O23 (Elite 80) series units are mid−efficiency upflow oil fur
naces manufactured with Beckett oil burners. O23 units are
available in heating capacities of 70,000 to 154,000 Btuh
(20.5 to 45.1 kW) and cooling applications from 2 through 5
tons (7.0 through 17.6 kW). Refer to Engineering Hand
book for proper sizing.
OHR23 (Elite 80) series units are mid−efficiency horizontal /
downflow oil furnaces. The OF23 (Elite 80) series units are
mid−efficiency loboy upflow oil furnaces, which come in front
(OF23) or rear (OF23R) flue openings, both with Beckett oil
burners. The OHR23 and OF23(R) units are available in heat
ing capacities of 105,000 to 154,000 Btuh (30.8 to 45.1 kW)
and cooling applications from 2 through 5 tons (7.0 through
17.6 kW). Refer to Engineering Handbook for proper siz
ing.
The drum type heat exchanger comes with strategically
placed ports allowing easy cleaning, while the oil burner
can be removed for inspection and service. The mainte
nance section gives a detailed description on how this is
done.
O23/OHR23
OF23
Information contained in this manual is intended for use by
experienced HVAC service technicians only. All specifica
tions are subject to change. Procedures outlined in this
manual are presented as a recommendation only and do
not supersede or replace local or state codes.
WARNING
Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at discon
nect switch(es). Unit may have multiple
power supplies.
WARNING
Improper installation, adjustment, alteration, ser
vice or maintenance can cause property damage,
personal injury or loss of life. Installation and service
must be performed by a qualified installer or service
agency.
*Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations. Isolated combustion system rating for nonweatherized furnaces.
**Cleanable frame type filters. Furnished with unit in Side Filter Adaptor Kit for field installation external to the cabinet.
Requires return air from both sides of cabinet.
Nozzle must be field provided for field conversion to higher heating input.
*Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations. Isolated combustion system rating for nonweatherized furnaces.
Nozzle must be field provided for field conversion to higher heating input.
Catalog no.35K0135K06
No. & size of filtersin. (mm)(2) 101/4 x 201/2 x 1 (260 x 521 x 25)(2) 113/4 x 231/2 x 1 (298 x 597 x 25)
*Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations. Isolated combustion system rating for nonweatherized furnaces.
Nozzle must be field provided for field conversion to higher heating input.
in.10 x 812 x 9
mm254 x 203305 x 229
in.(1) 18 x 19 x 1(1) 19 x 21 x 1
mm(1) 457 x 483 x 25(1) 483 x 533 x 25
OF23Q3105/120
OF23Q3105/120R
82.4% / 81.5%
82.5% / 82.4% R Models
.65 (2.5) 80° (105 input)
.75 (2.8) 80° (120 input)
OF23Q5140/154
OF23Q5140/154R
81.8% / 81.5%
82.0% / 81.8% R Models
.85 (3.2) 80° (140 input)
1.00 (3.8) 80° (154 input)
BLOWER PERFORMANCE DATA − O23
O23Q270 BLOWER PERFORMANCE
External Static
Pressure
in.w.g.PacfmL/scfmL/scfmL/s
.20501260595870410520245
.30751205570825390500235
.401001135535780370480225
.501251050495720340450210
.60150960455660310410195
NOTE All air data is measured external to the unit with the air filter in place.
Air Volume at Various Blower Speeds
HighMediumLow
O23Q5140/154 BLOWER PERFORMANCE
External Static
Pressure
in. w.g.PacfmL/scfmL/scfmL/s
.2050195092016207651250590
.3075190089515907501230580
.40100188088515607351210570
.50125185087515407251190560
.60150180085014907051155545
NOTE All air data is measured external to the unit with the air filter in place.
O23Q3105/120 BLOWER PERFORMANCE
External Static
Pressure
in. w.g.PacfmL/scfmL/scfmL/s
.20.50135063512155751080510
.3075128060511805551060500
.40100121057011405401040490
.50125118044410855101000470
.6015011005201025485950450
NOTE All air data is measured external to the unit with the air filter in place.
Air Volume at Various Blower Speeds
HighMediumLow
Air Volume at Various Blower Speeds
HighMediumLow
Page 3
Page 4
BLOWER PERFORMANCE DATA − OHR23
External Static
External Static
External Static
External Static
External Static
External Static
OHR23Q3105/120 BLOWER PERFORMANCE
External Static
Pressure
in w.g.PacfmL/scfmL/scfmL/s
.2050147069513606401070505
.3075140066013006151040490
.40100133063012305801020480
.5012512605951160545980460
.6015011805551085510920435
NOTE All air data is measured external to the unit with air filter in place.
Air Volume at Various Speeds
HighMediumLow
BLOWER PERFORMANCE DATA − OF23
FRONT FLUE MODELS
OF23Q3105/120 BLOWER PERFORMANCE
External Static
Pressure
in. w.g.PacfmL/scfmL/scfmL/s
.2050149070513706451190560
.3075143067513456351180555
.40100137565012806051160545
.50125130061512305801120530
.60150123058011605451080510
NOTE All air data is measured external to the unit with the air filter in place.
Air Volume at Various Blower Speeds
HighMediumLow
OHR23Q5140/154 BLOWER PERFORMANCE
External Static
Pressure
in w.g.PacfmL/scfmL/scfmL/s
.2050195092017008001340630
.3075192090516507801300615
.40100190089516007551270600
.50125187088015807451220575
.60150178084015007101170550
NOTE All air data is measured external to the unit with air filter in place.
Air Volume at Various Speeds
HighMediumLow
OF23Q5140/154 BLOWER PERFORMANCE
External Static
Pressure
in. w.g.PacfmL/scfmL/scfmL/s
.2050211099518508751500710
.3075203596018108551480700
.40100197093017508251450685
.50125195092016908001420670
.60150188088516207651375650
NOTE All air data is measured external to the unit with the air filter in place.
Air Volume at Various Blower Speeds
HighMediumLow
OF23Q3105/120R BLOWER PERFORMANCE
External Static
Pressure
in. w.g.PacfmL/scfmL/scfmL/s
.2050147069513306301150545
.3075141066512956101140540
.40100134063012505901125530
.50125128060511905601080510
.60150120567011305351030485
NOTE All air data is measured external to the unit with the air filter in place.
Air Volume at Various Blower Speeds
HighMediumLow
REAR FLUE MODELS
OF23Q5140/154R BLOWER PERFORMANCE
External Static
Pressure
in. w.g.PacfmL/scfmL/scfmL/s
.2050201095017658351380650
.3075196092517208101350635
.40100190089516607851330630
.50125188088516007551295610
.60150180085015607351230580
NOTE All air data is measured external to the unit with the air filter in place.
Page 4
Air Volume at Various Blower Speeds
HighMediumLow
Page 5
O23 GENERAL PARTS ORIENTATION
HEAT EXCHANGER
CLEANOUT PORT
LIMIT SWITCH
CONTROL BOX
WITH FAN
CONTROL
BECKETT
AFII BURNER
INDOOR BLOWER
VENT OPENING
CLEANOUT PORT
OBSERVATION PORT
COMBUSTION AIR INTAKE
BLOWER MOTOR
CAPACITOR
FIGURE 1
LIMIT SWITCH
BECKETT
AFII BURNER
COMBUSTION
AIR INTAKE
OBSERVATION
PORT
CLEANOUT
OHR23 GENERAL PARTS ORIENTATION
CLEANOUT PORT
HEAT EXCHANGER
PORT
VENT OPENING
CONTROL BOX
WITH FAN
CONTROL
BLOWER MOTOR
INDOOR BLOWER
FIGURE 2
Page 5
Page 6
OF23 GENERAL PARTS ORIENTATION
CLEANOUT
PORT
LIMIT SWITCH
CONTROL BOX
WITH FAN
CONTROL
BECKETT
AFII BURNER
FRONT VENT
OPENING (OF23)
COMBUSTION
AIR INTAKE
FILTER
INDOOR BLOWER
REAR VENT
OPENING (OF23R)
HEAT EXCHANGER
CLEANOUT PORT
OBSERVATION PORT
FIGURE 3
NEUTRAL
TERMINALS
24VAC OUTPUT
TO BURNER
(HEAT DEMAND)
24VAC IN FROM
PRIMARY LIMIT
24VAC THERMOSTAT
DEMAND OUTPUT
BCC2 / BCC3 BLOWER CONTROL BOARD
120VAC LINE
VOLTAGE IN
THERMOSTAT TERMINAL STRIP TB1
(DETACHABLE ON EARLY −1 AND −2
MODELS ONLY)
COOLING
SPEED TAP
TERMINAL
TRANSFORMER
120VAC
COMMON
FROM TRANSFORMER
CONTINUOUS FAN
TERMINAL
BLOWER TIME
ADJUSTMENT
JUMPER
24VAC INPUT
HEATING SPEED
TAP TERMINAL
ACCESSORY
TERMINAL
To Remove Terminal Strip,
Grasp Ends of Block Between
Thumb and Forefinger. Push
Block Down and Out.
(Jack / Plug 94)
24VAC COMMON
FROM TRANSFORMER
FIGURE 4
Page 6
Page 7
I−UNIT COMPONENTS
General parts orientation for the O23, OHR23 and OF23 are
shown in figures 1, 2 and 3 respectively. The O23 and OF23
control box, burner, limit switch and cleanout ports may be ac
cessed by removing the front access panel, while the OHR23
components are exposed. The blower can be accessed in the
O23 and OF23 by removing the blower access panel, while in
the OHR23 units two 1/4" screws must be removed before the
blower access panel can be removed.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic
components. Take precautions during unit instal
lation and service to protect the unit’s electronic
controls. Precautions will help to avoid control
exposure to electrostatic discharge by putting
the unit, the control and the technician at the
same electrostatic potential. Neutralize electro
static charge by touching hand and all tools on an
unpainted unit surface before performing any
service procedure.
A−Blower Control Board
BCC2 Blower Control Board (Figure 4)
−1 and −2 units
All O23, OHR23 and OF23−1 and −2 oil units utilize the BCC2
(A15) blower control manufactured by Heatcraft. The BCC2 is
a printed circuit board which controls the supply air blower and
monitors the limit controls and oil burner operation. The control
has a nonadjustable, factory preset fanon" timing. Fan off"
timing is adjustable. The board is divided into two sec
tions, 120 and 24VAC. Line voltage comes into the board
on the 120VAC side. See figure 4. See table 1 for BCC2
terminal designations.
DANGER
Shock hazard. Avoid personal injury. Make sure to
disconnect power before changing fan off" timing.
Blower Operation and Timing
Blower off" timing (time that the blower operates after the heat
demand has been satisfied) is determined by the arrange
ment of a jumper across pins on the BCC2 blower control
board. See figure 4. To adjust fan off " timing, gently discon
nect jumper and reposition across pins corresponding with
new timing. Fan on" time is factory set at 45 seconds and is
not adjustable.
NOTEIf fan off" time is set too low, residual heat in
heat exchanger may cause primary limit S10 or auxilary
limit S21 to trip resulting in frequent cycling of blower. If
this occurs, adjust blower to longer time setting.
Figure 5 shows the various fan off" timings and how
jumper should be positioned. Unit is shipped with a fac
tory fan off" setting of 150 seconds. Fan off" time will
affect comfort and efficiency and is adjustable to satisfy
individual applications. The fan off" timing is initiated
after a heating demand but not after a blower or cooling
demand (that is, when indoor thermostat switch is
changed from ON to AUTO and heating/cooling demand
is not present, the blower stops immediately).
FANOFF TIME ADJUSTMENT
TIMING
JUMPER
270
15090
To adjust fan−off timings:
Remove jumper from BCC2
and select one of the other pin com
binations to achieve the
desired time.
Leave jumper off to achieve
210
330 second fan−off timing.
TIMING PINS (seconds)
Fanoff timing is factory
set at 150 seconds
FIGURE 5
Thermostat Connection
Thermostat wires are connected to terminal strip TB1 found
on the BCC2 control board. The terminal strip is c l early
marked with the corresponding thermostat designation.
The terminal strip (jack / plug 94) is simply removed by
grasping the ends of the block and rotating down while pull
ing away (see figure 4).
TABLE 1
BLOWER CONTROL A15 TERMINAL DESIGNATIONS
Term inalTypeFunction
W
R
Y
C
G
NEUTRAL1/4" Spade120VAC Neutral
L11/4" Spade120VAC Line Voltage In
A1/4" Spade
XFMRN1/4" Spade120VAC Transformer Common
CF1/4" Spade
H1/4" Spade
ACC1/4" Spade
VALVE SENSE 3/16" Spade24VAC Output To Burner
LIMIT1/4" Spade
WI1/4" Spade
24V1/4" Spade
COM1/4" Spade
Detachable
Screw Strip
Detachable
Screw Strip
Detachable
Screw Strip
Detachable
Screw Strip
Detachable
Screw Strip
Heating Demand
24VAC to Thermostat
Cooling Demand
24VAC Common
To Indoor Thermostat
Blower Demand
Switched 120VAC
to Blower Cooling Tap
Switched 120VAC to
Continuous Blower Tap
Switched 120VAC to
Blower Heating Tap
Switched 120VAC to Accessory
(Electronic Air Cleaner,
Humidifier, Etc. 1 amp rating.)
24VAC In From Primary Limit.
Limit Open: Stops Burner and Turns
On Blower
Limit Closed: Allows Burner
Operation
24VAC Thermostat
Demand Output
24VAC Input
From Transformer
24VAC Common
From Transformer
Page 7
Page 8
BCC3 Blower Control Board (Figure 4)
−3 and −4 units
All O23, OHR23 and OF23−3 and −4 oil units utilize the BCC3
(A15) blower control manufactured by Heatcraft. The BCC3 is
a printed circuit board which controls the supply air blower and
monitors the limit controls and oil burner operation. The control
has a nonadjustable, factory preset fanon" timing. Fan off"
timing is adjustable. The board is divided into two sec
tions, 120 and 24VAC. Line voltage comes into the board
on the 120VAC side. See figure 4. See table 2 for BCC3
terminal designations.
DANGER
Shock hazard. Avoid personal injury. Make sure to
disconnect power before changing fan off" timing.
Blower Operation and Timing
Blower off" timing (time that the blower operates after the heat
demand has been satisfied) is determined by the arrange
ment of a jumper across pins on the BCC3 blower control
board. See figure 4. To adjust fan off " timing, gently discon
nect jumper and reposition across pins corresponding with
new timing. Fan on" time is factory set at 45 seconds and is
not adjustable.
NOTEIf fan off" time is set too low, residual heat in
heat exchanger may cause primary limit S10 or auxilary
limit S21 to trip resulting in frequent cycling of blower. If
this occurs, adjust blower to longer time setting.
Figure 5 shows the various fan off" timings and how
jumper should be positioned. Unit is shipped with a fac
tory fan off" setting of 150 seconds. Fan off" time will
affect comfort and efficiency and is adjustable to satisfy
individual applications. The fan off" timing is initiated
after a heating demand but not after a blower or cooling
demand (that is, when indoor thermostat switch is
changed from ON to AUTO and heating/cooling demand
is not present, the blower stops immediately).
FANOFF TIME ADJUSTMENT
TIMING
JUMPER
To adjust fan−off timings:
Remove jumper from BCC2
and select one of the other pin com
binations to achieve the
desired time.
Thermostat Connection
Thermostat wires are connected to terminal strip TB1 found
on the BCC3 control board. The terminal strip is clea r ly
marked with the corresponding thermostat designation.
The terminal strip (jack / plug 94) is simply removed by
grasping the ends of the block and rotating down while pull
ing away (see figure 4).
TABLE 2
BLOWER CONTROL A15 TERMINAL DESIGNATIONS
Term inalTypeFunction
W
R
Y
C
G
NEUTRAL1/4" Spade120VAC Neutral
L11/4" Spade120VAC Line Voltage In
A1/4" Spade
XFMRN1/4" Spade120VAC Transformer Common
CF1/4" Spade
H1/4" Spade
ACC1/4" Spade
VALVE SENSE 3/16" Spade24VAC Output To Burner
LIMIT1/4" Spade
WI1/4" Spade
24V1/4" Spade
COM1/4" Spade
Detachable
Screw Strip
Detachable
Screw Strip
Detachable
Screw Strip
Detachable
Screw Strip
Detachable
Screw Strip
Heating Demand
24VAC to Thermostat
Cooling Demand
24VAC Common
To Indoor Thermostat
Blower Demand
Switched 120VAC
to Blower Cooling Tap
Switched 120VAC to
Continuous Blower Tap
Switched 120VAC to
Blower Heating Tap
Switched 120VAC to Accessory
(Electronic Air Cleaner,
Humidifier, Etc. 4 amp rating.)
24VAC In From Primary Limit.
Limit Open: Stops Burner and Turns
On Blower
Limit Closed: Allows Burner
Operation
24VAC Thermostat
Demand Output
24VAC Input
From Transformer
24VAC Common
From Transformer
270
15090
Leave jumper off to achieve
210
330 second fan−off timing.
TIMING PINS (seconds)
Fanoff timing is factory
set at 150 seconds
FIGURE 6
Page 8
Page 9
ST9103A Blower Control Board (Figure 8)
−5 units
All O23, OHR23 and OF23 −5 oil units utilize the ST9103A
(A15) blower control manufactured by Honeywell. The
ST9103A is a printed circuit board which controls the supply
air blower and monitors the limit controls and oil burner opera
tion. The control has a nonadjustable, factory preset fanon"
timing. Fan off" timing is adjustable. See figure 8 and
table 3 for ST9103A terminal designations
ST9103A Blower Control Board
120V
DANGER
Shock hazard. Avoid personal injury. Make sure to
disconnect power before changing fan off" timing.
Blower Operation and Timing
The fan on time of 30 seconds is not adjustable. Fan off
time (time that the blower operates after the heat demand
has been satisfied) can be adjusted by moving the delay
switches on the fan control board. Fan off time will affect
comfort and is adjustable to satisfy individual applications.
See figure 7. Set the heat fan off delay switches to either
60, 90, 120, or 150 seconds. The factory setting is 90 sec
onds.
NOTEIf fan off" time is set too low, residual heat in
heat exchanger may cause primary limit S10 or auilary
limit S21 to trip resulting in frequent cycling of blower. If
this occurs, adjust blower to longer time setting.
Thermostat Connection
Thermostat wires are connected directly to the terminlas on
the ST9103A board. See figure 8.
Continuous Blower
If the ST9103A blower control board is wired for continuous
blower, the blower will energized on low speed and remain
energized when heat or cool demand is satisfied. Continuous
blower will also energized when indoor thermostat is left in the
OFF mode.
Fan Off Delay Switch Settings
ONONONON
120 sec90 sec60 sec
Figure 7
150 sec
fan off
delay switches
thermostat
terminal strip
Figure 8
TABLE 3
BLOWER CONTROL A15 TERMINAL DESIGNATIONS
J58 Pin #Function
1Limit S10
2L1 120V
3T1 24V
4L2 Common
5Jumpered to Pin 4
6T2 24V
7Combustion Air Inducer
120V
8Jumpered to Pin 7
9Limit S21 (if used)
Thermostat Connections
GBlower Demand
WHeating Demand
R24V
YCooling Demand
CCommon
24 VAC CONNECTIONS
X24V Transformer
CCommon Transformer
120 VAC
S2Line
S3120V To Transformer
N, 2, 3, 4, 6, 7Neutral
CONTContinuous Blower
COOLCool Tap
HEATHeat Tap
Page 9
Page 10
RETAINING
CLIP
HEAD
INSULATOR
−1THROUGH −4 UNIT OIL BURNER PARTS ARRANGEMENT
AIR TUBE
SCREWS
HOLE PLUG
ELECTRONIC IGNITION
TRANSFORMER
MAIN
HOUSING
ASSY
ESCUTCHEON
PLATE
CONNECTOR
TUBE
AIR TUBE
ASSY FOR
FB HEADS
FB–HEAD
NOZZLE
ADAPTER
NOZZLE LINE
ELECTRODE HEAD
FLANGE
GASKET
ASSY.
FLANGE
ELECTRODE
ASSY
REAR ACCESS
DOOR GASKET
VIEW PORT
REAR ACCESS
DOOR ASSY
OIL PUMP
SPLINED
NUT
ELECTRONIC IGNITION
TRANSFORMER
BURNER
CONTROL
RESET
BUTTON
AIR
ADJUSTMENT
0
3
4
5
6
7
8
DIAL
COUPLING
COMBUSTION AIR
MOTOR
BLOWER
FIGURE 9
Page 10
WHEEL
INLET
AIR SCOOP
Page 11
−5 UNIT BURNER PARTS ARRANGEMENT
RETAINING
CLIP
HEAD
INSULATOR
AIR TUBE
ASSY FOR
FB HEADS
1/4" HEX
HEAD SCREW
FB−HEAD
NOZZLE
ADAPTER
ELECTRODE HEAD
FLANGE
GASKET
NOZZLE LINE
ASSY.
ELECTRODE
FLANGE
ASSY
AIR TUBE
SCREWS
ELECTRONIC IGNITION
TRANSFORMER
ESCUTCHEON
CONNECTOR
PEDESTAL
PREMOUNTED PRE−PURGE VALVE
MAIN
HOUSING
ASSY
PLATE
TUBE
REAR ACCESS
DOOR ASSY
SPLINED
NUT
FUEL PUMP
COUPLING
REAR ACCESS
DOOR GASKET
MOTOR
IGNITOR
PRIMARY
CONTROL
BLOWER
WHEEL
4X4
BOX
0
3
4
5
6
7
8
AIR
ADJ.
DIAL
INLET
AIR SCOOP
FIGURE 10
Page 11
Page 12
TABLE 4
FURNACE / BURNER SPECIFICATIONS
Unit
7035K74AFII 853.0
10535K75AFII 854.0
12035K75AFII 854.5
14035K76AFII 1506.0
15435K76AFII 1506.5
*NOTE: The initial air dial setting is provided to get unit started. The air dial setting MUST be adjusted after startup to
achieve proper combustion.
Lennox Burner
Part Number
Burner
Model
*Initial
Air Dial
Setting
Output
57,000 BTU
(16.7 kW)
84,000 BTU
(24.6 kW)
105,000 BTU
(30.8 kW)
112,000 BTU
(32.8 kW)
125,000 BTU
(36.6 kW)
Nozzle Size
(Delevan)
0.50 X 80A
0.65 X 80B
0.75 X 80B
0.85 X 80B
1.00 X 80B
Pump
Pressure
100 psig
(689.5 kPa)
140 psig
965.3 kPa)
140 psig
965.3 kPa)
140 psig
965.3 kPa)
140 psig
965.3 kPa)
Head
FB0
FB3
FB3
FB6
FB6
B−Burner (Figures 9 & 10)
The O23, OHR23, and OF23 oil furnaces use the Beckett AFII
burner. The oil burner provides an atomized oil vapor mixed
with the correct proportion of air when it is ignited in the com
bustion chamber. Oil burner minimum and maximum ratings
are listed on the unit nameplate. Proper air adjustment for
these ratings is achieved through the air adjustment dial. Set
air dial to the initial air dial setting (see table 4). After start up
adjust air dial to achieve proper combustion. Remember to
tighten set screw on air dial.
The AFII burner is available in five sizes with either a single
or two stage pump. Table 4 identifies the burners used in
Lennox units. Figures 9 and 10 show the typical layout of the
burner assembly.
1−Combustion Air Blower / Pump Motor (B6)
The burner is activated by the primary control. A com
bustion air blower is mounted on the motor shaft. The
motor shaft also connects to the direct drive oil pump
through a coupler. The burner motor turns both the com
bustion air blower and the oil pump. The motor operates
at 3500 RPM.
Burner motors are overload protected. In the event of
excess motor temperature or current, the overload
opens to de−energize the motor. The overload automat
ically resets after temperature has returned to normal.
Keep motor clean to prevent starting switch from sticking.
All AFII motors are permanently lubricated. No further oiling is
required.
2−Combustion Air Blower / Pump Fuse (F22)
(−140 and −154 CSA units only)
In the −140 and −154 Canadian units an in line fuse (F22) is
used between the line voltage from the BCC2 blower con
trol and the blower / pump motor. The fuse is rated at 300
volts and 15 amps.
3− Pump (−1 through −4 units)
The O23, OHR23, and OF23 oil furnaces use a single
stage, 3450 RPM pump. A two stage pump is available
as an option (catalog # 65A44). The oil burner is shipped
from factory for use in a single line system. To convert the
pump to a two line system, install the bypass plug pro
vided in the attached bag according to the accompany
ing instructions.
4− Pump (−5 units only)
The O23, OHR23 and OF23−5 units all utilize the Cleancut
Fuel Unit manufactured by Becket. This pump uses a sole
noid valve to control the piston cut−on cut−off operation
instead of a cone valve and diaphram used by other con
ventional pumps. The solenoid works with the R7184B
Honeywell burner control to provide cut−on cut−off opera
tion while the burner motor is at full speed.
At startup the pump shaft is brought to full speed before the
solenoid is energized. At this time low pressure oil
(approximatley 20−25 psi) from the gearset circulates
around the pressure regulator piston which is closed and
through the open solenoid valve. The solenoid valve re
turns the oil to either the cover cavity (one pipe) or return
line (two pipe). When the solenoid vavle is energized, it
closes (and remains closed while energized) blocking the
return path to the cover cavity and return line creating pres
sure build up in the piston cavity. The piston opens and reg
ulates pressure and delivers pressurized oil to the nozzle.
At shutdown the solenoid valve will de−energize and open
before the pump shaft rotation stops. When the solenoid
valve opens the oil by−passes the cover cavity and return
line causing a pressure drop in the piston cavity. The piston
closes blocking oil to the nozzle while the burner motor is
running at full speed.
Page 12
Page 13
5−Burner Control (A3) & Transformer (T1)
−1 through −4 units
The burner control, along with the matching cad cell, proves
flame and controls the burner. After the cad cell closes a circuit
to the burner control, the burner control de−energizes the safe
ty switch heater to allow the unit to operate normally. The
burner control allows 45 seconds for the cad cell to close. If the
cad cell remains open after the 45 second time frame, the
burner control locks out. The burner control must be manually
reset by depressing the red reset button on top of the burner
control.
Transformer (T1) is part of the burner control. T1 provides
24VAC to the low voltage components in the unit and to the
thermostat.
6−Burner Control (A3) −5 units
All O 23, OHR23 and OF23 −5 units are equipped with a burn
er control R7184B manufactured by Honeywell. The burner
control, along with the matching cad cell, proves flame and
controls the burner. An LED on the control shows unit status.
See table 5 for status codes. After the cad cell closes a circuit
to the burner control, the burner control de−energizes the safe
ty switch heater to allow the unit to operate normally. When
there is a call for heat the control performs a 2 to 6 second
delay safety check. Once this is established a 15 second pre−
puge will follow. The valve then opens for a 15 second trial for
ignition. If flame is not sensed during the 15 second trial, the
control shuts down and must be manual re−set. After three
consecutive lockouts the control goes into restricted lockout.
Once flame is established after 10 seconds of run time, the ig
niiton shuts off.
If flame is lost during the heat cycle the control will shut
down the burner and begin a 60 second recycle delay. Af
ter 60 seconds the control repeats the ignition process. If
flame is lost three consecutive times during a single ther
mostat demand the control goas into restricted lockout.
Reset button
If the control lockouts three consecutive times the control
will go into restricted lockout. To reset control hold down
the reset button for 30 seconds until the LED flashes twice.
At any time the burner motor is energized, press and hold
the reset button to disable the buner. The burner will re
main disabled as long as the reset button is held and return
to operational once the button is released.
TABLE 5
LEDSTATUS
OnFlame sensed
OffFlame not sensed
Flashing
(1/2 sec on1/2 sec off)
Flashing
(2 sec on 2 sec off)
Lockout /
Restricted Lockout
Recycle
7−Heat Shutoff Relay (K125)
−1 and −2 units only
Heat shutoff relay K125 is a SPST N.O. relay, with a 24V
coil. K125 is located on the vestibule and wired in series
with the burner. When secondary limit S21 or primary limit
S10 open, the circuit breaks opening K125 contacts which
in turn de−energizes the burner.
8−Cad Cell (R26)
Together the cad cell and the burner control prove flame.
The cad cell senses the presence of burner light (less re
sistance) to close a circuit to the burner control.
IMPORTANT−Burner should not be installed so it is ex
posed to direct sunlight or electric bulb light. If the cell
is exposed to light on start up, the burner will not oper
ate.
O23, OHR23 & OF23 −5 Units Only
Resistance for the cad cell can be checked while the burn
er is firing and after ignition is off. Press (1/2 second or
less) and release the reset button. The LED will flash 1 to 4
times depending on the cad cell resistance. The cad cell
resistance should read less than 1600 Ohms. See table 6.
O23, OHR23 & OF23 −5 UNITS
LED FLASHESRESISTANCE
10 − 400Ohms
2400 − 800 Ohms
3800 − 1600 Ohms
4
TABLE 6
1600 Ohms
Page 13
Page 14
9−Electronic Ignitor (A73)
The electronic ignitor provides the needed hot spark at the
electrodes to ignite the fuel mixture. The ignitor is a solid
state transformer . O23, OHR23 and OF23−1 through −4
units have 115V primary and 14,000V secondary wind
ings. O23, OHR23 and OF23−5 units have 120V primary
and 20,000V secondary windings. The center of the sec
ondary winding is grounded. Each secondary terminal is
7000V to ground and the total voltage between the elec
trodes is 14,000V.
NOTE−The leads for the solid state transformer are re
placeable and are available in a kit form.
NOTE−When testing the solid state transformer, do not
use a transformer tester designed for iron magnet trans
formers. Damage to the tester may result.
Testing the Ignitor
WARNING
SHOCK HAZARD
Do not touch ignitor or any metal touching ignitor
when ignitor is energized. Can result in serious per
sonal injury.
10−Gun Assembly
The gun assembly receives oil from the oil pump and feeds
it to the nozzle. The nozzle converts liquid oil into a fog−like
mist that is discharged through the flame retention head
into the combustion chamber.
11−Flame Retention Heads
The stainless steel flame retention head (see figure 11)
is used to swirl (cone) the foglike oil and air mixture as it
enters the combustion chamber. Three different heads
are used in the O23/OHR23/OF23. The firing rate dic
tates which head is used. See table 4. The greater the
FB number the larger the slots on the head. When com
bustion takes place, the flame will be cylindrical com
pact shaped as a result.
FLAME RETENTION HEAD
FB3 SHOWN
If the ignitor fails it will not produce a spark. Looking and
listening for the arc is a simple way to check. The most sure
way is to perform the screwdriver check. By placing the
blade of an insulated screwdrivere across the ignitor termi
nal leads will test for an arc. First, remove power from the
burner and disconnect the oil supply from nozzle. The cad
cell will not let the control energize the ignitor if the cad cell
senses light. Therefore remove one lead of the cad cell
from the burner control, or remove the cad cell all together
(do not forget to put back when test is complete). Place the
screwdriver blade across the terminals and slowly raise
one end of the blade off the terminal while the other re
mains in contact with the other terminal. There should be
an arc from terminal to the blade up to 3/4" away. If not re
place the ignitor. If an arc is present then place one end of
the screwdriver on one terminal and the other end with the
grounded baseplate. Raise the blade from the baseplate
and draw an arc. Repeat with the other terminal. If the arc
from the baseplate to one terminal is weaker than the arc
from the baseplate to the other terminal, replace the ignitor.
FIGURE 11
C−Primary Limit Control (S10)
The primary limit on all O23, OHR23, and OF23 units, is
located on the vestibule panel (see figures 1 through 3 for
location and figure 12 for type). When excess heat is
sensed in the heat exchanger, the limit will open. If the limit
is tripped, the blower control deenergizes the thermostat,
in turn shutting down the unit. The limit automatically re
sets when unit temperature returns to normal. The switch is
factory set and cannot be adjusted. The switch has a different
setpoint for each unit model number (see table 7). The set
point is printed on the face plate of the limit.
Page 14
Page 15
TABLE 7
PRIMARY LIMIT CONTROL (S10)
UNIT
ACTUATES
ON TEMP. RISE
O23Q2−70210F (99C)180F (82C)
O23Q3−105/120220F (104C)190F (88C)
O23Q5−140/154210F (99C)180F (82C)
OHR23Q3−105/120240F (116C)210F (99C)
OHR23Q5−140/154190F (88C)160F (71C)
OF23Q3−105/120
OF23Q3−105/120R
OF23Q5−140/154
OF23Q5−140/154R
SPADE CONNECTORS
240F (116C)210F (99C)
210F (99C)180F (82C)
LIMIT CONTROL (S10)
INSULATING COVER
ACTUATES
ON TEMP. FALL
LIMIT
1.Blower Motor (B3) and Capacitor (C4)
All O23, OHR23, and OF23 series units use single phase
direct drive blower motors. All motors used are 115V perma
nent split capacitor motors to ensure maximum efficiency.
See SPECIFICATIONS tables for horsepower and motor
nameplate for capacitor rating.The blower motor is con
nected to the blower control board via the blower motor
plug P43.
2.Secondary Limit Control (S21)
The secondary limit (S21) is used on the OHR23 series unit
only. The N.C. limit is mounted on the side and toward the
back of the blower housing. See figure 13 for location and fig
ure 14 for type. When excess heat is sensed in the blower
compartment, the limit will open. If the limit is tripped, the blow
er control deenergizes the thermostat, inturn shutting down
the unit. The limit automatically resets when unit tempera
ture returns to normal. The switch opens at 150F + 5F
(65.5C + 2.8C) on a temperature rise and resets at
140F + 5F (60.0C + 2.8C) on a temperature fall. The
switch is factory set and cannot be adjusted. The set
point is printed on the face plate of the limit.
FIGURE 12
D−Blower Compartment (Figure 13)
Blower motor (B3), capacitor (C4), and secondary limit con
trol (S21) are located in the blower compartment. The blow
er compartment can be accessed by removing the blower
access panel.
BLOWER COMPARTMENT
(OHR23 SIDE VIEW SHOWN)
SECONDARY LIMIT
CONTROL (S21)
(OHR23 ONLY)
(BACK SIDE)
BLOWER
MOTOR
CAPACITOR
(C4)
SECONDARY LIMIT CONTROL (S21)
FIGURE 14
E−Optional Accessories
Optional accessories are available from Lennox for the O23,
OHR23, and OF23 series units. Some accessories are in kit
form which come with instructions.
1.Low Speed On − Off Switch (S68)
The low speed on off switch is a kit (catalog # 67H91) which
permits continuous low speed blower operation. The switch is
a DPDT toggle switch.
FIGURE 13
BLOWER MOTOR
(B3)
2.Economizer Relay (K43)
The economizer relay (catalog # 65G40) is used to energize
the economizer if used. The relay is a 120V coil, single pole
contact which is energized by the accessory terminal of the
blower control board.
Page 15
Page 16
II−PLACEMENT AND INSTALLATION
g
Make sure unit is installed in accordance with installation in
structions and applicable codes.
A−Piping
The piping system and it’s components (oil filter, safety valves,
shutoff valves, etc.) must be designed to provide clean, air
free fuel to the burner.
An oil filter is required for all models. Use an oil filter of gener
ous capacity for all installations. Install filter inside the building
between the tank shut−off valve and the burner. Locate filter
close to burner for easy servicing. The GAR−Ber 11BV−R or
equivalent filter (with the below specifications) is recom
mended.
Fill
Pipe
Air Vent
OIL PIPING
ONEPIPE SYSTEM
Fuel
Unit
Oil
Tank
Shut−off
Valve
Aux
Filter
8 ft (2.4 m)
Maximum
One Pipe Lift
Maximum Firing Rate: 10GPH (38LPH)
Micron Removal: 10
Filtering Area: 500 in.2 (3225.8 cm2)
Working Pressure: 15 PSI (103.4 kPa)
Inlet/Outlet Dimension: 3/8" (9.5 mm) NPT
Flow Rate: 45GPH (171LPH)
Care must be taken to ensure the restriction of the piping sys
tem, plus any lift involved, does not exceed the capabili
ty of the oil pump. Each installation will be different. Use
the following guide lines when determining to use a single or
two stage pump.
When using a single pipe system with the fuel supply level
with or above the burner (see figure 15) and a vacuum of 6"
(152 mm) Hg or below, a single stage fuel unit with a supply
line and no return line should be adequate. Manual bleeding of
the fuel unit is required on initial start up. Failure to bleed air
from the pump could result in an air lock/oil starvation condi
tion.
NOTE−As an extra precaution, cycle heating on and off
ten times after bleeding air from the pump. This will elim
inate air in the gun assembly.
When using a two pipe system with the fuel supply level
below the level of the burner (see figure 16) a single
stage fuel unit should be used in lift conditions of up to
10 feet (3 m) and/or a vacuum of 10" (254 mm) Hg or be
low. A two stage fuel unit should be used when lift ex
ceeds 10 feet (3 m) and/or a vacuum of 10" (254 mm) Hg
to 15" (381 mm) Hg. Both conditions require the use of a re
turn line that purges the fuel unit of air by returning it to the fuel
tank. Use table 8 when determining the run and lift for piping.
Before converting a onepipe system to a twopipe sys
tem the pump must be converted to a twopipe system.
To convert the pump, install the bypass plug according
to the instructions. Notice in the twopipe system the re
turn line must terminate 3" (76 mm) to 4" (102 mm)
above the supply inlet. Failure to do this may introduce
air into the system and could result in loss of prime.
NOTE−If using an outside tank in cold climates a number one
fuel or an oil treatment is strongly recommended.
Page 16
FIGURE 15
OIL PIPING
TWOPIPE SYSTEM
Air Vent
Fill
Pipe
Return
Line
Oil
Tank
3"−4"
Return
Line
OUTSIDE TANK FUEL UNIT ABOVE BOTTOM OF TANK.
(76mm −102mm)
R
FIGURE 16
TABLE 8
Fuel
Unit
Aux
Filter
Inlet
H
TWO−PIPE MAXIMUM LINE LENGTH (H + R)
3450 RPM − 3 GPH (11.4 LPH)
Lift H"
Figure 15
0’
(0.0 m)
2’
(0.6 m)
4’
(1.2m)
6’
(1.8m)
8’
(2.4m)
10’
(3.0m)
12’
(3.7m)
14’
(4.3m)
16’
(4.9m)
18’
(5.5m)
3/8" (10 mm) OD
Tubing
Single
Stage
84’
(25.6 m)
73’
(22.3 m)
63’
(19.2 m)
52’
(15.8 m)
42’
(12.8 m)
31’
(9.4 m)
21’
(6.4 m)
−−−
−−−
Two
Stage
93’
(28.3 m)
85’
(25.9 m)
77’
(23.5 m)
69’
(21.0 m)
60’
(18.3 m)
52’
(15.9 m)
44’
(13.4 m)
36’
(11.0 m)
27’
(8.2 m)
−−−−−−−−−
1/2" (12 mm) OD
Tubing
Single
Stage
Stage
100’
(30.5 m)
(30.5 m)
100’
(30.5 m)
(30.5 m)
100’
(30.5 m)
(30.5 m)
100’
(30.5 m)
(30.5 m)
100’
(30.5 m)
(30.5 m)
100’
(30.5 m)
(30.5 m)
83’
(25.3 m)
(30.5 m)
41’
(12.5 m)
−−−
(30.5 m)
(30.5 m)
(23.2 m)
Two
100’
100’
100’
100’
100’
100’
100’
100’
100’
76’
Page 17
B−Venting Considerations
2− The vent connector should be as short as possible to
do the job.
WARNING
Combustion air openings in front of the furnace
must be kept free of obstructions. Any obstruction
will cause improper burner operation and may re
sult in a fire hazard or injury.
WARNING
The barometric shall be in the same atmospheric
pressure zone as the combustion air inlet to the
furnace. Deviation from this practice will cause im
proper burner operation and may result in a fire
hazard or injury.
CAUTION
Do not store combustible materials near the fur
nace or supply air ducts. The material (such as
paint, motor oil, gasoline, paint thinner, etc.) may
ignite by spontaneous combustion creating a fire
hazard.
3− The vent connector should not be smaller than the
outlet diameter of the vent outlet of the furnace.
4− Pipe should be at least 24 gauge galvanized.
5− Single wall vent pipe should not run outside or through
any unconditioned space.
6− Chimney should extend 3 feet (0.9 m) above the high
est point where the vent passes through the roof, and 2
feet (0.6 m) higher than any portion of a building within
a horizontal distance of 10 feet (3 m).
7− The vent must not pass through a floor or ceiling. Clear
ances to single wall vent pipe should be no less than 6"
(152 mm); more if local codes require it.
8− The vent may pass through a wall where provisions have
been made for a thimble as specified in the Standards of
the National Board of Fire Underwriters. See figure 17.
9− The vent pipe should slope upward toward the chim
ney on horizontal run at least 1/4 inch (6 mm) to the
foot (0.3 m) and should be supported by something
other than the furnace, such as isolation hangers. See
figure 18.
WARNING
This furnace is certified for use with type L" vent.
B" vent must not be used with oil furnaces.
NOTE−Oil burning equipment may be vented into an ap
proved masonry chimney or type L vent. (Type L vent is
similar in construction to type B gas vent except it carries a
higher temperature rating and is constructed with an inner
liner of stainless steel rather than aluminum).
Prior to installation of unit, make a thorough inspection of the
chimney to determine whether repairs are necessary. Make
sure the chimney is properly constructed and sized accord
ing to the requirements of the National Fire Protection Asso
ciation. The smallest dimensions of the chimney should be
at least equal to the diameter of the furnace vent connector.
Make sure the chimney will produce a steady draft sufficient
to remove all the products of combustion from the furnace.
A draft of at least .04" w.c. (9.9 Pa) is required during burner
operation.
1− Local building codes may have more stringent instal
lation requirements and should be consulted before
installation of unit.
10− Extend the vent pipe into the chimney so that it is flush
with the inside of the vent liner. Seal the joint between
the pipe and the liner.
11− The furnace shall be connected to a factory built
chimney or vent complying with a recognized stan
dard, or masonry or concrete chimney lined with a
lining material acceptable to the authority having
jurisdiction.
WALL THIMBLE
THIMBLE
COMBUSTIBLE
WALL
VENT PIPE
FIGURE 17
Page 17
Page 18
BAROMETRIC
CONTROL*
(IN EITHER
LOCATION)
CLEANOUT
*Barometric control may be installed in either vertical or horizontal
section of vent pipe within 18" (457 mm) of vent outlet of furnace.
LINER
CLEANOUT
MASONRY
CHIMNEY
FIGURE 18
12− When two or more appliances vent into a common vent,
the area of the common vent should not be less than the
area of the largest vent or vent connection plus 50% of
the areas of the additional vent or vent connection. Chim
ney must be able to sufficiently vent all appliances oper
ating at the same time.
13− The vent pipe shall not be connected to a chimney vent
serving a solid fuel appliance or any mechanical draft
system.
14− All unused chimney openings should be closed.
15− All vent pipe run through unconditioned areas or outside
shall be constructed of factory built chimney sections.
See figure 19.
16− Where condensation of vent gas is apparent, the vent
should be repaired or replaced. Accumulation of con
densation in the vent is unacceptable.
FACTORY−BUILT CHIMNEY
MASONRY CHIMNEY
17− Vent connectors serving this appliance shall not be
connected into any portion of mechanical draft sys
tems operating under positive pressure.
18− Keep the area around the vent terminal free of snow,
ice and debris.
NOTE−If vent pipe needs to exit from side of cabinet, use the
cross hairs (located on either side of the unit) to cut a 6" (152
mm) round hole. Attach finishing plate (provided) with four
sheet metal screws to cover rough edges.
Combustion and Ventilation Air
(Confined and Unconfined Spaces)
Until recently, there was no problem in bringing in suffi
cient amounts of outdoor air for combustion −− infiltration
provided all the air that was needed and then some. In
today’s homes built with energy conservation in mind,
tight construction practices make it necessary to bring in
air from outside for combustion. Consideration must also be
given to the use of exhaust fans, appliance vents, chimneys
and fireplaces because they force additional air that could
be used for combustion out of the house. Unless outside
air is brought into the home for combustion, negative
pressure (pressure outside is greater than inside pres
sure) will build to the point that a down draft can occur in
the furnace vent pipe or chimney. Combustion gases e n ter
the living space creating a potentially dangerous situa
tion.
The importance of the previous paragraph cannot be
overstated. Users may inadvertently block fresh air in
takes after installation.
In the absence of local codes concerning air for combus
tion and ventilation, the following section outlines guide
lines and recommends procedures for operating oil fur
naces in a manner that ensures efficient and safe
operation. Special consideration must be given to com
bustion air needs as well as requirements for exhaust vents
and oil piping.
Combustion Air Requirements
BAROMETRIC
CONTROL*
(IN EITHER
LOCATION)
*Barometric control may be installed in either vertical or horizontal
section of vent pipe within 18" (457 mm) of vent outlet of furnace.
FIGURE 19
FACTORY
BUILT
CHIMNEY
CAUTION
Insufficient combustion air can cause headaches,
nausea, dizziness or asphyxiation. It will also
cause excess water in the heat exchanger result
ing in rusting and premature heat exchanger fail
ure. It can also cause property damage.
All oil−fired appliances require air to be used for the com
bustion process. If sufficient amounts of combustion air are not
available, the furnace or other appliance will operate in an inef
ficient and unsafe manner. Enough air must be provided to
meet the needs of all fuel−burning appliances, as well as ap
pliances such as exhaust fans which force air out of the home.
When fireplaces, exhaust fans, or clothes dryers are used at
the same time as the furnace, much more air is required
to ensure proper combustion and to prevent a down−
draft situation. Insufficient amounts of air also cause in
Page 18
Page 19
comp l ete combustion which can result in sooting. Require
ments for providing air for combustion and ventilation depend
largely on whether the furnace is installed in an uncon
fined or confined space.
Unconfined Space
CHIMNEY OR
OIL VENT
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM INSIDE
An unconfined space is an area such as a basement or
large equipment room with a volume greater than 50 cu
bic feet (1.4 cubic meters) per 1,000 Btu (293 W) per
hour of the combined input rating of all appliances
installed in that space. This space also includes adjacent
rooms which are not separated by a door. Though an area
may appear to be unconfined, it might be necessary to bring in
outdoor air for combustion if the structure does not provide
enough air by infiltration. If the furnace is located in a
building of tight construction with weather stripping and
caulking around the windows and doors, follow the proce
dures outlined for using air from the outside for combus
tion and ventilation.
Confined Space
A confined space is an area with volume less than 50 cu
bic feet (1.4 cubic meters) per 1,000 Btu (293 W) per
hour of the combined input rating of all appliances
installed in that space. This definition includes furnace closets
or small equipment rooms.
When the furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space con
taining the furnace, the return air must be handled by ducts
which are sealed to the furnace casing and which terminate
outside the space containing the furnace. This is especially
important when the furnace is mounted on a platform in a con
fined space such as a closet or small equipment room. Even a
small leak around the base of the unit at the platform or at the
return air duct connection can cause a potentially dangerous
negative pressure condition. Air for combustion and ventilation
can be brought into the confined space either from inside the
building or from outside.
Air from an Adjacent Space
If the confined space housing the furnace adjoins space
categorized as unconfined, air can be brought in by pro
viding two permanent openings between the two
spaces. Each opening must have a minimum free area
of 1 square inch(6.4 square centimeters) per 1,000 Btu
(293 W) per hour of the total input rating of all fuel−fired
equipment in the confined space. Each opening must
be at least 100 square inches (614.5 square centime
ters). One opening shall be within 12" (305 mm) of the
top of the enclosure and one opening within 12" (305
mm) of the bottom (See figure 20).
OIL
FURNACE
NOTE−Each opening shall have a free area of at least 1 square inch
(6.4 square centimeters) per 1,000 Btu (293 W) per hour of the total
input rating of all equipment in the enclosure, but not less than 100
square inches(614.5 square centimeters).
WATER
HEATER
OPENINGS
(To Adjacent Room)
FIGURE 20
Air from Outside
If air from outside is brought in for combustion and ven
tilation, the confined space shall be provided with two
permanent openings. One opening shall be within 12"
(305 mm) of the top of the enclosure and one within 12"
(305 mm) of the bottom. These openings must communicate
directly or by ducts with the outdoors or spaces (crawl or attic)
that freely communicate with the outdoors or indirectly
through vertical ducts. Each opening shall have a minimum
free area of 1 square inch (6.4 square centimeters) per 4,000
Btu (1172 W) per hour of total input rating of all equipment in
the enclosure (See figures 21 and 22). When communicating
with the outdoors through horizontal ducts, each opening
shall have a minimum free area of 1 square inch (6.4
square centimeters) per 2,000 Btu (586 W) per total input
rating of all equipment in the enclosure (See figure 23).
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
(Inlet Air from Crawl Space and
Outlet Air to Ventilated Attic)
CHIMNEY
OR OIL
VENT
VENTILATION LOUVERS
(Each end of attic)
OIL
FURNACE
VENTILATION
LOUVERS
(For unheated
crawl space)
NOTE−The inlet and outlet air openings shall each have a free area of
at least one square inch (6.4 square centimeters) per 4,000 Btu (1172
W) per hour of the total input rating of all equipment in the enclosure.
OUTLET
AIR
WATER
HEATER
INLET
AIR
FIGURE 21
Page 19
Page 20
CHIMNEY
OR OIL
VENT
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
OUTLET
AIR
CAUTION
Combustion air openings in the front of the furnace
must be kept free of obstructions. Any obstruction
will cause improper burner operation and may result
in a fire hazard or injury.
OIL
FURNACE
NOTE−The inlet and outlet air openings shall each have a free area of at
least one square inch (6.4 square centimeters) per 4,000 Btu (1172 W)
per hour of the total input rating of all equipment in the enclosure.
INLET AIR
(Ends 12" above
bottom)
WATER
HEATER
FIGURE 22
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
CHIMNEY
OR OIL
OIL
FURNACE
VENT
WATER
HEATER
OUTLET AIR
CAUTION
The barometric shall be in the same atmospheric
pressure zone as the combustion air inlet to the
furnace. Deviation from this practice will cause
improper burner operation and may result in a fire
hazard or injury.
Direct Connection of Outdoor Air for Combustion
The Beckett AFII burner was designed to allow for direct air
intake piping (4" [102 mm]). The maximum equivalent
length of pipe is 70 feet (21.3 m). A 90 elbow equals
6feet (1.8 m).
To convert the AFII burner from confined space to out
side combustion air, simply remove the three screws at
taching the inlet air scoop to the burner and insert 4"
(102 mm) direct air intake piping.
The use of a barometric relief placed in the intake pipe is
recommended when outdoor combustion air is directly
connected to the burner. This will allow confined space
air to be used as combustion air in the event that the
opening to the outdoor air becomes blocked. Using a
barometric relief in the intake will reduce the chance of
sooting.
INLET AIR
NOTE−Each air duct opening shall have a free area of at least one
square inch (6.4 square centimeters) per 2,000 Btu (586 W) per hour
of the total input rating of all equipment in the enclosure. If the equip
ment room is located against an outside wall and the air openings
communicate directly with the outdoors, each opening shall have a
free area of at least one square inch (6.4 square centimeters) per
4,000 Btu (1172 W) per hour of the total input rating of all other equip
ment in the enclosure.
FIGURE 23
When ducts are used, they shall be of the same cross−sec
tional area as the free area of the openings to which they
connect. The minimum dimension of rectangular air ducts
shall be no less than 3" (76 mm). In calculating free area, the
blocking effect of louvers, grilles, or screens must be con
sidered. If the design and free area of protective covering is
not known for calculating the size opening required, it may
be assumed that wood louvers will have 20 to 25 per
cent free area and metal louvers and grilles will have 60
to 75 percent free area. Louvers and grilles must be
fixed in the open position or interlocked with the equip
ment so that they are opened automatically during equip
ment operation.
CAUTION
DO NOT USE a barometric draft relief in exhaust
vent pipe if outdoor combustion air is connected
directly to the burner. The only exception are baro
metric draft reliefs as required by FIELD or TJERN
LUND power vents.
Removal of Unit from Common Venting System
In the event that an existing furnace is removed from a venting
system commonly run with separate appliances, the venting
system is likely to be too large to properly vent the remaining
attached appliances. The following test should be conducted
while each appliance is in operation and the o t her a p
pliances not in operation remain connected to the com
mon venting system. If venting system has been installed
improperly, the system must be corrected as outlined in the
previous section.
1− Seal any unused openings in the common venting sys
tem.
2− Visually inspect venting system for proper size and hori
zontal pitch and determine there is no blockage or restric
tion, leakage, corrosion or other deficiencies which could
cause an unsafe condition.
Page 20
Page 21
3− Insofar as is practical, close all building doors and
windows and all doors between the space in which
the appliances remaining connected to the com
mon venting system are located and other spaces of
the building. Turn on clothes dryers and any ap
pliances not connected to the common venting sys
tem. Turn on any exhaust fans, such as range hoods
and bathroom exhausts, so they will operate at maxi
mum speed. Do not operate a summer exhaust fan.
Close fireplace dampers.
4− Following the lighting instruction on the unit, place the
appliance being inspected in operation. Adjust thermo
stat so appliance will operate continuously.
5− Test for spillage using a draft gauge.
6− After it has been determined that each appliance re
maining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers and
any other fuel burning appliance to their previous condi
tion of use.
7− If improper venting is observed during any of the
above tests, the common venting system must be
corrected.
Horizontal Venting
(152 mm) is permissible. Calculate the equivalent vent pipe
footage from the furnace to the mechanical vent system
(Tjernlund or Field Controls) by adding the straight vent pipe
length and the equivalent elbow lengths together.
The barometric draft control must be used in horizontal (side
wall) venting system. It must be located within 18" (457 mm) of
the furnace vent outlet. See figure 24 for barometric draft con
trol location.
III−STARTUP
A−Preliminary and Seasonal Checks
1− Inspect electrical wiring, both field and factory installed
for loose connections. Tighten as required.
2− Check line voltage. Voltage must be within range
listed on the nameplate. If not, consult the power
company and have voltage condition corrected be
fore starting unit.
B−Heating StartUp
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING
Do not attempt to start the burner when excess
oil has accumulated in the chamber, when the
furnace is full of vapor or when the combus
tion chamber is very hot.
HORIZONTAL VENTING
BAROMETRIC
CONTROL*
*When using indoor air,
barometric control must be
installed in the horizontal
venting system and located
within 18" (457 mm) of vent
When using direct connection,
barometric control must be
installed in the intake air pipe.
CONTROL FOR
HORIZONTAL
VENTING
outlet of furnace.
FIGURE 24
The O23 is approved for horizontal venting with the fol
lowing mechanical vent systems:
Tjernlund (sideshot) #SS1C and Field Controls #SWG−5 with
the CK−61 control kit. Refer to manufacturers’ installation
instructions for proper installation procedures and service
parts information.
Do not common vent with any other appliance when using
sidewall vent system.
Maximum permissible vent length is 70 equivalent feet (21.3
m). Minimum length is 15 equivalent feet (4.6 m). Each 90
elbow is equal to 6 feet (1.8 m) of straight pipe, each 45 el
bow is equal to 3 feet (0.9 m) of straight pipe. Minimum vent
pipe diameter is 4" (102 mm). Vent pipe of 5" (127 mm) and 6"
1− Set thermostat for heating demand.
2− Turn on electrical supply to unit and open all shutoff
valves in the oil supply line to the burner..
3− Check air adjustment dial on the right side of the burn
er (see figure 9). Set according to table 4.
4− On single line applications the oil pump must be
primed by bleeding the oil line. Open air bleed port and
start burner. A hose may be attached to direct oil into a
container. After last bubble is seen, bleed pump for 15
seconds. Hurried bleeding will impair efficient unit op
eration. Close port to stop bleeding. Single line instal
lations must be absolutely air tight to prevent leaks or
loss of prime.
5− If burner stops after flame is established, repeat the
bleeding procedure.
NOTE−Air bleeding is automatic on two line applica
tions; however, opening air bleed port will allow a faster
bleed. Run return line back to tank and terminate three to
four inches above the inlet line. Failure to bleed the sys
tem may cause air to be introduced into the system result
ing in a loss of prime.
6− If the burner does not start immediately, check the
safety switch on the burner primary control.
7− If burner fails to light again, refer to the trouble
shooting section in the back of this manual.
8− Proceed to section IV to complete start up.
C−Safety or Emergency Shutdown
Turn off unit power. Close all shutoff valves in the oil sup
ply line.
Page 21
Page 22
D−Extended Period Shutdown
Turn off thermostat or set to UNOCCUPIED" mode.
Close all shutoff valves in the oil supply line to guarantee no
oil leaks into burner. Turn off all power to unit. All access
panels, covers and vent caps must be in place and se
cured.
To check that the nozzle is approximately centered with
the head inside diameter, align the center mark of the
gauge with the center of the nozzle orifice, as shown in
figure 27, and move the gauge from side to side at sev
eral points. Be careful not to scratch the nozzle sur
face.
IV−HEATING SYSTEM SERVICE CHECKS
A−Oil Piping
All oil supply piping (factory and field) must be carefully
checked for oil leaks.
B−Electrode Adjustment
When adjusting the electrode, use the AFII multipurpose
gauge (Beckett part # T−500) packaged with each oil fur
nace, also available from Beckett.
To set the electrode tip gap spacing, position the gauge as
shown in figure 25. Align the center mark with the nozzle
and adjust the electrodes to the two outer marks (1/8"
[3mm] to 1/16" [2mm] minimum).
AFII ELECTRODE TIP
GAP
The Z" or zero dimension is important because it locates the
nozzle for the precise relationship with the combustion head.
To set the Z" dimension, position the gauge as shown in fig
ure 27 and loosen the nozzle line electrode assembly so that
it can be moved forward or backward in the air tube until the
nozzle becomes flush against the gauge. Tighten the nozzle
line escutcheon plate screw (shown in figure 9) to lock this
Z" dimension securely.
AFII NOZZLE CENTERING
FIGURE 25
To position the electrode tips beyond the face of the nozzle
and above the center line, position the gauge as shown in
figure 26. Align the center mark with the nozzle and adjust
the electrodes to the AC cross marks.
AFII ELECTRODE POSITIONING
FIGURE 26
FIGURE 27
C−Pressure Check
On −1 through −4 units use either the gauge port or
nozzle port to check operating pressure. On −5 units use
the nozzle port (−5 unit pumps are not equipped with
gauge port). The pump is factory set at 100 psig (689.5kPa) for the O23Q2−70 and 140 psig (965.3 kPa) for all
other O23, OHR23, and OF23 units but is adjustable (see fig
ure 28). Never operate the pump in excess of 10 ps ig (6 9
kPa) above set point. Average nozzle cutoff pressure is
80 psig (551.6 kPa). To check the cutoff pressure install
a pressure gauge in nozzle port. For −5 units use the
same gauge used for operating pressure. Run the burn
Page 22
Page 23
er for a short period and then turn off. The gauge shows
cutoff pressure.
OIL PUMP PRESSURE CHECK
*PRESSURE GAUGE
**REGULATE PRESSURE
NOT SHOWN
(beside the inlet port)
PRESSURE
GAUGE
PORT (1/8" [3mm])
NOZZLE PORT
(1/8" [3mm])
INLET PORT
(1/4" [6mm])
*PRESSURE CHECKS: NORMAL OPERATING PRESSURE IS
100 PSIG (689.5 kPa) FOR THE 023Q270 AND 140 PSIG (965.3 kPa)
FOR ALL OTHER O23, OHR23, AND OF23 UNITS. NOZZLE CUTOFF
PRESSURE IS APPROXIMATELY 80 PSIG (551.6 kPa).
**TO ADJUST PRESSURE: INSERT STANDARD SCREWDRIVER.
TURN COUNTERCLOCKWISE BELOW DESIRED PRESSURE,
THEN TURN CLOCKWISE TO SET DESIRED PRESSURE.
RETURN PORT
(1/4" [6mm])
INLET PORT
SHOWN (1/4" [6mm])
BLEED PORT
1/16" (2mm) BYPASS PLUG
INSERT FOR TWOPIPE SYSTEM
(use 5/32" [4mm] allen wrench)
FIGURE 28
D−Burner Adjustment
The following instructions are essential to the proper opera
tion of O23 series oil furnaces. To prevent sooting, these in
structions must be followed in sequence:
NOTE−All w.c. measurements are below atmospheric
pressure (negative readings).
1−Draft
This test should be taken at the vent connector between
the breaching and the barometric damper. Generally a 1/4"
(6 mm) hole will need to be drilled for the draft gauge to be
inserted into the vent connector.
A minimum of 0.03" w.c. (7.5 Pa) draft must be estab
lished without the burner in operation. With the burner in
operation, the draft should be 0.04" w.c. (9.9 Pa) to 0.05"
w.c. (12.4 Pa). This is VERY critical to the flame retention
head burners.
Oil furnace installations also require careful inspection to
make sure the chimney is in good condition and can ac
commodate the products of combustion. The temperature
in unconditioned space will also affect the draft if long vent
connectors are allowed to get too cold.
2−Overfire Draft
This test should be taken with the burner in operation.
Remove the screw from the center of the center inspec
tion port. Insert your draft gauge into the hole.
A reading of the overfire draft should be 0.02" w.c. (5.0 Pa)
less than the reading found in the vent connector. If a posi
tive reading is seen at this point, the secondary heat ex
changer may be sooted or to much air may be entering
into the heat exchanger from the combustion fan. Adjust
ments to the combustion fan can be made using the air
adjustment dial.
3−Smoke Test
The smoke test should be taken at hole drilled in step 1.
Using a smoke test gun adjust the air inlet shutter so that
you will have just a trace of smoke. Somewhere be
tween a 0 and #1 smoke. This is the starting point. Do
not stop here. After the smoke test take a CO sample.
C.S.A. requires no more than 400ppm. However, a
properly installed unit under normal operating condi
tions should not read more than 50ppm.
4−CO2 Test
Again to be taken at the vent connector pipe. With the
unit firing at a trace of smoke, test for percentage of CO
in the vent gas.
From the results of this test, a window of operation" will be
determined. This window of operation establishes some tol
erance. The tolerance the installer builds in provides room
within the setup for those things which might affect com
bustion. Those things which might affect combustion can
then do so without causing the unit to start sooting/smoking.
Things which might affect combustion include a nozzle go
ing bad, draft that changes during different climatic condi
tions, dirty oil, dirt obstructing the air inlet, etc.
To build in a window of operation," set up the burner to be
2% less in CO2. For example, if you find a reading of 12%
CO2, adjust the air inlet shutter to increase the air and drop
the CO2 to 10%.
5−Retest the Smoke
With a drop in the CO2 and increase in the air you should
see that the smoke has returned to 0.
6−Retest the Overfire Draft
This test serves to confirm that you have not increased the air
too much. Again you do not want a positive pressure at the
test port. It should still be 0.02" w.c. (5.0 kPa) less than the
draft from the vent connector. You may need to increase the
stack draft by adjusting the barometric damper.
2
Page 23
Page 24
7−Stack Temperature
Take a stack temperature reading in the vent connector pipe.
Subtract the room air temperature from the stack temperature.
This will give you the net stack temperature. Using efficiency
charts provided in most CO2 analyzers you can tell at what ef
ficiency the furnace is operating.
V−DISASSEMBLY PROCEDURES
Use the following procedures to access and disassemble the
burner or blower if service to either is needed.
WARNING
Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at discon
nect switch(es). Unit may have multiple
power supplies.
A−Disassembling Burner
The burner assembly is attached to the vestibule panel by
three nuts. Slots are provided in the mounting flange for
removing the burner assembly from the vestibule. By
loosening the nuts and by turning the whole burner as
sembly counterclockwise (figure 29), the entire burner as
sembly will come out of the furnace. There is adequate wire
to remove the burner without disconnecting wires. Once re
moved, just turn the burner around in the vest panel area.
NOTE−Before disassembling any part of the burner, turn
off power and oil supply to the burner.
BURNER REMOVAL
First, loosen three nuts which
attach burner to vest panel.
nuts
Next, rotate burner counterclockwise
on slots then pull toward you.
IGNITION TRANSFORMER
IGNITION
TRANSFORMER
SCREWS
SCREW TO OPEN
ACCESS DOOR
FIGURE 30
SCREWS
ACCESS
DOOR
2−Removing Cad Cell
1− Loosen the screw to the back access door until door
opens. See figures 30 and 31.
2− The cad cell will be located on the right side of the
chassis wall hung on a bracket. See figure 31.
3− Remove by loosening the screw on the bracket.
4− Disconnect the leads from the primary control termi
nal strip.
FIGURE 29
1−Removing Ignition Transformer
1− Remove all four screws located on the side of the
ignition transformer. See figure 30.
2− Lift the ignition transformer straight up. Do
not hinge back. Porcelain isolators may break if
hinged back.
NOTE−When testing the solid state transformer, do not
use a transformer tester designed for iron magnet trans
formers. Damage to the tester may result
CAD CELL
CAD CELL
SCREW
ACCESS
DOOR
FIGURE 31
Page 24
Page 25
3−Removing Gun Assembly
1− Loosen the screw to the back access door until door
opens. See figures 30 and 31.
2− Remove flare fitting nut on oil line at pipe adjusting
plate located on outside of blower housing.
3− Remove nut connecting oil line to gun assembly oil
line. See figure 32.
4− Remove gun assembly from air tube.
5− Remove transformer leads.
NOTE−When reinstalling gun assembly, check and
set position and Z" dimension as shown in figure
27.
NOTE−When reconnecting gun assembly oil line, make
sure flat side of nut goes first.
5−Removing Motor / Combustion Air Blower
1− Disconnect supply line at pump and oil line at gun
assembly as shown in figure 33.
2− If motor and blower wheel are to be removed away
from the burner, disconnect motor wiring harness
from the primary control. If the motor and blower
wheel only need to be removed to check and clean,
there is adequate wire in the motor wiring harness
without disconnecting.
3− Loosen two bolts securing motor to blower hous
ing. Key hole slots are provided for easy removal.
See figure 34.
4− Loosen allen set screw holding the blower wheel
onto the motor shaft and remove blower wheel.
COMBUSTION AIR MOTOR & WHEEL
GUN ASSEMBLY
Remove
both nuts
Gun
Assembly
FIGURE 32
4−Removing Oil Pump
1− Disconnect supply line at pump and oil line at gun
assembly.
2− Loosen two bolts on sides of pump securing pump
to blower housing. See figure 33.
3− Detach pump and motor shaft coupler from pump.
OIL PUMP
OIL LINE GUN
ASSEMBLY ENTRANCE
SUPPLY LINE
INLET
BLOWER
MOTOR
BOLT
BOLT
PUMP
FIGURE 34
NOTE−When reinstalling blower wheel use the AFII mul
tipurpose gauge (Beckett part # T−500) to space the dis
tance from the back of the blower wheel to the face of the
motor (1/16" [2 mm]).
B−Removing Indoor Blower
1− Turn off electric power to furnace.
2− Remove blower access door.
3− Remove two screws located in the front blower rails. See
figure 35.
4− Pull blower forward enough to disconnect the motor leads
and the secondary limit on OHR units.
5− Pull blower assembly out and place to the side.
INDOOR BLOWER (OHR23 SHOWN)
BOLTBOLT
OIL PUMP MOTOR
FIGURE 33
Page 25
MOTOR LEADS
SCREW
SECONDARY
LIMIT
(OHR only)
SCREW
FIGURE 35
Page 26
VI−TYPICAL OPERATING CHARACTERISTICS
Unit
Speeds
A−Blower Operation and Adjustment
NOTE− The following is a generalized procedure and
does not apply to all thermostat controls.
1− Blower operation is dependent on thermostat con
trol system.
2− Generally, blower operation is set at thermostat sub
base fan switch. With fan switch in ON position, blower
operates continuously. With fan switch in AUTO position,
blower cycles with demand.
3− In all cases, blower and entire unit will be off when line
voltage is disconnected.
B−Temperature Rise
Temperature rise for O23, OHR23, and OF23 units depends
on unit input, blower speed, blower horsepower and static
pressure. The blower speed must be set for unit operation
within the range of AIR TEMP. RISE °F" listed on the unit rat
ing plate.
To Measure Temperature Rise:
1.Place plenum thermometers in the supply and return air
plenums. Locate supply air thermometer in the first hori
zontal run of the plenum where it will not pick up radiant
heat from the heat exchanger.
2. Set thermostat to highest setting.
3. After plenum thermometers have reached their
highest and steadiest readings, subtract the two
readings. The difference should be in the range
listed on the unit rating plate. If the temperature is too low,
decrease blower speed. If temperature is too high in
crease blower speed to reduce temperature. To change
blower speed see Blower Speed section.
C−Blower Speed
Blower speed selection is accomplished by changing the
wires at the blower motor spade connector.
To Change Blower Speed
1− Turn off electric power to furnace.
2− Remove blower access door.
3− Remove two screws located in the front blower rails.
4− Pull blower assembly forward enough to disconnect the
motor leads.
5− Disconnect heating (red) and / or Cooling (black)
wire(s) from the motor. The common (white) wire al
ways remains on C = common.
6− Select the desired speed for heating and cooling
(H = high, M = medium, L = Low). Table 9 lists the
factory connections.
7− If cooling and heating speeds are to be the same
speed, disconnect and discard the cooling wire.
Jumper the A and H spade terminals on the BCC2 and
BCC3 board and jumper COOL to HEAT on the
ST9103A board. Run the heating terminal wire from
the BCC2, BCC3 and ST9103A board to the correct
spade connection on the blower motor.
8− To achieve low speed on continuous blower on the
ST9103A board, run a FIELD supplied wire (16 AWG
or larger) from blower motor low speed terminal to the
ST9103A CONT terminal.
TABLE 9
BLOWER SPEED SELECTION
Factory Connected
Speed Taps
Cool
(Black)
Q270ML3
Q3105/120HM3
Q5140/154HM3
Heat
(Red)
Speeds
Available
D−External Static Pressure
1. Measure tap locations as shown in figure 36.
2. Punch a 1/4" (6 mm) diam
eter hole in supply and re
turn air plenums. Insert
manometer hose flush with
inside edge of hole or in
sulation. Seal around the
hose with permagum. Con
nect the zero end of the ma
nometer to the discharge (supply) side of the sys
tem. On ducted systems, connect the other end of
manometer to the return duct as above. For systems
with non−ducted returns, leave the other end of the
manometer open to the atmosphere.
3. With only the blower motor running and the evapo
rator coil dry, observe the manometer reading. Ad
just blower motor speed to deliver the air desired
according to the job requirements.
4.Pressure drop must not exceed 0.5" W.C. (124.3 Pa).
5. Seal around the hole when the check is complete.
STATIC PRESSURE
TEST
MANOMETER
OIL UNIT
FIGURE 36
Page 26
Page 27
VII−MAINTENANCE
CAUTION
Never operate unit with access panels to the
blower compartment off or partially open.
A−Filters
If throwaway type filters are used, check monthly and
replace when necessary to assure proper furnace op
eration. Replace filters with like kind and size.
If reusable type filters are used, check monthly and clean with
water and mild detergent when necessary. When dry, they
should be sprayed with filter handicoater prior to reinstallation.
Filter handicoater is RP Products coating no. 418 and is avail
able as Lennox part no. P85069.
B−Cleaning Heat Exchanger
NOTE−Use papers or protective covering in front of fur
nace while cleaning furnace.
Cleaning the heat exchanger is made easier with a heat
exchanger cleanout kit ABRSH380 (catalog # 35K09)
available from Lennox.
1− Remove vent pipe from furnace.
2− Remove locking screws and caps from cleanout
tubes. Remove vent access elbow.
3− Using a long spiral wire brush, sweep down the outer
drum of the heat exchanger. Then using the hose at
tachment, vacuum out loose debris.
4− Remove locking screw and cap from the observation
tube and with the spiral wire brush, reach upward to
ward the rear of the heat exchanger to clean out the
crossover tube.
NOTE− Do not attempt to clean the combustion chamber.
It can be easily damaged.
5− Replace the cleanout caps and vent access elbow.
Make sure locking screws are secure.
6− Brush out and vacuum the vent outlet area of the outer
drum and replace vent pipe.
7− Clean around the burner, blower deck and vestibule
area.
C−Annual Burner Maintenance
1− Replace the oil supply line filter.
2− Remove and clean the pump strainer if applicable.
3− Replace the nozzle with an equivalent nozzle.
4− Check the pump pressure when changing nozzle.
5− Clean and inspect the electrodes for damage, re
placing any that are cracked or chipped.
6− Clean the combustion head of all lint and soot.
7− Inspect the transformer cables and connectors.
8− Remove and clean the cad cell.
9− Clean the blower wheel and the air control of any lint.
10− Check all wiring for secure connections or insulation
breaks.
11− Readjust the burner as described in section IV of this
manual.
D−Supply Air Blower
1 Disconnect power to unit.
2 Check and clean blower wheel.
3 Motors are prelubricated for extended life; no further lu
brication is required.
E−Vent Pipe
The vent pipe should be inspected annually. Remove and
clean any soot or ash found in the vent pipe. Vent pipe dete
riorates from the inside out and must be disconnected in or
der to check thoroughly. Inspect pipe for holes or rusted
areas. Inspect the vent control device and replace if found
defective. Check for tightness and to make sure there is no
blockage or leaks.
F−Electrical
1 Check all wiring for loose connections.
2 Check for correct voltage at unit (unit operating).
3 Check ampdraw on blower motor.
Motor Nameplate_________Actual_________
4 Check to see that heat is operating.
Page 27
Page 28
VIII−WIRING DIAGRAMS AND SEQUENCE OF OPERATIONS
2
7
4
1
6
10
4
81212
3
7
9
5
8
12
4
9
O23 / OHR23 / OF23−1 through −4 UNIT OPERATION SEQUENCE:
1. When disconnect is closed, 120V is routed to the blower
control board BCC2 (A15). The BCC2 feeds line voltage
to transformer (T1).
2. T1 supplies 24VAC to the burner control (A3). In turn, A3
supplies 24VAC to A15, which supplies the indoor ther
mostat (not shown) with 24VAC.
3. When there is a call for heat, W1 of the thermostat ener
gizes W of the A15 board with 24VAC.
4. A15 energizes combustion air blower relay (K13). When
K132 closes, assuming primary limit (S10) and [secon
dary limit (S21) in OHR units only] are closed, 24VAC is
routed to 1K, which closes 1K1 and 1K2. When 1K2
closes combustion air blower / pump (B6) is energized.
Simultaneously 24VAC is routed through the blower relay
(K36). When K361 closes blower motor (B6) is ener
gized on heating speed.
5. When 1K2 closes the electronic ignitor is energized
causing a 14,000VAC spark, igniting the burner. When
1K1 closes the solid state switch and cad cell are ener
gized. When the cad cell senses light the solid state
switch deenergizes the safety heater, keeping the burner
operating.
6. A15 energizes accessory relay (K109). When K1091
closes the accessory terminal on the A15 board is ener
gized with 120VAC.
7. When heat demand is satisfied, W1 of the thermostat
deenergizes W of the ignition control. W deenergizes
K13 in turn deenergizing 1K. When 1K is deener
gized B6 and A73 stop immediately. The indoor blower
runs for a designated fan off" period (90−330 seconds)
as set by jumper on BCC2 control.
8. When there is a call for cooling, Y1 of the thermostat ener
gizes Y and G of the A15 board with 24VAC.
9. A15 energizes blower relay K3. When K31 closes B3
starts on the speed set for cooling.
10. A15 energizes accessory relay K109. When K1091
closes the accessory terminal on the A15 board is ener
gized with 120VAC.
11.Provided that condensing unit is connected to Y ter
minal, cooling will start.
12. When cooling demand is satisfied, Y1 of the thermostat
deenergizes Y and G. The indoor blower and condensing
unit stops immediately.
Page 28
Page 29
1
6
6
10
9
7
10
9
1
2
4
5
3
8
4
O23 / OHR23 / OF23−5 UNIT OPERATION SEQUENCE:
1. When disconnect is closed, 120V is routed to the blower
control board (A15). The blower control board feeds line
voltage to transformer (T1).
2. When there is a call for heat, W1 of the thermostat ener
gizes W of the A15 board with 24VAC.
3. A15 energizes combustion air inducer B6 assuming pri
mary limit (S10) and [secondary limit (S21) in OHR units
only] are closed.
4. Burner control A3 energizes the electronic ignitor caus
ing a 20,000VAC spark . Burner motor (B6) and pump
valve (L35) are delayed for a 15 second pre−purge. The
pre−purge is followed by a 15 second trial for ignition.
5. After the pre−purge and trial for ignition (30 seconds)
voltage passes through contactor K1 the energizing the
indoor blower B3 on heating speed.
6. When heat demand is satisfied, W1 of the thermostat
deenergizes W of the ignition control. Combustion air
inducer B6 is de−energized. The indoor blower runs for
a designated fan off" period (60−150 seconds) as set
delay switch on blower control.
7. When there is a call for cooling, Y1 of the thermostat ener
gizes Y and G of the A15 board with 24VAC.
8. A15 energizes relay K2. When K2 contacts close, the in
door blower B3 energizes on cooling speed.
9.When cooling demand is satisfied, Y1 of the thermostat
deenergizes Y and G. The indoor blower and condensing
unit stops immediately.
10. When there is a call for continuous fan the indoor blower
(B3) is energized on cool speed. If blower control board
is wired for continuous fan, the indoor blower will energize
on low speed and remain energized after thermostat de
mand is satisfied.
Page 29
Page 30
1
3
2
TJERNLUND HORIZONTAL VENTING SYSTEM (SIDESHOT) OPERATION SEQUENCE:
1. When 1K2 closes, 120VAC is routed through the relay/timer, electronic ignitor (A73), and the limit switch.
2. The relay/timer energizes the venter motor.
3. After the venter motor establishes a draft, the N.O. fan proving switch closes completing the circuit to the burner motor.
1
2
3
FIELD CONTROL HORIZONTAL VENTING SYSTEM OPERATION SEQUENCE:
1. When 1K2 closes, 120VAC is routed through the relay.
2. The relay energizes the venter motor.
3. After the venter motor establishes a draft, the N.O. fan proving switch closes, completing the circuit to the burner motor and electronic ignitor (A73).
Page 30
Page 31
IX−TROUBLESHOOTING
Burner failure or improper unit operation can be caused by various conditions. Often the problem can be solved by a logical pro
cess of checks and eliminations. The following pages lists a few common problems along with the solutions . Careful l y che c k
the most obvious items first before proceeding to more involved procedures.
COMMON CHIMNEY VENTING PROBLEMS
Problem: Top of chimney lower
than surrounding objects.
Solution:Extend chimney above
all objects within 10 feet
(3 meters).
Problem: Chimney cap or ventilator.
Solution: Remove.
Problem:Obstruction in chimney. Obstruction can be found by
light and mirror reflecting conditions in chimney.
Solution: Use weight to break and dislodge.
Problem: Joist projecting into chimney.
Can be found by lowering a light on an ex
tension cord.
Solution: Must be handled by a
competent brick contractor.
Problem: Break in chimney lining. Can be
found by Smoke testbuild smudge fire block
ing off other opening and watching for smoke
to escape.
Solution: Must be handled by a
competent brick contractor.
Problem: Collection of soot at narrow space in the
flue opening. Can be found by lowering light on
extension cord.
Problem: Clean out with weighted brush or bag of
loose gravel on end of line.
Problem: Loose−seated pipe in flue
opening. Detected by smoke test.
Solution: Leaks should be eliminated
by cementing all pipe openings.
Problem:Coping restricts opening.
Solution:Make opening as large as
inside of chimney.
Problem: Offset. Can be found
by lowering light on extension.
Solution: Change to straight or
long offset.
Problem: Two or more openings
into same chimney. Can be found
by inspection.
Solution: The least important
opening must be closed
FIRE
PLACE
DAMPER
FIREPLACE
Problem: Smoke pipe extends into chimney.
Detected by measurement of pipe from within or ob
servation of pipe by means of a lowered light.
Solution: Length of pipe must be reduced to allow end
of pipe to be flush with inside of tile.
Problem: Failure to extend the length of
the flue partition down to the floor. De
tected by inspection or smoke test.
Solution: Extend partition to floor level.
ASH DUMP
Problem:Loose fitting clean−out door.
Detected by smoke test.
Solution: Close all leaks with cement.
Page 31
Page 32
START
BCC2 / BCC3
TROUBLESHOOTING
FLOWCHART
REPLACE
BCC2
NO
(REMOVE R & G JUMPER)
IS
120VAC ACROSS
N & ACC?
YES
JUMPER ACROSS
R &W
YES
YES
DOES UNIT
OPERATE?
NO
IS
24VAC ACROSS
R & C?
YES
JUMPER ACROSS
SCREWS R & G
IS
BLOWER
RUNNING ON HIGH
SPEED?
IS
UNIT LIT?
YES
NO
NO
NO
CHECK:
1−UNIT POWER
2−TRANSFORMER
3−LIMIT SWITCH
IS
120VAC ACROSS
N & A?
YES
CHECK BLOWER
WIRING AND
BLOWER
CHECK:
1−PRIMARY CONTROL
2−IGNITION TRANSFORMER
3−FUEL PUMP
4−ELECTRODES
5−LIMIT SWITCH(ES)
NO
REPLACE
BCC2
IS
120VAC ACROSS
N & ACC?
YES
REMOVE
R & W
JUMPER
AFTER
THE SELECTED
TIME, DOES THE
BLOWER TURN
OFF?
END OF TEST
NO
REPLACE
BCC2
YES
YES
IS BLOWER
RUNNING ON LOW
SPEED, 45 SEC.
AFTER FURNACE LIGHTS?
NO
REPLACE
BCC2
Page 32
NO
IS
120VAC ACROSS
N & H?
NO
IS
24VAC ACROSS
C & V?
NO
CHECK
WIRING
YES
CHECK BLOWER
WIRING AND
BLOWER
REPLACE
YES
BCC2
Page 33
Troubelshooting: Blower Control ST9103A
ActionSystem Response
Thermostat calls for heat.
(W terminal is energized.)
Thermostat ends call for heat.
(W terminal is de−energized.)
Burner fails to light.Oil primary control locks out within lockout timing (timing depends on oil primary control).
Established flame fails.Burner motor is de−energized and oil primary control goes into recycle mode.
Thermostat begins call for cool.
(G and Y terminals are energized.)
Thermostat ends call for cool.
(G and Y terminals are de−energized.)
Thermostat begins call for fan.
(G terminal is energized.)
Thermostat ends call for fan.
(G terminal is de−energized.)
ST9103A closes oil primary control T−T connections.
Ignition system and oil primary control start the furnace. Oil flows as long as oil primary
control senses flame.
Burner motor is energized and heat fan on delay timing begins. When timing is complete,
the circulating fan is energized at heat speed and warm air is delivered to the controlled
space.
Oil primary control is de−energized, terminating the burner cycle.
Heat fan off delay timing begins. When timing is complete, the circulating fan is de−ener
gized.
ST9103A returns to standby mode (oil primary control and circulating fan are off).
Burner motor is de−energized.
If heat fan has started, it continues through the selected delay off period.
If selected heat fan off delay is longer than the recycle delay timing, the heat fan contin
ues to run through the next trial for ignition.
Circulating fan is energized at the cool speed.
Cooling compressor turns on immediately.
Circulating fan and cooling compressor turn off immediately.
Circulating fan is energized immediately at cool speed.
ST9103A may be factory−configured to operate heat speed in this mode.
Circulating fan is de−energized.
Limit switch string opens.Oil primary control shut off the burner.
Circulating fan is energized immediately at heat speed.
ST9103A opens oil primary control T−T connections.
Circulating fan runs as long as limit string stays open.
If there is a call for cooling or fan, the circulating fan switches from heat speed to cool
speed.
Limit switch string closes.ST9103A begins heat fan off delay sequence.
Circulating fan turns off after the selected heat fan off delay timing.
ST9103A closes oil primary control T−T connections.
Oil primary control is energized, initiating burner light off.
Continuous circulating fan is connected.
(Optional connectors are available for separate circu
lating fan speed tap.)
Electronic air cleaner is connected.
(Optional connectors are available for 120 Vac elec
tronic air cleaner.)
Humidity control is connected.
(Optional connectors are available for 120 Vac humidi
fier.)
Circulating fan is energized at low speed when there is no call for heat, cool or fan.
If fan operation is required by a call for heat, cool, or fan, the ST9103A switches off the
continuous fan speed tap before energizing the other fan speed.
Electronic air cleaner (EAC) connections are energized when the heat or cool speed of
the circulating fan is energized. EAC connections are not energized when the optional
continuous fan terminal is energized.
Humidifier connections are energized when the burner motor is energized.
Page 33
Page 34
Troubleshooting O23 / OHR23 / OF23 −1 through −4 Units
y
yy
Check f
t
Thermostat
mostatterminalsonprimary
fault is in the thermostat circuit
the burner starts, fault is in the
Pri
ili
l
indi
black
hite leads to th
p
blower wheel by hand. If seized,
power to the motor and burner
Burner fails to start.
SourceProcedureCausesCorrection
Thermostat in OFF or COOLSwitch to HEAT.
ThermostatCheck thermostat settings.
Check burner motor, primary
Safety Overloads
Power
CAD Cell
Primary Control
Burner
safety control, & auxiliary limit
switch.
urnace disconnec
switch & main disconnect.
Touch jumper wire across ther
mostat terminals on primary
control. If burner starts, then
Disconnect the flame detector
wires at the primary control. If
detector circuit.
Place trouble light between the
black and white leads. No light
cates that no power is going
to the control.
Place trouble light between the
orange and white leads. No light
indicates faulty control.
Place the trouble light between
the black and white leads to the
burner motor. No light indicates
that no power is getting to the
motor.
Place trouble light between the
and w
blower motor. Light indicates
ower to the motor and burner
fault.
e
Thermostat is set too low
Burner motor overload trippedPush reset button pump motor.
Primary control tripped on safe
ty
Auxiliary limit switch tripped on
safety
Open switchClose switch.
Blown fuse or tripped circuit
breaker
Broken or loose thermostat
wires
Loose thermostat screw con
nection
Dirty thermostat contactsClean contacts.
.
Thermostat not levelLevel thermostat.
Faulty thermostatReplace thermostat.
Flame detector leads are
shorted
Flame detector exposed to lightSeal off false source of light.
short circuit in the flame detec
tor
mary or aux
switch is open
Open circuit between discon
nect switch and limit control
Low line voltage or power fail
ure
Defective internal control circuitReplace the control.
Blown fuseReplace the fuse.
Binding burner blower wheel
Sized fuel pump
Defective burner motorReplace the motor.
ary contro
Turn thermostat to higher tem
perature.
Reset primary control.
Reset auxiliary limit.
Replace fuse or reset circuit
breaker.
Repair or replace wires.
Tighten connection.
Separate leads.
Replace detector.
Check adjustment. Set the
maximum setting.
Jumper terminals; if burner
starts, switch is faulty, replace
control.
Trace wiring and repair or re
place it.
Call the power company.
Turn off power and rotate the
blower wheel by hand. If seized,
free the wheel or replace the
fuel pump.
Page 34
Page 35
Burner starts, but no flame is established.
pp
OilFilters&OilLine
S
ilk
Air leak i
pggpp
pray (g
serve the oil spray (gun assem
Inspectthenozzleforplugged
t
Cl
gap
the gap to 5/32 inches and cor
g
to transformer primary
pp
ing or excessive drag
SourceProcedureCausesCorrection
Check tank gauge or use dip
stick.
Oil Supply
Oil Filters & Oil Line
Oil Pump
Coat dip stick with litmus paste
and insert into bottom of tank.
Listen for pump whine.Tank shut−off valve closedOpen valve.
Listen for pump whine.
Open bleed valve or gauge port.
tart the burner. No oil or m
oil indicates loss or prime.
Install pressure gauge on pump
and read pressure. Should not
be less than 140 psi.
y
No oil in tankFill tank.
Water in oil tank
Oil line filter is pluggedReplace filter cartridges.
Kinks or restriction in oil lineRepair or replace oil line.
Plugged fuel pump strainerClean strainer or replace pump.
n oil supply line
Pump is partially or completely
frozen. No pressure and the
motor locks out on overload.
Coupling disengaged or broken
− no pressure
Fuel pressure too lowAdjust to 100 psi.
If water depth exceeds 1 inch,
pump or drain water.
Locate and correct leak.
Tighten all connections.
Replace pump.
Re−engage or replace coupling.
Nozzle
Ignition Electrodes
Ignition
Transformer
Burner Motor
Disconnect ignition leads. Ob
serve the oil s
bly must be removed from unit).
Inspect the nozzle for plugged
orifice or carbon build−up around
orifice.
Remove gun assembly and in
spect electrodes and leads.
Connect ignition leads to the
transformer. Start burner and ob
serve spark. Check line voltage
Motor does not come up to
speed and trips out on overload.
Turn off power and rotate blower
wheel by hand to check for bind
un assem
.
.
Nozzle orifice plugged
Nozzle strainer plugged
Poor or off center spray
Fouled or shorted electrodes
Dirty electrodes and leads
Eroded electrode tips
Improper electrode gap spacing
Improper position of electrode
tips
Bad buss bar connectionRetension and realign.
Cracked or chipped insulatorsReplace electrode.
Cracked or burned lead insula
tors
Low line voltage
Burned out transformer wind
ings.
No spark or weak spark
Low line voltage
Pump or blower overloading
motor
Faulty motorReplace motor.
Replace nozzle with the same
size, spray angle, and spray
ype.
ean electrode leads.
Clean electrode tips and reset
the
rectly position tips.
Replace electrode leads.
Check voltage at power source.
Correct cause of voltage drop
or call the power company.
Replace the transformer.
Properly ground the transformer
case.
Check voltage at power source.
Correct cause of voltage drop
or the call power company.
Correct cause of overloading.
to 5/32 inches and cor
Page 35
Page 36
Burner starts and fires, but locks out on safety.
due to poor
,
acrossflame
If fire is good
fault may be
p
After burner
,
If fire is good
Fl
detector termi
in the fuel sys
pp
SourceProcedureCausesCorrection
Unbalanced fireReplace nozzle
Too much air − −lean short fire
Too little air − − long dirty fire
Excessive draft
Too little draft or restriction
Dirty cad cell faceClean cad cell face.
,
Faulty cad cell − exceeds 1500
hms
Loose or defective cad cell
wires
Primary control circuit defectiveReplace primary control.
Poor Fire
Flame Detector
Primary Control
After burner
fires, immedi
ately jumper
across flame
detector termi
nals at the pri
mary control.
If burner con
tinues to run,
this may be
fire. Inspect
fire.
If fire is good
fault is in the
flame detector.
Check detec
tor circuit.
If burner locks
out on safety,
fault is in the
primary con
trol.
Reduce combustion air − check
combustion.
Increase combustion air − check
combustion.
Adjust barometric damper for
correct draft.
Correct draft or remove restric
tion.
Replace cad cell.
Secure connections or replace
cad cell holder and wire leads.
Burner starts and fires, but loses flame and locks out on safety.
SourceProcedureCausesCorrection
Unbalanced fireReplace nozzle
Poor Fire
ame Detector
Oil Supply
After burner
fires, immedi
ately jumper
across flame
detector termi
nals at the pri
mary control.
Listen for pump whine
If burner con
tinues to run
(does not lock
out of safety),
due to poor
fire. Inspect
fire.
If fire is good
fault is in the
flame detector.
Check detec
tor circuit.
If burner loses
flame (does
not lock out on
safety), fault is
in the fuel sys
tem.
Too much air − − lean short fire
Too little air − − long dirty fire
Excessive draft
Too little draft or restriction
Dirty CAD cell faceClean CAD cell face.
,
Faulty CAD cell − − exceeds
15000 hms
Loose or defective cad cell
wires
Pump loses prime − air slugPrime pump at bleed port
Pump loses prime − air leak in
supply line
Water slug in lineCheck oil tank for water (over 1
Partially plugged nozzle or
nozzle strainer
Restriction in oil lineClear restriction.
Plugged fuel pump strainerClean strainer or replace pump.
Cold oil − outdoor tankChange to number 1 oil.
Reduce combustion air − check
combustion.
Increase combustion air − check
combustion.
Adjust barometric damper for
correct draft.
Correct draft or remove restric
tion.
Replace CAD cell.
Secure connections or replace
cad cell holder and wire leads.
Check supply line for loose con
nections and tighten fittings.
inch) pump or drain out water.
Replace nozzle.
Page 36
Page 37
Burner starts and fires, but short cycles (too little heat).
Thermostat
Check thermostat
(
Limit Control
control (black & white leads). If
P
If burner turns
Thermostat
Disconnect
circuit.
wires at the pri
SourceProcedureCausesCorrection
Heat anticipator set too lowCorrect heat anticipator setting.
ThermostatCheck thermostat.
Connect voltmeter between line
voltage connections to primary
Limit Control
ower
control
burner cycles due to power inter
ruption, it is cycling on limit.
If voltage fluctuates, fault is in the
power source. Recheck voltage
at the power source.
black & white leads). If
.
Vibration at thermostatCorrect source of vibration.
Thermostat in the path of a
warm air draft
Dirty furnace air filtersClean or replace filter.
Burner running too slow
Blower motor seized or burned
out
Blower bearings seizedReplace bearings and shaft.
Blower wheel dirtyClean blower wheel.
Blower wheel in backwardReverse blower wheel.
Wrong motor rotation
Restrictions in return or supply
air system
Adjustable limit control set too
low
Loose wiring connectionLocate and secure connection.
Low or fluctuating line voltageCall power company.
Shield thermostat from draft or
relocate.
Increase blower speed to main
tain proper temp. rise.
Replace motor.
Replace with properly rotating
wheel.
Correct cause of restriction.
Reset limit to maximum stop
setting.
Burner runs continuously (too much heat).
SourceProcedureCausesCorrection
If burner turns
Thermostat
Disconnect
thermostat
mary control.
Primary control
off, fault is in
the thermostat
circuit.
If burner does
not turn off,
fault is in the
primary control.
Shorted or welded thermostat
contacts
Stuck thermostat bimetal
Thermostat not levelLevel thermostat.
Shorted thermostat wiresRepair short or replace wires.
Thermostat out of calibrationReplace thermostat.
Thermostat in cold draft
Defective primary control
Repair or replace the thermo
stat.
Clear obstruction or replace
thermostat.
Correct draft or relocate the
thermostat.
Replace the defective primary
control.
Page 37
Page 38
Burner runs continuously cont.
L
CO
l
Dirt
g
Check b
reading more
CO2, stack tem
High stack tem
550 F Net.
Oil P
Inspect fire and check
)
SourceProcedureCausesCorrection
urner
Combustion
ressure
combustion for
CO2, stack tem
perature, and
smoke
Inspect fire and check
oil pressure.
Too much combustion airReduce combustion air.
Air leaks into heat exchanger
ow
2
than 10%.
ess
around inspection door, etc.
Excessive draft
Incorrect burner head adjust
ment
y or plugged heat exchanger
High smoke
readin
more
Insufficient draftIncrease draft.
than a trace.Incorrect burner head adjust
ment
Too little combustion airIncrease combustion air.
Too little blower air
Blower belt too loose (if
High stack tem
perature is
more than
F Net.
550
equipped)
Dirty or plugged heat exchanger Clean heat exchanger.
Dirty blower wheelClean blower wheel.
Dirty furnace air filtersClean or replace filter.
Restricted or closed registers or
dampers
Partially plugged or defective
nozzle
Oil pressure is too low: less
than 100 psi.
Correct cause of air leak.
Adjust barometric draft con
trol for correct draft.
Correct burner head setting.
Clean heat exchanger.
Readjust burner.
Correct burner setting.
Increase blower speed to
maintain proper temp. rise.
Tighten blower belt.
Readjust registers or damp
ers.
Replace nozzle.
Increase oil pressure top
100psi.
Troubelshooting O23 / OHR23 / OF23 −5 Units
ProcedureStatusCorrection
CONDITION 1: BURNER DOES NOT ENERGIZE WITH A CALL FOR HEAT.
1.1 Check limit switch contacts are
closed and clean.
1.2 Check for line votage at oil pri
mary control. Voltage should be
120V
1.3 Check LED light with burner off,
no call for heat (no flame
1.4 Sheild cad cell from external
light
1.5 On warm air systems, Remove
one thermostat lead and jumper
thermostat (T to T) terminals on
burner control.
LED is on
LED is offSee step 1.5.
LED is offEliminate exteranl light or shield light from cad cell
LED stays on
Burner energizes
Burner does not energize
Clean contacts. Replace limit switch if necessary.
Check primary voltage source. Take appropiate measures to cor
rect if necessary.
Cad cell or control is bad. Control sees external light or connections
are shorted. See step 1.4.
Replace cad cell and recheck.
If LED stays on remove cad cell lead wires from burner control
and recheck.
If LED turns off, replace cad cell bracket assembly.
If LED stays on replace buner control
Trouble in thermostat or limit circuit. Check thermostat or limit wir
ing connections.
Disconnect line voltage power and open line switch
Check all wiring and tighten any loose connections. Recheck
If burner does not energize replace burner control
Page 38
Page 39
Troubelshooting O23 / OHR23 / OF23 −5 Units Cont.
)
Ignit
Ignition is off
l
cell back in socket
B
S
K
p
Replace cad cell with new cad cell
Reconnectlinevoltageandclose
LED i
S
line switch
controlandleavewiresopen.
LED i
Repl
CONDITION 2: BURNER STARTS, THEN LOCKS OUT ON SAFETY WITH LED FLASHING 1/2 SECOND ON
2.1 Check limit switch contacts are
closed and clean.
2.2 Check for line votage at oil pri
mary control. Voltage should be
120V
2.3 Check LED light with burner off,
no call for heat (no flame
2.4 Sheild cad cell from external
light
2.5 On warm air systems, Remove
one thermostat lead and jumper
thermostat (T to T) terminals on
burner control.
2.6 Hit reset button on burner con
trol
2.7 Listen for spark after burner en
ergizes (after 2 second delay)
2.8 Check LED after flame is estab
lished, but before buner control
lockcs out.
2.9 Check cad cell sighting for view
of flame
Disconnect line voltage and open
line switch
Unplug cad cell and clean cad cell
face with soft cloth. Check sighting
for clear view of flame. Place cad
cell back in socket.
Reconnect line voltage and close
line switch.
Start burner
2.10 Check cad cell.
Disconnect line voltage and open
line switch
lace cad cell with new cad cell
Re
Disconnect all wires from thermo
stat to prevent a call for herat.
Reconnect line voltage and close
line switch.
Expose new cad cell to bright light,
such as a flash light
2.11 Check cad cell bracket assem
bly.
Disconnect line voltage and open
line switch
Remove cad cell wires from quick
connect connectors on the burner
control and leave wires open.
Apply power to buner control.
Place jumper across cad cell termi
nals after buner motor is energized.
.
LED is on
LED is offSee step 2.5.
LED is offEliminate exteranl light or shield light from cad cell
LED stays on
Burner energizes
Burner does not energize
LED stops flashingSee step 2.7.
LED continuse to flash
Ignition is off
Ignition is on
Ignition is on but no oil is
sprayed to combustion cham
ber
LED is on until the burner
control locks out and starts
flashing during lock out.
Burner locks outSee step 2.10
LED is on.Go back to step 2.6
LED is on.Replace cad cell assembly.
1/2 SECOND OFF
urner continuse to run
s off.
s off.
Clean contacts. Replace limit switch if necessary.
Check primary voltage source. Take appropiate measures to cor
rect if necessary.
Cad cell or control is bad. Control sees external light or connections
are shorted. See step 2.4.
Replace cad cell and recheck.
If LED stays on remove cad cell lead wires from burner control
and recheck.
If LED turns off, replace cad cell bracket assembly.
If LED stays on replace buner control
Trouble in thermostat or limit circuit. Check thermostat or limit wir
ing connections.
Disconnect line voltage power and open line switch
Check all wiring and tighten any loose connections. Recheck
If burner does not energize replace burner control
Verify burner control is not in restricted mode.
(1/2 second flash)
or could be bad. Check line voltage at ignitor terminals. If line
voltage is present, replace burner contro
Wait for 15 second pre−purge to complete. Check oil valve, oil valve
wiring, pump and oil supply.
Replace burner control
ystem is O.
ee step 2.11
ace burner control.
Page 39
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.