Lennox O23Q2-70, O23Q3-70, O23Q2-90, O23Q3-90, O23Q3-105 Installation Instructions Manual

...
Page 1
504,626M
*P504626M*
03/10
*2P0310*
Page 1
E 2002 Lennox Industries Inc.
Dallas, Texas, USA
FOR FUTURE REFERENCE
WARNING
Do not store or use gasoline or other flammable va­pors and liquids in the vicinity of this or any other ap­pliance.
WARNING
Improper installation, adjustment, alteration, ser­vice, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information, consult a licensed profes­sional installer, or equivalent, or service agency.
INSTALLATION INSTRUCTIONS
O23 SERIES UNITS
OIL UNITS
504,626M 38152A059 03/2010
Supersedes 01/2004
Table of Contents
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping & Packing 1. . . . . . . . . . . . . . . . . . . . . . . . . .
O23 Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . .
O23 Start−Up & Performance Check List 2. . . . . . . .
O23 Unit Parts Arrangement 3. . . . . . . . . . . . . . . . . . . . .
O23 Oil Burner Parts Arrangement 3. . . . . . . . . . . . . . . .
Requirements 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Locate & Level the Unit 5. . . . . . . . . . . . . . . . . . . . . . .
Unit Adjustments 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Venting 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Flue Connections 10. . . . . . . . . . . . . . . . . . . . . . . . . . .
Supply & Return Air Plenums 11. . . . . . . . . . . . . . . . .
Oil Supply Line & Filter Connections 12. . . . . . . . . . .
Leak Check 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Wiring 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Start-Up & Adjustments 16. . . . . . . . . . . . . . . . . .
Service 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CAUTION
When venting this appliance, keep vent terminal free of snow, ice and debris.
General
These instructions are intended as a general guide and do not supersede local codes in any way. Only licensed pro­fessional technicians, or equivalent, can install and service the Lennox Elite
®
Series O23 oil furnaces. In Canada, refer to CSA B139 for recommended installation procedures. Consult authorities who have jurisdiction before installa­tion.
CAUTION
Never burn garbage or paper in the heating system. Never leave papers near or around the unit.
Shipping & Packing List
1− Assembled oil furnace 1− Barometric draft control 1− Side exhaust pipe collar 1− Direct intake collar (AFII burner units only) Check the components for shipping damage. If you find
any damage, immediately contact the last carrier.
Litho U.S.A.
Page 2
Page 2
O23 Unit Dimensions − Inches (mm)
SUPPLY
AIR
OPENING
FLUE
CONNECTION
(On Heat
Exchanger)
AIR FLOW
ELECTRICAL INLET
(Right Side Only)
OIL PIPING INLET
(Left Side Only)
RETURN AIR
OPENING
(Either Side)
TOP VIEW
SIDE VIEW FRONT VIEW
22
(559)
14
(356)
2 (51)
1-1/2
(38)
23-1/2
(597)
54
(1372)
1-1/2
(38)
3/4
(19)
AB
C
D
3/4
(19)
22
(559)
RETURN AIR
E
RETURN AIR
1-1/4
(32)
TOP FLUE
OUTLET
SIDE
FLUE OUTLET
CENTERING HOLE
(Field Fabricate
Either Side)
OPT. OUTDOOR
COMBUSTION
AIR INLET
CENTERING HOLE
(Field Fabricate
Right Side only)
Model No. A B C D E
O23Q2/3-70/90 O23Q3/4-105/120
in. 19-1/2 30-5/8 18 19-5/8 16
mm 495 778 457 498 406
O23Q5-140/154
in. 22-1/2 33-1/8 21 22-1/8 18
mm 572 841 533 562 457
O23 Start−Up & Performance Check List
Filter Clean & Secure?
Supply Voltage
Electrical Connections Tight?
Job Name
Job Location Installer Unit Model No.
Oil Pump Pressure [recommended min. 100 psig for −70;
min. 140 psig for all other units )]
Job No.
City
City
Serial No.
Date
State
Serviceman
Draft Reading (recommended .03−.04 inches w.c.)
Flue Connections Tight?
HEATING SECTION
THERMOSTAT
Calibrated? Heat Anticipator Properly Set? Level?
Blower Motor Amps
Blower Motor H.P.
Blower Motor Lubrication O.K.?
Piping Connections Tight?
Vent Clear?
State
Temperature RiseFan Control Cutout
Fan Control Setting (maximum 130_ F)
Burner Model No.
Serial Number
All Valves Open?
PROPER DRAFT
% CO2 (recommended 12%)
(55_C)
Page 3
Page 3
O23 Unit Parts Arrangement
Figure 1
clean-out port
limit switch
control box
with fan control board
Beckettr
AFII burner
indoor blower
capacitor
blower motor
observation
port
clean−out port
flue opening
heat exchanger
combustion air intake
O23 Oil Burner Parts Arrangement
Figure 2
FB−HEAD
HEAD
INSULATOR
CLIP
RETAINING
1/4" HEX
HEAD SCREW
FB HEADS
ASSY FOR
AIR TUBE
ASSY.
ELECTRODE HEAD
NOZZLE LINE
PEDESTAL
ADAPTER
NOZZLE
AIR SCOOP
INLET
WHEEL
BLOWER
FLANGE
GASKET
MOTOR
4X4
BOX
IGNITOR
DOOR GASKET
REAR ACCESS
COUPLING
FUEL PUMP
PLATE
ESCUTCHEON
NUT
SPLINED
DOOR ASSY
REAR ACCESS
ASSY
HOUSING
MAIN
SCREWS
AIR TUBE
FLANGE
ASSY
ELECTRODE
6
5
4
3
7
0
8
ELECTRONIC IGNITION
TRANSFORMER
PRIMARY
CONTROL
AIR ADJ. DIAL
CONNECTOR
TUBE
PREMOUNTED OIL−DELAY VALVE
Page 4
Page 4
Requirements
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc.
P.O. Box 799900 Dallas, TX 75379−9900
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a qualified installer or service agency.
Installation of Lennox oil−fired furnaces must conform with the National Fire Protection Association Standard for the Installation of Oil Burning Equipment, NFPA No. 31, the National Electrical Code, ANSI/NFPA No.70 (in the U.S.A.), CSA Standard CAN/CSA−B139 (in Canada), Installation Code for Oil Burning Equipment, the Canadian Electrical Code Part1, CSA 22.1 (Canada), the recommen­dations of the National Environmental Systems Contrac­tors Association and any state or provincial laws or local or­dinances. Authorities having jurisdiction should be consulted before installation. Such applicable regulations or requirements take precedence over general instructions in this manual.
Chimneys and chimney connectors must be of the type and construction outlined in section 160 of NFPA No. 31.
Air for combustion and ventilation must conform to stan­dards outlined in section 140 of NFPA No. 31 or, in Canada, CSA Standard B139. When installing O23 units in confined spaces such as utility rooms, two combustion air openings are required. Dimensions of combustion air openings are shown in table 1. One opening shall be below burner level and the other opening shall be no more than 6"(152 mm) from the room’s ceiling.
IMPORTANT
An opening to the outside for combustion air is strongly recommended, especially in new homes. Refer to table 2 or the unit rating plate for specific combustion air opening dimensions.
The combustion air opening should provide a minimum free area one-half square inch per 1,000 Btu per hour input. This combustion air should be brought into the area con­taining the furnace below the level of the furnace burner.
Table 1
Combustion Air Opening Dimensions
Model No.
Combustion Air Opening
Dimensions (2 required)
O23−70/105/120 10" X 20" (254 mm X 508 mm)
O23−140/154 11" X 22" (279 mm X 559 mm)
This unit is approved for use on combustible flooring and for clearances to combustible material as listed on unit rat­ing plate and in table 2. Unit service and accessibility clear­ances take precedence over fire protection clearances.
Table 2
Installation Clearances inches (mm)
Clearances
70/105/120 140/154
top of plenum and duct 2 (51) 2 (51)
plenum sides 3 (76) 3 (76)
sides 0 (0) 0 (0)
rear 0 (0) 0 (0)
front 4 (120) 4 (120)
flue pipe measured from
above
6 (152) 6 (152)
flue pipe measured vertical 6 (152) 6 (152)
NOTE − Service access clearance must be maintained.
*Minimum clearance shown for flue pipe may be reduced by using special protection as provided by local building codes and the National Fire Protection Association Standards.
Unit must be adjusted to obtain a temperature rise in the range listed in table 6 in the Start-Up section of this manual.
When installed, furnace must be electrically grounded in accordance with local codes or, in the absence of local codes, with the current National Electric Code, ANSI/NFPA No. 70, or Canadian Electric Code (CEC) if an external electrical source is utilized.
Field wiring connection with unit must meet or exceed specifications of type T wire and withstand a 63_F (17_C) temperature rise.
Page 5
Page 5
When furnace is used in conjunction with cooling units, it shall be installed in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating element. With a parallel flow arrangement, a damper (or other means to control the flow of air) shall be adequate to pre­vent chilled air from entering the furnace and, if manually operated, must be equipped with means to prevent opera­tion of either unit, unless damper is in the full heat" or cool" position.
Locate & Level the Unit
1 − Set the unit in desired location keeping in mind the
clearances listed in table 2. Also keep in mind oil sup­ply connections, electrical supply, flue connections and sufficient clearance for installing and servicing unit.
2 − Level the unit from side to side and from front to rear. If
the furnace is not level, place fireproof wedges or shims between the low side of the furnace and the floor. Make sure the weight of the furnace is distributed evenly on all four corners. Strain on sides of cabinet causing cracking and popping noises may occur if weight of furnace is not evenly distributed.
Unit Adjustments
Neither the nozzle setting nor the air adjustments are facto­ry set. The furnace is fire tested and the limit control is checked to make sure it functions properly; no factory set­tings are made. During installation, the furnace must be set up." The installing dealer/contractor must have and use proper test equipment in order to correctly set up the oil furnace. Proper testing equipment is required to ensure correct operation of the unit. The use of test equipment is now more critical than ever due to tighter tolerances need­ed to keep the furnace operating efficiently. Among the test equipment for an oil furnace, the proper combustion test kit should contain the following:
D Draft gauge D CO
2
or O2 analyzer
D Smoke tester D Pressure gauge D High temperature thermometer D Beckett T−500 gauge D Oil vacuum gauge D Knowledge of proper test equipment operation
CAUTION
Improper nozzle and/or air adjustment of this unit may result in sooting problems. Refer to the follow­ing section for correct adjustment procedures.
Adjusting the Nozzle
Proper adjustment of the nozzle assembly is critical be­cause alignment may have changed during shipping. Be­fore the furnace and oil lines are installed, the nozzle as­sembly must be checked. To check the nozzle assembly, remove the entire burner assembly (not just the nozzle) from the furnace. The lower firing nozzle is factory installed. This should be verified by the installer. Inspect the spark transformer leads also to ensure they are still at­tached to the electrodes.
The burner assembly is attached to the vestibule panel by three nuts. Slots are provided in the mounting flange for re­moving the burner assembly from the vestibule. By loosen­ing the nuts and by turning the whole burner assembly counterclockwise (figure 3), the entire burner assembly will come out of the furnace. There is adequate wire to remove the burner without disconnecting wires. Once removed, turn the burner around in the vest panel area.
Figure 3
O23 Series Burner Removal
Loosen three nuts which at-
tach burner to vest panel.
Rotate burner counterclockwise on
slots then pull toward you.
To correctly adjust the nozzle, use a Beckett #T−500 gauge
Insert the small end of the gauge into the end of the cone and measure from the flat of the end cone to the tip of the nozzle. When nozzle depth is correct, the tip of the nozzle should just touch the end of the gauge. Refer to the illustra­tion sheet provided with the gauge. Note that the scale side of the gauge is not used for this purpose. Make corrections by sliding the nozzle assembly forward or backward within the blast tube (figure 4). At the same time, check the nozzle alignment.
Page 6
Page 6
To check nozzle alignment, again insert the small end into the end cone and measure the nozzle and electrode align­ment against the center lines marked on the gauge (again refer to enclosed illustration sheet). If the nozzle is not cen­tered, but found to be too far left or right, a new nozzle as­sembly will need to be ordered. Do not attempt to adjust by bending the 90 degree elbow in the oil line.
Figure 4
Beckett Oil Burner Nozzle Adjustment
TO ADJUST NOZZLE:
Burner must be removed from
furnace for this procedure.
GAUGE
1−Loosen screw. 2−Slide entire nozzle/electrode assembly back and forth until nozzle just touches gauge.
1
2
Venting
WARNING
Combustion air openings in front of the furnace must be kept free of obstructions. Any obstruction will cause improper burner operation and may result in a fire hazard.
WARNING
The barometric damper shall be in the same atmo­spheric pressure zone as the combustion air inlet to the furnace. Deviation from this practice will cause improper burner operation and may result in a fire hazard.
CAUTION
Do not store combustible materials near the furnace or supply air ducts. The material (such as paint, mo­tor oil, gasoline, paint thinner, etc.) may ignite by spontaneous combustion creating a fire hazard.
WARNING
This furnace is certified for use with type L" vent. B" vent must not be used with oil furnaces.
NOTE − Oil burning equipment may be vented into an ap­proved masonry chimney or type L vent. (Type L vent is similar in construction to type B gas vent except it carries a
higher temperature rating and is constructed with an inner liner of stainless steel rather than aluminum).
Prior to installation of unit, make a thorough inspection of the chimney to determine whether repairs are necessary. Make sure the chimney is properly constructed and sized according to the requirements of the National Fire Protec­tion Association. The smallest dimensions of the chimney should be at least equal to the diameter of the furnace vent connector. Make sure the chimney will produce a steady draft sufficient to remove all the products of combustion from the furnace. A draft of at least .04" w.c. (9.9 Pa) is re­quired during burner operation.
1 − Local building codes may have more stringent installa-
tion requirements and should be consulted before installation of unit.
2 − The vent connector should be as short as possible to
do the job.
3 − The vent connector should not be smaller than the out-
let diameter of the vent outlet of the furnace.
4 − Pipe should be at least 24 gauge galvanized.
5 − Single wall vent pipe should not run outside or through
any unconditioned space.
6 − Chimney should extend 3 feet (0.9 m) above highest
point where the vent passes through the roof, and 2 feet (0.6 m) higher than any portion of a building within a horizontal distance of 10 feet (3 m).
7 − The vent must not pass through a floor or ceiling.
Clearances to single wall vent pipe should be no less than 6" (152 mm); more if local codes require it.
8 − The vent may pass through a wall where provisions
have been made for a thimble as specified in the Stan­dards of the National Board of Fire Underwriters. See figure 5.
WALL THIMBLE
FIGURE 5
THIMBLE
VENT PIPE
COMBUSTIBLE
WALL
9 − The vent pipe should slope upward toward the chim-
ney on horizontal run at least 1/4 inch (6 mm) to the foot (0.3 m) and should be supported by something other than the furnace, such as isolation hangers. See figure 6.
Page 7
Page 7
MASONRY CHIMNEY
BAROMETRIC
CONTROL* (IN EITHER
LOCATION)
CLEAN OUT
CLEAN OUT
LINER
MASON-
RY
CHIMNEY
Figure 6
*Barometric control may be installed in either vertical or hori­zontal section of flue pipe within 18" of flue outlet of furnace.
10− Extend the vent pipe into the chimney so that it is flush
with the inside of the vent liner. Seal the joint between the pipe and the liner.
11− The furnace shall be connected to a factory built chim-
ney or vent complying with a recognized standard, or masonry or concrete chimney lined with a lining mate­rial acceptable to the authority having jurisdiction.
12− When two or more appliances vent into a common
vent, the area of the common vent should not be less than the area of the largest vent or vent connection plus 50% of the area of the additional vent or vent con­nection. Chimney must be able to sufficiently vent all appliances operating at the same time.
13− The vent pipe shall not be connected to a chimney
vent serving a solid fuel appliance or any mechanical draft system.
14− All unused chimney openings should be closed.
15− All vent pipe run through unconditioned areas or out-
side shall be constructed of factory built chimney sec­tions. See figure 7.
16− Where condensation of vent gas is apparent, the vent
should be repaired or replaced. Accumulation of con­densation in the vent is unacceptable.
17− Vent connectors serving this appliance shall not be
connected into any portion of mechanical draft sys­tems operating under positive pressure.
18− Keep the area around the vent terminal free of snow,
ice and debris.
NOTE − If vent pipe needs to exit from side of cabinet, use the pilot hole (located on either side of the unit) to cut a 6" (152 mm) round hole. Attach finishing plate (provided) with four sheet metal screws to cover rough edges.
FACTORY−BUILT CHIMNEY
BAROMETRIC
CONTROL* (IN EITHER
LOCATION)
DRAIN FOR
CONDENSATE
FACTORY
BUILT
CHIMNEY
Figure 7
*Barometric control may be installed in either vertical or hori­zontal section of flue pipe within 18" of flue outlet of furnace.
Combustion and Ventilation Air (Confined and Unconfined Spaces)
In the past, there was no problem in bringing in sufficient amounts of outdoor air for combustion − infiltration provided all the air that was needed and then some. In today’s homes built with energy conservation in mind, tight construction practices make it necessary to bring in air from outside for combustion. Consideration must also be given to the use of exhaust fans, appliance vents, chim­neys and fireplaces because they force additional air that could be used for combustion out of the house. Unless out­side air is brought into the home for combustion, negative pressure (pressure outside is greater than inside pressure) will build to the point that a down draft can occur in the fur­nace vent pipe or chimney. Combustion gases enter the liv­ing space creating a potentially dangerous situation.
The importance of the previous paragraph cannot be over­stated. Users may inadvertently block fresh air intakes af­ter installation.
In the absence of local codes concerning air for combus­tion and ventilation, the following section outlines guide­lines and recommends procedures for operating oil fur­naces in a manner that ensures efficient and safe operation. Special consideration must be given to combus­tion air needs as well as requirements for exhaust vents and oil piping.
Page 8
Page 8
Combustion Air Requirements
CAUTION
Insufficient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rust­ing and premature heat exchanger failure. It can also cause property damage.
All oil-fired appliances require air to be used for the com­bustion process. If sufficient amounts of combustion air are not available, the furnace or other appliance will operate in an inefficient and unsafe manner. Enough air must be pro­vided to meet the needs of all fuel-burning appliances, as well as appliances such as exhaust fans which force air out of the home. When fireplaces, exhaust fans, or clothes dry­ers are used at the same time as the furnace, much more air is required to ensure proper combustion and to prevent a down-draft situation. Insufficient amounts of air also cause incomplete combustion which can result in sooting. Requirements for providing air for combustion and ventila­tion depend largely on whether the furnace is installed in an unconfined or confined space.
Unconfined Space
An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.4 cubic meters) per 1,000 Btu (293 W) per hour of the combined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be unconfined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures outlined for using air from the outside for combustion and ventilation.
Confined Space
A confined space is an area with volume less than 50 cubic feet (1.4 cubic meters) per 1,000 Btu (293 W) per hour of the combined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms.
When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space con­taining the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room.
Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the confined space ei­ther from inside the building or from outside.
Air from an Adjacent Space
If the confined space housing the furnace adjoins space categorized as unconfined, air can be brought in by provid­ing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch
(6.4 square centimeters) per 1,000 Btu (293 W) per
hour of the total input rating of all fuel-fired equipment in the confined space. Each opening must be at least 100 square inches (614.5 square centimeters). One opening shall be within 12" (305 mm) of the top of the enclosure and one opening within 12" (305 mm) of the bottom (See figure 8).
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM INSIDE
CHIMNEY OR
OIL VENT
WATER
HEATER
OPENINGS
(To Adjacent Room)
FIGURE 8
NOTE−Each opening shall have a free area of at least 1 square inch (6.4 square centimeters) per 1,000 Btu (293 W) per hour of the total input rating of all equipment in the enclosure, but not less than 100 square inches
(614.5 square centimeters).
OIL
FURNACE
Air from Outside
If air from outside is brought in for combustion and ventila­tion, the confined space shall be provided with two perma­nent openings. One opening shall be within 12" (305 mm) of the top of the enclosure and one within 12" (305 mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (6.4 square centimeters) per 4,000 Btu (1172 W) per hour of total input rating of all equipment in the enclosure (See figures 9 and 11). When communi-
Page 9
Page 9
cating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (6.4 square centimeters) per 2,000 Btu (586 W) per total in­put rating of all equipment in the enclosure (See figure 11).
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
(Inlet Air from Crawl Space and
Outlet Air to Ventilated Attic)
NOTE − The inlet and outlet air openings shall each have a free area of at least one square inch (6.4 square centimeters) per 4,000 Btu (1172 W) per hour of the total input rating of all equipment in the en­closure.
VENTILATION LOUVERS
(Each end of attic)
OUTLET
AIR
WATER
HEATER
INLET
AIR
CHIMNEY
OR OIL
VENT
VENTILATION
LOUVERS
(For unheated
crawl space)
FIGURE 9
OIL
FURNACE
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (6.4 square centimeters) per 4,000 Btu (1172 W) per hour of the total input rating of all equipment in the enclosure.
CHIMNEY
OR OIL
VENT
WATER
HEATER
OUTLET
AIR
VENTILATION LOUVERS
(Each end of attic)
INLET AIR
(Ends 12" above
bottom)
FIGURE 10
OIL
FURNACE
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
OUTLET AIR
INLET AIR
WATER
HEATER
CHIMNEY
OR OIL
VENT
FIGURE 11
NOTE − Each air duct opening shall have a free area of at least one square inch (6.4 square centimeters) per 2,000 Btu (586 W) per hour of the total input rating of all equipment in the enclosure. If the equip­ment room is located against an outside wall and the air openings communicate directly with the outdoors, each opening shall have a free area of at least one square inch (6.4 square centimeters) per 4,000 Btu (1172 W) per hour of the total input rating of all other equipment in the enclosure.
OIL
FURNACE
When ducts are used, they shall be of the same cross−sec­tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3" (76 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protective cover­ing is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 per­cent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment opera­tion.
Direct Connection of Outdoor Air for Combustion
The Beckett AFII burner was designed to allow for direct air intake piping (4" [102 mm]). The maximum equivalent length of pipe is 70 feet (21.3 m). A 90_ elbow equals 6feet (1.8 m). The enclosed intake pipe ring may be used to facili­tate direct air intake to the burner through the right side of the cabinet. The AFG burner requires a special kit for direct air intake. Refer to kit instructions.
To convert the AFII burner from confined space to outside combustion air, simply remove the three screws attaching the inlet air scoop to the burner and insert 4" (102 mm) di­rect air intake piping.
The use of a barometric relief placed in the intake pipe is recommended when outdoor combustion air is directly connected to the burner. This will allow confined space air to be used as combustion air in the event that the opening to the outdoor air becomes blocked. Using a barometric re­lief in the intake will reduce the chance of sooting.
Page 10
Page 10
CAUTION
DO NOT USE a barometric draft relief in exhaust vent pipe if outdoor combustion air is connected directly to the burner.
Removal of Unit from Common Venting System
In the event that an existing furnace is removed from a venting system commonly run with separate appliances, the venting system is likely to be too large to properly vent the remaining attached appliances. The following test should be conducted while each appliance is in operation and the other appliances not in operation remain con­nected to the common venting system. If venting system has been installed improperly, the system must be cor­rected as outlined in the previous section.
1 − Seal any unused openings in the common venting
system.
2 − Visually inspect venting system for proper size and
horizontal pitch and determine there is no blockage or restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
3 − Insofar as is practical, close all building doors and win-
dows and all doors between the space in which the ap­pliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliances not con­nected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom ex­hausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace damp­ers.
4 − Following the lighting instruction on the unit, place the
appliance being inspected in operation. Adjust ther­mostat so appliance will operate continuously.
5 − Test for spillage using a draft gauge.
6 − After it has been determined that each appliance re-
maining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other fuel burning appliance to their previous con­dition of use.
7 − If improper venting is observed during any of the
above tests, the common venting system must be cor­rected.
Horizontal Venting
The O23 is approved for horizontal venting with the follow­ing mechanical vent systems: Tjernlund (sideshot) #SS1C (Cat. #35E08) or Field Con­trols #SWG−5 (Cat. #35P08) with the CK−61 (Cat. #18N28) control kit. Refer to the manufacturers’ installation instruc­tions for proper installation procedures and service parts information.
Do not use the same vent with any other appliance when using a sidewall vent system.
Maximum permissible vent length is 70 equivalent feet. Minimum length is 15 equivalent feet. Calculate the equiva­lent vent pipe footage from the furnace to the mechanical vent system (Tjernlund or Field Controls) by adding the straight vent pipe length and the equivalent elbow lengths together.
Locate the barometric draft control within 18 inches of the furnace flue outlet. See figure 12 for barometric draft con­trol location.
HORIZONTAL VENTING
barometric
control*
horizontal venting
control
Figure 12
*Barometric control must
be installed in the hori-
zontal venting system and
located within 18" of flue
outlet of furnace.
Flue Connections
IMPORTANT
When flue pipe is installed at less than minimum clearance listed in table 2, radiation shields must be installed. See figure 13.
Page 11
Page 11
1"
(25 mm)
min
Figure 13
combustible
material
Radiation Shield Installation
O23 unit
(top)
O23 UNIT
(front)
radiation
shields
flue
pipe
unit
cabinet
NOTE 1−Radiation shields must be constructed of 24 gauge sheet metal minimum.
NOTE 2−Radiation shields required when A is less than 9" (229 mm).
NOTE 3−Radiation shields should extend from the top of the unit to the top of the flue pipe.
noncombustible
spacers
radiation shields
(see note 1)
See note 2
See note 3
7"
(178 mm)
min
12"
(305 mm)
min
B
A
A
Use 24 gauge or heavier galvanized smoke pipe and fit­tings to connect the furnace to the vent. Connect flue pipe to chimney using the least number of elbows and angles possible. Flue pipe or vent connector must be inserted into but not beyond the outside wall of the chimney flue. No re­duction in diameter of flue pipe is acceptable. It is best to have flue pipe as short and direct as possible. Where two or more appliances vent into a common flue, the area of the common flue should be at least equal to the area of the larg-
est flue or vent connector, plus 50% of the area of any addi­tional flues or vent connectors. Install a barometric draft control (provided) and flue pipe according to instructions packed with control.
Inspect flue pipe annually. Clean soot or ash from flue pipe, if necessary. If pipe is rusted, replace.
Install draft control at least 12 inches beyond the furnace. If there is no space to install the draft control in the flue pipe it may be installed in the vent above the flue pipe. Follow the instructions packed with the draft control.
Alternate Side Flue Connections
The vent pipe may exit the top or sides of the cabinet. A hole is provided in the top cap for top exit. For side exit, lo­cate the center hole punched in the side of the cabinet. See unit dimensions on page 2. Using it as the center point, cut a 6 inch (152 mm) round hole in the cabinet’s side. Install the barometric draft control within 18 inches of the furnace flue outlet.
Attach the provided finishing plate to cover rough edges.
Supply & Return Air Plenums
Secure return air plenum to unit using sheet metal screws.
NOTE − The following are suggested procedures that should be followed when installing the supply air plenum.
1 − Use sealing strips of fiberglass. 2 − In all cases, the plenum should be secured to furnace
or evaporator cabinet with sheet metal screws.
3 − Install supply and return air ducts as desired.
Oil Supply Line Sizing
Ensure that the restrictions of the piping system, plus any lift involved, do not exceed the capability of the oil pump. Use the following guidelines when determining whether to use a single−or two−stage oil pump.
One−Pipe System
When using a one−pipe system even with the oil tank that is above the burner and a vacuum of 6" (152 mm) Hg or less, a single−stage fuel pump with a supply line and no return line should be adequate. See figure 14.
Page 12
Page 12
Manual bleeding of the fuel pump is required on initial start up. Failure to bleed air from the oil pump could result in an air lock/oil starvation condition.
NOTE − As an extra precaution, cycle heating on and off ten times after bleeding air from the oil pump. This will elimi­nate air in the gun assembly.
Figure 14
Oil Piping
air vent
fill
pipe
Oil
Tank
fuel
pump
Aux
Filter
Shut−off
Valve
8 ft (2.4 m)
Maximum
One Pipe Lift
One-Pipe System
To determine the correct tubing size for piping, refer to table 3 .
Table 3
One−Pipe Oil Line Sizing
Line Length
Pipe Diameter (OD Tubing)
0−50’ (15 m) 3/8" (10 mm)
51−100’ (15 m) 1/2" (12 mm)
Two−Pipe System
When using a two−pipe system with the oil tank below the level of the burner, use a single−stage fuel pump in lift con­ditions of up to 10 feet (3 m) and/or a vacuum of 10" (254 mm) Hg or less. See figure 15. Use a two−stage fuel pump when lift exceeds 10 feet (3 m) and/or a vacuum of 10" (254 mm) Hg to 15" (381 mm) Hg. Both conditions require that you use of a two−pipe system, which consists of a return line that purges the fuel pump of air by returning it to the tank. To determine the run and lift for piping, refer to table 4.
Use continuous lengths of heavy wall copper tubing or steel pipe for oil supply pipe. Install oil supply pipe under floor or near walls to protect it from damage. Avoid running pipes along joists or reverberating surfaces. Always use flare fittings. All fittings must be accessible. Do not use compression fittings.
IMPORTANT
Both oil supply and return pipes must be submerged in oil in the supply tank.
Figure 15
Oil Piping
fuel
pump
Aux
Filter
Return
pipe
Fill
Pipe
Air Vent
Oil
Tank
Inlet
Return
pipe
H
3"−4"
(76 mm −102 mm)
R
outside tank fuel pump above bottom of tank.
Two-Pipe System
Table 4
Two−Pipe Maximum Pipe Length (H + R)
Lift H"
3450 RPM − 3 GPH (11.4 LPH)
3/8" (10 mm) OD
Tubing
1/2" (12 mm) OD
Tubing
Single
Stage
Two
Stage
Single
Stage
Two
Stage
0’
(0.0 m)
84’
(25.6 m)
93’
(28.3 m)
100’
(30.5 m)
100’
(30.5 m)
2’
(0.6 m)
73’
(22.3 m)
85’
(25.9 m)
100’
(30.5 m)
100’
(30.5 m)
4’
(1.2 m)
63’
(19.2 m)
77’
(23.5 m)
100’
(30.5 m)
100’
(30.5 m)
6 ’
(1.8m)
52’
(15.8 m)
69’
(21.0 m)
100’
(30.5 m)
100’
(30.5 m)
8’
(2.4 m)
42’
(12.8 m)
60’
(18.3 m)
100’
(30.5 m)
100’
(30.5 m)
10’
(3.0 m)
31’
(9.4 m)
52’
(15.9 m)
100’
(30.5 m)
100’
(30.5 m)
12’
(3.7 m)
21’
(6.4 m)
44’
(13.4 m)
83’
(25.3 m)
100’
(30.5 m)
14’
(4.3 m)
−−−
36’
(11.0 m)
41’
(12.5 m)
100’
(30.5 m)
16’
(4.9 m)
−−−
27’
(8.2 m)
−−−
100’
(30.5 m)
18’
(5.5 m)
−−− −−− −−−
76’
(23.2 m)
Oil Supply Line & Filter Connections
One−Pipe Systems
CAUTION
Do not install the bypass plug into the pump on one− pipe systems.
The burner is shipped with fuel pump set for one−pipe op­eration. For one−pipe systems, the oil supply pipe is con­nected to the inlet tap on the pump. A one−pipe system should only be used where there is gravity oil flow to the pump and the pipe is not run at any point above the oil level in the tank.
Page 13
Page 13
1 − Connect the inlet pipe to the pump inlet. Start the burn-
er.
2 − Set the primary burner control for continuous opera-
tion during purging.
3 − Turn the bleed valve one turn counterclockwise to
open.
4 − Bleed the unit until all air bubbles disappear.
NOTE − Hurried bleeding will prevent the unit from op­erating properly.
5 − Tighten the bleed valve securely.
Two−Pipe Systems
If the installation requires a two−pipe operation, install the bypass plug included in the bag which is attached to the pump. To convert the pump, install the bypass plug accord­ing to the provided pump instructions. Notice in the two­pipe system the return pipe must terminate in the tank 3" (76 mm) to 4" (102 mm) above the supply inlet. Ensure the return pipe terminates at the correct measurement or air may escape into the system. This could result in loss of prime.
NOTE− If using an outside tank in cold climates a number one fuel or an oil treatment is strongly recommended.
1 − Remove 1/4" plug from return port.
2 − Insert bypass plug and tighten it. See figure 15.
3 − Attach the return and inlet pipes. Start the burner. Air
bleeding is automatic.
NOTE − If a faster bleed is necessary, open the bleed valve.
4 − The return pipe must terminate 3" to 4" above the sup-
ply pipe inlet. See figure 15.
NOTE − If the return pipe does not terminate where it should, air may enter the system, and prime may be lost.
An oil filter is required for all models. Install filter inside the building between the tank shut-off valve and the burner. Locate filter close to burner for easy maintenance. Table 5 lists the filters for the O23 furnace.
Table 5
Installation Clearances inches (mm)
Oil Filters
Cat.
Number
10 micron filter (no mounting bracket) 81P89
10 micron filter (mounting bracket) 53P92
10 micron replacement cartridge for filter, 45 gph 53P93
Filter restriction indicator gauge 53P90
Consult burner manufacturer’s instructions packaged with unit for further details concerning oil supply pipe connec­tions.
Leak Check
After oil piping is completed, carefully check all piping con­nections (factory and field) for oil leaks.
Oil Pipe Heater (Optional)
A heater for the oil pipe is available for applications that are located in cold climates. The heater warms the oil pipe to assist the initial start−up.
Electrical Wiring
All wiring must conform to the National Electric Code (NEC), or Canadian Electric Code (CEC) and any local codes. Refer to figure 16 for the terminal designations on the fan control board.
1 − Refer to the appliance rating plate for proper fuse size.
2 − Install the room thermostat and make wire connections
to the fan control board. Avoid installing thermostat on an outside wall or where it can be affected by radiant heat. Set the adjustable heat anticipator on thermostat according to the wiring diagram sticker provided on unit.
3 − Install a separate fused disconnect switch near unit so
power can be shut off for servicing.
4 − Complete line voltage wiring from disconnect switch
near unit to make-up box.
NOTE − An equipment ground screw is provided. Refer to unit wiring diagram and figures 17 or 18 for O23 se­ries units. Ground unit using a suitable ground wire.
5 − Any accessory rated up to 1 amp can be connected to
the accessory terminal. The accessory terminal is en­ergized when the blower is operating.
IMPORTANT
When an accessory is being used in a continuous fan application which does not include the S68 ON/OFF switch, the accessory must be wired between L1 and N on the fan control board to ensure proper voltage.
Fan Control Board
thermostat
terminal strip
Figure 16
Page 14
Page 14
Figure 17
Typical O23 Wiring Diagram
Page 15
Page 15
Figure 18
Typical O23 Wiring Diagram
Page 16
Page 16
Unit Start−Up & Adjustments
Before starting unit, make sure the oil tank is adequately filled with clean No. 1 or No. 2 furnace oil.
NOTE − Water, rust or other contaminants in oil supply sys­tem will cause malfunction and failure of the internal parts of the fuel pump.
CAUTION
Never burn garbage or paper in the heating system. Never leave papers near or around the unit.
CAUTION
Blower door must be in place before start−up.
1 − Set thermostat for heating demand and turn on electri-
cal supply to unit.
2 − Check initial air adjustment. All units are equipped with
an air adjustment dial on the right side of the burner. See burner parts arrangement illustration.
3 − Turn unit on. Place a can or container under the bleed
port located on the fuel pump. Loosen nut on bleed port to release air and oil mixture from fuel line. Allow mix­ture to escape until a steady stream of oil is emitted from the port. Drain at least 1/2 pint of oil from the pump. Retighten the nut on bleed port. If lockout oc­curs, press reset button and continue with bleed proce­dure.
NOTE − A two−pipe fuel system will normally bleed itself by forcing air back to the tank through the return line. This type of bleeding procedure is not necessary.
4 − If burner fails to start, push reset button on primary
safety control and the burner motor reset button. See part arrangement illustration.
CAUTION
Do not push the reset button on the primary control more than one time.
5 − If the burner fails to light again, refer to the trouble-
shooting section in this manual.
A − Fuel Pump Pressure
Measure fuel pump pressure with unit off. Attach pressure gauge to pump outlet. Turn unit on and check pressure and compare to table 6. Adjust if necessary.
B − Temperature Rise
To measure temperature rise, place plenum thermometers in warm air and return air plenums. Locate thermometer in warm air plenum where thermometer will not see" the heat exchanger to prevent it from picking up radiant heat. Set thermostat to its highest setting to start unit. After plenum thermometers have reached their highest and steadiest
readings, subtract the readings. The difference in tempera­tures in the supply and return air plenums should approxi­mate the temperature rise range listed in table 6 and the ap­pliance rating plate. If not, adjust the blower motor pulley to adjust the blower speed.
Table 6
O23 Unit
nozzle size,
spray angle,
& pattern
pump
PSIG
input
rating
BTU/HR
output
rating
BTU/HR
head temp
rise
−70 .50GPH−80° A 100 70,000 57,000 FB0 60−70
−105 .65GPH−80° B 140 105,000 84,000 FB3 65−75
−120 .75GPH−80° B 140 119,000 105,000 FB3 70−80
−140 .85GPH−80° B 140 140,000 112,000 FB6 65−75
−154 1.0GPH−80° B 140 154,000 125,000 FB6 70−80
C − Limit Control
Limit Control − Do not adjust it from factory setting.
D − Fan Control
The fan on time of 30 seconds is not adjustable. Fan off time (time that the blower operates after the heat demand has been satisfied) can be adjusted by moving the delay switches on the fan control board. Fan off time will affect comfort and is adjustable to satisfy individual applications. See figure 19. Set the heat fan off delay switches to either 60, 90, 120, or 150 seconds. The factory setting is 90 sec­onds.
150 sec
Figure 19
Fan Off Delay Switch Settings
120 sec90 sec60 sec
E − Burner Adjustment
The following instructions are essential to the proper op­eration of O23 series oil furnaces. To prevent sooting, these instructions must be followed in sequence:
1 − Draft
This test should be taken at the breach between the outlet of the vent connector and the barometric draft control. Gen­erally a 1/4" hole will need to be drilled for the draft gauge to be inserted into the vent connector. A minimum of 0.03 draft must be established without the burner in operation. With the burner in operation, the draft should be 0.04 to 0.05. This is VERY critical to the flame retention head burners.
Oil furnace installations also require careful inspection to make sure the chimney is in good shape and can accom­modate the products of combustion. The temperature in the unconditioned space will also affect the draft if long vent connectors are allowed to get too cold.
Page 17
Page 17
2 − Overfire Draft
This test should be taken with the burner in operation. Re­move the screw from the center of the inspection port. In­sert your draft gauge into the hole.
A reading of the overfire draft should be 0.02 less than the reading found in the vent connector. If a positive reading is seen at this point, the combustion fan is pumping too much air into the heat exchanger. Make the necessary adjust­ments at the air adjustment dial.
3 − Smoke Test
The smoke test should be taken at the hole drilled in step 1.
Using a smoke test gun adjust the air inlet shutter so that you will have just a trace of smoke. Somewhere between a 0 and #1 smoke. This is the starting point. Do not stop here.
4 − CO
2
Test
Again, take this sample at the vent pipe. With the unit firing at a trace of smoke, take a sample of the CO
2
.
From the results of this test, a window of operation" will be determined. This window of operation establishes some tolerance. The tolerance the installer builds in provides room within the set-up for those things which might affect combustion. Those things which might affect combustion can then do so without causing the unit to start sooting/ smoking. Things which might affect combustion include a nozzle going bad, draft that changes during different clima­tic conditions, dirty oil, dirt obstructing the air inlet, etc.
To build in a window of operation," set up the burner to be 2% less in CO
2
. For example, if you find a reading of 12%
CO
2
, adjust the air inlet shutter to increase the air and drop
the CO
2
to 10%.
5 − Retest the Smoke
With a drop in the CO
2
and increase in the air you should
see that the smoke has returned to 0.
6 − Retest the Overfire Draft
This test serves to confirm that you have not increased the air too much. Again you do not want a positive pressure at the test port. It should still be 0.02 less than the draft pres­sure reading taken at the breach. You may need to in­crease the stack draft by adjusting the barometric draft control.
7 − Stack Temperature
Take a stack temperature reading in the vent pipe. Subtract the room air temperature from the stack temperature. This will give you the net stack temperature. Use the efficiency charts provided in most CO
2
analyzers to determine fur-
nace efficiency.
Service
CAUTION
Do not tamper with unit controls. Call your qualified service technician.
A − Servicing Filter
NOTE − Under no circumstances should the access panels to the blower compartment be left off or left partially open.
Throw-Away Type Filters  Check filters monthly and re-
place when necessary to assure proper furnace operation. Replace filters with like kind and size filters.
Reusable Type Filters  Filters should be checked month­ly and cleaned when necessary to assure proper furnace operation.
B − Blower
Blower motor is prelubricated and sealed for extended op­eration. No further lubrication is required. Disconnect pow­er to unit before cleaning blower wheel for debris.
C − Flue Pipe Inspection
The flue pipe should be inspected annually by a qualified service technician. Remove and clean any soot or ash found in the flue pipe. Inspect pipe for holes or rusted areas. If replacement is necessary, replace with the same size and type as required by code. Inspect the flue draft control device and replace if found defective.
D − Cleaning the Heat Exchanger
1 − Remove the vent pipe from the furnace.
2 − Remove the locking screws and the caps from the
clean out tubes. Remove flue access elbow.
3 − Using a long spiral wire brush, sweep down the outer
drum of the heat exchanger. Then using the hose at­tachment, vacuum out loose debris.
4 − Remove the locking screw and cap from the observa-
tion tube and with the spiral wire brush, reach upward toward the rear of the heat exchanger to clean out the crossover tube.
CAUTION
Do not attempt to clean the combustion chamber. It can be easily damaged.
5 − Replace the clean out caps and flue access elbow.
Make sure locking screws are secure.
6 − Brush out and vacuum the vent outlet area of the outer
drum and replace vent pipe.
7 − Clean around the burner, blower deck and vestibule
area.
NOTE − A heat exchanger clean-out kit ABRSH380 (35K09) is available from Lennox.
Page 18
Page 18
Troubleshooting
Burner failure or improper operation can result from a num­ber of different causes. Often the cause can be pinpointed by observing the differ­ent types of failure or by the process of elimination. The fol-
lowing troubleshooting charts list some failures, causes and a sequence of steps to isolate the point of failure. Check the simplest and most obvious items before prog­ressing to other items.
Troubleshooting: Fan board operating sequence
Action System Response
Thermostat calls for heat. (W terminal is energized.)
ST9103A closes oil primary control T−T connections.
Ignition system and oil primary control start the furnace. Oil flows as long as oil primary control senses flame.
Burner motor is energized and heat fan on delay timing begins. When timing is complete, the circulating fan is energized at heat speed and warm air is delivered to the controlled space.
Thermostat ends call for heat. (W terminal is de−energized.)
Oil primary control is de−energized, terminating the burner cycle.
Heat fan off delay timing begins. When timing is complete, the circulating fan is de−ener­gized.
ST9103A returns to standby mode (oil primary control and circulating fan are off).
Burner fails to light. Oil primary control locks out within lockout timing (timing depends on oil primary control).
Burner motor is de−energized.
If heat fan has started, it continues through the selected delay off period.
Established flame fails. Burner motor is de−energized and oil primary control goes into recycle mode.
If selected heat fan off delay is longer than the recycle delay timing, the heat fan contin­ues to run through the next trial for ignition.
Thermostat begins call for cool. (G and Y terminals are energized.)
Circulating fan is energized at the cool speed.
Cooling compressor turns on immediately.
Thermostat ends call for cool. (G and Y terminals are de−energized.)
Circulating fan and cooling compressor turn off immediately.
Thermostat begins call for fan. (G terminal is energized.)
Circulating fan is energized immediately at cool speed.
ST9103A may be factory−configured to operate heat speed in this mode.
Thermostat ends call for fan. (G terminal is de−energized.)
Circulating fan is de−energized.
Limit switch string opens. Oil primary control shut off the burner.
Circulating fan is energized immediately at heat speed.
ST9103A opens oil primary control T−T connections.
Circulating fan runs as long as limit string stays open.
If there is a call for cooling or fan, the circulating fan switches from heat speed to cool speed.
Limit switch string closes. ST9103A begins heat fan off delay sequence.
Circulating fan turns off after the selected heat fan off delay timing.
ST9103A closes oil primary control T−T connections.
Oil primary control is energized, initiating burner light off.
Continuous circulating fan is connected. (Optional connectors are available for separate circu­lating fan speed tap.)
Circulating fan is energized at low speed when there is no call for heat, cool or fan.
If fan operation is required by a call for heat, cool, or fan, the ST9103A switches off the continuous fan speed tap before energizing the other fan speed.
Electronic air cleaner is connected. (Optional connectors are available for 120 Vac elec­tronic air cleaner.)
Electronic air cleaner (EAC) connections are energized when the heat or cool speed of the circulating fan is energized. EAC connections are not energized when the optional continuous fan terminal is energized.
Humidity control is connected. (Optional connectors are available for 120 Vac humidi­fier.)
Humidifier connections are energized when the burner motor is energized.
Page 19
Page 19
Troubleshooting: Burner fails to start.
Source Procedure Causes Correction
Thermostat Check thermostat settings.
Thermostat in OFF or COOL Switch to HEAT.
Thermostat is set too low
Turn thermostat to higher tem­perature.
Safety Overloads
Check burner motor, primary safety control, & auxiliary limit switch.
Burner motor overload tripped Push reset button pump motor.
Primary control tripped on safe­ty
Reset primary control.
Auxiliary limit switch tripped on safety
Reset auxiliary limit.
Power
Check furnace disconnect switch & main disconnect.
Open switch Close switch.
Blown fuse or tripped circuit breaker
Replace fuse or reset circuit breaker.
Thermostat
Touch jumper wire across ther­mostat terminals on primary control. If burner starts, then fault is in the thermostat circuit.
Broken or loose thermostat wires
Repair or replace wires.
Loose thermostat screw con­nection
Tighten connection.
Dirty thermostat contacts Clean contacts.
Thermostat not level Level thermostat.
Faulty thermostat Replace thermostat.
CAD Cell
Disconnect the flame detector wires at the primary control. If the burner starts, fault is in the detector circuit.
Flame detector leads are shorted
Separate leads.
Flame detector exposed to light Seal off false source of light.
short circuit in the flame detec­tor
Replace detector.
Primary Control
Place trouble light between the black and white leads. No light indicates that no power is going to the control.
Primary or auxiliary control switch is open
Check adjustment. Set the maximum setting.
Jumper terminals; if burner starts, switch is faulty, replace control.
Open circuit between discon­nect switch and limit control
Trace wiring and repair or re­place it.
Low line voltage or power fail­ure
Call the power company.
Place trouble light between the orange and white leads. No light indicates faulty control.
Defective internal control circuit Replace the control.
Burner
Place the trouble light between the black and white leads to the burner motor. No light indicates that no power is getting to the motor.
Blown fuse Replace the fuse.
Place trouble light between the black and white leads to the blower motor. Light indicates power to the motor and burner fault.
Binding burner blower wheel
Turn off power and rotate the blower wheel by hand. If seized, free the wheel or replace the fuel pump.
Sized fuel pump
Defective burner motor Replace the motor.
Page 20
Page 20
Troubleshooting: Burner starts, but no flame is established.
Source Procedure Causes Correction
Oil Supply
Check tank gauge or use dip stick.
No oil in tank Fill tank.
Coat dip stick with litmus paste and insert into bottom of tank.
Water in oil tank
If water depth exceeds 1 inch, pump or drain water.
Listen for pump whine. Tank shut−off valve closed Open valve.
Oil Filters & Oil Line
Listen for pump whine.
Oil line filter is plugged Replace filter cartridges.
Kinks or restriction in oil line Repair or replace oil line.
Plugged fuel pump strainer Clean strainer or replace pump.
Open bleed valve or gauge port. Start the burner. No oil or milky oil indicates loss or prime.
Air leak in oil supply line
Locate and correct leak.
Tighten all connections.
Oil Pump
Install pressure gauge on pump and read pressure. Should not be less than 140 psi.
Pump is partially or completely frozen. No pressure and the motor locks out on overload.
Replace pump.
Coupling disengaged or broken
− no pressure
Re−engage or replace coupling.
Fuel pressure too low Adjust to 100 psi.
Nozzle
Disconnect ignition leads. Ob­serve the oil spray (gun assem­bly must be removed from unit). Inspect the nozzle for plugged orifice or carbon build−up around orifice.
Nozzle orifice plugged
Replace nozzle with the same size, spray angle, and spray type.
Nozzle strainer plugged
Poor or off center spray
Ignition Electrodes
Remove gun assembly and in­spect electrodes and leads.
Fouled or shorted electrodes
Clean electrode leads.
Dirty electrodes and leads
Eroded electrode tips
Clean electrode tips and reset the gap to 5/32 inches and cor­rectly position tips.
Improper electrode gap spacing
Improper position of electrode tips
Bad buss bar connection Retension and realign.
Cracked or chipped insulators Replace electrode.
Cracked or burned lead insula­tors
Replace electrode leads.
Ignition
Transformer
Connect ignition leads to the transformer. Start burner and observe spark. Check line volt­age to transformer primary.
Low line voltage
Check voltage at power source. Correct cause of voltage drop or call the power company.
Burned out transformer wind­ings.
Replace the transformer.
No spark or weak spark
Properly ground the transformer case.
Burner Motor
Motor does not come up to speed and trips out on overload. Turn off power and rotate blower wheel by hand to check for bind­ing or excessive drag.
Low line voltage
Check voltage at power source. Correct cause of voltage drop or the call power company.
Pump or blower overloading motor
Correct cause of overloading.
Faulty motor Replace motor.
Page 21
Page 21
Troubleshooting: Burner starts and fires, but lock out on safety.
Source Procedure Causes Correction
Poor Fire
After burner fires, immedi­ately jumper across flame detector termi­nals at the pri­mary control.
If burner con­tinues to run, this may be due to poor fire. Inspect fire.
Unbalanced fire Replace nozzle
Too much air − −lean short fire
Reduce combustion air − check combustion.
Too little air − − long dirty fire
Increase combustion air − check combustion.
Excessive draft
Adjust barometric damper for correct draft.
Too little draft or restriction
Correct draft or remove restric­tion.
Flame Detector
If fire is good, fault is in the flame detector. Check detec­tor circuit.
Dirty cad cell face Clean cad cell face.
Faulty cad cell − exceeds 15000 hms
Replace cad cell.
Loose or defective cad cell wires
Secure connections or replace cad cell holder and wire leads.
Primary Control
If burner locks out on safety, fault is in the primary con­trol.
Primary control circuit defective Replace primary control.
Troubleshooting: Burner Starts and Fires, but Loses Flame and Lock Out on Safety
Source Procedure Causes Correction
Poor Fire
After burner fires, immedi­ately jumper across flame detector termi­nals at the pri­mary control.
If burner con­tinues to run (does not lock out of safety), fault may be due to poor fire. Inspect fire.
Unbalanced fire Replace nozzle
Too much air − − lean short fire
Reduce combustion air − check combustion.
Too little air − − long dirty fire
Increase combustion air − check combustion.
Excessive draft
Adjust barometric damper for correct draft.
Too little draft or restriction
Correct draft or remove restric­tion.
Flame Detector
If fire is good, fault is in the flame detector. Check detec­tor circuit.
Dirty CAD cell face Clean CAD cell face.
Faulty CAD cell − − exceeds 15000 hms
Replace CAD cell.
Loose or defective cad cell wires
Secure connections or replace cad cell holder and wire leads.
If burner loses flame (does not lock out on safety), fault is in the fuel sys­tem.
Pump loses prime − air slug Prime pump at bleed port
Oil Supply
Pump loses prime − air leak in supply line
Check supply line for loose con­nections and tighten fittings.
Water slug in line Check oil tank for water (over 1
inch) pump or drain out water.
Partially plugged nozzle or nozzle strainer
Replace nozzle.
Listen for pump whine
Restriction in oil line Clear restriction.
Plugged fuel pump strainer Clean strainer or replace pump.
Cold oil − outdoor tank Change to number 1 oil.
Page 22
Page 22
Troubleshooting: Burner starts and fires, but short cycles (too little heat)
Source Procedure Causes Correction
Thermostat Check thermostat.
Heat anticipator set too low Correct heat anticipator setting.
Vibration at thermostat Correct source of vibration.
Thermostat in the path of a warm air draft
Shield thermostat from draft or relocate.
Limit Control
Connect voltmeter between line voltage connections to primary control (black & white leads). If burner cycles due to power inter­ruption, it is cycling on limit.
Dirty furnace air filters Clean or replace filter.
Burner running too slow
Increase blower speed to main­tain proper temp. rise.
Blower motor seized or burned out
Replace motor.
Blower bearings seized Replace bearings and shaft.
Blower wheel dirty Clean blower wheel.
Blower wheel in backward Reverse blower wheel.
Wrong motor rotation
Replace with properly rotating wheel.
Restrictions in return or supply air system
Correct cause of restriction.
Adjustable limit control set too low
Reset limit to maximum stop setting.
Power
If voltage fluctuates, fault is in the power source. Recheck voltage at the power source.
Loose wiring connection Locate and secure connection.
Low or fluctuating line voltage Call power company.
Troubleshooting: Burner runs continuously (too much heat).
Source Procedure Causes Correction
Thermostat
Disconnect thermostat wires at the pri­mary control.
If burner turns off, fault is in the thermostat circuit.
Shorted or welded thermostat contacts
Repair or replace the thermo­stat.
Stuck thermostat bimetal
Clear obstruction or replace thermostat.
Thermostat not level Level thermostat.
Shorted thermostat wires Repair short or replace wires.
Thermostat out of calibration Replace thermostat.
Thermostat in cold draft
Correct draft or relocate the thermostat.
Primary control
If burner does not turn off, fault is in the primary control.
Defective primary control
Replace the defective primary control.
Page 23
Page 23
Troubleshooting: Burner runs continuously (too little heat).
Source Procedure Causes Correction
Combustion
Check burner combustion for CO2, stack tem­perature, and smoke
Low CO
2
less
than 10%.
Too much combustion air Reduce combustion air.
Air leaks into heat exchanger around inspection door, etc.
Correct cause of air leak.
Excessive draft
Adjust barometric draft con­trol for correct draft.
Incorrect burner head adjust­ment
Correct burner head setting.
High smoke reading more than a trace.
Dirty or plugged heat exchanger
Clean heat exchanger.
Readjust burner.
Insufficient draft Increase draft.
Incorrect burner head adjust­ment
Correct burner setting.
Too little combustion air Increase combustion air.
High stack tem­perature is more than 550
_F Net.
Too little blower air
Increase blower speed to maintain proper temp. rise.
Blower belt too loose (if equipped)
Tighten blower belt.
Dirty or plugged heat exchanger Clean heat exchanger.
Dirty blower wheel Clean blower wheel.
Dirty furnace air filters Clean or replace filter.
Restricted or closed registers or dampers
Readjust registers or damp­ers.
Oil Pressure
Inspect fire and check
oil pressure.
Partially plugged or defective nozzle
Replace nozzle.
Oil pressure is too low: less than 100 psi.
Increase oil pressure top 100psi.
Loading...