Lennox Montebello MDLX40IN, Montebello MDLX45IP, Montebello MDLX40IP, Montebello MDLX45IN Installation Instructions Manual

Page 1
INSTALLATION INSTRUCTIONS
AVERTISSEMENT : Assurez-vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d’incindie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result, causing property damage, personal injury, or death.
WARNING /AVERTISSEMENT/AVISO
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
UNE SURFACE VITRÉE CHAUDE
PEUT CAUSER DES BRÛLURES.
LAISSER REFROIDIR LA SURFACE
VITRÉE AVANT D'Y TOUCHER.
NE PERMETTEZ JAMAIS À UN ENFANT
DE TOUCHER LA SURFACE VITRÉE.
EL VIDRIO CALIENTE
CAUSARÁ QUEMADURAS.
USTED DEBE NUNCA
TOCAR EL VIDRIO CALIENTE.
LOS NIÑOS DEBEN NUNCA
TOCAR EL VIDRIO.
- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
- Ne pas entreposer ni utilizer d’essence ni d’autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucan interrupteur. Ne pas vous servir des
téléphones se trouvant dans le bâtiment où vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis
un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service des incindies.
- L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
Montebello® DLX Direct Vent Gas Fireplaces
Intertek Report No.
100513650
P/N 506023-15 Rev. B 04/2013
This manual is one of a set of two supporting this product. Refer to P/N 506025-07 for Care and Operation Instructions.
Ce manuel est disponible en francais, simplement en faire la demande. Numéro de la pièce 506223-41.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
INSTALLATEUR : Laissez cette notice avec l'appareil. CONSOMMATEUR : Conservez cette notice pour consultation ultérieure.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases unless a certified kit is used.
MODELS
MDLX40IN MDLX40IP
Decorative Product: Not for use as a heating appliance.
NOTICE: Fireplace is not to be operated by a thermostat.
ELECTRONIC
MDLX45IN MDLX45IP
Page 2
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
TABLE OF CONTENTS
Packaging ......................... 2
Introduction ........................ 2
General Information .................. 3
Massachusetts Requirements .......... 4
Cold Climate Insulation ............... 5
Manufactured Home Requirements ...... 5
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Vent Termination Clearances ........... 6
Minimum Clearances to Combustibles ..... 8
Detailed Installation Steps ............. 9
Typical Installation Sequence .......... 9
Step 1. Framing .................... 9
Fireplace and Framing Specifications ...... 10
Step 2. Routing Gas Line ............. 11
Proper Sizing of Gas Line .............. 11
Step 3. Install the Vent System ........ 12
Vertical Termination Systems ........... 13
Vent Section Length Chart ............. 13
Vertical Vent Tables and Figures ......... 16
Horizontal Termination System ......... 17
Horizontal Vent Tables and Figures ...... 19
Step 4. Field Wiring ................. 21
Step 5. Removing Glass Door
Frame Assembly .................. 23
Step 6. Connecting Gas Line .......... 23
Step 7. Checking Appliance
Operation ........................ 23
Step 8. Installing Logs and Panels ...... 24
Step 9. Installing Glass Door .......... 26
Step 10. Burner Adjustments ........... 26
Finishing Requirements ............... 28
Step 11. Attaching Safety-in-
Operation Warnings ................ 29
Installation Accessories ............... 30
Gas Conversion Kits .................. 31
Please read and understand these instructions before beginning your
installation.
PACKAGING
The assembled fireplace is packaged with the following:
Literature Kit (plastic bag shipped inside
rebox), containing Care and Operation
Instructions, Installation Instructions (this
manual), Safety-in-Operation Warning La­bels, and Warranty.
• One (1) bag Glowing Embers
• One (1) bag Platinum Embers
• One (1) bag Volcanic Stone
Pull Screen Kit
Remote Control and Wall Receiver Switch
Kit
Door Modesty Shield
Log Grate
NOTE: For use with fireplace as shipped from fac-
tory only. Not for use with Contemporary Burner/ Floor Kit.
REQUIRED ACCESSORIES
The following accessories are required:
• One of the following Firebox Liner Kits:
a. Ceramic Firebox Liner Kit - Buff Rustic b. Ceramic Firebox Liner Kit - Red Rustic c. Porcelain Firebox Liner Kit - Black d. Ceramic Firebox Liner Kit - Red Her-
ringbone
e. Ceramic Firebox Liner Kit - Buff Her-
ringbone
NOTE: Porcelain kits include side and back panels.
Optional for use with log sets. Required when using the contemporary burner/floor kit.
• One of the following Floor Options: a. Oak Log Set (For use with fireplace as
shipped from factory only. Not for use with contemporary burner/floor kit.)
b. Contemporary Burner/Floor Kit
Contemporary Burner/Floor Kit requires
one of the following Media Kits:
i. Crushed Glass - Reective Black
ii. Crushed Glass - Platinum
iii. Crushed Glass - Reective Blue
iv. Crushed Glass - Goldfinger v. Crushed Glass - Copper
NOTE
: The Contemporary Burner/Floor Kit instal-
lation and operation instructions are provided with the kit, and are not detailed in this manual.
INTRODUCTION
The Montebello® DLX direct-vent, sealed­combustion gas fireplaces operate on natural or propane gas. These appliances feature a remotely controlled electronic intermittent pilot ignition system (manual adjustment of the gas
valve settings is not possible). The Montebello DLX is a decorative replace
and may not be installed and operated as the primary heat source in a dwelling.
Electrical power (120 VAC line voltage) is rec- ommended to operate the fireplace; however,
four (4) "AA" batteries can be used for full-time
operation or as a backup in case of a power outage.
Approved Vent Components
These fireplaces are designed, tested, and listed for operation and installation with Secure
Vent® direct vent system components (8" inner,
11" outer) manufactured by Security Chimneys
International.
These approved vent system components are labeled for identification. USE ONLY AP-
PROVED VENT COMPONENTS. Do NOT use any other manufacturer’s vent components with these appliances.
Codes and Standards
These appliances comply with National Safety Standards and are tested and listed by Intertek
(Report No. 100513650) to Z21.50 (in Canada, CSA-2.22), and CAN/CGA-2.17-M91 in both
USA and Canada, as vented gas fireplaces.
These appliances are listed by Intertek for installation in bedrooms and mobile homes.
Installation must conform to local codes. In the absence of local codes, installation must comply with the current National Fuel Gas
Code, ANSI Z223.1 (in Canada, the current CAN/CGA-B149.1 installation code).
The appliance, when installed, must be electri­cally grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70 (latest
edition) or the Canadian Electrical Code, CSA C22.1 (latest edition).
2
Page 3
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
GENERAL INFORMATION
WARNING
Young children should be care­fully supervised when they are in the same room as the appli­ance. Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to a fireplace or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
AVERTISSEMENT
Les jeunes enfants devraient être surveillés étroitement lorsqu’ils se trouvent dans la même pièce que l’appareil. Les tout petits, les jeunes enfants ou les adultes peuvent subir des brûlures s’ils viennent en contact avec la sur­face chaude. Il est recommandé d’installer une barrière physique si des personnes à risques habi­tent la maison. Pour empêcher l’accès à un foyer ou à un poêle, installez une barrière de sécu­rité; cette mesure empêchera les tout petits, les jeunes enfants et toute autre personne à risque d’avoir accès à la pièce et aux surfaces chaudes.
Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition.
Les enfants et les adultes devraient être infor-més des dangers que posent les températures de surface élevées et se tenir à distance afin d’éviter des brûlures ou que leurs vêtements ne s’enflamment.
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERATION MAY VOID THE WARRANTY, CERTIFICATION AND LISTINGS OF THIS UNIT.
WARNING
Improper installation, adjust­ment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
WARNING
Failure to comply with these installation instructions will result in an improperly installed and operating appliance, voiding its warranty. Any change to this appli­ance and/or its operating controls is dangerous.
WARNING
Clothing or other flammable material should not be placed on or near the appliance.
AVERTISSEMENT
On ne devrait pas placer de vêtements ni d’autres matières inflammables sur l’appareil ni à proximité.
WARNING
Any safety screen or guard removed for servicing the appli­ance must be replaced prior to operating the appliance.
AVERTISSEMENT
Tout écran ou protecteur retiré pour permettre l’entretien de l’appareil doit être remis en place avant de mettre l’appareil en marche.
WARNING
Improper installation or use of this appliance can cause serious injury or death from fire, burns, explosion or carbon monoxide poisoning.
Installation and repair should be done by a qualified service person. The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding ma­terial, etcetera. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
L’installation et la réparation devrait être confiées à un technicien qualifié. L’appareil devrait faire l’objet d’une in­spection par un technicien professionnel avant d’être utilisé et au moins une fois l’an par la suite. Des nettoyages plus fréquents peuvent être nécessaires si les tapis, la literie, et cetera produisent une quantité importante de pous-sière. Il est essentiel que les compartiments abritant les commandes, les brûleurs et les con­duits de circulation d’air de l’appareil soient tenus propres.
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any parts of the control system and any gas control which have been under water.
Ne pas se servir de cet appareil s'il a été plongé dans l'eau, complètement ou en partie. Appeler un technicien qualifié pour inspecter l'appareil et remplacer toute partie du système de contrôle et toute commande qui ont été plongés dans l'eau.
Only trim kit(s) supplied by the manufacturer shall be used in the installation of this ap­pliance.
Seules les trousses de garniture fournies par le fabricant doivent être utilisées pour l’installation de cet appareil.
Provide adequate clearances around air open­ings and adequate accessibility clearance for
service and proper operation. Never obstruct the front openings of the appliance.
These appliances are designed to operate on natural or propane gas only. The use of other fuels or combination of fuels will degrade the performance of this system and may be dangerous.
These appliances must not be connected to a chimney or flue serving a separate solid fuel burning appliance.
3
Page 4
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
These electronic appliances are remotely controlled and feature an electronic intermit­tent pilot ignition system or standing pilot.
External electrical power is required to operate
these units.
These electronic models come standard with a remotely-modulated gas valve; flame appear­ance and heat output cannot be controlled at the gas valve. The BTU Input for these appli­ances is shown in Table 1.
Input (BTU/HR)
Model No. Input (BTU/Hr)
Natural Gas
MDLX40IN 32,000 to 50,000 MDLX45IN 38,500 to 60,000
Propane Gas
MDLX40IP 32,000 to 50,000 MDLX45IP 38,500 to 60,000
Table 1
Gas Pressure - All Models
Appliance inlet and manifold gas pressure requirements are listed in Tables 2 and 3.
Inlet Gas Supply Pressure
Fuel # Minimum Maximum
Natural
Gas
Propane
5.5" WC
(1.37 kPa)
11.0" WC
(2.74 kPa)
10.5" WC
(2.61 kPa)
13.0" WC
(3.23 kPa)
Table 2
Manifold Gas Supply Pressure
Fuel # Low High
Natural
Gas
Propane
1.6" WC (.4 kPa)
6.3" WC
(1.57 kPa)
3.5" WC
(.87 kPa)
10.0" WC
(2.49 kPa)
Table 3
Orifice Sizes - Sea Level To High Altitude (All Models)
These appliances are tested and approved
for installation at elevations of 0 - 4500 feet (0 - 1372 meters) above sea level, using the
standard burner orifice sizes (marked with an
asterisk (*) in Table 4). For elevations above 4500 feet, contact your gas supplier or qualied
service technician. Deration - At higher elevations, the amount
of BTU fuel value delivered must be reduced
by either:
• using gas that has been derated by the gas
company; or
• changing the burner orice to a smaller size
as regulated by the local authorities having
jurisdiction and by the (USA) National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition or, in Canada, the CAN/CGA-B149.1
codes - latest edition.
Install the appliance according to the regulations of the local authorities having jurisdiction and, in the USA, the National Fuel Gas Code NFPA
54 / ANSI Z223.1 - latest edition or , in Canada, the CAN/CGA-B149.1- latest edition.
NOTE: Flame appearance will diminish 4% per thousand feet of altitude.
Burner Orifice Sizes
Elevation 0 - 4500 ft ( 0 - 1372 m)
Model Nat.Gas
drill size (inches)
MDLX40 0.1405" (#28)*
• H2286
MDLX45 0.154" (#23)*
• H8808
Table 4
* Standard size installed at factory
• Part /Cat. Number
Propane
drill size (inches)
0.086" (#44)*
• H2287
0.093" (#42)*
• H4816
Gas Valve Diagram
The SIT Proflame gas valve is shown in Figure
1.
REQUIREMENTS FOR THE COMMON­WEALTH OF MASSACHUSETTS
These fireplaces are approved for installation in
the US state of Massachusetts if the following additional requirements are met:
• Install this appliance in accordance with Massachusetts Rules and Regulations 248 C.M.R.
• Installation and repair must be done by a
plumber or gas fitter licensed in the Com-
monwealth of Massachusetts.
• The exible gas line connector used shall not exceed 36 inches (92 centimeters) in
length.
• The individual manual shut-off must be a
T-handle type valve.
Massachusetts Horizontal Vent Requirements
In the Commonwealth of Massachusetts, hori­zontal terminations installed less than seven (7) feet above the finished grade must comply with the following additional requirements:
• A hard wired carbon monoxide detector
with an alarm and battery back-up must be installed on the floor level where the gas fireplace is installed. The carbon monoxide detector must comply with NFPA 720, be
ANSI/UL 2034 listed and be ISA certied.
• A metal or plastic identication plate must
be permanently mounted to the exterior of
the building at a minimum height of eight (8)
feet above grade and be directly in line with the horizontal termination. The sign must
read, in print size no less than one-half (1/2) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.
Test gauge connections are provided on the front of the gas control valve (identified IN for
the inlet and OUT for the manifold side).
Propane tanks are at pressures that will cause damage to valve components. Verify that the tanks have step-down regulators to reduce the pressure to safe levels.
The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in
excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the gas
supply piping system by closing its equipment
shutoff valve during any pressure testing of the gas supply piping system at test pressures
equal to or less than 1/2 psi (3.5 kPa).
4
Green Wire
(From DFC Wire
Harness)
Manifold (Out)
Test Port
Inlet (In) Test Port
Wire
(From DFC Wire
Harness)
Main Gas Inlet
3/8" NPT
Figure 1 - SIT Proflame Valve
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Connect GTMS Wire Harness
Pressure Regulator Tower
Yellow Ground Wire (From DFC Wire Harness)
Page 5
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
Drywall
Top Of Fireplace Opening
Non-Combustible
HORIZONTAL VENT
VERTICAL VENT
HORIZONTAL VENT
VERTICAL VENT
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room. It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests, if floor is above ground level. Gas line holes and other openings should be caulked or stuffed with unfaced fiberglass insulation.
If the fireplace is being installed on a cement slab in cold climates, a sheet of plywood or other raised platform can be placed underneath to prevent cold transfer to the fireplace and into the room. It also helps to sheetrock inside surfaces and tape for maximum air tightness and caulk firestops.
MANUFACTURED HOME REQUIREMENTS
This appliance may be installed in an aftermarket permanently located, manufactured home and must be installed in accordance with the manu-
facturer's instructions and the Manufactured
Home Construction and Safety Standard, Title
24 CFR, Part 3280, in the United States, or the Standard for Installation in Mobile Homes, CAN/ CSA Z240 MH Series, in Canada.
Cet appareil peut être installé cómme du matéri-el d'origine dans une maison
préfabriquée (É.U. seulement) ou mobile
et doit être installé selon les instructions du fabricant et conformément à la norme
Manufactured Home Constructions and Safety, Title 24 CFR, Part 3200 aux Unis ou à la norme Can/CSA-Z240 Série MM, Maisons mobiles au Canada.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, un­less a certified kit is used.
Cet appareil doit être utilisé uniquement avec le type de gaz indiqué sur la plaque signalétique. Cet appareil ne peut être con-
verti à d'autres gaz, sauf si une trousse de conversion est utilisée.
CAUTION: Ensure that the cross members are not cut or weakened during installa­tion. The structural integrity of the manu­factured home floor, wall, and ceiling / roof must be maintained.
When the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend beyond the front edge of the unit.
Figure 2 - Typical Installation
LOCATION
In selecting the location, the aesthetic and functional use of the appliance are primary concerns. However, vent system routing to the exterior and access to the fuel supply are also important.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies (Figure 2).
En raison des températures élevées, l’appareil devrait être installé dans un endroit où il y a peu de circulation et loin
du mobilier et des tentures (Figure 2).
The location should also be free of electrical, plumbing or other heating/air conditioning ducting.
These direct-vent appliances are uniquely suited for installations requiring a utility shelf
positioned directly above the fireplace. Utility shelves like these are commonly used for locating television sets and decorative plants.
Cross Corner
Application
Room Divider
Application
Recessed
Application
Island
Application
Flat
Application
Application
Flat on Wall
Be aware that this is a heat producing ap­pliance. Objects placed above the unit are exposed to elevated temperatures.
Do not insulate the space between the appliance and the area above it (see Figure
7 on Page 8).
The minimum height from the base of the appliance to the underside of combustible materials used to construct a utility shelf in this fashion is shown in Figure 7 on Page 8.
The appliance must be mounted on a fully supported base extending the full width and depth of the unit. The appliance may be located on or near conventional construction materials. However, if installed on combustible materials, such as carpeting, vinyl tile, or other combustible material other than wood flooring, the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance.
CAUTION: This appliance must be ground­ed to the chassis of the manufactured home in accordance with local codes or in the absence of local codes, with the National Electrical Code ANSI / NFPA 70
- latest edition or the Canadian Electrical Code CSA C22.1 - latest edition.
5
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 6
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
3"
(76 mm)
Termination Kit
Combustible Projection
greater than 2-1/2” in length
Horizontal Vent Termination Clearances
Combustible Projection 2-1/2” or less in length
24"
(610 mm)
Ventilated Or
Unventilated Soffit
12
X
Roof Pitch is X/12
2 FT MIN.
2 FT MIN.
Lowest
Discharge
Opening
H*
*H = MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING OF VENT
TERMINATION HEIGHTS FOR VENTS ABOVE
FLAT OR SLOPED ROOFS
Horizontal Overhang
Vertical
Wall
Vent
Termination
Storm Collar
Concentric
Vent Pipe
Flashing
1” (25.4 mm) Minimum Clearance to Combustibles
VENT TERMINATION CLEARANCES
These instructions should be used as a guideline and do not supersede local codes in any way. Install vent according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 in Canada.
Vertical Vent Termination Clearances
Terminate multiple vent terminations according to the installation codes listed above. Also see Figure 3.
Terminate single vent caps relative to building components according to Figures 3 and 4.
12”
(305mm)
Minimum
Vertical Vent Termination Clearances
The vent / air intake termination clearances above the high side of an angled roof is as shown in the following chart:
Figure 4
Termination Heights For Vents
Above Flat Or Sloped Roofs Ref. NFPA 54 / ANSI Z223.1
Roof Pitch * Feet * Meters
Flat to 6/12 1.0 0.3
6/12 to 7/12 1.25 0.38 7/12 to 8/12 1.5 0.46
8/12 to 9/12 2.0 0.61
9/12 to 10/12 2.5 0.76
10/12 to 11/12 3.25 0.99 11/12 to 12/12 4.0 1.22
12/12 to 14/12 5.0 1.52 14/12 to 16/12 6.0 1.83
16/12 to 18/12 7.0 2.13 18/12 to 20/12 7.5 2.29 20/12 to 21/12 8.0 2.44
Figure 3 - Multiple Terminations
6
Horizontal Vent Termination Clearances
The horizontal vent termination must have a minimum of 3" (76 mm) clearance to any overhead combustible projection of 2-1/2" (64 mm) or less (see Figure 5). For projections exceeding 2-1/2" (64 mm), see Figure 5. For additional vent location restrictions refer to Figure 6 on Page 7.
See Figure 28 on Page 18 for the recess allowances, into exterior walls, of the square horizontal terminations.
Figure 5 - Side Elevation View
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 7
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
NOTE: Local Codes Or Regulations May Require Different Clearances.
NOTE: Location Of The Vent Termination Must Not Interfere With Access To The Electrical Service.
3 ft.
X
A
3 ft.
Exterior Wall
Horizontal
Termination
B
V
L
X
= Air Supply Inlet
* See Item D in the Text Below.
*18”
24"
Inside Corner
Center Line
of Termination
18”
36"
DETAIL D
F
V
Ventilated Soffit
V
Fixed
Closed
Window
V
C
A
= Vent Terminal
V
Inside
Corner Detail
G
V
A
= 9" in U.S.
A
=12" in Canada
B
C
C
C
Operable
V
Window
B
B
= Area where Terminal is NOT permitted
B
A
J
Minimum Clearances Canadian Installation * US Installation **
A = Clearance above grade, veranda, porch, deck
or balcony.
B = Clearance to window or door that may be opened. 6" (15.2 cm) for appliances < 10,000 BTU/hr (3kW),
C = Clearance to permanently closed window 12" (305 mm) recommended to prevent window conden-
12" (30 cm) * 12" (30 cm) **
12" (30 cm) for appliances > 10,000 BTU/hr (3kW) and < 100,000 BTU/hr (30kW), 36" (91 cm) for appliances > 100,000 BTU/hr (30kW)*
sation
H
E
D
M
I
X
V
K
6" (15.2 cm) for appliances < 10,000 BTU/hr (3kW), 9" (23 cm) for appliances > 10,000 BTU/hr (3kW) and < 50,000 BTU/hr (15kW), 12" (30 cm) for appliances > 50,000 BTU/hr (15kW)*
9" (229 mm) recommended to prevent window con-
densation
V
D = Vertical clearance to ventilated soffit located
24" (61.0 cm) 24" (61.0 cm)
above the terminal within a horizontal distance of
36" (91.4cm) from the center line of the terminal
E = Clearance to unventilated soffit 24" (61.0 cm) 24" (61.0 cm) F = Clearance to outside corner 5" (12.7 cm) 5" (12.7 cm) G = Clearance to inside corner 36" (91.4 cm) 24" (61.0 cm)
H = Clearance to each inside of center line extended above meter / regulator assembly
3 feet (91 cm) within a height of 15 feet above the meter /
regulator assembly *
3 feet (91 cm) within a height of 15 feet above the meter
/ regulator assembly **
I = Clearance to service regulator vent outlet 3 feet (91 cm) * 3 feet (91 cm) **
J = Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance
6" (15.2 cm) for appliances < 10,000 BTU/hr (3kW), 12" (30 cm) for appliances > 10,000 BTU/hr (3kW) and < 100,000 BTU/hr (30kW), 36" (91 cm) for appliances > 100,000 BTU/ hr (30kW)*
6" (15.2 cm) for appliances < 10,000 BTU/hr (3kW), 9" (23 cm) for appliances > 10,000 BTU/hr (3kW) and < 50,000 BTU/hr (15kW), 12" (30 cm) for appliances > 50,000 BTU/hr (15kW)*
K = Clearance to mechanical air supply inlet 6 feet (1.83 meters) * 3 feet (91 cm) above, if within 10 feet (3 m) horizontally**
L = Clearance above paved sidewalk or paved
7 feet (2.13 m) ‡ 7 feet (2.13 m) ‡
driveway located on public property
M = Clearance under veranda, porch, deck or
18" (46.0 cm) * ‡ 18" (46.0 cm) ** ‡
balcony
* In accordance with the current CAN/CGA-B149.1 National Gas and B149.2 Propane Installation Code - Latest Editions.
** In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Codes - Latest Edition. ‡ A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings. *‡ Only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the oor.
Figure 6 - Exterior Horizontal Vent Termination Clearance Requirements
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
7
Page 8
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
17”
432 mm
14”
356 mm
8-1/4”
210 mm
45°
12”
305 mm
5”
127 mm
12 (305)
10 (254)
8 (203)
6 (152)
4 (102)
7
(178)
17
(432)
15
(381)
13
(330)
2 (51)
9
(229)
11
(279)
MINIMUM CLEARANCES TO COMBUSTIBLES
The appliance is approved with zero clearance to combustible materials on all sides (as detailed in Table 5), with the following exception: When
the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend beyond the front edge of the unit. In addition, when the unit is recessed, the side walls surrounding
the unit must not extend beyond the front edge of the unit (see Figure 2).
APPLIANCE MINIMUM CLEARANCES*
Inches (millimeters)
Sides 1/2 (13), 0 (0) Spacers **
Top Spacers 0 (0)
Floor 0 (0) Back 1/2 (13), 0 (0) Spacers
Bottom of Appliance To Ceiling 69 (1743)
Vent 3 (76)
Top * / 1 (25.4) Sides & Bottom
SERVICE CLEARANCES Feet (meters)
Front 3 feet (0.9 meters)
Table 5
Combustible Shelf Height -
Top Vent - with 2 Feet Vertical Vent and One 90 Degree Elbow
Model Secure Vent MDLX40 *84-1/16 (2135) MDLX45 *89-1/16 (2252)
* Includes 3" clearance to combustibles (required above vent components)
Do not insulate the space between the appliance and the area above it.
Shelf Height
(see table)
Figure 7
Shelf Above Fireplace With Top Venting
Inches (millimeters)
®
2-1/2 ft (to centerline) Vertical Vent (minimum)
*NOTE: 3" (75 mm) above any horizontal/inclined vent component. **NOTE: See Page 9, Step 1 for clearance requirements to the nailing
flange located at each side of the unit and any screw heads adjacent to it. See Page 28 for hearth extension requirements.
Shelf Height
To provide for the lowest possible shelf surface, the venting attached to the top vent should be routed in a way to minimize obstructions to the space above the appliance. Do not insulate the space between the ap- pliance and the area above it (see Figure 7). The minimum height from the base of the appliance to the underside of combustible materials used to construct a utility shelf in this fashion is shown in Figure 7.
Wall Finishes / Surrounds / Mantels
NOTE: Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined by the appliance front face (black sheet metal). Never allow combustible materials to be positioned
in front of or overlapping the appliance face. See Figure 9 and Figure 51 on Page 28.
Non-combustible materials, such as surrounds and other appliance trim, may be installed on the appliance front face with these exceptions: they must not cover any portion of the removable glass panel.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel. See Figure 8. Mantels constructed of non- combustible materials may be installed at any height above the appliance
opening. Minimum clearance requirements include any projections such
as shelves, window sills, mantels, etc. above the appliance.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
NOTE: We recommend the use of high temperature paint (rated 175° F or higher) on the underside of the mantel.
8
Figure 8
Combustible Materials Allowed In Shaded Area "Safe Zone"
Side Wall
Figure 9
Top of Appliance
Side Wall
MANTEL
MANTEL
MANTEL
MANTEL
MANTEL
MANTEL
Top View of
Minimum Distance to Protected Side Wall
Minimum Distance to Unprotected Side Wall
CLEARANCES
Inches (mm)
Fireplace
(side view)
Fireplace
MANTEL
Page 9
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
WARNING
Failure to position the parts in accordance with these diagrams or failure to use only parts specifi­cally approved with this appliance may result in property damage or personal injury.
AVERTISSEMENT
Risque de dommages ou de blessures si les pièces ne sont pas installées conformément à ces schémas et ou si des pièces autres que celles spécifiquement approuvées avec cet appareil sont utilisées.
DETAILED INSTALLATION STEPS
The appliance is shipped with all gas controls and components installed and pre­wired.
1. Remove the shipping carton, exposing the front glass door on the valve access side.
2. Using a Phillips screwdriver, unfasten two
(2) screws located at the top of the glass
frame (see Figure 46 on page 26). Tilt the top of the glass frame away from the unit. Lift it carefully off the bottom door track and set the door aside, protecting it from inadvertent damage.
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation is outlined below. However, each installation is unique and
may result in variations to the steps described.
See the Page numbers references in the follow­ing steps for detailed procedures.
Step 1. (Page 9) Construct the appliance
framing. Position the appliance within the framing and secure with nailing brackets.
Step 2. (Page 11) Route gas supply line to the
right side.
Step 3. (Page 12) Install the vent system and
exterior termination.
Step 4. (Page 21) Connect 120 VAC electrical
power to the appliance receptacle.
Step 5. (Page 23) Remove glass door assem-
bly.
Step 6. (Page 23) Make connection to gas
supply.
Step 7. (Page 23) Verifying appliance opera-
tion.
Step 8. (Page 24) Install firebox liner panels,
logs, and glowing embers
OR
contemporary burner/floor kit, porce-
lain panels, and media.
Step 9. (Page 26) Install glass door assembly. Step 10. (Page 26) Adjust burner to ensure
proper flame appearance.
Step 11. (Page 29) Attach safety in operation
warnings.
Step 1. FRAMING
Frame these appliances as illustrated in Figure 11 on Page 10, unless the appliance is to be installed in a corner. See Figure 12 on Page 11 for corner framing installations. All framing
details must allow for a minimum clearance to combustible framing members as shown in Table 5 on Page 8.
If the appliance is to be elevated above floor level, a solid continuous platform must be constructed below the appliance.
Headers may be in direct contact with the appliance top spacers but must not be sup­ported by them or notched to fit around them. All construction above the appliance must be self-supporting, DO NOT use the appliance for structural support.
The fireplace should be secured to the side framing members using the unit's nailing flanges - one top and bottom on each side of the fireplace front (see Figure 10). Use 8d nails
or their equivalent.
Use Top Flange For 1/2” Thick Drywall
Front Of Fireplace
Use Center Flange For Flush Mount
Use Bottom Flange For 5/8” Thick Drywall
Left Side Front Corner of Fireplace Shown
(Right Side Requirements the Same)
Unit Being Secured By Its Nailing Flanges
To The Framing
NOTE: The nailing flanges, combustible members and screw heads located in areas directly adjacent to the nailing flanges, are EXEMPT from the 1/2” clear­ance to combustible requirements for the firebox outer wrapper. Combustible framing may be in direct contact with the nailing flanges and may be located closer than 1/2” from screw heads and the firebox wrapper in areas adjacent to the nailing flanges. Frame the opening to the exact dimensions speci­fied in the framing details of this manual.
Unit Being Secured by Its Nailing
Flanges to the Framing
Figure 10
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
9
Page 10
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
E
A
B
D
Top View
Front View
5-3/32 (129)
Right Side View
14-1/8 8-1/2” (216)
5-1/4” (133)
(359)
26-15/32
(672)
C
25-29/32
(658)
25-1/2
(648)
7
2-1/2 (64)
(178)
19-5/8
(498)
Gas Inlet
(This
Side
Only)
Electrical
Inlet
8-3/8 (213)
F
G
H
J
Framing should be constructed
of 2x4 or larger lumber.
A
B
C
8-1/2 (216)
13
(
330
)
VENT FRAMING TOP VENT WITH 2 FEET VERTICAL VENT AND ONE 90° ELBOW
Framing should be constructed
of 2x4 or larger lumber.
Inches (mm)
(641)
25-1/4
15
(
381
)
6-1/2 (165)
1/2 A
PIPE CENTERLINE
Framing Dimensions
Models A B C
MDLX40
in. 50-3/4 43 75-1/8
mm 1289 1092 1908
MDLX45
in. 56-7/8 48 80-1/16
mm 1445 1219 2034
Thermal Efficiency (%)
Natural Gas Propane
Models P4 P4
MDLX40 35.8 TBD MDLX45 51.2 TBD
MDLX40
MDLX45
Figure 11 - Fireplace and Framing Specifications
10
Model
No.
Notes
A B C D E F G H J
in. 50-5/8 37-1/4 42-7/8 25-5/16 34 37-5/8 33-3/32 29-9/32 34-3/4
mm 1286 946 1089 643 864 956 840 744 883
in. 56-11/16 42-1/4 47-7/8 28-3/8 40-1/8 43-5/8 38-3/32 34-1/2 40-59/64
mm 1440 1073 1216 721 1019 1108 968 876 1039
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Fireplace Dimensions
Diagrams, illustrations and photo­graphs are not to scale - consult installation instructions. Product designs, materials, dimensions, specifications, colors and prices are subject to change or discontinuance without notice.
Vent Size
Coaxial DV
Vent Size
8" Inner
11" Outer
Page 11
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
Right Side Front Corner Of Fireplace Framing
6-1/4”
(159 mm)
19-5/8”
(498 mm)
C
Back wall of chase/enclosure
(including any finishing materials)
D
A
B
Model
No.
MDLX40
in. 50-5/8 83-5/8 59-1/8 41-7/8
A B C D
mm 1286 2124 1502 1064
MDLX45
in. 56-3/4 89-7/8 63-1/2 44-7/8
mm 1441 2283 1613 1140
Figure 12 - Corner Framing with Square Termination (SV8HTS)
Step 2. ROUTING GAS LINE
Route a 1/2" (13 mm) gas line along the inside
of the right side framing as shown in Figure
13. Gas lines must be routed, constructed and
made of materials that are in strict accordance with local codes and regulations.
All appliances are factory-equipped with a exible gas line connector and 1/2" shutoff
valve. (See Step 6 on Page 22).
The incoming gas line should be piped into the valve compartment and connected in one of the two methods as shown in Figure 36 on Page 23.
Figure 13
Proper Sizing of Gas Line
Properly size and route the gas supply line from the supply regulator to the area where the
appliance is to be installed per requirements
outlined in the National Fuel Gas Code, NFPA
54 - latest edition (USA) or CAN/CGA-B149.1
- latest edition (Canada).
Never use galvanized or plastic pipe. Refer to Table 6 for proper sizing of the gas supply line, if black iron pipe is being used. Gas lines must be routed, constructed and made of materials that are in strict accordance with
local codes and regulations. We recommend that a qualied individual such as a plumber
or gas fitter be hired to correctly size and route the gas supply line to the appliance. Installing a gas supply line from the fuel supply to the appliance involves numerous considerations of materials, protection, sizing, locations, controls, pressure, sediment, and more. Certainly no one
unfamiliar and unqualied should attempt sizing
or installing gas piping.
Schedule 40 - Black Iron Pipe
Inside Diameter (Inches)
Schedule 40 Pipe
Length (feet)
0 - 10 1/2" 3/8"
10 - 40 1/2" 1/2"
40 - 100 1/2" 1/2"
100 - 150 3/4" 1/2" 150 - 200 3/4" 1/2"
Table 6
Natural
Gas
Propane
Gas
NOTES:
• All appliances are factory-equipped with a exible gas line connector and 1/2" shutoff
valve (see Figure 36 on Page 23).
• See Massachusetts Requirements on Page 4 for additional requirements for installations
in the state of Massachusetts in the USA.
• The gas supply line should Not be connected
to the appliance until Step 6 (Page 23).
• A pipe joint compound rated for gas should be
used on the threaded joints. Ensure propane resistant compounds are used in propane applications. Be very careful that the pipe
compound does not get inside the pipe.
• It is recommended to install a sediment trap
in the supply line as close as possible to the appliance (see Figure 36 on Page 23).
• Check with local building ofcial for local code requirements.
IMPORTANT: If propane is used, be aware that if tank size is too small (i.e. under 100 lbs, if this is the only gas appliance in the dwelling. Ref. NPFA 58), there may be loss of pressure, resulting in insufficient fuel delivery (which can result in sooting, severe delayed ignition or other malfunctions). Any damage resulting from an improper installation, such as this, is not covered under the limited warranty.
11
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 12
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
RESTRICTOR
APPLIANCE VENT OUTLET
When vertically terminating the vent system above the roof, install a vent restrictor in the top vent of the fireplace outlet. Install the restrictor as shown from inside the unit, in the inner fireplace collar
Step 3. INSTALL THE VENT SYSTEM
General Information These instructions should be used as a guide-
line and do not supersede local codes in any way. Install vent according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 and
-B149.2 in Canada. Ensure clearances are in accordance with
local installation codes and the requirements of the gas supplier.
Dégagement conforme aux codes d'installation locaux et aux exigences du foumisseunde gaz.
Use only approved venting components. See Approved Vent Components on Page 2.
These fireplaces must be vented directly to the outside.
The vent system may not service multiple appliances, and must never be connected to a flue serving a separate solid fuel burning ap­pliance. The vent pipe is tested to be run inside
an enclosing wall (such as a chase). There is no requirement for inspection openings in the
enclosing wall at any of the joints in the vent pipe.
Installation of Vent Restrictor
A vent restrictor may be needed with this appliance. The restrictor is installed in the appliance top flue outlet as shown in Figure 14,
For vertical venting from 6 feet to 12 feet or more, from the top of the fireplace to the top of the termination, the installation of a vent restrictor is required.
If necessary, install a vent restrictor in the appliance flue outlet as shown in Figure 14. The vent restrictor is held in place by friction, only.
NOTE: The restrictor is included within the firebox.
Figure 14 - Vent Restrictor Installation
Select Venting System - Horizontal or Vertical
With the appliance secured in framing, de­termine vent routing and identify the exterior termination location. The following sections
describe vertical (roof) and horizontal (exterior wall) vent applications. Refer to the section
relating to your installation. A list of approved venting components is shown on Page 30.
12
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 13
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
Termination
Flashing And Storm Collar
Firestop/Spacer
SV8 6/12/24/36/48 Vent Sections
40' Max
(12.2 M)
6' Min
(1.8 M)
1" (25 mm) Minimum Clearance to Combustibles
lanimoN
38
22
32
Hs
04
04
04
noitceSlanimoN )sehcni(htgneL
621426384
T O T A L
Q T Y
noitceSteN
)sehcni(htgneL
2/1-42/1-012/1-222/1-432/1-64
tneVfothgieHsnoitceStneVforebmuN
sehcnitf
44121100034
0515.21010034
5.451578.21110035
5.061573.31020035
5.271573.41000505
77157.41100506
38152.51010506
6815.51000044
5.091578.51100045
5.691573.61010045
5.502521.71011507
70252.71000606
5.112526.71100607
5.712521.81010607
5.922521.91001607
5.232573.91000055
73257.91100056
5.142521.02000707
6425.02100708
25212010708
46222001708
67232000808
97252.32000066
5.082573.32100809
5.382526.32100
067
5.982521.42010067
5.103521.52001067
5.013578.52000909
5135.621009001
5.523521.72000077
0335.72100078
63382010078
54357.82000 01001
5.943521.92100 01011
27313000088
5.673573.13100089
5.973526.13000 11011
5.814578.43000099
32452.531000901
56457.8300000101
VERTICAL TERMINATION SYSTEMS (ROOF)
See Figure 15 and Figures 23 through 25 on Page 16 and their associated Vertical Vent
Tables which illustrate the various vertical venting configurations that are possible for use with these appliances. Secure Vent
®
pipe applications are shown in these figures. A Vertical Vent Table summarizes each system’s minimum and maximum vertical and horizontal length values
5.4573.0100001
957.0200002
5152.1110002
that can be used to design and install the vent components in a variety of applications.
1257.1020002
The vertical vent system terminates through the roof. The minimum vent height above the roof and/or adjacent walls is specified in ANSI
Z223.1 - latest edition (In Canada, the current CAN/CGA-B149.1 installation code) by major
building codes. Always consult your local
codes for specic requirements. A general
guide to follow is the Gas Vent Rule (refer to
Figure 4 on Page 6).
Vertical (Straight) Installation
(Figure 15)
Determine the number of straight vent sections
required. 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm) net section lengths are
available (see Tables on this page and Page 30 - Vent Sections). Plan the vent lengths so
that a joint does not occur at the intersection of ceiling or roof joists. Refer to the Vent Section Length Chart.
Figure 15
5457.3002002
1552.4100012
7557.4001102
6652.5022004
9657.5000202
27610 30
1857.6000112
095.7021014
3957.7000022
69810 12
2015.8200024
80191003
4115.9020024
71157.9105006
6215.01001304
53152.11006006
8315.11000404
Table 7: Vent Section Length Chart
NOTE: Convert inches into metric equivalent measurement, as follows:
Millimeters (mm) = Inches x 25.4 Centimeters (cm) = Inches x 2.54 Meters (M) = Inches x .0254
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
htgneLnoitceS
621426
)sehcni(
noitceSteN
2/1-42/1-012/1-2
)sehcni(htgneL
tneVfothgie
sehcnitf
5.01578.0010001
5.91526.12100
5.22578.1001001
5.52521.2120003
5.13526.2030003
5.43578.2000101
5.73521.3111003
5.34526.3021003
5.64578.3000011
5.94521.4102003
5.55526.4012003
5.76526.5003003
5.37521.6100203
5.97526.6010203
5.19526.7002013
5.79521.8100023
5.301526.8000303
5.811578.9110305
5.031578.01101305
5.931526.11000033
5.241578.11100405
4
/1-4
/1-64
noitceStneVforebmuN
0
T O T A L
Q T Y
3
Model Effective Length
SV8L6 4-1/2" SV8L12 10-1/2" SV8L24 22-1/2" SV8L36 34-1/2" SV8L48 46-1/2"
Table 8 - Effective Vent Length
13
Page 14
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
Minimum
13”
(330 mm)
Minimum
13”
(330 mm)
Vertical (Offset) Installation
Analyze the vent routing and determine the
quantities of vent sections and number of elbows required. Refer to Vertical Vent Figures and
Tables on Page 16 to select the type of vertical installation desired. Vent sections are available
in net lengths of 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm). Refer to the Vent Section
Length Chart on Page 13 for an aid in select- ing length combinations. Elbows are available
in 90° and 45° congurations. Refer to Figure 20 on Page 15 for the SV8 E45 and SV8 E90
elbow dimensional specifications.
Where required, a telescopic vent section (SV8LA) may be used to provide the installer
with an option in installing in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesirable
location, or will not build up to the required
length. The SV8LA Telescopic Vent Section has
an effective length of from 1-1/2" (38 mm) to 6-3/4" (171 mm). The SV8LA is tted with a
dimpled end (identical to a normal vent section
component) and a plain end with 3 pilot holes.
Slip the dimpled end over the locking channel end of a standard SV8 vent component the
required distance and secure with three screws.
Maintain a minimum 1" (25 mm) clearance to combustible materials for all vertical ele­ments. Clearances for all horizontal elements are 3" (76 mm) on top, 1" (25 mm) on sides and 1" (25 mm) on the bottom.
A. Frame ceiling opening - Use a plumb line
from the ceiling above the appliance to locate center of the vertical run. Cut and/or frame an
opening, 13" x 13" (330 mm x 330 mm) inside
dime nsions, about this center mark (Figure 16).
Roof Framing
Ceiling Framing
Plumb Bob
Figure 16
B. Attach vent components to appliance ­Secure Vent
®
SV8 direct-vent system compo­nents are unitized concentric pipe components featuring positive twist lock connections (see
Figure 17).
All of the appliances covered in this document are fitted with collars having locking inclined channels. The dimpled end of the vent compo­nents fit over the appliance collar to create the positive twist lock connection.
Align the dimple (four places) of the upper vent section with the opening of the locking incline channel on the lower vent section or appliance col­lar. Twist vent component clockwise to engage and seal until arrow and
Arrow
Appliance Collar or Vent Section
dimple align.
Dimple
Locking Incline Channel
Connected Vent Sections
Arrow
Figure 17
To attach a vent component to the appliance collar, align the dimpled end over the collar, adjusting the radial alignment until the four locking dimples are aligned with the inlet of the four inclined channels on the collar (refer to Figure 17). Push the vent component against the collar until it fully engages, then twist the component clockwise, running the dimples down and along the incline channels until they seat at the end of the channels. The unitized design of the Secure Vent components will engage and seal both the inner and outer pipe without the need for sealant or screws. If desired
a #6 x 1/2" screw may be used at the joint, but it is not required as the pipe will securely lock
when twisted. C. Attach vent components to each other - Other
vent sections may be added to the previously installed section in accordance with the require­ments of the vertical vent figures and tables. To add another vent component to a length of vent run, align the dimpled end over the inclined channel end of the previously installed section, adjusting the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels of the previous section.
Push the vent component against the previous section until it fully engages, then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels. This seating position
is indicated by the alignment of the arrow and dimple as shown in Figure 17.
D. Install firestop/spacer at ceiling - When
using Secure Vent, use SV8BF restop/spacer
at ceiling joists. If there is living space above the ceiling level, the firestop/spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the firestop/spacer must be installed on the top side of the joist.
Route the vent sections through the framed opening and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner. Remember to maintain 1" (25 mm)
clearance to combustibles, framing members, and attic or ceiling insulation when running vertical chimney sections. Attic insulation shield (H3908) may be used to obtain the required clearances indicated here. See installation accessories on Page 30. The gap
between the vent pipe and a vertical firestop can be sealed with non-combustible caulking.
E. Support the vertical vent run sections -
NOTE: Proper venting support is very important. The weight of the vent must not be supported by the fireplace in any degree.
Support the vertical portion of the venting
system every 8 feet (2.4 m) above the replace
vent outlet.
Blocking
Support Straps (Plumber's tape)
8 feet (2.4 m)
Maximum
1" (25.4 mm) minimum clearance to combustibles
Figure 18
14
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 15
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
C
D
Storm Collar
One method of support is by utilizing field pro­vided support straps (conventional plumber's
tape). Secure the plumber's tape to the framing
members with nails or screws. Strap the tape around the vent, securing the ends of the tape to the framing. If desired, sheet metal screws
#6 x 1/2" length may be used to secure the
support straps to the vent pipe. See Figure 18 on Page 14.
F. Change vent direction to horizontal/inclined run - At transition from or to a horizontal/inclined
run, install the SV8 E45 and SV8 E90 elbows in
the same manner as the straight vent sections. The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with the required direc­tion of the next vent run element. Twist elbow
sections in a clockwise direction only so as to avoid the possibility of unlocking any of the previously connected vent sections. See
Figure 17 on Page 14 and Figure 19.
10"
(254mm)
Swivel Joint
(360° swivel)
SV8E45
(45° Elbow)
6"
(153mm)
Swivel Joint
(360° swivel)
SV8E90
(90° Elbow)
Figure 19
G. Continue installation of horizontal/inclined sections - Continue with the installation of the
straight vent sections in horizontal/inclined run as described in Step C. Install support straps
every 3 ft (914 mm) along horizontal/inclined
vent runs using conventional plumber’s tape.
See Page 17, Figure 26. It is very important that the horizontal/inclined run be maintained in
a straight (no dips), slightly elevated plane. The recommended incline is approximately 1/4" per foot (20 mm per meter) horizontal, in a direction
away from the fireplace. The rise per foot run ratios that are smaller are acceptable all the way down to at or near level. Use a carpenter’s level to measure from a constant surface and adjust the support straps as necessary.
It is important to maintain the required clear­ances to combustibles: 1" (25 mm) at all sides for all vertical runs; and 3" (76 mm) at the top, 1" (25 mm) at sides, and 1" (25 mm) at the bottom for all horizontal/inclined runs.
H. Frame roof opening - Identify location for vent at the roof. Cut and/or frame opening per Roof Framing Chart (Figure 20).
Framing Dimensions for Roof
Inches (millimeters)
Pitch C D
0/12
6/12
12/12
13"
(330 mm)
13"
(330 mm)
13"
(330 mm)
13"
(330 mm)
15-1/2"
(394 mm)
20-1/2"
(541 mm)
Figure 20 - Roof Framing
I. Install the roof flashing - Extend the vent sections through the roof structure. Install the roof flashing over the vent section and posi­tion such that the vent column rises vertically (use carpenters level) (Figure 21). Nail along perimeter to secure flashing or adjust roofing to overlap the flashing edges at top and sides only and trim where necessary. Seal the top and both sides of the flashing with waterproof caulking.
J. Install the storm collar - Install the storm collar, supplied with the flashing, over the vent/ flashing joint (see Figure 21). Loosen the storm collar screw. Slide collar down until it meets the top of the flashing. Tighten the adjusting screw. Apply non-combustible caulking or mastic around the circumference of the joint to provide a water tight seal.
Storm
Flashing
Collar
Figure 21
K. Install the vertical termination - The final step involves installation of the Vertical Termina­tion. Extend the vent sections to the height as
shown in the "Vertical vent termination section"
on Page 6. The SV8VTR Vertical Termination (Figure 22) can be installed in the exact same fashion as any other Secure Vent® section. Align the termination over the end of the previously installed section, adjusting the radial alignment until the four locking dimples of the termination are aligned with the inlets of the four incline channels of the last vent section. Push the ter­mination down until it fully engages, then twist the termination clockwise running the dimples down and along the incline channels until they seat at the end of the channels.
Figure 22
If the vent system extends more than 5 feet (1.5
m) above the roof ashing, stabilizers may be
necessary. Additional screws may be used at section joints for added stability. Guide wires may be attached to the joint for additional sup­port on multiple joint configurations.
15
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 16
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
V
H
1
H
V
1
Ceiling Firestop/Spacer (SV8BF)
Wall Firestop/Spacer (SV8HF)
H
V
V1
Ceiling
Firestop/Spacer
(SV8BF)
40 feet (12.2 meters)
Maximum
6 feet (1.8 meters)
Minimum
Ceiling
Firestop/Spacer
(SV8BF)
VERTICAL VENT FIGURES/TABLES
Notes:
• SecureVent
the figures.
• It is very important that the horizontal/
inclined run be maintained in a straight (no dips), slightly elevated plane. The recommended incline is approximately 1/4" per foot (20 mm per meter) horizontal, in a direction away from the fireplace. The rise per foot run ratios that are smaller are acceptable all the way down to at or near level.
• SV8BF (Secure Vent) firestop/spacer must
be used anytime vent pipe passes through a combustible floor or ceiling. SV8HF (Secure Vent) firestop/spacer must be used anytime vent pipe passes through a combustible wall.
• Two 45º elbows may be used in place of one
90º elbow. The same rise to run ratios, as shown in the venting figures for 90º elbows, must be followed if 45º elbows are used.
®
(rigid vent pipe) is shown in
Table A
H Maximum
feet (meter) feet (meter)
10 (3.1) 2.5 (0.762) 15 (4.65) 3.5 (1.07) 20 (6.2) 4.5 (1.37)
+ H = 40 feet (12.4 meters) Max.
V + V
V + V1 = 11 feet (3.3 meters) Minimum for MDLX40
V + V1 = 10.5 feet (3.2 meters) Minimum for MDLX45
1
Example: If 20 feet of (H) horizontal vent run is needed, then 4-1/2 feet minimum of (V) vertical vent will be required.
A Vent Restrictor, as shown in Figure 14 on Page 12, must be used in this application.
V Minimum
A Vent Restrictor, as shown in Figure 15 on Page 12, may need to be used in this application
Figure 23 - Top Vent - Straight
Figure 24 - Top Vent - Two 90 Degree Elbows (Corner Framing with Square Termination (SV8HTS))
Table B
H + H
Maximum
1
feet (meter) feet (meter)
10 (3.1) 2.5 (0.762) 15 (4.65) 3.5 (1.06) 20 (6.2) 4.5 (1.37)
H + H1 = 20 feet (6.2 m) Max.
V + V1 + H + H1 = 40 ft. (12.4 m) Max.
V + V1 = 11 feet (3.3 meters) Min. for MDLX40
V + V1 = 10.5 feet (3.2 meters) Min. for MDLX45
V Minimum
A Vent Restrictor, as shown in Figure 14 on Page 12, must be used in this application.
Example: If 20 feet of (H+ H tal vent run is needed, then 4-1/2 feet minimum of (V) vertical vent will be required.
Figure 25 - Top Vent - Three Elbows
) horizon-
1
16
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 17
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
Support
HORIZONTAL (OUTSIDE WALL) TERMINATION SYSTEM
See Figures 26 - 31 and their associated Horizontal Vent tables that illustrate the vari­ous horizontal venting configurations that are possible for use with these appliances. Secure
®
Vent
pipe applications are shown in these Figures. A Horizontal Vent table summarizes each system’s minimum and maximum vertical and horizontal length values that can be used to design and install the vent components in a variety of applications.
The horizontal vent system terminates through
an outside wall. Building Codes limit or prohibit
terminating in specific areas. Refer to Figure 6
on Page 7 for location guidelines. Secure Vent SV8 direct-vent system compo-
nents are unitized concentric pipe components featuring positive twist lock connection, (refer to Figure 17 on Page 14). All of the appli­ances covered in this document are fitted with collars having locking inclined channels. The dimpled end of the vent components fit over the appliance collar to create the positive twist lock connection.
A. Plan the vent run. Analyze the vent routing and determine the
types and quantities of sections required 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm) net
section lengths are available. It is recommended that you plan the venting so that a joint does not occur in the ceiling or roof joists. Allow for elbows as indicated in Figure 20 on Page 15.
Maintain a minimum 1" (25 mm) clearance to combustibles on the vertical sections. Clearances for the horizontal runs are; 3" (76 mm) on top, 1" (25 mm) on sides, and 1" (25 mm) at the bottom.
B. Frame exterior wall opening - Locate the
center of the vent outlet on the exterior wall according to the dimensions shown in Figure 11 on Page 10. Cut and/or frame an opening,
15" x 13" (381 mm x 330 mm) inside dimen­sions, with 9" above center and 7" below center.
C. Frame ceiling opening - If the vertical route is to penetrate a ceiling, use plumb line to locate the center above the appliance. Cut
and/or frame an opening, 13" x 13" (330 mm x 330 mm) inside dimensions, about this center
(refer to Figure 17 on Page 14). D. Attach vent components to appliance - To
attach a vent component to the appliance collar, align the dimpled end over the collar, adjust­ing the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels on the collar (refer to Figure 16 on Page 14).
Building
Support
Framing
SV8E90
Elbow
Vertical
Rise
Brackets
Ceiling
Firestop/Spacer
Support the vertical portion of the venting system every 8 feet (2.4m) above the fireplace vent outlet.
Horizontal / Inclined Run
Support Bracket Spacing Every 3 ft (914 mm)
2-1/2 Foot Vertical
Fireplace
Figure 26 - Typical Horizontal Vent Installation
Push the vent component against the collar until it fully engages, then twist the component clockwise, running the dimples down and along the incline channels until they seat at the end of the channels. The unitized design of the Secure Vent components will engage and seal both the inner and outer pipe elements with the same procedure. Sealant and securing screws are
not required.
E. Attach vent components to each other - Other vent sections may be added to the previously installed section in accordance with the re-
quirements of the vent tables. To add another
vent component to a length of vent run, align the dimpled end of the component over the inclined channel end of the previously installed section, adjusting the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels of the previous section. Push the vent component against the previous section until it fully engages, then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels. This
seating position is indicated by the alignment of the arrow and dimple as shown in Figure
17 on Page 14.
F. Install firestop/spacer at ceiling - When using Secure Vent, use SV8BF restop/spacer at ceiling joists. If there is living space above the ceiling level, the firestop/ spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the firestop/ spacer must be installed on the top side of the joist. Route the vent sections through the framed opening and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner.
Remember to maintain 1" (25 mm) clearance to combustibles, framing members, and attic or ceiling insulation when running vertical chimney sections.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
SV8HTS Termination Shown
SV8 L6/12/24/36/48
Vent Sections
Vent (min.)
Exterior Wall
SV8HTS Termination Shown
Exterior Wall
G. Support the vertical run sections - See Step E on Page 14.
H. Change vent direction - At transition from or
to a horizontal/inclined run, install the SV8E45 and SV8E90 elbows in the same manner as the
straight vent sections. The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align
with the required direction of the next vent run
element. Twist elbow sections in a clockwise direction only so as to avoid the possibility of unlocking any of the previously connected vent sections (see Figure 17 on Page 14).
I. Continue installation of horizontal/inclined sections - Continue with the installation of the
straight vent sections in horizontal/inclined run as described in Step E on Page 14. Install
support straps every 3 feet (1914 mm) along
horizontal/inclined vent runs using conventional plumber’s tape.
See Figure 26, It is very important that the
horizontal/inclined run be maintained in a straight (no dips), slightly elevated plane. The recommended incline is approximately 1/4" per foot (20 mm per meter) horizontal, in a direction away from the fireplace. The rise per foot run ratios that are smaller are acceptable all the way down to at or near level.
It is important to maintain the required clear­ances to combustibles: 1" (25 mm) at all sides for all vertical runs; and 3" (76 mm) at the top, 1" (25 mm) at sides, and 1" (25 mm) at the bottom for all horizontal/inclined runs.
Use a carpenter’s level to measure from a constant surface and adjust the support straps as necessary.
17
Page 18
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
Siding
Stucco
1-1/4” Maximum Recess of Square Termination into Exterior Finishing Material
Exterior Surface of
Framing
5” to 8-1/2”
(127 to 216 mm)
Exterior Surface of Siding
Minimum wall thickness
5” (127 mm)
Interior Surface of
Finished Wall
Maximum wall thickness
8-1/2” (216 mm)
SV8HTS
Square Termination
shown
Maximum Extent of Vent Run Sections to Exterior Surface of Framing
Last Vent Section. Use Telescopic Vent Section (SV8LA), If Necessary
Adaptor
SV8RCH
SV8HTS
Square Termination
Shown
Venting Connection and Exterior Wall Recessing
of the Horizontal Square Termination (SV8HTS).
J. Assemble vent run to exterior wall - If not previously measured, locate the center of the vent at the exterior wall. Prepare an opening as described in Step B on Page 17. Assemble the vent system to point where the terminus of the
last section is within 5" (127 mm) to 8-1/2" (216 mm) inboard of the exterior surface to which
the SV8HTS termination is to be attached, see Figure 29 and Table 9 on Page 19.
If the terminus of the last section is not within this distance, use the telescopic vent section SV8LA, as the last vent section. For wall thick­nesses greater than that shown in Figure 28, refer to Table 9 on Page 19. This table lists the additional venting components needed (in
addition to the termination and adaptor) for a
particular range of wall thicknesses.
K. Attach termination adaptor - Attach the adaptor (adaptor - SV8RCH - provided with the
termination) to the vent section or telescoping vent section), or elbow as shown in Figure 27
in the same manner as any SV vent component (refer to Step E on Page 17).
L. Install Firestop/Spacer at exterior wall
- When using the square termination, install
SV8HF Firestop/Spacer over the opening at the exterior side of the framing, long side up, with
the 3" spacer clearance at the top as shown in
Figure 27, and nail into place.
To help minimize water infiltration it is recommended that the Firestop/ Spacer (SV4.5HF) be installed on the exterior side of the wall.
8-1/2”
15"
(381 mm)
Adaptor
SV8RCH
6” to 48” Vent Section,
Telescopic vent section.
(216 mm)
6-1/2”
(165 mm)
13"
(330mm)
NOTE: Centerline of Vent Piping is NOT the Same as the Centerline of the Framed Opening.
See Figure 12 on Page 10 for Minimum Distance to Base of Appliance
Base of Appliance
1"
(25 mm)
(25 mm)
Figure 27 - Installing the Square Horizontal Termination (SV8HTS)
1"
SV8HTS
Termination
Shown.
3"
(76 mm)
u
(The Firestop/Spacer may also be installed over
the opening at the interior side of the framing).
M. Install the square termination (SV8HTS)
- For the last step, from outside the exterior
wall, slide the collars of the termination onto the adaptor (the outer over the outer and the
inner inside the inner) until the termination
seats against the exterior wall surface to which it will be attached. Orient the housing of the termination with the arrow pointed upwards. Secure the termination to the exterior wall. The
horizontal termination must not be recessed into the exterior wall or siding by more than the 1-1/4" (32 mm) as shown in Figure 28.
IMPORTANT: The vent termination is hot while in operation and for a period of time following the use of the fireplace. Young children should be carefully supervised when they are in the same area as a hot termination.
18
For wall thicknesses greater than
u
Figure 28 - Wall Thickness and Horizontal Termination Requirements
Horizontal terminations have been designed to perform in a wide range of weather condi­tions. Our terminations meet or exceed industry standards.
When selecting the locations of your horizontal terminations, do not place the termination where water from eaves and adjoining rooflines may create a heavy flow of cascading water
8-1/2", see Table 9
onto the termination cap. If the cap must be placed where the possibility of cascading water exists, it is the responsibility of the builder to direct the water away from the termination cap by using gutters or other means.
Take care to carefully follow the installation instructions for the termination, including the use of silicone caulking where required.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 19
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
H
V
Wall Firestop/Spacer
(SV8HF)
Ceiling
Firestop/Spacer
(SV8BF)
See Table 9 as an aid in venting component selection for a particular range of exterior wall thicknesses.
Venting Components Required for Various Exterior
Wall Thicknesses, when using Square Termination Kit
(SV8HTS - see Figure 28)
Vent Components Required Exterior Wall Thickness - inches (mm)
Termination Kit Only 5 to 8-1/2 (127 to 216) Termination Kit and 6" Vent
Section (SV8L6)
Termination Kit and Tele-
scopic Section (SV8LA)
Termination Kit and Tele-
scopic Section (SV8LA) and
9-3/4 to 14 (248 to 356)
6-3/4 to 15-1/4 (171 to 387)
11-1/4 to 19-3/4 (286 to 502)
6" vent section (SV8L6)
Table 9
Table C
H Maximum
V Minimum
feet (meter) feet (meter)
3.5 (1.07) 2.5 (0.762)
6.5 (1.98) 3.5 (1.07)
8.5 (2.6) 4.5 (1.37)
10.5 (3.2) 5.5 (1.68)
12.5 (3.8) 6.5 (1.98)
14.5 (4.4) 7.5 (2.3)
16.5 (5.0) 8.5 (2.6)
18.5 (5.6) 9.5 (2.9) 20 (6.0) 10 (3.0)
V + H = 40 feet (12.4 m) Max.
H = 20 ft. (6.2 m) Max.
Example: If 20 feet of (H) horizontal vent run is needed, then 10 feet minimum of (V) vertical vent will be required.
HORIZONTAL VENT FIGURES/TABLES
NOTES:
• SecureVent
in the figures.
• Two 45º elbows may be used in place of one 90º elbow. The same rise
to run ratios, as shown in the venting figures for 90º elbows, must be followed if 45º elbows are used.
• SV8BF (Secure Vent) firestop/spacer must be used anytime vent pipe
passes through a combustible floor or ceiling. SV8HF (Secure Vent) firestop/spacer must be used anytime vent pipe passes through a combustible wall.
• Itisveryimportantthatthehorizontal/inclinedrunbemaintained
in a straight (no dips), slightly elevated plane. The recommended incline is approximately 1/4" per foot (20 mm per meter) horizontal, in a direction away from the fireplace. The rise per foot run ratios that are smaller are acceptable all the way down to at or near level.
®
components (rigid vent pipe and terminal) are shown
Square termination (SV8HTS) shown.
See Table 9 as an aid in venting component selection for a particular range of exterior wall thicknesses.
Figure 29 - Top Vent - One 90 Degree Elbow (Elbow Connection Not Directly at Appliance)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
19
Page 20
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
V
H
H
1
Wall Firestop/Spacer
(SV8HF)
Wall Firestop/Spacer
(SV8HF)
Ceiling
Firestop/Spacer
(SV8BF)
V
H
H
1
V
1
Wall Firestop/Spacer
(SV8HF)
Ceiling
Firestop/Spacer
(SV8BF)
Wall
Firestop/Spacer
(SV8HF)
Ceiling
Firestop/Spacer
(SV8BF)
HORIZONTAL VENT FIGURES/TABLES
(continued)
See Table 9 on Page 19 as an aid in venting component selection for a particular range of exterior wall thicknesses.
Table D
H
+ H
1
Maximum
V Minimum
feet (meter) feet (meter)
3.5 (1.07) 2.5 (0.762)
6.5 (1.98) 3.5 (1.07)
8.5 (2.6) 4.5 (1.37)
10.5 (3.2) 5.5 (1.68)
12.5 (3.8) 6.5 (1.98)
14.5 (4.4) 7.5 (2.3)
16.5 (5.0) 8.5 (2.6)
18.5 (5.6) 9.5 (2.9) 20 (6.0) 10 (3.0)
V + H + H1 = 40 feet (12.4 m) Max.
H + H
= 20 ft. (6.2 m) Max.
1
Figure 30 - Top Vent - Two 90 Degree Elbows
Table E
H
+ H1 = 20 feet (6.2 m) Max.
V + V
+ H + H1 = 40 ft. (12.4 m) Max.
1
V = 2.5 feet Min. (0.762 m)
V + V
= 11 feet (3.35 m) Min. for MDLX40
1
V + V
= 10.5 feet (3.2 m) Min. for MDLX45
1
20
See Table 9 on Page 19 as an aid in venting component selection for a particular range of exterior wall thicknesses.
Figure 31 - Top Vent - Three 90 Degree Elbows
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 21
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
Pilot Tube
Spark Electrode
Flame Sensor
IPI Pilot
885 Valve
Optional Split Flow
BL
W
Y
Y
BR
G
O
O
R
R
B
B
G
GR
R
B
BL
WH
B
B
W
G
Battery Holder w/Switch ON/ Remote /OFF
Battery Holder Wire Harness
Reset Switch
(See instructions.)
Power Vent Blower
Power Vent Models Only
Air Pressure Switch
Power Vent Only
Note: On models without pressure
switch, these
connectors are
plugged together.
Main Wire
Harness
Main Power Cord
Control Module
G
B
G
W
B
Fuse
ELECTRONIC WIRING DIAGRAM
Ground Y
B
Battery Holder with Switch
ON/Remote/OFF
(Schematic representation only)
COLOR CODE: B = Black BB = Brown w/Black Stripe BG = Brown w/Green Stripe BL = Blue BR = Brown G = Green GY = Gray O = Orange R = Red W = White Y = Yellow
J-BOX/RECEPTIACLE
WIRING
120V, 60HZ, 1PH
Factory Wired
Field Wired
Junction Box
Tab Intact
Tab Intact
n e e r G - d n u o r G
e t i h W - l a r
t u e N
120 VAC - Black
Green Ground Screw
White
Green
Neutral Side of Receptacle
Hot Side of Receptacle
Black
Step 4. FIELD WIRING
CAUTION
Ground supply lead must be con­nected to the wire attached to the green ground screw located on the outlet box. Failure to do so will result in a potential safety hazard. The appliance must be electrically grounded in accordance with local codes or, in the absence of local codes, the National Electrical Code, ANSI/NFPA 70-latest edition. (In Canada, the current CSA C22-1 Cana­dian Electrical Code).
CAUTION: Label all wires prior to disconnec­tion when servicing controls. Wiring errors can cause improper and dangerous operation.
ATTENTION: Au moment de l commandes, étiquetez tous les fils avant de les débrancher. Des erreurs de cáblage peuvent entraîner un fonctionnement inadéquat et dangereux.
entretien des
Verify proper operation after servicing.
S’assurer que l’appareil fonctionne adéquatement une fois l’entretien terminé.
The gas valve is set in place and pre-wired at the factory.
Electronic Wiring
NOTE: The electronic appliance must be connected to the main power supply.
1. Route a 3-wire 120Vac 60Hz 1ph power
supply to the appliance junction box.
2. Remove the electrical inlet cover plate from
the side of the unit by removing the plate's securing screws (see Figure 11 on Page 10).
3. Remove the cover plate's knockout and then
feed the power supply wire through the knock­out opening and into the unit junction box.
4. Connect the black power supply wire to the power outlet's red pigtail lead and the white
power supply wire to the common terminal of the outlet as shown in Figures 32 and 33.
5. Connect the ground supply wire to the pig­tail lead attached to outlet's green ground screw.
6. Install the wall-mounted ON/OFF control, as
described in "Installing and initializing the Remote Control System" on Page 22, in a
convenient location near the fireplace.
7. After the wiring is complete, replace the
cover plate.
Figure 33 - J-BOX WIRING
A wiring diagram is provided here for reference purposes only. This information is also provided on schematics attached directly to the appliance on a pullout panel located within the control compartment.
Figure 32
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
21
Page 22
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
Hot Fireplace Will Cause
Severe Burns
Never Allow Children to Touch Glass or other Fire-
place Parts
WARNING
Installing and initializing the Remote Control System
REQUIRED ITEMS (not provided):
• Standard Junction Box
Paper Clip or similar object (for remote control system initialization)
Installing and Wiring the Receiver (Wall Switch)
The receiver for the Total Comfort Control™ Remote Control System connects directly to the gas valve, stepper motor, and fan control module with an umbilical cord wiring harness.
1. Install a junction box (not provided) on
the wall adjacent to the appliance, within reach of the remote system umbilical cord wiring harness. Position the 6-pin termi­nal within the junction box in preparation for attachment to the remote receiver.
2. When wall nish is complete, install the
receiver in the previously installed junc­tion box, and connect the 6-pin terminal to the 6-pin connector on the back of the receiver.
3. Install the receiver cover plate, taking care to ensure the receiver switch is properly indexed with the switch cover when align­ing the components for attachments.
Initializing the Remote Control System
After completing fireplace installation, initialize the remote control system before operating the fireplace.
4. Insert the three (3) provided AAA batteries
into the battery bay in the transmitter, tak­ing care to correctly align polarity (+/ - ).
5. Insert the four (4) provided AA batteries
into the receiver battery bay (behind the
wall switch plate), taking care to correctly
align polarity (+/ - ).
6. On the receiver, place the three-position
slider switch in the REMOTE position
(Figure 34).
7. On the receiver front cover, insert the end of a paper clip (or other similar object; not
provided) into the hole marked “PRG.”
The receiver will “beep” three times to
indicate it is ready to synchronize with the transmitter.
8. On the transmitter, press the ON button.
The receiver will “beep” four times to
indicate acceptance of the transmitter’s command (and set the receiver to the
transmitter’s specic code). The system
is now initialized.
The remote control system provides remote operation of the following fireplace functions:
Primary burner ON/OFF
Flame height and heat output adjustment (six levels)
The receiver accepts commands via radio
frequency from the transmitter and does not require line-of-sight operation.
The slider switch on the receiver can be set to one of three positions:
• ON (manual override)
• OFF (manual override)
• REMOTE (remote control)
See the fireplace Care and Operation Instruc­tions for detailed instructions on using the remote control system to operate the fireplace.
Three-position slider switch in REMOTE position
On
Remote
Off
PRG
Figure 34 - Receiver (Wall Switch)
LCD Display
ON/OFF Key
ROOM TEMP. Key
UP/DOWN Arrow Key
MODE Key
Figure 35 - Transmitter (Remote Control)
WARNING
Fire hazard. Can cause severe injury or death. The receiver causes ignition of the appliance. The appliance can turn on suddenly. Keep away from the appliance burner when operating the remote system or activating manual bypass of the remote system.
CAUTION
Property damage hazard. Exces­sive heat can cause property damage. The appliance can stay lit for many hours. Turn off the appliance if it is not going to be attended for any length of time. Always place the transmitter where children can not reach it.
22
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 23
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
Gas Valve
Access Plate
Right Side
Modesty Panel
Gas Valve
3/8" NPT x
Flare Fitting
3/8" Flex Tubing
3/8" Nipple
3/8" Union
3/8" Close Nipple
3/8" Shut-off Valve
1/2" x 3/8"
Reducer
Gas
Stub
1/2" x 3/8" Flare
Shut-off Valve
Gas Solid Line Connector
Gas Flex Line Connector
*Sediment Trap
3"
Min
Igniter
Step 5. REMOVE GLASS DOOR FRAME
Remove the glass door assembly. See Installa­tion and Removal of Glass Door on Page 26.
Step 6. CONNECTING GAS LINE
All codes require a shut-off valve mounted in the
supply line. The orientation of the shut-off valve should face the front. Figure 36 illustrates two methods for connecting the gas supply. A Sedi­ment Trap is recommended to prevent moisture and debris in gas line from damaging the valve.
The flex-line method is acceptable in the U.S.A. where local codes permit, however, Canadian requirements vary depending on locality. Instal­lation must be in compliance with local codes.
These appliances are equipped with a gas ex-
line for use in connecting the unit to the gas line. See Figure 36 for flex-line description. The flex-line is rated for both natural and propane gas. A manual shut off valve is also provided with the flex-line.
The gas control valve is located on the right side of the unit.
When using solid gas line connector, access
the valve by removing the front door assembly on the valve access side and the access plate (see Figure 37).
The electronic control valve has a 3/8" (10 mm)
NPT thread gas supply inlet.
Bring the shutoff valve on the end of the ex-line
over to the hard pipe and tighten with wrenches from above through the firebox opening.
Secure all joints tightly using appropriate tools and sealing compounds (ensure propane resistant compounds are used in propane ap­plications). It is recommended to seal around the gas line to prevent cold air leakage.
Figure 37
TEST ALL CONNECTIONS FOR GAS LEAKS (FACTORY AND FIELD):
WARNING
Never use an open flame to check for leaks.
Turn on gas supply and test for gas leaks using a gas leak test solution (also referred to as bubble
leak solution).
NOTE: Using a soapy water solution is an
effective leak test solution but it is not recom­mended, because the soap residue that is left on the pipes/fittings can result in corrosion
over time.
A. Light the appliance (refer to the lighting
instructions label in the control compartment or in the Care and Operation Instructions
manual).
B. Brush all joints and connections with the gas
leak test solution to check for leaks. If bubbles are formed, or gas odor is detected, turn the
receiver or remote control to the “OFF” position.
Either tighten or refasten the leaking connection, then retest as described above.
C. When the gas lines are tested and leak-free
be sure to rinse off the leak testing solution.
D. Re-install the access plate, making certain the
gasket has not been damaged.
Step 7. CHECKING APPLIANCE OPERATION
Turn on burner then observe the individual
tongues of ame on the burner. Make sure all
ports are open and producing flame evenly across the burner. If any ports are blocked, or partially blocked, clean out the ports.
With gas line installed run initial system check­out before closing up the front of the unit. Follow the lighting instructions provided in the Care and Operation Instructions manual.
NOTE: Lighting Instructions are also found on the literature tag tied to the bracket above the gas valve. To access the tag, reach into the right side opening.
When rst lighting the appliance, it will take a few
minutes for the line to purge itself of air. Once purging is complete, the pilot and burner will light and operate as indicated in the instruction
manual. Subsequent lighting of the appliance will not require such purging. Inspect the pilot ame (remove logs, if necessary, handling carefully).
Electronic Appliance Checkout
To light the burner, turn “ON” the optional remote
wall switch or turn the appliance mounted ON/
OFF switch to the “ON” position. Ensure the
igniter lights the pilot. The pilot flame should engulf the flame sensor as shown in Figure 38.
Figure 36 - Gas Connection
NOTE: The gas supply line must be installed in accordance with building codes by a quali­fied installer approved and/or licensed as required by the locality. In the Commonwealth of Massachusetts, installation must be performed by a licensed plumber or gas fitter.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Pilot Hood
Flame Rod (Sensor)
Figure 38
23
Page 24
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
Step 8. LOG, VOLCANIC STONE, AND GLOWING EMBER PLACEMENT
NOTE: If installing the Contemporary Burner/Floor Kit, skip this step and instead refer to the instructions provided with the kit.
WARNING
• DO NOT operate this appliance without the
required accessories properly installed:
- floor (log set or contemporary kit), and
- firebox liner panels (ceramic or porcelain).
WARNING
DO NOT attempt to install the logs until the appliance installation has been completed, the gas line connected and tested for leaks and the initial burner operation has been checked out.
The size and position of the log set was engineered
to give the appliance a safe, reliable and attractive flame pattern. Any attempt to use a different log set in the fireplace will void the warranty and will result in incomplete combustion, sooting, and poor flame quality.
Logs get very hot and will remain hot up to one
hour after gas supply is turned off. Handle only when logs are cool. Turn off all electricity to the appliance before you install grate, volcanic stone, embers and logs.
This appliance is not designed to burn wood. Any
attempt to do so could cause irreparable damage to the appliance and prove hazardous to your safety.
If logs are not installed according to the log
installation instructions, flame impingement and improper combustion could occur and result in soot and/or excessive production of carbon monoxide (CO), a colorless, odorless, toxic gas.
Step 4. Position the individual logs as shown in Figures 42 through 46.
Logs should be placed in the order shown. Place logs 2 and 3 against the pins on the grate, NOT over them.
Proper log and twig placement is critical to encourage outstand-
ing ame appearance and prevent sooting. When positioned
properly as shown, twigs will be positioned between flame peaks and will not impinge any flames.
Cat. No. Model Description
88L53 FGE Bag of Glowing Embers 80L42 FDVS Bag of Volcanic Stone H8312 PGE Bag of Platinum Embers
Table 10 - Firebox Accessories / Parts
Figure 39
For Propane Gas Only: Do Not Place Embers On Main Ports.
Glowing Embers (Rockwool)
Step 1. Install the ceramic or porcelain firebox liner panels per the
instructions provided in kit (P/N 506019-91).
Step 2. Place volcanic stone around the burner (the entire bag of volcanic
stone will NOT be used). DO NOT PLACE VOLCANIC STONE ON THE BURNER. See Figure 41.
Step 3. Separate the glowing embers (rockwool) into pieces about the
size of a quarter (see Figure 39). Keep the pieces fluffed, not matted. Distribute these pieces over the burner as shown in Figure
40. Do not use more than necessary. When properly positioned,
the Glowing Embers will cover approximately 75% of the burner on natural gas. For propane gas, do not place embers on main ports.
NOTE: Excessive use of embers may result in sooting or poor flame. This appliance is provided with enough Glowing Embers for several ap­plications, do not feel compelled to use all that is in a new bag. For best glowing effect, replace the ember material annually. Replacement Glowing Embers are available (Catalog Number 88L53).
24
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Figure 40
Volcanic Stone
Figure 41
Page 25
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
MDLX40 & MDLX45 Log Placement
2
6
Figure 42
3
7
5
1
Log Number Description
1 Log, Center
2 Log, Rear
3 Log, Center/Left 4 Log, Center/Right
5 Log, Rear/Top
6 Log, Front/Left
7 Log, Front/Center
2
4
Figure 44
Align Groove At The Bottom Of Log (2) Over The Grate And Push It Towards The Rear.
3
4
Figure 43
1
Align Two Holes At Bottom Of Log (1) Over The Pins On The Gas Burner.
Engage Logs (3 & 4) With The Grate Pins And Align Groves At The Bottom Of The Logs Over The Grate.
Figure 45
6 5
Engage Log (6) With The Grate Pin And Align Groove At The Bottom Of The Log Over The Grate.
Align Hole At Bottom Of Log (5) Over The Pin On Log (2).
Engage Log (7) With The Pin On Log (4).
Figure 46
7
2
4
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
25
Page 26
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
Step 9. INSTALLATION AND REMOVAL OF GLASS DOOR
WARNING
When reinstalling the glass
door, the door latch screws must be securely tightened to prevent the glass door from falling out, which could potentially cause damage and possible injury.
Do not attempt to substitute the
materials used on this door, or replace cracked or broken glass.
Handle this glass with extreme
care! Glass is susceptible to damage - Do not scratch or handle roughly while reinstall­ing the glass door frame.
The glass door of this appli-
ance must only be replaced as a complete unit as provided by the manufacturer. Do not attempt to replace broken, cracked or chipped glass sepa­rately.
Do not attempt to touch the
front enclosure glass with your hands while the fireplace is in use.
WARNING
Do not operate appliance with the glass front removed, cracked or broken.
AVERTISSEMENT
Ne pas utiliser l'appareil si le panneau frontal en verre n'est pas en place, est craqué ou brisé.
Only doors certified with the appliance shall be used.
Seules des portes certifiées pour cet appareil doivent être utilisées.
Installing Glass Enclosure Panel (see Figure 47)
Retrieve the glass door. Visually inspect the gasket on the backside of the frame. Gasket surface must be clean, free of irregularities and seated firmly.
Position the door in front of the firebox opening with the top of the door held away from the fireplace (Figure 47). Lower the bottom of the door assembly on the bottom door track and set on padded surface. Pivot the door up after engaging and centering in the base channel.
Using a Phillips screwdriver, fasten the door
frame to the door latch with the two (2) screws.
The latch should pull forward to engage the door frame.
Install the door modesty shield on top flange glass door as follows: grab the door modesty shield with both hands, with the open hem going down and engage it with the upper lip of the glass door frame by pushing it all the
way down. Make sure the installed shield is
firmly in place.
With the rescreen hanging on the screen rod,
insert the right side of the rod into the existing
hole on the right modesty panel. Bend down
the rod at the center and drop the left end into the slot on the left modesty panel, being careful not to scratch the paint.
Top Flange Glass door assembly
Screws
Firebox Floor
Glass Door Assembly
Glass Door Latch (2)
Figure 47 - Installing the Glass Door
Step 10. BURNER ADJUSTMENTS
Flame Appearance and sooting
Proper flame appearance is a flame which is blue at the base and becomes yellowish-orange
in the body of the ame. When the appliance is
first lit, the entire flame may be blue and will gradually turn yellowish-orange during the first 15 minutes of operation. After 15 minutes of operation, if the flame is blue, or if the flame is
orange with evidence of sooting (black tip), the
air shutter opening may need to be adjusted.
If the air shutter opening is closed too far, sooting may develop. Sooting is indicated by black puffs developing at the tips of very long orange flames. Sooting results in black deposits forming on the logs, appliance inside surfaces and on exterior surfaces adjacent to the vent termination.
Sooting is caused by incomplete combustion in the flames and lack of combustion air enter­ing the air shutter opening. To achieve a warm yellowish-orange flame with an orange body that does not soot, the shutter opening must be adjusted between these two extremes.
Air Shutter Adjustment Guidelines
• If there is smoke or soot present, rst check
the log set positioning to ensure that the flames are not impinging on any of the logs. If the log set is properly positioned and a sooting condition still exists, then the air shutter opening should be increased.
• The more offsets in the vent system, the larger
the air shutter opening will need to be.
• An appliance operated with the air shutter
opened too far, may have flames that appear blue and transparent. These weak, blue and transparent flames are termed anemic.
• Propane models may exhibit ames which
candle or appear stringy. If this is present and persists, adjust the air shutter to a more closed position, then operate the appliance for a few more minutes to ensure that the flame normalizes and the flames do not appear sooty.
The following chart is provided to aid you in achieving the correct air shutter adjustment for your installation.
Amount of
Primary Air
If air shutter is closed too far
If air shutter is open too far
Flame
Color
Flame will be orange
Flame will be blue
Air Shutter
Adjustment
Air shutter gap should be increased
Air shutter gap should be decreased
WARNING: DO NOT abuse glass door by striking or slamming shut.
26
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 27
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
Air Shutter
Opening
Burner
Orifice
Gas
Valve
Venturi
Venturi
Burner Air Shutter Adjustment Procedure
WARNING
Air shutter adjustment should only be performed by a quali­fied professional service technician.
Ensure that the front glass
door assembly is in place and sealed After adjustment.
CAUTION
Main Burner Factory Air Shutter
Opening Setting - Inches (millimeter)
Model Nat.Gas Propane Gas
MDLX40 MDLX45
1/16 (1.59) 9/32 (7.14) 1/16 (1.59) 9/32 (7.14)
Soot will be produced if the air shutter is closed too much. Any damage due to carboning result­ing from improperly setting the air shutter is not covered under the warranty.
To adjust the flame, rotate the air shutter toward the back or toward the front of the fireplace. Position the air shutter to the factory setting as shown in the table in Figure 48. Allow the burner to operate for at least 15 minutes. Observe the flame continuously. If it appears weak or sooty as previously described, adjust the air shutter until the flame appearance is as desired.
Use the remote to adjust the flame height as desired.
Propane models may exhibit a flame pattern that may candle or appear stringy. If this is problematic or persists as the appliance is continually operated, adjust the air shutter closed as described in the previous paragraphs. Operate the appliance for a period of time as the effect diminishes, ensuring that the appliance
does not develop sooty ames. When satised
that the appliance operates properly, proceed to finish the installation.
Figure 48
Contemporary Media Shown (MDLX40)
Figure 49 - Burner Flame Appearance
Rustic Oak Logs Shown (MDLX45)
Figure 50 - Burner Flame Appearance
27
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 28
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
Glass Door
Assembly
Fireplace
Finish Combustible Or Non-Combustible Material
Bottom Of Fireplace
1/8”
Minimum
Door Track
Finish Combustible Or Non-Combustible Material
Front Face Of Fireplace
Floor Panel
FINISHING REQUIREMENTS Wall Details
Complete finished interior wall. To install the appliance facing flush with the finished wall, position framework to accommodate the thickness of the finished wall (Figure 51).
Combustible Finished Wall Materials
Header (2x4’s)
Combustible materials are
allowed above this point on the face of the appliance.
8-3/8" Min.
(213 mm)
The gray shaded area must be non-combustible or Dura Rock
Vent & 90° Elbow
Appliance
3" Min.
(76 mm)*
2 Foot Vertical
1
*
Top of
Spacers
Non-combustible materials, such as surrounds and other appliance trim, may be installed on the appliance front face with the exceptions.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel (see Figure 8). Mantels constructed of non- combustible materials may be installed at any height above the appliance opening.
Combustible materials may project beyond the side of the fireplace open­ing as long as it is kept within the shaded area illustrated in Figure 9.
A hearth extension is not required with this appliance. If a hearth extension
is used, there are two methods of installation. One, the finish combustible or non-combustible material could be ended by butting up against the front face of the fireplace and the floor panel (refer to Figure 52).
Two, the finish combustible or non-combustible material could be ended below the fireplace (refer to Figure 53). Remove the floor panel as shown in Figure 52 by removing the screws on the right side of the panel and sliding the left side away from the tab. Discard the screws and floor panel.
It is critical that there is at least a 1/8" gap between the bottom of the door track and the surface of the finish material.
28
Top of Door Frame
Fireplace (right side)
Installations with horizontal terminations which have minimum
1
vertical vent height only will require 4”(102mm) minimum side clearance as shown in shaded zone above. All other installations require 1" (25mm) minimum side clearance as specified in Figure 4 on Page 6.
* Insulation is NOT ALLOWED in the clearance zones around vent components. Keep this area free from combustible materials.
Figure 51
Figure 52
Figure 53
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 29
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
Step 11. INSTALLER INSTRUCTIONS - ATTACHING SAFETY-IN-OPERATION WARNINGS It is the installers responsibility to ensure these warnings are properly affixed during installation. These warning labels are a
critical step in informing consumers of safe operation of this appliance.
ATTACHING SAFETY IN OPERATION WARNINGS
It is required that the set of safety instruction labels
that have been furnished with the fireplace be affixed to the operation and control points of the fireplace. A safety instruction label must be affixed to the receiver wall switch plate where the fireplace is turned on and off (See Figure A) and on the remote control handheld transmitter (See Figure B). To properly complete the installation of this fireplace, locate the multi-lingual adhesive labels provided with the Care and Operation Instructions and proceed as follows:
1. Locate the wall receiver that controls the fireplace (verify the switch operates the fireplace by turn-
ing it on and off). Clean the wall receiver plate
thoroughly to remove any dust and oils. Affix the label to the surface of the plate of the wall receiver that controls the fireplace (Figure A). Choose the language primarily spoken in the home. If unknown, affix the English language label.
2. Locate the remote control transmitter and clean it thoroughly to remove any dust and oils. Affix the label to the surface of handheld transmitter (Figure B). Choose the language primarily spo­ken in the home. If unknown, affix the English language label.
3. If you are unable to locate the labels, please call Lennox Hearth Products or your nearest Lennox Hearth Products dealer to receive additional safety instruction labels free of charge.
Cat. No. H8024 Replacement Label Kit
LENNOX HEARTH PRODUCTS 1-800-655-2008
NOTE: English is red text on clear label. French and Spanish are white text on black label.
APPOSITION DES MISES EN GARDE RELATIVES À LA SÉCURITÉ D’UTILISATION
Il est impératif que le jeu d’étiquettes de sécurité qui
ont été fournies avec le foyer soient collées à côté
des dispositifs de contrôle du foyer. Une étiquette de sécurité doit être collée sur la plaque du récepteur mural
contrôlant l’allumage du foyer (voir Figure A) et sur le boîtier de la télécommande (Figure B). Pour achever l’installation correcte de ce foyer, procédez comme suit
avec les étiquettes adhésives en langues étrangères
fournies avec les instructions d’utilisation et d’entretien :
1. Repérez le récepteur mural qui contrôle le foyer (vériez que l’interrupteur contrôle le fonction ­nement du foyer en le faisant basculer de Marche à Arrêt, et vice-versa). Nettoyez soigneusement la plaque du récepteur mural pour éliminer la poussière et les traces de graisse ou d’huile. Collez l’étiquette sur la surface de la plaque du récepteur mural qui contrôle le foyer (Figure A). Choisissez la langue qui est principalement parlée dans la
résidence du propriétaire. En cas de doute, collez
l’étiquette en anglais.
2. Repérez la télécommande et nettoyez-la soigneuse-
ment pour éliminer la poussière et les traces de graisse ou d’huile. Collez l’étiquette sur le boîtier
de la télécommande (Figure B). Choisissez la langue qui est principalement parlée dans la résidence du propriétaire. En cas de doute, collez
l’étiquette en anglais.
3. Si vous ne trouvez pas les étiquettes, veuillez
appeler Lennox Hearth Products ou votre distribu­teur Lennox Hearth Products local pour recevoir
gratuitement des étiquettes supplémentaires.
Étiquettes de remplacement, n° cat. H8024
LENNOX HEARTH PRODUCTS 1-800-655-2008
Remarque : Le texte anglais est rouge sur un support transparent. Le texte français et espagnol est blanc sur un support noir.
COLOCACIÓN DE ADVERTENCIAS DE SEGURIDAD EN OPERACIÓN
Se requiere que el juego de etiquetas de instrucciones de seguridad que se incluyeron con la chimenea se coloque en los puntos de operación y control de la misma. Se debe colocar una etiqueta de instrucciones
de seguridad en la placa del interruptor de pared del receptor desde el cual se enciende y se apaga la chimenea (ver la Figura A) y en el transmisor de control remoto (ver la Figura B). Para completar correctamente la instalación de esta chimenea, encuentre las etiquetas adhesivas multilingües incluidas con las instrucciones de cuidado y operación y haga lo siguiente:
1. Identique el receptor de pared que controla la chimenea (verique que el interruptor opera la chimenea encendiéndola y apagándola). Limpie bien la placa del receptor de pared para quitar el polvo y aceite. Pegue la etiqueta en la supercie de la placa del receptor de pared que controla la
chimenea (Figura A). Seleccione el idioma que más se habla en la casa. Si no sabe cuál es, use la
etiqueta en inglés.
2. Identique el transmisor de control remoto y límpielo bien para quitar el polvo y aceite. Pegue la etiqueta
en la superficie del transmisor (Figura B). Seleccione
el idioma que más se habla en la casa. Si no sabe cuál es, use la etiqueta en inglés.
3. Si no puede encontrar las etiquetas, sírvase
llamar a Lennox Hearth Products o al distribuidor de Lennox Hearth Products más cercano para
recibir etiquetas de instrucciones de seguridad
adicionales gratuitas.
Juego de etiquetas de repuesto - Nº de cat. H8024
LENNOX HEARTH PRODUCTS 1-800-655-2008
Nota: La etiqueta en inglés es transparente con texto rojo. Las etiquetas en francés y español son negras con texto blanco.
Illustrations are for example only. Your accessories may be different.
Les illustrations sont par exemple uniquement. Vos accessoires peuvent être différents.
Las ilustraciones son sólo ejemplos. Tu accesorios pueden ser diferentes.
Figure 54
SAFETY LABEL
DIAGRAMS
DIAGRAMMES DES ÉTIQUETTES
DE SÉCURITÉ
Figure A
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
On
Remote
Off
PRG
DIAGRAMAS DE ETIQUETAS
DE SEGURIDAD
Figure B
29
Page 30
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
INSTALLATION ACCESSORIES
Listed Secure Vent® Components
Cat.
No.
H2266 SV8HTS Horizontal Square
H2265 SV8VTR Vertical Termination
H2250 SV8L6 6" (152mm) Vent
H2251 SV8L12 12" (305mm) Vent
H2252 SV8L24 24" (610mm) Vent
H2253 SV8L36 36" (914mm) Vent
H2254 SV8L48 48" (1219mm) Vent
H2255 SV8LA Telescopic Section H2256 SV8E45 45 Degree Elbow
H2257 SV8E90 90 Degree Elbow
Model
No.
Termination with Firestop/Spacer (H2260) and Adaptor (H2267)
Section
Section
Section
Section
Section
Description
H2262 SV8SU Support Strap
H2263 SV8SP Support Plate
H3908 SV8ARSA Attic Insulation
Shield (adjustable 12" to 22")
2a
B
CTSO-33/44 Shrouds for Single terminations
C
D
E
(ref. Instruction P/N
750193M)
A
CTSO-46 Shroud for double terminations
C
D
1 typ.
2a
2b
2a
2b
2b
A
2a
Open Top Shroud Kits
Inches (millimeters)
Cat. No. Model A B C D *E
H1985 CTSO-33
H1987
CTSO-44
H1986 CTSO-46
37-5/8
(955)
48-5/8 (1235)
48-5/8 (1235)
37-5/8
(955)
48-5/8 (1235)
73 1/4
(1860)
7-1/2 (191)
7-1/2 (191)
7-1/2 (191)
24-1/2
24-1/2
24-1/2
typ.
B
(622)3 (76)
(622)3(76)
(622)3(76)
12typ.
E
30
The following flashings come packaged with a storm collar
H3236 SV8F Flat Roof Flashing H2258 SV8FA 1/12 to 7/12 Adjust-
able Flashing
H2259 SV8FB 7/12 to 12/12
Adjustable Flashing
H3237 SV8SC6 Storm Collars,
6 pack
H2260 SV8HF Firestop/Spacer -
Horizontal (3-1-1 spacing)
H2261 SV8BF Firestop/Spacer -
Vertical (1-1-1 spacing)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
A
B
C
(ref. Instruction P/N 750194M)
D
Closed Top Shroud Termination Kits
Inches (millimeters)
Cat. No. Model A B C D
H1988 CTSA-33
34
(864)
5
(127)
34
(864)
(864)
34
Page 31
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
GAS CONVERSION KITS
WARNING
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instruction is not followed exactly, a fire, explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life. The qualified service agency is responsible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manu­facturer’s instructions supplied with the kit. The qualified service agency performing this installation assumes responsibility for this conversion.
AVERTISSEMENT
Cette trousse de conversion doit être installée par un technicien agréé, selon les instructions du fabricant et selon toutes les exigences et tous les codes pertinents de l’autorité compétente. Assurez-vous de bien suivre les instructions dans cette notice pour réduire au minimum le risque d’incendie, d’explosion ou la production de monoxyde de carbone pouvant causer des dommages matériels, des blessures ou la mort. Le tecnicien agréé est responsable de l’installation de cette trousse. L’installation n’est pas adéquate ni complète tant que le bon fonctionnement de l’appareil converti n’a pas été vérifié selon les instructions du fabricant fournies avec la trousse. Le fournisseur de service qualifié ayant réalisé l'installation assume les responsabilités liées à la conversion.
Step 1. TURN OFF THE GAS SUPPLY TO THE APPLIANCE and disconnect power supply at the circuit breaker. Ensure appliance is cold.
CAUTION: THE GAS SUPPLY SHALL BE SHUT OFF PRIOR TO DISCONNECTING THE ELECTRICAL POWER, BEFORE PROCEEDING WITH THE CONVERSION.
ATTENTION. AVANT D’EFFECTUER LA CONVERSION, COUPEZ D’ABORD L’ALIMENTATION EN GAZ, ENSUITE, COUPEZ L’ALIMENTATION ÉLECTRIQUE.
Step 2. Remove the front glass door/frame
and the access plate from the appliance. See Figures 37 and 47.
Step 3. Carefully remove the logs and the grate assembly / contemporary media. Exercise care
so as not to break the logs / contemporary media.
Step 4. Refer to Figure 55. Remove the two
5/16" screws securing the burner to the burner
brackets. Carefully slide the burner to the left to clear the venturi from the orifice. Set aside the screws and burner assembly in a secure location for later reinstallation.
Burner Assembly
In Canada: THE CONVERSION SHALL BE CAR-
RIED OUT IN ACCORDANCE WITH THE REQUIREMENTS OF THE PROVINCIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE RE­QUIREMENTS OF THE CAN/CGA-B149.1 INSTALLATION CODE.
LA CONVERSION DEVRA ÊTRE EF­FECTUÉE CONFORMÉMENT AUX RECOMMANDATIONS DES AUTORITÉS PROVINCIALES AYANT JURIDICTION ET CONFORMÉMENT AUX EXIGENCES DU CODE D'INSTALLATION CAN/CGA­B149.1.
Gas conversion kits are available to adapt your appliance from the use of one type of gas to the use of another. These kits contain all the necessary components needed to complete the task including labeling that must be affixed to ensure safe operation.
Kit part numbers are listed below, and the fol­lowing steps detail the conversion procedure.
Natural Gas to Propane Gas
Conversion Kits
Fireplace
Model No. MDLX40IN GCK-
MDLX45IN GCK-
Fireplace
Model No. MDLX40IP GCK-MDLX-
MDLX45IP GCK-MDLX-
Conversion Kit
Model No.
MDLX40NP
MDLX45NP
Propane Gas to Natural Gas
Conversion Kits
Conversion Kit
Model No.
40PN
45PN
Cat. No.
Conversion
Kit Cat. No.
H8668
H8669
H8670
H8671
Gas Valve Assembly
Burner Orifice
Figure 55
Step 5. Remove the control compartment access
door and gasket by removing the twelve (12)
screws securing it, and set it aside for later rein­stallation.The gas valve can be accessed through the opening, or the complete assembly can be removed by sliding the assembly to the right.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
31
Page 32
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
Step 6. Refer to the instructions provided with the SIT regulator conversion kit. Using a
Torx T20 (with 1/4" shank and center hole) or
slotted screwdriver, remove and discard the two pressure regulator mounting screws, the pressure regulator tower, and the diaphragm
assembly (if applicable). Properly dispose of all removed components. Make sure the rubber
gasket installed on the back of the replacement pressure regulator is properly positioned.
Step 7. Install the new stepper motor pressure regulator assembly using the supplied screws.
Securely tighten the screws (25 lb-in).
Step 8. Attach the enclosed identification label to the valve body where it can be easily seen.
Step 9. Make stepper motor and valve electrical connections.
Step 10. Remove the pilot hood assembly to access the hexed pilot orice. Using a 5/32". al­len wrench, remove and replace the pilot orifice with the one provided with the kit.
NOTE: Use extreme care to avoid damaging the igniter assembly.
Step 11. Refer to Figure 57 and remove the pilot hood assembly to access the hexed pilot orifice. Remove and replace the orifice with the one provided with the kit.
Step 12. (Refer to Figure 55 on Page 31 and Figure 58)
VERIFY THE PROPER ORIFICE SIZE BE­FORE INSTALLING IT.
Pilot Hood
Pilot Orifice
Figure 57
A. Remove the orifice from the manifold and
replace it with the one provided in the kit. See the following table for orifice sizes for natural and propane models. Figure 58 illustrates the orifice. Use pipe joint compound or Tef­lon tape on all pipe fittings before installing (ensure propane resistant compounds are used in propane applications, do not use pipe
joint compounds on are ttings).
B. Retrieve the burner and slide the venturi tube
over the orifice. Set the burner assembly into its position and secure it.
C. Reinstall the grate assembly. Step 13. Reassemble the remaining compo-
nents by reversing the procedures outlined in the preceding steps.
Step 14. Attach the conversion label provided in the conversion kit to the rating plate on the appliance.
Step 15. Apply gas to the system and relight
appliance. With the main burner "ON", test the
new pressure regulator assembly and all gas line joints for leaks using a gas leak test solu­tion. See Test All Connections For Gas Leaks on Page 23.
Burner Orifice Sizes
Elevation 0-4500 feet ( 0-1372 meters)
Model Natural Gas
drill size (inches)
MDLX40
MDLX45
Table 11
0.1405" (#28)*
• H2286
0.161" (#20)*
• H2288
* Standard size installed at factory
• Part /Cat. Number
Propane
drill size (inches)
0.086" (#44)*
• H2287
0.093" (#42)*
• H4816
Figure 58
Step 16. Relight the main burner and verify proper burner ignition and operation. See Burner Adjustments Pages 26 and 27.
Inspect the pilot system for proper flame. The pilot flame should engulf the flame sensor as shown in Figure 59.
The lighting instructions can be found on the lighting label in the control compartment or in
the Care and Operation Manual provided with
the appliance. Step 17. Using a manometer, test the inlet and
manifold gas pressures. See Tables 2 and 3 on Page 4.
ALWAYS TEST PRESSURES WITH THE VALVE REGULATOR CONTROL AT THE HIGHEST SETTING.
SEE PAGE 26 FOR AIR SHUTTER ADJUSTMENT GUIDELINES.
Igniter Rod
Pilot Hood
32
(from DFC Wire Harness)
Manifold (OUT) Test Port
Inlet (IN) Test Port
Wire
(from DFC Wire
Harness)
Main Gas Inlet
3/8" NPT
Figure 56
Green Wire
Connect GTMS wire harness.
Pressure Regulator Tower
Yellow Ground Wire (from DFC Wire Harness)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Flame Sensor
Figure 59
Pilot Nozzles
Page 33
NOTES
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
33
Page 34
LENNOX HEARTH PRODUCTS • MONTEBELLO® DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information.
LENNOX®, the LENNOX design, DAVE LENNOX, the image of DAVE LENNOX and other related LENNOX marks are registered or common law trademarks of Lennox Industries Inc. and are used with permission.
Printed in U.S.A. © 2012 Lennox Hearth Products LLC
34
P/N 506023-15 Rev. B 04/2013
1508 Elm Hill Pike, Suite 108 • Nashville, TN 37210
Loading...