Lennox MMDA009S4-*P, MPA012S4S-*P, MPA018S4S-*P, MMDA012S4-*P, MPB018S4S-*P Installation Instructions Manual

...
Page 1
INSTALLATION
©
2018 Lennox Industries Inc.
Dallas, Texas, USA
Table of Contents
General ...........................................................................1
Included Parts.................................................................2
Indoor / Outdoor Unit Match-Ups....................................2
Model Number Identication ...........................................3
Typical System Components ..........................................4
System Dimensions ........................................................5
Outdoor Units ..............................................................5
Indoor Units .................................................................6
System Clearances ........................................................7
Outdoor Unit ................................................................7
Indoor Unit ...................................................................7
Torque Requirements for Caps and Fasteners...............8
Indoor Unit Installation ....................................................8
Unit Placement Considerations ...................................8
Installation ...................................................................8
Installation Guidelines .................................................9
Field-Relocation of Return Air Filter .............................9
Indoor Unit Condensate Piping Connections .............10
Outdoor Unit Installation ...............................................10
Placement Considerations .........................................11
Direct Sunlight, Rain, Snow and Ice Protection ......... 11
Prevailing Winds ........................................................12
Buried Refrigerant Pipe Protection ............................12
Condensate Piping ....................................................13
Securing the Outdoor Unit .........................................13
Refrigerant Piping Connections ....................................13
Leak Test and Evacuation ............................................16
Leak Test ...................................................................16
Triple Evacuation Procedure......................................16
Wiring Connections ......................................................16
Outdoor Unit .............................................................16
Indoor Unit .................................................................16
Unit Start-Up .................................................................26
Adding Refrigerant for Longer Line Set ........................26
Troubleshooting ............................................................27
Test Run .......................................................................27
Pre-Checks ................................................................27
Procedure ..................................................................27
Dry Mode Operation (Dehumidication) .......................27
Procedure ..................................................................27
Sequence of Operation ..............................................27
INSTRUCTIONS
MLA/MPA/MPB
and MMDA Series
SINGLE-ZONE MINI-SPLIT SYSTEMS (208/230V) -- Medium-Ducted Indoor Unit 507547-06 1/2018 Supersedes 12/2017
THIS MANUAL MUST BE LEFT WITH THE OWNER
FOR FUTURE REFERENCE
WARNING
Installation and service must be performed by a li censed professional HVAC installer (or equivalent) or a service agency.
WARNING
The clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs, and HFCs) as of July, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for non-compliance.
WARNING
This product contains a chemical known to the State of California to cause cancer, birth defects, or other reproductive harm.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
General
Refer to the Product Specications bulletin (EHB) for more
product information. These instructions are intended as a general guide and
do not supersede local or national codes in any way. Authorities having jurisdiction should be consulted before installation.
The MMDA Medium-Static Ducted indoor units are matched with an outdoor heat pump unit to create a mini­split system that uses HFC-410A refrigerant.
Page 2
Included Parts
Package 1 of 1 contains the following:
1 - Assembled Indoor Unit The assembled indoor unit will include the following items:
Parts Figure Quantity Parts Figure Quantity
M0STAT61Q-1
Wired controller
Wired controller extension cable 6 ft (2m)
1
1
Installation and owner’s
manual
1 ea.
1 - Assembled Outdoor Unit and the following items:
Parts Figure Quantity Parts Figure Quantity
Drain connector 1 Seal ring 1
Indoor / Outdoor Unit Match-Ups
Outdoor Unit Indoor Unit Voltage
MPA009S4S-*P or MPB009S4S-*P MMDA009S4-*P
MPA012S4S-*P or MPB012S4S-*P MMDA012S4-*P
MPA018S4S-*P or MPB018S4S-*P MMDA018S4-*P
MPA024S4S-*P or MPB024S4S-*P MMDA024S4-*P
MPA036S4S-*P or MPB036S4S-*P MMDA036S4-*P
MPA048S4S-*P or MPB048S4S-*P MMDA048S4-*P
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
MLA009S4S-*P MMDA009S4-2P
MLA012S4S-*P MMDA012S4-2P
MLA018S4S-*P MMDA018S4-2P
MLA024S4S-*P MMDA024S4-2P
208/230V
208/230V
208/230V
208/230V
2
Page 3
Model Number Identication
OUTDOOR SINGLE ZONE HEAT PUMP UNITS
M P A 009 S 4 S - 1 P
Series Type
M = Mini-Split
Unit Type
L = Low Ambient Heat Pump
P = Heat Pump
Major Design Sequence
A = 1st Generation
B = 2nd Generation
Nominal Cooling Capacity
009 = 0.75 tons
012 = 1 tons
018 = 1.5 tons
024 = 2 tons 036 = 3 tons 048 = 4 tons
MEDIUM-STATIC DUCTED INDOOR UNITS
M MD A 012 S 4 - 1 P
Series Type
M = Mini-Split
Unit Type
MD = Medium-Static Ducted Unit
Voltage
P = 208/230V-1 phase-60hz
Minor Design Sequence
1 = 1st Revision
Refrigerant Circuits
S = Single Circuit
Refrigerant Type
4 = HFC-410A
Cooling Efciency
S = Standard Efciency
Voltage
P = 208/230V-1 phase-60hz
Minor Design Sequence
1 = 1st Revision 2 = 2nd Revision
Major Design Sequence
A = 1st Generation
B = 2nd Generation
Nominal Cooling Capacity
009 = .75 tons
012 = 1 tons
018 = 1.5 tons
024 = 2 tons 036 = 3 tons 048 = 4 tons
Refrigerant Type
4 = HFC-410A
Cooling Efciency
S = Standard Efciency
3
Page 4
Typical System Components
IMPORTANT - Condensate drain line must always
Indoor Unit
Supply Air
Opening
be located at the bottom of the bundle.)
Indoor unit wiring connections (under access plate)
Wiring
Condensate drain line
(wrapped in foam insulation)
Refrigerant Line Set, Condensate Line
And Indoor / Outdoor Cable
UV-rated tape (field-provided)
Line set (wrapped in foam insulation)
Communication cable 036 and 048 only
Tape
(field-provided)
Filter
Return Air
Liquid and vapor shut off valves
Wired Remote
Control
Outdoor Unit
009-036 shown
Utility
Bundle
Access cover for valves
IMPORTANT - The refrigerant metering device for this system is located in the outdoor unit. This makes it necessary to insulate the refrigerant lines individually to prevent sweating.
208/230V Outdoor Unit
Terminal Block
1 2 3 L1 L2
To Indoor Condensate drain from indoor unit
Unit
Communication Cable
036 and 048 only
XT2
TO INDOOR COMM. BUS
NOTEφ
To Power
Supply
LLEY
ARG Y
WO
S2
S1
Use 2-conductor shielded wire
Figure 1. Typical System Shown
4
Page 5
System Dimensions
A
E
D
B
C
TYPICAL APPEARANCE OF UNITS
Outdoor Units
Model
MPA009S4S-*P
MPA012S4S-*P
MPA018S4S-*P
MPA024S4S-*P
MPA036S4S-*P
MPA048S4S-*P
MPB009S4S-*P
MPB012S4S-*P
MPB018S4S-*P
MPB024S4S-*P
MPB036S4S-*P
MPB048S4S-*P
Unit of
Measurement
inches 33-1/4 21-5/8 22 11-3/8 12-3/4
mm 845 549 559 289 324
inches 36-1/8 22 27-1/2 12-3/4 13
mm 918 559 699 324 330
inches 40-5/8 25-1/4 31-7/8 15-1/8 16
mm 1032 641 810 384 406
inches 40-1/4 25 53-3/4 15-3/8 16
mm 1023 635 1365 391 406
inches 33-1/8 19-1/8 21-7/8 11-7/8 11-3/4
mm 842 486 556 302 298
inches 34-1/4 20-1/4 21-7/8 13-1/8 13-3/8
mm 870 514 556 333 340
inches 36 21-1/4 27-5/8 14-1/4 13-3/4
mm 914 540 702 362 349
inches 37-1/4 26-1/2 31-7/8 16-3/8 15-7/8
mm 1032 673 810 416 403
inches 41-1/8 25 52-1/2 16-3/8 15-7/8
mm 1045 635 1334 416 403
A B C D E
MLA009S4S-*P
MLA012S4S-*P
MLA018S4S-*P
MLA024S4S-*P
inches 34-1/4 20-1/4 21-3/4 12-1/4 13-3/8
mm 870 514 552 311 594
inches 36 21-1/4 27-5/8 13-3/4 16
mm 914 540 702 349 406
inches 40-3/4 26-1/2 31-7/8 15-1/8 16
mm 1035 673 810 384 406
Figure 2. Outdoor Unit Dimensions - inches (mm)
5
Page 6
Indoor Units
FRESH AIR INTAKE
3-5/8 (92) Diameter (015 thru 018)
5 (127) Diameter (024 thru 048)
SIDE VIEW
MOUNTING
LUGS (4)
D
C
CONDENSATE
GRAVITY
DRAIN
MOUNTING
LUGS (4)
P
1 (25) 1 (25)
N
TOP VIEW
H
I
J
F
M
SUPPLY AIR
OPENING
G
A E
FRONT VIEW
OPTIONAL BOTTON
RETURN AIR OPENING
BOTTOM VIEW
3/4 (19)3/4 (19)
ELECTRICAL
CONTROL
P
B
CONDENSATE PUMP DRAIN
GRAVITY CONDENSATE DRAIN
AIR FILTER
ELECTRICAL
CONTROL
BOX
LIQUID
PIPE
BOX
GAS PIPE
Size
RETURN AIR
OPENING
K
REAR VIEW
A B C D E F G H
in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm
L
AIR FILTER
009 thru 012 27-5/8 702 8-1/4 210 25 635 22-1/2 572 31-1/8 791 2-5/8 67 19-1/2 495 1-3/8 35
018 36-1/4 921 8-1/4 210 25 635 22-1/2 572 39-3/4 1010 2-5/8 67 28 711 1-3/8 35 024 36-1/4 921 10-5/8 270 25 635 22-1/2 572 39-3/4 1010 2-5/8 67 28 711 1-3/8 35 036 44-7/8 1140 10-5/8 270 30-1/2 775 28 711 48-1/2 1232 2-5/8 67 36-3/4 933 1-3/8 35 048 47-1/4 1200 11-7/8 302 34-1/8 867 31-1/2 800 50-3/4 1289 3-1/8 79 38-1/8 968 1-1/2 38
Size
J K L M N P
in. mm in. mm in. mm in. mm in. mm in. mm
009 thru 012 4-5/8 117 23-1/2 597 7-7/8 200 3-1/8 79 29-1/8 740 13-3/4 349
018 4-5/8 117 32 813 7-7/8 200 3-1/8 79 37-3/4 959 13-3/4 349 024 7 178 32 813 10-1/4 260 3/4 19 37-3/4 959 13-3/4 349 036 7 178 40-3/4 1035 10-1/4 260 3/4 19 46-1/2 1181 19-1/4 489 048 8 203 43 1092 11-3/8 289 1-3/4 44 48-7/8 1241 19-5/8 498
Figure 3. MMDA Indoor Ducted Unit Dimensions - Inches (mm)
6
Page 7
System Clearances
Outdoor Unit
Indoor Unit
12
(305)
24 (610)
24
(610)
1
Minimum rear clearance can be 6 inches (152 mm) when mounted on brackets
and with no obstructions on the other three sides.
Figure 4. Outdoor Unit Clearances - Inches (mm)
Wall
20” (508 mm) Minimum Service Clearance
79
(2007)
Air Outlet
Air Inlet
1
12
(305)
Wall
Air
DUCTED
UNIT
Flow
24” (610 mm)
Minimum
Service
Clearance
TOP VIEW
Ceiling
1” (25 mm) Minimum Clearance
1” (25 mm) Minimum Clearance
FRONT VIEW
CeilingSuspended
24” (610 mm)
Minimum Service Clearance
Figure 5. Indoor Unit Clearances - Inches (mm)
7
Page 8
Torque Requirements for Caps and Fasteners
When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. “Table 1. Torque Requirements” provides torque values for fasteners.
IMPORTANT
Only use Allen wrenches of sufcient hardness (50Rc -
Rockwell scale minimum). Fully insert the wrench into the valve stem recess.
Service valve stems are factory-torqued from 9 ft.-lbs. (12 N*m) for small valves, to 25 ft.-lbs. (34 N) for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
See the Lennox Service and Application Notes C-08-1 for further details and information.
Table 1. Torque Requirements
Parts
Service valve cap 8 ft.-lb. 11
Sheet metal screws 16 in.-lb. 2
Machine screws #10 27 in.-lb. 3
Compressor bolts 7 ft.-lb. 10
Gauge port seal cap 8 ft.-lb. 11
Recommended Torque
U.S. Newton-Meter- N
Indoor Unit Installation
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
Unit Placement Considerations
AVOID
Do not install the unit in the following locations:
• Areas exposed to petrochemicals or petrochemical products
• Areas exposed to salt or other corrosive materials or caustic gases
• Areas exposed to extreme voltage variations (such as factories
• Tightly enclosed areas that may impede service of the unit
• Areas exposed to fossil fuels (such as oil or gas in kitchens)
• Areas exposed to strong electromagnetic forces
• Areas exposed to acids or alkaline detergents
DO
• Place the unit so that it is not exposed to direct sunlight
Ensure the structural ceiling can support the weight of the unit
• Select a location where condensate line will have the shortest run to a suitable drain per local codes
Allow sufcient space around unit for proper operation and maintenance
• Install unit a minimum of 3 feet (1m) away from any antenna, power cord (line) radio, telephone, security
system, or intercom. Electrical interference and radio
frequencies from any of these sources may affect op­eration
Be sure to instruct customers how to properly operate the unit (especially maintenance of air lter, and oper­ation procedure) by having them carry out operations themselves while looking at the manual provided with the controller
Installation
1. Make sure that the structural ceiling or slab is able to support the weight of the indoor unit. It may be necessary to add extra support.
2. Install suspension rods in the structural ceiling or concrete slab in a suitable location. If the structural ceiling is constructed of concrete, install
anchors to accept four ⅜” threaded rods to suspend
the indoor unit. If the structural ceiling includes
wooden joists, use angle iron or Unistrut channel xed securely in place to accept the ⅜” threaded rods.
NOTE: Threaded rod is the ONLY acceptable method of
suspending the unit; do not use chains or straps. See “Figure 6. Suspending Methods”.
⅜” THREADED
CONCRETE CEILING
USING ANCHORS
ANCHOR
ANGLE IRON
BOLTED IN
PLACE ACROSS
WOODEN JOISTS
⅜” THREADED
ROD
ANGLE IRON
WOODEN JOISTS
WOODEN JOIST
ROD
ACROSS
Figure 6. Suspending Methods
3. Slide one nut and one washer onto each threaded rod. Use electrical tape to keep the washer from failing
off. Position the nuts slightly above the nal resting
place of the four suspension brackets. See”Figure 7. Suspending Hardware”
8
Page 9
4. Use either a mechanical lifting device or a minimum of
INDOOR UNIT
LEVELING
NUT
” THREADED
ROD
SUSPENSION
BRACKET
SUPPLY AIR
OPENING
FRONT VIEW
When unit is level, tighten
nut to secure
position of
suspension
bracket on
rod.
Remove the return air filter from its existing location at the rear of the unit.
Remove the screws that secure the filter frame to the rear of the unit and set the frame aside.
Remove the screws that secure the return air cover plate to the bottom of the unit. Set the cover plate aside.
e
Side rail
Dentilation panel
1
2
RETURN AIR
FILTER FRAME
RETURN AIR
COVER PLATE
Re-install the return air filter in the repositioned filter frame in the bottom of the unit. Refer to the arrows in the illustration below.
two people to raise the unit and insert the threaded rods into the suspension brackets on the unit chassis. Slide a washer and then a nut onto each rod below each suspension bracket. Use the leveling nut (beneath suspension bracket) to adjust the unit to the correct height. Remove the electrical tape holding the upper washers and nuts in place and tighten each of the four nuts above the brackets down onto the brackets. This will ensure that the unit remains level.
Figure 7. Suspending Hardware
5. If necessary, install a eld-provided isolation grommet as shown in “Figure 8. Isolation Grommet” to prevent transmission of vibration from unit to structural ceiling.
6. If the unit is being installed in an application that includes a sheet rock (plasterboard) ceiling, it is required that an access panel be installed in a suitable location. This will also allow access for future maintenance. Access is required during the start up process to test the condensate disposal system. See “Figure 13. Condensate Drain Test” on page 10.
7. The unit is factory-congured for the supply air to be
delivered from the front and the return air lter at the rear of the unit. The return air lter location can be relocated in the eld for bottom return air lter access,
if more convenient. See “Figure 8. Isolation Grommet”.
Use exible joints (canvas) at the point where the duct connects to the unit on both ends. Material must meet all local and national code requirements
• When unit is being installed in a location where even the slightest noise would be a problem (meeting room or other very quiet space), design duct system to avoid transmission of vibration to the structure to the extent possible
Follow ACCA manual D guidelines for return air l-
ter grille sizing. The return air lter grille should have
a minimum surface area of 200 square inch per ton (1290 cm2 per 3.5kW)
Field-Relocation of Return Air Filter
Depending on installation requirements, the return air lter
may need to be relocated as a bottom return air. See “Figure 9. Field-Relocation of Return Air Filter (Typical) -
Bottom Return Air” on page 9 for eld-relocating the return air lter.
” THREADED
ROD
FIELD-PROVIDED
ISOLATION GROMMET
WASHER
LEVELING
NUT
Figure 8. Isolation Grommet
NOTE: No part of the suspended ceiling, or other supports
not directly associated with the indoor unit
installation, can be xed to, or touch the indoor
Installation Guidelines
• Provide separate support for the weight of the duct
unit, in any form. Minimum clearances must be observed at all times.
system. Duct system must not be supported by the indoor unit
SUSPENSION
BRACKET
Figure 9. Field-Relocation of Return Air Filter
(Typical) - Bottom Return Air
9
Page 10
Indoor Unit Condensate Piping Connections
INSULATION
INDOOR
UNIT
CONDENSATE
LINE STUB
HOSE CLAMP
FLEXIBLE DRAIN
CONNECTOR
PVC DRAIN
PIPE
SUSPENSION RODS
DRAIN LINE
STRUCTURAL CEILING
8 in.
(203 mm)
Max. 28 in.
SUPPORT
STRAPS
3 ft. (1 m)
IMPORTANT
Make sure that drain piping is properly routed and insulated to prevent both leaks and condensation.
1. Use a eld-provided hose clamp to secure the drain line
stub on the side of the unit chassis to a eld-supplied
1” (25 mm) drain line.
NOTE: Take care not to over-tighten the hose clamp as
this may damage the drain line stub.
NOTE: Connection between stub and drain line must be
watertight. Apply non hardening plumbing joint compound if needed to ensure a watertight seal.
Figure 10. Condensate Gravity Drain Option
2. For applications including an indoor unit and a gravity drain. In this case, ensure that the drain line is properly sloped (no less than 1/4 inch per foot (18 mm per m)) and condensate lines are routed to ensure moisture is drained away from the indoor unit.
Structural Ceiling
Anti-siphon vent must extend above the height of the coil drain pan by 2” (51 mm).
4. In all cases, drain should be as short as possible and should not have any droops or kinks that would restrict
condensate ow and shall be constructed using an
approved pipe. There must be a 2-inch (51 mm) space
between the end of the condensate drain and the nal
termination point (ground, open drain, etc.) to ensure that the line will drain freely.
IMPORTANT
Drain should have a slope of at least ¼ inch per foot and
should be approved corrosion-resistant pipe. You must conrm operation of every drain and pump in the system
as part of the commissioning procedure.
5. After system installation is complete, the condensate drain line must be checked for leaks and the condensate pumps must be checked to ensure proper operation. This check is part of the start-up process which must be done by the installing contractor. Turn the condensate drain pan test cover latch counterclockwise to open the cover and access the drain pan. Funnel enough water to engage the pump into the drain pan through
a exible tube.
6. Operate the system in the cooling mode. If the internal pump is being used, ensure that the pump is operating and the water in the pan is draining freely. If the internal pump is not being used, pour the water into the drain
pan and conrm that it has owed freely out of the
pan and out of the drain termination. If a leak is found, shut down power to the unit at once and do not restore power to the unit until the problem has been resolved.
7. Return the test cover and turn the latch clockwise to re-lock it.
1 ft.
Suspension Rods
Indoor Unit
Do not operate unit without condensate drain trap.
NOTE - Drain line should be sloped 1/4 inch per foot (18 mm per m) AWAY from unit and should be supported as needed to prevent sagging.
Do not overtighten drain fitting.
(305 mm) max
Clean Out Do not glue
3”
3”
Figure 11. Slope Condensate Drain
3. For applications including an indoor unit using the internal drain pump.
Figure 12. Condensate Drain with Factory
Condensate Pump
3 ft.
(1 m)
Support
straps
Drain line
COVER LATCH
DRAIN PAN
TEST COVER
OSE
PE
N
CL
D
O
D
O
E
PE N
CLOS
(Turn latch
counterclockwise
to unlock)
FUNNEL WATER INTO PAN THROUGH TUBE
FOR TEST
Figure 13. Condensate Drain Test
Outdoor Unit Installation
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
10
Page 11
Placement Considerations
Air Inlet
Air Outlet
Consider the following when positioning the unit:
• In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life of the unit. In coastal areas, the coil should be cleaned with potable water several times per year to avoid corrosive buildup (salt)
• Some localities are adopting sound ordinances based on the unit’s sound level registered from the adjacent property, not from the property where the unit is in­stalled. Install the unit as far as possible from the prop­erty line
• When possible, do not install the unit directly outside a window. Glass has a very high level of sound trans­mission
• Install unit level
Building Structure
opy” or “Figure 20. Dog House-Style Shelter” on page 12
IMPORTANT
The construction of a canopy or shade is necessary because of an ambient limit control set to 122°F (50°C) to protect the electronics. If the outdoor unit is placed in direct sunlight it is possible that the limit may activate and shut down the unit.
• Place unit away from overhanging roof lines which would allow water or ice to drop on, or in front of, coil or into unit. Construct a canopy as illustrated in “Figure
15. Outdoor Unit on Pedestal (Stand) and Protective
Canopy”
• The unit base should be elevated above the depth of
average snows as illustrated in “Figure 16. Outdoor Unit on Brackets above Snow Line”
• In heavy snow areas, do not place the unit where drift-
ing will occur as illustrated in “Figure 17. Outdoor Unit Air Flow Obstructed by Snow”
• Carefully consider how to manage defrost water dis­posal to prevent ice from blocking walkways or creat­ing a safety hazard near the outdoor unit as illustrated in “Figure 18. Avoid Defrost Water Ice Hazard”
Ground Level
Figure 14. Install Unit Level
• Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will not
be amplied
• Choose a location where the hot air discharged from the unit or the operation noise will not be a nuisance to neighbors
• Avoid installing the outdoor unit near a bedroom or other places where noise may cause a problem
There must be sufcient space to carry the unit into and out of the site
There must be unobstructed air ow around the air in­let and the air outlet
The unit must not be installed in areas where a am­mable gas leak may occur
• Install the outdoor unit a minimum of 3 feet (1m) away from any antenna, power cord (line), radio, telephone,
security system, or intercom. Electrical interference
and radio frequencies from any of these sources may affect operation
• Since water drains from the outdoor unit during vari­ous stages of operation, do not place anything which may be damaged by moisture under the unit
Protective canopy
Air Outlet
Pedestal
(stand)
Side View
12 in
305 mm
Air Inlet
Protective canopy
24 in
610 mm
Front View
Pedestal (stand)
Figure 15. Outdoor Unit on Pedestal (Stand) and
Protective Canopy
Direct Sunlight, Rain, Snow and Ice Protection
• If the outdoor unit is subjected to prolong exposure to direct sunlight with temperatures over 100°F (38°C) a canopy is recommended as illustrated in”Figure 15. Outdoor Unit on Pedestal (Stand) and Protective Can-
Figure 16. Outdoor Unit on Brackets above Snow
Line
11
Page 12
Air Outlet
Air Inlet
12 in
305 mm
79 in
2007 mm
Prevailing Winter Winds from Air Inlet Side
12 in
305 mm
24 in
610 mm
12 in
305 mm
24 in
610 mm
NOTE - Minimum clearances shown.
Wind Barrier
Inlet Air
Discharge Air
Wind Barrier
12” (305mm) Min. Distance
79” (2007mm) Min. Distance
Figure 17. Outdoor Unit Air Flow Obstructed by
Snow
Figure 18. Avoid Defrost Water Ice Hazard
Prevailing Winds
Normally wind bafes are not required for a outdoor unit.
However, in order to maximize reliability and performance, the following best practices should be followed.
If unit coil cannot be installed away from prevailing winter winds, some method of protecting the coil is recommended. However, minimum clearances as reference in “Figure 4.
Outdoor Unit Clearances - Inches (mm)” on page 7
must be observed at all times. Common application examples are:
• When prevailing winds are from the air inlet side, then position the wind barrier a minimum of 12 inches (305 mm) from the unit as illustrated in “Figure 19. Wind
Barrier”
• When prevailing wind is into the discharge side, then position the wind barrier a minimum 79 inches (2007 mm) from the front of the unit as illustrated in “Figure
19. Wind Barrier”
Outdoor unit can be installed in a dog house style shelter as illustrated in “Figure 20. Dog House-Style Shelter”
Outdoor unit can be installed in a alcove or under a roof overhang as illustrated in “Figure 21. Unit installed in Alcove”
Prevailing Winter Winds From Air Discharge Side
Figure 19. Wind Barrier
24 in
12 in
305 mm
610 mm
NOTE - Minimum clearances shown.
24 in
610 mm
12 in
305 mm
Figure 20. Dog House-Style Shelter
Figure 21. Unit installed in Alcove
Buried Refrigerant Pipe Protection
• All refrigerant lines must be insulated regardless of if
it is buried
• In addition to insulating each line of piping, buried lines must rest inside a sealed, watertight conduit
• The conduit must be designed so it cannot collect and retain water
12
Page 13
Condensate Piping
Condensate formed during the heating and defrost processes must be drained from heat pump units. Drain holes are provided in the base of the units to ensure proper drainage. Heat pumps must be raised when installed on a concrete pad or the ground to allow drainage to occur. If the heat pump unit is installed on wall mounting bracket, insert the provided drain connector into one of the 1
inch (25 mm) drain holes and attached a eld-provided insulated drain hose to the connector. Use eld-provided
rubber plugs to cover any unused drain holes (see “Figure
22. Condensate Drain” on page 13).
Four Field-provided Anchor Bolts
Figure 23. Securing Outdoor Unit to Slab
Four Field-Provided
Anchor Bolts
Drain Connector
Chassis
Condensate Drain (location varies per model)
Figure 22. Condensate Drain
Securing the Outdoor Unit
Slab or Roof Mounting
Install the unit a minimum of 4 inches (102 mm) above the roof or ground surface to avoid ice build-up around the unit. Place the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications.
CAUTION
Roof Damage! This system contains both refrigerant and oil. Some
rubber roong material may absorb oil. This will cause
the rubber to swell when it comes into contact with oil. The rubber will then bubble and could cause leaks. Protect the roof surface to avoid exposure to refrigerant and oil during service and installation. Failure to follow this notice could result in damage to roof surface.
Securing Outdoor Unit to Slab, Frame, or Rails
If the outdoor unit is installed on a eld-provided slab or
frame, use lag bolts or equivalent to secure the outdoor unit to the slab or frame.
Figure 24. Securing Outdoor Unit to Rails
Securing Outdoor Unit To Hanging Brackets
If the outdoor unit is installed on eld-provided wall
mounting brackets, use lag bolts or equivalent to secure the outdoor unit to the bracket. Minimum rear clearance can be reduced to 6 inches (152 mm) when mounted on brackets and with no obstructions on the other three sides. Allow for condensate disposal when placing units above one another.
6 in
152 mm
Air Inlet
Air Outlet
Figure 25. Securing Outdoor Unit to Brackets
Refrigerant Piping Connections
Field piping consists of two copper lines connecting the outdoor unit to the indoor unit. “Table 3. Refrigerant Piping and Indoor Unit Connection Sizes” lists the connection sizes. The connections are made using the provided brass
are nuts at the end of the refrigerant piping connections.
1. Choose the correct pipe sizes for your application using “Table 3. Refrigerant Piping and Indoor Unit Connection Sizes” on page 14.
13
Page 14
2. Conrm that you are using the correct diameter piping.
90
Lean
Crude
Burr
o
3. Determine the necessary piping length required for the application.
4. Cut the selected pipes with a pipe cutter. Make the
cuts at and smooth as illustrated in “Figure 26.
Cutting Pipe”.
13. Slide the are nuts onto the ends of the eld-provided
refrigerant piping before using a suitable aring tool to are the end of the copper pipe.
14. Apply recommended HFC-410A refrigerant lubricant
to the outside of the ared refrigerant lines.
IMPORTANT
The compressor in this unit contains PVE oil (Polyvinyl ether). PVE oil is formulated for hydrouorocarbon (HFC) refrigerants, such as HFC-
410A, which this system contains. While it may have some miscibility properties with mineral-based oil and
POE oil (Polyolester), it is not recommended to mix PVE
oil with any other type of refrigerant oil.
15. Align the threaded connections with the ared
refrigerant lines. Tighten the are nuts lightly at rst to
obtain a smooth match as illustrated in
Figure 26. Cutting Pipe
5. Insulate the copper piping.
6. Insert a are nut onto each pipe before aring.
7. Use “Table 2. Flaring Pipe” to properly are the pipe.
Table 2. Flaring Pipe
Flare Dimension
Pipe Diameter
1/4” (6.35) 8.3 8.7
3/8” (9.62) 12.0 12.4
1/2” (9.52” 15.4 15.8
5/8” (15.9) 18.6 19.1
3/4” (22.9) 22.9 23.3
A (mm)
Min Max
Flare Shape
90
A
+
°
-
4
45
°
R0.4~0.8
8. After aring the pipe, temporarily sealed pipe ends with adhesive tape to avoid contaminants from entering the pipes.
9. The seal on the unit refrigerant piping connections should remain in place until the last possible moment. This will prevent dust or water from getting into the refrigerant piping before it is connected.
10. CAREFULLY adjust refrigerant piping connections to suit the application.
11. Slowly loosen one of the are nuts to release the factory nitrogen charge from the indoor units only.
12. Remove the are nuts from the connections on the unit and discard the seal from each of the piping connections.
Table 3. Refrigerant Piping and Indoor Unit
Connection Sizes
Size
(Btuh)
9000 1/4 3/8
12000 1/4 1/2
18000 1/4 1/2
24000 3/8 5/8
36000 & 48000 3/8 5/8
A
B
Liquid Line
in.
Gas Line
in.
CANT ON THE OUTSIDE OF
THE FLARE
MALE FLARE
CONNECTION
Figure 27. Making Connections
(Male to Female Connection)
16. Once snug, continue another half-turn on each nut which should create a leak-free joint. A torque
wrench may be used to tighten are nuts using table
4 recommendations (“Table 4. Flare Nut Torque Recommendations and Tightening Procedure” on page 15). Do not over-tighten a ared joint.
Flared connections should always be accessible and must be insulated to prevent condensation.
17. After refrigerant piping has been installed and checked
for leaks, apply insulation over all ared connections.
14
Page 15
Table 4. Flare Nut Torque Recommendations and Tightening Procedure
TORQUE WRENCH
TO INDOOR
UNIT
TO OUTDOOR UNIT
BACKUP
WRENCH
OUTDOOR UNIT
OUTDOOR UNIT
INDOOR UNIT
INDOOR UNIT
Maximum Line Set Length
Maximum Line Set
Length
Maximum
Elevation -
Outdooor
Unit BELOW
Indoor Unit
Maximum
Elevation -
Outdooor
Unit ABOVE
Indoor Unit
Minimum Line Set Length - 10 ft. (3m)
Minimum Line Set Length - 10 ft. (3m)
Outside Unit BELOW Indoor Unit Outside Unit ABOVE Indoor Unit
Do not allow for excess length of line sets to be left rolled up as part of the required distance, or in general. This will also cause additional performance issues.
IMPORTANT
Outside
Diameter
Inches
1/4 15 ft.-lb. (20 N) 1/4 turn
3/8 26 ft.-lb. (35 N) 1/2 turn
1/2 41 ft.-lb. (56 N) 7/8 turn
5/8 48 ft.-lb. (65 N) 1 full turn
Recommended
Torque
No torque wrench available
Finger tighten and use an appropriately sized
wrench to turn an additional:
Table 5. Refrigerant Line Set Requirements
IMPORTANT
Always use two wrenches when tightening are nuts to avoid twisting refrigerant piping. DO NOT over-tighten are nuts.
System Size (KBtu)
009 1/4 3/8 40 (12) 40 (12) 82 (25)
012 1/4 1/2 40 (12) 40 (12) 82 (25)
018 1/4 1/2 66 (20) 66 (20) 98 (30)
024 3/8 5/8 82 (25) 82 (25) 164 (50)
036/048 3/8 5/8 98 (30) 98 (30) 213 (65)
Each system size has a line set length and vertical elevation parameters.
Line Set Diameters (in.)
Liquid Gas
Outdoor Unit BELOW
Maximum Elevation
Indoor Unit - Feet
(Meter)
15
Maximum Elevation
Outdoor Unit ABOVE
Indoor Unit - Feet
(Meter)
Maximum Line
Set Length - Feet
(Meters)
Page 16
Leak Test and Evacuation
Air and moisture remaining in the refrigerant system will have undesirable effects as indicated below:
• Pressure in the system rises
Operating current rises
Cooling or heating efciency drops
• Moisture in the refrigerant circuit may freeze
• Water may lead to corrosion of parts in the refrigera­tion system
The line set between the indoor and outdoor units must be leak tested and evacuated to remove any non­condensables and moisture from the system.
Leak Test
Use the following procedure to test for system leaks:
1. Connect the manifold gauge set and dry nitrogen gas cylinder to the liquid and gas service ports
2. Open valve on nitrogen cylinder
3. Pressurize the system per the pressure test
specications in “Table 6. Pressure Test Specications”
4. Check that the system pressure remains stable. If there is any movement check system for leaks
5. After the system is found to be free of leaks:
• Close valve on nitrogen cylinder.
• Relieve the nitrogen pressure by: loosening the charge hose connector at the nitrogen cylinder.
• When the system pressure is reduced to normal, disconnect the hose from the cylinder.
4. Break the vacuum by allowing nitrogen into the port connections (liquid and gas line pipes) until a positive pressure is achieved
5. Evacuate the system to a minimum reading of 500 Microns (0.5 Torr).
6. For a moisture-free system, ensure the vacuum is held without movement for a minimum of 4 hours.
7. If vacuum fails to hold, carry out steps 2 through 6 until vacuum holds.
Wiring Connections
WARNING
Electric Shock Hazard. Can cause injury or death. Unit
must be rounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power sources.
CAUTION
All terminal connections must be made as illustrated in the following diagrams. Improperly connected wiring could damage unit or cause communication errors between indoor and outdoor units.
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the
current Canadian Electrical Code (CEC).
Table 6. Pressure Test Specications
Bar Psig kPa Duration
1 3 44 303 Minimum of 10 minutes
2 15 220 1517 Minimum of 10 minutes
3 32 470 3241 Minimum of 10 minutes
4 45 650 4482
5 32 470 3241
1 hour. Stress test to prove the integrity of the complete installation.
24 hours. Lower system pressure test,
after conrmation No. 4 was successfully
completed.
IMPORTANT
Use only oxygen-free nitrogen (OFN).
Triple Evacuation Procedure
A Micron or Torr gauge must be used for this procedure.
1. Discharge the oxygen-free nitrogen and evacuate the system to a reading of 8000 Microns (8 Torr) using all service valves.
2. Break the vacuum by allowing nitrogen into the port connections (liquid and gas line pipes) until a positive pressure is achieved.
3. Evacuate the system to a reading of 5000 Microns (5 Torr).
Outdoor Unit
• Refer to unit nameplate for minimum circuit ampacity and maximum over-current protection size.
• Make all electrical power wiring connections at the out­door unit.
Be sure to reattach all electrical box covers after con­nections are complete.
Indoor Unit
• All indoor units are powered by the outdoor unit.
Communication Wiring (Indoor Units 24K and Below): Use one stranded 4-conductor wire to provide power and communication.
• Communication Wiring (Indoor Units 36K and Above): Use one stranded 3-conductor wire to provide power and one stranded 2-conductor wire to provide commu­nication.
• Use minimum of 15 GA stranded wiring.
• When installing a condensate pump, wire in-line with
the CN5 oat switch.
16
Page 17
IMPORTANT
208/230V Outdoor Unit
Terminal Block
From Power
Supply
1 2 3 L1 L2
Terminal Block
1 2 3
208/230V Indoor Unit
Outdoor Unit Indoor Unit
From Power
Supply
Indoor Unit
CommunicationTerminal Block
L1 L2
Power Terminal Block
208/230V Outdoor Unit
L1 L2
L1 L2
Power Terminal Block
208/230V Outdoor Unit
Power Terminal Block
208/230V Indoor Unit
S1 S2
Communication Terminal Block
Outdoor Unit
E Y XYQS1E P
S2
Outdoor Unit
Indoor Unit
This unit must be properly grounded and protected by a circuit breaker. The ground wire for the unit must not be connected to a gas or water pipe, a lightning conductor or a telephone ground wire.
Do not connect power wires to the outdoor unit until all other wiring and piping connections have been completed. Do not install the unit near a lighting appliance that includes a ballast. The ballast may affect remote control operation.
IMPORTANT
All diagrams (Figure 30 through Figure 43) are typical wiring diagrams. Refer to the wiring diagram on the unit for actual wiring.
Figure 28. Single-Zone Wiring 24K and Below
Figure 29. Single-Zone Wiring 36K and 48K Only
17
Page 18
System and Terminal
Designations
Indoor to Outdoor
Wiring
(Communication/
Power)
1, 2, 3 and GND
Table 7. Single Zone Installation Wiring Requirements
System Capacity System Voltage
09K and 12K 208/230VAC 4
Number of
Conductors
Wire Type Wire Gauge / MCA
Stranded and
unshielded
16AWG
Outdoor to Main Power
L1, L2 and GND
Indoor to Outdoor
Wiring
(Communication/
Power)
1, 2, 3 and GND
Outdoor to Main Power
L1, L2 and GND
Indoor to Outdoor
Wiring
(Communication/
Power)
1, 2, 3 and GND
Outdoor to Main Power
L1, L2 and GND
Indoor to Outdoor
Wiring
(Power only)
L1, L2 and GND
Indoor to Outdoor
Wiring
(Communication only)
(S1, S2 and GND)
09K and 12K 208/230VAC 3
18K 208/230VAC 4
18K 208/230VAC 3
24K 208/230VAC 4
24K 208/230VAC 3
36K 208/230VAC 3
36K 208/230VAC 3 Stranded and shielded 24AWG
Stranded and
unshielded
Stranded and
unshielded
Stranded and
unshielded
Stranded and
unshielded
Stranded and
unshielded
Stranded and
unshielded
16AWG / 9A
16AWG
14AWG / 18A
16AWG
12AWG / 20A
16AWG
Outdoor to Main Power
L1, L2 and GND
Indoor to Outdoor
Wiring
(Power only)
L1, L2 and GND
Indoor to Outdoor
Wiring
(Communication only)
(S1, S2 and GND)
Outdoor to Main Power
L1, L2 and GND
MCA = Minimum Circuit Amps
36K 208/230VAC 3
48K 208/230VAC 3
48K 208/230VAC 3 Stranded and shielded 24AWG
48K 208/230VAC 3
Stranded and
unshielded
Stranded and
unshielded
Stranded and
unshielded
10AWG / 30A
16AWG
8AWG / 35A
18
Page 19
3
M
FAN
CN3
CN1 3
D C M OT O R
D R IV E R MO D U L E
5
CN1 5
INDOOR UNIT MAIN BOARD
CN9
CN3
E Y X
Y/G
To LVM Comm.Bus
Alarm Output
ALA R M
CN3 3
C N 1
RED
Remote Control
ON/ OFF
CN2 3
C N 2
C N 41
BLACK
FILTER-BOA RD
CN13
CN40
CN10
CN6
CN5
• • • • • COMPONENT IN DASH LINE IS OPTIONAL OR FIELD WIRING.
RE D
CN 8
CN 1 8
2
2
10
4
PUMP
DISPLAY
BOARD
BLACK
WHITE
WA TE R L EV EL SW IT CH
YELLOW
BLACK
RED
Note: The programmable wired controller and regular wired controller use the same wiring connector
M
4
PROGRAMMABLE
2
INDOOR COIL TEMP. SENSOR
1
WIRED
CONTROLLER
5
TO WIRED
CONTROLLER
ROOM TEMP. SENSOR
3
2
TO
T2
T1
Y/G
Figure 30. MMDA009S4-*P, MMDA012S4-*P, MMDA018S4-*P Ducted Units Wiring Diagram
3
Alarm
Remote
M
FAN
CN3
CN1 3
D C M OT O R
D R IV E R MO D U L E
5
CN1 5
Output
ALA R M
CN3 3
Control
ON/ OFF
CN2 3
INDOOR UNIT MAIN BOARD
CN9
CN3
C N 1
C N 2
RED
C N 41
BLACK
FILTER-BOA RD
E Y X
To LVM Comm.Bus
Y/G
CN13
CN40
CN10
CN6
CN5
• • • • • COMPONENT IN DASH LINE IS OPTIONAL OR FIELD WIRING.
RE D
CN 8
CN 1 8
2
2
10
4
PUMP
DISPLAY
BOARD
BLACK
WHITE
WA TE R L EV EL SW IT CH
YELLOW
BLACK
RED
Note: The programmable wired controller and regular wired controller use the same wiring connector
M
4
PROGRAMMABLE
2
INDOOR COIL TEMP. SENSOR
1
WIRED
CONTROLLER
5
TO WIRED
CONTROLLER
ROOM TEMP. SENSOR
3
2
TO
T2
T1
Y/G
Figure 31. MMDA024S4-*P Ducted Units Wiring Diagram
19
Page 20
To LVM Comm. Bus
• • • • • COMPONENT IN DASH LINE IS OPTIONAL OR FIELD WIRING.
CN40
2
Note: The programmabl e wired cont roller and regula r wired cont roller use the same wiring con nector
PROGRAMMABLE
4
2
TO
WIRE
CONTROLLER
Figure 32. MMDA036S4-*P & MMDA048SA-*P Ducted Units Wiring Diagram
OR
CN9-1
WHITE
REACTOR
COMPRESSOR
BLACK
CN28
CN32-1
WHITE
RED
CN29
BLUE
CN30
CN7
3
DC-FAN
COMPRESSOR
DISCHARGE TEMP. SENSOR
CN3
CN22
Y/G
COIL TEMP. SENS
OUTDOOR
CN21
OUTDOOR TEMP. SENSOR
6
CRANKCASE
4-WAY
VALVE
BLUE
BROWN
1
HEATER
PAN HEATER
2
YELLOW
BLUE
RED
3
L2
Y/G
CN31
CN26 CN27
CN16
CN1
CN2
CN33
Y/G
Figure 33. 208/230V MPA009S4S-*P and MPA012S4S-*P Outdoor Unit Wiring Diagram
20
Page 21
OUT DOOR FAN
3
CN414
CRANKCASE HEATER
RED
Y/G
4-WAY VALVE
BLACK
YELLOW
Y/G
RED
CN6
BLUE
CN3
CN4
CN8
CN7 CN2
CN6-1
Y/G
CN15
CN18
RY1
OUTDOOR
MAIN
PCB
6
OUTDOOR TEMP.SENSOR
L-OUT
WHITE
CN1
O UTD OOR C O IL TEM P.
CN14
BLACK
CN13
CN12
BLUE
RED
BLACK
CN10
COMPRESSOR
U V
W
TEMP.SENSOR
Figure 34. 208/230V MPA018S4S-*P Outdoor Unit Wiring Diagram
BLUE
1
RED
2
BLACK
3
W
COMPRESSOR
BLUE
BLUE
U
V
Y/G
Compressor
L-OUT
Control Board
2
BLACK
RED
Y/G
PAN HEATER
Y/G
CRANK CASE HEATER
Figure 35. 208/230V MPA024S4S-*P Outdoor Unit Wiring Diagram
RED
COMPRESSOR DISCHARGE TEMP.SENSOR
S
CN10
YELLOW
BLACK
21
Page 22
CODE PART NAME
COMP
EXV
FM1
HEAT1
HEAT2
H-PRO
L
L-PRO
SV
T3
T4
COMPRESSOR
ELECTRIC EXPANSION VALVE
OUTDOOR DC FAN
CRANKCASE HEATER
PAN HEATER
HIGH PRESSURE SWITCH
PFC INDUCTOR
LOW PRESSURE SWITCH
4 WAY VALVE
OUTDOOR COIL TEMP. SENSOR
OUTDOOR TEMP. SENSOR
W
COMP
V
Y/G
U
DRIVER BOARD
YELLOW
BLACK
RED
BLUE
L
BLACK
RED
BLUE
BLUE
BLUE
YELLOW
CN54
CN51
CN53
CN52
COMPRESSOR DISCHARGE TEMP. SENSOR
EXV
M
FM1
5
CN55
CN19
7
W
V
U
RED
BLACK
SV
HEAT1
HEAT2
4 WAY VALVE
ORANGE
ORANGE
ORANGE
CN3
CN4
CN10
ORANGE
CN22
CN40
CN44
CN33
MAIN BOARD
T3
T4
H-PRO
L-PRO
7
CN8
CN9
BLACK
CN5
CN7
CN6
RED
CN20
CN34
CN12 CN11
BLACK
CN2
P-1
RED
CN1
Y/G
CODE
COMP
CT1
D
DCFAN1,DCFAN2
HEAT_Y
HEAT_D
H-PRO
L
L-PRO
SV
T5
T3
T4
TH
PART NAME
COMPRESSOR
AC CURRENT DETECTOR
DIODE MODULE
OUTDOOR DC FAN
CRANKCASE HEATER
PAN HEATER
HIGH PRESSURE SWITCH
PFC INDUCTOR
LOW PRESSURE SWITCH
4-WAY VALVE
DISCHARGE TEMP. SENSOR
OUTDOOR COIL TEMP. SENSOR
OUTDOOR TEMP. SENSOR
HEATSINK TEMP. SENSOR
YELLOW
GRAY
S2
S1
XT2
TO INDOOR COMM. BUS
NOTEP lease use 2-core
shielded wire.
Figure 36. 208/230V MPA036S4S-*P Outdoor Unit Wiring Diagram
YELLOW
L
A
CN15
6
ELECTRONIC EXPANSION VALVE A
Y/G
P-6
Compressor and Outdoor Fan Control Board
W
BLACK
BLUE
V
U
COMP
U
CN55
V
W
RED
Y/G
D
RED
BLUE
CN9
DCFAN2
CN8
BLACK
CN6
CN3
7
CN7
5
CN11
5
DCFAN1
HEAT_Y
HEAT_D
CN15
CN14
RED
CN39
BLACK
12
4
RED
3
5
5
4-WAY
SV
BLACK
BLUE
BLUE
CN4
CN39
CN18
CN25
CN20
CT1
CN2
CH5
CN17
CN24
CN19
YELLOW
CN5
CN6
MAIN BOARD
TO INDOOR UNIT POWER SUPPLY
CN3
CN1
CN22
CN12
TH
RED
BLACK
( )
2)(1
L1
L2
Y/G
BLACK
WHITE
2
TO INDOOR COMM. BUS
NOTE
shielded wire.
9NC
T4 T3
YELLOW
01NC
RED
CN8
T5
RED
BLACK
XT1
L1
L2
MAIN
PO W ER S UP PLY
Y/G
BLAC K
RED
LLEY OW
ARG Y
S2
S1
XT2
Please use 2-core
H-PRO
L-PRO
XT1
L2
L1
MAIN
POWER SUPPLY
L2
L2
)
) 2
2
(
(
L1
1
1
( )
( )
TO INDOOR UNIT
XT3
Figure 37. 208/230V MPA048S4S-*P Outdoor Unit Wiring Diagram
22
Page 23
4-WAY VALVE
OUTDOOR
FAN
CN 7
3
6
CN 31
PAN HEATER
CN 15
CN 60
CRANKCASE HEATER
CN 17
BLUE
BROWN
BLACK
3
2
L2
RED
BLUE
Y/G
1
Y/G
CN 21
Y/G
CN 1A
Y/G
Y/G
COMPRESSOR
Y/G
CN 50
3
U
V
W
BLUE
RED
BLACK
EXV
OUTDOOR MAIN PCB
OUTDOOR
TEMP. S ENS OR
COMPRES S OR
DISCHARGE
T E MP. S E NS OR
OU TDOOR C OIL
T E MP. S E NS OR
RED
BLACK
WHTIE
T5
T4
T3
Figure 38. 208/230V MPB009S4S-*P and MPB012S4S-*P Outdoor Unit Wiring Diagram
Figure 39. 208/230V MPB018S4S-*P and MPB024S4S-*P Outdoor Unit Wiring Diagram
23
COMPRESSOR
(T5)
(T3)
(T4)
Page 24
CO MP
MAIN B OA RD
R ED
BLACK
U
V
W
Y/G
Y/G
L
L-PRO
T3
T4
CODE PART NAME
COMPRESSOR
HEAT 1
4-W AY VALVE
COMP
EXV
ELECTRIC EXPANSIO N VALV E
H-PRO
L-PRO
LOW PRESSURE SWIT CH
HIGH PRE SSURE SW IT CH
T3
T4
OUTDOOR COIL TEMPERATURE SENSOR
OUTDOOR TEMPERATURE SENSOR
CRANKCAS E HEAT ER
POWER SUPPLY
H-PRO
SV
L
PFC INDUCTOR
T5
T5
COMPRESSOR DISCHARGE TEMP ERA TURE SENS OR
RED
BLA CK
V
U
CN19
CN51
CN55
W
EXV
BLACK
DRIVER BOARD
RED
7
7
YELLOW
BLUE
P-1
FM1
OUTDOOR DC FAN
CN53
CN20
CN34
CN3
CN4
CN10
CN40
CN22
CN44
C N8
C N9
CN7
CN2
C N1
CN5
CN54
CN52
CN33
5
CN6
SV
4-WAY VALVE
BLUE
BLUE
HEAT2
HEAT1
BLACK
RED
BLUE
BLUE
BLUE
YELLOW
RED
BLACK
RED
BLACK
TO INDO OR COMM. BUS
XT 2
YE LLO W
GR AY
S1
S2
XT 1
L1
L2
L1
L2
2)(1
()
RED
BLAC K
MAIN
TO INDOOR UNIT POWER SUPPLY
FM 1
Y/G
BLACK
BLACK
RED
RED
HEAT 2
PAN HEAT ER
NOTE: PLEASE USE 2-CORE SHIELDED WIRE
Figure 40. 208/230V MPB036S4S-*P Outdoor Unit Wiring Diagram
24
Page 25
DR IV ER B OA RD
CODE
PART NAME
COMPRESSOR
D
HEAT 1
CT1
AC CURRENT DETECTOR
4-WAY VALVE
COMP
EXV
ELECTRIC EXPANSIO N VALVE
H-PRO
L-PRO
LOW PRESSURE SWIT CH
HIGH PRE SSURE SWITCH
T3
T4
OUTDOOR COIL TEMPERATURE SENSOR
OUTDOOR TEMPERATURE SENSOR
CRANKCAS E HEAT ER
DIODE MODULE
SV
L
PFC INDUCTOR
TH
HEATSINK TEMPERATURE SENSOR
T5
COMPRESSOR DISCHARGE TEMPERATURE SENSOR
MAIN BOARD
FM1,FM2
OUTDOOR DC FAN
EX V
O UTDO
OR T E MP
. S E NS OR
O UTDO OR C O
L
I T E MP .
SE NSO R
D
12
3
4
5
P5
CN19
CN20
CN24
CN25
CN17
FAN1
CN18
HEAT1
HEAT2
SV
4-WAY VALVE
BLUE
RED
BLUE
CN4
CN2
CN3
CN1
CO MP
U
V
W
Y/G
CN6
CN9
10
3
CN1
CN2
L
YELLOW
YELLOW
U
V
W
BLUE
BLACK
RED
RED/WIHTE
BLACK
RED
BLACK
CH1
CT1
FM 2
FM 1
Y/G
Y/G
DC MOT OR DR IV ER B OA RD
CON1
FAN1
CN1
FAN2
3
3
P6
2
CN6
CN3
Y/G
BLACK
TO IND OOR COMM. BUS
XT 2
YE LLOW
GR AY
S1
S2
NOTE: PLEASE USE 2-CORE SHIELDED WIRE
L2
L1
MAIN
POWER SUPPLY
XT1
TO INDOOR UNIT
L1
Y/G
XT2
1L21
L2
1
NL
N
L
P9
P7
P8
CN22
RED
BLUE/BLACK
ORAN GE
ORA NGE
RED
BLACK
CH2
CH2
CH2
~
~
~
COM PR E S S
OR D SI
CHA RG E
T E MP .
S E NS
OR
HEAT 2
PAN HEAT ER
Figure 41. 208/230V MPB048S4S-*P Outdoor Unit Wiring Diagram
Figure 42. 208/230V MLA009, 012 and 018S4S-*P Outdoor Unit Wiring Diagram
25
Page 26
COMP
YELLOW
CODE
COMP
CAP1
EEV
FM1
H-PRO
L-PRO
SV
TS
T3
T4
BLACK
W
RED
V
BLUE
U
DRIVER BOARD
BLACK
RED
BLUE
BLUE
BLUE
YELLOW
L
PART NAME
FAN MOTOR CAPACITOR
ELECTRIC EXPANSION VALVE
OUTDOOR DC FAN
HIGH PRESSURE SWITCH
L
PFC INDUCTOR LOW PRESSURE SWITCH
4-WAY VALVE
DISCHARGE TEMPERATURE SENSOR CONDENSER TEMPERATURE SENSOR
OUTDOOR AMBIENT TEMPERATURE SENSOR
FM1
3
3
CN5 5
CN1 9
W V U
RED
CN54
CN51
BLACK
CN53
CN52
COMPRESSOR
Y/G
4-WAY1
SV
HEAT1
Crankcase H eater
HEAT2
Bas e Pan Hea ter
36K ODU
ONLY FOR
T3 T4
BLUE
H-PRO
L-PRO
BLUE
CN3
CN4
CN10
CN8
CN9
CN7
CN33
CN22 CN40 CN44
MAIN BOARD
BLACK
CN5
CN6
RED
Y/G
EEV
5(6 )
CN20
RED
BLACK
1
2
TO INDOO R UNIT
YELLOW
L1
3
S
CN2
CN1
P-1
BLACK
RED
L2
L1
L2
POWER SU PPLY
YELLOW BLACK
RED
Y/G
Y/G
Figure 43. 208/230V MLA024S4S-*P Outdoor Unit Wiring Diagram
Unit Start-Up
IMPORTANT
Units should be energized 24 hours before unit start-up to prevent compressor damage as a result of slugging.
1. Inspect all factory- and eld-installed wiring for loose connections.
2. Verify that the manifold gauge set is connected.
3. Add additional refrigerant charge if required before opening valves and while system is still under a vacuum.
4. Open the liquid and gas line service valves to release the refrigerant charge contained in outdoor unit into the system.
5. Replace the stem caps and tighten to the value listed in “Table 4. Flare Nut Torque Recommendations and Tightening Procedure” on page 15.
6. Check voltage supply at the outdoor unit terminal strip. The voltage must be within the range listed on the unit’s nameplate. If not, do not start the equipment until you have consulted with the power company and the voltage condition has been corrected.
7. Refer to the included user guide to operate the system using the provided remote control.
8. Visually check for binding of both indoor and outdoor fans.
Adding Refrigerant for Longer Line Set
The outdoor unit is factory-charged with refrigerant. Calculate the additional refrigerant required according to the diameter and the length of the liquid pipe between the outdoor unit and indoor unit connections.
Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced performance.
Table 8. Additional Refrigerant Charge
System Size
(KBtu)
09 >25 (7.5) 0.161 oz/ft (15g/m)
12 >25 (7.5) 0.161 oz/ft (15g/m)
18 >25 (7.5) 0.161 oz/ft (15g/m)
24 >25 (7.5) 0.322 oz/ft (30g/m)
36 >25 (7.5) 0.322 oz/ft (30g/m)
48 >25 (7.5) 0.322 oz/ft (30g/m)
Pipe Length
(feet / meters)
Amount of Refrigerant
to add
26
Page 27
Troubleshooting
Table 9. Indoor Unit Troubleshooting Codes
Display Description
E0 Indoor unit EEPROM error
E1 Communication error between indoor and outdoor units
(E2 for outdoor code)
E3 Indoor fan speed error
E4 Indoor return air temperature sensor error
E5 Indoor coil temperature sensor error
EC Low refrigerant
EE High water level alarm (for ducted units only)
F0 Outdoor current overload sensed Note: (outdoor unit
display --) two dashes
F1 Outdoor ambient temperature sensor error (T4
malfunction) outdoor unit display E4
F2 Outdoor coil temperature sensor error (T3) Malfunction
outdoor unit display E4
F3 Compressor discharge temperature sensor error (T5)
Malfunction outdoor unit display E4
F4 Outdoor unit EEPROM error - outdoor display E0
F5 Outdoor unit fan speed error - outdoor Error display E8
P0 Inverter module IPM error - outdoor display P6
P1 High or low voltage protection - outdoor display E5
P3 Outdoor unit low temperature lockout - outdoor unit
display LP
P4 Compressor drive error
P6 Mode conict
P7 Compressor high- or low-pressure switch open - outdoor
unit display P2
Test Run
Pre-Checks
Only perform test run after you have completed the
following steps:
Electrical Safety Checks – Conrm that the unit’s electrical system is safe and operating properly
Refrigerant Leak Checks – Check all are nut connec-
tions and conrm that the system is not leaking
Conrm that liquid and gas valves are fully open
Procedure
You should perform the Test Run for at least 30 minutes.
1. Connect power to the unit.
2. Press the ON/OFF button on the remote controller to turn it on.
3. Press the mode button to scroll through the following functions, one at a time:
COOL - Select lowest possible temperature
HEAT - Select highest possible temperature
4. Let each function run for 5 minutes, and perform the following checks:
Table 8. Test Run Checklist
Checks Pass Fail
No electrical leakage
Unit is properly grounded
All electrical terminals properly covered
Indoor and outdoor units are solidly installed
All pipe connection points do not leak
Water drains properly from drain hose
All piping is properly insulated
Unit performs COOL function
properly
Unit performs HEAT function
properly
Indoor unit louvers rotate properly
Indoor unit responds to remote controller
Dry Mode Operation (Dehumidication)
Procedure
1. Using the provided wired remote control, press the MODE button and select DRY mode.
2. Press the UP/ DOWN button to select the desired temperature. The temperature setting range is from 62°F (17°C) to 86°F (30°C) in one degree increments.
NOTE: The blower is preset at a low speed and cannot be
changed therefore it will get cold and most likely will over shoot the temperature setting by 6-10°F (3-5°C) depending on the room size or other various factors. Also the Follow Me mode does not operate in this mode.
NOTE: In addition, the indoor units do not have a humidistat
installed therefore they are unable to determine humidity levels. This product is not recommend as
a main source for dehumidication.
Sequence of Operation
When in dry mode operation the unit is actually in cooling mode with a low speed blower operation. Set remote temp to a lower room temp to begin the dry mode operation. The compressor will stop when the room temperature is 4°F (2°C) lower than the temperature setting.
However there is a temperature compensation for cooling mode that is two degrees Celsius. So the unit will stop when the temperature is 8°F (4°C) lower than the room temperature settings.
27
Page 28
28
Loading...