Lennox Montebello MDLX40IN-PV, Montebello MDLX45IN-PV Installation Instructions Manual

Page 1
INSTALLATION INSTRUCTIONS
AVERTISSEMENT : Assurez-vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d’incindie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result, causing property damage, personal injury, or death.
WARNING /AVERTISSEMENT/AVISO
• HOT GLASS WILL CAUSE BURNS.
• DO NOT TOUCH GLASS UNTIL COOLED.
• NEVER ALLOW CHILDREN TO TOUCH GLASS.
• UNE SURFACE VITRÉE CHAUDE PEUT CAUSER DES BRÛLURES.
• LAISSER REFROIDIR LA SURFACE VITRÉE AVANT D'Y TOUCHER.
• NE PERMETTEZ JAMAIS À UN ENFANT DE TOUCHER LA SURFACE VITRÉE.
• EL VIDRIO CALIENTE CAUSARÁ QUEMADURAS.
• USTED DEBE NUNCA TOCAR EL VIDRIO CALIENTE.
• LOS NIÑOS DEBEN NUNCA TOCAR EL VIDRIO.
- Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
- Ne pas entreposer ni utilizer d’essence ni d’autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucan interrupteur. Ne pas vous servir des
téléphones se trouvant dans le bâtiment où vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis
un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service des incindies.
- L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
Montebello® DLX Power Vent Direct-Vent Gas Fireplaces
P/N 506023-16 Rev. NC 08/2012
This manual is one of a set of two supporting this product. Refer to P/N
Ce manuel est disponible en francais, simplement en faire la demande. Numéro de la pièce 506223-49.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
506025-08
for Care and Operation Instructions.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
INSTALLATEUR : Laissez cette notice avec l'appareil. CONSOMMATEUR : Conservez cette notice pour consultation ultérieure.
MODELS
MDLX40IN-PV MDLX45IN-PV
Intertek Report No. 100513650PRT-001
Please read and understand these instructions
before starting installation.
ELECTRONIC:
®
Page 2
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
TABLE OF CONTENTS
Packaging .........................................Page 2
Introduction ......................................Page 2
General Information ..........................Page 2
Massachusetts Requirements ...........Page 4
Cold Climate Insulation .....................Page 5
Manufactured Home Requirements ..Page 5
Location ............................................Page 5
Vent Termination Clearances ............Page 6
Minimum Clearances to Combustibles Page 8
Pre-Installation Steps ........................Page 9
Typical Installation Sequence ...........Page 9
Detailed Installation Steps .................Page 9
Step 1. Framing ...............................Page 9
Fireplace and Framing Specifications Page 10
Step 2. Routing Gas Line ................Page 11
Proper Sizing of Gas Line ..................Page 11
Step 3. Install the Vent System .......Page 12
General Vent Information ..................Page 12
Power Vent Components...................Page 12
Vent Section Length Chart ................Page 13
Offset Installation ..............................Page 13
Horizontal Termination System .........Page 16
Installing Power Vent Termination ....Page 16
Step 4. Field Wiring .........................Page 18
Step 5. Removing Glass Door
Frame Assembly ...............................Page 20
Step 6. Connecting Gas Line ...........Page 21
Step 7 Install Firebox Liner ............Page 21
Step 8. Verifying Appliance
Operation ..........................................Page 21
Step 9. Installing Logs ...................Page 22
Step 10. Install/Remove Glass
Door Assembly .................................Page 24
Step 11. Burner Adjustments ............ Page 24
Finishing Requirements ....................Page 26
Step 12. Attaching Safety-in-
Operation Warnings ...................
Installation Accessories ....................Page 28
PACKAGING
The assembled vented gas fireplace is packaged with:
BOX 1—Fireplace:
Literature Kit (plastic bag shipped
inside rebox),
Bags of Glowing Embers, Platinum Embers,
and Volcanic Stone
Pull Screen
Door Modesty Shield
Adaptor with Probe Assembly
(1) Remote Control Kit and Receiver Kit
Page 27
BOX 2—Power Vent Components:
(1) Power Vent Termination
(1) Termination Adaptor
(1) Horizontal Firestop Assembly
(1) Vacuum Hose
(1) 11/32 in. Hose Clamp
(1) Strain Relief
(1) Bushing
(4) Insulated 1/4 in. Male Terminals
(2) #10 Ring Terminals
REQUIRED ACCESSORIES
The following accessories are required:
• One of the following Firebox Liner Kits:
a. Ceramic Liner Kit—Buff Rustic
b. Ceramic Liner Kit—Red Rustic
c. Porcelain Liner Kit—Black d. Ceramic Liner Kit—Red Herringbone e. Ceramic Liner Kit—Buff Herringbone
NOTE: Porcelain kits include side and back
panels. Optional for use with log sets. Required when using the contemporary burner/floor kit.
• One of the following Floor Options:
a. Oak Log Set (For use with fireplace as
shipped from factory only. Not for use with contemporary burner/floor kit.)
b. Contemporary Burner/Floor Kit
Contemporary Burner/Floor Kit requires
one of the following Media Kits:
i. Crushed Glass—Reective Black
ii. Crushed Glass—Platinum
iii. Crushed Glass—Reective Blue
iv. Crushed Glass—Goldfinger v. Crushed Glass—Copper
NOTE: The Contemporary Burner/Floor Kit
installation instructions are provided with the kit, and are not detailed in this manual.
INTRODUCTION
These Electronic appliances are designed to operate on natural gas and have an electronic
intermittent pilot ignition system. External 120 Volt AC electrical power is required to
operate these units. These vented gas fireplaces are sealed
combustion gas replaces designed for residential, manufactured home, and
commercial applications. Use Only These Approved Vent Components
These replaces are designed, tested and listed for operation and installation with, the following (4 1/2 in. inner and 7 1/2 in. outer) vent components only:
Secure Vent® Direct-vent system
components manufactured by Security
Chimneys International.
These approved vent system components
are labeled for identication. Do NOT use any
other manufacturer’s vent components with these appliances.
GENERAL INFORMATION
WARNING
Young children should be carefully supervised when they are in the same room as the appliance. Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to a fireplace or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
AVERTISSEMENT
Les jeunes enfants devraient être surveillés étroitement lorsqu’ils se trouvent dans la même pièce que l’appareil. Les tout petits, les jeunes enfants ou les adultes peuvent subir des brûlures s’ils viennent en contact avec la surface chaude. Il est recommandé d’installer une barrière physique si des personnes à risques habitent la maison. Pour empêcher l’accès à un foyer ou à un poêle, installez une barrière de sécurité; cette mesure empêchera les tout petits, les jeunes enfants et toute autre personne à risque d’avoir accès à la pièce et aux surfaces chaudes.
Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition.
Les enfants et les adultes devraient être infor-més des dangers que posent les températures de surface élevées et se tenir à distance afin d’éviter des brûlures
ou que leurs vêtements ne s’enflamment.
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERATION MAY VOID THE WARRANTY, CERTIFICATION AND LISTINGS OF THIS UNIT.
2
Page 3
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
Codes and Standards
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
WARNING
Failure to comply with these installation instructions will result in an improperly installed and operating appliance, voiding its warranty. Any change to this appliance and/or its operating controls is dangerous.
WARNING
Clothing or other flammable material should not be placed on or near the appliance.
AVERTISSEMENT
On ne devrait pas placer de vêtements ni d’autres matières inflammables sur l’appareil ni à proximité.
WARNING
Any safety screen or guard removed for servicing the appliance must be replaced prior to operating the appliance.
AVERTISSEMENT
Tout écran ou protecteur retiré pour permettre l’entretien de l’appareil doit être remis en place avant de mettre l’appareil en marche.
WARNING
Improper installation or use
Failure to position the parts in accordance with these diagrams or failure to use only parts specifi­cally approved with this appliance may result in property damage or personal injury.
Risque de dommages ou de blessures si les pièces ne sont pas installées conformément à ces schémas et ou si des pièces autres que celles spécifiquement approuvées avec cet appareil sont utilisées.
NOTE: Installation and repair should be done by a qualified service person. The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etcetera. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
Do not use these appliances if any part has been under water. Immediately call a qualified, professional service technician to inspect the appliance and to replace any parts of the control system and any gas control which have been under water.
Only trim kit(s) supplied by the manufacturer shall be used in the installation of this appliance.
WARNING
AVERTISSEMENT
Remarque : L’installation et la réparation devrait être confiées à un technicien qualifié. L’appareil devrait faire l’objet d’une inspection par un technicien professionnel avant d’être utilisé et au moins une fois l’an par la suite. Des nettoyages plus fréquents peuvent être nécessaires si les tapis, la literie, et cetera produisent une quantité importante de pous-sière. Il est essentiel que les compartiments abritant les commandes, les brûleurs et les conduits de circulation d’air de l’appareil soient tenus propres.
Ne pas utiliser cet appareil s’il a été plongé, même partiellement, dans l’eau. Appeler un technicien qualifié pour inspecter l’appareil et remplacer toute partie du système de commande et toute commande qui a été plongée dans l’eau.
These appliances comply with National Safety Standards and are tested and listed
by Intertek (Report No. 100513650) to Z21.50b-2009 (in Canada, CSA-2.22b-2009), and CAN/CGA-2.17-M91 (R2009) in both USA and Canada, as vented gas replaces.
These appliances are listed by Intertek for installation in bedrooms and manufactured (mobile) homes.
Installation must conform to local codes. In
the absence of local codes, installation must
comply with the current National Fuel Gas
Code, ANSI Z223.1/NFPA 54 (in Canada, the current CAN/CGA-B149.1 installation code).
The appliance, when installed, must be
electrically grounded in accordance with local
codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70— latest edition, or the Canadian Electrical Code,
CSA C22.1—latest edition.
Provide adequate clearances around air openings and adequate accessibility
clearance for service and proper operation.
Never obstruct the front openings of
the appliance.
These appliances are designed to operate on natural gas. The use of other fuels or combination of fuels will degrade the performance of this system and may be dangerous.
These appliances must not be connected to a
chimney or flue serving a separate solid fuel
burning appliance.
These electronic appliances are remotely controlled and feature an electronic
intermittent pilot ignition system. External electrical power is required to operate
these units.
These electronic models come standard with a remotely-modulated gas valve; flame
appearance and heat output cannot be controlled at the gas valve. The BTU Input
for these appliances is shown in Table 1.
Model No. Input (BTU/Hr) MDLX40IN-PV 26,500–42,000 MDLX45IN-PV 35,000–48,000
Table 1: Input (BTU/HR), Natural Gas
of this appliance can cause serious injury or death from fire, burns, explosion or carbon monoxide poisoning.
Seules les trousses de garniture fournies par le fabricant doivent être utilisées pour l’installation de cet appareil.
3
Page 4
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (LSM40/45EN-PV) • INSTALLATION INSTRUCTIONS
Gas Pressure—All Models
Tables 2 and 3 show the appliance inlet and
manifold gas pressure requirements.
Minimum Maximum
5.5 in. WC
(1.37 kPa)
10.5 in. WC
(2.62 kPa)
Table 2: Inlet Gas Supply Pressure
Low High
1.6 in. WC
(.40 kPa)
3.5 in. WC
(.87 kPa)
Table 3: Manifold Gas Supply Pressure
Test gauge connections are provided on the front of the gas control valve; identified IN for the inlet and OUT for the manifold side (see Figure 1).
The appliance and its appliance main gas
valve must be disconnected from the gas
supply piping system during any pressure testing of that system at test pressures in
excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its equipment shutoff valve during any
pressure testing of the gas supply piping system at test pressures equal to or less
than 1/2 psi (3.5 kPa).
Gas Valve Diagram
See Figure 1 for gas valve diagram.
Green Wire
(From DFC Wire
Harness)
Manifold (Out)
Test Port
Inlet (In) Test Port
Wire
(From DFC Wire
Harness)
Main Gas Inlet
3/8 in. NPT
PURGE CYCLE This is a power vented fireplace that requires household electrical power to operate. It will not operate during a power failure. When the fireplace is turned off, the exhaust blower will continue to operate for approximately fifteen (15) seconds after shutdown to expel the exhaust gases from the venting system.
Orifice Sizes—Sea Level To High Altitude
These appliances are tested and approved
for installation at elevations of 0–4500 ft (0–1370 m) above sea level, using the standard burner orice sizes (marked with an "*" in Table 4). For elevations above 4500 ft, contact your gas supplier or qualied service
technician.
Deration—At higher elevations, the amount of BTU fuel value delivered must be reduced by either:
• Using gas that has been derated by the
gas company.
• Changing the burner orice to a smaller size as regulated by the local Authorities Having Jurisdiction and by the (USA) National Fuel Gas Code NFPA 54/ANSI Z223.1—latest edition, or in Canada, the CAN/CGA-B149.1 code—latest edition.
Install the appliance according to the regulations of the local authorities having
jurisdiction, and the (USA) National Fuel Gas Code NFPA 54 / ANSI Z223.1—latest edition, or (Canada) CAN/CSA-B149.1—latest edition.
NOTE: Flame appearance will diminish 4% per one thousand feet of altitude.
Connect GTMS Wire Harness
Pressure Regulator Tower
Yellow Ground Wire (From DFC Wire Harness)
Model Orifice Size / Catalog Number
MDLX40IN-PV 0.125 in. (1/8 in.) * H7924 • MDLX45IN-PV 0.136 in. (#29) * H8141 •
* Standard size installed at factory
• Part /Cat. Number
Table 4: Burner Orifice Size Elevation 0–4500 ft (0–1370 m)
In Canada - CAN/CGA-2.17-M91 (R2009) (high altitude):
THE CONVERSION SHALL BE CARRIED OUT BY A MANUFACTURER’S AUTHORIZED REPRESENTATIVE, IN ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURER, PROVINCIAL OR TERRITORIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN/CGA-B149.1 OR CAN/CGA-B149.2 INSTALLATION CODES.
REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
These fireplaces are approved for installation
in the US state of Massachusetts if the following additional requirements are met:
• Install this appliance in accordance with Massachusetts Rules and Regulations 248 C.M.R.
• Installation and repair must be done by a plumber or gas tter licensed in the Commonwealth of Massachusetts.
• The exible gas line connector used shall not exceed 36 in. (92 centimeters) in
length.
• The individual manual shut-off must be a
T-handle type valve.
Massachusetts Horizontal Vent Requirements In the Commonwealth of Massachusetts,
horizontal terminations installed less than seven (7) feet above the finished grade must comply with the following additional requirements:
• A hard wired carbon monoxide detector with an alarm and battery back-up must be installed on the oor level where the gas replace is installed. The carbon monoxide detector must comply with NFPA 720, be ANSI/UL 2034 listed and be
ISA certified.
• A metal or plastic identication plate must be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade and be directly
in line with the horizontal termination.
The sign must read, in print size no less than one-half (1/2) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.
Figure 1: SIT Electronic Gas Valve
4
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 5
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks around your appliance with noncombustible
material and wherever cold air could enter the room. It is especially important to insulate
outside chase cavity between studs and under oor on which appliance rests, if oor is above ground level. Gas line holes and other openings should be caulked or stuffed with unfaced berglass insulation.
If the replace is being installed on a cement
Cross Corner
Application
Room Divider
Application
Recessed
Application
Island
Application
Flat
Application
Application
Flat on Wall
NOTE: When the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend beyond the front edge of the unit.
slab in cold climates, a sheet of plywood or other raised platform can be placed
underneath to prevent cold transfer to the fireplace and into the room. It also helps to sheetrock inside surfaces and tape for
maximum air tightness and caulk restops.
Horizontal
Termination
Drywall
MANUFACTURED HOME REQUIREMENTS
This appliance may be installed in an aftermarket permanently located, manufactured home and must be installed
in accordance with the manufacturer's instructions.
Cet appareil peut être installé cómme du matéri-el d'origine dans une maison
préfabriquée (É.U. seulement) ou mobile
et doit être installé selon les instructions
du fabricant.
Figure 2: Typical Installation
Fireplace
Top of Fireplace
Opening
Noncombustible
This appliance is only for use with the type of gas indicated on the rating plate. This
appliance is not convertible for use with
other gases.
Cet appareil doit être utilisé uniquement avec le type de gaz indiqué sur la plaque signalétique. Cet appareil ne peut être
converti à d'autres gaz.
CAUTION: Ensure that the cross members are not cut or weakened during installation. The structural integrity of the manufactured home floor, wall, and ceiling/roof must be maintained.
CAUTION: This appliance must be grounded to the chassis of the manufactured home in accordance with local codes or in the absence of local codes, with the National Electrical Code ANSI / NFPA 70—latest edition.
LOCATION
In selecting the location, the aesthetic and
functional use of the appliance are primary
concerns. However, vent system routing to the exterior and access to the fuel supply are
also important.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies (Figure 2).
En raison des températures élevées, l’appareil devrait être installé dans un endroit où il y a peu de circulation et loin du mobilier et des tentures (Figure 2).
The location should also be free of electrical, plumbing or other heating/air
conditioning ducting.
Be aware that this is a heat producing appliance. Objects placed above the unit are exposed to elevated temperatures.
Do not insulate the space between the appliance and the area above it.
The appliance must be mounted on a fully supported base extending the full
width and depth of the unit. The appliance
may be located on or near conventional construction materials. However, if installed on combustible materials, such as carpeting, vinyl tile, or other combustible material other than wood ooring, the appliance shall be installed on a metal or wood panel extending
the full width and depth of the appliance.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
5
Page 6
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
VENT TERMINATION CLEARANCES
These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according to local codes, these instructions, and the current (USA) National Fuel Gas Code ANSI-Z223.1 / NFPA 54, or (Canada) CAN/ CSA-B149.1 standards.
Horizontal Vent Termination Clearances
The horizontal vent termination must have
a minimum of 3 in. (76 mm) clearance to any overhead combustible projection of 2 1/2 in. (64 mm) or less (see Figure 3). For projections exceeding 2 1/2 in. (64 mm),
see Figure 4. For additional vent location restrictions refer to Figure 4 and Table 5 on Page 7.
2 1/2 in. or less in length
Combustible Projection
Greater than 2 1/2 in. in length
Ventilated or
Unventilated Soffit
See Figure 19 on Page 17 for the re­cess allowances, into exterior walls, of the power vent terminations.
24 in.
(610 mm)
Side Elevation View
Power Vent Termination
Combustible
Figure 3: Horizontal Vent Termination Clearances
Combustible Projection
3 in.
(76 mm)
18 in.
(457 mm)
6
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 7
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
NOTE: Local Codes Or Regulations May Require Different Clearances.
NOTE: Location Of The Vent Termination Must Not Interfere With Access To The Electrical Service.
H
3 ft.
X
A
3 ft.
M
I
E
D
X
V
K
Exterior Wall
Horizontal
Termination
B
V
L
X
= Air Supply Inlet
* See Item D in the Text Below.
*18”
24 in.
Inside Corner
of Termination
18”
36 in.
DETAIL D
F
V
Center Line
Ventilated Soffit
V
Window
V
C
A
= Vent Terminal
V
Fixed
Closed
Inside
Corner Detail
G
V
A
= 9 in. in U.S.
A
=12 in. in Canada
B
C
C
C
Operable
V
Window
B
B
= Area where Terminal is NOT permitted
B
A
J
Figure 4: Exterior Horizontal Vent Termination Clearance Requirements
Minimum Clearances Canadian Installation * US Installation **
Clearance above grade, veranda, porch, deck
A
or balcony.
B Clearance to window or door that may be opened.
C Clearance to permanently closed window
12 in. (30 cm) * 12 in. (30 cm) **
6 in. (15.2 cm) for appliances < 10,000 BTU/hr (3kW), 12 in. (30 cm) for appliances > 10,000 BTU/hr (3kW)
and < 100,000 BTU/hr (30kW), 36 in. (91 cm) for appliances > 100,000 BTU/hr
(30kW)*
12 in. (305 mm) recommended to prevent
window condensation
6 in. (15.2 cm) for appliances < 10,000 BTU/hr (3kW), 9 in. (23 cm) for appliances > 10,000 BTU/hr (3kW)
and < 50,000 BTU/hr (15kW), 12 in. (30 cm) for appliances > 50,000 BTU/hr
(15kW)*
9 in. (229 mm) recommended to prevent
window condensation
Vertical clearance to ventilated soft located above
D
the terminal within a horizontal distance of 36 in.
24 in. (61.0 cm) 24 in. (61.0 cm)
(91.4cm) from the center line of the terminal
E Clearance to unventilated soffit 24 in. (61.0 cm) 24 in. (61.0 cm)
F Clearance to outside corner 5 in. (12.7 cm) 5 in. (12.7 cm)
G Clearance to inside corner 36 in. (91.4 cm) 24 in. (61.0 cm)
Clearance to each inside of center line extended
H
above meter / regulator assembly
3 ft (91 cm) within a height of 15 ft above the meter / regulator assembly *
3 ft (91 cm) within a height of 15 ft above the meter / regulator assembly **
I Clearance to service regulator vent outlet 3 ft (91 cm) * 3 ft (91 cm) **
Clearance to non-mechanical air supply inlet to
J
building or the combustion air inlet to any other
appliance
6 in. (15.2 cm) for appliances < 10,000 BTU/hr (3kW), 12 in. (30 cm) for appliances > 10,000 BTU/hr (3kW)
and < 100,000 BTU/hr (30kW), 36 in. (91 cm) for appliances > 100,000 BTU/hr
(30kW)*
6 in. (15.2 cm) for appliances < 10,000 BTU/hr (3kW), 9 in. (23 cm) for appliances > 10,000 BTU/hr (3kW)
and < 50,000 BTU/hr (15kW), 12 in. (30 cm) for appliances > 50,000 BTU/hr
(15kW)*
K Clearance to mechanical air supply inlet 6 ft (1.83 m) * 3 ft (91 cm) above, if within 10 ft (3 m) horizontally**
Clearance above paved sidewalk or paved
L
driveway located on public property
7 ft (2.13 m) ‡ 7 ft (2.13 m) ‡
M Clearance under veranda, porch, deck or balcony 18 in. (46.0 cm) * ‡ 18 in. (46.0 cm) ** ‡
Table 5: Exterior Horizontal Vent Termination Clearance Requirements
* In accordance with the current CAN/CGA-B149.1 National Gas and B149.2 Propane Installation Code—Latest Editions. ** In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code—Latest Edition. ‡ A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings. *‡ Only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the oor.
V
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
7
Page 8
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
12 (305) MANTEL
10 (254) MANTEL
8 (203) MANTEL
6 (152) MANTEL
4 (102) MANTEL
4
(102)
14
(356)
12
(305)
10
(254)
2 (51) MANTEL
TOP OF APPLIANCE
6
(152)
NOTE: Hood shown as positioned in louvered front model. The hood position in the flush faced front model is lower than shown.
8
(203)
MANTEL CLEARANCES
Inches (mm)
MINIMUM CLEARANCES TO COMBUSTIBLES
Appliance And Vent Clearances
The appliance is approved with zero clearance to combustible materials
on all sides. Refer to Table 6 for minimum clearance values. For typical installations, see Figure 2 on Page 5.
Sides
Top Spacers
Floor
Back
Bottom of Appliance To C eili ng
Vent
1/2 in. (13 mm)
0 in. (0 mm) Spacers **
0 in. (0 mm) 0 in. (0 mm)
1/2 in. (13 mm)
0 in. (0 mm) Spacers
64 in. (1626 mm)
3 in. (76 mm) Top*
1 in. (25.4 mm) Sides & Bottom
Table 6: Appliance Minimum Clearances
Front
3 ft (0.9 m)
Table 7: Appliance Service Clearances
* 3 in. (75 mm) above any horizontal/inclined vent component.
** See Page 9, Step 1 for clearance requirements to the nailing flange located at each side of the unit and any screw heads adjacent to it.
Wall Finishes / Surrounds / Mantels
NOTE: Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined by the appliance front face (black sheet metal). Never allow combustible materials to be positioned in front of or overlapping the appliance face. See
Figure 6 and Figure 44 on Page 26.
Noncombustible materials, such as surrounds and other appliance trim, may be installed on the appliance front face with these exceptions: they must not cover any portion of the removable glass
panel.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel (see Figure 5). Mantels constructed of noncombustible materials may be installed at any height above the appliance. Minimum clearance requirements include any projections such as shelves, window sills, mantels, etc. above the appliance.
Figure 5: Minimum Mantel Clearances
Top View of
Fireplace
At 0 in. minimum side wall clearance, one combustible wall can project to any length.
Mantel Leg,
Trim, or Wall
3 1/2 in.
(89 mm)
Combustible materials may project beyond either side of the fireplace opening as long as they are kept within the shaded “Safe Zone” area.
45
o
Figure 6: Minimum Distance to Unprotected Side Wall
NOTE: We recommend the use of high temperature paint (rated 175 °F or higher) on the underside of the mantel.
8
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 9
5/8 in. Thick Drywall
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
PRE-INSTALLATION STEPS
The appliance is shipped with all gas controls and components installed and pre-wired.
Before installing the appliance, follow these steps:
1. Remove the shipping carton.
2. Remove the shipping pad, exposing the
front glass door.
3. Using a Phillips screwdriver, unfasten the two (2) screws located at the top of the glass
frame (see Figure 40 on Page 24). Tilt the top of the glass frame away from the unit.
Lift it carefully off the bottom door track and set the door aside, protecting it from
inadvertent damage.
4. Remove the embers and volcanic stone
from the control compartment.
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation is outlined below. However, each installation is unique and may result in variations to the steps described.
See the page numbers references in the
following steps for detailed procedures.
DETAILED INSTALLATION STEPS
Step 1. FRAMING
Frame these appliances as illustrated in Figure 8 on Page 10, unless the appliance is
to be installed in a corner. See Figure 9 on Page 11 for corner framing installations. All
framing details must allow for a minimum
clearance to combustible framing members
as shown in Table 6 on Page 8.
If the appliance is to be elevated above oor level, a solid continuous platform must be constructed below the appliance.
Headers may be in direct contact with the appliance top spacers but must not be supported by them or notched to t
around them.
The replace should be secured to the side framing members using the unit nailing anges—one top and bottom on each side
of the fireplace front (see Figure 7). Use 8d
nails or their equivalent.
Use Top Flange For 1/2 in. Thick Drywall
Front Of Fireplace
Use Center Flange For Flush Mount
Use Bottom Flange For
Note: The nailing flanges, combustible members and screw heads located in areas directly adjacent to the nailing flanges, are EXEMPT from the 1/2 in. clearance to combustible requirements for the firebox outer wrapper. Combustible framing may be in direct contact with the nailing flanges and may be located closer than 1/2 in. from screw heads and the firebox wrapper in areas adjacent to the nailing flanges. Frame the opening to the exact dimensions specified in the framing details of this manual.
Left Side Front Corner of Fireplace Shown (Right Side Requirements the Same).
Figure 7: Unit Secured by Nailing
Flanges to the Framing
Step 1. (Page 9) Construct the appliance
framing. Position the appliance within the framing and secure with
nailing brackets.
Step 2. (Page 11) Route gas supply line to
the right side.
Step 3. (Page 12) Install the vent system and
exterior termination.
Step 4. (Page 18) Field Wiring Connect 120 VAC electrical power to
the appliance receptacle.
Step 5. (Page 20) Remove glass door
assembly.
Step 6. (Page 21) Make connection to gas
supply.
Step 7. (Page 21) Install rebox liner kit. Step 8. (Page 21) Verify appliance operation. Step 9. (Page 22) Install volcanic stone,
glowing embers, and logs.
Step 10. (Page 24) Install glass door
assembly.
Step 11. (Page 24) Adjust burner to ensure
proper flame appearance.
Step 12. (Page 27) Attach Safety-in-
Operation Warnings.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
9
Page 10
E
A
B
D
Top View
Front View
5 3/32 in. (129)
Right Side View
14 1/8 in. 8 1/2 in. (216)
5 1/4 in. (133)
(359)
26 15/32 in.
(672)
C
25 29/32 in.
(658)
25 1/2 in.
(648)
7 in.
2 1/2 in. (64)
(178)
19 5/8 in.
(498)
Gas Inlet
(This
Side
Only)
Electrical
Inlet
8 3/8 in.
(213)
F
G
H
J
8 / 11 in.
Vent / Intake
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
A
B
C
VENT FRAMING TOP VENT WITH 2 FEET VERTICAL VENT AND ONE 90° ELBOW
Framing should be constructed
of 2x4 or larger lumber.
Inches (mm)
(641)
25 1/4 in.
1/2 A
10 1/2 in. (267)
7 in.
(178)
5 1/8 in.
(130)
12 1/8 in.
(308)
FIREPLACE AND FRAMING SPECIFICATIONS
Adaptor Plus 4 ft Vertical Vent (min.) and 90° Elbow
Model No. A B C *
MDLX40IN-PV
MDLX45IN-PV
Table 8: Framing Dimensions
* C = Adaptor Plus 4 ft Vertical Vent (min.) and 90° Elbow
in. 50 3/4 43 139 1/8
mm 1289 1092 3534
in. 56 7/8 48 144 1/8
mm 1445 1219 3661
10
Model
No.
MDLX40IN-PV
MDLX45IN-PV
in. 50 5/8 37 1/4 42 7/8 25 5/16 34 37 5/8 33 3/32 29 9/32 34 3/4
mm 1286 946 1089 643 864 956 840 744 883
in. 56 11/16 42 1/4 47 7/8 28 3/8 40 1/8 43 5/8 38 3/32 34 1/2 40 59/64
mm 1440 1073 1216 721 1019 1108 968 876 1039
A B C D E F G H J
Table 9: Fireplace Dimensions
Figure 8: Fireplace and Framing Specifications
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Vent Size
Co-axial DV
Vent Size
Diagrams, illustrations and photographs are not to scale – consult installation instructions. Product designs, materi­als, dimensions, specifications, colors and prices are subject to change or discontinuance without notice.
4 1/2 in. Inner 7 1/2 in. Outer
Notes
Page 11
C
Back wall of chase/enclosure
(including any finishing materials)
D
A
B
6 1/4 in.
(159 mm)
19 5/8 in.
(498 mm)
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
Length Inside Diameter
0–10 ft (0–3.1 m) 1/2 in. (12.7 mm)
10–40 ft (3.1–12.2 m) 1/2 in. (12.7 mm)
40–100 ft (12.2–30.5 m) 1/2 in. (12.7 mm) 100–150 ft (30.5–45.7 m) 3/4 in. (19.1 mm) 150–200 ft (45.7–61.0 m) 3/4 in. (19.1 mm)
Table 11: Schedule 40 Black Iron Pipe Inside Diameter
Gas lines must be routed, constructed
and made of materials that are in strict accordance with local codes and regulations.
We recommend hiring a qualied plumber
or gas fitter to correctly size and route the gas supply line to the appliance. Installing a gas supply line from the fuel supply to the appliance involves numerous considerations
Figure 9: Corner Framing with Power Vent Termination
of materials, protection, sizing, locations, controls, pressure, sediment, and more. Only a qualied installer should attempt sizing or
installing gas pipe.
Model No. A B C D
MDLX40IN-PV
MDLX45IN-PV
in. 50 5/8 83 5/8 59 1/8 41 7/8
mm 1286 2124 1502 1064
in. 56 3/4 89 7/8 63 1/2 44 7/8
mm 1441 2283 1613 1140
Table 10: Dimensions for Corner Framing with Power Vent Terminations
Step 2. ROUTING GAS LINE
Route a 1/2 in. (13 mm) gas line along the
inside of the right side framing as shown in Figure 10. Gas lines must be routed, constructed and made of materials that are in strict accordance with local codes and regulations.
All appliances are factory-equipped with a exible gas line connector and 1/2 in. shutoff
valve. (see Step 6 on Page 21).
Proper Sizing of Gas Line
Figure 10: Right-Front Corner of
Fireplace Framing
Properly size and route the gas supply line from the supply regulator to the area
where the appliance is to be installed per requirements outlined in the (USA) National Fuel Gas Code, ANSI Z223.1/NFPA 54—latest edition, or (Canada) CAN/CSA-B149.1—
latest edition.
Notes:
• All appliances are factory-equipped with a exible gas line connector and 1/2 in.
shutoff valve (see Figure 30 on Page 21).
• See Massachusetts Requirements on Page 4 for additional requirements for
installations in the state of Massachusetts
in the USA.
• The gas supply line should Not be
connected to the appliance until Step 6 (Page 21).
• A pipe joint compound rated for gas should be used on the threaded joints. Be
very careful that the pipe compound does not get inside the pipe.
• Installing a sediment trap in the supply line as close as possible to the appliance
is recommended.
• Check with local building ofcial for local code requirements.
Never use galvanized or plastic pipe. Refer to Table 11 for proper sizing of the gas supply
line, if black iron pipe is being used.
11
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 12
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
Step 3. INSTALL THE VENT SYSTEM
General Information
These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according to local codes, these instructions, and
the (USA) National Fuel Gas Code, ANSI Z223.1/NFPA 54—latest edition, or (Canada) CAN/CSA-B149.1—latest edition.
These fireplaces are designed, tested and listed for operation and installation only with Secure Vent® (SV4.5) and Secure Flex® Direct-Vent System Components, manufactured by Security Chimneys International. These approved vent system components are labeled for identification. DO NOT use any other manufacturer's vent components with these appliances.
Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier.
Dégagement conforme aux codes d'installation locaux et aux exigences du foumisseunde gaz.
Power Vent Components
Locate the replace as instructed in this manual. Make the following modications to add the components used with the Power Vent Kit. This kit may only be used in conjunction with Direct­Vent series electronic versions of Lennox Hearth Products Fireplaces. This installation must conform with local codes, or, in the absence of local codes, with the (USA) National Fuel Gas Code, ANSI Z223.1/NFPA 54—latest edition, or (Canada) CAN/CGA-B149.1—latest edition.
CAUTION: This power vent kit cannot be used with millivolt appliances. Use the kit only with the electronically controlled fireplaces listed for its use as shown in this document.
Item No.
1 604187-01 Adaptor Assembly With Probe 1
2 601970-01 Vacuum Hose 1 3 601451-01 Termination Assembly 1 4 74L61 SV Termination Adaptor (SV4.5RCH) 1
5 102010-01 Strain Relief—3/8 in. 1 6 H2246 Firestop Assembly (Horizontal) 1
7 102022-01 Hose Clamp—11/32 in. 2 8 P-8-7102 Snap Bushing 1 9 Ring Terminal—#10 2
10 Insulated 1/4 in. Male Terminal 4
Part
Number
Description Qty.
Table 12: Power Vent Kit Components
Use only approved venting components. See Approved Vent Components on Page 2.
These fireplaces must be vented directly to the outside.
The vent system may not service multiple
appliances, and must never be connected to a ue serving a separate solid fuel burning appliance. The vent pipe is tested to be run inside an enclosed wall (such as a chase). There is no requirement for inspection
openings in the enclosing wall at any of the
joints in the vent pipe.
Venting System
With the appliance secured in framing,
determine vent routing and identify the
exterior termination location. The following sections describe horizontal (exterior wall)
vent applications. A list of approved venting components is shown on Page 28.
1
2
3
5
7
4
6
8
8
9
12
Figure 11: Power Vent Kit Components
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 13
TRAHCHTGNELNOITCESTNEV
lanimoN
htgneLnoitceS
)sehcni(
6 21 42 63 84
T OOOOO TTTTT AAAAA LLLLL
QQQQQ TTTTT YYYYY
noitceSteN
)sehcni(htgneL
2/1-4 2/1-01 2/1-22 2/1-43 2/1-64
tneVfothgieH snoitceStneVforebmuN
sehcni tf
5.4 573.0 1 0 0 0 0 1
9 57.0 2 0 0 0 0 2
5.01 578.0 0 1 0 0 0 1
51 52.1 1 1 0 0 0 2
5.22 578.1 0 0 1 0 0 1
5.13 526.2 0 3 0 0 0 3
5.43 578.2 0 0 0 1 0 1
5.73 521.3 1 1 1 0 0 3
5.34 526.3 0 2 1 0 0 3
54 57.3 0 0 2 0 0 2
5.64 578.3 0 0 0 0 1 1
15 52.4 1 0 0 0 1 2
5.55 526.4 0 1 2 0 0 3
75 57.4 0 0 1 1 0 2
5.76 526.5 0 0 3 0 0 3
96 57
.5 0 0 0 2 0 2
5.37 521.6 1 0 0 2 0 3
5.97 526.6 0 1 0 2 0 3
18 57.6 0 0 0 1 1 2
5.19 526.7 0 0 2 0 1 3
39 57.7 0 0 0 0 2 2
5.79 521.8 1 0 0 0 2 3
5.301 526.8 0 0 0 3 0 3 801 9 1 0 0 3 0 4
711 57.9 1 0 5 0 0 6
5.811 578.9 1 1 0 3 0 5
621 5.01 0 0 1 3 0 4
5.031 578.01 1 0 1 3 0 5
531 52.11 0 0 6 0 0 6
5.931 526.11 0 0 0 0 3 3
5.241 578.11 1 0 0 4 0 5
441 21 1 0 0 0 3 4
5.451 578.21 1 1 0 0 3 5
5.061 573.31 0 2 0 0 3 5
5.271 573.41 0 0 0 5 0 5
771 57.41 1 0 0 5 0 6
681 5.51 0 0 0 0 4 4
5.691 573.61 0 1 0 0 4 5
702 52.71 0 0 0 6 0 6
5.112 526.71 1 0 0 6 0 7
5.712 521.81 0 1 0 6 0 7
5.922 521.91 0 0 1 6 0 7
5.23
2 573.91 0 0 0 0 5 5
5.142 521.02 0 0 0 7 0 7
642 5.02 1 0 0 7 0 8
252 12 0 1 0 7 0 8
TRAHCHTGNELNOITCESTNEV
lanimoN
htgneLnoitceS
)sehcni(
6 21 42 63 84
T OOOOO TTTTT AAAAA LLLLL
QQQQQ TTTTT YYYYY
noitceSteN
)sehcni(htgneL
2/1-4 2/1-01 2/1-22 2/1-43 2/1-64
tneVfothgieH snoitceStneVforebmuN
sehcni tf
5.4 573.0 1 0 0 0 0 1
9 57.0 2 0 0 0 0 2
5.01 578.0 0 1 0 0 0 1
51 52.1 1 1 0 0 0 2
5.22 578.1 0 0 1 0 0 1
5.13 526.2 0 3 0 0 0 3
5.43 578.2 0 0 0 1 0 1
5.73 521.3 1 1 1 0 0 3
5.34 526.3 0 2 1 0 0 3
54 57.3 0 0 2 0 0 2
5.64 578.3 0 0 0 0 1 1
15 52.4 1 0 0 0 1 2
5.55 526.4 0 1 2 0 0 3
75 57.4 0 0 1 1 0 2
5.76 526.5 0 0 3 0 0 3
96 57
.5 0 0 0 2 0 2
5.37 521.6 1 0 0 2 0 3
5.97 526.6 0 1 0 2 0 3
18 57.6 0 0 0 1 1 2
5.19 526.7 0 0 2 0 1 3
39 57.7 0 0 0 0 2 2
5.79 521.8 1 0 0 0 2 3
5.301 526.8 0 0 0 3 0 3 801 9 1 0 0 3 0 4
711 57.9 1 0 5 0 0 6
5.811 578.9 1 1 0 3 0 5
621 5.01 0 0 1 3 0 4
5.031 578.01 1 0 1 3 0 5
531 52.11 0 0 6 0 0 6
5.931 526.11 0 0 0 0 3 3
5.241 578.11 1 0 0 4 0 5
441 21 1 0 0 0 3 4
5.451 578.21 1 1 0 0 3 5
5.061 573.31 0 2 0 0 3 5
5.271 573.41 0 0 0 5 0 5
771 57.41 1 0 0 5 0 6
681 5.51 0 0 0 0 4 4
5.691 573.61 0 1 0 0 4 5
702 52.71 0 0 0 6 0 6
5.112 526.71 1 0 0 6 0 7
5.712 521.81 0 1 0 6 0 7
5.922 521.91 0 0 1 6 0 7
5.23
2 573.91 0 0 0 0 5 5
5.142 521.02 0 0 0 7 0 7
642 5.02 1 0 0 7 0 8
252 12 0 1 0 7 0 8
TRAHCHTGNELNOITCESTNEV
lanimoN
htgneLnoitceS
)sehcni(
6 21 42 63 84
T O T A L
Q T Y
noitceSteN
)sehcni(htgneL
2/1-4 2/1-01 2/1-22 2/1-43 2/1-64
tneVfothgieH snoitceStneVforebmuN
sehcni tf
672 32 0 0 0 8 0 8
972 52.32 0 0 0 0 6 6
5.082 573.32 1 0 0 8 0 9
5.982 521.42 0 1 0 0 6 7
5.103 521.52 0 0 1 0 6 7
5.013 578.52 0 0 0 9 0 9
5.523 521.72 0 0 0 0 7 7
033 5.72 1 0 0 0 7 8
543 57.82 0 0 0 01 0 01
5.943 521.92 1 0 0 01 0 11
273 13 0 0 0 0 8 8
5.973 526.13 0 0 0 11 0 11
5.814 578.43 0 0 0 0 9 9
564 57.83 0 0 0 0 01 01
5.574 526.93 0 1 0 0 01 11
084 04 1 1 0 0 01 11
294 14 1 0 1 0 01 21
5.994 526.14 0 0 0 1 01 11
405 24 1 0 0 1 01 21
5.115 526.24 0 0 0 0 11 11
5.025 573.34 0 2 0 1 11 41
135 52.44 0 2 2 0 11 51
5.835 578.44 1 0 0 2 11 41
945 57.54 1 0 2 1 11 51
855 5.64 0 0 0 0 21 21
5.265 578.64 1 0 0 0 21 31
5.865 573.74 0 1 0 0 21 31
375 57.74 1 1 0 0 21 41
5.085 573.84 0 0 1 0 21 31
5.985 521.94 0 1 2 2 01 51
5.595 526.94 1 1 1 0 21 51
5.406 573.05 0 0 0 0 31 31
516 52.15 0 1 0 0 31 41
5.526 521.25 0 2 0 0 31 51
5.136 526.25 1 0 1 0 31 51
5.736 521.35 0 1 1 0 31 51
156 52.45 0 0 0 0 41 41
5.556 526.45 1 0 0 0 41 51
276 65 0 2 0 0 41 61
876 5.65 1 0 1 0 41 61
5.886 573.75 1 1 1 0 41 71
5.796 521.85 0 0 0 0 51 51
207 5.85 1 0 0 0 51 61
5.217 573.95 1 1 0 0 51 71
027 06 0 0 1 0 51 61
TRAHCHTGNELNOITCESTNEV
lanimoN
htgneLnoitceS
)sehcni(
6 21 42 63 84
T O T A L
Q T Y
noitceSteN
)sehcni(htgneL
2/1-4 2/1-01 2/1-22 2/1-43 2/1-64
tneVfothgieH snoitceStneVforebmuN
sehcni tf
672 32 0 0 0 8 0 8
972 52.32 0 0 0 0 6 6
5.082 573.32 1 0 0 8 0 9
5.982 521.42 0 1 0 0 6 7
5.103 521.52 0 0 1 0 6 7
5.013 578.52 0 0 0 9 0 9
5.523 521.72 0 0 0 0 7 7
033 5.72 1 0 0 0 7 8
543 57.82 0 0 0 01 0 01
5.943 521.92 1 0 0 01 0 11
273 13 0 0 0 0 8 8
5.973 526.13 0 0 0 11 0 11
5.814 578.43 0 0 0 0 9 9
564 57.83 0 0 0 0 01 01
5.574 526.93 0 1 0 0 01 11
084 04 1 1 0 0 01 11
294 14 1 0 1 0 01 21
5.994 526.14 0 0 0 1 01 11
405 24 1 0 0 1 01 21
5.115 526.24 0 0 0 0 11 11
5.025 573.34 0 2 0 1 11 41
135 52.44 0 2 2 0 11 51
5.835 578.44 1 0 0 2 11 41
945 57.54 1 0 2 1 11 51
855 5.64 0 0 0 0 21 21
5.265 578.64 1 0 0 0 21 31
5.865 573.74 0 1 0 0 21 31
375 57.74 1 1 0 0 21 41
5.085 573.84 0 0 1 0 21 31
5.985 521.94 0 1 2 2 01 51
5.595 526.94 1 1 1 0 21 51
5.406 573.05 0 0 0 0 31 31
516 52.15 0 1 0 0 31 41
5.526 521.25 0 2 0 0 31 51
5.136 526.25 1 0 1 0 31 51
5.736 521.35 0 1 1 0 31 51
156 52.45 0 0 0 0 41 41
5.556 526.45 1 0 0 0 41 51
276 65 0 2 0 0 41 61
876 5.65 1 0 1 0 41 61
5.886 573.75 1 1 1 0 41 71
5.796 521.85 0 0 0 0 51 51
207 5.85 1 0 0 0 51 61
5.217 573.95 1 1 0 0 51 71
027 06 0 0 1 0 51 61
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
VENT SECTION LENGTHS
Determine the number of straight vent sections required. 4 1/2 in. (114 mm), 10 1/2 in. (267 mm), 22 1/2 in. (572 mm), 34 1/2 in. (876 mm) and 46 1/2 in. (1181 mm) net section lengths are available (see Table 14).
Offset Installation
Analyze the vent routing and determine
the quantities of vent sections and number of elbows required. Refer to Figures 16
and 17 on Page 15 showing vent run
requirements to aid in selecting the type of
vertical installation desired. Vent sections are available in net lengths of 4 1/2 in. (114 mm), 10 1/2 in. (267 mm), 22 1/2 in. (572 mm), 34 1/2 in. (876 mm) and 46 1/2 in. (1181 mm). Refer to the Vent Section Length Chart for an aid in selecting length
combinations. Elbows are available in 90° and 45° congurations. Refer to Figure 15 on Page 14 for the SV4.5 E45 and SV4.5 E90 elbow dimensional specications.
Where required, a telescopic vent section (SV4.5LA) may be used to provide the
installer with an option in installing in tight and confined spaces or where the vent run
made up of xed length pieces develops a joint in a undesirable location, or will not build up to the required length. The SV4.5LA
Telescopic Vent Section has an effective length of from 1 1/2 in. (38 mm) to 6 3/4 in. (171 mm). The SV4.5LA is tted with a dimpled end (identical to a normal vent
section component) and a plain end with 3
pilot holes. Slip the dimpled end over the
locking channel end of a standard SV4.5 vent component the required distance and secure
with three screws.
Maintain a minimum 1 in. (25 mm) clearance to combustible materials for all vertical elements. Clearances for all horizontal elements are 3 in. (76 mm) on top, 1 in. (25 mm) on sides and 1 in. (25 mm) on the bottom.
Model Effective Length
SV4.5L6 4 1/2 in. SV4.5L12 10 1/2 in. SV4.5L24 22 1/2 in. SV4.5L36 34 1/2 in. SV4.5L48 46 1/2 in.
Table 13: Effective Vent Length
Table 14: Vent Section Length
Note: Convert inches into metric equivalent measurement, as follows:
Millimeters (mm) = Inches x 25.4 Centimeters (cm) = Inches x 2.54 Meters (m) = Inches x .0254
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
13
Page 14
8 1/8 in.
(206 mm)
4 13/16 in.
(122 mm)
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
A. Frame ceiling opening—Use a plumb line from the ceiling above the appliance to locate
center of the vertical run. Cut and/or frame
an opening, 10 1/2 in. x 10 1/2 in. (267 mm x 267 mm) inside dimensions, about this center
mark (Figure 12).
10 1/2 in. min.
(267 mm)
10 1/2 in. min.
(267 mm)
Plumb Bob
Ceiling Framing
Figure 12: Framing Ceiling Opening
B. Attach adaptor (with probe) to appliance collar—Secure Vent® SV4.5 direct-vent
system components are unitized concentric pipe components featuring positive twist lock connections (see Figure 13).
All of the appliances covered in this document are fitted with collars having locking inclined channels. The dimpled end of the adaptor fits over the appliance collar to create the positive twist lock connection.
Align the dimple (four places) of the upper vent section with the opening of the locking incline channel on the lower vent section or appliance collar. Twist vent component clockwise to engage and seal until
Arrow
Adaptor on Appliance Collar or Vent Section
arrow and dimple align.
Dimple
Locking Incline Channel
Connected Vent Sections
Arrow
Figure 13: Attaching the Vent Adaptor
The unitized design of the Secure Vent®
components will engage and seal both the inner
and outer pipe without the need for sealant or
screws. If desired a #6 x 1/2 in. screw may be used at the joint, but it is not required as the
pipe will securely lock when twisted.
C. Attach vent components to each other—
Other vent sections may be added to the
previously installed section in accordance
with the requirements shown in Figures 16 and 17 on Page 15.
To add another vent component to a length
of vent run, align the dimpled end over
the inclined channel end of the previously
installed section, adjusting the radial
alignment until the four locking dimples are aligned with the inlets of the four incline channels of the previous section.
Push the vent component against the
previous section until it fully engages, then
twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels.
This seating position is indicated by the alignment of the arrow and dimple as shown in Figure 13.
D. Install firestop/spacer at ceiling—When
using Secure Vent, use SV4.5VF restop/ spacer at ceiling joists. If there is living space above the ceiling level, the restop/spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the restop/spacer must be installed on the top side of the joist. Route the vent sections
through the framed opening and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner.
Maintain 1 in. (25 mm) clearance to combustibles, framing members, and attic or ceiling insulation when running vertical chimney sections. Attic insulation shield (H3907) may be used to obtain the required clearances indicated here. See installation accessories on Page 28. The gap between the vent pipe and a vertical firestop may be sealed with noncombustible caulking.
E. Support the vertical vent run sections -
Blocking
Support Straps (Plumber's tape)
Support the vertical portion of the venting system every eight feet (2.4 m) above the fireplace vent outlet. One method of support
is by utilizing eld provided support straps (conventional plumber's tape). Secure the plumber's tape to the framing members
with nails or screws. Strap the tape around
the vent, securing the ends of the tape to the framing. If desired, sheet metal screws #6 x 1/2 in. length may be used to secure the
support straps to the vent pipe.
F. Change vent direction to horizontal/ inclined run—At transition from or to a
horizontal/inclined run, install the SV4.5E45 and SV4.5E90 elbows in the same manner as the straight vent sections. The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with the required direction of the next vent run element. Twist elbow
sections in a clockwise direction only so as to avoid the possibility of unlocking any of the previously connected vent sections (see
Figures 13 and 15).
Swivel Joint
(360° swivel)
SV4.5E45
45° Elbow)
Swivel Joint
(360° swivel)
SV4.5E90
90° Elbow)
Figure 15: Vent Elbow Sections
G. Continue installation of horizontal/ inclined sections—Continue with the
installation of the straight vent sections in
horizontal/inclined run as described in Step C. Install support straps every three feet
(914 mm) along horizontal/inclined vent runs using conventional plumber’s tape (Figure 16 on Page 15).
NOTE: Maintain the horizontal/inclined run in a straight, slightly elevated plane— approximately 1/4 in. per foot (20 mm per meter)—in a direction away from the fireplace. Smaller rise per foot run ratios are acceptable, down to at or near level. Use a carpenter’s level to measure from a constant surface and adjust the support straps as necessary.
To attach a vent component to the adaptor
on appliance collar, align the dimpled end over the adaptor collar, adjusting the radial
alignment until the four locking dimples are aligned with the inlet of the four inclined channels on the collar (refer to Figure 13). Push the vent component against the
collar until it fully engages, then twist the component clockwise, running the dimples
down and along the incline channels until they seat at the end of the channels.
14
8 ft (2.4 m)
Maximum
1/2 in. (13 mm) minimum clearance to combustibles
Figure 14: Supporting Vertical Vents
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
NOTE: Maintain the required clearances to combustibles: 1 in. (25 mm) at all sides for all vertical runs; and 3 in. (76 mm) at the top, 1 in. (25 mm) at sides, and 1 in. (25 mm) at the bottom for all horizontal/ inclined runs.
Page 15
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
VENT FIGURES
Notes:
• Secure Vent® components (rigid vent pipe and terminal) are shown.
• Two 45° elbows may be used in place of one 90° elbow.
• SV4.5VF (Secure Vent) firestop/spacer must be used anytime vent pipe passes through a combustible floor or ceiling. SV4.5HF (Secure Vent) firestop/spacer must be used anytime vent pipe passes through a combustible wall.
• Maintain the horizontal/inclined run in a straight, slightly elevated plane—approximately 1/4 in. per foot (20 mm per meter)—in a direction away from the fireplace. Smaller rise per foot run ratios are acceptable, down to at or near level. Use a carpenter’s level to measure from a constant surface and adjust the support straps as necessary.
Power Vent Termination
Exterior Wall
Horizontal / Inclined Run
SV4.5L 6 / 12 / 24 / 36 / 48
Vent Sections
Firestop / Spacer
Support Brackets
Ceiling
Building Support Framing
SV4.5E90 Elbow
Vertical Rise
66 ft max.
4 ft min.
Exterior Wall
Minimum
Vent Run
Horizontal
10 ft
Power Vent Termination
Figure 16: Typical Power Vent Routing
Maximum Number Of Elbows
Maximum Feet Of Run
Minimum Horizontal Run
Minimum Vertical Run
Maximum Vertical Rise
6
A + B 110 ft
B 10 ft
A
A 66 ft
Table 15: Power Venting
Maximum Horizontal
Venting 110 ft
Up to 6 Elbows
Floor
Venting Can Run Up To 3 ft Below Unit
Adaptor Plus 4 ft Vertical Vent
(min.) and 90° Elbow
Probe Adaptor (required)
A
(See Chart)
Probe Adaptor
(required)
Fireplace
B
Probe Adaptor
(Required)
Vertical Vent Pipe
Horizontal Vent Pipe
1.0 in. (25.4 mm)
Top—3 in. (76.2 mm)
Sides—1 in. (25.4 mm)
Bottom—1 in. (25.4 mm)
Table 16: Minimum Clearance to Combustibles
Figure 17: Power Vent Routing with Probe Adaptor
15
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 16
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
HORIZONTAL (OUTSIDE WALL) TERMINATION SYSTEM
See Figures 16 and 17 on Page 15
illustrating the various horizontal venting
congurations that are possible for use
with these appliances. Table 15 on Page 15 shows each system’s minimum and
maximum vertical and horizontal length values that can be used to design and
install the vent components in a variety of applications.
The horizontal vent system terminates
through an outside wall. Building codes limit or prohibit terminating in specic
areas. Refer to Figure 4 on Page 7 for location guidelines.
Secure Vent® SV4.5 direct-vent system components are unitized concentric pipe components featuring positive twist
lock connection, (refer to Figure 13 on Page 14). All of the appliances covered in
this document are fitted with collars having locking inclined channels. The dimpled end of the vent components fit over the appliance collar to create the positive twist lock connection.
A. Plan the vent run— Analyze the vent routing and determine
the types and quantities of sections required 4 1/2 in. (114 mm), 10 1/2 in. (267 mm), 22 1/2 in. (572 mm), 34 1/2 in. (876 mm) and 46 1/2 in. (1181 mm) net section lengths are available. Make allowances for elbows as indicated in
Figure 15 on Page 14.
Maintain a minimum 1 in. (25 mm)
clearance to combustibles on the vertical sections. Clearances for the horizontal runs are: 3 in. (76 mm) on top, 1 in. (25 mm) on sides, and 1 in. (25 mm) at the bottom.
B. Frame exterior wall opening—
Locate the center of the vent outlet on the
exterior wall according to the dimensions
shown in Figure 8 on Page 10.
Cut and/or frame an opening, 10 1/2 in.
x 12 1/8 in. (267 mm x 308 mm) inside dimensions, about this center.
C. Frame ceiling opening—If the vertical
route is to penetrate a ceiling, use a plumb line to locate the center above the appliance. Cut and/or frame an opening, 10 1/2 in. x 10 1/2 in.(267 mm x 267 mm) inside dimensions, about this center (see
Figure 12 on Page 14).
16
D. Attach vent components to appliance—
To attach a vent component to the
appliance collar, align the dimpled end over the collar, adjusting the radial
alignment until the four locking dimples are aligned with the inlets of the four incline channels on the collar (refer to Figure 13 on Page 14).
Push the vent component against the
collar until it fully engages, then twist the component clockwise, running the dimples
down and along the incline channels until they seat at the end of the channels. The unitized design of the Secure Vent
components will engage and seal both the
inner and outer pipe elements with the same procedure. Sealant and securing screws are
not required.
E. Attach vent components to each other—
Other vent sections may be added to the
previously installed section in accordance
with the requirements of the vent tables.
To add another vent component to a
length of vent run, align the dimpled
end of the component over the inclined channel end of the previously installed
section, adjusting the radial alignment
until the four locking dimples are aligned with the inlets of the four incline channels of the previous section. Push the vent component against the previous section
until it fully engages, then twist the
component clockwise running the dimples down and along the incline channels until they seat at the end of the channels.
This seating position is indicated by the alignment of the arrow and dimple as shown in Figure 13 on Page 14.
F. Install firestop/spacer at ceiling—
When using Secure Vent, use SV4.5VF
restop/spacer at ceiling joists. If there is living space above the ceiling level, the restop/ spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the restop/ spacer must be installed on the top side of the joist. Route the vent sections through the
framed opening and secure the firestop/ spacer with 8d nails or other appropriate
fasteners at each corner. The gap between the vent pipe and a restop can be sealed with noncombustible caulking.
Maintain 1 in. (25 mm) clearance to
combustibles, framing members, and attic or ceiling insulation when running vertical chimney sections.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
G. Support the vertical run sections—
On the vertical run, support the venting
system every eight feet (2.4 m) above the
fireplace vent outlet with field provided
support straps (Plumber's tape). Attach
the straps to the vent pipe and secure to
the framing members with nails or screws. H.Change vent direction—At transitions
from or to a horizontal/inclined run, install the SV4.5E45 and SV4.5E90 elbows in
the same manner as the straight vent
sections. The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with the required direction of the next vent run element. Twist elbow
sections in a clockwise direction only so as to avoid the possibility of unlocking any of the previously connected vent sections (see Figure 13 on Page 14).
I. Continue installation of horizontal/
inclined sections—Continue with the
installation of the straight vent sections
in horizontal/inclined run as described
in Step E. Install support straps every
three feet (1914 mm) along horizontal/
inclined vent runs using conventional
plumber’s tape (see Figure 16 on Page 15).
NOTE: Maintain the horizontal/inclined run in a straight, slightly elevated plane—approximately 1/4 in. per foot (20 mm per meter)—in a direction away from the fireplace. Smaller rise per foot run ratios are acceptable, down to at or near level. Use a carpenter’s level to measure from a constant surface and
adjust the support straps as necessary.
Installing Power Vent Termination
J. Assemble vent run to exterior wall—If
not previously measured, locate the center of the vent on the exterior wall. Prepare an opening as described in this manual. Assemble the vent system to
a point where the terminus of the last section is within 8 in. of the outside wall
surface where the power vent is to be
mounted (see Figure 18 on Page 17).
If the terminus of the last section is not
within this distance, use the telescopic vent section SV4.5LA, as the last vent
section. For wall thicknesses greater than that shown in Figure 19 on Page 17, refer to Table 17 on Page 17 for the additional venting components needed (in addition
to the termination and adaptor) for a
particular range of wall thicknesses.
K. Attach termination adaptor—Attach
the adaptor (SV4.5RCH—provided with the power vent kit) to the vent section telescoping vent section, or elbow, as
shown in Figures 18 and 19 on Page 17
in the same manner as any SV4.5
vent component.
Page 17
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
L. Install Firestop/Spacer at exterior wall—
Install SV4.5HF Firestop/Spacer, provided
with the power vent kit, over the opening at the exterior side of the framing, long side up, with the 3 in. spacer clearance
at the top as shown in Figure 18, and nail into place. The Firestop/Spacer may
also be installed over the opening at
the interior side of the framing. The gap
between the vent pipe and a restop can be sealed with noncombustible caulking.
(The Firestop/Spacer may also be installed
over the opening at the interior side of the
framing).
M. Install the Power Vent termination—
From outside the exterior wall, slide
the collars of the termination onto the adaptor until the termination seats against
the exterior wall surface to which it will be attached. Orient the housing of
the termination with the arrow pointed upwards. Secure the termination to the
exterior wall. The termination must not be recessed into the exterior wall or siding by more that the 1 1/4 in. (32 mm)
as shown in Figure 19.
The Power Vent termination has been designed to perform in a wide range of weather conditions. Terminations meet or exceed industry standards.
When selecting the location of termination, do not place the termination where water from eaves and adjoining roof lines may create a heavy flow of cascading water onto the termination. If the termination must be placed where the possibility of cascading water exists, it is the responsibility of the builder to direct the water away from the termination cap by using gutters or other means.
Carefully follow the Installation Instructions for the termination, including the use of silicone caulking where required.
Power Vent
1 in.
Termination
3 in.
(76 mm)
it is recommended that the Firestop/Spacer (SV4.5HF)
7 in.
5 1/8 in.
(130 mm)
(178)
12 1/8 in. (308 mm)
Adaptor
SV4.5RCH
6 to 48 in. Vent Section,
Telescopic vent section,
Elbow or Appliance Collar
To help minimize water infiltration
be installed on the exterior side of the wall.
10 1/2 in. (267 mm)
Note: Centerline of Vent Piping is
NOT the Same as the Centerline of
the Frame Opening.
See Figure 8 on Page 10 for Minimum Distance to Base of Appliance
Base of Appliance
(25.4 mm)
Figure 18: Installing Power Vent Horizontal Termination
*Use silicone caulking to seal the top and sides of the termination, up to the underlayment, stucco, or masonry wall surface.
*Caulk
*Caulk
Stucco
Siding
**For thicknesses greater than 9 1/4 in., see Table 17
Interior Surface of
Finished Wall
Maximum Extent of Vent Run Sections Relative to Exterior Surface of Framing
Last Vent Section.
Use Telescopic Vent
Section (SV4.5LA),
If Necessary
Power Vent
Termination
Adaptor SV4.5RCH
Maximum wall thickness
9 1/4 in.(235 mm)**
Exterior Surface of Siding
Exterior Surface of
Framing
6 in. to 9 1/4 in.
(152 to 235 mm)**
Power Vent Termination
1 1/4 in. Maximum Recess of the Square Termination into Exterior Finishing Material
Figure 19: Venting Connection and Exterior Wall Recessing of the Power Vent
Horizontal Termination
See Table 17 as an aid in venting component selection for a particular range of exterior wall thicknesses.
WARNING: The vent termination is hot while in operation and for a period of time following the use of the fireplace. Young children should be carefully supervised when in the same area as a hot termination.
Vent Components Required Exterior Wall Thickness
Termination Kit Only 6–9 1/4 in.(152–235 mm)
Termination Kit and 6 in. Vent Section (SV4.5L6) 10 3/4–14 in. (273–356 mm) Termination Kit and 12 in. Vent Section (SV4.5L12) 16 3/4–20 in. (426–508 mm) Termination Kit and Telescopic Section (SV4.5L12) 11 3/4–20 in. (299–508 mm)
Table 17: Venting Components Required for Various Exterior Wall Thicknesses— when Using the Power Vent Termination
17
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 18
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
Step 4. FIELD WIRING CAUTION: Label all wires prior to disconnection when
servicing controls. Wiring errors can cause improper and dangerous operation.
ATTENTION: Au moment de l'entretien des commandes, étiquetez tous les fils avant de les débrancher. Des erreurs de cáblage peuvent entraîner un fonctionnement inadéquat et dangereux.
Verify proper operation after servicing.
S'assurer que l'appareil fonctionne adéquatement une fois l'entretien terminé.
CAUTION: Ground supply lead must be connected to the wire attached to the green ground screw located on the outlet box. See Figures 27 and 28 on Page 20. Failure to do so will result in a potential safety hazard. The appliance must be electrically grounded in accordance with local codes or, in the absence of local codes, the (USA) National Electrical Code, ANSI/NFPA 70—latest edition, or the Canadian Electrical Code, CSA C22.1—latest edition.
Route Cable
NOTE: Electrical wiring must be performed by a qualified electrician.
• Install the strain relief in the hole provided on the right side of
fireplace for the electrical wiring (see Figure 20).
• Either use the intgrated junction box, or position an electrical junction box (not provided) within reach of the termination wiring pigtail (see Figure 23 on Page 19). Route the pigtail to the junction box as the termination is installed.
• Route 14 gauge AWG grounded solid wire Romex® or equally-sized stranded cable (e.g., SJOT) from the replace to the newly installed junction box near the termination. Ensure the cable is safety
plated to prevent damage from framing nails and finish drywall screws. Route it into the lower control compartment and cut to
length before installing the terminals. Install provided hardware on the ends of the cable. Cable is not provided. The provided crimp terminals are intended for use with stranded cable. If using Romex,
connect per National Electric Code or local code.
• Refer to Figure 25 on Page 19 and install the electrical hardware on the ends of the cable. Male terminals on the Black and White wires, and ring terminals on the ground wire.
• Using standard electrical practices and the terminals provided, connect the three wires of the cable to the termination pigtail within the Electrical junction box. Ensure ground.
• The replace end of the cable will be addressed in Connecting
The Power Vent To The Fireplace Control System.
Probe (1 *)
Hose Clamp (7 *)
Vacuum Hose (2 *)
Adaptor Assembly
* See Figure 11 on Page 12
Figure 21: Vacuum Hose Connection to Probe
Vacuum Hose
Pressure Switch
Strain Relief
14 Gauge Grounded Romex or
similar
Stranded
Cable
Vacuum
Hose
Snap
Bushing
Wall Switch
Harness
Figure 20: Routing Wiring
18
Pressure switch is located behind the panel on the right side of firebox
Right Side
of Fireplace
Firebox
Vacuum Hose
Junction Box
Pressure Switch
NOTE: Pressure switch style may vary from that shown.
Figure 22: Vacuum Hose Connection to Pressure Switch
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 19
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
Wiring—Fireplace (See Figures 27 and 28 on Page 20)
NOTE: These electronic appliances must be connected to the main power supply. The gas valve is set in place and pre-wired at the factory.
1. Route a 3-wire 120 Vac 60 Hz 1ph power supply to the appliance
junction box.
2. Remove the electrical inlet cover plate from the side of the unit by
removing the plate securing screws (see Figure 8 on Page 10).
3. Remove the cover plate knockout and then feed the power supply
through the knockout opening and into the unit junction box.
4. Connect the black power supply to the power outlet red pigtail lead and the white power supply to the common terminal of the outlet as shown in Figures 27 and 28 on Page 20.
5. Connect the ground supply to the pigtail lead attached to outlet green ground screw.
6. Wall-mounted ON/REMOTE/OFF burner control switch and remote
control kits may be used. Mount the switch in a convenient location
on a wall near the fireplace.
NOTE: One end of the supplied wire (15 ft) is factory-connected and the other end is attached to the side of the unit.
CAUTION: Do Not connect the ON/REMOTE/OFF wall switch to a 120 V power supply.
8. Turn the wall-mounted ON/REMOTE/OFF burner control switch to
the OFF position.
9. After the wiring is complete, replace the cover plate.
• Refer to Figure 26 and install the electrical hardware on the fireplace end of the cable. Male terminals (#10) on the Black and White wires, and ring terminals (#9) on the ground. The termination end of the cable will be connected to the termination with wire nuts (not provided).
• Refer to Figure 26 to connect the three wires of the cable to the termination. Ensure the ground ring terminal is grounded beneath a structural screw as shown. Attach the junction box cover to the
termination with the screw previously removed.
• The replace end of the cable will be addressed in Connecting The Power Vent To The Fireplace Control System.
Black and White
Cable
Ground Wire
10
9
Figure 24: Cable Connections
Wiring—Power Vent Termination
Alternate Instructions (For use when access to the termination is easy
and a secondary electrical junction box installation is not desired).
• Remove the junction box cover from the termination by removing
the attaching screw (see Figure 23).
• Loosen the strain relief on the termination shown in Figure 25. Pull the pigtail in and shorten it to t within the junction box cover.
WARNING: Crimp connectors may be used on stranded cables (such as SJOT cable) only. Solid wire Romex must be connected per the National Electric Code, NEC 70—latest version, or local codes.
• Route 14 gauge AWG grounded solid wire Romex or equally sized stranded cable (e.g., SJOT) from the replace to the newly installed junction box near the termination. Ensure the cable is safety
plated to prevent damage from framing nails and finish drywall screws. Route it into the lower control compartment and cut to
length before installing the terminals. Install provided hardware on the ends of the cable. Cable is not provided. The provided crimp terminals are intended for use with stranded cable. If using Romex,
connect per National Electric Code or local code.
Strain Relief
Figure 25: Back of Termination
Pigtail Wires Cut
Off and Shortened
Cable
Ground Cable to The Termination
Pigtail
Junction Box Cover
Figure 23: Bottom of Termination
Attaching Screw
Figure 26: Junction Box Cover Removed
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Strain Relief Holding Cable
Wire Nuts
19
Page 20
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
Field Wired
Junction Box
Tab Intact
Tab Intact
n e e r G - d n u o r G
e t i h W - l a r
t u e N
120 VAC - Black
Green Ground
White
Green
Neutral
Side
Hot
Side
Red
Black
ELECTRONIC WIRING DIAGRAM
(Schematic representation only)
COLOR CODE: B = Black BB = Brown w/Black Stripe BG = Brown w/Green Stripe BL = Blue BR = Brown G = Green GY = Gray O = Orange R = Red W = White Y = Yellow
Note: On models without pressure
switch, these
connectors are
plugged together.
Air Pressure Switch
BR
Power Vent Only
Main Wire
Harness
G
Y
Battery Holder with Switch
Battery Holder w/Switch ON/ Remote /OFF
Y
Battery Holder Wire Harness
GR
ON/Remote/OFF
B
O
R
BL
O
G
BL
G
W
R
B
R
B
WH
B
W
Power Vent Blower
Power Vent Models Only
885 Valve
G
Optional Split Flow
Reset Switch
(See instructions.)
B
Pilot Tube
Control Module
IPI Pilot
Fuse
Flame Sensor
Spark Electrode
B
B
Ground Y
B
W
G
Main Power Cord
580489-01
Figure 27: Electronic Wiring Diagram
Figure 28: Junction Box Wiring—
20
120 V, 60 hz, 1-phase
Step 5. REMOVE THE GLASS DOOR ASSEMBLY
Refer to Figure 40 on Page 24 and remove the front glass door assembly as follows:
To remove the rescreens, lift up the center
of the rod to disengage it from the center
WARNING
bracket, bend down at center, hold left side with hand until it disengages from left side,
Handle this glass with extreme care! Glass is susceptible to damage— Do not scratch or handle roughly.
Do not attempt to substitute the materials used on this door, or replace cracked or broken glass with any
being careful not to scratch the paint. Slowly
remove the rod from the right side.
Using a Phillips screwdriver, unfasten the two (2) screws located at the top of the glass door assembly.
Tilt the glass door assembly at the top away from the unit. Lift it carefully off the bottom door track and set the glass door assembly aside, protecting it from inadvertent damage.
materials other than those provided by the appliance manufacturer.
The glass door of this appliance must only be replaced as a complete unit as provided by the manufacturer. Do not attempt to replace broken, cracked, or chipped glass separately.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 21
Gas Valve
3/8 in. NPT x
Flare Fitting
3/8 in. Flex Tubing
3/8 in. Nipple
3/8 in. Union
3/8 in. Close
Nipple
3/8 in. Shut-off Valve
1/2 x 3/8 in.
Reducer
Gas
Stub
1/2 x 3/8 in. Flare
Shut-off Valve
Gas Solid Line Connector
Gas Flex Line Connector
*Sediment Trap
3 in.
Min
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
Step 6. CONNECTING GAS LINE
All codes require a shut-off valve mounted in
the supply line. The orientation of the shut­off valve should face the front. Figure 30 illustrates two methods for connecting the gas supply. A Sediment Trap is recommended
to prevent moisture and debris in gas line
from damaging the valve.
The ex-line method is acceptable in the USA
where local codes permit. Installation must
be in compliance with local codes. These appliances are equipped with a gas ex-line
for use in connecting the unit to the gas line. See Figure 30 for ex-line description.
A manual shutoff valve is also provided with
the ex-line. The gas control valve is located
on the right side of the unit.
When using solid gas line connector, access the valve by removing the front door assembly on the valve access side and the
access plate (see Figure 29).
The electronic control valve has a 3/8 in.
(10 mm) NPT thread gas supply inlet.
Secure all joints tightly using appropriate tools and sealing compounds.
NOTE: Using a soapy water solution is
an effective leak test solution but it is not recommended, because the soap residue that is left on the pipes/fittings can result in corrosion over time.
A. Light the appliance (refer to the
lighting instructions label in control
compartment or in the Care and Operation
instructions manual).
B. Brush all joints and connections with the
gas leak test solution to check for leaks.
If bubbles are formed, or gas odor is
detected, turn the unit off. Either tighten or refasten the leaking connection, then retest as described above.
C. When the gas lines are tested and leak
free be sure to rinse off the leak testing
solution.
D. Re-install the access plate, making certain
the gasket has not been damaged.
Note: The gas supply line must be installed in accordance with building codes by a qualified installer approved and/ or licensed as required by the locality. In the Commonwealth of Massachusetts, installation must be performed by a licensed plumber or gas fitter.
Bring the shutoff valve on the end of the ex-line over to the hard pipe and tighten with wrenches from above through the rebox opening.
Right Side
Modesty Panel
Access Plate
Gas Shutoff
Valve
Gas Valve
Figure 29: Fireplace Right Side
TEST ALL CONNECTIONS FOR GAS LEAKS (FACTORY AND FIELD)
Never use an open flame to check for leaks.
Turn on gas supply and test for gas leaks using a gas leak test solution (also referred to as
bubble leak solution).
WARNING
Figure 30: Gas Connection
Step 7. INSTALL FIREBOX LINER KIT
Install the rebox liner kit per the
included instructions.
Step 8. VERIFYING APPLIANCE OPERATION
Turn on burner then observe the individual tongues of ame on the burner. Make sure all
ports are open and producing flame evenly
across the burner. If any ports are blocked, or partially blocked, clean out the ports.
With gas line installed run initial system
checkout before closing up the front
of the unit. Follow the pilot lighting instructions provided.
NOTE: Lighting Instructions are also found on the literature tag tied to the bracket above the gas valve. To access the tag, reach into the right side opening.
When rst lighting the appliance, it will take
a few minutes for the line to purge itself of
air. Once purging is complete, the pilot and burner will light and operate as indicated in the instruction manual. Subsequent lighting of the appliance will not require such
purging. Inspect the pilot flame (remove
logs, if necessary, handling carefully).
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Electronic Appliance Checkout
To light the burner, turn the ON/REMOTE/
OFF wall switch or remote control to the ON position. Ensure the igniter lights the pilot. The pilot flame should engulf the flame sensor as shown in Figure 31.
NOTE: The control must detect the pressure switch in the open state, at startup, and then close after the blower starts.
Igniter Rod
Flame Sensor
Pilot Nozzels
Pilot Hood
Figure 31: Electronic Pilot
Assembly—Proper Pilot Flame Appearance
21
Page 22
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
Step 9. INSTALL VOLCANIC STONE, GLOWING EMBERS, AND LOGS
NOTE: If installing the contemporary burner/floor kit, skip this step and instead refer to the instructions provided with the kit.
WARNING
DO NOT operate this appliance without the required accessories properly installed:
—floor (log set or contemporary kit), and —panels (ceramic or porcelain).
WARNING
• DO NOT attempt to install the logs until the
appliance installation has been completed, the gas line connected and tested for leaks and the initial burner operation has been checked out.
• The size and position of the log set was
engineered to give the appliance a safe, reliable and attractive flame pattern. Any attempt to use a different log set in the fireplace will void the warranty and will result in incomplete combustion, sooting, and poor flame quality.
• Logs get very hot and will remain hot up to one
hour after gas supply is turned off. Handle only when logs are cool. Turn off all electricity to the appliance before you install grate, volcanic stone, embers and logs.
• This appliance is not designed to burn wood. Any
attempt to do so could cause irreparable damage to the appliance and prove hazardous to your safety.
• If logs are not installed according to the log
installation instructions, flame impingement and improper combustion could occur and result in soot and/or excessive production of carbon monoxide (CO), a colorless, odorless, toxic gas.
Cat. No. Model Description
88L53 FGE Bag of Glowing Embers 80L42 FDVS Bag of Volcanic Stone
H8312 PGE Bag of Platinum Embers
Table 18: Firebox Accessories
Step 5. Position the individual logs as shown in Figures 36
through 39. Logs should be placed in the order shown. Place
logs 2 and 3 against the pins on the grate, NOT over them.
Proper log and twig placement is critical to encourage
outstanding flame appearance and prevent sooting. When
positioned properly, as shown, twigs will be positioned between ame peaks and will not impinge any ames.
Volcanic Stone
Figure 32: Volcanic Stone Placement
(MDLX45IN-PV Shown)
Figure 33: Separating Glowing Embers
Step 1. Install the ceramic or porcelain panels per the instructions
provided in kit (P/N 506019-91).
Step 2. Place volcanic stone around the burner (the entire bag of
volcanic stone will NOT be used). DO NOT PLACE VOLCANIC
STONE ON THE BURNER. See Figure 32.
Step 3. Separate the glowing embers (rockwool) into pieces about the
size of a quarter (see Figure 33). Keep the pieces uffed, not matted. Distribute these pieces over the burner as shown in
Figure 34. Do not use more than is necessary. When properly
positioned, the glowing embers will cover approximately 75% of the burner.
Step 4. Distribute the platinum embers over the burner as desired. Do
not use more than is necessary.
NOTE: Excessive use of embers may result in sooting or poor flame. This appliance is provided with enough embers for several applications, do not use all that is in a new bag. For best glowing effect, replace the ember material annually. Replacement volcanic stone, glowing embers,
22
and platinum embers are available (see Table 18).
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Glowing Embers (Rockwool)
Figure 34: Glowing Ember Placement
Page 23
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
MDLX40IN-PV and MDLX45IN-PV Log Placement
2
3
6
7
5
Log Number Description
1 Log, Center 2 Log, Rear 3 Log, Center/Left
4 Log, Center/Right
5 Log, Rear/Top 6 Log, Front/Left 7 Log, Front/Center
Figure 35: Complete Log Set
2
1
4
Align Groove At The Bottom Of Log (2) Over The Grate And Push It Towards The Rear.
Figure 37: Placing Log 2
3
4
Align Two Holes At Bottom Of Log (1) Over The Pins On The Gas Burner.
Figure 36: Placing Log 1
1
Engage Logs (3 & 4) With The Grate Pins And Align Groves At The Bottom Of The Logs Over The Grate.
Figure 38: Placing Logs 3 and 4
6 5
Engage Log (6) With The Grate Pin And Align Groove At The Bottom Of The Log Over The Grate.
Align Hole At Bottom Of Log (5) Over The Pin On Log (2).
Engage Log (7) With The Pin On Log (4).
7
2
4
Figure 39: Placing Logs 5, 6 and 7
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
23
Page 24
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
Step 10. INSTALLATION AND REMOVAL OF GLASS DOOR
WARNING
When reinstalling the glass
door, the door latch screws must be securely tightened to prevent the glass door from falling out, which could potentially cause damage and possible injury.
Do not attempt to substitute
the materials used on this door, or replace cracked or broken glass.
Handle this glass with
extreme care! Glass is susceptible to damage—Do not scratch or handle roughly while reinstalling the glass door frame.
The glass door of this
appliance must only be replaced as a complete unit as provided by the manufacturer. Do not attempt to replace broken, cracked or chipped glass separately.
Do not attempt to touch
the front enclosure glass with your hands while the fireplace is in use.
WARNING
Do not operate appliance with the glass front removed, cracked or broken.
AVERTISSEMENT
Ne pas utiliser l'appareil si le panneau frontal en verre n'est pas en place, est craqué ou brisé.
WARNING: Any safety screen or guard removed for servicing the appliance must be replaced prior to operating the appliance.
AVERTISSEMENT : Tout écran ou protecteur retiré pour permettre l’entretien de l’appareil doit être remis en place avant de mettre l’appareil en marche.
Installing Glass Enclosure Panel (see Figure 40)
To install the front glass door assembly, proceed as follows:
1. Retrieve the glass door assembly. Visually inspect the gasket on the backside of the panel. The gasket surface must be clean, free
of irregularities and seated firmly.
2. Position the door frame in front of the
rebox opening and engage the bottom ange over the rail at the bottom of the rebox opening.
3. Swing the door up and back. Ensure the
gasket seats evenly as the door draws shut. Engage the nut insert and fasten with two screws to secure the door.
4. Install the door modesty shield on top ange glass door as follows: grab the door modesty shield with both hands, with the
open hem going down and engage it with the
upper lip of the glass door frame by pushing it all the way down. Make sure the installed
shield is firmly in place.
5. With the firescreen hanging on the screen
rod, drop in the right side of the rod to the right
modesty panel. Then drop in the left side of the rod through the slot of the left modesty panel.
Make sure that the rod is supported by the bracket in the center of the replace.
WHEN INSTALLING THE GLASS DOOR, SECURELY TIGHTEN THE LATCH SCREWS— SEE THE FIRST WARNING ON THIS PAGE.
When installing the glass door, ensure the spacing on both sides are equal.
Top Flange Glass door assembly
Latch Screws
Glass Door Latch (2)
Step 11. BURNER ADJUSTMENTS
Flame Appearance and sooting
Proper flame appearance is a flame which is
blue at the base and becomes yellow-orange in the body of the ame. When the appliance is rst lit, the entire ame may be blue and
will gradually turn yellow-orange during the first 15 minutes of operation. After 15
minutes of operation, if the ame is blue, or if
the flame is orange with evidence of sooting
(black tip), the air shutter opening may need to be adjusted.
If the air shutter opening is closed too far,
sooting may develop. Sooting is indicated
by black puffs developing at the tips of very long orange ames. Sooting results in black deposits forming on the logs, appliance inside surfaces and on exterior surfaces adjacent to the vent termination.
Sooting is caused by incomplete combustion in the ames and lack of combustion air
entering the air shutter opening. To achieve a warm yellow-orange flame with an
orange body that does not soot, the shutter opening must be adjusted between these
two positions.
Air Shutter Adjustment Guidelines
• If there is smoke or soot present, rst
check the log set positioning to ensure that the flames are not impinging on any of the logs. If the log set is properly positioned and a sooting condition still
exists, then the air shutter opening should be increased.
• The more offsets in the vent system, the larger the air shutter opening will need to be.
• An appliance operated with the air shutter opened too far, may have ames that appear blue and transparent. These weak, blue and
transparent flames are termed anemic.
The following chart is provided to aid in
correctly adjusting the air shutter.
Amount of
Primary Air
If air shutter is closed too far
If air shutter is open too far
Flame
Color
Flame will be orange
Flame will be blue
Air Shutter
Adjustment
Air shutter gap should be increased
Air shutter gap should be decreased
Table 19: Air Shutter Adjustment
Only doors certified with the appliance shall be used.
Seules des portes certifiées pour cet appareil doivent être utilisées.
WARNING: DO NOT abuse glass door by striking or slamming shut.
24
Firebox Floor
Glass Door Assembly
Figure 40: Installing the Glass Door
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 25
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
Air Shutter
Opening
Burner
Orifice
Gas
Valve
Venturi
Venturi
Burner Air Shutter Adjustment Procedure
WARNING
Air shutter adjustment should only be performed by a qualified professional service technician.
Ensure that the front glass
door assembly is in place and sealed After adjustment.
Main Burner Factory Air Shutter
Opening Setting—Inches (millimeter)
Model Nat.Gas
MDLX40IN-PV MDLX45IN-PV
1/8 in. (3.18 mm) 1/8 in. (3.18 mm)
CAUTION
Soot will be produced if the air shutter is closed too much. Any damage due to carboning resulting from improperly setting the air shutter is not covered under the warranty.
To adjust the ame, move the adjustment air shutter (located on the lower venturi) back or
forward to increase or reduce the air shutter
opening, respectively. Position the air shutter
to the factory setting as shown in Figure 41.
Allow the burner to operate for at least 15 minutes. Observe the ame continuously.
If it appears weak or sooty as previously
described, adjust the air shutter until the
flame appearance is as desired.
When satisfied that the appliance operates
properly, nish the installation. Leave the ON/REMOTE/OFF wall switch in the REMOTE
position and turn the remote switch OFF.
Use the remote to adjust the flame height as desired.
Figure 41: Air Shutter Adjustment
Contemporary Media Shown (MDLX40)
Figure 42: Burner Flame Appearance
Rustic Oak Logs Shown (MDLX45)
Figure 43: Burner Flame Appearance
25
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 26
Glass Door
Assembly
Fireplace
Finish Combustible Or Non-Combustible Material
Bottom Of Fireplace
1/8 in. Minimum
Door Track
Finish Combustible Or Non-Combustible Material
Front Face Of Fireplace
Floor Panel
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
FINISHING REQUIREMENTS Wall Details
Complete the finished interior wall. To install the appliance facing
ush with the nished wall, position framework to accommodate the
thickness of the finished wall (Figure 44).
3 in. Min.
(76 mm)*
Combustible Finished Wall Materials
Header (2x4’s)
Combustible materials are allowed above this point on the face of the appliance.
8 3/8 in. Min.
(213 mm)
The gray shaded area must be non-combustible or Dura Rock
1 in.
(25.4mm)
Minimum
Top of
Appliance
Spacers
Adaptor Plus 4
Feet Vertical
Vent (Min.) & 90° Elbow
Noncombustible materials, such as surrounds and other appliance trim, may be installed on the appliance front face with the exceptions.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel (see Figure 5 on Page 8). Mantels constructed of noncombustible materials may be installed at any height above the
appliance opening.
Combustible materials may project beyond the side of the replace opening
as long as it is kept within the shaded area illustrated in Figure 6 on Page 8.
Top of Door Frame
Fireplace (right side)
* Insulation is NOT ALLOWED in the clearance zones around vent compo-
nents. Keep this area free from combustible materials.
Figure 44: Finished Wall
A hearth extension is not required with this appliance. If a hearth extension is used, there are two methods of installation:
Combustible or noncombustible nish material may abut the front face
of the fireplace and the floor panel (see Figure 45).
Combustible or noncombustible nish material may be positioned below the replace (see Figure 46). Remove the oor panel as shown in Figure 45 by removing the screws on the right side of the panel and sliding the left side away from the tab. Discard the screws and
floor panel.
Figure 45: Hearth Extension
NOTE: There must be least a 1/8 in. gap between the bottom of the door track and the surface of the finish material.
26
Figure 46: Hearth Extension Profile
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 27
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
Step 12. INSTALLER INSTRUCTIONS—ATTACHING SAFETY-IN-OPERATION WARNINGS It is the installers responsibility to ensure these warnings are properly affixed during installation. These warning labels are a
critical step in informing consumers of safe operation of this appliance.
ATTACHING SAFETY-IN-OPERATION WARNINGS
It is required that the set of safety instruction labels that have been furnished with the replace be afxed to the operation and control points of the replace. A safety instruction label must be afxed to the receiver wall switch plate where the
fireplace is turned on and off (See Figure A) and on the remote control handheld transmitter (See
Figure B). To properly complete the installation of this replace, locate the multi-lingual adhesive labels provided with the Care and Operation Instructions and proceed as follows:
1. Locate the wall receiver that controls the fireplace (verify the switch operates the
replace by turning it on and off). Clean the
wall receiver plate thoroughly to remove any
dust and oils. Afx the label to the surface of
the plate of the wall receiver that controls the fireplace (Figure A). Choose the language
primarily spoken in the home. If unknown, afx the English language label.
2. Locate the remote control transmitter and clean it thoroughly to remove any dust and
oils. Afx the label to the surface of handheld transmitter (Figure B). Choose the language primarily spoken in the home. If unknown, afx the English language label.
3. If you are unable to locate the labels, please call Lennox Hearth Products or your nearest Lennox Hearth Products dealer to receive additional safety instruction labels free of
charge.
Cat. No. H8024 Replacement Label Kit
LENNOX HEARTH PRODUCTS 1-800-655-2008
NOTE: English is red text on clear label. French and Spanish are white text on black label.
SAFETY LABEL
DIAGRAMS
APPOSITION DES MISES EN GARDE RELATIVES À LA SÉCURITÉ D’UTILISATION
Il est impératif que le jeu d’étiquettes de sécurité qui
ont été fournies avec le foyer soient collées à côté
des dispositifs de contrôle du foyer. Une étiquette de sécurité doit être collée sur la plaque du récepteur mural contrôlant l’allumage du foyer (voir Figure A) et sur le boîtier de la télécommande (Figure B). Pour achever l’installation correcte de ce foyer, procédez comme suit avec les étiquettes adhésives en langues
étrangères fournies avec les instructions d’utilisation
et d’entretien :
1. Repérez le récepteur mural qui contrôle le foyer (vériez que l’interrupteur contrôle le fonction ­nement du foyer en le faisant basculer de Marche à Arrêt, et vice-versa). Nettoyez soigneusement la plaque du récepteur mural pour éliminer la
poussière et les traces de graisse ou d’huile.
Collez l’étiquette sur la surface de la plaque du récepteur mural qui contrôle le foyer (Figure A). Choisissez la langue qui est principalement parlée
dans la résidence du propriétaire. En cas de
doute, collez l’étiquette en anglais.
2. Repérez la télécommande et nettoyez-la soigneuse ment pour éliminer la poussière et les
traces de graisse ou d’huile. Collez l’étiquette sur le boîtier de la télécommande (Figure B). Choisissez la langue qui est principalement parlée
dans la résidence du propriétaire. En cas de
doute, collez l’étiquette en anglais.
3. Si vous ne trouvez pas les étiquettes, veuillez appeler Lennox Hearth Products ou votre distributeur Lennox Hearth Products local pour recevoir gratuitement des étiquettes
supplémentaires.
Étiquettes de remplacement, n° cat. H8024
LENNOX HEARTH PRODUCTS 1-800-655-2008
Remarque : Le texte anglais est rouge sur un support transparent. Le texte français et espagnol est blanc sur un support noir.
DIAGRAMMES DES ÉTIQUETTES
DE SÉCURITÉ
COLOCACIÓN DE ADVERTENCIAS DE SEGURIDAD EN OPERACIÓN
Se requiere que el juego de etiquetas de instrucciones de seguridad que se incluyeron con la chimenea se coloque en los puntos de operación y control de la misma. Se debe colocar una etiqueta
de instrucciones de seguridad en la placa del interruptor de pared del receptor desde el cual se enciende y se apaga la chimenea (ver la Figura A) y en el transmisor de control remoto (ver la Figura B). Para completar correctamente la instalación de
esta chimenea, encuentre las etiquetas adhesivas
multilingües incluidas con las instrucciones de
cuidado y operación y haga lo siguiente:
1. Identique el receptor de pared que controla la chimenea (verique que el interruptor opera la chimenea encendiéndola y apagándola). Limpie bien la placa del receptor de pared para quitar el polvo y aceite. Pegue la etiqueta en la supercie de la placa del receptor de pared que controla la chimenea (Figura A). Seleccione el idioma que más se habla en la casa. Si no sabe cuál es, use la etiqueta en inglés.
2. Identique el transmisor de control remoto y límpielo bien para quitar el polvo y aceite. Pegue la etiqueta en la supercie del transmisor (Figura B). Seleccione el idioma que más se habla en la casa. Si no sabe cuál es, use la etiqueta
en inglés.
3. Si no puede encontrar las etiquetas, sírvase llamar a Lennox Hearth Products o al distribuidor de Lennox Hearth Products más cercano para recibir etiquetas de instrucciones de seguridad
adicionales gratuitas.
Juego de etiquetas de repuesto - Nº de cat. H8024
LENNOX HEARTH PRODUCTS 1-800-655-2008
Nota: La etiqueta en inglés es transparente con texto rojo. Las etiquetas en francés y español son negras con texto blanco.
DIAGRAMAS DE ETIQUETAS
DE SEGURIDAD
Figure A
Remote
PRG
On
Figure B
Off
27
Page 28
S
e
a
l
a
n t
LENNOX HEARTH PRODUCTS • MONTEBELLO® POWER VENT DV GAS FIREPLACES (MDLX40/45IN-PV) • INSTALLATION INSTRUCTIONS
INSTALLATION ACCESSORIES
Listed Secure Vent® Components
Cat. No. Model No. Description
77L70 SV4.5L6
77L71 SV4.5L12
77L72 SV4.5L24
77L73 SV4.5L36
77L74 SV4.5L48
77L75 SV4.5LA
77L76 SV4.5E45
77L77 SV4.5E90
H2246 SV4.5HF
H2247 SV4.5VF
The following ashings come packaged with a storm collar:
H5816 SV4.5-TWSK
6 in. (152mm) Vent Section
12 in. (305mm) Vent Section
24 in. (610mm) Vent Section
36 in. (914mm) Vent Section
48 in. (1219mm) Vent Section
Telescopic Section
45 Degree Elbow
90 Degree Elbow
Firestop/Spacer, Horizontal (3 - 1 - 1 spacing) 10 pack
Firestop/Spacer, Vertical (1 - 1 - 1 spacing) 10 pack
Through Wall Shield Kit (used to shield the direct-vent pipe from blown insulation) Ref. instr. # 750247M
Listed Secure Vent / Secure Flex® Components
Cat. No. Model No. Description
Attic Insulation Shield
H3907 SV4.5RSA
H7748 FVK36
10K81 SFMP
89L40 SFMP-12
91L66 SF-GC4-6
91L67 SF-GC7-6
(adjustable 12 in. to 22 in.)
36 in. Flex Vent Kit
Note: Flex attaches to appliance collar at one end and to rigid venting at the other end.
Mill-Pac, Black, High Temperature Sealant
Mill-Pac, Black, High Temperature Sealant—Bulk 12 pack
Gear Clamp 4.5 in. (114 mm) for flex (6 pieces)
Gear Clamp 7.5 in. (190.5 mm) for flex (6 pieces)
96K93 SV4.5SU
96K92 SV4.5SP
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design, materials, specications, prices and also to discontinue colors, styles and products. Consult your local distributor for replace code information.
LENNOX®, the LENNOX design, DAVE LENNOX, the image of DAVE LENNOX and other related
LENNOX marks are registered or common law trademarks of Lennox Industries Inc. and are used
with permission.
Printed in U.S.A. © 2012 Lennox Hearth Products LLC
P/N 506023-16 Rev. NC 08/2012
28
Support Strap
Support Plate
1508 Elm Hill Pike, Suite 108 • Nashville, TN 37210
Loading...