Lennox MPDT33RPM, MPD35CNM, MPDR33RNM, MPDR33RPM, MPD35RNM Installation Instructions Manual

...
Page 1
INSTALLATION INSTRUCTIONS
AVERTISSEMENT : Assurez-vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d’incindie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result, causing property damage, personal injury, or death.
WARNING /AVERTISSEMENT/AVISO
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
UNE SURFACE VITRÉE CHAUDE
PEUT CAUSER DES BRÛLURES.
LAISSER REFROIDIR LA SURFACE
VITRÉE AVANT D'Y TOUCHER.
NE PERMETTEZ JAMAIS À UN ENFANT
DE TOUCHER LA SURFACE VITRÉE.
EL VIDRIO CALIENTE
CAUSARÁ QUEMADURAS.
USTED DEBE NUNCA
TOCAR EL VIDRIO CALIENTE.
LOS NIÑOS DEBEN NUNCA
TOCAR EL VIDRIO.
- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
- Ne pas entreposer ni utilizer d’essence ni d’autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
Ne pas tenter d’allumer d’appareil.
Ne touchez à aucan interrupteur. Ne pas vous servir des téléphones se trouvant dans le bâtiment où vous trouvez.
Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournisseur.
Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le service des incindies.
- L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
MODELS
P/N 506015-07 Rev. B 06/2013
This manual is one of a set of two supporting this product. Refer to P/N 506017-06 for Care and Operation Instructions.
Ce manuel est disponible en francais, simplement en faire la demande. Numéro de la pièce 506223-43.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
INSTALLATEUR : Laissez cette notice avec l’appareil. CONSOMMATEUR : Conservez cette notice pour consultation ultérieure.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
MPDT33RNM MPDT33RPM MPDR33RNM MPDR33RPM MPD35CNM MPD35RNM
Please read and understand these instructions
MILLIVOLT:
MPD35RPM MPD40CNM MPD40RNM MPD40RPM MPD45RNM MPD45RPM
OTL No. 116-F-13g-5
MPDT33RNE MPDR33RNE MPD35CNE MPD35RNE MPD35RNE-R
US
before starting installation.
ELECTRONIC:
MPD40CNE MPD40RNE MPD45RNE MPD40RNE-R
Portland
Page 2
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
TABLE OF CONTENTS
Packaging .................................................... 2
Introduction ................................................. 2
General Information ..................................... 2
Requirements for the
Commonwealth of Massachusetts ............ 4
Cold Climate Insulation ................................ 5
Manufactured Home Requirements ............. 5
Location ........................................................5
Vent Termination Clearances ....................... 6
Appliance and Vent Clearances .................... 8
Pre-Installation Steps ................................... 9
Typical Installation Sequence ...................... 9
Detailed Installation Steps ............................ 9
Step 1. Framing ............................................ 9
Fireplace and Framing Specifications ....... 10
Step 2. Routing Gas Line ........................... 11
Step 3. Preparing Appliance Vent Collar ..... 12
Step 4. Installing Vent System ................... 12
Vertical Termination Systems .................. 13
Vent Section Length Chart ...................... 13
Vertical Vent Tables and Figures .............. 16
Horizontal Termination System ............... 18
Horizontal Vent Tables and Figures ......... 20
Venting Using Flexible Vent Pipe ............. 23
Step 5. Field Wiring ................................... 24
Step 6. Optional Blower Kit Wiring ............ 25
Step 7. Connecting Gas Line ..................... 25
Step 8. Verifying Appliance Operation ........... 26
Step 9. Installing Logs ............................. 27
Step 10. Remove/Install Glass Door .......... 31
Step 11. Burner Adjustments ..................... 31
Step 12. Hood Installation .......................... 33
Finishing Requirements ............................. 33
Step 13. Attaching Safety-in-Operation
Warnings .................................... 34
Installation Accessories ............................. 35
Gas Conversion Kits ................................... 37
Please read and understand these instructions before beginning your
installation.
PACKAGING
The assembled vented gas fireplace heater is packaged with:
• (1 set) Logs (packaged in a carton inside the
firebox).
• (1 bag) Glowing Embers (in bottom compart­ment).
• Literature Kit (envelope in bottom com­partment containing Care and Operation Instructions, Installation Instructions, Safety­In-Operation Warning Labels, Warranty).
• (1) U-Shaped Vent Restrictor (attached to Literature Kit envelope).
• (1) Hood (inside rebox).
INTRODUCTION
The Millivolt appliances have a millivolt gas control valve with piezo ignition system. If any optional accessories that will require electrical power are to be installed, the electrical power must be provided at the time of appliance installation.
The Electronic appliances are designed to operate on natural or propane gas. An electronic intermittent pilot ignition system provides safe, efficient operation. External electrical power is required to operate these units. In the event of a power outage, four (4) "AA" batteries (in battery holder) provide backup power for appliance operation (excluding [optional] blower).
These vented gas fireplace heaters are sealed combustion, air-circulating gas fireplaces designed for residential applications.
Approved Vent Components
These fireplaces are designed, tested and listed for operation and installation with the following vent components only:
®
Secure Vent
nents manufactured by Security Chimneys International,
Secure Flex
manufactured by Security Chimneys Inter­national and
Z-FLEX
to UL1777 and ULCS635 manufactured by Flexmaster Canada Limited.
Use only the correct size venting (4-1/2" inner and 7-1/2" outer).
These approved vent system components are labeled for identification. DO NOT use any other manufacturer’s vent components with these appliances.
Direct-Vent System Compo-
®
Flexible Vent Components
®
Model GA Venting Systems listed
GENERAL INFORMATION
WARNING
Young children should be care­fully supervised when they are in the same room as the appli­ance. Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to a fireplace or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
AVERTISSEMENT
Les jeunes enfants devraient être surveillés étroitement lorsqu’ils se trouvent dans la même pièce que l’appareil. Les tout petits, les jeunes enfants ou les adultes peuvent subir des brûlures s’ils viennent en contact avec la sur­face chaude. Il est recommandé d’installer une barrière physique si des personnes à risques habi­tent la maison. Pour empêcher l’accès à un foyer ou à un poêle, installez une barrière de sécu­rité; cette mesure empêchera les tout petits, les jeunes enfants et toute autre personne à risque d’avoir accès à la pièce et aux surfaces chaudes.
Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition.
Les enfants et les adultes devraient être informés des dangers que posent les températures de surface élevées et se tenir à distance afin d’éviter des brûlures ou que leurs vêtements ne s’enflamment.
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERATION MAY VOID THE WARRANTY, CERTIFICATION AND LISTINGS OF THIS UNIT.
2
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 3
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
WARNING
Improper installation, adjust­ment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
WARNING
Failure to comply with these installation instructions will result in an improperly installed and operating appliance, voiding its warranty. Any change to this appliance and/or its operating controls is dangerous.
WARNING
Clothing or other flammable material should not be placed on or near the appliance.
AVERTISSEMENT
On ne devrait pas placer de vêtements ni d’autres matières inflammables sur l’appareil ni à proximité.
WARNING
Any safety screen or guard removed for servicing the appli­ance must be replaced prior to operating the appliance.
AVERTISSEMENT
Tout écran ou protecteur retiré pour permettre l’entretien de l’appareil doit être remis en place avant de mettre l’appareil en marche.
WARNING
Improper installation or use of this appliance can cause serious injury or death from fire, burns, explosion or carbon monoxide poisoning.
WARNING
Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury.
AVERTISSEMENT
Risque de dommages ou de blessures si les pièces ne sont pas installées conformément à ces schémas et ou si des pièces autres que celles spécifiquement approuvées avec cet appareil sont utilisées.
NOTE: Installation and repair should be done by a qualified service person. The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etcetera. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
Remarque: L’installation et la réparation devrait être confiées à un technicien qualifié. L’appareil devrait faire l’objet d’une inspection par un technicien professionnel avant d’être utilisé et au moins une fois l’an par la suite. Des nettoyages plus fréquents peuvent être nécessaires si les tapis, la literie, et cetera produisent une quantité importante de pous-sière. Il est essentiel que les compartiments abritant les commandes, les brûleurs et les conduits de circulation d’air de l’appareil soient tenus propres.
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any parts of the control system and any gas control which has been under water.
Ne pas utiliser cet appareil s’il a été plongé, même partiellement, dans l’eau. Appeler un technicien qualifié pour inspecter l’appareil et remplacer toute partie du système de commande et toute commande qui a été plongée dans l’eau.
Only trim kit(s) supplied by the manufacturer shall be used in the installation of this appliance.
Seules les trousses de garniture fournies par le fabricant doivent être utilisées pour l’installation de cet appareil.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
These appliances comply with National Safety Standards and are tested and listed by OMNI­Test Laboratories, Inc. (Report No. 116-F-13g-5) to ANSI Z21.88-2009 (in Canada, CSA-2.33-
2009), and CAN/CGA-2.17-M91(R2009) in both USA and Canada, as vented gas fireplace heaters.
Both millivolt and electronic versions of these appliances are listed by OMNI-Test Laboratories for installation in bedrooms and Manufactured Homes.
Misc. Codes / Standards
The Installation must conform to local codes or, in the absence of local codes, with the
National Fuel Gas Code, ANSI Z223.1 / NFPA 54 - latest edition (In Canada, the current CAN/
CGA-B149.1 installation code).The appliance, when installed, must be electrically grounded and wired in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70 - latest edition, or the Canadian Electrical Code, CSA C22.1 - latest edition.
Provide adequate clearances around air openings and adequate accessibility clearance for service and proper operation. Never obstruct the front or back openings of the appliance.
These appliances are designed to operate on natural or propane gas only. The use of other fuels or combination of fuels will degrade the performance of this system and may be dangerous.
These fireplaces are designed as supplemental heaters. Therefore, it is advisable to have an alternate primary heat source when installed in a dwelling.
These appliances must not be connected to a chimney or flue serving a separate solid fuel burning appliance.
Both millivolt and electronic systems can be operated during a power outage, and feature manually operated hi-low flame control. The BTU Input for these appliances is shown in Table 1.
Models
MPD33
MPD35
MPD40
MPD45
Table 1 - Input (BTU/HR) Gas Valves (Millivolt and Electronic)
Input Rate (BTU/HR)
Nat. Gas Prop. Gas
17,500 high
11,700 low
20,000 high
12,800 low
27,000 high
18,500 low
29,000 high
20,500 low
17,500 high
14,000 low
20,000 high
15,200 low
27,000 high
21,500 low
29,000 high
22,500 low
3
Page 4
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
Gas Pressure - All Models
Tables 2 and 3 show the appliances' inlet and manifold gas pressure requirements:
Fuel # Minimum Maximum
Natural
Gas
Propane
4.5" WC
(1.12 kPa)
11.0" WC
(2.74 kPa)
10.5" WC
(2.61 kPa)
13.0" WC
(3.23 kPa)
Table 2: Inlet Gas Supply Pressure
Fuel # Low High
Natural
Gas
Propane
1.6" WC
(0.40 kPa)
6.3" WC
(1.57 kPa)
3.5" WC
(0.87 kPa)
10.0" WC
(2.49 kPa)
Table 3: Manifold Gas Supply Pressure
Test gauge connections are provided on the front of the millivolt and electronic gas control valve (identified IN for the inlet and OUT for the manifold side). The control valves have a 3/8" (10 mm) NPT thread inlet and outlet side of the valve (refer to Figures 1 and 2).
Propane tanks are at pressures that will cause damage to valve components. Verify that the tanks have step down regulators to reduce the pressure to safe levels.
The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).
Orifice Sizes - Sea Level to High Altitude (All Models)
These appliances are tested and approved for installation at elevations of 0-4500 ft (0-1372 m) above sea level using the standard burner orifice sizes (marked with an "*" in Table 4). For elevations above 4500 ft, contact your gas supplier or qualified service technician.
Deration - At higher elevations, the amount of BTU fuel value delivered must be reduced by either:
• Using gas that has been derated by the gas
company.
• Changing the burner orice to a smaller size
as regulated by the local authorities having jurisdiction and by the (USA) National Fuel Gas Code NFPA 54 - latest edition / ANSI Z223.1 or, in Canada, the CAN/CGA-B149.1
codes - latest edition. Install the appliance according to the regulations of the local authorities having jurisdiction and,
4
in the USA, the National Fuel Gas Code NFPA 54 - latest edition / ANSI Z223.1 or, in Canada, the CAN/CGA-B149.1 - latest edition.
Flame breadth, height and width will diminish 4% for every 1,000 feet of altitude. Gas Valve
Diagrams
. See Figure 1 for Millivolt models
and Figure 2 For Electronic Models.
Burner Orifice Sizes
Elevation 0-4500 feet ( 0-1372 meters)
Model
Series
MPD33
MPD35
MPD40
MPD45
Table 4
Nat.Gas
drill size (inches)
#47 (0.0785")*
99K74 •
#44 (0.086")*
60J80 •
#38 (0.102") *
99K76 •
#37 (0.104")*
24M10 •
* Standard size installed at factory
• Part /Cat. Number
Propane
drill size (inches)
0.048"
99K78 •
#55 (0.052")*
19L52 •
0.062"
21L01 •
#52 (0.0635")*
37G00 •
In Canada - CAN/CGA-2.17-M91 (R2009) (high altitude): THE CONVERSION SHALL BE CARRIED OUT BY A MANUFACTURER’S AUTHORIZED REPRESENTATIVE,IN ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURER, PROVINCIAL OR TERRITORIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN/CGA-B149.1 OR CAN/CGA-B149.2 INSTALLATION CODES.
Main Gas Control Knob
OFF/PILOT/ON
N
O
T
O
t
i
L
I
P
O
F
F
OUT
IN
Manifold Pressure Tap
Inlet Pressure Tap
Figure 1 - SIT Millivolt
Pilot Adjustment
L
I
P
W
O
L
H
I
HI/LO Variable Flame Height Adjustment
Screw
T
O
H T P T H T P T
Gas Valve
(from DFC Wire Harness)
Inlet (IN) Test Port
Manifold (OUT) Test Port
Orange Wire
(from DFC Wire
Harness)
Main Gas Inlet
3/8" NPT
Green Wire
Figure 2 - SIT Electronic Gas Valve
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
These fireplaces are approved for installation in the US state of Massachusetts if the following additional requirements are met:
• Install this appliance in accordance with
Massachusetts Rules and Regulations 248 C.M.R.
• Installation and repair must be done by
a plumber or gas fitter licensed in the Commonwealth of Massachusetts.
• The exible gas line connector used shall
not exceed 36 (92 cm) in length.
• The individual manual shut-off must be a
T-handle type valve.
Massachusetts Horizontal Vent Requirements in the Commonwealth of Massachusetts, horizontal terminations installed less than seven (7) feet above the finished grade must comply with the following additional requirements:
• A hard wired carbon monoxide detector
with an alarm and battery back-up must be installed on the floor level where the gas fireplace is installed. The carbon monoxide detector must comply with NFPA 720, be ANSI/UL 2034 listed and be ISA certified.
• A metal or plastic identication plate must be
permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade and be directly in line with the horizontal termination. The sign must read, in print size no less than one-half (1/2) inch
in size, GAS VENT DIRECTLY BELOW. KEEP
CLEAR OF ALL OBSTRUCTIONS.
Hi/Lo Flame Control Knob
Yellow Ground Wire (from DFC Wire Harness)
Page 5
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room. It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests, if floor is above ground level. Gas line holes and other openings should be caulked or stuffed with unfaced fiberglass insulation.
If the fireplace is being installed on a cement slab in cold climates, a sheet of plywood or other raised platform can be placed underneath to prevent conduction of cold transferring to the fireplace and into the room. It also helps to sheetrock inside surfaces and tape for maximum air tightness and caulk firestops.
MANUFACTURED HOME REQUIREMENTS
This appliance may be installed in an aftermarket permanently located, manufactured home and must be installed in accordance with the manufacturer's instructions.
Cet appareil peut être installé cómme du matériel d'origine dans une maison préfabriquée (É.U. seulement) ou mobile et doit être installé selon les instructions du fabricant.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
TOP VENT
APPLICATION
APPLICATION
TOP VENT
INSTALLATION
VERTICAL VENT (Rear Vent Application)
HORIZONTAL VENT (Rear Vent Application with a chase)
RECESSED
REAR VENT
APPLICATION
TOP VENT
APPLICATION
TOP VENT
APPLICATION
HORIZONTAL VENT (Rear Vent Application without a chase)
Figure 3 - Typical Locations
REAR VENT
APPLICATION
TOP VENT
APPLICATION
TOP VENT
APPLICATION
HORIZONTAL VENT (Top Vent Application)
VERTICAL VENT (Top Vent Application)
Cet appareil doit être utilisé uniquement avec le type de gaz indiqué sur la plaque signalétique. Cet appareil ne peut être converti à d'autres gaz, sauf si une trousse de conversion est utilisée.
CAUTION: Ensure that the cross mem­bers are not cut or weakened during installation. The structural integrity of the manufactured home floor, wall, and ceiling / roof must be maintained.
CAUTION: This appliance must be ground­ed to the chassis of the manufactured home in accordance with local codes or in the absence of local codes, with the National Electrical Code ANSI / NFPA 70
- latest edition or the Canadian Electrical Code CSA C22.1 - latest edition.
LOCATION
In selecting the location, the aesthetic and functional use of the appliance are primary concerns. However, vent system routing to the exterior and access to the fuel supply are also important.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies (Figure 3).
En raison des températures élevées, l’appareil devrait être installé dans un endroit où il y a peu de circulation et loin du mobilier et des tentures (Figure 3).
The location should also be free of electrical, plumbing or other heating/air conditioning ducting.
These direct-vent appliances are uniquely suited for installations requiring a utility shelf positioned directly above the fireplace. Util­ity shelves like these are commonly used for locating television sets and decorative plants.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Be aware that this is a heat producing appliance. Objects placed above the unit are exposed to elevated temperatures.
Do not insulate the space between the ap­pliance and the area above it (see Figure 8).
The minimum height from the base of the appli­ance to the underside of combustible materials used to construct a utility shelf in this fashion is shown in Figure 8.
The appliance must be mounted on a fully supported base extending the full width and depth of the unit. The appliance may be located on or near conventional construction materials. However, if installed on combustible materials, such as carpeting, vinyl tile or other combustible material other than wood flooring, the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance.
5
Page 6
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
VENT TERMINATION CLEARANCES
These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 in Canada.
Vertical Vent Termination Clearances
Terminate multiple vent terminations according to the installation codes listed above and Figures 4 and 5.
12"
(305mm)
Minimum
Figure 4 - Multiple Terminations
Vertical Vent Termination Clearances
The vent / air intake termination clearances above the high side of an angled roof are as
TERMINATION HEIGHTS FOR VENTS ABOVE
Horizontal Overhang
2 FT MIN.
Termination
Storm Collar
Flashing
Concentric
Vent Pipe
FLAT OR SLOPED ROOFS
Vent
*H = MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING OF VENT
2 FT MIN.
Lowest
Discharge
Opening
H*
1 inch (25.4 mm) Minimum Clearance to Combustibles
Vertical
Wall
X
12
Roof Pitch is X/12
Figure 5 - Termination Heights for Vents Above Flat or Sloped Roofs
shown in the following chart:
Termination Heights For Vents
Above Flat Or Sloped Roofs Ref. NFPA 54 / ANSI Z223.1
Roof Pitch *H (ft) *H (m)
Flat-6/12 1.0 0.3 6/12-7/12 1.25 0.38 7/12-8/12 1.5 0.46 8/12-9/12 2.0 0.61
9/12-10/12 2.5 0.76 10/12-11/12 3.25 0.99 11/12-12/12 4.0 1.22 12/12-14/12 5.0 1.52 14/12-16/12 6.0 1.83 16/12-18/12 7.0 2.13 18/12-20/12 7.5 2.29 20/12-21/12 8.0 2.44
Horizontal Vent Termination Clearances
The horizontal vent termination must have a minimum of 6" (152 mm) clearance to any overhead combustible projection of 2-1/2" (64 mm) or less, see Figure 6. For projections exceeding 2-1/2" (64 mm), see Figure 6. For additional vent location restrictions, refer to Figure 7 on Page 7.
Horizontal Vent Termination Clearances
Combustible Projection
2-1/2”
or less in length
Combustible Projection greater
than 2-1/2” in length
Ventilated
Soffit
Unventilated
Soffit
18"
(457 mm)
12"
(305 mm)
Side Elevation View
Termination Kit
Figure 6 - Horizontal Vent Termination Clearances
6"
(152 mm)
All horizontal terminations may be located as close as 6” (152mm) to any (non-combustible and combustible) exterior sidewall. This distance may be decreased to 2” (51mm) for non-­combustible exterior sidewalls only, if the SV4.5HT-2 termination is used.
Termination Kit
NOTE: See Figure 34 on Page 20 for the exterior wall recess
allowances of the square horizontal termination.
6
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 7
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS
NOTE: Local Codes Or Regulations
* See Item D in the Text Below.
Exterior Wall
*18”
Horizontal Termination
Inside Corner
B
V
L
V
6”
Detail D
F
V
A
Ventilated Soffit
V
Fixed
Closed
Window
V
C
X
= Air Supply Inlet
C
C
C
V
Inside
Corner Detail
V
A
B
Operable
V
Window
B
B
= Vent Termination
G
B
= Area where Termination is not Permitted
May Require Different Clearances.
NOTE: Location Of The Vent Termination Must Not Interfere With Access To The Electrical Service.
= 9” in U.S.
= 12” in Canada
3 ft.
X
J
3 ft.
P
N
V
Q
H
M
V
I
K
N
O
D
E
V
X
Minimum Clearances Canadian Installation * US Installation **
A = Clearance above grade, veranda, porch, deck or balcony.
B = Clearance to window or door that may be opened 6" (15.2 cm) for appliances < 10,000 BTU/hr (3kW),
C = Clearance to permanently closed window 12" (305 mm) recommended to prevent window conden-
D = Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 18" (458 mm)
E = Clearance to unventilated soffit 12" (30 cm) 12" (30 cm) F = Clearance to outside corner 5" (12.7 cm) 5" (12.7 cm) G = Clearance to inside corner 2" (5.08cm) minimum - SV4.5HT-2 •
H = Clearance to each inside of center line extended above meter / regulator assembly
I = Clearance to service regulator vent outlet 3 feet (91 cm) * 3 feet (91 cm) **
J = Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance
K = Clearance to mechanical air supply inlet 6 feet (1.83 meters) * 3 feet (91 cm) above, if within 10 feet (3 m) horizontally** L = Clearance above paved sidewalk or paved
driveway located on public property M = Clearance under veranda, porch, deck or
balcony N = Depth of Alcove (Maximum) 6 feet (1.83m)* 6 feet (1.83m)** O = Clearance to Termination (Alcove) 6" (15.2mm)* 6" (15.2mm)** P = Width of Alcove (Minimum) 3 feet (91cm)* 3 feet (91cm)** Q = Clearance to Combustible Above (Alcove) 18" (457mm)* 18" (457mm)** * In accordance with the current CAN/CGA-B149.1 National Gas and Propane Installation Code.
** In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Codes. ‡ A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings. *‡ Only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor.
• 2" Clearance to Non-Combustibles for SV4.5HT-2 Only.
12" (30 cm) * 12" (30 cm) **
6" (15.2 cm) for appliances < 10,000 BTU/hr (3kW),
12" (30 cm) for appliances > 10,000 BTU/hr (3kW)
9" (23 cm) for appliances > 10,000 BTU/hr (3kW) and < 50,000 BTU/hr (15kW), 12" (30 cm) for appliances > 50,000 BTU/hr (15kW)**
9" (229 mm) recommended to prevent window con-
sation
densation
18" (458 mm) 18" (458 mm)
2" (5.08cm) minimum - SV4.5HT-2 •
6" (15.2cm) minimum - SV4.5HTSS •
3 feet (91 cm) within a height of 15 feet above the meter / regulator assembly *
6" (15.2 cm) for appliances < 10,000 BTU/hr (3kW), 12" (30 cm) for appliances > 10,000 BTU/hr (3kW)
6" (15.2cm) minimum - SV4.5HTSS •
3 feet (91 cm) within a height of 15 feet above the meter / regulator assembly **
6" (15.2 cm) for appliances < 10,000 BTU/hr (3kW), 9" (23 cm) for appliances > 10,000 BTU/hr (3kW) and < 50,000 BTU/hr (15kW), 12" (30 cm) for appliances > 50,000 BTU/hr (15kW)**
7 feet (2.13 m) ‡ 7 feet (2.13 m) ‡
12" (30 cm) * ‡ 12" (30 cm) ‡
Figure 7 - Exterior Horizontal Vent Termination Clearance Requirements
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
7
Page 8
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
12 (305) MANTEL
10 (254) MANTEL
8 (203) MANTEL
6 (152) MANTEL
4 (102) MANTEL
4
(102)
14
(356)
12
(305)
10
(254)
2 (51) MANTEL
TOP OF APPLIANCE
6
(152)
NOTE - Hood shown as positioned in louvered front model. The hood position in the flush faced front model is lower than shown.
8
(203)
MANTEL CLEARANCES
Inches (mm)
MINIMUM CLEARANCES TO COMBUSTIBLES
Appliance And Vent Clearances
The appliance is approved with zero clearance to combustible materials on all sides (as detailed in Table 5), with the following exception: When
the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend beyond the front edge of the unit. In addition, when the unit is recessed, the side walls surrounding
the unit must not extend beyond the front edge of the unit (see Figure 3).
MINIMUM CLEARANCES* Inches (millimeters)
Back 1/2 (13)
Sides 1/2 (13)
Top of Fireplace
Floor 0 (0)
From Bottom of Unit To Ceiling 64 (1626)
Vent 3 (76) Top* / 1 (25.4) Sides & Bottom
SERVICE CLEARANCES Feet (meters)
Front 3 feet (0.9 meters)
Table 5
*NOTE: 3" (75 mm) above any horizontal/inclined vent component.
**NOTE: See Page 10, Step 1 for clearance requirements to the nailing
flange located at each side of the unit and any screw heads adjacent to it.
0 (0) from Spacers or Dimples
0 (0) from Spacers or Dimples **
3 (76)
0" (0 mm) with standoff(s) in vertical
position (see Figure 11)
Models
MPDT33 MPDR33
MPD35 45-3/4 (1162) 47-1/2 (1207) 35-1/4 (895) 35-1/4 (895) MPD40
MPD45
Shelf Above Fireplace With Rear Venting
Figure 8 -
Top Vent - with One 90 Degree Elbow Rear Vent - Straight Out The Back
Secure Vent
43-3/4 (1111) 45-1/2 (1156) 33-1/4 (845) 33-1/4 (845)
50-3/4 (1289) 52-1/2 (1334) 40-1/4 (1022) 40-1/4 (1022)
Do not insulate the space between the appliance and the area above it.
Shelf Height
(see table)
Shelf Height Minimum Clearances
Combustible Shelf Height - inches (millimeters)
®
®
Secure Flex
Do not insulate the space between the ap­pliance and the area above it.
Shelf Above Fireplace With Top Venting
Secure Vent Secure Flex
Shelf Height
(see table)
Inches (millimeters)
Hearth Extension - A hearth extension is not required with this appliance.
If a hearth extension is used, do not block the lower control compartment door. Any hearth extension used is for appearance only and does not have to conform to standard hearth extension installation requirements.
Shelf Height - To provide for the lowest possible shelf surface, use the
alternate rear vent outlet, the venting attached to the top vent should be routed in a way to minimize obstructions to the space above the appliance.
Do not insulate the space between the appliance and the area above it (see Figure 8). The minimum height from the base of the appliance to
the underside of combustible materials used to construct a utility shelf in this fashion is shown in Figure 8.
Wall Finishes / Surrounds / Mantels
NOTE: Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined by the appliance front face (black sheet metal). Never allow combustible materials to be positioned in front
of or overlapping the appliance face (see Figures 61 and 62 on Page 34). Non-combustible materials, such as surrounds and other appliance trim,
may be installed on the appliance face with these exceptions: they must not cover any portion of the removable glass panel or control compartment.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel. See Figure 9. Mantels constructed of non­combustible materials may be installed at any height above the appliance opening; however, do not allow anything to hang below the fireplace hood.
Minimum clearance requirements include any projections such as shelves, window sills, mantels, etc. above the appliance.
NOTE: We recommend the use of high temperature paint (rated 175° F or higher) on the underside of the mantel.
8
Figure 9 - Minimum Mantel Clearances
At 6" minimum side wall clearance, a combustible wall can project to any length.
6
(152)
Figure 10 - Minimum Distance to Side Wall
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Top View of
Fireplace
o
45
3-1/2
Combustible Materials Allowed In Shaded Area
(89)
“Safe Zone”
Combustible Walls shown in dark gray
Combustible materials may project beyond either side of the fireplace opening as long as they are kept within the shaded area illustrated here.
Inches (millimeters)
Page 9
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
PRE-INSTALLATION STEPS
The appliance is shipped with all gas controls and components installed and pre-wired.
Before installing the appliance, follow these steps:
1. Remove the shipping carton.
2. Remove the shipping pad, exposing the front glass door.
3. Open the two spring latches securing the glass door (under the firebox floor). Remove the door by tilting it outward at the bottom and lifting it up. Set the door aside, taking care to protect it from inadvertent damage.
See Removing The Glass Enclosure Panel
on Page 32.
5. Remove the log set from the firebox. Handle
logs carefully to prevent breakage.
6. Remove the embers and volcanic stone from the control compartment.
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation is outlined below; however, each installation is unique and may result in variations to the steps described. See the pages referenced in the following steps for detailed procedures.
Step 1. FRAMING (Page 10): Construct the appliance framing. Position the appliance within the framing and secure with nailing brackets.
IMPORTANT! Bend up the appropriate header
spacing standoffs for the drywall/finish material thickness to be used (see Figure 11).
Bend up the outer pair for 1/2" materials and the inner pair for 5/8" materials.
Bend out the appropriate nailing flanges for the drywall/finish material to be used. Nailing flanges are provided for flush framing, 1/2" and 5/8" framing depths (see Figure 11).
Step 2. ROUTING GAS LINE (Page 12): Route gas supply line to appliance location.
Step 3. PREPARING APPLIANCE VENT COLLAR
(MPD35/40/45 models with combined top/rear vent) (Page 13).
Step 4. INSTALLING VENT SYSTEM (Page 13): Install the vent system and exterior termination.
Step 5. FIELD WIRING (Page 25).
a. Millivolt Appliances - Install the operating
control switch (not factory provided). If installing the optional forced air circulating blower, bring in electrical service line.
b. Electronic Appliances - Field wire and install operating control switch.
Step 6. WIRING - OPTIONAL FORCED AIR BLOWER KIT (Page 26).
Step 7. CONNECTING GAS LINE (Page 26):
Make connection to gas supply. Step 8. VERIFYING APPLIANCE OPERATION
(Page 27).
Step 9. INSTALL VOLCANIC STONE, GLOWING EMBERS, AND LOGS (Page 28).
Step 10. INSTALLING GLASS DOOR ASSEMBLY (Page 32).
Step 11. BURNER ADJUSTMENTS (Page
32): Adjust burner to ensure proper flame appearance.
Step 12. HOOD INSTALLATION (Page 34). Step 13. ATTACHING SAFETY-IN-OPERATION
WARNINGS (Page 35).
DETAILED INSTALLATION STEPS Step 1. FRAMING
Frame the appliance as illustrated in Figures 12 and 13 on Pages 11 and 12 (Figure 13
applies to corner framing installations only). All framing details must allow for a minimum clearance to combustible framing members as shown in Table 5 on Page 8.
If the appliance is to be elevated above floor level, a solid continuous platform must be constructed below the appliance.
Headers may be in direct contact with the appliance top standoff spacers when they are bent up vertically, maintaining the 3" clearance to the fireplace top, but must not be supported by them or notched to fit around them. All construction above the appliance must be self-supporting. DO NOT use the appliance
for structural support.
Secure the fireplace to the side framing members using the unit’s nailing flanges - one top and bottom on each side of the fireplace front. See Figure 11. Use 8d nails or their equivalent.
Bend up the appropriate header spacing top standoffs before installing the fireplace.
Header Spacing Top Standoffs
(two pairs on front edge of firebox top)
Lift up outer pair for 1/2” finish materials
Side
Framing
NOTE: The nailing flanges, combustible members, and screw heads in areas directly adjacent to the nailing flanges are EXEMPT from the 1/2" clearance to combustible requirements for the firebox outer wrapper.
Combustible framing may be in direct contact with the nailing flanges and may be located closer than 1/2" from screw heads and the firebox wrapper in areas adjacent to the nailing flanges.
Frame the opening to the exact dimensions specified in the framing details in this manual.
Figure 11 - Unit Secured to Framing by
Nailing Flange
IMPORTANT!
Lift up inner pair for 5/8” finish materials
Unit Nailing Flange
(No clearance to combustible framing is required)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
9
Page 10
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
Framing
Model A B C D E
MPDT33
MPDR33
MPD35
MPD40
MPD45
Diagrams, illustrations and photographs are not to scale. Consult installation instructions. Product designs, materials, dimensions, specifications, colors, and prices are subject to change or discontinuance without notice.
Fireplace
Model
MPDT33 62 45 64 49 MPDR33 61 53 64 55
MPD35 62 53 60 55 MPD40 67 59 67 60 MPD45 67 59 67 59
33-1/4 33-1/4 --- 37-3/4 12-7/8
845 845 --- 959 327
in. 33-1/4 33-1/4 19-5/8 --- 12-7/8
mm 845 845 498 --- 327
in. 35-1/4 35-1/4 21-11/16 39-3/4 16
mm 895 895 551 1010 406
in. 40-1/4 40-1/4 26-11/16 44-3/4 16
mm 1022 1022 678 1137 406
in. 45-1/4 40-1/4 26-11/16 44-3/4 16
mm 1149 1022 678 1137 406
Notes
Thermal Efficiency (%)
Natural Gas Propane
AFUE EnerGuide
(P4)
AFUE EnerGuide
(P4)
Based on CSA P.4.1-09
VENT FRAMING: TOP VENT WITH ONE 90° ELBOW
VENT FRAMING: REAR VENT WITH NO ELBOWS
B
1/2
10-1/2
(
)
267
7
(178)
5-1/8 (130)
7
(178)
5-1/8
D
(130)
C
E
A
A
Dimension “E” is the required framing depth when the finish material (drywall) thickness is 1/2 in. (13mm).
Framing should be constructed of 2x4 or larger lumber.
12-1/8
(308)
12-1/8
(308)
Inches (mm)
Vertical Venting through the Ceiling
Frame ceiling opening: Use a plumb line from the ceiling above the appliance to locate center of the vertical run. Cut and/or frame an opening,
10-1/2" x 10-1/2" (267 mm x 267 mm) inside dimensions, about this center mark (see Figure 20).
Top View
Rear/Side
Framing
Spacers
Header
Spacing
Top
Standoffs
Notes: [1] MPD models have a top and rear vent. MPDR models
have a rear vent only. MPDT models have a top vent only. [2] Collars protrude one inch on MPDT33 and MPDR33 models.
G
H
Concentric Flue:
4-1/2” (114 mm);
Flue Combustion Air 7-1/2” (190 mm).
See Notes [1] and [2].
J
Front View
E
A
D
3 (76)
Gas Inlet (either
side and bottom)
Optional Electrical Inlet
Knockout requiring a
C
B
Field-Provided Junction
Box (either side)
1-3/8 (35)
K
6 (152)
Right Side View
N
L
1/2 (13)
See Note [2].
1-5/8 (42)
M
F (rear vent models only)
Electrical Inlet 2-3/4" x 2" (70 x 51 mm) Cover Plate with Knockout
Model A B C D E F G H J K L M N
MPD33
MPD35
MPD40
MPD45
in. 33-1/8 30-1/8 17 27-1/2 33-1/8 19-5/8 21-1/2 10-3/4 6-13/16 3 8-11/32 2-3/4 13
mm 841 765 432 699 841 498 546 273 173 76 212 70 330
in. 35-1/8 32-1/8 19 29-1/2 35-1/8 21-11/16 24-7/8 12-7/16 9 3 9 3 16
mm 892 816 483 749 892 551 632 316 220 76 220 76 406
in. 40-1/8 37-1/8 24 34-1/2 40-1/8 26-11/16 29-7/8 14-15/16 9 3 9 3 16
mm 1019 943 610 876 1019 678 759 379 220 76 220 76 406
in. 40-1/8 37-1/8 24 39-1/2 45-1/8 26-11/16 34-7/8 17-7/16 9 3 9 3 16
mm 1146 943 610 1003 1146 678 886 443 220 76 220 76 406
Figure 12 - Fireplace and Framing Specifications
10
Page 11
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
FIREPLACE FRAMING SPECIFICATIONS
Framing
Model A B C D E F
MPDT33
MPDR33
MPD35
MPD40
MPD45
NOTE:
Rear Vent Applications in Corner Installations: The horizontal vent length
(from a to b) must not exceed 28 inches (711 mm).
MPDT33 and MPDR33 Models: Dimensions A through F occur when one
45-degree elbow is connected directly to the appliance collar.
MPD35, MPD40, and MPD45 Models: Dimensions D through F occur when
one 45-degree elbow is connected directly to the appliance collar.
in. 33-1/8 48-1/2 34-5/16 17-3/16 24-1/4 5
mm 841 1232 872 437 616 127
in. 35-1/8 57-1/2 40-5/8 19-3/16 28-3/4 6-1/8
mm 892 1461 1032 487 730 156
in. 40-1/8 61-3/16 43-11/32 19-3/16 30-11/16 7-7/8
mm 1019 1554 1101 487 779 200
in. 45-1/8 66-3/8 46-15/16 19-3/16 33-3/16 9-3/4
mm 1146 1686 1192 487 843 248
Figure 13 - Corner Framing with Horizontal Termination
Step 2. ROUTING GAS LINE
Route a 1/2" (13 mm) gas line to the left side of the appliance as shown in Figure 14. Gas lines must be routed, constructed and made of materials that are in strict accordance with local codes and regulations. All appliances are factory-equipped with a flexible gas line connector and 1/2" shutoff valve. (See Step 7 on Page 26).
Never use galvanized or plastic pipe. Refer to Table 6 for proper sizing of the gas supply line, if black iron pipe is being used. Gas lines must be routed, constructed and made of materials that are in strict accordance with local codes and regulations. We recommend that a qualified individual such as a plumber or gas fitter be hired to correctly size and route the gas supply line to the appliance. Installing a gas supply line from the fuel supply to the appliance involves numerous considerations
Left Side Front
Corner of Fireplace
Framing
Pipe Coupling
(Recommended)
of materials, protection, sizing, locations, controls, pressure, sediment, and more. Certainly no one unfamiliar and unqualified should attempt sizing or installing gas piping.
Schedule 40 Pipe
Length (feet)
0-10 1/2" 3/8"
10-40 1/2" 1/2"
40-100 1/2" 1/2" 100-150 3/4" 1/2" 150-200 3/4" 1/2"
3"
(76 mm)
Also see Figure 12.
Figure 14 - Route Gas Line
6-1/2"
(152 mm)
Table 6 - Schedule 40 Black Iron Pipe ­Inside Diameter
Proper Sizing of Gas Line
Properly size and route the gas supply line from the supply regulator to the area where the appliance is to be installed per requirements outlined in the National Fuel Gas Code, NFPA 54 - latest edition (USA) or CAN/CGA-B149.1
- latest edition (Canada).
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
MPD and MPDR units
MPD and MPDT units
C
Back wall of chase/enclosure (including any finishing materials)
Natural
Gas
Propane
Gas
b
F
7" (178 mm)
E
D
a
A
B
Notes:
• All appliances are factory-equipped with
a flexible gas line connector and 1/2 inch shutoff valve (see Figure 47 on Page 27).
• See Massachusetts Requirements on Page 4 for additional requirements for installations
in the state of Massachusetts in the USA.
• The gas supply line should Not be connected
to the appliance until Step 7 (Page 26).
• A pipe joint compound rated for gas should be
used on the threaded joints. Ensure propane resistant compounds are used in propane applications. Be very careful that the pipe
compound does not get inside the pipe.
• It is recommended to install a sediment trap
in the supply line as close as possible to the appliance.
• Check with local building ofcial for local
code requirements.
IMPORTANT: If propane is used, be aware that if tank size is too small (i.e. under 100 lbs, if
this is the only gas appliance in the dwelling.
Ref. NPFA 58), there may be loss of pressure,
resulting in insufficient fuel delivery (which
can result in sooting, severe delayed ignition
or other malfunctions). Any damage resulting
from an improper installation, such as this,
is not covered under the limited warranty.
11
Page 12
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
A vent restrictor may be needed when
TOP VENT SEAL AND COVER PLATE REMOVAL
REAR VENT SEAL AND COVER PLATE REMOVAL
Step 3. PREPARING APPLIANCE VENT COLLAR (MPD35/-40/-45 models with
combined top/rear vent)
Each of the unit’s two vent collars are sealed with a cover plate and a seal plate and gasket. The cover, and seal plate and gasket must be removed from the vent collar being used. Refer to Figure 15 for top vent usage and Figure 16 for rear, and the following steps to prepare the appropriate collar for use.
From the vent collar being used, remove the four screws securing the vent seal plate and gasket. Remove and discard the seal plate and gasket.
When the top vent collar is being used, from inside the firebox, loosen the two screws in the keyhole slots of the cover plate and remove the remaining two cover plate securing screws. Remove and discard the cover plate. Reinstall
and securely tighten all four screws. When the rear vent collar is being used, from
inside the firebox, remove the two screws securing the lintel to the rear wall of the firebox, then remove the lintel. Remove the four cover plate securing screws. Remove and discard the cover plate.
Reinstall and securely tighten all four cover plate screws. Re-secure the lintel to the rear wall of the firebox.
WARNING
Failure to reinstall and securely tighten cover plate screws could result in leakage of flue products into the living space. Vent cover plate and vent seal cap must remain securely installed on unused vent collar. Failure to do so could result in leakage of flue products into living space.
Installation of Vent Restrictor
A vent restrictor may be needed with this appliance, install vent restrictor (provided) in the appliance top flue outlet as shown in Figure 17 (MPDT33, MPD35, MPD40 and MPD45) or rear flue outlet as shown in Figure 18 (MPD35, MPD40 and MPD45). It is held in
place by friction, only.
NOTE: The vent restrictor is included in the rebox.
12
WHEN USING THE TOP VENT
(OUTSIDE UNIT)
CABINET TOP
FIREBOX TOP
VENT
COVER PLATE
(INSIDE UNIT)
CROSS SECTION
GASKET
TOP VENT
KNOCKOUT
COVER PLATE SECURING SCREWS
Figure 15 - Top vent seal and cover plate
removal - MPD35/40/45 series models
(combined top and rear vent units)
WHEN USING THE REAR VENT
COVER PLATE
SECURING SCREWS
(INSIDE UNIT)
REAR VENT
CROSS SECTION
CAP AND GASKET
CABINET BACK
(OUTSIDE UNIT)
KNOCKOUT
Figure 16 - Rear vent seal and cover plate
removal - MPD35/40/45 series models
(combined top and rear vent units)
A vent restrictor may be needed when vertically terminating the vent system above the roof (when using the appliance top vent),install vent restrictor in the top vent of the fireplace outlet on MPD35/40/45 and MPDT33 series models.
If needed, install the restrictor orientated as shown, either from inside or outside the unit, in the inner fireplace collar.
U-Shaped Vent Restrictor
Inner Fireplace Collar
Appliance Top
Vent Outlet
Figure 17 - Vent restrictor installation ­Top vent
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
horzontally terminating the vent system from
the rear of the appliance (when using the
appliance rear vent), install vent restrictor in
the rear vent of the fireplace outlet on MPD35/40/45 series models, in any
installation that has a vertical vent run in
excess of three feet (0.914 meters).
If needed, install the restrictor orientated as
shown, either from inside or outside the unit,
in the inner fireplace collar.
INNER FIREPLACE
COLLAR
APPLIANCE REAR
VENT OUTLET
U-SHAPED VENT RESTRICTOR
Figure 18 -Vent restrictor installation ­Rear vent
Select Venting System - Horizontal or Vertical
With the appliance secured in framing, determine vent routing and identify the exterior termination location. The following sections describe vertical (roof) and horizontal (exterior wall) vent applications. Refer to the section relating to your installation. A list of approved venting
components are shown on Pages 36 and 37.
Use only approved vent components (see Approved Vent Components on Page 2).
These fireplaces must be vented directly to the outside.
The vent system may not service multiple appliances, and must never be connected to a flue serving a separate solid fuel burning appliance. The vent pipe is tested to be run inside an enclosed wall (such as a chase). There is no requirement for inspection openings in the enclosing wall at any of the joints in the vent pipe.
Step 4. INSTALLING VENT SYSTEM
These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 in Canada.
Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier.
Dégagement conforme aux codes d'installa­tion locaux et aux exigences du foumisseunde gaz.
Page 13
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
lanimoN
38
T
32
Hs
04
04
04
38
T
32
Hs
0010
VERTICAL TERMINATION SYSTEMS (ROOF)
See Figure 19 and Figures 27 through 29
)sehcni(
on Page 17 and their associated Vertical Vent Tables, which illustrate the various vertical venting configurations that are possible for use with these appliances. Secure Vent applications are shown in these Figures; Secure
®
pipe may also be used. A Vertical Vent
Flex
®
pipe
Table summarizes each system’s minimum and maximum vertical and horizontal length values that can be used to design and install the vent components in a variety of applications.
Both these vertical vent systems terminate through the roof. The minimum vent height above the roof and/or adjacent walls is specified in ANSI Z223.1 (In Canada, the current CAN/ CGA-B149.1 installation code) by major building codes. Always consult your local codes for specific requirements. A general guide to follow is the Gas Vent Rule (refer to Figure 5 on Page 6).
Vertical (Straight) Installation
(Figure 19)
Determine the number of straight vent sections required. 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46 1/2" (1181 mm) net section lengths are available (see Tables on this page and Pages 36 and 37 - Vent Sections). Plan the vent lengths so that a joint does not occur at the intersection of ceiling or roof joists. Refer to the Vent Section Length Chart.
SV4.5CGV-1
Termination
Max. 40 ft (12.2 m)
SV4.5FA or SV4.5FB Flashing AND SV4.5SC Storm Collar
1 in (25.4 mm) Minimum Clearance to Combustibles
SV4.5VF Firestop/Spacer*
*When using Secure Flex, use Firestop/Spacer
SF4.5VF.
SV4.5L6/12/24/36/48 Vent Sections
sehcnitf
5.4573.0100001
957.0200002
5.01578.0010001
5152.1110002
5.91526.12100
1257.1020002
5.22578.1001001
5.52521.2120003
5.13526.2030003
5.43578.2000101
5.73521.3111003
5.34526.3021003
5457.3002002
5.64578.3000011
5.94521.4102003
1552.4100012
5.55526.4012003
7557.4001102
6652.5022004
5.76526.5003003
9657.5000202 2761030
5.37521.6100203
5.97526.6010203
1857.6000112
095.7021014
5.19526.7002013
3957.7000022 6981012
5.79521.8100023
2015.8200024
5.301526.8000303
80191003
4115.9020024
71157.9105006
5.811578.9110305
6215.01001304
5.031578.01101305
53152.11006006
8315.11000404
5.931526.11000033
5.241578.11100405
Table 7: Vent Section Length
NOTE: Convert inches into metric equivalent measurement, as follows:
Millimeters (mm) = Inches x 25.4 Centimeters (cm) = Inches x 2.54 Meters (M) = Inches x .0254
htgneLnoitceS
621426
noitceSteN
2/1-42/1-012/1-222/1-4
)sehcni(htgneL
tneVfothgie
noitceSlanimoN
4
O T A
/1-64
L
noitceStneVforebmuN
Q T
sehcnitf
Y
44121100034
0515.21010034
5.451578.21110035
0
5.061573.31020035
3
5.271573.41000505
77157.41100506
38152.51010506
6815.51000044
5.091578.51100045
5.691573.61010045
5.502521.71011507
70252.71000606
5.112526.71100607
5.712521.81010607
5.922521.91001607
5.232573.91000055
73257.91100056
5.142521.02000707
6425.02100708 25212010708 46222001708 67232000808
97252.32000066
5.082573.32100809
5.382526.32100067
5.982521.42010067
5.103521.52001067
5.013578.52000909
5135.621009001
5.523521.72000077
0335.72100078 63382010078
54357.82000 01001
5.943521.921
27313000088
5.673573.13100089
5.973526.13000 11011
5.814578.43000099
32452.531000901
56457.83000
621426
)sehcni(htgneL
noitceSteN
2/1-42/1-012/1-222/1-4
)sehcni(htgneL
tneVfothgie
00 01011
4
O T A
/1-64
L
noitceStneVforebmuN
Q T Y
1
Model Effective Length
SV4.5L6 4-1/2" SV4.5L12 10-1/2" SV4.5L24 22-1/2" SV4.5L36 34-1/2" SV4.5L48 46 1/2"
Table 8 - Effective Vent Length
Figure 19
13
Page 14
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
Vertical (Offset) Installation
Analyze the vent routing and determine the quantities of vent sections and number of elbows required. Refer to Vertical Vent Figures and Tables on Page 17 to select the type of vertical installation desired. Vent sections are available in net lengths of 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46 1/2" (1181 mm). Refer to the Vent Section Length Chart on Page 14 for an aid in selecting length combinations. Elbows are available in 90° and 45° configurations. Refer to Figure 23 for the SV4.5E45 and SV4.5E90 elbow dimensional specifications.
Where required, a telescopic vent section (SV4.5LA) may be used to provide the installer with an option in installing in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesirable location, or will not build up to the required length. The SV4.5LA Telescopic Vent Section has an effective length of from 1 1/2" (38 mm) to 7 1/2" (191 mm). The SV4.5LA is fitted with a locking inclined channel end (identical to a normal vent section component) and a plain end with 3 pilot holes. Slip the plain end over the locking channel end of a standard SV4.5 vent component the required distance and secure with three screws.
Maintain a minimum 1" (25 mm) clearance to combustible materials for all vertical elements. Clearances for all horizontal elements are 3" (76 mm) on top, 1" (25 mm) on sides and 1" (25 mm) on the bottom.
A. Frame ceiling opening - Use a plumb line
from the ceiling above the appliance to locate center of the vertical run. Cut and/or frame an opening, 10-1/2" x 10-1/2" (267 mm x 267 mm) inside dimensions, about this center mark (Figure 20).
B. Attach vent components to appliance
- Secure Vent
®
SV4.5 direct vent system components are unitized concentric pipe components featuring positive twist lock connections (see Figure 19). All of the appliances covered in this document are fitted with collars having locking inclined channels.
Min. 10-1/2" (267 mm)
Roof Framing
Ceiling Framing
Min. 10-1/2" (267 mm)
Plumb Bob
Figure 20
The dimpled end of the vent components fit over the appliance collar to create the positive twist lock connection.To attach a vent component to the appliance collar, align the dimpled end over the collar, adjusting the radial alignment until the four locking dimples are aligned with the inlet of the four inclined channels on the collar (refer to Figure 21). Push the vent component against the collar until it fully engages, then twist the component clockwise, running the dimples down and along the incline channels until they seat at the end of the channels. The unitized design of the Secure Vent
®
components will engage and seal both the inner and outer pipe without the need for sealant or screws. If desired a #6 x 1/2" screw may be used at the joint, but it is not required as the pipe will securely lock when twisted.
NOTE: An elbow may also be attached to the appliance collar. Attach in the same manner as you would a vent section.
C. Attach vent components to each other
- Other vent sections may be added to the
previously installed section in accordance with the requirements of the vertical vent figures and tables. To add another vent component to a length of vent run, align the dimpled end over the inclined channel end of the previously installed section, adjusting the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels of the previous section.
Push the vent component against the previous section until it fully engages, then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels.This seating position
is indicated by the alignment of the arrow and dimple as shown in Figure 21.
D. Install firestop/spacer at ceiling - When
using Secure Vent, use SV4.5VF firestop/spacer at ceiling joists; when using Secure Flex
®
, use SF4.5VF firestop/spacer. If there is living space above the ceiling level, the firestop/spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the firestop/ spacer must be installed on the top side of the joist. Route the vent sections through the framed opening and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner.
Remember to maintain 1" (25 mm) clearance to combustibles, framing members, and attic or ceiling insulation when running vertical chimney sections. Attic insulation shield (96K94) may be used to obtain the required clearances indicated here. See installation accessories table on Pages 36 and 37. The gap between the vent pipe and a vertical firestop can be sealed with non-combustible caulking.
E. Support the vertical vent run sections -
NOTE: Proper venting support is very important.
Support the vertical portion of the venting system every 8 feet (2.4m) above the fireplace vent outlet. One method of support is by utilizing field provided support straps (conventional plumber's tape). Secure the plumber's tape to the framing members with nails or screws. Loop the tape around the vent, securing the ends of the tape to the framing. If desired, sheet metal screws #6 x 1/2" length may be used to secure the support straps to the vent pipe. See Figure 22.
Align the dimple (four places) of the upper vent section with the opening of the locking incline channel on the lower vent section or appliance collar. Twist vent component clockwise to engage and seal until arrow and dimple
Arrow
Appliance Collar or Vent Section
align.
Dimple
Locking Incline Channel
Connected Vent Sections
Arrow
Figure 21
Blocking
Support Straps (Plumber's tape)
8 feet (2.4 m)
Maximum
1/2 inch (12.7 mm) minimum clearance to combustibles
Figure 22
14
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 15
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
SV4.5E90
(90
°
Elbow)
8-1/8"
(206 mm)
Swivel Joint
(360
°
swivel)
4-13/16"
(122 mm)
SV4.5E45
(45
°
Elbow)
Swivel Joint
(360
°
swivel)
C
D
Storm Collar
F. Change vent direction to horizontal/inclined run - At transition from or to a horizontal/
inclined run, install the SV4.5E45 and SV4.5E90 elbows in the same manner as the straight vent sections. The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with the required direction of the next vent run element.
Twist elbow sections in a clockwise direction only so as to avoid the possiblity of unlocking any of the previously connected vent sections.
See Figure 23.
Figure 23
G. Continue installation of horizontal/inclined sections - Continue with the installation of the
straight vent sections in horizontal/inclined run as described in Step C. Install support straps every 5 ft (1.52 m) along horizontal/inclined vent runs using conventional plumber’s tape.
It is very important that the horizontal/inclined run be maintained in a straight (no dips), slightly elevated plane. The recommended incline is approximately 1/4" per foot (20 mm per meter) horizontal, in a direction away from the fireplace. The rise per foot run ratios that
are smaller are acceptable all the way down to at or near level. Use a carpenter’s level to measure from a constant surface and adjust the support straps as necessary.
It is important to maintain the required clearances to combustibles: 1" (25 mm) at all sides for all vertical runs; and 3" (76 mm) at the top, 1" (25 mm) at sides, and 1" (25 mm) at the bottom for all horizontal/inclined runs.
H. Frame roof opening - Identify location for
vent at the roof. Cut and/or frame opening per Roof Framing Chart and Figure 24.
Framing Dimensions for Roof
Pitch C D
0/12
6/12
12/12
10-1/2"
(267 mm)
10-1/2"
(267 mm)
10-1/2"
(267 mm)
10-1/2"
(267 mm)
12"
(305 mm)
17-3/4"
(451 mm)
Figure 24
I. Install the roof flashing - Extend the vent sections through the roof structure. Install the roof flashing over the vent section and posi­tion such that the vent column rises vertically (use carpenters level) (Figure 25 ). Nail along perimeter to secure flashing or adjust roofing to overlap the flashing edges at top and sides only and trim where necessary. Seal the top and both sides of the flashing with waterproof caulking.
J. Install the storm collar - Install the storm collar, supplied with the flashing, over the vent/ flashing joint. See Figure 25. Loosen the storm collar screw. Slide collar down until it meets the top of the flashing. Tighten the adjusting screw. Apply non-combustible caulking or mastic around the circumference of the joint to provide a water tight seal.
K. Install the vertical termination - The final step involves installation of the SV4.5CGV-1 Vertical Termination. Extend the vent sections to the height as shown in the "Vertical vent termination section" on Page 6. The SV4.5CGV-1 Vertical Termination (Figure 26) installs in the exact same fashion as any other Secure Vent® section. Align the termination over the end of the previously installed section, adjusting the radial alignment until the four locking dimples of the termination are aligned with the inlets of the four incline channels of the last vent section. Push the termination down until it fully engages, then twist the termination clockwise running the dimples down and along the incline channels until they seat at the end of the channels.
Figure 26
If the vent system extends more than 5' (1.5 m) above the roof flashing, stabilizers may be necessary. Additional screws may be used at section joints for added stability. Guide wires may be attached to the joint for additional sup­port on multiple joint configurations.
Figure 25
15
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 16
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
SF4.5VF.
VERTICAL VENT FIGURES/TABLES
NOTE: Secure Vent® (rigid vent pipe) is shown in the figures; Secure Flex® (flexible vent pipe) may also be used.
NOTE: It is very important that the horizontal/ inclined run be maintained in a straight (no dips), slightly elevated plane. The recommended incline is approximately 1/4" per foot (20 mm per meter) horizontal, in a direction away from the fireplace. The rise per foot run ratios that are smaller are acceptable all the way down to at or near level.
NOTE: SV4.5VF (Secure Vent), SF4.5VF (Secure
®
) firestop/spacer must be used anytime
Flex vent pipe passes through a combustible floor or ceiling. SV4.5HF (Secure Vent), SF4.5HF (Secure Flex®)firestop/spacer must be used anytime vent pipe passes through a combustible wall.
NOTE: Two 45 degree elbows may be used in place of one 90 degree elbow. The same rise to run ratios, as shown in the venting figures for 90 elbows, must be followed if 45 degree elbows are used.
NOTE: An elbow is acceptable as 1 foot of vertical rise, except where an elbow is the
only vertical component in the system. (See Figure 36 on Page 21).
Ceiling Firestop/ Spacer SV4.5VF*
Max. 40 ft
(12.2 m)
*When using Secure Flex, use
Ceiling Firestop/ Spacer SF4.5VF.
TABLE A
H Maximum V Minimum
(meters)
feet feet
(meters)
2 (0.610) 1 (0.305)
4 (1.219) 2 (0.610)
6 (1.829) 3 (0.914)
V
8 (2.438) 4 (1.219)
V + H = 40 feet (12.2 meters) Max.
H = 8 feet (2.4 meters) Max.
Ratio V to H ratio is 1:2
This table shows a 1 (V) to 2 (H) ratio. For every 1 foot of (V) vertical, you are allowed 2 feet of (H) horizontal run, up to a maximum horizontal run of 8 feet.
Example: If 8 feet of (H) horizontal vent run is needed, then 4 feet minimum (V) vertical vent will be required.
Figure 28 - Rear Vent - ONE 90-DEGREE ELBOW
H
Ceiling Firestop/Spacer SV4.5VF*
Wall Firestop/Spacer
V1
*When using Secure Flex, use Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use Wall Firestop/Spacer SF4.5HF.
SV4.5HF**
V
Figure 29 - Top Vent - TWO 90-DEGREE ELBOWS
Ceiling Firestop/Spacer SV4.5VF*
*When using Secure Flex, use
Ceiling Firestop/Spacer
H
NOTE: Install the U-shaped vent restrictor in any vent run with more than 8 ft of vertical rise (See Page 13).
TABLE B
H Maximum
feet
(meters)
(1.524)
5
(1.524)
5
(3.048)
10
(4.572)
15
(6.096)
20
V + V1+ H = 40 feet (12.2 m) Max.
H = 20 feet (6.096 meters) Max.
V Minimum
feet
Elbow Only
1
2
3
4
(meters)
(0.305)
(0.610)
(0.914)
(1.219)
Example: If 20 feet of (H) horizontal vent run is needed, then 4 feet minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V) vertical, you are allowed 5 feet of (H) horizontal run, up to a maximum horizontal run of 20 feet.
An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only vertical component in the system. See Figure 36.
NOTE: Install the U-shaped vent restrictor in any vent run with more than 8 ft of vertical rise (See Page 13).
A Vent Restrictor, as shown in Figure 17 on
Page 13, must be used in this application.
Figure 27 - Top Vent - STRAIGHT
16
WARNING
Under no circumstances, may separate sections of concentric flexible vent pipe be joined together.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 17
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
VERTICAL VENT FIGURES/TABLES
(continued)
TABLE C
+H
Maximum H Maximum V Minimum
H
1
2
4
6
8
(meters)
(0.610)
(1.219)
(1.829)
(2.438)
(meters)
feet feet feet
(1.524)
5
(3.048)
10
(4.572)
15
(6.096)
20
V + V1+ H + H1 = 40 feet (12.2 m) Max
H = 8 feet (2.438 meters) Max.
H + H1= 20 feet (6.096 meters) Max.
1
2
3
4
(meters)
(0.305)
(0.610)
(0.914)
(1.219)
Example: If 20 feet of (H) horizontal vent run is needed, then 4 feet minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V) vertical, you are allowed 5 feet of (H) horizontal run, up to a maximum horizontal run of 20 feet.
NOTE: Install the U-shaped vent restrictor in any vent run with more than 8 ft of vertical rise (See Page 13).
Figure 30 - Rear Vent - THREE ELBOWS
V1
H1
Ceiling Firestop/Spacer SV4.5VF*
Wall Firestop/Spacer SV4.5HF**
V
*When using Secure Flex, use Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use Wall Firestop/Spacer SF4.5HF.
Ceiling Firestop/Spacer SV4.5VF*
H
TABLE D
H
Maximum
H +
1
feet feet
5
5
10
15
20
(meters) (meters)
(1.524) Elbow Only
(1.524)
(3.048)
(4.572)
(6.096)
H + H1 = 20 feet (6.096 m) Max.
+ H + H1 = 40 ft. (12.192 m) Max.
V + V
1
V Minimum
1
2
3
4
(0.305)
(0.610)
(0.914)
(1.219)
Example: If 20 feet of (H) horizontal vent run is needed, then 4 feet minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V) vertical, you are allowed 5 feet of (H) horizontal run, up to a maximum horizontal run of 20 feet.
An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only vertical component in the system. See Figure 36.
NOTE: Install the U-shaped vent restrictor in any vent run with more than 8 ft of vertical rise (See Page 13).
Ceiling
V
1
Firestop/Spacer SV4.5VF*
Wall Firestop/Spacer SV4.5HF**
H
H
1
V
*When using Secure Flex, use Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use Wall Firestop/Spacer SF4.5HF.
Figure 31: Top Vent - THREE ELBOWS
17
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 18
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
TYPICAL HORIZONTAL VENT INSTALLATION
HORIZONTAL (OUTSIDE WALL) TERMINATION SYSTEM
Figure 32, and Figures 35 to 41 on Pages 21 to 23 and their associated Horizontal
Vent Table illustrate the various horizontal venting configurations that are possible for use with these appliances. Secure Vent applications are shown in these figures; Secure
®
Flex
pipe may also be used. A Horizontal Vent Table summarizes each system’s minimum and maximum vertical and horizontal length values that can be used to design and install the vent components in a variety of applications. Both of these horizontal vent systems terminate through an outside wall. Building Codes limit or prohibit terminating in specific areas. Refer to Figure 7
on Page 7 for location guidelines. Secure Vent SV4.5 direct vent system compon-
ents are unitized concentric pipe components featuring positive twist lock connection, (refer to Figure 21 on Page 15). All of the appliances covered in this document are fitted with collars having locking inclined channels. The dimpled end of the vent components fit over the appliance collar to create the positive twist lock connection.
A. Plan the vent run - Analyze the vent routing and determine the types and quantities of sections required 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46-1/2". (1181 mm) net section lengths are available. It is recommended that you plan the venting so that a joint does not occur in the ceiling or roof joists. Allow for elbows as indicated in Figure 23 on Page 16.
Maintain a minimum 1" (25 mm) clearance to combustibles on the vertical sections. Clearances for the horizontal runs are; 3" (76 mm) on top, 1" (25 mm) on sides, and 1" (25 mm) at the bottom.
B. Frame exterior wall opening - Locate the
center of the vent outlet on the exterior wall according to the dimensions shown in Figure 12 on Page 11. Cut and/or frame an opening, 10-1/2" x 12-1/8" (267 mm x 308 mm) inside dimensions, about this center.
C. Frame ceiling opening - If the vertical route is to penetrate a ceiling, use plumb line to locate the center above the appliance. Cut and/or frame an opening, 10-1/2" x 10-1/2" (267 mm x 267 mm) inside dimensions, about this center (refer to Figure 20 on Page 15).
D. Attach vent components to appliance - To attach a vent component to the appliance collar, align the dimpled end over the collar, adjusting the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels on the collar (refer to Figure 21 on Page 15).
18
®
pipe
Building
Support
Framing
SV4.5E90
ertical
V
Rise
Support
Brackets
Elbow
Ceiling
Firestop/Spacer
Horizontal / Inclined Run
See Figure 24 on Page 15 for vertical vent section support.
Fireplace
Figure 32 - Typical Horizontal Vent Installation
Push the vent component against the collar until it fully engages, then twist the component clockwise, running the dimples down and along the incline channels until they seat at the end of the channels. The unitized design of the Secure Vent components will engage and seal both the inner and outer pipe elements with the same procedure. Sealant and securing screws are not required.
NOTE: An elbow may also be attached to the appliance collar. Attach in the same manner as you would a vent section.
E. Attach vent components to each other
- Other vent sections may be added to the
previously installed section in accordance with the requirements of the vent tables. To add another vent component to a length of vent run, align the dimpled end of the component over the inclined channel end of the previously installed section, adjusting the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels of the previous section. Push the vent component against the previous section until it fully engages, then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels.This seating position
is indicated by the alignment of the arrow and dimple as shown in Figure 21 on Page 15.
F. Install firestop/spacer at ceiling - When
using Secure Vent, use SV4.5VF firestop/spacer at ceiling joists; when using Secure Flex
®
, use SF4.5VF firestop/spacer. If there is living space above the ceiling level, the firestop/ spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the firestop/ spacer must be installed on the top side of the joist. Route the vent sections through the framed opening and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner.
Remember to maintain 1" (25 mm) clearance to combustibles, framing members, and attic or ceiling insulation when running vertical chimney sections.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
SV4.5HT-2 Termination
SV4.5L6/12/24/36/48
Vent Sections
Support bracket spacing every 5 ft (1.52 m)
Exterior Wall
SV4.5HT-2 Termination
Exterior Wall
G. Support the vertical run sections - On the vertical run, support the venting system every 8 feet (2.4m) above the fireplace vent outlet with field provided support straps (Plumber's tape). Attach the straps to the vent pipe and secure to the framing members with nails or screws. See Figure 22 on Page 15.
H. Change vent direction - At transition from or to a horizontal/inclined run, install the SV4.5E45 and SV4.5E90 elbows in the same manner as the straight vent sections. The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with the required direction of the next vent run element. Twist elbow sections in a
clockwise direction only so as to avoid the possiblity of unlocking any of the previously connected vent sections. See Figure 23 on
Page 16.
I. Continue installation of horizontal/inclined sections - Continue with the installation of the
straight vent sections in horizontal/inclined run as described in Step E. Install support straps every 5 ft. (1.52 m) along horizontal/inclined vent runs using conventional plumber’s tape. See Figure 32, It is very important that the
horizontal/inclined run be maintained in a straight (no dips), slightly elevated plane. The recommended incline is approximately 1/4" per foot (20 mm per meter) horizontal, in a direction away from the fireplace. The
rise per foot run ratios that are smaller are acceptable all the way down to at or near level. Use a carpenter’s level to measure from a constant surface and adjust the support straps as necessary.
It is important to maintain the required clearances to combustibles: 1" (25 mm) at all sides for all vertical runs; and 3" (76 mm) at the top, 1" (25 mm) at sides, and 1" (25 mm) at the bottom for all horizontal/inclined runs.
Page 19
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
SV4.5HT-2
Termination
10-1/2”
(267mm)
7”
(178)
5-1/8”
(130 mm)
12-1/8”
(308 mm)
NOTE: Centerline of Vent Piping is NOT the Same as the Centerline of the Framed Opening.
6 to 48” Vent Section,
Telescopic vent section,
Elbow or Appliance Collar
Base of Appliance
3”
(76 mm)
1”
(25.4 mm)
Adaptor
SV4.5RCH
Siding
Stucco
1-1/4" Maximum Recess of the Square Termination into Exterior Finishing Material
Exterior Surface of
Framing
6” to 9-1/4”
(152 to 235 mm)**
Exterior Surface of Siding
Interior Surface of
Finished Wall
Maximum wall thickness
10” (254 mm)**
SV4.5HT-2
Square Termination
Maximum Extent of Vent Run Sections Relative to Exterior Surface of Framing
Last Vent Section. Use Telescopic Vent Section (SV4.5LA), If Necessary
Adaptor
SV4.5RCH
SV4.5HT-2
Square Termination
*Use silicone caulking to seal the top and sides of the termination, up to the underlayment, stucco, or masonry wall surface.
**For thicknesses greater than 10” see Table 8.
*Caulk
*Caulk
J. Assemble vent run to exterior wall - If not previously measured, locate the center of the vent at the exterior wall. Prepare an opening as described in Step B. Assemble the vent system to point where the terminus of the last section is within 7" (178 mm) to 11-1/4" (286 mm) inboard of the exterior surface to which the SV4.5 HT termination is to be attached, see Figure 34. If the terminus of the last section is not within this distance, use the telescopic vent section SV4.5LA, as the last vent section. For wall thicknesses greater than that shown in Figure 34, refer to Table 9 on Page 21. This table lists the additional venting components needed (in addition to the termination and adaptor) for a particular range of wall thicknesses.
K. Attach termination adaptor - Attach the adaptor (SV4.5RCH, provided with the termination) to the vent section or telescoping vent section), elbow or appliance collar as shown in Figure 33 in the same manner as any SV4.5 vent component (refer to Step E).
L. Install Firestop/Spacer at exterior wall
- When using the square termination, install
SV4.5HF (Secure Vent
®
Flex
) Firestop/Spacer over the opening at the exterior side of the framing, long side up, with the 3 inch spacer clearance at the top as shown in Figure 33, and nail into place (the Firestop/ Spacer may also be installed over the opening at the interior side of the framing).
M. Install the desired termination
1. Install the square termination (SV4.5HT-2 or SV4.5HTSS) - For the last step , from
outside the exterior wall, slide the collars of the termination onto the adaptor (the outer over the outer and the inner inside the inner) until the termination seats against the exterior wall surface to which it will be attached. Orient the housing of the termination with the arrow pointed upwards. Secure the termination to the exterior wall. The horizontal termination
must not be recessed into the exterior wall or siding by more than the 1-1/4" (32 mm) as
shown in Figure 34. SVHRK Snorkel Cap - The snorkel cap is
designed to be fitted into a basement window
box. The SVHRK cap is for use with ex vent.
The vertical distance between the inlet and outlet of the cap is 28" (711 mm).
IMPORTANT: The vent termination is hot while in operation and for a period of time following the use of the fireplace. To prevent contact with hot surfaces, we recommend the use of a Termination Guard. See Page 36. This can be purchased at your local dealer.
®
), SF4.5HF (Secure
To help minimize water infil­tration it is recommended that the Firestop/Spacer (SV4.5HF) be installed on the exterior side of the wall.
See Figure 12 on Page 10 for Min. Distance to Base of Appliance.
Figure 33 - Installing the Square Horizontal Termination (SV4.5HT-2)
** For thicknesses greater than 10" (254mm) see Table 9.
Figure 34 - Venting Connection and Exterior Wall Recessing of the Horizontal Square
Termination (SV4.5HT-2)
Horizontal terminations have been designed to perform in a wide range of weather conditions. Our terminations meet or exceed industry standards.
When selecting the locations of your horizontal terminations, do not place the termination where water from eaves and adjoining rooflines may create a heavy flow of cascading water onto the termination cap. If the cap must be placed where the possibility of cascading water exists, it is the responsibility of the builder to direct the water away from the termination cap by using gutters or other means.
Take care to carefully follow the installation instructions for the termination, including the use of silicone caulking where required.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
19
Page 20
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
HORIZONTAL VENT FIGURES/TABLES
NOTE: Secure Vent® components (rigid vent pipe and terminal) are shown in the figures; Secure Flex® components (flexible vent pipe and terminal) may also be used.
NOTE: Two 45 degree elbows may be used in place of one 90 degree elbow. The same rise to run ratios, as shown in the venting figures for 90 elbows, must be followed if 45 degree elbows are used.
NOTE: It is very important that the horizontal/inclined run be maintained in a straight (no dips), slightly elevated plane. The recommended incline is approximately 1/4" per foot (20 mm per meter) horizontal,
in a direction away from the fireplace. The rise per foot run ratios that are smaller are acceptable all the way down to at or near level.
®
NOTE: SV4.5VF (Secure Vent
), SF4.5VF (Secure Flex) firestop/spacer must be used anytime vent pipe passes through a combustible floor or ceiling. SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer must be used anytime vent pipe passes through a combustible wall.
WARNING
Under no circumstances, may separate sections of concentric flexible vent pipe be joined together.
Venting Components Required for Various Exterior Wall Thick-
nesses, when using Typical Termination Kits
Vent Components Required Exterior Wall Thickness - in. (mm)
Termination Kit Only 6 to 9-1/4 (152 to 235)
Termination Kit and 6" Vent
Section (SV4.5L6)
Termination Kit and 12"
Vent Section (SV4.5L12)
Termination Kit and
Telescopic Section (SV4.5L12)
Table 9
10-3/4 to 14 (2733 to 356)
16-3/4 to 20 (426 to 508)
11-3/4 to 20 (299 to 508)
NOTE: See Figure 34 showing wall thickness range
when using SV4.5HT-2 termination kit.
TABLE F
H Maximum V Minimum
(meters)
feet
(0.914)
3
**When using Secure Flex, use Wall Firestop/ Spacer SF4.5HF.
Square termination (SV4.5HT-2) shown.
See Table 9 as an aid in venting component selection for a particular range of exterior wall thicknesses.
feet
Elbow Only
(meters)
NOTE: Install the U-shaped vent restrictor in any vent run with more than 8 ft of vertical rise (See Page 13).
H
V
Wall Firestop/ Spacer SV4.5HF**
Figure 36 - Top Vent - ONE 90-DEGREE ELBOW - ELBOW CONNECTION AT APPLIANCE
TABLE G
H Maximum
(meters)
feet feet
(1.524)
5
V Minimum
(meters)
1(0.305)
10 (3.048) 2 (0.610)
15 (4.572) 3(0.914)
20 (6.096) 4 (1.219)
V + H = 40 feet (12.2 m) Max.
H = 20 ft. (6.096 m) Max.
H
Example: If 20 feet of (H) horizontal vent run is needed, then 4 feet minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V) vertical, you are allowed 5 feet of (H) horizontal run, up to a maximum horizontal run of 20 feet.
H = 28 in. (711 mm) Maximum.
H
Wall Firestop/ Spacer
7 in
(178 mm)
Only the square termination (SV4.5HT-2) may be used.
See Table 9 as an aid in venting component selection for a particular range of exterior wall thicknesses.
Figure 35 - Rear Vent - NO ELBOWS
20
SV4.5HF**
**When using Secure Flex, use Wall Firestop/Spacer SF4.5HF.
Wall Firestop/ Spacer SV4.5HF**
*When using Secure Flex, use Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use Wall Firestop/Spacer SF4.5HF.
Square termination (SV4.5HT-2) shown.
See Table 9 as an aid in venting component selection for a particular range of exterior wall thicknesses.
NOTE: Install the U-shaped vent restrictor in any vent run with more than 8 ft of vertical rise (See Page 13).
Figure 37 - Top Vent - ONE 90-DEGREE ELBOW - ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
V
Ceiling
Firestop/
Spacer
SV4.5VF*
Page 21
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
HORIZONTAL VENT FIGURES/TABLES (continued)
H
H
1
Ceiling Firestop/Spacer
SV4.5VF*
Wall Firestop/ Spacer
SV4.5HF**
V
*When using Secure Flex , use Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use Wall Firestop/Spacer SF4.5HF.
Square termination (SV4.5HT-2) shown.
TABLE H
Maximum H Maximum
+H
H
1
(meters)
feet
(1.524)
5
(3.048)
10
(4.572)
15
(6.096)
20
V + H + H1 = 40 feet (12.2 m) Max.
H = 8 feet (2.438 meters) Max.
H + H1= 20 feet (6.096 meters) Max.
(meters)
feet
2 (0.610) 1 (0.305)
4 (1.219) 2 (0.610)
6 (1.829) 3 (0.914)
8 (2.438) 4 (1.219)
V Minimum
(meters)
feet
Example: If 20 feet of (H) horizontal vent run is needed, then 4 feet minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V) vertical, you are allowed 5 feet of (H) horizontal run, up to a maximum horizontal run of 20 feet.
®
See Table 9 on Page 21 as an aid in venting component selection for a particular range of exterior wall thicknesses.
NOTE: Install the U-shaped vent restrictor in any vent run with more than 8 ft of vertical rise (See Page 13).
Figure 38 - Rear Vent - TWO 90-DEGREE ELBOWS
Wall Firestop/Spacer
SV4.5HF**
H
H
1
*When using Secure Flex, use Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use Wall Firestop/Spacer SF4.5HF.
Wall Firestop/Spacer
SV4.5HF**
Ceiling Firestop/Spacer
SV4.5VF*
Square termination (SV4.5HT-2) shown.
See Table 9 on Page 21 as an aid in venting component selection for a particular range of exterior wall thicknesses.
NOTE: Install the U-shaped vent restrictor in any vent run with more than 8 ft of vertical rise (See Page 13).
Figure 39 - Top Vent - TWO 90-DEGREE ELBOWS
TABLE J
+ H
H
Maximum
1
(meters)
feet
(0.914) Elbow Only
3
(1.524)
5
(3.048)
V
10
(4.572)
15
(6.096)
20
V +H+ H1 = 40 feet (12.2 m) Max.
+ H1 = 20 ft. (6.096 m) Max.
H
V Minimum
(meters)
feet
1 (0.305)
2 (0.610)
3 (0.914)
4 (1.219)
Example: If 20 feet of (H) horizontal vent run is needed, then 4 feet minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V) vertical, you are allowed 5 feet of (H) horizontal run, up to a maximum horizontal run of 20 feet.
An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only vertical component in the system. See Figure 36.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
21
Page 22
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
HORIZONTAL VENT FIGURES/TABLES (continued)
H
2
*When using Secure Flex , use Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use Wall Firestop/Spacer SF4.5HF.
®
Square termination (SV4.5HT-2) shown.
See Table 9 on Page 21 as an aid in venting component selection for a particular range of exterior wall thicknesses.
NOTE: Install the U-shaped vent restrictor in any vent run with more than 8 ft of vertical rise (See Page 13).
Wall Firestop/Spacer SV4.5HF**
H
1
Ceiling
Firestop/Spacer
SV4.5VF*
V
TABLE K
+ H1+ H
H
feet feet feet
Maximum
2
(meters)
H Maximum
(meters)
V Minimum
(meters)
5 (1.524) 2 (0.610) 1 (0.305)
10 (3.048) 4 (1.219) 2 (0.610)
15
(4.572)
6 (1.829) 3 (0.914)
20 (6.096) 8 (2.438) 4 (1.219)
V + H + H1+ H2 = 40 feet (12.2 m) Max.
H = 8 feet (2.438 meters) Max.
H + H1+ H2= 20 feet (6.096 meters) Max.
Example: If 20 feet of (H) horizontal vent run is needed, then 4 feet minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V) vertical, you are allowed 5
H
feet of (H) horizontal run, up to a maximum horizontal run of 20 feet.
Figure 40 - Rear Vent - THREE 90-DEGREE ELBOWS
H
1
Wall Firestop/Spacer SV4.5HF**
V
1
Square termination (SV4.5HT-2) shown.
See Table 9 on Page 21 as an aid in venting component selection for a particular range of exterior wall thicknesses.
NOTE: Install the U-shaped vent restrictor in any vent run with more than 8 ft of vertical rise (See Page 13).
Figure 41 - Top Vent - THREE 90-DEGREE ELBOWS
22
*When using Secure Flex, use Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use Wall Firestop/Spacer SF4.5HF.
Ceiling Firestop/Spacer
SV4.5VF*
H
Wall Firestop/Spacer SV4.5HF**
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
TABLE L
H Maximum
(meters)
feet
(1.524)
5
(1.524)
5
10
15
20
Example: If 20 feet of (H) horizontal vent
V
(3.048)
(4.572)
(6.096)
+ H1 = 20 feet (6.096 m) Max.
H
+ V+H+ H = 40 ft. (12.192 m) Max.
V
11
V Minimum
feet
Elbow Only
1
2
3
4
run is needed, then 4 feet minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V) vertical, you are allowed 5 feet of (H) horizontal run, up to a maximum horizontal run of 20 feet.
An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only vertical component in the system. See Figure 36.
(meters)
(0.305)
(0.610)
(0.914)
(1.219)
Page 23
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
5 in. (127 mm) Radius Minimum
Flexible Vent Section
GEAR CLAMPS
Adaptor
(SV4.5RF)
Apply ONLY MIL-PAC BLACK HIGH TEMPERATURE SEALANT (Catalog No. 10K81) to the outside surface of both collars of the adaptor (be especially careful to fill the grooves of the outer collar to be covered by the flexible pipe) and slide flexible pipe over inner and outer adaptor collars.
NOTE: OUTER PIPE IS PULLED AWAY TO SHOW THE DETAIL OF THE INNER PIPE
FLEX VENT
1-3/4 in. (44 mm) Flexible Pipe and
Adaptor Outer Collar Overlap
1-3/4 in. (44 mm) Flexible Pipe and
Adaptor Inner Collar Overlap
SECURING SCREW
(3 PLACES EQUALLY SPACED
JUST BELOW GEAR CLAMP)
Attach Adaptor to Appliance
Collar, or Secure Vent Sections
SECURING SCREW
(3 PLACES EQUALLY SPACED
JUST BELOW GEAR CLAMP)
VERTICAL OR HORIZONTAL VENTING USING
SECURE FLEX
Secure Flex
be used in any venting application where rigid
Secure Vent
can be used. All restrictions, clearances and allowances that pertain to the rigid piping apply to the flexible venting. Secure Flex kits may not
be modified; also, under no circumstances may separate sections of flex pipe be joined together. Secure Flex kits may be added to the end of a vent run made up of rigid Secure Vent (SV4.5) vent sections provided that
doing so does not violate any of the venting length, height, routing, horizontal to vertical ratio requirements or clearance considerations detailed in this manual.
Secure Flex kits come with an included adaptor that can be fitted to the appliance collar or the inclined channel end of the last Secure Vent (SV4.5) vent section in a rigid system in the exact same fashion as any other Secure Vent section. Align the dimpled end of the adaptor over the previously installed section or appliance collar, adjusting the radial alignment until the four locking dimples of the adaptor are aligned with the inlets of the four incline channels of the last vent section or collar. Push on the adaptor until it fully engages, then twist the adaptor clockwise running the dimples down and along the incline channels until they seat at the end of the channels.
Attach the flexible vent to the adaptor as follows (see Figure 42):
A. Install the Inner Flex Pipe
1. Install the small gear clamp loosely around
the inner flexible vent pipe, push it back out of the way.
2. Apply a bead of Mill-Pac Black (700°F) high temperature sealant - Catalog No. 10K81) to
the inner adaptor collar, approximately 1/2 inch from the end.
3. Pull and extend the inner flexible vent pipe.
4. Slide the inner flex pipe over the adaptor
collar. Ensure the flexible vent pipe completely engages the adaptor collar to a distance of 1 3/4 inches from the end, and that it is free from damage or tears.
5. Slide the gear clamp down and tighten it fully to secure the flexible vent to the adaptor inner collar approximately 3/4 inch from the end of the flex.
6. Install three screws 120 degrees apart through the flexible vent pipe and into the adaptor collar just below the gear clamp to provide additional security to the connection.
B. Install the Outer Flex Pipe
1. Install the large gear clamp loosely around
the outer flexible vent pipe, push it back out of the way.
®
venting kits and components may
®
(SV4.5) direct vent components
®
KITS AND COMPONENTS
Figure 42
2. Apply a bead of Mill-Pac Black (700°F) high temperature sealant - Catalog No. 10K81) to
the outer adaptor collar; to the grooves of the collar which extend approximately 1 inch from the end and to the flat surface, approximately 1 3/8 inches from the end.
3. Pull and extend the outer flexible vent pipe.
4. Slide the outer flex pipe over the adaptor
collar. Ensure the flexible vent pipe completely engages the adaptor collar to a distance of 1 3/4" from the end, and that it is free from damage or tears.
5. Slide the gear clamp down and tighten it fully to secure the flexible vent to the adaptor outer collar approximately 3/4 inch from the end of the flex.
6. Install three screws 120 degrees apart through the flexible vent pipe and into the adaptor collar just below the gear clamp to provide additional security to the connection.
C. Route Flex Vent
Ensure that the flex vent is properly routed to provide the required clearance. Do Not allow the flexible vent to bend in a radius tighter than 5" (127 mm). Refer to Figure 43. Place the internal flex vent spacers evenly and avoid kinking the inner pipe. Support horizontal sections of flex vent with metal straps at 2 ft (0.61 m) intervals.
D. Install Firestop/Spacers at ceilings and walls
When Secure Flex penetrates a wall or ceiling, a firestop/spacer is required: use the SF4.5 VF firestop/spacer for ceilings and the SF4.5 HF firestop/spacer for walls.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
See the appropriate sections and figures shown throughout the venting section for their installation requirments.
Figure 43
E. Attach Flex Vent to Termination Secure Flex components can be purchased
separately and attached to bulk lengths of Secure Flex flexible tubing cut to size at the job site. Secure the flexible vent to the Secure Flex terminations in the same manner (see Figure 42) as it was attached to the adaptor.
NOTE: Secure Flex vent must be attached to Secure Flex terminations only. DO NOT
substitute Secure Vent terminations or
the Secure Vent adaptor for Secure Flex components. The collars of Secure Flex
terminations and adaptors have a different circumference than what is used with the
Secure Vent pipe. Additionally, Secure Flex components have an extended length center tube for use in attaching the exible vent.
23
Page 24
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
JUNCTION BOX
Step 5. FIELD WIRING
CAUTION
The ground supply lead must be connected to the wire attached to the green ground screw located on the outlet box (see wiring diagrams). Failure to do so will result in a potential safety hazard. The appliance must be electrically grounded in accordance with local codes or, in the absence of local codes, the National Electrical Code, ANSI/NFPA 70-latest edition (in Canada, the current CSA C22.1 Canadian Electrical Code).
CAUTION: Label all wires prior to discon­nection when servicing controls. Wiring errors can cause improper and dangerous operation.
ATTENTION: Au moment de l’entretien des commandes, étiquetez tous les fils avant de les débrancher. Des erreurs de cáblage peuvent entraîner un fonc­tionnement inadéquat et dangereux.
Verify proper operation after servicing.
S’assurer que l’appareil fonctionne adé­quatement une fois l'entretien terminé.
R
BATTERY HOLDER
AC/DC POWER ADAPTOR
Y
G
O
B
120V AC
HOT
NEUTRAL
GROUND
LIMIT SWITCH
B-VENT MODELS
ONLY
BL = BLUE G = GREEN O = ORANGE W = WHITE Y = YELLOW
SCHEMATIC REPRESENTATION ONLY
WIRING COLOR CODE
P/N 580491-01
B
W
G
OPTIONAL
REMOTE RECEIVER
ON/OFF SWITCH
WALL SWITCH
B = BLACK BR = BROWN GY = GRAY PU = PURPLE R = RED
Figure 45 - Wiring Diagram - Electronic Gas Valves
APPLIANCE- MOUNTED ON/OFF SWITCH (OPTIONAL)
BK/W(1)
WALL-MOUNTED ON/OFF SWITCH (OPTIONAL) THERMOSTAT (OPTIONAL)
WALL MOUNTED CONFIGURATION FOR FAN SWITCH (OPTIONAL)
(OPTIONAL)
BK/W(1)
FAN
THERMOPILE
TP-TH
TP
TH
JUNCTION BOX
GAS VALVE
Figure 44 - Wiring Diagram - Millivolt
Gas Valves
ELECTRONIC PILOT ASSEMBLY
HOOD
PROFLAME VALVE
B
R
W
BL
PILOT TUBE
SPARK WIRE CABLE
PILOT GROUND WIRE
R
R
B
Y
Y
G O
W
PROFLAME DFC BOARD
BL
B
G
B
OPTIONAL CPI SWITCH OFF (O) = INTERMITTENT PILOT MODE ON (-) = STANDING PILOT MODE
BLACK
BK
R
W
GR
IGNITER ROD
FLAME SENSOR
B PILOT SENSOR CABLE
DFC WIRE HARNESS
Refer to Section A for millivolt appliances and Section B for electronic appliances. The gas valve is set in place and pre-wired at the factory on both models.
A. Millivolt Wiring (see Figure 44)
Millivolt units are not provided with any factory-installed controls; therefore, one of the optional control switches is required to operate the unit (ON/OFF Wall Switch, Unit­Mountable ON/OFF Switch*, Thermostat, Remote Control). See the fireplace Care and Operation Instructions for details.
[*If using a Unit-Mountable ON/OFF Rocker Switch with an optional Style View Door, mount the Rocker Switch on the door instead of the unit.]
1. If installing an ON/OFF wall switch or
thermostat, mount it in a convenient location on a wall near the fireplace.
2. Wire the control switch within the millivolt
control circuit using the 15 feet of 2
AC
120 V
conductor wire supplied with the unit.
NOTE: The supplied 15 feet of 2 conductor
wire has one end of each conductor connected to the gas valve circuit and the other end of each conductor placed loose inside the bottom compartment.
CAUTION
In millivolt systems, do NOT connect a Wall Switch to a 120V power supply.
B. Electronic Wiring (Figures 45 & 46)
One of the following optional controls also may be used: ON/OFF Wall Switch, Thermostat, Remote Control (see fireplace Care and Operation Instructions for details.).
NOTE: Electronic models must be connected to the main power supply.
1. Route a 3-wire 120Vac 60Hz 1ph power
supply to the appliance junction box.
2. Remove the electrical inlet cover plate from
the side of the unit by removing the plate’s securing screws (see Figure 12, Page 11).
3. Remove the cover plate knockout; then
feed the power supply wire through the knockout opening and into the unit junction box.
4. See Figures 45 & 46. Connect the black power supply wire to the lower outlet’s red pigtail lead.
Connect the white power supply wire to the
outlet’s common terminal.
5. Connect the ground supply wire to the pigtail lead attached to the outlet’s green ground screw.
24
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 25
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
BLOWER CONTROL CIRCUIT WIRING
NOTE: Remote receiver should be located in the wall, or if installed in the control compartment, pulled all the way forward and completely to the left or right against the corner posts.
6. If wall-mounted ON/OFF control or
thermostat is to be used, mount it in a convenient location on a wall near the fireplace.
7. If an optional control is to be used, wire it in
the low voltage circuit as shown in Figure
45.
NOTE: The supplied 15 feet of 2 conductor wire has one end of each conductor connected to the gas valve circuit and the other end of each conductor placed loose inside the bottom compartment.
8. After the wiring is complete, replace the
cover plate.
WARNING
Electronic models of these appli­ances are equipped with a three­prong (grounding) plug utilized in connecting the electronic components to the junction box in the lower compartment. This grounding plug provides protec­tion against shock hazard and should be plugged directly into the properly grounded three­prong receptacle. DO NOT cut or remove the grounding prong from the plug.
Step 6. WIRING - OPTIONAL FORCED AIR BLOWER KIT
FBK-100 and FBK-200 Kits
(See Figure 46)
An electrical outlet box is provided for the installation of the FBK-100, FBK-200 forced air blower kits. Electrical power must be provided to this box to operate these blowers. Install the blower kits according to the installation instructions provided with the kits.
120V, 60HZ, 1PH
neerG - dnuorG
etihW - lar
t ueN
Black
White
Green
Plug blower into this receptacle
Blower
Ground
Figure 46 - Junction Box Wiring
FBK-250 Blower Kit
(See Figure 46)
An electrical outlet box is provided for the installation of the FBK-250 forced air blower kit. Electrical power must be provided to this box to operate these blowers. Install the blower kit according to the installation instructions provided with the kit.
NOTE: The tab connecting the receptacles of the outlet box must be broken in FBK-100 and FBK-200 blower kit applications. See Figure 46.
* Wall-mounted ON/ OFF Blower Switch or Variable Speed Control Switch.
120 VAC - Black
Junction Box
Tab Intact
Field Wired
Factory Wired
Tab Broken
Red
Hot Side of Receptacle
Neutral Side of Receptacle
Green Ground Screw
Step 7. CONNECTING GAS LINE
Make gas line connections. All codes require a shut-off valve mounted in the supply line. Figure 47 illustrates two methods for connecting the gas supply. The flex-line method is acceptable in the U.S., however, Canadian requirements vary depending on locality. Installation must be in compliance with local codes.
These appliances are equipped with a gas flex line for use (where permitted) in connecting the unit to the gas line. A gas flex line is provided to aid in attaching the direct vent appliance to the gas supply. The gas flex line can only be used where local codes permit. Refer to Figure 47 for flex line description. The flex line is rated for both natural and propane gas. A manual shut off valve is also provided with the flex line.
The gas control valve is located in the lower control compartment.
To access the valve open the lower control compartment door (see Figure 48 ) by pushing in the right top corner of the door. (The door is hinged at the bottom.) Remove the bottom compartment door by sliding the hinge pin, located at the door’s left side, to the right until it disengages from the left corner post hole. Pull the door diagonally to the left, away from the fireplace.
The millivolt control valve has a 3/8" (10 mm) NPT thread inlet port. The electronic control valve has a 1/2" (13 mm) NPT thread inlet port and is fitted with a 1/2" x 3/8" (13 mm x 10 mm) NPT fitting.
Secure all joints tightly using appropriate tools and sealing compounds (ensure propane resistant compounds are used in propane applications). Optional: Seal around the gas line to prevent cold air leakage. Gas line holes and other openings can be caulked or stuffed with unfaced fiberglass insulation.
All codes require a shut-off valve mounted in the supply line. The orientation of the shut-off valve should face the front. Figure 47 illustrates two methods for connecting the gas supply. A sediment Trap is recommended to prevent moisture and debris in the gas line for damaging the valve.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
25
Page 26
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
Gas Stub
1/2" x 3/8" Flare
Shut-Off Valve
3/8" Flex Tubing
3/8" NPT x 3/8"
Flare Fitting
3/8" Nipple
3/8" Union
3/8" Close Nipple
3/8" Shut-Off Valve
1/2" x 3/8"
Reducer
Gas Valve
Optional Gas Flex Line Connector
Thermocouple
Hood Igniter Rod
Thermopile
Pilot Nozzels
3/8”
(9 mm)
Min
Figure 47 - Gas Connection
Millivolt Appliance Checkout
The pilot flame should be steady, not lifting or floating. Flame should be blue in color with traces of orange at the outer edge.
The top 3/8" (10 mm) at the pilot generator (thermopile) and the top 1/8" minimum (tip) of the quick drop out thermocouple should be engulfed in the pilot flame.
The flame should project 1" (25 mm) beyond the hood at all three ports (see Figure 49). Replace logs if removed for pilot inspection.
To light the burner; turn “ON” the remote wall switch and rotate the gas valve control knob counterclockwise to the “ON” position (“ON” will be at the top side of the valve).
TEST ALL CONNECTIONS FOR GAS LEAKS (FACTORY AND FIELD)
Turn on gas supply and test for gas leaks, us­ing a gas leak test solution (also referred to as bubble leak solution).
NOTE: Using a soapy water solution is an effec­tive leak test solution but it is not recommended, because the soap residue that is left on the pipes/fittings can result in corrosion over time.
A. Light the appliance (refer to the lighting
B. Brush all joints and connections with the gas
C. When the gas lines are tested and leak free,
26
Main Gas Shut-Off Valve
Gas Valve
(Optional) Burner ON/OFF Switch
Figure 48 - Millivolt Gas Valve - Lower Control Compartment
Step 8. VERIFYING APPLIANCE OPERA­TION
With gas line installed, run initial system
WARNING
Never use an open flame to check for leaks.
instructions label in the control compartment or in the Care and Operation Instructions manual).
leak test solution to check for leaks. If bubbles are formed, or gas odor is detected, turn the gas control knob (off/pilot/on) to the “OFF” position (millivolt units), or turn the receiver or remote control to the “OFF” position (electronic units). Either tighten or refasten the leaking connection, then retest as described above.
be sure to rinse off the leak testing solution.
checkout before closing up the front of the unit. Follow the pilot lighting instructions provided in the Care and Operation Instruc- tions. For piezo igniter location on millivolt appliances, see Figure 48.
NOTE: Lighting Instructions are also found on the literature tag tied to the gas piping next to the gas valve. To access the tag, open the lower control compartment door (Figure 48) by pushing in simultaneously the left and right top corners of the door (the door is hinged at the bottom). Remove the bottom compartment door by sliding the hinge pin, located at the door’s left side, to the right until it disengages from the left corner post hole.
When first lighting the appliance, it will take a few minutes for the line to purge itself of air. Once purging is complete, the pilot and burner will light and operate as indicated in the instruction manual. Subsequent lighting of the appliance will not require such purging. Inspect the pilot flame (remove logs, if neces­sary, handling carefully)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Piezo
Door Latch
Figure 49 - Millivolt Pilot
Electronic Appliance Checkout
To light the burner, turn ‘ON’ the wall or remote control switch. Ensure the igniter lights the pilot. The pilot flame should engulf the flame rod as shown in Figure 50.
Ignitor
Igniter
Pilot
Pilot Hood
Hood
Flame Rod
Sensor
(sensor)
Figure 50 - Electronic Pilot
Page 27
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
Glowing Embers
Step 9. INSTALL VOLCANIC STONE, GLOWING EMBERS, AND LOGS
WARNING
DO NOT attempt to install the logs until the appliance instal­lation has been completed, the gas line connected and tested for leaks and the initial burner operation has been checked out.
The size and position of the log
set was engineered to give the appliance a safe, reliable and attractive flame pattern. Any attempt to use a different log set in the fireplace will void the warranty and will result in incomplete combustion, soot­ing, and poor flame quality.
Logs get very hot and will
remain hot up to one hour after gas supply is turned off. Handle only when logs are cool. Turn off all electricity to the appli­ance before you install grate, volcanic stone, embers and logs.
This appliance is not designed
to burn wood. Any attempt to do so could cause irreparable damage to the appliance and prove hazardous to your safety.
If logs are not installed accord-
ing to the log installation instructions, flame impinge­ment and improper combus­tion could occur and result in soot and/or excessive produc­tion of carbon monoxide (CO), a colorless, odorless, toxic gas.
Figure 52 - Glowing Ember Placement
NOTE: Turn off all electricity to the appliance before you install volcanic stone, embers and logs.
Step 1. Remove the appliance front door (see Removing Glass Encloslure panel on Page 32.
Step 2. Install decorative volcanic stone -
Sprinkle the decorative volcanic stone in a pleas­ing pattern. The volcanic stone should be placed directly on top of the firebox bottom, along the front and to the back at the right and left sides of the burner. Position any optional ceramic fiber liners before placing the stone. Logs should be positioned after the volcanic stone.
NOTE: This appliance is provided with enough Glowing Embers for several applications, do not feel compelled to use all that is in a new bag. For best glowing effect, replace the em­ber material annually. Replacement Glowing Embers are available (Catalog Number 88L53).
Glowing Embers
Separate into Quarter Size (separate) Pieces
Bag of Glowing Embers (rockwool)
Figure 51
Step 3. Separate the Glowing Ember (Rockwool) into pieces about the size of a quarter (Figure
51). Keep the pieces uffed up, not matted.
Distribute these pieces over the front surface of the burner, as shown in Figure 52. Do not use more than is necessary. When properly positioned, the Glowing Embers will cover approximately 65% of the front burner and with no appreciable gaps or openings. Ensure that the main burner ports remain uncovered by the ember material.
Step 4. Placement of Logs - All top logs that rest on lower logs, do so over notches, indents or nubs. Proper log placement is critical to prevent sooting. Logs should be placed in the gaps between the flame peaks and should be positioned so they do not impinge the flames.
Step 5. Position the individual logs as shown in Figures 53, 54, and 55. Logs should be placed in the order shown. All logs that have notches to fit over the grate tines should be positioned with these notches directly against the grate.
Handle logs carefully to prevent breakage.
Proper log placement is critical to encourage outstanding flame appearance and prevent sooting. When positioned properly as shown, logs will be positioned between flame peaks and will not impinge any flames.
Refer to Figure 53 for MPD33 Series appli­ances, to Figure 54 for MPD35 Series appli­ances and to Figure 55 for MPD40 and MPD45 Series appliances.
REFERENCE
Firebox Accessories / Parts
Cat. No. Model No. Description
88L53 FGE Bag of Glowing Embers
80L42 FDVS
Bag of Decorative Volcanic Stone
27
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 28
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
MPD33 LOG PLACEMENT
Log Number Description (Stamped #)
1
3
2
Position the individual logs as shown below. Logs should be placed
4
6
5
in the order shown. Position the rear log on the brackets at the rear of the firebox with the log's notches directly over the brackets. Position the right log (log no. 3) by inserting the pin from the rear log into the hole on its upper end. Place the left log and then the smaller left and right top logs. All logs that have notches to fit over the grate tines should be positioned with these notches directly against the grate. All top logs that rest on lower logs, do so over flattened mounting faces in the bottom logs.
1 Log, Rear (39-12) 2 Log, Left (39-1) 3 Log, Right (39-2) 4 Log, Top Center (39-13) 5 Log, Top/Left (39-3) 6 Log, Top/Right (39-4)
Catalog Number for the entire log set: 24M15
Proper log and twig placement is critical to encourage outstanding flame appearance and prevent sooting.
1
4
3
2
5
6
28
Figure 53
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 29
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
MPD35 LOG PLACEMENT
Log
1
3
2
Number Description (Stamped #)
1 Log, Rear (39-5) 2 Log, Left (39-1) 3 Log, Right (39-2) 4 Log, Top Center (39-6) 5 Log, Top/Left (39-3) 6 Log, Top/Right (39-4)
Catalog Number for the entire log set: H6197
4
5
6
Position the individual logs as shown below. Logs should be placed in the order shown. Position the rear log on the brackets at the rear of the firebox with the log's notches directly over the brackets. Position the right log (log no. 3) by inserting the pin from the rear log into the hole on its upper end. Place the left log and then the smaller left and right top logs. All logs that have notches to fit over the grate tines should be positioned with these notches directly against the grate. All top logs that rest on lower logs, do so over flattened mounting faces in the bottom logs.
Proper log and twig placement is critical to encourage outstanding flame appearance and prevent sooting.
1
4 3
2
Figure 54
5
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
6
29
Page 30
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
MPD40 AND MPD45 LOG PLACEMENT
Log
1
2
3
Number Description (Stamped #)
1 Log, Center (39-8) 2 Log, Rear (138) 3 Log, Right (39-10) 4 Log, Left (39-9) 5 Log, Top/Left (39-11) 6 Log, Top/Right (39-11)
Catalog Number for the entire log set: 24M25
4
5
6
Position the individual logs as shown below. Logs should be placed in the order shown. Position the center log on the burner first, then place the glowing embers as shown in Figure 52. Place the rear log, both the right and left, and then the smaller left and right top logs. All logs that have notches to fit over the grate tines should be positioned with these notches directly against the grate. All top logs that rest on lower logs, do so over flattened mounting faces in the bottom logs.
Proper log and twig placement is critical to encourage outstanding flame appearance and prevent sooting.
1
4
3
2
30
Figure 55
5
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
6
Page 31
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
Step 10. REMOVING AND INSTALLING THE GLASS DOOR
WARNING
Do not attempt to substitute the
materials used on these doors, or replace cracked or broken glass.
• Handle this glass with extreme
care! Glass is susceptible to damage - Do not scratch or handle roughly while reinstall­ing the glass door frame.
• The glass door of this appli­ance must only be replaced as a complete unit as provided by the manufacturer. Do not attempt to replace broken, cracked or chipped glass sepa­rately.
Do not attempt to touch the
front enclosure glass with your hands while the fireplace is in use.
WARNING
Do not operate appliance with the glass front removed, cracked or broken.
AVERTISSEMENT
Ne pas utiliser l'appareil si le panneau frontal en verre n'est pas en place, est craqué ou brisé.
Only doors certified with the appliance shall be used.
Removing the Glass Enclosure Panel (see Figure 56)
Remove the top louver assembly or radiant panel. To access the glass door securing latches, first open the lower control compartment door (Figure 56 ) by pushing in simultaneously the left and right top corners of the door (the door is hinged at the bottom).
Remove the bottom compartment door by sliding the hinge pin, located at the door’s left side, to the right until it disengages from the left corner post hole. Pull the door diagonally to the left, away from the fireplace.
Locate the two (2) latches at the top of the control compartment and disengage them from the door frame bottom vee-flange, pulling down on their handles to open them.
Installing the Glass Enclosure Panel (see Figure 56)
Retrieve the glass door. Visually inspect the gasket on the backside of the frame. Gasket surface must be clean, free of irregularities and seated firmly.
Position the door in front of the firebox opening with the bottom of the door held away from the fireplace (Figure 56). Hook the top flange of the door frame over the top of the firebox frame.
Let the bottom of the door frame swing gently in towards the fireplace ensuring that the gasket seats evenly as the door frame draws shut. Fasten the two latches located underneath the firebox floor to the door's vee-flange. Close both the latches securely.
Lower Compartment Door and Hinge
Glass Door
Glass Door Frame Top Flange
Step 11. BURNER ADJUSTMENTS
Flame Appearance and Sooting
Proper flame appearance is a flame that is blue at the base and becomes yellowish-orange in the body of the flame.
When the appliance is first lit, the entire flame may be blue and will gradually turn yellowish­orange during the first 15 minutes of operation. If the flame remains blue, or if the flame is orange with evidence of sooting (black tip), the air shutter opening may need to be adjusted.
If the air shutter opening is closed too far, sooting may develop. Sooting is indicated by black puffs developing at the tips of very long orange flames. Sooting results in black deposits forming on the logs, appliance inside surfaces and on exterior surfaces adjacent to the vent termination.
Sooting is caused by incomplete combustion in the flames and lack of combustion air enter­ing the air shutter opening. To achieve a warm yellowish-orange flame with an orange body that does not soot, the shutter opening must be adjusted between these two extremes.
Air Shutter Adjustment Guidelines
• If there is smoke or soot present, rst check
the log set positioning to ensure that the flames are not impinging on any of the logs. If the log set is properly positioned and a sooting condition still exists, then the air shutter opening should be increased.
• The more offsets in the vent system, the larger
the air shutter opening will need to be.
• An appliance operated with the air shutter
opened too far, may have flames that appear blue and transparent. These weak, blue and transparent flames are termed anemic.
• Propane models may exhibit ames which
candle or appear stringy. If this is present and persists, adjust the air shutter to a more closed position, then operate the appliance for a few more minutes to ensure that the flame normalizes and the flames do not appear sooty.
The following chart is provided to aid you in achieving the correct air shutter adjustment for your installation.
Seules des portes certifiées pour cet appareil doivent être utilisées.
WARNING: DO NOT abuse glass door by striking or slamming shut.
Glass Door Frame Bottom Vee-flange
Glass Door Latch
Figure 56
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Firebox Floor
Air Shutter Adjustment Guidelines
Amount of
Primary Air
If air shutter is closed too far
If air shutter is open too far
Flame
Color
Flame will be orange
Flame will be blue
Air Shutter
Adjustment
Air shutter gap should be increased
Air shutter gap should be decreased
31
Page 32
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
WARNING
Air shutter adjustment should
only be performed by a qualified professional service technician.
Ensure front glass panel are
in place and sealed during adjustment.
CAUTION
Soot will be produced if the
air shutter is closed too much. Any damage due to sooting, resulting from improperly setting the air shutter, is not covered under the warranty.
The air shutter door and
nearby appliance surfaces are hot. Exercise caution to avoid injury while adjusting flame appearance.
1. Refer to Figures 57, 58, and 59 for proper
flame app earance. To adjust the flame, rotate the adjustment rod toward the back or toward the front of the fireplace (rod located in the lower control area). Position the air shutter to the factory setting as shown in the table in Figure 60.
2. Light appliance (follow lighting procedure
on lighting label in control compartment or in the Care and Operation Instructions).
3. Allow the burner to operate for at least 15
minutes while observing the flame continu­ously to ensure that the proper flame ap­pearance has been achieved. If the following conditions are present, adjust accordingly.
• If ame appears weak or sooty, adjust
the air shutter, incrementally, to a more open position until the proper flame appearance is achieved.
• If ame remains blue, adjust the air
shutter, incrementally, to a more closed position until the proper flame appear­ance is achieved.
4. When satisfied that the burner flame appear-
ance is normal, reinstall the lower control compartment door, then proceed to finish the installation.
Figure 57 - MPD33 MODEL
Figure 58 - MPD35 MODEL
Figure 59 - MPD40 AND MPD45 MODEL
32
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 33
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
Burner Tube
Air Shutter
Adjustment Rod Down
(fully open position)
Models
MPD33
MPD35
MPD40
MPD45
Figure 60
Adjusting Set Screw
Adjustment Rod Up
(minimum air opening position)
Gas
Type
Factory Air
Shutter Setting
inches (mm)
Nat. 1/32 (0.8)
Prop. 3/16 (4.76)
Nat. 1/32 (0.8)
Prop. 3/16 (4.76)
Nat. 1/8 (3.2)
Prop. 1/2 (13)
Nat. 1/8 (3.2)
Prop. 1/2 (13)
Step 12. HOOD INSTALLATION
Refer to Figures 61 and 62. All models must have hoods installed prior to operating.
On all Radiant Panel units, slide the hood into the slots on the lower edge of the radiant panel (Figure 61).
On louvered face units, slide the hood into the slots on the lower edge of the cabinet top (Figure 62).
FINISHING REQUIREMENTS Wall Details
Complete finished interior wall. To install the appliance facing flush with the finished wall, position framework to accommodate the thick­ness of the finished wall (Figures 61 and 62)
See Page 5 for
Cold Climate Insulation and
Page 8 for Clearances.
Combustible
Finished Wall
Materials
Combustible material may touch top of appliance.
Combustible materials NOT allowed below this point on face of appliance.
Hood must be installed as shown.
This area must remain clear of combustible materials.
Header Spacing Top Standoff
Top of Appliance
Radiant panel
Top of Door Frame
Figure 61 - Radiant Panel Models
Combustible
Finished Wall
Materials
Combustible material may touch top of appliance.
Combustible materials NOT allowed below this point on face of appliance.
This area must remain clear of combustible materials.
Header Spacing Top Standoff
Top of Appliance
Louvers
Top of Door Frame
Min. 1 in. (25 mm)
Min. 1 in. (25 mm)
Hood must be installed as shown.
Figure 62 - Louver Face Models
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
33
Page 34
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
STEP 13. INSTALLER INSTRUCTIONS - ATTACHING SAFETY IN OPERATION WARNINGS It is the installers responsibility to ensure these warnings are properly affixed during installation. These warning labels are a
critical step in informing consumers of safe operation of this appliance.
ATTACHING SAFETY IN OPERATION WARNINGS
It is required that the safety instruction labels furnished with the fireplace be affixed to the op­eration and control point of the fireplace. A safety instruction label must be affixed to the wall switch plate where the fireplace is turned on and off (See Figure A) or wall thermostat (See Figure B) and if used on the remote control handheld transmitter (Figure C). To properly complete the installation of this fireplace, locate the multi-lingual adhesive labels provided with the Care and Operation Instructions and proceed as follows:
1. Locate the wall switch or wall thermostat that controls the fireplace (verify the switch operates the fireplace by turning it on and off). Clean the wall switch plate or wall thermostat thoroughly to remove any dust and oils. Affix the label to the surface of the plate of the wall switch that controls the fireplace (Figure A) or the wall thermostat (Figure B). Choose the language primarily spoken in the home. If unknown, affix the English language label.
2. If a remote control is used to control the fireplace, locate the transmitter and clean it thoroughly to remove any dust and oils. Affix the label to the surface of handheld transmitter (Figure C). Choose the language primarily spoken in the home. If unknown, affix the English language label.
3. If you are unable to locate the labels, please call Lennox Hearth Products or your nearest Lennox Hearth Products dealer to receive additional safety instruction labels free of charge.
Cat. No. H8024 Replacement Label Kit
LENNOX HEARTH PRODUCTS 1-800-655-2008
NOTE: English is red text on clear label. French and Spanish are white text on black label.
APPOSITION DES MISES EN GARDE RELATIVES À LA SÉCURITÉ D’UTILISATION
Il est impératif que les étiquettes de sécurité fournies avec le foyer soient collées à côté des dispositifs de contrôle du foyer. Une étiquette de sécurité doit être collée sur la plaque de l’interrupteur contrôlant l’allumage du foyer (voir Figure A) ou sur le thermostat mural (voir Figure B) et, le cas échéant, sur le boîtier de la télécommande (Figure C). Pour achever l’instal lation correcte de ce foyer, procédez comme suit avec les étiquettes adhésives en langues étrangères fournies avec les instructions d’utilisation et d’entretien :
1. Repérez l’interrupteur ou le thermostat mural qui contrôle le foyer (vérifiez que l’interrupteur contrôle le fonctionnement du foyer en le faisant basculer de Marche à Arrêt, et vice-versa). Nettoyez soigneusement la plaque murale de l’interrupteur ou le thermostat mural pour éliminer la poussière et les traces de graisse ou d’huile. Collez l’étiquette sur la surface de la plaque de l’interrupteur mural qui contrôle le foyer (Figure A) ou du thermostat mural (Figure B). Choisissez la langue qui est principalement parlée dans la résidence du propriétaire. En cas de doute, collez l’étiquette en anglais.
2. Si une télécommande est utilisée pour contrôler le foyer, nettoyez la soigneusement pour éliminer la poussière et les traces de graisse ou d’huile. Collez l’étiquette sur le boîtier de la télé commande (Figure C). Choisissez la langue qui est principalement parlée dans la résidence du proprié taire. En cas de doute, collez l’étiquette en anglais.
3. Si vous ne trouvez pas les étiquettes, veuillez appeler Lennox Hearth Products ou votre distribu­teur Lennox Hearth Products local pour recevoir gratuitement des étiquettes supplémentaires.
Étiquettes de remplacement, n° cat. H8024
LENNOX HEARTH PRODUCTS 1-800-655-2008
Remarque : Le texte anglais est rouge sur un support transparent. Le texte français et espagnol est blanc
sur un support noir.
COLOCACIÓN DE ADVERTENCIAS DE SEGURIDAD EN OPERACIÓN
Se requiere que las etiquetas de instrucciones de seguridad incluidas con la chimenea se coloquen en el punto de operación y control de la misma. Se debe colocar una etiqueta de instrucciones de seguridad en la placa del interruptor de pared desde el cual se enciende y se apaga la chimenea (ver la Figura A) o en el termostato de pared (ver la Figura B) y en el transmisor de control remoto (Figura C) si se usa. Para completar correctamente la instalación de esta chimenea, encuentre las etiquetas adhesivas multilingües incluidas con las instrucciones de cuidado y operación y haga lo siguiente:
1. Identifique el interruptor o el termostato de pared que controla la chimenea (verifique que el interruptor opera la chimenea encendiéndola y apagándola). Limpie bien la placa del interruptor o el termostato de pared para quitar el polvo y aceite. Pegue la etiqueta en la superficie de la placa del interruptor que controla la chimenea (Figura A) o en el termostato de pared (Figura B). Seleccione el idioma que más se habla en la casa. Si no sabe cuál es, use la etiqueta en inglés.
2. Si se usa un control remoto para controlar la chimenea, encuentre el transmisor y límpielo bien para quitar el polvo y aceite. Pegue la etiqueta en la superficie del transmisor (Figura C). Seleccione el idioma que más se habla en la casa. Si no sabe cuál es, use la etiqueta en inglés.
3. Si no puede encontrar las etiquetas, sírvase llamar a Lennox Hearth Products o al distribuidor de Lennox Hearth Products más cercano para recibir etiquetas de instrucciones de seguridad adicionales gratuitas.
Juego de etiquetas de repuesto - Nº de cat. H8024
LENNOX HEARTH PRODUCTS 1-800-655-2008
Nota: La etiqueta en inglés es transparente con texto
rojo. Las etiquetas en francés y español son negras
con texto blanco.
34
SAFETY LABEL DIAGRAMS DIAGRAMAS DE ETIQUETAS DE
Illustrations are for example only. Your accessories may be different.
Les illustrations sont par exemple
uniquement. Vos accessoires peuvent être différents.
Las ilustraciones son sólo ejemplos. Tu accesorios pueden ser diferentes.
Figure A
DIAGRAMMES DES ÉTIQUETTES
DE SÉCURITÉ
Figure B
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
SEGURIDAD
Figure C
Page 35
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
S
e
a
l
a
n t
INSTALLATION ACCESSORIES
Listed Secure Vent® Components
Cat. No. Model Description
H1968 SV4.5HT-2 Horizontal Square Ter-
mination with Firestop/ Spacer (H2246) and Adaptor (74L61)
H2152 SV4.5CGV-1 Vertical Termination Cap,
High Wind
94L10* SV4.5HTSS Horizontal Small Square
Termination with
Firestop/Spacer (96K80)
and Adaptor (74L61)
98L27* SV4.5HTSSL Horizontal Small Square
- Long Termination with
Firestop/Spacer (96K80)
and Adaptor (74L61)
17M52 SV4.5HGS-1 Termination Guard,
Square (1 pack)
Instr. #750109M)
17M53 SV4.5HGS-12 Termination Guard, Hori-
zontal Square (12 pack)
(Ref. Instr. #750109M)
87L02 SV4.5HGS Termination Guard for
Horizontal Square Termi­nation (Deluxe) (1 pack)
(Ref. Instr. #750055M)
(Ref.
Vent Sections
(Rigid)
Listed Secure Vent® Components
Cat. No. Model Description
77L70 SV4.5L6 6 Inch (152 mm) 77L71 SV4.5L12 12 Inch (305 mm) 77L72 SV4.5L24 24 Inch (610 mm) 77L73 SV4.5L36 36 Inch (914 mm) 77L74 SV4.5L48 48 Inch (1219 mm) 77L75 SV4.5LA Telescopic Length Slip
Section (2" to 7-1/2" rigid)
77L76 SV4.5E45 45 Degree Elbow
77L77 SV4.5E90 90 Degree Elbow
10K81 SFMP Mill-Pac, Black, High-
Temperature Sealant
89L40 SFMP-12 Mill-Pac, Black, High-
Temperature Sealant, Bulk 12 pack
99L02 SV4.5HRK14 Horizontal Riser Kit, 14",
(Ref. Instr. #750146M)
99L03 SV4.5HRK36 Horizontal Riser Kit, 36",
(Ref. Instr. #750146M)
96K93 SV4.5SU Support Strap
H5820 SV4.5HTSK Termination Shroud
(Guard) for Horizontal Square Termination (1 pack)
(Ref. Instr.
#750246M)
H3907 SV4.5ARSA Attic Insulation Shield with
adjustable height, 12"-22"
H1988 CTSA-33 Chase Top Shroud Kit,
Arch Top 3 X 3 Ft.,
Instr. #750194M)
(Ref.
H1985 CTSO-33 Chase Top Shroud Kit,
Open Top 3 X 3 Ft., (Ref.
Instr. #750193M)
H1987 CTSO-44 Chase Top Shroud Kit,
Open Top 4 X 4 Ft., (Ref.
Instr. #750193M)
H1986 CTSO-46 Chase Top Shroud Kit,
Open Top 4 X 6 Ft., (Ref.
Instr. #750193M)
H5816 SV4.5-
TWSK10
Through Wall Shield Kit
(used to shield the direct-vent pipe from blown insulation)
(Ref. Instr. #750247M)
The following flashings come packaged with a storm collar:
77L78 SV4.5F Flat Roof Flashing
77L79 SV4.5FA 1/12 to 7/12 Adjustable
Flashing
77L80 SV4.5FB 7/12 to 12/12 Adjustable
Flashing
77L81 SV4.5SC6 Storm Collar (6 per box)
H6183 SV4.5HF5 Firestop Spacer, 5", rigid H6184 SF4.5HF5 Firestop Spacer, 5", ex H2246 SV4.5HF-10 Firestop / Spacer - Hori-
zontal, rigid (3-1-1 spac­ing), 10 Pack
H2247 SV4.5VF-10 Firestop/Spacer - Verti-
cal, rigid (1-1-1 spac­ing), 10 Pack
96K92 SV4.5SP Support Plate
*Only for use with MPDT33 and MPD35 models.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
35
Page 36
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
INSTALLATION ACCESSORIES CONTINUED
Listed Secure Flex® Components
Cat. # Model Description
These termination kits include firestop/spacer, gear clamps and flex adaptor.
60L10 SF-18 18 feet (5.49 m) *
98K03 SF-12 12 feet (3.66 m)*
H2248 SF4.5HF-10 Firestop / Spacer -
H2249 SF4.5VF-10 Firestop/Spacer - Vertical,
56L74 SFVT30 Vertical Termination for ex
56L75 SFVT45 Vertical Termination for ex
91L66 SFGC4-6 Gear Clamp 4.5" (114 mm)
91L67 SFGC7-6 Gear Clamp 7.5" (190.5 mm)
H7748 H7748 36" Flex Connector Kit. 36"
compressed ex
(Ref. Instr. #750053M)
compressed ex (Ref. Instr.
#750052M)
Horizontal, ex (3-1-1 spacing), 10 Pack
ex (1-1-1 spacing), 10 Pk
(flat to 6/12) with flex adaptor,
section of rigid vent, roof support collar assembly, roof flashing and storm collar.
(Ref. Instr. #750052M)
(6/12 to 12/12) with flex adaptor, section of rigid vent, roof support collar assembly, roof flashing, and storm collar.
#750052M)
(Ref. Instr.
for ex (6 pack)
for ex (6 pack)
of flex with two adaptors for mating two rigid sections of vent together.
Listed Secure Flex® Components
Cat. # Model Description
H1969 SF4.5HT-2 Horizontal Square Termina-
77L87 SFKIT12S Square Term. for ex (with
77L88 SFKIT18S Square Term. for ex (with
77L89 SFKIT24S Square Term. for ex (with
77L90 SFKIT36S Square Term. for ex (with
77L91 SFKIT48S Square Term. for ex (with
94L04* SFKIT12SS Small Square Termination for
94L05* SFKIT18SS Small Square Termination for
94L06* SFKIT24SS Small Square Termination for
94L07* SFKIT36SS Small Square Termination for
94L08* SFKIT48SS Small Square Termination for
94L09* SF-HTSS Horizontal Small Square
tion for ex (without flex vent)
12" [305 mm] compressed flex vent**)
18" [457 mm] compressed flex vent**)
24" [610 mm] compressed flex vent**)
36" [914 mm] compressed flex vent**)
48" [1219 mm] compressed flex vent**)
ex, with 12" (305 mm) of compressed flex vent**
(Ref. Instr. #750204M)
ex, with 18" (457 mm) of compressed flex vent**
(Ref. Instr. #750204M)
ex, with 24" (610 mm) of compressed flex vent**
(Ref. Instr. #750204M)
ex, with 36" (914 mm) of compressed flex vent**
(Ref. Instr. #750204M)
ex, with 48" (1219 mm) of compressed flex vent** (Ref.
Instr. #750204M)
Termination for ex, without flex vent (Ref. Instr. #750204M)
36
*Only for use with MPDT33 and MPD35 models. **All compressed flex vents can be expanded up to two times.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 37
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
GAS CONVERSION KITS
WARNING
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instruction is not followed exactly, a fire, explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life. The qualified service agency is responsible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manu­facturer’s instructions supplied with the kit.The qualified service agency performing this installation assumes responsibility for this conversion.
AVERTISSEMENT
Cette trousse de conversion doit être installée par un technicien agréé, selon les instructions du fabricant et selon toutes les exigences et tous les codes pertinents de l’autorité compétente. Assurez-vous de bien suivre les instructions dans cette notice pour réduire au minimum le risque d’incendie, d’explosion ou la production de monoxyde de carbone pouvant causer des dommages matériels, des blessures ou la mort. Le tecnicien agréé est responsable de l’installation de cette trousse. L’installation n’est pas adéquate ni complète tant que le bon fonctionnement de l’appareil converti n’a pas été vérifié selon les instructions du fabricant fournies avec la trousse. Le fournisseur de service qualifié ayant réalisé l'installation assume les responsabilités liées à la conversion.
In Canada: THE CONVERSION SHALL BE CAR­RIED OUT IN ACCORDANCE WITH THE REQUIREMENTS OF THE PROVINCIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE RE­QUIREMENTS OF THE CAN/CGA-B149.1 INSTALLATION CODE.
LA CONVERSION DEVRA ÊTRE EFFECTUÉE CONFORMÉMENT AUX RECOMMANDATIONS DES AUTORI­TÉS PROVINCIALES AYANT JURIDIC­TION ET CONFORMÉMENT AUX EXI­GENCES DU CODE D'INSTALLATION CAN/CGA-B149.1.
Gas conversion kits are available to adapt your appliance from the use of one type of gas to the use of another. These kits contain all the necessary components needed to complete the task including labeling that must be affixed to ensure safe operation.
Kit part numbers are listed here and the follow­ing steps detail the conversion procedure. Refer to the instructions provided with the conversion kit when performing any gas conversion.
Millivolt SIT Systems
Natural Gas To Propane Gas
Conversion Kits Models Catalog No. MPD33 H2009 MPD35 H2011 MPD40 H2013 MPD45 H2015
Millivolt SIT Systems
Propane Gas to Natural Gas
Conversion Kits Models Catalog No. MPD33 H2010 MPD35 H2012 MPD40 H2014 MPD45 H2016
Electronic SIT Systems
Natural Gas To Propane Gas
Conversion Kits
Models Catalog No.
MPD33 H8632 MPD35 H8634 MPD40 H8636 MPD45 H8638
Electronic SIT Systems
Propane Gas To Natural Gas
Conversion Kits Models Catalog No. MPD33 H8631 MPD35 H8633 MPD40 H8635 MPD45 H8637
INSTALLATION INSTRUCTIONS
Step 1. TURN OFF THE GAS SUPPLY TO THE APPLIANCE and disconnect power supply at the circuit breaker. Ensure appliance is cold.
CAUTION: THE GAS SUPPLY SHALL BE SHUT OFF PRIOR TO DISCONNECTING THE ELECTRICAL POWER, BEFORE PROCEED­ING WITH THE CONVERSION.
ATTENTION: AVANT D’EFFECTUER LA CONVERSION, COUPEZ D’ABORD L’ALIMENTATION EN GAZ, ENSUITE, COUPEZ L’ALIMENTATION ÉLECTRIQUE.
Step 2. Open the lower control compartment
door (see Figure 48 on Page 27) by pushing on the right top corner of the door (the door is hinged at the bottom).
[Optional] Remove the control compartment door by sliding the hinge pin, located at the door’s left side, to the right until it disengages from the left corner post hole. Pull the control compartment door diagonally to the left, away from the fireplace.
Step 3. Remove the front glass door/frame from the appliance (see Page 32).
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
37
Page 38
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
Pressure Regulator
Remove These Components
Pilot
Orifice
Step 4. Carefully remove the logs. Exercise care so as not to break the logs.
Step 5. Refer to Figure 53, 54, or 55. A. Remove the grate and sub floor. B. Remove the two (2) screws securing the
burner assembly. C. Remove the burner assembly with attached
venturi tube.
Millivolt and Electronic Ignition System Appliances
Step 6. SIT Systems - Refer to Figure 63
and the instructions provided with the SIT
Regulator Conversion Kit. Using a Torx T20
driver (with 1/4" shank and center hole) or slotted screwdriver, remove and discard the pressure regulator mounting screws (two screws for electronic models, three screws for millivolt models), pressure regulator tower, the diaphragm assembly (if applicable) and the spring. Discard all removed components.
Step 7. Install the new pressure regulator as­sembly using the supplied screws as shown in Figure 63. Tighten the screws to 25 in-lb.
Millivolt Valve
Electronic Valve
Figure 63: Regulator Conversion
Step 8. Install the enclosed identification label to the valve body where it can be easily seen.
Step 9. Refer to Figure 64. Remove the pilot hood assembly to access the hexed pilot orifice. Remove and replace the orifice with the one provided with the kit. Exercise extreme care to prevent damage to or breakage of the igniter assembly.
Figure 64: Millivolt Pilot (electronic pilot is similar)
Step 10. Remove the orifice from the manifold and replace it with the one provided in the kit. See Table 10 for orifice sizes for natural and propane models. Figure 65 illustrates the orifice.
Burner Orifice Sizes
Elevation 0-4500 feet ( 0-1372 meters)
Model
Series
MPD33
MPD35
MPD40
MPD45
Table 10
Nat.Gas
drill size (inches)
#47 (0.0785")*
99K74 •
#44 (0.086")*
60J80 •
#38 (0.102") *
99K76 •
#37 (0.104")*
24M10 •
* Standard size installed at factory
• Part /Cat. Number
Propane
drill size (inches)
0.048"
99K78 •
#55 (0.052")*
19L52 •
0.062"
21L01 •
#52 (0.0635")*
37G00 •
Figure 65: Orice
Use pipe joint compound or Teflon tape on all pipe fittings before installing (ensure propane resistant compounds are used in propane ap­plications, do not use pipe joint compounds on flare fittings).
Step 11. Retrieve the burner and hold the
venturi tube above the orifice. Place the shutter adjusting rod in the slot of the shutter arm (see Figure 60 on Page 34). Set the burner assem- bly into its position and secure the trapezoidal plate with the two screws previously removed.
Step 12. Reinstall the baffle with the two baffle securing screws.
Step 13. Reassemble the remaining compo­nents by reversing the procedures outlined in the Steps 1-5.
Step 14. Attach the conversion label provided in the conversion kit next to the rating plate on the appliance.
Step 15. Turn on gas supply and test for gas leaks (refer to Page 27).
Step 16. Relight the main burner. The lighting instructions can be found on the lighting label in the control compartment or in the Care and Operation Manual provided with the appliance. Verify proper burner ignition and operation. See Burner Adjustments and Burner Flame Appear­ance on Page 33.
Step 17. Inspect the pilot system for proper flame. The pilot flame should engulf the flame sensor as shown in Figures 49 and 50 on Page 27.
Step 18. Using a manometer, test the inlet and manifold gas pressures. See Tables 2 and 3 on Page 4.
ALWAYS TEST PRESSURES WITH THE VALVE REGULATOR CONTROL AT THE HIGHEST SETTING.
38
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design, materials, specifications, and prices, and also to discontinue colors, styles, and products. Consult your local distributor for fireplace code information.
LENNOX®, the LENNOX design, DAVE LENNOX, the image of DAVE LENNOX and other related LENNOX marks are registered or common law trademarks of Lennox Industries Inc. and are used with permission.
Printed in U.S.A. © 2012 Lennox Hearth Products LLC
P/N 506015-07 Rev. B 06/2013
1508 Elm Hill Pike, Suite 108 • Nashville, TN 37210
Loading...