Lennox MWC 380, MWC 330, MWC 450, MWC 510, MWC 570 Application Manual

...
APPLICATION GUIDE
Water cooled chillers Heat pumps
MWC MWR
180 720 kW
lennoxemeia.com
TABLE OF CONTENTS
APPLICATION GUIDE
1.
GENERAL
Features and benefi ts Options and accessories Model number description
2.
GENERAL DATA
General data Pressure drops Hydraulic data Acoustic data Operating limits
Ref : MWC-AGU-0410-E
2 4 5
6 10 11 12 13
ELECTRICAL DATA
4.
Electrical tables
PERFORMANCES
5.
MWC - Cooling mode MRC - Cooling mode MWC - Heating mode
DIMENSIONAL DATA
6.
Dimensional data
14
15 16 17
18
Our company is member of the Eurovent certifi cation program.
The MWC™ Lennox chillers are tested and rated in accordance with Eurovent certifi cation program.
Our products comply with the European standards.
Product designed and manufactured under a quality management system certifi ed ISO 9001.
All the technical and technological information contained in this manual, including any drawing and technical descriptions provided by us, remain the property of Lennox and must not be utilised (except in operation of this product), reproduced, issued to or made available to third parties without the prior written agreement of Lennox.
Application Guide MWC-0410-E • 1 •
FEATURES AND BENEFITS
Water cooled liquid chiller for indoor installation
GENERAL CHARACTERISTICS OF THE UNIT
The MWC unit is designed for industrial and commercial applications where customers require reduced total cost of ownership for new air conditioning equipment.
As main characteristics the MWC unit offers multi scroll R410A compressors with two circuits for safety operation and oversized heat exchangers for high full and part load energy performances (Class B effi ciency / ESEER > 6.0).
The MWC is the solution for indoor installation. Thanks to very compact dimensions and limited footprint MWC can be installed easily into any technical room.
The MWC is available in 2 main versions to meet all customer requirements and applications :
- MWC version is the water-cooled chiller. This version can be used for air conditioning applications in association with a separate dry-cooler or using ground water. The MWC ver­sion can also be used for heating applications. With the “hot water set point control” option the MWC range can supply hot water up to +50°C.
- MRC version is the split version without condenser. This version can be used for air conditioning applications in as­sociation with a remote air-cooled condenser
COMPRESSOR
MWC is using R410A vibration-free compliant® scroll compressors to guarantee a low operating sound level, a high durability and reliability and no maintenance.
- Exclusive Compliant® Scroll design with both axial and radial compliance to increase compressor operation tolerance to liquid refrigerant, substantially improving durability and re­liability.
- Motor cooled by suction gas.
- Electronic control of the compressor discharge tempera­ture.
- Motor protection device against high temperature or over current situations.
- Discharge non-return valve.
- Compressors assembly installed on an independent chassis supported by anti-vibration mountings.
- Optional sound-proofed panel enclosures to reduce noise emissions.
WATER HEAT EXCHANGER (EVAPORATOR AND CONDENSER)
MWC is using stainless steel brazed plate heat exchangers with true dual circuit.
REFRIGERANT CIRCUIT
MWC is using R410A refrigerant in 2 independent circuits that allows operation at 50% of the capacity in case of issue on one circuit.
Each circuit includes:
- A refrigerant charge reduced by 30% thanks to the use of R410A combined with plate heat exchanger
- Suction piping with thermal insulation.
- Moisture sight glass on the MRC version
- Filter drier with removable cartridge fi lter.
- Thermostatic valve or electronic expansion valve (optional from size 180 to 570, standard on size 650 & 720).
- Temperature sensors and pressure transducers.
- Leak-tight refrigerant circuit with brazing carried out under nitrogen by certifi ed technicians.
- Each refrigerant circuit is pressure and leak tested with a Hydrogen/Nitrogen mixture, and vacuumed before being charged with refrigerant. All units are then subjected to a complete functional and operational run test to guarantee perfect sealing before leaving the factory.
- Copper brazed stainless steel plate heat exchanger.
- 13 mm closed cell thermal foam insulation.
- Evaporator protected against freezing risks thanks to an electronic water fl ow switch
- Condenser protected against low condensing temperature thanks to a 0-10 V output signal available from the controller to control a condenser water inlet valve (Not from Lennox supply).
CASING/CHASSIS
- Chassis made of galvanised steel sheet metal painted with a RAL 7016 (grey) powdered polyester paint.
- Optional casing with removable panels made of galvanised steel sheet metal painted with a RAL 7016 (grey) powdered polyester paint.
• 2 • Application Guide MWC-0410-E
FEATURES AND BENEFITS
ELECTRICAL BOX
The MWC is designed for 400V/3/50Hz supply.
- Unit electrical cabinet, components and wiring in compliance with EN 60204-1 electrical directive.
- 400V/3/50Hz power supply (without neutral) with a single point of power connection.
- IP24 protection class.
- Recognized brand electrical components for ease of main­tenance.
- Main on/off switch mounted on the front panel.
- DC50 user interface mounted on the front panel.
- 400/24 V transformer to supply the control circuit.
- Labelled electrical wires to facilitate maintenance and dia­gnostic.
- Optional power and control circuit for the pumps.
CONTROL
CLIMATIC™ microprocessor based control is providing the following functions:
- 4 scheduling time zones per day over 7 days to allow energy consumption management according to the building use and environmental constraints.
- PI control of the water temperature with operating time equalisation of the compressors.
- Intelligent advanced control algorithm to protect the compres­sors against excessive short-cycling and to allow operation of the unit without buffer tank in most comfort air conditioning applications (e.g. unit with fan-coils). Refer to minimum ins­tallation water loop volume recommendations.
- Water pump control with operating time equalization and automatic change-over in case of a pump fault (Twin pump only).
- Master/slave or cascade control of two chillers operating in parallel with operating time equalization and automatic change-over in case of a unit fault.
CLIMATIC™ is pre-factory confi gured with default settings allowing a fast commissioning on site. The DC50™ user interface with graphical display is easy to use, intuitive. Main customer parameters can be read or modifi ed without main power shut-off (Entering/leaving water temperatures, alarms, water set-points, high and low pressure readings). The DS50™ service display (optional) is a .plug and play" controller that allows service people to read and modify all unit parameters (Unit settings, operating time and number of compressor starts, low and high pressure reading, read the history of last 32 faults...).
COMMUNICATION
The control board is equipped with a RS485 serial communication port to allow remote management through communication bus. According to the wished communication protocol, our control board can be fi tted with ModBUS®, LonWorks® or BacNET® communication interface (options). The main control board has free dry contacts that allow remote control of the unit by wired cable:
- Remote on/off of the unit.
- Remote alarm reset to re-start the unit.
- Alarm or alert indications.
- Free customer contact.
With the optional extension board BE50, it is possible to get additional customized digital or analog inputs/outputs for remote control of the unit:
- Fault pumps (dry contact).
- Operation indication at 100% on circuit 1 or 2 (dry contact).
- Dual water set-point management (dry contact).
- Force heating or cooling mode (24V AC input).
- Power limitation by disabling circuit 1 or 2 (24V AC input).
- Force unoccupied mode (24V AC input).
- Water set-point offset based on a 4-20mA signal.
DIRECTIVES
The unit is built to meet European norms and standards & Eurovent certiFIcation performance standards.
. DI 97/23/CE Pressure Equipment Directive.
. DI 98/37/CE Machinery Directive.
. DI 73/23/CE Low Voltage Directive.
. DI 89/336/CE Electro Magnetic Compatibility Directive
. EN 378-2 Safety and Environmental Directive.
. The European Restriction of the Use of Certain Hazardous-
Substances (RoHS).
Application Guide MWC-0410-E • 3 •
OPTIONS AND ACCESSORIES
OPTIONS DESCRIPTION ADVANTAGES MODELS
Control/Power electrical equipment of single evaporator pump
Control/Power electrical equipment of dual evaporator pump
Control/Power electrical equipment of single condenser pump
Control/Power electrical equipment of dual condenser pump
Electronic expansion valve
Evaporator fi lter (supplied loose)
Unit equipped with electrical power and control circuit for one single speed pump
Unit equipped with electrical power and control circuit for dual single speed pumps.
Unit equipped with electrical power and control circuit for one single speed pump
Unit equipped with electrical power and control circuit for dual single speed pumps.
Unit equipped with an electronic expansion valve for smooth operation in every temperature conditions
1000 microns water fi lter delivered with piping and Victaulic connections.
Quick start-up on job site.
Quick start-up on job site.
Quick start-up on job site.
Quick start-up on job site.
Allows applications with changing temperature conditions.
This protection must be fi tted to protect the evaporator from any possible impurities.
MWC/MRC
180 720
MWC/MRC
180 720
MWC
180 720
MWC
180 720
MWC
180 570
MWC/MRC
180 720
Condenser fi lter (supplied loose)
Evaporator fl ange connections (supplied loose)
Condenser fl ange connections (supplied loose)
Hot water set-point control (Heat pump mode)
DC50™ remote comfort display (supply loose)
DS50™ service display (supply loose)
1000 microns water fi lter delivered with piping and Victaulic connections.
Two connection sleeves with Victaulic groove and fl ange on opposite side.
Two connection sleeves with Victaulic groove and fl ange on opposite side
Unit equipped with insulated heat exchanger and hot water sensor on condenser side for heating purpose.
Customer display located at 600 meters maximum from the unit.
Plug and play display delivered with 1 meter cable and connector for quick connection on Climatic controller.
This protection must be fi tted to protect the condenser from any possible impurities.
Allow easy connection with fl anges on customer side.
Allow easy connection with fl anges on customer side.
Allow heat pump operation.
Remote customer parameter reading and modifi cation.
Display for service technicians only.
MWC
180 720
MWC/MRC
180 720
MWC
180 720
MWC
180 720
MWC/MRC
180 720
MWC/MRC
180 720
Communication card using ModBus/
Modbus communication interface
LonWorks® communication interface
• 4 • Application Guide MWC-0410-E
.
JBus protocol
Communication card using LonTalk® protocol.
Communication interface with a building management system.
Communication interface with a building management system.
MWC/MRC
180 720
MWC/MRC
180 720
OPTIONS AND ACCESSORIES
OPTIONS DESCRIPTION ADVANTAGES MODELS
BACnet® communication interface
Adalink™ supervision (Customer friendly web based supervision)
BE50™ extension board for additional inputs/outputs
Anti-vibration mounts (supplied loose)
Panel enclosure (compressors)
Communication card using Bacnet® protocol.
Electronic board with RS485 cables, RJ11 phone cable, Ethernet cable and power supply cable.
Electronic extension board with additional analog inputs (4), digital inputs (4) and digital outputs (4). See control manual.
Rubber anti-vibration mounts to be mounted under the unit.
Unit equipped with removable panels around the compressors to reduce sound level.
Communication interface with a building management system.
Remote supervision of the unit via an intuitive web page.
Relay card for remote control and alarm report using dry contacts, 24 Vac or 4-20 mA signals.
Reduction of the transmission of vibration to the ground.
Reduction of the unit sound power level.
MWC/MRC
180 720
MWC/MRC
180 720
MWC/MRC
180 720
MWC/MRC
180 720
MWC/MRC
180 720
MODEL NUMBER DESCRIPTION
EXAMPLE : MWC 200D
M
W
C
200
D
N
M
1
Medium
W = Water cooled R = Remote condenser
C = Cooling mode
Cooling capacity in kW
Number of circuits : D = 2 circuits
Non ducted
R410 A refrigerant
Revision number
M
Application Guide MWC-0410-E • 5 •
400V/3/50 Hz
GENERAL DATA
COOLING ONLY
MWC
MWC™ 180 230 280 330 380
Cooling mode
Cooling capacity
Power input
Full load amps
EER 4,74 4,66 4,70 4,70 4,70
(2)
ESEER
Evaporator water fl ow
Evaporator pressure drop
Condenser water fl ow
Condenser pressure drop
Heating mode
Heating capacity
Power input
Full load amps
COP
Condenser water fl ow
Condenser pressure drop
Evaporator water fl ow
Evaporator pressure drop
Compressor Scroll - Hermetic
Number of compressor nr
Capacity steps
Oil charge per compressor
Oil type type MOBIL EAL Arctic 22CC or ICI EMKARATE RL32CF
Refrigerant
Expansion type Thermostatic expansion valve
Number of circuit nr
Charge per circuit
Condenser (Heating mode) AISI 316 stainless steel plate brazed with copper heat exchanger
Water volume
Water operating pressure
Hydraulic connections Victaulic
Water inlet/outlet Inches
Evaporator (Cooling mode) AISI 316 stainless steel plate brazed with copper heat exchanger
Water volume
Water operating pressure
Hydraulic connections Victaulic
Water inlet/outlet Inches
Acoustic
Global sound power level
Electrical data
Start-up intensity
Maximum current
Dimensions
Length
Width
Height
Footprint
Operating weight
Shipping weight
(1)
(1)
(1)
kW
186,1 232,8 280,7 333,6 380,4
kW 39,3 49,9 59,7 70,9 81,0
A 70,6 86,6 101,1 118,1 133,2
6,74 6,31 6,38 6,25 6,03
(1)
(1)
(1)
(1)
(3)
(3)
(3)
m3/h 32,0 40,1 48,3 57,4 65,4
kPa 34,9 28,9 40,7 31,5 40,2
m3/h 37,2 46,7 56,2 66,8 76,2
kPa 46,2 38,3 30,3 41,8 40,5
kW
196,5 246,4 296,9 351,9 401,7
kW 48,5 61,5 73,1 86,9 99,1
A 86,6 110,0 130,7 155,3 177,1
4,05 4,00 4,06 4,05 4,05
(3)
(3)
(3)
(3)
3
/h 33,8 42,4 51,1 60,5 69,1
m
kPa 38,6 32,1 25,4 34,8 33,7
m3/h 32,0 40,1 48,3 57,4 65,4
kPa 34,9 28,9 40,7 31,5 40,2
44444
%
l
20-50-75-
100%
(2 x 3,2)
+ (2 x 3,2)
21-43-62-83-
100%
(3,2+6,3)
+ (2 x 3,2)
21-36-53-71-
85-100% (3,2+6,3)
+ (3,2+6,3)
15-46-61-87-
100%
(2 x 6,3)
+ (3,2+6,3)
25-50-75-
100%
(2 x 6,3)
+ (2 x 6,3)
R410A
22222
kg8 12141422
l 13 24 35 35 43
kPa 600 600 600 600 600
4" 4" 4" 4" 4"
l 13 24 24 35 35
kPa 600 600 600 600 600
4" 4" 4" 4" 4"
(1)
dB(A) 81 87 89 90 92
400V / III / 50 Hz
A 266,9 402,9 431,7 460,1 488,3
A 123,8 152,2 181,0 209,4 237,6
mm 2150 2150 2150 2150 2150
mm 820 820 820 820 820
mm 1645 1870 1870 1870 1870
1,8 1,8 1,8 1,8 1,8
kg 756 974 1158 1328 1534
kg 736 914 1088 1248 1444
All data are at Eurovent conditions : (1) Gross cooling capacity with 12/7°C evaporator water temperature and
30/35°C condenser water temperature.
(*) Except for MWC 720 :13/7°C evaporator water temperature.
(2) ESEER according to EN14511 Eurovent calculation method.
(3) Gross heating capacity with 40/45°C condenser water temperature and 10°C
evaporator water inlet, with the same evaporator water fl ow as in cooling mode.
OPERATING LIMITS on page 13