Lennox MWHA018S4-1P, MWHA009S4-1L, MWHA024S4-1P, MWHA012S4-1L, MHA009S4S-1P Installation Instructions Manual

...
Page 1
INSTALLATION
©
2019 Lennox Industries Inc.
Dallas, Texas, USA
Table of Contents
General ...........................................................................1
Use of Mini-Split System During Construction................1
Included Parts.................................................................2
Catalog Numbers............................................................2
Model Number Identication ...........................................3
Typical System Components ..........................................4
System Dimensions ........................................................4
Outdoor Units ..............................................................4
Indoor Units .................................................................5
Indoor Unit Wall Mounts ..............................................5
System Clearances ........................................................5
Outdoor Unit ................................................................5
Indoor Unit ...................................................................6
Multiple Outdoor Units .................................................6
Torque Requirements for Caps and Fasteners...............7
Indoor Unit Installation ....................................................7
Unit Placement Considerations ...................................7
Determining Wall Mounting Plate Location ..................7
Installation of Wall Mounting Plate...............................7
Installation of Wall Sleeve............................................8
Installation of Indoor Unit on Wall Mounting Plate .......8
Indoor Unit Condensate Piping Connections ...............8
Outdoor Unit Installation .................................................9
Placement Considerations ...........................................9
Direct Sunlight, Rain and Ice Protection ......................9
Condensate Piping ....................................................10
Buried Refrigerant Pipe Protection ............................10
Securing the Outdoor Unit .........................................11
Refrigerant Piping Connections ....................................11
Adding Refrigerant for Longer Line Set ........................13
Leak Test and Evacuation ............................................13
Leak Test ...................................................................13
Triple Evacuation Procedure......................................13
Wiring Connections ......................................................14
Outdoor Unit .............................................................14
Indoor Unit .................................................................14
Wiring Diagrams ........................................................16
Unit Start-Up .................................................................18
Troubleshooting ............................................................18
Test Run .......................................................................19
Pre-Checks ................................................................19
Procedure ..................................................................19
Test Run Checklist ........................................................19
Double-Check Line Set Connections............................19
Ambient Temperature is Below 63ºF (17ºC) .................19
INSTRUCTIONS
MHA Series Units
SINGLE-ZONE MINI-SPLIT SYSTEM (115V and 208/230V) 507927-01 6/2019 Supersedes 3/2019
THIS MANUAL MUST BE LEFT WITH THE OWNER
FOR FUTURE REFERENCE
WARNING
Improper installation, adjustment, alteration, ser vice or maintenance can cause property damage, personal injury or loss of life.
Installation and service must be performed by a li­censed professional HVAC installer (or equivalent) or a service agency.
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
General
Refer to the Product Specications bulletin (EHB) for more
product information. These instructions are intended as a general guide and do not supersede local or national codes in any way. Authorities having jurisdiction should be consulted before installation.
This wall-mounted indoor unit is matched with an outdoor heat pump unit to create a mini-split system that uses HFC-410A refrigerant.
Use of Mini-Split System During Construction
Lennox does not recommend the use of its mini-split systems during any phase of construction. Very low return air temperatures, harmful vapors and operation of the unit
with clogged or misplaced lters will damage the system.
However, mini-split systems may be used for cooling of buildings under construction, if the following conditions are met:
Air lter must be installed in the system and must be maintained during construction.
Air lter must be replaced upon construction comple­tion.
• The indoor wall unit assembly must be thoroughly
cleaned following nal construction clean-up.
All mini-split operating conditions must be veried ac- cording to these installation instructions.
Page 2
Included Parts
The assembled indoor unit will include the following items:
Table 1. Included Parts
Parts Figure Quantity Parts Figure Quantity
ON/OFF
SILENCE
Wireless controller
FP
TIMER
MODE
ON
TEMP
TIMER
FAN
OFF
SLEEP
SWING DIRECT
LED FOLLOW
TURBO SEL F
ME
CLEAN
1
Installation instruction,
user guide and warranty
1 ea.
Wireless control holder with 2 mounting screws
Batteries (AAA) 2
1
Mounting plate
(shipped attached to the
back of the indoor unit)
Mounting plate securing
screws
Return Air Filters
(Shipped installed in
Plastic screw anchors 5
indoor unit.)
Catalog Numbers
Table 2. Component Catalog Number Cross-Reference
Product Capacity Voltage Lennox Model Number
Wall Mounted (Indoor Unit) 9K 115V MWHA009S4-1L 17K07
Wall Mounted (Indoor Unit) 12K 115V MWHA012S4-1L 17K09
1
5
Catalog
Numbers
Wall Mounted (Indoor Unit) 9K 208-230V MWHA009S4-1P 17K08
Wall Mounted (Indoor Unit) 12K 208-230V MWHA012S4-1P 17K10
Wall Mounted (Indoor Unit) 18K 208-230V MWHA018S4-1P 17K11
Wall Mounted (Indoor Unit) 24K 208-230V MWHA024S4-1P 17K12
Heat Pump (Outdoor Unit) 9K 115V MHA009S4S-1L 17K01
Heat Pump (Outdoor Unit) 12K 115V MHA012S4S-1L 17K03
Heat Pump (Outdoor Unit) 9K 208-230V MHA009S4S-1P 17K02
Heat Pump (Outdoor Unit) 12K 208-230V MHA012S4S-1P 17K04
Heat Pump (Outdoor Unit) 18K 208-230V MHA018S4S-1P 17K05
Heat Pump (Outdoor Unit) 24K 208-230V MHA024S4S-1P 17K06
2
Page 3
WARNING
The clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs, and HFCs) as of July, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for non-compliance.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
Model Number Identication
OUTDOOR SINGLE ZONE HEAT PUMP UNITS
M H A 009 S 4 S - 1 P
IMPORTANT
All illustrations in this instruction are typical and do not always represent the exact appearance of the equipment.
IMPORTANT
The compressor in this unit contains PVE oil (Polyvinylether). PVE oil is formulated for hydrouorocarbon (HFC) refrigerants, such as HFC-
410A, which this system contains. While it may have some miscibility properties with mineral-based oil and
POE oil (Polyolester), it is not recommended to mix PVE
oil with any other type of refrigerant oil.
Series Type
M = Mini-Split
Unit Type
H = Heat Pump
Major Design Sequence
A = First Generation
Nominal Cooling Capacity
009 = 0.75 ton
018 = 1.5 tons
024 = 2 tons
WALL-MOUNTED INDOOR UNITS
Series Type
M = Mini-Split
Unit Type
WH = Wall-Mounted Non-Ducted Unit
012 = 1 ton
Voltage
L = 115V-1 phase-60Hz P = 208/230V-1 phase-60Hz
Minor Design Sequence
1 = 1st Revision
Refrigerant Circuits
S = Single Circuit
Refrigerant Type
4 = HFC-410A
Cooling Efciency
S = Standard Efciency
M WH A 009 S 4 - 1 P
Voltage
L = 115V-1 phase-60Hz P = 208/230V-1 phase-60Hz
Minor Design Sequence
1 = 1st Revision
Major Design Sequence
A = First Generation
Nominal Cooling Capacity
009 = 0.75 ton
012 = 1 ton
018 = 1.5 tons
024 = 2 tons
Refrigerant Type
4 = HFC-410A
Cooling Efciency
S = Standard Efciency
3
Page 4
Typical System Components
1
2
3
4
6
7
8
9
10
5
Wall Mounting Plate
Refrigerant Piping
Signal Cable
Wireless Remote Control
Condensate Line
Louver
Wireless Remote Control Holder
Return Air Filters (2)
Front Panel
Outdoor Unit Power Cable
1
2
3
4 5
6
7 8
9
10
ON/OFF
TEMP
FP
TIMER ON
TIMER OFF
MODE
FAN/SLC
SLEEP
SWING
DIRECT
TURBO
CLEAN
LED
FOLLOW
19-1/8 (486)
2-3/4
(70)
11-7/8 (302)
21-7/8
(556)
30-3/8 (772)
30-5/8 (778)
2-1/2
(64)
1/2 (13)
1/2
(13)
MHA009S4S
BOTTOM VIEW
FRONT VIEWSIDE VIEW
SIDE VIEW
12-5/8
(322)
11-1/4
(286)
2-3/8 (60)
3-5/8 (92)
DRAIN HOLE (bottom of unit)
11-3/4
(298)
BOTTOM VIEW
FRONT VIEW
SIDE VIEW
SIDE VIEW
MHA012S4S, MHA018S4S
2-3/8 (60)
3/4
(19)
14-3/8
(365)
12-1/4
(311)
13-3/8
(340)
2-3/8 (60)
3-3/8 (86)
21-7/8
(556)
1/2
(13)
20-1/4 (514)
31-1/2 (800)
31-1/2 (815)
13-1/8 (333)
2-3/4
(70)
MHA024S4S
27-5/8
(702)
BOTTOM VIEW
FRONT VIEW
SIDE VIEW
SIDE VIEW
1/2
(13)
14-1/4 (362)
2-3/4
(70)
33-5/8 (854)
21-1/4 (540)
33-1/4 (845)
7-7/8 (200)
1-3/8 (35)
15
(381)
13-1/8
(333)
2-3/8 (60)
3-5/8 (92)
13-3/4
(349)
Figure 3. 12K and 18K Outdoor Unit
Dimensions - Inches (mm)
System Dimensions
Outdoor Units
Figure 1. Typical System Shown
Figure 2. 9K Outdoor Unit
Dimensions - Inches (mm)
Figure 4. 24K Outdoor Unit Dimensions - Inches
(mm)
4
Page 5
Indoor Units
A
B
C
TOP VIEW
FRONT VIEW
BOTTOM VIEW
SIDE VIEWSIDE VIEW
MHWA024S4
diameter
diameter
Unit Outline
13-1/4 (337)
24 (610)
Air Outlet
Air Inlet
24
(610)
12
(305)
79
(2007)
1
12
(305)
1
Minimum rear clearance can be 6 inches (152 mm) when mounted on brackets
and with no obstructions on the other three sides.
MHWA018S4
6-3/4 (171)
2-1/4
(57)
12-1/2 (318)
5-3/8 (137)
Left Rear Hole
2-1/2 in. (64 mm)
diameter
38 (965)
20-3/8 (518)
5-5/8 (143)
Right Rear Hole
2-1/2 in. (64 mm)
diameter
2-1/4 (57)
Wall-Mount Unit Outline
2-3/8 (60)
Figure 8. 18K Indoor Unit Wall Plate Dimensions -
Inches (mm)
Figure 5. Indoor Unit Dimensions - Inches (mm)
Size
9K 29-5/8 752 11-3/8 289 8-5/8 219
12K 32-3/4 832 11-3/4 298 8-3/4 222
18K 39-1/8 994 12-1/2 318 9-7/8 251
24K 44 1118 13-1/4 337 10-1/4 260
A B C
in. mm in. mm in. mm
Indoor Unit Wall Mounts
MHWA009S4
11-3/8 (289)
1-7/8
(48)
4
(102)
Left Rear Hole
2-1/2 in. (64 mm)
diameter
28-1/2 (724)
13-3/4 (349)
5-3/8 (136)
Right Rear Hole
2-1/2 in. (64 mm)
diameter
7 (178)
1-1/2 (38)
Wall-Mount Unit Outline
2 (51)
21-3/4 (553)
11-7/8
(301)
Right Rear Hole
2-1/2 in. (64 mm)
2-1/8 (54)
Wall-Mount
1-7/8 (48)
1-7/8
(48)
8-5/8 (219)
6-7/8 (175)
Left Rear Hole
2-1/2 in. (64 mm)
42-1/2 (1080)
Figure 9. 24K Indoor Unit Wall Plate Dimensions -
Inches (mm)
System Clearances
Outdoor Unit
Figure 6. 9K Indoor Unit Wall Plate Dimensions -
Inches (mm)
MHWA012S4
7-1/2 (191)
11-3/4 (298)
1-3/4
(44)
Figure 7. 12K Indoor Unit Wall Plate Dimensions -
31-5/8 (803)
Inches (mm)
Left Rear Hole
2-1/2 in. (64 mm)
diameter
16-3/4 (425)
9-1/8 (232)
5
(127)
Right Rear Hole
2-1/2 in. (64 mm)
diameter
1-3/4 (44)
1-3/4 (44)
Wall-Mount Unit Outline
Figure 10. Outdoor Unit Clearances - Inches (mm)
5
Page 6
Indoor Unit
FRONT VIEW
Wall
Vertical Clearance - Clearance to Floor -
72 inches (1829 mm) Minimum
96 inches (2438 mm) Recommended
5”
(127 mm)
Minimum
6” (152 mm)
Minimum Clearance
Ceiling
Wall
Floor
5”
(127 mm) Minimum
59”
(1499 mm)
Minimum
SIDE VIEW
Any Object
Multiple Outdoor Units
10 (254)
(Minimum)
(Minimum)
CLEARANCE NOTES FOR MULTIPLE UNITS:
If the height of the wall (C) is less than or equal to the height of the smallest unit (A), the distance from the unit to the wall (B) must be a minimum of 10 inches (254 mm).
If 1/2 the height of the unit (A) is less than the height of the wall (C), the distance from the unit to the wall (B) must be a minimum of 12 inches (305 mm).
If the height of the wall (C) is greater than the height of the unit (A), the distance from the unit to the wall (B) must be a minimum of 20 inches (508 mm).
Figure 11. Indoor Unit Clearances - Inches (mm)
AIR
FLOW
10 (254)
Unit
Height (A)
AIR
FLOW
60 (1500)
(Minimum)
24 (610)
(Minimum)
Figure 12. Multiple Outdoor Unit Clearances - Inches (mm)
118 (2997)
(Minimum)
Height of
Wall (C)
Unit to
Wall (B)
6
Page 7
Torque Requirements for Caps and Fasteners
When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. “Table 3. Torque Requirements” on page 7 provides torque values for fasteners.
IMPORTANT
Only use Allen wrenches of sufcient hardness (50Rc -
Rockwell scale minimum). Fully insert the wrench into the valve stem recess.
Service valve stems are factory-torqued from 9 ft.-lbs. (12 N*m) for small valves, to 25 ft.-lbs. (34 N) for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
See the Lennox Service and Application Notes C-08-1 for further details and information.
Table 3. Torque Requirements
Parts
Service valve cap 8 ft.-lb. 11
Sheet metal screws 16 in.-lb. 2
Machine screws #10 27 in.-lb. 3
Compressor bolts 7 ft.-lb. 10
Gauge port seal cap 8 ft.-lb. 11
Recommended Torque
U.S. Newton-Meter- N
DO
• Place the unit so that it is not exposed to direct sun­light.
Ensure the structural wall can support the weight of the unit.
• Select a location where condensate line will have the shortest run to a suitable drain per local codes.
Allow sufcient space around unit for proper operation and maintenance.
• Install unit a minimum of 3 feet (1m) away from any antenna, power cord (line) radio, telephone, security
system, or intercom. Electrical interference and radio
frequencies from any of these sources may affect op­eration.
Be sure to instruct homeowners on how to properly
operate the unit (especially maintenance of air lter,
and operation procedure) by having them carry out operations themselves while looking at the manual provided with the controller.
Determining Wall Mounting Plate Location
Left piping
Left back piping
Right back piping
Right piping
Figure 13. Determining Exit Locations
Indoor Unit Installation
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
Unit Placement Considerations
AVOID
Do not install the unit in the following locations:
• Areas exposed to petrochemicals or petrochemical products.
• Areas exposed to salt or other corrosive materials or caustic gases.
• Areas exposed to extreme voltage variations (such as factories).
• Tightly enclosed areas that may impede service of the unit.
• Areas exposed to fossil fuels (such as oil or gas in kitchens).
• Areas exposed to strong electromagnetic forces.
• Areas exposed to acids or alkaline detergents.
1. Remove the wall mounting plate from the back of the indoor unit.
2. Determine the best exit location for utility bundle (line set, condensate line and wiring). See the following section concerning wall sleeve installation instructions.
3. Position the wall mounting plate on the wall so that, when installed, the unit will be at least 6 inches (152 mm) from the ceiling and 5 inches (127 mm) from the wall on either side. The wall mounting plate must be level side-to-side.
4. Use the wall mounting plate as a template to determine the exit point for utility bundle. Mark the wall to facilitate drilling hole for utility bundle.
Installation of Wall Mounting Plate
Install the wall mounting plate (see “Figure 6. 9K Indoor Unit Wall Plate Dimensions - Inches (mm)” on page 5) so that it is correctly positioned horizontally and vertically. The indoor unit must be installed level on the wall to allow proper condensate drainage.
1. Use a carpenter’s level or measuring tape to verify the wall mounting plate is horizontally level.
2. Secure the wall mounting plate to the wall using the provided screws and screw anchors.
NOTE: It is important to use all screws provided to secure
the wall mounting plate to the wall. Additional holes may be drilled through the metal wall mounting plate to better secure wall plate. Field-provided
anchors/xings may be required depending on
7
Page 8
wall construction. Use the appropriate type of anchors for the application.
3. The wall mounting plate must be installed ush against the wall so that the indoor unit will be ush
after installation. Any space between the wall and unit will cause noise and vibration.
4. The wall mounting plate must be installed horizontally level on the wall.
Installation of Wall Sleeve
The utility bundle may be routed out of the back of the unit or out either side. If the bundle is to be routed out the back
through an external wall, use a eld-provided wall sleeve
to protect the utility bundle.
NOTE: If the utility bundle will be routed out the side of the
indoor unit and up the wall above a false ceiling,
continue to the next section.
1. Prior to making the hole and installing the wall sleeve for the utility bundle, check to ensure that there are no other utilities located in the wall behind the hole location.
2. Cut a hole in the wall using a suitable hole saw. Hole should be at a slight downward slant - 3/16” to 3/8” toward the outdoor side.
3. Measure the thickness of the wall from the inside
edge to the outside edge and cut the eld-provided
wall sleeve at a slight angle 1/4” (6 mm) shorter than the thickness of the wall.
Installation of Indoor Unit on Wall Mounting Plate
1. A length of eld-provided exible condensate piping should be connected to the drain prior to securing the unit to the wall mounting plate.
2. If the factory-provided refrigerant piping connections
and eld-provided exible condensate piping are long enough to enable nal eld connections after unit is installed on wall mounting plate, use eld-provided
tape to bundle them together.
3. The utility bundle may be routed out of the back of the unit or out either side. If the bundle is to be routed out the back through an external wall, feed the utility bundle through the wall sleeve. If the utility bundle is to be routed out of the side of the indoor unit and up an inside wall, carefully form the utility bundle so that it makes a gentle 90° turn.
4. Align the back of the indoor unit with the hooks at the top of the wall mounting plate. Move the unit from side to side to make sure that it settles securely.
5. The bottom of the unit can be lifted to facilitate refrigerant piping and condensate drain connections, if necessary.
HOOKS AT TOP
OF MOUNTING
BRACKET
TEMPORARY
SPACER
(To facilitate
connections)
INSIDE
OUTSIDE
Typical
installation
procedure
shown.
Figure 14. Boring Hole for Wall Sleeve
USE SUITABLE TOOL TO CUT PVC FOR WALL
SLEEVE AT SLIGHT ANGLE AS SHOWN.
Figure 15. PVC Wall Sleeve Installation
NOTE: When passing bundled services through an
exterior brick or concrete wall, protect the
copper pipes and wiring from the effects of these construction materials by using a sleeve made of suitable material. The integrity of copper pipe
and wiring can deteriorate when exposed to these
construction materials.
Figure 16. Secure Unit to Wall Mounting Plate
Indoor Unit Condensate Piping Connections
IMPORTANT
Make sure that drain piping is properly routed and insulated to prevent both leaks and condensation.
1. Use a eld-provided hose clamp to secure the drain
line stub on the side of the cabinet to a eld-supplied
1-inch (25 mm) drain line.
NOTE: Take care not to over-tighten the hose clamps this
may damage the drain line stub.
NOTE: Connection between stub and drain line must be
watertight. Apply non-hardening plumbing joint compound if needed to ensure a watertight seal.
2. Conrm proper slope (not less than 1/4 inch per foot (18 mm per meter) and routing of condensate lines to ensure moisture is drained away from the indoor unit.
3. Drain should be as short as possible and should not have any droops or kinks that would restrict
condensate ow and shall be approved resistant pipe.
There must be a 2-inch (51 mm) space between the
end of the condensate drain and the nal termination
point (ground, open drain, etc.) to ensure that the line will drain freely.
4. After the system installation is complete, the condensate drain line must be checked for leaks
and proper drainage. If a eld-provided condensate
8
Page 9
pump has been installed, it must be checked to
12 in
305 mm
24 in
610 mm
24 in
610 mm
12 in
305 mm
NOTE - Minimum clearances shown.
ensure proper operation. This check is part of the start-up process which must be done by the installing contractor.
IMPORTANT
Drain should have a slope of at least ¼ inch per foot and
should be approved corrosion-resistant pipe. You must conrm operation of every drain and pump in the system
as part of the commissioning procedure.
CORRECT
Make sure there are no
kinks or dent in drain
hose to ensure proper
drainage.
Figure 17. Condensate Line
• Avoid installing the outdoor unit near a bedroom or other places where noise may cause a problem.
There must be sufcient space to carry the unit into and out of the site.
There must be unobstructed air ow around the air inlet and the air outlet.
The unit must not be installed in areas where a am­mable gas leak may occur.
• Install the outdoor unit a minimum of 3 feet (1m) away from any antenna, power cord (line), radio, telephone,
security system, or intercom. Electrical interference
and radio frequencies from any of these sources may affect operation.
• Since water drains from the outdoor unit during vari­ous stages of operation, do not place anything which may be damaged by moisture under the unit.
Direct Sunlight, Rain and Ice Protection
• If the outdoor unit is subjected to prolong exposure to direct sunlight with temperatures over 100°F (38°C) a canopy is recommended as illustrated in “Figure 19.
Outdoor Unit on Pedestal and Protective Canopy”or
“Figure 20. Dog House-Style Shelter” on page 9.
Outdoor Unit Installation
Placement Considerations
Consider the following when positioning the unit:
• In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life of the unit. In coastal areas, the coil should be cleaned with potable water several times per year to avoid corro­sive buildup (salt).
• Some localities are adopting sound ordinances based on the unit’s sound level registered from the adja­cent property, not from the property where the unit is installed. Install the unit as far as possible from the property line.
• When possible, do not install the unit directly outside a window. Glass has a very high level of sound trans­mission.
• Install unit level.
Building Structure
Protective canopy
Pedestal
(stand)
Air Outlet
Side View
12 in
305 mm
Air Inlet
Protective canopy
24 in
610 mm
Front View
Pedestal (stand)
Figure 19. Outdoor Unit on Pedestal and Protective
Canopy
Ground Level
Figure 18. Install Unit Level
• Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will not
be amplied.
• Choose a location where the hot air discharged from the unit or the operation noise will not be a nuisance to neighbors.
Figure 20. Dog House-Style Shelter
9
Page 10
12 in
305 mm
24 in
610 mm
12 in
305 mm
24 in
610 mm
NOTE - Minimum clearances shown.
Figure 21. Unit installed in Alcove
Air Inlet
Air Outlet
Air Outlet
Air Inlet
12 in
305 mm
79 in
2007 mm
IMPORTANT
The construction of a canopy or shade is necessary because of an ambient limit control set to 122°F (50°C) to protect the electronics. If the outdoor unit is placed in direct sunlight it is possible that the limit may activate and shut down the unit.
• Place unit away from overhanging roof lines which would allow water or ice to drop on, or in front of, coil or into unit. Construct a canopy as illustrated in “Fig­ure 19. Outdoor Unit on Pedestal and Protective Can­opy”.
• The unit base should be elevated above the depth of
average snows as illustrated in “Figure 22. Outdoor Unit on Brackets above Snow Line”.
• In heavy snow areas, do not place the unit where drift-
ing will occur as illustrated in “Figure 23. Outdoor Unit Air Flow Obstructed by Snow”.
• Carefully consider how to manage defrost water dis­posal to prevent ice from blocking walkways or creat­ing a safety hazard near the outdoor unit as illustrated in “Figure 24. Avoid Defrost Water Ice Hazard”.
Figure 23. Outdoor Unit Air Flow Obstructed by
Snow
Figure 24. Avoid Defrost Water Ice Hazard
Condensate Piping
Condensate formed during the heating and defrost processes must be drained from heat pump units. Drain holes are provided in the base of the units to ensure proper drainage. Heat pumps must be raised when installed on a concrete pad or the ground to allow drainage to occur. If the heat pump unit is installed on wall mounting bracket, insert the provided drain connector into one of the 1
inch (25 mm) drain holes and attached a eld-provided insulated drain hose to the connector. Use eld-provided
rubber plugs to cover any unused drain holes (see “Figure
25. Condensate Drain” on page 10).
Figure 22. Outdoor Unit on Brackets above Snow
Line
Drain Connector
Chassis
Condensate Drain (location varies per model)
Figure 25. Condensate Drain
Buried Refrigerant Pipe Protection
• All refrigerant lines must be insulated regardless of if it is buried.
• In addition to insulating each line of piping, buried lines must rest inside a sealed, watertight conduit.
10
Page 11
• The conduit must be designed so it cannot collect and
90
Lean
Crude
Burr
o
retain water.
Securing the Outdoor Unit
Slab or Roof Mounting
Install the unit a minimum of 4 inches (102 mm) above the roof or ground surface to avoid debris build-up around the unit. Place the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications.
CAUTION
Roof Damage!
This system contains both refrigerant and oil. Some
rubber roong material may absorb oil. This will cause
the rubber to swell when it comes into contact with oil. The rubber will then bubble and could cause leaks. Protect the roof surface to avoid exposure to refrigerant and oil during service and installation. Failure to follow this notice could result in damage to roof surface.
Securing Outdoor Unit to Slab, Frame, or Rails
If the outdoor unit is installed on a eld-provided slab or
frame, use lag bolts or equivalent to secure the outdoor unit to the slab or frame.
6 in
152 mm
Air Inlet
Air Outlet
Figure 28. Securing Outdoor Unit to Brackets
Refrigerant Piping Connections
Field piping consists of two copper lines connecting the outdoor unit to the indoor unit. “Table 5. Refrigerant Piping and Indoor Unit Connection Sizes” on page 12 lists the connection sizes. The connections are made using
the provided brass are nuts at the end of the refrigerant
piping connections.
1. Choose the correct pipe sizes for your application using “Table 5. Refrigerant Piping and Indoor Unit Connection Sizes” on page 12.
2. Conrm that you are using the correct diameter piping.
3. Determine the necessary piping length required for the application.
4. Cut the selected pipes with a pipe cutter. Make the
cuts at and smooth as illustrated in “Figure 29.
Cutting Piping”.
Four Field-provided Anchor Bolts
Figure 26. Securing Outdoor Unit to Slab
Four Field-Provided
Anchor Bolts
Figure 27. Securing Outdoor Unit to Rails
Securing Outdoor Unit to Hanging Brackets
If the outdoor unit is installed on eld-provided wall
mounting brackets, use lag bolts or equivalent to secure the outdoor unit to the bracket. Minimum rear clearance can be reduced to 6 inches (152 mm) when mounted on brackets and with no obstructions on the other three sides. Allow for moisture disposal when placing units above one another.
Figure 29. Cutting Piping
5. Insulate the copper piping.
6. Insert a are nut onto each pipe before aring.
7. Use “Table 4. Flaring Pipe” to properly are the pipe.
11
Page 12
Table 4. Flaring Pipe
R0.4~0.8
A
45
°
90
°
4
-
+
Flare Dimension
Pipe Diameter
1/4” 8.3 8.7
3/8” 12.0 12.4
1/2” 15.4 15.8
5/8” 18.6 19.1
3/4” (22.9) 22.9 23.3
A (mm)
Min Max
Flare Shape
A
CANT ON THE OUTSIDE OF
THE FLARE
MALE FLARE
CONNECTION
B
Figure 30. Making Connections
(Male to Female Connection)
8. After aring the pipe, temporarily sealed pipe ends with adhesive tape to avoid contaminants from entering the pipes.
9. The seal on the unit refrigerant piping connections should remain in place until the last possible moment. This will prevent dust or water from getting into the refrigerant piping before it is connected.
10. CAREFULLY adjust refrigerant piping connections to suit the application.
11. Slowly loosen one of the are nuts to release the factory nitrogen charge from the indoor units only.
12. Remove the are nuts from the connections on the unit and discard the seal from each of the piping connections.
13. Slide the are nuts onto the ends of the eld-provided
refrigerant piping before using a suitable aring tool to are the end of the copper pipe.
14. Apply recommended HFC-410A refrigerant lubricant
to the outside of the ared refrigerant lines.
15. Align the threaded connections with the
ared refrigerant lines. Tighten the are nuts lightly at rst to obtain a smooth match as
illustrated in “Figure 30. Making Connections (Male to Female Connection)”.
Table 5. Refrigerant Piping and Indoor Unit
Connection Sizes
Size
(Btuh)
9K 1/4 3/8
12K 1/4 1/2
18K 1/4 1/2
24K
Liquid Line
in.
3/8 5/8
Suction Line
in.
16. Once snug, continue another half-turn on each nut which should create a leak-free joint. A torque wrench
may be used to tighten are nuts using “Table 6. Flare
Nut Torque Recommendations”.
17. After refrigerant piping has been installed and checked
for leaks, apply insulation over all ared connections.
IMPORTANT
Always use two wrenches when tightening are nuts to avoid twisting refrigerant piping. DO NOT over-tighten are nuts.
TORQUE WRENCH
TO INDOOR
UNIT
TO OUTDOOR UNIT
BACKUP
WRENCH
Figure 31. Tighten Flare Nut
Table 6. Flare Nut Torque Recommendations
Outside
Diameter
Inches
1/4 15 ft.-lb. (20 N) 1/4 turn
3/8 26 ft.-lb. (35 N) 1/2 turn
1/2 41 ft.-lb. (56 N) 7/8 turn
5/8 48 ft.-lb. (65 N) 1 full turn
Recommended
Torque
No torque wrench available
Finger tighten and use an
appropriately sized wrench to
turn an additional:
IMPORTANT
Do not allow for excess length of line sets to be left rolled up as part of the required, or in general. This will also cause additional performance issues.
IMPORTANT
Do not over-tighten a ared joint. Flared connections
should always be accessible and must be insulated to prevent condensation.
12
Page 13
OUTDOOR UNIT
OUTDOOR UNIT
INDOOR UNIT
INDOOR UNIT
Maximum Line Set Length
Maximum Line Set
Length
Maximum
Elevation -
Outdooor
Unit BELOW
Indoor Unit
Maximum
Elevation -
Outdooor
Unit ABOVE
Indoor Unit
Minimum Line Set Length - 10 ft. (3m)
Minimum Line Set Length - 10 ft. (3m)
Outside Unit BELOW Indoor Unit Outside Unit ABOVE Indoor Unit
Figure 32. Indoor and Outdoor Unit Elevation Relationships
Table 7. Line Set Guide
Each system size has a line set length and vertical elevation parameters.
Line Set Diameters (in.)
System
Size (KBtu)
009 1/4 3/8 33 (10) 33 (10) 82 (25)
012 1/4 1/2 33 (10) 33 (10) 82 (25)
018 1/4 1/2 66 (20) 66 (20) 98 (30)
024 3/8 5/8 66 (20) 66 (20) 98 (30)
Liquid Gas
Maximum Elevation
Outdoor Unit BELOW
Indoor Unit - Feet
(Meter)
Maximum
Elevation
Outdoor Unit
ABOVE Indoor
Unit - Feet (Meter)
Maximum Line
Feet (Meters)
Set Length -
Additional Refrigerant for
greater than 25 Foot Line Set
Length
For the additional charging, add 0.16 oz. for 1/4” liquid line and 0.32 oz. for 3/8” liquid line per foot.
Adding Refrigerant for Longer Line Set
The outdoor unit is factory-charged with refrigerant to accommodate up to 25 feet of line set. For adding additional refrigerant for longer line sets, see “Table 7. Line Set Guide”.
Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced performance.
Leak Test and Evacuation
Air and moisture remaining in the refrigerant system will have undesirable effects as indicated below:
• Pressure in the system rises.
Operating current rises.
Cooling or heating efciency drops.
• Moisture in the refrigerant circuit may freeze.
• Water may lead to corrosion of parts in the refrigera­tion system.
The line set between the indoor and outdoor units must be leak tested and evacuated to remove any non­condensables and moisture from the system.
Leak Test
Use the following procedure to test for system leaks:
1. Connect the manifold gauge set and dry nitrogen gas cylinder to the suction and gas service ports.
2. Open valve on nitrogen cylinder.
3. Pressurize the system per the pressure test
specications in “Table 8. Pressure Test Specications”.
4. Check that the system pressure remains stable. If there is any movement check system for leaks.
5. After the system is found to be free of leaks:
• Close valve on nitrogen cylinder.
• Relieve the nitrogen pressure by: loosening the
charge hose connector at the nitrogen cylinder.
• When the system pressure is reduced to normal,
disconnect the hose from the cylinder.
Table 8. Pressure Test Specications
Bar Psig kPa Duration
1 3 44 303 Minimum of 10 minutes
2 15 220 1517 Minimum of 10 minutes
3 32 470 3241 Minimum of 10 minutes
4 45 650 4482
5 32 470 3241
1 hour. Stress test to prove the integrity of the complete installation.
24 hours. Lower system pressure
test, after conrmation No. 4 was
successfully completed.
IMPORTANT
Use only oxygen-free nitrogen (OFN).
Triple Evacuation Procedure
A Micron or Torr gauge must be used for this procedure.
1. Discharge the oxygen-free nitrogen and evacuate the system to a reading of 8000 Microns (8 Torr) using all service valves.
2. Break the vacuum by allowing nitrogen into the port connections (liquid and gas line pipes) until a positive pressure is achieved.
13
Page 14
3. Evacuate the system to a reading of 5000 Microns (5
Terminal Block
208/230V Outdoor Unit
Terminal Block
From Power
Supply
Terminal Block
208/230V Indoor Unit
Outdoor Unit Indoor Unit
3
2
L1
L2
1
Y/G
1
3
Y/G
Y/G
115VAC Outdoor Unit
Terminal Block
From Power
Supply
Terminal Block
115VAC Indoor Unit
Outdoor Unit Indoor Unit
3
2
L
N
1
Y/G
1
3
Y/G
Y/G
*
*
18 and 24K unit has five terminal sets.
Torr).
4. Break the vacuum by allowing nitrogen into the port connections (liquid and gas line pipes) until a positive pressure is achieved.
5. Evacuate the system to a minimum reading of 500 Microns (0.5 Torr).
6. For a moisture-free system, ensure the vacuum is held without movement for a minimum of 4 hours.
7. If vacuum fails to hold, carry out steps 2 through 6 until vacuum holds.
Wiring Connections
Be sure to reattach all electrical box covers after con­nections are complete.
Indoor Unit
• Indoor unit is powered by the outdoor unit.
• Communication, power and ground wiring - Use one stranded 3-conductor with ground wire.
See “Table 9. Single Zone Installation Wiring Require- ments” on page 15 for wiring requirements.
NOTE: When installing a condensate pump the line voltage
will have to be broken by using the condensate
wiring or through the use of an external relay or
contactor.
In the U.S.A., wiring must conform with current local
codes and the current National Electric Code (NEC).
In Canada, wiring must conform with current local codes
and the current Canadian Electrical Code (CEC).
WARNING
Electric Shock Hazard. Can cause injury or death. Unit
must be rounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power sources.
CAUTION
All terminal connections must be made as illustrated in the following diagrams. Improperly connected wiring could damage unit or cause communication errors between indoor and outdoor units.
Outdoor Unit
• Refer to unit nameplate for minimum circuit ampacity and maximum over-current protection size.
• Make all electrical power wiring connections at the outdoor unit.
IMPORTANT
All illustrations listed are typical wiring diagrams. Refer to the wiring diagram on the unit for actual wiring.
Terminal block
Cover
Screw
Cable Clamp
The wiring diagram is located on the inside of the indoor unit’s
terminal block cover.
Figure 33. Indoor Unit Terminal Block
Figure 34. Single Zone Wiring
14
Page 15
IMPORTANT
This unit must be properly grounded and protected by a circuit breaker. The ground wire for the unit must not be connected to a gas or water pipe, a lightning conductor or a telephone ground wire.
Do not connect power wires to the outdoor unit until all other wiring and piping connections have been completed.
Do not install the unit near a lighting appliance that includes a ballast. The ballast may affect remote control operation.
Table 9. Single Zone Installation Wiring Requirements
Systems and Terminal
Designations
Indoor to Outdoor Wiring
(Communication/Power)
1, 2, 3 and GND
Outdoor to Main Power
L, N and GND
Indoor to Outdoor Wiring
(Communication/Power)
1, 2, 3 and GND
Outdoor to Main Power
L, N and GND
System Capacity System Voltage
09K 115VAC 4 16AWG / 16A
09K 115VAC 3 16AWG / 16A
12K 115VAC 4
12K 115VAC 3 16AWG / 15A
Number of
Conductors
Wire Type
Wire Gauge /
Minimum Circuit
Ampacity
16AWG / 15A
Max Fuse
20A
20A
Indoor to Outdoor Wiring
(Communication/Power)
1, 2, 3 and GND
Indoor to Outdoor Wiring
(Communication/Power)
1, 2, 3 and GND
Indoor to Outdoor Wiring
(Communication/Power)
1, 2, 3 and GND
Outdoor to Main Power
L1, L2 and GND
Indoor to Outdoor Wiring
(Communication/Power)
1, 2, 3 and GND
Outdoor to Main Power
L1, L2 and GND
Indoor to Outdoor Wiring
(Communication/Power)
1, 2, 3 and GND
Outdoor to Main Power
L1, L2 and GND
09K 208/230VAC 4 16AWG / 10A
15A
09K 208/230VAC 4 16AWG / 10A
Stranded and
unshielded
12K 208/230VAC 4 16AWG / 15A
15A
12K 208/230VAC 3 16AWG / 15A
18K 208/230VAC 4 16AWG / 15A
20A
18K 208/230VAC 3 16AWG / 15A
24K 208/230VAC 4 16AWG / 20A
25A
24K 208/230VAC 3 16AWG / 20A
MCA = Minimum Circuit Amps
15
Page 16
Wiring Diagrams
FOR REMOTE ON/OF
S5
MODE
FACTORY SETTING
RED
BLACK
YELLOW
2
3
1
FOR SETTING NETADDRESS
ENC2+S1
CODE
NETADDRESS
REMOTE ON/OFF OFFREMOTE ON/OFF ON
0
1
ON
F
2
E
3
D
4
C
5
B
6
A
7
9
1
8
0~F 0~F 0~F 0~F
0~15
WIRING DIAGRAM (INDOOR UNIT)
0
1
F
E
D
C
B
A
2
ON
2
3
4
5
6
7
9
1
8
16~31 32~47 48~63
0
1
ON
F
2
E
3
D
4
C
5
B
6
A
7
9
2
8
2
1
E
D
C
B
CN10A
0
1
F
A
9
8
M
M
5
ON
2
1
DI SP LA Y BOARD
CN2(CN201)
8
2
3
4
5
6
7
SWING MOTOR1
CN3(CN301)
OPTIONAL
Wired Controller
OPTIONAL
Programmable Wired Controller
Note: The programmable wired controller and LVM use the same port CN403.
NOTE: COMPONENT IN DASH LINE IS OPTIONAL OR FIELD WIRING
5
5
4
ADAPTER BOARD
CN501
CN402
CN403
X Y E
YELLOW
BROWN
To LVM Comm.Bus
RED
Figure 35. 09K,12K, 18K and 24K - 115V and 208/230VAC Indoor Unit Wiring Diagram
BLACK
BLUE
RED
BLACK
V
U
W
COMPRESSOR
CAPACITOR
BROWN
REACTOR
BLACK
CN4_1
CN4_2
BLACK
CN4_3
CN4_4
BROWN
Y/G
OUTDOOR CONTROL
CN 30 CN 29 CN 28
CN 50
Y/G
CN 3
BLUE
CN 1
CN 2
CN 1A
CN 60
CN 17
CN 15
BROWN
CN 16
Y/G
2
2
1
2
4-WAY
CRANKCASE HEATER
PAN HEATER
3
Y/G
RED
BLUE
L
N
Y/G
DISCHARGE TEMP. SENSOR
T5/
CN 21
T3
.
T4
AMBIENT TEMP. SENSOR
CN 7
3
DC-FAN
TP
Figure 36. 9K - 115VAC Outdoor Unit Wiring Diagram
16
Page 17
YELLOW OR BLACK
BLUE
RED
BLACK
V
U
COMPRESSOR
W
CAPACITOR
BROWN
REACTOR
BLACK
CN4_1
CN4_2
OUTDOOR CONTROL
CN 50
CN 30
CN 29
CN 28
CN4_3
Y/G
CN 3
BLUE
CN 1
CN 1A
CN 2
2
BROWN
CN 16
1
Y/G
CN 60
2
2
4-WAY
CN 17
CN 15
CRANKCASE HEATER
PAN HEATER
BROWN
Y/G
BLACK
CN4_4
RED
BLUE
L
3
N
Y/G
Y/G
CN 21
DISCHARGE TEMP. SENSOR
CN 7
AMBIENT TEMP. SENSOR
3
DC-FAN
.
Y/G
TP/
T3
T4
T5
Figure 37. 12K - 115VAC Outdoor Unit Wiring Diagram
BLACK
BLUE
BROWN
Y/G
BLUE
RED
BLACK
V
W
U
COMPRESSOR
Y/G
OUTDOOR CONTROL
CN 50
3
CN 21
CN 7
Y/G
Y/G
CN 1A
CN 60
CN 17
CN 15
CN 31
2
1
3
4-WAY VALVE
CRANKCASE HEATER
PAN HEATER
BLUE
RED
L2
Y/G
RED
TEMP. SENSOR
DISCHARGE
COMPRESSOR
BLACK
OUTDOOR COIL
TEMP. SENSOR
TEMP. SENSOR
WHTIE
OUTDOOR
3
OU TDOOR
FA N
6
EXV
Y/G
T3
T5
T4
Figure 38. 09K, 12K and 18K - 208/230VAC) Outdoor Unit Wiring Diagram
17
Page 18
Y/G
Y/G
CN 7
CN 6
CN 3
OUTDOOR CONTROL
BLUE
CN 8 CN 2
S
BROWN 1
Y/G
BLACK 3
1
2
BLUE L2
RED
L2
L1
3
L1
L2
Y/G
CN 17
CN 21
U V W
CN 414
AMBI ENT TEMP. SENSOR
.
Y/G
3
DC- FAN
BLUE
RED
BLACK
V
W
U
COMPRESSOR
Y/G
DISCHARGE TEMP. SENSOR
TP/
T5
Figure 39. 24K - 208/230VAC Outdoor Unit Wiring Diagram
Unit Start-Up
IMPORTANT
Units should be energized 24 hours before unit start-up to prevent compressor damage as a result of slugging.
1. Inspect all factory- and eld-installed wiring for loose connections.
2. Verify that the manifold gauge set is connected.
3. Add additional refrigerant charge if required before opening valves and while system is still under a vacuum.
4. Open the liquid and suction line service valves to release the refrigerant charge contained in outdoor unit into the system.
5. Replace the stem caps and tighten to the value listed in “Table 3. Torque Requirements” on page 7.
6. Check voltage supply at the outdoor unit terminal strip. The voltage must be within the range listed on the unit’s nameplate. If not, do not start the equipment until you have consulted with the power company and the voltage condition has been corrected.
7. Refer to the included user guide to operate the system using the provided remote control.
8. Visually check for binding of both indoor and outdoor fans.
CN 60
Blue
CN 16
Red
CN 19
White
4-WAY
CRANKCASE HEATER
PAN HEATER
Troubleshooting
Table 10. Indoor Unit Error Codes
Display Error Information
E0 Indoor unit EEPROM parameter error
E1 Indoor / outdoor units communication error
E2 Zero-crossing signal detection error
The indoor fan speed is operating outside of the normal
E3
range
Indoor room temperature sensor T1 is in open circuit or
E4
has short circuited
Evaporator coil temperature sensor T2 is in open circuit or
E5
has short circuited
EC Refrigerant leak detected
F0 Overload current protection
Outdoor ambient temperature sensor T4 open circuit or
F1
short circuit
Condenser coil temperature sensor T3 is in open circuit or
F2
has short circuited
Compressor discharge temperature sensor TP open circuit
F3
or short circuit
F4 Outdoor unit EEPROM parameter error
The outdoor fan speed is operating outside of the normal
F5
range
p0 IPM malfunction or IGBT over-strong current protection
p1 Over voltage or over low voltage protection
p2 High temperature protection of IPM module
18
Page 19
Table 10. Indoor Unit Error Codes
Indoor Unit Control Box Area (under front panel)
Manual Control Button
Ambient Temperature is Below 63ºF (17ºC)
Display Error Information
P3 Outdoor ambient temperature too low.
p4 Inverter compressor drive error
Test Run
Pre-Checks
Only perform test run after you have completed the
following steps:
Electrical Safety Checks – Conrm that the unit’s electrical system is safe and operating properly.
Refrigerant Leak Checks – Check all are nut connec-
tions and conrm that the system is not leaking.
Conrm that suction and liquid valves are fully open.
Procedure
You should perform the Test Run for at least 30 minutes.
1. Connect power to the unit.
2. Press the ON/OFF button on the remote controller to turn it on.
3. Let each function run for 5 minutes, and perform the following checks:
After installation, conrm that all electrical wiring is
installed in accordance with local and national regulations, and according to the installation instruction.
You cannot use the wireless remote control to turn on the COOL function when the ambient temperature is below
63°F (17°C). In this instance, you can use the MANUAL
CONTROL button on the indoor unit to test the COOL
function.
1. Lift the front panel of the indoor unit, and raise it until it clicks in place.
2. The MANUAL CONTROL button is located on the right-hand side of the unit. Press it two times to select
the COOL function. See “Figure 40. Manual Control Button”.
3. Perform Test Run as normal.
Test Run Checklist
Table 11. Test Run Checklist
Checks Pass Fail
No electrical leakage
Unit is properly grounded
All electrical terminals properly covered
Indoor and outdoor units are solidly installed
All pipe connection points do not leak
Water drains properly from drain hose
All piping is properly insulated
Unit performs COOL function properly
Indoor unit louvers rotate properly
Indoor unit responds to wireless remote
Double-Check Line Set Connections
During operation, the pressure of the refrigerant circuit will increase. This may reveal leaks that were not present during your initial leak check. Take time during the Test Run to double-check refrigerant line set connections and verify there are no leaks.
1. Using the wireless remote control, return unit to the normal operating temperature.
2. Using insulation tape, wrap the indoor refrigerant pipe connections that you left uncovered during the indoor unit installation process.
Figure 40. Manual Control Button
19
Page 20
20
Loading...