Lennox O23Q2-70, O23Q3-70, O23Q2-90, O23Q3-90, O23Q3-105 Installation Instructions Manual

...
504,626M
*P504626M*
03/10
*2P0310*
Page 1
E 2002 Lennox Industries Inc.
Dallas, Texas, USA
FOR FUTURE REFERENCE
WARNING
Do not store or use gasoline or other flammable va­pors and liquids in the vicinity of this or any other ap­pliance.
WARNING
Improper installation, adjustment, alteration, ser­vice, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information, consult a licensed profes­sional installer, or equivalent, or service agency.
INSTALLATION INSTRUCTIONS
O23 SERIES UNITS
OIL UNITS
504,626M 38152A059 03/2010
Supersedes 01/2004
Table of Contents
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping & Packing 1. . . . . . . . . . . . . . . . . . . . . . . . . .
O23 Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . .
O23 Start−Up & Performance Check List 2. . . . . . . .
O23 Unit Parts Arrangement 3. . . . . . . . . . . . . . . . . . . . .
O23 Oil Burner Parts Arrangement 3. . . . . . . . . . . . . . . .
Requirements 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Locate & Level the Unit 5. . . . . . . . . . . . . . . . . . . . . . .
Unit Adjustments 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Venting 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Flue Connections 10. . . . . . . . . . . . . . . . . . . . . . . . . . .
Supply & Return Air Plenums 11. . . . . . . . . . . . . . . . .
Oil Supply Line & Filter Connections 12. . . . . . . . . . .
Leak Check 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Wiring 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Start-Up & Adjustments 16. . . . . . . . . . . . . . . . . .
Service 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CAUTION
When venting this appliance, keep vent terminal free of snow, ice and debris.
General
These instructions are intended as a general guide and do not supersede local codes in any way. Only licensed pro­fessional technicians, or equivalent, can install and service the Lennox Elite
®
Series O23 oil furnaces. In Canada, refer to CSA B139 for recommended installation procedures. Consult authorities who have jurisdiction before installa­tion.
CAUTION
Never burn garbage or paper in the heating system. Never leave papers near or around the unit.
Shipping & Packing List
1− Assembled oil furnace 1− Barometric draft control 1− Side exhaust pipe collar 1− Direct intake collar (AFII burner units only) Check the components for shipping damage. If you find
any damage, immediately contact the last carrier.
Litho U.S.A.
Page 2
O23 Unit Dimensions − Inches (mm)
SUPPLY
AIR
OPENING
FLUE
CONNECTION
(On Heat
Exchanger)
AIR FLOW
ELECTRICAL INLET
(Right Side Only)
OIL PIPING INLET
(Left Side Only)
RETURN AIR
OPENING
(Either Side)
TOP VIEW
SIDE VIEW FRONT VIEW
22
(559)
14
(356)
2 (51)
1-1/2
(38)
23-1/2
(597)
54
(1372)
1-1/2
(38)
3/4
(19)
AB
C
D
3/4
(19)
22
(559)
RETURN AIR
E
RETURN AIR
1-1/4
(32)
TOP FLUE
OUTLET
SIDE
FLUE OUTLET
CENTERING HOLE
(Field Fabricate
Either Side)
OPT. OUTDOOR
COMBUSTION
AIR INLET
CENTERING HOLE
(Field Fabricate
Right Side only)
Model No. A B C D E
O23Q2/3-70/90 O23Q3/4-105/120
in. 19-1/2 30-5/8 18 19-5/8 16
mm 495 778 457 498 406
O23Q5-140/154
in. 22-1/2 33-1/8 21 22-1/8 18
mm 572 841 533 562 457
O23 Start−Up & Performance Check List
Filter Clean & Secure?
Supply Voltage
Electrical Connections Tight?
Job Name
Job Location Installer Unit Model No.
Oil Pump Pressure [recommended min. 100 psig for −70;
min. 140 psig for all other units )]
Job No.
City
City
Serial No.
Date
State
Serviceman
Draft Reading (recommended .03−.04 inches w.c.)
Flue Connections Tight?
HEATING SECTION
THERMOSTAT
Calibrated? Heat Anticipator Properly Set? Level?
Blower Motor Amps
Blower Motor H.P.
Blower Motor Lubrication O.K.?
Piping Connections Tight?
Vent Clear?
State
Temperature RiseFan Control Cutout
Fan Control Setting (maximum 130_ F)
Burner Model No.
Serial Number
All Valves Open?
PROPER DRAFT
% CO2 (recommended 12%)
(55_C)
Page 3
O23 Unit Parts Arrangement
Figure 1
clean-out port
limit switch
control box
with fan control board
Beckettr
AFII burner
indoor blower
capacitor
blower motor
observation
port
clean−out port
flue opening
heat exchanger
combustion air intake
O23 Oil Burner Parts Arrangement
Figure 2
FB−HEAD
HEAD
INSULATOR
CLIP
RETAINING
1/4" HEX
HEAD SCREW
FB HEADS
ASSY FOR
AIR TUBE
ASSY.
ELECTRODE HEAD
NOZZLE LINE
PEDESTAL
ADAPTER
NOZZLE
AIR SCOOP
INLET
WHEEL
BLOWER
FLANGE
GASKET
MOTOR
4X4
BOX
IGNITOR
DOOR GASKET
REAR ACCESS
COUPLING
FUEL PUMP
PLATE
ESCUTCHEON
NUT
SPLINED
DOOR ASSY
REAR ACCESS
ASSY
HOUSING
MAIN
SCREWS
AIR TUBE
FLANGE
ASSY
ELECTRODE
6
5
4
3
7
0
8
ELECTRONIC IGNITION
TRANSFORMER
PRIMARY
CONTROL
AIR ADJ. DIAL
CONNECTOR
TUBE
PREMOUNTED OIL−DELAY VALVE
Page 4
Requirements
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc.
P.O. Box 799900 Dallas, TX 75379−9900
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a qualified installer or service agency.
Installation of Lennox oil−fired furnaces must conform with the National Fire Protection Association Standard for the Installation of Oil Burning Equipment, NFPA No. 31, the National Electrical Code, ANSI/NFPA No.70 (in the U.S.A.), CSA Standard CAN/CSA−B139 (in Canada), Installation Code for Oil Burning Equipment, the Canadian Electrical Code Part1, CSA 22.1 (Canada), the recommen­dations of the National Environmental Systems Contrac­tors Association and any state or provincial laws or local or­dinances. Authorities having jurisdiction should be consulted before installation. Such applicable regulations or requirements take precedence over general instructions in this manual.
Chimneys and chimney connectors must be of the type and construction outlined in section 160 of NFPA No. 31.
Air for combustion and ventilation must conform to stan­dards outlined in section 140 of NFPA No. 31 or, in Canada, CSA Standard B139. When installing O23 units in confined spaces such as utility rooms, two combustion air openings are required. Dimensions of combustion air openings are shown in table 1. One opening shall be below burner level and the other opening shall be no more than 6"(152 mm) from the room’s ceiling.
IMPORTANT
An opening to the outside for combustion air is strongly recommended, especially in new homes. Refer to table 2 or the unit rating plate for specific combustion air opening dimensions.
The combustion air opening should provide a minimum free area one-half square inch per 1,000 Btu per hour input. This combustion air should be brought into the area con­taining the furnace below the level of the furnace burner.
Table 1
Combustion Air Opening Dimensions
Model No.
Combustion Air Opening
Dimensions (2 required)
O23−70/105/120 10" X 20" (254 mm X 508 mm)
O23−140/154 11" X 22" (279 mm X 559 mm)
This unit is approved for use on combustible flooring and for clearances to combustible material as listed on unit rat­ing plate and in table 2. Unit service and accessibility clear­ances take precedence over fire protection clearances.
Table 2
Installation Clearances inches (mm)
Clearances
70/105/120 140/154
top of plenum and duct 2 (51) 2 (51)
plenum sides 3 (76) 3 (76)
sides 0 (0) 0 (0)
rear 0 (0) 0 (0)
front 4 (120) 4 (120)
flue pipe measured from
above
6 (152) 6 (152)
flue pipe measured vertical 6 (152) 6 (152)
NOTE − Service access clearance must be maintained.
*Minimum clearance shown for flue pipe may be reduced by using special protection as provided by local building codes and the National Fire Protection Association Standards.
Unit must be adjusted to obtain a temperature rise in the range listed in table 6 in the Start-Up section of this manual.
When installed, furnace must be electrically grounded in accordance with local codes or, in the absence of local codes, with the current National Electric Code, ANSI/NFPA No. 70, or Canadian Electric Code (CEC) if an external electrical source is utilized.
Field wiring connection with unit must meet or exceed specifications of type T wire and withstand a 63_F (17_C) temperature rise.
Page 5
When furnace is used in conjunction with cooling units, it shall be installed in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating element. With a parallel flow arrangement, a damper (or other means to control the flow of air) shall be adequate to pre­vent chilled air from entering the furnace and, if manually operated, must be equipped with means to prevent opera­tion of either unit, unless damper is in the full heat" or cool" position.
Locate & Level the Unit
1 − Set the unit in desired location keeping in mind the
clearances listed in table 2. Also keep in mind oil sup­ply connections, electrical supply, flue connections and sufficient clearance for installing and servicing unit.
2 − Level the unit from side to side and from front to rear. If
the furnace is not level, place fireproof wedges or shims between the low side of the furnace and the floor. Make sure the weight of the furnace is distributed evenly on all four corners. Strain on sides of cabinet causing cracking and popping noises may occur if weight of furnace is not evenly distributed.
Unit Adjustments
Neither the nozzle setting nor the air adjustments are facto­ry set. The furnace is fire tested and the limit control is checked to make sure it functions properly; no factory set­tings are made. During installation, the furnace must be set up." The installing dealer/contractor must have and use proper test equipment in order to correctly set up the oil furnace. Proper testing equipment is required to ensure correct operation of the unit. The use of test equipment is now more critical than ever due to tighter tolerances need­ed to keep the furnace operating efficiently. Among the test equipment for an oil furnace, the proper combustion test kit should contain the following:
D Draft gauge D CO
2
or O2 analyzer
D Smoke tester D Pressure gauge D High temperature thermometer D Beckett T−500 gauge D Oil vacuum gauge D Knowledge of proper test equipment operation
CAUTION
Improper nozzle and/or air adjustment of this unit may result in sooting problems. Refer to the follow­ing section for correct adjustment procedures.
Adjusting the Nozzle
Proper adjustment of the nozzle assembly is critical be­cause alignment may have changed during shipping. Be­fore the furnace and oil lines are installed, the nozzle as­sembly must be checked. To check the nozzle assembly, remove the entire burner assembly (not just the nozzle) from the furnace. The lower firing nozzle is factory installed. This should be verified by the installer. Inspect the spark transformer leads also to ensure they are still at­tached to the electrodes.
The burner assembly is attached to the vestibule panel by three nuts. Slots are provided in the mounting flange for re­moving the burner assembly from the vestibule. By loosen­ing the nuts and by turning the whole burner assembly counterclockwise (figure 3), the entire burner assembly will come out of the furnace. There is adequate wire to remove the burner without disconnecting wires. Once removed, turn the burner around in the vest panel area.
Figure 3
O23 Series Burner Removal
Loosen three nuts which at-
tach burner to vest panel.
Rotate burner counterclockwise on
slots then pull toward you.
To correctly adjust the nozzle, use a Beckett #T−500 gauge
Insert the small end of the gauge into the end of the cone and measure from the flat of the end cone to the tip of the nozzle. When nozzle depth is correct, the tip of the nozzle should just touch the end of the gauge. Refer to the illustra­tion sheet provided with the gauge. Note that the scale side of the gauge is not used for this purpose. Make corrections by sliding the nozzle assembly forward or backward within the blast tube (figure 4). At the same time, check the nozzle alignment.
Page 6
To check nozzle alignment, again insert the small end into the end cone and measure the nozzle and electrode align­ment against the center lines marked on the gauge (again refer to enclosed illustration sheet). If the nozzle is not cen­tered, but found to be too far left or right, a new nozzle as­sembly will need to be ordered. Do not attempt to adjust by bending the 90 degree elbow in the oil line.
Figure 4
Beckett Oil Burner Nozzle Adjustment
TO ADJUST NOZZLE:
Burner must be removed from
furnace for this procedure.
GAUGE
1−Loosen screw. 2−Slide entire nozzle/electrode assembly back and forth until nozzle just touches gauge.
1
2
Venting
WARNING
Combustion air openings in front of the furnace must be kept free of obstructions. Any obstruction will cause improper burner operation and may result in a fire hazard.
WARNING
The barometric damper shall be in the same atmo­spheric pressure zone as the combustion air inlet to the furnace. Deviation from this practice will cause improper burner operation and may result in a fire hazard.
CAUTION
Do not store combustible materials near the furnace or supply air ducts. The material (such as paint, mo­tor oil, gasoline, paint thinner, etc.) may ignite by spontaneous combustion creating a fire hazard.
WARNING
This furnace is certified for use with type L" vent. B" vent must not be used with oil furnaces.
NOTE − Oil burning equipment may be vented into an ap­proved masonry chimney or type L vent. (Type L vent is similar in construction to type B gas vent except it carries a
higher temperature rating and is constructed with an inner liner of stainless steel rather than aluminum).
Prior to installation of unit, make a thorough inspection of the chimney to determine whether repairs are necessary. Make sure the chimney is properly constructed and sized according to the requirements of the National Fire Protec­tion Association. The smallest dimensions of the chimney should be at least equal to the diameter of the furnace vent connector. Make sure the chimney will produce a steady draft sufficient to remove all the products of combustion from the furnace. A draft of at least .04" w.c. (9.9 Pa) is re­quired during burner operation.
1 − Local building codes may have more stringent installa-
tion requirements and should be consulted before installation of unit.
2 − The vent connector should be as short as possible to
do the job.
3 − The vent connector should not be smaller than the out-
let diameter of the vent outlet of the furnace.
4 − Pipe should be at least 24 gauge galvanized.
5 − Single wall vent pipe should not run outside or through
any unconditioned space.
6 − Chimney should extend 3 feet (0.9 m) above highest
point where the vent passes through the roof, and 2 feet (0.6 m) higher than any portion of a building within a horizontal distance of 10 feet (3 m).
7 − The vent must not pass through a floor or ceiling.
Clearances to single wall vent pipe should be no less than 6" (152 mm); more if local codes require it.
8 − The vent may pass through a wall where provisions
have been made for a thimble as specified in the Stan­dards of the National Board of Fire Underwriters. See figure 5.
WALL THIMBLE
FIGURE 5
THIMBLE
VENT PIPE
COMBUSTIBLE
WALL
9 − The vent pipe should slope upward toward the chim-
ney on horizontal run at least 1/4 inch (6 mm) to the foot (0.3 m) and should be supported by something other than the furnace, such as isolation hangers. See figure 6.
Page 7
MASONRY CHIMNEY
BAROMETRIC
CONTROL* (IN EITHER
LOCATION)
CLEAN OUT
CLEAN OUT
LINER
MASON-
RY
CHIMNEY
Figure 6
*Barometric control may be installed in either vertical or hori­zontal section of flue pipe within 18" of flue outlet of furnace.
10− Extend the vent pipe into the chimney so that it is flush
with the inside of the vent liner. Seal the joint between the pipe and the liner.
11− The furnace shall be connected to a factory built chim-
ney or vent complying with a recognized standard, or masonry or concrete chimney lined with a lining mate­rial acceptable to the authority having jurisdiction.
12− When two or more appliances vent into a common
vent, the area of the common vent should not be less than the area of the largest vent or vent connection plus 50% of the area of the additional vent or vent con­nection. Chimney must be able to sufficiently vent all appliances operating at the same time.
13− The vent pipe shall not be connected to a chimney
vent serving a solid fuel appliance or any mechanical draft system.
14− All unused chimney openings should be closed.
15− All vent pipe run through unconditioned areas or out-
side shall be constructed of factory built chimney sec­tions. See figure 7.
16− Where condensation of vent gas is apparent, the vent
should be repaired or replaced. Accumulation of con­densation in the vent is unacceptable.
17− Vent connectors serving this appliance shall not be
connected into any portion of mechanical draft sys­tems operating under positive pressure.
18− Keep the area around the vent terminal free of snow,
ice and debris.
NOTE − If vent pipe needs to exit from side of cabinet, use the pilot hole (located on either side of the unit) to cut a 6" (152 mm) round hole. Attach finishing plate (provided) with four sheet metal screws to cover rough edges.
FACTORY−BUILT CHIMNEY
BAROMETRIC
CONTROL* (IN EITHER
LOCATION)
DRAIN FOR
CONDENSATE
FACTORY
BUILT
CHIMNEY
Figure 7
*Barometric control may be installed in either vertical or hori­zontal section of flue pipe within 18" of flue outlet of furnace.
Combustion and Ventilation Air (Confined and Unconfined Spaces)
In the past, there was no problem in bringing in sufficient amounts of outdoor air for combustion − infiltration provided all the air that was needed and then some. In today’s homes built with energy conservation in mind, tight construction practices make it necessary to bring in air from outside for combustion. Consideration must also be given to the use of exhaust fans, appliance vents, chim­neys and fireplaces because they force additional air that could be used for combustion out of the house. Unless out­side air is brought into the home for combustion, negative pressure (pressure outside is greater than inside pressure) will build to the point that a down draft can occur in the fur­nace vent pipe or chimney. Combustion gases enter the liv­ing space creating a potentially dangerous situation.
The importance of the previous paragraph cannot be over­stated. Users may inadvertently block fresh air intakes af­ter installation.
In the absence of local codes concerning air for combus­tion and ventilation, the following section outlines guide­lines and recommends procedures for operating oil fur­naces in a manner that ensures efficient and safe operation. Special consideration must be given to combus­tion air needs as well as requirements for exhaust vents and oil piping.
Loading...
+ 16 hidden pages