Lennox O23Q3-105, O23Q3-120, O23Q5-140, O23Q5-154, OHR23Q3-105 Unit Information

...
Corp. 9535−L8
Service Literature
Revised 09/2003
O23 (Elite 80) series units are mid−efficiency upflow oil fur naces manufactured with Beckett oil burners. O23 units are available in heating capacities of 70,000 to 154,000 Btuh (20.5 to 45.1 kW) and cooling applications from 2 through 5 tons (7.0 through 17.6 kW). Refer to Engineering Hand book for proper sizing.
OHR23 (Elite 80) series units are mid−efficiency horizontal / downflow oil furnaces. The OF23 (Elite 80) series units are mid−efficiency loboy upflow oil furnaces, which come in front (OF23) or rear (OF23R) flue openings, both with Beckett oil burners. The OHR23 and OF23(R) units are available in heat ing capacities of 105,000 to 154,000 Btuh (30.8 to 45.1 kW) and cooling applications from 2 through 5 tons (7.0 through
17.6 kW). Refer to Engineering Handbook for proper siz ing.
The drum type heat exchanger comes with strategically placed ports allowing easy cleaning, while the oil burner can be removed for inspection and service. The mainte nance section gives a detailed description on how this is done.
O23/OHR23
OF23
Information contained in this manual is intended for use by experienced HVAC service technicians only. All specifica tions are subject to change. Procedures outlined in this manual are presented as a recommendation only and do not supersede or replace local or state codes.
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at discon nect switch(es). Unit may have multiple power supplies.
WARNING
Improper installation, adjustment, alteration, ser vice or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer or service agency.
O23 SHOWN
TABLE OF CONTENTS
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Indoor Blower Data 4. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts Arrangement 5. . . . . . . . . . . . . . . . . . . . . . . . . . . .
I Unit Components 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
II Placement and Installation 16. . . . . . . . . . . . . . . . . . . .
III Start Up 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IV Heating Systems Service Checks 22. . . . . . . . . . . . .
V Disassembling Burner 24. . . . . . . . . . . . . . . . . . . . . . . .
VI Typical Operating Characteristics 26. . . . . . . . . . . . . .
VII Maintenance 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VIII Wiring Diagrams 28. . . . . . . . . . . . . . . . . . . . . . . . . .
IX Troubleshooting 31. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page 1
1995 Lennox Industries Inc.
Litho U.S.A.
SPECIFICATIONS − O23
Blower wheel nominal
Fil
Model Number O23Q270 O23Q3105/120 O23Q5140/154
InputBtuh (kW) low/high 70,000 (20.5) 105,000 / 120,000(30.8 / 35.2) 140,000 / 154,000(41.0 / 45.1)
Output Btuh (kW) low/high 57,000 (16.7) 85,000 / 97,000 (24.9 / 28.4) 113,000 / 125,000 (33.1 / 36.6)
*A.F.U.E. 83.8% 82.8% (105) / 82.5% (120) 82.5% (140) / 81.4% (154)
Nozzle Rating  gph (L/hr) and spray angle .50 (1.9)  80°hollow
Flue Size Diameterin. (mm) 6 (152) 6 (152) 6 (152)
Oil Burner Pump 1 Stage 1 Stage 1 Stage
Oil Burner Pump Pressure  psig (Pa) 100 (690) 140 (965) 140 (965)
Blower wheel nominal
diameter x width
Blower Motor Output  hp (W) 1/3 (249) 1/3 (249) 3/4 (560)
Nominal cooling that can be added
**Number and size of filtersin. (mm) (1) 16 x 25 x 1 (1) 16 x 25 x 1 (2) 16 x 25 x 1
Shipping weight  lbs. (kg) 1 package 225 (102) 225 (102) 275 (125)
Electrical characteristics 115 volts  60 hertz  1 phase
Two Stage Oil Pump 65A44
Oil Filter 81P89
*Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations. Isolated combustion system rating for nonweatherized furnaces. **Cleanable frame type filters. Furnished with unit in Side Filter Adaptor Kit for field installation external to the cabinet.
Requires return air from both sides of cabinet.Nozzle must be field provided for field conversion to higher heating input.
in. 10 x 6 10 x 8 12 x 9
mm 254 x 152 254 x 203 305 x 229
Tons 2 thru 2.5 2 thru 3.5 3 thru 5
kW 7.0 thru 8.8 7.0 thru 12.3 10.6 thru 17.6
Optional Accessories (Must Be Ordered Extra)
.65 (2.5)  80° (105 input) solid
.75 (2.8)  80°(120 input) solid
.85 (3.2)  80° (140 input) solid
1.00 (3.8)  80° (154 input) solid
SPECIFICATIONS − OHR23
Model Number OHR23Q3105/120 OHR23Q5140/154
InputBtuh (kW) low/high 105,000 / 120,000(30.8 / 35.2) 140,000 / 154,000(41.0 / 45.1)
OutputBtuh (kW) low/high 85,000 / 97,000 (24.9 / 28.4) 113,000 / 125,000 (33.1 / 36.6)
*A.F.U.E. (low/high) 81.8% / 81.3% 81.5% / 81.7%
Nozzle RatingU.S. gph (L/hr) and spray angle
Flue Size Diameterin. (mm) 6 (152) 6 (152)
Oil Burner Pump 1 Stage 1 Stage
Oil Burner Pump Pressure  psig (Pa) 140 (965) 140 (965)
Blower wheel nominal diameter x width  in. (mm) 10 x 10 (254 x 254) 12 x 9 (305 x 229)
Blower motor outputhp (W) 1/2 (373) 3/4 (560)
Nominal cooling that can be added
Shipping weightlbs. (kg) 1 package 225 (102) 265 (120)
Electrical characteristics 115 volts  60 hertz  1 phase
Two Stage Oil Pump 65A44
ter Kit
Downflo Additive Base 35K07 35K08
Horizontal Venting Kit 62J01
Burner Cover 84H26
Vestibule Cover Kit (full front cover) 37K28 37K29
Oil Filter 81P89
*Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations. Isolated combustion system rating for nonweatherized furnaces. Nozzle must be field provided for field conversion to higher heating input.
Catalog no. 35K01 35K06
No. & size of filtersin. (mm) (2) 101/4 x 201/2 x 1 (260 x 521 x 25) (2) 113/4 x 231/2 x 1 (298 x 597 x 25)
Tons 2 to 3 3 to 5
kW 7.0 to 10.6 10.6 to 17.6
Optional Accessories (Must Be Ordered Extra)
.65 (2.5)  8 0 (105 input) solid
.75 (2.8 )  80 (120 input) solid
.85(3.2) 8 0(140 input) solid
1.00 (3.8)  80 (154 input) solid
Page 2
SPECIFICATIONS − OF23
Blower wheel nominal
External Static
External Static
External Static
Model Number
InputBtuh (kW) low/high 105,000 / 120,000(30.8 / 35.2) 140,000 / 154,000(41.0 / 45.1)
OutputBtuh (kW) low/high 85,000 / 97,000 (24.9 / 28.4) 113,000 / 125,000 (33.1 / 36.6)
*A.F.U.E. (low/high)
Nozzle Ratinggph (L/hr) and spray angle
Flue Size Diameterin. (mm) 6 (152) 6 (152)
Oil Burner Pump 1 Stage 1 Stage
Oil Burner Pump Pressure  psig (Pa) 140 (965) 140 (965)
Optional 2 Stage Fuel Pump 65A44
Blower wheel nominal
diameter x width
Blower Motor Outputhp (W) 1/3 (249) 3/4 (560)
Nominal cooling that can be addedTons (kW) 2 thru 3 (7.0 thru 10.6) 3 thru 5 (10.6 thru 17.6)
Number and size of filters
Shipping weightlbs. (kg) 1 package 255 (116) 290 (132)
Electrical Characteristics 115  60 hertz  1 phase
Optional Accessories (Must Be Ordered Extra)
Two Stage Oil Pump 65A44
Oil Filter 91P89
*Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations. Isolated combustion system rating for nonweatherized furnaces. Nozzle must be field provided for field conversion to higher heating input.
in. 10 x 8 12 x 9
mm 254 x 203 305 x 229
in. (1) 18 x 19 x 1 (1) 19 x 21 x 1
mm (1) 457 x 483 x 25 (1) 483 x 533 x 25
OF23Q3105/120
OF23Q3105/120R
82.4% / 81.5%
82.5% / 82.4% R Models
.65 (2.5)  80° (105 input)
.75 (2.8)  80° (120 input)
OF23Q5140/154
OF23Q5140/154R
81.8% / 81.5%
82.0% / 81.8% R Models
.85 (3.2)  80° (140 input)
1.00 (3.8)  80° (154 input)
BLOWER PERFORMANCE DATA − O23
O23Q270 BLOWER PERFORMANCE
External Static
Pressure
in.w.g. Pa cfm L/s cfm L/s cfm L/s
.20 50 1260 595 870 410 520 245
.30 75 1205 570 825 390 500 235
.40 100 1135 535 780 370 480 225
.50 125 1050 495 720 340 450 210
.60 150 960 455 660 310 410 195
NOTE  All air data is measured external to the unit with the air filter in place.
Air Volume at Various Blower Speeds
High Medium Low
O23Q5140/154 BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s cfm L/s cfm L/s
.20 50 1950 920 1620 765 1250 590
.30 75 1900 895 1590 750 1230 580
.40 100 1880 885 1560 735 1210 570
.50 125 1850 875 1540 725 1190 560
.60 150 1800 850 1490 705 1155 545
NOTE  All air data is measured external to the unit with the air filter in place.
O23Q3105/120 BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s cfm L/s cfm L/s
.20. 50 1350 635 1215 575 1080 510
.30 75 1280 605 1180 555 1060 500
.40 100 1210 570 1140 540 1040 490
.50 125 1180 444 1085 510 1000 470
.60 150 1100 520 1025 485 950 450
NOTE  All air data is measured external to the unit with the air filter in place.
Air Volume at Various Blower Speeds
High Medium Low
Air Volume at Various Blower Speeds
High Medium Low
Page 3
BLOWER PERFORMANCE DATA − OHR23
External Static
External Static
External Static
External Static
External Static
External Static
OHR23Q3105/120 BLOWER PERFORMANCE
External Static
Pressure
in w.g. Pa cfm L/s cfm L/s cfm L/s
.20 50 1470 695 1360 640 1070 505
.30 75 1400 660 1300 615 1040 490
.40 100 1330 630 1230 580 1020 480
.50 125 1260 595 1160 545 980 460
.60 150 1180 555 1085 510 920 435
NOTE  All air data is measured external to the unit with air filter in place.
Air Volume at Various Speeds
High Medium Low
BLOWER PERFORMANCE DATA − OF23
FRONT FLUE MODELS
OF23Q3105/120 BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s cfm L/s cfm L/s
.20 50 1490 705 1370 645 1190 560
.30 75 1430 675 1345 635 1180 555
.40 100 1375 650 1280 605 1160 545
.50 125 1300 615 1230 580 1120 530
.60 150 1230 580 1160 545 1080 510
NOTE  All air data is measured external to the unit with the air filter in place.
Air Volume at Various Blower Speeds
High Medium Low
OHR23Q5140/154 BLOWER PERFORMANCE
External Static
Pressure
in w.g. Pa cfm L/s cfm L/s cfm L/s
.20 50 1950 920 1700 800 1340 630
.30 75 1920 905 1650 780 1300 615
.40 100 1900 895 1600 755 1270 600
.50 125 1870 880 1580 745 1220 575
.60 150 1780 840 1500 710 1170 550
NOTE  All air data is measured external to the unit with air filter in place.
Air Volume at Various Speeds
High Medium Low
OF23Q5140/154 BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s cfm L/s cfm L/s
.20 50 2110 995 1850 875 1500 710
.30 75 2035 960 1810 855 1480 700
.40 100 1970 930 1750 825 1450 685
.50 125 1950 920 1690 800 1420 670
.60 150 1880 885 1620 765 1375 650
NOTE  All air data is measured external to the unit with the air filter in place.
Air Volume at Various Blower Speeds
High Medium Low
OF23Q3105/120R BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s cfm L/s cfm L/s
.20 50 1470 695 1330 630 1150 545
.30 75 1410 665 1295 610 1140 540
.40 100 1340 630 1250 590 1125 530
.50 125 1280 605 1190 560 1080 510
.60 150 1205 670 1130 535 1030 485
NOTE  All air data is measured external to the unit with the air filter in place.
Air Volume at Various Blower Speeds
High Medium Low
REAR FLUE MODELS
OF23Q5140/154R BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s cfm L/s cfm L/s
.20 50 2010 950 1765 835 1380 650
.30 75 1960 925 1720 810 1350 635
.40 100 1900 895 1660 785 1330 630
.50 125 1880 885 1600 755 1295 610
.60 150 1800 850 1560 735 1230 580
NOTE  All air data is measured external to the unit with the air filter in place.
Page 4
Air Volume at Various Blower Speeds
High Medium Low
O23 GENERAL PARTS ORIENTATION
HEAT EXCHANGER
CLEANOUT PORT
LIMIT SWITCH
CONTROL BOX
WITH FAN CONTROL
BECKETT
AFII BURNER
INDOOR BLOWER
VENT OPENING
CLEANOUT PORT
OBSERVATION PORT
COMBUSTION AIR INTAKE
BLOWER MOTOR
CAPACITOR
FIGURE 1
LIMIT SWITCH
BECKETT
AFII BURNER
COMBUSTION
AIR INTAKE
OBSERVATION
PORT
CLEANOUT
OHR23 GENERAL PARTS ORIENTATION
CLEANOUT PORT
HEAT EXCHANGER
PORT
VENT OPENING
CONTROL BOX
WITH FAN
CONTROL
BLOWER MOTOR
INDOOR BLOWER
FIGURE 2
Page 5
OF23 GENERAL PARTS ORIENTATION
CLEANOUT
PORT
LIMIT SWITCH
CONTROL BOX
WITH FAN CONTROL
BECKETT
AFII BURNER
FRONT VENT
OPENING (OF23)
COMBUSTION
AIR INTAKE
FILTER
INDOOR BLOWER
REAR VENT
OPENING (OF23R)
HEAT EXCHANGER
CLEANOUT PORT
OBSERVATION PORT
FIGURE 3
NEUTRAL
TERMINALS
24VAC OUTPUT
TO BURNER
(HEAT DEMAND)
24VAC IN FROM
PRIMARY LIMIT
24VAC THERMOSTAT
DEMAND OUTPUT
BCC2 / BCC3 BLOWER CONTROL BOARD
120VAC LINE
VOLTAGE IN
THERMOSTAT TERMINAL STRIP TB1
(DETACHABLE ON EARLY −1 AND −2
MODELS ONLY)
COOLING
SPEED TAP
TERMINAL
TRANSFORMER
120VAC
COMMON
FROM TRANSFORMER
CONTINUOUS FAN
TERMINAL
BLOWER TIME
ADJUSTMENT
JUMPER
24VAC INPUT
HEATING SPEED
TAP TERMINAL
ACCESSORY
TERMINAL
To Remove Terminal Strip,
Grasp Ends of Block Between
Thumb and Forefinger. Push
Block Down and Out.
(Jack / Plug 94)
24VAC COMMON
FROM TRANSFORMER
FIGURE 4
Page 6
I−UNIT COMPONENTS
General parts orientation for the O23, OHR23 and OF23 are shown in figures 1, 2 and 3 respectively. The O23 and OF23 control box, burner, limit switch and cleanout ports may be ac cessed by removing the front access panel, while the OHR23 components are exposed. The blower can be accessed in the O23 and OF23 by removing the blower access panel, while in the OHR23 units two 1/4" screws must be removed before the blower access panel can be removed.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic components. Take precautions during unit instal lation and service to protect the unit’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the control and the technician at the same electrostatic potential. Neutralize electro static charge by touching hand and all tools on an unpainted unit surface before performing any service procedure.
A−Blower Control Board
BCC2 Blower Control Board (Figure 4)
−1 and −2 units
All O23, OHR23 and OF23−1 and −2 oil units utilize the BCC2 (A15) blower control manufactured by Heatcraft. The BCC2 is a printed circuit board which controls the supply air blower and monitors the limit controls and oil burner operation. The control has a nonadjustable, factory preset fanon" timing. Fan off" timing is adjustable. The board is divided into two sec tions, 120 and 24VAC. Line voltage comes into the board on the 120VAC side. See figure 4. See table 1 for BCC2 terminal designations.
DANGER
Shock hazard. Avoid personal injury. Make sure to disconnect power before changing fan off" timing.
Blower Operation and Timing
Blower off" timing (time that the blower operates after the heat demand has been satisfied) is determined by the arrange ment of a jumper across pins on the BCC2 blower control board. See figure 4. To adjust fan off " timing, gently discon nect jumper and reposition across pins corresponding with new timing. Fan on" time is factory set at 45 seconds and is not adjustable.
NOTEIf fan off" time is set too low, residual heat in heat exchanger may cause primary limit S10 or auxilary limit S21 to trip resulting in frequent cycling of blower. If this occurs, adjust blower to longer time setting.
Figure 5 shows the various fan off" timings and how jumper should be positioned. Unit is shipped with a fac tory fan off" setting of 150 seconds. Fan off" time will affect comfort and efficiency and is adjustable to satisfy individual applications. The fan off" timing is initiated after a heating demand but not after a blower or cooling demand (that is, when indoor thermostat switch is changed from ON to AUTO and heating/cooling demand is not present, the blower stops immediately).
FANOFF TIME ADJUSTMENT
TIMING
JUMPER
270
150 90
To adjust fan−off timings:
Remove jumper from BCC2
and select one of the other pin com
binations to achieve the
desired time.
Leave jumper off to achieve
210
330 second fan−off timing.
TIMING PINS (seconds)
Fanoff timing is factory
set at 150 seconds
FIGURE 5
Thermostat Connection
Thermostat wires are connected to terminal strip TB1 found on the BCC2 control board. The terminal strip is c l early marked with the corresponding thermostat designation. The terminal strip (jack / plug 94) is simply removed by grasping the ends of the block and rotating down while pull ing away (see figure 4).
TABLE 1
BLOWER CONTROL A15 TERMINAL DESIGNATIONS
Term inal Type Function
W
R
Y
C
G
NEUTRAL 1/4" Spade 120VAC Neutral
L1 1/4" Spade 120VAC Line Voltage In
A 1/4" Spade
XFMRN 1/4" Spade 120VAC Transformer Common
CF 1/4" Spade
H 1/4" Spade
ACC 1/4" Spade
VALVE SENSE 3/16" Spade 24VAC Output To Burner
LIMIT 1/4" Spade
WI 1/4" Spade
24V 1/4" Spade
COM 1/4" Spade
Detachable Screw Strip
Detachable Screw Strip
Detachable Screw Strip
Detachable Screw Strip
Detachable Screw Strip
Heating Demand
24VAC to Thermostat
Cooling Demand
24VAC Common
To Indoor Thermostat
Blower Demand
Switched 120VAC
to Blower Cooling Tap
Switched 120VAC to
Continuous Blower Tap
Switched 120VAC to
Blower Heating Tap
Switched 120VAC to Accessory
(Electronic Air Cleaner,
Humidifier, Etc. 1 amp rating.)
24VAC In From Primary Limit.
Limit Open: Stops Burner and Turns
On Blower
Limit Closed: Allows Burner
Operation
24VAC Thermostat
Demand Output
24VAC Input
From Transformer
24VAC Common
From Transformer
Page 7
BCC3 Blower Control Board (Figure 4)
−3 and −4 units
All O23, OHR23 and OF23−3 and −4 oil units utilize the BCC3 (A15) blower control manufactured by Heatcraft. The BCC3 is a printed circuit board which controls the supply air blower and monitors the limit controls and oil burner operation. The control has a nonadjustable, factory preset fanon" timing. Fan off" timing is adjustable. The board is divided into two sec tions, 120 and 24VAC. Line voltage comes into the board on the 120VAC side. See figure 4. See table 2 for BCC3 terminal designations.
DANGER
Shock hazard. Avoid personal injury. Make sure to disconnect power before changing fan off" timing.
Blower Operation and Timing
Blower off" timing (time that the blower operates after the heat demand has been satisfied) is determined by the arrange ment of a jumper across pins on the BCC3 blower control board. See figure 4. To adjust fan off " timing, gently discon nect jumper and reposition across pins corresponding with new timing. Fan on" time is factory set at 45 seconds and is not adjustable.
NOTEIf fan off" time is set too low, residual heat in heat exchanger may cause primary limit S10 or auxilary limit S21 to trip resulting in frequent cycling of blower. If this occurs, adjust blower to longer time setting.
Figure 5 shows the various fan off" timings and how jumper should be positioned. Unit is shipped with a fac tory fan off" setting of 150 seconds. Fan off" time will affect comfort and efficiency and is adjustable to satisfy individual applications. The fan off" timing is initiated after a heating demand but not after a blower or cooling demand (that is, when indoor thermostat switch is changed from ON to AUTO and heating/cooling demand is not present, the blower stops immediately).
FANOFF TIME ADJUSTMENT
TIMING
JUMPER
To adjust fan−off timings:
Remove jumper from BCC2
and select one of the other pin com
binations to achieve the
desired time.
Thermostat Connection
Thermostat wires are connected to terminal strip TB1 found on the BCC3 control board. The terminal strip is clea r ly marked with the corresponding thermostat designation. The terminal strip (jack / plug 94) is simply removed by grasping the ends of the block and rotating down while pull ing away (see figure 4).
TABLE 2
BLOWER CONTROL A15 TERMINAL DESIGNATIONS
Term inal Type Function
W
R
Y
C
G
NEUTRAL 1/4" Spade 120VAC Neutral
L1 1/4" Spade 120VAC Line Voltage In
A 1/4" Spade
XFMRN 1/4" Spade 120VAC Transformer Common
CF 1/4" Spade
H 1/4" Spade
ACC 1/4" Spade
VALVE SENSE 3/16" Spade 24VAC Output To Burner
LIMIT 1/4" Spade
WI 1/4" Spade
24V 1/4" Spade
COM 1/4" Spade
Detachable Screw Strip
Detachable Screw Strip
Detachable Screw Strip
Detachable Screw Strip
Detachable Screw Strip
Heating Demand
24VAC to Thermostat
Cooling Demand
24VAC Common
To Indoor Thermostat
Blower Demand
Switched 120VAC
to Blower Cooling Tap
Switched 120VAC to
Continuous Blower Tap
Switched 120VAC to
Blower Heating Tap
Switched 120VAC to Accessory
(Electronic Air Cleaner,
Humidifier, Etc. 4 amp rating.)
24VAC In From Primary Limit.
Limit Open: Stops Burner and Turns
On Blower
Limit Closed: Allows Burner
Operation
24VAC Thermostat
Demand Output
24VAC Input
From Transformer
24VAC Common
From Transformer
270
150 90
Leave jumper off to achieve
210
330 second fan−off timing.
TIMING PINS (seconds)
Fanoff timing is factory
set at 150 seconds
FIGURE 6
Page 8
ST9103A Blower Control Board (Figure 8)
−5 units
All O23, OHR23 and OF23 −5 oil units utilize the ST9103A (A15) blower control manufactured by Honeywell. The ST9103A is a printed circuit board which controls the supply air blower and monitors the limit controls and oil burner opera tion. The control has a nonadjustable, factory preset fanon" timing. Fan off" timing is adjustable. See figure 8 and table 3 for ST9103A terminal designations
ST9103A Blower Control Board
120V
DANGER
Shock hazard. Avoid personal injury. Make sure to disconnect power before changing fan off" timing.
Blower Operation and Timing
The fan on time of 30 seconds is not adjustable. Fan off time (time that the blower operates after the heat demand has been satisfied) can be adjusted by moving the delay switches on the fan control board. Fan off time will affect comfort and is adjustable to satisfy individual applications. See figure 7. Set the heat fan off delay switches to either 60, 90, 120, or 150 seconds. The factory setting is 90 sec onds.
NOTEIf fan off" time is set too low, residual heat in heat exchanger may cause primary limit S10 or auilary limit S21 to trip resulting in frequent cycling of blower. If this occurs, adjust blower to longer time setting.
Thermostat Connection
Thermostat wires are connected directly to the terminlas on the ST9103A board. See figure 8.
Continuous Blower
If the ST9103A blower control board is wired for continuous blower, the blower will energized on low speed and remain energized when heat or cool demand is satisfied. Continuous blower will also energized when indoor thermostat is left in the OFF mode.
Fan Off Delay Switch Settings
ONON ON ON
120 sec90 sec60 sec
Figure 7
150 sec
fan off
delay switches
thermostat
terminal strip
Figure 8
TABLE 3
BLOWER CONTROL A15 TERMINAL DESIGNATIONS
J58 Pin # Function
1 Limit S10
2 L1 120V
3 T1 24V
4 L2 Common
5 Jumpered to Pin 4
6 T2 24V
7 Combustion Air Inducer
120V 8 Jumpered to Pin 7
9 Limit S21 (if used)
Thermostat Connections
G Blower Demand
W Heating Demand
R 24V
Y Cooling Demand
C Common
24 VAC CONNECTIONS
X 24V Transformer
C Common Transformer
120 VAC
S2 Line
S3 120V To Transformer
N, 2, 3, 4, 6, 7 Neutral
CONT Continuous Blower
COOL Cool Tap
HEAT Heat Tap
Page 9
RETAINING
CLIP
HEAD
INSULATOR
−1THROUGH −4 UNIT OIL BURNER PARTS ARRANGEMENT
AIR TUBE SCREWS
HOLE PLUG
ELECTRONIC IGNITION
TRANSFORMER
MAIN
HOUSING
ASSY
ESCUTCHEON
PLATE
CONNECTOR
TUBE
AIR TUBE
ASSY FOR
FB HEADS
FB–HEAD
NOZZLE
ADAPTER
NOZZLE LINE
ELECTRODE HEAD
FLANGE
GASKET
ASSY.
FLANGE
ELECTRODE
ASSY
REAR ACCESS
DOOR GASKET
VIEW PORT
REAR ACCESS
DOOR ASSY
OIL PUMP
SPLINED
NUT
ELECTRONIC IGNITION
TRANSFORMER
BURNER
CONTROL
RESET
BUTTON
AIR
ADJUSTMENT
0
3 4 5
6 7 8
DIAL
COUPLING
COMBUSTION AIR
MOTOR
BLOWER
FIGURE 9
Page 10
WHEEL
INLET
AIR SCOOP
−5 UNIT BURNER PARTS ARRANGEMENT
RETAINING
CLIP
HEAD
INSULATOR
AIR TUBE
ASSY FOR
FB HEADS
1/4" HEX
HEAD SCREW
FB−HEAD
NOZZLE
ADAPTER
ELECTRODE HEAD
FLANGE
GASKET
NOZZLE LINE
ASSY.
ELECTRODE
FLANGE
ASSY
AIR TUBE SCREWS
ELECTRONIC IGNITION
TRANSFORMER
ESCUTCHEON
CONNECTOR
PEDESTAL
PREMOUNTED PRE−PURGE VALVE
MAIN
HOUSING
ASSY
PLATE
TUBE
REAR ACCESS
DOOR ASSY
SPLINED
NUT
FUEL PUMP
COUPLING
REAR ACCESS
DOOR GASKET
MOTOR
IGNITOR
PRIMARY
CONTROL
BLOWER
WHEEL
4X4
BOX
0
3 4 5
6 7 8
AIR ADJ. DIAL
INLET
AIR SCOOP
FIGURE 10
Page 11
TABLE 4
FURNACE / BURNER SPECIFICATIONS
Unit
70 35K74 AFII 85 3.0
105 35K75 AFII 85 4.0
120 35K75 AFII 85 4.5
140 35K76 AFII 150 6.0
154 35K76 AFII 150 6.5
*NOTE: The initial air dial setting is provided to get unit started. The air dial setting MUST be adjusted after startup to achieve proper combustion.
Lennox Burner
Part Number
Burner
Model
*Initial Air Dial Setting
Output
57,000 BTU
(16.7 kW)
84,000 BTU
(24.6 kW)
105,000 BTU
(30.8 kW)
112,000 BTU
(32.8 kW)
125,000 BTU
(36.6 kW)
Nozzle Size
(Delevan)
0.50 X 80A
0.65 X 80B
0.75 X 80B
0.85 X 80B
1.00 X 80B
Pump
Pressure
100 psig
(689.5 kPa)
140 psig
965.3 kPa)
140 psig
965.3 kPa)
140 psig
965.3 kPa)
140 psig
965.3 kPa)
Head
FB0
FB3
FB3
FB6
FB6
B−Burner (Figures 9 & 10)
The O23, OHR23, and OF23 oil furnaces use the Beckett AFII burner. The oil burner provides an atomized oil vapor mixed with the correct proportion of air when it is ignited in the com bustion chamber. Oil burner minimum and maximum ratings are listed on the unit nameplate. Proper air adjustment for these ratings is achieved through the air adjustment dial. Set air dial to the initial air dial setting (see table 4). After start up adjust air dial to achieve proper combustion. Remember to tighten set screw on air dial.
The AFII burner is available in five sizes with either a single or two stage pump. Table 4 identifies the burners used in Lennox units. Figures 9 and 10 show the typical layout of the burner assembly.
1−Combustion Air Blower / Pump Motor (B6)
The burner is activated by the primary control. A com bustion air blower is mounted on the motor shaft. The motor shaft also connects to the direct drive oil pump through a coupler. The burner motor turns both the com bustion air blower and the oil pump. The motor operates at 3500 RPM.
Burner motors are overload protected. In the event of excess motor temperature or current, the overload opens to de−energize the motor. The overload automat ically resets after temperature has returned to normal. Keep motor clean to prevent starting switch from sticking. All AFII motors are permanently lubricated. No further oiling is required.
2−Combustion Air Blower / Pump Fuse (F22)
(−140 and −154 CSA units only)
In the −140 and −154 Canadian units an in line fuse (F22) is used between the line voltage from the BCC2 blower con trol and the blower / pump motor. The fuse is rated at 300 volts and 15 amps.
3− Pump (−1 through −4 units)
The O23, OHR23, and OF23 oil furnaces use a single stage, 3450 RPM pump. A two stage pump is available as an option (catalog # 65A44). The oil burner is shipped from factory for use in a single line system. To convert the pump to a two line system, install the bypass plug pro vided in the attached bag according to the accompany ing instructions.
4− Pump (−5 units only)
The O23, OHR23 and OF23−5 units all utilize the Cleancut Fuel Unit manufactured by Becket. This pump uses a sole noid valve to control the piston cut−on cut−off operation instead of a cone valve and diaphram used by other con ventional pumps. The solenoid works with the R7184B Honeywell burner control to provide cut−on cut−off opera tion while the burner motor is at full speed.
At startup the pump shaft is brought to full speed before the solenoid is energized. At this time low pressure oil (approximatley 20−25 psi) from the gearset circulates around the pressure regulator piston which is closed and through the open solenoid valve. The solenoid valve re turns the oil to either the cover cavity (one pipe) or return line (two pipe). When the solenoid vavle is energized, it closes (and remains closed while energized) blocking the return path to the cover cavity and return line creating pres sure build up in the piston cavity. The piston opens and reg ulates pressure and delivers pressurized oil to the nozzle.
At shutdown the solenoid valve will de−energize and open before the pump shaft rotation stops. When the solenoid valve opens the oil by−passes the cover cavity and return line causing a pressure drop in the piston cavity. The piston closes blocking oil to the nozzle while the burner motor is running at full speed.
Page 12