éviter tout dommage matériel, toute blessure ou la mort.
WARNING /AVERTISSEMENT/AVISO
MPB B-Vent
Gas Fireplaces
MODELS
P/N 506015-05 Rev. D 04/2013
This manual is one of a set of two supporting this product.
Refer to P/N 506017-04 for Care and Operation Instructions.
Ce manuel est disponible en francais, simplement
en faire la demande. Numéro de la pièce 506223-45.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
INSTALLATEUR : Laissez cette notice avec l’appareil.
CONSOMMATEUR : Conservez cette notice pour
consultation ultérieure.
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
UNE SURFACE VITRÉE CHAUDE
PEUT CAUSER DES BRÛLURES.
LAISSER REFROIDIR LA SURFACE
VITRÉE AVANT D'Y TOUCHER.
NE PERMETTEZ JAMAIS À UN ENFANT
DE TOUCHER LA SURFACE VITRÉE.
Decorative Product: Not for use as a heating appliance.
NOTICE: Fireplace is not to be operated by a thermostat.
MPB33CNM
MPB33CPM
MPB35CNM
MILLIVOLT:
MPB35CPM
MPB40CNM
MPB45CNM
OTL Report No. 116-F-36d-5
EL VIDRIO CALIENTE
CAUSARÁ QUEMADURAS.
USTED DEBE NUNCA
TOCAR EL VIDRIO CALIENTE.
LOS NIÑOS DEBEN NUNCA
TOCAR EL VIDRIO.
ELECTRONIC:
MPB33CNE
MPB35CNE
MPB40CNE
MPB45CNE
WARNING: If the information in these instructions
is not followed exactly, a fire or explosion may
result, causing property damage, personal injury,
AVERTISSEMENT : Assurez-vous de bien suivre les
instructions données dans cette notice pour réduire au
minimum le risque d’incindie ou d’explosion ou pour
or death.
- Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the fire
department.
- Installation and service must be performed by a
qualified installer, service agency or the gas supplier.
- Ne pas entreposer ni utilizer d’essence ni d’autres vapeurs
ou liquides inflammables dans le voisinage de cet appareil
ou de tout autre appareil.
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucan interrupteur. Ne pas vous servir des
téléphones se trouvant dans le bâtiment où vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis
un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service des incindies.
- L’installation et l’entretien doivent être assurés par un
installateur ou un service d’entretien qualifié ou par le
fournisseur de gaz.
Please read and understand these
instructions before beginning your
installation.
2
PACKAGING
The assembled vented gas fireplace is packaged with:
• (1 set) Logs (packaged in a carton inside
the firebox).
• (1 bag) Volcanic Stone (included in the
firebox or bottom compartment).
• (1 bag) Glowing Embers (in bottom compartment).
• Literature Kit (envelope in bottom compartment containing Care and Operation
Instructions, Installation Instructions,
Safety-In-Operation Warning Labels, Warranty).
• (1) Hood (behind the top louver assembly).
INTRODUCTION
The Millivolt appliances have a millivolt gas
control valve with piezo ignition system. If any
optional accessories that will require electrical
power are to be installed, the electrical power
must be provided at the time of appliance installation.
The Electronic appliances are designed to operate on natural or propane gas. An electronic
intermittent pilot ignition system provides safe,
efficient operation. External electrical power is
required to operate these units. In the event of a
power outage, four (4) "AA" batteries (in battery
holder) provide backup power for appliance
operation (excluding [optional] blower).
APPROVED VENT COMPONENTS
These vented gas fireplaces are designed for
residential applications. They must be installed
with approved Type-B, double wall vent pipe
systems and a listed vent termination routed
to the outside atmosphere. Use only the proper
size listed below.
B-Vent appliances are not
designed to operate in negatively
pressured environments (pressure within the home is less than
pressures outside). Significant
negatively pressured environments caused by weather, home
design, or other devices may
impact the operation of these
appliances. Negative pressures may result in poor flame
appearance, sooting, damage to
property and/or severe personal
injury. Do not operate these
appliances in negatively pressured environments.
GENERAL INFORMATION
WARNING
Young children should be carefully supervised when they are
in the same room as the appliance. Toddlers, young children
and others may be susceptible
to accidental contact burns. A
physical barrier is recommended
if there are at risk individuals in
the house. To restrict access to
a fireplace or stove, install an
adjustable safety gate to keep
toddlers, young children and
other at risk individuals out of
the room and away from hot
surfaces.
AVERTISSEMENT
Les jeunes enfants devraient être
surveillés étroitement lorsqu’ils
se trouvent dans la même pièce
que l’appareil. Les tout petits,
les jeunes enfants ou les adultes
peuvent subir des brûlures s’ils
viennent en contact avec la surface chaude. Il est recommandé
d’installer une barrière physique
si des personnes à risques habitent la maison. Pour empêcher
l’accès à un foyer ou à un poêle,
installez une barrière de sécurité; cette mesure empêchera les
tout petits, les jeunes enfants et
toute autre personne à risque
d’avoir accès à la pièce et aux
surfaces chaudes.
Children and adults should be alerted to the
hazards of high surface temperature and
should stay away to avoid burns or clothing
ignition.
Les enfants et les adultes devraient être
informés des dangers que posent les
températures de surface élevées et se
tenir à distance afin d’éviter des brûlures
ou que leurs vêtements ne s’enflamment.
DO NOT ATTEMPT TO ALTER OR MODIFY
THE CONSTRUCTION OF THE APPLIANCE
OR ITS COMPONENTS. ANY MODIFICATION
OR ALTERATION MAY VOID THE WARRANTY,
CERTIFICATION AND LISTINGS OF THIS UNIT.
Improper installation, adjustment, alteration, service or
maintenance can cause injury
or property damage. Refer to
this manual. For assistance or
additional information consult
a qualified installer, service
agency or the gas supplier.
WARNING
Failure to comply with these installation instructions will result
in an improperly installed and
operating appliance, voiding its
warranty. Any change to this appliance and/or its operating controls
is dangerous.
WARNING
Clothing or other flammable
material should not be placed
on or near the appliance.
AVERTISSEMENT
On ne devrait pas placer de
vêtements ni d’autres matières
inflammables sur l’appareil ni à
proximité.
WARNING
Any safety screen or guard removed for servicing the appliance must be replaced prior to
operating the appliance.
AVERTISSEMENT
Tout écran ou protecteur retiré
pour permettre l’entretien de
l’appareil doit être remis en
place avant de mettre l’appareil
en marche.
WARNING
Improper installation or use of
this appliance can cause serious
injury or death from fire, burns,
explosion or carbon monoxide
poisoning.
WARNING
Failure to position the parts in
accordance with these diagrams
or failure to use only parts
specifically approved with this
appliance may result in property
damage or personal injury.
AVERTISSEMENT
Risque de dommages ou de
blessures si les pièces ne sont
pas installées conformément à
ces schémas et ou si des pièces
autres que celles spécifiquement
approuvées avec cet appareil sont
utilisées.
Installation and repair should be done by
a qualified service person. The appliance
should be inspected before use and at least
annually by a professional service person.
More frequent cleaning may be required due
to excessive lint from carpeting, bedding
material, etcetera. It is imperative that control
compartments, burners and circulating air
passageways of the appliance be kept clean.
L’installation et la réparation devrait
être confiées à un technicien qualifié.
L’appareil devrait faire l’objet d’une
inspection par un technicien professionnel
avant d’être utilisé et au moins une fois
l’an par la suite. Des nettoyages plus
fréquents peuvent être nécessaires si les
tapis, la literie, et cetera produisent une
quantité importante de pous-sière. Il est
essentiel que les compartiments abritant
les commandes, les brûleurs et les
conduits de circulation d’air de l’appareil
soient tenus propres.
Do not use this appliance if any part has
been under water. Immediately call a
qualified service technician to inspect the
appliance and to replace any part of the
control system and any gas control which
has been under water.
Ne pas utiliser cet appareil s’il a été
plongé, même partiellement, dans
l’eau. Appeler un technicien qualifié
pour inspecter l’appareil et remplacer
toute partie du système de commande
et toute commande qui a été plongée
dans l’eau.
Only trim kit(s) supplied by the manufacturer
shall be used in the installation of this
appliance.
Seules les trousses de garniture fournies
par le fabricant doivent être utilisées pour
l’installation de cet appareil.
These appliances comply with National
Safety Standards and are tested and listed
by OMNI-Test Laboratories, Inc. (Report No.
116-F-36d-5) to ANSI Z21.50b-2009 (in Canada,
CSA 2.22b-2009), and CAN/CGA-2.17-M91
(R2009) in both USA and Canada, as vented
gas fireplaces.
Both millivolt and electronic versions of these
appliances may be used in bedrooms only
when the room is an "unconfined space" as
defined by the National Fuel Gas Code. Use
in bedrooms may not be allowed by your local
building codes. You should obtain prior approval from the Authority having jurisdiction
prior to installation.
MISC. CODES / STANDARDS
The Installation must conform to local codes or, in
the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 / NFPA 54 - latest edition
(In Canada, the current CAN/CGA-B149.1 installation
code).The appliance, when installed, must be
electrically grounded and wired in accordance with
local codes or, in the absence of local codes, with
the National Electrical Code, ANSI/NFPA 70 - latest
edition, or the Canadian Electrical Code, CSA C22.1
- latest edition.
Provide adequate clearances around air
openings and adequate accessibility clearance for
service and proper operation. Never obstruct the
front or back openings of the appliance.
These appliances are designed to operate on
natural or propane gas only. The use of other
fuels or combination of fuels will degrade
the performance of this system and may be
dangerous.
These fireplaces are designed as decorative
appliances and are not intended for use as
area heaters. They must not be equipped
with wall thermostats or remote controls with
thermostat functions.
OUTSIDE COMBUSTION AIR HOOK UP
These appliances are equipped with an
integral combustion air door and actuator arm.
Combustion air kits are optional. Install as shown
in Step 7 on Page 13.
These appliances must not be connected to a
chimney or flue serving a separate solid fuel
burning appliance.
Both millivolt and electronic systems can be
operated during a power outage, and feature
manually operated hi-low flame control. The BTU
Input for these appliances is shown in Table 1.
Tables 2 and 3 show the appliances' inlet and
manifold gas pressure requirements:
Fuel #MinimumMaximum
Natural Gas4.5" WC
Propane11.0" WC
(1.12 kPa)
(2.74 kPa)
10.5" WC
(2.62 kPa)
13.0" WC
(3.24 kPa)
Table 2 - Inlet Gas Supply Pressure
Fuel #LowHigh
Natural Gas2.2" WC
Propane6.3" WC
(0.55 kPa)
(1.57 kPa)
3.5" WC
(0.87 kPa)
10.0" WC
(2.49 kPa)
Table 3 - Manifold Gas Supply Pressure
Test gauge connections are provided on the
front of the millivolt and electronic gas control
valve (identified IN for the inlet and OUT for the
manifold side). The control valves have a 3/8"
(10 mm) NPT thread inlet and outlet side of the
valve (refer to Figures 1 and 2).
Propane tanks are at pressures that will cause
damage to valve components. Verify that the
tanks have step down regulators to reduce the
pressure to safe levels.
The appliance and its appliance main gas
valve must be disconnected from the gas
supply piping system during any pressure
testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the gas
supply piping system by closing its equipment
shutoff valve during any pressure testing of
the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).
ORIFICE SIZES - SEA LEVEL TO HIGH
ALTITUDE (ALL MODELS)
These appliances are tested and approved for
installation at elevations of 0 - 4500 ft (0 - 1372
m) above sea level using the standard burner
orifice sizes (marked with an "*" in Table 4).
For elevations above 4500 ft, contact your gas
supplier or qualified service technician.
Deration - At higher elevations, the amount
of BTU fuel value delivered must be reduced
by either:
• Using gas that has been derated by the gas
company.
Install the appliance according to the regulations
of the local authorities having jurisdiction and,
in the USA, the National Fuel Gas Code NFPA
54 - latest edition / ANSI Z223.1 or, in Canada,
the CAN/CGA-B149.1 - latest edition.
Flame breadth, height and width will diminish
4% for every 1,000 feet of altitude. Gas Valve
Diagrams
. See Figure 1 for millivolt models
and Figure 2 for electronic models.
In Canada - CAN/CGA-2.17-M91 (R2009)
(high altitude): THE CONVERSION SHALL
BE CARRIED OUT BY A MANUFACTURER’S AUTHORIZED REPRESENTATIVE,
IN ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURER, PROVINCIAL OR TERRITORIAL AUTHORITIES
HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF
THE CAN/CGA-B149.1 OR CAN/CGAB149.2 INSTALLATION CODES.
Main Gas Control Knob
OFF/PILOT/ON
N
O
T
O
it
L
I
P
O
F
F
OUT
IN
Manifold Pressure Tap
Inlet Pressure Tap
Pilot Adjustment
I
P
W
O
L
H
I
HI/LO Variable
Flame Height
Adjustment
Screw
T
O
L
HTPTHTPT
Figure 1 - SIT Millivolt Gas Valve
(from DFC Wire Harness)
Inlet (IN) Test Port
Manifold (OUT) Test Port
Orange Wire
(from DFC Wire
Harness)
Green Wire
Burner Orifice Sizes
Elevation 0-4500 feet ( 0-1372 meters)
Model
MPB33
MPB35
MPB40
MPB45
Table 4
Nat.Gas
drill size (inches)
#47 (0.0785")*
99K74 •
#44 (0.086")*
60J80 •
#38 (0.102")*
99K76 •
#37 (0.104")*
24M10 •
* Standard size installed at factory
• Part /Cat. Number
Propane
drill size (inches)
(0.048")*
99K78 •
#55 (0.052")*
19L52 •
(0.062")*
21L01 •
#52 (0.0635")*
37G00 •
REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
These fireplaces are approved for installation in
the US state of Massachusetts if the following
additional requirements are met:
• Install this appliance in accordance with
Massachusetts Rules and Regulations 248
C.M.R.
• Installation and repair must be done by a
plumber or gas fitter licensed in the Commonwealth of Massachusetts.
• The exible gas line connector used shall
not exceed 36 inches (92 centimeters) in
length.
• The individual manual shut-off must be a
T-handle type valve.
Cold Climate Insulation
For cold climate installations, seal all cracks
around your appliance with noncombustible
material and wherever cold air could enter
the room. It is especially important to insulate
outside chase cavity between studs and under
floor on which appliance rests, if floor is above
ground level. Gas line holes and other openings
should be caulked or stuffed with unfaced
fiberglass insulation.
Hi/Lo Flame
Control Knob
• Changing the burner orice to a smaller size
as regulated by the local authorities having
jurisdiction and by the (USA) National Fuel
Gas Code NFPA 54/ANSI Z223.1 - latest
edition or, in Canada, the CAN/CGA-B149.1
codes - latest edition.
If the fireplace is being installed on a cement
slab in cold climates, a sheet of plywood or
other raised platform can be placed underneath
to prevent conduction of cold transferring to
the fireplace and into the room. It also helps to
sheetrock inside surfaces and tape for maximum
air tightness and caulk firestops.
MANUFACTURED HOUSING
B-Vent Fireplaces are not approved for use in
OEM or aftermarket manufactured housing built
to HUD standards.
LOCATION
In selecting the location, the aesthetic and
functional use of the appliance are primary
concerns. However, vent system routing to
the exterior and access to the fuel supply are
also important.
Due to high temperatures, the appliance
should be located out of traffic and away from
furniture and draperies (Figure 3).
En raison des températures élevées,
l’appareil devrait être installé dans un
endroit où il y a peu de circulation et loin
du mobilier et des tentures (Figure 3).
The location should also be free of electrical,
plumbing or other heating/air conditioning
ducting.
Be aware that this is a heat producing appliance. Objects placed above the unit are
exposed to elevated temperatures.
Do not insulate the space between the appliance and the area above it (see Figure10
on Page 8).
The appliance must be mounted on a fully
supported base extending the full width
and depth of the unit. The appliance may be
located on or near conventional construction
materials. However, if installed on combustible
materials, such as carpeting, vinyl tile or other
combustible material other than wood flooring,
the appliance shall be installed on a metal or
wood panel extending the full width and depth
of the appliance
VENT TERMINATION CLEARANCES
Gas Vent Rule - Gas vent caps are not per-
mitted within 8 feet (2.4 mm) of a vertical
wall or similar obstruction. Gas vent caps
that are located 8' or more from a portion
of a building which extends at an angle
greater than 45° upward from the horizontal
may terminate in accordance with Figure 4,
provided that in no case shall any discharge
opening on the cap be less than 2' (610 mm)
horizontally from the roof surface (National
Fuel Gas Code ANSI Z223.1 (NFPA 54) Gas
Vent Termination) (CAN/CGA B149.1).
MULTIPLE TERMINATIONS
These appliances may vent adjacent to and at
the same level with any other gas appliances
(including direct-vent appliances) provided that
there is at least 2 ft. (0.6m) between the proximal
edges of the vent caps. These appliances may
be vented adjacent to a chimney vent servicing
a solid fuel fireplace provided the B-vent cap
is at least 2 ft. (0.6m) away from the nearest
point of the chimney opening.
Vertical
Venting
Shown with Outside Air Kit
installed (model FOAK-4 or
FOAK-4LD)
When the unit is installed with one side flush with a
wall, the wall on the other side of the unit must not
extend beyond the front edge of the unit.
Figure 3 - Typical Installations
X
12
Roof Pitch is X/12
Minimum Height from Roof to
Lowest Discharge Opening
Flat to 6/121.00.3
6/12 to 7/121.250.38
7/12 to 8/121.50.46
8/12 to 9/122.00.61
9/12 to 10/122.50.76
10/12 to 11/123.250.99
11/12 to 12/124.01.22
12/12 to 14/125.01.52
14/12 to 16/126.01.83
16/12 to 18/127.02.13
18/12 to 20/127.52.29
20/12 to 21/128.02.44
5
12 (305) MANTEL
10 (254) MANTEL
8 (203) MANTEL
6 (152) MANTEL
4 (102) MANTEL
4
(102)
14
(356)
12
(305)
10
(254)
2 (51) MANTEL
TOP OF
APPLIANCE
6
(152)
NOTE - Hood shown as positioned in louvered
front model. The hood position in the flush
faced front model is lower than shown.
The appliance is approved with zero
clearance to combustible materials on
all sides. Refer to Table 5 for minimum
clearance values. For typical installations,
see Figure 3 on Page 5.
Minimum Clearances
Back1/2" (13 mm)
Sides1/2" (13 mm)
Top Spacers3" (76 mm)
Floor0" (0 mm)
Bottom of
Appliance
To Ceiling
Vent1" (25.4 mm)
Front 3' (0.9 m)
0 (0) from Spacers or Dimples
0 (0) from Spacers or Dimples
0" (0 mm)
with standoff(s) in vertical
position
64" (1626 mm)
SERVICE CLEARANCES
Table 5
NOTE: 3" (75 mm) minimum clearance is
required above any inclined vent component.
1" minimum clearance is required to the sides
of vertical vent.
Hearth Extension- A hearth extension is not
required with this appliance. If a hearth extension is used, do not block the lower control
compartment door. Any hearth extension used
is for appearance only and does not have to
conform to standard hearth extension installation requirements.
WALL FINISHES / SURROUNDS / MANTELS
NOTE: Combustible wall finish materials and/
or surround materials must not be allowed to
encroach the area defined by the appliance
front face (black sheet metal). Never allow
combustible materials to be positioned in
front of or overlapping the appliance face.
Refer to Figure 36 on Page 21 for clearance
recommendations and requirements.
Figures 6 and 7 illustrate the areas surrounding
the fireplace where clearances are an issue. The
outer edge of the metal trim on only one side
of the fireplace may abutt a perpendicular wall.
For this type of installation, the other side of the
fireplace must be a flat wall to allow for proper
air flow and burner operation.
Combustible materials may project beyond one
or both sides of the fireplace opening when
these materials are kept within the "Safe Zone"
illustrated in Figure 6.
Top View of
Fireplace
At 0 in. minimum
side wall clearance,
one combustible
wall can project to
any length.
Figure 6 - Clearance References
Non-combustible materials, such as surrounds
and other appliance trim, may be installed on the
appliance face with these exceptions:
They must not cover any portion of the removable
glass panel, louvers, or control compartment.
Vertical installation clearances to combustible
mantels vary according to the depth of the
mantel (see Figure 7). Mantels constructed of
non-combustible materials may be installed
at any height above the appliance opening;
however, do not allow anything to hang below
the fireplace hood.
Minimum clearance requirements include any
projections such as shelves, window sills,
mantels, etc. above the appliance.
NOTE: We recommend the use of high
temperature paint (rated 175 °F, or higher)
on the underside of the mantel.
Mantel Leg,
Trim, or Wall
3 1/2 in.
(89 mm)
45
o
Combustible materials
may project beyond
either side of the
fireplace opening as
long as they are kept
within the shaded
“Safe Zone” area.
Note: The nailing flanges, combustible members
and screw heads located in areas directly adjacent
to the nailing flanges, are EXEMPT from the 1/2”
clearance to combustible requirements for the
firebox outer wrapper.
Combustible framing may be
in
direct contact with the nailing flanges and may
be located closer than 1/2” from screw heads and
the firebox wrapper in areas adjacent to the nailing
flanges. Frame the opening to the exact dimensions
specified in the framing details of this manual.
Side
Framing
Unit Nailing Flange
(No clearance to
combustible
framing is required)
Left Side Front Corner of Fireplace Shown
(Right Side Requirements the Same)
PRE-INSTALLATION STEPS
The appliance is shipped with all gas controls
and components installed and pre-wired.
1. Before installing the appliance, follow these
steps:
2. Remove the shipping carton.
3. Remove the shipping pad, exposing the front
glass door.
4. Open the spring latch securing the glass
door (under the firebox floor). Remove the
door by tilting it outward at the bottom and
lifting it up. Set the door aside, taking care to protect it from inadvertent damage. See
Removing the Glass Enclosure Panel on Page
19.
5. Remove the log set from the firebox. Handle
logs carefully to prevent breakage.
6. Remove the embers and volcanic stone from
the control compartment.
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation is outlined
below; however, each installation is unique and
may result in variations to the steps described.
See the pages referenced in the following steps
for detailed procedures.
Step 1. FRAMING (Page 7): Construct the
appliance framing. Position the appliance within
the framing and secure with nailing flanges and
floor anchor tabs.
Bend out the appropriate nailing flanges for
the drywall/finish material to be used. Nailing
flanges are provided for flush framing, 1/2" and
5/8" framing depths (see Figure 8).
Step 2. ROUTING GAS LINE (Page 9): Route
gas supply line to appliance location.
Step 3. INSTALLING VENT SYSTEM (Page 10):
Install the vent system and exterior termination.
Step 4. FIELD WIRING (Page 11).
a. Millivolt Appliances - Install the operating
control switch (not factory provided). If
installing the optional forced air circulating
blower, bring in electrical service line.
b. Electronic Appliances - Field wire and
install operating control switch.
Frame the appliance as illustrated in Figure 11
on Page 8. All framing details must allow for
a minimum clearance to combustible framing
members as shown in the table on Page 8.
If the appliance is to be elevated above floor
level, a solid continuous platform must be
constructed below the appliance.
NOTE: The framed depth, 16" (406 mm) from
a framed wall, must always be measured from
a finished surface. If a wall covering such as
drywall is to be attached to the rear wall, then
the 16" (406 mm) must be measured from the
drywall surface. It is important that this dimension be exact.
Headers may be in direct contact with the
appliance top standoff spacers, but must not
be supported by them or notched to fit around
them. All construction above the appliance
must be self-supporting. DO NOT use the
appliance for structural support.
Secure the fireplace to the side framing members
using the unit’s nailing flanges - one top and
bottom on each side of the fireplace front (see
Figure 9). Use 8d nails or their equivalent.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
FLOOR NAILING TABS
Fireplace may be anchored to floor. Bend down
two anchor tabs (one on each side) located
at the base of the fireplace and secure to the
floor by nailing with 8d nails or equivalent (see
Figure 10).
Figure 9 - Unit Secured to Framing by
Nailing Flange
Figure 10 - Floor Anchor Tabs
NOTE: Some units only have one anchor tab
on each side.
Back Wall of Chase/Enclosure
Including Finishing Materials
C
F
A
Inside Chase
if any
G
G
Rough
Framing Face
(Unfinished Shown)
All framing dimensions calculated for 1/2" dry wall at the appliance face. If sheathing the chase or finishing with other thickness materials,
calculations will need to be made.
* Outside air kit - FOAK (without adaptor). See Figure 23 on Page 14.
8
Figure 11 - Framing Specifications
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.