This is a safety alert symbol and should never be
ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and wear gloves and
protective clothing.
AIR FLOW
Contents
Unit Dimensions .............................................................2
ML180DF Gas Furnace .................................................. 3
Shipping and Packing List ..............................................3
Safety Information ..........................................................3
Use of Furnace as Construction Heater .........................4
General ........................................................................... 4
Combustion, Dilution & Ventilation Air ............................5
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal
injury or loss of life. Installation and service must be
performed by a licensed professional HVAC installer or
equivalent, service agency, or the gas supplier.
Gas Piping .................................................................... 16
Repait Parts .................................................................. 28
Page 1
Page 2
Unit Dimensions - inches (mm)
A
B
AIR FLOW
9/16
(14)
FLUE OUTLET
(Top)
3/4 (19)
Front Panel
3-1/8
(79)
D
9/16
(14)
RETURN AIR
OPENING
B
19-7/16
(494)
9/16
(14)
TOP VIEW
27-3/4
(705)
19-7/16
(494)
9/16
(14)
9/16
(14)
ELECTRICAL INLET
(Either Side)
GAS PIPING INLET
(Either Side)
19-1/4
Supply
(489)
Air
3/4
(19)
C
Supply
Air
33
(838)
5-3/8 (137) Right
2-3/16 (56) Left
6-5/8 (168) Right
7-1/8 (181) Left
3/4
(19)
FRONT VIEWSIDE VIEW
Model No.
ABCD
inmminmminmminmm
ML180DF045P24A
ML180DF045P36A
14-1/236813-3/8340133304-3/4121
ML180DF070P36A
ML180DF090P36B
ML180DF090P48B
ML180DF110P60C2153319-7/850419-1/24958203
17-1/244616-3/8416164066-1/4
3/4
(19)
159
Page 2
Page 3
ML180DF Gas Furnace
The ML180DF gas furnace is shipped ready for installation in the downow position fueled by natural gas. A conversion kit (ordered separately) is required for use in LP/
Propane gas applications.
Shipping and Packing list
Package 1 of 1 contains
1 - Assembled ML180DF unit
1 - Bag assembly containing the following:
1 - Owner’s manual and warranty card
The following items may be ordered separately:
1 - Thermostat
1 - LP/Propane changeover kit
1 - Combustible ooring base
1 - High altitude kit
Check equipment for shipping damage. If you nd any
damage, immediately contact the last carrier.
Safety Information
DANGER
Danger of explosion.
There are circumstances in which odorant used with LP/
propane gas can lose its scent. In case of a leak, LP/
propane gas will settle close to the oor and may be
difcult to smell. An LP/propane leak detector should be
installed in all LP applications.
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal
injury or loss of life. Installation and service must be
performed by a licensed professional installer (or
equivalent), service agency or the gas supplier.
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and wear gloves
and protective clothing.
Certications
ML180DF units are CSA International certied.
In the USA, installation of gas furnaces must conform with
local building codes. In the absence of local codes, units
must be installed according to the current National Fuel
Gas Code (ANSI-Z223.1). The National Fuel Gas Code is
available from the following address:
American National Standards Institute, Inc.
11 West 42nd Street
New York, NY 10036
Clearances
Adequate clearance must be made around the air openings into the vestibule area. In order to ensure proper unit
operation, combustion and ventilation air supply must
be provided according to the current National Fuel Gas
Code. Vent installations must be consistent with the National Fuel Gas Code venting tables (in this instruction)
and applicable provisions of local building codes.
This furnace is CSA International certied for installation
clearances to combustible material as listed on the unit
nameplate and in the tables in gure 13. Accessibility and
service clearances must take precedence over re protec-
tion clearances.
Installed Locations
For installation in a residential garage, the furnace must
be installed so that the burner(s) and the ignition source
are located no less than 18 inches (457 mm) above the
oor. The furnace must be located or protected to avoid
physical damage by vehicles. When a furnace is installed
in a public garage, hangar, or other building that has a
hazardous atmosphere, the furnace must be installed according to recommended good practice requirements and
current National Fuel Gas Code.
NOTE - Furnace must be adjusted to obtain a temperature
rise within the range(s) specied on the unit nameplate.
Failure to do so may cause erratic limit operation and
may also result in premature heat exchanger failure. This
ML180DF furnace must be installed so that its electrical
components are protected from water.
Installed in Combination with a Cooling Coil
When this furnace is used with cooling units, it shall be installed in parallel with, or on the upstream side of, cooling
units to avoid condensation in the heating compartment.
With a parallel ow arrangement, a damper (or other
means to control the ow of air) must adequately prevent
chilled air from entering the furnace (see gure 1). If the
damper is manually operated, it must be equipped to prevent operation of either the heating or the cooling.
Page 3
Page 4
• The return air duct must be provided and sealed
to the furnace.
• Return air temperature range between 60°F (16°C)
and 80°F (27°C) must be maintained.
GAS UNIT
Dampers
(open during heating
operation only)
AIR HANDLER
Dampers
(open during cooling
operation only)
FIGURE 1
When installed, this furnace must be electrically grounded
according to local codes. In addition, in the United States,
installation must conform with the current National Electric Code, ANSI/NFPA No. 70. The National Electric Code
(ANSI/NFPA No. 70) is available from the following address:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
NOTE - This furnace is designed for a minimum continuous return air temperature of 60°F (16°C) or an intermittent
operation down to 55°F (13°C) dry bulb for cases where a
night setback thermostat is used. Return air temperature
must not exceed 85°F (29°C) dry bulb.
The ML180DF furnace may be installed in alcoves, closets, attics, basements, garages, and utility rooms in the
downow position.
This furnace design has not been CSA International
certied for installation in mobile homes, recreational
vehicles, or outdoors.
Safety Information
Lennox does not recommend the use of ML180DF units
as a construction heater during any phase of construction. Very low return air temperatures, harmful vapors and
operation of the unit with clogged or misplaced lters will
damage the unit.
ML180DF units may be used for heating of buildings or
structures under construction, if the following conditions
are met:
• The vent system must be permanently installed per
these installation instructions.
• A room thermostat must control the furnace. The
use of xed jumpers that will provide continuous
heating is not allowed.
• Air lters must be installed in the system and must
be maintained during construction.
• Air lters must be replaced upon construction com-
pletion.
• The input rate and temperature rise must be set per
the furnace rating plate.
• One hundred percent (100%) outdoor air must be
provided for combustion air requirements during
construction. Temporary ducting may supply outdoor air to the furnace. Do not connect duct directly
to the furnace. Size the temporary duct following
these instructions in section for Combustion, Dilution and Ventilation Air in a conned space with air
from outside.
• The furnace heat exchanger, components, duct
system, air lters and evaporator coils must be
thoroughly cleaned following nal construction
clean-up.
• All furnace operating conditions (including ignition,
input rate, temperature rise and venting) must be
veried according to these installation instructions.
General
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
In addition to the requirements outlined previously, the
following general recommendations must be considered
when installing a ML180DF furnace:
• Place the furnace as close to the center of the air
distribution system as possible. The furnace should
also be located close to the chimney or vent termination point.
• Do not install the furnace where drafts might blow
directly into it. This could cause improper combustion and unsafe operation.
• Do not block the furnace combustion air openings
with clothing, boxes, doors, etc. Air is needed for
proper combustion and safe unit operation.
• When the furnace is installed in an attic or other
insulated space, keep insulation away from the fur-
nace.
NOTE - The Commonwealth of Massachusetts
stipulates these additional requirements:
• Gas furnaces shall be installed by a licensed
plumber or tter only.
• The gas cock must be “T handle” type.
• When a furnace is installed in an attic, the pas-
sageway to and service area surrounding the
equipment shall be oored.
Page 4
Page 5
WARNING
This prodcut contains a chemical known to the State
of California to cause cancer, birth defects, or other
reproductive harm.
Combustion, Dilution & Ventilation Air
In the past, there was no problem in bringing in sufcient
outdoor air for combustion. Inltration provided all the air
that was needed. In today’s homes, tight construction
practices make it necessary to bring in air from outside for
combustion. Take into account that exhaust fans, appli-
ance vents, chimneys, and replaces force additional air
that could be used for combustion out of the house. Unless outside air is brought into the house for combustion,
negative pressure (outside pressure is greater than inside
pressure) will build to the point that a downdraft can occur in the furnace vent pipe or chimney. As a result, combustion gases enter the living space creating a potentially
dangerous situation.
In the absence of local codes concerning air for combustion and ventilation, use the guidelines and procedures in
this section to install ML180DF furnaces to ensure efcient and safe operation. You must consider combustion
air needs and requirements for exhaust vents. A portion of
this information has been reprinted with permission from
the National Fuel Gas Code (ANSI-Z223.1). This reprint-
ed material is not the complete and ofcial position of the
ANSI on the referenced subject,
CAUTION
Do not install the furnace in a corrosive or contaminated
atmosphere. Meet all combustion and ventilation air
requirements, as well as all local codes.
All gas-red appliances require air for the combustion
process. If sufcient combustion air is not available, the
furnace or other appliances will operate inefciently and
unsafely. Enough air must be provided to meet the needs
of all fuel-burning appliances and appliances such as exhaust fans which force air out of the house. When replaces, exhaust fans, or clothes dryers are used at the
same time as the furnace, much more air is necessary
to ensure proper combustion and to prevent a downdraft.
Insufcient air causes incomplete combustion which can
result in carbon monoxide.
CAUTION
Insufcient combustion air can cause headaches,
nausea, dizziness or asphyxiation. It will also cause
excess water in the heat exchanger resulting in rusting
and premature heat exchanger failure. Excessive
exposure to contaminated combustion air will result
in safety and performance related problems. Avoid
exposure to the following substances in the combustion
air supply:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine base swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
In addition to providing combustion air, fresh outdoor air
dilutes contaminants in the indoor air. These contaminants
may include bleaches, adhesives, detergents, solvents
and other contaminants which can corrode furnace components.
The requirements for providing air for combustion and
ventilation depend largely on whether the furnace is in-
stalled in an unconned or a conned space.
Unconned Space
An unconned space is an area such as a basement or
large equipment room with a volume greater than 50 cubic
feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space.
This space also includes adjacent rooms which are not
separated by a door. Though an area may appear to be
unconned, it might be necessary to bring in outdoor air
for combustion if the structure does not provide enough air
by inltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around
the windows and doors, follow the procedures in the air
from outside section.
Conned Space
A conned space is an area with a volume less than 50
cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of
the combined input rating of all appliances installed in that
space. This denition includes furnace closets or small
equipment rooms.
Page 5
Page 6
When the furnace is installed so that supply ducts carry
air circulated by the furnace to areas outside the space
containing the furnace, the return air must be handled by
ducts which are sealed to the furnace casing and which
terminate outside the space containing the furnace. This
is especially important when the furnace is mounted on
a platform in a conned space such as a closet or small
equipment room. Even a small leak around the base of
the unit at the platform or at the return air duct connection
can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought
into the conned space either from inside the building or
from outside.
EQUIPMENT IN CONFINED
CHIMNEY
OR GAS
VENT
FURNACE
AIR FLOW
NOTE - Each opening shall have a free area of at least one square
inch (645 mm
ing of all equipment in the enclosure, but not less than 100 square
inches (64516 mm
2
2
).
SPACE ALL AIR FROM INSIDE
WATER
HEATER
OPENINGS
(To Adjacent
Room)
FIGURE 2
Air from Inside
If the conned space that houses the furnace adjoins a
space categorized as unconned, air can be brought in by
providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1
square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of
total input rating of all gas-red equipment in the conned
space. Each opening must be at least 100 square inches
(64516 mm2). One opening shall be within 12 inches (305
mm) of the top of the enclosure and one opening within 12
inches (305 mm) of the bottom. See gure 2.
Air from Outside
If air from outside is brought in for combustion and ventilation, the conned space must have two permanent openings. One opening shall be within 12 inches (305 mm) of
the top of the enclosure and one opening within 12 inches
(305 mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl
or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a
minimum free area of 1 square inch (645 mm2) per 4,000
Btu (1.17 kW) per hour of total input rating of all equipment
in the enclosure. See gures 3 and 4. When communicating with the outdoors through horizontal ducts, each
opening shall have a minimum free area of 1 square inch
(645 mm2) per 2,000 Btu (.56 kW) per total input rating of
all equipment in the enclosure. See gure 5.
When ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they
connect. The minimum dimension of rectangular air ducts
shall be no less than 3 inches (75 mm). In calculating free
area, the blocking effect of louvers, grilles, or screens
must be considered. If the design and free area of protective covering is not known for calculating the size opening
required, it may be assumed that wood louvers will have
20 to 25 percent free area and metal louvers and grilles
will have 60 to 75 percent free area. Louvers and grilles
must be xed in the open position or interlocked with the
equipment so that they are opened automatically during
equipment operation.
Page 6
Page 7
CHIMNEY OR
EQUIPMENT IN CONFINED SPACE
ment in the enclosure.
S
other equipment in the enclosure.
GAS VENT
FURNACE
(Inlet Air from Crawlspace and Outlet Air to Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
OUTLET
AIR
WATER
HEATER
CHIMNEY
OR GAS
VENT
FURNACE
VENTILATION
LOUVERS
(For unheated crawl space)
AIR FLOW
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch (645
2
mm
) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equipment in the enclosure.
INLET
AIR
Figure 3
ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
VENTILATION LOUVER
(Each end of attic)
OUTLET
AIR
INLET AIR
(Ends 12 in.
above bottom)
FURNACE
CHIMNEY
OR GAS
VENT
CONFINED SPACE
WATER
HEATER
OUTLET AIR
EQUIPMENT IN
ALL AIR FROM
OUTSIDE
AIR FLOW
NOTE-The inlet and outlet air openings shall each have a
free area of at least one square inch (645 mm
FIGURE 4
WATER
HEATER
2
) per 4,000
Page 7
AIR FLOW
NOTE - Each air duct opening shall have a free area of at least
one square inch (645 mm
2
) per 2,000 Btu (.59 kW) per hour of
INLET AIR
the total input rating of all equipment in the enclosure. If the
equipment room is located against an outside wall and the air
openings
ing shall have a free area of at least one square inch (645 mm
per 4,000 Btu (1.17 kW) per hour of the total input rating of all
FIGURE 5
2
)
Page 8
Downow Installation
Downow unit installs in three ways: on non-combustible
ooring, on combustible ooring using a downow com-
bustible ooring base, or on a reverse-ow cooling cabinet. Do not drag the unit across the oor.
Installation on Non-Combustible Flooring (Figure 6)
1 - Cut oor opening keeping in mind clearances listed
on unit rating plate. Also keep in mind gas supply
connections, electrical supply, ue and air intake
connections and sufcient installation and servicing
clearances. See table 1 for correct oor opening
size.
2 - Flange warm air plenum and lower the plenum into
the opening.
3 - Set the unit over the plenum and seal the plenum
to the unit.
4 - Ensure that the seal is adequate.
SUPPLY AIR
OPENING
PLENUM
FIGURE 6
TABLE 1
NON-COMBUSTIBLE FLOOR OPENING SIZE
Cabinet
Width
A (14.5”)
B (17.5”)16-3/4413
Front to RearSide to Side
inmminmm
13-1/4337
19-3/4502
C (21”)19-3/4502
NOTE - Floor opening dimensions listed are 1/4 inch (6 mm) larger than
the unit opening. See unit dimensions on page 2.
Installation on Combustible Flooring (Figure 7)
1 - When unit is installed on a combustible oor,
a downow combustible ooring base must be
installed between the furnace and the oor. The
base must be ordered separately.
See table 2 for opening size to cut in oor.
CAUTION
The furnace and downow combustible ooring base
shall not be installed directly on carpeting, tile, or other
combustible material other than wood ooring.
SUPPLY AIR PLENUM
PROPERLY
SIZED FLOOR
OPENING
FIGURE 7
TABLE 2
COMBUSTIBLE FLOOR OPENING SIZE
Cabinet
Width
Front to RearSide to Side
inmminmm
A (14.5”)
B (17.5”)18-3/4476
22569
C (21”)22-3/4
2 - After opening is cut, set combustible ooring base
into opening.
3 - Check sealing strips on combustible ooring base to
make sure they are properly glued and positioned.
4 - Lower supply air plenum into downow combustible
ooring base until plenum anges seal against the
strips.
NOTE - Be careful not to damage sealing strips.
Check for a tight seal.
5 - Set the furnace over the plenum.
6 - Ensure that the seal between the furnace and
plenum s adequate.
Installation on Cooling Cabinet (Figure 8)
1 - Refer to reverse-ow coil installation instructions for
correctly sized opening in oor and installation of
cabinet.
NOTE - Downow combustible ooring kit is not
used.
2 - When cooling cabinet is in place, set and secure
the furnace according to the instructions that are
provided with the cooling coil. Secure the furnace
to the cabinet.
3 - Seal the cabinet and check for air leaks.
DOWNFLOW
COMBUSTIBLE
FLOORING BASE
15-3/4400
578
Page 8
Page 9
PROPERLY
Blower motor with three exible legs and one
SIZED FLOOR
OPENING
FIGURE 8
Return Air Opening -- Downow Units
COOLING COIL
PLENUM
Setting Equipment
WARNING
Do not install the furnace on its front, back or in the
horizontal position. See gure 12. Do not connect the
return air ducts to the back of the furnace. Doing so
will adversely affect the operation of the safety control
devices, which could result in personal injury or death.
Install the ML180DF gas furnace as shipped in the down-
ow position only. Do not install the furnace horizontally.
Select a location that allows for the required clearances
that are listed on the unit nameplate. Also consider gas
supply connections, electrical supply, vent connection,
and installation and service clearances [24 inches (610
mm) at unit front]. The unit must be level.
The following steps should be taken when installing plenum:
1 - Bottom edge of plenum should be anged with a
hemmed edge (See gure 9).
PLENUM
SECURE FROM
OUTSIDE CABINET
Side View
HEMMED EDGE
SEALING STRIP
(Field Provided)
CABINET SIDE PANEL
FIGURE 9
2 - Sealing strip should be used.
3 - In all cases, plenum should be secured to top
anges of furnace with sheet metal screws.
PLENUM
SIDE CABINET
HEMMED EDGE
Side View
NOTE - Units with 1/3HP and 1/2HP blower motors are
equipped with three exible legs and one shipping leg. See
gure 11. In some units with 1/3HP blower motor, the shipping leg is exible with rubber mounting grommets similar
to the other three mounting legs and require no modication. The rest of the units with 1/3HP and 1/2HP blower
motors (these blower motor housings will be tagged) have
a rigid shipping leg equipped with a shipping bolt and at
white plastic washer. The bolt and washer must be re-moved before the furnace is placed into operation. After the bolt and washer have been removed, the rigid leg
will not touch the blower housing.
rigid shipping leg. Blower motor housings
will be tagged for shipping bolt removal
RIGID LEG
(Remove shipping bolt
and washer)
FIGURE 11
FIBERGLASS
SEALING STRIP
(Field Provided)
CABINET SIDE
PANEL
FIGURE 10
4 - In closet installations, it may be impossible to install
sheet metal screws from the outside. In this case,
make plenum with a removable front and install
screws from the inside (See gure 10).
5 - Make certain that an adequate seal is made.
WARNING
The blower access panel must be securely in place when
the blower and burners are operating. Gas fumes, which
could contain carbon monoxide, can be drawn into living
space resulting in personal injury or death.
Page 9
Page 10
Front
Back
Figure 12
Downow Application
Allow for clearances to combustible materials as indicated
on the unit nameplate. Minimum clearances for closet or
alcove installations are shown in gure 13.
Downflow Application Installation Clearances
Top
Horizontal
CAUTION
If this unit is being installed in a space serviced by an
exhaust fan, power exhaust fan, or other device which
may create a negative pressure in the space, take care
when sizing the inlet air opening. The inlet air opening
must be sized to accommodate the maximum volume
of exhausted air as well as the maximum volume of
combustion air required for all gas appliances serviced
by this space.
Left Side
Bottom
Type of Vent
Connector
Top1 in. (25 mm)1 in. (25 mm)
*Front2-1/4 in. (57 mm)**2-1/4 in. (57 mm)
Back00
Sides0†0
Vent6 in. (152 mm)1 in. (25 mm)
FloorNC††NC††
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
** 4-1/2 in. if a single wall vent pipe is used.
inets, or 2 in. if a single wall vent is used on 17 - 1/2 in. cabinets.
††The furnace may be installed on a combustible wood floor if an
optional additive base is installed between the furnace and the
combustible floor.
Type CType B1
Right Side
FIGURE 13
WARNING
Improper installation of the furnace can result in personal
injury or death. Combustion and ue products must
never be allowed to enter the return air system or the
living space. Use screws and joint tape to seal the return
air system to the furnace.
In platform installations with bottom return air, the furnace
should be sealed airtight to the return air plenum. A door
must never be used as a portion of the return air duct
system. The base must provide a stable support and an
airtight seal to the furnace. Allow absolutely no sagging,
cracks, gaps, etc.
The return and supply air duct systems must never be
connected to or from other heating devices such as a
replace or stove, etc. Fire, explosion, carbon monoxide
poisoning, personal injury and/or property damage could
result.
Filters
This unit is not equipped with a lter or rack. A eld-provided high-velocity lter is required for the unit to operate
properly. Table 3 lists recommended lter sizes.
A lter must be in place any time the unit is operating.
Page 10
Page 11
TABLE 3
V
Cabinet Width inchesAir Filter Size inches
A - 14-1/214 x 25 x 1
B - 17-1/216 x 25 x 1
C - 2120 x 25 x 1
Duct System
Use industry-approved standards (such as those published by Air Conditioning Contractors of America or American Society of Heating, Refrigerating and Air Conditioning Engineers) to size and install the supply and return
air duct system. This will result in a quiet and low-static
system that has uniform air distribution.
NOTE - Do not operate the furnace in the heating mode
with an external static pressure that exceeds 0.5 inches
w.c. Higher external static pressures may cause erratic
limit operation.
Ensure that you have made a seal between the supply air
plenum and the furnace and between the furnace and the
return air plenum.
Return Air Plenum
Return air must not be drawn from a room where this
furnace, or any other gas-fueled appliance (i.e., water
heater), or carbon monoxide-producing device (i.e.,
wood replace) is installed. When return air is drawn
from a room, a negative pressure is created in the room. If
a gas appliance is operating in a room with negative pres-
sure, the ue products can be pulled back down the vent
pipe and into the room. This reverse ow of the ue gas
may result in incomplete combustion and the formation of
carbon monoxide gas. This toxic gas might then be distributed throughout the house by the furnace duct system
.
Venting
A 4-inch diameter ue transition is factory-installed on all
models. Modifying or removing the ue transition will
cause the unit to operate unsafely and will void the
unit certication. The vent connector does not require
insulation.
The ML180DF series units are classied as fan-assisted
Category I furnaces when vertically vented according to
the latest edition of National Fuel Gas Code (NFPA 54
/ ANSI Z223.1). A fan-assisted Category I furnace is an
appliance equipped with an integral mechanical means
to either draw or force combustion products through the
combustion chamber and/or heat exchanger.
NOTE - Use these instructions as a guide. They do not
supersede local codes. This furnace must be vented according to all local codes, these installation instructions,
and the provided venting tables in these instructions.
The venting tables in this manual were extracted from the
National Fuel Gas Code (NFPA 54 / ANSI Z223.1) and are
provided as a guide for proper vent installation. Proper
application, termination, construction and location of vents
must conform to local codes having jurisdiction. In the ab-
sence of local codes, the NFGC serves as the dening
document.
Refer to the tables and the venting information contained
in these instructions to properly size and install the venting
system.
IMPORTANT
Once the venting system is installed, attach the
“Disconnected Vent” warning sticker to a visible area
of the plenum near the vent pipe. The warning sticker
is provided in the bag assembly. Order kit 66W04 for
additional stickers.
WARNING
Asphyxiation hazard. The exhaust vent for this furnace
must be securely connected to the furnace ue transition
at all times.
ENT CONNECTION
VENT PIPE
(min. 6” length)
FLUE TRANSITION
COLLAR
FIGURE 14
Use self-drilling sheet metal screws or a mechanical fas-
tener to rmly secure the vent pipe to the round collar of
the ue transition. If self-drilling screws are used to attach
the vent pipe, it is recommended that three be used. Drive
one self-drilling screw through the front and one through
each side of the vent pipe and collar. See gure 14.
Install the rst vent connector elbow at a minimum of six
inches (152 mm) from the furnace vent outlet. Masonry
chimneys used to vent Category I central furnaces must
be either tile-lined or lined with a listed metal lining system or dedicated gas vent. Unlined masonry chimneys are
prohibited. See gures 15 and 16 for common venting.
“DISCONNECTED VENT”
WARNING
STICKER
Page 11
Page 12
Common Venting Using Tile-Lined Interior Masonry Chimney and Combined Vent Connector
Common Venting Using Metal-Lined Masonry Chimney
MINIMUM LENGTH = AS SHORT AS PRACTICAL.
FOR MAXIMUM LENGTH SEE NOTE TO LEFT
NOTE- Refer to provided venting tables
for installations.
OTHER
APPLIANCE
Venting Using a Masonry Chimney
The following additional requirements apply when a lined
masonry chimney is used to vent this furnace.
A chimney with one or more sides exposed to the outside
of the structure is considered to be an exterior chimney.
An exterior masonry chimney that is not tile-lined must be
lined with B1 vent or a listed insulated exible metal vent.
An exterior tile-lined chimney that is sealed and capped
may be lined with a listed uninsulated exible metal vent.
If the existing chimney will not accommodate a listed metal liner, either the chimney must be rebuilt to accommodate one of these liners or an alternate approved venting
method must be found.
Insulation for the exible vent pipe must be an encapsulated berglass sleeve recommended by the exible vent
pipe manufacturer. See gure 16.
SEALED
MAX. LENGTH
-- SEE NOTE 1
5 ft. (1.5 m)
minimum
VENT CONNECTOR
4 in. (102 mm)
minimum
OTHER
APPLIANCE
NOTE 1 - Refer to the provided venting tables for installations. Refer
to the capacity requirements shown in the provided venting tables.
BELOW.
MIN. LENGTH -- AS
SHORT AS PRACTICAL
FURNACE
AIR FLOW
CHIMNEY WITH
PERMANENTLY
SEALED FIREPLACE
OPENING
FIGURE 16
AIR FLOW
EXTERIOR
METAL
LINER
VENT
CONNECTOR
FURNACE
Figure 15
DO NOT insulate the space between the liner and
the chimney wall with puffed mica or any other loose
granular insulating material
SINGLE appliance venting of a fan-assisted furnace into
a tile-lined masonry chimney (interior or outside wall)
is PROHIBITED. The chimney must rst be lined with
either type B1 vent or an insulated single wall exible
vent lining system which has been sized according to the
provided venting tables and the vent pipe manufacturer’s
instructions.
A fan-assisted furnace may be commonly vented into an
existing lined masonry chimney if the following conditions
are met:
If type B1 double-wall vent is used inside a chimney, no
other appliance can be vented into the chimney. The out-
er wall of type B1 vent pipe must not be exposed to ue
products.
A type B1 vent or masonry chimney liner shall terminate
above the roof surface with a listed cap or a listed roof assembly according to the terms of their respective listings
and the vent manufacturer’s instructions.
When inspection reveals that an existing chimney is not
safe for the intended purpose, it shall be rebuilt to conform
to nationally recognized standards, lined or relined with
suitable materials, or replaced with a gas vent or chimney
suitable for venting ML180DF series units. The chimney
passageway must be checked periodically to ensure that
it is clear and free of obstructions.
Do not install a manual damper, barometric draft regulator,
or ue restrictor between the furnace and the chimney.
INTERIOR TILE-LINED
MASONRY CHIMNEY
NOTE - the chimney must be properly
sized per provided venting tables or
lined with listed metal lining system.
PERMANENTLY
SEALED FIREPLACE
OPENING
IMPORTANT
• The chimney is currently serving at least one drafthood equipped appliance
• The vent connectors and chimney are sized according to the provided venting tables.
Page 12
Page 13
Never connect a Category I appliance to a chimney that is
servicing a solid-fuel appliance. If a replace chimney ue
is used to vent this appliance, the replace opening must
be permanently sealed.
A type B or listed chimney lining system that passes
through an unused masonry chimney ue is not considered to be exposed to the outdoors.
General Venting Requirements
Vent all ML180DF furnaces according to these instructions:
1 - Vent diameter recommendations and maximum
allowable piping runs are found in the provided
venting tables.
2 - In no case should the vent or vent connector
diameter be less than the diameter specied in the
provided venting tables.
3 - The minimum vent capacity determined by the
sizing tables must be less than the low re input
rating and the maximum vent capacity must be
greater than the high re input rating.
4 - Single appliance vents - If the vertical vent or tile-
lined chimney has a larger diameter or ow area than
the vent connector, use the vertical vent diameter to
determine the minimum vent capacity and the vent
connector diameter to determine the maximum vent
capacity. The ow area of the vertical vent, however,
shall not exceed 7 times the ow area of the listed
appliance categorized vent area, drafthood outlet
area or ue collar area unless designed according
to approved engineering methods.
5 - Multiple appliance vents - The ow area of the
largest section of vertical vent or chimney shall
not exceed 7 times the smallest listed appliance
categorized vent area, drafthood outlet area or ue
collar area unless designed according to approved
engineering methods.
6 - The entire length of single wall metal vent connector
shall be readily accessible for inspection, cleaning,
and replacement.
7 - Single appliance venting congurations with zero
lateral lengths (table 5) are assumed to have
no elbows in the vent system. For all other vent
congurations, the vent system is assumed to have
two 90° elbows. For each additional 90° elbow or
equivalent (for example two 45° elbows equal one
90° elbow) beyond two, the maximum capacity
listed in the venting table should be reduced by
10% (0.90 x maximum listed capacity).
8 - The common venting tables (6 and 7) were
generated using a maximum horizontal vent
connector length of 1-1/2 feet (.46 m) for each inch
(25 mm) of connector diameter as follows:
NOTE - Single Wall Vent Connectors may be used if the
requirements set forth by the National Fuel Gas Code
are met. Please consult latest edition of NFPA 54/ANSI
Z223.1 for proper sizing and application.
TABLE 4
Connector Diameter
inches (mm)
Maximum Horizontal
Connector Length feet (m)
3 (76)4-1/2 (1.37)
4 (102)6 (1.83)
5 (152)7-1/2 (2.29)
6 (152)9 (2.74)
7 (178)
10-1/2 (3.20)
9 - If the common vertical vent is offset, the maximum
common vent capacity listed in the common venting
tables should be reduced by 20%, the equivalent
of two 90° elbows (0.80 x maximum common vent
capacity). The horizontal length of the offset shall
not exceed 1-1/2 feet (.46 m) for each inch (25 mm)
of common vent diameter.
10 - The vent pipe should be as short as possible with
the least number of elbows and angles required to
complete the job. Route the vent connector to the
vent using the shortest possible route.
11 - A vent connector shall be supported without any
dips or sags and shall slope a minimum of 1/4 inch
(6.4 mm) per linear foot (305 mm) of connector,
back toward the appliance.
12 - Vent connectors shall be rmly attached to the
furnace ue collar by self-drilling screws or other
approved means, except vent connectors of listed
type B vent material which shall be assembled
according to the manufacturer’s instructions. Joints
between sections of single wall connector piping
shall be fastened by screws or other approved
means.
13 - When the vent connector used for Category I
appliances must be located in or pass through a
crawlspace or other areas which may be cold, that
portion of the vent connector shall be constructed
of listed double-wall type B vent material or material
having equivalent insulation qualities.
14 - All venting pipe passing through oors, walls, and
ceilings must be installed with the listed clearance
to combustible materials and be re stopped
according to local codes. In absence of local codes,
refer to NFGC (Z223.1).
15 - No portion of the venting system can extend into,
or pass through any circulation air duct or plenum.
16 - Vent connectors serving Category I appliances shall
not be connected to any portion of mechanical draft
systems operating under positive pressure such as
Category III or IV venting systems.
17 - If vent connectors are combined prior to entering
the common vent, the maximum common vent
capacity listed in the common venting tables must
be reduced by 10%, the equivalent of one 90° elbow
(0.90 x maximum common vent capacity).
18 - The common vent diameter must always be at least
as large as the largest vent connector diameter.
Page 13
Page 14
19 - In no case, shall the vent connector be sized more
than two consecutive table size diameters over the
size of the draft hood outlet or ue collar outlet.
20 - Do not install a manual damper, barometric draft
regulator or ue restrictor between the furnace and
the chimney.
21 - When connecting this appliance to an existing
dedicated or common venting system, you must
inspect the venting system’s general condition
and look for signs of corrosion. The existing vent
pipe size must conform to these instructions and
the provided venting tables. If the existing venting
system does not meet these requirements, it must
be resized.
TABLE 5
Capacity of Type B Double-Wall Vents with Type B Double-Wall Connectors
Serving a Single Category I Appliance
Height
H
(feet)
6
8
10
15
20
30
NOTE - Single appliance venting congurations with zero lateral lengths are assumed to have no elbows in the vent system. For
all other vent congurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for
example two 45° elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by
10 percent (0.90 x maximum listed capacity).
Appliance Input Rating in Thousands of Btu Per Hour
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a
venting system commonly run with separate gas appliances, the venting system is likely to be too large to properly
vent the remaining attached appliances.
Conduct the following test while each appliance is operating and the other appliances (which are not operating)
remain connected to the common venting system. If the
venting system has been installed improperly, you must
correct the system as indicated in the general venting re-
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being placed
into operation could result in carbon monoxide poisoning
or death. The following steps shall be followed for each
appliance connected to the venting system being placed
into operation, while all other appliances connected to
the venting system are not in operation:
WARNING
quirements section.
Page 15
Page 16
1 - Seal any unused openings in the common venting
system.
2 - Inspect the venting system for proper size and
horizontal pitch. Determine that there is no blockage,
restriction, leakage, corrosion, or other deciencies
which could cause an unsafe condition.
3 - Close all building doors and windows and all
doors between the space in which the appliances
remaining connected to the common venting system
are located and other spaces of the building. Turn on
clothes dryers and any appliances not connected to
the common venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts,
so they will operate at maximum speed. Do not
operate a summer exhaust fan. Close replace
dampers.
4 - Follow the lighting instructions. Turn on the appliance
that is being inspected. Adjust the thermostat so
that the appliance operates continuously.
5 - After the main burner has operated for 5 minutes,
test for leaks of ue gases at the draft hood relief
opening. Use the ame of a match or candle, or
smoke from a cigarette, cigar, or pipe.
6 - After determining that each appliance connected
to the common venting system is venting properly,
(step 3) return all doors, widows, exhaust fans,
replace dampers, and any other gas-burning
appliances to their previous mode of operation.
7 - If a venting problem is found during any of the
preceding tests, the common venting system must
be modied to correct the problem.
Resize the common venting system to the minimum vent
pipe size determined by using the appropriate tables in
Appendix G. (These are in the current standards of the
National Fuel Gas Code ANSI Z223.1.
Gas Piping
Gas supply piping should not allow more than 0.5”W.C.
drop in pressure between gas meter and unit. Supply gas
pipe must not be smaller than unit gas connection.
CAUTION
If a exible gas connector is required or allowed by the
authority that has jurisdiction, black iron pipe shall be
installed at the gas valve and extend outside the furnace
cabinet. The exible connector can then be added
between the black iron pipe and the gas supply line.
Gas Supply
1 - This unit is shipped standard for left or right side
installation of gas piping (or top entry in horizontal
applications). Connect the gas supply piping into the
gas valve. The maximum torque is 800 in lbs and
minimum torque is 350 in lbs when when attaching
the gas piping to the gas valve.
WARNING
Do not over torque (800 in-lbs) or under torque (350 inlbs) when attaching the gas piping to the gas valve.
2 - When connecting the gas supply piping, consider
factors such as length of run, number of ttings, and
furnace rating to avoid excessive pressure drop.
Table 8 lists recommended pipe sizes for typical
applications.
3 - The gas piping must not run in or through air ducts,
clothes chutes, gas vents or chimneys, dumb
waiters, or elevator shafts.
4 - The piping should be sloped 1/4 inch (6.4 mm) per
15 feet (4.57 m) upward toward the meter from the
furnace. The piping must be supported at proper
intervals [every 8 to 10 feet (2.44 to 3.01 m)] with
suitable hangers or straps. Install a drip leg inside
vertical pipe runs to the unit.
5 - A 1/8” N.P.T. plugged tap or pressure post is located
on the gas valve to facilitate test gauge connection.
See gure 22.
6 - In some localities, codes may require the installation
of a manual main shut-off valve and union (furnished
by the installer) external to the unit. The union must
be of the ground joint type.
CAUTION
Compounds used on threaded joints of gas piping must
be resistant to the actions of liquied petroleum gases.
NOTE - If emergency shutoff is necessary, shut off the
main manual gas valve and disconnect main power to the
furnace. The installer should properly label these devices
Page 16
Page 17
TABLE 8
Gas Pipe Capacity - ft3/hr (m3/hr)
Nominal
Iron Pipe
Size Inches
(mm)
1/2
(12.7)
3/4
(19.05)
1
(25.4)
1-1/4
(31.75)
1-1/2
(38.1)
2
(50.8)
2-1/2
(63.5)
3
(76.2)
Internal
Diameter
inches
(mm)
.622
(17.799)
.824
(20.930)
1.049
(26.645)
1.380
(35.052)
1.610
(40.894)
2.067
(52.502)
2.469
(67.713)
3.068
(77.927)
10
(3.048)
172
(4.87)
360
(10.19)
678
(19.19)
1350
(38.22)
2090
(59.18)
4020
(113.83)
6400
(181.22)
11300
(319.98)
20
(6.096)
118
(3.34)
247
(7.000)
466
(13.19)
957
(27.09)
1430
(40.49)
2760
(78.15)
4400
(124.59)
7780
(220.30)
30
(9,144)
95
(2.69)
199
(5.63)
374
(10.59)
768
(22.25)
1150
(32.56)
2220
(62.86)
3530
(99.95)
6250
(176.98)
40
(12,192)
81
(2.29)
170
(4.81)
320
(9.06)
657
(18.60)
985
(27.89)
1900
(53.80)
3020
(85.51)
5350
(151.49)
Length of Pipe - feet (m)
50
(15.240)
72
(2.03)
151
(4.23)
284
(8.04)
583
(16.50)
873
(24.72)
1680
(47.57)
2680
(75.88)
4740
(134.22)
60
(18.288)
65
(1.84)
137
(3.87)
257
(7.27)
528
(14.95)
791
(22.39)
1520
(43.04)
2480
(70.22)
4290
(121.47)
70
(21.336)
60
(1.69)
126
(3.56)
237
(6.71)
486
(13.76)
728
(20.61)
1400
(39.64)
2230
(63.14)
3950
(111.85)
(24.384)
(1.58)
(3.31)
(6.23)
(12.79)
(19.17)
1300
(36.81)
2080
(58.89)
3670
(103.92)
NOTE - Capacity given in cubic feet (m3 ) of gas per hour and based on 0.60 specic gravity gas.
.
80
56
117
220
452
677
90
(27.432)
52
(1.47)
110
(3.11)
207
(5.86)
424
(12.00)
635
(17.98)
1220
(34.55)
1950
(55.22)
3450
(97.69)
100
(30,480)
50
(1.42)
104
(2.94)
195
(5.52)
400
(11.33)
600
(17.00)
1160
(32.844)
1840
(52.10)
3260
(92.31)
MANUAL
MAIN SHUT-OFF
VALV E
GROUND
JOINT
UNION
Left Side Piping
(Standard)
DRIP LEG
AUTOMATIC
GAS VALV E
AUTOMATIC
GAS VALV E
(with manual
shut-off valve)
FIELD
PROVIDED
AND INSTALLED
NOTE - BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET
(with manual
shut-off valve)
Figure 17
MANUAL
MAIN SHUT-OFF
VALV E
GROUND
JOINT
UNION
DRIP LEG
Right Side Piping
(Alternate)
Page 17
Page 18
Leak Check
INTERIOR MAKE-UP BOX INSTALLATION
Cut the two wire ties to extend power wires for right side onl
y
After gas piping is completed, carefully check all piping
connections (factory- and eld-installed) for gas leaks.
Use a leak detecting solution or other preferred means.
NOTE - If emergency shutoff is necessary, shut off the
main manual gas valve and disconnect the main power
to the furnace. The installer should properly label these
devices.
CAUTION
Some soaps used for leak detection are corrosive to
certain metals. Carefully rinse piping thoroughly after
leak test has been completed. Do not use matches,
candles, ame or other sources of ignition to check for
gas leaks.
The furnace must be isolated from the gas supply system
by closing its individual manual shut-off valve during any
pressure testing of the gas supply system at pressures
greater than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.)
.
IMPORTANT
When testing pressure of gas lines, gas valve must be
disconnected and isolated. See gure 18. Gas valves
can be damaged if subjected to pressures greater than
1/2 psig (3.48 kPa, 14 inches w.c.).
MANUAL MAIN
SHUT-OFF VALV E
WILL NOT HOLD
NORMAL TEST
PRESSURE
1/8 NPT PLUG
CAP
FIGURE 18
Electrical
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
ISOLATE
GAS VALV E
FURNACE
CAUTION
Electrostatic discharge can affect electronic
components. Take precautions to neutralize
electrostatic charge by touching your hand
and tools to metal prior to handling the
control.
The unit is equipped with a eld make-up box on the left
hand side of the cabinet. The make-up box may be moved
to the right side of the furnace to facilitate installation. If
the make-up box is moved to the right side, clip the wire
ties that bundle the wires together. The excess wire must
be pulled into the blower compartment. Secure the excess
wire to the existing harness to protect it from damage.
(Right Side)
MAKE-UP
BOX
FIGURE 19
Refer to gure 20 for schematic wiring diagram and troubleshooting.
The power supply wiring must meet Class I restrictions.
Protected by either a fuse or circuit breaker, select circuit
protection and wire size according to unit nameplate.
CAUTION
Failure to use properly sized wiring and circuit breaker
may result in property damage. Size wiring and circuit
breaker(s) per Product Specications bulletin (EHB) and
unit rating plate.
NOTE - Unit nameplate states maximum current draw.
Maximum over-current protection allowed is 15 AMP.
Holes are on both sides of the furnace cabinet to facilitate
wiring.
Install a separate (properly sized) disconnect switch near
the furnace so that power can be turned off for servicing.
Before connecting the thermostat, check to make sure
the wires will be long enough for servicing at a later date.
Make sure that thermostat wire is long enough to facilitate
future removal of blower for service.
WARNING
Fire Hazard. Use of aluminum wire with this product may
result in a re, causing property damage, severe injury
or death. Use copper wire only with this product.
Page 18
Page 19
Complete the wiring connections to the equipment. Use
the provided unit wiring diagram. Use 18-gauge wire or
larger that is suitable for Class II rating for thermostat connections.
Electrically ground the unit according to local codes or, in
the absence of local codes, according to the current National Electric Code (ANSI/NFPA No. 70). A green ground
wire is provided in the eld make-up box.
NOTE - The ML180DF furnace contains electronic components that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.
WARNING
Electric Shock Hazard. Can cause injury or
death. Unit must be properly grounded in
accordance with national and local codes.
Accessory Terminals
One line voltage “EAC” 1/4” spade terminal is provided on
the furnace integrated control. See gure 21 for integrated
control conguration. This terminal is energized when the
indoor blower is operating. Any accessory rated up to one
amp can be connected to this terminal with the neutral leg
of the circuit being connected to one of the provided neutral terminals. If an accessory rated at greater than one
amp is connected to this terminal, it is necessary to use
an external relay.
One line voltage “HUM” 1/4” spade terminal is provided
on the furnace integrated control. See gure 21 for integrated control conguration. This terminal is energized in
the heating mode when the combustion air inducer is operating.
Any humidier rated up to one amp can be connected to
this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. If a hu-
midier rated at greater than one amp is connected to this
terminal, it is necessary to use an external relay relay.
Generator Use - Voltage Requirements
The following requirements must be kept in mind when
specifying a generator for use with this equipment:
• The furnace requires 120 volts + 10% (Range: 108
volts to 132 volts).
• The furnace operates at 60 Hz + 5% (Range: 57 Hz
to 63 Hz).
• The furnace integrated control requires both polarity and proper ground. Both polarity and proper
grounding should be checked before attempting to
operate the furnace on either permanent or temporary power.
• Generator should have a wave form distortion of
less than 5% THD (total harmonic distortion).
Thermostat
Install the room thermostat according to the instructions
provided with the thermostat. See gure 20 for thermostat
designations. If the furnace is being matched with a heat
pump, refer to the FM21 installation instruction or appropriate dual fuel thermostat instructions.
Indoor Blower Speeds
1 - When the thermostat is set to “FAN ON,” the indoor
blower will run continuously on the heating speed
when there is no cooling or heating demand.
2 - When the ML180DF is running in the heating mode,
the indoor blower will run on the heating speed.
3 - When there is a cooling demand, the indoor blower
will run on the cooling speed.
Page 19
Page 20
ML180DF Schematic Wiring Diagram
Figure 20
Page 20
Page 21
Integrated Control
LED
TWIN
PUSH BUTTON
INTEGRATED CONTROL
(Automatic Hot Surface Ignition System)
TERMINAL DESIGNATIONS
HUM
LINE
XFMR
EAC
COOL
HEAT
PARK
CONT
NEUTRALS
Humidifier (120VAC)
Input (120VAC)
Transformer (120VAC)
Indoor Air Qality Accessory Air Cleaner (120VAC)
Blower - Cooling Speed (120VAC)
Blower - Heating Speed (120VAC)
Dead terminals to park alternate spd taps
Continuous blower
Neutral terminals (120VAC)
BLOWER OFF
DELAY JUMPER
Integrated Control Diagnostic Codes
LED StatusDescription
LED Off
LED OffNormal operation.
1 Flash
2 Flashes
3 Flashes
4 FlashesPrimary limit switch open.
5 FlashesRollout switch open.
6 FlashesPressure switch cycle lockout.
7 FlashesLockout, burners fail to light.
8 Flashes
9 FlashesLine voltage polarity incorrect.
No power to control or control
harware fault detected.
Flame present with gas vavle
de-energized.
Pressure switch closed with
combustion air inducer de-energized.
Pressure switch open with
combustion air inducer energized.
Lockout, buners lost ame too
many times.
Figure 21
Note - This control is equipped with a push button switch
for diagnostic code recall. The control stores the last 5
fault codes in non-volatile memory. The most recent fault
code is ashed rst, the oldest fault code is ashed last.
There is a 2 second pause between codes. When the
push button switch is pressed for less than 5 seconds, the
control will ash the stored fault codes when the switch is
released. The fault code history may be cleared by pressing the push button switch for more than 5 seconds.
Page 21
Page 22
Unit Start-Up
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING
Electric shock hazard. Can cause injury
or death. Do not use this unit if any part
has been under water. Immediately call a
qualied service technician to inspect the
unit and to replace any part of the control
system and any gas control which has been
under water.
7 - Wait ve minutes to clear out any gas. If you then
smell gas, STOP! Immediately call your gas supplier
from a neighbor’s phone. Follow the gas supplier’s
instructions. If you do not smell gas go to next step.
8 - Move switch on gas valve to ON. Do not force. See
gure 22.
MANIFOLD
PRESSURE
ADJUSTMENT
SCREW
MANIFOLD
PRESSURE
OUTLET
PORT
WARNING
If overheating occurs or if gas supply fails to shut off,
shut off the manual gas valve to the appliance before
shutting off electrical supply.
CAUTION
Before attempting to perform any service or maintenance,
turn the electrical power to unit OFF at disconnect switch.
BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the oor because some
gas is heavier than air and will settle on the oor.
The gas valve on the ML180DF unit is equipped with a
gas control switch. Use only your hand to move the switch.
Never use tools. If the switch will not turn or if the control
switch will not move by hand, do not try to repair it.
Placing the furnace into operation:
ML180DF units are equipped with an automatic ignition
system. Do not attempt to manually light burners on these
furnaces. Each time the thermostat calls for heat, the
burners will automatically light. The ignitor does not get
hot when there is no call for heat on units with an automatic ignition system.
WARNING
Danger of explosion and re. Can cause
injury or product or property damage. You
must follow these instructions exactly.
Gas Valve Operation (Figure 22)
1 - STOP! Read the safety information at the beginning
of this section.
2 - Set the thermostat to the lowest setting.
3 - Turn off all electrical power to the unit.
4 - This furnace is equipped with an ignition device
which automatically lights the burners. Do not try to
light the burners by hand.
5 - Remove the access panel.
6 - Move switch on gas valve to OFF. Do not force. See
gure 22.
INLET
PRESSURE
PORT
9 - Replace the access panel.
10 - Turn on all electrical power to to the unit.
11 - Set the thermostat to desired setting.
NOTE - When unit is initially started, steps 1 through
11 may need to be repeated to purge air from gas
line.
12 - If the appliance will not operate, follow the
instructions “Turning Off Gas to Unit” and call your
service technician or gas supplier.
Turning Off Gas to Unit
1 - Set the thermostat to the lowest setting.
2 - Turn off all electrical power to the unit if service is to
be performed.
3 - Remove the access panel.
4 - Move switch on gas valve to OFF. Do not force.
5 - Replace the upper access panel.
Failure To Operate
If the unit fails to operate, check the following:
1 - Is the thermostat calling for heat?
2 - Are access panels securely in place?
3 - Is the main disconnect switch closed?
4 - Is there a blown fuse or tripped circuit breaker?
5 - Is the lter dirty or plugged? Dirty or plugged lters
will cause the limit control to shut the unit off.
6 - Is gas turned on at the meter?
7 - Is the manual main shut-off valve open?
8 - Is the internal manual shut-off valve open?
9 - Is the unit ignition system in lock out? If the unit locks
out again, call the service technician to inspect the
unit for blockages.
10 - Is pressure switch closed? Obstructed ue will
cause unit to shut off at pressure switch. Check ue
and outlet for blockages.
GAS VALVE SHOWN IN ON POSITION
FIGURE 22
Page 22
Page 23
11 - Are ame rollout switches tripped? If ame rollout
switches are tripped, call the service technician for
inspection.
Heating Sequence Of Operation
1 - When thermostat calls for heat, combustion air
blower starts.
2 - Combustion air pressure switch proves blower
operation. Switch is factory-set and requires no
adjustment.
3 - After a 15-second prepurge, the hot surface ignitor
energizes.
4 - After a 20-second ignitor warm-up period, the gas
valve solenoid opens. A 4-second trial for ignition
period begins.
5 - Gas is ignited, ame sensor proves the ame, and
the combustion process continues.
6 - If ame is not detected after rst ignition trial,
the ignition control will repeat steps 3 and 4 four
more times before locking out the gas valve
(”WATCHGUARD” ame failure mode).The ignition
control will then automatically repeat steps 1
through 6 after a 60 minute.
7 - To interrupt the 60-minute (“WATCHGUARD”)
period, move thermostat from “Heat” to “OFF” then
back to “Heat.” Heating sequence then restarts at
step 1.
Gas Pressure Adjustment
Gas Flow (Approximate)
TABLE 9
GAS METER CLOCKING CHART
Seconds for One Revolution
ML180
Unit
-04580160200400
-07055110136272
-0904182102204
-110336682164
-135275468136
Natural-1000 btu/cu ft LP-2500 btu/cu ft
NaturalLP
1 cu ft
Dial
2 cu ft
Dial
1 cu ft
Dial
2 cu ft
Dial
Furnace should operate at least 5 minutes before checking gas ow. Determine time in seconds for two revolutions of gas through the meter. (Two revolutions assures a
more accurate time.) Divide by two and compare to time in
table 9 below. If manifold pressure matches table 11 and
rate is incorrect, check gas orices for proper size and
restriction. Remove temporary gas meter if installed.
NOTE - To obtain accurate reading, shut off all other gas
appliances connected to meter.
Supply Pressure Measurement
A threaded plug on the inlet side of the gas valve provides
access to the supply pressure tap. Remove the threaded
plug, install a eld-provided barbed tting and connect a
manometer to measure supply pressure. Furnace should
operate at least 5 minutes before checking supply pressure. See table 11 for proper supply pressure. Replace
the threaded plug after measurements have been taken
Manifold Pressure Measurement
1 - Remove the threaded plug from the outlet side of
the gas valve and install a eld-provided barbed
tting. Connect to a manometer to measure manifold
pressure.
2 - Start unit and allow 5 minutes for unit to reach
steady state.
3 - While waiting for the unit to stabilize, observe the
ame. Flame should be stable and should not lift
from burner. Natural gas should burn blue.
4 - After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in
table 11.
5 - Shut unit off and remove manometer as soon as an
accurate reading has been obtained. Take care to
replace pressure tap plug.
6 - Start unit and perform leak check. Seal leaks if
found.
Proper Combustion
Furnace should operate a minimum 15 minutes with cor-
rect manifold pressure and gas ow rate before checking
combustion. Take combustion sample beyond the ue out-
let and compare to the tables below. The maximum carbon monoxide reading should not exceed 100 ppm.
TABLE 10
ML180UH UnitCO2% For NatCO2% For L.P.
-045
-070
-090
-110
6.0 - 7.56.9 - 8.5
High Altitude
The manifold pressure may require adjustment and combustion air pressure switch may need replacing to ensure
proper combustion at higher altitudes. Refer to table 11
for manifold pressure and table 12 for pressure switch
change and gas conversion kits.
IMPORTANT
For safety, shut unit off and remove manometer as soon
as an accurate reading has been obtained. Take care to
replace pressure tap plug.
Page 23
Page 24
TABLE 11
Manifold Pressure Settings at all Altitudes
Model
Input Size
045
070
090
110
Gas0 - 4500 ft.4501 - 7500 ft .7501 - 10,000 ft.
Nat3.53.53.54.513.0
LP/Propane10.010.010.011.013.0
Nat3.53.33.54.513.0
LP/Propane10.010.010.011.013.0
Nat3.53.33.54.513.0
LP/Propane10.010.010.011.013.0
Nat3.53.33.54.513.0
LP/Propane10.010.010.011.013.0
Line Pressure in. wg.
MinMax
TABLE 12
Pressure Switch and Gas Conversion Kits at all Altitudes
High Altitude Pressure Switch KitNatuarl Gas Orice KitLP/Propane Orice Kit
No Change
No Change
80W52
80W5173W8173W3711K4911K44
NOTE - A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.
Other Unit Adjustments
NOTE - Do not secure the electrical conduit directly to the
air ducts or structure.
Primary and Secondary Limits
The primary limit is located on the heating compartment
vestibule panel. The secondary limits (if equipped) are located in the blower compartment, attached to the back
side of the blower. These auto reset limits are factory-set
and require no adjustment.
Flame Rollout Switch
The manually reset switch is located on the front of the
burner box.
Pressure Switch
The pressure switch is located in the heating compartment
adjacent to the combustion air inducer. The switch checks
for proper combustion air inducer operation before allowing ignition trial. The switch is factory-set and requires no
adjustment.
Temperature Rise
After the furnace has been started, and supply and return
air temperatures have been allowed to stabilize, check the
temperature rise. If necessary, adjust the blower speed
to maintain the temperature rise within the range shown
on the unit nameplate. Increase the blower speed to decrease the temperature. Decrease the blower speed to
increase the temperature rise. Failure to adjust the temperature rise may cause erratic limit operation.
Fan Control
The heat fan-on time of 30 seconds is not adjustable. The
heat fan-off delay (amount of time that the blower oper-
ates after the heat demand has been satised) may be
adjusted by changing the jumper position across the ve
pins on the integrated control. The unit is shipped with a
factory fan-off delay setting of 120 seconds. The fan-off
delay affects comfort and is adjustable to satisfy individual
applications. Adjust the fan-off delay to achieve a supply
air temperature between 90° and 110°F at the moment
that the blower is de-energized. Longer off delay settings
provide lower return air temperatures; shorter settings
provide higher return air temperatures. See gure 23.
Page 24
Page 25
HEAT FAN‐OFF TIME IN SECONDS
NO JUMPER
To adjust fan-off timing, reposition jumper across pins to
60 Second
off Time
60
90
120
180
achieve desired setting.
90 Second
off Time
60
90
120
180
120 Second
off Time
60
90
120
180
180 Second
off Time
60
90
120
180
FIGURE 23
Blower Speeds
Follow the steps below to change the blower speeds.
1 - Turn off electrical power to furnace.
2 - Remove blower access panel.
3 - Disconnect existing speed tap at integrated control
speed terminal.
See unit Product Specications Manual for indoor blower
data.
NOTE - Termination of any unused motor leads must be
insulated.
4 - Place unused blower speed tap on integrated
control “PARK” terminal or insulate.
5 - Refer to blower speed selection chart on unit wiring
diagram for desired heating or cooling speed. See
Blower performance data beginning on the next
page.
6 - Connect selected speed tap at integrated control
speed terminal.
7 - Resecure blower access panel.
8 - Turn on electrical power to furnace.
9 - Recheck temperature rise.
Twinning 2 ML180DF Furnaces
The control board in this furnace is equipped with a provision to ”twin” (interconnect) two(2) adjacent furnaces with
a common plenum such that they operate as one (1) large
unit.
When twinned, the circulating blower speeds are synchronized between the furnaces. If either furnace has a need
to run the blower, both furnaces will run the blower on the
same speed. The cooling speed has highest priority, followed by heating speed and fan speed.
Field installation of twinning consists of connecting wires
between the ”C” and ”Twin” terminals of the two controls.
The 24 VAC secondary of the two systems must be in
phase. All thermostat connections are made to one control only. Figure 24 show wiring for two-stage and single
stage thermostats.
The twinned furnace without thermostat connections is
to have the call for heat supplied by an external 24VAC
isolation relay to prevent its rollout switch from being bypassed by the other twinned furnace. The coil of the isolation relay connects from the thermostat ”W” to 24 VAC
common. The contacts of the relay connect ”R” to ”W” on
the non-thermostat twin.
Page 25
Page 26
TWO-STAGE THERMOSTAT
TWIN
FIELD WIRING FOR TWINNING
SINGLE STAGE THERMOSTAT
TWIN
Call For Cool
Call For Fan
Call For 1st
Stage Heat
Call For 2nd
StageHeat
R
Y
G
W1
W2
ISOLATION
RELAY
TWIN
R
TWIN 1
Y
G
W
C
R
TWIN 2
Y
G
W
C
Call For Cool
Call For Fan
Call For Heat
R
Y
G
W
ISOLATION
RELAY
TWIN
R
TWIN 1
Y
G
W
C
R
TWIN 2
Y
G
W
C
FIGURE 24
Service
WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result in
dangerous operation, serious injury, death or property
damage.
Improper servicing could result in dangerous operation,
serious injury, death, or property damage.
Before servicing, disconnect all electrical power to
furnace.
When servicing controls, label all wires prior to
disconnecting. Take care to reconnect wires correctly.
Verify proper operation after servicing.
WARNING
The blower access panel must be securely in place when
the blower and burners are operating. Gas fumes, which
could contain carbon monoxide, can be drawn into living
space resulting in personal injury or death.
Annual Furnace Maintenance
At the beginning of each heating season, and to comply
with the Lennox Limited Warranty, your system should be
checked by a licensed professional technician (or equivalent) as follows:
1 - Check wiring for loose connections, voltage at
indoor unit and amperage of indoor motor.
2 - Check the condition of the belt and shaft bearings
if applicable.
3 - Inspect all gas pipe and connections for leaks.
4 - Check the cleanliness of lters and change if
necessary (monthly).
5 - Check the condition and cleanliness of burners and
heat exchanger and clean if necessary.
6 - Check the cleanliness of blower assembly and
clean the housing, blower wheel and blower motor
if necessary . The blower motors are prelubricated
for extended bearing life. No further lubrication is
needed.
7 - Inspect the combustion air inducer and clean if
necessary.
8 - Evaluate the heat exchanger integrity by inspecting
the heat exchanger per the AHRI heat exchanger
inspection procedure. This procedure can be
viewed at www.ahrinet.org.
Page 26
Page 27
9 - Ensure sufcient combustion air is available to the
furnace. Fresh air grilles and louvers (on the unit
and in the room where the furnace is installed)
must be properly sized, open and unobstructed to
provide combustion air.
10 - Inspect the furnace venting system to make sure
it is in place, structurally sound, and without holes,
corrosion, or blockage. Vent system must be free
and clear of obstructions and must slope upward
away from the furnace . Vent system should be
installed per the National Fuel Gas Code
11 - Inspect the furnace return air duct connection to
ensure the duct is sealed to the furnace. Check for
air leaks on supply and return ducts and seal where
necessary.
12 - Check the condition of the furnace cabinet insulation
and repair if necessary.
13 - Perform a complete combustion analysis during the
furnace inspection to ensure proper combustion
and operation. Consult Service Literature for proper
combustion values.
14 - Verify operation of CO detectors and replace
batteries as required.
Perform a general system test. Turn on the furnace to
check operating functions such as the start-up and shut-
off operation.
1 - Check the operation of the ignition system, inspect
and clean ame sensor. Check microamps before
and after. Check controls and safety devices (gas
valve, ame sensor, temperature limits). Consult
Service Manual for proper operating range. Thermal
Limits should be checked by restricting airow and
not disconnecting the indoor blower. For additional
details, please see Service and Application Note
H049.
2 - Verify that system total static pressure and airow
settings are within specic operating parameters.
3 - Clock gas meter to ensure that the unit is operating
at the specied ring rate. Check the supply
pressure and the manifold pressure. On two-stage
gas furnaces check the manifold pressure on high
re and low re. If manifold pressure adjustment is
necessary, consult the Service Literature for unit
specic information on adjusting gas pressure.
Not all gas valves are adjustable. Verify correct
temperature rise.
Cleaning the Burners
NOTE - Use papers or protective covering in front of the
furnace
during cleaning.
1 - Turn off both electrical and gas power supplies to
furnace.
2 - Label the wires from gas valve, rollout switches,
primary limit switch and make-up box then
disconnect them.
3 - Disconnect gas supply piping. Remove the four
screws securing the burner manifold assembly to
the vestibule panel and remove the assembly from
the unit.
4 - Remove 4 screws securing burner box and remove
burner box.
5 - To clean burners, run a vacuum cleaner with a soft
brush attachment over the face of burners. Visually
box cover.
7 - Reconnect all wires.
8 - Reconnect gas supply piping.
9 - Turn on power and gas supply to unit.
10 - Set thermostat and check for proper operation.
11 - Check all piping connections, factory and eld, for
gas leaks. Use a leak detecting solution or other
preferred means.
CAUTION
Some soaps used for leak detection are corrosive to
certain metals. Carefully rinse piping thoroughly after
leak test has been completed. Do not use matches,
candles, ame or other sources of ignition to check for
gas leaks.
12 - If a leak is detected, shut gas and electricity off and
repair leak.
13 - Repeat steps 12 and 13 until no leaks are detected.
14 - Replace access panel.
Page 27
Page 28
Ignitor
BURNER ASSEMBLY & REMOVAL
Burner Detail Front View
Rollout Switches
Sensor
Manifold And Gas Valve
Cross Over
Retention Rings
FIGURE 25
Repair Parts List
The following repair parts are available through independent Lennox dealers. When ordering parts, include the complete
furnace model number listed on the CSA International nameplate -- Example: ML180DF110P60C-01. All service must be
performed by a licensed professional installer (or equivalent), service agency, or gas supplier.
Cabinet Parts
Upper access panel
Blower panel
Top cap
Control Panel Parts
Transformer
Integrated control
Door interlock switch
Circuit breaker
Blower Parts
Blower wheel
Blower housing
Motor
Heating Parts
Flame sensor
Heat exchanger assembly
Gas manifold
Combustion air inducer
Gas valve
Main burner cluster
Main burner orices
Pressure switch
Ignitor
Primary limit control
Flame rollout switch (s)
Secondary limit
Motor mounting frame
Motor capacitor
Blower housing cutoff plate
Page 28
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.