Lennox Merit Plus Series, MPD Pro Series, MPDP40IP, MPDP35IN, MPDP40IN Installation Instructions Manual

...
INSTALLATION INSTRUCTIONS
AVERTISSEMENT : Assurez-vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d’incindie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result, causing property damage, personal injury, or death.
WARNING /AVERTISSEMENT/AVISO
• HOT GLASS WILL CAUSE BURNS.
• DO NOT TOUCH GLASS UNTIL COOLED.
• NEVER ALLOW CHILDREN TO TOUCH GLASS.
• UNE SURFACE VITRÉE CHAUDE PEUT CAUSER DES BRÛLURES.
• LAISSER REFROIDIR LA SURFACE VITRÉE AVANT D'Y TOUCHER.
• NE PERMETTEZ JAMAIS À UN ENFANT DE TOUCHER LA SURFACE VITRÉE.
• EL VIDRIO CALIENTE CAUSARÁ QUEMADURAS.
• USTED DEBE NUNCA TOCAR EL VIDRIO CALIENTE.
• LOS NIÑOS DEBEN NUNCA TOCAR EL VIDRIO.
- Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
- Ne pas entreposer ni utilizer d’essence ni d’autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucan interrupteur. Ne pas vous servir des
téléphones se trouvant dans le bâtiment où vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis
un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service des incindies.
- L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
P/N 506015-06 Rev. NC 06/2012
This manual is one of a set of two supporting this product. Refer to P/N 506017-05 for Care and Operation Instructions.
Ce manuel est disponible en francais, simplement en faire la demande. Numéro de la pièce 506223-39.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
INSTALLATEUR : Laissez cette notice avec l’appareil. CONSOMMATEUR : Conservez cette notice pour consultation ultérieure.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
MODELS
US
OTL Report No. 116-F-59-5
Please read and understand these instructions
before starting installation.
MPDP35IN MPDP40IN
Portland
ELECTRONIC:
MPDP35IP MPDP40IP
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
TABLE OF CONTENTS
Packaging . . . . . . . . . . . . . . . . . . . . . . . . . 2
Introduction . . . . . . . . . . . . . . . . . . . . . . . . 2
General Information . . . . . . . . . . . . . . . . . . 2
Requirements for the
Commonwealth of Massachusetts . . . . . 4
Cold Climate Insulation . . . . . . . . . . . . . . . 5
Manufactured Home Requirements . . . . . . 5
Location . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Vent Termination Clearances . . . . . . . . . . . 6
Appliance and Vent Clearances . . . . . . . . . 8
Wall Finishes/Surrounds/Mantels. . . . . . . . 8
Pre-Installation Steps . . . . . . . . . . . . . . . . . 9
Typical Installation Sequence . . . . . . . . . . 9
Detailed Installation Steps . . . . . . . . . . . . . 9
Step 1. Framing . . . . . . . . . . . . . . . . . . . . . 9
Fireplace and Framing Specifications . . . 10
Step 2. Routing Gas Line . . . . . . . . . . . . . 11
Step 3. Preparing Appliance Vent Collar . . 12
Step 4. Installing Vent System . . . . . . . . . 12
Vent Restrictor Installation . . . . . . . . . . . 13
Vertical Termination Systems (Roof) . . . 15
Vent Section Length Chart . . . . . . . . . . . 15
Vertical Vent Tables and Figures . . . . . . . 18
Horizontal (Outside Wall) Termination
System . . . . . . . . . . . . . . . . . . . . . . . 20
Horizontal Vent Tables and Figures . . . . 22
Venting Using Flexible Vent Pipe . . . . . . 25
Step 5. Field Wiring . . . . . . . . . . . . . . . . 26
Step 6. Remote Control System . . . . . . . 27
Step 7. Connecting Gas Line . . . . . . . . . 28
Step 8. Verifying Appliance Operation . . . . 28
Step 9. Installing Volcanic Stone,
Glowing Embers, and Logs . . . . . . . . . 29
Step 10. Remove/Install Glass Door . . . . 32
Step 11. Burner Adjustments . . . . . . . . . . 32
Step 12. Hood Installation . . . . . . . . . . . . 34
Finishing Requirements . . . . . . . . . . . . . . 34
Step 13. Attaching Safety-in-Operation
Warnings . . . . . . . . . . . . . . . . . . . . . . . 35
Installation Accessories . . . . . . . . . . . . . . 36
Gas Conversion Kits . . . . . . . . . . . . . . . . 38
Please read and understand these instructions before beginning your
installation.
2
PACKAGING
The assembled vented gas fireplace heater is packaged with:
(1 set) Logs (packaged in a carton inside the
firebox).
(1 bag) Glowing Embers and (1 bag) Volcanic
Stone (in bottom compartment).
Literature Kit (envelope in bottom com-
partment containing Care and Operation Instructions, Installation Instructions, Safety- In-Operation Warning Labels w/instructions, Warranty).
(1) Top Vent Flue Restrictor
(1) Rear Vent Restrictor Plate
(1) U-shaped Vent Restrictor
(1) Top Standoff (taped to outer wrapper)
(1) Hood (taped to outer wrapper)
(1) Remote Control Kit and Receiver Kit
Required Firebox Liner Kits
(One of the following kits must be installed
- sold separately)
H8572 - Black Porcelain, MPDP35
H8573 - Black Porcelain, MPDP40
H8595 - Brickaded, MPDP35
H8596 - Brickaded, MPDP40
INTRODUCTION
These Electronic appliances are designed to operate on natural or propane gas. The system is switchable between standing and intermit­tent pilot modes. External electrical power is required to operate these units. In the event of a power outage, four (4) "AA" batteries (in receiver) can be used as a backup (excluding blower operation).
These vented gas fireplace heaters are sealed combustion, air-circulating gas fireplaces de­signed for residential applications.
Approved Vent Components
These fireplaces are designed, tested and listed for operation and installation with the following vent components only:
®
Secure Vent
nents manufactured by Security Chimneys International,
Secure Flex
manufactured by Security Chimneys Inter­national and
Z-FLEX
to UL1777 and ULCS635 manufactured by Flexmaster Canada Limited.
Use only the correct size venting (4-1/2" inner and 7-1/2" outer).
These approved vent system components are labeled for identification. DO NOT use any other manufacturer’s vent components with these appliances.
Direct-Vent System Compo-
®
Flexible Vent Components
®
Model GA Venting Systems listed
GENERAL INFORMATION
WARNING
Young children should be care­fully supervised when they are in the same room as the appli­ance. Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to a fireplace or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
AVERTISSEMENT
Les jeunes enfants devraient être surveillés étroitement lorsqu’ils se trouvent dans la même pièce que l’appareil. Les tout petits, les jeunes enfants ou les adultes peuvent subir des brûlures s’ils viennent en contact avec la sur­face chaude. Il est recommandé d’installer une barrière physique si des personnes à risques habi­tent la maison. Pour empêcher l’accès à un foyer ou à un poêle, installez une barrière de sécu­rité; cette mesure empêchera les tout petits, les jeunes enfants et toute autre personne à risque d’avoir accès à la pièce et aux surfaces chaudes.
Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition.
Les enfants et les adultes devraient être infor-més des dangers que posent les températures de surface élevées et se tenir à distance afin d’éviter des brûlures ou que leurs vêtements ne s’enflamment.
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERATION MAY VOID THE WARRANTY, CERTIFICATION AND LISTINGS OF THIS UNIT.
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
WARNING
Improper installation, adjust­ment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
WARNING
Failure to comply with these installation instructions will result in an improperly installed and operating appliance, voiding its warranty. Any change to this appli­ance and/or its operating controls is dangerous.
WARNING
Clothing or other flammable material should not be placed on or near the appliance.
AVERTISSEMENT
On ne devrait pas placer de vêtements ni d’autres matières inflammables sur l’appareil ni à proximité.
WARNING
Any safety screen or guard removed for servicing the appli­ance must be replaced prior to operating the appliance.
AVERTISSEMENT
Tout écran ou protecteur retiré pour permettre l’entretien de l’appareil doit être remis en place avant de mettre l’appareil en marche.
WARNING
Improper installation or use of this appliance can cause serious injury or death from fire, burns, explosion or carbon monoxide poisoning.
WARNING
Failure to position the parts in accordance with these diagrams or failure to use only parts specifi­cally approved with this appliance may result in property damage or personal injury.
AVERTISSEMENT
Risque de dommages ou de blessures si les pièces ne sont pas installées conformément à ces schémas et ou si des pièces autres que celles spécifiquement approuvées avec cet appareil sont utilisées.
Note: Installation and repair should be done by a qualified service person. The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etcetera. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
Remarque: L’installation et la réparation devrait être confiées à un technicien quali­fié. L’appareil devrait faire l’objet d’une inspection par un technicien professionnel avant d’être utilisé et au moins une fois l’an par la suite. Des nettoyages plus fréquents peuvent être nécessaires si les tapis, la literie, et cetera produisent une quantité importante de pous-sière. Il est essentiel que les compartiments abritant les commandes, les brûleurs et les con­duits de circulation d’air de l’appareil soient tenus propres.
Do not use these appliances if any part has been under water. Immediately call a qualified, professional service technician to inspect the appliance and to replace any parts of the control system and any gas control which have been under water.
Ne pas utiliser cet appareil s’il a été plongé, même partiellement, dans l’eau. Appeler un technicien qualifié pour inspecter l’appareil et remplacer toute partie du système de commande et toute commande qui a été plongée dans l’eau.
Only trim kit(s) supplied by the manufacturer shall be used in the installation of this ap­pliance.
Seules les trousses de garniture fournies par le fabricant doivent être utilisées pour l’installation de cet appareil.
These appliances comply with National Safety Standards and are tested and listed by OMNI-Test Laboratories, Inc. (Report No. 116-F-59-5) to ANSI Z21.88-2009 (in Canada, CSA-2.33-2009), and CAN/CGA-2.17-M91 (R2009) in both USA and Canada, as vented gas fireplace heaters.
These appliances are listed by OMNI-Test Laboratories for installation in bedrooms and Manufactured Homes.
Misc. Codes / Standards
The Installation must conform to local codes or, in the absence of local codes, with the National
Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest edition (In Canada, the current CAN/CSA-B149.1
installation code).
The appliance, when installed, must be electri­cally grounded and wired in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA
70 - latest edition, or the Canadian Electrical Code, CSA C22.1 - latest edition.
Provide adequate clearances around air open­ings and adequate accessibility clearance for service and proper operation. Never obstruct the front or back openings of the appliance.
These appliances are designed to operate on natural or propane gas only. The use of other fuels or combination of fuels will degrade the performance of this system and may be dangerous.
These fireplaces are designed as supplemental heaters; therefore, it is advisable to have an alternate primary heat source when installed in a dwelling.
These appliances must not be connected to a chimney or flue serving a separate solid fuel burning appliance.
These electronic models come standard with a remotely-modulated gas valve; flame appear­ance and heat output cannot be controlled at the gas valve. The BTU Input for these appliances is shown in Table 1.
Input (BTU/HR) Gas Valves (all models)
Models
MPDP35 25,000 high
MPDP40 31,000 high
Table 1
Input Rate (BTU / HR)
Nat. Gas Prop. Gas
22,000 high
16,400 low
20,100 low
18,000 low
29,000 high
22,200 low
3
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
Gas Pressure - All Models
Tables 2 and 3 show the appliances' inlet and manifold gas pressure requirements:
Inlet Gas Supply Pressure
(all models)
Fuel # Minimum Maximum
Natural Gas
Propane
4.5" WC
(1.12 kPa)
11.0" WC
(2.74 kPa)
10.5" WC
(2.61 kPa)
13.0" WC
(3.23 kPa)
Table 2
Manifold Gas Supply Pressure
(all models)
Fuel # Low High
Natural
Gas
Propane
(Lo)
1.6" WC
(0.40 kPa)
(Lo)
6.3" WC
(1.57 kPa)
(Hi) 3.5" WC
(0.87 kPa)
(Hi) 10.0" WC
(2.49 kPa)
Table 3
Test gauge connections are provided on the front of the electronic gas control valve (identi­fied IN for the inlet and OUT for the manifold side). The control valves have a 3/8" (10mm) NPT thread inlet and outlet side of the valve (refer to Figure 1).
Propane tanks are at pressures that will cause damage to valve components. Verify that the tanks have step down regulators to reduce the pressure to safe levels.
The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).
Orifice Sizes - Sea Level to High Altitude (All Models)
Deration - At higher elevations, the amount
of BTU fuel value delivered must be reduced by either:
• Using gas that has been derated by the gas company.
• Changing the burner orifice to a smaller size as regulated by the local authorities having jurisdiction and by the (USA) National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition or, in Canada, the CAN/CSA-B149.1 codes - latest edition.
Flame breadth, height and width will diminish 4% for every 1,000 feet of altitude.
Burner Orifice Sizes
Elevation 0-4500 feet ( 0-1372 meters)
Model Nat.Gas
MPDP35
MPDP40
Table 4
drill size (inches)
#42 (.093")*
H3721•
#36 (.1065")*
18L40•
* Standard size installed at factory
• Part /Cat. Number
Propane
drill size (inches)
#54 (.055")*
99K79•
#52 (.063")*
21L01•
In Canada - CAN/CGA-2.17-M91 (R2009) (high altitude):
THE CONVERSION SHALL BE CARRIED OUT BY A MANUFACTURER’S AUTHO­RIZED REPRESENTATIVE, IN ACCOR­DANCE WITH THE REQUIREMENTS OF THE MANUFACTURER, PROVINCIAL OR TERRITORIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN/CGA-B149.1 OR CAN/CGA-B149.2 INSTALLATION CODES.
Green Wire
(From DFC Wire
Harness)
Manifold (Out)
Test Port
Inlet (In) Test Port
REQUIREMENTS FOR THE COMMON­WEALTH OF MASSACHUSETTS
These fireplaces are approved for installation in the US state of Massachusetts if the following additional requirements are met:
• Install this appliance in accordance with Massachusetts Rules and Regulations 248 C.M.R.
• Installation and repair must be done by a plumber or gas fitter licensed in the Com­monwealth of Massachusetts.
• The flexible gas line connector used shall not exceed 36 inches (92 centimeters) in length.
• The individual manual shut-off must be a T-handle type valve.
Massachusetts Horizontal Vent Requirements In the Commonwealth of Massachusetts, hori-
zontal terminations installed less than seven (7) feet above the finished grade must comply with the following additional requirements:
• A hard wired carbon monoxide detector with an alarm and battery back-up must be installed on the floor level where the gas fireplace is installed. The carbon monoxide detector must comply with NFPA 720, be ANSI/UL 2034 listed and be ISA certified.
• A metal or plastic identification plate must be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade and be directly in line with the horizontal termination. The sign must read, in print size no less than one-half (1/2) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.
Connect GTMS Wire Harness
Pressure Regulator Tower
These appliances are tested and approved for installation at elevations of 0-4500 feet (0-1372 meters) above sea level using the standard burner orifice sizes (marked with an "*" in Table 4).
For elevations above 4500 feet, contact your gas supplier or qualified service technician.
4
Orange Wire
(From DFC Wire
Harness)
Main Gas Inlet
3/8" NPT
Figure 1: SIT Proflame Valve
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Yellow Ground Wire (From DFC Wire Harness)
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room. It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests, if floor is above ground level. Gas line holes and other open­ings should be caulked or stuffed with unfaced fiberglass insulation.
If the fireplace is being installed on a cement slab in cold climates, a sheet of plywood or other raised platform can be placed underneath to prevent conduction of cold transferring to the fireplace and into the room. It also helps to sheetrock inside surfaces and tape for maximum air tightness and caulk firestops.
MANUFACTURED HOME REQUIREMENTS
This appliance may be installed in an aftermar­ket permanently located, manufactured home and must be installed in accordance with the manufacturer's instructions.
Cet appareil peut être installé cómme du matéri-el d'origine dans une maison préfab­riquée (É.U. seulement) ou mobile et doit être installé selon les instructions du fabricant.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
Cet appareil doit être utilisé uniquement avec le type de gaz indiqué sur la plaque signalétique. Cet appareil ne peut être con­verti à d'autres gaz, sauf si une trousse de conversion est utilisée.
CAUTION: Ensure that the cross mem­bers are not cut or weakened during installation. The structural integrity of the manufactured home floor, wall, and ceiling / roof must be maintained.
CAUTION: This appliance must be ground­ed to the chassis of the manufactured home in accordance with local codes or in the absence of local codes, with the National Electrical Code ANSI / NFPA 70
- latest edition or the Canadian Electrical Code CSA C22.1 - latest edition.
REAR VENT
APPLICA
TION
TOP VENT
APPLICA
APPLICATION
TOP VENT
INSTALLATION
VERTICAL VENT (Rear Vent Application)
HORIZONTAL VENT (Rear Vent Application with a chase)
RECESSED
REAR VENT
APPLICATION
TOP VENT
APPLICATION
TOP VENT
APPLICATION
HORIZONTAL VENT (Rear Vent Application without a chase)
TION
TOP VENT
APPLICATION
TOP VENT
APPLICATION
HORIZONTAL VENT (Top Vent Application)
Figure 2: Typical Locations
LOCATION
In selecting the location, the aesthetic and functional use of the appliance are primary concerns. However, vent system routing to the exterior and access to the fuel supply are also important.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies (Figure 2).
En raison des températures élevées, l’appareil devrait être installé dans un endroit où il y a peu de circulation et loin du mobilier et des tentures (Figure 2).
The location should also be free of electrical, plumbing or other heating/air conditioning ducting.
These direct-vent appliances are uniquely suited for installations requiring a utility shelf positioned directly above the fireplace. Util­ity shelves like these are commonly used for locating television sets and decorative plants.
VERTICAL VENT (Top Vent Application)
Be aware that this is a heat producing ap­pliance. Objects placed above the unit are exposed to elevated temperatures.
Do not insulate the space between the ap­pliance and the area above it (see Figure 7).
The minimum height from the base of the appli­ance to the underside of combustible materials used to construct a utility shelf in this fashion is shown in Figure 7.
The appliance must be mounted on a fully sup­ported base extending the full width and depth of the unit. The appliance may be located on or near conventional construction materials. However, if installed on combustible materials, such as carpeting, vinyl tile or other combustible material other than wood flooring, the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
5
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
LOWEST DISCHARGE OPENING OF VENT
TERMINATION HEIGHTS FOR VENTS ABOVE
VENT TERMINATION CLEARANCES
These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CSA-B149.1 in Canada.
Vertical Vent Termination Clearances
Terminate multiple vent terminations according to the installation codes listed above and Figures 3 and 4.
12”
(305mm)
Minimum
Vertical Vent Termination Clearances
Horizontal Overhang
2 FT MIN.
Termination
Storm Collar
Flashing
Concentric
Vent Pipe
FLAT OR SLOPED ROOFS
Vent
*H = MINIMUM HEIGHT FROM ROOF TO
2 FT MIN.
Lowest
Discharge
Opening
H*
1 inch (25.4 mm) Minimum Clearance to Combustibles
Vertical Wall
X
12
Roof Pitch is X/12
Figure 4
Horizontal Vent Termination Clearances
The vent / air intake termination clearances above the high side of an angled roof are as shown in the following chart:
Termination Heights For Vents
Above Flat Or Sloped Roofs Ref. NFPA 54 / ANSI Z223.1
Roof Pitch *H (ft) *H (m)
Flat to 6/12 1.0 0.3 6/12 to 7/12 1.25 0.38 7/12 to 8/12 1.5 0.46 8/12 to 9/12 2.0 0.61
9/12 to 10/12 2.5 0.76 10/12 to 11/12 3.25 0.99 11/12 to 12/12 4.0 1.22 12/12 to 14/12 5.0 1.52 14/12 to 16/12 6.0 1.83 16/12 to 18/12 7.0 2.13 18/12 to 20/12 7.5 2.29 20/12 to 21/12 8.0 2.44
Figure 3: Multiple Terminations
The horizontal vent termination must have a minimum of 6" (152 mm) clearance to any overhead combustible projection of 2-1/2" (64 mm) or less (Figure 5). For projections exceeding 2-1/2" (64 mm), see Figure 6. For additional vent location restrictions, refer to Figure 6 on Page 7.
Horizontal Vent Termination Clearances
Combustible Projection
inches or less in length
2-1/2
Combustible Projection greater
than 2-1/2 inches in length
Ventilated
Soffit
Unventilated
Soffit
18"
(457 mm)
12"
(305 mm)
6"
(152 mm)
All horizontal terminations may be located as close as 6” (152mm) to any (non-combustible and combustible) exterior sidewall. This distance may be decreased to 2” (51mm) for non-­combustible exterior sidewalls only, if the SV4.5HT-2 termination is used.
Termination Kit
Side Elevation View
Termination Kit
Note: See Figure 41 on Page 21 for exterior
Figure 5
wall recess allowances for square horizontal termination.
6
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
NOTE: Local Codes Or Regulations
*noitallatsnInaidanaC **noitallatsnISU
.ynoclabro,kced,hcrop,adnarev,edargevobaecnaraelC=A *)mc03(sehcni21 **)mc03(sehcni21
.denepoebyamtahtroodrowodniwotecnaraelC=B secnailpparof)mc51(sehcni6
)mc03(sehcni21,)Wk3(hutB000,01<
)Wk3(hutB000,01>secnailpparof
secnailpparof)mc51(sehcni6
)mc32(sehcni9,)Wk3(hutB000,01<
dna)Wk3(hutB000,01>secnailpparof
)mc03(sehcni21,)Wk51(hutB000,05<
**)Wk51(hutB000,05>secnailpparof
wodn
iwdesolcyltnenamrepotecnaraelC=C otdednemmocer)mm503(sehcni21
noitasnednocwodniwtneverp
otdednemmocer)mm922(sehcni9
noitasnednocwodniwtneverp
ehtevobadetacoltiffosdetalitnevotecnaraelclacitreV=D
)mm854(sehcni81foecnatsidlatnozirohanihtiwnoitanimret
)mm854(sehcni81 )mm854(sehcni81
tiffosdetalitnevnuotecnaraelC=E )mm503(sehcni21 )mm503(sehcni21
renrocedistuootecnaraelC=F muminim)mc7.21(sehcni5 muminim)mc7.21(sehcni5
renrocedisniotecnaraelC=G •2-TH5.4VS-muminim)mc80.5(sehcni2
SSTH5.4VS-muminim)mc2.51(sehcni6
•2-TH5.4VS-muminim)mc80.5(sehcni2
SSTH5.4VS-muminim)mc2.51(sehcni6
evobadednetxeenilretnecfoedisnihcaeotecnaraelC=H
ylbmessarotaluger/retem
teef51fothgiehanihtiw)mc19(teef3
*ylbmessarotaluger/retemehtevoba
teef51fothgiehanihtiw)mc19(teef3
**ylbmessarotaluger/retemehtevoba
teltuotnevrotalugerecivresotecnaraelC=I *)mc19
(teef3 **)mc19(teef3
rognidliubottelniylppusrialacinahcemnonotecnaraelC=J
ecnailpparehtoynaottelnirianoitsubmoceht
secnailpparof)mc51(sehcni6
)mc03(sehcni21,)Wk3(hutB000,01<
)Wk3(hutB000,01>secnailpparof
secnailpparof)mc51(sehcni6
)mc32(sehcni9,)Wk3(hutB000,01<
dna)Wk3(hutB000,01>secnailpparof
)mc03(sehcni21,)Wk51(hutB000,05<
**)Wk51(hutB000,05>secnailpparof
telniylppusrialacinahcemaotecnaraelC=K *)m38.1(teef6 )
m3(teef01nihtiwfievoba)mc19(teef3
**yllatnoziroh
detacolyaweviddevaproklawedisdevapevobaecnaraelC=L
ytreporpcilbupno
‡)m31.2(teef7 ‡)m31.2(teef7
ynoclabrokced,hcrop,adnarevrednuecnaraelC=M ‡*)mc03(sehcni21 ‡)mc03(sehcni21
)mumixaM(evoclAfohtpeD=N *)m38.1(teef6 **)m38.1(teef6
)evoclA(noitanimreTotecnaraelC=O *)mm2.51(sehcni6 **)mm2.51(sehcni6
)muminiM(evoclAfohtdiW=P *)mc19(teef3 *)mc19(teef3
)evoclA(evobAelbitsubmoCotec
naraelC=Q *)mm754(sehcni81 **)mm754(sehcni81
.edoCnoitallatsnIenaporPdnAsaGlanoitaN1.941B-ASCtnerrucehthtiwecnadroccanI*
.sedoCsaGleuFlanoitaN45APFN/1.322ZSISNAtnerucehthtiwecnadroccanI**
htobsevresdnasgnillewdylimafelgnisowtneewtebdetacolsihcihwyawevirddevaproklawedisaevobayltceridetanimrettonllahstnevA
.sgnillewd
.roolfehthtaenebsedis2muminimanonepoyllufsiynoclabrokced,hcrop,adnarevfidettimrepylnO‡*
.yl
nO2-TH5.4VSrofselbitsubmoC-noNotecnaraelChcni2•
EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS
* See Item D in the Text Below.
Exterior Wall
*18”
Horizontal Termination
Inside Corner
B
V
L
V
6”
Detail D
F
V
A
Ventilated Soffit
V
Fixed
Closed
Window
V
C
X
= Air Supply Inlet
C
C
C
V
Inside
Corner Detail
G
V
A
B
Operable
V
Window
B
B
= Vent Termination
May Require Different Clearances.
NOTE: Location Of The Vent Termination Must Not Interfere With Access To The Electrical Service.
= 9” in U.S.
1
= 12” in Canada
3 ft.
X
1
J
B
= Area where Termination is not Permitted
1
3 ft.
P
N
Q
H
M
V
I
N
O
V
D
E
V
X
K
Figure 6
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
7
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
12 (305) MANTEL
10 (254) MANTEL
8 (203) MANTEL
6 (152) MANTEL
4 (102) MANTEL
6
(152)
16
(406)
14
(356)
12
(305)
2 (51) MANTEL
TOP OF APPLIANCE
8
(203)
10
(254)
MANTEL CLEARANCES
Inches (mm)
NOTE: Hood shown.
MINIMUM CLEARANCES TO COMBUSTIBLES
Appliance And Vent Clearances
The appliance is approved with zero clearance to combustible materials on all sides (as detailed in Table 5).
MINIMUM CLEARANCES* Inches (millimeters)
Back 1/2 (13)
0 (0) from Spacers Or Dimples
Sides 1/2 (13)
0 (0) from Spacers Or Dimples **
Top of Fireplace 4 (102)
Floor 0 (0)
From Bottom of Unit To Ceiling 64 (1626)
Vent 3 (76) Top* / 1 (25.4) Sides & Bottom
SERVICE CLEARANCES Feet (meters)
Front 3 feet (0.9 meters)
Table 5
*Note: 3 in. (75 mm) above any horizontal/inclined vent component.
**Note: See Page 9, Step 1 for clearance requirements to the nailing flange located at each side of the unit and any screw heads adjacent to it.
Combustible Shelf Height - inches (millimeters)
Models
MPDP35 MPDP40
Do not insulate the space between the appliance and the area above it.
Shelf Height
(see table)
Shelf Above Fireplace With Rear Venting
Figure 7:
Top Vent with 1-foot section
and one 90-degree elbow
®
Secure Vent 55-7/8 (1419) 57-5/8 (1464) 36-1/4 (921) 36-1/4 (921) 60-7/8 (1546) 62-5/8 (1591) 41-1/4 (1048) 41-1/4 (1048)
Secure Flex®Secure Vent Secure Flex
Shelf Height Minimum Clearances
Rear Vent
(straight out the back)
Do not insulate the space between the ap­pliance and the area above it.
Shelf Height
(see table)
Shelf Above Fireplace With Top Venting
Min. 1 ft. section required.
Hearth Extension - A hearth extension is not required with this appliance.
If a hearth extension is used, do not block the lower control compartment door. Any hearth extension used is for appearance only and does not have to conform to standard hearth extension installation requirements.
Shelf Height - To provide for the lowest possible shelf surface, use the
alternate rear vent outlet, the venting attached to the top vent should be routed in a way to minimize obstructions to the space above the appliance.
Do not insulate the space between the appliance and the area above it (see Figure 7). The minimum height from the base of the appliance to
the underside of combustible materials used to construct a utility shelf in this fashion is shown in Figure 7.
Wall Finishes / Surrounds / Mantels
Note: Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined by the appliance front face (black sheet metal). Never allow combustible materials to be positioned
in front of or overlapping the appliance face (see Figure 62 on Page 34). Non-combustible materials, such as surrounds and other appliance trim,
may be installed on the appliance face with these exceptions: they must not cover any portion of the removable glass panel or control compartment.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel. See Figure 8. Mantels constructed of non­combustible materials may be installed at any height above the appliance opening; however, do not allow anything to hang below the fireplace hood.
Minimum clearance requirements include any projections such as shelves, window sills, mantels, etc. above the appliance.
NOTE: We recommend the use of high temperature paint (rated 175° F or higher) on the underside of the mantel.
8
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Inches (millimeters)
Figure 8: Minimum Mantel Clearances
At 6" minimum side wall clearance, a combustible wall can project to any
Top View of
Fireplace
length.
o
45
3-1/2
Combustible Materials Allowed In Shaded Area
(89)
“Safe Zone”
Combustible Walls shown in dark gray
Combustible materials may project beyond either side of the fireplace opening as long as they are kept within the shaded area illustrated here.
Inches (millimeters)
(152)
6
Figure 9: Minimum Distance to Side Wall
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
Side
Framing
Unit Nailing Flange
(No clearance to combustible framing is required.)
Unit Secured to Framing
by Nailing Flange
Header Spacing Top Standoffs
(two pairs on front edge of firebox top)
Lift up outer pair for 1/2" finish materials.
Lift up inner pair for 5/8" finish materials.
Left Side Front Corner of Fireplace Shown
(Right side requirements are the same)
PRE-INSTALLATION STEPS
The appliance is shipped with all gas controls and components installed and pre-wired.
Before installing the fireplace, follow these steps:
1. Remove the shipping carton.
2. Remove the shipping pad, exposing the front glass door.
3. Open the two spring latches securing the glass door (under the firebox floor). Remove the door by tilting it outward at the bottom and lifting it up. Set aside the door, taking care to protect it from inadvertent damage
(see Removing and Installing the Glass Door on Page 32).
4. Remove the log set and top vent flue restrictor from the firebox. Handle logs
carefully to prevent breakage.
5. Remove the embers and volcanic stone from the control compartment.
6. Remove top standoff and hood (taped to back of outer wrapper).
7. Remove the 4 screws on top, and install the top standoff with the 4 screws (Figure 10).
IMPORTANT!
Install top standoff
and bend up appropriate
drywall backstops (1/2" or 5/8")
before installing fireplace.
Top Standoff (installed)
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation is outlined below; however, each installation is unique and may result in variations to the steps described.
See the pages referenced in the following steps for detailed procedures.
Step 1. FRAMING (Page 9): Construct the ap- pliance framing. Position the appliance within the framing and secure with nailing brackets.
IMPORTANT! Before installing the fireplace, install the top standoff on the top front edge of the fireplace using the 4 existing screws on the fireplace top (see Figure 10). Then, bend up the applicable drywall backstops on the top standoff (1/2" or 5/8"), based on the thickness of the drywall/finish material to be used (see Figure 10).
Bend out the appropriate side nailing flanges for the drywall/finish material to be used. Nailing flanges are provided for flush framing, 1/2-inch and 5/8-inch framing depths (see Figure 11).
Step 2. ROUTING GAS LINE (Page 11): Route gas supply line to appliance location.
Step 3. PREPARING APPLIANCE VENT COLLAR
(Page 12).
Step 4. INSTALLING VENT SYSTEM (Page 12): Install the vent system and exterior termination.
Step 5. FIELD WIRING (Page 26): Field wire and install operating control switch.
Step 6. REMOTE CONTROL SYSTEM (Page
27).
DETAILED INSTALLATION STEPS Step 1. FRAMING
Frame the appliance as illustrated in Figures 12 and 13 on Pages 10 and 11 (Figure 13
applies to corner framing installations only). All framing details must allow for a minimum clearance to combustible framing members as shown in Table 5 on Page 8.
If the appliance is to be elevated above floor level, a solid continuous platform must be constructed below the appliance.
Headers may be in direct contact with the ap­pliance top standoff spacer, maintaining the 4" clearance to the fireplace top, but must not be
supported by them or notched to fit around them. All construction above the appliance must be self-supporting. DO NOT use the ap- pliance for structural support.
Secure the fireplace to the side framing members using the unit’s nailing flanges — one top and bottom on each side of the fireplace front. See
Figure 11. Use 8d nails or their equivalent.
Figure 10
Drywall Backstops (bent up for 1/2" or 5/8")
Step 7. CONNECTING GAS LINE (Page 28):
Make connection to gas supply.
Step 8. VERIFYING APPLIANCE OPERATION (Page 28).
Step 9. INSTALL LOGS, VOLCANIC STONE, AND GLOWING EMBERS (Page 29).
Step 10. INSTALLING GLASS DOOR ASSEM­BLY (Page 32).
Step 11. BURNER ADJUSTMENTS (Page 32):
Adjust burner to ensure proper flame appear­ance.
Step 12. HOOD INSTALLATION (Page 34).
Step 13. ATTACHING SAFETY-IN-OPERATION WARNINGS (Page 35).
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
NOTE: The nailing flanges, combustible members, and screw heads in areas directly adjacent to the nailing flanges are EXEMPT from the 1/2" clearance to combustible requirements for the firebox outer wrapper.
Combustible framing may be in direct contact with the nailing flanges and may be located closer than 1/2" from screw heads and the firebox wrapper in areas adjacent to the nailing flanges.
Frame the opening to the exact dimensions specified in the framing details in this manual.
Figure 11
9
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
FIREPLACE AND FRAMING SPECIFICATIONS
Framing
Model No. A B C D E
in. 35-1/4 36-1/4 21-11/16 49 16
MPDP35
mm 895 921 551 1245 406
in. 40-1/4 41-1/4 26-11/16 54 16
MPDP40
Diagrams, illustrations and photographs are not to scale. Consult installation instructions. Product designs, materials, dimensions, specifications, colors, and prices are subject to change or discontinuance without notice.
Fireplace
Model
(Rear Vent)
MPDP35 70 69 70 71 MPDP40 71 70 71 72
Based on CSA P.4.1-09
mm 1022 1048 678 1372 406
Notes
Efficiencies %
Natural Gas Propane
AFUE
EnerGuide
(P4)
Rear/Side
Framing
Spacers
Standoff
AFUE
Top
EnerGuide
(P4)
G
H
VENT FRAMING: REAR VENT with no elbows
B
Concentric Flue*: Flue =
4-1/2" (114 mm);
Combustion Air = (190 mm).
J
VENT FRAMING: TOP VENT with 1 ft. of pipe and 90-degree elbow
A
1/2
7-1/2"
Framing should be
)
7
(178)
7
(178)
constructed of 2x4 or larger lumber.
12-1/8
(308)
12-1/8
(308)
10-1/2
(
267
5-1/8 (130)
5-1/8
D
(130)
C
E
A
Dimension “E” is required framing depth when finish material (drywall) thickness is 1/2 in. (13mm).
Inches (mm)
10
Top View
E
Top Standoff
A
C
D
4" (102 mm)
Gas Inlet (either
side and bottom)
Optional Electrical Inlet
Knockout (either side;
B
requires field-provided
Eyebrow Hood
Front View
*All MPDP models have a top and rear vent.
N
6"(152 mm)
L
junction box)
1-3/8" (35 mm)
K
Right Side View
Model No. A B C D E F G H J K L M N
in. 36-1/8 32-1/8 19 29-1/2 35-1/8 21-11/16 24-7/8 12-7/16 9 3 9 3 16
MPDP35
mm 918 816 483 749 892 551 632 316 220 76 220 76 406
in. 41-1/8 37-1/8 24 34-1/2 40-1/8 26-11/16 29-7/8 14-15/16 9 3 9 3 16
MPDP40
mm 1045 943 610 876 1019 678 759 379 220 76 220 76 406
Figure 12
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
1/2" (13 mm)
Framing Spacer
F
1-5/8"
M
Electrical Inlet Cover Plate 2" x 2-3/4"
(51 x 70 mm)
with Knockout
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
FIREPLACE FRAMING SPECIFICATIONS
Model No. A B C D E F
MPDP35
MPDP40
Note:
• Rear Vent Applications in Corner Installations: The horizontal vent length
(from a to b) must not exceed 28 inches (711 mm).
• MPDP35 and MPDP40: Dimensions D through F apply when one 45-degree
elbow is connected directly to the appliance collar.
in. 35-1/8 57-1/2 40-5/8 19-3/16 28-3/4 6-1/8
mm 892 1461 1032 487 730 156
in. 40-1/8 61-3/16 43-11/32 19-3/16 30-11/16 7-7/8
mm 1019 1554 1101 487 779 200
Figure 13: Corner Framing with Horizontal Termination
Step 2. ROUTING GAS LINE
Route a 1/2" (13 mm) gas line to the left side of the appliance as shown in Figure 14. Gas lines must be routed, constructed and made of materials that are in strict accordance with local codes and regulations. All appliances are factory-equipped with a flexible gas line connector and 1/2-inch shutoff valve (see Step 7 on Page 28).
Never use galvanized or plastic pipe. Refer to Table 6 for proper sizing of the gas supply line, if black iron pipe is being used. Gas lines must be routed, constructed and made of materials that are in strict accordance with local codes and regulations. We recommend that a quali­fied individual such as a plumber or gas fitter be hired to correctly size and route the gas supply line to the appliance. Installing a gas supply line from the fuel supply to the appliance involves numerous considerations of materials,
Left Side Front
Corner of Fireplace
Framing
protection, sizing, locations, controls, pressure, sediment, and more. Certainly no one unfamil­iar and unqualified should attempt sizing or installing gas piping.
Pipe Coupling
(Recommended)
6-1/2"
(152 mm)
Inside Diameter (Inches)
Schedule 40 Pipe
3"
(76 mm)
Also see Figure 12.
Length (feet)
0-10 1/2 3/8
10-40 1/2 1/2
40-100 1/2 1/2
Figure 14: Route Gas Line
100-150 3/4 1/2 150-200 3/4 1/2
Proper Sizing of Gas Line
Table 6
Properly size and route the gas supply line from the supply regulator to the area where the appliance is to be installed per requirements outlined in the National Fuel Gas Code, NFPA 54 - latest edition (USA) or CAN/CSA-B149.1
- latest edition (Canada).
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Schedule 40
Black Iron Pipe
Natural
Gas
b
Rear Vent
F
Top Vent
C
7" (178 mm)
D
a
A
B
Back wall of chase/enclosure (including any finishing materials)
Notes:
• All appliances are factory-equipped with a flexible gas line connector and 1/2 inch shutoff valve (see Figure 52 on Page 28).
• See Massachusetts Requirements on Page 4 for additional requirements for installations in the state of Massachusetts in the USA.
• The gas supply line should Not be connected to the appliance until Step 7 on Page 28.
• A pipe joint compound rated for gas should be used on the threaded joints. Ensure propane
resistant compounds are used in propane applications. Be very careful that the pipe
compound does not get inside the pipe.
• It is recommended to install a sediment trap in the supply line as close as possible to the appliance.
Propane
Gas
• Check with local building official for local code requirements (i.e. are below grade penetrations of the gas line allowed?, etc).
IMPORTANT: If propane is used, be aware that if tank size is too small (i.e. under 100-lbs, if this is the only gas appliance in the dwelling. Ref. NPFA 58), there may be loss of pressure, resulting in insufficient fuel delivery (which can result in sooting, severe delayed ignition or other malfunctions). Any damage resulting from an improper installation, such as this, is not covered under the limited warranty.
E
11
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
Step 3. PREPARING APPLIANCE VENT COLLAR
The unit’s top and rear vent collars are each sealed with a cover plate and gasket. The cover plate and gasket must be removed from the ap­plicable vent collar being used. Refer to Page 13 for rear vent applications and Page 14 for top vent applications. Also refer to the following steps to prepare the appropriate collar for use.
From the vent collar being used, remove the four screws securing the cover plate and gasket. Discard the cover plate and gasket. Reinstall all four screws and tighten securely.
WARNING
Vent cover plate and vent seal cap must remain securely installed on unused vent collar. Failure to reinstall and securely tighten cover plate screws could result in leakage of flue products into the living space.
Step 4. INSTALLING VENT SYSTEM
These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CSA-B149.1 in Canada.
Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier.
Dégagement conforme aux codes d'installa­tion locaux et aux exigences du foumis­seunde gaz.
Use only approved vent components (see Approved Vent Components on Page 2).
NOTE: These fireplaces must be vented directly to the outside.
The vent system may not service multiple appliances, and must never be connected to a flue serving a separate solid fuel burning appli­ance. The vent pipe is tested to be run inside an enclosed wall (such as a chase). There is no requirement for inspection openings in the enclosing wall at any of the joints in the vent pipe.
12
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Loading...
+ 28 hidden pages