AVERTISSEMENT : Assurez-vous de bien suivre les
instructions données dans cette notice pour réduire au
minimum le risque d’incindie ou d’explosion ou pour
éviter tout dommage matériel, toute blessure ou la mort.
WARNING: If the information in these instructions
is not followed exactly, a fire or explosion may
result, causing property damage, personal injury,
or death.
WARNING /AVERTISSEMENT/AVISO
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
UNE SURFACE VITRÉE CHAUDE
PEUT CAUSER DES BRÛLURES.
LAISSER REFROIDIR LA SURFACE
VITRÉE AVANT D'Y TOUCHER.
NE PERMETTEZ JAMAIS À UN ENFANT
DE TOUCHER LA SURFACE VITRÉE.
EL VIDRIO CALIENTE
CAUSARÁ QUEMADURAS.
USTED DEBE NUNCA
TOCAR EL VIDRIO CALIENTE.
LOS NIÑOS DEBEN NUNCA
TOCAR EL VIDRIO.
- Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the fire
department.
- Installation and service must be performed by a
qualified installer, service agency or the gas supplier.
- Ne pas entreposer ni utilizer d’essence ni d’autres vapeurs
ou liquides inflammables dans le voisinage de cet appareil
ou de tout autre appareil.
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucan interrupteur. Ne pas vous servir des
téléphones se trouvant dans le bâtiment où vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis
un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service des incindies.
- L’installation et l’entretien doivent être assurés par un
installateur ou un service d’entretien qualifié ou par le
fournisseur de gaz.
MPD Direct-Vent
Gas Fireplaces
MODELS
P/N 506015-07 Rev. B 06/2013
This manual is one of a set of two supporting this product. Refer to P/N 506017-06 for
Care and Operation Instructions.
Ce manuel est disponible en francais, simplement en faire la demande. Numéro de la pièce
506223-43.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
INSTALLATEUR : Laissez cette notice avec l’appareil.
CONSOMMATEUR : Conservez cette notice pour
consultation ultérieure.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile
home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating
plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
Gas Conversion Kits ................................... 37
Please read and understand these
instructions before beginning your
installation.
PACKAGING
The assembled vented gas fireplace heater is
packaged with:
• (1 set) Logs (packaged in a carton inside the
firebox).
• (1 bag) Glowing Embers (in bottom compartment).
• Literature Kit (envelope in bottom compartment containing Care and Operation
Instructions, Installation Instructions, SafetyIn-Operation Warning Labels, Warranty).
• (1) U-Shaped Vent Restrictor (attached to
Literature Kit envelope).
• (1) Hood (inside rebox).
INTRODUCTION
The Millivolt appliances have a millivolt gas
control valve with piezo ignition system. If any
optional accessories that will require electrical
power are to be installed, the electrical power
must be provided at the time of appliance
installation.
The Electronic appliances are designed to
operate on natural or propane gas. An electronic
intermittent pilot ignition system provides safe,
efficient operation. External electrical power is
required to operate these units. In the event of a
power outage, four (4) "AA" batteries (in battery
holder) provide backup power for appliance
operation (excluding [optional] blower).
These vented gas fireplace heaters are sealed
combustion, air-circulating gas fireplaces
designed for residential applications.
Approved Vent Components
These fireplaces are designed, tested and listed
for operation and installation with the following
vent components only:
®
• Secure Vent
nents manufactured by Security Chimneys
International,
• Secure Flex
manufactured by Security Chimneys International and
• Z-FLEX
to UL1777 and ULCS635 manufactured by
Flexmaster Canada Limited.
Use only the correct size venting (4-1/2" inner
and 7-1/2" outer).
These approved vent system components are
labeled for identification. DO NOT use any
other manufacturer’s vent components with
these appliances.
Direct-Vent System Compo-
®
Flexible Vent Components
®
Model GA Venting Systems listed
GENERAL INFORMATION
WARNING
Young children should be carefully supervised when they are
in the same room as the appliance. Toddlers, young children
and others may be susceptible
to accidental contact burns. A
physical barrier is recommended
if there are at risk individuals in
the house. To restrict access to
a fireplace or stove, install an
adjustable safety gate to keep
toddlers, young children and
other at risk individuals out of
the room and away from hot
surfaces.
AVERTISSEMENT
Les jeunes enfants devraient être
surveillés étroitement lorsqu’ils
se trouvent dans la même pièce
que l’appareil. Les tout petits,
les jeunes enfants ou les adultes
peuvent subir des brûlures s’ils
viennent en contact avec la surface chaude. Il est recommandé
d’installer une barrière physique
si des personnes à risques habitent la maison. Pour empêcher
l’accès à un foyer ou à un poêle,
installez une barrière de sécurité; cette mesure empêchera les
tout petits, les jeunes enfants et
toute autre personne à risque
d’avoir accès à la pièce et aux
surfaces chaudes.
Children and adults should be alerted to the
hazards of high surface temperature and
should stay away to avoid burns or clothing
ignition.
Les enfants et les adultes devraient être
informés des dangers que posent les
températures de surface élevées et se
tenir à distance afin d’éviter des brûlures
ou que leurs vêtements ne s’enflamment.
DO NOT ATTEMPT TO ALTER OR MODIFY
THE CONSTRUCTION OF THE APPLIANCE
OR ITS COMPONENTS. ANY MODIFICATION
OR ALTERATION MAY VOID THE WARRANTY,
CERTIFICATION AND LISTINGS OF THIS UNIT.
2
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 3
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
WARNING
Improper installation, adjustment, alteration, service or
maintenance can cause injury
or property damage. Refer to
this manual. For assistance or
additional information consult
a qualified installer, service
agency or the gas supplier.
WARNING
Failure to comply with these
installation instructions will
result in an improperly installed
and operating appliance, voiding
its warranty. Any change to this
appliance and/or its operating
controls is dangerous.
WARNING
Clothing or other flammable
material should not be placed
on or near the appliance.
AVERTISSEMENT
On ne devrait pas placer de
vêtements ni d’autres matières
inflammables sur l’appareil ni à
proximité.
WARNING
Any safety screen or guard
removed for servicing the appliance must be replaced prior to
operating the appliance.
AVERTISSEMENT
Tout écran ou protecteur retiré
pour permettre l’entretien de
l’appareil doit être remis en
place avant de mettre l’appareil
en marche.
WARNING
Improper installation or use of
this appliance can cause serious
injury or death from fire, burns,
explosion or carbon monoxide
poisoning.
WARNING
Failure to position the parts in
accordance with these diagrams
or failure to use only parts
specifically approved with this
appliance may result in property
damage or personal injury.
AVERTISSEMENT
Risque de dommages ou de
blessures si les pièces ne sont
pas installées conformément à
ces schémas et ou si des pièces
autres que celles spécifiquement
approuvées avec cet appareil sont
utilisées.
NOTE: Installation and repair should be done
by a qualified service person. The appliance
should be inspected before use and at least
annually by a professional service person.
More frequent cleaning may be required due
to excessive lint from carpeting, bedding
material, etcetera. It is imperative that control
compartments, burners and circulating air
passageways of the appliance be kept clean.
Remarque: L’installation et la réparation
devrait être confiées à un technicien
qualifié. L’appareil devrait faire l’objet
d’une inspection par un technicien
professionnel avant d’être utilisé et au
moins une fois l’an par la suite. Des
nettoyages plus fréquents peuvent être
nécessaires si les tapis, la literie, et
cetera produisent une quantité importante
de pous-sière. Il est essentiel que les
compartiments abritant les commandes,
les brûleurs et les conduits de circulation
d’air de l’appareil soient tenus propres.
Do not use this appliance if any part has
been under water. Immediately call a
qualified service technician to inspect the
appliance and to replace any parts of the
control system and any gas control which
has been under water.
Ne pas utiliser cet appareil s’il a été
plongé, même partiellement, dans
l’eau. Appeler un technicien qualifié
pour inspecter l’appareil et remplacer
toute partie du système de commande
et toute commande qui a été plongée
dans l’eau.
Only trim kit(s) supplied by the manufacturer
shall be used in the installation of this
appliance.
Seules les trousses de garniture fournies
par le fabricant doivent être utilisées pour
l’installation de cet appareil.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
These appliances comply with National Safety
Standards and are tested and listed by OMNITest Laboratories, Inc. (Report No. 116-F-13g-5)
to ANSI Z21.88-2009 (in Canada, CSA-2.33-
2009), and CAN/CGA-2.17-M91(R2009) in both
USA and Canada, as vented gas fireplace heaters.
Both millivolt and electronic versions of
these appliances are listed by OMNI-Test
Laboratories for installation in bedrooms
and Manufactured Homes.
Misc. Codes / Standards
The Installation must conform to local codes
or, in the absence of local codes, with the
National Fuel Gas Code, ANSI Z223.1 / NFPA
54 - latest edition (In Canada, the current CAN/
CGA-B149.1 installation code).The appliance,
when installed, must be electrically grounded
and wired in accordance with local codes or, in
the absence of local codes, with the National Electrical Code, ANSI/NFPA 70 - latest edition,
or the Canadian Electrical Code, CSA C22.1 - latest edition.
Provide adequate clearances around air
openings and adequate accessibility clearance
for service and proper operation. Never obstruct
the front or back openings of the appliance.
These appliances are designed to operate on
natural or propane gas only. The use of other
fuels or combination of fuels will degrade
the performance of this system and may be
dangerous.
These fireplaces are designed as supplemental
heaters. Therefore, it is advisable to have an
alternate primary heat source when installed
in a dwelling.
These appliances must not be connected to a
chimney or flue serving a separate solid fuel
burning appliance.
Both millivolt and electronic systems can be
operated during a power outage, and feature
manually operated hi-low flame control. The BTU
Input for these appliances is shown in Table 1.
Models
MPD33
MPD35
MPD40
MPD45
Table 1 - Input (BTU/HR) Gas Valves
(Millivolt and Electronic)
Input Rate (BTU/HR)
Nat. GasProp. Gas
17,500 high
11,700 low
20,000 high
12,800 low
27,000 high
18,500 low
29,000 high
20,500 low
17,500 high
14,000 low
20,000 high
15,200 low
27,000 high
21,500 low
29,000 high
22,500 low
3
Page 4
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
Gas Pressure - All Models
Tables 2 and 3 show the appliances' inlet and
manifold gas pressure requirements:
Fuel #MinimumMaximum
Natural
Gas
Propane
4.5" WC
(1.12 kPa)
11.0" WC
(2.74 kPa)
10.5" WC
(2.61 kPa)
13.0" WC
(3.23 kPa)
Table 2: Inlet Gas Supply Pressure
Fuel #LowHigh
Natural
Gas
Propane
1.6" WC
(0.40 kPa)
6.3" WC
(1.57 kPa)
3.5" WC
(0.87 kPa)
10.0" WC
(2.49 kPa)
Table 3: Manifold Gas Supply Pressure
Test gauge connections are provided on the
front of the millivolt and electronic gas control
valve (identified IN for the inlet and OUT for
the manifold side). The control valves have a
3/8" (10 mm) NPT thread inlet and outlet side
of the valve (refer to Figures 1 and 2).
Propane tanks are at pressures that will cause
damage to valve components. Verify that the
tanks have step down regulators to reduce the
pressure to safe levels.
The appliance and its appliance main gas
valve must be disconnected from the gas
supply piping system during any pressure
testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the
gas supply piping system by closing its
equipment shutoff valve during any pressure
testing of the gas supply piping system at
test pressures equal to or less than 1/2 psi
(3.5 kPa).
Orifice Sizes - Sea Level to High Altitude
(All Models)
These appliances are tested and approved for
installation at elevations of 0-4500 ft (0-1372
m) above sea level using the standard burner
orifice sizes (marked with an "*" in Table 4).
For elevations above 4500 ft, contact your gas
supplier or qualified service technician.
Deration - At higher elevations, the amount
of BTU fuel value delivered must be reduced
by either:
• Using gas that has been derated by the gas
company.
• Changing the burner orice to a smaller size
as regulated by the local authorities having
jurisdiction and by the (USA) National Fuel
Gas Code NFPA 54 - latest edition / ANSI
Z223.1 or, in Canada, the CAN/CGA-B149.1
codes - latest edition.
Install the appliance according to the regulations
of the local authorities having jurisdiction and,
4
in the USA, the National Fuel Gas Code NFPA
54 - latest edition / ANSI Z223.1 or, in Canada,
the CAN/CGA-B149.1 - latest edition.
Flame breadth, height and width will diminish
4% for every 1,000 feet of altitude. Gas Valve
Diagrams
. See Figure 1 for Millivolt models
and Figure 2 For Electronic Models.
Burner Orifice Sizes
Elevation 0-4500 feet ( 0-1372 meters)
Model
Series
MPD33
MPD35
MPD40
MPD45
Table 4
Nat.Gas
drill size (inches)
#47 (0.0785")*
99K74 •
#44 (0.086")*
60J80 •
#38 (0.102") *
99K76 •
#37 (0.104")*
24M10 •
* Standard size installed at factory
• Part /Cat. Number
Propane
drill size (inches)
0.048"
99K78 •
#55 (0.052")*
19L52 •
0.062"
21L01 •
#52 (0.0635")*
37G00 •
In Canada - CAN/CGA-2.17-M91 (R2009)
(high altitude): THE CONVERSION SHALL
BE CARRIED OUT BY A MANUFACTURER’S
AUTHORIZED REPRESENTATIVE,IN
ACCORDANCE WITH THE REQUIREMENTS
OF THE MANUFACTURER, PROVINCIAL
OR TERRITORIAL AUTHORITIES HAVING
JURISDICTION AND IN ACCORDANCE WITH
THE REQUIREMENTS OF THE CAN/CGA-B149.1
OR CAN/CGA-B149.2 INSTALLATION CODES.
Main Gas Control Knob
OFF/PILOT/ON
N
O
T
O
t
i
L
I
P
O
F
F
OUT
IN
Manifold Pressure Tap
Inlet Pressure Tap
Figure 1 - SIT Millivolt
Pilot Adjustment
L
I
P
W
O
L
H
I
HI/LO Variable
Flame Height
Adjustment
Screw
T
O
H T P T H T P T
Gas Valve
(from DFC Wire Harness)
Inlet (IN) Test Port
Manifold (OUT) Test Port
Orange Wire
(from DFC Wire
Harness)
Main Gas Inlet
3/8" NPT
Green Wire
Figure 2 - SIT Electronic Gas Valve
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
REQUIREMENTS FOR THE
COMMONWEALTH OF MASSACHUSETTS
These fireplaces are approved for installation in
the US state of Massachusetts if the following
additional requirements are met:
• Install this appliance in accordance with
Massachusetts Rules and Regulations 248
C.M.R.
• Installation and repair must be done by
a plumber or gas fitter licensed in the
Commonwealth of Massachusetts.
• The exible gas line connector used shall
not exceed 36 (92 cm) in length.
• The individual manual shut-off must be a
T-handle type valve.
Massachusetts Horizontal Vent Requirements
in the Commonwealth of Massachusetts,
horizontal terminations installed less than
seven (7) feet above the finished grade
must comply with the following additional
requirements:
• A hard wired carbon monoxide detector
with an alarm and battery back-up must be
installed on the floor level where the gas
fireplace is installed. The carbon monoxide
detector must comply with NFPA 720, be
ANSI/UL 2034 listed and be ISA certified.
• A metal or plastic identication plate must be
permanently mounted to the exterior of the
building at a minimum height of eight (8) feet
above grade and be directly in line with the
horizontal termination. The sign must read,
in print size no less than one-half (1/2) inch
in size, GAS VENT DIRECTLY BELOW. KEEP
CLEAR OF ALL OBSTRUCTIONS.
Hi/Lo Flame
Control Knob
Yellow Ground Wire
(from DFC Wire Harness)
Page 5
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks
around your appliance with noncombustible
material and wherever cold air could enter
the room. It is especially important to insulate
outside chase cavity between studs and under
floor on which appliance rests, if floor is above
ground level. Gas line holes and other openings
should be caulked or stuffed with unfaced
fiberglass insulation.
If the fireplace is being installed on a cement
slab in cold climates, a sheet of plywood or
other raised platform can be placed underneath
to prevent conduction of cold transferring to
the fireplace and into the room. It also helps to
sheetrock inside surfaces and tape for maximum
air tightness and caulk firestops.
MANUFACTURED HOME
REQUIREMENTS
This appliance may be installed in an aftermarket
permanently located, manufactured home
and must be installed in accordance with the
manufacturer's instructions.
Cet appareil peut être installé cómme
du matériel d'origine dans une maison
préfabriquée (É.U. seulement) ou mobile
et doit être installé selon les instructions
du fabricant.
This appliance is only for use with the type of
gas indicated on the rating plate. This appliance
is not convertible for use with other gases,
unless a certified kit is used.
TOP VENT
APPLICATION
APPLICATION
TOP VENT
INSTALLATION
VERTICAL VENT
(Rear Vent Application)
HORIZONTAL VENT
(Rear Vent Application with a chase)
RECESSED
REAR VENT
APPLICATION
TOP VENT
APPLICATION
TOP VENT
APPLICATION
HORIZONTAL VENT
(Rear Vent Application without a chase)
Figure 3 - Typical Locations
REAR VENT
APPLICATION
TOP VENT
APPLICATION
TOP VENT
APPLICATION
HORIZONTAL VENT
(Top Vent Application)
VERTICAL VENT
(Top Vent Application)
Cet appareil doit être utilisé uniquement
avec le type de gaz indiqué sur la plaque
signalétique. Cet appareil ne peut être
converti à d'autres gaz, sauf si une trousse
de conversion est utilisée.
CAUTION: Ensure that the cross members are not cut or weakened during
installation. The structural integrity of
the manufactured home floor, wall, and
ceiling / roof must be maintained.
CAUTION: This appliance must be grounded to the chassis of the manufactured
home in accordance with local codes or
in the absence of local codes, with the
National Electrical Code ANSI / NFPA 70
- latest edition or the Canadian Electrical
Code CSA C22.1 - latest edition.
LOCATION
In selecting the location, the aesthetic and
functional use of the appliance are primary
concerns. However, vent system routing to
the exterior and access to the fuel supply are
also important.
Due to high temperatures, the appliance
should be located out of traffic and away from
furniture and draperies (Figure 3).
En raison des températures élevées, l’appareil
devrait être installé dans un endroit où il y a
peu de circulation et loin du mobilier et des
tentures (Figure 3).
The location should also be free of electrical,
plumbing or other heating/air conditioning
ducting.
These direct-vent appliances are uniquely
suited for installations requiring a utility shelf
positioned directly above the fireplace. Utility shelves like these are commonly used for
locating television sets and decorative plants.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Be aware that this is a heat producing
appliance. Objects placed above the unit are
exposed to elevated temperatures.
Do not insulate the space between the appliance and the area above it (see Figure 8).
The minimum height from the base of the appliance to the underside of combustible materials
used to construct a utility shelf in this fashion
is shown in Figure 8.
The appliance must be mounted on a fully
supported base extending the full width
and depth of the unit. The appliance may be
located on or near conventional construction
materials. However, if installed on combustible
materials, such as carpeting, vinyl tile or other
combustible material other than wood flooring,
the appliance shall be installed on a metal or
wood panel extending the full width and depth
of the appliance.
5
Page 6
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
VENT TERMINATION CLEARANCES
These instructions should be used as a
guideline and do not supersede local codes
in any way. Install venting according to local
codes, these instructions, the current National
Fuel Gas Code (ANSI-Z223.1) in the USA or
the current standards of CAN/CGA-B149.1
in Canada.
Vertical Vent Termination Clearances
Terminate multiple vent terminations according
to the installation codes listed above and
Figures 4 and 5.
12"
(305mm)
Minimum
Figure 4 - Multiple Terminations
Vertical Vent Termination Clearances
The vent / air intake termination clearances
above the high side of an angled roof are as
TERMINATION HEIGHTS FOR VENTS ABOVE
Horizontal Overhang
2 FT MIN.
Termination
Storm Collar
Flashing
Concentric
Vent Pipe
FLAT OR SLOPED ROOFS
Vent
*H = MINIMUM HEIGHT FROM ROOF TO
LOWEST DISCHARGE OPENING OF VENT
2 FT
MIN.
Lowest
Discharge
Opening
H*
1 inch (25.4 mm) Minimum
Clearance to Combustibles
Vertical
Wall
X
12
Roof Pitch is X/12
Figure 5 - Termination Heights for Vents
Above Flat or Sloped Roofs
The horizontal vent termination must have a minimum of 6" (152 mm) clearance to any overhead
combustible projection of 2-1/2" (64 mm) or less, see Figure 6. For projections exceeding 2-1/2"
(64 mm), see Figure 6. For additional vent location restrictions, refer to Figure 7 on Page 7.
Horizontal Vent Termination Clearances
Combustible Projection
2-1/2”
or less in length
Combustible Projection greater
than 2-1/2” in length
Ventilated
Soffit
Unventilated
Soffit
18"
(457 mm)
12"
(305 mm)
Side Elevation View
Termination Kit
Figure 6 - Horizontal Vent
Termination Clearances
6"
(152 mm)
All horizontal terminations
may be located as close as
6” (152mm) to any
(non-combustible and
combustible) exterior
sidewall. This distance
may be decreased to 2”
(51mm) for non-combustible exterior
sidewalls only, if the
SV4.5HT-2 termination
is used.
Termination Kit
NOTE: See Figure 34 on Page 20 for the exterior wall recess
allowances of the square horizontal termination.
6
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 7
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
A = Clearance above grade, veranda, porch, deck
or balcony.
B = Clearance to window or door that may be opened 6" (15.2 cm) for appliances < 10,000 BTU/hr (3kW),
C = Clearance to permanently closed window12" (305 mm) recommended to prevent window conden-
D = Vertical clearance to ventilated soffit located
above the terminal within a horizontal distance of
18" (458 mm)
E = Clearance to unventilated soffit12" (30 cm)12" (30 cm)
F = Clearance to outside corner5" (12.7 cm)5" (12.7 cm)
G = Clearance to inside corner2" (5.08cm) minimum - SV4.5HT-2 •
H = Clearance to each inside of center line extended
above meter / regulator assembly
I = Clearance to service regulator vent outlet3 feet (91 cm) *3 feet (91 cm) **
J = Clearance to non-mechanical air supply inlet
to building or the combustion air inlet to any other
appliance
K = Clearance to mechanical air supply inlet6 feet (1.83 meters) *3 feet (91 cm) above, if within 10 feet (3 m) horizontally**
L = Clearance above paved sidewalk or paved
driveway located on public property
M = Clearance under veranda, porch, deck or
balcony
N = Depth of Alcove (Maximum)6 feet (1.83m)*6 feet (1.83m)**
O = Clearance to Termination (Alcove)6" (15.2mm)*6" (15.2mm)**
P = Width of Alcove (Minimum)3 feet (91cm)*3 feet (91cm)**
Q = Clearance to Combustible Above (Alcove)18" (457mm)*18" (457mm)**
* In accordance with the current CAN/CGA-B149.1 National Gas and Propane Installation Code.
** In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Codes.
‡ A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.
*‡ Only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor.
• 2" Clearance to Non-Combustibles for SV4.5HT-2 Only.
12" (30 cm) *12" (30 cm) **
6" (15.2 cm) for appliances < 10,000 BTU/hr (3kW),
12" (30 cm) for appliances > 10,000 BTU/hr (3kW)
9" (23 cm) for appliances > 10,000 BTU/hr (3kW) and
< 50,000 BTU/hr (15kW), 12" (30 cm) for appliances >
50,000 BTU/hr (15kW)**
9" (229 mm) recommended to prevent window con-
sation
densation
18" (458 mm)18" (458 mm)
2" (5.08cm) minimum - SV4.5HT-2 •
6" (15.2cm) minimum - SV4.5HTSS •
3 feet (91 cm) within a height of 15 feet above the meter /
regulator assembly *
6" (15.2 cm) for appliances < 10,000 BTU/hr (3kW), 12"
(30 cm) for appliances > 10,000 BTU/hr (3kW)
6" (15.2cm) minimum - SV4.5HTSS •
3 feet (91 cm) within a height of 15 feet above the meter
/ regulator assembly **
6" (15.2 cm) for appliances < 10,000 BTU/hr (3kW), 9"
(23 cm) for appliances > 10,000 BTU/hr (3kW) and <
50,000 BTU/hr (15kW), 12" (30 cm) for appliances >
50,000 BTU/hr (15kW)**
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
12 (305) MANTEL
10 (254) MANTEL
8 (203) MANTEL
6 (152) MANTEL
4 (102) MANTEL
4
(102)
14
(356)
12
(305)
10
(254)
2 (51) MANTEL
TOP OF
APPLIANCE
6
(152)
NOTE - Hood shown as positioned in louvered
front model. The hood position in the flush
faced front model is lower than shown.
8
(203)
MANTEL CLEARANCES
Inches (mm)
MINIMUM CLEARANCES TO COMBUSTIBLES
Appliance And Vent Clearances
The appliance is approved with zero clearance to combustible materials
on all sides (as detailed in Table 5), with the following exception: When
the unit is installed with one side flush with a wall, the wall on the
other side of the unit must not extend beyond the front edge of the
unit. In addition, when the unit is recessed, the side walls surrounding
the unit must not extend beyond the front edge of the unit (see Figure 3).
MINIMUM CLEARANCES* Inches (millimeters)
Back1/2 (13)
Sides1/2 (13)
Top of Fireplace
Floor0 (0)
From Bottom of Unit To Ceiling64 (1626)
Vent3 (76) Top* / 1 (25.4) Sides & Bottom
SERVICE CLEARANCES Feet (meters)
Front3 feet (0.9 meters)
Table 5
*NOTE: 3" (75 mm) above any horizontal/inclined vent component.
**NOTE: See Page 10, Step 1 for clearance requirements to the nailing
flange located at each side of the unit and any screw heads adjacent to it.
Do not insulate the
space between the
appliance and the area
above it.
Shelf Height
(see table)
Shelf Height Minimum Clearances
Combustible Shelf Height - inches (millimeters)
®
®
Secure Flex
Do not insulate the
space between the appliance and the area
above it.
Shelf Above Fireplace With Top Venting
Secure VentSecure Flex
Shelf Height
(see table)
Inches (millimeters)
Hearth Extension - A hearth extension is not required with this appliance.
If a hearth extension is used, do not block the lower control compartment
door. Any hearth extension used is for appearance only and does not
have to conform to standard hearth extension installation requirements.
Shelf Height - To provide for the lowest possible shelf surface, use the
alternate rear vent outlet, the venting attached to the top vent should be
routed in a way to minimize obstructions to the space above the appliance.
Do not insulate the space between the appliance and the area above
it (see Figure 8). The minimum height from the base of the appliance to
the underside of combustible materials used to construct a utility shelf in
this fashion is shown in Figure 8.
Wall Finishes / Surrounds / Mantels
NOTE: Combustible wall finish materials and/or surround materials must not
be allowed to encroach the area defined by the appliance front face (black
sheet metal). Never allow combustible materials to be positioned in front
of or overlapping the appliance face (see Figures 61 and 62 on Page 34).
Non-combustible materials, such as surrounds and other appliance trim,
may be installed on the appliance face with these exceptions: they must not
cover any portion of the removable glass panel or control compartment.
Vertical installation clearances to combustible mantels vary according
to the depth of the mantel. See Figure 9. Mantels constructed of noncombustible materials may be installed at any height above the appliance
opening; however, do not allow anything to hang below the fireplace hood.
Minimum clearance requirements include any projections such as shelves,
window sills, mantels, etc. above the appliance.
NOTE: We recommend the use of high temperature paint (rated 175° F
or higher) on the underside of the mantel.
8
Figure 9 - Minimum Mantel Clearances
At 6" minimum
side wall clearance,
a combustible wall
can project to any
length.
6
(152)
Figure 10 - Minimum Distance to Side Wall
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Top View of
Fireplace
o
45
3-1/2
Combustible Materials
Allowed In Shaded Area
(89)
“Safe Zone”
Combustible Walls
shown in dark gray
Combustible materials may
project beyond either side
of the fireplace opening
as long as they are kept
within the shaded area
illustrated here.
Inches (millimeters)
Page 9
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
PRE-INSTALLATION STEPS
The appliance is shipped with all gas controls
and components installed and pre-wired.
Before installing the appliance, follow these
steps:
1. Remove the shipping carton.
2. Remove the shipping pad, exposing the front
glass door.
3. Open the two spring latches securing the
glass door (under the firebox floor). Remove
the door by tilting it outward at the bottom
and lifting it up. Set the door aside, taking
care to protect it from inadvertent damage.
See Removing The Glass Enclosure Panel
on Page 32.
5. Remove the log set from the firebox. Handle
logs carefully to prevent breakage.
6. Remove the embers and volcanic stone from
the control compartment.
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation is outlined
below; however, each installation is unique and
may result in variations to the steps described.
See the pages referenced in the following steps
for detailed procedures.
Step 1. FRAMING (Page 10): Construct the
appliance framing. Position the appliance within
the framing and secure with nailing brackets.
IMPORTANT! Bend up the appropriate header
spacing standoffs for the drywall/finish
material thickness to be used (see Figure 11).
Bend up the outer pair for 1/2" materials and
the inner pair for 5/8" materials.
Bend out the appropriate nailing flanges for
the drywall/finish material to be used. Nailing
flanges are provided for flush framing, 1/2" and
5/8" framing depths (see Figure 11).
Step 2. ROUTING GAS LINE (Page 12): Route
gas supply line to appliance location.
Step 3. PREPARING APPLIANCE VENT
COLLAR
(MPD35/40/45 models with combined top/rear
vent) (Page 13).
Step 4. INSTALLING VENT SYSTEM (Page 13):
Install the vent system and exterior termination.
Step 5. FIELD WIRING (Page 25).
a. Millivolt Appliances - Install the operating
control switch (not factory provided). If
installing the optional forced air circulating
blower, bring in electrical service line.
b. Electronic Appliances - Field wire and
install operating control switch.
Frame the appliance as illustrated in Figures
12 and 13 on Pages 11 and 12 (Figure 13
applies to corner framing installations only).
All framing details must allow for a minimum
clearance to combustible framing members as
shown in Table 5 on Page 8.
If the appliance is to be elevated above floor level,
a solid continuous platform must be constructed
below the appliance.
Headers may be in direct contact with the
appliance top standoff spacers when they are bent up vertically, maintaining the 3" clearance
to the fireplace top, but must not be supported by them or notched to fit around them. All
construction above the appliance must be
self-supporting. DO NOT use the appliance
for structural support.
Secure the fireplace to the side framing members
using the unit’s nailing flanges - one top and
bottom on each side of the fireplace front. See
Figure 11. Use 8d nails or their equivalent.
Bend up the appropriate header spacing top
standoffs before installing the fireplace.
Header Spacing Top Standoffs
(two pairs on front edge of firebox top)
Lift up outer pair for
1/2” finish materials
Side
Framing
NOTE: The nailing flanges, combustible members,
and screw heads in areas directly adjacent to
the nailing flanges are EXEMPT from the 1/2"
clearance to combustible requirements for the
firebox outer wrapper.
Combustible framing may be in direct contact with
the nailing flanges and may be located closer than
1/2" from screw heads and the firebox wrapper in
areas adjacent to the nailing flanges.
Frame the opening to the exact dimensions
specified in the framing details in this manual.
Figure 11 - Unit Secured to Framing by
Nailing Flange
IMPORTANT!
Lift up inner pair for
5/8” finish materials
Unit Nailing Flange
(No clearance to
combustible framing
is required)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
9
Page 10
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
Framing
ModelABCDE
MPDT33
MPDR33
MPD35
MPD40
MPD45
Diagrams, illustrations and photographs are not to scale. Consult installation
instructions. Product designs, materials, dimensions, specifications, colors,
and prices are subject to change or discontinuance without notice.
Fireplace
Model
MPDT3362456449
MPDR3361536455
MPD3562536055
MPD4067596760
MPD4567596759
33-1/433-1/4---37-3/412-7/8
845845---959327
in.33-1/433-1/419-5/8---12-7/8
mm845845498---327
in.35-1/435-1/4 21-11/16 39-3/416
mm8958955511010406
in.40-1/440-1/4 26-11/16 44-3/416
mm102210226781137406
in.45-1/440-1/4 26-11/16 44-3/416
mm114910226781137406
Notes
Thermal Efficiency (%)
Natural GasPropane
AFUE EnerGuide
(P4)
AFUE EnerGuide
(P4)
Based on CSA P.4.1-09
VENT FRAMING:
TOP VENT WITH ONE
90° ELBOW
VENT FRAMING:
REAR VENT WITH
NO ELBOWS
B
1/2
10-1/2
(
)
267
7
(178)
5-1/8
(130)
7
(178)
5-1/8
D
(130)
C
E
A
A
Dimension “E” is the required framing depth when the
finish material (drywall) thickness is 1/2 in. (13mm).
Framing should be
constructed of 2x4
or larger lumber.
12-1/8
(308)
12-1/8
(308)
Inches (mm)
Vertical Venting through the Ceiling
Frame ceiling opening: Use a plumb line from the ceiling above the appliance to locate center of the vertical run. Cut and/or frame an opening,
10-1/2" x 10-1/2" (267 mm x 267 mm) inside dimensions, about this center mark (see Figure 20).
Top View
Rear/Side
Framing
Spacers
Header
Spacing
Top
Standoffs
Notes:
[1] MPD models have a top and rear vent. MPDR models
have a rear vent only. MPDT models have a top vent only.
[2] Collars protrude one inch on MPDT33 and MPDR33 models.
G
H
Concentric Flue:
4-1/2” (114 mm);
Flue
Combustion Air
7-1/2” (190 mm).
See Notes [1] and [2].
J
Front View
E
A
D
3 (76)
Gas Inlet (either
side and bottom)
Optional Electrical Inlet
Knockout requiring a
C
B
Field-Provided Junction
Box (either side)
1-3/8 (35)
K
6 (152)
Right Side View
N
L
1/2 (13)
See Note [2].
1-5/8 (42)
M
F (rear vent
models only)
Electrical Inlet
2-3/4" x 2"
(70 x 51 mm)
Cover Plate
with Knockout
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
FIREPLACE FRAMING SPECIFICATIONS
Framing
ModelABCDEF
MPDT33
MPDR33
MPD35
MPD40
MPD45
NOTE:
• Rear Vent Applications in Corner Installations: The horizontal vent length
(from a to b) must not exceed 28 inches (711 mm).
• MPDT33 and MPDR33 Models: Dimensions A through F occur when one
45-degree elbow is connected directly to the appliance collar.
• MPD35, MPD40, and MPD45 Models: Dimensions D through F occur when
one 45-degree elbow is connected directly to the appliance collar.
in. 33-1/8 48-1/2 34-5/16 17-3/1624-1/45
mm8411232872437616127
in. 35-1/8 57-1/240-5/8 19-3/1628-3/46-1/8
mm89214611032487730156
in. 40-1/8 61-3/16 43-11/32 19-3/16 30-11/16 7-7/8
mm 101915541101487779200
in. 45-1/8 66-3/8 46-15/16 19-3/16 33-3/169-3/4
mm 114616861192487843248
Figure 13 - Corner Framing with Horizontal Termination
Step 2. ROUTING GAS LINE
Route a 1/2" (13 mm) gas line to the left side
of the appliance as shown in Figure 14. Gas
lines must be routed, constructed and made
of materials that are in strict accordance with
local codes and regulations. All appliances
are factory-equipped with a flexible gas line
connector and 1/2" shutoff valve. (See Step 7 on Page 26).
Never use galvanized or plastic pipe. Refer to
Table 6 for proper sizing of the gas supply
line, if black iron pipe is being used. Gas lines
must be routed, constructed and made of
materials that are in strict accordance with
local codes and regulations. We recommend
that a qualified individual such as a plumber
or gas fitter be hired to correctly size and route
the gas supply line to the appliance. Installing
a gas supply line from the fuel supply to the
appliance involves numerous considerations
Left Side Front
Corner of Fireplace
Framing
Pipe Coupling
(Recommended)
of materials, protection, sizing, locations,
controls, pressure, sediment, and more.
Certainly no one unfamiliar and unqualified
should attempt sizing or installing gas piping.
Schedule 40 Pipe
Length (feet)
0-101/2"3/8"
10-401/2"1/2"
40-1001/2"1/2"
100-1503/4"1/2"
150-2003/4"1/2"
3"
(76 mm)
Also see Figure 12.
Figure 14 - Route Gas Line
6-1/2"
(152 mm)
Table 6 - Schedule 40 Black Iron Pipe Inside Diameter
Proper Sizing of Gas Line
Properly size and route the gas supply line
from the supply regulator to the area where the
appliance is to be installed per requirements
outlined in the National Fuel Gas Code, NFPA
54 - latest edition (USA) or CAN/CGA-B149.1
- latest edition (Canada).
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
MPD and MPDR units
MPD and MPDT units
C
Back wall of chase/enclosure (including any finishing materials)
Natural
Gas
Propane
Gas
b
F
7"
(178 mm)
E
D
a
A
B
Notes:
• All appliances are factory-equipped with
a flexible gas line connector and 1/2 inch
shutoff valve (see Figure 47 on Page 27).
• See Massachusetts Requirements on Page
4 for additional requirements for installations
in the state of Massachusetts in the USA.
• The gas supply line should Not be connected
to the appliance until Step 7 (Page 26).
• A pipe joint compound rated for gas should be
used on the threaded joints. Ensure propane
resistant compounds are used in propane
applications. Be very careful that the pipe
compound does not get inside the pipe.
• It is recommended to install a sediment trap
in the supply line as close as possible to the
appliance.
• Check with local building ofcial for local
code requirements.
IMPORTANT: If propane is used, be aware that
if tank size is too small (i.e. under 100 lbs, if
this is the only gas appliance in the dwelling.
Ref. NPFA 58), there may be loss of pressure,
resulting in insufficient fuel delivery (which
can result in sooting, severe delayed ignition
or other malfunctions). Any damage resulting
from an improper installation, such as this,
is not covered under the limited warranty.
11
Page 12
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
A vent restrictor may be needed when
TOP VENT SEAL AND COVER PLATE REMOVAL
REAR VENT SEAL AND COVER PLATE REMOVAL
Step 3. PREPARING APPLIANCE VENT
COLLAR (MPD35/-40/-45 models with
combined top/rear vent)
Each of the unit’s two vent collars are sealed
with a cover plate and a seal plate and gasket.
The cover, and seal plate and gasket must be
removed from the vent collar being used. Refer
to Figure 15 for top vent usage and Figure 16
for rear, and the following steps to prepare the
appropriate collar for use.
From the vent collar being used, remove the four
screws securing the vent seal plate and gasket.
Remove and discard the seal plate and gasket.
When the top vent collar is being used, from
inside the firebox, loosen the two screws in the
keyhole slots of the cover plate and remove the
remaining two cover plate securing screws.
Remove and discard the cover plate. Reinstall
and securely tighten all four screws.
When the rear vent collar is being used, from
inside the firebox, remove the two screws
securing the lintel to the rear wall of the firebox,
then remove the lintel. Remove the four cover
plate securing screws. Remove and discard
the cover plate.
Reinstall and securely tighten all four cover
plate screws. Re-secure the lintel to the rear
wall of the firebox.
WARNING
Failure to reinstall and securely
tighten cover plate screws could
result in leakage of flue products
into the living space. Vent cover
plate and vent seal cap must
remain securely installed on
unused vent collar. Failure to
do so could result in leakage of
flue products into living space.
Installation of Vent Restrictor
A vent restrictor may be needed with this
appliance, install vent restrictor (provided)
in the appliance top flue outlet as shown in
Figure 17 (MPDT33, MPD35, MPD40 and
MPD45) or rear flue outlet as shown in Figure 18 (MPD35, MPD40 and MPD45). It is held in
place by friction, only.
NOTE: The vent restrictor is included in the
rebox.
12
WHEN USING THE TOP VENT
(OUTSIDE UNIT)
CABINET TOP
FIREBOX TOP
VENT
COVER PLATE
(INSIDE UNIT)
CROSS SECTION
GASKET
TOP VENT
KNOCKOUT
COVER PLATE
SECURING SCREWS
Figure 15 - Top vent seal and cover plate
removal - MPD35/40/45 series models
(combined top and rear vent units)
WHEN USING THE REAR VENT
COVER PLATE
SECURING SCREWS
(INSIDE UNIT)
REAR VENT
CROSS SECTION
CAP AND
GASKET
CABINET BACK
(OUTSIDE UNIT)
KNOCKOUT
Figure 16 - Rear vent seal and cover plate
removal - MPD35/40/45 series models
(combined top and rear vent units)
A vent restrictor may be needed when vertically
terminating the vent system above the roof
(when using the appliance top vent),install vent
restrictor in the top vent of the fireplace outlet
on MPD35/40/45 and MPDT33 series models.
If needed, install the restrictor orientated as
shown, either from inside or outside the unit,
in the inner fireplace collar.
With the appliance secured in framing, determine
vent routing and identify the exterior termination
location. The following sections describe
vertical (roof) and horizontal (exterior wall)
vent applications. Refer to the section relating
to your installation. A list of approved venting
components are shown on Pages 36 and 37.
Use only approved vent components (see
Approved Vent Components on Page 2).
These fireplaces must be vented directly
to the outside.
The vent system may not service multiple
appliances, and must never be connected to
a flue serving a separate solid fuel burning
appliance. The vent pipe is tested to be run
inside an enclosed wall (such as a chase). There
is no requirement for inspection openings in the
enclosing wall at any of the joints in the vent pipe.
Step 4. INSTALLING VENT SYSTEM
These instructions should be used as a
guideline and do not supersede local codes
in any way. Install venting according to local
codes, these instructions, the current National
Fuel Gas Code (ANSI-Z223.1) in the USA or
the current standards of CAN/CGA-B149.1
in Canada.
Ensure clearances are in accordance with
local installation codes and the requirements
of the gas supplier.
Dégagement conforme aux codes d'installation locaux et aux exigences du foumisseunde
gaz.
Page 13
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
lanimoN
38
T
32
Hs
04
04
04
38
T
32
Hs
0010
VERTICAL TERMINATION SYSTEMS (ROOF)
See Figure 19 and Figures 27 through 29
)sehcni(
on Page 17 and their associated Vertical
Vent Tables, which illustrate the various vertical
venting configurations that are possible for
use with these appliances. Secure Vent
applications are shown in these Figures; Secure
®
pipe may also be used. A Vertical Vent
Flex
®
pipe
Table summarizes each system’s minimum and
maximum vertical and horizontal length values
that can be used to design and install the vent
components in a variety of applications.
Both these vertical vent systems terminate
through the roof. The minimum vent height
above the roof and/or adjacent walls is specified
in ANSI Z223.1 (In Canada, the current CAN/
CGA-B149.1 installation code) by major building
codes. Always consult your local codes for
specific requirements. A general guide to follow
is the Gas Vent Rule (refer to Figure 5 on Page 6).
Vertical (Straight) Installation
(Figure 19)
Determine the number of straight vent sections
required. 4-1/2" (114 mm), 10-1/2" (267 mm),
22-1/2" (572 mm), 34-1/2" (876 mm) and 46
1/2" (1181 mm) net section lengths are available
(see Tables on this page and Pages 36 and 37 - Vent Sections). Plan the vent lengths so
that a joint does not occur at the intersection of
ceiling or roof joists. Refer to the Vent Section
Length Chart.
SV4.5CGV-1
Termination
Max. 40 ft
(12.2 m)
SV4.5FA or
SV4.5FB Flashing
AND SV4.5SC
Storm Collar
1 in (25.4 mm)
Minimum
Clearance to
Combustibles
SV4.5VF
Firestop/Spacer*
*When using Secure Flex,
use Firestop/Spacer
SF4.5VF.
SV4.5L6/12/24/36/48
Vent Sections
sehcnitf
5.4573.0100001
957.0200002
5.01578.0010001
5152.1110002
5.91526.12100
1257.1020002
5.22578.1001001
5.52521.2120003
5.13526.2030003
5.43578.2000101
5.73521.3111003
5.34526.3021003
5457.3002002
5.64578.3000011
5.94521.4102003
1552.4100012
5.55526.4012003
7557.4001102
6652.5022004
5.76526.5003003
9657.5000202
2761030
5.37521.6100203
5.97526.6010203
1857.6000112
095.7021014
5.19526.7002013
3957.7000022
6981012
5.79521.8100023
2015.8200024
5.301526.8000303
80191003
4115.9020024
71157.9105006
5.811578.9110305
6215.01001304
5.031578.01101305
53152.11006006
8315.11000404
5.931526.11000033
5.241578.11100405
Table 7: Vent Section Length
NOTE: Convert inches into metric equivalent
measurement, as follows:
Millimeters (mm) = Inches x 25.4
Centimeters (cm) = Inches x 2.54
Meters (M) = Inches x .0254
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
Vertical (Offset) Installation
Analyze the vent routing and determine the
quantities of vent sections and number of
elbows required. Refer to Vertical Vent Figures and Tables on Page 17 to select the type of
vertical installation desired. Vent sections are
available in net lengths of 4-1/2" (114 mm),
10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2"
(876 mm) and 46 1/2" (1181 mm). Refer to the
Vent Section Length Chart on Page 14 for an
aid in selecting length combinations. Elbows are
available in 90° and 45° configurations. Refer
to Figure 23 for the SV4.5E45 and SV4.5E90
elbow dimensional specifications.
Where required, a telescopic vent section (SV4.5LA) may be used to provide the installer
with an option in installing in tight and confined
spaces or where the vent run made up of fixed
length pieces develops a joint in a undesirable
location, or will not build up to the required
length. The SV4.5LA Telescopic Vent Section
has an effective length of from 1 1/2" (38 mm)
to 7 1/2" (191 mm). The SV4.5LA is fitted with
a locking inclined channel end (identical to a
normal vent section component) and a plain end
with 3 pilot holes. Slip the plain end over the
locking channel end of a standard SV4.5 vent
component the required distance and secure
with three screws.
Maintain a minimum 1" (25 mm) clearance to
combustible materials for all vertical elements.
Clearances for all horizontal elements are 3"
(76 mm) on top, 1" (25 mm) on sides and 1"
(25 mm) on the bottom.
A. Frame ceiling opening - Use a plumb line
from the ceiling above the appliance to locate
center of the vertical run. Cut and/or frame
an opening, 10-1/2" x 10-1/2" (267 mm x 267
mm) inside dimensions, about this center mark
(Figure 20).
B. Attach vent components to appliance
- Secure Vent
®
SV4.5 direct vent system
components are unitized concentric pipe
components featuring positive twist lock
connections (see Figure 19). All of the
appliances covered in this document are fitted
with collars having locking inclined channels.
Min. 10-1/2"
(267 mm)
Roof
Framing
Ceiling
Framing
Min. 10-1/2"
(267 mm)
Plumb
Bob
Figure 20
The dimpled end of the vent components fit over
the appliance collar to create the positive twist
lock connection.To attach a vent component to
the appliance collar, align the dimpled end over
the collar, adjusting the radial alignment until
the four locking dimples are aligned with the
inlet of the four inclined channels on the collar
(refer to Figure 21). Push the vent component
against the collar until it fully engages, then twist
the component clockwise, running the dimples
down and along the incline channels until they
seat at the end of the channels. The unitized
design of the Secure Vent
®
components will
engage and seal both the inner and outer pipe
without the need for sealant or screws. If desired
a #6 x 1/2" screw may be used at the joint, but
it is not required as the pipe will securely lock
when twisted.
NOTE: An elbow may also be attached to the
appliance collar. Attach in the same manner as
you would a vent section.
C. Attach vent components to each other
- Other vent sections may be added to the
previously installed section in accordance with
the requirements of the vertical vent figures
and tables. To add another vent component
to a length of vent run, align the dimpled end
over the inclined channel end of the previously
installed section, adjusting the radial alignment
until the four locking dimples are aligned with
the inlets of the four incline channels of the
previous section.
Push the vent component against the previous
section until it fully engages, then twist the
component clockwise running the dimples down
and along the incline channels until they seat at
the end of the channels.This seating position
is indicated by the alignment of the arrow and
dimple as shown in Figure 21.
D. Install firestop/spacer at ceiling - When
using Secure Vent, use SV4.5VF firestop/spacer
at ceiling joists; when using Secure Flex
®
, use
SF4.5VF firestop/spacer. If there is living space
above the ceiling level, the firestop/spacer must
be installed on the bottom side of the ceiling.
If attic space is above the ceiling, the firestop/
spacer must be installed on the top side of
the joist. Route the vent sections through the
framed opening and secure the firestop/spacer
with 8d nails or other appropriate fasteners at
each corner.
Remember to maintain 1" (25 mm) clearance
to combustibles, framing members, and attic
or ceiling insulation when running vertical
chimney sections. Attic insulation shield
(96K94) may be used to obtain the required
clearances indicated here. See installation
accessories table on Pages 36 and 37. The gap
between the vent pipe and a vertical firestop
can be sealed with non-combustible caulking.
E. Support the vertical vent run sections -
NOTE: Proper venting support is very important.
Support the vertical portion of the venting
system every 8 feet (2.4m) above the fireplace
vent outlet. One method of support is by utilizing
field provided support straps (conventional
plumber's tape). Secure the plumber's tape
to the framing members with nails or screws.
Loop the tape around the vent, securing the
ends of the tape to the framing. If desired,
sheet metal screws #6 x 1/2" length may be
used to secure the support straps to the vent
pipe. See Figure 22.
Align the dimple (four places) of
the upper vent section with the
opening of the locking incline
channel on the lower vent section
or appliance collar. Twist vent
component clockwise to engage
and seal until arrow and dimple
Arrow
Appliance Collar or
Vent Section
align.
Dimple
Locking Incline
Channel
Connected Vent
Sections
Arrow
Figure 21
Blocking
Support Straps
(Plumber's tape)
8 feet (2.4 m)
Maximum
1/2 inch (12.7
mm) minimum
clearance to
combustibles
Figure 22
14
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 15
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
SV4.5E90
(90
°
Elbow)
8-1/8"
(206 mm)
Swivel Joint
(360
°
swivel)
4-13/16"
(122 mm)
SV4.5E45
(45
°
Elbow)
Swivel Joint
(360
°
swivel)
C
D
Storm
Collar
F. Change vent direction to horizontal/inclined
run - At transition from or to a horizontal/
inclined run, install the SV4.5E45 and SV4.5E90
elbows in the same manner as the straight vent
sections. The elbows feature a twist section to
allow them to be routed about the center axis
of their initial collar section to align with the
required direction of the next vent run element.
Twist elbow sections in a clockwise direction
only so as to avoid the possiblity of unlocking
any of the previously connected vent sections.
See Figure 23.
Figure 23
G. Continue installation of horizontal/inclined
sections - Continue with the installation of the
straight vent sections in horizontal/inclined run
as described in Step C. Install support straps
every 5 ft (1.52 m) along horizontal/inclined
vent runs using conventional plumber’s tape.
It is very important that the horizontal/inclined
run be maintained in a straight (no dips),
slightly elevated plane. The recommended
incline is approximately 1/4" per foot (20 mm
per meter) horizontal, in a direction away from
the fireplace. The rise per foot run ratios that
are smaller are acceptable all the way down
to at or near level. Use a carpenter’s level to
measure from a constant surface and adjust
the support straps as necessary.
It is important to maintain the required
clearances to combustibles: 1" (25 mm) at all
sides for all vertical runs; and 3" (76 mm) at
the top, 1" (25 mm) at sides, and 1" (25 mm)
at the bottom for all horizontal/inclined runs.
H. Frame roof opening - Identify location for
vent at the roof. Cut and/or frame opening per
Roof Framing Chart and Figure 24.
Framing Dimensions for Roof
PitchCD
0/12
6/12
12/12
10-1/2"
(267 mm)
10-1/2"
(267 mm)
10-1/2"
(267 mm)
10-1/2"
(267 mm)
12"
(305 mm)
17-3/4"
(451 mm)
Figure 24
I.Install the roof flashing - Extend the vent
sections through the roof structure. Install the
roof flashing over the vent section and position such that the vent column rises vertically
(use carpenters level) (Figure 25 ). Nail along
perimeter to secure flashing or adjust roofing to
overlap the flashing edges at top and sides only
and trim where necessary. Seal the top and both
sides of the flashing with waterproof caulking.
J. Install the storm collar - Install the storm
collar, supplied with the flashing, over the vent/
flashing joint. See Figure 25. Loosen the storm
collar screw. Slide collar down until it meets
the top of the flashing. Tighten the adjusting
screw. Apply non-combustible caulking or
mastic around the circumference of the joint
to provide a water tight seal.
K. Install the vertical termination - The final
step involves installation of the SV4.5CGV-1
Vertical Termination. Extend the vent sections
to the height as shown in the "Vertical vent
termination section" on Page 6. The SV4.5CGV-1
Vertical Termination (Figure 26) installs in the
exact same fashion as any other Secure Vent®
section. Align the termination over the end of
the previously installed section, adjusting the
radial alignment until the four locking dimples
of the termination are aligned with the inlets of
the four incline channels of the last vent section.
Push the termination down until it fully engages,
then twist the termination clockwise running the
dimples down and along the incline channels
until they seat at the end of the channels.
Figure 26
If the vent system extends more than 5' (1.5
m) above the roof flashing, stabilizers may be
necessary. Additional screws may be used at
section joints for added stability. Guide wires
may be attached to the joint for additional support on multiple joint configurations.
Figure 25
15
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 16
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
SF4.5VF.
VERTICAL VENT FIGURES/TABLES
NOTE:Secure Vent® (rigid vent pipe) is shown
in the figures; Secure Flex® (flexible vent pipe)
may also be used.
NOTE: It is very important that the horizontal/
inclined run be maintained in a straight (no
dips), slightly elevated plane. The recommended
incline is approximately 1/4" per foot (20 mm
per meter) horizontal, in a direction away from
the fireplace. The rise per foot run ratios that
are smaller are acceptable all the way down to
at or near level.
NOTE: SV4.5VF (Secure Vent), SF4.5VF (Secure
®
) firestop/spacer must be used anytime
Flex
vent pipe passes through a combustible floor
or ceiling. SV4.5HF (Secure Vent), SF4.5HF
(Secure Flex®)firestop/spacer must be used
anytime vent pipe passes through a combustible
wall.
NOTE: Two 45 degree elbows may be used in
place of one 90 degree elbow. The same rise
to run ratios, as shown in the venting figures
for 90 elbows, must be followed if 45 degree
elbows are used.
NOTE: An elbow is acceptable as 1 foot of
vertical rise, except where an elbow is the
only vertical component in the system. (See
Figure 36 on Page 21).
Ceiling
Firestop/
Spacer
SV4.5VF*
Max. 40 ft
(12.2 m)
*When using
Secure Flex, use
Ceiling Firestop/
Spacer SF4.5VF.
TABLE A
H MaximumV Minimum
(meters)
feetfeet
(meters)
2(0.610)1(0.305)
4(1.219)2(0.610)
6(1.829)3(0.914)
V
8(2.438)4(1.219)
V + H = 40 feet (12.2 meters) Max.
H = 8 feet (2.4 meters) Max.
Ratio V to H ratio is 1:2
This table shows a 1 (V) to 2 (H) ratio.
For every 1 foot of (V) vertical, you are
allowed 2 feet of (H) horizontal run, up
to a maximum horizontal run of 8 feet.
Example: If 8 feet of (H) horizontal vent
run is needed, then 4 feet minimum (V)
vertical vent will be required.
Figure 28 - Rear Vent - ONE 90-DEGREE ELBOW
H
Ceiling
Firestop/Spacer
SV4.5VF*
Wall
Firestop/Spacer
V1
*When using Secure Flex, use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
SV4.5HF**
V
Figure 29 - Top Vent - TWO 90-DEGREE ELBOWS
Ceiling
Firestop/Spacer
SV4.5VF*
*When using Secure Flex, use
Ceiling Firestop/Spacer
H
NOTE: Install the U-shaped vent restrictor in
any vent run with more than 8 ft of vertical rise
(See Page 13).
TABLE B
H Maximum
feet
(meters)
(1.524)
5
(1.524)
5
(3.048)
10
(4.572)
15
(6.096)
20
V + V1+ H = 40 feet (12.2 m) Max.
H = 20 feet (6.096 meters) Max.
V Minimum
feet
Elbow Only
1
2
3
4
(meters)
(0.305)
(0.610)
(0.914)
(1.219)
Example: If 20 feet of (H) horizontal vent
run is needed, then 4 feet minimum of
(V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio.
For every 1 foot of (V) vertical, you are
allowed 5 feet of (H) horizontal run, up
to a maximum horizontal run of 20 feet.
An elbow is acceptable as 1 foot of vertical
rise except where an elbow is the only
vertical component in the system. See
Figure 36.
NOTE: Install the U-shaped vent
restrictor in any vent run with more
than 8 ft of vertical rise (See Page 13).
A Vent Restrictor, as shown in Figure 17 on
Page 13, must be used in this application.
Figure 27 - Top Vent - STRAIGHT
16
WARNING
Under no circumstances, may separate sections of concentric flexible vent
pipe be joined together.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 17
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
VERTICAL VENT FIGURES/TABLES
(continued)
TABLE C
+H
MaximumH MaximumV Minimum
H
1
2
4
6
8
(meters)
(0.610)
(1.219)
(1.829)
(2.438)
(meters)
feetfeetfeet
(1.524)
5
(3.048)
10
(4.572)
15
(6.096)
20
V + V1+ H + H1 = 40 feet (12.2 m) Max
H = 8 feet (2.438 meters) Max.
H + H1= 20 feet (6.096 meters) Max.
1
2
3
4
(meters)
(0.305)
(0.610)
(0.914)
(1.219)
Example: If 20 feet of (H) horizontal vent run is needed,
then 4 feet minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of
(V) vertical, you are allowed 5 feet of (H) horizontal run, up
to a maximum horizontal run of 20 feet.
NOTE: Install the U-shaped vent restrictor in any vent run
with more than 8 ft of vertical rise (See Page 13).
Figure 30 - Rear Vent - THREE ELBOWS
V1
H1
Ceiling
Firestop/Spacer
SV4.5VF*
Wall
Firestop/Spacer
SV4.5HF**
V
*When using Secure Flex, use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
Ceiling
Firestop/Spacer
SV4.5VF*
H
TABLE D
H
Maximum
H +
1
feetfeet
5
5
10
15
20
(meters)(meters)
(1.524)Elbow Only
(1.524)
(3.048)
(4.572)
(6.096)
H + H1 = 20 feet (6.096 m) Max.
+ H + H1 = 40 ft. (12.192 m) Max.
V + V
1
V Minimum
1
2
3
4
(0.305)
(0.610)
(0.914)
(1.219)
Example: If 20 feet of (H) horizontal vent run is needed, then 4 feet
minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V) vertical,
you are allowed 5 feet of (H) horizontal run, up to a maximum
horizontal run of 20 feet.
An elbow is acceptable as 1 foot of vertical rise except where an
elbow is the only vertical component in the system. See Figure 36.
NOTE: Install the U-shaped vent restrictor in any vent run with more
than 8 ft of vertical rise (See Page 13).
Ceiling
V
1
Firestop/Spacer
SV4.5VF*
Wall
Firestop/Spacer
SV4.5HF**
H
H
1
V
*When using Secure Flex, use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
Figure 31: Top Vent - THREE ELBOWS
17
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 18
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
TYPICAL HORIZONTAL VENT INSTALLATION
HORIZONTAL (OUTSIDE WALL) TERMINATION
SYSTEM
Figure 32, and Figures 35 to 41 on Pages
21 to 23 and their associated Horizontal
Vent Table illustrate the various horizontal
venting configurations that are possible for
use with these appliances. Secure Vent
applications are shown in these figures; Secure
®
Flex
pipe may also be used. A Horizontal Vent
Table summarizes each system’s minimum and
maximum vertical and horizontal length values
that can be used to design and install the vent
components in a variety of applications. Both of
these horizontal vent systems terminate through
an outside wall. Building Codes limit or prohibit
terminating in specific areas. Refer to Figure 7
on Page 7 for location guidelines.
Secure Vent SV4.5 direct vent system compon-
ents are unitized concentric pipe components
featuring positive twist lock connection, (refer to Figure 21 on Page 15). All of the appliances
covered in this document are fitted with collars
having locking inclined channels. The dimpled
end of the vent components fit over the appliance
collar to create the positive twist lock connection.
A.Plan the vent run - Analyze the vent routing
and determine the types and quantities of sections
required 4-1/2" (114 mm), 10-1/2" (267 mm),
22-1/2" (572 mm), 34-1/2" (876 mm) and 46-1/2".
(1181 mm) net section lengths are available. It is
recommended that you plan the venting so that a
joint does not occur in the ceiling or roof joists. Allow
for elbows as indicated in Figure 23 on Page 16.
Maintain a minimum 1" (25 mm) clearance to
combustibles on the vertical sections. Clearances
for the horizontal runs are; 3" (76 mm) on top, 1"
(25 mm) on sides, and 1" (25 mm) at the bottom.
B. Frame exterior wall opening - Locate the
center of the vent outlet on the exterior wall
according to the dimensions shown in Figure 12 on Page 11. Cut and/or frame an opening,
10-1/2" x 12-1/8" (267 mm x 308 mm) inside
dimensions, about this center.
C.Frame ceiling opening - If the vertical route
is to penetrate a ceiling, use plumb line to locate
the center above the appliance. Cut and/or frame
an opening, 10-1/2" x 10-1/2" (267 mm x 267
mm) inside dimensions, about this center (refer
to Figure 20 on Page 15).
D. Attach vent components to appliance - To
attach a vent component to the appliance collar,
align the dimpled end over the collar, adjusting the
radial alignment until the four locking dimples are
aligned with the inlets of the four incline channels
on the collar (refer to Figure 21on Page 15).
18
®
pipe
Building
Support
Framing
SV4.5E90
ertical
V
Rise
Support
Brackets
Elbow
Ceiling
Firestop/Spacer
Horizontal / Inclined Run
See Figure 24 on Page 15 for
vertical vent section support.
Fireplace
Figure 32 - Typical Horizontal Vent Installation
Push the vent component against the collar
until it fully engages, then twist the component
clockwise, running the dimples down and along
the incline channels until they seat at the end of
the channels. The unitized design of the Secure Vent components will engage and seal both the
inner and outer pipe elements with the same
procedure. Sealant and securing screws are
not required.
NOTE: An elbow may also be attached to the
appliance collar. Attach in the same manner as
you would a vent section.
E. Attach vent components to each other
- Other vent sections may be added to the
previously installed section in accordance with
the requirements of the vent tables. To add
another vent component to a length of vent run,
align the dimpled end of the component over the
inclined channel end of the previously installed
section, adjusting the radial alignment until the
four locking dimples are aligned with the inlets of
the four incline channels of the previous section.
Push the vent component against the previous
section until it fully engages, then twist the
component clockwise running the dimples down
and along the incline channels until they seat at
the end of the channels.This seating position
is indicated by the alignment of the arrow and
dimple as shown in Figure 21 on Page 15.
F. Install firestop/spacer at ceiling - When
using Secure Vent, use SV4.5VF firestop/spacer
at ceiling joists; when using Secure Flex
®
, use
SF4.5VF firestop/spacer. If there is living space
above the ceiling level, the firestop/ spacer must
be installed on the bottom side of the ceiling.
If attic space is above the ceiling, the firestop/
spacer must be installed on the top side of
the joist. Route the vent sections through the
framed opening and secure the firestop/spacer
with 8d nails or other appropriate fasteners at
each corner.
Remember to maintain 1" (25 mm) clearance
to combustibles, framing members, and attic
or ceiling insulation when running vertical
chimney sections.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
SV4.5HT-2
Termination
SV4.5L6/12/24/36/48
Vent Sections
Support bracket spacing
every 5 ft (1.52 m)
Exterior
Wall
SV4.5HT-2
Termination
Exterior
Wall
G.Support the vertical run sections - On the
vertical run, support the venting system every
8 feet (2.4m) above the fireplace vent outlet
with field provided support straps (Plumber's
tape). Attach the straps to the vent pipe and
secure to the framing members with nails or
screws. See Figure 22 on Page 15.
H. Change vent direction - At transition from or
to a horizontal/inclined run, install the SV4.5E45
and SV4.5E90 elbows in the same manner as
the straight vent sections. The elbows feature a
twist section to allow them to be routed about
the center axis of their initial collar section to
align with the required direction of the next
vent run element. Twist elbow sections in a
clockwise direction only so as to avoid the
possiblity of unlocking any of the previously
connected vent sections. See Figure 23 on
Page 16.
I. Continue installation of horizontal/inclined
sections - Continue with the installation of the
straight vent sections in horizontal/inclined run
as described in Step E. Install support straps
every 5 ft. (1.52 m) along horizontal/inclined
vent runs using conventional plumber’s tape.
See Figure 32, It is very important that the
horizontal/inclined run be maintained in a
straight (no dips), slightly elevated plane.
The recommended incline is approximately
1/4" per foot (20 mm per meter) horizontal,
in a direction away from the fireplace. The
rise per foot run ratios that are smaller are
acceptable all the way down to at or near level.
Use a carpenter’s level to measure from a
constant surface and adjust the support straps
as necessary.
It is important to maintain the required
clearances to combustibles: 1" (25 mm) at all
sides for all vertical runs; and 3" (76 mm) at
the top, 1" (25 mm) at sides, and 1" (25 mm)
at the bottom for all horizontal/inclined runs.
Page 19
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
SV4.5HT-2
Termination
10-1/2”
(267mm)
7”
(178)
5-1/8”
(130 mm)
12-1/8”
(308 mm)
NOTE: Centerline of Vent Piping is NOT
the Same as the Centerline of the
Framed Opening.
6 to 48” Vent Section,
Telescopic vent section,
Elbow or Appliance Collar
Base of Appliance
3”
(76 mm)
1”
(25.4 mm)
Adaptor
SV4.5RCH
Siding
Stucco
1-1/4" Maximum Recess of
the Square Termination into
Exterior Finishing Material
Exterior Surface of
Framing
6” to 9-1/4”
(152 to 235 mm)**
Exterior Surface of Siding
Interior Surface of
Finished Wall
Maximum wall thickness
10” (254 mm)**
SV4.5HT-2
Square Termination
Maximum Extent of
Vent Run Sections
Relative to Exterior
Surface of Framing
Last Vent Section. Use
Telescopic Vent
Section (SV4.5LA), If
Necessary
Adaptor
SV4.5RCH
SV4.5HT-2
Square Termination
*Use silicone caulking to seal
the top and sides of the
termination, up to the
underlayment, stucco, or
masonry wall surface.
**For thicknesses greater
than 10” seeTable 8.
*Caulk
*Caulk
J.Assemble vent run to exterior wall - If not
previously measured, locate the center of the
vent at the exterior wall. Prepare an opening as
described in Step B. Assemble the vent system
to point where the terminus of the last section is
within 7" (178 mm) to 11-1/4" (286 mm) inboard
of the exterior surface to which the SV4.5 HT
termination is to be attached, see Figure 34.
If the terminus of the last section is not within
this distance, use the telescopic vent section SV4.5LA, as the last vent section. For wall
thicknesses greater than that shown in Figure 34, refer to Table 9 on Page 21. This table lists
the additional venting components needed (in
addition to the termination and adaptor) for a
particular range of wall thicknesses.
K.Attach termination adaptor - Attach
the adaptor (SV4.5RCH, provided with the
termination) to the vent section or telescoping
vent section), elbow or appliance collar as shown
in Figure 33 in the same manner as any SV4.5
vent component (refer to Step E).
L. Install Firestop/Spacer at exterior wall
- When using the square termination, install
SV4.5HF (Secure Vent
®
Flex
) Firestop/Spacer over the opening at the
exterior side of the framing, long side up, with
the 3 inch spacer clearance at the top as shown
in Figure 33, and nail into place (the Firestop/
Spacer may also be installed over the opening
at the interior side of the framing).
M. Install the desired termination
1. Install the square termination (SV4.5HT-2
or SV4.5HTSS) - For the last step , from
outside the exterior wall, slide the collars of
the termination onto the adaptor (the outer
over the outer and the inner inside the inner)
until the termination seats against the exterior
wall surface to which it will be attached. Orient
the housing of the termination with the arrow
pointed upwards. Secure the termination to
the exterior wall. The horizontal termination
must not be recessed into the exterior wall
or siding by more than the 1-1/4" (32 mm) as
shown in Figure 34.
SVHRK Snorkel Cap - The snorkel cap is
designed to be fitted into a basement window
box. The SVHRK cap is for use with ex vent.
The vertical distance between the inlet and
outlet of the cap is 28" (711 mm).
IMPORTANT: The vent termination is hot
while in operation and for a period of
time following the use of the fireplace.
To prevent contact with hot surfaces,
we recommend the use of a Termination Guard. See Page 36. This can be
purchased at your local dealer.
®
), SF4.5HF (Secure
To help minimize water infiltration it is recommended that
the Firestop/Spacer (SV4.5HF)
be installed on the exterior
side of the wall.
See Figure 12 on Page 10 for Min.
Distance to Base of Appliance.
Figure 33 - Installing the Square Horizontal Termination (SV4.5HT-2)
** For thicknesses greater than
10" (254mm) see Table 9.
Figure 34 - Venting Connection and Exterior Wall Recessing of the Horizontal Square
Termination (SV4.5HT-2)
Horizontal terminations have been designed to perform in a wide range of weather
conditions. Our terminations meet or exceed industry standards.
When selecting the locations of your horizontal terminations, do not place the termination
where water from eaves and adjoining rooflines may create a heavy flow of cascading water
onto the termination cap. If the cap must be placed where the possibility of cascading water
exists, it is the responsibility of the builder to direct the water away from the termination
cap by using gutters or other means.
Take care to carefully follow the installation instructions for the termination, including the
use of silicone caulking where required.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
19
Page 20
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
HORIZONTAL VENT FIGURES/TABLES
NOTE:Secure Vent® components (rigid vent pipe and terminal) are
shown in the figures; Secure Flex® components (flexible vent pipe and
terminal) may also be used.
NOTE: Two 45 degree elbows may be used in place of one 90 degree
elbow. The same rise to run ratios, as shown in the venting figures for
90 elbows, must be followed if 45 degree elbows are used.
NOTE: It is very important that the horizontal/inclined run be maintained
in a straight (no dips), slightly elevated plane. The recommended
incline is approximately 1/4" per foot (20 mm per meter) horizontal,
in a direction away from the fireplace. The rise per foot run ratios that
are smaller are acceptable all the way down to at or near level.
®
NOTE: SV4.5VF (Secure Vent
), SF4.5VF (Secure Flex) firestop/spacer
must be used anytime vent pipe passes through a combustible floor or
ceiling. SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer
must be used anytime vent pipe passes through a combustible wall.
WARNING
Under no circumstances, may separate sections of
concentric flexible vent pipe be joined together.
Venting Components Required for Various Exterior Wall Thick-
nesses, when using Typical Termination Kits
Vent Components RequiredExterior Wall Thickness - in. (mm)
Termination Kit Only6 to 9-1/4 (152 to 235)
Termination Kit and 6" Vent
Section (SV4.5L6)
Termination Kit and 12"
Vent Section (SV4.5L12)
Termination Kit and
Telescopic Section
(SV4.5L12)
Table 9
10-3/4 to 14 (2733 to 356)
16-3/4 to 20 (426 to 508)
11-3/4 to 20 (299 to 508)
NOTE: See Figure 34 showing wall thickness range
when using SV4.5HT-2 termination kit.
TABLE F
H MaximumV Minimum
(meters)
feet
(0.914)
3
**When using SecureFlex, use Wall Firestop/
Spacer SF4.5HF.
Square termination (SV4.5HT-2) shown.
See Table 9 as an aid in venting component selection for a particular range of
exterior wall thicknesses.
feet
Elbow Only
(meters)
NOTE: Install the U-shaped vent
restrictor in any vent run with
more than 8 ft of vertical rise
(See Page 13).
H
V
Wall Firestop/
Spacer
SV4.5HF**
Figure 36 - Top Vent - ONE 90-DEGREE ELBOW -
ELBOW CONNECTION AT APPLIANCE
TABLE G
H Maximum
(meters)
feetfeet
(1.524)
5
V Minimum
(meters)
1(0.305)
10(3.048)2(0.610)
15(4.572)3(0.914)
20(6.096)4(1.219)
V + H = 40 feet (12.2 m) Max.
H = 20 ft. (6.096 m) Max.
H
Example: If 20 feet of (H)
horizontal vent run is needed, then
4 feet minimum of (V) vertical vent
will be required.
This table shows a 1 (V) to 5
(H) ratio. For every 1 foot of
(V) vertical, you are allowed 5
feet of (H) horizontal run, up
to a maximum horizontal run
of 20 feet.
H = 28 in. (711 mm) Maximum.
H
Wall Firestop/
Spacer
7 in
(178 mm)
Only the square termination (SV4.5HT-2) may be used.
See Table 9 as an aid in venting component selection for a particular
range of exterior wall thicknesses.
Figure 35 - Rear Vent - NO ELBOWS
20
SV4.5HF**
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
Wall Firestop/
Spacer SV4.5HF**
*When using Secure Flex, use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
Square termination (SV4.5HT-2) shown.
See Table 9 as an aid in venting component selection for a particular range of
exterior wall thicknesses.
NOTE: Install the U-shaped vent restrictor in any vent run with more
than 8 ft of vertical rise (See Page 13).
Figure 37 - Top Vent - ONE 90-DEGREE ELBOW -
ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
V
Ceiling
Firestop/
Spacer
SV4.5VF*
Page 21
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
HORIZONTAL VENT FIGURES/TABLES (continued)
H
H
1
Ceiling
Firestop/Spacer
SV4.5VF*
Wall Firestop/
Spacer
SV4.5HF**
V
*When using Secure Flex , use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
Square termination (SV4.5HT-2) shown.
TABLE H
MaximumH Maximum
+H
H
1
(meters)
feet
(1.524)
5
(3.048)
10
(4.572)
15
(6.096)
20
V + H + H1 = 40 feet (12.2 m) Max.
H = 8 feet (2.438 meters) Max.
H + H1= 20 feet (6.096 meters) Max.
(meters)
feet
2(0.610)1(0.305)
4(1.219)2(0.610)
6(1.829)3(0.914)
8(2.438)4(1.219)
V Minimum
(meters)
feet
Example: If 20 feet of (H) horizontal vent run is needed, then 4
feet minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V)
vertical, you are allowed 5 feet of (H) horizontal run, up to a
maximum horizontal run of 20 feet.
®
See Table 9 on Page 21 as an aid in venting component selection
for a particular range of exterior wall thicknesses.
NOTE: Install the U-shaped vent restrictor in any vent run with
more than 8 ft of vertical rise (See Page 13).
Figure 38 - Rear Vent - TWO 90-DEGREE ELBOWS
Wall Firestop/Spacer
SV4.5HF**
H
H
1
*When using Secure Flex, use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
Wall Firestop/Spacer
SV4.5HF**
Ceiling Firestop/Spacer
SV4.5VF*
Square termination (SV4.5HT-2) shown.
See Table 9 on Page 21 as an aid in venting component selection for a particular range
of exterior wall thicknesses.
NOTE: Install the U-shaped vent restrictor in any vent run with more than 8 ft of vertical
rise (See Page 13).
Figure 39 - Top Vent - TWO 90-DEGREE ELBOWS
TABLE J
+ H
H
Maximum
1
(meters)
feet
(0.914)Elbow Only
3
(1.524)
5
(3.048)
V
10
(4.572)
15
(6.096)
20
V +H+ H1 = 40 feet (12.2 m) Max.
+ H1 = 20 ft. (6.096 m) Max.
H
V Minimum
(meters)
feet
1(0.305)
2(0.610)
3(0.914)
4(1.219)
Example: If 20 feet of (H) horizontal vent run is
needed, then 4 feet minimum of (V) vertical vent
will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot
of (V) vertical, you are allowed 5 feet of (H) horizontal
run, up to a maximum horizontal run of 20 feet.
An elbow is acceptable as 1 foot of vertical rise except
where an elbow is the only vertical component in the
system. See Figure 36.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
21
Page 22
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
HORIZONTAL VENT FIGURES/TABLES (continued)
H
2
*When using Secure Flex , use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
®
Square termination
(SV4.5HT-2) shown.
See Table 9 on Page 21 as
an aid in venting component
selection for a particular range
of exterior wall thicknesses.
NOTE: Install the U-shaped vent
restrictor in any vent run with
more than 8 ft of vertical rise
(See Page 13).
Wall Firestop/Spacer
SV4.5HF**
H
1
Ceiling
Firestop/Spacer
SV4.5VF*
V
TABLE K
+ H1+ H
H
feetfeetfeet
Maximum
2
(meters)
H Maximum
(meters)
V Minimum
(meters)
5(1.524)2(0.610)1(0.305)
10(3.048)4(1.219)2(0.610)
15
(4.572)
6(1.829)3(0.914)
20(6.096)8(2.438)4(1.219)
V + H + H1+ H2 = 40 feet (12.2 m) Max.
H = 8 feet (2.438 meters) Max.
H + H1+ H2= 20 feet (6.096 meters) Max.
Example: If 20 feet of (H) horizontal vent run
is needed, then 4 feet minimum of (V) vertical
vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For
every 1 foot of (V) vertical, you are allowed 5
H
feet of (H) horizontal run, up to a maximum
horizontal run of 20 feet.
Figure 40 - Rear Vent - THREE 90-DEGREE ELBOWS
H
1
Wall Firestop/Spacer
SV4.5HF**
V
1
Square termination (SV4.5HT-2) shown.
See Table 9 on Page 21 as an aid in venting component selection for a particular range of
exterior wall thicknesses.
NOTE: Install the U-shaped vent restrictor in any vent run with more than 8 ft of vertical rise
(See Page 13).
Figure 41 - Top Vent - THREE 90-DEGREE ELBOWS
22
*When using Secure Flex, use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
Ceiling
Firestop/Spacer
SV4.5VF*
H
Wall Firestop/Spacer
SV4.5HF**
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
TABLE L
H Maximum
(meters)
feet
(1.524)
5
(1.524)
5
10
15
20
Example: If 20 feet of (H) horizontal vent
V
(3.048)
(4.572)
(6.096)
+ H1 = 20 feet (6.096 m) Max.
H
+ V+H+ H = 40 ft. (12.192 m) Max.
V
11
V Minimum
feet
Elbow Only
1
2
3
4
run is needed, then 4 feet minimum of (V)
vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio.
For every 1 foot of (V) vertical, you are
allowed 5 feet of (H) horizontal run, up to a
maximum horizontal run of 20 feet.
An elbow is acceptable as 1 foot of vertical
rise except where an elbow is the only
vertical component in the system. See
Figure 36.
(meters)
(0.305)
(0.610)
(0.914)
(1.219)
Page 23
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
5 in. (127 mm)
Radius Minimum
Flexible Vent Section
GEAR
CLAMPS
Adaptor
(SV4.5RF)
Apply ONLY MIL-PAC BLACK HIGH
TEMPERATURE SEALANT (Catalog No.
10K81) to the outside surface of both
collars of the adaptor (be especially
careful to fill the grooves of the outer
collar to be covered by the flexible
pipe) and slide flexible pipe over
inner and outer adaptor collars.
NOTE: OUTER PIPE IS PULLED AWAY TO
SHOW THE DETAIL OF THE INNER PIPE
FLEX VENT
1-3/4 in. (44 mm)
Flexible Pipe and
Adaptor Outer
Collar Overlap
1-3/4 in. (44 mm)
Flexible Pipe and
Adaptor Inner
Collar Overlap
SECURING SCREW
(3 PLACES EQUALLY SPACED
JUST BELOW GEAR CLAMP)
Attach Adaptor to Appliance
Collar, or Secure Vent Sections
SECURING SCREW
(3 PLACES EQUALLY SPACED
JUST BELOW GEAR CLAMP)
VERTICAL OR HORIZONTAL VENTING USING
SECURE FLEX
Secure Flex
be used in any venting application where rigid
Secure Vent
can be used. All restrictions, clearances and
allowances that pertain to the rigid piping apply
to the flexible venting. Secure Flex kits may not
be modified; also, under no circumstances
may separate sections of flex pipe be joined
together. Secure Flex kits may be added to the end of a vent run made up of rigid Secure
Vent (SV4.5) vent sections provided that
doing so does not violate any of the venting
length, height, routing, horizontal to vertical
ratio requirements or clearance considerations
detailed in this manual.
Secure Flex kits come with an included adaptor
that can be fitted to the appliance collar or the
inclined channel end of the last Secure Vent
(SV4.5) vent section in a rigid system in the
exact same fashion as any other Secure Vent
section. Align the dimpled end of the adaptor
over the previously installed section or appliance
collar, adjusting the radial alignment until the
four locking dimples of the adaptor are aligned
with the inlets of the four incline channels of the
last vent section or collar. Push on the adaptor
until it fully engages, then twist the adaptor
clockwise running the dimples down and along
the incline channels until they seat at the end
of the channels.
Attach the flexible vent to the adaptor as
follows (see Figure 42):
A. Install the Inner Flex Pipe
1. Install the small gear clamp loosely around
the inner flexible vent pipe, push it back out
of the way.
2. Apply a bead of Mill-Pac Black (700°F) high
temperature sealant - Catalog No. 10K81) to
the inner adaptor collar, approximately 1/2 inch
from the end.
3. Pull and extend the inner flexible vent pipe.
4. Slide the inner flex pipe over the adaptor
collar. Ensure the flexible vent pipe completely
engages the adaptor collar to a distance of 1
3/4 inches from the end, and that it is free from
damage or tears.
5. Slide the gear clamp down and tighten it
fully to secure the flexible vent to the adaptor
inner collar approximately 3/4 inch from the
end of the flex.
6. Install three screws 120 degrees apart
through the flexible vent pipe and into the
adaptor collar just below the gear clamp to
provide additional security to the connection.
B. Install the Outer Flex Pipe
1. Install the large gear clamp loosely around
the outer flexible vent pipe, push it back out
of the way.
®
venting kits and components may
®
(SV4.5) direct vent components
®
KITS AND COMPONENTS
Figure 42
2. Apply a bead of Mill-Pac Black (700°F) high
temperature sealant - Catalog No. 10K81) to
the outer adaptor collar; to the grooves of the
collar which extend approximately 1 inch from
the end and to the flat surface, approximately
1 3/8 inches from the end.
3. Pull and extend the outer flexible vent pipe.
4. Slide the outer flex pipe over the adaptor
collar. Ensure the flexible vent pipe completely
engages the adaptor collar to a distance of
1 3/4" from the end, and that it is free from
damage or tears.
5. Slide the gear clamp down and tighten it
fully to secure the flexible vent to the adaptor
outer collar approximately 3/4 inch from the
end of the flex.
6. Install three screws 120 degrees apart
through the flexible vent pipe and into the
adaptor collar just below the gear clamp to
provide additional security to the connection.
C. Route Flex Vent
Ensure that the flex vent is properly routed to
provide the required clearance. Do Not allow the
flexible vent to bend in a radius tighter than 5"
(127 mm). Refer to Figure 43. Place the internal
flex vent spacers evenly and avoid kinking the
inner pipe. Support horizontal sections of flex
vent with metal straps at 2 ft (0.61 m) intervals.
D. Install Firestop/Spacers at ceilings and walls
When Secure Flex penetrates a wall or ceiling,
a firestop/spacer is required: use the SF4.5 VF
firestop/spacer for ceilings and the SF4.5 HF
firestop/spacer for walls.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
See the appropriate sections and figures
shown throughout the venting section for
their installation requirments.
Figure 43
E. Attach Flex Vent to Termination
Secure Flex components can be purchased
separately and attached to bulk lengths of
Secure Flex flexible tubing cut to size at the
job site. Secure the flexible vent to the Secure
Flex terminations in the same manner (see
Figure 42) as it was attached to the adaptor.
NOTE: Secure Flex vent must be attached
to Secure Flex terminations only. DO NOT
substitute Secure Vent terminations or
the Secure Vent adaptor for Secure Flex
components. The collars of Secure Flex
terminations and adaptors have a different
circumference than what is used with the
Secure Vent pipe. Additionally, Secure Flex
components have an extended length center
tube for use in attaching the exible vent.
23
Page 24
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
JUNCTION BOX
Step 5. FIELD WIRING
CAUTION
The ground supply lead must be
connected to the wire attached
to the green ground screw
located on the outlet box (see wiring diagrams). Failure to
do so will result in a potential
safety hazard. The appliance
must be electrically grounded
in accordance with local codes
or, in the absence of local codes,
the National Electrical Code,
ANSI/NFPA 70-latest edition (in
Canada, the current CSA C22.1
Canadian Electrical Code).
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring
errors can cause improper and dangerous
operation.
ATTENTION: Au moment de l’entretien
des commandes, étiquetez tous les fils
avant de les débrancher. Des erreurs
de cáblage peuvent entraîner un fonctionnement inadéquat et dangereux.
Verify proper operation after servicing.
S’assurer que l’appareil fonctionne adéquatement une fois l'entretien terminé.
R
BATTERY HOLDER
AC/DC
POWER
ADAPTOR
Y
G
O
B
120V AC
HOT
NEUTRAL
GROUND
LIMIT SWITCH
B-VENT MODELS
ONLY
BL = BLUE
G = GREEN
O = ORANGE
W = WHITE
Y = YELLOW
SCHEMATIC REPRESENTATION ONLY
WIRING COLOR CODE
P/N 580491-01
B
W
G
OPTIONAL
REMOTE RECEIVER
ON/OFF SWITCH
WALL SWITCH
B = BLACK
BR = BROWN
GY = GRAY
PU = PURPLE
R = RED
Figure 45 - Wiring Diagram - Electronic Gas Valves
WALL MOUNTED CONFIGURATION FOR FAN SWITCH (OPTIONAL)
(OPTIONAL)
BK/W(1)
FAN
THERMOPILE
TP-TH
TP
TH
JUNCTION BOX
GAS VALVE
Figure 44 - Wiring Diagram - Millivolt
Gas Valves
ELECTRONIC PILOT ASSEMBLY
HOOD
PROFLAME VALVE
B
R
W
BL
PILOT TUBE
SPARK WIRE CABLE
PILOT GROUND WIRE
R
R
B
Y
Y
G
O
W
PROFLAME DFC BOARD
BL
B
G
B
OPTIONAL CPI SWITCH
OFF (O) = INTERMITTENT PILOT MODE
ON (-) = STANDING PILOT MODE
BLACK
BK
R
W
GR
IGNITER ROD
FLAME SENSOR
B
PILOT
SENSOR
CABLE
DFC WIRE HARNESS
Refer to Section A for millivolt appliances and
Section B for electronic appliances. The gas
valve is set in place and pre-wired at the factory
on both models.
A. Millivolt Wiring(see Figure 44)
Millivolt units are not provided with any
factory-installed controls; therefore, one of
the optional control switches is required to
operate the unit (ON/OFF Wall Switch, UnitMountable ON/OFF Switch*, Thermostat,
Remote Control). See the fireplace Care and Operation Instructions for details.
[*If using a Unit-Mountable ON/OFF Rocker Switch
with an optional Style View Door, mount the Rocker
Switch on the door instead of the unit.]
1. If installing an ON/OFF wall switch or
thermostat, mount it in a convenient
location on a wall near the fireplace.
2. Wire the control switch within the millivolt
control circuit using the 15 feet of 2
AC
120 V
conductor wire supplied with the unit.
NOTE: The supplied 15 feet of 2 conductor
wire has one end of each conductor
connected to the gas valve circuit and the
other end of each conductor placed loose
inside the bottom compartment.
CAUTION
In millivolt systems, do NOT connect
a Wall Switch to a 120V power supply.
B. Electronic Wiring(Figures 45 & 46)
One of the following optional controls also may
be used: ON/OFF Wall Switch, Thermostat,
Remote Control (see fireplace Care and Operation Instructions for details.).
NOTE: Electronic models must be connected
to the main power supply.
1. Route a 3-wire 120Vac 60Hz 1ph power
supply to the appliance junction box.
2. Remove the electrical inlet cover plate from
the side of the unit by removing the plate’s
securing screws (see Figure 12, Page 11).
3. Remove the cover plate knockout; then
feed the power supply wire through the
knockout opening and into the unit junction
box.
4. SeeFigures 45 & 46. Connect the black
power supply wire to the lower outlet’s
red pigtail lead.
Connect the white power supply wire to the
outlet’s common terminal.
5. Connect the ground supply wire to the
pigtail lead attached to the outlet’s green
ground screw.
24
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 25
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
BLOWER CONTROL CIRCUIT WIRING
NOTE: Remote receiver should be located in the
wall, or if installed in the control compartment,
pulled all the way forward and completely to the
left or right against the corner posts.
6. If wall-mounted ON/OFF control or
thermostat is to be used, mount it in a
convenient location on a wall near the
fireplace.
7. If an optional control is to be used, wire it in
the low voltage circuit as shown in Figure
45.
NOTE: The supplied 15 feet of 2 conductor wire
has one end of each conductor connected to
the gas valve circuit and the other end of each
conductor placed loose inside the bottom
compartment.
8. After the wiring is complete, replace the
cover plate.
WARNING
Electronic models of these appliances are equipped with a threeprong (grounding) plug utilized
in connecting the electronic
components to the junction box
in the lower compartment. This
grounding plug provides protection against shock hazard and
should be plugged directly into
the properly grounded threeprong receptacle. DO NOT cut
or remove the grounding prong
from the plug.
Step 6.WIRING - OPTIONAL FORCED AIR
BLOWER KIT
FBK-100 and FBK-200 Kits
(See Figure 46)
An electrical outlet box is provided for the
installation of the FBK-100, FBK-200 forced air
blower kits. Electrical power must be provided
to this box to operate these blowers. Install
the blower kits according to the installation
instructions provided with the kits.
120V, 60HZ, 1PH
neerG - dnuorG
etihW - lar
t
ueN
Black
White
Green
Plug blower
into this
receptacle
Blower
Ground
Figure 46 - Junction Box Wiring
FBK-250 Blower Kit
(See Figure 46)
An electrical outlet box is provided for the
installation of the FBK-250 forced air blower
kit. Electrical power must be provided to this
box to operate these blowers. Install the blower
kit according to the installation instructions
provided with the kit.
NOTE: The tab connecting the receptacles of
the outlet box must be broken in FBK-100 and
FBK-200 blower kit applications. See Figure 46.
* Wall-mounted
ON/ OFF Blower
Switch or Variable
Speed Control Switch.
120 VAC - Black
Junction Box
Tab Intact
Field Wired
Factory Wired
Tab
Broken
Red
Hot
Side of
Receptacle
Neutral
Side of
Receptacle
Green
Ground
Screw
Step 7. CONNECTING GAS LINE
Make gas line connections. All codes require a
shut-off valve mounted in the supply line. Figure 47 illustrates two methods for connecting the
gas supply. The flex-line method is acceptable
in the U.S., however, Canadian requirements
vary depending on locality. Installation must
be in compliance with local codes.
These appliances are equipped with a gas flex
line for use (where permitted) in connecting the
unit to the gas line. A gas flex line is provided to
aid in attaching the direct vent appliance to the
gas supply. The gas flex line can only be used
where local codes permit. Refer to Figure 47
for flex line description. The flex line is rated
for both natural and propane gas. A manual
shut off valve is also provided with the flex line.
The gas control valve is located in the lower
control compartment.
To access the valve open the lower control
compartment door (see Figure 48 ) by pushing
in the right top corner of the door. (The door
is hinged at the bottom.) Remove the bottom
compartment door by sliding the hinge pin,
located at the door’s left side, to the right until
it disengages from the left corner post hole.
Pull the door diagonally to the left, away from
the fireplace.
The millivolt control valve has a 3/8" (10 mm)
NPT thread inlet port. The electronic control
valve has a 1/2" (13 mm) NPT thread inlet
port and is fitted with a 1/2" x 3/8" (13 mm x
10 mm) NPT fitting.
Secure all joints tightly using appropriate
tools and sealing compounds (ensure propane
resistant compounds are used in propane
applications). Optional: Seal around the gas
line to prevent cold air leakage. Gas line holes
and other openings can be caulked or stuffed
with unfaced fiberglass insulation.
All codes require a shut-off valve mounted
in the supply line. The orientation of the
shut-off valve should face the front. Figure 47 illustrates two methods for connecting the
gas supply. A sediment Trap is recommended
to prevent moisture and debris in the gas line
for damaging the valve.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
25
Page 26
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
Gas
Stub
1/2" x 3/8" Flare
Shut-Off Valve
3/8" Flex Tubing
3/8" NPT x 3/8"
Flare Fitting
3/8" Nipple
3/8" Union
3/8" Close Nipple
3/8" Shut-Off Valve
1/2" x 3/8"
Reducer
Gas
Valve
Optional Gas Flex Line Connector
Thermocouple
HoodIgniter Rod
Thermopile
Pilot
Nozzels
3/8”
(9 mm)
Min
Figure 47 - Gas Connection
Millivolt Appliance Checkout
The pilot flame should be steady, not lifting
or floating. Flame should be blue in color with
traces of orange at the outer edge.
The top 3/8" (10 mm) at the pilot generator
(thermopile) and the top 1/8" minimum (tip)
of the quick drop out thermocouple should be
engulfed in the pilot flame.
The flame should project 1" (25 mm) beyond the
hood at all three ports (see Figure 49). Replace
logs if removed for pilot inspection.
To light the burner; turn “ON” the remote wall
switch and rotate the gas valve control knob
counterclockwise to the “ON” position (“ON”
will be at the top side of the valve).
TEST ALL CONNECTIONS FOR GAS LEAKS
(FACTORY AND FIELD)
Turn on gas supply and test for gas leaks, using a gas leak test solution (also referred to as
bubble leak solution).
NOTE: Using a soapy water solution is an effective leak test solution but it is not recommended,
because the soap residue that is left on the
pipes/fittings can result in corrosion over time.
A. Light the appliance (refer to the lighting
B. Brush all joints and connections with the gas
C. When the gas lines are tested and leak free,
26
Main Gas
Shut-Off Valve
Gas Valve
(Optional) Burner
ON/OFF Switch
Figure 48 - Millivolt Gas Valve - Lower Control Compartment
Step 8. VERIFYING APPLIANCE OPERATION
With gas line installed, run initial system
WARNING
Never use an open flame to
check for leaks.
instructions label in the control compartment
or in the Care and Operation Instructions
manual).
leak test solution to check for leaks. If bubbles
are formed, or gas odor is detected, turn the gas
control knob (off/pilot/on) to the “OFF” position
(millivolt units), or turn the receiver or remote
control to the “OFF” position (electronic units).
Either tighten or refasten the leaking connection,
then retest as described above.
be sure to rinse off the leak testing solution.
checkout before closing up the front of the
unit. Follow the pilot lighting instructions
provided in the Care and Operation Instruc-tions. For piezo igniter location on millivolt
appliances, see Figure 48.
NOTE: Lighting Instructions are also found on
the literature tag tied to the gas piping next
to the gas valve. To access the tag, open the
lower control compartment door (Figure 48)
by pushing in simultaneously the left and right
top corners of the door (the door is hinged at
the bottom). Remove the bottom compartment
door by sliding the hinge pin, located at the
door’s left side, to the right until it disengages
from the left corner post hole.
When first lighting the appliance, it will take
a few minutes for the line to purge itself of
air. Once purging is complete, the pilot and
burner will light and operate as indicated in
the instruction manual. Subsequent lighting
of the appliance will not require such purging.
Inspect the pilot flame (remove logs, if necessary, handling carefully)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Piezo
Door Latch
Figure 49 - Millivolt Pilot
Electronic Appliance Checkout
To light the burner, turn ‘ON’ the wall or remote
control switch. Ensure the igniter lights the pilot.
The pilot flame should engulf the flame rod as
shown in Figure 50.
Ignitor
Igniter
Pilot
Pilot Hood
Hood
Flame Rod
Sensor
(sensor)
Figure 50 - Electronic Pilot
Page 27
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
Glowing Embers
Step 9. INSTALL VOLCANIC STONE,
GLOWING EMBERS, AND LOGS
WARNING
• DO NOT attempt to install the
logs until the appliance installation has been completed, the
gas line connected and tested
for leaks and the initial burner
operation has been checked
out.
•
The size and position of the log
set was engineered to give the
appliance a safe, reliable and
attractive flame pattern. Any
attempt to use a different log
set in the fireplace will void
the warranty and will result in
incomplete combustion, sooting, and poor flame quality.
•
Logs get very hot and will
remain hot up to one hour after
gas supply is turned off. Handle
only when logs are cool. Turn
off all electricity to the appliance before you install grate,
volcanic stone, embers and
logs.
•
This appliance is not designed
to burn wood. Any attempt to
do so could cause irreparable
damage to the appliance and
prove hazardous to your safety.
•
If logs are not installed accord-
ing to the log installation
instructions, flame impingement and improper combustion could occur and result in
soot and/or excessive production of carbon monoxide (CO),
a colorless, odorless, toxic
gas.
Figure 52 - Glowing Ember Placement
NOTE: Turn off all electricity to the appliance
before you install volcanic stone, embers and
logs.
Step 1. Remove the appliance front door (see
Removing Glass Encloslure panel on Page 32.
Step 2. Install decorative volcanic stone -
Sprinkle the decorative volcanic stone in a pleasing pattern. The volcanic stone should be placed
directly on top of the firebox bottom, along the
front and to the back at the right and left sides of
the burner. Position any optional ceramic fiber
liners before placing the stone. Logs should be
positioned after the volcanic stone.
NOTE: This appliance is provided with enough
Glowing Embers for several applications, do
not feel compelled to use all that is in a new
bag. For best glowing effect, replace the ember material annually. Replacement Glowing
Embers are available (Catalog Number 88L53).
Glowing Embers
Separate into Quarter
Size (separate) Pieces
Bag of Glowing
Embers (rockwool)
Figure 51
Step 3. Separate the Glowing Ember (Rockwool)
into pieces about the size of a quarter (Figure
51). Keep the pieces uffed up, not matted.
Distribute these pieces over the front surface
of the burner, as shown in Figure 52. Do not
use more than is necessary. When properly
positioned, the Glowing Embers will cover
approximately 65% of the front burner and
with no appreciable gaps or openings. Ensure
that the main burner ports remain uncovered
by the ember material.
Step 4. Placement of Logs - All top logs that
rest on lower logs, do so over notches, indents
or nubs. Proper log placement is critical to
prevent sooting. Logs should be placed in the
gaps between the flame peaks and should be
positioned so they do not impinge the flames.
Step 5. Position the individual logs as shown in
Figures 53, 54, and 55. Logs should be placed
in the order shown. All logs that have notches
to fit over the grate tines should be positioned
with these notches directly against the grate.
Handle logs carefully to prevent breakage.
Proper log placement is critical to encourage
outstanding flame appearance and prevent
sooting. When positioned properly as shown,
logs will be positioned between flame peaks
and will not impinge any flames.
Refer to Figure 53 for MPD33 Series appliances, to Figure 54 for MPD35 Series appliances and to Figure 55 for MPD40 and MPD45
Series appliances.
REFERENCE
Firebox Accessories / Parts
Cat. No.Model No.Description
88L53FGEBag of Glowing Embers
80L42FDVS
Bag of Decorative
Volcanic Stone
27
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 28
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
MPD33 LOG PLACEMENT
Log
Number Description (Stamped #)
1
3
2
Position the individual logs as shown below. Logs should be placed
4
6
5
in the order shown. Position the rear log on the brackets at the rear
of the firebox with the log's notches directly over the brackets.
Position the right log (log no. 3) by inserting the pin from the rear
log into the hole on its upper end. Place the left log and then the
smaller left and right top logs. All logs that have notches to fit over
the grate tines should be positioned with these notches directly
against the grate. All top logs that rest on lower logs, do so over
flattened mounting faces in the bottom logs.
1 Log, Rear (39-12)
2 Log, Left (39-1)
3 Log, Right (39-2)
4 Log, Top Center (39-13)
5 Log, Top/Left (39-3)
6 Log, Top/Right (39-4)
Catalog Number for the entire log set: 24M15
Proper log and twig placement is critical to encourage outstanding
flame appearance and prevent sooting.
1
4
3
2
5
6
28
Figure 53
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 29
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
MPD35 LOG PLACEMENT
Log
1
3
2
Number Description (Stamped #)
1 Log, Rear (39-5)
2 Log, Left (39-1)
3 Log, Right (39-2)
4 Log, Top Center (39-6)
5 Log, Top/Left (39-3)
6 Log, Top/Right (39-4)
Catalog Number for the entire log set: H6197
4
5
6
Position the individual logs as shown below. Logs should be placed
in the order shown. Position the rear log on the brackets at the rear
of the firebox with the log's notches directly over the brackets.
Position the right log (log no. 3) by inserting the pin from the rear
log into the hole on its upper end. Place the left log and then the
smaller left and right top logs. All logs that have notches to fit over
the grate tines should be positioned with these notches directly
against the grate. All top logs that rest on lower logs, do so over
flattened mounting faces in the bottom logs.
Proper log and twig placement is critical to encourage outstanding
flame appearance and prevent sooting.
1
43
2
Figure 54
5
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
6
29
Page 30
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
MPD40 AND MPD45 LOG PLACEMENT
Log
1
2
3
Number Description (Stamped #)
1 Log, Center (39-8)
2 Log, Rear (138)
3 Log, Right (39-10)
4 Log, Left (39-9)
5 Log, Top/Left (39-11)
6 Log, Top/Right (39-11)
Catalog Number for the entire log set: 24M25
4
5
6
Position the individual logs as shown below. Logs should be placed
in the order shown. Position the center log on the burner first, then
place the glowing embers as shown in Figure 52. Place the rear
log, both the right and left, and then the smaller left and right top
logs. All logs that have notches to fit over the grate tines should
be positioned with these notches directly against the grate. All top
logs that rest on lower logs, do so over flattened mounting faces
in the bottom logs.
Proper log and twig placement is critical to encourage outstanding
flame appearance and prevent sooting.
1
4
3
2
30
Figure 55
5
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
6
Page 31
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
Step 10. REMOVING AND INSTALLING
THE GLASS DOOR
WARNING
• Do not attempt to substitute the
materials used on these doors,
or replace cracked or broken
glass.
• Handle this glass with extreme
care! Glass is susceptible to
damage - Do not scratch or
handle roughly while reinstalling the glass door frame.
• The glass door of this appliance must only be replaced
as a complete unit as provided
by the manufacturer. Do not
attempt to replace broken,
cracked or chipped glass separately.
• Do not attempt to touch the
front enclosure glass with your
hands while the fireplace is in
use.
WARNING
Do not operate appliance with
the glass front removed, cracked
or broken.
AVERTISSEMENT
Ne pas utiliser l'appareil si le
panneau frontal en verre n'est
pas en place, est craqué ou
brisé.
Only doors certified with the appliance
shall be used.
Removing the Glass Enclosure Panel
(see Figure 56)
Remove the top louver assembly or radiant
panel. To access the glass door securing latches,
first open the lower control compartment door
(Figure 56 ) by pushing in simultaneously the
left and right top corners of the door (the door
is hinged at the bottom).
Remove the bottom compartment door by
sliding the hinge pin, located at the door’s left
side, to the right until it disengages from the
left corner post hole. Pull the door diagonally
to the left, away from the fireplace.
Locate the two (2) latches at the top of the
control compartment and disengage them from
the door frame bottom vee-flange, pulling down
on their handles to open them.
Installing the Glass Enclosure Panel
(see Figure 56)
Retrieve the glass door. Visually inspect the
gasket on the backside of the frame. Gasket
surface must be clean, free of irregularities
and seated firmly.
Position the door in front of the firebox opening
with the bottom of the door held away from the
fireplace (Figure 56). Hook the top flange of the
door frame over the top of the firebox frame.
Let the bottom of the door frame swing gently
in towards the fireplace ensuring that the gasket
seats evenly as the door frame draws shut.
Fasten the two latches located underneath the
firebox floor to the door's vee-flange. Close
both the latches securely.
Lower Compartment Door and Hinge
Glass
Door
Glass Door Frame
Top Flange
Step 11. BURNER ADJUSTMENTS
Flame Appearance and Sooting
Proper flame appearance is a flame that is blue
at the base and becomes yellowish-orange in
the body of the flame.
When the appliance is first lit, the entire flame
may be blue and will gradually turn yellowishorange during the first 15 minutes of operation.
If the flame remains blue, or if the flame is
orange with evidence of sooting (black tip), the
air shutter opening may need to be adjusted.
If the air shutter opening is closed too far,
sooting may develop. Sooting is indicated by
black puffs developing at the tips of very long
orange flames. Sooting results in black deposits
forming on the logs, appliance inside surfaces
and on exterior surfaces adjacent to the vent
termination.
Sooting is caused by incomplete combustion
in the flames and lack of combustion air entering the air shutter opening. To achieve a warm
yellowish-orange flame with an orange body
that does not soot, the shutter opening must be
adjusted between these two extremes.
Air Shutter Adjustment Guidelines
• If there is smoke or soot present, rst check
the log set positioning to ensure that the
flames are not impinging on any of the logs.
If the log set is properly positioned and a
sooting condition still exists, then the air
shutter opening should be increased.
• The more offsets in the vent system, the larger
the air shutter opening will need to be.
• An appliance operated with the air shutter
opened too far, may have flames that appear
blue and transparent. These weak, blue and
transparent flames are termed anemic.
• Propane models may exhibit ames which
candle or appear stringy. If this is present
and persists, adjust the air shutter to a more
closed position, then operate the appliance
for a few more minutes to ensure that the
flame normalizes and the flames do not
appear sooty.
The following chart is provided to aid you in
achieving the correct air shutter adjustment
for your installation.
Seules des portes certifiées pour cet
appareil doivent être utilisées.
WARNING: DO NOT abuse glass door by
striking or slamming shut.
Glass Door Frame
Bottom Vee-flange
Glass Door Latch
Figure 56
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Firebox Floor
Air Shutter Adjustment Guidelines
Amount of
Primary Air
If air shutter is
closed too far
If air shutter is
open too far
Flame
Color
Flame will
be orange
Flame will
be blue
Air Shutter
Adjustment
Air shutter
gap should be
increased
Air shutter
gap should be
decreased
31
Page 32
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
WARNING
• Air shutter adjustment should
only be performed by a
qualified professional service
technician.
• Ensure front glass panel are
in place and sealed during
adjustment.
CAUTION
• Soot will be produced if the
air shutter is closed too much.
Any damage due to sooting,
resulting from improperly
setting the air shutter, is not
covered under the warranty.
• The air shutter door and
nearby appliance surfaces
are hot. Exercise caution to
avoid injury while adjusting
flame appearance.
1. Refer to Figures 57, 58, and 59 for proper
flame app earance. To adjust the flame, rotate
the adjustment rod toward the back or toward
the front of the fireplace (rod located in the
lower control area). Position the air shutter
to the factory setting as shown in the table
in Figure 60.
2. Light appliance (follow lighting procedure
on lighting label in control compartment or
in the Care and Operation Instructions).
3. Allow the burner to operate for at least 15
minutes while observing the flame continuously to ensure that the proper flame appearance has been achieved. If the following
conditions are present, adjust accordingly.
• If ame appears weak or sooty, adjust
the air shutter, incrementally, to a more
open position until the proper flame
appearance is achieved.
• If ame remains blue, adjust the air
shutter, incrementally, to a more closed
position until the proper flame appearance is achieved.
4. When satisfied that the burner flame appear-
ance is normal, reinstall the lower control
compartment door, then proceed to finish
the installation.
Figure 57 - MPD33 MODEL
Figure 58 - MPD35 MODEL
Figure 59 - MPD40 AND MPD45 MODEL
32
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 33
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
Burner Tube
Air Shutter
Adjustment Rod Down
(fully open position)
Models
MPD33
MPD35
MPD40
MPD45
Figure 60
Adjusting Set Screw
Adjustment Rod Up
(minimum air
opening position)
Gas
Type
Factory Air
Shutter Setting
inches (mm)
Nat.1/32 (0.8)
Prop.3/16 (4.76)
Nat.1/32 (0.8)
Prop.3/16 (4.76)
Nat.1/8 (3.2)
Prop.1/2 (13)
Nat.1/8 (3.2)
Prop.1/2 (13)
Step 12.HOOD INSTALLATION
Refer to Figures 61 and 62. All models must
have hoods installed prior to operating.
On all Radiant Panel units, slide the hood into
the slots on the lower edge of the radiant panel
(Figure 61).
On louvered face units, slide the hood into the slots
on the lower edge of the cabinet top (Figure 62).
FINISHING REQUIREMENTS
Wall Details
Complete finished interior wall. To install the
appliance facing flush with the finished wall,
position framework to accommodate the thickness of the finished wall (Figures 61 and 62)
See Page 5 for
Cold Climate Insulation and
Page 8 for Clearances.
Combustible
Finished Wall
Materials
Combustible
material may
touch top of
appliance.
Combustible
materials
NOT allowed
below this point
on face
of appliance.
Hood must be installed as shown.
This area must remain
clear of combustible
materials.
Header
Spacing
Top Standoff
Top of Appliance
Radiant panel
Top of Door Frame
Figure 61 - Radiant Panel Models
Combustible
Finished Wall
Materials
Combustible
material may
touch top of
appliance.
Combustible
materials
NOT allowed
below this point
on face
of appliance.
This area must remain
clear of combustible
materials.
Header
Spacing
Top Standoff
Top of Appliance
Louvers
Top of Door Frame
Min. 1 in.
(25 mm)
Min. 1 in.
(25 mm)
Hood must be installed as shown.
Figure 62 - Louver Face Models
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
33
Page 34
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
STEP 13. INSTALLER INSTRUCTIONS - ATTACHING SAFETY IN OPERATION WARNINGS
It is the installers responsibility to ensure these warnings are properly affixed during installation. These warning labels are a
critical step in informing consumers of safe operation of this appliance.
ATTACHING SAFETY IN OPERATION WARNINGS
It is required that the safety instruction labels
furnished with the fireplace be affixed to the operation and control point of the fireplace. A safety
instruction label must be affixed to the wall switch
plate where the fireplace is turned on and off (See
Figure A) or wall thermostat (See Figure B) and if
used on the remote control handheld transmitter
(Figure C). To properly complete the installation of
this fireplace, locate the multi-lingual adhesive labels
provided with the Care and Operation Instructions
and proceed as follows:
1. Locate the wall switch or wall thermostat that
controls the fireplace (verify the switch operates
the fireplace by turning it on and off). Clean the
wall switch plate or wall thermostat thoroughly
to remove any dust and oils. Affix the label to
the surface of the plate of the wall switch that
controls the fireplace (Figure A) or the wall
thermostat (Figure B). Choose the language
primarily spoken in the home. If unknown, affix
the English language label.
2. If a remote control is used to control the fireplace,
locate the transmitter and clean it thoroughly
to remove any dust and oils. Affix the label to
the surface of handheld transmitter (Figure C).
Choose the language primarily spoken in the
home. If unknown, affix the English language
label.
3. If you are unable to locate the labels, please call
Lennox Hearth Products or your nearest Lennox
Hearth Products dealer to receive additional
safety instruction labels free of charge.
Cat. No. H8024 Replacement Label Kit
LENNOX HEARTH PRODUCTS
1-800-655-2008
NOTE: English is red text on clear label. French
and Spanish are white text on black label.
APPOSITION DES MISES EN GARDE RELATIVES
À LA SÉCURITÉ D’UTILISATION
Il est impératif que les étiquettes de sécurité fournies
avec le foyer soient collées à côté des dispositifs
de contrôle du foyer. Une étiquette de sécurité doit
être collée sur la plaque de l’interrupteur contrôlant
l’allumage du foyer (voir Figure A) ou sur le thermostat
mural (voir Figure B) et, le cas échéant, sur le boîtier de
la télécommande (Figure C). Pour achever l’instal lation
correcte de ce foyer, procédez comme suit avec les
étiquettes adhésives en langues étrangères fournies
avec les instructions d’utilisation et d’entretien :
1. Repérez l’interrupteur ou le thermostat mural
qui contrôle le foyer (vérifiez que l’interrupteur
contrôle le fonctionnement du foyer en le faisant
basculer de Marche à Arrêt, et vice-versa). Nettoyez
soigneusement la plaque murale de l’interrupteur
ou le thermostat mural pour éliminer la poussière
et les traces de graisse ou d’huile. Collez l’étiquette
sur la surface de la plaque de l’interrupteur mural
qui contrôle le foyer (Figure A) ou du thermostat
mural (Figure B). Choisissez la langue qui est
principalement parlée dans la résidence du
propriétaire. En cas de doute, collez l’étiquette en
anglais.
2. Si une télécommande est utilisée pour contrôler le
foyer, nettoyez la soigneusement pour éliminer la
poussière et les traces de graisse ou d’huile. Collez
l’étiquette sur le boîtier de la télé commande (Figure C). Choisissez la langue qui est principalement parlée
dans la résidence du proprié taire. En cas de doute,
collez l’étiquette en anglais.
3. Si vous ne trouvez pas les étiquettes, veuillez
appeler Lennox Hearth Products ou votre distributeur Lennox Hearth Products local pour recevoir
gratuitement des étiquettes supplémentaires.
Étiquettes de remplacement, n° cat. H8024
LENNOX HEARTH PRODUCTS
1-800-655-2008
Remarque : Le texte anglais est rouge sur un support
transparent. Le texte français et espagnol est blanc
sur un support noir.
COLOCACIÓN DE ADVERTENCIAS DE SEGURIDAD
EN OPERACIÓN
Se requiere que las etiquetas de instrucciones de
seguridad incluidas con la chimenea se coloquen en
el punto de operación y control de la misma. Se debe
colocar una etiqueta de instrucciones de seguridad
en la placa del interruptor de pared desde el cual
se enciende y se apaga la chimenea (ver la Figura A) o en el termostato de pared (ver la Figura B) y
en el transmisor de control remoto (Figura C) si se
usa. Para completar correctamente la instalación de
esta chimenea, encuentre las etiquetas adhesivas
multilingües incluidas con las instrucciones de cuidado
y operación y haga lo siguiente:
1. Identifique el interruptor o el termostato de pared
que controla la chimenea (verifique que el interruptor
opera la chimenea encendiéndola y apagándola).
Limpie bien la placa del interruptor o el termostato de
pared para quitar el polvo y aceite. Pegue la etiqueta
en la superficie de la placa del interruptor que controla
la chimenea (Figura A) o en el termostato de pared
(Figura B). Seleccione el idioma que más se habla
en la casa. Si no sabe cuál es, use la etiqueta en
inglés.
2. Si se usa un control remoto para controlar la
chimenea, encuentre el transmisor y límpielo bien
para quitar el polvo y aceite. Pegue la etiqueta en
la superficie del transmisor (Figura C). Seleccione
el idioma que más se habla en la casa. Si no sabe
cuál es, use la etiqueta en inglés.
3. Si no puede encontrar las etiquetas, sírvase llamar a
Lennox Hearth Products o al distribuidor de Lennox
Hearth Products más cercano para recibir etiquetas
de instrucciones de seguridad adicionales gratuitas.
Juego de etiquetas de repuesto - Nº de cat. H8024
LENNOX HEARTH PRODUCTS
1-800-655-2008
Nota: La etiqueta en inglés es transparente con texto
rojo. Las etiquetas en francés y español son negras
con texto blanco.
34
SAFETY LABEL DIAGRAMSDIAGRAMAS DE ETIQUETAS DE
Illustrations are for example only.
Your accessories may be different.
Les illustrations sont par exemple
uniquement. Vos accessoires
peuvent être différents.
Las ilustraciones son sólo ejemplos.
Tu accesorios pueden ser diferentes.
Figure A
DIAGRAMMES DES ÉTIQUETTES
DE SÉCURITÉ
Figure B
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
SEGURIDAD
Figure C
Page 35
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
S
e
a
l
a
n
t
INSTALLATION ACCESSORIES
Listed Secure Vent® Components
Cat. No.ModelDescription
H1968SV4.5HT-2Horizontal Square Ter-
mination with Firestop/
Spacer (H2246) and
Adaptor (74L61)
H2152SV4.5CGV-1Vertical Termination Cap,
High Wind
94L10*SV4.5HTSSHorizontal Small Square
Termination with
Firestop/Spacer (96K80)
and Adaptor (74L61)
98L27*SV4.5HTSSL Horizontal Small Square
- Long Termination with
Firestop/Spacer (96K80)
and Adaptor (74L61)
17M52SV4.5HGS-1 Termination Guard,
Square (1 pack)
Instr. #750109M)
17M53SV4.5HGS-12 Termination Guard, Hori-
zontal Square (12 pack)
(Ref. Instr. #750109M)
87L02SV4.5HGSTermination Guard for
Horizontal Square Termination (Deluxe) (1 pack)
(Ref. Instr. #750055M)
(Ref.
Vent Sections
(Rigid)
Listed Secure Vent® Components
Cat. No.ModelDescription
77L70SV4.5L66 Inch (152 mm)
77L71SV4.5L1212 Inch (305 mm)
77L72SV4.5L2424 Inch (610 mm)
77L73SV4.5L3636 Inch (914 mm)
77L74SV4.5L4848 Inch (1219 mm)
77L75SV4.5LATelescopic Length Slip
Section (2" to 7-1/2" rigid)
77L76SV4.5E4545 Degree Elbow
77L77SV4.5E9090 Degree Elbow
10K81SFMPMill-Pac, Black, High-
Temperature Sealant
89L40SFMP-12Mill-Pac, Black, High-
Temperature Sealant,
Bulk 12 pack
99L02SV4.5HRK14 Horizontal Riser Kit, 14",
(Ref. Instr. #750146M)
99L03SV4.5HRK36 Horizontal Riser Kit, 36",
(Ref. Instr. #750146M)
96K93SV4.5SUSupport Strap
H5820SV4.5HTSKTermination Shroud
(Guard) for Horizontal
Square Termination
(1 pack)
(Ref. Instr.
#750246M)
H3907SV4.5ARSAAttic Insulation Shield with
adjustable height, 12"-22"
H1988CTSA-33Chase Top Shroud Kit,
Arch Top 3 X 3 Ft.,
Instr. #750194M)
(Ref.
H1985CTSO-33Chase Top Shroud Kit,
Open Top 3 X 3 Ft., (Ref.
Instr. #750193M)
H1987CTSO-44Chase Top Shroud Kit,
Open Top 4 X 4 Ft., (Ref.
Instr. #750193M)
H1986CTSO-46Chase Top Shroud Kit,
Open Top 4 X 6 Ft., (Ref.
Instr. #750193M)
H5816SV4.5-
TWSK10
Through Wall Shield Kit
(used to shield the
direct-vent pipe from
blown insulation)
(Ref. Instr. #750247M)
The following flashings come packaged with a storm collar:
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
INSTALLATION ACCESSORIES CONTINUED
Listed Secure Flex® Components
Cat. #ModelDescription
These termination kits include firestop/spacer, gear clamps and flex adaptor.
60L10SF-1818 feet (5.49 m) *
98K03SF-1212 feet (3.66 m)*
H2248SF4.5HF-10 Firestop / Spacer -
H2249SF4.5VF-10 Firestop/Spacer - Vertical,
56L74SFVT30Vertical Termination for ex
56L75SFVT45Vertical Termination for ex
91L66SFGC4-6Gear Clamp 4.5" (114 mm)
91L67SFGC7-6Gear Clamp 7.5" (190.5 mm)
H7748H774836" Flex Connector Kit. 36"
compressed ex
(Ref. Instr. #750053M)
compressed ex (Ref. Instr.
#750052M)
Horizontal, ex (3-1-1
spacing), 10 Pack
ex (1-1-1 spacing), 10 Pk
(flat to 6/12) with flex adaptor,
section of rigid vent, roof
support collar assembly, roof
flashing and storm collar.
(Ref. Instr. #750052M)
(6/12 to 12/12) with flex
adaptor, section of rigid
vent, roof support collar
assembly, roof flashing,
and storm collar.
#750052M)
(Ref. Instr.
for ex (6 pack)
for ex (6 pack)
of flex with two adaptors
for mating two rigid
sections of vent together.
Listed Secure Flex® Components
Cat. #ModelDescription
H1969SF4.5HT-2 Horizontal Square Termina-
77L87SFKIT12SSquare Term. for ex (with
77L88SFKIT18SSquare Term. for ex (with
77L89SFKIT24SSquare Term. for ex (with
77L90SFKIT36SSquare Term. for ex (with
77L91SFKIT48SSquare Term. for ex (with
94L04* SFKIT12SS Small Square Termination for
94L05* SFKIT18SS Small Square Termination for
94L06* SFKIT24SS Small Square Termination for
94L07* SFKIT36SS Small Square Termination for
94L08* SFKIT48SS Small Square Termination for
94L09*SF-HTSSHorizontal Small Square
tion for ex (without flex
vent)
12" [305 mm] compressed
flex vent**)
18" [457 mm] compressed
flex vent**)
24" [610 mm] compressed
flex vent**)
36" [914 mm] compressed
flex vent**)
48" [1219 mm] compressed
flex vent**)
ex, with 12" (305 mm) of
compressed flex vent**
(Ref. Instr. #750204M)
ex, with 18" (457 mm) of
compressed flex vent**
(Ref. Instr. #750204M)
ex, with 24" (610 mm) of
compressed flex vent**
(Ref. Instr. #750204M)
ex, with 36" (914 mm) of
compressed flex vent**
(Ref. Instr. #750204M)
ex, with 48" (1219 mm) of
compressed flex vent** (Ref.
Instr. #750204M)
Termination for ex, without
flex vent (Ref. Instr. #750204M)
36
*Only for use with MPDT33 and MPD35 models.
**All compressed flex vents can be expanded up to two times.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 37
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
GAS CONVERSION KITS
WARNING
This conversion kit shall be installed by a qualified service agency in
accordance with the manufacturer’s instructions and all applicable codes
and requirements of the authority having jurisdiction. If the information in
these instruction is not followed exactly, a fire, explosion or production of
carbon monoxide may result causing property damage, personal injury
or loss of life. The qualified service agency is responsible for the proper
installation of this kit. The installation is not proper and complete until the
operation of the converted appliance is checked as specified in the manufacturer’s instructions supplied with the kit.The qualified service agency
performing this installation assumes responsibility for this conversion.
AVERTISSEMENT
Cette trousse de conversion doit être installée par un technicien agréé,
selon les instructions du fabricant et selon toutes les exigences et tous les
codes pertinents de l’autorité compétente. Assurez-vous de bien suivre
les instructions dans cette notice pour réduire au minimum le risque
d’incendie, d’explosion ou la production de monoxyde de carbone pouvant
causer des dommages matériels, des blessures ou la mort. Le tecnicien
agréé est responsable de l’installation de cette trousse. L’installation n’est
pas adéquate ni complète tant que le bon fonctionnement de l’appareil
converti n’a pas été vérifié selon les instructions du fabricant fournies avec
la trousse. Le fournisseur de service qualifié ayant réalisé l'installation
assume les responsabilités liées à la conversion.
In Canada:
THE CONVERSION SHALL BE CARRIED OUT IN ACCORDANCE WITH THE
REQUIREMENTS OF THE PROVINCIAL
AUTHORITIES HAVING JURISDICTION
AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN/CGA-B149.1
INSTALLATION CODE.
LA CONVERSION DEVRA ÊTRE
EFFECTUÉE CONFORMÉMENT AUX
RECOMMANDATIONS DES AUTORITÉS PROVINCIALES AYANT JURIDICTION ET CONFORMÉMENT AUX EXIGENCES DU CODE D'INSTALLATION
CAN/CGA-B149.1.
Gas conversion kits are available to adapt your
appliance from the use of one type of gas to
the use of another. These kits contain all the
necessary components needed to complete the
task including labeling that must be affixed to
ensure safe operation.
Kit part numbers are listed here and the following steps detail the conversion procedure. Refer
to the instructions provided with the conversion
kit when performing any gas conversion.
Step 1. TURN OFF THE GAS SUPPLY TO THE
APPLIANCE and disconnect power supply at
the circuit breaker. Ensure appliance is cold.
CAUTION: THE GAS SUPPLY SHALL BE
SHUT OFF PRIOR TO DISCONNECTING THE
ELECTRICAL POWER, BEFORE PROCEEDING WITH THE CONVERSION.
ATTENTION: AVANT D’EFFECTUER
LA CONVERSION, COUPEZ D’ABORD
L’ALIMENTATION EN GAZ, ENSUITE,
COUPEZ L’ALIMENTATION ÉLECTRIQUE.
Step 2. Open the lower control compartment
door (see Figure 48 on Page 27) by pushing
on the right top corner of the door (the door is
hinged at the bottom).
[Optional] Remove the control compartment
door by sliding the hinge pin, located at the
door’s left side, to the right until it disengages
from the left corner post hole. Pull the control
compartment door diagonally to the left, away
from the fireplace.
Step 3. Remove the front glass door/frame
from the appliance (see Page 32).
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
37
Page 38
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
Pressure
Regulator
Remove
These
Components
Pilot
Orifice
Step 4. Carefully remove the logs. Exercise
care so as not to break the logs.
Step 5. Refer to Figure 53, 54, or 55.
A. Remove the grate and sub floor.
B. Remove the two (2) screws securing the
burner assembly.
C. Remove the burner assembly with attached
venturi tube.
Millivolt and Electronic Ignition System
Appliances
Step 6. SIT Systems - Refer to Figure 63
and the instructions provided with the SIT
Regulator Conversion Kit. Using a Torx T20
driver (with 1/4" shank and center hole) or
slotted screwdriver, remove and discard the
pressure regulator mounting screws (two
screws for electronic models, three screws
for millivolt models), pressure regulator tower,
the diaphragm assembly (if applicable) and
the spring. Discard all removed components.
Step 7. Install the new pressure regulator assembly using the supplied screws as shown
in Figure 63. Tighten the screws to 25 in-lb.
Millivolt Valve
Electronic Valve
Figure 63: Regulator Conversion
Step 8. Install the enclosed identification label
to the valve body where it can be easily seen.
Step 9. Refer to Figure 64. Remove the pilot
hood assembly to access the hexed pilot orifice.
Remove and replace the orifice with the one
provided with the kit. Exercise extreme care to
prevent damage to or breakage of the igniter
assembly.
Figure 64: Millivolt Pilot
(electronic pilot is similar)
Step 10. Remove the orifice from the manifold
and replace it with the one provided in the kit.
See Table 10 for orifice sizes for natural and
propane models. Figure 65 illustrates the orifice.
Burner Orifice Sizes
Elevation 0-4500 feet ( 0-1372 meters)
Model
Series
MPD33
MPD35
MPD40
MPD45
Table 10
Nat.Gas
drill size (inches)
#47 (0.0785")*
99K74 •
#44 (0.086")*
60J80 •
#38 (0.102") *
99K76 •
#37 (0.104")*
24M10 •
* Standard size installed at factory
• Part /Cat. Number
Propane
drill size (inches)
0.048"
99K78 •
#55 (0.052")*
19L52 •
0.062"
21L01 •
#52 (0.0635")*
37G00 •
Figure 65: Orice
Use pipe joint compound or Teflon tape on all
pipe fittings before installing (ensure propane
resistant compounds are used in propane applications, do not use pipe joint compounds
on flare fittings).
Step 11. Retrieve the burner and hold the
venturi tube above the orifice. Place the shutter
adjusting rod in the slot of the shutter arm (see
Figure 60 on Page 34). Set the burner assem-
bly into its position and secure the trapezoidal
plate with the two screws previously removed.
Step 12. Reinstall the baffle with the two baffle
securing screws.
Step 13. Reassemble the remaining components by reversing the procedures outlined in
the Steps 1-5.
Step 14. Attach the conversion label provided
in the conversion kit next to the rating plate on
the appliance.
Step 15. Turn on gas supply and test for gas
leaks (refer to Page 27).
Step 16. Relight the main burner. The lighting
instructions can be found on the lighting label
in the control compartment or in the Care and
Operation Manual provided with the appliance.
Verify proper burner ignition and operation. See
Burner Adjustments and Burner Flame Appearance on Page 33.
Step 17. Inspect the pilot system for proper
flame. The pilot flame should engulf the flame
sensor as shown in Figures 49 and 50 on
Page 27.
Step 18. Using a manometer, test the inlet and
manifold gas pressures. See Tables 2 and 3
on Page 4.
ALWAYS TEST PRESSURES WITH THE VALVE
REGULATOR CONTROL AT THE HIGHEST
SETTING.
38
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Lennox Hearth Products reserves the right to make changes at any time, without notice, in
design, materials, specifications, and prices, and also to discontinue colors, styles, and products.
Consult your local distributor for fireplace code information.
LENNOX®, the LENNOX design, DAVE LENNOX, the image of DAVE LENNOX and other related
LENNOX marks are registered or common law trademarks of Lennox Industries Inc. and are
used with permission.