Lennox MP-36OD User Manual

INSTALLATION INSTRUCTIONS
MERIT PLUS® SERIES
36" Indoor / Outdoor Wood Burning Fireplaces P/N 850,030M REV. B 04/2006
MODEL
MP-36OD
This installation manual will enable you to obtain a safe, effi cient and de­pendable installation of your fi replace system. Please read and understand these instructions before beginning your installation.
Do not alter or modify the fi replace or its components under any circum­stances. Any modifi cation or alteration of the fi replace system, including but not limited to the fi replace, chimney components and accessories, may void the warranty, listings and approvals of this system and could result in an unsafe and potentially dangerous installation.
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
VEUILLEZ GARDER CE MANUEL
POUR RÉFÉRENCE FUTURE.
A French manual is available upon request. Order P/N 850,030CF
Ce manuel d’installation est disponible en francais, simplement en faire la demande. Numéro de la pièce 850,030CF.
OTL Report No.
116-F-35-2
IMPORTANT! TO ASSURE PROPER ALIGNMENT OF GLASS DOORS: INSTALL THIS FIREPLACE IN A SQUARE AND PLUMB CONDITION, USING SHIMS AS NECESSARY AT SIDES AND/OR BOTTOM.
NOTE: This fi replace has been listed and approved for use outdoors or indoors.
CAUTION! THIS FIREPLACE IS EQUIPPED TO BE READILY IN­STALLED OUTDOORS. IF INSTALLED INDOORS, YOU MUST INSTALL THE COMBUSTION AIR COVER PROVIDED WITH THE INSTALLATION KIT OR PURCHASE THE OPTIONAL OUTSIDE AIR KIT GATE OAKG-OD. SEE INSTRUCTIONS INSIDE THIS MANUAL FOR FURTHER DETAILS.
IMPORTANT! POUR ASSURER L’ALIGNEMENT APPROPRIÉ DES PORTES DE VERRE : INSTALLEZ CE FOYER SUR UNE SURFACE PLANE ET METTRE À NIVEAU EN UTILISANT DES CALES AU BESOIN SUR LES CÔTÉS OU EN DESSOUS.
ATTENTION! CETTE CHEMINÉE A ÉTÉ ÉNUMÉRÉE ET APPROU­VÉE POUR ÊTRE AISÉMENT INSTALLÉE À L’INTÉRIEUR OU DEHORS. S’INSTALLÉ À L’INTÉRIEUR, VOUS DEVEZ INSTALLER LA COUVERTURE D’AIR DE COMBUSTION ÉQUIPÉE DE KIT D’INSTALLATION OU ACHETER LA PORTE EXTÉRIEURE FAC­ULTATIVE OAKG-OD DE KIT D’AIR. VOIR LES INSTRUCTIONS À
L’INTÉRIEUR DE CE MANUEL POUR D’AUTRES DÉTAILS.
TABLE OF CONTENTS
Safety Rules ......................................Page 2
Tools and Building Supplies ..............Page 2
Precautions .......................................Page 2
Introduction ......................................Page 3
Clearances/Height Requirements ......Page 4
Chimney System ...............................Page 4
Assembly Outline ..............................Page 4
Location of Fireplace .........................Page 5
Clearances ........................................Page 5
Assembly Steps ................................Page 6
Preinstallation Notes .........................Page 6
Waterproofi ng Fireplace ....................Page 6
Outside Air Kit .................................Page 8
Fireplace & Framing Specifi cations ...Page 9
Installing the Fireplace ......................Page 10
Installing the Chimney System ..........Page 12
30° Offset through Floor/Ceiling .......Page 13
Ten Foot Rule Summary ....................Page 15
Multiple Terminations .......................Page 15
Chimney Component Calculations ....Page 15
Special Offset Instructions ................Page 15
Offset Calculations ............................Page 16
Vertical Elevation Charts ..................Page 16
Installing Offsets ...............................Page 17
Offset Elevation Chart ........................Page 18
Gas Line Connection .........................Page 18
Vent Free Appliances .........................Page 19
Glass Doors ......................................Page 19
Cold Climate Insulation .....................Page 20
Fireplace Finishes - Mantels and Trim ..Page 20
Hearth Extensions/Wall Shields ........Page 20
Finish Requirements .........................Page 22
Installation Components ...................Page 23
PACKAGING
The assembled indoor/outdoor fi replace is packaged with: 1 - One envelope containing the literature pack-
age which consists of the homeowner's manual, installation instructions, warranty and combustion air cover (located in the
fi rebox). 2 - One Outside Air Kit. 3 - Hearth Extension Strips.
PLEASE READ AND UNDERSTAND THESE IMPORTANT SAFETY RULES.
WARNING
To avoid the risk of damaging fi replace materials and increas­ing the risk of fi re, do not use the fi replace to cook or warm food.
2
AVERTISSEMENT
Pour éviter le risque d’endommager les matériaux du foyer et d’augmenter le risque d’incendie, n’employez pas le foyer pour faire cuire ou réchauffer de la nourriture.
1. Before starting your fi replace installation,
read these installation instructions carefully to be sure you understand them completely and in entirety. Failure to follow them could cause a fi replace malfunction resulting in serious injury and/or property damage.
2. Always check your local building codes.
The installation must comply with all lo­cal, regional, state and national codes and regulations.
3. This fi replace must be installed with Security
Chimneys FTF8 [8" (203mm) inside diam­eter] Chimney System only. This fi replace is intended for indoor or outdoor installations. The chimney system must always vent to the outside of the building or structure.
4. To ensure a safe fi replace system and to
prevent the build-up of soot and creosote, inspect and clean the fi replace and chimney prior to use and periodically during the heat­ing season.
5. Burn approved fuels only as defi ned in the
Homeowner's Care and Operation Manual.
6. NEVER use gasoline, gasoline-type lantern
fuel, kerosene, charcoal lighter fl uid, or similar liquids to start or “freshen up” a fi re in this fi replace. Keep any fl ammable liquids at safe distance from the fi replace.
7. NEVER leave children unattended when there
is a fi re burning in the fi replace.
8. Always keep fl ue damper open when heat is
present in the fi replace.
9. Before ser vicing, allow the fi replace to cool.
Always shut off any gas to the fi replace while working on it. This will prevent the possibility of burns.
10.This fi replace is not a heater. It is designed
to ensure homeowner comfort by providing supplemental heat to its immediate area.
11. Keep screens closed after feeding fi re to
keep embers from fl ying out ot fi replace.
12.INDOOR INSTALLATIONS:
• Always ensure that an adequate supply of replacement combustion air from the outside of the house is accessible to the fi re to support normal combustion. Fireplaces consume large volumes of air during the normal combustion process.
• In the event the home is tightly sealed with modern energy effi cient features, the optional outside air kit may not provide all the air required to support combustion.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
• The manufacturer is not responsible for any
smoking or related problems that may result from the lack of adequate combustion air. It is the responsibility of the builder/contractor to ensure that adequate combustion air has been provided for the fi replace.
• An Outside Air Cover (provided) or an Out- side Air Kit Gate, model OAKG-OD (optional) must be installed to prevent signifi cant cold air infi ltration.
13. Always ensure that the air inlet to the fi replace is free from debris and any other obstructions that can block the entrance of air.
14. DO NOT use a fi replace insert or any other product not specifi ed by Lennox for use with this fi replace. All gas log sets must
be operated with the damper clamped open, including unlisted “vent free” log sets. Listed “vent-free” log sets may be operated with the damper closed.
15."Smoke free” operation is not warranteed nor are we responsible for inadequate sys­tem draft, general construction conditions, inadequate chimney heights, adverse wind conditions and/or unusual environmental factors or conditions beyond our control.
16.Never, under any circumstances, install a fi replace, chimney component or any acces­sories, that has visible or suspected physical damage as a result of handling or transporta­tion. These items should be inspected by your distributor or qualifi ed factory representative to ensure safe condition. When in doubt, consult your distributor.
17. For additional safety considerations and complete operating instructions, refer to the Care and Operation Manual provided with the fi replace.
TOOLS AND BUILDING SUPPLIES
NORMALLY REQUIRED
Tools Supplies
Phillips screwdriver Hammer Saw and/or sabersaw Level Measuring tape Plumb line Electric drill and bits Pliers Square
Framing materials Wall fi nishing materials Caulking materials (noncombustible) Fireplace surround and hearth extension materials
(noncombustible)
PRECAUTIONS
The most important areas of concern dealing with the installation of factory-built fi replaces are clearances to combustible materials, proper assembly of component parts, height of the chimney system, the proper use of accessories supplied by the manufacturer and the techniques employed in using fi nishing materials applied to the wall surrounding the fi replace, hearth exten­sions and wall shields. Each of these topics will be covered in thorough detail throughout this manual. Please give each your special attention as you progress with your installation.
Note: These fi replace systems are not diffi cult to install. However, in the interest of safety, it is recommended that the installer be a qualifi ed or certifi ed “tradesman” familiar with commonly accepted fi replace installation and safety tech­niques as well as prevailing local codes.
INTRODUCTION General Information
These fi replaces are traditional radiant heat fi replaces with standard bar grates, optional Outside Air Kits (required for outdoor installa­tions) and optional Operable Bi-Fold Stainless Outdoor Glass Doors and Weather Cover.
These appliances are approved for installation indoors or outdoors.
Indoors: These appliances are approved for installation in residential homes and other buildings of conventional construction including commercial, not in manufactured homes(see Figure 5).
Outdoors: These appliances are approved for installion against an outside wall of a house, or as a freestanding fi replace on the porch, patio, or located in the yard (see Figure 6). The Outdoor Fireplace must be enclosed to prevent impact damage to the outside of the fi replace. Build an outside enclosure out of standard building materials, being careful to maintain the minimum air clearances speci­fi ed in these Installation Instructions. When installing the fi replace as a freestanding unit on your porch, patio or backyard, it must also be enclosed to prevent impact damage to the fi replace. However, the enclosure must now be fi nished on all four (4) sides. The exterior of the enclosure may be fi nished in a textured plywood, a wood clapboard siding, brick, or a cultured stone.
Vinyl siding is not recommended for use on the front of the fi replace due to the heat the unit produces. This can cause the vinyl siding to deteriorate.
Note: Illustrations shown refl ect “typical” installations with nominal dimensions and are for design and framing reference only. Actual installations may vary due to individual design preferences. However, always maintain minimum clearances to combustible materials and do not violate any specifi c installation requirements.
These fi replaces have been tested and listed by OMNI-Test Laboratories, Inc. (Report No. 116-F-35-2) to U.L. 127 (USA) and U.L.C. S610 (Canada). These units are intended for indoor and outdoor installations as specifi ed in this manual.
For installations in Canada, the chimney clear­ance to combustibles must be 2 inches and the Cold Climate Kit must be installed.
WARNING
Do not pack or fi ll required air spaces with insulation or other material. No material is allowed in these areas.
AVERTISSEMENT
Ne remplissez pas les espaces libres d’une matière isolante ou de tout autre type de matériel. Aucun matériel n’est permis dans ces espaces vides.
WARNING
If insulation is used, the fi replace must not be placed directly against it. Insulation or vapor barriers, if used, must fi rst be covered with gypsum board, plywood, particle board or other material to assure insulation and vapor barriers remain in place.
AVERTISSEMENT
Si un isolant est utilisé, il ne doit pas venir en contact avec le foyer. L’isolant ou le coupe vapeurs, si utilisée, doit d’abord être couvert d’un panneau de gypse, contre­plaqué, panneau de particules ou d’un autre matériel pour s’assurer que l’isolant et le coupe vapeurs demeurent en place.
These fi replace systems are designed for in­stallation in accordance with the National Fire Protection Standard for chimneys, fi replaces and solid fuel burning appliances; NFPA 211­latest edition and in accordance with codes such as the BOCA Basic/National Codes, the Standard Mechanical Code and the Uniform Building Codes.
TYPICAL INSTALLATION - INDOORS
Termination (FTF8-CTD/CTDT)
Storm Collar
Flashing
(Locally
* Outside Air Kit (provided) must be installed in outdoor installation.
Use Only Non-Combustible Materi­als From Top Of Spacers Down And Within 1/2" Min. To Side Frame.
And Hearth Extension
Required When Installed
On Combustible Floor
Fabricated)
Side Frame
Metal Safety Strips
Or In Proximity To
Combustible
Floor/Covering.
(FSC)
TYPICAL INSTALLATION - OUTDOORS
Outdoor fi replace system less than 15 feet height must be a
Chimney Section (FTF8-48)
7' 3" Min. (using one 4' section)
*Air Inlet (Provided)
minimum of 10 feet away from a building or combustible structure. If installed closer than 10 feet, the 10 Foot Rule applies (see Ten Foot Rule Summary on
Page 15).
Notes:
• Framing is shown as reference only. It can differ according to design and local building codes.
• Fireplace is shown for illustration purposes only. It may differ from actual model.
Figure 1
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Chimney and
Termination
Outside Air Kit installa-
tion is optional unless
mandated by local build-
Note: Framing and fi replace shown as reference only. It can differ according to design and local building codes.
ing codes.
Outside Combustion Air Kit (Optional)
Figure 2
3
WARNING
Failure to use manufacture provided parts, variations in techniques and construction materials or practices other than those described in this manual may create a fi re hazard and void the limited warranty.
AVERTISSEMENT
L’échec d’utiliser la fabrication les parties fournies, les varia­tions dans les techniques et le matériel de construction ou les pratiques autre que ceux-là ont décrit dans ce manuel peut créer un risque d’incendie et un vide la garantie limitée.
When complete these fi replace systems consists of fi ve basic “sub-systems”:
1. The Fireplace
2. The Chimney and Termination
3. The Optional Glass Doors
4. The Optional Outside Air Kits
5. The Optional Weather Cover (for outdoor
installations)
CLEARANCES AND HEIGHT REQUIREMENTS
The fi replace may be placed on or near normal construction materials*. The outside air kit, fi restop spacer and roof fl ashing (not chase fl ashings) may be placed directly on or against normal construction materials. **
A combustible mantel may be installed 12" above the opening of the fi replace as per NFPA 211-latest edition. In Canada, the minimum is 18" above the fi replace opening.
* In the USA, the chimney and fi replace outer wrapper require a minimum 1" to insulation and construction materials.
In Canada, the chimney and fi replace outer
wrapper require a minimum 2" air space to insulation and construction materials.
** Construction Materials:
• Framing Materials • Paneling
• Particle Board • Flooring
• Dry Wall • Plywood
• Noncombustible Insulating Materials
• Etc.
air space
INDOOR INSTALLATIONS - The minimum installed height of the completed fi replace system for is 15' 0." The maximum height is 60' 0" (see Table 1).
OUTDOOR INSTALLATIONS - The minimum installed height of the completed fi replace system is 7' 3." The maximum height is 60" (see Table 2).
The fi replace and chimney system must be enclosed when installed in or passing through a living area where combustibles or people may come in contact with it. This is important to pre­vent possible personal injury or fi re hazard.
For questions, please call your distributor or the manufacturer. Special restrictions apply to the front and facing of the fi replace and nearby walls (See Pages 20, 21 & 22).
CHIMNEY SYSTEM
These fi replaces are designed and code listed for use with Security Chimneys FTF8 chimney Sys­tem only. Always use Security Chimneys FTF8 chimney components with these fi replaces. Do not modify or alter these components as this may cause a potential serious hazard and void the Warranty.
Chimney Height - Indoor Installations
The total height of your completed fi replace system from the surface the fi replace rests on to the chimney top must not exceed 60' and must also meet minimum height requirements. Refer to the minimum system height chart (see
Table 1).
Chimney Height - Outdoor Installations
The total height of your completed fi replace system from the surface the fi replace rests on to the chimney top must not exceed 60' and must also meet minimum height requirements. Refer to the minimum system height chart (see
Table 2).
INDOOR INSTALLATIONS Minimum System Height
Security's FTF8 Pipe Vertical Installation 15' 0" One Offsets 15' 0" Two Offsets 25' 0"
Table 1
OUTDOOR INSTALLATIONS
Minimum System Height
Security's FTF8 Pipe Vertical Installation 7' 3" One Offsets 15' 0" Two Offsets 25' 0"
Table 2 - See following Notes
Notes (Table 2)
• Outdoor fi replace system less than 15 feet height must be a minimum of 10 feet away from a building or combustible structure. The 10 foot rule applies on all cases (see ten foot rule summary on Page 15).
• The system height may be reduced to a single length of FTF8-48 pipe and termination with either the FTF8-CTD or FTF8-CTDT for a minimum height on a complete system of 7' 3." The fi replace must be installed as a Freestanding system and located a minimum of 10' away from any building or structure (refer to Figure 1).
• The minimum height will vary when using other Firecraft or Lennox Terminations.
Chase Enclosure
A chase is a vertical box-like structure con­structed to surround the fi replace and chimney. Refer to Figure 4 for a typical chase confi gura­tion. As with all chimney installations, avoid overhead obstructions such as trees, power lines, etc. A chase should be constructed and insulated just like any outside wall. In a cold climate, we recommend the base of the chase should also be insulated between the solid continuous fl oor beneath the fi replace and the chase bottom. Chase insulation in a cold climate installation is not required for safety.
Note: Do not insulate the chase cavity with blown or fi ll type insulation materials.
Note: Local codes may not require fi restopping at the ceiling levels for outside chase installa­tions. However, it is recommended for safety and the reduction of heat loss.
ASSEMBLY OUTLINE Before You Start
Check your inventory list to be sure you have all the necessary parts supplied in good us­able condition. Check also for any concealed damage.
Check the operation of the damper. The damper is controlled through the use of a control lever located within the fi rebox opening at the top center in front of the fi rebox lintel (Figure 3). The control lever snaps into place at either extreme of its range of motion. When locked in position all the way to the right, the damper is open. When locked in position all the way to
the left, the damper is closed.
4
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Lintel
Damper
Open
Damper Closed
Combustion Air Actuator
(when installed)
Figure 3
Chase Enclosure - Indoor Installation
Insulate Joists Same As Ceiling
Draft Stops
Firestop
CTDT Termination
Note: Non­Combustible Chase Flashing Must Be Used To Cover Chase Opening
Optional Insulation In Outside Walls Of Chase
8'
Level
Solid Continuous Surface
Outside Insulation (Thermal Barrier)
Base
Figure 4
LOCATION OF FIREPLACE
Carefully select the proper location for heat circulation, aesthetics, chimney obstructions, air inlet location and clearance to side wall(s). With proper pre-planning, a slight adjustment of a few inches can save considerable time and expense later during construction and assembly.
Figures 5 & 6 for examples.
See
When locating the fi replace, consideration must be given to combustibles and fi nal fi nishing. See Figure 5 and confi ne the fi nal location of combustible fi nish materials to the "Safe Zone."
DO NOT permanently place furniture or other items such as decorative pillows within 60" of the fi replace front face.
Indoor Locations - Carefully consider the position of the fi replace opening with re­spect to the location of adjacent or nearby stairwells, bath or kitchen exhaust fans and/or return air registers for forced air furnaces/air conditioners that could cause a smoking fi replace condition if the house is tightly insulated.
Indoor Locations - Top View
Hearth
Hearth
Figure 5
Optional Outside Chase
CAUTION
To ensure that the outside air kit remains open for an outdoor installation, this fi replace should not have a combustion air gate control installed (OAKG-OD). If this unit is installed indoors, you must install the outside combustion air cover provided or an optional outside air kit gate (OAKG-OD) before the fi replace
is framed in place.
ATTENTION
Assurer que les restes extérieurs de kit d’air ouverts pour une instal­lation extérieure, cette cheminée n’ont pas une commande de porte d’air de combustion a installé (OAKG-OD). Si cette unité est installée à l’intérieur, vous devez installer la couverture extérieure d’air de combustion fournie ou une porte extérieure facultative de kit d’air (OAKG-OD) avant que la cheminée soit encadrée en place.
Outdoor Locations - Carefully consider the position of the fi replace opening with respect to the location of adjacent or nearby stair­wells, doors, windows, walk ways and over hanging trees, patios and wires.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
When choosing a location, care must be taken to avoid places where fl ooding or running water may be a problem.
DO NOT place furniture or other items such as plants or decorative objects within 60” of
the fi replace front face.
Outdoor Locations - Top View
LIVING SPACE
Air Inlet (inlet
Optional Hearth Extension
must be free of any obstructions)
PATIO
Figure 6
Restrictions for Outdoor installations:
Outside Air Kit must be installed and fully open on the outdoor installation. On the indoor installation is optional unless mandated by local building codes.
• Minimum chimney height for the outdoor in­stallation is 7' 3" (one 4 foot pipe section).
• Only non-combustible materials are al­lowed on the front face (Front Fireplace Frame) and around the perimeter within 1-5/8” on the top and 1/2" on the sides (see Figures 1, 51 & 52).
Combustible materials may project beyond the sides of the fi replace opening as long as they are kept within the shaded areas illustrated in
Figure 7.
CLEARANCES
Minimum clearance to combustibles for the appliance is as follows: sides and back - 1” (25 mm), fl oor - 0” (0 mm), adjacent wall - 12” (305 mm), ceiling - 37 1/2” (953 mm).
Note: Clearance at the nailing tab is 0" (0mm)
(see Figure 25).
Note: Adjacent wall considerations are for an adjacent wall on only a single side. Walls should not be placed at minimum distance at both sides of the fi replace.
Frame Surface Not to Be Covered With Combustible Materials
12"
45°
1"
Door
Opening
12"
Wall Covering
Safe Zone
Figure 7 Clearances
5
ASSEMBLY STEPS
Note: The following steps represent the normal sequence of installation. Each installation is unique, however, and might require a different sequence.
1. Position fi rebox prior to framing or into
prepared framing.
2. (Outdoor Installations) Waterproof the
fi replace. See Waterproofi ng The Fireplace on Page 6.
3. Install the chimney system.
4. Install an outside air cover or an airgate kit, if
fi replace is being installed indoors (optional accessory, see Page 23 for ordering infor­mation). The Airgate kit is required on all
INDOOR installations when an outside air kit is installed. The Airgate Kit is NOT ap­proved for use on outdoor installations.
5. Install outside air kit (provided). This kit
is required on ALL outdoor installations (optional for indoor installations).
6. Plumb gas line if a decorative gas appliance
will be used. (Gas connections should only be performed by an experienced, licensed/ certifi ed tradesman).
7. Complete the installation, fi nish wall mate-
rial, surround and hearth extension to your individual taste.
8. Assemble and attach optional glass door
assembly.
Study the illustration of the installation, Figures 1 & 2, to get a general idea of each element of your fi replace system.
PRE-INSTALLATION NOTES
The fi replace may be installed directly on a combustible fl oor or raised on a platform of an appropriate height. Do not place fi replace on car­peting, vinyl or other soft fl oor coverings. It may, however, be placed on fl at wood, plywood, particle board or other hard surfaces. Be sure fi replace rests on a solid continuous fl oor or platform with appropriate framing for support (and for indoor installation ensure that no cold air can enter the room from under the fi replace).
The fi replace may be positioned and then the framing built around it, or the framing may be constructed and the fi replace positioned into the opening.
Usually, no special fl oor support is needed for the fi replace, however, to be certain:
1. Estimate the total weight of the fi replace system including chimney and surround materials such as brick, stone, etc., to be installed. Shipping weight for the fi replace may be found on Page 9 (see Product Reference Information).
2. Measure the square footage of the fl oor space to be occupied by the system, surrounds and hearth extensions.
3. Note the fl oor construction, i.e. 2 x 6’s, 2 x 8’s or 2 x 10’s, single or double joists, type and thickness of fl oor boards.
4. Use this information and consult your local
6
building code to determine if you need ad­ditional support.
If you plan to raise the fi replace and hearth extension, build the platform assembly then position fi replace and hearth extension on top. Secure the platform to the fl oor to prevent possible shifting.
WATERPROOFING THE FIREPLACE
Outdoor Installations
Although the fi replace is designed to drain to the front most of the water from rain and other sources that may enter the hearth area, conden­sation and unusual conditions may cause water to collect inside the fi replace bottom.
To prevent water collection, the builder must provide a means to drain water from under
the fi replace by building or installing a water collector of the builder's choice before posi­tioning the fi replace on its location.
INDOOR INSTALLATIONS ONLY
Outside Air Cover
If the optional outside air kit is not required in an indoor installlation, you must install the outside air cover to close the opening for the outside air kit (see Figure 8, Photo C).
WARNING
Indoor Installations - If the optional outside air kit is not required, the outside air cover must be installed for safe fi replace operation.
AVERTISSEMENT
Installations d’intérieur - si le kit extérieur facultatif d’air n’est pas exigé, la couverture extérieure d’air est exigent pour l’opération sûre de cheminée.
The Outside Air Cover is included in the Instal- lation Instrctuions package provided with this fi replace. Follow the steps below:
a. Remove the Outside air collar located on
the side of the fi replace. Do not discrd the screws (see Figure 8, Photos A & B).
b. With the screws previously removed, install
the cover provided with the installation instructions kit (see Figure 8, Photo C).
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Outside Air Collar
Right Side Outside Panel on Fireplace
Four (4) Screws
A
Right Outside Panel on Fireplace
Outside air collar Removed
B
Outside Air Cover Installed
Right Side Outside Panel on Fireplace
Required on indoor installations if an outside air kit is NOT installed.
Viewed from right side of fi replace
Figure 8
Outside Air Kit Gate Installation (optional kit) Indoor Installations Only
The installation of the Air Gate (shutter) is required on all indoor installations to prevent cold air infi ltration when an outside air kit, OAK-OD (duct & hood), is installed. The Outside Air Kit Gate, OAKG-OD (air gate & arm), must be purchased and installed before the fi replace is installed.
1. Remove the Outside Air Collar located on
the right hand side of the fi replace (retain the screws). See Figure 8, Photos A & B.
2. Install the Outside Air Kit Gate (OAKG-
OD) per the instructions in the kit and the following instructions using the screws provided.
a. Assemble the Air Gate Arm to the Air
Gate as shown in Figure 9.
b. Take the Air Gate Assembly and feed the
arm through the round opening (see Figure 10 ) and then through the side frame opening in the front as shown in Figure 11.
C
Assemble the Air Gate and Arm as shown.
Air Gate Assembly
Using a screwdriver bend this tab outward, if necessary, for the arm to clear the opening
4. Install an Outside Air Kit (with duct and hood)
per the instructions provided with kit.
a. If the outside air kit is NOT installed, you
must install the Outside Air Cover provided with the instructions kit.
b. If an outside air kit IS installed, the Outside
Air Kit Gate must be installed (see Page 23 of ordering information).
Air Gate Arm
Air Gate Assembly
Air Gate Arm
When assembled onto appliance, the
notch here must be positioned as shown
Figure 9- Outside Air Kit Gate
IMPORTANT! IF THE AIR GATE IS INSTALLED UPSIDE DOWN (WITH THE NOTCH POSI­TIONED ON THE UPPER HALF) IT WILL NOT WORK PROPERLY. REFER TO FIGURE 9.
c. Ensure the air gate arm remains attached
to the air gate, secure the Air Gate to the fi replace, with the screws provided, as shown
in Figures 12 & 13.
d. Verify the mechanism is working by pulling
to open and pushing to close.
3. Install the Outside Air Collar with the screws removed earlier (see Figure 14).
Right Outside Panel on Fireplace
Position the Air Gate Assembly as Shown
Firebox
Feed The Arm Through Side Frame Opening
Arm
Front Face
Side Frame Opening
Figure 11 - Air Gate Arm in Front
Align Air Gate Assembly to Opening
Figure 12 - Position Air Gate
Secure Air Gate Assembly 4 Places
Figure 13 - Install Screws
Reinstall Outside Air Collar
The Outside Air Kit Gates are required on all indoor installations only. They are not approved for use on oudoor installations.
Air Gate Operation Instructions
Install the Air Gate Kit per the instructions provided with kit (see Page 23 for ordering information).
Air Gate Kit (purchased separately)
Combustion Air Actuator
Pull Forward to Open, Push Back to Close
Figure 15
To operate, push the end of the actuator arm to the left as shown in Figure 15, until it "pops" free of its "locked" position. Pull the actuator forward to open the combustion air door, and push it back to close. To "lock" the combustion air door closed, ensure the actuator is pushed all the way back then push the end of the actua­tors to the right until the step in the actuator moves behind the appliance front face within the slotted opening.
Operate the actuator through several cycles including the "lock" position. Ensuring proper operation and freedom of movement. Return the actuator arm to the locked position.
Figure 10 - Air Gate Assembly to Fireplace
Figure 14 - Reinstall Connector
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
7
Outside Air Kit Installation (provided)
These appliances are equipped with a com­bustion air inlet collar so that it is possible to duct combustion air from the outdoors to the fi rebox. To accomplish an outside air hook­up, use only the Outside Air Kit provided with these appliances. These kits come complete with all components necessary in completing a combustion air vent system.
Indoor Installations - An Air Gate Kit must be installed prior to the installation of the Outside Air Kit (purchased separately - see Page 23 for ordering information).
Install as follows:
Connect the 4" (102 mm) Class 0 air duct provided, to the collar on the fi replace with the clamps provided in the kit’s hardware package (Figure 16).
Route the Class 0 metallic air duct out the back wall or side wall, up through the ceiling or fl oor joists to an outside wall. The air duct’s inlet
should be located above any anticipated snow level. Check local building codes for any
restrictions. We recommend that the inlet be at least 4 feet above grade level.
Note: Air inlet ducts must not terminate in attic space.
Note: Secure the duct hood to a vertical post with the inlet positioned downward. Ensure that nothing blocks the hood opening. This duct must never terminate higher than 3 feet below the fi replace termination (Figure 17).
3 Feet
Outdoor Installations - Units installed outdoors are required to have the Outside Air Kit (pro­vided) installed without the Air Gate Kit. The optional Air Gate Kit is not approved on outdoor installations.
Outside Air Kit (provided)
Required on all Outdoor installations Optional on Indoor installations
Air Duct
Air Inlet
Clamps
Note: Air Inlet Must Be Free Of Any Obstructions
Figure 16
CAUTION
Avoid installing the air inlet where the opening could be blocked by snow, bushes or other obstacles. The maximum height for the outside air is 50 feet above the hearth, provid­ing the air inlet is terminated a minimum of three (3) feet below the chimney cap level.
ATTENTION
Évitez d’installer la prise d’air ou l’ouverture pourrait etre bloquee par la neige, les buissons ou d’autres obstacles. La hauteur maximum pour la prise d’air est de 50 pi. Au dessus de la base du foyer à condition qu’elle se situe à au moins 3 pi. En dessous de la sortie de la cheminée.
Air Inlet
(duct hood)
Figure 17
Duct Hole Framing:
Cut or frame a hole through the outside of the enclosure for the installation of the duct inlet hood. A 5" (127 mm) diameter hole is required. Feed the loose end of the fl exible duct through the hole cut for the inlet hood and attach to the collar on the inlet hood using two (2) screws. Insert the hood into the opening. Secure in place with nails driven through the holes in hood fl ange. Seal with noncombustible waterproof silicon type caulking. If additional duct is needed, use Class 0 metallic air duct (refer to Figure 16).
8
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Loading...
+ 16 hidden pages