Lennox ML180DF045P24A, ML180DF090P36B, ML180DF045P36A, ML180DF110P60C, ML180DF090P48B Installation Instructions Manual

...
Page 1
© 2017 Lennox Industries Inc.
DOWNFLOW
Dallas, Texas USA
INSTALLATION INSTRUCTIONS ML180DF
MERIT® SERIES GAS FURNACE DOWNFLOW AIRDISCHARGE
507326-02 11/2017 Supersedes 05/2016
THIS MANUAL MUST BE LEFT WITH THE
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in man­uals, be alert to the potential for personal injury or death
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
AIR FLOW
Contents
Unit Dimensions .............................................................2
ML180DF Gas Furnace .................................................. 3
Shipping and Packing List ..............................................3
Safety Information ..........................................................3
Use of Furnace as Construction Heater .........................4
General ........................................................................... 4
Combustion, Dilution & Ventilation Air ............................5
Setting Equipment .........................................................9
Filters ............................................................................ 10
Duct System ................................................................. 11
Venting..........................................................................11
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier.
Gas Piping .................................................................... 16
Electrical ....................................................................... 18
Integrated Control ......................................................... 21
Unit Start Up ................................................................. 22
Gas Pressure Adjustment ............................................. 23
Proper Combustion.......................................................23
High Altitude .................................................................23
Other Unit Adjustments................................................. 24
Service..........................................................................26
Repait Parts .................................................................. 28
Page 1
Page 2
Unit Dimensions - inches (mm)
A
B
AIR FLOW
9/16
(14)
FLUE OUTLET
(Top)
3/4 (19)
Front Panel
3-1/8
(79)
D
9/16
(14)
RETURN AIR
OPENING
B
19-7/16
(494)
9/16
(14)
TOP VIEW
27-3/4
(705)
19-7/16
(494)
9/16
(14)
9/16 (14)
ELECTRICAL INLET
(Either Side)
GAS PIPING INLET
(Either Side)
19-1/4
Supply
(489)
Air
3/4
(19)
C
Supply
Air
33
(838)
5-3/8 (137) Right 2-3/16 (56) Left
6-5/8 (168) Right 7-1/8 (181) Left
3/4
(19)
FRONT VIEW SIDE VIEW
Model No.
A B C D
in mm in mm in mm in mm
ML180DF045P24A
ML180DF045P36A
14-1/2 368 13-3/8 340 13 330 4-3/4 121
ML180DF070P36A
ML180DF090P36B
ML180DF090P48B
ML180DF110P60C 21 533 19-7/8 504 19-1/2 495 8 203
17-1/2 446 16-3/8 416 16 406 6-1/4
3/4
(19)
159
Page 2
Page 3
ML180DF Gas Furnace
The ML180DF gas furnace is shipped ready for installa­tion in the downow position fueled by natural gas. A con­version kit (ordered separately) is required for use in LP/ Propane gas applications.
Shipping and Packing list
Package 1 of 1 contains
1 - Assembled ML180DF unit 1 - Bag assembly containing the following:
2 - Screws 1 - Snap bushing 1 - Snap plug 1 - Wire tie 1 -Vent warning label
1 - Owner’s manual and warranty card The following items may be ordered separately: 1 - Thermostat 1 - LP/Propane changeover kit
1 - Combustible ooring base
1 - High altitude kit
Check equipment for shipping damage. If you nd any
damage, immediately contact the last carrier.
Safety Information
DANGER
Danger of explosion. There are circumstances in which odorant used with LP/
propane gas can lose its scent. In case of a leak, LP/
propane gas will settle close to the oor and may be difcult to smell. An LP/propane leak detector should be
installed in all LP applications.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
Certications
ML180DF units are CSA International certied.
In the USA, installation of gas furnaces must conform with local building codes. In the absence of local codes, units must be installed according to the current National Fuel Gas Code (ANSI-Z223.1). The National Fuel Gas Code is available from the following address:
American National Standards Institute, Inc. 11 West 42nd Street New York, NY 10036
Clearances
Adequate clearance must be made around the air open­ings into the vestibule area. In order to ensure proper unit operation, combustion and ventilation air supply must be provided according to the current National Fuel Gas Code. Vent installations must be consistent with the Na­tional Fuel Gas Code venting tables (in this instruction) and applicable provisions of local building codes.
This furnace is CSA International certied for installation
clearances to combustible material as listed on the unit
nameplate and in the tables in gure 13. Accessibility and service clearances must take precedence over re protec-
tion clearances.
Installed Locations
For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are located no less than 18 inches (457 mm) above the
oor. The furnace must be located or protected to avoid
physical damage by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a hazardous atmosphere, the furnace must be installed ac­cording to recommended good practice requirements and current National Fuel Gas Code.
NOTE - Furnace must be adjusted to obtain a temperature
rise within the range(s) specied on the unit nameplate. Failure to do so may cause erratic limit operation and may also result in premature heat exchanger failure. This ML180DF furnace must be installed so that its electrical components are protected from water.
Installed in Combination with a Cooling Coil
When this furnace is used with cooling units, it shall be in­stalled in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating compartment.
With a parallel ow arrangement, a damper (or other means to control the ow of air) must adequately prevent chilled air from entering the furnace (see gure 1). If the
damper is manually operated, it must be equipped to pre­vent operation of either the heating or the cooling.
Page 3
Page 4
The return air duct must be provided and sealed
to the furnace.
Return air temperature range between 60°F (16°C)
and 80°F (27°C) must be maintained.
GAS UNIT
Dampers
(open during heating
operation only)
AIR HANDLER
Dampers
(open during cooling
operation only)
FIGURE 1
When installed, this furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Elec­tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available from the following ad­dress:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
NOTE - This furnace is designed for a minimum continu­ous return air temperature of 60°F (16°C) or an intermittent operation down to 55°F (13°C) dry bulb for cases where a night setback thermostat is used. Return air temperature must not exceed 85°F (29°C) dry bulb.
The ML180DF furnace may be installed in alcoves, clos­ets, attics, basements, garages, and utility rooms in the
downow position.
This furnace design has not been CSA International
certied for installation in mobile homes, recreational
vehicles, or outdoors.
Safety Information
Lennox does not recommend the use of ML180DF units as a construction heater during any phase of construc­tion. Very low return air temperatures, harmful vapors and
operation of the unit with clogged or misplaced lters will
damage the unit. ML180DF units may be used for heating of buildings or
structures under construction, if the following conditions are met:
The vent system must be permanently installed per
these installation instructions.
A room thermostat must control the furnace. The
use of xed jumpers that will provide continuous heating is not allowed.
Air lters must be installed in the system and must
be maintained during construction.
Air lters must be replaced upon construction com-
pletion.
The input rate and temperature rise must be set per
the furnace rating plate.
One hundred percent (100%) outdoor air must be
provided for combustion air requirements during construction. Temporary ducting may supply out­door air to the furnace. Do not connect duct directly to the furnace. Size the temporary duct following these instructions in section for Combustion, Dilu­tion and Ventilation Air in a conned space with air from outside.
The furnace heat exchanger, components, duct
system, air lters and evaporator coils must be thoroughly cleaned following nal construction clean-up.
All furnace operating conditions (including ignition,
input rate, temperature rise and venting) must be veried according to these installation instructions.
General
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
In addition to the requirements outlined previously, the following general recommendations must be considered
when installing a ML180DF furnace:
• Place the furnace as close to the center of the air distribution system as possible. The furnace should also be located close to the chimney or vent termi­nation point.
• Do not install the furnace where drafts might blow directly into it. This could cause improper combus­tion and unsafe operation.
• Do not block the furnace combustion air openings with clothing, boxes, doors, etc. Air is needed for proper combustion and safe unit operation.
• When the furnace is installed in an attic or other insulated space, keep insulation away from the fur-
nace.
NOTE - The Commonwealth of Massachusetts stipulates these additional requirements:
Gas furnaces shall be installed by a licensed
plumber or tter only.
The gas cock must be “T handle” type.
When a furnace is installed in an attic, the pas-
sageway to and service area surrounding the equipment shall be oored.
Page 4
Page 5
WARNING
This prodcut contains a chemical known to the State of California to cause cancer, birth defects, or other reproductive harm.
Combustion, Dilution & Ventilation Air
In the past, there was no problem in bringing in sufcient outdoor air for combustion. Inltration provided all the air
that was needed. In today’s homes, tight construction practices make it necessary to bring in air from outside for combustion. Take into account that exhaust fans, appli-
ance vents, chimneys, and replaces force additional air
that could be used for combustion out of the house. Un­less outside air is brought into the house for combustion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a downdraft can oc­cur in the furnace vent pipe or chimney. As a result, com­bustion gases enter the living space creating a potentially dangerous situation.
In the absence of local codes concerning air for combus­tion and ventilation, use the guidelines and procedures in this section to install ML180DF furnaces to ensure ef­cient and safe operation. You must consider combustion air needs and requirements for exhaust vents. A portion of this information has been reprinted with permission from the National Fuel Gas Code (ANSI-Z223.1). This reprint-
ed material is not the complete and ofcial position of the
ANSI on the referenced subject,
CAUTION
Do not install the furnace in a corrosive or contaminated atmosphere. Meet all combustion and ventilation air requirements, as well as all local codes.
All gas-red appliances require air for the combustion process. If sufcient combustion air is not available, the furnace or other appliances will operate inefciently and
unsafely. Enough air must be provided to meet the needs of all fuel-burning appliances and appliances such as ex­haust fans which force air out of the house. When re­places, exhaust fans, or clothes dryers are used at the same time as the furnace, much more air is necessary to ensure proper combustion and to prevent a downdraft.
Insufcient air causes incomplete combustion which can
result in carbon monoxide.
CAUTION
Insufcient combustion air can cause headaches,
nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rusting and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Avoid exposure to the following substances in the combustion
air supply: Permanent wave solutions Chlorinated waxes and cleaners Chlorine base swimming pool chemicals Water softening chemicals De-icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents (such as perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials
In addition to providing combustion air, fresh outdoor air dilutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace com­ponents.
The requirements for providing air for combustion and ventilation depend largely on whether the furnace is in-
stalled in an unconned or a conned space.
Unconned Space
An unconned space is an area such as a basement or
large equipment room with a volume greater than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com­bined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be
unconned, it might be necessary to bring in outdoor air
for combustion if the structure does not provide enough air
by inltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around the windows and doors, follow the procedures in the air from outside section.
Conned Space
A conned space is an area with a volume less than 50
cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that
space. This denition includes furnace closets or small
equipment rooms.
Page 5
Page 6
When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on
a platform in a conned space such as a closet or small
equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure con­dition. Air for combustion and ventilation can be brought
into the conned space either from inside the building or
from outside.
EQUIPMENT IN CONFINED
CHIMNEY
OR GAS
VENT
FURNACE
AIR FLOW
NOTE - Each opening shall have a free area of at least one square inch (645 mm ing of all equipment in the enclosure, but not less than 100 square inches (64516 mm
2
2
).
SPACE ALL AIR FROM INSIDE
WATER
HEATER
OPENINGS
(To Adjacent
Room)
FIGURE 2
Air from Inside
If the conned space that houses the furnace adjoins a space categorized as unconned, air can be brought in by
providing two permanent openings between the two spac­es. Each opening must have a minimum free area of 1
square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of
total input rating of all gas-red equipment in the conned
space. Each opening must be at least 100 square inches (64516 mm2). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12
inches (305 mm) of the bottom. See gure 2.
Air from Outside
If air from outside is brought in for combustion and ventila­tion, the conned space must have two permanent open­ings. One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. These openings must communi­cate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or in­directly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of total input rating of all equipment in the enclosure. See gures 3 and 4. When communi­cating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (645 mm2) per 2,000 Btu (.56 kW) per total input rating of
all equipment in the enclosure. See gure 5.
When ducts are used, they shall be of the same cross-sec­tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protec­tive covering is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 percent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles
must be xed in the open position or interlocked with the
equipment so that they are opened automatically during equipment operation.
Page 6
Page 7
CHIMNEY OR
EQUIPMENT IN CONFINED SPACE
ment in the enclosure.
S
other equipment in the enclosure.
GAS VENT
FURNACE
(Inlet Air from Crawlspace and Outlet Air to Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
OUTLET
AIR
WATER
HEATER
CHIMNEY
OR GAS
VENT
FURNACE
VENTILATION
LOUVERS
(For unheated crawl space)
AIR FLOW
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch (645
2
mm
) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equipment in the enclosure.
INLET
AIR
Figure 3
ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
VENTILATION LOUVER
(Each end of attic)
OUTLET
AIR
INLET AIR
(Ends 12 in.
above bottom)
FURNACE
CHIMNEY
OR GAS
VENT
CONFINED SPACE
WATER
HEATER
OUTLET AIR
EQUIPMENT IN
ALL AIR FROM
OUTSIDE
AIR FLOW
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch (645 mm
FIGURE 4
WATER
HEATER
2
) per 4,000
Page 7
AIR FLOW
NOTE - Each air duct opening shall have a free area of at least one square inch (645 mm
2
) per 2,000 Btu (.59 kW) per hour of
INLET AIR
the total input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings ing shall have a free area of at least one square inch (645 mm per 4,000 Btu (1.17 kW) per hour of the total input rating of all
FIGURE 5
2
)
Page 8
Downow Installation
Downow unit installs in three ways: on non-combustible ooring, on combustible ooring using a downow com-
bustible ooring base, or on a reverse-ow cooling cabi­net. Do not drag the unit across the oor.
Installation on Non-Combustible Flooring (Figure 6)
1 - Cut oor opening keeping in mind clearances listed
on unit rating plate. Also keep in mind gas supply
connections, electrical supply, ue and air intake connections and sufcient installation and servicing clearances. See table 1 for correct oor opening
size.
2 - Flange warm air plenum and lower the plenum into
the opening.
3 - Set the unit over the plenum and seal the plenum
to the unit.
4 - Ensure that the seal is adequate.
SUPPLY AIR
OPENING
PLENUM
FIGURE 6
TABLE 1
NON-COMBUSTIBLE FLOOR OPENING SIZE
Cabinet
Width
A (14.5”)
B (17.5”) 16-3/4 413
Front to Rear Side to Side
in mm in mm
13-1/4 337
19-3/4 502
C (21”) 19-3/4 502
NOTE - Floor opening dimensions listed are 1/4 inch (6 mm) larger than the unit opening. See unit dimensions on page 2.
Installation on Combustible Flooring (Figure 7)
1 - When unit is installed on a combustible oor,
a downow combustible ooring base must be installed between the furnace and the oor. The
base must be ordered separately.
See table 2 for opening size to cut in oor.
CAUTION
The furnace and downow combustible ooring base
shall not be installed directly on carpeting, tile, or other
combustible material other than wood ooring.
SUPPLY AIR PLENUM
PROPERLY
SIZED FLOOR
OPENING
FIGURE 7
TABLE 2
COMBUSTIBLE FLOOR OPENING SIZE
Cabinet
Width
Front to Rear Side to Side
in mm in mm
A (14.5”)
B (17.5”) 18-3/4 476
22 569
C (21”) 22-3/4
2 - After opening is cut, set combustible ooring base
into opening.
3 - Check sealing strips on combustible ooring base to
make sure they are properly glued and positioned.
4 - Lower supply air plenum into downow combustible
ooring base until plenum anges seal against the
strips.
NOTE - Be careful not to damage sealing strips. Check for a tight seal.
5 - Set the furnace over the plenum. 6 - Ensure that the seal between the furnace and
plenum s adequate.
Installation on Cooling Cabinet (Figure 8)
1 - Refer to reverse-ow coil installation instructions for
correctly sized opening in oor and installation of
cabinet.
NOTE - Downow combustible ooring kit is not used.
2 - When cooling cabinet is in place, set and secure
the furnace according to the instructions that are provided with the cooling coil. Secure the furnace to the cabinet.
3 - Seal the cabinet and check for air leaks.
DOWNFLOW
COMBUSTIBLE
FLOORING BASE
15-3/4 400
578
Page 8
Page 9
PROPERLY
Blower motor with three exible legs and one
SIZED FLOOR
OPENING
FIGURE 8
Return Air Opening -- Downow Units
COOLING COIL
PLENUM
Setting Equipment
WARNING
Do not install the furnace on its front, back or in the
horizontal position. See gure 12. Do not connect the
return air ducts to the back of the furnace. Doing so will adversely affect the operation of the safety control devices, which could result in personal injury or death.
Install the ML180DF gas furnace as shipped in the down-
ow position only. Do not install the furnace horizon­tally.
Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, and installation and service clearances [24 inches (610 mm) at unit front]. The unit must be level.
The following steps should be taken when installing ple­num:
1 - Bottom edge of plenum should be anged with a
hemmed edge (See gure 9).
PLENUM
SECURE FROM
OUTSIDE CABINET
Side View
HEMMED EDGE
SEALING STRIP (Field Provided)
CABINET SIDE PANEL
FIGURE 9
2 - Sealing strip should be used. 3 - In all cases, plenum should be secured to top
anges of furnace with sheet metal screws.
PLENUM
SIDE CABINET
HEMMED EDGE
Side View
NOTE - Units with 1/3HP and 1/2HP blower motors are equipped with three exible legs and one shipping leg. See gure 11. In some units with 1/3HP blower motor, the ship­ping leg is exible with rubber mounting grommets similar to the other three mounting legs and require no modica­tion. The rest of the units with 1/3HP and 1/2HP blower motors (these blower motor housings will be tagged) have a rigid shipping leg equipped with a shipping bolt and at white plastic washer. The bolt and washer must be re- moved before the furnace is placed into operation. Af­ter the bolt and washer have been removed, the rigid leg will not touch the blower housing.
rigid shipping leg. Blower motor housings will be tagged for shipping bolt removal
RIGID LEG
(Remove shipping bolt
and washer)
FIGURE 11
FIBERGLASS SEALING STRIP (Field Provided)
CABINET SIDE
PANEL
FIGURE 10
4 - In closet installations, it may be impossible to install
sheet metal screws from the outside. In this case, make plenum with a removable front and install
screws from the inside (See gure 10).
5 - Make certain that an adequate seal is made.
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.
Page 9
Page 10
Front
Back
Figure 12
Downow Application
Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or
alcove installations are shown in gure 13.
Downflow Application Installation Clearances
Top
Horizontal
CAUTION
If this unit is being installed in a space serviced by an exhaust fan, power exhaust fan, or other device which may create a negative pressure in the space, take care when sizing the inlet air opening. The inlet air opening must be sized to accommodate the maximum volume of exhausted air as well as the maximum volume of combustion air required for all gas appliances serviced by this space.
Left Side
Bottom
Type of Vent
Connector
Top 1 in. (25 mm) 1 in. (25 mm)
*Front 2-1/4 in. (57 mm)** 2-1/4 in. (57 mm)
Back 0 0
Sides 0 0
Vent 6 in. (152 mm) 1 in. (25 mm)
Floor NC†† NC††
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. ** 4-1/2 in. if a single wall vent pipe is used.
inets, or 2 in. if a single wall vent is used on 17 - 1/2 in. cabinets. ††The furnace may be installed on a combustible wood floor if an optional additive base is installed between the furnace and the combustible floor.
Type C Type B1
Right Side
FIGURE 13
WARNING
Improper installation of the furnace can result in personal
injury or death. Combustion and ue products must
never be allowed to enter the return air system or the living space. Use screws and joint tape to seal the return air system to the furnace.
In platform installations with bottom return air, the furnace should be sealed airtight to the return air plenum. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Allow absolutely no sagging, cracks, gaps, etc.
The return and supply air duct systems must never be connected to or from other heating devices such as a
replace or stove, etc. Fire, explosion, carbon monoxide
poisoning, personal injury and/or property damage could result.
Filters
This unit is not equipped with a lter or rack. A eld-pro­vided high-velocity lter is required for the unit to operate properly. Table 3 lists recommended lter sizes.
A lter must be in place any time the unit is operating.
Page 10
Page 11
TABLE 3
V
Cabinet Width inches Air Filter Size inches
A - 14-1/2 14 x 25 x 1
B - 17-1/2 16 x 25 x 1
C - 21 20 x 25 x 1
Duct System
Use industry-approved standards (such as those pub­lished by Air Conditioning Contractors of America or Amer­ican Society of Heating, Refrigerating and Air Condition­ing Engineers) to size and install the supply and return air duct system. This will result in a quiet and low-static system that has uniform air distribution.
NOTE - Do not operate the furnace in the heating mode with an external static pressure that exceeds 0.5 inches w.c. Higher external static pressures may cause erratic limit operation.
Ensure that you have made a seal between the supply air plenum and the furnace and between the furnace and the return air plenum.
Return Air Plenum
Return air must not be drawn from a room where this furnace, or any other gas-fueled appliance (i.e., water heater), or carbon monoxide-producing device (i.e.,
wood replace) is installed. When return air is drawn from a room, a negative pressure is created in the room. If a gas appliance is operating in a room with negative pres-
sure, the ue products can be pulled back down the vent pipe and into the room. This reverse ow of the ue gas
may result in incomplete combustion and the formation of carbon monoxide gas. This toxic gas might then be dis­tributed throughout the house by the furnace duct system
.
Venting
A 4-inch diameter ue transition is factory-installed on all
models. Modifying or removing the ue transition will
cause the unit to operate unsafely and will void the
unit certication. The vent connector does not require insulation.
The ML180DF series units are classied as fan-assisted
Category I furnaces when vertically vented according to the latest edition of National Fuel Gas Code (NFPA 54 / ANSI Z223.1). A fan-assisted Category I furnace is an appliance equipped with an integral mechanical means to either draw or force combustion products through the combustion chamber and/or heat exchanger.
NOTE - Use these instructions as a guide. They do not supersede local codes. This furnace must be vented ac­cording to all local codes, these installation instructions, and the provided venting tables in these instructions.
The venting tables in this manual were extracted from the National Fuel Gas Code (NFPA 54 / ANSI Z223.1) and are provided as a guide for proper vent installation. Proper application, termination, construction and location of vents must conform to local codes having jurisdiction. In the ab-
sence of local codes, the NFGC serves as the dening
document. Refer to the tables and the venting information contained
in these instructions to properly size and install the venting system.
IMPORTANT
Once the venting system is installed, attach the “Disconnected Vent” warning sticker to a visible area of the plenum near the vent pipe. The warning sticker is provided in the bag assembly. Order kit 66W04 for additional stickers.
WARNING
Asphyxiation hazard. The exhaust vent for this furnace
must be securely connected to the furnace ue transition
at all times.
ENT CONNECTION
VENT PIPE
(min. 6” length)
FLUE TRANSITION
COLLAR
FIGURE 14
Use self-drilling sheet metal screws or a mechanical fas-
tener to rmly secure the vent pipe to the round collar of the ue transition. If self-drilling screws are used to attach
the vent pipe, it is recommended that three be used. Drive one self-drilling screw through the front and one through
each side of the vent pipe and collar. See gure 14. Install the rst vent connector elbow at a minimum of six
inches (152 mm) from the furnace vent outlet. Masonry chimneys used to vent Category I central furnaces must be either tile-lined or lined with a listed metal lining sys­tem or dedicated gas vent. Unlined masonry chimneys are
prohibited. See gures 15 and 16 for common venting.
“DISCONNECTED VENT”
WARNING
STICKER
Page 11
Page 12
Common Venting Using Tile-Lined Interior Masonry Chimney and Combined Vent Connector
Common Venting Using Metal-Lined Masonry Chimney
MINIMUM LENGTH = AS SHORT AS PRACTICAL. FOR MAXIMUM LENGTH SEE NOTE TO LEFT
NOTE- Refer to provided venting tables for installations.
OTHER
APPLIANCE
Venting Using a Masonry Chimney
The following additional requirements apply when a lined masonry chimney is used to vent this furnace.
A chimney with one or more sides exposed to the outside of the structure is considered to be an exterior chimney.
An exterior masonry chimney that is not tile-lined must be
lined with B1 vent or a listed insulated exible metal vent.
An exterior tile-lined chimney that is sealed and capped
may be lined with a listed uninsulated exible metal vent.
If the existing chimney will not accommodate a listed met­al liner, either the chimney must be rebuilt to accommo­date one of these liners or an alternate approved venting method must be found.
Insulation for the exible vent pipe must be an encapsu­lated berglass sleeve recommended by the exible vent pipe manufacturer. See gure 16.
SEALED
MAX. LENGTH
-- SEE NOTE 1
5 ft. (1.5 m)
minimum
VENT CONNECTOR
4 in. (102 mm)
minimum
OTHER
APPLIANCE
NOTE 1 - Refer to the provided venting tables for installations. Refer to the capacity requirements shown in the provided venting tables.
BELOW.
MIN. LENGTH -- AS
SHORT AS PRACTICAL
FURNACE
AIR FLOW
CHIMNEY WITH
PERMANENTLY
SEALED FIREPLACE
OPENING
FIGURE 16
AIR FLOW
EXTERIOR
METAL
LINER
VENT
CONNECTOR
FURNACE
Figure 15
DO NOT insulate the space between the liner and the chimney wall with puffed mica or any other loose granular insulating material
SINGLE appliance venting of a fan-assisted furnace into a tile-lined masonry chimney (interior or outside wall)
is PROHIBITED. The chimney must rst be lined with either type B1 vent or an insulated single wall exible
vent lining system which has been sized according to the provided venting tables and the vent pipe manufacturer’s instructions.
A fan-assisted furnace may be commonly vented into an existing lined masonry chimney if the following conditions are met:
If type B1 double-wall vent is used inside a chimney, no other appliance can be vented into the chimney. The out-
er wall of type B1 vent pipe must not be exposed to ue
products. A type B1 vent or masonry chimney liner shall terminate
above the roof surface with a listed cap or a listed roof as­sembly according to the terms of their respective listings and the vent manufacturer’s instructions.
When inspection reveals that an existing chimney is not safe for the intended purpose, it shall be rebuilt to conform to nationally recognized standards, lined or relined with suitable materials, or replaced with a gas vent or chimney suitable for venting ML180DF series units. The chimney passageway must be checked periodically to ensure that it is clear and free of obstructions.
Do not install a manual damper, barometric draft regulator,
or ue restrictor between the furnace and the chimney.
INTERIOR TILE-LINED MASONRY CHIMNEY
NOTE - the chimney must be properly sized per provided venting tables or lined with listed metal lining system.
PERMANENTLY SEALED FIREPLACE OPENING
IMPORTANT
• The chimney is currently serving at least one draft­hood equipped appliance
• The vent connectors and chimney are sized accord­ing to the provided venting tables.
Page 12
Page 13
Never connect a Category I appliance to a chimney that is
servicing a solid-fuel appliance. If a replace chimney ue is used to vent this appliance, the replace opening must
be permanently sealed. A type B or listed chimney lining system that passes
through an unused masonry chimney ue is not consid­ered to be exposed to the outdoors.
General Venting Requirements
Vent all ML180DF furnaces according to these instruc­tions:
1 - Vent diameter recommendations and maximum
allowable piping runs are found in the provided venting tables.
2 - In no case should the vent or vent connector
diameter be less than the diameter specied in the
provided venting tables.
3 - The minimum vent capacity determined by the
sizing tables must be less than the low re input
rating and the maximum vent capacity must be
greater than the high re input rating.
4 - Single appliance vents - If the vertical vent or tile-
lined chimney has a larger diameter or ow area than
the vent connector, use the vertical vent diameter to determine the minimum vent capacity and the vent connector diameter to determine the maximum vent
capacity. The ow area of the vertical vent, however, shall not exceed 7 times the ow area of the listed
appliance categorized vent area, drafthood outlet
area or ue collar area unless designed according
to approved engineering methods.
5 - Multiple appliance vents - The ow area of the
largest section of vertical vent or chimney shall not exceed 7 times the smallest listed appliance
categorized vent area, drafthood outlet area or ue
collar area unless designed according to approved engineering methods.
6 - The entire length of single wall metal vent connector
shall be readily accessible for inspection, cleaning, and replacement.
7 - Single appliance venting congurations with zero
lateral lengths (table 5) are assumed to have no elbows in the vent system. For all other vent
congurations, the vent system is assumed to have
two 90° elbows. For each additional 90° elbow or equivalent (for example two 45° elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10% (0.90 x maximum listed capacity).
8 - The common venting tables (6 and 7) were
generated using a maximum horizontal vent connector length of 1-1/2 feet (.46 m) for each inch (25 mm) of connector diameter as follows:
NOTE - Single Wall Vent Connectors may be used if the requirements set forth by the National Fuel Gas Code are met. Please consult latest edition of NFPA 54/ANSI Z223.1 for proper sizing and application.
TABLE 4
Connector Diameter
inches (mm)
Maximum Horizontal
Connector Length feet (m)
3 (76) 4-1/2 (1.37)
4 (102) 6 (1.83)
5 (152) 7-1/2 (2.29)
6 (152) 9 (2.74)
7 (178)
10-1/2 (3.20)
9 - If the common vertical vent is offset, the maximum
common vent capacity listed in the common venting tables should be reduced by 20%, the equivalent of two 90° elbows (0.80 x maximum common vent capacity). The horizontal length of the offset shall not exceed 1-1/2 feet (.46 m) for each inch (25 mm) of common vent diameter.
10 - The vent pipe should be as short as possible with
the least number of elbows and angles required to complete the job. Route the vent connector to the vent using the shortest possible route.
11 - A vent connector shall be supported without any
dips or sags and shall slope a minimum of 1/4 inch (6.4 mm) per linear foot (305 mm) of connector, back toward the appliance.
12 - Vent connectors shall be rmly attached to the
furnace ue collar by self-drilling screws or other
approved means, except vent connectors of listed type B vent material which shall be assembled according to the manufacturer’s instructions. Joints between sections of single wall connector piping shall be fastened by screws or other approved means.
13 - When the vent connector used for Category I
appliances must be located in or pass through a crawlspace or other areas which may be cold, that portion of the vent connector shall be constructed of listed double-wall type B vent material or material having equivalent insulation qualities.
14 - All venting pipe passing through oors, walls, and
ceilings must be installed with the listed clearance
to combustible materials and be re stopped
according to local codes. In absence of local codes, refer to NFGC (Z223.1).
15 - No portion of the venting system can extend into,
or pass through any circulation air duct or plenum.
16 - Vent connectors serving Category I appliances shall
not be connected to any portion of mechanical draft systems operating under positive pressure such as Category III or IV venting systems.
17 - If vent connectors are combined prior to entering
the common vent, the maximum common vent capacity listed in the common venting tables must be reduced by 10%, the equivalent of one 90° elbow (0.90 x maximum common vent capacity).
18 - The common vent diameter must always be at least
as large as the largest vent connector diameter.
Page 13
Page 14
19 - In no case, shall the vent connector be sized more
than two consecutive table size diameters over the
size of the draft hood outlet or ue collar outlet.
20 - Do not install a manual damper, barometric draft
regulator or ue restrictor between the furnace and
the chimney.
21 - When connecting this appliance to an existing
dedicated or common venting system, you must inspect the venting system’s general condition and look for signs of corrosion. The existing vent pipe size must conform to these instructions and the provided venting tables. If the existing venting system does not meet these requirements, it must be resized.
TABLE 5
Capacity of Type B Double-Wall Vents with Type B Double-Wall Connectors
Serving a Single Category I Appliance
Height
H
(feet)
6
8
10
15
20
30
NOTE - Single appliance venting congurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other vent congurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45° elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maximum listed capacity).
Lateral
L
(feet)
0 0 78 0 152 0 251 0 375 2 13 51 18 97 27 157 32 232 4 21 49 30 94 39 153 50 227 6 25 46 36 91 47 149 59 223 0 0 84 0 165 0 276 0 415 2 12 57 16 109 25 178 28 263 5 23 53 32 103 42 171 53 255 8 28 49 39 98 51 164 64 247 0 0 88 0 175 0 295 0 447 2 12 61 17 118 23 194 26 289 5 23 57 32 113 41 187 52 280
10 30 51 41 104 54 176 67 267
0 0 94 0 191 0 327 0 502 2 11 69 15 136 20 226 22 339
5 22 65 30 130 39 219 49 330 10 29 59 40 121 51 206 64 315 15 35 53 48 112 61 195 76 301
0 0 97 0 202 0 349 0 540
2 10 75 14 149 18 250 20 377
5 21 71 29 143 38 242 47 367
10 28 64 38 133 50 229 62 351 15 34 58 46 124 59 217 73 337 20 48 52 55 116 69 206 84 322
0 0 100 0 213 0 374 0 587
2 9 81 13 166 14 283 18 432
5 21 77 28 160 36 275 45 421 10 27 70 37 150 48 262 59 405 15 33 64 44 141 57 249 70 389 20 56 58 53 132 66 237 80 374 30 NA NA 73 113 88 214 104 346
3 inch 4 inch 5 inch 6 inch
Min Max Min Max Min Max Min Max
Vent and Connector Diameter - D (inches)
Appliance Input Rating in Thousands of Btu Per Hour
Page 14
Page 15
Height
H
(feet)
6
8
10
15
20
30
TABLE 6
Vent Connector Capacity
Type B Double-Wall Vents with Type B Double-Wall Connectors Serving Two or More Category I Appliances
Lateral
L
(feet)
1 22 37 35 66 46 106 58 164
2 23 41 37 75 48 121 60 183
3 24 44 38 81 49 132 62 199
1 22 40 35 72 49 114 64 176
2 23 44 36 80 51 128 66 195
3 24 47 37 87 53 139 67 210
1 22 43 34 78 49 123 65 189
2 23 47 36 86 51 136 67 206
3 24 50 37 92 52 146 69 220
1 21 50 33 89 47 142 64 220
2 22 53 35 96 49 153 66 235
3 24 55 36 102 51 163 68 248
1 21 54 33 99 46 157 62 246
2 2 57 34 105 48 167 64 259
3 23 60 35 110 50 176 66 271
1 20 62 31 113 45 181 60 288
2 21 64 33 118 47 190 62 299
3 22 66 34 123 48 198 64 309
3 inch 4 inch 5 inch 6 inch
Min Max Min Max Min Max Min Max
Vent and Connector Diameter - D (inches)
Appliance Input Rating in Thousands of Btu Per Hour
TABLE 7
Common Vent Capacity
Type B Double-Wall Vents with Type B Double-Wall Connectors Serving Two or More Category I Appliances
Vent
Height
H
(feet)
6 92 81 140 116 204 161 309 248
8 101 90 155 129 224 178 339 275
10 110 97 169 141 243 194 367 299
15 125 11 2 195 164 283 228 427 352
20 136 123 215 183 314 255 475 394
30 152 138 244 210 361 297 547 459
FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT
4 inch 5 inch 7 inch 7 inch
Vent and Connector Diameter - D (inches)
Appliance Input Rating in Thousands of Btu Per Hour
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a venting system commonly run with separate gas applianc­es, the venting system is likely to be too large to properly vent the remaining attached appliances.
Conduct the following test while each appliance is oper­ating and the other appliances (which are not operating) remain connected to the common venting system. If the venting system has been installed improperly, you must correct the system as indicated in the general venting re-
CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each
appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
WARNING
quirements section.
Page 15
Page 16
1 - Seal any unused openings in the common venting
system.
2 - Inspect the venting system for proper size and
horizontal pitch. Determine that there is no blockage,
restriction, leakage, corrosion, or other deciencies
which could cause an unsafe condition.
3 - Close all building doors and windows and all
doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not
operate a summer exhaust fan. Close replace
dampers.
4 - Follow the lighting instructions. Turn on the appliance
that is being inspected. Adjust the thermostat so that the appliance operates continuously.
5 - After the main burner has operated for 5 minutes,
test for leaks of ue gases at the draft hood relief opening. Use the ame of a match or candle, or
smoke from a cigarette, cigar, or pipe.
6 - After determining that each appliance connected
to the common venting system is venting properly, (step 3) return all doors, widows, exhaust fans,
replace dampers, and any other gas-burning
appliances to their previous mode of operation.
7 - If a venting problem is found during any of the
preceding tests, the common venting system must
be modied to correct the problem.
Resize the common venting system to the minimum vent pipe size determined by using the appropriate tables in Appendix G. (These are in the current standards of the National Fuel Gas Code ANSI Z223.1.
Gas Piping
Gas supply piping should not allow more than 0.5”W.C. drop in pressure between gas meter and unit. Supply gas pipe must not be smaller than unit gas connection.
CAUTION
If a exible gas connector is required or allowed by the
authority that has jurisdiction, black iron pipe shall be installed at the gas valve and extend outside the furnace
cabinet. The exible connector can then be added
between the black iron pipe and the gas supply line.
Gas Supply
1 - This unit is shipped standard for left or right side
installation of gas piping (or top entry in horizontal applications). Connect the gas supply piping into the gas valve. The maximum torque is 800 in lbs and minimum torque is 350 in lbs when when attaching the gas piping to the gas valve.
WARNING
Do not over torque (800 in-lbs) or under torque (350 in­lbs) when attaching the gas piping to the gas valve.
2 - When connecting the gas supply piping, consider
factors such as length of run, number of ttings, and
furnace rating to avoid excessive pressure drop. Table 8 lists recommended pipe sizes for typical applications.
3 - The gas piping must not run in or through air ducts,
clothes chutes, gas vents or chimneys, dumb waiters, or elevator shafts.
4 - The piping should be sloped 1/4 inch (6.4 mm) per
15 feet (4.57 m) upward toward the meter from the furnace. The piping must be supported at proper intervals [every 8 to 10 feet (2.44 to 3.01 m)] with suitable hangers or straps. Install a drip leg inside vertical pipe runs to the unit.
5 - A 1/8” N.P.T. plugged tap or pressure post is located
on the gas valve to facilitate test gauge connection.
See gure 22.
6 - In some localities, codes may require the installation
of a manual main shut-off valve and union (furnished by the installer) external to the unit. The union must be of the ground joint type.
CAUTION
Compounds used on threaded joints of gas piping must
be resistant to the actions of liquied petroleum gases.
NOTE - If emergency shutoff is necessary, shut off the main manual gas valve and disconnect main power to the furnace. The installer should properly label these devices
Page 16
Page 17
TABLE 8
Gas Pipe Capacity - ft3/hr (m3/hr)
Nominal
Iron Pipe
Size Inches
(mm)
1/2
(12.7)
3/4
(19.05)
1
(25.4)
1-1/4
(31.75)
1-1/2
(38.1)
2
(50.8)
2-1/2
(63.5)
3
(76.2)
Internal
Diameter
inches
(mm)
.622
(17.799)
.824
(20.930)
1.049
(26.645)
1.380
(35.052)
1.610
(40.894)
2.067
(52.502)
2.469
(67.713)
3.068
(77.927)
10
(3.048)
172
(4.87)
360
(10.19)
678
(19.19)
1350
(38.22)
2090
(59.18)
4020
(113.83)
6400
(181.22)
11300
(319.98)
20
(6.096)
118
(3.34)
247
(7.000)
466
(13.19)
957
(27.09)
1430
(40.49)
2760
(78.15)
4400
(124.59)
7780
(220.30)
30
(9,144)
95
(2.69)
199
(5.63)
374
(10.59)
768
(22.25)
1150
(32.56)
2220
(62.86)
3530
(99.95)
6250
(176.98)
40
(12,192)
81
(2.29)
170
(4.81)
320
(9.06)
657
(18.60)
985
(27.89)
1900
(53.80)
3020
(85.51)
5350
(151.49)
Length of Pipe - feet (m)
50
(15.240)
72
(2.03)
151
(4.23)
284
(8.04)
583
(16.50)
873
(24.72)
1680
(47.57)
2680
(75.88)
4740
(134.22)
60
(18.288)
65
(1.84)
137
(3.87)
257
(7.27)
528
(14.95)
791
(22.39)
1520
(43.04)
2480
(70.22)
4290
(121.47)
70
(21.336)
60
(1.69)
126
(3.56)
237
(6.71)
486
(13.76)
728
(20.61)
1400
(39.64)
2230
(63.14)
3950
(111.85)
(24.384)
(1.58)
(3.31)
(6.23)
(12.79)
(19.17)
1300
(36.81)
2080
(58.89)
3670
(103.92)
NOTE - Capacity given in cubic feet (m3 ) of gas per hour and based on 0.60 specic gravity gas.
.
80
56
117
220
452
677
90
(27.432)
52
(1.47)
110
(3.11)
207
(5.86)
424
(12.00)
635
(17.98)
1220
(34.55)
1950
(55.22)
3450
(97.69)
100
(30,480)
50
(1.42)
104
(2.94)
195
(5.52)
400
(11.33)
600
(17.00)
1160
(32.844)
1840
(52.10)
3260
(92.31)
MANUAL
MAIN SHUT-OFF
VALV E
GROUND
JOINT
UNION
Left Side Piping
(Standard)
DRIP LEG
AUTOMATIC
GAS VALV E
AUTOMATIC
GAS VALV E
(with manual
shut-off valve)
FIELD
PROVIDED
AND INSTALLED
NOTE - BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET
(with manual
shut-off valve)
Figure 17
MANUAL
MAIN SHUT-OFF
VALV E
GROUND
JOINT
UNION
DRIP LEG
Right Side Piping
(Alternate)
Page 17
Page 18
Leak Check
INTERIOR MAKE-UP BOX INSTALLATION
Cut the two wire ties to extend power wires for right side onl
y
After gas piping is completed, carefully check all piping
connections (factory- and eld-installed) for gas leaks.
Use a leak detecting solution or other preferred means.
NOTE - If emergency shutoff is necessary, shut off the main manual gas valve and disconnect the main power to the furnace. The installer should properly label these devices.
CAUTION
Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly after leak test has been completed. Do not use matches,
candles, ame or other sources of ignition to check for
gas leaks.
The furnace must be isolated from the gas supply system by closing its individual manual shut-off valve during any pressure testing of the gas supply system at pressures greater than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.)
.
IMPORTANT
When testing pressure of gas lines, gas valve must be
disconnected and isolated. See gure 18. Gas valves
can be damaged if subjected to pressures greater than 1/2 psig (3.48 kPa, 14 inches w.c.).
MANUAL MAIN
SHUT-OFF VALV E
WILL NOT HOLD
NORMAL TEST
PRESSURE
1/8 NPT PLUG
CAP
FIGURE 18
Electrical
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
ISOLATE
GAS VALV E
FURNACE
CAUTION
Electrostatic discharge can affect electronic components. Take precautions to neutralize electrostatic charge by touching your hand and tools to metal prior to handling the control.
The unit is equipped with a eld make-up box on the left
hand side of the cabinet. The make-up box may be moved to the right side of the furnace to facilitate installation. If the make-up box is moved to the right side, clip the wire ties that bundle the wires together. The excess wire must be pulled into the blower compartment. Secure the excess wire to the existing harness to protect it from damage.
(Right Side)
MAKE-UP
BOX
FIGURE 19
Refer to gure 20 for schematic wiring diagram and trou­bleshooting.
The power supply wiring must meet Class I restrictions. Protected by either a fuse or circuit breaker, select circuit protection and wire size according to unit nameplate.
CAUTION
Failure to use properly sized wiring and circuit breaker may result in property damage. Size wiring and circuit
breaker(s) per Product Specications bulletin (EHB) and
unit rating plate.
NOTE - Unit nameplate states maximum current draw. Maximum over-current protection allowed is 15 AMP. Holes are on both sides of the furnace cabinet to facilitate wiring.
Install a separate (properly sized) disconnect switch near the furnace so that power can be turned off for servicing. Before connecting the thermostat, check to make sure the wires will be long enough for servicing at a later date. Make sure that thermostat wire is long enough to facilitate future removal of blower for service.
WARNING
Fire Hazard. Use of aluminum wire with this product may
result in a re, causing property damage, severe injury
or death. Use copper wire only with this product.
Page 18
Page 19
Complete the wiring connections to the equipment. Use the provided unit wiring diagram. Use 18-gauge wire or larger that is suitable for Class II rating for thermostat con­nections.
Electrically ground the unit according to local codes or, in the absence of local codes, according to the current Na­tional Electric Code (ANSI/NFPA No. 70). A green ground
wire is provided in the eld make-up box.
NOTE - The ML180DF furnace contains electronic com­ponents that are polarity sensitive. Make sure that the fur­nace is wired correctly and is properly grounded.
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be properly grounded in accordance with national and local codes.
Accessory Terminals
One line voltage “EAC” 1/4” spade terminal is provided on
the furnace integrated control. See gure 21 for integrated control conguration. This terminal is energized when the
indoor blower is operating. Any accessory rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neu­tral terminals. If an accessory rated at greater than one amp is connected to this terminal, it is necessary to use an external relay.
One line voltage “HUM” 1/4” spade terminal is provided
on the furnace integrated control. See gure 21 for inte­grated control conguration. This terminal is energized in
the heating mode when the combustion air inducer is op­erating.
Any humidier rated up to one amp can be connected to
this terminal with the neutral leg of the circuit being con­nected to one of the provided neutral terminals. If a hu-
midier rated at greater than one amp is connected to this
terminal, it is necessary to use an external relay relay.
Generator Use - Voltage Requirements
The following requirements must be kept in mind when specifying a generator for use with this equipment:
• The furnace requires 120 volts + 10% (Range: 108 volts to 132 volts).
• The furnace operates at 60 Hz + 5% (Range: 57 Hz to 63 Hz).
• The furnace integrated control requires both po­larity and proper ground. Both polarity and proper grounding should be checked before attempting to operate the furnace on either permanent or tempo­rary power.
• Generator should have a wave form distortion of less than 5% THD (total harmonic distortion).
Thermostat
Install the room thermostat according to the instructions
provided with the thermostat. See gure 20 for thermostat
designations. If the furnace is being matched with a heat pump, refer to the FM21 installation instruction or appro­priate dual fuel thermostat instructions.
Indoor Blower Speeds
1 - When the thermostat is set to “FAN ON,” the indoor
blower will run continuously on the heating speed when there is no cooling or heating demand.
2 - When the ML180DF is running in the heating mode,
the indoor blower will run on the heating speed.
3 - When there is a cooling demand, the indoor blower
will run on the cooling speed.
Page 19
Page 20
ML180DF Schematic Wiring Diagram
Figure 20
Page 20
Page 21
Integrated Control
LED
TWIN
PUSH BUTTON
INTEGRATED CONTROL
(Automatic Hot Surface Ignition System)
TERMINAL DESIGNATIONS
HUM LINE XFMR EAC COOL HEAT PARK CONT NEUTRALS
Humidifier (120VAC) Input (120VAC) Transformer (120VAC) Indoor Air Qality Accessory Air Cleaner (120VAC) Blower - Cooling Speed (120VAC) Blower - Heating Speed (120VAC) Dead terminals to park alternate spd taps Continuous blower Neutral terminals (120VAC)
BLOWER OFF
DELAY JUMPER
Integrated Control Diagnostic Codes
LED Status Description
LED Off
LED Off Normal operation.
1 Flash
2 Flashes
3 Flashes
4 Flashes Primary limit switch open.
5 Flashes Rollout switch open.
6 Flashes Pressure switch cycle lockout.
7 Flashes Lockout, burners fail to light.
8 Flashes
9 Flashes Line voltage polarity incorrect.
No power to control or control harware fault detected.
Flame present with gas vavle
de-energized.
Pressure switch closed with combustion air inducer de-en­ergized.
Pressure switch open with combustion air inducer ener­gized.
Lockout, buners lost ame too
many times.
Figure 21
Note - This control is equipped with a push button switch for diagnostic code recall. The control stores the last 5 fault codes in non-volatile memory. The most recent fault code is ashed rst, the oldest fault code is ashed last. There is a 2 second pause between codes. When the push button switch is pressed for less than 5 seconds, the control will ash the stored fault codes when the switch is released. The fault code history may be cleared by press­ing the push button switch for more than 5 seconds.
Page 21
Page 22
Unit Start-Up
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING
Electric shock hazard. Can cause injury or death. Do not use this unit if any part has been under water. Immediately call a
qualied service technician to inspect the
unit and to replace any part of the control system and any gas control which has been under water.
7 - Wait ve minutes to clear out any gas. If you then
smell gas, STOP! Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you do not smell gas go to next step.
8 - Move switch on gas valve to ON. Do not force. See
gure 22.
MANIFOLD PRESSURE
ADJUSTMENT
SCREW
MANIFOLD
PRESSURE
OUTLET
PORT
WARNING
If overheating occurs or if gas supply fails to shut off, shut off the manual gas valve to the appliance before shutting off electrical supply.
CAUTION
Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch.
BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor.
The gas valve on the ML180DF unit is equipped with a gas control switch. Use only your hand to move the switch. Never use tools. If the switch will not turn or if the control switch will not move by hand, do not try to repair it.
Placing the furnace into operation:
ML180DF units are equipped with an automatic ignition system. Do not attempt to manually light burners on these furnaces. Each time the thermostat calls for heat, the burners will automatically light. The ignitor does not get hot when there is no call for heat on units with an automat­ic ignition system.
WARNING
Danger of explosion and re. Can cause
injury or product or property damage. You must follow these instructions exactly.
Gas Valve Operation (Figure 22)
1 - STOP! Read the safety information at the beginning
of this section. 2 - Set the thermostat to the lowest setting. 3 - Turn off all electrical power to the unit. 4 - This furnace is equipped with an ignition device
which automatically lights the burners. Do not try to light the burners by hand.
5 - Remove the access panel. 6 - Move switch on gas valve to OFF. Do not force. See
gure 22.
INLET
PRESSURE
PORT
9 - Replace the access panel. 10 - Turn on all electrical power to to the unit. 11 - Set the thermostat to desired setting.
NOTE - When unit is initially started, steps 1 through 11 may need to be repeated to purge air from gas line.
12 - If the appliance will not operate, follow the
instructions “Turning Off Gas to Unit” and call your service technician or gas supplier.
Turning Off Gas to Unit
1 - Set the thermostat to the lowest setting. 2 - Turn off all electrical power to the unit if service is to
be performed. 3 - Remove the access panel. 4 - Move switch on gas valve to OFF. Do not force. 5 - Replace the upper access panel.
Failure To Operate
If the unit fails to operate, check the following:
1 - Is the thermostat calling for heat? 2 - Are access panels securely in place? 3 - Is the main disconnect switch closed? 4 - Is there a blown fuse or tripped circuit breaker? 5 - Is the lter dirty or plugged? Dirty or plugged lters
will cause the limit control to shut the unit off. 6 - Is gas turned on at the meter? 7 - Is the manual main shut-off valve open? 8 - Is the internal manual shut-off valve open? 9 - Is the unit ignition system in lock out? If the unit locks
out again, call the service technician to inspect the
unit for blockages. 10 - Is pressure switch closed? Obstructed ue will
cause unit to shut off at pressure switch. Check ue
and outlet for blockages.
GAS VALVE SHOWN IN ON POSITION
FIGURE 22
Page 22
Page 23
11 - Are ame rollout switches tripped? If ame rollout
switches are tripped, call the service technician for inspection.
Heating Sequence Of Operation
1 - When thermostat calls for heat, combustion air
blower starts.
2 - Combustion air pressure switch proves blower
operation. Switch is factory-set and requires no adjustment.
3 - After a 15-second prepurge, the hot surface ignitor
energizes.
4 - After a 20-second ignitor warm-up period, the gas
valve solenoid opens. A 4-second trial for ignition period begins.
5 - Gas is ignited, ame sensor proves the ame, and
the combustion process continues.
6 - If ame is not detected after rst ignition trial,
the ignition control will repeat steps 3 and 4 four more times before locking out the gas valve
(”WATCHGUARD” ame failure mode).The ignition
control will then automatically repeat steps 1 through 6 after a 60 minute.
7 - To interrupt the 60-minute (“WATCHGUARD”)
period, move thermostat from “Heat” to “OFF” then back to “Heat.” Heating sequence then restarts at step 1.
Gas Pressure Adjustment
Gas Flow (Approximate)
TABLE 9
GAS METER CLOCKING CHART
Seconds for One Revolution
ML180
Unit
-045 80 160 200 400
-070 55 110 136 272
-090 41 82 102 204
-110 33 66 82 164
-135 27 54 68 136
Natural-1000 btu/cu ft LP-2500 btu/cu ft
Natural LP
1 cu ft
Dial
2 cu ft
Dial
1 cu ft
Dial
2 cu ft
Dial
Furnace should operate at least 5 minutes before check­ing gas ow. Determine time in seconds for two revolu­tions of gas through the meter. (Two revolutions assures a more accurate time.) Divide by two and compare to time in table 9 below. If manifold pressure matches table 11 and
rate is incorrect, check gas orices for proper size and
restriction. Remove temporary gas meter if installed.
NOTE - To obtain accurate reading, shut off all other gas appliances connected to meter.
Supply Pressure Measurement
A threaded plug on the inlet side of the gas valve provides access to the supply pressure tap. Remove the threaded
plug, install a eld-provided barbed tting and connect a
manometer to measure supply pressure. Furnace should operate at least 5 minutes before checking supply pres­sure. See table 11 for proper supply pressure. Replace the threaded plug after measurements have been taken
Manifold Pressure Measurement
1 - Remove the threaded plug from the outlet side of
the gas valve and install a eld-provided barbed tting. Connect to a manometer to measure manifold
pressure.
2 - Start unit and allow 5 minutes for unit to reach
steady state. 3 - While waiting for the unit to stabilize, observe the
ame. Flame should be stable and should not lift
from burner. Natural gas should burn blue. 4 - After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in
table 11. 5 - Shut unit off and remove manometer as soon as an
accurate reading has been obtained. Take care to
replace pressure tap plug. 6 - Start unit and perform leak check. Seal leaks if
found.
Proper Combustion
Furnace should operate a minimum 15 minutes with cor-
rect manifold pressure and gas ow rate before checking combustion. Take combustion sample beyond the ue out-
let and compare to the tables below. The maximum car­bon monoxide reading should not exceed 100 ppm.
TABLE 10
ML180UH Unit CO2% For Nat CO2% For L.P.
-045
-070
-090
-110
6.0 - 7.5 6.9 - 8.5
High Altitude
The manifold pressure may require adjustment and com­bustion air pressure switch may need replacing to ensure proper combustion at higher altitudes. Refer to table 11 for manifold pressure and table 12 for pressure switch change and gas conversion kits.
IMPORTANT
For safety, shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to replace pressure tap plug.
Page 23
Page 24
TABLE 11
Manifold Pressure Settings at all Altitudes
Model
Input Size
045
070
090
110
Gas 0 - 4500 ft. 4501 - 7500 ft . 7501 - 10,000 ft.
Nat 3.5 3.5 3.5 4.5 13.0
LP/Propane 10.0 10.0 10.0 11.0 13.0
Nat 3.5 3.3 3.5 4.5 13.0
LP/Propane 10.0 10.0 10.0 11.0 13.0
Nat 3.5 3.3 3.5 4.5 13.0
LP/Propane 10.0 10.0 10.0 11.0 13.0
Nat 3.5 3.3 3.5 4.5 13.0
LP/Propane 10.0 10.0 10.0 11.0 13.0
Line Pressure in. wg.
Min Max
TABLE 12
Pressure Switch and Gas Conversion Kits at all Altitudes
Model Input
Size
045 0-4500 ft 4501-7500 ft 7501-10,000 ft 0 - 7500 ft 7501 - 10,000 ft 0 - 7500 ft 7501 - 10,000 ft
070
110 80W52
090 No Change
090 (X)
110
High Altitude Pressure Switch Kit Natuarl Gas Orice Kit LP/Propane Orice Kit
No Change
No Change
80W52
80W51 73W81 73W37 11K49 11K44
NOTE - A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit instal­lation instruction for the conversion procedure.
Other Unit Adjustments
NOTE - Do not secure the electrical conduit directly to the air ducts or structure.
Primary and Secondary Limits
The primary limit is located on the heating compartment vestibule panel. The secondary limits (if equipped) are lo­cated in the blower compartment, attached to the back side of the blower. These auto reset limits are factory-set and require no adjustment.
Flame Rollout Switch
The manually reset switch is located on the front of the burner box.
Pressure Switch
The pressure switch is located in the heating compartment adjacent to the combustion air inducer. The switch checks for proper combustion air inducer operation before allow­ing ignition trial. The switch is factory-set and requires no adjustment.
Temperature Rise
After the furnace has been started, and supply and return air temperatures have been allowed to stabilize, check the temperature rise. If necessary, adjust the blower speed to maintain the temperature rise within the range shown on the unit nameplate. Increase the blower speed to de­crease the temperature. Decrease the blower speed to increase the temperature rise. Failure to adjust the tem­perature rise may cause erratic limit operation.
Fan Control
The heat fan-on time of 30 seconds is not adjustable. The heat fan-off delay (amount of time that the blower oper-
ates after the heat demand has been satised) may be adjusted by changing the jumper position across the ve
pins on the integrated control. The unit is shipped with a factory fan-off delay setting of 120 seconds. The fan-off delay affects comfort and is adjustable to satisfy individual applications. Adjust the fan-off delay to achieve a supply air temperature between 90° and 110°F at the moment that the blower is de-energized. Longer off delay settings provide lower return air temperatures; shorter settings
provide higher return air temperatures. See gure 23.
Page 24
Page 25
HEAT FANOFF TIME IN SECONDS
NO JUMPER
To adjust fan-off timing, reposition jumper across pins to
60 Second
off Time
60
90
120
180
achieve desired setting.
90 Second
off Time
60
90
120
180
120 Second
off Time
60
90
120
180
180 Second
off Time
60
90
120
180
FIGURE 23
Blower Speeds
Follow the steps below to change the blower speeds.
1 - Turn off electrical power to furnace. 2 - Remove blower access panel. 3 - Disconnect existing speed tap at integrated control
speed terminal.
See unit Product Specications Manual for indoor blower
data.
NOTE - Termination of any unused motor leads must be insulated.
4 - Place unused blower speed tap on integrated
control “PARK” terminal or insulate.
5 - Refer to blower speed selection chart on unit wiring
diagram for desired heating or cooling speed. See
Blower performance data beginning on the next
page. 6 - Connect selected speed tap at integrated control
speed terminal. 7 - Resecure blower access panel. 8 - Turn on electrical power to furnace. 9 - Recheck temperature rise.
Twinning 2 ML180DF Furnaces
The control board in this furnace is equipped with a provi­sion to ”twin” (interconnect) two(2) adjacent furnaces with a common plenum such that they operate as one (1) large unit.
When twinned, the circulating blower speeds are synchro­nized between the furnaces. If either furnace has a need to run the blower, both furnaces will run the blower on the same speed. The cooling speed has highest priority, fol­lowed by heating speed and fan speed.
Field installation of twinning consists of connecting wires between the ”C” and ”Twin” terminals of the two controls. The 24 VAC secondary of the two systems must be in phase. All thermostat connections are made to one con­trol only. Figure 24 show wiring for two-stage and single stage thermostats.
The twinned furnace without thermostat connections is to have the call for heat supplied by an external 24VAC isolation relay to prevent its rollout switch from being by­passed by the other twinned furnace. The coil of the iso­lation relay connects from the thermostat ”W” to 24 VAC common. The contacts of the relay connect ”R” to ”W” on the non-thermostat twin.
Page 25
Page 26
TWO-STAGE THERMOSTAT
TWIN
FIELD WIRING FOR TWINNING
SINGLE STAGE THERMOSTAT
TWIN
Call For Cool
Call For Fan
Call For 1st Stage Heat
Call For 2nd
StageHeat
R
Y
G
W1
W2
ISOLATION RELAY
TWIN
R
TWIN 1
Y
G
W
C
R
TWIN 2
Y
G
W
C
Call For Cool
Call For Fan
Call For Heat
R
Y
G
W
ISOLATION RELAY
TWIN
R
TWIN 1
Y
G
W
C
R
TWIN 2
Y
G
W
C
FIGURE 24
Service
WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury, death, or property damage.
Before servicing, disconnect all electrical power to furnace.
When servicing controls, label all wires prior to disconnecting. Take care to reconnect wires correctly.
Verify proper operation after servicing.
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.
Annual Furnace Maintenance
At the beginning of each heating season, and to comply with the Lennox Limited Warranty, your system should be checked by a licensed professional technician (or equiva­lent) as follows:
1 - Check wiring for loose connections, voltage at
indoor unit and amperage of indoor motor.
2 - Check the condition of the belt and shaft bearings
if applicable. 3 - Inspect all gas pipe and connections for leaks. 4 - Check the cleanliness of lters and change if
necessary (monthly). 5 - Check the condition and cleanliness of burners and
heat exchanger and clean if necessary. 6 - Check the cleanliness of blower assembly and
clean the housing, blower wheel and blower motor
if necessary . The blower motors are prelubricated
for extended bearing life. No further lubrication is
needed. 7 - Inspect the combustion air inducer and clean if
necessary. 8 - Evaluate the heat exchanger integrity by inspecting
the heat exchanger per the AHRI heat exchanger
inspection procedure. This procedure can be
viewed at www.ahrinet.org.
Page 26
Page 27
9 - Ensure sufcient combustion air is available to the
furnace. Fresh air grilles and louvers (on the unit and in the room where the furnace is installed) must be properly sized, open and unobstructed to provide combustion air.
10 - Inspect the furnace venting system to make sure
it is in place, structurally sound, and without holes, corrosion, or blockage. Vent system must be free and clear of obstructions and must slope upward away from the furnace . Vent system should be installed per the National Fuel Gas Code
11 - Inspect the furnace return air duct connection to
ensure the duct is sealed to the furnace. Check for air leaks on supply and return ducts and seal where necessary.
12 - Check the condition of the furnace cabinet insulation
and repair if necessary.
13 - Perform a complete combustion analysis during the
furnace inspection to ensure proper combustion and operation. Consult Service Literature for proper combustion values.
14 - Verify operation of CO detectors and replace
batteries as required.
Perform a general system test. Turn on the furnace to check operating functions such as the start-up and shut-
off operation.
1 - Check the operation of the ignition system, inspect
and clean ame sensor. Check microamps before
and after. Check controls and safety devices (gas
valve, ame sensor, temperature limits). Consult
Service Manual for proper operating range. Thermal
Limits should be checked by restricting airow and
not disconnecting the indoor blower. For additional details, please see Service and Application Note H049.
2 - Verify that system total static pressure and airow
settings are within specic operating parameters.
3 - Clock gas meter to ensure that the unit is operating
at the specied ring rate. Check the supply
pressure and the manifold pressure. On two-stage gas furnaces check the manifold pressure on high
re and low re. If manifold pressure adjustment is
necessary, consult the Service Literature for unit
specic information on adjusting gas pressure.
Not all gas valves are adjustable. Verify correct temperature rise.
Cleaning the Burners
NOTE - Use papers or protective covering in front of the furnace
during cleaning.
1 - Turn off both electrical and gas power supplies to
furnace.
2 - Label the wires from gas valve, rollout switches,
primary limit switch and make-up box then
disconnect them. 3 - Disconnect gas supply piping. Remove the four
screws securing the burner manifold assembly to
the vestibule panel and remove the assembly from
the unit. 4 - Remove 4 screws securing burner box and remove
burner box. 5 - To clean burners, run a vacuum cleaner with a soft
brush attachment over the face of burners. Visually
inspect inside the burners and crossovers for any
blockage caused by foreign matter. Remove any
blockage. Figure 25 shows burner detail. 6 - Reinstall burner box, manifold assembly and burner
box cover. 7 - Reconnect all wires. 8 - Reconnect gas supply piping. 9 - Turn on power and gas supply to unit. 10 - Set thermostat and check for proper operation. 11 - Check all piping connections, factory and eld, for
gas leaks. Use a leak detecting solution or other
preferred means.
CAUTION
Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly after leak test has been completed. Do not use matches,
candles, ame or other sources of ignition to check for
gas leaks.
12 - If a leak is detected, shut gas and electricity off and
repair leak. 13 - Repeat steps 12 and 13 until no leaks are detected. 14 - Replace access panel.
Page 27
Page 28
Ignitor
BURNER ASSEMBLY & REMOVAL
Burner Detail Front View
Rollout Switches
Sensor
Manifold And Gas Valve
Cross Over
Retention Rings
FIGURE 25
Repair Parts List
The following repair parts are available through independent Lennox dealers. When ordering parts, include the complete furnace model number listed on the CSA International nameplate -- Example: ML180DF110P60C-01. All service must be performed by a licensed professional installer (or equivalent), service agency, or gas supplier.
Cabinet Parts
Upper access panel Blower panel Top cap
Control Panel Parts
Transformer Integrated control Door interlock switch Circuit breaker
Blower Parts
Blower wheel Blower housing Motor
Heating Parts
Flame sensor Heat exchanger assembly Gas manifold Combustion air inducer Gas valve Main burner cluster
Main burner orices
Pressure switch Ignitor Primary limit control Flame rollout switch (s) Secondary limit
Motor mounting frame Motor capacitor Blower housing cutoff plate
Page 28
Loading...