AVERTISSEMENT : Assurez-vous de bien suivre les
instructions données dans cette notice pour réduire au
minimum le risque d’incindie ou d’explosion ou pour
éviter tout dommage matériel, toute blessure ou la mort.
WARNING: If the information in these instructions
is not followed exactly, a fire or explosion may
result, causing property damage, personal injury,
or death.
WARNING /AVERTISSEMENT/AVISO
• HOT GLASS WILL CAUSE
BURNS.
• DO NOT TOUCH GLASS
UNTIL COOLED.
• NEVER ALLOW CHILDREN
TO TOUCH GLASS.
• UNE SURFACE VITRÉE CHAUDE
PEUT CAUSER DES BRÛLURES.
• LAISSER REFROIDIR LA SURFACE
VITRÉE AVANT D'Y TOUCHER.
• NE PERMETTEZ JAMAIS À UN ENFANT
DE TOUCHER LA SURFACE VITRÉE.
• EL VIDRIO CALIENTE
CAUSARÁ QUEMADURAS.
• USTED DEBE NUNCA
TOCAR EL VIDRIO CALIENTE.
• LOS NIÑOS DEBEN NUNCA
TOCAR EL VIDRIO.
- Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the fire
department.
- Installation and service must be performed by a
qualified installer, service agency or the gas supplier.
- Ne pas entreposer ni utilizer d’essence ni d’autres vapeurs
ou liquides inflammables dans le voisinage de cet appareil
ou de tout autre appareil.
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucan interrupteur. Ne pas vous servir des
téléphones se trouvant dans le bâtiment où vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis
un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service des incindies.
- L’installation et l’entretien doivent être assurés par un
installateur ou un service d’entretien qualifié ou par le
fournisseur de gaz.
MPD Pro Direct-Vent
Gas Fireplaces
P/N 506015-06 Rev. NC 06/2012
This manual is one of a set of two supporting this product.
Refer to P/N 506017-05 for Care and Operation Instructions.
Ce manuel est disponible en francais, simplement
en faire la demande. Numéro de la pièce 506223-39.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
INSTALLATEUR : Laissez cette notice avec l’appareil.
CONSOMMATEUR : Conservez cette notice pour
consultation ultérieure.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile
home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating
plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
MODELS
US
OTL Report No. 116-F-59-5
Please read and understand these instructions
before starting installation.
MPDP35IN
MPDP40IN
Portland
ELECTRONIC:
MPDP35IP
MPDP40IP
Page 2
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
Please read and understand these
instructions before beginning your
installation.
2
PACKAGING
The assembled vented gas fireplace heater is
packaged with:
• (1 set) Logs (packaged in a carton inside the
firebox).
• (1 bag) Glowing Embers and (1 bag) Volcanic
Stone (in bottom compartment).
• Literature Kit (envelope in bottom com-
partment containing Care and Operation Instructions, Installation Instructions, Safety-
In-Operation Warning Labels w/instructions,
Warranty).
• (1) Top Vent Flue Restrictor
• (1) Rear Vent Restrictor Plate
• (1) U-shaped Vent Restrictor
• (1) Top Standoff (taped to outer wrapper)
• (1) Hood (taped to outer wrapper)
• (1) Remote Control Kit and Receiver Kit
Required Firebox Liner Kits
(One of the following kits must be installed
- sold separately)
• H8572 - Black Porcelain, MPDP35
• H8573 - Black Porcelain, MPDP40
• H8595 - Brickaded, MPDP35
• H8596 - Brickaded, MPDP40
INTRODUCTION
These Electronic appliances are designed to
operate on natural or propane gas. The system
is switchable between standing and intermittent pilot modes. External electrical power is
required to operate these units. In the event
of a power outage, four (4) "AA" batteries (in
receiver) can be used as a backup (excluding
blower operation).
These vented gas fireplace heaters are sealed
combustion, air-circulating gas fireplaces designed for residential applications.
Approved Vent Components
These fireplaces are designed, tested and listed
for operation and installation with the following
vent components only:
®
•Secure Vent
nents manufactured by Security Chimneys
International,
•Secure Flex
manufactured by Security Chimneys International and
•Z-FLEX
to UL1777 and ULCS635 manufactured by
Flexmaster Canada Limited.
Use only the correct size venting (4-1/2" inner
and 7-1/2" outer).
These approved vent system components are
labeled for identification. DO NOT use any
other manufacturer’s vent components with
these appliances.
Direct-Vent System Compo-
®
Flexible Vent Components
®
Model GA Venting Systems listed
GENERAL INFORMATION
WARNING
Young children should be carefully supervised when they are
in the same room as the appliance. Toddlers, young children
and others may be susceptible
to accidental contact burns. A
physical barrier is recommended
if there are at risk individuals in
the house. To restrict access to
a fireplace or stove, install an
adjustable safety gate to keep
toddlers, young children and
other at risk individuals out of
the room and away from hot
surfaces.
AVERTISSEMENT
Les jeunes enfants devraient être
surveillés étroitement lorsqu’ils
se trouvent dans la même pièce
que l’appareil. Les tout petits,
les jeunes enfants ou les adultes
peuvent subir des brûlures s’ils
viennent en contact avec la surface chaude. Il est recommandé
d’installer une barrière physique
si des personnes à risques habitent la maison. Pour empêcher
l’accès à un foyer ou à un poêle,
installez une barrière de sécurité; cette mesure empêchera les
tout petits, les jeunes enfants et
toute autre personne à risque
d’avoir accès à la pièce et aux
surfaces chaudes.
Children and adults should be alerted to the
hazards of high surface temperature and
should stay away to avoid burns or clothing
ignition.
Les enfants et les adultes devraient être
infor-més des dangers que posent les
températures de surface élevées et se
tenir à distance afin d’éviter des brûlures
ou que leurs vêtements ne s’enflamment.
DO NOT ATTEMPT TO ALTER OR MODIFY
THE CONSTRUCTION OF THE APPLIANCE
OR ITS COMPONENTS. ANY MODIFICATION
OR ALTERATION MAY VOID THE WARRANTY,
CERTIFICATION AND LISTINGS OF THIS UNIT.
Page 3
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
WARNING
Improper installation, adjustment, alteration, service or
maintenance can cause injury
or property damage. Refer to
this manual. For assistance or
additional information consult
a qualified installer, service
agency or the gas supplier.
WARNING
Failure to comply with these
installation instructions will result
in an improperly installed and
operating appliance, voiding its
warranty. Any change to this appliance and/or its operating controls
is dangerous.
WARNING
Clothing or other flammable
material should not be placed
on or near the appliance.
AVERTISSEMENT
On ne devrait pas placer de
vêtements ni d’autres matières
inflammables sur l’appareil ni à
proximité.
WARNING
Any safety screen or guard
removed for servicing the appliance must be replaced prior to
operating the appliance.
AVERTISSEMENT
Tout écran ou protecteur retiré
pour permettre l’entretien de
l’appareil doit être remis en
place avant de mettre l’appareil
en marche.
WARNING
Improper installation or use of
this appliance can cause serious
injury or death from fire, burns,
explosion or carbon monoxide
poisoning.
WARNING
Failure to position the parts in
accordance with these diagrams
or failure to use only parts specifically approved with this appliance
may result in property damage or
personal injury.
AVERTISSEMENT
Risque de dommages ou de
blessures si les pièces ne sont
pas installées conformément à
ces schémas et ou si des pièces
autres que celles spécifiquement
approuvées avec cet appareil sont
utilisées.
Note: Installation and repair should be done
by a qualified service person. The appliance
should be inspected before use and at least
annually by a professional service person.
More frequent cleaning may be required due
to excessive lint from carpeting, bedding
material, etcetera. It is imperative that control
compartments, burners and circulating air
passageways of the appliance be kept clean.
Remarque: L’installation et la réparation
devrait être confiées à un technicien qualifié. L’appareil devrait faire l’objet d’une
inspection par un technicien professionnel
avant d’être utilisé et au moins une fois
l’an par la suite. Des nettoyages plus
fréquents peuvent être nécessaires si les
tapis, la literie, et cetera produisent une
quantité importante de pous-sière. Il est
essentiel que les compartiments abritant
les commandes, les brûleurs et les conduits de circulation d’air de l’appareil
soient tenus propres.
Do not use these appliances if any part
has been under water. Immediately call a
qualified, professional service technician
to inspect the appliance and to replace
any parts of the control system and any
gas control which have been under water.
Ne pas utiliser cet appareil s’il a été
plongé, même partiellement, dans
l’eau. Appeler un technicien qualifié
pour inspecter l’appareil et remplacer
toute partie du système de commande
et toute commande qui a été plongée
dans l’eau.
Only trim kit(s) supplied by the manufacturer
shall be used in the installation of this appliance.
Seules les trousses de garniture fournies
par le fabricant doivent être utilisées pour
l’installation de cet appareil.
These appliances comply with National
Safety Standards and are tested and listed
by OMNI-Test Laboratories, Inc. (Report No.
116-F-59-5) to ANSI Z21.88-2009 (in Canada,
CSA-2.33-2009), and CAN/CGA-2.17-M91
(R2009) in both USA and Canada, as vented
gas fireplace heaters.
These appliances are listed by OMNI-Test
Laboratories for installation in bedrooms
and Manufactured Homes.
Misc. Codes / Standards
The Installation must conform to local codes or,
in the absence of local codes, with the National
Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest
edition (In Canada, the current CAN/CSA-B149.1
installation code).
The appliance, when installed, must be electrically grounded and wired in accordance with
local codes or, in the absence of local codes,
with the National Electrical Code, ANSI/NFPA
70 - latest edition, or the Canadian Electrical
Code, CSA C22.1 - latest edition.
Provide adequate clearances around air openings and adequate accessibility clearance for
service and proper operation. Never obstruct
the front or back openings of the appliance.
These appliances are designed to operate on
natural or propane gas only. The use of other
fuels or combination of fuels will degrade
the performance of this system and may be
dangerous.
These fireplaces are designed as supplemental
heaters; therefore, it is advisable to have an
alternate primary heat source when installed
in a dwelling.
These appliances must not be connected to a
chimney or flue serving a separate solid fuel
burning appliance.
These electronic models come standard with a
remotely-modulated gas valve; flame appearance and heat output cannot be controlled at the
gas valve. The BTU Input for these appliances
is shown in Table 1.
Input (BTU/HR) Gas Valves (all models)
Models
MPDP3525,000 high
MPDP4031,000 high
Table 1
Input Rate (BTU / HR)
Nat. GasProp. Gas
22,000 high
16,400 low
20,100 low
18,000 low
29,000 high
22,200 low
3
Page 4
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
Gas Pressure - All Models
Tables 2 and 3 show the appliances' inlet and
manifold gas pressure requirements:
Inlet Gas Supply Pressure
(all models)
Fuel #MinimumMaximum
Natural Gas
Propane
4.5" WC
(1.12 kPa)
11.0" WC
(2.74 kPa)
10.5" WC
(2.61 kPa)
13.0" WC
(3.23 kPa)
Table 2
Manifold Gas Supply Pressure
(all models)
Fuel #LowHigh
Natural
Gas
Propane
(Lo)
1.6" WC
(0.40 kPa)
(Lo)
6.3" WC
(1.57 kPa)
(Hi) 3.5" WC
(0.87 kPa)
(Hi) 10.0" WC
(2.49 kPa)
Table 3
Test gauge connections are provided on the
front of the electronic gas control valve (identified IN for the inlet and OUT for the manifold
side). The control valves have a 3/8" (10mm)
NPT thread inlet and outlet side of the valve
(refer to Figure 1).
Propane tanks are at pressures that will cause
damage to valve components. Verify that the
tanks have step down regulators to reduce the
pressure to safe levels.
The appliance and its appliance main gas
valve must be disconnected from the gas
supply piping system during any pressure
testing of that system at test pressures in
excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the
gas supply piping system by closing its
equipment shutoff valve during any pressure
testing of the gas supply piping system at
test pressures equal to or less than 1/2 psi
(3.5 kPa).
Orifice Sizes - Sea Level to High Altitude
(All Models)
Deration - At higher elevations, the amount
of BTU fuel value delivered must be reduced
by either:
• Using gas that has been derated by the gas
company.
• Changing the burner orifice to a smaller size
as regulated by the local authorities having
jurisdiction and by the (USA) National Fuel Gas
Code NFPA 54/ANSI Z223.1 - latest edition or,
in Canada, the CAN/CSA-B149.1 codes - latest
edition.
Flame breadth, height and width will diminish
4% for every 1,000 feet of altitude.
Burner Orifice Sizes
Elevation 0-4500 feet ( 0-1372 meters)
ModelNat.Gas
MPDP35
MPDP40
Table 4
drill size (inches)
#42 (.093")*
H3721•
#36 (.1065")*
18L40•
* Standard size installed at factory
• Part /Cat. Number
Propane
drill size (inches)
#54 (.055")*
99K79•
#52 (.063")*
21L01•
In Canada - CAN/CGA-2.17-M91 (R2009)
(high altitude):
THE CONVERSION SHALL BE CARRIED
OUT BY A MANUFACTURER’S AUTHORIZED REPRESENTATIVE, IN ACCORDANCE WITH THE REQUIREMENTS OF
THE MANUFACTURER, PROVINCIAL OR
TERRITORIAL AUTHORITIES HAVING
JURISDICTION AND IN ACCORDANCE
WITH THE REQUIREMENTS OF THE
CAN/CGA-B149.1 OR CAN/CGA-B149.2
INSTALLATION CODES.
Green Wire
(From DFC Wire
Harness)
Manifold (Out)
Test Port
Inlet (In) Test Port
REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
These fireplaces are approved for installation in
the US state of Massachusetts if the following
additional requirements are met:
• Install this appliance in accordance with
Massachusetts Rules and Regulations 248
C.M.R.
• Installation and repair must be done by a
plumber or gas fitter licensed in the Commonwealth of Massachusetts.
• The flexible gas line connector used shall
not exceed 36 inches (92 centimeters) in
length.
• The individual manual shut-off must be a
T-handle type valve.
Massachusetts Horizontal Vent Requirements
In the Commonwealth of Massachusetts, hori-
zontal terminations installed less than seven
(7) feet above the finished grade must comply
with the following additional requirements:
• A hard wired carbon monoxide detector
with an alarm and battery back-up must be
installed on the floor level where the gas
fireplace is installed. The carbon monoxide
detector must comply with NFPA 720, be
ANSI/UL 2034 listed and be ISA certified.
• A metal or plastic identification plate must
be permanently mounted to the exterior of
the building at a minimum height of eight (8)
feet above grade and be directly in line with
the horizontal termination. The sign must
read, in print size no less than one-half (1/2)
inch in size, GAS VENT DIRECTLY BELOW.
KEEP CLEAR OF ALL OBSTRUCTIONS.
Connect GTMS
Wire Harness
Pressure
Regulator
Tower
These appliances are tested and approved for
installation at elevations of 0-4500 feet (0-1372
meters) above sea level using the standard burner
orifice sizes (marked with an "*" in Table 4).
For elevations above 4500 feet, contact your
gas supplier or qualified service technician.
4
Orange Wire
(From DFC Wire
Harness)
Main Gas Inlet
3/8" NPT
Figure 1: SIT Proflame Valve
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Yellow Ground Wire
(From DFC Wire
Harness)
Page 5
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks
around your appliance with noncombustible
material and wherever cold air could enter
the room. It is especially important to insulate
outside chase cavity between studs and under
floor on which appliance rests, if floor is above
ground level. Gas line holes and other openings should be caulked or stuffed with unfaced
fiberglass insulation.
If the fireplace is being installed on a cement
slab in cold climates, a sheet of plywood or
other raised platform can be placed underneath
to prevent conduction of cold transferring to
the fireplace and into the room. It also helps to
sheetrock inside surfaces and tape for maximum
air tightness and caulk firestops.
MANUFACTURED HOME
REQUIREMENTS
This appliance may be installed in an aftermarket permanently located, manufactured home
and must be installed in accordance with the
manufacturer's instructions.
Cet appareil peut être installé cómme du
matéri-el d'origine dans une maison préfabriquée (É.U. seulement) ou mobile et doit être
installé selon les instructions du fabricant.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is
not convertible for use with other gases, unless
a certified kit is used.
Cet appareil doit être utilisé uniquement
avec le type de gaz indiqué sur la plaque
signalétique. Cet appareil ne peut être converti à d'autres gaz, sauf si une trousse de
conversion est utilisée.
CAUTION: Ensure that the cross members are not cut or weakened during
installation. The structural integrity of
the manufactured home floor, wall, and
ceiling / roof must be maintained.
CAUTION: This appliance must be grounded to the chassis of the manufactured
home in accordance with local codes or
in the absence of local codes, with the
National Electrical Code ANSI / NFPA 70
- latest edition or the Canadian Electrical
Code CSA C22.1 - latest edition.
REAR VENT
APPLICA
TION
TOP VENT
APPLICA
APPLICATION
TOP VENT
INSTALLATION
VERTICAL VENT
(Rear Vent Application)
HORIZONTAL VENT
(Rear Vent Application with a chase)
RECESSED
REAR VENT
APPLICATION
TOP VENT
APPLICATION
TOP VENT
APPLICATION
HORIZONTAL VENT
(Rear Vent Application without a chase)
TION
TOP VENT
APPLICATION
TOP VENT
APPLICATION
HORIZONTAL VENT
(Top Vent Application)
Figure 2: Typical Locations
LOCATION
In selecting the location, the aesthetic and
functional use of the appliance are primary
concerns. However, vent system routing to
the exterior and access to the fuel supply are
also important.
Due to high temperatures, the appliance
should be located out of traffic and away from
furniture and draperies (Figure 2).
En raison des températures élevées,
l’appareil devrait être installé dans un
endroit où il y a peu de circulation et loin
du mobilier et des tentures (Figure 2).
The location should also be free of electrical,
plumbing or other heating/air conditioning
ducting.
These direct-vent appliances are uniquely
suited for installations requiring a utility shelf
positioned directly above the fireplace. Utility shelves like these are commonly used for
locating television sets and decorative plants.
VERTICAL VENT
(Top Vent Application)
Be aware that this is a heat producing appliance. Objects placed above the unit are
exposed to elevated temperatures.
Do not insulate the space between the appliance and the area above it (see Figure 7).
The minimum height from the base of the appliance to the underside of combustible materials
used to construct a utility shelf in this fashion
is shown in Figure 7.
The appliance must be mounted on a fully supported base extending the full width and depth of
the unit. The appliance may be located on or near
conventional construction materials. However,
if installed on combustible materials, such as
carpeting, vinyl tile or other combustible material
other than wood flooring, the appliance shall be
installed on a metal or wood panel extending the
full width and depth of the appliance.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
5
Page 6
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
LOWEST DISCHARGE OPENING OF VENT
TERMINATION HEIGHTS FOR VENTS ABOVE
VENT TERMINATION CLEARANCES
These instructions should be used as a
guideline and do not supersede local codes
in any way. Install venting according to local
codes, these instructions, the current National
Fuel Gas Code (ANSI-Z223.1) in the USA or
the current standards of CAN/CSA-B149.1
in Canada.
Vertical Vent Termination Clearances
Terminate multiple vent terminations according to
the installation codes listed above and Figures 3 and 4.
12”
(305mm)
Minimum
Vertical Vent Termination Clearances
Horizontal Overhang
2 FT MIN.
Termination
Storm Collar
Flashing
Concentric
Vent Pipe
FLAT OR SLOPED ROOFS
Vent
*H = MINIMUM HEIGHT FROM ROOF TO
2 FT
MIN.
Lowest
Discharge
Opening
H*
1 inch (25.4 mm) Minimum
Clearance to Combustibles
Vertical
Wall
X
12
Roof Pitch is X/12
Figure 4
Horizontal Vent Termination Clearances
The vent / air intake termination clearances
above the high side of an angled roof are as
shown in the following chart:
Flat to 6/121.00.3
6/12 to 7/121.250.38
7/12 to 8/121.50.46
8/12 to 9/122.00.61
9/12 to 10/122.50.76
10/12 to 11/123.250.99
11/12 to 12/124.01.22
12/12 to 14/125.01.52
14/12 to 16/126.01.83
16/12 to 18/127.02.13
18/12 to 20/127.52.29
20/12 to 21/128.02.44
Figure 3: Multiple Terminations
The horizontal vent termination must have a minimum of 6" (152 mm) clearance to any overhead
combustible projection of 2-1/2" (64 mm) or less (Figure 5). For projections exceeding 2-1/2" (64
mm), see Figure 6. For additional vent location restrictions, refer to Figure 6 on Page 7.
Horizontal Vent Termination Clearances
Combustible Projection
inches or less in length
2-1/2
Combustible Projection greater
than 2-1/2 inches in length
Ventilated
Soffit
Unventilated
Soffit
18"
(457 mm)
12"
(305 mm)
6"
(152 mm)
All horizontal terminations
may be located as close as
6” (152mm) to any
(non-combustible and
combustible) exterior
sidewall. This distance
may be decreased to 2”
(51mm) for non-combustible exterior
sidewalls only, if the
SV4.5HT-2 termination
is used.
Termination Kit
Side Elevation View
Termination Kit
Note: See Figure 41 on Page 21 for exterior
Figure 5
wall recess allowances for square horizontal
termination.
6
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 7
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
Do not insulate the
space between the appliance and the area
above it.
Shelf Height
(see table)
Shelf Above Fireplace With Top Venting
Min. 1 ft.
section
required.
Hearth Extension - A hearth extension is not required with this appliance.
If a hearth extension is used, do not block the lower control compartment
door. Any hearth extension used is for appearance only and does not
have to conform to standard hearth extension installation requirements.
Shelf Height - To provide for the lowest possible shelf surface, use the
alternate rear vent outlet, the venting attached to the top vent should be
routed in a way to minimize obstructions to the space above the appliance.
Do not insulate the space between the appliance and the area above
it (see Figure 7). The minimum height from the base of the appliance to
the underside of combustible materials used to construct a utility shelf in
this fashion is shown in Figure 7.
Wall Finishes / Surrounds / Mantels
Note: Combustible wall finish materials and/or surround materials must
not be allowed to encroach the area defined by the appliance front face
(black sheet metal). Never allow combustible materials to be positioned
in front of or overlapping the appliance face (see Figure 62 on Page 34).
Non-combustible materials, such as surrounds and other appliance trim,
may be installed on the appliance face with these exceptions: they must not
cover any portion of the removable glass panel or control compartment.
Vertical installation clearances to combustible mantels vary according
to the depth of the mantel. See Figure 8. Mantels constructed of noncombustible materials may be installed at any height above the appliance
opening; however, do not allow anything to hang below the fireplace hood.
Minimum clearance requirements include any projections such as shelves,
window sills, mantels, etc. above the appliance.
NOTE: We recommend the use of high temperature paint (rated 175° F
or higher) on the underside of the mantel.
8
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Inches (millimeters)
Figure 8: Minimum Mantel Clearances
At 6" minimum
side wall clearance,
a combustible wall
can project to any
Top View of
Fireplace
length.
o
45
3-1/2
Combustible Materials
Allowed In Shaded Area
(89)
“Safe Zone”
Combustible Walls
shown in dark gray
Combustible materials may
project beyond either side
of the fireplace opening
as long as they are kept
within the shaded area
illustrated here.
Inches (millimeters)
(152)
6
Figure 9: Minimum Distance to Side Wall
Page 9
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
Side
Framing
Unit Nailing Flange
(No clearance to
combustible framing
is required.)
Unit Secured to Framing
by Nailing Flange
Header Spacing Top Standoffs
(two pairs on front edge of firebox top)
Lift up outer pair for1/2" finish materials.
Lift up inner pair for5/8" finish materials.
Left Side Front Corner of Fireplace Shown
(Right side requirements are the same)
PRE-INSTALLATION STEPS
The appliance is shipped with all gas controls
and components installed and pre-wired.
Before installing the fireplace, follow these steps:
1. Remove the shipping carton.
2. Remove the shipping pad, exposing the front
glass door.
3. Open the two spring latches securing the
glass door (under the firebox floor). Remove
the door by tilting it outward at the bottom
and lifting it up. Set aside the door, taking
care to protect it from inadvertent damage
(see Removing and Installing the Glass Door
on Page 32).
4. Remove the log set and top vent flue
restrictor from the firebox. Handle logs
carefully to prevent breakage.
5. Remove the embers and volcanic stone from
the control compartment.
6. Remove top standoff and hood (taped to
back of outer wrapper).
7. Remove the 4 screws on top, and install the
top standoff with the 4 screws (Figure 10).
IMPORTANT!
Install top standoff
and bend up appropriate
drywall backstops (1/2" or 5/8")
before installing fireplace.
Top Standoff
(installed)
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation is outlined
below; however, each installation is unique and
may result in variations to the steps described.
See the pages referenced in the following steps
for detailed procedures.
Step 1. FRAMING (Page 9): Construct the ap-
pliance framing. Position the appliance within
the framing and secure with nailing brackets.
IMPORTANT! Before installing the fireplace,
install the top standoff on the top front edge
of the fireplace using the 4 existing screws
on the fireplace top (see Figure 10). Then,
bend up the applicable drywall backstops on
the top standoff (1/2" or 5/8"), based on the
thickness of the drywall/finish material to be
used (see Figure 10).
Bend out the appropriate side nailing flanges for
the drywall/finish material to be used. Nailing
flanges are provided for flush framing, 1/2-inch
and 5/8-inch framing depths (see Figure 11).
Step 2. ROUTING GAS LINE (Page 11): Route
gas supply line to appliance location.
Step 3. PREPARING APPLIANCE VENT COLLAR
(Page 12).
Step 4. INSTALLING VENT SYSTEM (Page 12):
Install the vent system and exterior termination.
Step 5. FIELD WIRING (Page 26): Field wire
and install operating control switch.
Step 6. REMOTE CONTROL SYSTEM (Page
27).
DETAILED INSTALLATION STEPS
Step 1. FRAMING
Frame the appliance as illustrated in Figures
12 and 13 on Pages 10 and 11 (Figure 13
applies to corner framing installations only).
All framing details must allow for a minimum
clearance to combustible framing members as
shown in Table 5 on Page 8.
If the appliance is to be elevated above floor level,
a solid continuous platform must be constructed
below the appliance.
Headers may be in direct contact with the appliance top standoff spacer, maintaining the 4"
clearance to the fireplace top, but must not be
supported by them or notched to fit around
them. All construction above the appliance must be self-supporting. DO NOT use the ap-
pliance for structural support.
Secure the fireplace to the side framing members
using the unit’s nailing flanges — one top and
bottom on each side of the fireplace front. See
NOTE: The nailing flanges, combustible
members, and screw heads in areas directly
adjacent to the nailing flanges are EXEMPT
from the 1/2" clearance to combustible
requirements for the firebox outer wrapper.
Combustible framing may be in direct contact
with the nailing flanges and may be located
closer than 1/2" from screw heads and the
firebox wrapper in areas adjacent to the
nailing flanges.
Frame the opening to the exact dimensions
specified in the framing details in this manual.
Figure 11
9
Page 10
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
FIREPLACE AND FRAMING SPECIFICATIONS
Framing
Model No.ABCDE
in.35-1/4 36-1/4 21-11/164916
MPDP35
mm8959215511245406
in.40-1/4 41-1/4 26-11/165416
MPDP40
Diagrams, illustrations and photographs are not to scale. Consult installation
instructions. Product designs, materials, dimensions, specifications, colors,
and prices are subject to change or discontinuance without notice.
Fireplace
Model
(Rear Vent)
MPDP3570697071
MPDP4071707172
Based on CSA P.4.1-09
mm102210486781372406
Notes
Efficiencies %
Natural GasPropane
AFUE
EnerGuide
(P4)
Rear/Side
Framing
Spacers
Standoff
AFUE
Top
EnerGuide
(P4)
G
H
VENT FRAMING:
REAR VENT
with no elbows
B
Concentric Flue*:
Flue =
4-1/2" (114 mm);
Combustion Air =
(190 mm).
J
VENT FRAMING:
TOP VENT with
1 ft. of pipe and
90-degree elbow
A
1/2
7-1/2"
Framing should be
)
7
(178)
7
(178)
constructed of 2x4
or larger lumber.
12-1/8
(308)
12-1/8
(308)
10-1/2
(
267
5-1/8
(130)
5-1/8
D
(130)
C
E
A
Dimension “E” is required framing depth when
finish material (drywall) thickness is 1/2 in. (13mm).
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
FIREPLACE FRAMING SPECIFICATIONS
Model No.ABCDEF
MPDP35
MPDP40
Note:
• Rear Vent Applications in Corner Installations: The horizontal vent length
(from a to b) must not exceed 28 inches (711 mm).
• MPDP35 and MPDP40: Dimensions D through F apply when one 45-degree
elbow is connected directly to the appliance collar.
in.35-1/857-1/240-5/819-3/1628-3/46-1/8
mm89214611032487730156
in.40-1/8 61-3/1643-11/3219-3/1630-11/167-7/8
mm101915541101487779200
Figure 13: Corner Framing with Horizontal Termination
Step 2. ROUTING GAS LINE
Route a 1/2" (13 mm) gas line to the left side
of the appliance as shown in Figure 14. Gas
lines must be routed, constructed and made
of materials that are in strict accordance with
local codes and regulations. All appliances
are factory-equipped with a flexible gas line
connector and 1/2-inch shutoff valve (see Step 7 on Page 28).
Never use galvanized or plastic pipe. Refer to
Table 6 for proper sizing of the gas supply line,
if black iron pipe is being used. Gas lines must
be routed, constructed and made of materials
that are in strict accordance with local codes
and regulations. We recommend that a qualified individual such as a plumber or gas fitter
be hired to correctly size and route the gas
supply line to the appliance. Installing a gas
supply line from the fuel supply to the appliance
involves numerous considerations of materials,
Left Side Front
Corner of Fireplace
Framing
protection, sizing, locations, controls, pressure,
sediment, and more. Certainly no one unfamiliar and unqualified should attempt sizing or
installing gas piping.
Pipe Coupling
(Recommended)
6-1/2"
(152 mm)
Inside Diameter (Inches)
Schedule 40 Pipe
3"
(76 mm)
Also see Figure 12.
Length (feet)
0-101/23/8
10-401/21/2
40-1001/21/2
Figure 14: Route Gas Line
100-1503/41/2
150-2003/41/2
Proper Sizing of Gas Line
Table 6
Properly size and route the gas supply line
from the supply regulator to the area where the
appliance is to be installed per requirements
outlined in the National Fuel Gas Code, NFPA
54 - latest edition (USA) or CAN/CSA-B149.1
- latest edition (Canada).
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Schedule 40
Black Iron Pipe
Natural
Gas
b
Rear Vent
F
Top Vent
C
7"
(178 mm)
D
a
A
B
Back wall of chase/enclosure (including any finishing materials)
Notes:
• All appliances are factory-equipped with
a flexible gas line connector and 1/2 inch
shutoff valve (see Figure 52 on Page 28).
• See Massachusetts Requirements on Page 4 for additional requirements for installations
in the state of Massachusetts in the USA.
• The gas supply line should Not be connected
to the appliance until Step 7 on Page 28.
• A pipe joint compound rated for gas should be
used on the threaded joints. Ensure propane
resistant compounds are used in propane
applications. Be very careful that the pipe
compound does not get inside the pipe.
• It is recommended to install a sediment trap
in the supply line as close as possible to the
appliance.
Propane
Gas
• Check with local building official for local
code requirements (i.e. are below grade
penetrations of the gas line allowed?, etc).
IMPORTANT: If propane is used, be aware that
if tank size is too small (i.e. under 100-lbs, if
this is the only gas appliance in the dwelling.
Ref. NPFA 58), there may be loss of pressure,
resulting in insufficient fuel delivery (which
can result in sooting, severe delayed ignition
or other malfunctions). Any damage resulting
from an improper installation, such as this,
is not covered under the limited warranty.
E
11
Page 12
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
Step 3. PREPARING APPLIANCE VENT
COLLAR
The unit’s top and rear vent collars are each
sealed with a cover plate and gasket. The cover
plate and gasket must be removed from the applicable vent collar being used. Refer to Page 13
for rear vent applications and Page 14 for top
vent applications. Also refer to the following
steps to prepare the appropriate collar for use.
From the vent collar being used, remove the
four screws securing the cover plate and gasket.
Discard the cover plate and gasket. Reinstall all
four screws and tighten securely.
WARNING
Vent cover plate and vent seal cap
must remain securely installed
on unused vent collar. Failure
to reinstall and securely tighten
cover plate screws could result
in leakage of flue products into
the living space.
Step 4. INSTALLING VENT SYSTEM
These instructions should be used as a
guideline and do not supersede local codes
in any way. Install venting according to local
codes, these instructions, the current National
Fuel Gas Code (ANSI-Z223.1) in the USA or
the current standards of CAN/CSA-B149.1
in Canada.
Ensure clearances are in accordance with
local installation codes and the requirements
of the gas supplier.
Dégagement conforme aux codes d'installation locaux et aux exigences du foumisseunde gaz.
Use only approved vent components (see
Approved Vent Components on Page 2).
NOTE: These fireplaces must be vented
directly to the outside.
The vent system may not service multiple
appliances, and must never be connected to a
flue serving a separate solid fuel burning appliance. The vent pipe is tested to be run inside
an enclosed wall (such as a chase). There is
no requirement for inspection openings in the
enclosing wall at any of the joints in the vent pipe.
12
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 13
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
U-SHAPED VENT
RESTRICTOR
APPLIANCE REAR
VENT OUTLET
INNER FIREPLACE
COLLAR
Installation of the U-shaped vent restrictor is
required in rear vent applications with vertical
vent runs over 8 feet.
Install the vent restrictor from outside the unit
in the inner fireplace collar of the rear vent outlet,
oriented as shown below.
U-SHAPED VENT RESTRICTOR INSTALLATION
(REAR VENT)
Vent Restrictor Installation
The fireplace ships with the following:
• (1) rear solid cover plate (ships installed
over rear vent hole; similar to top solid cover plate shown in Figure 16)
• (1) top solid cover plate (ships installed
over top vent hole; refer to Figure 16)
• (1) rear vent restrictor plate (square
plate with two rectangular holes; ships
uninstalled in literature bag)
• (1) U-shaped vent restrictor (ships
uninstalled in literature bag)
• (1) top vent flue restrictor (ships
uninstalled and taped to log set in firebox)
Vent Restrictor Installation in Rear Vent
Systems
IF REAR VENT HORIZONTAL VENT
LENGTH IS 7 INCHES OR SHORTER:
MPDP35 models: Install the rear vent
restrictor plate as shipped (seeFigure
15, View A; do NOT bend back the
perforated tab) over the rear vent hole
using the 4 previously removed screws,
as shown in Figure 16.
MPDP40 models: Hand-bend the per-
forated tab on the rear vent restrictor plate back 90 degrees (as shown in Figure 15, View B), and then install
it over the rear vent hole using the 4
previously removed screws, as shown
in Figure 16.
Perforated
Tab
A. Rear Vent Restrictor Plate
as shipped from factory.
(Use in this position on MPDP35 only.)
B. Rear Vent Restrictor Plate
with perforated tab bent 90 degrees.
(Use in this position on MPDP40 only.)
Figure 15
Top Solid Cover Plate (shown
installed over top vent hole)
When rear venting, remove the outer wrapper
knockout, cover plate, and gasket from outside
the unit (Figure 17).
REAR VENT SEAL AND COVER PLATE REMOVAL
WHEN USING THE REAR VENT
COVER PLATE
SECURING SCREWS
(INSIDE UNIT)
REAR VENT
CROSS SECTION
CAP AND
GASKET
CABINET BACK
(OUTSIDE UNIT)
KNOCKOUT
Figure 17
IF REAR VENT VERTICAL VENT LENGTH
IS 8 FEET OR LONGER:
All models: Before attaching the first
piece of venting pipe or elbow, install the
U-shaped vent restrictor into the rear vent
collar from outside the unit (Figure 18).
The U-shaped vent restrictor is held in
place by friction.
IF REAR VENT HORIZONTAL VENT
LENGTH IS LONGER THAN 7 INCHES:
All models: Reinstall the 4 previously
removed screws only, into the rear
cover plate screw holes. Do NOT install
the rear vent restrictor plate.
Rear Vent Restrictor Plate
(shown installed over rear vent hole
after Rear Solid Cover Plate was
removed)
Figure 16
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Figure 18
13
Page 14
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
U-shaped
Vent Restrictor
Appliance Top
Vent OUtlet
Inner
Fireplace
Collar
Installation of the U-shaped vent restrictor
is required in top vent applications with vent
runs over 8 feet.
Install the vent restrictor from outside the
unit in the inner fireplace collar of the top
vent outlet, oriented as shown below.
U-SHAPED VENT RESTRICTOR INSTALLATION
(TOP VENT)
Vent Restrictor Installation in Top Vent
Systems
Note: When top venting the fireplace, the top
vent flue restrictor MUST be installed.
Figure 19
1. Remove the 2 top front screws and loosen
the 2 top rear screws of the rear solid cover
plate (Figures 19 and 20).
2. Install the top vent flue restrictor by
sliding the two notches in the top vent flue
restrictor (Figure 20) under and behind the
two screws loosened in the previous step,
and then tighten the screws (Figure 21).
3. Bend the top vent flue restrictor FORWARD
and UP (Figure 22), and secure with the
other 2 previously removed screws (Figure
23).
Figure 22
IF TOP VENT VERTICAL VENT LENGTH
IS 8 FEET OR LONGER:
Before attaching the first piece of venting
pipe, install the U-shaped vent restrictor
into the top vent collar from outside the
unit (Figure 25). The U-shaped vent
restrictor is held in place by friction.
Note: An elbow may NOT be directly
attached to the fireplace top vent collar. A minimum of 1 ft. of vertical vent
pipe must be attached to the top vent
collar before installing any elbow.
Loosen screws.
Top Vent Flue Restrictor
Figure 20
Tighten screws.
Figure 23
When top venting, remove the outer top
knockout and gasket from outside the unit
(Figure 24).
TOP VENT SEAL AND COVER PLATE REMOVAL
WHEN USING THE TOP VENT
(OUTSIDE UNIT)
CABINET TOP
FIREBOX TOP
VENT
COVER PLATE
(INSIDE UNIT)
CROSS SECTION
GASKET
TOP VENT
KNOCKOUT
COVER PLATE
SECURING SCREWS
Figure 24
Figure 25
Select Venting System
(Horizontal or Vertical)
With the appliance secured in framing, determine
vent routing and identify the exterior termination location. The following sections describe
vertical (roof) and horizontal (exterior wall) vent
applications. Refer to the section relating to your
installation. See Pages 36 and 37 for a list of
approved venting components.
14
Figure 21
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 15
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
TRAHCHTGNELNOITCESTNEV
lanimoN
htgneLnoitceS
)sehcni(
621426384
T
O
T
A
L
Q
T
Y
noitceSteN
)sehcni(htgneL
2/1-42/1-012/1-222/1-432/1-64
tneVfothgieHsnoitceStneVforebmuN
sehcnitf
5.4573.0100001
957.0200002
5.01578.0010001
5152.1110002
5.91526.12100
0
3
1257.1020002
5.22578.1001001
5.52521.2120003
5.13526.2030003
5.43578.2000101
5.73521.3111003
5.34526.3021003
5457.3002002
5.64578.3000011
5.94521.4102003
1552.4100012
5.55526.4012003
7557.4001102
6652.5022004
5.76526.5003003
9657.5000202
276103004
5.37521.6100203
5.97526.6010203
1857.6000112
095.7021014
5.
19526.7002013
3957.7000022
698101204
5.79521.8100023
2015.8200024
5.301526.8000303
8019100304
4115.9020024
71157.9105006
5.811578.9110305
6215.01001304
5.031578.01101305
53152.11006006
8315.11000404
5.931526.11000033
5.241578.11100405
VERTICAL TERMINATION SYSTEMS (ROOF)
See Figure 26 and Figures 34 through 38 on
Pages 18 and 19 and their associated Verti-
cal Vent Tables, which illustrate the various vertical venting configurations that are possible for
use with these appliances. Secure Vent
applications are shown in these figures. Secure
®
pipe may also be used. A Vertical Vent
Flex
Table summarizes each system’s minimum and
maximum vertical and horizontal length values
that can be used to design and install the vent
components in a variety of applications.
Both these vertical vent systems terminate
through the roof. The minimum vent height
above the roof and/or adjacent walls is specified in ANSI Z223.1-(latest edition) (In Canada,
the current CAN/CSA-B149.1 installation code)
by major building codes. Always consult your
local codes for specific requirements. A general
guide to follow is the Gas Vent Rule (refer to
Figure 4 on Page 6).
Vertical (Straight) Installation (Figure 26)
Determine the number of straight vent sections
required. 4-1/2" (114 mm), 10-1/2" (267 mm),
22-1/2" (572 mm), 34-1/2" (876 mm) and
46-1/2" (1181 mm) net section lengths are
available (see tables on this page and Pages 36 and 37 - Vent Components). Plan the vent
lengths so that a joint does not occur at the
intersection of ceiling or roof joists. Refer to
the Vent Section Length Chart.
SV4.5CGV-1
Termination
Max. 40 ft
(12.2 m)
Figure 26
SV4.5FA or
SV4.5FB Flashing
AND SV4.5SC
Storm Collar
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
Blocking
Support Straps
(Plumber's tape)
8 feet (2.4 m)
Maximum
1/2 inch (12.7
mm) minimum
clearance to
combustibles
Vertical (Offset) Installation
Analyze the vent routing and determine the
quantities of vent sections and number of elbows
required. Refer to Vertical Vent figures and tables on Pages 18 and 19 to select the type
of vertical installation desired. Vent sections
are available in net lengths of 4-1/2" (114 mm),
10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2"
(876 mm) and 46-1/2" (1181 mm). Refer to the
Vent Section Length Chart on Page 15 for an
aid in selecting length combinations. Elbows are
available in 90° and 45° configurations. Refer
to Figure 30 for the SV4.5E45 and SV4.5E90
elbow dimensional specifications.
Where required, a telescopic vent section (SV4.5LA) may be used to provide the installer
with an option in installing in tight and confined
spaces or where the vent run made up of fixed
length pieces develops a joint in a undesirable
location, or will not build up to the required
length. The SV4.5LA Telescopic Vent Section
has an effective length of from 1-1/2" (38 mm)
to 7-1/2" (191 mm). The SV4.5LA is fitted with
a locking inclined channel end (identical to a
normal vent section component) and a plain end
with 3 pilot holes. Slip the plain end over the
locking channel end of a standard SV4.5 vent
component the required distance and secure
with three screws.
Maintain a minimum 1" (25 mm) clearance to
combustible materials for all vertical elements.
Clearances for all horizontal elements are 3"
(76 mm) on top, 1" (25 mm) on sides and 1"
(25 mm) on the bottom.
A. Frame ceiling opening - Use a plumb line
from the ceiling above the appliance to locate
center of the vertical run. Cut and/or frame an
opening, 10-1/2" x 10-1/2" (267mm x 267mm)
inside dimensions, about this center mark
(Figure 27).
All of the appliances covered in this document
are fitted with collars having locking inclined
channels. The dimpled end of the vent components fit over the appliance collar to create
the positive twist lock connection.
Align the dimple (four places) of
the upper vent section with the
opening of the locking incline
channel on the lower vent section
or appliance collar. Twist vent
component clockwise to engage
and seal until arrow and dimple
Arrow
Appliance Collar or
Vent Section
align.
Dimple
Locking Incline
Channel
Connected Vent
Sections
Arrow
Figure 28
To attach a vent component to the appliance
collar, align the dimpled end over the collar,
adjusting the radial alignment until the four
locking dimples are aligned with the inlet of
the four inclined channels on the collar (refer to Figure 28). Push the vent component against
the collar until it fully engages, then twist the
component clockwise, running the dimples
down and along the incline channels until they
seat at the end of the channels. The unitized
design of the Secure Vent components will
engage and seal both the inner and outer pipe
without the need for sealant or screws. If desired
a #6 x 1/2" screw may be used at the joint, but
it is not required as the pipe will securely lock
when twisted.
Push the vent component against the previous
section until it fully engages, then twist the
component clockwise running the dimples down
and along the incline channels until they seat at
the end of the channels. This seating position
is indicated by the alignment of the arrow and
dimple as shown in Figure 28.
D. Install firestop/spacer at ceiling - When
using Secure Vent, use SV4.5VF firestop/spacer
®
at ceiling joists; when using Secure Flex
, use
SF4.5VF firestop/spacer. If there is living space
above the ceiling level, the firestop/spacer must
be installed on the bottom side of the ceiling.
If attic space is above the ceiling, the firestop/
spacer must be installed on the top side of
the joist. Route the vent sections through the
framed opening and secure the firestop/spacer
with 8d nails or other appropriate fasteners at
each corner. Remember to maintain 1" (25
mm) clearance to combustibles, framing
members, and attic or ceiling insulation
when running vertical chimney sections.
Attic insulation shield (96K94) may be used
to obtain the required clearances indicated
here. See installation accessories table on
Pages 36 and 37. The gap between the vent
pipe and a vertical firestop can be sealed with
non-combustible caulking.
E. Support the vertical vent run sections -
Note - Proper venting support is very important.
Support the vertical portion of the venting
system every 8 feet (2.4m) above the fireplace
vent outlet. One method of support is by utilizing field provided support straps (conventional
plumber's tape). Secure the plumber's tape to
the framing members with nails or screws. Loop
the tape around the vent, securing the ends of
the tape to the framing. If desired, sheet metal
screws #6 x 1/2" length may be used to secure the
support straps to the vent pipe. See Figure 29.
Min. 10-1/2"
(267 mm)
Min. 10-1/2"
Roof
Framing
Ceiling
Framing
(267 mm)
Plumb
Bob
Figure 27
B. Attach vent components to appliance Secure Vent
®
SV4.5 direct vent system components are unitized concentric pipe components
featuring positive twist lock connections (see Figure 28).
16
C. Attach vent components to each other - Other
vent sections may be added to the previously
installed section in accordance with the requirements of the vertical vent figures and tables.
To add another vent component to a length of
vent run, align the dimpled end over the inclined
channel end of the previously installed section,
adjusting the radial alignment until the four
locking dimples are aligned with the inlets of
the four incline channels of the previous section.
Figure 29
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 17
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
SV4.5E90
(90
°
Elbow)
8-1/8"
(206 mm)
Swivel Joint
(360
°
swivel)
4-13/16"
(122 mm)
SV4 .5E45
(45
°
El bow)
Swivel Joint
(360
°
swivel)
Storm
Collar
Flashing
F. Change vent direction to horizontal/inclined
run - At transition from or to a horizontal/in-
clined run, install the SV4.5E45 and SV4.5E90
elbows in the same manner as the straight vent
sections. The elbows feature a twist section to
allow them to be routed about the center axis
of their initial collar section to align with the
required direction of the next vent run element.
Twist elbow sections in a clockwise direction
only so as to avoid the possibility of unlocking
any of the previously connected vent sections.
See Figure 30.
Figure 30
G. Continue installation of horizontal/inclined
sections - Continue with the installation of the
straight vent sections in horizontal/inclined run
as described in Step C. Install support straps
every 5' (1.52 m) along horizontal/inclined vent
runs using conventional plumber’s tape. It is
very important that the horizontal/inclined run
be maintained in a straight (no dips), slightly
elevated plane. The recommended incline
is approximately 1/4" per foot (20 mm per
meter) horizontal, in a direction away from
the fireplace. The rise per foot run ratios that
are smaller are acceptable all the way down
to at or near level. Use a carpenter’s level to
measure from a constant surface and adjust
the support straps as necessary.
H.Frame roof opening - Identify location for
vent at the roof. Cut and/or frame opening per
Roof Framing Chart and Figure 31.
C
D
Framing Dimensions for Roof
PitchCD
0/12
6/12
12/12
10-1/2 in.
(267 mm)
10-1/2 in.
(267 mm)
10-1/2 in.
(267 mm)
10-1/2 in.
(267 mm)
12 in.
(305 mm)
17-3/4 in.
(451 mm)
Figure 31
I.Install the roof flashing - Extend the vent
sections through the roof structure. Install the
roof flashing over the vent section and position such that the vent column rises vertically
(use carpenters level) (Figure 32 ). Nail along
perimeter to secure flashing or adjust roofing to
overlap the flashing edges at top and sides only
and trim where necessary. Seal the top and both
sides of the flashing with waterproof caulking.
J. Install the storm collar - Install the storm
collar, supplied with the flashing, over the vent/
flashing joint. See Figure 32. Loosen the storm
collar screw. Slide collar down until it meets
the top of the flashing. Tighten the adjusting
screw. Apply non-combustible caulking or
mastic around the circumference of the joint
to provide a water tight seal.
K. Install the vertical termination - The final
step involves installation of the SV4.5CGV-1
Vertical Termination. Extend the vent sections
to the height as shown in the "Vertical vent termination section" on Page 6. The SV4.5CGV-1
Vertical Termination (Figure 33) installs in the
exact same fashion as any other Secure Vent®
section. Align the termination over the end of
the previously installed section, adjusting the
radial alignment until the four locking dimples
of the termination are aligned with the inlets of
the four incline channels of the last vent section.
Push the termination down until it fully engages,
then twist the termination clockwise running the
dimples down and along the incline channels
until they seat at the end of the channels.
Figure 33
It is important to maintain the required clearances to combustibles: 1" (25 mm) at all sides
for all vertical runs; and 3" (76 mm) at the
top, 1" (25 mm) at sides, and 1" (25 mm) at
the bottom for all horizontal/inclined runs.
If the vent system extends more than 5 ft. (1.5
meters) above the roof flashing, stabilizers may
be necessary. Additional screws may be used
at section joints for added stability. Guide wires
may be attached to the joint for additional support on multiple joint configurations.
Figure 32
17
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 18
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
SF4.5VF.
H
V
V1
Ceiling
Firestop/Spacer
SV4.5VF*
Wall
Firestop/Spacer
SV4.5HF**
H
V
V1
CeilingFirestop/SpacerSV4.5VF*
WallFirestop/SpacerSV4.5HF**
*When using Secure Flex, use Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use Wall Firestop/Spacer SF4.5HF.
CeilingFirestop/SpacerSV4.5VF*
*When using Secure Flex,useCeiling Firestop/Spacer SF4.5VF.
TABLEB
HMaximum
VMinimum
feet
(meters)
feet
5
(1.524)
ElbowOnly
(meters)
VERTICAL VENT FIGURES/TABLES
Note:Secure Vent
in the figures; Secure Flex® (flexible vent pipe)
may also be used.
Note: It is very important that the horizontal/
inclined run be maintained in a straight (no
dips), slightly elevated plane. The recommended
incline is approximately 1/4" per foot (20 mm
per meter) horizontal, in a direction away from
the fireplace. The rise per foot run ratios that
are smaller are acceptable all the way down to
at or near level.
Note: SV4.5VF (Secure Vent), SF4.5VF (Secure
Flex) firestop/spacer must be used anytime vent
pipe passes through a combustible floor or ceiling. SV4.5HF (Secure Vent), SF4.5HF (Secure
Flex)firestop/spacer must be used anytime vent
pipe passes through a combustible wall.
Note: Two 45 degree elbows may be used in
place of one 90 degree elbow. The same rise
to run ratios, as shown in the venting figures
for 90 elbows, must be followed if 45 degree
elbows are used.
Note: An elbow is acceptable as 1 foot of
vertical rise.
®
(rigid vent pipe) is shown
TABLE A
H MaximumV Minimum
(meters)
feetfeet
(meters)
2(0.610)1(0.305)
4(1.219)2(0.610)
6(1.829)3(0.914)
V
8(2.438)4(1.219)
V + H = 40 feet (12.2 meters) Max.
H = 8 feet (2.4 meters) Max.
Ratio V to H ratio is 1:2
This table shows a 1 (V) to 2 (H) ratio.
For every 1 foot of (V) vertical, you are
allowed 2 feet of (H) horizontal run, up
to a maximum horizontal run of 8 feet.
Example: If 8 feet of (H) horizontal vent
run is needed, then 4 feet minimum (V)
vertical vent will be required.
Figure 35: Rear Vent - ONE 90-DEGREE ELBOW
Ceiling
Firestop/Spacer
SV4.5VF*
*When using Secure Flex, use
Ceiling Firestop/Spacer
H
Note: Install the U-shaped vent restrictor in
any vent run with more than 8 ft. of vertical
rise. See Pages 13 and 14.
TABLE B
H Maximum
(meters)
feet
(1.524)
5
(3.048)
10
(4.572)
15
(6.096)
20
V + V1+ H = 40 feet (12.2 m) Max.
H = 20 feet (6.096 meters) Max.
V Minimum
feet
2
1
3
2
4
3
5
4
(meters)
(0.305)
0.610
(0.610)
0.914
1.219
(0.914)
(1.219)
0.524
Ceiling
Firestop/
Spacer
SV4.5VF*
18
A Vent Restrictor, as shown in Figure
25 on Page 14, must be used in this
application.
Figure 34: Top Vent - STRAIGHT
Max. 40 ft
(12.2 m)
*When using
Secure Flex, use
Ceiling Firestop/
Spacer SF4.5VF.
Example: If 20 feet of (H) horizontal vent
run is needed, then 4 feet minimum of
(V) vertical vent will be required.
An elbow is acceptable as 1 foot
of vertical rise.
Min. 1 ft. vent
section required
Note:
• An elbow may NOT be attached
directly to the vent collar.
• Install the U-shaped vent restrictor
in any vent run with more than 8
ft. of vertical rise. See Pages 13
and 14.
Figure 36: Top Vent - TWO 90-DEGREE ELBOWS
WARNING
Under no circumstances, may separate sections of concentric flexible vent
pipe be joined together.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 19
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
CeilingFirestop/SpacerSV4.5VF*
*When using Secure Flex,useCeiling Firestop/Spacer SF4.5VF.
TABLED
H+
H
1
Maximum
VMinimum
feetfeet
5
(1.524)ElbowOnly
(meters)(meters)
V
H
CeilingFirestop/SpacerSV4.5VF*
WallFirestop/SpacerSV4.5HF**
VERTICAL VENT FIGURES/TABLES
(continued)
TABLE C
+H
MaximumH MaximumV Minimum
H
1
2
4
6
8
(meters)
(0.610)
(1.219)
(1.829)
(2.438)
(meters)
feetfeetfeet
(1.524)
5
(3.048)
10
(4.572)
15
(6.096)
20
V + V1+ H + H1 = 40 feet (12.2 m) Max
H = 8 feet (2.438 meters) Max.
H + H1= 20 feet (6.096 meters) Max.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V) vertical, you are allowed 5 feet of (H) horizontal run, up to a maximum
horizontal run of 20 feet.
Example: If 20 feet of (H) horizontal vent run is needed, then 4
feet minimum of (V) vertical vent will be required.
Note: Install the U-shaped vent restrictor in any vent run with
more than 8 ft. of vertical rise. See Pages 13 and 14.
1
2
3
4
(meters)
(0.305)
(0.610)
(0.914)
(1.219)
V1
H1
Ceiling
Firestop/Spacer
SV4.5VF*
Wall
Firestop/Spacer
SV4.5HF**
V
*When using Secure Flex®, use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use Wall Firestop/Spacer SF4.5HF.
Ceiling
Firestop/Spacer
SV4.5VF*
Figure 37: Rear Vent - THREE ELBOWS
H
Maximum
H +
1
feetfeet
5
10
15
20
H + H1 = 20 feet (6.096 m) Max.
V + V
Example: If 20 feet of (H) horizontal vent run is needed, then 4 feet minimum
of (V) vertical vent will be required.
An elbow is acceptable as 1 foot of vertical rise.
Note:
• An elbow may NOT be attached directly to the vent collar.
• Install the U-shaped vent restrictor in any vent run with more than 8 ft.
of vertical rise. See Pages 13 and 14.
Figure 38: Top Vent - THREE ELBOWS
TABLE D
V Minimum
(meters)(meters)
(1.524)
(3.048)
(4.572)
(6.096)
+ H + H1 = 40 ft. (12.192 m) Max.
1
2
1
3
2
4
3
5
4
(0.305)
0.610
(0.610)
0.914
(0.914)
1.219
(1.219)
0.524
H
Ceiling
V
1
Firestop/Spacer
SV4.5VF*
Wall
Firestop/Spacer
SV4.5HF**
H
H
1
V
Min. 1 ft. vent
section required
*When using Secure Flex,useCeiling Firestop/Spacer SF4.5VF.
When using Secure Flex, use
**When using Secure Flex,useWall Firestop/Spacer SF4.5HF.
SF4.5VF.
When using Secure Flex, use
SF4.5HF.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
19
Page 20
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
HORIZONTAL (OUTSIDE WALL)
TERMINATION SYSTEM
Figure 39 (at right) and Figures 42 to 47 (Pages 22 to 24) and illustrate the various horizontal
venting configurations that are possible for use
with these appliances. Secure Vent
plications are shown in these figures. Secure
®
pipe may also be used. A Horizontal Vent
Flex
Table summarizes each system’s minimum and
maximum vertical and horizontal length values
that can be used to design and install the vent
components in a variety of applications.
Both of these horizontal vent systems terminate
through an outside wall. Building Codes limit
or prohibit terminating in specific areas. Refer
to Figure 6 on Page 7 for location guidelines.
Secure Vent (SV4.5) direct vent system components are unitized concentric pipe components
featuring positive twist lock connection (refer to Figure 28 on Page 16). All appliances covered
in this document are fitted with collars having
locking inclined channels. The dimpled end of the
vent components fit over the appliance collar to
create the positive twist lock connection.
A.Plan the vent run.
Analyze the vent routing and determine the
types and quantities of sections required
4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572
mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm) net
section lengths are available. It is recommended
that you plan the venting so that a joint does not
occur in the ceiling or roof joists. Allow for elbows
as indicated in Figure 30 on Page 17.
Maintain a minimum 1" (25 mm) clearance to
combustibles on the vertical sections. Clearances
for the horizontal runs are; 3" (76 mm) on top, 1"
(25 mm) on sides, and 1" (25 mm) at the bottom.
B. Frame the exterior wall opening.
Locate the center of the vent outlet on the exterior wall according to the dimensions shown
in Figure 12 on Page 10. Cut and/or frame an
opening, 10-1/2" x 12-1/8" (267 mm x 308mm)
inside dimensions, about this center.
C.Frame the ceiling opening.
If the vertical route is to penetrate a ceiling,
use plumb line to locate the center above
the appliance. Cut and/or frame an opening,
10-1/2" x 10-1/2" (267 mm x 267 mm) inside
dimensions, about this center (refer to Figure
27 on Page 16).
D. Attach vent components to appliance.
To attach a vent component to the appliance collar,
align the dimpled end over the collar, adjusting the
radial alignment until the four locking dimples are
aligned with the inlets of the four incline channels
on the collar (refer to Figure 28 on Page 16).
Push the vent component against the collar until it
fully engages, then twist the component clockwise,
running the dimples down and along the incline
channels until they seat at the end of the channels.
20
®
pipe ap-
TYPICAL HORIZONTAL VENT INSTALLATION
Building
Support
Framing
SV4.5E90
ertical
V
Rise
Support
Brackets
Elbow
Ceiling
Firestop/Spacer
See Figure 24 for vertical
vent section support.
Figure 39
The unitized design of the Secure Vent compo-
nents will engage and seal both the inner and
outer pipe elements with the same procedure.
Sealant and securing screws are not required.
E. Attach vent components to each other.
Other vent sections may be added to the previously installed section in accordance with the
requirements of the vent tables. To add another
vent component to a length of vent run, align the
dimpled end of the component over the inclined
channel end of the previously installed section,
adjusting the radial alignment until the four locking dimples are aligned with the inlets of the four
incline channels of the previous section. Push
the vent component against the previous section
until it fully engages, then twist the component
clockwise running the dimples down and along
the incline channels until they seat at the end of
the channels. This seating position is indicated
by the alignment of the arrow and dimple as
shown in Figure 28 on Page 16.
F. Install firestop/spacer at ceiling.
When using Secure Vent, use SV4.5VF firestop/
spacer at ceiling joists; when using Secure Flex,
use SF4.5VF firestop/spacer. If there is living
space above the ceiling level, the firestop/
spacer must be installed on the bottom side of
the ceiling. If attic space is above the ceiling,
the firestop/ spacer must be installed on the
top side of the joist. Route the vent sections
through the framed opening and secure the
firestop/spacer with 8d nails or other appropriate fasteners at each corner. The gap between
the vent pipe and a firestop can be sealed with
noncombustible caulking.
Remember to maintain 1" (25 mm) clearance
to combustibles, framing members, and attic
or ceiling insulation when running vertical
chimney sections.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Horizontal / Inclined Run
SV4.5L6/12/24/36/48
Vent Sections
Support bracket spacing
every 5 ft (1.52 m)
Min. 1 ft. vent
Min. 1 ft vent
section required.
section required
Fireplace
Exterior
Wall
G.Support the vertical run sections.
On the vertical run, support the venting system every 8 feet (2.4m) above the fireplace
vent outlet with field provided support straps
(Plumber's tape). Attach the straps to the vent
pipe and secure to the framing members with
nails or screws. See Figure 29 on Page 16.
H. Change vent direction.
At transition from or to a horizontal/inclined run,
install the SV4.5E45 and SV4.5E90 elbows in
the same manner as the straight vent sections.
The elbows feature a twist section to allow them
to be routed about the center axis of their initial
collar section to align with the required direction of the next vent run element. Twist elbow
sections in a clockwise direction only so as
to avoid the possibility of unlocking any of
the previously connected vent sections. See
Figure 30 on Page 17.
I. Continue installation of horizontal/inclined
sections. Continue with the installation of the
straight vent sections in horizontal/inclined run
as described in Step E. Install support straps
every 5 ft. (1.52 m) along horizontal/inclined
vent runs using conventional plumber’s tape.
SeeFigure 39. It is very important that the
horizontal/inclined run be maintained in a
straight (no dips), slightly elevated plane.
The recommended incline is approximately
1/4" per foot (20 mm per meter) horizontal,
in a direction away from the fireplace. The
rise per foot run ratios that are smaller are
acceptable all the way down to at or near level.
Use a carpenter’s level to measure from a
constant surface and adjust the support straps
as necessary.
It is important to maintain the required clearances to combustibles: 1" (25 mm) at all sides
for all vertical runs; and 3" (76 mm) at the
top, 1" (25 mm) at sides, and 1" (25 mm) at
the bottom for all horizontal/inclined runs.
SV4.5HT-2
Termination
SV4.5HT-2
Termination
Exterior
Wall
Page 21
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
J.Assemble vent run to exterior wall - If not
previously measured, locate the center of the
vent at the exterior wall. Prepare an opening
as described in Step B. Assemble the vent
system to point where the terminus of the last
section is within 7 in. (178 mm) to 11-1/4 in.
(286 mm) inboard of the exterior surface to
which the SV4.5 HT termination is to be attached, see Figure 40. If the terminus of the
last section is not within this distance, use the
telescopic vent section SV4.5LA, as the last
vent section. For wall thicknesses greater than
that shown in Figure 40, refer to Table 8 on Page 22. This table lists the additional venting
components needed (in addition to the termination and adaptor) for a particular range of
wall thicknesses.
To help minimize water infiltration it is recommended that
the Firestop/Spacer (SV4.5HF)
be installed on the exterior
side of the wall.
K. Attach termination adaptor. Attach the adap-
tor (adaptor - SV4.5RCH - provided with the
termination) to the vent section or telescoping
vent section), elbow or appliance collar as shown
in Figure 40 in the same manner as any SV4.5
vent component (refer to Step E).
L.Install Firestop/Spacer at exterior wall.
When using the square termination, install
SV4.5HF (Secure Vent
®
) Firestop/Spacer over the opening at the
Flex
exterior side of the framing, long side up, with
the 3 inch spacer clearance at the top as shown
in Figure 40, and nail into place. The Firestop/
Spacer may also be installed over the opening at
the interior side of the framing. The gap between
the vent pipe and a firestop can be sealed with
noncombustible caulking.
M. Install the desired termination.
1. Install the square termination (SV4.5HT-2
or SV4.5HTSS). From outside the exterior
wall, slide the collars of the termination onto
the adaptor (the outer over the outer and the
inner inside the inner) until the termination
seats against the exterior wall surface to which
it will be attached. Orient the housing of the
termination with the arrow pointed upwards.
Secure the termination to the exterior wall. The
horizontal termination must not be recessed
into the exterior wall or siding by more than
the 1-1/4" (32 mm) as shown in Figure 41.
SVHRK Snorkel Cap: The snorkel cap is de-
signed to be fitted into a basement window box.
The SVHRK cap is for use with flex vent. The
vertical distance between the inlet and outlet
of the cap is 28 in. (711 mm).
IMPORTANT: The vent termination is HOT
while in operation and for a period of
time following the use of the fireplace.
To prevent contact with hot surfaces,
we recommend the use of a Termination Guard (see Page 36). This can be
purchased at your local dealer.
See Figure 12 on Page 10
for Min. Distance to Base
of Appliance.
Figure 40: Installing the Square Horizontal Termination (SV4.5HT-2)
®
), SF4.5HF (Secure
* Use silicone caulking to
seal the top and sides of the
termination, up to the underlayment, stucco, or masonry
wall surface.
*Caulk
*Caulk
Stucco
Figure 41
Siding
Square Termination
than 10 inches, see Table 8.
Venting Connection and Exterior Wall Recessing of the
Last Vent Section. Use
Telescopic Vent Section
(SV4.5LA), If Necessary
SV4.5HT-2
**For thicknesses greater
Horizontal Square Termination (SV4.5HT-2).
Interior Surface of
Finished Wall
Maximum Extent of
Vent Run Sections
Relative to Exterior
Surface of Framing
Adaptor
SV4.5RCH
Horizontal terminations have been designed to perform in a wide range of weather
Maximum Wall Thickness
10 in.(254 mm)**
Exterior Surface of Siding
Exterior Surface of
Framing
6 in. to 9-1/4 in.
(152 to 235 mm)**
SV4.5HT-2
Square Termination
1-1/4 in. Maximum Recess
of the Square Termination
into Exterior Finishing
Material
conditions. Our terminations meet or exceed industry standards.
When selecting the locations of your horizontal terminations, do not place the termination
where water from eaves and adjoining rooflines may create a heavy flow of cascading water
onto the termination cap. If the cap must be placed where the possibility of cascading water
exists, it is the responsibility of the builder to direct the water away from the termination
cap by using gutters or other means.
Take care to carefully follow the installation instructions for the termination, including the
use of silicone caulking where required.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
21
Page 22
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
H
V
When using Secure Flex,
use Firestop/Spacer
SF4.5VF.
Ceiling
Firestop/Spacer
(SV4.5VF)
When using Secure Flex,
use Firestop/Spacer
SF4.5HF.
Wall Firestop/Spacer
(SV4.5HF)
Min. One
Foot Vent
Section
Required
HORIZONTAL VENT FIGURES/TABLES
Note:
• Secure Vent
the figures; Secure Flex
®
components (rigid vent pipe and terminal) are shown in
®
components (flexible vent pipe and terminal)
may also be used.
• Two 45-degree elbows may be used in place of one 90 degree elbow.
The same rise to run ratios, as shown in the venting figures for 90
elbows, must be followed if 45-degree elbows are used.
• It is very important that the horizontal/inclined run be maintained
in a straight (no dips), slightly elevated plane. The recommended
incline is approximately 1/4" per foot (20 mm per meter) horizontal,
in a direction away from the fireplace. The rise per foot run ratios
that are smaller are acceptable all the way down to at or near level.
• SV4.5VF (Secure Vent), SF4.5VF (Secure Flex) firestop/spacer must be
used anytime vent pipe passes through a combustible floor or ceiling.
SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer must be
used anytime vent pipe passes through a combustible wall.
WARNING
Under no circumstances, may separate sections of
concentric flexible vent pipe be joined together.
• An elbow is acceptable as 1 ft. of vertical rise.
• An elbow may NOT be attached directly to the vent collar.
• Install the U-shaped vent restrictor in any run with more than
8 ft. of vertical rise (see Pages 13 and 14).
• See Table 8 on Page 22 as an aid in venting component
selection for a particular range of exterior wall thicknesses.
* Minimum 1 ft. section and elbow
Figure 44: Top Vent - TWO 90-DEGREE ELBOWS
H
H
1
Ceiling
Firestop/Spacer
SV4.5VF*
Wall Firestop/
Spacer
SV4.5HF**
V
*When using Secure Flex, use Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use Wall Firestop/Spacer SF4.5HF.
Square termination (SV4.5HT-2) shown.
Example: If 20 feet of (H + H1) horizontal
vent run is needed, then 4 feet minimum of
(V) vertical vent will be required.
TABLE H
TABLE G
MaximumH Maximum
+H
H
1
(meters)
feet
(1.524)
5
(3.048)
10
(4.572)
15
(6.096)
20
V + H + H1 = 40 feet (12.2 m) Max.
H = 8 feet (2.438 meters) Max.
H + H1= 20 feet (6.096 meters) Max.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V)
vertical, you are allowed 5 feet of (H) horizontal run, up to a
maximum horizontal run of 20 feet.
Example: If 20 feet of (H) horizontal vent run is needed, then
4 feet minimum of (V) vertical vent will be required.
See Table 8 on Page 22 as an aid in venting component
selection for a particular range of exterior wall thicknesses.
Note: Install the U-shaped vent restrictor in any run with more
than 8 ft. of vertical rise. See Pages 13 and 14.
(meters)
feet
2(0.610)1(0.305)
4(1.219)2(0.610)
6(1.829)3(0.914)
8(2.438)4(1.219)
V Minimum
feet
(meters)
Figure 45: Rear Vent - TWO 90-DEGREE ELBOWS
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
23
Page 24
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
HORIZONTAL VENT FIGURES/TABLES (continued)
Typical termination shown.
H
1
Wall Firestop/Spacer
(SV4.5HF)
Note:
• An elbow is acceptable as 1
ft. of vertical rise.
• An elbow may NOT be
attached directly to the vent
collar.
• Install the U-shaped vent
restrictor in any run with
more than 8 ft. of vertical
rise. See Pages 13 and 14.
• See Table 8 on Page 22 as
an aid in venting component
selection for a particular
range of exterior wall
thicknesses.
Example: If 20 feet total (H+H
is needed, then 4 feet minimum of (V) vertical vent
will be required.
) horizontal vent run
1
Figure 46: Top Vent - THREE 90-DEGREE ELBOWS
Wall Firestop/Spacer
SV4.5HF**
H
1
H
2
*When using Secure Flex, use Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use Wall Firestop/Spacer SF4.5HF.
Ceiling
Firestop/Spacer
SV4.5VF*
V
TABLE K
TABLE I
+ H1+ H
H
feetfeetfeet
Maximum
2
(meters)
H Maximum
(meters)
V Minimum
(meters)
5(1.524)2(0.610)1(0.305)
10(3.048)4(1.219)2(0.610)
15
(4.572)
6(1.829)3(0.914)
20(6.096)8(2.438)4(1.219)
V + H + H1+ H2 = 40 feet (12.2 m) Max.
H = 8 feet (2.438 meters) Max.
H + H1+ H2= 20 feet (6.096 meters) Max.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot
of (V) vertical, you are allowed 5 feet of (H) horizontal
run, up to a maximum horizontal run of 20 feet.
Example: If 20 feet of (H) horizontal vent run is needed,
then 4 feet minimum of (V) vertical vent will be required.
Note: Install the U-shaped vent restrictor in any
H
run with more than 8 ft. of vertical rise. See Pages
13 and 14.
Square termination (SV4.5HT-2) shown.
See Table 8 on Page 22 as an aid in venting component selection for a particular range of exterior wall thicknesses.
Figure 47: Rear Vent - THREE 90-DEGREE ELBOWS
24
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 25
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
5" (127 mm)
Radius Minimum
Flexible Vent Section
VERTICAL OR HORIZONTAL VENTING USING
SECURE FLEX
Secure Flex
be used in any venting application where rigid
Secure Vent
can be used. All restrictions, clearances and
allowances that pertain to the rigid piping apply
to the flexible venting. Secure Flex kits may
not be modified; also, under no circumstances
may separate sections of flex pipe be joined
together. Secure Flex kits may be added to the end of a vent run made up of rigid Secure
Vent (SV4.5) vent sections provided that doing
so does not violate any of the venting length,
height, routing, horizontal to vertical ratio requirements or clearance considerations detailed
in this manual.
Secure Flex kits come with an included adaptor
that can be fitted to the appliance collar or the
inclined channel end of the last Secure Vent
(SV4.5) vent section in a rigid system in the
exact same fashion as any other Secure Vent
section. Align the dimpled end of the adaptor
over the previously installed section or appliance
collar, adjusting the radial alignment until the
four locking dimples of the adaptor are aligned
with the inlets of the four incline channels of
the last vent section or collar. Push on the
adaptor until it fully engages, then twist the
adaptor clockwise running the dimples down
and along the incline channels until they seat
at the end of the channels.
Attach the flexible vent to the adaptor as follows (see Figure 48):
A. Install the Inner Flex Pipe.
1. Install the small gear clamp loosely around
the inner flexible vent pipe, push it back out
of the way.
2. Apply a bead of Mill-Pac Black (700°F) high
temperature sealant - Catalog No. 10K81) to
the inner adaptor collar, approximately 1/2 inch
from the end.
3. Pull and extend the inner flexible vent pipe.
4. Slide the inner flex pipe over the adaptor
collar. Ensure the flexible vent pipe completely
engages the adaptor collar to a distance of
1-3/4 inches from the end, and that it is free
from damage or tears.
5. Slide the gear clamp down and tighten it
fully to secure the flexible vent to the adaptor
inner collar approximately 3/4 inch from the
end of the flex.
6. Install three screws 120 degrees apart
through the flexible vent pipe and into the adaptor collar just below the gear clamp to provide
additional security to the connection.
B. Install the Outer Flex Pipe.
1. Install the large gear clamp loosely around
the outer flexible vent pipe, push it back out
of the way.
®
KITS AND COMPONENTS
®
venting kits and components may
®
(SV4.5) direct vent components
NOTE: OUTER PIPE IS PULLED AWAY TO
SHOW THE DETAIL OF THE INNER PIPE
Apply ONLY MIL-PAC BLACK HIGH
TEMPERATURE SEALANT (Catalog No.
10K81) to the outside surface of both
collars of the adaptor (be especially
careful to fill the grooves of the outer
collar to be covered by the flexible
pipe) and slide flexible pipe over
inn er and outer adaptor collars.
1-3/4 in. (44 mm)
Flexible Pipe and
Adaptor Outer
Collar Overlap
Adaptor
(SV4.5RF)
Attach Adaptor to Appliance
Figure 48
Collar, or Secure Vent Sections
2. Apply a bead of Mill-Pac Black (700°F) high
temperature sealant - Catalog No. 10K81) to
the outer adaptor collar; to the grooves of the
collar which extend approximately 1 inch from
the end and to the flat surface, approximately
1-3/8 inches from the end.
3. Pull and extend the outer flexible vent pipe.
4. Slide the outer flex pipe over the adaptor
collar. Ensure the flexible vent pipe completely
engages the adaptor collar to a distance of 1³⁄₄
inches from the end, and that it is free from
damage or tears.
5. Slide the gear clamp down and tighten it
fully to secure the flexible vent to the adaptor
outer collar approximately 3/4 inch from the
end of the flex.
6. Install three screws 120 degrees apart
through the flexible vent pipe and into the adaptor collar just below the gear clamp to provide
additional security to the connection.
C. Route Flex Vent.
Ensure that the flex vent is properly routed to
provide the required clearance. Do Not allow
the flexible vent to bend in a radius tighter than
5" (127 mm). Refer to Figure 49. Space out
the internal flex vent spacers evenly and avoid
kinking of inner pipe. Support horizontal sections of flex with metal straps at 2 foot (0.61
m) intervals.
D. Install Firestop/Spacers at ceilings and walls.
When Secure Flex penetrates a wall or ceiling,
a firestop/spacer is required: use the SF4.5 VF
firestop/spacer for ceilings and the SF4.5 HF
firestop/spacer for walls.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
FLEX VENT
SECURING SCREW
(3 PLACES EQUALLY SPACED
JUST BELOW GEAR CLAMP)
GEAR
CLAMPS
1-3/4 in. (44 mm)
Flexible Pipe and
Adaptor Inner
Collar Overlap
SECURING SCREW
(3 PLACES EQUALLY SPACED
JUST BELOW GEAR CLAMP)
See the appropriate sections and figures shown
throughout the venting section for their installation requirements.
Figure 49
E. Attach Flex Vent to Termination.
Secure Flex components can be purchased
separately and attached to bulk lengths of
Secure Flex flexible tubing cut to size at the
job site. Secure the flexible vent to the Secure Flex terminations in the same manner (see
Figure 48) as it was attached to the adaptor.
Note: Secure Flex vent must be attached
to Secure Flex terminations only. DO NOT
substitute Secure Vent terminations or the
Secure Vent adaptor for Secure Flex components. The collars of Secure Flex terminations
and adaptors have a different circumference
than that used with the Secure Vent pipe.
Additionally, Secure Flex components have
an extended length center tube for use in
attaching the flexible vent.
25
Page 26
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
Step 5. FIELD WIRING
CAUTION
The ground supply lead must be
connected to the wire attached
to the green ground screw
located on the outlet box (see wiring diagrams). Failure to
do so will result in a potential
safety hazard. The appliance
must be electrically grounded
in accordance with local codes
or, in the absence of local codes,
the National Electrical Code,
ANSI/NFPA 70-latest edition (in
Canada, the current CSA C22.1
Canadian Electrical Code).
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring
errors can cause improper and dangerous
operation.
ATTENTION: Au moment de l’entretien
des commandes, étiquetez tous les fils
avant de les débrancher. Des erreurs
de cáblage peuvent entraîner un fonctionnement inadéquat et dangereux.
Verify proper operation after servicing.
S’assurer que l’appareil fonctionne adéquatement une fois l'entretien terminé.
Electronic Wiring(see Figures 50 and 51)
All models must be connected to the main
power supply.
1. Route a 3-wire 120Vac 60Hz 1ph power
supply to the appliance junction box.
2. Remove the electrical inlet cover plate
from the side of the unit by removing the
plate's securing screws. See Figure 12 on
Page 10.
3. Remove the cover plate's knockout and
then feed the power supply wire through
the knockout opening and into the unit
junction box.
4. Connect the black power supply wire to the
lower outlet's red and black pigtail leads
and the white power supply wire to the
common terminal of the outlet as shown
in Figures 50 and 51.
5. Connect the ground supply wire to the
pigtail lead attached to outlet's green
ground screw.
6. After the wiring is complete, replace the
cover plate.
7. Acquire and locate a standard junction
box on the wall adjacent to the appliance
within the reach of the remote system
umbilical cord wiring harness. Position
the 14 pin terminal within the junction box
in preparation for its attachment to the
remote receiver.
WARNING
Electronic models of these appliances are equipped with a threeprong (grounding) plug utilized
in connecting the electronic
components to the junction box
in the lower compartment. This
grounding plug provides protection against shock hazard and
should be plugged directly into
the properly grounded threeprong receptacle. DO NOT cut
or remove the grounding prong
from the plug.
8. When wall finish is complete install the
receiver in the previously located junction
box and connect the 14 pin terminal to
the 14 pin connector on the back of the
receiver.
9. Install the receiver cover plate, taking care
to ensure the receiver switch is properly
indexed with the switch cover when aligning the components for attachments.
26
ELECTRONIC
IGNITION WIRING
DIAGRAM
FAN CONTROL
MODULE
Figure 50
JUNCTION BOX
FAN
G
POWER CORD
120V
Fan
Out
WALL
RECEIVER
CABLE HARNESS
HIGH-TEMP SLEEVE
Schematic Representation Only
W
B
POWER CORD
Power
Aux
Out
CAV 021
G
R,PU,GY
Wiring Color Code
B = Black
BL = Blue
BR = Brown
B, BR, Y, O
G = Green
GY = Gray
O= Orange
PROFLAME
ELECTRONIC
VALVE
GG
P, BL
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
PU = Purple
W = White
R = Red
Y
O
G
W
W
UNIT MOUNTED
ROCKER SWITCH*
P = Pink
Y = Yellow
W
P, BL
* Unit Mounted Rocker Switch
*Unit Mounted CPI Rocker Switch
OFF (o) = Intermittent Pilot Mode
ON (-) = Standing Pilot Mode
PILOT BURNER
IGNITER-SENSOR
ASSEMBLY
PILOT TUBE
PROFLAME DFC BOARD
DFC WIRE HARNESS
IGNITER ROD
FLAME
SENSOR
SPARK WIRE
CABLE
B
PILOT SENSOR
B
CABLE
Y
DIGITAL
BURNER
CONTROL
FIREPLACE
NOTES:
1. If any of the original wire as supplied must be replaced, use Type AWM 105°C - 18 gage wire ONLY.
2. 120 VAC, 60 Hz - Less than 5 Amps.
CAUTION: label all wires prior to disconnection
when servicing controls. Wiring errors can cause
improper and dangerous operation. Verify proper
operation after servicing.
Page 27
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
Tab Intact
Green
Ground
Screw
Figure 51- J-Box Wiring
Neutral
Side of
Receptacle
Green
White
Tab Intact
Hot
Side of
Receptacle
Step 6. REMOTE CONTROL SYSTEM
The remote control system allows you to operate
your fireplace from the comfort of your chair
and is configured to control the ON/OFF primary
burner operation, its flame levels (through six
levels) and provides ON/OFF and Smart thermostatic control of the appliance
The system controls fan speed through six (6)
levels and has a constantly powered 120V/60Hz
power outlet.
The Receiver connects directly to the gas valve,
stepper motor and the Fan Control Module with
and umbilical cord wiring harness.
The Receiver is powered by 4 AA type batteries,
located within.
The Receiver accepts commands via radio
frequency from the Transmitter and does not
require line-of-sight operation.
The Receiver three position slider switch can
be set to one of three positions: ON (Manual
Override), REMOTE (Remote Control) or OFF.
Ground - Green
Neutral - White
120 VAC - Black
Junction Box
Black
Initializing The System For The First Time
Install the 4 AA batteries into the receiver battery
bay (behind the wall switch plate).
Note: The polarity of the battery and insert
into the battery bay as indicated on the Battery
cover (+/-).
Place the 3 position slider switch on the wall
receiver in the "Remote" position (seeFigure 50 and Page 35). Using the end of a paper clip, or
other similar object, insert the end of the paper
clip into the hole marked "PRG" on the Receiver
front cover. The Receiver will "beep" three (3)
times to indicate that it is ready to synchronize
with a Transmitter.
Install the 3 AAA type batteries in the Transmitter battery bay, located on the base of the
Transmitter. With the batteries already installed
in the Transmitter, push the ON button. The
Receiver will "beep" four times to indicate the
Transmitter's command is accepted and sets
to the particular code of that Transmitter. The
system is now initialized.
J-BOX / RECEPTACLE
WIRING
120V, 60HZ, 1PH
Field Wired
Factory Wired
Low Battery Power Detection
The life span of the Receiver batteries depends
on various factors: quality of the batteries used,
the number of ignitions of the appliance, the
number of changes to the room thermostat
set point, etc.
When the Receiver batteries are low, two
"beeps" will be emitted from the Receiver when
it receives and ON/OFF command from the
Transmitter. This is an alert for a low battery
condition for the Receiver. When the batteries
are replaced the "beep" will be emitted from the
Receiver when the ON/OFF key is pressed (See
Initializing The System).
Refer to the fireplace Care and Operation Instructions for detailed remote control system
operation instructions.
WARNING
Fire hazard. Can cause severe
injury or death. The receiver causes
ignition of the appliance. The appliance can turn on suddenly. Keep
away from the appliance burner
when operating the remote system
or activating manual bypass of the
remote system.
CAUTION
Property damage hazard. Excessive
heat can cause property damage. The
appliance can stay lit for many hours.
Turn off the appliance if it is not going
to be attended for any length of time.
Always place the Transmitter where
children cannot reach it.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
27
Page 28
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
Gas
Stub
1/2" x 3/8" Flare
Shut-Off Valve
3/8" Flex Tubing
3/8" NPT x 3/8"
Flare Fitting
3/8" Nipple
3/8" Union
3/8" Close Nipple
3/8" Shut-Off Valve
1/2" x 3/8"
Reducer
Gas
Valve
Optional Gas Flex Line Connector
Step 8. VERIFYING APPLIANCE
OPERATION
With gas line installed, run initial system
checkout before closing up the front of the
unit. Follow the lighting instructions provided
in the Care and Operation Instructions.
Note: Lighting Instructions are also found on
the literature tag tied to the gas piping next
to the gas valve. To access the tag, open the
lower control compartment door by pushing
in the right top corner of the door (the door
is hinged at the bottom). Remove the bottom
compartment door by sliding the hinge pin,
located at the door’s left side, to the right until
it disengages from the left corner post hole.
28
Figure 52: Gas Connection
Step 7. CONNECTING GAS LINE
Make gas line connections. All codes require a
shut-off valve mounted in the supply line. Figure 52 illustrates two methods for connecting the
gas supply. The flex-line method is acceptable
in the U.S., however, Canadian requirements
vary depending on locality. Installation must
be in compliance with local codes.
A sediment trap is recommended in the gas
piping within the home to prevent moisture
and debris in the line from damaging the valve.
These appliances are equipped with a gas flex
line for use (where permitted) in connecting the
unit to the gas line. A gas flex line is provided
to aid in attaching the direct vent appliance to
the gas supply. The gas flex line can only be
used where local codes permit. Refer to Figure 52 for flex line description. The flex line is rated
for both natural and propane gas. A manual
shut off valve is also provided with the flex line.
The gas control valve is located in the lower
control compartment.
To access the valve, open the lower control
compartment door by pushing in the right top
corner of the door (the door is hinged at the
bottom). Remove the bottom compartment door
by sliding the hinge pin, located at the door’s
left side, to the right until it disengages from the
left corner post hole. Pull the door diagonally
to the left, away from the fireplace.
Secure all joints tightly using appropriate
tools and sealing compounds (ensure propane
resistant compounds are used in propane
applications). Optional: Seal around the gas
line to prevent cold air leakage. Gas line holes
and other openings can be caulked or stuffed
with unfaced fiberglass insulation.
TEST ALL CONNECTIONS FOR GAS LEAKS
(FACTORY AND FIELD):
WARNING
Never use an open flame to
check for leaks.
Turn on gas supply and test for gas leaks, using a gas leak test solution (also referred to as
bubble leak solution).
Note: Using a soapy water solution is an effective leak test solution but it is not recommended,
because the soap residue that is left on the
pipes/fittings can result in corrosion over time.
A. Light the appliance (refer to the lighting
instructions label in the control compartment
or in the Care and Operation Instructions
manual).
B. Brush all joints and connections with the gas
leak test solution to check for leaks. If bubbles
are formed, or gas odor is detected, turn the
receiver or remote control to the “OFF” position.
Either tighten or refasten the leaking connection,
then retest as described above.
C. When the gas lines are tested and leak free,
be sure to rinse off the leak testing solution.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
When first lighting the appliance, it will take a
few minutes for the line to purge itself of air.
Once purging is complete, the pilot and burner
will light and operate as indicated in the instruction manual.
Subsequent lighting of the appliance will not
require such purging. Inspect the pilot flame
(remove logs, if necessary, handling carefully).
Electronic Appliance Checkout
To light the burner, turn on the remote control.
Ensure the igniter lights the pilot. The pilot
flame should engulf the flame rod as shown
in Figure 53.
Igniter
Ignitor
Pilot
Pilot Hood
Hood
Flame Rod
Sensor
(sensor)
Figure 53
Page 29
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
Glowing Embers
Step 9. INSTALL VOLCANIC STONE,
GLOWING EMBERS, AND LOGS
WARNINGS
• DO NOT attempt to install the
logs until the appliance installation has been completed, the
gas line connected and tested
for leaks and the initial burner
operation has been checked
out.
•
The size and position of the log
set was engineered to give the
appliance a safe, reliable and
attractive flame pattern. Any
attempt to use a different log
set in the fireplace will void
the warranty and will result in
incomplete combustion, sooting, and poor flame quality.
•
Logs get very hot and will
remain hot up to one hour after
gas supply is turned off. Handle
only when logs are cool. Turn
off all electricity to the appliance before you install grate,
volcanic stone, embers and
logs.
•
This appliance is not designed
to burn wood. Any attempt to
do so could cause irreparable
damage to the appliance and
prove hazardous to your safety.
•
If logs are not installed accord-
ing to the log installation
instructions, flame impingement and improper combustion could occur and result in
soot and/or excessive production of carbon monoxide (CO),
a colorless, odorless, toxic
gas.
Step 2. Install decorative volcanic stone.
Sprinkle the decorative volcanic stone in a
pleasing pattern. The volcanic stone should
be placed directly on top of the firebox bottom,
along the front and to the back at the right and
left sides of the burner. Position any optional
ceramic fiber liners before placing the stone.
Logs should be positioned after the volcanic
stone.
Note: This appliance is provided with enough
Glowing Embers for several applications,
do not feel compelled to use all that is in a
new bag. For best glowing effect, replace the
ember material annually. Replacement Glowing Embers are available (Catalog Number
88L53).
Glowing Embers
Separate into Quarter
Size (separate) Pieces
Bag of Glowing
Embers (rockwool)
Figure 54
Step 3. Separate the Glowing Embers into
pieces about the size of a quarter (Figure 54).
Keep the pieces fluffed up, not matted.
Distribute the pieces over the front surface
of the burner, as shown in Figure 55, but DO NOT PLACE OVER BURNER SLOTS.
Do not use more than necessary. The ember
material should cover approximately 65% of
the front burner, with no appreciable gaps or
openings. Make sure the main burner ports
are NOT covered by the ember material.
Step 4. Placement of Logs
All top logs that rest on lower logs, do so over
notches, indents or nubs. Proper log placement
is critical to prevent sooting. Logs should be
placed in the gaps between the flame peaks and
should be positioned so they do not impinge
the flames.
Step 5. Position the individual logs as shown
in Figures 56 and 57. Logs should be placed
in the order shown. All logs that have notches
to fit over the grate tines should be positioned
with these notches directly against the grate.
Handle logs carefully to prevent breakage.
Proper log placement is critical to encourage
outstanding flame appearance and prevent
sooting. When positioned properly as shown,
logs will be positioned between flame peaks
and will not impinge any flames.
Refer to Figure 56 for MPDP35 Series appliances and Figure 57 for MPDP40 Series
appliances.
REFERENCE
Firebox Accessories / Parts
Cat. No.Model No.Description
88L53FGEBag of Glowing Embers
80L42FDVS
Bag of Decorative
Volcanic Stone
NOTE: Turn off all electricity to the appliance
before installing volcanic stone, embers,
and logs.
Step 1. Remove the appliance front door (see
Removing Glass Enclosure Panel on Page 32).
Figure 55
29
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 30
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
MPDP35 LOG PLACEMENT
Log
1
3
2
Number Description (Stamped #)
1 Log, Rear (39-5)
2 Log, Left (39-1)
3 Log, Right (39-2)
4 Log, Top Center (39-6)
5 Log, Top/Left (39-3)
6 Log, Top/Right (39-4)
Catalog Number for the entire log set: 24M22
4
5
6
Position the individual logs as shown below. Logs should be placed
in the order shown. Position the rear log on the brackets at the
rear of the firebox with the log's notches directly over the brackets.
Position the right log (log no. 3) by inserting the pin from the rear
log into the hole on its upper end. Place the left log and then the
smaller left and right top logs. All logs that have notches to fit over
the grate tines should be positioned with these notches directly
against the grate. All top logs that rest on lower logs, do so over
flattened mounting faces in the bottom logs.
Proper log and twig placement is critical to encourage outstanding
flame appearance and prevent sooting.
1
43
30
2
Figure 56
5
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
6
Page 31
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
MPDP40 LOG PLACEMENT
Log
1
2
3
Number Description (Stamped #)
1 Log, Center (39-8)
2 Log, Rear (138)
3 Log, Right (39-10)
4 Log, Left (39-9)
5 Log, Top/Left (39-11)
6 Log, Top/Right (39-11)
Catalog Number for the entire log set: 24M25
4
5
6
Position the individual logs as shown below. Logs should be placed
in the order shown. Position the center log on the burner first, then
place the glowing embers as shown in Figure 55. Place the rear
log, both the right and left, and then the smaller left and right top
logs. All logs that have notches to fit over the grate tines should
be positioned with these notches directly against the grate. All top
logs that rest on lower logs, do so over flattened mounting faces
in the bottom logs.
Proper log and twig placement is critical to encourage outstanding
flame appearance and prevent sooting.
1
4
3
2
Figure 57
5
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
6
31
Page 32
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
Step 10. REMOVING AND INSTALLING
THE GLASS DOOR
WARNING
• Do not attempt to substitute the
materials used on these doors,
or replace cracked or broken
glass.
• Handle this glass with extreme
care! Glass is susceptible to
damage – Do not scratch or
handle roughly while reinstalling the glass door frame.
• The glass door of this appli-
ance must only be replaced
as a complete unit as provided
by the manufacturer. Do not
attempt to replace broken,
cracked or chipped glass separately.
• Do not attempt to touch the
front enclosure glass with your
hands while the fireplace is in
use.
WARNING
Do not operate appliance with
the glass front removed, cracked
or broken.
AVERTISSEMENT
Ne pas utiliser l'appareil si le
panneau frontal en verre n'est
pas en place, est craqué ou
brisé.
Only doors certified with the appliance
shall be used.
Seules des portes certifiées pour cet
appareil doivent être utilisées.
WARNING: DO NOT abuse glass door by
striking or slamming shut.
32
Removing the Glass Enclosure Panel
Remove the top radiant panel.
To access the two glass door securing latches,
first open the lower control compartment door
(Figure 58) by pushing in the right top corner
of the door (the door is hinged at the bottom).
[Optional] Remove the bottom compartment door by sliding the hinge pin, located
at the door’s left side, to the right until it
disengages from the left corner post hole.
Pull the door diagonally to the left, away
from the fireplace.
Locate the two latches at the top of the lower
control compartment, and disengage them
from the door frame bottom vee-flange by
pulling the latches forward and down to release
them from the door channel.
Pull the bottom of the door out a few inches
and grasp it on the right and left. Gently lift to
release the door from its channel above the
door. Pull the door forward.
Installing the Glass Enclosure Panel
Retrieve the glass door. Visually inspect the
gasket on the backside of the frame. Gasket
surface must be clean, free of irregularities
and seated firmly.
Position the door in front of the firebox opening with the bottom of the door held away
from the fireplace (Figure 58). Hook the top
flange of the door frame over the top of the
firebox frame.
Let the bottom of the door frame swing gently
in towards the fireplace ensuring that the gasket seats evenly as the door frame draws shut.
Fasten the two latches located underneath the
firebox floor to the door's vee-flange. Close
both the latches securely.
Lower Compartment Door and Hinge
Glass
Door
Glass Door Frame
Bottom Vee-flange
Glass Door Spring Latch
Figure 58
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Glass Door Frame
Top Flange
Firebox Floor
Step 11. BURNER ADJUSTMENTS
Flame Appearance and Sooting
Proper flame appearance is a flame that is blue
at the base and becomes yellowish-orange in
the body of the flame.
When the appliance is first lit, the entire flame
may be blue and will gradually turn yellowishorange during the first 15 minutes of operation.
If the flame remains blue, or if the flame is
orange with evidence of sooting (black tip), the
air shutter opening may need to be adjusted.
If the air shutter opening is closed too far,
sooting may develop. Sooting is indicated by
black puffs developing at the tips of very long
orange flames. Sooting results in black deposits
forming on the logs, appliance inside surfaces
and on exterior surfaces adjacent to the vent
termination.
Sooting is caused by incomplete combustion
in the flames and lack of combustion air entering the air shutter opening. To achieve a warm
yellowish-orange flame with an orange body
that does not soot, the shutter opening must be
adjusted between these two extremes.
Air Shutter Adjustment Guidelines
• If there is smoke or soot present, first
check the log set positioning to ensure that
the flames are not impinging on any of the
logs. If the log set is properly positioned
and a sooting condition still exists, then the
air shutter opening should be increased.
• The more offsets in the vent system, the larger
the air shutter opening will need to be.
• An appliance operated with the air shutter
opened too far, may have flames that appear
blue and transparent. These weak, blue and
transparent flames are termed anemic.
• Propane models may exhibit flames which
candle or appear stringy. If this is present
and persists, adjust the air shutter to a more
closed position, then operate the appliance
for a few more minutes to ensure that the
flame normalizes and the flames do not
appear sooty.
The following chart is provided to aid you in
achieving the correct air shutter adjustment
for your installation.
Air Shutter Adjustment Guidelines
Amount of
Primary Air
If air shutter is
closed too far
If air shutter is
open too far
Flame
Color
Flame will
be orange
Flame will
be blue
Air Shutter
Adjustment
Air shutter
gap should be
increased
Air shutter
gap should be
decreased
Page 33
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
Adjustment Rod Up
(Fully Open Position)
Air Shutter
Burner Tube
Adjusting Set Screw
Adjustment Rod Down
(minimum air
opening position)
Burner Flame Adjustments
WARNINGS
•Air shutter adjustment should
only be performed by a qualified professional service technician.
•Ensure front glass panel are
in place and sealed during
adjustment.
CAUTIONS
•Soot will be produced if the
air shutter is closed too much.
Any damage due to sooting,
resulting from improperly
setting the air shutter, is not
covered under the warranty.
• The air shutter door and
nearby appliance surfaces
are hot. Exercise caution to
avoid injury while adjusting
flame appearance.
Figure 59 - Burner Flame Appearance, Model MPDP35
1. Refer to Figures 59 and 60 for proper flame
appearance. To adjust the flame, rotate the
adjustment rod toward the back or toward
the front of the fireplace (rod located in the
lower control area). Position the air shutter
to the factory setting as shown in the table
in Figure 61.
2. Light the appliance (follow lighting procedure
on lighting label in control compartment or
in the Care and Operation Instructions).
3. Allow the burner to operate for at least 15
minutes while observing the flame continuously to ensure that the proper flame appearance has been achieved. If the following
conditions are present, adjust accordingly.
• If flame appears weak or sooty, adjust
the air shutter, incrementally, to a more
open position until the proper flame
appearance is achieved.
• If flame remains blue, adjust the air
shutter, incrementally, to a more closed
position until the proper flame appearance is achieved.
4. When satisfied that the burner flame appear-
ance is normal, reinstall the lower control
compartment door, then proceed to finish
the installation.
Figure 60 - Burner Flame Appearance, Model MPDP40
Adjustment Rod Up
(minimum air
opening position)
MPDP35
Adjustment Rod Down
(fully open position)
Figure 61
MPDP40
saG
sledoM
epyT
Nat.
.porP61/3)67.4(
.taN8/1)2.3(
.porP
1/16 (1.6)
3/8 (9.6)
RIAYROTCAF
RETTUHS
GNITTES
)mm(sehcni
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
33
Page 34
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
Step 12.HOOD INSTALLATION
All models must have hoods installed prior
to operating.
Slide the hood into the slots on the lower edge of
the radiant panel (Figure 62).
FINISHING REQUIREMENTS
Wall Details
Complete finished interior wall. To install the
appliance facing flush with the finished wall,
position framework to accommodate the thickness of the finished wall (Figure 62).
See Page 5 for
Cold Climate Insulation and
Page 8 for Clearances.
Combustible
Finished Wall
Materials
Combustible
materials NOT
allowed below
this point on
appliance face.
(100 mm)
Hood must be installed as shown.
Figure 62
This area must remain
clear of combustible
materials.
Min. 1"
(25 mm)
Drywall Backstop
(bent up for
1/2" or 5/8")
4"
Top Standoff
Top of Appliance
Radiant panel
Top of Door Frame
34
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 35
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
STEP 13. INSTALLER INSTRUCTIONS - ATTACHING SAFETY IN OPERATION WARNINGS
It is the installer’s responsibility to ensure these warnings are properly affixed during installation. These warning labels are a
critical step in informing consumers of safe operation of this appliance.
ATTACHING SAFETY IN OPERATION
WARNINGS
It is required that the set of safety instruction labels
that have been furnished with the fireplace be affixed
to the operation and control points of the fireplace. A
safety instruction label must be affixed to the receiver
wall switch plate where the fireplace is turned on and
off (See Figure A) and on the remote control handheld
transmitter (See Figure B). To properly complete the
installation of this fireplace, locate the multi-lingual
adhesive labels provided with the Care and Operation
Instructions and proceed as follows:
1. Locate the wall receiver that controls the fireplace
(verify the switch operates the fireplace by turning it on and off). Clean the wall receiver plate
thoroughly to remove any dust and oils. Affix the
label to the surface of the plate of the wall receiver
that controls the fireplace (Figure A). Choose
the language primarily spoken in the home. If
unknown, affix the English language label.
2. Locate the remote control transmitter and clean
it thoroughly to remove any dust and oils. Affix
the label to the surface of handheld transmitter
(Figure B). Choose the language primarily spoken in the home. If unknown, affix the English
language label.
3. If you are unable to locate the labels, please call
Lennox Hearth Products or your nearest Lennox
Hearth Products dealer to receive additional
safety instruction labels free of charge.
Cat. No. H8024 Replacement Label Kit
LENNOX HEARTH PRODUCTS
1-800-655-2008
Note: English is red text on clear label. French and
Spanish are white text on black label.
APPOSITION DES MISES EN GARDE RELATIVES
À LA SÉCURITÉ D’UTILISATION
Il est impératif que le jeu d’étiquettes de sécurité qui
ont été fournies avec le foyer soient collées à côté
des dispositifs de contrôle du foyer. Une étiquette de
sécurité doit être collée sur la plaque du récepteur mural
contrôlant l’allumage du foyer (voir Figure A) et sur le
boîtier de la télécommande (Figure B). Pour achever
l’installation correcte de ce foyer, procédez comme suit
avec les étiquettes adhésives en langues étrangères
fournies avec les instructions d’utilisation et d’entretien :
1. Repérez le récepteur mural qui contrôle le foyer
(vérifiez que l’interrupteur contrôle le fonction nement du foyer en le faisant basculer de Marche
à Arrêt, et vice-versa). Nettoyez soigneusement
la plaque du récepteur mural pour éliminer la
poussière et les traces de graisse ou d’huile. Collez
l’étiquette sur la surface de la plaque du récepteur
mural qui contrôle le foyer (Figure A). Choisissez
la langue qui est principalement parlée dans la
résidence du propriétaire. En cas de doute, collez
l’étiquette en anglais.
2. Repérez la télécommande et nettoyez-la soigneusement pour éliminer la poussière et les traces
de graisse ou d’huile. Collez l’étiquette sur le boîtier
de la télécommande (Figure B). Choisissez la
langue qui est principalement parlée dans la
résidence du propriétaire. En cas de doute, collez
l’étiquette en anglais.
3. Si vous ne trouvez pas les étiquettes, veuillez
appeler Lennox Hearth Products ou votre distributeur Lennox Hearth Products local pour recevoir
gratuitement des étiquettes supplémentaires.
Étiquettes de remplacement, n° cat. H8024
LENNOX HEARTH PRODUCTS
1-800-655-2008
Remarque : Le texte anglais est rouge sur un support
transparent. Le texte français et espagnol est blanc
sur un support noir.
COLOCACIÓN DE ADVERTENCIAS DE SEGURIDAD
EN OPERACIÓN
Se requiere que el juego de etiquetas de instrucciones
de seguridad que se incluyeron con la chimenea se
coloque en los puntos de operación y control de la
misma. Se debe colocar una etiqueta de instrucciones
de seguridad en la placa del interruptor de pared
del receptor desde el cual se enciende y se apaga
la chimenea (ver la Figura A) y en el transmisor de
control remoto (ver la Figura B). Para completar
correctamente la instalación de esta chimenea,
encuentre las etiquetas adhesivas multilingües
incluidas con las instrucciones de cuidado y operación
y haga lo siguiente:
1. Identifique el receptor de pared que controla la
chimenea (verifique que el interruptor opera la
chimenea encendiéndola y apagándola). Limpie
bien la placa del receptor de pared para quitar el
polvo y aceite. Pegue la etiqueta en la superficie
de la placa del receptor de pared que controla la
chimenea (Figura A). Seleccione el idioma que
más se habla en la casa. Si no sabe cuál es, use la
etiqueta en inglés.
2. Identifique el transmisor de control remoto y límpielo
bien para quitar el polvo y aceite. Pegue la etiqueta
en la superficie del transmisor (Figura B). Seleccione
el idioma que más se habla en la casa. Si no sabe
cuál es, use la etiqueta en inglés.
3. Si no puede encontrar las etiquetas, sírvase
llamar a Lennox Hearth Products o al distribuidor
de Lennox Hearth Products más cercano para
recibir etiquetas de instrucciones de seguridad
adicionales gratuitas.
Juego de etiquetas de repuesto - Nº de cat. H8024
LENNOX HEARTH PRODUCTS
1-800-655-2008
Nota: La etiqueta en inglés es transparente con texto
rojo. Las etiquetas en francés y español son negras
con texto blanco.
SAFETY LABEL
DIAGRAMS
Figure A
DIAGRAMMES DES ÉTIQUETTES
DE SÉCURITÉ
On
Remote
Off
PRG
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Figure B
DIAGRAMAS DE ETIQUETAS
DE SEGURIDAD
35
Page 36
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
S
e
a
l
a
n
t
INSTALLATION ACCESSORIES
Listed Secure Vent® Components
Cat. No.ModelDescription
H1968SV4.5HT-2Horizontal Square
Termination with
Firestop/ Spacer (H2246)
and Adaptor (74L61)
H2152SV4.5CGV-1Vertical Termination Cap,
High Wind
87L02SV4.5HGSTermination Guard for
Horizontal Square Termination (Deluxe) (1 pack)
(Ref. Instr. #750055M)
H5820SV4.5HTSKTermination Shroud
(Guard) for Horizontal
Square Termination
(1 pack)
(Ref. Instr. #750246M)
H3907SV4.5ARSAAttic Insulation Shield w/
adjustable height, 12"-22"
H1988CTSA-33Chase Top Shroud Kit,
Arch Top 3 X 3 Ft.,
(Ref. Instr. #750194M)
H1985CTSO-33Chase Top Shroud Kit,
Open Top 3 X 3 Ft.,
(Ref. Instr. #750193M)
H1987CTSO-44Chase Top Shroud Kit,
Open Top 4 X 4 Ft.,
(Ref. Instr. #750193M)
H1986CTSO-46Chase Top Shroud Kit,
Open Top 4 X 6 Ft.,
(Ref. Instr. #750193M)
Listed Secure Vent Components
Cat. No.ModelDescription
Vent Sections
(Rigid)
The following flashings come packaged with a storm collar:
77L70SV4.5L66 Inch (152 mm)
77L71SV4.5L1212 Inch (305 mm)
77L72SV4.5L2424 Inch (610 mm)
77L73SV4.5L3636 Inch (914 mm)
77L74SV4.5L4848 Inch (1219 mm)
77L75SV4.5LATelescopic Length Slip
Section (2" to 7-1/2" rigid)
77L76SV4.5E4545 Degree Elbow
77L77SV4.5E9090 Degree Elbow
10K81SFMPMill-Pac, Black, High-
Temperature Sealant
89L40SFMP-12Mill-Pac, Black, High-
Temperature Sealant,
Bulk 12 pack
99L02SV4.5HRK14 Horizontal Riser Kit, 14",
(Ref. Instr. #750146M)
99L03SV4.5HRK36 Horizontal Riser Kit, 36",
(Ref. Instr. #750146M)
96K93SV4.5SUSupport Strap
H5816SV4.5-
TWSK10
Through Wall Shield Kit
(used to shield the
direct-vent pipe from
blown insulation)
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
INSTALLATION ACCESSORIES CONTINUED
Listed Secure Flex® Components
Cat. #ModelDescription
These termination kits include firestop/spacer, gear clamps and flex adaptor.
60L10SF-1818 feet (5.49 m) *
compressed flex
(Ref. Instr. #750053M)
98K03SF-1212 feet (3.66 m)*
compressed flex
(Ref. Instr. #750052M)
H2248SF4.5HF-10Firestop / Spacer -
Horizontal, flex (3-1-1
spacing), 10 Pack
H2249SF4.5VF-10Firestop/Spacer-Vertical,
flex (1-1-1 spacing), 10 Pk
56L74SFVT30Vertical Termination for flex
(flat to 6/12) with flex adaptor,
section of rigid vent, roof
support collar assembly, roof
flashing and storm collar.
(Ref. Instr. #750052M)
56L75SFVT45Vertical Termination for flex
(6/12 to 12/12) with flex
adaptor, section of rigid
vent, roof support collar
assembly, roof flashing,
and storm collar.
(Ref. Instr. #750052M)
91L66SFGC4-6Gear Clamp 4.5 in. (114 mm)
for flex (6 pack)
91L67SFGC7-6Gear Clamp 7.5 in. (190.5
mm) for flex (6 pack)
H7748H774836" Flex Connector
Kit. 36" of flex with two
adaptors for mating two
rigid sections of vent
together.
Listed Secure Flex Components
Cat. #ModelDescription
H1969SF4.5HT-2Horizontal Square Termina-
tion for flex (without flex
vent)
77L87SFKIT12SSquare Term. for flex
(with 12 inch [305 mm]
compressed flex vent**)
77L88SFKIT18SSquare Term. for flex
(with 18 inch [457 mm]
compressed flex vent**)
77L89SFKIT24SSquare Term. for flex
(with 24 inch [610 mm]
compressed flex vent**)
77L90SFKIT36SSquare Term. for flex
(with 36 inch [914 mm]
compressed flex vent**)
77L91SFKIT48SSquare Term. for flex
(with 48 inch [1219 mm]
compressed flex vent**)
**All compressed flex vents can be expanded up to two times.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
37
Page 38
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
GAS CONVERSION KITS
WARNING
This conversion kit shall be installed by a qualified service agency in
accordance with the manufacturer’s instructions and all applicable codes
and requirements of the authority having jurisdiction. If the information in
these instruction is not followed exactly, a fire, explosion or production of
carbon monoxide may result causing property damage, personal injury
or loss of life. The qualified service agency is responsible for the proper
installation of this kit. The installation is not proper and complete until the
operation of the converted appliance is checked as specified in the manufacturer’s instructions supplied with the kit.The qualified service agency
performing this installation assumes responsibility for this conversion.
AVERTISSEMENT
Cette trousse de conversion doit être installée par un technicien agréé,
selon les instructions du fabricant et selon toutes les exigences et tous les
codes pertinents de l’autorité compétente. Assurez-vous de bien suivre
les instructions dans cette notice pour réduire au minimum le risque
d’incendie, d’explosion ou la production de monoxyde de carbone pouvant
causer des dommages matériels, des blessures ou la mort. Le tecnicien
agréé est responsable de l’installation de cette trousse. L’installation n’est
pas adéquate ni complète tant que le bon fonctionnement de l’appareil
converti n’a pas été vérifié selon les instructions du fabricant fournies avec
la trousse. Le fournisseur de service qualifié ayant réalisé l'installation
assume les responsabilités liées à la conversion.
INSTALLATION INSTRUCTIONS
Step 1. TURN OFF THE GAS SUPPLY TO THE
APPLIANCE and disconnect power supply at
the circuit breaker. Ensure appliance is cold.
CAUTION: THE GAS SUPPLY SHALL BE
SHUT OFF PRIOR TO DISCONNECTING THE
ELECTRICAL POWER, BEFORE PROCEEDING WITH THE CONVERSION.
ATTENTION: AVANT D’EFFECTUER
LA CONVERSION, COUPEZ D’ABORD
L’ALIMENTATION EN GAZ, ENSUITE,
COUPEZ L’ALIMENTATION ÉLECTRIQUE.
Step 2. Open the lower control compartment
door (see Figure 58 on Page 32) by pushing
on the right top corner of the door (the door is
hinged at the bottom).
[Optional] Remove the control compartment
door by sliding the hinge pin, located at the
door’s left side, to the right until it disengages
from the left corner post hole. Pull the control
compartment door diagonally to the left, away
from the fireplace.
Step 3. Remove the front glass door/frame
from the appliance (see Page 32).
Step 4. Carefully remove the logs. Exercise
care so as not to break the logs.
In Canada:
THE CONVERSION SHALL BE CARRIED OUT IN ACCORDANCE WITH THE
REQUIREMENTS OF THE PROVINCIAL
AUTHORITIES HAVING JURISDICTION
AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN/CSA-B149.1
INSTALLATION CODE.
LA CONVERSION DEVRA ÊTRE
EFFECTUÉE CONFORMÉMENT AUX
RECOMMANDATIONS DES AUTORITÉS PROVINCIALES AYANT JURIDICTION ET CONFORMÉMENT AUX EXIGENCES DU CODE D'INSTALLATION
CAN/CSA-B149.1.
Gas conversion kits are available to adapt your
appliance from the use of one type of gas to
the use of another. These kits contain all the
necessary components needed to complete
the task including labeling that must be affixed
to ensure safe operation.
Kit part numbers are listed below, and the
following steps detail the conversion procedure. Refer to the instructions provided with
the conversion kit when performing any gas
conversion.
Electronic SIT Systems
Natural Gas to Propane Gas
Conversion Kits
ModelsCatalog No.
MPDP35H8608
MPDP40H8609
Propane Gas to Natural Gas
Conversion Kits
ModelsCatalog No.
MPDP35H8610
MPDP40H8611
38
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 39
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
Step 5. On the left side of the burner, remove
the two securing screws. Remove the burner
assembly.
Step 6. Refer to Figure 64 and the instructions
provided with the SIT Regulator Conversion
Kit. Using a Torx T20 (with 1/4” shank and
center hole) or slotted screwdriver, remove and
discard the two (2) pressure regulator mounting screws, pressure regulator tower, the
diaphragm assembly (A) (if applicable) and the
spring (B). Discard all removed components.
Ensure the rubber gasket (C), which is prefitted as part of the assembly, is properly
positioned (see Figure 64).
Step 7. Install the new Stepper Motor pressure regulator assembly using the supplied
screws as shown in Figure 64. Tighten screws
securely (reference torque = 25 lb. in.).
Step 8. Install the enclosed identification label
to the valve body where it can be easily seen.
Step 10. See Figure 63 and replace the pilot
orifice. Remove the pilot hood assembly to
access the hexed pilot orifice. Remove and replace the orifice with the one provided with the
kit. Exercise extreme care to prevent damage to
or breakage of the igniter assembly.
Pilot Orifice
Figure 63
Step 11. Replace Burner Orifice
A. Remove the orifice from the manifold and
replace it with the one provided in the kit.
See Table 9 for orifice sizes for natural and
propane models. Figure 65 illustrates the ori-
fice. Use pipe joint compound or Teflon tape
on all pipe fittings before installing (ensure
propane resistant compounds are used in
propane applications, do not use pipe joint
compounds on flare fittings).
B. Retrieve the burner and hold the venturi tube
above the orifice. Place the shutter adjusting
rod in the slot of the shutter arm (see Figure 61 on Page 34). Set the burner assembly into its
position and secure the burner assembly with
the two screws previously removed.
Burner Orifice Sizes
Elevation 0-4500 feet ( 0-1372 meters)
ModelNat.Gas
MPDP35
MPDP40
Table 9
drill size (inches)
#42 (.093")*
H3721•
#36 (.1065")*
18L40•
* Standard size installed at factory
• Part /Cat. Number
Propane
drill size (inches)
#54 (.055")*
99K79•
#52 (.063")*
21L01•
size
Figure 65
Step 12. Reassemble the remaining components by reversing the procedures outlined in
the preceding steps.
Step 13. Attach the conversion label provided
in the conversion kit next to the rating plate on
the appliance.
Step 14. Turn on gas supply and test for gas
leaks (refer to Page 28).
Step 15. Relight the main burner. The lighting
instructions can be found on the lighting label
in the control compartment or in the Care and
Operation Manual provided with the appliance.
Verify proper burner ignition and operation.
See Burner Adjustments and Burner Flame Appearance on Pages 32 and 33.
Inspect the pilot system for proper flame. The
pilot flame should engulf the flame sensor as
shown in Figure 53 on Page 28.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Step 16. Using a manometer, test the inlet and
manifold gas pressures. See Tables 2 and 3 on
Page 4 and Figure 64.
ALWAYS TEST PRESSURES WITH THE VALVE
REGULATOR CONTROL AT THE HIGHEST
SETTING.
39
Page 40
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPDP35/40) • INSTALLATION INSTRUCTIONS
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design,
materials, specifications, and prices, and also to discontinue colors, styles, and products.
Consult your local distributor for fireplace code information.
LENNOX®, the LENNOX design, DAVE LENNOX, the image of DAVE LENNOX and other related
LENNOX marks are registered or common law trademarks of Lennox Industries Inc. and are used
with permission.