.
Air from an Adjacent Space
If the confined space housing the furnace adjoins space categorized as unconfined, air can be brought in by pro viding two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (6.4 square centimeters) per 1,000 Btu (293 W) per hour of the total input rating of all fuel−fired equipment in the confined space. Each opening must be at least 100 square inches (614.5 square centime ters). One opening shall be within 12" (305 mm) of the top of the enclosure and one opening within 12" (305 mm) of the bottom (See figure 20).
OIL
FURNACE
NOTE−Each opening shall have a free area of at least 1 square inch (6.4 square centimeters) per 1,000 Btu (293 W) per hour of the total input rating of all equipment in the enclosure, but not less than 100 square inches (614.5 square centimeters).
WATER
HEATER
OPENINGS
(To Adjacent Room)
FIGURE 20
Air from Outside
If air from outside is brought in for combustion and ven tilation, the confined space shall be provided with two permanent openings. One opening shall be within 12" (305 mm) of the top of the enclosure and one within 12" (305 mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (6.4 square centimeters) per 4,000 Btu (1172 W) per hour of total input rating of all equipment in the enclosure (See figures 21 and 22). When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (6.4 square centimeters) per 2,000 Btu (586 W) per total input rating of all equipment in the enclosure (See figure 23).
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
(Inlet Air from Crawl Space and
Outlet Air to Ventilated Attic)
CHIMNEY
OR OIL
VENT
VENTILATION LOUVERS
(Each end of attic)
OIL
FURNACE
VENTILATION
LOUVERS
(For unheated
crawl space)
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (6.4 square centimeters) per 4,000 Btu (1172 W) per hour of the total input rating of all equipment in the enclosure.
OUTLET
AIR
WATER
HEATER
INLET
AIR
FIGURE 21
Page 19
Page 20
CHIMNEY
OR OIL
VENT
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
OUTLET
AIR
CAUTION
Combustion air openings in the front of the furnace must be kept free of obstructions. Any obstruction will cause improper burner operation and may result in a fire hazard or injury.
OIL
FURNACE
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (6.4 square centimeters) per 4,000 Btu (1172 W) per hour of the total input rating of all equipment in the enclosure.
INLET AIR
(Ends 12" above
bottom)
WATER
HEATER
FIGURE 22
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
CHIMNEY
OR OIL
OIL
FURNACE
VENT
WATER
HEATER
OUTLET AIR
CAUTION
The barometric shall be in the same atmospheric pressure zone as the combustion air inlet to the furnace. Deviation from this practice will cause improper burner operation and may result in a fire hazard or injury.
Direct Connection of Outdoor Air for Combustion
The Beckett AFII burner was designed to allow for direct air intake piping (4" [102 mm]). The maximum equivalent length of pipe is 70 feet (21.3 m). A 90 elbow equals 6feet (1.8 m).
To convert the AFII burner from confined space to out side combustion air, simply remove the three screws at taching the inlet air scoop to the burner and insert 4" (102 mm) direct air intake piping.
The use of a barometric relief placed in the intake pipe is recommended when outdoor combustion air is directly connected to the burner. This will allow confined space air to be used as combustion air in the event that the opening to the outdoor air becomes blocked. Using a barometric relief in the intake will reduce the chance of sooting.
INLET AIR
NOTE−Each air duct opening shall have a free area of at least one square inch (6.4 square centimeters) per 2,000 Btu (586 W) per hour of the total input rating of all equipment in the enclosure. If the equip ment room is located against an outside wall and the air openings communicate directly with the outdoors, each opening shall have a free area of at least one square inch (6.4 square centimeters) per 4,000 Btu (1172 W) per hour of the total input rating of all other equip ment in the enclosure.
FIGURE 23
When ducts are used, they shall be of the same cross−sec tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3" (76 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be con sidered. If the design and free area of protective covering is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 per cent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equip ment so that they are opened automatically during equip ment operation.
CAUTION
DO NOT USE a barometric draft relief in exhaust vent pipe if outdoor combustion air is connected directly to the burner. The only exception are baro metric draft reliefs as required by FIELD or TJERN LUND power vents.
Removal of Unit from Common Venting System
In the event that an existing furnace is removed from a venting system commonly run with separate appliances, the venting system is likely to be too large to properly vent the remaining attached appliances. The following test should be conducted while each appliance is in operation and the o t her a p pliances not in operation remain connected to the com mon venting system. If venting system has been installed improperly, the system must be corrected as outlined in the previous section.
1− Seal any unused openings in the common venting sys
tem.
2− Visually inspect venting system for proper size and hori
zontal pitch and determine there is no blockage or restric tion, leakage, corrosion or other deficiencies which could cause an unsafe condition.
Page 20
Page 21
3− Insofar as is practical, close all building doors and
windows and all doors between the space in which the appliances remaining connected to the com mon venting system are located and other spaces of the building. Turn on clothes dryers and any ap pliances not connected to the common venting sys tem. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maxi mum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4− Following the lighting instruction on the unit, place the
appliance being inspected in operation. Adjust thermo stat so appliance will operate continuously.
5− Test for spillage using a draft gauge.
6− After it has been determined that each appliance re
maining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other fuel burning appliance to their previous condi tion of use.
7− If improper venting is observed during any of the
above tests, the common venting system must be corrected.
Horizontal Venting
(152 mm) is permissible. Calculate the equivalent vent pipe footage from the furnace to the mechanical vent system (Tjernlund or Field Controls) by adding the straight vent pipe length and the equivalent elbow lengths together.
The barometric draft control must be used in horizontal (side wall) venting system. It must be located within 18" (457 mm) of the furnace vent outlet. See figure 24 for barometric draft con trol location.
III−STARTUP
A−Preliminary and Seasonal Checks
1− Inspect electrical wiring, both field and factory installed
for loose connections. Tighten as required.
2− Check line voltage. Voltage must be within range
listed on the nameplate. If not, consult the power company and have voltage condition corrected be fore starting unit.
B−Heating StartUp
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING
Do not attempt to start the burner when excess oil has accumulated in the chamber, when the furnace is full of vapor or when the combus tion chamber is very hot.
HORIZONTAL VENTING
BAROMETRIC
CONTROL*
*When using indoor air,
barometric control must be
installed in the horizontal
venting system and located
within 18" (457 mm) of vent
When using direct connection,
barometric control must be
installed in the intake air pipe.
CONTROL FOR
HORIZONTAL
VENTING
outlet of furnace.
FIGURE 24
The O23 is approved for horizontal venting with the fol lowing mechanical vent systems: Tjernlund (sideshot) #SS1C and Field Controls #SWG−5 with the CK−61 control kit. Refer to manufacturers’ installation instructions for proper installation procedures and service parts information.
Do not common vent with any other appliance when using sidewall vent system.
Maximum permissible vent length is 70 equivalent feet (21.3 m). Minimum length is 15 equivalent feet (4.6 m). Each 90 elbow is equal to 6 feet (1.8 m) of straight pipe, each 45 el bow is equal to 3 feet (0.9 m) of straight pipe. Minimum vent pipe diameter is 4" (102 mm). Vent pipe of 5" (127 mm) and 6"
1− Set thermostat for heating demand.
2− Turn on electrical supply to unit and open all shutoff
valves in the oil supply line to the burner..
3− Check air adjustment dial on the right side of the burn
er (see figure 9). Set according to table 4.
4− On single line applications the oil pump must be
primed by bleeding the oil line. Open air bleed port and start burner. A hose may be attached to direct oil into a container. After last bubble is seen, bleed pump for 15 seconds. Hurried bleeding will impair efficient unit op eration. Close port to stop bleeding. Single line instal lations must be absolutely air tight to prevent leaks or loss of prime.
5− If burner stops after flame is established, repeat the
bleeding procedure.
NOTE−Air bleeding is automatic on two line applica tions; however, opening air bleed port will allow a faster bleed. Run return line back to tank and terminate three to four inches above the inlet line. Failure to bleed the sys tem may cause air to be introduced into the system result ing in a loss of prime.
6− If the burner does not start immediately, check the
safety switch on the burner primary control.
7− If burner fails to light again, refer to the trouble
shooting section in the back of this manual.
8− Proceed to section IV to complete start up.
C−Safety or Emergency Shutdown
Turn off unit power. Close all shutoff valves in the oil sup ply line.
Page 21
Page 22
D−Extended Period Shutdown
Turn off thermostat or set to UNOCCUPIED" mode. Close all shutoff valves in the oil supply line to guarantee no oil leaks into burner. Turn off all power to unit. All access panels, covers and vent caps must be in place and se cured.
To check that the nozzle is approximately centered with the head inside diameter, align the center mark of the gauge with the center of the nozzle orifice, as shown in figure 27, and move the gauge from side to side at sev eral points. Be careful not to scratch the nozzle sur
face.
IV−HEATING SYSTEM SERVICE CHECKS
A−Oil Piping
All oil supply piping (factory and field) must be carefully checked for oil leaks.
B−Electrode Adjustment
When adjusting the electrode, use the AFII multipurpose gauge (Beckett part # T−500) packaged with each oil fur nace, also available from Beckett.
To set the electrode tip gap spacing, position the gauge as shown in figure 25. Align the center mark with the nozzle and adjust the electrodes to the two outer marks (1/8" [3mm] to 1/16" [2mm] minimum).
AFII ELECTRODE TIP
GAP
The Z" or zero dimension is important because it locates the nozzle for the precise relationship with the combustion head. To set the Z" dimension, position the gauge as shown in fig ure 27 and loosen the nozzle line electrode assembly so that it can be moved forward or backward in the air tube until the nozzle becomes flush against the gauge. Tighten the nozzle line escutcheon plate screw (shown in figure 9) to lock this Z" dimension securely.
AFII NOZZLE CENTERING
FIGURE 25
To position the electrode tips beyond the face of the nozzle and above the center line, position the gauge as shown in figure 26. Align the center mark with the nozzle and adjust the electrodes to the AC cross marks.
AFII ELECTRODE POSITIONING
FIGURE 26
FIGURE 27
C−Pressure Check
On −1 through −4 units use either the gauge port or nozzle port to check operating pressure. On −5 units use the nozzle port (−5 unit pumps are not equipped with gauge port). The pump is factory set at 100 psig (689.5 kPa) for the O23Q2−70 and 140 psig (965.3 kPa) for all other O23, OHR23, and OF23 units but is adjustable (see fig ure 28). Never operate the pump in excess of 10 ps ig (6 9 kPa) above set point. Average nozzle cutoff pressure is 80 psig (551.6 kPa). To check the cutoff pressure install a pressure gauge in nozzle port. For −5 units use the same gauge used for operating pressure. Run the burn
Page 22
Page 23
er for a short period and then turn off. The gauge shows cutoff pressure.
OIL PUMP PRESSURE CHECK
*PRESSURE GAUGE
**REGULATE PRESSURE
NOT SHOWN
(beside the inlet port)
PRESSURE
GAUGE
PORT (1/8" [3mm])
NOZZLE PORT
(1/8" [3mm])
INLET PORT
(1/4" [6mm])
*PRESSURE CHECKS: NORMAL OPERATING PRESSURE IS 100 PSIG (689.5 kPa) FOR THE 023Q270 AND 140 PSIG (965.3 kPa) FOR ALL OTHER O23, OHR23, AND OF23 UNITS. NOZZLE CUTOFF PRESSURE IS APPROXIMATELY 80 PSIG (551.6 kPa).
**TO ADJUST PRESSURE: INSERT STANDARD SCREWDRIVER. TURN COUNTERCLOCKWISE BELOW DESIRED PRESSURE, THEN TURN CLOCKWISE TO SET DESIRED PRESSURE.
RETURN PORT
(1/4" [6mm])
INLET PORT
SHOWN (1/4" [6mm])
BLEED PORT
1/16" (2mm) BYPASS PLUG
INSERT FOR TWOPIPE SYSTEM
(use 5/32" [4mm] allen wrench)
FIGURE 28
D−Burner Adjustment
The following instructions are essential to the proper opera tion of O23 series oil furnaces. To prevent sooting, these in structions must be followed in sequence:
NOTE−All w.c. measurements are below atmospheric pressure (negative readings).
1−Draft
This test should be taken at the vent connector between the breaching and the barometric damper. Generally a 1/4" (6 mm) hole will need to be drilled for the draft gauge to be inserted into the vent connector.
A minimum of 0.03" w.c. (7.5 Pa) draft must be estab lished without the burner in operation. With the burner in operation, the draft should be 0.04" w.c. (9.9 Pa) to 0.05" w.c. (12.4 Pa). This is VERY critical to the flame retention head burners.
Oil furnace installations also require careful inspection to make sure the chimney is in good condition and can ac commodate the products of combustion. The temperature in unconditioned space will also affect the draft if long vent connectors are allowed to get too cold.
2−Overfire Draft
This test should be taken with the burner in operation. Remove the screw from the center of the center inspec tion port. Insert your draft gauge into the hole.
A reading of the overfire draft should be 0.02" w.c. (5.0 Pa) less than the reading found in the vent connector. If a posi tive reading is seen at this point, the secondary heat ex changer may be sooted or to much air may be entering into the heat exchanger from the combustion fan. Adjust ments to the combustion fan can be made using the air adjustment dial.
3−Smoke Test
The smoke test should be taken at hole drilled in step 1.
Using a smoke test gun adjust the air inlet shutter so that you will have just a trace of smoke. Somewhere be tween a 0 and #1 smoke. This is the starting point. Do not stop here. After the smoke test take a CO sample. C.S.A. requires no more than 400ppm. However, a properly installed unit under normal operating condi tions should not read more than 50ppm.
4−CO2 Test
Again to be taken at the vent connector pipe. With the unit firing at a trace of smoke, test for percentage of CO in the vent gas.
From the results of this test, a window of operation" will be determined. This window of operation establishes some tol erance. The tolerance the installer builds in provides room within the setup for those things which might affect com bustion. Those things which might affect combustion can then do so without causing the unit to start sooting/smoking. Things which might affect combustion include a nozzle go ing bad, draft that changes during different climatic condi tions, dirty oil, dirt obstructing the air inlet, etc.
To build in a window of operation," set up the burner to be 2% less in CO2. For example, if you find a reading of 12% CO2, adjust the air inlet shutter to increase the air and drop the CO2 to 10%.
5−Retest the Smoke
With a drop in the CO2 and increase in the air you should see that the smoke has returned to 0.
6−Retest the Overfire Draft
This test serves to confirm that you have not increased the air too much. Again you do not want a positive pressure at the test port. It should still be 0.02" w.c. (5.0 kPa) less than the draft from the vent connector. You may need to increase the stack draft by adjusting the barometric damper.
2
Page 23
Page 24
7−Stack Temperature
Take a stack temperature reading in the vent connector pipe. Subtract the room air temperature from the stack temperature. This will give you the net stack temperature. Using efficiency charts provided in most CO2 analyzers you can tell at what ef ficiency the furnace is operating.
V−DISASSEMBLY PROCEDURES
Use the following procedures to access and disassemble the burner or blower if service to either is needed.
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at discon nect switch(es). Unit may have multiple power supplies.
A−Disassembling Burner
The burner assembly is attached to the vestibule panel by three nuts. Slots are provided in the mounting flange for removing the burner assembly from the vestibule. By loosening the nuts and by turning the whole burner as sembly counterclockwise (figure 29), the entire burner as sembly will come out of the furnace. There is adequate wire to remove the burner without disconnecting wires. Once re moved, just turn the burner around in the vest panel area.
NOTE−Before disassembling any part of the burner, turn off power and oil supply to the burner.
BURNER REMOVAL
First, loosen three nuts which
attach burner to vest panel.
nuts
Next, rotate burner counterclockwise
on slots then pull toward you.
IGNITION TRANSFORMER
IGNITION
TRANSFORMER
SCREWS
SCREW TO OPEN
ACCESS DOOR
FIGURE 30
SCREWS
ACCESS
DOOR
2−Removing Cad Cell
1− Loosen the screw to the back access door until door
opens. See figures 30 and 31.
2− The cad cell will be located on the right side of the
chassis wall hung on a bracket. See figure 31.
3− Remove by loosening the screw on the bracket.
4− Disconnect the leads from the primary control termi
nal strip.
FIGURE 29
1−Removing Ignition Transformer
1− Remove all four screws located on the side of the
ignition transformer. See figure 30.
2− Lift the ignition transformer straight up. Do
not hinge back. Porcelain isolators may break if hinged back.
NOTE−When testing the solid state transformer, do not use a transformer tester designed for iron magnet trans formers. Damage to the tester may result
CAD CELL
CAD CELL
SCREW
ACCESS
DOOR
FIGURE 31
Page 24
Page 25
3−Removing Gun Assembly
1− Loosen the screw to the back access door until door
opens. See figures 30 and 31.
2− Remove flare fitting nut on oil line at pipe adjusting
plate located on outside of blower housing.
3− Remove nut connecting oil line to gun assembly oil
line. See figure 32.
4− Remove gun assembly from air tube.
5− Remove transformer leads.
NOTE−When reinstalling gun assembly, check and set position and Z" dimension as shown in figure
27.
NOTE−When reconnecting gun assembly oil line, make sure flat side of nut goes first.
5−Removing Motor / Combustion Air Blower
1− Disconnect supply line at pump and oil line at gun
assembly as shown in figure 33.
2− If motor and blower wheel are to be removed away
from the burner, disconnect motor wiring harness from the primary control. If the motor and blower wheel only need to be removed to check and clean, there is adequate wire in the motor wiring harness without disconnecting.
3− Loosen two bolts securing motor to blower hous
ing. Key hole slots are provided for easy removal. See figure 34.
4− Loosen allen set screw holding the blower wheel
onto the motor shaft and remove blower wheel.
COMBUSTION AIR MOTOR & WHEEL
GUN ASSEMBLY
Remove
both nuts
Gun
Assembly
FIGURE 32
4−Removing Oil Pump
1− Disconnect supply line at pump and oil line at gun
assembly.
2− Loosen two bolts on sides of pump securing pump
to blower housing. See figure 33.
3− Detach pump and motor shaft coupler from pump.
OIL PUMP
OIL LINE GUN
ASSEMBLY ENTRANCE
SUPPLY LINE
INLET
BLOWER
MOTOR
BOLT
BOLT
PUMP
FIGURE 34
NOTE−When reinstalling blower wheel use the AFII mul tipurpose gauge (Beckett part # T−500) to space the dis tance from the back of the blower wheel to the face of the motor (1/16" [2 mm]).
B−Removing Indoor Blower
1− Turn off electric power to furnace.
2− Remove blower access door.
3− Remove two screws located in the front blower rails. See
figure 35.
4− Pull blower forward enough to disconnect the motor leads
and the secondary limit on OHR units.
5− Pull blower assembly out and place to the side.
INDOOR BLOWER (OHR23 SHOWN)
BOLT BOLT
OIL PUMP MOTOR
FIGURE 33
Page 25
MOTOR LEADS
SCREW
SECONDARY
LIMIT
(OHR only)
SCREW
FIGURE 35
Page 26
VI−TYPICAL OPERATING CHARACTERISTICS
Unit
Speeds
A−Blower Operation and Adjustment
NOTE− The following is a generalized procedure and does not apply to all thermostat controls.
1− Blower operation is dependent on thermostat con
trol system.
2− Generally, blower operation is set at thermostat sub
base fan switch. With fan switch in ON position, blower operates continuously. With fan switch in AUTO position, blower cycles with demand.
3− In all cases, blower and entire unit will be off when line
voltage is disconnected.
B−Temperature Rise
Temperature rise for O23, OHR23, and OF23 units depends on unit input, blower speed, blower horsepower and static pressure. The blower speed must be set for unit operation within the range of AIR TEMP. RISE °F" listed on the unit rat ing plate.
To Measure Temperature Rise:
1. Place plenum thermometers in the supply and return air plenums. Locate supply air thermometer in the first hori zontal run of the plenum where it will not pick up radiant heat from the heat exchanger.
2. Set thermostat to highest setting.
3. After plenum thermometers have reached their highest and steadiest readings, subtract the two readings. The difference should be in the range listed on the unit rating plate. If the temperature is too low, decrease blower speed. If temperature is too high in crease blower speed to reduce temperature. To change blower speed see Blower Speed section.
C−Blower Speed
Blower speed selection is accomplished by changing the wires at the blower motor spade connector.
To Change Blower Speed
1− Turn off electric power to furnace.
2− Remove blower access door.
3− Remove two screws located in the front blower rails.
4− Pull blower assembly forward enough to disconnect the
motor leads.
5− Disconnect heating (red) and / or Cooling (black)
wire(s) from the motor. The common (white) wire al ways remains on C = common.
6− Select the desired speed for heating and cooling
(H = high, M = medium, L = Low). Table 9 lists the factory connections.
7− If cooling and heating speeds are to be the same
speed, disconnect and discard the cooling wire. Jumper the A and H spade terminals on the BCC2 and BCC3 board and jumper COOL to HEAT on the ST9103A board. Run the heating terminal wire from the BCC2, BCC3 and ST9103A board to the correct spade connection on the blower motor.
8− To achieve low speed on continuous blower on the
ST9103A board, run a FIELD supplied wire (16 AWG or larger) from blower motor low speed terminal to the ST9103A CONT terminal.
TABLE 9
BLOWER SPEED SELECTION
Factory Connected
Speed Taps
Cool
(Black)
Q270 M L 3 Q3105/120 H M 3 Q5140/154 H M 3
Heat
(Red)
Speeds
Available
D−External Static Pressure
1. Measure tap locations as shown in figure 36.
2. Punch a 1/4" (6 mm) diam eter hole in supply and re turn air plenums. Insert manometer hose flush with inside edge of hole or in sulation. Seal around the hose with permagum. Con nect the zero end of the ma nometer to the discharge (supply) side of the sys tem. On ducted systems, connect the other end of manometer to the return duct as above. For systems with non−ducted returns, leave the other end of the manometer open to the atmosphere.
3. With only the blower motor running and the evapo rator coil dry, observe the manometer reading. Ad just blower motor speed to deliver the air desired according to the job requirements.
4. Pressure drop must not exceed 0.5" W.C. (124.3 Pa).
5. Seal around the hole when the check is complete.
STATIC PRESSURE
TEST
MANOMETER
OIL UNIT
FIGURE 36
Page 26
Page 27
VII−MAINTENANCE
CAUTION
Never operate unit with access panels to the blower compartment off or partially open.
A−Filters
If throwaway type filters are used, check monthly and replace when necessary to assure proper furnace op eration. Replace filters with like kind and size.
If reusable type filters are used, check monthly and clean with water and mild detergent when necessary. When dry, they should be sprayed with filter handicoater prior to reinstallation. Filter handicoater is RP Products coating no. 418 and is avail able as Lennox part no. P85069.
B−Cleaning Heat Exchanger
NOTE−Use papers or protective covering in front of fur nace while cleaning furnace.
Cleaning the heat exchanger is made easier with a heat exchanger cleanout kit ABRSH380 (catalog # 35K09) available from Lennox.
1− Remove vent pipe from furnace. 2− Remove locking screws and caps from cleanout
tubes. Remove vent access elbow.
3− Using a long spiral wire brush, sweep down the outer
drum of the heat exchanger. Then using the hose at tachment, vacuum out loose debris.
4− Remove locking screw and cap from the observation
tube and with the spiral wire brush, reach upward to ward the rear of the heat exchanger to clean out the crossover tube.
NOTE− Do not attempt to clean the combustion chamber. It can be easily damaged.
5− Replace the cleanout caps and vent access elbow.
Make sure locking screws are secure.
6− Brush out and vacuum the vent outlet area of the outer
drum and replace vent pipe.
7− Clean around the burner, blower deck and vestibule
area.
C−Annual Burner Maintenance
1− Replace the oil supply line filter.
2− Remove and clean the pump strainer if applicable.
3− Replace the nozzle with an equivalent nozzle.
4− Check the pump pressure when changing nozzle.
5− Clean and inspect the electrodes for damage, re
placing any that are cracked or chipped.
6− Clean the combustion head of all lint and soot.
7− Inspect the transformer cables and connectors.
8− Remove and clean the cad cell.
9− Clean the blower wheel and the air control of any lint.
10− Check all wiring for secure connections or insulation
breaks.
11− Readjust the burner as described in section IV of this
manual.
D−Supply Air Blower
1 Disconnect power to unit.
2 Check and clean blower wheel.
3 Motors are prelubricated for extended life; no further lu
brication is required.
E−Vent Pipe
The vent pipe should be inspected annually. Remove and clean any soot or ash found in the vent pipe. Vent pipe dete riorates from the inside out and must be disconnected in or der to check thoroughly. Inspect pipe for holes or rusted areas. Inspect the vent control device and replace if found defective. Check for tightness and to make sure there is no blockage or leaks.
F−Electrical
1 Check all wiring for loose connections. 2 Check for correct voltage at unit (unit operating). 3 Check ampdraw on blower motor.
Motor Nameplate_________Actual_________
4 Check to see that heat is operating.
Page 27
Page 28
VIII−WIRING DIAGRAMS AND SEQUENCE OF OPERATIONS
2
7
4
1
6
10
4
81212
3
7
9
5
8
12
4
9
O23 / OHR23 / OF23−1 through −4 UNIT OPERATION SEQUENCE:
1. When disconnect is closed, 120V is routed to the blower control board BCC2 (A15). The BCC2 feeds line voltage to transformer (T1).
2. T1 supplies 24VAC to the burner control (A3). In turn, A3 supplies 24VAC to A15, which supplies the indoor ther mostat (not shown) with 24VAC.
3. When there is a call for heat, W1 of the thermostat ener gizes W of the A15 board with 24VAC.
4. A15 energizes combustion air blower relay (K13). When K132 closes, assuming primary limit (S10) and [secon dary limit (S21) in OHR units only] are closed, 24VAC is routed to 1K, which closes 1K1 and 1K2. When 1K2 closes combustion air blower / pump (B6) is energized. Simultaneously 24VAC is routed through the blower relay (K36). When K361 closes blower motor (B6) is ener gized on heating speed.
5. When 1K2 closes the electronic ignitor is energized causing a 14,000VAC spark, igniting the burner. When 1K1 closes the solid state switch and cad cell are ener gized. When the cad cell senses light the solid state switch deenergizes the safety heater, keeping the burner operating.
6. A15 energizes accessory relay (K109). When K1091 closes the accessory terminal on the A15 board is ener gized with 120VAC.
7. When heat demand is satisfied, W1 of the thermostat deenergizes W of the ignition control. W deenergizes K13 in turn deenergizing 1K. When 1K is deener gized B6 and A73 stop immediately. The indoor blower runs for a designated fan off" period (90−330 seconds) as set by jumper on BCC2 control.
8. When there is a call for cooling, Y1 of the thermostat ener gizes Y and G of the A15 board with 24VAC.
9. A15 energizes blower relay K3. When K31 closes B3 starts on the speed set for cooling.
10. A15 energizes accessory relay K109. When K1091 closes the accessory terminal on the A15 board is ener gized with 120VAC.
11.Provided that condensing unit is connected to Y ter minal, cooling will start.
12. When cooling demand is satisfied, Y1 of the thermostat deenergizes Y and G. The indoor blower and condensing unit stops immediately.
Page 28
Page 29
1
6
6
10
9
7
10
9
1
2
4
5
3
8
4
O23 / OHR23 / OF23−5 UNIT OPERATION SEQUENCE:
1. When disconnect is closed, 120V is routed to the blower control board (A15). The blower control board feeds line voltage to transformer (T1).
2. When there is a call for heat, W1 of the thermostat ener gizes W of the A15 board with 24VAC.
3. A15 energizes combustion air inducer B6 assuming pri mary limit (S10) and [secondary limit (S21) in OHR units only] are closed.
4. Burner control A3 energizes the electronic ignitor caus ing a 20,000VAC spark . Burner motor (B6) and pump valve (L35) are delayed for a 15 second pre−purge. The pre−purge is followed by a 15 second trial for ignition.
5. After the pre−purge and trial for ignition (30 seconds) voltage passes through contactor K1 the energizing the indoor blower B3 on heating speed.
6. When heat demand is satisfied, W1 of the thermostat deenergizes W of the ignition control. Combustion air inducer B6 is de−energized. The indoor blower runs for a designated fan off" period (60−150 seconds) as set delay switch on blower control.
7. When there is a call for cooling, Y1 of the thermostat ener gizes Y and G of the A15 board with 24VAC.
8. A15 energizes relay K2. When K2 contacts close, the in door blower B3 energizes on cooling speed.
9. When cooling demand is satisfied, Y1 of the thermostat deenergizes Y and G. The indoor blower and condensing unit stops immediately.
10. When there is a call for continuous fan the indoor blower (B3) is energized on cool speed. If blower control board is wired for continuous fan, the indoor blower will energize on low speed and remain energized after thermostat de mand is satisfied.
Page 29
Page 30
1
3
2
TJERNLUND HORIZONTAL VENTING SYSTEM (SIDESHOT) OPERATION SEQUENCE:
1. When 1K2 closes, 120VAC is routed through the relay/timer, electronic ignitor (A73), and the limit switch.
2. The relay/timer energizes the venter motor.
3. After the venter motor establishes a draft, the N.O. fan proving switch closes completing the circuit to the burner motor.
1
2
3
FIELD CONTROL HORIZONTAL VENTING SYSTEM OPERATION SEQUENCE:
1. When 1K2 closes, 120VAC is routed through the relay.
2. The relay energizes the venter motor.
3. After the venter motor establishes a draft, the N.O. fan proving switch closes, completing the circuit to the burner motor and electronic ignitor (A73).
Page 30
Page 31
IX−TROUBLESHOOTING
Burner failure or improper unit operation can be caused by various conditions. Often the problem can be solved by a logical pro cess of checks and eliminations. The following pages lists a few common problems along with the solutions . Careful l y che c k the most obvious items first before proceeding to more involved procedures.
COMMON CHIMNEY VENTING PROBLEMS
Problem: Top of chimney lower than surrounding objects. Solution:Extend chimney above all objects within 10 feet (3 meters).
Problem: Chimney cap or ventilator. Solution: Remove.
Problem:Obstruction in chimney. Obstruction can be found by
light and mirror reflecting conditions in chimney.
Solution: Use weight to break and dislodge.
Problem: Joist projecting into chimney.
Can be found by lowering a light on an ex tension cord. Solution: Must be handled by a competent brick contractor.
Problem: Break in chimney lining. Can be found by Smoke testbuild smudge fire block ing off other opening and watching for smoke to escape. Solution: Must be handled by a competent brick contractor.
Problem: Collection of soot at narrow space in the flue opening. Can be found by lowering light on extension cord.
Problem: Clean out with weighted brush or bag of loose gravel on end of line.
Problem: Loose−seated pipe in flue opening. Detected by smoke test. Solution: Leaks should be eliminated by cementing all pipe openings.
Problem:Coping restricts opening. Solution:Make opening as large as
inside of chimney.
Problem: Offset. Can be found by lowering light on extension. Solution: Change to straight or long offset.
Problem: Two or more openings into same chimney. Can be found by inspection. Solution: The least important opening must be closed
FIRE
PLACE
DAMPER
FIREPLACE
Problem: Smoke pipe extends into chimney. Detected by measurement of pipe from within or ob servation of pipe by means of a lowered light. Solution: Length of pipe must be reduced to allow end of pipe to be flush with inside of tile.
Problem: Failure to extend the length of the flue partition down to the floor. De tected by inspection or smoke test. Solution: Extend partition to floor level.
ASH DUMP
Problem:Loose fitting clean−out door. Detected by smoke test. Solution: Close all leaks with cement.
Page 31
Page 32
START
BCC2 / BCC3
TROUBLESHOOTING
FLOWCHART
REPLACE
BCC2
NO
(REMOVE R & G JUMPER)
IS
120VAC ACROSS
N & ACC?
YES
JUMPER ACROSS
R &W
YES
YES
DOES UNIT
OPERATE?
NO
IS
24VAC ACROSS
R & C?
YES
JUMPER ACROSS
SCREWS R & G
IS
BLOWER
RUNNING ON HIGH
SPEED?
IS
UNIT LIT?
YES
NO
NO
NO
CHECK: 1−UNIT POWER 2−TRANSFORMER 3−LIMIT SWITCH
IS
120VAC ACROSS
N & A?
YES
CHECK BLOWER
WIRING AND
BLOWER
CHECK: 1−PRIMARY CONTROL 2−IGNITION TRANSFORMER 3−FUEL PUMP 4−ELECTRODES 5−LIMIT SWITCH(ES)
NO
REPLACE
BCC2
IS
120VAC ACROSS
N & ACC?
YES
REMOVE
R & W
JUMPER
AFTER
THE SELECTED
TIME, DOES THE
BLOWER TURN
OFF?
END OF TEST
NO
REPLACE
BCC2
YES
YES
IS BLOWER
RUNNING ON LOW
SPEED, 45 SEC.
AFTER FURNACE LIGHTS?
NO
REPLACE
BCC2
Page 32
NO
IS
120VAC ACROSS
N & H?
NO
IS
24VAC ACROSS
C & V?
NO
CHECK WIRING
YES
CHECK BLOWER
WIRING AND
BLOWER
REPLACE
YES
BCC2
Page 33
Troubelshooting: Blower Control ST9103A
Action System Response
Thermostat calls for heat. (W terminal is energized.)
Thermostat ends call for heat. (W terminal is de−energized.)
Burner fails to light. Oil primary control locks out within lockout timing (timing depends on oil primary control).
Established flame fails. Burner motor is de−energized and oil primary control goes into recycle mode.
Thermostat begins call for cool. (G and Y terminals are energized.)
Thermostat ends call for cool. (G and Y terminals are de−energized.)
Thermostat begins call for fan. (G terminal is energized.)
Thermostat ends call for fan. (G terminal is de−energized.)
ST9103A closes oil primary control T−T connections.
Ignition system and oil primary control start the furnace. Oil flows as long as oil primary control senses flame.
Burner motor is energized and heat fan on delay timing begins. When timing is complete, the circulating fan is energized at heat speed and warm air is delivered to the controlled space.
Oil primary control is de−energized, terminating the burner cycle.
Heat fan off delay timing begins. When timing is complete, the circulating fan is de−ener gized.
ST9103A returns to standby mode (oil primary control and circulating fan are off).
Burner motor is de−energized.
If heat fan has started, it continues through the selected delay off period.
If selected heat fan off delay is longer than the recycle delay timing, the heat fan contin ues to run through the next trial for ignition.
Circulating fan is energized at the cool speed.
Cooling compressor turns on immediately.
Circulating fan and cooling compressor turn off immediately.
Circulating fan is energized immediately at cool speed.
ST9103A may be factory−configured to operate heat speed in this mode.
Circulating fan is de−energized.
Limit switch string opens. Oil primary control shut off the burner.
Circulating fan is energized immediately at heat speed.
ST9103A opens oil primary control T−T connections.
Circulating fan runs as long as limit string stays open.
If there is a call for cooling or fan, the circulating fan switches from heat speed to cool speed.
Limit switch string closes. ST9103A begins heat fan off delay sequence.
Circulating fan turns off after the selected heat fan off delay timing.
ST9103A closes oil primary control T−T connections.
Oil primary control is energized, initiating burner light off.
Continuous circulating fan is connected. (Optional connectors are available for separate circu lating fan speed tap.)
Electronic air cleaner is connected. (Optional connectors are available for 120 Vac elec tronic air cleaner.)
Humidity control is connected. (Optional connectors are available for 120 Vac humidi fier.)
Circulating fan is energized at low speed when there is no call for heat, cool or fan.
If fan operation is required by a call for heat, cool, or fan, the ST9103A switches off the continuous fan speed tap before energizing the other fan speed.
Electronic air cleaner (EAC) connections are energized when the heat or cool speed of the circulating fan is energized. EAC connections are not energized when the optional continuous fan terminal is energized.
Humidifier connections are energized when the burner motor is energized.
Page 33
Page 34
Troubleshooting O23 / OHR23 / OF23 −1 through −4 Units
y
yy
Check f
t
Thermostat
mostat terminals on primary fault is in the thermostat circuit
the burner starts, fault is in the
Pri
ili
l
indi
black
hite leads to th
p
blower wheel by hand. If seized, power to the motor and burner
Burner fails to start.
Source Procedure Causes Correction
Thermostat in OFF or COOL Switch to HEAT.
Thermostat Check thermostat settings.
Check burner motor, primary
Safety Overloads
Power
CAD Cell
Primary Control
Burner
safety control, & auxiliary limit switch.
urnace disconnec
switch & main disconnect.
Touch jumper wire across ther mostat terminals on primary control. If burner starts, then
Disconnect the flame detector wires at the primary control. If
detector circuit.
Place trouble light between the black and white leads. No light
cates that no power is going
to the control.
Place trouble light between the orange and white leads. No light indicates faulty control.
Place the trouble light between the black and white leads to the burner motor. No light indicates that no power is getting to the motor.
Place trouble light between the
and w
blower motor. Light indicates
ower to the motor and burner
fault.
e
Thermostat is set too low
Burner motor overload tripped Push reset button pump motor.
Primary control tripped on safe ty
Auxiliary limit switch tripped on safety
Open switch Close switch.
Blown fuse or tripped circuit breaker
Broken or loose thermostat wires
Loose thermostat screw con nection
Dirty thermostat contacts Clean contacts.
.
Thermostat not level Level thermostat.
Faulty thermostat Replace thermostat.
Flame detector leads are shorted
Flame detector exposed to light Seal off false source of light.
short circuit in the flame detec tor
mary or aux
switch is open
Open circuit between discon nect switch and limit control
Low line voltage or power fail ure
Defective internal control circuit Replace the control.
Blown fuse Replace the fuse.
Binding burner blower wheel
Sized fuel pump
Defective burner motor Replace the motor.
ary contro
Turn thermostat to higher tem perature.
Reset primary control.
Reset auxiliary limit.
Replace fuse or reset circuit breaker.
Repair or replace wires.
Tighten connection.
Separate leads.
Replace detector.
Check adjustment. Set the maximum setting.
Jumper terminals; if burner starts, switch is faulty, replace control.
Trace wiring and repair or re place it.
Call the power company.
Turn off power and rotate the blower wheel by hand. If seized, free the wheel or replace the fuel pump.
Page 34
Page 35
Burner starts, but no flame is established.
pp
Oil Filters & Oil Line
S
ilk
Air leak i
pggpp
pray (g
serve the oil spray (gun assem
Inspect the nozzle for plugged t Cl
gap
the gap to 5/32 inches and cor
g
to transformer primary
pp
ing or excessive drag
Source Procedure Causes Correction
Check tank gauge or use dip stick.
Oil Supply
Oil Filters & Oil Line
Oil Pump
Coat dip stick with litmus paste and insert into bottom of tank.
Listen for pump whine. Tank shut−off valve closed Open valve.
Listen for pump whine.
Open bleed valve or gauge port.
tart the burner. No oil or m
oil indicates loss or prime.
Install pressure gauge on pump and read pressure. Should not be less than 140 psi.
y
No oil in tank Fill tank.
Water in oil tank
Oil line filter is plugged Replace filter cartridges.
Kinks or restriction in oil line Repair or replace oil line.
Plugged fuel pump strainer Clean strainer or replace pump.
n oil supply line
Pump is partially or completely frozen. No pressure and the motor locks out on overload.
Coupling disengaged or broken
− no pressure
Fuel pressure too low Adjust to 100 psi.
If water depth exceeds 1 inch, pump or drain water.
Locate and correct leak.
Tighten all connections.
Replace pump.
Re−engage or replace coupling.
Nozzle
Ignition Electrodes
Ignition
Transformer
Burner Motor
Disconnect ignition leads. Ob serve the oil s bly must be removed from unit). Inspect the nozzle for plugged orifice or carbon build−up around orifice.
Remove gun assembly and in spect electrodes and leads.
Connect ignition leads to the transformer. Start burner and ob serve spark. Check line voltage
Motor does not come up to speed and trips out on overload. Turn off power and rotate blower wheel by hand to check for bind
un assem
.
.
Nozzle orifice plugged
Nozzle strainer plugged
Poor or off center spray
Fouled or shorted electrodes
Dirty electrodes and leads
Eroded electrode tips
Improper electrode gap spacing
Improper position of electrode tips
Bad buss bar connection Retension and realign.
Cracked or chipped insulators Replace electrode.
Cracked or burned lead insula tors
Low line voltage
Burned out transformer wind ings.
No spark or weak spark
Low line voltage
Pump or blower overloading motor
Faulty motor Replace motor.
Replace nozzle with the same size, spray angle, and spray
ype.
ean electrode leads.
Clean electrode tips and reset the rectly position tips.
Replace electrode leads.
Check voltage at power source. Correct cause of voltage drop or call the power company.
Replace the transformer.
Properly ground the transformer case.
Check voltage at power source. Correct cause of voltage drop or the call power company.
Correct cause of overloading.
to 5/32 inches and cor
Page 35
Page 36
Burner starts and fires, but locks out on safety.
due to poor
,
across flame
If fire is good
fault may be
p
After burner
,
If fire is good
Fl
detector termi
in the fuel sys
pp
Source Procedure Causes Correction
Unbalanced fire Replace nozzle
Too much air − −lean short fire
Too little air − − long dirty fire
Excessive draft
Too little draft or restriction
Dirty cad cell face Clean cad cell face.
,
Faulty cad cell − exceeds 1500 hms
Loose or defective cad cell wires
Primary control circuit defective Replace primary control.
Poor Fire
Flame Detector
Primary Control
After burner fires, immedi ately jumper across flame detector termi nals at the pri mary control.
If burner con tinues to run, this may be
fire. Inspect fire.
If fire is good fault is in the flame detector. Check detec tor circuit.
If burner locks out on safety, fault is in the primary con trol.
Reduce combustion air − check combustion.
Increase combustion air − check combustion.
Adjust barometric damper for correct draft.
Correct draft or remove restric tion.
Replace cad cell.
Secure connections or replace cad cell holder and wire leads.
Burner starts and fires, but loses flame and locks out on safety.
Source Procedure Causes Correction
Unbalanced fire Replace nozzle
Poor Fire
ame Detector
Oil Supply
After burner fires, immedi ately jumper across flame detector termi nals at the pri mary control.
Listen for pump whine
If burner con tinues to run (does not lock out of safety),
due to poor fire. Inspect fire.
If fire is good fault is in the flame detector. Check detec tor circuit.
If burner loses flame (does not lock out on safety), fault is in the fuel sys tem.
Too much air − − lean short fire
Too little air − − long dirty fire
Excessive draft
Too little draft or restriction
Dirty CAD cell face Clean CAD cell face.
,
Faulty CAD cell − − exceeds 15000 hms
Loose or defective cad cell wires
Pump loses prime − air slug Prime pump at bleed port
Pump loses prime − air leak in supply line
Water slug in line Check oil tank for water (over 1
Partially plugged nozzle or nozzle strainer
Restriction in oil line Clear restriction.
Plugged fuel pump strainer Clean strainer or replace pump.
Cold oil − outdoor tank Change to number 1 oil.
Reduce combustion air − check combustion.
Increase combustion air − check combustion.
Adjust barometric damper for correct draft.
Correct draft or remove restric tion.
Replace CAD cell.
Secure connections or replace cad cell holder and wire leads.
Check supply line for loose con nections and tighten fittings.
inch) pump or drain out water.
Replace nozzle.
Page 36
Page 37
Burner starts and fires, but short cycles (too little heat).
Thermostat
Check thermostat
(
Limit Control
control (black & white leads). If
P
If burner turns
Thermostat
Disconnect
circuit.
wires at the pri
Source Procedure Causes Correction
Heat anticipator set too low Correct heat anticipator setting.
Thermostat Check thermostat.
Connect voltmeter between line voltage connections to primary
Limit Control
ower
control burner cycles due to power inter ruption, it is cycling on limit.
If voltage fluctuates, fault is in the power source. Recheck voltage at the power source.
black & white leads). If
.
Vibration at thermostat Correct source of vibration.
Thermostat in the path of a warm air draft
Dirty furnace air filters Clean or replace filter.
Burner running too slow
Blower motor seized or burned out
Blower bearings seized Replace bearings and shaft.
Blower wheel dirty Clean blower wheel.
Blower wheel in backward Reverse blower wheel.
Wrong motor rotation
Restrictions in return or supply air system
Adjustable limit control set too low
Loose wiring connection Locate and secure connection.
Low or fluctuating line voltage Call power company.
Shield thermostat from draft or relocate.
Increase blower speed to main tain proper temp. rise.
Replace motor.
Replace with properly rotating wheel.
Correct cause of restriction.
Reset limit to maximum stop setting.
Burner runs continuously (too much heat).
Source Procedure Causes Correction
If burner turns
Thermostat
Disconnect thermostat
mary control.
Primary control
off, fault is in the thermostat circuit.
If burner does not turn off, fault is in the primary control.
Shorted or welded thermostat contacts
Stuck thermostat bimetal
Thermostat not level Level thermostat.
Shorted thermostat wires Repair short or replace wires.
Thermostat out of calibration Replace thermostat.
Thermostat in cold draft
Defective primary control
Repair or replace the thermo stat.
Clear obstruction or replace thermostat.
Correct draft or relocate the thermostat.
Replace the defective primary control.
Page 37
Page 38
Burner runs continuously cont.
L
CO
l
Dirt
g
Check b
reading more CO2, stack tem
High stack tem
550 F Net.
Oil P
Inspect fire and check
)
Source Procedure Causes Correction
urner
Combustion
ressure
combustion for CO2, stack tem perature, and smoke
Inspect fire and check
oil pressure.
Too much combustion air Reduce combustion air.
Air leaks into heat exchanger
ow
2
than 10%.
ess
around inspection door, etc.
Excessive draft
Incorrect burner head adjust ment
y or plugged heat exchanger
High smoke readin
more
Insufficient draft Increase draft.
than a trace. Incorrect burner head adjust
ment
Too little combustion air Increase combustion air.
Too little blower air
Blower belt too loose (if
High stack tem perature is more than
F Net.
550
equipped)
Dirty or plugged heat exchanger Clean heat exchanger.
Dirty blower wheel Clean blower wheel.
Dirty furnace air filters Clean or replace filter.
Restricted or closed registers or dampers
Partially plugged or defective nozzle
Oil pressure is too low: less than 100 psi.
Correct cause of air leak.
Adjust barometric draft con trol for correct draft.
Correct burner head setting.
Clean heat exchanger.
Readjust burner.
Correct burner setting.
Increase blower speed to maintain proper temp. rise.
Tighten blower belt.
Readjust registers or damp ers.
Replace nozzle.
Increase oil pressure top 100psi.
Troubelshooting O23 / OHR23 / OF23 −5 Units
Procedure Status Correction
CONDITION 1: BURNER DOES NOT ENERGIZE WITH A CALL FOR HEAT.
1.1 Check limit switch contacts are closed and clean.
1.2 Check for line votage at oil pri mary control. Voltage should be 120V
1.3 Check LED light with burner off, no call for heat (no flame
1.4 Sheild cad cell from external light
1.5 On warm air systems, Remove one thermostat lead and jumper thermostat (T to T) terminals on burner control.
LED is on
LED is off See step 1.5.
LED is off Eliminate exteranl light or shield light from cad cell
LED stays on
Burner energizes
Burner does not energize
Clean contacts. Replace limit switch if necessary.
Check primary voltage source. Take appropiate measures to cor rect if necessary.
Cad cell or control is bad. Control sees external light or connections are shorted. See step 1.4.
Replace cad cell and recheck. If LED stays on remove cad cell lead wires from burner control and recheck.
If LED turns off, replace cad cell bracket assembly.If LED stays on replace buner control
Trouble in thermostat or limit circuit. Check thermostat or limit wir ing connections.
Disconnect line voltage power and open line switch
Check all wiring and tighten any loose connections. RecheckIf burner does not energize replace burner control
Page 38
Page 39
Troubelshooting O23 / OHR23 / OF23 −5 Units Cont.
)
Ignit
Ignition is off
l
cell back in socket B
S
K
p
 Replace cad cell with new cad cell
Reconnect line voltage and close
LED i
S
line switch
control and leave wires open. LED i
Repl
CONDITION 2: BURNER STARTS, THEN LOCKS OUT ON SAFETY WITH LED FLASHING 1/2 SECOND ON
2.1 Check limit switch contacts are closed and clean.
2.2 Check for line votage at oil pri mary control. Voltage should be 120V
2.3 Check LED light with burner off, no call for heat (no flame
2.4 Sheild cad cell from external light
2.5 On warm air systems, Remove one thermostat lead and jumper thermostat (T to T) terminals on burner control.
2.6 Hit reset button on burner con trol
2.7 Listen for spark after burner en ergizes (after 2 second delay)
2.8 Check LED after flame is estab lished, but before buner control lockcs out.
2.9 Check cad cell sighting for view of flame Disconnect line voltage and open line switch Unplug cad cell and clean cad cell face with soft cloth. Check sighting for clear view of flame. Place cad cell back in socket. Reconnect line voltage and close line switch. Start burner
2.10 Check cad cell. Disconnect line voltage and open line switch
lace cad cell with new cad cell
Re Disconnect all wires from thermo
stat to prevent a call for herat. Reconnect line voltage and close line switch. Expose new cad cell to bright light, such as a flash light
2.11 Check cad cell bracket assem bly. Disconnect line voltage and open line switch Remove cad cell wires from quick connect connectors on the burner control and leave wires open.
Apply power to buner control. Place jumper across cad cell termi
nals after buner motor is energized.
.
LED is on
LED is off See step 2.5.
LED is off Eliminate exteranl light or shield light from cad cell
LED stays on
Burner energizes
Burner does not energize
LED stops flashing See step 2.7.
LED continuse to flash
Ignition is off
Ignition is on
Ignition is on but no oil is sprayed to combustion cham ber
LED is on until the burner control locks out and starts flashing during lock out.
Burner locks out See step 2.10
LED is on. Go back to step 2.6
LED is on. Replace cad cell assembly.
1/2 SECOND OFF
urner continuse to run
s off.
s off.
Clean contacts. Replace limit switch if necessary.
Check primary voltage source. Take appropiate measures to cor rect if necessary.
Cad cell or control is bad. Control sees external light or connections are shorted. See step 2.4.
Replace cad cell and recheck. If LED stays on remove cad cell lead wires from burner control and recheck.
If LED turns off, replace cad cell bracket assembly.If LED stays on replace buner control
Trouble in thermostat or limit circuit. Check thermostat or limit wir ing connections.
Disconnect line voltage power and open line switch
Check all wiring and tighten any loose connections. RecheckIf burner does not energize replace burner control
Verify burner control is not in restricted mode. (1/2 second flash)
or could be bad. Check line voltage at ignitor terminals. If line
voltage is present, replace burner contro
Wait for 15 second pre−purge to complete. Check oil valve, oil valve wiring, pump and oil supply.
Replace burner control
ystem is O.
ee step 2.11
ace burner control.
Page 39
Loading...