Lennox o23v User Manual

Corp. 0609−L1
Service Literature

O23V SERIES UNITS

The O23V is a member of the DAVE LENNOX SIGNA­TUREt COLLECTION t. The O23V is an upflow oil fur-
nace equipped with a variable speed motor and manufac­tured with a Beckett oil burner. The O23V is available in heating capacities of 70,000 to 154,000 Btuh (20.5 to 45.1 kW) with AFUE up to 83% and cooling applications from 1 1/2 to 5 tons (5.3 through 17.6 kW). Refer to Engineering Handbook for proper sizing.
The drum type heat exchanger comes with strategically placed ports allowing easy cleaning, while the oil burner can be removed for inspection and service. The mainte­nance section gives a detailed description on how this is done.
Information contained in this manual is intended for use by experienced HVAC service technicians only. All specifica­tions are subject to change. Procedures outlined in this manual are presented as a recommendation only and do not supersede or replace local or state codes.
O23V
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at discon­nect switch(es). Unit may have multiple power supplies.
WARNING
Improper installation, adjustment, alteration, ser­vice or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer or service agency.
IMPORTANT
If using programmable thermostat, be sure to use a type of thermostat that retains its memory in event of a power loss.
TABLE OF CONTENTS
General Page 1. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications Page 2. . . . . . . . . . . . . . . . . . . . . . .
Parts Arrangement Page 3. . . . . . . . . . . . . . . . . .
I Unit Components Page 3. . . . . . . . . . . . . . . . . .
II Placement and Installation Page 11. . . . . . . . . .
III Start Up Page 16. . . . . . . . . . . . . . . . . . . . . . . . . .
IV Heating Systems Service Checks Page 17. . .
V Disassembling Burner Page 19. . . . . . . . . . . . . .
VI Typical Operating Characteristics Page 21. . .
VII Maintenance Page 22. . . . . . . . . . . . . . . . . . . . .
VIII Wiring Diagrams Page 23. . . . . . . . . . . . . . . .
IX Troubleshooting Page 25. . . . . . . . . . . . . . . . . .
Page 1
© 2005 Lennox Industries Inc.
Litho U.S.A.
SPECIFICATIONS
Perf
g
g
Oil Heating
ormance
Low Fire
High Fire
Flue Connection Round − in. (mm) 6 (152) 6 (152) 6 (152)
Temperature Rise Range °F (°C)
Oil Burner
Nozzle rating − gph (L/hr) − Low
Nozzle spray angle − Low 80° hollow 80° solid 80° solid
Oil Burner Pump Pressure − psig (Pa) 100 (690) 140 (965) 140 (965)
Oil Burner Air Inlet Connection (dia.) − in (mm) 4 (102) 4 (102) 4 (102)
Blower Data
Wheel nom. diameter x width − in. (mm)
Nominal add−on cooling − Tons (kW) 1.5 − 3 (5.3 − 10.6) 2 − 3.5 (7.0 − 12.3) 3 − 5 (10.6 − 17.6)
2
Filter
Shipping weight  lbs. (kg) 1 package 225 (102) 225 (102) 275 (125)
Electrical Characteristics 120V−60hz−1ph 120V−60hz−1ph 120V−60hz−1ph
Maximum overcurrent protection (amps) 15 15 15
Model Number O23V2/3−70/90 O23V3/4−105/120 O23V5−140/154
Input − Btuh (kW)
Output − Btuh (kW)
Input
Output
1
A.F.U.E.
70,000 (20.5)
58,000 (16.7)
90,000 (26.4) 119,000(34.8) 154,000(45.1)
74,000 (21.7)
83% 81% 81%
50 − 80 (28 − 44)
105,000 (30.8) 140,000 (41.0)
85,000 (24.9) 113,000 (33.1)
97,000 (24.9) 125,000 (36.6)
50 − 80 (28 − 44) 55 − 85 (31 − 47)
.50 (1.9) .65 (2.5) .85 (3.2)
4
High
4
High 80° solid 80° solid 80° solid
4
.65 (2.5)
4
.75 (2.8)
4
1.00 (3.8)
Oil Burner Pump 1 Stage 1 Stage 1 Stage
Motor hp (W) 1/2 (373) 1/2 (373) 3/4 (560)
10 x 8 (254 x 203)
Number of filters 1 1
Size of filters − in.
mm
16 x 25 x 1 16 x 25 x 1 16 x 25 x 1
406 x 635 x 25 406 x 635 x 25 406 x 635 x 25
10 x 10 (254 x 254) 12 x 11 (305 x 280)
3
2
Optional Accessories − Must Be Ordered Extra
Half−Height Coil Case
Fits uncased C33 coils B"−width B"−width C"−width
Dimensions − in. 5 x 19−1/2 x 21−3/4 5 x 19−1/2 x 21−3/4 5 x 22−1/2 x 22−7/8
mm 127 x 495 x 552 127 x 495 x 552 127 x 572 x 581
Oil Filters
10 micron without mounting bracket 81P89 81P89 81P89
10 micron with mounting bracket 53P92 53P92 53P92
Replacement cartridge − 10 micron, 45 gph 53P93 53P93 53P93
Filter restriction indicator gauge 53P90 53P90 53P90
SignatureStatt Home Comfort Control 81M27 81M27 81M27
Two Stage Oil Pump 65A44 65A44 65A44
1
Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations. Isolated combustion system rating for non−weatherized furnaces.
2
Cleanable frame type filters. Furnished with unit in Side Filter Adaptor Kit for field installation external to the cabinet.
3
Requires return air from both sides of cabinet.
4
Nozzle must be field provided for field conversion to higher heating input.
19M11 19M11 19M12
Page 2
O23 GENERAL PARTS ORIENTATION
HEAT EXCHANGER
CLEAN-OUT PORT
LIMIT SWITCH
CONTROL BOX
WITH FAN CONTROL
BECKETT
AFII BURNER
INDOOR BLOWER
I−UNIT COMPONENTS
VENT OPENING
CLEAN-OUT PORT
OBSERVATION PORT
COMBUSTION AIR INTAKE
VARIABLE SPEED
BLOWER MOTOR
FIGURE 1
A−Blower Control Board (A54) Figure 2
General parts orientation for the O23V is shown in fig­ure 1. The O23V control box, burner, limit switch and clean-out ports may be accessed by removing the front access panel. The blower can be accessed by removing the blower access panel.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic components. Take precautions during unit instal­lation and service to protect the unit’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the control and the technician at the same electrostatic potential. Neutralize electro­static charge by touching hand and all tools on an unpainted unit surface before performing any service procedure.
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
O23V units are equipped with a variable speed motor which is controlled by the A54 blower control board. Blower control board settings and operation are described in this section.
O23V units equipped with a variable speed motor are ca­pable of maintaining a specified CFM throughout the exter­nal static range. A particular CFM can be obtained by posi­tioning jumpers (COOL, HEAT, and ADJUST) on the blower control board. The HEAT and COOL jumpers are labeled A, B, C and D; each letter corresponds with an air volume (CFM) setting. The ADJUST jumper is labeled Test, −, +, and Norm. The + and − pin settings are used to add or subtract a percentage of the CFM selected in the COOL mode only. The Test jumper is used to operate the motor in the test mode.
Page 3
Factory settings for the blower speed jumpers are given in the wiring diagram. Use tables 1, 2 and 3 to determine the correct air volume for operation in heat and cool mode.
The CFM LED located on the blower control board flashes one time per 100 cfm to indicate selected blower speed. For example, if the unit is operating at 1000 CFM, CFM LED will flash 10 times.
At times, the light may appear to flicker or glow. This takes place when the control is communicating with the motor between cycles. This is normal operation. Read through the jumper settings section before adjusting the jumper to obtain the appropriate blower speed.
Blower Control Board (A54)
16−PIN PLUG
(BOARD TO MOTOR)
To change jumper positions, gently pull the jumper off the pins and place it on the desired set of pins. Th e fo ll o w i n g sec t i o n outlines the different jumper selections available and conditions associated with each one (see figure 2).
After the CFM for each application has been deter­mined, the jumper settings must be adjusted to reflect those given in tables 1, 2 and 3. From the tables, deter­mine which row most closely matches the desired CFM. Once a specific row has been chosen (+, NORMAL, or
−), CFM volumes from other rows cannot be used. Page 5 has descriptions of the jumper selections.
The variable speed motor slowly ramps up to and down from the selected air flow during both cooling and heat­ing demand. This minimizes noise and eliminates the initial blast of air when the blower is initially energized.
DIAGNOSTIC LED
ADJUST SELECTOR PINS (Setting affect cooling only)
HEATING SPEED SELECTOR PINS (SEE TABLE)
O23V−Q2/3−090 O23V−Q3/4−120
O23V−Q2/3−070 O23V−Q3/4−105 O23V−Q5−140
FIGURE 2
COOLING SPEED SELECTOR PINS
NOTE − The JW1 resistor must be cut to activate the HUM terminal.
O23V−Q5−154
HEAT SPEED SELECTOR PINS (JUMPERS)
Page 4
ADJUST
The ADJUST pins allow the motor to run at approximately 15% higher, or approximately 15% lower, than normal speed. Tables 1, 2 and 3 give three rows (+, NORM, and −) with their respective CFM volumes. Notice that the normal (NORM) adjustment setting for cool speed position C in table 1 is 800 CFM. The + adjustment setting for that posi­tion is 920 CFM (115% of 800 CFM) and for the − adjust­ment setting is 680 CFM (85% of 800 CFM). After the ad­justment setting has been determined, choose the remaining speed settings from those offered in the table in that row.
The TEST pin is available to bypass the blower control and run the motor at approximately 70% to make sure that the motor is operational. This is used mainly in troubleshoot­ing. The G terminal must be energized for the motor to run.
COOL
The COOL jumper is used to determine the CFM during cooling operation. This jumper selection is activated for cooling when Y1 is energized. Y1 and Y2 must be jump­ered for single stage cooling.
The blower motor runs at 82% of the selected air flow for the first 7−1/2 minutes of each cooling demand. This fea­ture allows for greater humidity removal and saves energy.
Y
7.5 minutes
82%
Y − Cool Demand Present
y − Cool Demand Satisfied
100%
y
60 sec
82%
OFFCALL
When the demand for cool is met, the blower ramps down to 82% for 60 seconds, then turns off.
HEAT
The HEAT jumper is used to determine CFM during heat operation only. These jumper selections are activated only when W1 is energized.
During the heat ON delay, the blower runs at 13% CFM for the first minute, 50% for the second minute, and full CFM after two minutes.
W
60 sec60sec
13%
50%
100%
W − Heat Demand Present
w − Heat Demand Satisfied
w
210 seconds
82%
OFFCALL
When the demand for heat is met, the blower ramps down to 82% for 3−1/2 minutes, then turns off.
Continuous Fan
When the thermostat is set for Continuous Fan" operation and there is no demand for heating or cooling, the blower control will provide 50% of the COOL CFM selected.
G
50%
G − Fan switch ON
g − Fan switch OFF
g
OFFCALL
When a continuous fan is on (G demand present), the fan runs at 50% until switched off; there is no ramp up or off de­lays.
NOTE − With the proper thermostat and subbase, continu­ous blower operation is possible by closing the R to G cir­cuit.
Dehumidification
The A54 blower control board (see figure 2) includes a HUM terminal which provides for connection of a humidis­tat. The JW1 resistor on the blower control board must be cut to activate the HUM terminal. The humidistat must be wired to open on humidity rise. When the dehumidification circuit is used, the variable speed motor will reduce the se­lected air flow rate by 18% when humidity levels are high. An LED (D1) lights when the blower is operating in the de­humidification mode.
Humidification
Terminals are provided on the A15 control board for 120 volt output to operate a humidifier. The HUM" terminal is energized when there is a call for heat. See unit wiring dia­gram.
Electronic Air Cleaner
Terminals are provided on A15 control board for 120 volt output to an electronic air cleaner. The EAC" terminal is energized when there is a call for heat, cool, or continuous blower. See unit wiring diagram.
Page 5
AD
ADJUST
Jumper
A
ADJUST
Jumper
A
ADJUST
Jumper
A
Jumper Setting
+
NORM
AD
Jumper
Setting
+
NORM
TABLE 1
O23V−Q2/3−70/90 Blower Performance
0 through 0.80 in. w.g. (0 through 200 Pa) External Static Pressure Range
Jumper Speed Positions
COOL" Speed HEAT" Speed CONTINUOUS FAN" Speed
T"
A B C D A B C D A B C D
cfm L/sBcfm L/sCcfm L/sDcfm L/sAcfm L/sBcfm L/sCcfm L/sDcfm L/sAcfm L/sBcfm L/sCcfm L/sDcfm L/s
1380 565 1150 540 920 435 690 325 SAME AS NORM
1200 565 1000 470 800 380 600 285 1300 614 1100 520 1000 470 750 354 600 285 500 235 400 190 300 143
1020 480 850 400 680 320 510 240 SAME AS NORM
Do not use −90 −70
TABLE 2
O23V−Q3/4−105/120 Blower Performance
0 through 0.80 in. w.g. (0 through 200 Pa) External Static Pressure Range
Jumper Speed Positions
COOL" Speed HEAT" Speed CONTINUOUS FAN" Speed
T"
A B C D A B C D A B C D
cfm L/sBcfm L/sCcfm L/sDcfm L/sAcfm L/sBcfm L/sCcfm L/sDcfm L/sAcfm L/sBcfm L/sCcfm L/sDcfm L/s
1620 765 1380 650 1150 540 920 435 SAME AS NORM
1400 660 1200 565 1000 470 800 360 1500 713 1400 660 1300 613 1200 565 700 333 600 285 500 235 400 190
1190 560 1020 480 850 400 680 320 SAME AS NORM
Do not use −120 −105
Jumper
Setting
NORM
TABLE 3
O23V−Q5−140/154 Blower Performance
0 through 0.80 in. w.g. (0 through 200 Pa) External Static Pressure Range
Jumper Speed Positions
COOL" Speed HEAT" Speed CONTINUOUS FAN" Speed
Do not
"
A B C D A B C D A B C D
cfm L/sBcfm L/sCcfm L/sDcfm L/sAcfm L/sBcfm L/sCcfm L/sDcfm L/sAcfm L/sBcfm L/sCcfm L/sDcfm L/s
+
2300 1085 2070 975 1840 870 1380 650 SAME AS NORM
2000 944 1800 850 1600 755 1200 565 1850 873 1730 816 1550 732 1400 660 1000 470 900 425 800 380 600 285
1700 802 1530 720 1360 640 1020 480 SAME AS NORM
use
−154
Do not
use
−140
Page 6
B−Burner Control (A3)
All O23V units are equipped with a burner control R7184B manufactured by Honeywell. The burner control, along with the matching cad cell, proves flame and controls the burner. An LED on the control shows unit status. See table 4 for status codes. After the cad cell closes a circuit to the burner control, the burner control de−energizes the safety switch heater to al­low the unit to operate normally. When there is a call for heat the control performs a 2 to 6 second delay safety check. Once this is established a 15 second pre−purge will follow. The valve then opens for a 15 second trial for ignition. If flame is not sensed during the 15 second trial, the control shuts down and must be manually re−set. After three consecutive lockouts the control goes into restricted lockout. Once flame is established after 10 seconds of run time, the ignitor is de−energized.
If flame is lost during the heat cycle the control will shut down the burner and begin a 60 second recycle delay. Af­ter 60 seconds the control repeats the ignition process. If flame is lost three consecutive times during a single ther­mostat demand the control goes into restricted lockout.
C−Control ST9103A (A15)
Control ST9103A manufactured by Honeywell, is a printed circuit board which monitors limit operation and oil burner operation. Line voltage and thermostat con­nections are made on this control. See table 5 for termi­nal designations.
TABLE 5
J58 Pin #
1 Limit S10
2 L1 120V
3 24V
4 L2 Common
5 Jumpered to Pin 4
6 24V
7 Burner Motor
8 Jumpered to Pin 7
9 Limit S21 (if used)
Function
Reset button
If the control locks out three consecutive times the control will go into restricted lockout. To reset control hold down the reset button for 30 seconds until the LED flashes twice.
At any time the burner motor is energized, press and hold the reset button to disable the burner. The burner will re­main disabled as long as the reset button is held down and return to operation once the button is released.
TABLE 4
LED
On Flame sensed
Off Flame not sensed
Flashing
(1/2 sec on1/2 sec off)
Flashing
(2 sec on 2 sec off)
STATUS
Lockout /
Restricted Lockout
Recycle
D−Transformer (T1)
Transformer T1 provides power to the low voltage sec­tion of the unit. Transformers are rated 40VA with a 120V primary and 24V secondary.
E−Primary Limit Control (S10)
The primary limit on all O23V units, is located on the vesti­bule panel. When excess heat is sensed in the heat ex­changer, the limit will open. If the limit is tripped, 24 volt power to terminal R" on the indoor thermostat is lost and the unit shuts down but the indoor blower continues to run. The limit automatically resets when unit temperature returns to normal. The switch is factory set and cannot be adjusted. The setpoint is printed on the face plate of the limit.
IMPORTANT
If using programmable thermostat, be sure to use a type of thermostat that retains its memory in event of a power loss.
Page 7
O23V BURNER PARTS ARRANGEMENT
RETAINING
CLIP
HEAD
INSULATOR
AIR TUBE
ASSY FOR
FB HEADS
1/4" HEX
HEAD SCREW
FB−HEAD
NOZZLE
ADAPTER
ELECTRODE HEAD
FLANGE
GASKET
NOZZLE LINE
ASSY.
FLANGE
ELECTRODE
ASSY
AIR TUBE SCREWS
ELECTRONIC IGNITION
TRANSFORMER
CONNECTOR
PEDESTAL
PREMOUNTED PRE−PURGE VALVE
MAIN
HOUSING
ASSY
ESCUTCHEON
PLATE
TUBE
REAR ACCESS
DOOR ASSY
SPLINED
NUT
FUEL PUMP
COUPLING
REAR ACCESS
DOOR GASKET
MOTOR
IGNITOR
PRIMARY
CONTROL
BLOWER
WHEEL
4X4
BOX
0
3 4 5
6 7 8
AIR ADJ. DIAL
INLET
AIR SCOOP
FIGURE 3
Page 8
Unit
Lennox Burner
Part Number
TABLE 6
FURNACE / BURNER SPECIFICATIONS
Burner
Model
*Initial Air Dial Setting
Output
Nozzle Size
(Delevan)
Pump
Pressure
Head
-70 39M85 AFII 85 3.0
-090 39M85 AFII 85 3.5
-105 39M86 AFII 85 4.0
-120 39M86 AFII 85 4.5
-140 39M87 AFII 150 6.0
-154 39M87 AFII 150 6.5
*NOTE: The initial air dial setting is provided to get unit started. The air dial setting MUST be adjusted after start-up to achieve proper combustion.
F−Burner (Figure 3)
The O23V oil furnace uses the Beckett AFII burner. The oil burner provides an atomized oil vapor mixed with the correct proportion of air when it is ignited in the combustion chamber. Oil burner minimum and maximum ratings are listed on the unit nameplate. Proper air adjustment for these ratings is achieved through the air adjustment dial. Set air dial to the ini­tial air dial setting (see table 6). After start up adjust air dial to achieve proper combustion. Remember to tighten set screw on air dial.
The AFII burner is available in six sizes with either a single or two stage pump. Table 6 identifies the burners used in Lennox units.
G−Combustion Air Blower / Pump Motor (B6)
The burner is activated by the primary control. A com­bustion air blower is mounted on the motor shaft. The motor shaft also connects to the direct drive oil pump through a coupler. The burner motor turns both the com­bustion air blower and the oil pump. The motor operates at 3500 RPM. Burner motors are overload protected. In the event of excess motor temperature or current, the overload opens to de−energize the motor. The overload automat­ically resets after temperature has returned to normal. Keep motor clean to prevent starting switch from sticking. All AFII motors are permanently lubricated. No further oiling is required.
57,000 BTU
(16.7 kW)
74,000 BTU
(21.7 kW)
84,000 BTU
(24.6 kW)
105,000 BTU
(30.8 kW)
112,000 BTU
(32.8 kW)
125,000 BTU
(36.6 kW)
0.50 X 80_A
0.50 X 80_A
0.65 X 80_B
0.75 X 80_B
0.85 X 80_B
1.00 X 80_B
H− Pump
The O23V units all utilize the Cleancut Fuel Unit manufac­tured by Beckett. This pump uses a solenoid valve to con­trol the piston cut−on cut−off operation instead of a cone valve and diaphram used by other conventional pumps. The solenoid works with the R7184B Honeywell burner control to provide cut−on cut−off operation while the burner motor is at full speed.
At start up the pump shaft is brought to full speed before the solenoid is energized. At this time low pressure oil (approximately 20−25 psi) from the gear set circulates around the pressure regulator piston which is closed and through the open solenoid valve. The solenoid valve re­turns the oil to either the cover cavity (one−pipe) or return line (two−pipe). When the solenoid valve is energized, it closes (and remains closed while energized) blocking the return path to the cover cavity and return line creating pres­sure build up in the piston cavity. The piston opens and reg­ulates pressure and delivers pressurized oil to the nozzle.
At shutdown the solenoid valve will de−energize and open before the pump shaft rotation stops. When the solenoid valve opens the oil by−passes the cover cavity and return line causing a pressure drop in the piston cavity. The piston closes blocking oil to the nozzle while the burner motor is running at full speed.
100 psig
(689.5 kPa)
100 psig
(689.5 kPa)
140 psig
965.3 kPa)
140 psig
965.3 kPa)
140 psig
965.3 kPa)
140 psig
965.3 kPa)
FB0
FBO
FB3
FB3
FB6
FB6
Page 9
Loading...
+ 21 hidden pages