Lennox ML193DF User Manual

INSTALLATION
2010 Lennox Industries Inc.
Dallas, Texas, USA
INSTRUCTIONS ML193DF
®
MERIT DOWNFLOW AIR DISCHARGE
506475−01 01/2011 Supersedes 10/2010
SERIES GAS FURNACE
Litho U.S.A.
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death.
CAUTION
AIR FLOW
Table of Contents
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ML193DF Parts Arrangement 3. . . . . . . . . . . . . . . . . . . . .
ML193DF Gas Furnace 4. . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping and Packing List 4. . . . . . . . . . . . . . . . . . . . . . . .
Safety Information 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use of Furnace as a Construction Heater 5. . . . . . . . . . .
General 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Combustion, Dilution and Ventilation Air 6. . . . . . . . . . . .
Setting Equipment 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Filters 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Duct System 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pipe and Fittings Specifications 12. . . . . . . . . . . . . . . . . . .
Joint Cementing Procedure 14. . . . . . . . . . . . . . . . . . . . . .
Venting Practices 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
Vent Piping Guidelines 15. . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Piping 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Start Up 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Pressure Measurement 38. . . . . . . . . . . . . . . . . . . . .
Proper Combustion 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
High Altitude 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Testing Non Direct Appliances for Proper Air 39. . . . . . .
Other Unit Adjustments 40. . . . . . . . . . . . . . . . . . . . . . . . . .
Blower Motor Performance 41. . . . . . . . . . . . . . . . . . . . . . .
Service 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Planned Service 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Integrated Control Diagnostic Codes 44. . . . . . . . . . . . . .
Troubleshooting 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repair Parts List 49. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start Up Checklist 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
01/11
*2P0111*
Page 1
506475−01
*P506475-01*
ML193DF Unit Dimensions − inches (mm)
COMBUSTION
AIR INTAKE
EXHAUST AIR
OUTLET
21/16 (52)
5
(127)
21/4
(57)
9/16
(14)
RETURN AIR
B
OPENING
9/16 (14)
TOP VIEW
3/4
(19)
AIR
C
A
B
FLOW
Supply
Air
9/16 (14)
3/4
(19)
33
(838)
1 (25)
Front Panel
2 (51)
Either Side
GAS PIPING INLET
(Either Side)
91/8 (232) Right 69/16 (167) Left
273/4
(705)
197/16
(494)
ELECTRICAL INLET
(Either Side)
CONDENSATE
TRAP CONNECTION
(Either Side)
61/2 (165) Either Side
191/4
(489)
Supply
Air
9/16 (14)
3/4
(19)
ML193DF
Model No.
04536B 07036B
09048C 11060C
FRONT VIEW SIDE VIEW
A B C
in. mm in. mm in. mm
17−1/2 446 16−3/8 416 16 406
21 533 19−7/8 504 19−1/2 495
Page 2
ML193DF Parts Arrangement
CONTROL BOX
(Includes integrated control,
transformer and door switch)
BLOWER MOTOR
(hidden)
BLOWER
ACCESS
PANEL
BAG ASSEMBLY
BURNER ACCESS
PANEL
COMBUSTION AIR INDUCER
BLOWER DECK
PRIMARY LIMIT
COLD END HEADER BOX
HEAT EXCHANGER
GAS VALVE
BURNER BOX ASSEMBLY
(includes sensor, rollout switches and ignitor)
FIGURE 1
Page 3
ML193DF Gas Furnace
The ML193DF Category IV gas furnace is shipped ready for installation in the downflow position.
The furnace is equipped for installation in natural gas ap­plications. A conversion kit (ordered separately) is re­quired for use in propane/LP gas applications.
The ML193DF can be installed as a Direct Vent or Non− Direct Vent gas central furnace.
NOTE − In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors. In Non−Direct Vent installations, combustion air is taken from indoors and flue gases are discharged outdoors. See figure 2 for applications involving roof termination.
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
The following items may also be ordered separately: 1 − Thermostat 1 − Propane/LP changeover kit
Safety Information
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
DIRECT VENT INSTALLATION NON−DIRECT VENT
EXHAUST COMBUSTION AIR INTAKE OUTSIDE OF HOUSE
ML193DF
OUTLET
INSTALLATION
ML193DF
EXHAUST OUTLET
COMBUSTION
AIR INTAKE INSIDE
OF HOUSE
FIGURE 2
Shipping and Packing List
Package 1 of 1 contains
1 − Assembled ML193DF unit 1 − Bag assembly containing the following:
3 − Wire nuts 1 − Snap bushing 1 − Snap plug 1 − Wire tie 1 − Condensate trap 1 − Condensate trap cap 1 − Condensate trap clamp 1 − 2" diameter Air intake screen
DANGER
Danger of explosion.
There are circumstances in which odorant used with LP/propane gas can lose its scent. In case of a leak, LP/propane gas will settle close to the floor and may be difficult to smell. An LP/propane leak detector should be installed in all LP applications.
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
Use only the type of gas approved for use with this furnace. Refer to unit nameplate. ML193DF units are CSA International certified to ANSI Z21.47 and CSA 2.3 standards.
Building Codes
In the USA, installation of gas furnaces must conform with lo­cal building codes. In the absence of local codes, units must be installed according to the current National Fuel Gas Code (ANSI-Z223.1/NFPA 54). The National Fuel Gas Code is available from the following address:
American National Standards Institute, Inc. 11 West 42nd Street
New York, NY 10036 In Canada, installation must conform with current National Standard of Canada CSA-B149 Natural Gas and Propane
Installation Codes, local plumbing or waste water codes and other applicable local codes. In order to ensure proper unit operation in non−direct vent applications, combustion and ventilation air supply must be provided according to the current National Fuel Gas Code or CSA-B149 standard.
Locations and Clearances
This furnace is CSA International certified for installation clearances to combustible material as listed on the unit nameplate and in the table in figure 11. Accessibility and ser­vice clearances must take precedence over fire protection clearances.
For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are located no less than 18 inches (457 mm) above the floor. The furnace must be located or protected to avoid physical damage by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a haz­ardous atmosphere, the furnace must be installed accord­ing to recommended good practice requirements and cur­rent National Fuel Gas Code or CSA B149 standards.
Page 4
NOTE − Furnace must be adjusted to obtain a temperature rise within the range specified on the unit nameplate. Failure to do so may cause erratic limit operation and premature heat exchanger failure.
This ML193DF furnace must be installed so that its electri­cal components are protected from water.
Installation in Combination with a Cooling Coil
When this furnace is used with cooling units (figure 3), it shall be installed in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating compart­ment. With a parallel flow arrangement, a damper (or other means to control the flow of air) must adequately prevent chilled air from entering the furnace. If the damper is manu­ally operated, it must be equipped to prevent operation of ei­ther the heating or the cooling unit, unless it is in the full HEAT or COOL setting.
When installed, this furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Electric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available from the following ad­dress:
National Fire Protection Association 1 Battery March Park Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit must be installed according to the current regulations of the Canadian Electrical Code Part I (CSA Standard C22.1) and/or local codes.
Heating Unit Installed Parallell to Air Handler Unit
GAS UNIT
Dampers
(open during heating
operation only)
AIR HANDLER
Dampers
(open during cooling
operation only)
FIGURE 3
NOTE − This furnace is designed for a minimum continu­ous return air temperature of 60°F (16°C) or an intermit-
tent operation down to 55°F (13°C) dry bulb for cases where a night setback thermostat is used. Return air tem­perature must not exceed 85°F (29°C) dry bulb.
The ML193DF furnace may be installed in alcoves, closets, attics, basements, garages, utility rooms and crawl spaces.
This furnace design has not been CSA certified for installa­tion in mobile homes, recreational vehicles, or outdoors.
Never use an open flame to test for gas leaks. Check all connections using a commercially available soap solution made specifically for leak detection.
Use of Furnace as Construction Heater
Lennox does not recommend the use of ML193DF units as a construction heater during any phase of construction. Very low return air temperatures, harmful vapors and op­eration of the unit with clogged or misplaced filters will dam­age the unit.
ML193DF units may be used for heating of buildings or structures under construction, if the following conditions are met:
The vent system must be permanently installed per these installation instructions.
A room thermostat must control the furnace. The use of fixed jumpers that will provide continuous heating is not allowed.
The return air duct must be provided and sealed to the furnace.
Return air temperature range between 60°F (16°C) and 80°F (27°C) must be maintained.
Air filters must be installed in the system and must be maintained during construction.
Air filters must be replaced upon construction comple­tion.
The input rate and temperature rise must be set per the furnace rating plate.
One hundred percent (100%) outdoor air must be pro­vided for combustion air requirements during construc­tion. Temporary ducting may supply outdoor air to the furnace. Do not connect duct directly to the furnace. Size the temporary duct following these instructions in section for Combustion, Dilution and Ventilation Air in a confined space with air from outside.
The furnace heat exchanger, components, duct system, air filters and evaporator coils must be thoroughly cleaned following final construction clean−up.
All furnace operating conditions (including ignition, in­put rate, temperature rise and venting) must be verified according to these installation instructions.
Page 5
General
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
In addition to the requirements outlined previously, the fol­lowing general recommendations must be considered when installing a ML193DF furnace:
Place the furnace as close to the center of the air dis­tribution system as possible. The furnace should also be located close to the chimney or vent termination point.
When the furnace is installed in non−direct vent applica­tions, do not install the furnace where drafts might blow directly into it. This could cause improper combustion and unsafe operation.
When the furnace is installed in non−direct vent applica­tions, do not block the furnace combustion air opening with clothing, boxes, doors, etc. Air is needed for proper combustion and safe unit operation.
When the furnace is installed in an attic or other insu­lated space, keep insulation away from the furnace.
When the furnace is installed in an unconditioned space, consider provisions required to prevent freezing of condensate drain system.
CAUTION
ML193DF unit should not be installed in areas nor­mally subject to freezing temperatures.
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of Cal­ifornia to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
WARNING
Insufficient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rust­ing and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Avoid exposure to the following substances in the com­bustion air supply:
Permanent wave solutions Chlorinated waxes and cleaners Chlorine base swimming pool chemicals Water softening chemicals De−icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents (such as perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials
In the past, there was no problem in bringing in sufficient outdoor air for combustion. Infiltration provided all the air that was needed. In today’s homes, tight construction practices make it necessary to bring in air from outside for combustion. Take into account that exhaust fans, ap­pliance vents, chimneys, and fireplaces force additional air that could be used for combustion out of the house. Unless outside air is brought into the house for combus­tion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a downdraft can occur in the furnace vent pipe or chimney. As a result, combustion gases enter the living space creating a po­tentially dangerous situation.
In the absence of local codes concerning air for combus− tion and ventilation, use the guidelines and procedures in this section to install ML193DF furnaces to ensure effi­cient and safe operation. You must consider combustion air needs and requirements for exhaust vents and gas pip−ing. A portion of this information has been reprinted with permission from the National Fuel Gas Code (ANSI− Z223.1/NFPA 54). This reprinted material is not the com­plete and official position of the ANSI on the referenced subject, which is represented only by the standard in its entirety.
Combustion, Dilution & Ventilation Air
If the ML193DF is installed as a Non−Direct Vent Fur­nace, follow the guidelines in this section.
NOTE − In Non−Direct Vent installations, combustion air is taken from indoors and flue gases are discharged out− doors.
In Canada, refer to the CSA B149 installation codes.
CAUTION
Do not install the furnace in a corrosive or contami­nated atmosphere. Meet all combustion and ventila­tion air requirements, as well as all local codes.
Page 6
All gas-fired appliances require air for the combustion pro­cess. If sufficient combustion air is not available, the fur­nace or other appliance will operate inefficiently and un­safely. Enough air must be provided to meet the needs of all fuel−burning appliances and appliances such as exhaust fans which force air out of the house. When fireplaces, ex­haust fans, or clothes dryers are used at the same time as the furnace, much more air is required to ensure proper combustion and to prevent a downdraft. Insufficient air causes incomplete combustion which can result in carbon monoxide.
In addition to providing combustion air, fresh outdoor air di­lutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace compo­nents.
The requirements for providing air for combustion and ven­tilation depend largely on whether the furnace is installed in an unconfined or a confined space.
Unconfined Space
An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com­bined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be un­confined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures in the air from outside section.
Confined Space
A confined space is an area with a volume less than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com− bined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms.
When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space con­taining the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially
dangerous negative pressure condition. Air for combustion and ventilation can be brought into the confined space ei­ther from inside the building or from outside.
Air from Inside
If the confined space that houses the furnace adjoins a space categorized as unconfined, air can be brought in by providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of total input rating of all gas−fired equipment in the confined space. Each opening must be at least 100 square inches (64516 mm2). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. See figure 4.
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM INSIDE
ROOF TERMINATED
EXHAUST PIPE
OPENINGS
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE − Each opening shall have a free area of at least one square inch per 1,000 Btu (645mm rating of all equipment in the enclosure, but not less than 100 square inches (64516mm.
2
per .29kW) per hour of the total input
2).
(To Adjacent
Unconfined
Space)
FIGURE 4
Air from Outside
If air from outside is brought in for combustion and ventila­tion, the confined space shall be provided with two perma­nent openings. One opening shall be within 12" (305mm) of the top of the enclosure and one within 12" (305mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a mini­mum free area of 1 square inch per 4,000 Btu (645mm per 1.17kW) per hour of total input rating of all equipment in the enclosure. When communicating with the outdoors through horizontal ducts, each opening shall have a mini­mum free area of 1 square inch per 2,000 Btu (645mm per .59kW) per total input rating of all equipment in the en­closure (See figure 5).
2
2
Page 7
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE
(Inlet Air from Crawl Space and Outlet Air to Ventilated Attic)
VENTILATION LOUVERS
OUTLET
AIR
(Each end of attic)
ROOF TERMINATED
EXHAUST PIPE
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
ROOF TERMINATED
EXHAUST PIPE
OUTLET
AIR
VENTILATION LOUVERS
(Each end of attic)
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
INLET
AIR
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm
VENTILATION
LOUVERS
(For unheated
crawl space)
2
per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
FIGURE 5
If air from outside is brought in for combustion and ventila­tion, the confined space must have two permanent open­ings. One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. These openings must communi­cate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indi­rectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of total input rating of all equipment in the enclosure. See figures 5 and 6. When communicat­ing with the outdoors through horizontal ducts, each open­ing shall have a minimum free area of 1 square inch (645 mm2) per 2,000 Btu (.56 kW) per total input rating of all equipment in the enclosure. See figure 7.
When ducts are used, they shall be of the same cross−sec­tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protec­tive covering is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 percent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation.
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm
INLET AIR
(Ends 12" above
bottom)
2
per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
FIGURE 6
EQUIPMENT IN CONFINED SPACE −
ALL AIR FROM OUTSIDE
ROOF TERMINATED
EXHAUST PIPE
OUTLET AIR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE−Each air duct opening shall have a free area of at least one square inch per 2,000 Btu (645mm
2
per .59kW) per hour of the total
INLET AIR
input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings communi­cate directly with the outdoors, each opening shall have a free area of at least 1 square inch per 4,000 Btu (645mm
2
per 1.17kW) per
hour of the total input rating of all other equipment in the enclosure.
FIGURE 7
Shipping Bolt Removal
NOTE − The ML193DF09048C is equipped with a 1/2 hp blower motor which has three flexible legs and one rigid leg. The rigid leg is equipped with a shipping bolt and a flat white plastic washer (rather than the rubber mounting grommet used with a flexible mounting leg). See figure 8.
The bolt and washer must be removed before the fur­nace is placed into operation. After the bolt and washer
have been removed, the rigid leg will not touch the blower housing.
Page 8
ML193DF09048C BLOWER MOTOR
remove shipping bolt and washer
RIGID LEG
FIGURE 8
Installation − Setting Equipment
Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or al­cove installations are shown in figure 11.
WARNING
Blower access panel must be securely in place when blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.
WARNING
Do not install the furnace on its front, back or in the horizontal position. See figure 10. Do not connect the return air ducts to the back of the furnace. Doing so will adversely affect the operation of the safety con­trol devices, which could result in personal injury or death.
Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, condensate trap and drain connections, and installation and service clearances [24 inches (610 mm) at unit front]. The unit must be level from side to side. Unit may
be positioned from level to 1/2" toward the front to aid in draining. See figure 9.
SETTING EQUIPMENT
AIR FLOW
FRONT VIEW SIDE VIEW
Unit must be level side−to−side. Unit may be positioned from level to 1/2" toward the front to aid in draining.
AIR FLOW
FIGURE 9
AIR FLOW
SIDE VIEW
1/2"
max.
Front
Back
NOTE − Do not install the furnace on its front, back or in the horizontal position
FIGURE 10
Page 9
Horizontal
WARNING
Improper installation of the furnace can result in per­sonal injury or death. Combustion and flue products must never be allowed to enter the return air system or air in the living space. Use sheet metal screws and joint tape to seal return air system to furnace. In platform installations with furnace return, the fur­nace should be sealed airtight to the return air ple­num. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Al­low absolutely no sagging, cracks, gaps, etc. For no reason should return and supply air duct sys­tems ever be connected to or from other heating de­vices such as a fireplace or stove, etc. Fire, explo­sion, carbon monoxide poisoning, personal injury and/or property damage could result.
The unit may be installed three ways in downflow applica­tions: on non−combustible flooring, on combustible flooring using an additive base, or on a reverse−flow cooling coil cabinet. Do not drag the unit across the floor in the
downflow position. Floor and furnace flange damage will result. Refer to figure 11 for clearances in downflow applica-
tions.
Installation on Non−Combustible Flooring Figure 12
1 − Cut floor opening keeping in mind clearances listed on
unit rating plate. Also keep in mind gas supply connec­tions, electrical supply, flue and air intake connections and sufficient installation and servicing clearances. See table 1 for correct floor opening size.
2 − Flange warm air plenum and lower the plenum into the
opening.
3 − Set the unit over the plenum and seal the plenum to
the unit.
4 − Ensure that the seal is adequate.
TABLE 1
NON−COMBUSTIBLE FLOOR OPENING SIZE
Cabinet Width
B Cabinet (17.5") 19 − 3/4 502 16 − 5/8 422
C Cabinet (21") 19 − 3/4 502 20−1/8 511
NOTE − Floor opening dimensions listed are 1/4 inch (6 mm) larger than the unit opening. See dimension drawing on page 2.
Front to Rear Side to Side
in. mm in. mm
Downflow Application Installation Clearances
Top
Left Side Right Side
Bottom
Top 0
*Front 0
Back 0
Sides 0†
Vent 0
Floor NC
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. †Allow proper clearances to accommodate condensate trap and vent pipe installation. The furnace may be installed on a combustible wood floor if an op­tional additive base is installed between the furnace and the com­bustible floor.
FIGURE 11
FURNACE
PROPERLY
SIZED FLOOR
OPENING
SUPPLY AIR
PLENUM
FIGURE 12
Installation on Combustible Flooring Figure 13
1 − When unit is installed on a combustible floor, a down-
flow combustible flooring base must be installed be­tween the furnace and the floor. The base must be or­dered separately. See table 2 for opening size to cut in floor.
CAUTION
The furnace and combustible flooring base shall not be installed directly on carpeting, tile, or other com­bustible material other than wood flooring.
Page 10
TABLE 2
COMBUSTIBLE FLOORING BASE OPENING SIZE
Cabinet
Width
B Cabinet
(17.5")
Catalog Number
11M60
Front to Rear Side to Side
in. mm in. mm
22 559 18 − 3/4 476
FURNACE
C Cabinet
(21")
FURNACE
PROPERLY
SIZED FLOOR
OPENING
11M61
22 559 22 − 3/4 578
SUPPLY AIR
PLENUM
COMBUSTIBLE FLOORING BASE
FIGURE 13
2 − After opening is cut, set the combustible flooring base
into opening.
3 − Check fiberglass strips on the combustible flooring
base to make sure they are properly glued and posi­tioned.
4 − Lower supply air plenum into the combustible flooring
base until plenum flanges seal against fiberglass strips.
NOTE − Be careful not to damage fiberglass strips. Check for a tight seal.
5 − Set the furnace over the plenum.
6 − Ensure that the seal between the furnace and plenum
is adequate.
Installation on Cooling Coil Cabinet Figure 14
NOTE − Downflow combustible flooring kit is not used..
1 − Refer to reverse−flow coil installation instructions for
correctly sized opening in floor and installation of cabi­net.
2 − When cooling cabinet is in place, set and secure the
furnace according to the instructions that are provided with the cooling coil. Secure the furnace to the cabinet.
3 − Seal the cabinet and check for air leaks.
COOLING COIL
PROPERLY
SIZED FLOOR
OPENING
PLENUM
FIGURE 14
Return Air Opening −− Downflow Units
Return air may be brought in only through the top opening of a furnace installed in the downflow position. The follow­ing steps should be taken when installing plenum:
1 − Bottom edge of plenum should be flanged with a
hemmed edge (See figure 15 or 16).
2 − Sealing strips should be used to ensure an airtight seal
between the cabinet and the plenum.
3 − In all cases, plenum should be secured to top of fur-
nace using sheet metal screws.
4 − Make certain that an adequate seal is made.
PLENUM
(Field Provided)
SEALING STRIP (Field Provided)
SECURE FROM
OUTSIDE CABINET
CABINET
SIDE PANEL
Side View
FIGURE 15
PLENUM
(Field Provided)
SECURE FROM
INSIDE CABINET
Side View
SEALING STRIP
(Field Provided)
CABINET
SIDE PANEL
FIGURE 16
Page 11
Filters
This unit is not equipped with a filter or rack. A field−pro­vided filter is required for the unit to operate properly. Table 3 lists recommended filter size. A filter must be in place whenever the unit is operating.
TABLE 3
Furnace
Cabinet Width
17−1/2"
21"
Filter Size
16 x 25 x 1 (1)
Pipe & Fittings Specifications
All pipe, fittings, primer and solvent cement must conform with American National Standard Institute and the Ameri­can Society for Testing and Materials (ANSI/ASTM) stan­dards. The solvent shall be free flowing and contain no lumps, undissolved particles or any foreign matter that ad­versely affects the joint strength or chemical resistance of the cement. The cement shall show no gelation, stratifica­tion, or separation that cannot be removed by stirring. Re­fer to the table 4 below for approved piping and fitting ma­terials.
Duct System
Use industry-approved standards to size and install the supply and return air duct system. Refer to ACCA Manual D. This will result in a quiet and low-static system that has uniform air distribution.
NOTE − This furnace is not certified for operation in heating mode (indoor blower operating at selected heating speed) with an external static pressure which exceeds 0.5 inches w.c. Operation at these conditions may result in improper limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a removable access panel should be installed in the supply air duct. The access panel should be large enough to permit inspection of the heat exchanger. The furnace access panel must al­ways be in place when the furnace is operating and it must not allow leaks into the supply air duct system.
Return Air Plenum
NOTE − Return air must not be drawn from a room where this furnace, or any other gas−fueled appliance (i.e., water heater), or carbon monoxide−producing de­vice (i.e., wood fireplace) is installed.
When return air is drawn from a room, a negative pres­sure is created in the room. If a gas appliance is operating in a room with negative pressure, the flue products can be pulled back down the vent pipe and into the room. This reverse flow of the flue gas may result in incomplete com­bustion and the formation of carbon monoxide gas. This raw gas or toxic fumes might then be distributed through­out the house by the furnace duct system.
Use fiberglass sealing strips, caulking, or equivalent seal­ing method between the plenum and the furnace cabinet to ensure a tight seal. If a filter is installed, size the return air duct to fit the filter frame.
CAUTION
Solvent cements for plastic pipe are flammable liq­uids and should be kept away from all sources of ignition. Do not use excessive amounts of solvent cement when making joints. Good ventilation should be maintained to reduce fire hazard and to minimize breathing of solvent vapors. Avoid contact of cement with skin and eyes.
PIPING AND FITTINGS SPECIFICATIONS
Schedule 40 PVC (Pipe) D1785 Schedule 40 PVC (Cellular Core Pipe) F891
Schedule 40 PVC (Fittings) D2466
Schedule 40 CPVC (Pipe) F441
Schedule 40 CPVC (Fittings) F438
SDR−21 PVC or SDR−26 PVC (Pipe) D2241
SDR−21 CPVC or SDR−26 CPVC (Pipe) F442
Schedule 40 ABS Cellular Core DWV (Pipe) F628
Schedule 40 ABS (Pipe) D1527
Schedule 40 ABS (Fittings) D2468
ABS−DWV (Drain Waste & Vent) (Pipe & Fittings)
PVC−DWV (Drain Waste & Vent) Pipe & Fittings)
PRIMER & SOLVENT CEMENT
PVC & CPVC Primer F656 PVC Solvent Cement D2564
CPVC Solvent Cement F493
ABS Solvent Cement D2235
PVC/CPVC/ABS All Purpose Cement For Fittings & Pipe of the same material
ABS to PVC or CPVC Transition Solvent Cement
CANADA PIPE & FITTING & SOLVENT
CEMENT
PVC & CPVC Pipe and Fittings PVC & CPVC Solvent Cement
ABS to PVC or CPVC Transition Cement
TABLE 4
D2661
D2665
ASTM
SPECIFICATION
D2564, D2235, F493
D3138
MARKING
ULCS636
Page 12
IMPORTANT
ML193DF exhaust and intake connections are made of PVC. Use PVC primer and solvent cement when using PVC vent pipe. When using ABS vent pipe, use transitional solvent cement to make connections to the PVC fittings in the unit.
Use PVC primer and solvent cement or ABS solvent cement meeting ASTM specifications, refer to Table 4. As an alter­nate, use all purpose cement, to bond ABS, PVC, or CPVC pipe when using fittings and pipe made of the same materi­als. Use transition solvent cement when bonding ABS to ei­ther PVC or CPVC.
TABLE 5
ML193
UNIT
OUTDOOR TERMINATION KITS USAGE
STANDARD CONCENTRIC
Outdoor
VENT
PIPE
DIA. (in.)
2 YES YES YES* YES YES YES
Exhaust
Accelerator
(Dia. X
Length)
1−1/2" X 12" 2" X 12"
Outdoor Exhaust
Accelerator
(Dia. X
Length)
2" Wall Plate
Kit
22G44
or 30G28
Low temperature solvent cement is recommended during cooler weather. Metal or plastic strapping may be used for vent pipe hangers. Uniformly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean in­side socket surface of fitting and male end of pipe to depth of fitting socket.
Canadian Applications Only − Pipe, fittings, primer and solvent cement used to vent (exhaust) this ap­pliance must be certified to ULC S636 and supplied by a single manufacturer as part of an approved vent (ex­haust) system. In addition, the first three feet of vent pipe from the furnace flue collar must be accessible for inspection.
3" Wall Plate
Kit
44J40
or 81J20
2" Wall
Ring Kit
15F74 51W11**
Flush­Mount
Kit
1−1/2"
Concentric
Kit
71M80
or
44W92
2"
Concentric
Kit
69M29
or
44W92
3"
Concentric
Kit
60L46
or 44W93
045
070
090
110 3 YES YES YES YES YES YES
*Requires field−provided and installed 1−1/2" exhaust accelerator. ** Kit 51W11 is provided with a 1−1/2" accelerator which must be used for all ML193DF−045, −070 and −090 installations.  Termination kits 44W92, 44W93, 30G28 and 81J20 approved for use in Canadian installations to meet CSAB149.  The 44W92 Concentric kit is provided with a 1−1/2" accelerator which must be installed on the exhaust outlet when this kit is used with the ML193DF045P36B and
ML193DF070P36B
2−1/2 YES YES YES* YES YES YES
3 YES YES YES* YES YES YES
2 YES YES YES* YES YES YES
2−1/2 YES YES YES* YES YES YES
3 YES YES YES* YES YES YES
2 YES YES YES YES YES YES
2−1/2 YES YES YES YES YES YES
3 YES YES YES YES YES YES
furnaces.
Page 13
Joint Cementing Procedure
Venting Practices
All cementing of joints should be done according to the specifications outlined in ASTM D 2855.
NOTE − A sheet metal screw may be used to secure the intake pipe to the connector, if desired. Use a drill or self tapping screw to make a pilot hole.
DANGER
DANGER OF EXPLOSION!
Fumes from PVC glue may ignite during system check. Allow fumes to dissipate for at least 5 minutes before placing unit into operation.
1 − Measure and cut vent pipe to desired length.
2 − Debur and chamfer end of pipe, removing any ridges
or rough edges. If end is not chamfered, edge of pipe may remove cement from fitting socket and result in a leaking joint.
3 − Clean and dry surfaces to be joined.
4 − Test fit joint and mark depth of fitting on outside of pipe.
5 − Uniformly apply a liberal coat of PVC primer for PVC or
use a clean dry cloth for ABS to clean inside socket surface of fitting and male end of pipe to depth of fitting socket.
6 − Promptly apply solvent cement to end of pipe and in-
side socket surface of fitting. Cement should be ap­plied lightly but uniformly to inside of socket. Take care to keep excess cement out of socket. Apply sec­ond coat to end of pipe.
NOTE − Time is critical at this stage. Do not allow prim­er to dry before applying cement.
7 − Immediately after applying last coat of cement to pipe,
and while both inside socket surface and end of pipe are wet with cement, forcefully insert end of pipe into socket until it bottoms out. Turn PVC pipe 1/4 turn dur­ing assembly (but not after pipe is fully inserted) to dis­tribute cement evenly. DO NOT turn ABS or cellular core pipe.
NOTE − Assembly should be completed within 20 sec­onds after last application of cement. Hammer blows should not be used when inserting pipe.
8 − After assembly, wipe excess cement from pipe at end
of fitting socket. A properly made joint will show a bead around its entire perimeter. Any gaps may indi­cate an improper assembly due to insufficient sol­vent.
9 − Handle joints carefully until completely set.
Piping Suspension Guidelines
SCHEDULE 40
PVC − 5’
all other pipe* − 3’
* See table 4 for allowable pipe.
NOTE − Isolate piping at the point where it exits the outside wall or roof in order to prevent transmission of vibration to the structure.
Wall Thickness Guidelines
24" maximum 3/4" minimum
inside outside
Wall
FIGURE 17
REPLACING FURNACE THAT
CHIMNEY
OR GAS
VENT
(Check sizing
for water
heater only)
FURNACE
(Replaced
by ML193)
If an ML193DF furnace replaces a furnace which was com­monly vented with another gas appliance, the size of the ex­isting vent pipe for that gas appliance must be checked. Without the heat of the original furnace flue products, the existing vent pipe is probably oversized for the single water heater or other appliance. The vent should be checked for proper draw with the remaining appliance.
WAS PART OF A COMMON
VENT SYSTEM
WATER
HEATER
OPENINGS
(To Adjacent
Room)
FIGURE 18
1 − In areas where piping penetrates joists or interior
walls, hole must be large enough to allow clearance on all sides of pipe through center of hole using a hanger.
Page 14
2 − When furnace is installed in a residence where unit is
shut down for an extended period of time, such as a vacation home, make provisions for draining conden­sate collection trap and lines.
Exhaust Piping (Figures 20 and 21)
Route piping to outside of structure. Continue with installa­tion following instructions given in piping termination sec­tion.
Use the following steps to correctly size vent pipe diameter.
045, 070,
1
Furnace capacity?
090, 110 or 135 btuh
CAUTION
Do not discharge exhaust into an existing stack or stack that also serves another gas appliance. If verti­cal discharge through an existing unused stack is re­quired, insert PVC pipe inside the stack until the end is even with the top or outlet end of the metal stack.
CAUTION
The exhaust vent pipe operates under positive pres­sure and must be completely sealed to prevent leak­age of combustion products into the living space.
Vent Piping Guidelines
The ML193DF can be installed as either a Non−Direct Vent or a Direct Vent gas central furnace.
NOTE − In Non-Direct Vent installations, combustion air is taken from indoors and flue gases are discharged outdoors. In Direct Vent installations, combustion air is taken from out­doors and flue gases are discharged outdoors.
Intake and exhaust pipe sizing −− Size pipe according to
tables 6 and 7. Table 6 lists the minimum vent pipe lengths permitted. Table 7 lists the maximum pipe lengths per- mitted.
MINIMUM VENT PIPE LENGTHS
ML193DF
MODEL
045, 070, 090, 110
*Any approved termination may be added to the minimum length listed.
Regardless of the diameter of pipe used, the standard roof and wall terminations described in section Exhaust Piping Terminations should be used. Exhaust vent termination pipe is sized to optimize the velocity of the exhaust gas as it exits the termination. Refer to table 8.
In some applications which permit the use of several differ­ent sizes of vent pipe, a combination vent pipe may be used. Contact Lennox’ Application Department for assis­tance in sizing vent pipe in these applications.
TABLE 6
MIN. VENT LENGTH*
15 ft. or
5 ft plus 2 elbows or
10 ft plus 1 elbow
Standard or
Which termination?
2
3
4
5
6
7
NOTE − It is acceptable to use any pipe size which fits within the guidelines allowed in table 7.
NOTE − toward unit. A minimum of 1/4" (6mm) drop for each 12" (305mm) of horizontal run is mandatory for drainage.
Which needs most elbows?
How many?
Desired pipe size?
What is the altitude?
Use table 7 to find max intake or exhaust pipe length.
FIGURE 19
All horizontal runs of exhaust pipe must slope back
Concentric? See table 5
Intake or exhaust
2", 2−1/2" or 3"
IMPORTANT
Do not use screens or perforated metal in exhaust or intake terminations. Doing so will cause freeze−ups and may block the terminations.
Page 15
NOTE − Exhaust pipe MUST be glued to furnace exhaust fittings.
NOTE − Exhaust piping should be checked carefully to make sure there are no sags or low spots.
Maximum Allowable Intake or Exhaust Vent Length in Feet
TABLE 7
*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size.
Standard Termination at Elevation 0 − 10,000 ft.
Number
Of 90°
Elbows
Used
1 61 46 24
2 56 41 19 95 75 38 122 122 103 103
3 51 36 14 90 70 33 11 7 117 98 98
4 46 31
5 41 26 80 60 23 107 107 88 88
6 36 21 75 55 18 102 102 83 83
7 31 16 70 50 13 97 97 78 78
8 26 11 65 45
9 21
10 16 55 35 82 82 63 63
Number
Of 90°
Elbows
Used
1 53 38 22
2 48 33 17 85 65 34 106 106 99 99
3 43 28 12 80 60 29 101 101 94 94
4 38 23
5 33 18 70 50 19 91 91 84 84
6 28 13 65 45 14 86 86 79 79
7 23
8 18 55 35 76 76 69 69
9 13 50 30 71 71 64 64
10 n/a 45 25 66 66 59 59
045 070 090 110 045 070 090 110 045 070 090 110
045 070 090 110 045 070 090 110 045 070 090 110
2" Pipe 2−1/2" Pipe 3" Pipe
Model Model Model
100 80 43
85 65 28 11 2 112 93 93
n/a
n/a
n/a
Concentric Termination Elevation 0 − 10,000 ft.
2" Pipe 2−1/2" Pipe 3" Pipe
Model Model Model
n/a
n/a
n/a
60 40 87 87 68 68
90 70 39
75 55 24 96 96 89 89
60 40
n/a
n/a
n/a
n/a
127 127 108 108
92 92 73 73
111 111 104 104
81 81 74 74
Page 16
Loading...
+ 36 hidden pages