Lennox MLBV-35NM, MLBV-40NM, MLBV-35PM, MLBV-40NE, MLBV-40PM Installation Instructions Manual

...
Page 1
AVERTISSEMENT : Assurez-vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d’incindie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result, causing property damage, personal injury, or death.
WARNING /AVERTISSEMENT/AVISO
• HOT GLASS WILL CAUSE BURNS.
• DO NOT TOUCH GLASS UNTIL COOLED.
• NEVER ALLOW CHILDREN TO TOUCH GLASS.
• UNE SURFACE VITRÉE CHAUDE PEUT CAUSER DES BRÛLURES.
• LAISSER REFROIDIR LA SURFACE VITRÉE AVANT D'Y TOUCHER.
• NE PERMETTEZ JAMAIS À UN ENFANT DE TOUCHER LA SURFACE VITRÉE.
• EL VIDRIO CALIENTE CAUSARÁ QUEMADURAS.
• USTED DEBE NUNCA TOCAR EL VIDRIO CALIENTE.
• LOS NIÑOS DEBEN NUNCA TOCAR EL VIDRIO.
- Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
- Ne pas entreposer ni utilizer d’essence ni d’autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucan interrupteur. Ne pas vous servir des
téléphones se trouvant dans le bâtiment où vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis
un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service des incindies.
- L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
B-Vent Gas Fireplaces MLBV 35/40 Models
P/N 506015-04 Rev. C 01/2012
This manual is one of a set of two supporting this product. Refer to P/N 506017-03 for Care and Operation Instructions.
Ce manuel est disponible en francais, simplement en faire la demande. Numéro de la pièce 506223-21.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
INSTALLATEUR : Laissez cette notice avec l'appareil. CONSOMMATEUR : Conservez cette notice pour consultation ultérieure.
MODELS
MLBV-35NM MLBV-35PM
ITS Report No. 100017854
Please read and understand these instructions
MILLIVOLT:
MLBV-40NM MLBV-40PM
before starting installation.
ELECTRONIC:
MLBV-35NE MLBV-40NE
Page 2
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
TABLE OF CONTENTS
Packaging .........................................Page 2
Introduction ......................................Page 2
General Information ..........................Page 2
Gas Pressure Requirements ..............Page 4
Orifice Sizes ......................................Page 4
Gas Valve Diagrams ..........................Page 4
Requirements for the Commonwealth
of Massachusetts .......................Page 4
New York City Approval .....................Page 4
Cold Climate Insulation .....................Page 5
Location ............................................Page 5
Vent Termination Clearances:
Multiple Terminations.....................Page 6
Gas Vent Rule ................................Page 6
Minimum Clearances to Combustibles:
Appliance and Vent Clearances ......Page 7
Hearth Extension ............................Page 7
Wall Finishes / Surrounds /
Mantels .......................................Page 7
Pre-Installation Steps (Remove
Glass Enclosure Panel) ...............Page 8
Typical Installation Sequence ............Page 8
Detailed Installation Steps: Step 1. Construct Appliance
Framing ............................Page 8
Fireplace and Framing
Specifications ...................Page 9
Step 2. Route the Gas Line ..............Page 11
Step 3. Install Venting System and
Exterior Termination .........Page 11
Step 4. Install Field Wiring ..............Page 12
Wiring Diagrams .................Page 13
Step 5. [Optional] Install Outside
Combustion Air Kit ............Page 14
Installation Accessories ......Page 14
Step 6. Connect the Gas Line ..........Page 15
Step 7. Verify Appliance
Operation .........................Page 16
Step 8. Install Volcanic Stone, Glowing
Embers, and Logs ...........Page 17
MLBV-35 Log Placement ....Page 18
MLBV-40 Log Placement ....Page 19
Step 9. Install the Glass Enslosure
Panel ...............................Page 20
Step 10. Burner Air Shutter
Adjustments .....................Page 20
Step 11. Perform Spillage Test ..........Page 22
Manually-Reset Safety Limit
Switch ..............................Page 22
Step 12. Install Hood .........................Page 23
Step 13. Finishing Requirements ......Page 23
Step 14.
Warnings ......................................Page 24
Gas Conversion Kits .........................Page 25
2
Attach Safety-in-Operation
PACKAGING
The assembled vented gas fireplace is packaged with the following items:
1 - One log set located in firebox area.
2 - One envelope containing the literature
package which consists of the care and operations manual, installation instruc­tions, safety-in-operation warning labels and warranty; envelope is located in the control compartment.
3 - One hood located behind the glass enclo-
sure panel assembly.
4 - One bag of decorative volcanic stone located
in the lower control compartment.
5 - One bag of glowing embers located in the
lower control compartment.
INTRODUCTION
The Millivolt appliances have a millivolt gas control valve with piezo ignition system.
The Electronic appliances have a battery backed-up electronic intermittent pilot ignition system. No external electrical power is required to operate these appliances; however, 120V AC is recommended (see Step 4, “Install Field Wiring,” on Page 12).
Use Only These Approved Vent Components:
These vented gas fireplaces are designed for residential applications. They must be installed with approved Type-B double-wall vent pipe systems and a listed vent termination routed to the outside atmosphere. Use only the proper size listed below.
• 4" B-Vent for 35" models and 5" B-Vent for 40" models.
GENERAL INFORMATION
WARNING
B-Vent appliances are not designed to operate in negatively pressured environments (pressure within the home is less than pressures outside). Significant negatively pressured environments caused by weather, home design, or other devices may impact the operation of these appliances. Negative pressures may result in poor flame appearance, sooting, damage to property and/or severe personal injury. Do not operate these appliances in negatively pressured environments.
WARNING
Young children should be care­fully supervised when they are in the same room as the appli­ance. Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recom­mended if there are at risk individuals in the house. To restrict access to a fireplace or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
AVERTISSEMENT
Les jeunes enfants devraient être surveillés étroitement lorsqu’ils se trouvent dans la même pièce que l’appareil. Les tout petits, les jeunes enfants ou les adultes peuvent subir des brûlures s’ils viennent en contact avec la sur­face chaude. Il est recommandé d’installer une barrière physique si des personnes à risques habi­tent la maison. Pour empêcher l’accès à un foyer ou à un poêle, installez une barrière de sécu­rité; cette mesure empêchera les tout petits, les jeunes enfants et toute autre personne à risque d’avoir accès à la pièce et aux surfaces chaudes.
Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition.
Les enfants et les adultes devraient être infor-més des dangers que posent les températures de surface élevées et se tenir à distance afin d’éviter des brûlures ou que leurs vêtements ne s’enflamment.
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERATION MAY VOID THE WARRANTY, CERTIFICATION, AND LISTINGS OF THIS UNIT.
Page 3
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
GENERAL INFORMATION
(continued)
WARNING
Improper installation, adjust­ment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualied installer, service agency or the gas supplier.
WARNING
Failure to comply with these installation instructions will result in an improperly installed and operating appliance, void­ing its warranty. Any change to this appliance and/or its operat­ing controls is dangerous.
WARNING
Clothing or other ammable material should not be placed on or near the appliance.
AVERTISSEMENT
On ne devrait pas placer de vêtements ni d’autres matières inammables sur l’appareil ni à proximité.
WARNING
Any safety screen or guard removed for servicing the appli­ance must be replaced prior to operating the appliance.
AVERTISSEMENT
Tout écran ou protecteur retiré pour permettre l’entretien de l’appareil doit être remis en place avant de mettre l’appareil en marche.
WARNING
Improper installation or use of this appliance can cause serious injury or death from re, burns, explosion or carbon monoxide poisoning.
Note: Installation and repair should be done by a qualified service person. The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etcetera. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
Remarque : L’installation et la répara­tion devrait être confiées à un technicien qualifié. L’appareil devrait faire l’objet d’une inspection par un technicien profes­sionnel avant d’être utilisé et au moins une fois l’an par la suite. Des nettoyages plus fréquents peuvent être nécessaires si les tapis, la literie, et cetera produisent une quantité importante de pous-sière. Il est essentiel que les compartiments abritant les commandes, les brûleurs et les conduits de circulation d’air de l’appareil soient tenus propres.
Do not use these appliances if any part has been under water. Immediately call a qualified, professional service technician to inspect the appliance and to replace any parts of the control system and any gas control which have been under water.
Ne pas utiliser cet appareil s’il a été plongé, même partiellement, dans l’eau. Appeler un technicien qualifié pour inspecter l’appareil et remplacer toute partie du système de commande et toute commande qui a été plongée dans l’eau.
Only trim kit(s) supplied by the manufacturer shall be used in the installation of this ap­pliance.
Seules les trousses de garniture fournies par le fabricant doivent être utilisées pour l’installation de cet appareil.
These appliances comply with National Safety Standards and are tested and listed by ITS (Report No. 100017854) to ANSI Z21.50 (in Canada, CSA-2.22) and to CAN/CGA-2.17-M91 in both USA and Canada (latest editions at time of manual publication) as vented gas fireplaces.
Both millivolt and electronic versions of these appliances are listed by ITS for instal­lation in bedrooms in the United States (not approved in Canada).
These appliances must not be connected to a chimney or flue serving a separate solid fuel burning appliance.
Installation must conform to local codes, or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 (latest edition), or the Natural Gas and Propane Instal­lation Code, CAN/CSA B149.1 (latest edition).
The appliance, when installed, must be electri­cally grounded and wired in accordance with local codes or, in the absence of local codes, with the USA National Electrical Code, ANSI/NFPA
70 (latest edition) or, in Canada, the Canadian Electrical Code, CSA C22.1 (latest edition).
Provide adequate clearances around air open­ings and adequate accessibility clearance for service and proper operation. Never obstruct the front opening of the appliance.
These appliances are designed to operate on natural or propane gas only. The use of other fuels or combination of fuels will degrade the performance of this system and may be dangerous.
These fireplaces are designed as supplemental heaters; therefore, it is advisable to have an alternate primary heat source when installed in a dwelling.
MILLIVOLT MODELS: The millivolt appliances are manually controlled and feature a spark igniter (piezo) that allows the appliance's pilot gas to be lit without the use of matches or bat­teries. This system provides continued service in the event of a power outage.
ELECTRONIC MODELS: The electronic appli­ances are manually controlled and feature an electronic intermittent pilot ignition system. External electrical power is required to operate these units.
ALL MODELS: Both millivolt and electronic models come standard with a manually­modulated gas valve; flame appearance and heat output can be controlled at the gas valve. BTU input rates for all models are listed in Table 1, below.
Input (BTU/hr) Manually-Modulated
Gas Valves (all models)
Models
MLBV-35
MLBV-40
Table 1
Input Rate (BTU / HR)
Natural Gas Propane Gas
17,000 high
13,000 low
22,000 high
17,000 low
17,000 high
14,000 low
20,000 high
15,500 low
3
Page 4
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
GAS PRESSURE REQUIREMENTS
(All Models)
Tables 2 and 3 show the appliances' inlet and manifold gas pressure requirements:
Inlet Gas Supply Pressure
(All models)
Fuel # Minimum Maximum
Natural Gas
Propane
4.5" WC
(1.12 kPa)
11.0" WC
(2.74 kPa)
Table 2
Manifold Gas Supply Pressure
(All models)
Fuel # Low High
Natural
Gas
Propane
(Lo) 2.2" WC
(0.55 kPa)
(Lo) 6.3" WC
(1.57 kPa)
Table 3
Test gauge connections are provided on the front of the gas control valve, identified IN for the inlet and OUT for the manifold side (see Figures 1 and 2).
Propane tanks are at pressures that will cause damage to valve components. Verify that the tanks have step-down regulators to reduce the pressure to safe levels.
These appliances must be isolated from the gas supply piping system (by closing their individual manual shut-off valve) during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
These appliances and their individual shut-off valves must be disconnected from the gas supply piping system during any pressure testing of that system at pressures greater than 1/2 psig (3.5 kPa).
4
10.5" WC
(2.61 kPa)
13.0" WC
(3.23 kPa)
(Hi) 3.5" WC
(0.87 kPa)
(Hi) 10.0" WC
(2.49 kPa)
ORIFICE SIZES
Sea Level to High Altitude
(All Models)
These appliances are tested and approved for installation at elevations of 0–4500 feet (0–1372 meters) above sea level using the standard burner orifice sizes (marked with an asterisk (*) in Table 4, below).
For elevations above 4500 feet, contact your gas supplier or a qualified service technician.
Deration
At higher elevations, the amount of BTU fuel value delivered must be reduced by either:
• using gas that has been derated by the gas
company,
• changing the burner orifice to a smaller size
as regulated by the local authorities having jurisdiction and by the (USA) National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition or, in Canada, the CAN/CSA-B149.1 codes - latest edition.
Install the appliance according to the regulations of the local authorities having jurisdiction and, in the USA, the National Fuel Gas Code NFPA 54 / ANSI Z223.1 - latest edition or, in Canada, the CAN/CSA-B149.1 - latest edition.
NOTE: Flame appearance will diminish 4% per thousand feet of altitude.
Burner Orifice Sizes
Elevation 0-4500 feet ( 0-1372 meters)
Model
Series
MLBV-35
MLBV-40
Table 4
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Nat.Gas
drill size (inches)
#48 (0.076")*
drill size (inches)
#56 (0.046")*
H1236•
#43 (0.089")*
#55 (0.052")*
99K75•
Standard size installed at factory.
*
Part /Catalog Number.
Propane
62L37•
19L52•
GAS VALVE DIAGRAMS
See Figure 1 for millivolt models and Figure 2 for electronic models.
Main Gas Control Knob
OFF/PILOT/ON
N
O
T
O
it
L
I
P
O
F
F
OUT
IN
Manifold Pressure Tap
Inlet Pressure Tap
Pilot Adjustment
I
P
W
O
L
H
I
HI/LO Variable Flame Height Adjustment
Screw
T
O
L
HTPTHTPT
Figure 1 - SIT Millivolt Gas Valve
Supply Gas Inlet
Pressure-Tap (Manifold)
IN
PILOT
Pilot Gas Outlet
Regulator Mounting Screw
Pressure-Tap (Inlet)
Burner Stage
Terminal
VENT
OUT
IN
HI
Ground (TP)
LO
TH
TH
TP
Pilot Stage Terminal
TP
Figure 2 - Dexen Electronic Gas Valve
REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
These fireplaces are approved for installation in the US state of Massachusetts if the following additional requirements are met:
• Install this appliance in accordance with Massachusetts Rules and Regulations 248 C.M.R.
• Installation and repair must be done by a plumber or gas fitter licensed in the Com­monwealth of Massachusetts.
• The flexible gas line connector used shall not exceed 36 inches (92 centimeters) in length.
• The individual manual shut-off must be a T-handle type valve.
NEW YORK CITY APPROVAL
New York City, NY (MEA)
These fireplaces are approved for installation in New York City in the US state of New York if the following additional requirement is met:
• An Outside Combustion Air Kit (FOAK-4, FOAK-4LD, or DK-4) must be installed. See Step 5 on Page 14.
Page 5
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room. It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests, if floor is above ground level. Gas line holes and other openings should be caulked or stuffed with unfaced fiberglass insulation. Check local codes for
additional requirements.
If the fireplace is being installed on a cement slab in cold climates, a sheet of plywood or other raised, insulated platform can be placed underneath to prevent cold transfer to the fireplace and into the room. It also may help to sheetrock the inside surfaces and/or tape for maximum air tightness.
LOCATION
In selecting the location, the aesthetic and functional use of the appliance are primary concerns. However, vent system routing to the exterior and access to the fuel supply are also important.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies (Figure 3).
En raison des températures élevées, l’appareil devrait être installé dans un endroit où il y a peu de circulation et loin du mobilier et des tentures (Figure 3).
The location should also be free of electrical, plumbing or other heating/air conditioning ducting.
These appliances are equipped with an inte­gral combustion air door and actuator arm.
Combustion air kits are optional and must be installed before removing the securing screw allowing the movement of the combustion air actuator arm (see Step 5 on Page 14).
Be aware that this is a heat-producing ap­pliance. Objects placed above the unit are exposed to elevated temperatures.
The appliance should be mounted on a fully supported base extending the full width and depth of the unit. The appliance may be located on or near conventional construction materials. However, if installed on combustible materials, such as carpeting, vinyl tile, etc., a metal or wood barrier covering the entire bottom surface must be used.
These appliances may be used for bedroom installations in the United States and are listed accordingly. These units may not be installed in bedrooms in Canada.
Figure 3: Typical Locations
Note: When the unit is installed with one side flush with a wall, see Figure 5 on Page 7.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
5
Page 6
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
VENT TERMINATION CLEARANCES
Multiple Terminations
These appliances may vent adjacent to and at the same level with any other gas appliances (including direct vent appliances), provided there is at least 2 ft (0.6 m) between the proxi­mal edges of the vent caps. These appliances may be vented adjacent to a chimney vent servicing a solid fuel fireplace, provided the B-vent cap is at least 2 ft (0.6 m) away from the nearest point of the chimney opening.
Gas Vent Rule
Gas vent caps are not permitted within 8 ft (2.4 m) of a vertical wall or similar obstruction. Gas vent caps that are located 8 ft or more from a portion of a building that extends at an angle greater than 45° upward from the horizontal may terminate in accordance with Figure 4,
provided that any discharge opening on the cap is NEVER LESS THAN 2 ft (0.6 m) horizontally from the roof surface (National
Fuel Gas Code ANSI Z223.1 (NFPA 54) “Gas Vent Termination” section) (CAN/CGA B149.1).
Gas Vent Rule
Figure 4
X
12
Roof Pitch is X/12
Minimum Height from Roof to Lowest Discharge Opening
1" (25 mm) Minimum
Termination Heights For Vents
Above Flat Or Sloped Roofs Ref. NFPA 54 / ANSI Z223.1
Roof Pitch * Feet * Meters
Flat to 6/12 1.0 0.3 6/12 to 7/12 1.25 0.38 7/12 to 8/12 1.5 0.46 8/12 to 9/12 2.0 0.61
9/12 to 10/12 2.5 0.76 10/12 to 11/12 3.25 0.99 11/12 to 12/12 4.0 1.22 12/12 to 14/12 5.0 1.52 14/12 to 16/12 6.0 1.83 16/12 to 18/12 7.0 2.13 18/12 to 20/12 7.5 2.29 20/12 to 21/12 8.0 2.44
Table 5
6
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 7
5 (127)
8-1/4
(209)
14
(356)
12 (305)
19
(483)
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
MINIMUM CLEARANCES TO COMBUSTIBLES
Appliance and Vent Clearances
The appliance is approved with zero clearance to combustible materials on all sides (as detailed in Table 6), with the following exception: When
the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend beyond the front edge of the unit (see Figure 5).
MINIMUM CLEARANCES
Back 0 in. (0 mm) to Standoffs or Dimples
Sides 0 in. (0 mm) to Standoffs or Dimples**
Top 3 in. (76 mm)
Floor 0 in. (0 mm)
From Bottom of Unit
to Ceiling
Vent 1 in. (25.4 mm)
SERVICE CLEARANCES
Front 3 ft. (0.9 m)
Table 6
**Note: See Step 1 on Page 8 for clearance requirements to the nailing flange at each side of the unit and any screw heads adjacent to it.
64 in. (1626 mm)
At 14" minimum side wall clearance, a combustible wall can project to any length.
At 8-1/4" side wall clearance, a combustible wall can project 12".
o
45
Protected wall shown in white
Top View of
Fireplace
Combustible Materials Allowed In Shaded Area “Safe Zone”
Combustible walls shown in dark gray.
Combustible materials may project beyond one side of the fireplace opening as long as they are kept within the shaded areas illustrated here.
Inches (millimeters)
Figure 5 - Minimum Distance to Unprotected Side Wall
Mantel Depth
18 (457)
16 (406)
inches (millimeters)
Hearth Extension
A hearth extension is not required with this appliance. If a hearth extension is used, do not block the lower control compartment door. Any hearth extension used is for appearance only and does not have to conform to standard hearth extension installation requirements.
Wall Finishes / Surrounds / Mantels
Note: Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined by the appliance front face (black sheet metal). Never allow combustible materials to be positioned
in front of or overlapping the appliance face (see Figure 5; also see Figure 30 on Page 23).
Non-combustible materials, such as surrounds and other appliance trim, may be installed on the appliance face with these exceptions: they must not cover any portion of the removable glass panel.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel. See Figure 6. Mantels constructed of non­combustible materials may be installed at any height above the appliance opening; however, do not allow anything to hang below the fireplace hood.
Note: We recommend the use of high-temperature paint (rated 175°F or higher) on the underside of the mantel.
14 (356)
12 (305)
10 (254)
8 (203)
12
(305)
10
(254)
(203)
6
8
(152)
(102)
2
4
(51)
Figure 6 - Minimum Mantel Clearances
Header
Top of Appliance
Note - Hood shown as positioned.
7
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 8
Top Standoff Spacers*
Flush Nailing
1/2" Nailing Flange
5/8" Nailing Flange
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
PRE-INSTALLATION STEPS
(Remove Glass Enclosure Panel)
The appliance is shipped with all gas controls and components installed and pre-wired.
Note: Remove the glass enclosure panel before installing the fireplace.
To remove the glass enclosure panel:
1. Remove the shipping carton, and then re­move the shipping pad, exposing the front glass panel.
2. Open the two latches securing the glass panel (under the firebox floor).
3. Remove the glass panel by tilting it outward at the bottom and lifting it up.
4. Set aside the glass enclosure panel in a safe location to protect it from inadvertent damage.
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation is outlined below, with page number references to the related detailed instructions.
NOTE: Each installation is unique and may result in variations to these steps.
Step 1. (Pages 8–10) Construct the appliance
framing.
Position the appliance within the
framing and secure with nailing brackets.
IMPORTANT! Bend up the appropri-
ate top standoff spacers for the drywall/finish material thickness to be used (see Figure 7). Bend up the
outer pair for 1/2" ma terials and the inner pair for 5/8" materials.
Bend up the outer pair for 1/2" ma-
terials and the inner pair for 5/8" materials.
Bend out the appropriate nailing
flanges for the drywall/finish material to be used.
Nailing flanges are provided for flush
framing, 1/2 inch and 5/8 inch fram­ing depths (see Figure 7).
Step 2. (Page 11) Route the gas supply line
to the appliance location.
Step 3. (Page 11) Install the vent system and
exterior termination.
Step 4. (Page 12) Install field wiring. a. Millivolt Appliances: Install the
operating control switch (not factory provided).
b. Electronic Appliances: Field wire
8
and install operating control switch.
Step 5. (Page 14) [OPTIONAL]: Install
outside supplemental combustion air kit.
Step 6. (Page 15) Make connection to gas
supply.
Step 7. (Page 16) Verify appliance operation.
Step 8. (Page 17) Install the logs, decorative
volcanic stone, and glowing embers.
Step 9. (Page 20) Install the glass enclosure
panel.
Step 10. (Page 20) Adjust burner air shutter
to ensure proper flame appearance.
Step 11. (Page 22) Perform spillage test.
Step 12. (Page 23) Install hood.
Step 13. (Page 23) Complete finished interior
wall.
Step 14. (Page 24) Attach "Safety-in-
Operation" warnings.
DETAILED INSTALLATION STEPS
Step 1. Construct Appliance Framing
Frame the appliance as illustrated in Figures 8-1 and 8-2. All framing details must allow for
a minimum clearance to combustible framing members as shown in Table 6, Page 7.
If the appliance is to be elevated above floor level, a solid continuous platform must be constructed below the appliance.
Headers may be in direct contact with the appli­ance top standoff spacers when they are bent up vertically, maintaining the 3" clearance to the fireplace top, but must not be supported by them or notched to fit around them. All construction above the appliance must be self-supporting. DO NOT use the appliance
for structural support.
Secure the fireplace to the side framing mem­bers using the unit's nailing flanges — one top and bottom on each side of the fireplace front. See Figure 7. Use 8d nails or equivalent.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Header Spacing Top Standoffs
*IMPORTANT! Bend up the Top Standoff Spacers before installation.
Use outer pair for 1/2" materials and inner pair for 5/8" materials.
Side
Framing
(Left side front corner of fireplace shown.
NOTE: The nailing flanges, combustible members, and screw heads in areas directly adjacent to the nailing flanges are EXEMPT from the 1/2” clearance to combustible requirements for the firebox outer wrapper.
Combustible framing may be in direct contact with the nailing flanges and may be located closer than 1/2” from screw heads and the firebox wrapper in areas adjacent to the nailing flanges.
Frame the opening to the exact dimensions specified in the framing details in this manual.
Figure 7
~
Nailing flanges are provided at all four corners at 5/8", 1/2", and flush settings.
Fireplace secured to framing
by nailing flanges
Right side requirements are the same.)
5/8” Nailing Flange
1/2” Nailing Flange
Fireplace Nailing Flanges
WARNING
Failure to position the parts in accordance with these diagrams or failure to use only parts specifi­cally approved with this appliance may result in property damage or personal injury.
AVERTISSEMENT
Risque de dommages ou de blessures si les pièces ne sont pas installées conformément à ces schémas et ou si des pièces autres que celles spécifiquement approuvées avec cet appareil sont utilisées.
Page 9
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
FIREPLACE AND FRAMING SPECIFICATIONS
NOTE: Diagrams, illustrations and photographs are not to scale. Product designs, materials, dimensions, specifications, colors, and prices are subject to change or discontinuance without notice.
Input (BTU/hr) Manually-Modulated
Gas Valves (all models)
Model
MLBV-35
MLBV-40
Input Rate (BTU / HR) Natural Gas Propane Gas 17,000 high
13,000 low
22,000 high
17,000 low
17,000 high
14,000 low
20,000 high
15,500 low
FIREPLACE FRAMING DIMENSIONS
Construct framing with 2x4 or larger lumber.
B
C
1/2
A
A
Framing Dimensions
Model No. A B C
MLBV-35
MLBV-40
in. 35-1/4 35-1/4 16
mm 895 895 406
in. 40-1/4 40-1/4 16
mm 1022 1022 406
“C” is the required framing depth dimension when the finish material (drywall) thickness is 1/2 in. (13mm).
Figure 8-1
CORNER FRAMING DIMENSIONS
F
D
E
Back wall of chase/enclosure (including any finishing materials)
Corner Framing Dimensions
Model No. D E F G
MLBV-35
MLBV-40
in. 35-1/4 57-1/2 40-5/8 28-3/4
mm 895 1461 1032 730
in. 40-1/4 61-13/16 48-11/32 30-11/16
mm 1022 1554 1101 779
G
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
9
Page 10
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
J
(13 mm)
M
Front View
H
L
K
J
Q
N
P
Top View
Flue Outlet for B-Vent Connection: 35 Models = 4 in. (102 mm) 40 Models = 5 in. (127 mm)
9-1/4 in. (235 mm)
1/2 in.
(13 mm)
APPLIANCE SPECIFICATIONS
M
N
P
1/2 in.
Top View
Flue Outlet for B-Vent Connection: 35 Models = 4 in. (102 mm) 40 Models = 5 in. (127 mm)
9-1/4 in. (235 mm)
H
K
L
Q
Front View
Figure 8-2
in.
mm
in.
mm
32-1/4
819
37-1/4
946
H J L M N P QK
28-1/8
23-1/4
714
28-1/4
33-1/8
841
59032813
71837940
35-1/4
89525635
40-1/4
1022307621538138965
12-1/2
31733838
Model No.
MLBV-35
MLBV-40
Vertical Venting Through Ceiling
Frame Ceiling Opening: To locate the center of the vertical run, use a plumb line from the ceiling above the appliance.
ELECTRICAL INLET
2-3/4 in. x 2 in.
(70 mm x 51 mm)
COVER PLATE with
KNOCKOUT (Right Side)
GAS INLET KNOCKOUT*
*NOTE: It is recommended that gas be stubbed in from LEFT side only.
Optional Electrical Inlet
Knockout requiring a
field-provided Junction
3 in. (76 mm)
Box (Either Side)
3 in. (76 mm)
Hood
16 in.
(406 mm)
5-7/8 in. (149 mm)
Right Side View
9-1/2 in. (241 mm)
1-5/8 in. (42 mm)
9-1/2 in. (241 mm)
7-1/8 in. (181 mm)
7-3/8 in. (187 mm)
Hood
16 in.
(406 mm)
5-7/8 in.
(149 mm)
Left Side View
10
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 11
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
Step 2. Route the Gas Line
Route a 1/2" (13 mm) gas line to either side of the appliance (left side routing is shown in Figure 9 ). Gas lines must be routed, con­structed, and made of materials that are in strict accordance with local codes and regulations. All appliances are factory-equipped with a flex­ible gas line connector and 1/2-inch shutoff valve. (See Step 6 on Page 15.)
NOTE: Gas line can be routed to either side. Reverse this illustration if routing to right side.
Also see Figures 8-1 and 8-2.
Figure 9: Route Gas Line
Proper Sizing of Gas Line
Properly size and route the gas supply line from the supply regulator to the area where the appliance is to be installed per requirements outlined in the National Fuel Gas Code, NFPA 54 - latest edition (USA) or CAN/CSA-B149.1 ­latest edition (Canada).
Never use galvanized or plastic pipe. Gas lines must be routed, constructed and made of ma­terials that are in strict accordance with local codes and regulations.
IMPORTANT: It is critical that a licensed installer perform this step strictly per NFPA.
We recommend that a qualified, licensed plumber or gas fitter be hired to correctly size and route the gas supply line to the appliance. Installing a gas supply line from the fuel supply to the appliance involves numerous considerations of materials, protection, sizing, locations, con­trols, pressure, sediment, and more. Certainly no one unfamiliar and unqualified should attempt sizing or installing gas piping.
Notes:
• All appliances are factory-equipped with a flexible gas line connector and 1/2 inch shutoff valve (see Figure 17 on Page 15).
• See Massachusetts Requirements on Page 4 for additional requirements for installa­tions in the state of Massachusetts in the USA.
• The gas supply line should NOT be con­nected to the appliance until Step 6 on Page
15).
• A pipe joint compound rated for gas should be used on the threaded joints. Ensure that
propane-resistant compounds are used in propane applications. Be very careful that
the pipe compound does not get inside the pipe.
• It is recommended to install a sediment trap in the supply line as close as possible to the appliance. Appliances using propane should have a sediment trap at the base of the tank.
• Check with local building official for local code requirements (e.g., whether below­grade penetrations of the gas line are al­lowed, etc.).
IMPORTANT: If propane is used, be aware that if the tank size is too small (i.e., under 100 lbs if this is the only gas appliance in the dwell­ing; ref. NPFA 58), there may be pressure loss resulting in insufficient fuel delivery, which can result in sooting, severe delayed ignition, or other malfunctions. Any damage resulting from an improper installation, such as this, is not covered under the limited warranty.
Step 3. Install Venting System and Exterior Termination
These instructions should be used as a guideline and do not supercede local codes in any way.
Install venting according to local codes, these instructions, the current National Fuel Gas Code in the USA (ANSI-Z223.1) or the current standards in Canada (CAN/CSA-B149.1).
MLBV-35 and MLBV-40 series fireplaces must be vertically vented using listed type­B, double-walled vent pipe with the proper diameter as listed below and a listed vent termination.
Required Pipe Diameter
MLBV-35 series: Requires 4 in. (102 mm) MLBV-40 series: Requires 5 in. (127 mm)
WARNING
Sharp Edges. Watch Your Fingers!
WARNING: EDGES OF SHEET METAL ARE SHARP! WEAR PROTECTIVE GLOVES AND USE EXTREME CARE WHEN HANDLING.
Required tools:
• Sheet Metal-resistant Gloves
• Tin Snips
1. Using tin snips, cut the three connecting
points securing the slug to the three tabs in the flue collar (as shown in Figure 10a), and remove the slug.
Carefully dispose of slug in an appropriate
container.
Cutting
points
Slug
Figure 10a
2. Connect the proper size Type B-vent system
to the fireplace flue collar by bending up the three tabs and securing with three sheet metal screws (No. 8 or larger) bend up tabs. See Figure 10b. Then install the remainder of the Type B-vent to the outside.
Type B-Vent
MLBV-35 models: 4 in. (102 mm) MLBV-40 models: 5 in. (127 mm)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Figure 10b
11
Page 12
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
Back View
Of Appliance
*12 ft. Min.
**15 ft. Min.
Installations
10 ft.
Minimum
Back View
Of Appliance
Figure 11
3. Refer to Figure 11. The following venting
configurations may be installed:
Vertical Installations
Minimum overall height of the vent
system and appliance without an offset must be 10 ft (2.54 m).
Offset Installations
Offset up to 45 degrees from vertical:
Minimum overall height of the vent system and appliance must be 12 ft (3.66 m). The lower part of the offset may start at the fireplace flue collar.
Offset greater than 45 degrees and up
to 60 degrees from vertical: Minimum overall height of the vent system and appliance must be 15 ft (4.57 m). The lower part of the offset may start at the fireplace flue collar.
Maximum overall height of the vent system
and appliance should not exceed 40 ft (12.19 m).
Install the B-vent system in accordance with the vent manufacturer's instructions.
CAUTION: THIS APPLIANCE CANNOT BE VENTED HORIZONTALLY.
Note: Refer to the vent manufacturers instal­lation instructions for variations of venting techniques. If common venting of several units is contemplated, it should be discussed with an architect and the local Building Department.
Do not place insulation materials within 1 in. of the gas vent system.
12
Vertical
Offset
Installations
*12 ft. Min.
**15 ft. Min.
Back View
Of Appliance
*with an offset up to 45 degrees
** with an offset greater than 45
degrees and up to 60 degrees
Step 4. Install Field Wiring
CAUTION
Ground supply lead must be con­nected to the wire attached to the green ground screw located on the outlet box. See
Figure 13. Failure to
do so will result in a potential safety hazard. The appliance must be electrically grounded in accordance with local codes or, in the absence of local codes, the National Electrical Code, ANSI/NFPA 70-latest edition.
(In Canada, the current CSA C22-1 Canadian Electrical Code).
CAUTION: Label all wires prior to disconnec­tion when servicing controls. Wiring errors can cause improper and dangerous operation.
ATTENTION : Au moment de l'entretien des commandes, étiquetez tous les fils avant de les débrancher. Des erreurs de cáblage peuvent entraîner un fonc­tionnement inadéquat et dangereux.
Verify proper operation after installing.
A. All Models
• An optional unit-mounted ON/OFF switch may be installed in the lower control com­partment.
• An optional wall-mounted ON/OFF switch or optional ON/OFF remote control kit also may be used.
• If a wall-mounted ON/OFF control switch is used, mount it in a convenient location on a wall near the fireplace.
• If an optional Style View Door is used in conjunction with an optional unit-mounted
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
ON/OFF switch, the switch may be mounted onto the Style View Door per instructions provided in kit.
• The gas valve is set in place and pre-wired at the factory on all models.
Refer to Section B (below) for millivolt appli­ances and Section C (below) for electronic appliances.
B. Millivolt Wiring (see Figure 12)
1. Read Section A, “All Models,” at left.
2. Wire the control switch within the millivolt
control circuit using the 15 feet of 2 conductor wire supplied with the unit.
Note: The supplied 15 feet of 2 conductor
wire has one end of each conductor con­nected to the gas valve circuit and the other end of each conductor placed loose inside the bottom compartment.
CAUTION: Do NOT connect the optional wall switch to a 120V power supply.
C. Electronic Wiring (see Figure 13)
Note: The electronic appliance must be con­nected to the main power supply.
1. Read Section A, “All Models,” at left.
2. Route a 3-wire 120Vac 60Hz 1ph power
supply to the appliance junction box.
3. Remove the electrical inlet cover plate from
the side of the unit by removing the plate's securing screws (see Figures 8-1 and 8-2
on Pages 9 and 10).
4. Remove the cover plate's knockout; then feed
the power supply wire through the knockout opening and into the unit junction box.
5. Connect the black power supply wire to the
lower outlet's red pigtail lead and the white
power supply wire to the common terminal of the outlet as shown in Figures 13 and 14.
6. Connect ground supply wire to pigtail lead
attached to outlet's green ground screw.
Note: Remote receiver should be located in the wall, or if installed in the control compartment, pulled all the way forward and completely to the left or right against the corner posts. The glass enclosure panel must be removed first to place the receiver in the lower control compartment.
7. If using an optional control, wire it in the low
voltage circuit as shown in Figure 13.
Note: The supplied 15 feet of 2 conductor wire
has one end of each conductor connected to the gas valve circuit and the other end of each conductor placed loose inside the bottom compartment.
8. After wiring is complete, replace cover plate.
Note: Do NOT install batteries in the battery holder until needed (i.e., in the event of a
power outage or if operating the appliance solely by batteries). The battery holder requires two [2] "D" batteries.
Page 13
H
I
L
O
W
P
I
L
O
T
O
N
ti
O
F
F
IN
OUT
TRANSFORMER 3V
BROWN
BROWN
BLACK
BATTERY BACK-UP
BLACK (SENSOR)
BLACK (IGNITER)
IGNITER MODULE
3V
RED
PILOT
IN
OUT
VENT
LO
HI
TH
TP
TH
TP
IN
ORANGE (THTP)
BLACK (TP)
GREEN (TH)
HIGH LIMIT SWITCH
Pilot Burner
Pilot Tube
Assembly
Schematic Representation Only
Electronic Gas Control Valve - DEXEN
B-Vent appliances only - High limit switch must be factory installed as shown. If wires to this switch are replaced, wires must be Type AWM 200°C - 18 gage wire ONLY.
CONTROL SWITCH *
UNIT MOUNTED
ON/OFF SWITCH,
IF SUPPLIED
Junction Box
J-Box Wiring
BK W
G
CAV 021
* Control Switches: Wall On/Off Switch, Unit Mounted On/Off Switch or Remote Control Switch.
NOTES:
1. If any of the original wire as supplied must be replaced, use Type AWM 105°C - 18 gage wire ONLY.
2. 120 VAC, 60 Hz - Less than 3 Amps. CAUTION: label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
MILLIVOLT WIRING DIAGRAM
CAUTION: WHEN SERVICING CONTROLS, LABEL ALL WIRES PRIOR TO DISCONNECTION. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION.
VERIFY PROPER OPERATION AFTER SERVICING.
Figure 12
B-VENT APPLIANCES ONLY: The High Limit Switch must be factory installed in series, as shown. If wires to this switch must be replaced, use Type AWM 200°C - 18 gage wire ONLY.
High Limit Switch
Control Switch*
If any of the original wire must be replaced, use Type AWM 105º C - 18 gage wire ONLY.
_________ *Control switch options: ON/OFF wall switch, unit-mountable
ON/OFF switch, or ON/OFF remote control system (see "Accessory Components" in the Care and Operation Instructions).
Thermopile
Gas Control
Valve Terminals
J-BOX/RECEPTACLE WIRING
J-BOX / RECEPTACLE
120V, 60HZ, 1PH
120V, 60HZ, 1PH
Neutral - White
Ground - Green
120 VAC - Black
WIRING
Junction Box
T
TP HTP
Black
Tab Intact
Hot Side of
TH
White
Green
Receptacle
Neutral Side of Receptacle
Tab Intact
Field Wired
Green Ground Screw
Factory Wired
Figure 14
Figure 13
ELECTRONIC IGNITION WIRING DIAGRAM
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
See Figure 14 for detailed drawing of junction box / receptacle wiring.
_________ *Control switch options: ON/OFF wall switch, unit-mountable
ON/OFF switch, or ON/OFF remote control system (see "Accessory Components" in the Care and Operation Instructions).
13
Page 14
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
Step 5. [OPTIONAL] Install Outside Combustion Air Kit
An optional outside combustion air kit (model FOAK-4, FOAK-4LD, or DK-4) may be used with these appliances (see "Installation Acces­sories," at right).
Refer to the instructions included with the air kits for specific installation information. If used, the outside air kit must be installed before the fireplace is framed and enclosed in the finished wall.
Outside air drawn into the fireplace supplies supplemental combustion air to the fire. Only one outside air duct is necessary, if installed.
If additional length of duct is necessary, pur­chase locally available U.L. Class 0 or Class 1 metallic ducting. The duct may extend up to 50' (15.24 m) in one continuous piece.
Note: When installing the air duct vertically, do NOT terminate the duct closer than 3' below
the chimney top.
Outside supplemental combustion air ducting may be run upward or vertically through fram­ing and ceiling joists, with the hood installed through an outside wall and 3' (1 m) below the termination. Ducting may also be run down­ward through floor joists and under the home to a ventilated crawlspace not considered part of the living area of the home.
Note: NEVER terminate an outside supple­mental combustion air kit in attic space under any circumstances.
Failure to do so may result in extensive and costly rework. Before the operation of the vent system can be tested, the lever securing screw must be removed. See Figure 15.
The hand-operated outside air control lever is located on the left side of the lower control compartment opening. See Figure 15.
To open the outside air shutter, open the bottom control access panel, reach into the control com­partment, and pull the outside air control lever all the way out. The outside air shutter should be fully open when the fireplace is in use and completely closed when the fireplace is not being used. Closing it when not in use will help limit the amount of outside cold air entering the dwelling.
Operate the actuator through several cycles including the closed position. Ensuring proper operation and freedom of movement. Return the actuator arm to the closed position.
Securing Screw Installed
Outside Air Control Lever pushed UP (Air Shutter CLOSED)
IMPORTANT: Do NOT move Air Control Lever if securing screw is installed (or if not sure it was removed).
INSTALLATION ACCESSORIES
The following accessory items are available for use in the installation of this appliance.
Outside Combustion Air Kits Models FOAK-4 and FOAK-4LD
Outside combustion air kits are available with duct (FOAK-4) and without duct (FOAK-4LD) for use if supplemental outside combustion air is required or desired. If model FOAK-4LD is used, it must be used in conjunction with locally purchased, non-combustible Class 1 or Class 0 flexible duct.
Outside Combustion Air Kits
Cat. No. Model No. Description
81L87 FOAK-4 Combustion Air Kit (w/duct)
81L88 FOAK-4LD Combustion Air Kit (w/o duct)
H5377 DK-4 Single 4" Duct Kit
After completing installation of the optional outside air vent system the outside air control lever must be put in service and tested to en­sure proper operation before completing any enclosure around the firebox.
CAUTION
Never locate inlet where it can be blocked by shrubs, snow drifts, etc. Never locate inlet in garage or any area where there is another fuel burning appliance or products emitting combustible gases such as paint, gasoline, etc. In cold climates, it is recommended the outside air duct be insulated.
14
Securing Screw Removed
Outside Air Control Lever pulled DOWN (Air Shutter OPEN)
Left Side of
Lower Control Compartment
Figure 15
WARNING
Do not operate the shutoff lever unless a complete outside com­bustion air system has been installed with your appliance.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 15
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
Gas Valve
3/8" NPT x
Flare Fitting
3/8" Flex Tubing
3/8" Nipple
3/8" Union
3/8" Close Nipple
3/8" Shut-off Valve
1/2" x 3/8"
Reducer
Gas
Stub
1/2" x 3/8" Flare
Shut-off Valve
Gas Solid Line Connector
Gas Flex Line Connector
*Sediment Trap
3"
Mi
n
Note: Millivolt system shown. Electronic system controls are similarly located.
Step 6. Connect the Gas Line
All codes require a shut-off valve mounted in the supply line. The orientation of the shut­off valve should face the front. Figure 16 illustrates two methods for connecting the gas supply. A sediment trap is recommended in the gas piping within the home to prevent moisture and debris in the line from damaging the valve.
The flex-line method is acceptable in the U.S.A. where local codes permit, however, Canadian requirements vary depending on locality. Instal­lation must be in compliance with local codes. These appliances are equipped with a gas flex­line for use in connecting the unit to the gas line. See Figure 16 for flex-line description. The flex-line is rated for both natural and propane gas. A manual shut off valve is also provided with the flex-line.
The gas control valve is located in the lower control compartment.
Access the valve compartment by removing the lower control compartment panel (see Figure
17) by lifting and pulling the panel forward. The panel is mounted on supporting tabs at the extreme right and left hand sides. Engage the tabs into the reliefs in the panel.
The millivolt and electronic control valve has a 3/8" (10 mm) NPT thread inlet port.
Secure all joints tightly using appropriate tools and sealing compounds (ensure propane resistant compounds are used in propane ap­plications). It is recommended to seal around the gas line to prevent cold air leakage.
Gas line connection may be performed largely outside of the confines of the control compart­ment and without having to enter the firebox behind the glass. Proceed as follows:
Acquire the shut-off valve and gas flex-line and pull the assembly forward out of the compart­ment. Separate the shut-off valve from the gas flex-line. Determine the length of pipe needed to route the gas line from the last fitting (shown in Figure 9) to a point within the control com­partment that will allow the shut-off valve to be easily attached by hand to the gas flex-line.
Using pipe-dressing materials appropriate for the gas type, securely affix the shut-off valve to this determined pipe length at a convenient location outside of the appliance lower control compartment.
Refer to Figure 18. Insert the last length of gas pipe with its attached shut-off valve into the lower control compartment, and pass it through the gas line access hole on the left side of the appliance outer wrapper.
Using appropriate materials for the gas type, thread the last length of pipe into the end of the gas vent run and tighten in place using a
pipe wrench external to the appliance between the appliance outer wrapper and the framing.
Important: Turn the last piece of gas pipe in the last fitting until the shut-off valve is posi­tioned in a way that allows the shut-off valve handle to be accessed in the lower control compartment, easily operated throughout its full range of motion.
Bring the flex-line to the shutoff valve by hand and align the flare fittings. Tighten the fittings by hand, and then use wrench to tighten com­pletely, 1/4-turn at a time.
Figure 16: Gas Connection
Gas Flex Line
(Gas Shut-Off Valve is behind
door latch; see DETAIL, below)
DETAIL:
Gas Shut-Off Valve
in ON position (gas line OPEN)
To shut OFF gas: Turn valve handle perpendicular (cross-wise) to gas line.
Figure 17
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Gas Control
{
Valve
Optional
Unit-Mounted
ON/OFF Switch
Note: The gas supply line must be installed in accordance with building codes by a qualied installer approved and/or licensed as required by the locality. In the Commonwealth of Massachusetts, installation must be performed by a licensed plumber or gas tter.
~
Piezo
(Millivolt
units only)
DETAIL: Lower Control Compartment
Length of pipe with attached
Gas Shut-Off Valve in OFF position
Figure 18
Spring
Door Latch
(one of two)
Lower Control
Compartment
Door Tab
(gas line CLOSED)
(shaded area)
15
Page 16
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
MILLIVOLT
Thermocouple
Hood Igniter Rod
3/8" Min (9 mm)
Thermopile
Pilot Nozzels
Test All Connections for Gas Leaks (Factory and Field)
WARNING
Never use an open flame to check for leaks.
Turn on gas supply and test for gas leaks, us­ing a gas leak test solution (also referred to as bubble leak solution).
Note: Using a soapy water solution is an
effective leak test solution but it is not recom­mended, because the soap residue that is left on the pipes/fittings can result in corrosion over time.
A. Light the appliance (refer to the lighting
instructions label in the control compartment or in the Care and Operation Instructions manual).
B. Brush all joints and connections with the gas
leak test solution to check for leaks. If bubbles are formed, or gas odor is detected, turn the gas control knob (off/pilot/on) to the “OFF” position. Either tighten or refasten the leaking connection, then retest as described above.
C. When the gas lines are tested and leak free,
be sure to rinse off the leak testing solution.
Step 7. Verify Appliance Operation
Turn on burner then observe the individual tongues of flame on the burner. Make sure all ports are open and producing flame evenly across the burner. If any ports are blocked, or partially blocked, clean out the ports.
With gas line installed run initial system check­out before closing up the front of the unit. Follow the pilot lighting instructions provided in the Care and Operation Instructions manual. For piezo igniter location, see Figure 17 (millivolt appliances only).
Note: Lighting Instructions are also found on the literature tag tied to the gas piping next to the gas valve. To access the tag, open the lower control compartment door by pulling the panel forward (see Figures 17 and 25).
When first lighting the appliance, it will take a few minutes for the line to purge itself of air. Once purging is complete, the pilot and burner will light and operate as indicated in the instruction manual. Subsequent lighting of the appliance will not require such purging. Inspect the pilot flame (remove logs, if necessary, handling carefully).
Millivolt Appliance Checkout
The pilot flame should be steady, not lifting or floating. Flame should be blue in color with traces of orange at the outer edge.
The top 3/8" (10 mm) at the pilot generator (thermopile) and the top 1/8" minimum (tip) of the quick drop out thermocouple should be engulfed in the pilot flame.
The flame should project 1" (25 mm) beyond the hood at all three ports (see Figure 19). Replace logs if removed for pilot inspection.
To light the burner; turn “ON” the remote wall switch and rotate the gas valve control knob counterclockwise to the “ON” position (“ON” will be at the top side of the valve).
Figure 19
Electronic Appliance Checkout
To light the burner, turn ‘ON’ the unit mounted On/Off switch or the optional remote wall switch. Ensure the igniter lights the pilot. The pilot flame should engulf the flame rod as shown in Figure 20.
ELECTRONIC
Sensor
Igniter
Figure 20
Pilot Hood
16
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 17
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
Step 8. Install Volcanic Stone, Glowing Embers (Rockwool), and Logs
NOTE: Turn OFF all electricity to the fire­place before installing volcanic stone, glowing embers, or logs.
1. Remove the front glass enclosure panel
(see “Removal and Installation of Glass Enclosure Panel,” on previous page).
2. Install ceramic brickaded panel liners.
3. Install decorative volcanic stone. Refer to
Figure 21. Sprinkle the decorative volcanic stone in a pleasing pattern directly on the firebox bottom, along the slope and to the back, at the right and left sides of the burner.
Volcanic Stone
Place Volcanic Stone As Shown
Figure 21
4. Place the glowing ember material (rockwool).
Note: The bag of Glowing Embers contains enough rockwool for several applications; therefore, do not use the entire bag at one time. For best glow­ing effect, replace the ember material annually.
Refer to Figure 22. Separate the glowing
ember material into pieces about the size of a quarter. Keep the pieces fluffed up, not matted. Distribute the pieces over the sur­face of the burner, as shown in Figures 23 and 24. Do not use more than is necessary. Position the embers on the small holes of the ember bed area.
Note: Make sure the glowing ember material does NOT cover the main burner slots.
Bag of Glowing Embers (Rockwool)
Separate into individual “Quarter-sized” pieces.
Figure 22
5. Install the Logs.
The logs have locating notches or slots to help ensure that they are properly positioned. The top logs that rest on lower logs, do so over notches, indents or nubs. Proper log placement is critical to prevent sooting. Logs should be placed in the gaps between the flame peaks and should be positioned so they do not impinge the flames. Follow the log placement instructions exactly.
MLBV-35: Install logs as shown in Figure 23. MLBV-40: Install logs as shown in Figure 24.
WARNING
• DO NOT attempt to install the logs until the appliance installation has been completed, the gas line connected and tested for leaks and the initial burner operation has been checked out.
• The size and position of the log set was engineered to give the appliance a safe, reliable and attractive flame pattern. Any attempt to use a different log set in the fireplace will void the warranty and will result in incomplete combustion, sooting, and poor flame quality.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
• Logs get very hot and will remain hot up to one hour after gas supply is turned off. Handle only when logs are cool. Turn off all electricity to the appliance before you install grate, volcanic stone, embers, and logs.
• This appliance is not designed to burn wood. Any attempt to do so could cause irreparable damage to the appliance and prove hazardous to your safety.
• If logs are not installed according to the log installation instructions, flame impingement and improper combustion could occur and result in soot and/or excessive production of carbon monoxide (CO), a colorless, odorless, toxic gas.
17
Page 18
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
MLBV-35 LOG PLACEMENT INSTRUCTIONS
Rear Log
4
Left Cross Log Right Cross Log
2
Left Rear Log Bracket
1
Left Front Log
5
Right Front Log
3
Right Rear Log Bracket
Note:
Ceramic fiber logs are FRAGILE! Handle carefully to prevent breakage.
Install volcanic stone and glowing embers BEFORE installing logs.
To prevent sooting, make sure logs do not cover any burner openings.
MLBV Firebox Accessories/Parts
Cat. No. Model No. Description
H7666 MLBV-35 Log Set Assembly
88L53 FGE Bag of Glowing Embers (Rockwool)
80L42 FDVS Bag of Decorative Volcanic Stone
Fit onto left rear log bracket
1
and rear bar of grate.
Right Rear
Log Bracket
Glowing Embers
GrateVolcanic Stone
(Do not place glowing embers over burner openings.)
NOTE: Install volcanic stone and glowing embers FIRST.
Position against left front corner of grate.
2
1
Position against right front
3
corner of grate.
Step 2. Fit bottom slots of Left Front Log (2) onto left front
corner of grate.
Step 3. Fit bottom slots of Right Front Log (3) onto right front
corner of grate.
Step 1. Fit bottom slots of Rear Log (1) onto left rear log bracket
and rear bar of grate.
Position over Rear Log (1)
4
and against front bar of grate.
1
2
Position over Right Front Log (3);
5
then fit onto right rear log bracket.
3
Step 4. Place Left Cross Log (4) over Rear Log (1); then fit
the bottom slot over the center front bar of grate.
Step 5. Place Right Cross Log (5) over and behind Right Front Log
(3); then fit the bottom slot onto the Right Rear Log Bracket.
18
Figure 23
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 19
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
MLBV-40 LOG PLACEMENT INSTRUCTIONS
Rear Log
4
Left Cross Log Right Cross Log
2
Fit onto left rear log bracket
1
and rear bar of grate.
1
Left Front Log
5
Right Front Log
3
Right Rear Log Bracket
Note:
Ceramic fiber logs are FRAGILE! Handle carefully to prevent breakage.
Install volcanic stone and glowing embers BEFORE installing logs.
To prevent sooting, make sure logs do not cover any burner openings.
MLBV Firebox Accessories/Parts
Cat. No. Model No. Description
H7667 MLBV-40 Log Set Assembly
88L53 FGE Bag of Glowing Embers (Rockwool)
80L42 FDVS Bag of Decorative Volcanic Stone
Position against left front corner of grate.
2
1
Glowing Embers
GrateVolcanic Stone
(Do not place glowing embers over burner openings.)
NOTE: Install volcanic stone and glowing embers FIRST. Step 1. Fit bottom slots of Rear Log (1) onto left rear log bracket
and rear bar of grate.
Position over Rear Log (1)
4
and against front bar of grate.
1
2 3
Step 4. Place Left Cross Log (4) over Rear Log (1); then fit
the bottom slot over the center front bar of grate.
Figure 24
Position against right front
3
corner of grate.
Step 2. Fit bottom slots of Left Front Log (2) onto left front
corner of grate.
Step 3. Fit bottom slots of Right Front Log (3) onto right front
corner of grate.
Position over Right Front Log (3);
5
then fit onto right rear log bracket.
4
2 3
1
Step 5. Place Right Cross Log (5) over and behind Right Front
Log (3); then fit the bottom slot onto the right rear log bracket.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
19
Page 20
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
Top Standoff Spacers*
Flush Nailing
1/2" Nailing Flange
5/8" Nailing Flange
Step 9. Install the Glass Enclosure Panel
WARNING
• Do not attempt to substitute the materials used on these doors, or replace cracked or broken glass.
• Handle this glass with extreme care! Glass is susceptible to damage – Do not scratch or handle roughly while reinstalling the glass door frame.
• The glass door(s) of this appli­ance must only be replaced as a complete unit as provided by the manufacturer. Do not attempt to replace broken, cracked or chipped glass separately.
• Do not attempt to touch the front enclosure glass with your hands while the fireplace is in use.
WARNING
Do not operate appliance with the glass front removed, cracked or broken.
AVERTISSEMENT
Ne pas utiliser l'appareil si le panneau frontal en verre n'est pas en place, est craqué ou brisé.
Only doors certified with the appliance shall be used.
Seules des portes certifiées pour cet appareil doivent être utilisées.
CAUTION: DO NOT abuse glass enclosure panel by striking or slamming shut.
Installing the Glass Enclosure Panel
1. Refer to Figure 25. Position the glass enclo-
sure panel in front of the firebox opening, with the bottom of the enclosure panel held away from the fireplace. Hook the top flange of the enclosure panel frame over the top of the firebox frame.
2. Gently move the bottom of the enclosure
panel frame toward the fireplace, ensuring that the gasket seats evenly. Fasten the two latches under the firebox floor to the vee-flange on the enclosure panel. Close
20
both latches securely.
3. Install the hood. Note the location of the
three clips inside the top air channel above the glass enclosure panel. The clips are equally spaced on the top surface of the air channel opening. If needed, use a screw­driver to open the clips slightly. Engage the back edge of the hood into the clips to secure.
Removing the Glass Enclosure Panel
1. Refer to Figure 25. To access the spring
latches securing the front glass enclosure panel, open the lower control compartment door by lifting and pulling the bottom panel forward.
2. Pull the spring latches forward and down to
release them from the lower door channel.
3. Pull the bottom of the glass enclosure panel
out a few inches, and grasp it on the right and left sides. Gently lift to release the panel from its upper channel, and then pull the enclosure panel forward to remove it.
4. Visually inspect the gasket on the backside
of the enclosure panel frame. The gasket surface must be clean, free of irregularities, and firmly seated.
This appliance is designed to operate only when the glass enclosure panel is installed.
Do NOT remove the glass enclosure panel un­less necessary (e.g., to gain access to compo­nents within the firebox or to clean the glass).
Top Standoff Spacers*
*IMPORTANT!
*IMPORTANT!
Bend up the
Bend up the
Top Standoff
Top Standoff Spacers before
Spacers before
installation.
installation.
Use outer pair
Use outer pair
for 1/2" materials
for 1/2" materials
and inner pair
and inner pair
for 5/8" materials.
for 5/8" materials.
Glass Enclosure Panel
Enclosure Panel Spring Latch
Lower Control Compartment Panel
Note: When installing the glass enclosure panel, make sure spacing on both sides is even and equal.
Figure 25
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Hood
5/8" Nailing Flange
1/2" Nailing Flange
Flush Nailing Flange
Step 10. Burner Air Shutter Adjustments
(QUALIFIED TECHNICIANS ONLY)
Flame Appearance and Sooting
Proper flame appearance is a flame which is blue at the base and becomes yellowish-orange in the body of the flame. When the appliance is first lit, the entire flame may be blue and will gradually turn yellowish-orange during the first 15 minutes of operation. After 15 minutes of operation, if the flame is blue, or if the flame is orange with evidence of sooting (black tip), the air shutter opening may need to be adjusted.
If the air shutter opening is closed too far, sooting may develop. Sooting is indicated by black puffs developing at the tips of very long orange flames. Sooting results in black deposits forming on the logs, appliance inside surfaces and on exterior surfaces adjacent to the vent termination.
Sooting is caused by incomplete combustion in the flames and lack of combustion air enter­ing the air shutter opening. To achieve a warm yellowish-orange flame with an orange body that does not soot, the shutter opening must be adjusted between these two extremes.
Air Shutter Adjustment Guidelines
• If there is smoke or soot present, first check the log set positioning to ensure that the flames are not impinging on any of the logs. If the log set is properly positioned and a sooting condition still exists, then the air shutter opening should be increased.
• The more offsets in the vent system, the larger the air shutter opening will need to be.
• An appliance operated with the air shutter opened too far, may have flames that appear blue and transparent. These weak, blue and transparent flames are termed anemic.
• Propane models may exhibit flames which candle or appear stringy. If this is present and persists, adjust the air shutter to a more open position, then operate the appliance for a few more minutes to ensure that the flame normal­izes and the flames do not appear sooty.
The following chart is provided to aid you in achieving the correct air shutter adjustment for your installation.
Air Shutter Adjustment Guidelines:
Amount of
Primary Air
If air shutter is closed too far
If air shutter is open too far
Flame
Color
Flame will be orange
Flame will be blue
Air Shutter
Adjustment
Air shutter gap should be increased
Air shutter gap should be decreased
Page 21
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
Burner Air Shutter Adjustment Procedure
WARNING
Air shutter adjustment should only be performed by a qualified professional service technician.
Ensure front glass panel are in place and sealed during adjustment.
CAUTION
Soot will be produced if the air shutter is closed too much. Any damage due to sooting resulting from improperly setting the air shutter is not covered under the warranty.
The air shutter door and nearby appliance surfaces are hot. Exercise caution to avoid injury while adjusting flame appearance.
1. Locate adjustment rod and adjust air shutter to the standard set-
ting as shown in Figure 26 (adjustment rod is located in the lower control compartment).
Note: Move the adjustment rod DOWN to decrease air and UP to increase air.
Adjustment Set-Screw
Adjustment Rod Up
Burner Tube
Air Shutter
Adjustment Rod Down
min. air opening position)
Main Burner Factory Air Shutter
Opening Setting - inches (millimeters)
Model Nat.Gas Propane Gas
MLBV-35 Closed 3/32 (2.362) MLBV-40 Closed 3/32 (2.362)
Figure 26: Burner Air Shutter Adjustment
(Fully Open Position)
2. Light appliance (follow lighting procedure on lighting label in con-
trol compartment or see the Care and Operation manual).
3. Allow the burner to operate for at least 15 minutes while observing the flame continuously to ensure that the proper flame appearance has been achieved (see Figure 27 and 28). If the following conditions are present, adjust accordingly:
• If flame appears weak or sooty, adjust the air shutter, incremen­tally, to a more open position until the proper flame appearance is achieved.
• If flame stays lowered blue, adjust the air shutter, incrementally, to a more closed position until the proper flame appearance is achieved.
4. Leave the control knob (off/pilot/on) in the ON position and the burner OFF/ON switch OFF (and remote switches, if applicable).
5. When satisfied that the burner flame appearance is normal, re­install the lower control compartment door then proceed to finish the installation.
Figure 27: Burner Flame Appearance – Model MLBV-35
Figure 28: Burner Flame Appearance – Model MLBV-40
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
21
Page 22
Frame
Upper Right Side of Firebox
Lintel Screw Hole
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
Step 11. Perform Spillage Test
After appliance installation, perform this spillage test to verify proper venting conditions:
1 - Place unit in its normally-operated condi-
tion, that is, with the glass enclosure panel in place.
2 - Close all doors and windows in the room.
Turn on all exhaust fans in the house.
3 - Light the appliance. 4 - Wait 15 minutes. 5 - To check for venting action, start by hold-
ing a smoke producing device below the glass enclosure panel. The smoke should be drawn into the control compartment. Continue the test by moving the smoke­producing device along the entire length of the lower edge of the glass enclosure panel.
6 - If the smoke is NOT drawn into the con-
trol compartment, turn off the appliance and call a qualified service technican.
Manually-Reset Safety Limit Switch
This appliance is equipped with a manually­reset safety limit switch in the upper RIGHT side of the firebox, behind the right side scoop. Refer to Figure 29 for its location.
If, during appliance operation, the flame goes out (independently of the burner ON/ OFF switch), the safety limit switch may have tripped.
Some causes for a tripped safety limit switch include the following:
• Incorrect flue configuration
• Blocked flue
• Negative pressure inside house
Before resetting the safety limit switch, have a qualified service technician inspect the fireplace and venting for these conditions and repair as needed.
To RESET the safety limit switch, push the
reset button located between the wire terminals on the back of the switch. Follow the steps be-
low to access the switch (also see Figure 29-C).
To REPLACE the safety limit switch, follow the steps below.
IMPORTANT: This procedure should only be
performed by a qualified service technician.
Figure 29-A
Figure 29-B
Figure 29-C
Figure 29
Lintel Screw Hole
in Cabinet Top
Right Side
Scoop
Right Side
of Firebox
(right side Scoop removed)
~
~
Bracket (right side Scoop removed)
To access the Safety Limit Switch, reach in and up behind the Bracket, and push the red reset button located between the two Wire Terminals.
Safety Limit Switch / Reset Button Location
Inside View of Firebox (upper right side)
~
~
3 Scoop Screws
in Cabinet Top
Limit Switch Wire Terminals
(Red reset button is between the two terminals.)
Cabinet Corner
Door
1 - Turn OFF electrical power to appliance. 2 - Allow the appliance to cool. 3 - Remove the lower control compartment
access panel.
4 - Refer to Figure 25 on Page 20. Open both
latches under the firebox floor securing the glass enclosure panel. Remove the panel by tilting it outward at the bottom
22
and lifting it up. Set aside the panel, taking care to protect it from damage.
5 - Remove the (3) screws securing the lintel,
and then remove the lintel. One of the lintel cabinet top holes is shown in Figure 29.
6 - Remove the (3) screws securing the
scoop, and then remove the scoop. Refer to Figure 29 for correct location for model size.
7 - Reset the limit switch per Figure 29-B. If
unit does not reset, remove the (2) screws securing the safety switch bracket, and
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
pull the switch/bracket assembly (with low voltage wires attached) through the side panel slot into the firebox.
8 - Replace the switch, if necessary.. 9 - Reinstall the scoop and lintel. 10 - Reinstall the glass enclosure panel and
control compartment access panel.
The appliance should then relight and remain lit. If this does not occur, contact your dealer.
Page 23
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
Step 12. Install Hood
NOTE: All models must have a hood installed prior to operating.
Refer to Figure 30. Install hood by sliding it into the slots on the lower edge of the cabinet top.
Combustible Finished
Wall Materials
1 in (25 mm) min.
Header
Step 13. Finishing Requirements
Wall Details
Complete finished interior wall. To install the appliance facing flush with the
finished wall, position framework to accom­modate the thickness of the finished wall
(Figure 30).
For Cold Climate Insulation, see Page 5. For Clearances, see Page 7.
IMPORTANT!
Bend up standoffs
to vertical position.
Combustible material may touch appliance top.
Hood
Figure 30: Combustible Wall Framing
Top of Appliance
3" Clearance min.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
23
Page 24
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
Step 14. Attach Safety-In-Operation Warnings
It is the installer's responsibility to ensure these warning labels are properly affixed during installation. These warning labels are a critical step in informing consumers of the safe operation of this appliance.
ATTACHING SAFETY-IN-OPERATION WARNINGS
It is required that the safety instruction labels fur­nished with the fireplace be affixed to the operation and control point of the fireplace. A safety instruction label must be affixed to the wall switch plate where the fireplace is turned on and off (See Figure A) and if used on the remote control handheld transmitter (Figure B). To properly complete the installation of this fireplace, locate the multi-lingual adhesive labels provided with the Care and Operation Instructions and proceed as follows:
1. Locate the wall switch that controls the fireplace (verify the switch operates the fireplace by turn­ing it on and off). Clean the wall switch plate thoroughly to remove any dust and oils. Affix the label to the surface of the plate of the wall switch that controls the fireplace (Figure A). Choose the language primarily spoken in the home. If unknown, affix the English language label.
2. If a remote control is used to control the fireplace, locate the transmitter and clean it thoroughly to remove any dust and oils. Affix the label to the surface of handheld transmitter (Figure B). Choose the language primarily spoken in the home. If unknown, affix the English language label.
3. If you are unable to locate the labels, please call Lennox Hearth Products or your nearest Lennox Hearth Products dealer to receive additional safety instruction labels free of charge.
Cat. No. H8024 Replacement Label Kit
LENNOX HEARTH PRODUCTS 1-800-9-LENNOX
Note: English is red text on clear label. French and Spanish are white text on black label.
APPOSITION DES MISES EN GARDE RELATIVES À LA SÉCURITÉ D’UTILISATION
Il est impératif que les étiquettes de sécurité fournies avec le foyer soient collées à côté des dispositifs de contrôle du foyer. Une étiquette de sécurité doit être collée sur la plaque de l’interrupteur contrôlant l’allumage du foyer (voir Figure A) et, le cas échéant, sur le boîtier de la télécommande (Figure B). Pour achever l’installation correcte de ce foyer, procédez comme suit avec les étiquettes adhésives en langues étrangères fournies avec les instructions d’utilisation et d’entretien :
1. Repérez l’interrupteur qui contrôle le foyer (vérifiez que l’interrupteur contrôle le fonctionnement du foyer en le faisant basculer de Marche à Arrêt, et vice-versa). Nettoyez soigneusement la plaque murale de l’interrupteur pour éliminer la poussière et les traces de graisse ou d’huile. Collez l’étiquette sur la surface de la plaque de l’interrupteur mural qui contrôle le foyer (Figure A). Choisissez la langue qui est principalement parlée dans la résidence du propriétaire. En cas de doute, collez l’étiquette en anglais.
2. Si une télécommande est utilisée pour contrôler le foyer, nettoyez la soigneusement pour éliminer la poussière et les traces de graisse ou d’huile. Collez l’étiquette sur le boîtier de la télécommande (Figure B). Choisissez la langue qui est principale- ment parlée dans la résidence du propriétaire. En cas de doute, collez l’étiquette en anglais.
3. Si vous ne trouvez pas les étiquettes, veuillez appeler Lennox Hearth Products ou votre distribu­teur Lennox Hearth Products local pour recevoir gratuitement des étiquettes supplémentaires.
Étiquettes de remplacement, n° cat. H8024
LENNOX HEARTH PRODUCTS 1-800-9-LENNOX
Remarque : Le texte anglais est rouge sur un support transparent. Le texte français et espagnol est blanc sur un support noir.
COLOCACIÓN DE ADVERTENCIAS DE SEGURIDAD EN OPERACIÓN
Se requiere que las etiquetas de instrucciones de seguridad incluidas con la chimenea se coloquen en el punto de operación y control de la misma. Se debe colocar una etiqueta de instrucciones de seguridad en la placa del interruptor de pared desde el cual se enciende y se apaga la chimenea (ver la Figura A) y en el transmisor de control remoto (Figura B) si se usa. Para completar correctamente la instalación de esta chimenea, encuentre las etiquetas adhesivas multilingües incluidas con las instrucciones de cuidado y operación y haga lo siguiente:
1. Identifique el interruptor de pared que controla la chimenea (verifique que el interruptor opera la chimenea encendiéndola y apagándola). Limpie bien la placa del interruptor de pared para quitar el polvo y aceite. Pegue la etiqueta en la superficie de la placa del interruptor que controla la chimenea (Figura A). Seleccione el idioma que más se habla en la casa. Si no sabe cuál es, use la etiqueta en inglés.
2. Si se usa un control remoto para controlar la chimenea, encuentre el transmisor y límpielo bien para quitar el polvo y aceite. Pegue la etiqueta en la superficie del transmisor (Figura B). Seleccione el idioma que más se habla en la casa. Si no sabe cuál es, use la etiqueta en inglés.
3. Si no puede encontrar las etiquetas, sírvase llamar a Lennox Hearth Products o al distribuidor de Lennox Hearth Products más cercano para recibir etiquetas de instrucciones de seguridad adicionales gratuitas.
Juego de etiquetas de repuesto - Nº de cat. H8024
LENNOX HEARTH PRODUCTS 1-800-9-LENNOX
Nota: La etiqueta en inglés es transparente con texto rojo. Las etiquetas en francés y español son negras con texto blanco.
24
SAFETY LABEL
DIAGRAMS
Figure A Figure B
DIAGRAMMES DES ÉTIQUETTES
DE SÉCURITÉ
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
DIAGRAMAS DE ETIQUETAS
DE SEGURIDAD
Page 25
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
GAS CONVERSION KITS
WARNING
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instruction is not followed exactly, a fire, explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life. The qualified service agency is responsible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manu­facturer’s instructions supplied with the kit.The qualified service agency performing this installation assumes responsibility for this conversion.
AVERTISSEMENT
Cette trousse de conversion doit être installée par un technicien agréé, selon les instructions du fabricant et selon toutes les exigences et tous les codes pertinents de l’autorité compétente. Assurez-vous de bien suivre les instructions dans cette notice pour réduire au minimum le risque d’incendie, d’explosion ou la production de monoxyde de carbone pouvant causer des dommages matériels, des blessures ou la mort. Le tecnicien agréé est responsable de l’installation de cette trousse. L’installation n’est pas adéquate ni complète tant que le bon fonctionnement de l’appareil converti n’a pas été vérifié selon les instructions du fabricant fournies avec la trousse. Le fournisseur de service qualifié ayant réalisé l'installation assume les responsabilités liées à la conversion.
In Canada: THE CONVERSION SHALL BE CARRIED OUT IN ACCORDANCE WITH THE REQUIREMENTS OF THE PROVINCIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN/ CSA-B149.1 INSTALLATION CODE.
LA CONVERSION DEVRA ÊTRE EFFECTUÉE CONFORMÉMENT AUX RECOMMANDATIONS DES AUTORITÉS PROVINCIALES AYANT JURIDICTION ET CONFORMÉMENT AUX EXIGENCES DU CODE D'INSTALLATION CAN/CSA-B149.1.
Gas conversion kits are available to adapt your appliance from the use of one type of gas to the use of another. These kits contain all the necessary components needed to complete the task including labeling that must be affixed to ensure safe operation.
Kit part numbers are listed here and the follow­ing steps detail the conversion procedure. Refer to the instructions provided with the conversion kit when performing any gas conversion.
Millivolt SIT Systems
Natural Gas To Propane Gas
Conversion Kits
Models Catalog No. MLBV-35 H8270 MLBV-40 H7673
Millivolt SIT Systems
Propane Gas to Natural Gas
Conversion Kits
Models Catalog No. MLBV-35 H8271 MLBV-40 H7675
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Electronic DEXEN Systems
Natural Gas To Propane Gas
Conversion Kits
Models Catalog No. MLBV-35 H8268 MLBV-40 H7669
Electronic DEXEN Systems
Propane Gas To Natural Gas
Conversion Kits
Models Catalog No. MLBV-35 H8269 MLBV-40 H7671
Gas Conversion Kit Installation Instructions
Step 1. TURN OFF THE GAS SUPPLY TO THE
APPLIANCE and disconnect power supply at the circuit breaker. Ensure appliance is cold.
CAUTION: THE GAS SUPPLY SHALL BE SHUT OFF PRIOR TO DISCONNECTING THE ELECTRICAL POWER, BEFORE PROCEED­ING WITH THE CONVERSION.
ATTENTION: AVANT D’EFFECTUER LA CONVERSION, COUPEZ D’ABORD L’ALIMENTATION EN GAZ, ENSUITE, COUPEZ L’ALIMENTATION ÉLECTRIQUE.
Step 2. Remove the front glass enclosure
panel. See Figure 25 on Page 20.
Step 3. Carefully remove the logs.
Note: Logs are fragile. Handle gently
to prevent breakage.
Step 4. Refer to Figure 31. Remove the burner
assembly with attached venturi tube.
For Millivolt Systems, continue to Step 5. For Electronic Systems, skip to Step 8. Step 5. SIT Millivolt Valve: Refer to Figure 32
and the instructions provided with the kit.
a. Using a Torx T20 (with 1/4" shank
and center hole), remove and dis­card the three pressure regulator mounting screws.
b. Remove the pressure regulator,
spring, poppet, diaphragm and bushing.
c. Discard all removed components. d. Make sure the rubber gasket in-
stalled on the back of the replace­ment pressure regulator is properly positioned. Tighten screws to 25 in.-lb. torque.
25
Page 26
PILOT
OUT
VENT
LO
TH
TP
TH
TP
HI
IN
IN
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
ELECTRONIC
Burner Assembly
Gas Valve Assembly
Orifice
Figure 31: SIT Millivolt System
Pressure
Regulator
Electronic Appliances
Step 8. Dexen Electronic Valves: Refer to
Figure 34 and the instructions pro­vided with the kit.
a. Remove and discard the two pres-
sure regulator mounting screws.
b. Remove the pressure regulator and
diaphragm.
c. Discard all removed components. d. Make sure the provided diaphragm
is installed properly onto the re­placement pressure regulator.
e. Install the new pressure regulator
using the new screws supplied with the kit; tighten the screws.
Supply Gas Inlet
Pressure-Tap (Manifold)
Regulator Mounting Screw
Burner Stage Terminal
Gas
Outlet
To Burner
All Models
Note the following: Use pipe joint compound or Teflon tape on
all pipe fittings before installing. Ensure propane-resistant compounds are
used in propane applications. Do NOT use pipe joint compounds on flare
fittings.
Step 10. Refer to Figure 31.
a. VERIFY PROPER ORIFICE SIZE
BEFORE INSTALLING IT.
b. Remove the orifice from the mani-
fold and replace it with the one provided in the kit. See Table 7 for orifice sizes for natural and propane models. Figure 36 illustrates the orifice. Always check and verify orifice size.
c. Retrieve the burner. Slide the venturi
tube over the orifice.
d. Adjust the burner air shutter as
shown in Figure 26 on Page 21.
Remove These Components
Figure 32: SIT Millivolt System
Step 6. (Millivolt systems only): Attach ma-
nometer to the manifold side pressure test fitting and verify manifold pressure reads 3.5 inches water column (0.87 kPa) for natural gas, and 10.0 inches water column (2.49 kPa) for propane gas.
Step 7. (Millivolt systems only): Refer to Figure
33. Remove the pilot hood assembly to
access the hexed pilot orifice. Remove and replace the orifice with the one provided in the kit.
Skip to Step 10.
Pressure-Tap (Inlet)
Pilot Gas Outlet
Ground (TP)
Pilot Stage Terminal
Figure 34: Dexen Electronic Gas Valve
Step 9. Refer to Figure 35. Follow these steps
to replace the pilot orifice: a. Remove pilot hood assembly to
access the phillipped pilot orifice.
b. Remove and replace the orifice
with the one provided with the kit.
Exercise extreme care to prevent damage to or breakage of the igniter assembly.
Sensor
Igniter
Pilot Hood
Burner Orifice Sizes
Elevation 0-4500 feet ( 0-1372 meters)
Model
Series
MLBV-35
MLBV-40
Table 7
Nat.Gas
drill size (inches)
#48 (0.076")*
H1236•
#43 (0.089")*
99K75•
Standard size installed at factory.
*
Part /Cat. Number.
Propane
drill size (inches)
#56 (0.046")*
62L37•
#55 (0.052")*
19L52•
Figure 36
Step 11. Reassemble the remaining compo-
nents by reversing the procedures outlined in the preceding steps.
Step 12. Attach the conversion label (provided
in the conversion kit) next to the rat­ing plate on the appliance.
Step 13. Turn on gas supply and test for gas
leaks (refer to Page 16).
Pilot Orifice
Figure 35: Dexen Electronic System
ALWAYS TEST PRESSURES WITH THE VALVE REGULATOR CONTROL AT THE HIGHEST SETTING.
Figure 33: SIT Millivolt System
26
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 27
Notes
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
27
Page 28
LENNOX HEARTH PRODUCTS • MERIT® SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information.
Printed in U.S.A. © 2010/2012 Lennox Hearth Products
P/N 506015-04 Rev. C 01/2012
28
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
1508 Elm Hill Pike, Suite 108 • Nashville, TN 37210
Loading...