AVERTISSEMENT : Assurez-vous de bien suivre les
instructions données dans cette notice pour réduire au
minimum le risque d’incindie ou d’explosion ou pour
éviter tout dommage matériel, toute blessure ou la mort.
WARNING: If the information in these instructions
is not followed exactly, a fire or explosion may
result, causing property damage, personal injury,
or death.
WARNING /AVERTISSEMENT/AVISO
• HOT GLASS WILL CAUSE
BURNS.
• DO NOT TOUCH GLASS
UNTIL COOLED.
• NEVER ALLOW CHILDREN
TO TOUCH GLASS.
• UNE SURFACE VITRÉE CHAUDE
PEUT CAUSER DES BRÛLURES.
• LAISSER REFROIDIR LA SURFACE
VITRÉE AVANT D'Y TOUCHER.
• NE PERMETTEZ JAMAIS À UN ENFANT
DE TOUCHER LA SURFACE VITRÉE.
• EL VIDRIO CALIENTE
CAUSARÁ QUEMADURAS.
• USTED DEBE NUNCA
TOCAR EL VIDRIO CALIENTE.
• LOS NIÑOS DEBEN NUNCA
TOCAR EL VIDRIO.
- Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the fire
department.
- Installation and service must be performed by a
qualified installer, service agency or the gas supplier.
- Ne pas entreposer ni utilizer d’essence ni d’autres vapeurs
ou liquides inflammables dans le voisinage de cet appareil
ou de tout autre appareil.
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucan interrupteur. Ne pas vous servir des
téléphones se trouvant dans le bâtiment où vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis
un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service des incindies.
- L’installation et l’entretien doivent être assurés par un
installateur ou un service d’entretien qualifié ou par le
fournisseur de gaz.
MLDVTCD Direct-Vent
Gas Fireplaces
P/N 506015-09 Rev. A 04/2013
This manual is one of a set of two supporting this product.
Refer to P/N 506017-08 for Care and Operation Instructions.
Ce manuel est disponible en francais, simplement
en faire la demande. Numéro de la pièce 506223-60.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
INSTALLATEUR : Laissez cette notice avec l’appareil.
CONSOMMATEUR : Conservez cette notice pour
consultation ultérieure.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile
home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the
rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
MODELS
MLDVTCD-35NM
MLDVTCD-35NM-FB
Report No. 100353019PRT-002
Please read and understand these instructions
before starting installation.
ELECTRONIC:MILLIVOLT:
MLDVTCD35NE-2
MLDVTCD-35NE-FB
™
Page 2
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
TABLE OF CONTENTS
Packaging ............................ 2
Introduction .......................... 2
General Information .................... 2
Requirements for the Commonwealth
of Massachusetts ...................... 4
Cold Climate Insulation.................. 4
Manufactured Home Requirements ........ 5
Location ............................. 5
Vent Termination Clearances ............. 6
Minimum Clearance to Combustibles ....... 8
Pre-Installation Steps ................... 9
Typical Installation Sequence ............. 9
Detailed Installation Steps................ 9
Optional Blower Kit Wiring ............... 9
Framing.............................. 9
Fireplace and Framing Specifications ...... 10
Routing Gas Line ..................... 11
Installing the Venting System . . . . . . . . . . . . 12
Vertical Termination Systems ............ 12
Vent Section Length Chart .............. 13
Vertical Vent Tables and Figures .......... 16
Horizontal Termination System........... 18
Horizontal Vent Tables and Figures ........ 20
Venting Using Flexible Vent Pipe.......... 22
Field Wiring.......................... 23
Optional Blower Kit Wiring .............. 24
Connecting Gas Line................... 24
Verifying Appliance Operation............ 25
Installing Logs ....................... 26
Removing/Installing Glass Door .......... 28
Adjusting Burner...................... 28
Installing Hood ....................... 30
Finishing Requirements ................ 30
Attaching Safety-in-Operation Warnings.... 31
Installation Accessories ................ 32
Gas Conversion Kits ................... 34
Please read and understand these
instructions before beginning
your installation.
2
PACKAGING
The assembled vented gas fireplace heater
is packaged with:
• Literature Kit
(Envelope in bottom compartment
containing Care and Operation
Instructions, Installation Instructions,
Safety-In-Operation Warning Labels,
Warranty)
• (1) U-Shaped Vent Restrictor
(Attached to Literature Kit envelope)
• (1) Hood
(Inside firebox)
• One of the following contemporary floor
media kits (sold separately):
• Tumbled River Stone
• Crushed Glass, Obsidian Black
• Crushed Glass, Diamond White
• Crushed Glass, Deep Sea Blue
• White Beach Sand
• Optional Contemporary facade kits
(sold separately)
INTRODUCTION
Millivolt appliances have a millivolt gas
control valve with piezo ignition system. If
any optional accessories that will require
electrical power are to be installed, the
electrical power must be provided at the
time of appliance installation.
Electronic appliances are designed to
operate on natural or propane gas. An
electronic intermittent pilot ignition system
provides safe, efficient operation. External
electrical power is required to operate
these units. In the event of a power outage,
four (4) “AA” batteries (in battery holder)
provide backup power for appliance
operation (excluding [optional] blower).
These vented gas fireplace heaters
are sealed combustion, aircirculating gas fireplaces designed for
residential applications.
Approved Vent Components
These fireplaces are designed, tested and
listed for operation and installation with the
following vent components only:
• Secure Vent® Direct-Vent System
Components manufactured by Security
Chimneys International,
• Secure Flex® Flexible Vent Components
manufactured by Security Chimneys
International, and
• Z-FLEX® Model GA Venting Systems
listed to UL1777 and ULCS635
manufactured by Flexmaster
Canada Limited.
Use only the correct size venting (4 1/2 in.
inner and 7 1/2 in. outer).
These approved vent system components
are labeled for identification. DO NOT use
any other manufacturer’s vent components
with these appliances.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
GENERAL INFORMATION
WARNING
Young children should be
carefully supervised when
they are in the same room
as the appliance. Toddlers,
young children and others may
be susceptible to accidental
contact burns. A physical
barrier is recommended if
there are at-risk individuals in
the house. To restrict access
to a fireplace or stove, install
an adjustable safety gate to
keep toddlers, young children
and other at risk individuals
out of the room and away from
hot surfaces.
AVERTISSEMENT
Les jeunes enfants devraient
être surveillés étroitement
lorsqu’ils se trouvent dans la
même pièce que l’appareil.
Les tout petits, les jeunes
enfants ou les adultes
peuvent subir des brûlures
s’ils viennent en contact
avec la surface chaude. Il
est recommandé d’installer
une barrière physique si des
personnes à risques habitent
la maison. Pour empêcher
l’accès à un foyer ou à un
poêle, installez une barrière
de sécurité; cette mesure
empêchera les tout petits,
les jeunes enfants et toute
autre personne à risque
d’avoir accès à la pièce et aux
surfaces chaudes.
NOTE: Children and adults should be alerted
to the hazards of high surface temperature
and should stay away to avoid burns or
clothing ignition.
Remarqué : Les enfants et les adultes
devraient être infor-més des dangers
que posent les températures de surface
élevées et se tenir à distance afin d’éviter
des brûlures ou que leurs vêtements ne
s’enflamment.
DO NOT ATTEMPT TO ALTER OR
MODIFY THE CONSTRUCTION OF THE
APPLIANCE OR ITS COMPONENTS.
ANY MODIFICATION OR ALTERATION
MAY VOID THE WARRANTY,
CERTIFICATION, AND LISTINGS OF
THIS UNIT.
Page 3
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
WARNING
Improper installation,
adjustment, alteration, service
or maintenance can cause injury
or property damage. Refer to
this manual. For assistance or
additional information consult
a qualified installer, service
agency or the gas supplier.
WARNING
Failure to comply with these
installation instructions will
result in an improperly installed
and operating appliance, voiding
its warranty. Any change to this
appliance and/or its operating
controls is dangerous.
WARNING
Clothing or other flammable
material should not be placed on
or near the appliance.
AVERTISSEMENT
On ne devrait pas placer de
vêtements ni d’autres matières
inflammables sur l’appareil ni à
proximité.
WARNING
Any safety screen or guard
removed for servicing the
appliance must be replaced prior
to operating the appliance.
AVERTISSEMENT
Tout écran ou protecteur retiré
pour permettre l’entretien de
l’appareil doit être remis en
place avant de mettre l’appareil
en marche.
WARNING
Improper installation or use of
this appliance can cause serious
injury or death from fire, burns,
explosion or carbon monoxide
poisoning.
WARNING
Failure to position the parts in
accordance with these diagrams
or failure to use only parts
specifically approved with this
appliance may result in property
damage or personal injury.
AVERTISSEMENT
Risque de dommages ou de
blessures si les pièces ne sont
pas installées conformément à
ces schémas et ou si des pièces
autres que celles spécifiquement
approuvées avec cet appareil
sont utilisées.
NOTE: Installation and repair should be
done by a qualified service person. The
appliance should be inspected before use
and at least annually by a professional
service person. More frequent cleaning
may be required due to excessive lint from
carpeting, bedding material, etcetera. It
is imperative that control compartments,
burners and circulating air passageways of
the appliance be kept clean.
Remarqué : L’installation et la
réparation devrait être confiées à un
technicien qualifié. L’appareil devrait
faire l’objet d’une inspection par un
technicien professionnel avant d’être
utilisé et au moins une fois l’an par la
suite. Des nettoyages plus fréquents
peuvent être nécessaires si les tapis,
la literie, et cetera produisent une
quantité importante de pous-sière. Il
est essentiel que les compartiments
abritant les commandes, les brûleurs
et les conduits de circulation d’air de
l’appareil soient tenus propres.
NOTE: Do not use these appliances if any
part has been under water. Immediately call
a qualified, professional service technician
to inspect the appliance and to replace any
parts of the control system and any gas
control which have been under water.
Remarqué : Ne pas utiliser cet appareil
s’il a été plongé, même partiellement,
dans l’eau. Appeler un technicien
qualifié pour inspecter l’appareil et
remplacer toute partie du système de
commande et toute commande qui a été
plongée dans l’eau.
NOTE: Only trim kit(s) supplied by
the manufacturer shall be used in the
installation of this appliance.
Remarqué : Seules les trousses de
garniture fournies par le fabricant
doivent être utilisées pour l’installation
de cet appareil.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Codes and Standards
These appliances comply with National
Safety Standards and are tested and
listed by ETL/Intertek. (Report No.
100353019PRT-002) to ANSI Z21.50
(in Canada, CSA 2.22), and CAN/
CGA-2.17-M91 in both USA and Canada, as
vented gas fireplaces.
Both millivolt and electronic versions of
these appliances may be used in bedrooms
only when the room is an “unconfined
space” as defined by the National Fuel Gas
Code. Use in bedrooms may not be allowed
by your local building codes. You should
obtain prior approval from the Authority
Having Jurisdiction prior to installation.
The installation must conform to local
codes or, in the absence of local codes, with
the National Fuel Gas Code, ANSI Z223.1/
NFPA 54—latest edition (In Canada, the
current CAN/CSA-B149.1 installation code).
The appliance, when installed, must
be electrically grounded and wired in
accordance with local codes or, in the
absence of local codes, with the National
Electrical Code, ANSI/NFPA 70—latest
edition, or the Canadian Electrical Code,
CSA C22.1—latest edition.
Provide adequate clearances around
air openings and adequate accessibility
clearance for service and proper operation.
Never obstruct the front or back openings
of the appliance.
These appliances are designed to operate
on natural or propane gas only. The use
of other fuels or combination of fuels will
degrade the performance of this system and
may be dangerous.
These appliances are designed as
decorative fireplaces. It is advisable to have
an alternate primary heat source when
installed in a dwelling.
These appliances must not be connected to
a chimney or flue serving a separate solid
fuel burning appliance.
Electronic models come standard with
a remotely-modulated gas valve. Flame
appearance and heat output cannot be
controlled at the gas valve. The BTU Input
for these appliances is shown in Table 1.
Table 1: Input Rate, Gas Valves
Models
MLDVTCD-35
Input Rate (BTU/HR)
Natural GasPropane Gas
14,500 high
11,500 low
13,500 high
10,500 low
3
Page 4
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
Gas Pressure
Table 2 and Table 3 show the appliance
inlet and manifold gas pressure
requirements.
Table 2: Inlet Gas Supply Pressure
FuelMinimumMaximum
Natural Gas
Propane
4.5 in. WC
(1.12 kPa)
11.0 in. WC
(2.74 kPa)
Table 3: Manifold Gas Supply Pressure
FuelLowHigh
Natural Gas
Propane
2.2 in. WC
(0.55 kPa)
6.3 in. WC
(1.57 kPa)
Test gauge connections are provided on
the front of the electronic gas control valve
(identified IN for the inlet and OUT for the
manifold side). The control valves have a
3/8 in. (10 mm) NPT thread inlet and outlet
side of the valve (Figure 1 and Figure 2 ).
Figure 1: SIT Millivolt Gas Valve
Main Gas Control Knob
OFF/PILOT/ON
N
O
T
O
it
L
I
P
O
F
F
OUT
IN
Manifold Pressure Tap
Inlet Pressure Tap
W
O
H
I
Figure 2: SIT Electronic Gas Valve
Green Wire
Inlet (IN) Test Port
Manifold (OUT)
Test Port
Orange Wire
(from DFC
Wire
Harness)
Main
Gas Inlet
3/8 in. NPT
(from DFC Wire
Propane tanks are at pressures that will
cause damage to valve components. Verify
that the tanks have step down regulators to
4
reduce the pressure to safe levels.
10.5 in. WC
(2.61 kPa)
13.0 in. WC
(3.23 kPa)
3.5 in. WC
(0.87 kPa)
10.0 in. WC
(2.49 kPa)
Pilot Adjustment
Screw
T
O
L
I
P
L
HI/LO Variable
Flame Height
Adjustment
Hi/Lo
Flame
Harness)
Yellow Ground Wire
(from DFC
Wire Harness)
Control
Knob
The appliance and its appliance main gas
valve must be disconnected from the gas
supply piping system during any pressure
testing of that system at test pressures in
excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from
the gas supply piping system by closing
its equipment shutoff valve during any
pressure testing of the gas supply piping
system at test pressures equal to or less
than 1/2 psi (3.5 kPa).
Orifice Sizes—Sea Level to
High Altitude
These appliances are tested and approved
for installation at elevations of 0–4500 ft
(0–1372 m) above sea level using the
standard burner orifice sizes (marked with
an “*” in Table 4).
For elevations above 4500 ft, contact your
gas supplier or qualified service technician.
Deration
At higher elevations, the amount of BTU fuel
value delivered must be reduced by either:
• Using gas that has been derated by the
gas company.
• Changing the burner orifice to a
smaller size as regulated by the local
authorities having jurisdiction and by
the (USA) National Fuel Gas Code NFPA
HTPTHTPT
54/ANSI Z223.1—latest edition or, in
Canada, the CAN/CSA-B149.1 codes—
latest edition.
NOTE: Flame breadth, height and width will
diminish 4% for every 1,000 feet of altitude.
Table 4: Burner Orifice Sizes,
Elevation 0–4500 ft ( 0–1372 m)
Model
MLDVTCD-35
* Standard size installed at factory
• Catalog number
Natural Gas
drill size
(inches)
#49 (0.073 in.)*
21L82•
(0.045 in.)*
In Canada—CAN/CGA-2.17-M91
(high altitude):
THE CONVERSION SHALL BE CARRIED
OUT BY A MANUFACTURER’S
AUTHORIZED REPRESENTATIVE, IN
ACCORDANCE WITH THE REQUIREMENTS
OF THE MANUFACTURER, PROVINCIAL
OR TERRITORIAL AUTHORITIES HAVING
JURISDICTION AND IN ACCORDANCE
WITH THE REQUIREMENTS OF THE
CAN/CGA-B149.1 OR CAN/CGA-B149.2
INSTALLATION CODES.
REQUIREMENTS FOR THE
COMMONWEALTH OF
MASSACHUSETTS
These fireplaces are approved for
installation in the U.S. state of
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Propane
drill size
(inches)
75L10•
Massachusetts if the following additional
requirements are met:
• Install this appliance in accordance with
Massachusetts Rules and Regulations
248 C.M.R..
• Installation and repair must be done by
a plumber or gas fitter licensed in the
Commonwealth of Massachusetts.
• The flexible gas line connector used
shall not exceed 36 in. (92 cm)
in length.
• The individual manual shut-off must be
a T-handle type valve.
Massachusetts Horizontal Vent
Requirements
In the Commonwealth of Massachusetts,
horizontal terminations installed less than
seven (7) feet above the finished grade
must comply with the following additional
requirements:
• A hard wired carbon monoxide detector
with an alarm and battery back-up must
be installed on the floor level where the
gas fireplace is installed. The carbon
monoxide detector must comply with
NFPA 720, be ANSI/UL 2034 listed and
be ISA certified.
• A metal or plastic identification plate
must be permanently mounted to the
exterior of the building at a minimum
height of eight (8) feet above grade and
be directly in line with the horizontal
termination. The sign must read, in
print size no less than one-half (1/2)
inch in size, GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS.
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks
around your appliance with noncombustible
material and wherever cold air could enter
the room. It is especially important to
insulate outside chase cavity between studs
and under floor on which appliance rests, if
floor is above ground level. Gas line holes
and other openings should be caulked or
stuffed with unfaced fiberglass insulation.
If the fireplace is being installed on a
cement slab in cold climates, a sheet of
plywood or other raised platform can be
placed underneath to prevent conduction
of cold transferring to the fireplace and
into the room. It also helps to sheetrock
inside surfaces and tape for maximum air
tightness and caulk firestops.
Page 5
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
MANUFACTURED HOME
REQUIREMENTS
This appliance may be installed in
an aftermarket permanently located,
manufactured home and must be installed
in accordance with the manufacturer’s
instructions.
Cet appareil peut être installé cómme
du matéri-el d’origine dans une maison
préfabriquée (É.U. seulement) ou
mobile et doit être installé selon les
instructions du fabricant.
This appliance is only for use with the type
of gas indicated on the rating plate. This
appliance is not convertible for use with
other gases, unless a certified kit is used.
Cet appareil doit être utilisé uniquement
avec le type de gaz indiqué sur la plaque
signalétique. Cet appareil ne peut être
converti à d’autres gaz, sauf si une
trousse de conversion est utilisée.
CAUTION
Ensure that the cross members
are not cut or weakened during
installation. The structural
integrity of the manufactured
home floor, wall, and ceiling /
roof must be maintained.
LOCATION
In selecting the location, the aesthetic and
functional use of the appliance are primary
concerns. However, vent system routing to
the exterior and access to the fuel supply
are also important.
Due to high temperatures, the appliance
should be located out of traffic and away
from furniture and draperies (Figure 3).
En raison des températures élevées,
l’appareil devrait être installé dans
un endroit où il y a peu de circulation
et loin du mobilier et des tentures
(Figure 3).
Figure 3: Typical Locations
TNEVPOT
NOITACILPPA
NOITACILPPA
TNEVPOT
NOITACILPPA
TNEVPOT
APPLICATION
TOP VENT
RECESSED
INSTALLATION
NOITACILPPA
TNEVPOT
TOP VENT
APPLICATION
The minimum height from the base of the
appliance to the underside of combustible
materials used to construct a utility shelf in
this fashion is shown in Table 8.
The appliance must be mounted on a
fully supported base extending the full
width and depth of the unit. The appliance
may be located on or near conventional
construction materials. However, if
installed on combustible materials, such as
carpeting, vinyl tile or other combustible
material other than wood flooring, the
appliance shall be installed on a metal or
wood panel extending the full width and
depth of the appliance.
NOTE: When the unit is installed with
one side flush with a wall, the wall
on the other side of the unit must
not extend beyond the front edge of
the unit.
CAUTION
This appliance must be
grounded to the chassis of
the manufactured home in
accordance with local codes or
in the absence of local codes,
with the National Electrical Code
ANSI / NFPA 70—latest edition or
the Canadian Electrical Code CSA
C22.1—latest edition.
HORIZONTAL VENT
(Top Vent Application)
VERTICAL VENT
(Top Vent Application)
The location should also be free of
electrical, plumbing or other heating/air
conditioning ducting.
These direct-vent appliances are uniquely
suited for installations requiring a utility
shelf positioned directly above the fireplace.
Utility shelves like these are commonly
used for locating television sets and
decorative plants.
Be aware that this is a heat producing
appliance. Objects placed above the unit are
exposed to elevated temperatures.
Do not insulate the space between the
appliance and the area above it (Table 8).
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
5
Page 6
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
VENT TERMINATION CLEARANCES
These instructions should be used
as a guideline and do not supersede
local codes in any way. Install venting
according to local codes, these
instructions, the current National
Fuel Gas Code (ANSI-Z223.1) in the
USA or the current standards of CAN/
CSA-B149.1 in Canada.
Vertical Vent Termination Clearances
Terminate multiple vent terminations
according to the installation codes listed
above, Figure 4, Figure 5, and Table 5.
Figure 4: Multiple Terminations
12 in.
(305 mm)
Minimum
Figure 5: Vertical Vent Termination
Clearances
TERMINATION HEIGHTS FOR VENTS ABOVE
Horizontal Overhang
2 FT MIN.
Termination
Storm Collar
Flashing
Concentric
Vent Pipe
FLAT OR SLOPED ROOFS
Vent
*H = MINIMUM HEIGHT FROM ROOF TO
LOWEST DISCHARGE OPENING OF VENT
2 FT
MIN.
Lowest
Discharge
Opening
H*
1 inch (25.4 mm) Minimum
Clearance to Combustibles
Vertical
Wall
X
12
Roof Pitch is X/12
Table 5: Termination Heights for Vents
above Flat or Sloped Roofs
Roof PitchFeet *Meters *
Flat to 6 1/210.3
6 1/2 to 7 1/21 1/40.38
7 1/2 to 8 1/21 1/20.46
8 1/2 to 9 1/220.61
9 1/2 to 10 1/22 1/20.76
10 1/2 to 11 1/23 1/40.99
11 1/2 to 12 1/241.22
12 1/2 to 14 1/251.52
14 1/2 to 16 1/261.83
16 1/2 to 18 1/272.13
18 1/2 to 201/27 1/22.29
20 1/2 to 21 1/282.44
Horizontal Vent
Termination Clearances
The horizontal vent termination must have
a minimum of 6 in. (152 mm) clearance
to any overhead combustible projection of
2 1/2 in. (64 mm) or less. For projections
exceeding 2 1/2 in. (64 mm), see Figure 7.
For additional vent location restrictions,
refer to Table 6.
Figure 6: Horizontal Vent Termination
Clearances, Side Elevation
Combustible Projection
2-1/2
inches or less in length
Combustible Projection greater
than 2-1/2 inches in length
Ventilated
Soffit
Unventilated
Soffit
6"
18"
(457 mm)
12"
(305 mm)
Figure 7: Horizontal Vent Termination
Clearances
All horizontal terminations
may be located as close as
6” (152mm) to any
(non-combustible and
combustible) exterior
sidewall. This distance
may be decreased to 2”
(51mm) for non-combustible exterior
sidewalls only, if the
SV4.5HT-2 termination
is used.
(152 mm)
Termination Kit
Termination Kit
6
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 7
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
Clearance above grade, veranda, porch, desk, or balcony12 in. (300 mm) **12 in. (300 mm) *
A
Clearance to window or door that may be opened6 in. (150 mm)
B
for appliances < 10,000 Btuh (3 kW),
9 in. (230 mm)
for appliances > 10,000 Btuh (3 kW), and < 50,000 Btuh (15 kW),
12 in. (300 mm)
for appliances > 50,000 Btuh (15 kW) **
Clearance to permanently closed window9 in. (229 mm)
C
Vertical clearance to ventilated soffit located above the
D
termination within a horizontal distance of 18 in. (458 mm)
Clearance to unventilated soffit12 in. (305 mm)12 in. (305 mm)
E
Clearance to outside corner5 in. (127 mm)
F
Clearance to inside corner2 in. (50.8 mm)
G
recommended to prevent window condensation
18 in. (458 mm)18 in. (458 mm)
minimum
minimum—SV4.5HT-2 •
6 in. (152 mm)
minimum—SV4.5HTSS
Clearance to each inside of center line extended above
H
meter / regulator assembly
Clearance to service regulator vent outlet36 in. (910 mm)**36 in. (910 mm)*
I
Clearance to nonmechanical air supply inlet to building or
J
the combustion air inlet to any other appliance
36 in. (910 mm)
within a height of 15 ft above the meter / regulator assembly **
6 in. (150 mm)
for appliances < 10,000 Btuh (3 kW),
9 in. (230 mm)
for appliances > 10,000 Btuh (3 kW) and < 50,000 Btuh (15 kW),
12 in. (300 mm)
for appliances > 50,000 Btuh (15 kW)**
Clearance to a mechanical air supply inlet36 in. (910 mm) above if within 10 ft (3 m) horizontally **72 in. (1830 mm) *
K
Clearance above paved sidewalk or paved diveway located
L
on public property
Clearance under veranda, porch, deck or balcony12 in. (300 mm) *‡12 in. (300 mm) *‡
M
Depth of alcove (maximum)72 in. (1830 mm) **72 in. (1830 mm) *
N
Clearance to termination (alcove)6 in. (15.2 mm) **6 in. (15.2 mm)*
O
Width of alcove (minimum)36 in. (910 mm) **36 in. (910 mm) *
P
Clearance to combustible above (alcove)18 in. (457 mm) **18 in. (457 mm) *
Q
*
In accordance with the current CSA-B149.1 National Gas And Propane Installation Code
**
In accordance with the curent ANSI SZ223.1/NFPA 54 National Fuel Gas Codes
‡
A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
*‡
Only permitted if veranda, porch, deck, or balcony is fully-open on a minimum two sides beneath the floor
•
2 in. clearance to non-combustibles for SV4.5HT-2 only
84 in. (2130 mm) ‡84 in. (2130 mm) ‡
May Require Different Clearances.
NOTE: Location Of The Vent Termination
Must Not Interfere With Access To The
Electrical Service.
= 9 in. in U.S.
1
= 12 in. in Canada
3 ft
X
1
1
3 ft
J
N
H
M
I
6 in. (150 mm)
for appliances < 10,000 Btuh (3 kW),
12 in. (300 mm)
for appliances > 10,000 Btuh (3 kW)
12 in. (305 mm)
recommended to prevent
window condensation
5 in. (127 mm)
minimum
2 in. (50.8 mm)
minimum—SV4.5HT-2 •
6 in. (152 mm)
minimum—SV4.5HTSS
36 in. (910 mm)
within a height of 15 ft above the meter /
regulator assembly *
6 in. (150 mm)
for appliances < 10,000 Btuh (3 kW),
12 in. (300 mm)
for appliances > 10,000 Btuh (3 kW)
P
N
O
V
Q
D
E
V
V
X
K
7
Page 8
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
mantel legs may
MINIMUM CLEARANCE TO
COMBUSTIBLES
The appliance is approved with zero
clearance to combustible materials on
all sides (Table 7), with the following
exception: When the unit is installed with
one side flush with a wall, the wall on the
other side of the unit must not extend
beyond the front edge of the unit. In
addition, when the unit is recessed, the side
walls surrounding the unit must not extend
beyond the front edge of the unit (Figure 3).
Hearth Extension—A hearth extension is
not required with this appliance. If a hearth
extension is used, do not block the lower
control compartment door. Any hearth
extension used is for appearance only
and does not have to conform to standard
hearth extension installation requirements.
Shelf Height—To provide for the lowest
possible shelf surface, use the alternate
rear vent outlet, the venting attached to
the top vent should be routed in a way to
minimize obstructions to the space above
the appliance. Do not insulate the space
between the appliance and the area above
it (Table 8). The minimum height from the
base of the appliance to the underside of
combustible materials used to construct
a utility shelf in this fashion is shown in
Table 8.
The appliance should be mounted on a
fully supported base extending the full
width and depth of the unit. The appliance
may be located on or near conventional
construction materials. However, if
installed on combustible materials, such as
carpeting, vinyl tile, etc., a metal or wood
barrier covering the entire bottom surface
must be used.
Table 7: Minimum Clearances *
Back
Sides
Top of
Fireplace
Floor
From
Bottom
of Unit To
Ceiling
Vent
Front
Service
* Note: 3 in. (75 mm) above any horizontal/
inclined vent component.
** Note: See Frame the Fireplace on Page 9
for clearance requirements to the nailing flange
located at each side of the unit and any screw heads
adjacent to it.
0 in. (0 mm) from Spacers or Dimples
0 in. (0 mm) from Spacers or Dimples **
0 in. (0 mm) with standoff(s) in vertical
1 in. (25.4 mm)—Sides and Bottom
1/2 in. (13 mm)
1/2 in. (13 mm)
3 in. (76 mm)
position (Figure 10)
0 in. (0 mm)
minimum of 64 in. (1626 mm)
3 in. (76 mm)—Top *
36 in. (914 mm)
Table 8: Shelf Height Minimum Clearances
Do not insulate the
space between the
appliance and the
area above it.
Shelf Height
(see table)
Model
MLDVTCD-3546 1/2 in. (1181 mm)48 1/4 in. (1226 mm)
Secure VentSecure Flex
Wall Finishes, Surrounds,
and Mantels
NOTE: Combustible wall finish materials
and/or surround materials must not be
allowed to encroach the area defined by the
appliance front face (black sheet metal).
Never allow combustible materials to be
positioned in front of or overlapping the
appliance face (Figure 35 on Page 30).
Non-combustible materials, such as
surrounds and other appliance trim,
may be installed on the appliance face,
but they must not cover any portion of
the removable glass panel or control
compartment.
Vertical installation clearances to
combustible mantels vary according to the
depth of the mantel (Figure 8). Mantels
constructed of non-combustible materials
may be installed at any height above the
appliance opening. However, do not allow
anything to hang below the fireplace hood.
Minimum clearance requirements include
any projections such as shelves, window
sills, mantels, etc. above the appliance.
NOTE: We recommend the use of high
temperature paint (rated 175 °F, or higher)
on the underside of the mantel.
Top Vent—with One 90° Elbow
Figure 8: Minimum Mantel Clearances
Mantel
(305)
Depth
inches (millimeters)
Header
6
12
8
10
(203)
(254)
(152)
(102)
2
4
(51)
Top of
Appliance
Hood
18 (457)
16 (406)
14 (356)
12 (305)
10 (254)
8 (203)
Figure 9: Minimum Distance to
Side Wall
At 6 in. minimum
side wall clearance,
a combustible wall
can project to any
length.
o
45
6 in.
(152 mm)
3 1/2 in.
(89 mm)
Top View of
Fireplace
Combustible Materials
Allowed In Shaded Area
“Safe Zone”
Combustible Walls
shown in dark gray
Combustible
project beyond either side
of the fireplace opening
as long as they are kept
within the shaded area
illustrated here.
8
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 9
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
PRE-INSTALLATION STEPS
The appliance is shipped with all gas
controls and components installed and prewired. Before installing the appliance, follow
these steps:
1. Remove the shipping carton.
2. Remove the shipping pad, exposing the
front glass door.
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation is
outlined below; however, each installation
is unique and may result in variations to the
steps described.
1. Wire the [Optional] Blower Kit Before
Installation in the Framing
2. Frame the Fireplace
3. Route the Gas Line
4. Install the Vent System
5. Field Wiring
6. Wire the [Optional] Blower Kit After
Installation in the Framing
7. Connect the Gas Line
8. Verify Proper Appliance Operation
9. Install the Contemporary Media
10. Install the Glass Door
11. Adjust the Burner
12. Install the Hood
13. Attach the Safety-inOperation Warnings
DETAILED INSTALLATION STEPS
Follow these steps to complete fireplace
installation:
Wire the [Optional] Blower Kit Before
Installation in the Framing
Remove the left side blower cover panel
screw, and blower cover panel (Table 11).
Retain the panel and screw for later
reinstallation.
Slide the blower through the opening
and position it with the bracket oriented
to the front of the firebox and the blower
discharge to the rear of the firebox. Bend
the two tabs in the firebox floor to secure
the blower to the floor.
Reinstall the blower cover panel and secure
with the removed screw.
Access the blower supply wiring through
the front of the firebox and plug it into the
junction box in the right, rear of the firebox
(Figure 28).
Install the blower control switch according
to its included instructions.
Frame the Fireplace
Frame the appliance as illustrated in
Table 9 on Page 10. For corner
framing installations, use Table 10 on Page 10. All framing details must allow
for a minimum clearance to combustible
framing members as shown in Table 7 on Page 8.
If the appliance is to be elevated above floor
level, a solid continuous platform must be
constructed below the appliance.
Bend up the outer pair for 1/2 in. materials
and the inner pair for 5/8 in. materials.
Headers may be in direct contact with the
appliance top standoff spacers when they
are bent up vertically, maintaining the 3 in.
clearance to the fireplace top, but must
not be supported by them or notched to fit
around them. All construction above the
appliance must be self-supporting. DO NOT
use the appliance for structural support.
Bend out the appropriate nailing flanges
for the drywall/finish material to be
used (Figure 10). Nailing flanges are
provided for:
• flush framing,
• 1/2 in., and
• 5/8 in. framing depths.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Secure the fireplace to the side framing
members using the unit’s nailing flanges
—one top and bottom on each side of the
fireplace front (Figure 10). Use 8d nails or
their equivalent.
9
Page 10
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
Framing should be constructed
Inches (mm)
Table 9: Fireplace Framing Specifications
Model
MLDVTCD-35
Based on CSA P.4.1-09
mm895895984406
Note:
Diagrams, illustrations and photographs are not to scale. Consult installation
instructions. Product designs, materials, dimensions, specifications, colors, and
prices are subject to change or discontinuation without notice.
ABCD
in.35 1/435 1/438 3/416
VENT FRAMINGTOP VENT WITH ONE
90° ELBOW
B
1/2
of 2x4 or larger lumber
10-1/2
)
267
(
7
(178)
5-1/8
(130)
12-1/8
(308)
C
D
A
Add Minimum Of 6 in. For
Raised Platform If Installing
With Contemporary Facade.
Table 10: Fireplace Framing Specifications—Corner Installation with Horizontal Termination
Model
MLDVTCD-35
ABCDE
in.35 1/457 1/240 5/828 3/413 3/4
mm89514611032730349
Back wall of chase/enclosure
(including any finishing materials)
A
Raised Platform
Or Floor
D is the required framing depth dimension when the
finish material (drywall) thickness is 1/2 in. (13mm)
E
7 (178)
C
D
A
B
Inches
(millimeters)
10
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 11
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
Header Spacing Top Standoffs
(two pairs on front edge of firebox top)
Table 11: Fireplace Specifications
K
L
1/2
(13)
Top View
ModelEFGHJKLM
MLDVTCD-35
*CONCENTRIC FLUE
FLUE: 4 1/2 (114)
COMBUSTION AIR:
7 1/2 (190)
9 1/4 (235)
in.32 1/428 1/823 1/43235 1/42512 1/233
mm819714590813895635317838
NOTE: It is recommended that the gas be stubbed in from the left
side only.
ELECTRICAL INLET
KNOCKOUT - 2-3/4 X 2
J
E
Front View
G
H
M
(70 X 51) COVER PLATE
(With KNOCKOUT Right Side Only)
GAS INLET
KNOCKOUT
(Either Side)
F
INLET KNOCKOUT,
REQUIRING A FIELD
JUNCTION BOX
OPTIONAL
ELECTRICAL
PROVIDED
(Either Side)
3 (76)
EYEBROW
HOOD
16 (406)
5 7/8
(149)
Right Side View
9 1/2
(241)
1 5/8
3 (76)
(42)
5.125
(130.2)
0.5 (12.7)
BLOWER
ACCESS PANEL
0.525 (13.3)
Left Side View
Table 12: Thermal Efficiency (%)
Model
MLDVTCD-35—48—51
Natural GasPropane
AFUEP4AFUEP4
Figure 10: Unit Secured to Framing by
Nailing Flange
NOTE: Bend up the appropriate
header spacing top standoffs
before installing the fireplace.
Lift up outer pair for
1/2 in. finish materials
Side
Framing
Lift up inner pair for
5/8 in. finish materials
Unit Nailing
(No clearance to
combustible framing
is required)
Flange
NOTE: The nailing flanges, combustible
members, and screw heads in areas directly
adjacent to the nailing flanges are EXEMPT
from the 1/2 in. (13 mm) clearance to
combustible requirements for the firebox
outer wrapper.
Combustible framing may be in direct
contact with the nailing flanges and may be
located closer than 1/2 in. (13 mm) from
screw heads and the firebox wrapper in
areas adjacent to the nailing flanges.
Frame the opening to the exact dimensions
specified in the framing details in
this manual.
Vertical Venting through the Ceiling
Use a plumb line from the ceiling above
the appliance to locate center of the
vertical run. Cut and/or frame an opening,
10 1/2 x 10 1/2 in. (267 x 267 mm) inside
dimensions, about this center mark
(Figure 14).
Route the Gas Line
Route a 1/2 in. (13 mm) gas line to the
left side of the appliance as shown in
Figure 11. Gas lines must be routed,
constructed, and made of materials that
are in strict accordance with local codes
and regulations. All appliances are factoryequipped with a flexible gas line connector
and 1/2 in. shutoff valve. (see Connect the
Gas Line on Page 24).
Figure 11: Route the Gas Line
Left Side Front
Corner of Fireplace
Framing
Pipe Coupling
(Recommended)
6-1/2"
(152 mm)
3"
(76 mm)
Also see Table 11.
Properly size and route the gas supply
line from the supply regulator to the area
where the appliance is to be installed per
requirements outlined in the National Fuel
Gas Code, NFPA 54—latest edition (USA) or
CAN/CSA-B149.1—latest edition (Canada).
Never use galvanized or plastic pipe.
Refer to Table 13 for proper sizing of
the gas supply line, if black iron pipe is
being used. Gas lines must be routed,
constructed and made of materials that
are in strict accordance with local codes
and regulations. We recommend that a
qualified individual such as a plumber or
gas fitter be hired to correctly size and
route the gas supply line to the appliance.
Installing a gas supply line from the fuel
supply to the appliance involves numerous
considerations of materials, protection,
sizing, locations, controls, pressure,
sediment, and more. Certainly no one
unfamiliar and unqualified should attempt
sizing or installing gas piping.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
11
Page 12
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
A vent restrictor may be needed when
vertically terminating the vent system above
the roof (when using the appliance top vent),
install vent restrictor in the top vent of the
fireplace outlet on MPD35/40/45
and MPDT33 series models.
If needed, install the restrictor orientated as
shown, either from inside or outside the unit,
in the inner fireplace collar.
Table 13: Schedule 40 Black Iron Pipe—
Inside Diameter
Schedule 40
Pipe Length
(feet)
0–101/2 in.3/8 in.
10–401/2 in.1/2 in.
40–1001/2 in.1/2 in.
100–1503/4 in.1/2 in.
150–2003/4 in.1/2 in.
Natural
Gas
NOTE:
• All appliances are factory-equipped with
a flexible gas line connector and 1/2 in.
shutoff valve (Figure 29).
• See Massachusetts Horizontal Vent
Requirements on Page 4 for
additional requirements for installations
in the state of Massachusetts in the
USA.
• The gas supply line should Not be
connected to the appliance until
Connect the Gas Line on Page 24.
• A pipe joint compound rated for gas
should be used on the threaded joints.
Ensure propane resistant compounds
are used in propane applications. Be
very careful that the pipe compound
does not get inside the pipe.
• It is recommended to install a sediment
trap in the supply line as close as
possible to the appliance.
• Check with local building official for
local code requirements.
NOTE: If propane is used, be aware
that if tank size is too small (i.e., under
100 lbs, if this is the only gas appliance
in the dwelling. Ref. NPFA 58), there
may be loss of pressure, resulting
in insufficient fuel delivery (which
can result in sooting, severe delayed
ignition or other malfunctions). Any
damage resulting from an improper
installation, such as this, is not covered
under the limited warranty.
Propane
Gas
Install the Vent System
These instructions should be used
as a guideline and do not supersede
local codes in any way. Install venting
according to local codes, these
instructions, the current National Fuel
Gas Code (ANSI-Z223.1) in the USA or
the current standards of CAN/CSA-B149.1
in Canada.
Ensure clearances are in accordance
with local installation codes and the
requirements of the gas supplier.
Dégagement conforme aux codes
d’installa tion locaux et aux exigences
du foumisseunde gaz.
Use only approved vent components
(Page 2).
NOTE: These fireplaces must be vented
directly to the outside.
The vent system may not service multiple
appliances, and must never be connected to
a flue serving a separate solid fuel burning
appliance. The vent pipe is tested to be run
inside an enclosed wall (such as a chase).
There is no requirement for inspection
openings in the enclosing wall at any of the
joints in the vent pipe.
Installation of Vent Restrictor
A vent restrictor may be needed with
this appliance, install vent restrictor
(provided) in the appliance top flue outlet
as shown in Figure 12. It is held in place by
friction, only.
NOTE: The vent restrictor is included in
the firebox.
Select Venting System—
Horizontal or Vertical
With the appliance secured in framing,
determine vent routing and identify the
exterior termination location. The following
sections describe vertical (roof) and
horizontal (exterior wall) vent applications.
Refer to the section relating to your
installation. A list of approved venting
components are shown on Page 32.
A vent restrictor may be needed when
vertically terminating the vent system
above the roof (when using the appliance
top vent), install vent restrictor in the top
vent of the fireplace outlet. If needed, install
the restrictor orientated as shown, either
from inside or outside the unit, in the inner
fireplace collar.
Figure 12: Vent restrictor installation—
Top vent
U-SHAPED VENT
RESTRICTOR
INNER
FIREPLACE
COLLAR
APPLIANCE TOP
VENT OUTLET
Vertical Termination Systems
See Figure 13, Figure 20, Table 17, and Table 18 on Page 16 that illustrate the
various vertical venting configurations that
are possible for use with these appliances.
Secure Vent® pipe applications are shown in
these Figures; Secure Flex® pipe may also
be used. A vertical vent table summarizes
each system’s minimum and maximum
vertical and horizontal length values that
can be used to design and install the vent
components in a variety of applications.
Both these vertical vent systems terminate
through the roof. The minimum vent height
above the roof and/or adjacent walls is
specified in ANSI Z223.1 (In Canada, the
current CAN/CSA-B149.1 installation code)
by major building codes. Always consult
your local codes for specific requirements.
A general guide to follow is the Gas Vent
Rule (Figure 6 on Page 6).
12
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 13
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
Vertical (Straight) Installation
Determine the number of straight vent
sections required:
• 4 1/2 in. (114 mm),
• 10 1/2 in. (267 mm),
• 22 1/2 in. (572 mm),
• 34 1/2 in. (876 mm), and
• 46 1/2 in. (1181 mm)
net section lengths are available (Table 14
and Installation Accessories on Page 32). Plan the vent lengths so that
a joint does not occur at the intersection of
ceiling or roof joists (Table 14).
Figure 13: Vertical (Straight) Installation
SV4.5CGV-1
Termination
Max. 40 ft
(12.2 m)
Table 14: Vent Section Length
Nominal
Section Length
(in.)
Net Section
Length (in.)
Height of Vent
in.ft
4.50.375100001
90.75200002
10.50.875010001
151.25110002
19.51.625210003
211.75020002
22.51.875001001
25.52.125120003
31.52.625030003
612243648
4.510.522.534.546.5
SV4.5FA or
SV4.5FB Flashing
AND SV4.5SC
Storm Collar
1 in (25.4 mm)
Minimum
Clearance to
Combustibles
SV4.5VF
Firestop/Spacer*
*When using Secure Flex,
use Firestop/Spacer
SF4.5VF.
SV4.5L6/12/24/36/48
Vent Sections
Number of Vent Sections
Table 14: Vent Section Length
Nominal
Section Length
(in.)
Net Section
Length (in.)
Height of Vent
in.ft
34.52.875000101
37.53.125111003
43.53.625021003
453.75002002
46.53.875000011
49.54.125102003
514.25100012
55.54.625012003
574.75001102
665.25022004
67.55.625003003
695.75000202
726103004
73.56.125100203
79.56.625010203
816.75000112
907.5021014
91.57.625002013
937.75000022
968101204
97.58.125100023
1028.5200024
103.58.625000303
1089100304
1149.5020024
1179.75105006
118.59.875110305
12610.5001304
130.5 10.875101305
13511.25006006
13811.5000404
139.5 11.625000033
142.5 11.875100405
14412100034
15012.5010034
154.5 12.875110035
160.5 13.375020035
172.5 14.375000505
Total Qty
17714.75100506
18315.25010506
18615.5000044
190.5 15.875100045
196.5 16.375010045
205.5 17.125011507
20717.25000606
211.5 17.625100607
217.5 18.125010607
229.5 19.125001607
232.5 19.375000055
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
612243648
4.510.522.534.546.5
Number of Vent Sections
Table 14: Vent Section Length
Nominal
Section Length
(in.)
Net Section
Length (in.)
Total Qty
Height of Vent
in.ft
23719.75100056
241.5 20.125000707
24620.5100708
25221010708
26422001708
27623000808
27923.25000066
280.5 23.375100809
283.5 23.625100067
289.5 24.125010067
301.5 25.125001067
310.5 25.875000909
31526.51009010
325.5 27.125000077
33027.5100078
33628010078
34528.7500010010
349.5 29.12510010011
37231000088
376.5 31.375100089
379.5 31.62500011011
418.5 34.875000099
42335.251000910
46538.7500001010
612243648
4.510.522.534.546.5
Number of Vent Sections
Table 15: Effective Vent Length
ModelEffective Length
SV4.5L64 1/2 in.
SV4.5L1210 1/2 in.
SV4.5L2422 1/2 in.
SV4.5L3634 1/2 in.
SV4.5L4846 1/2 in.
Total Qty
13
Page 14
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
Vertical (Offset) Installation
Analyze the vent routing and determine the
quantities of vent sections and number of
elbows required. Refer to Table 14 to select
the type of vertical installation desired. Vent
sections are available in net lengths of
• 4 1/2 in. (114 mm),
• 10 1/2 in. (267 mm),
• 22 1/2 in. (572 mm),
• 34 1/2 in. (876 mm), and
• 46 1/2 in. (1181 mm).
Refer to Table 14 for an aid in selecting
length combinations. Elbows are available
in 90° and 45° configurations. Refer to
Figure 17 for the SV4.5E45 and SV4.5E90
elbow dimensional specifications.
Where required, a telescopic vent section
(SV4.5LA) may be used to provide the
installer with an option of installing in
tight and confined spaces or where the
vent run made up of fixed length pieces
develops a joint in a undesirable location,
or will not build up to the required length.
The SV4.5LA telescopic vent section
has an effective length of from 1 1/2 in.
(38 mm) to 7 1/2 in. (191 mm). The
SV4.5LA is fitted with a locking inclined
channel end (identical to a normal vent
section component) and a plain end with
3 pilot holes. Slip the plain end over the
locking channel end of a standard SV4.5
vent component the required distance and
secure with three (3) screws.
Maintain a minimum 1 in. (25 mm)
clearance to combustible materials for
all vertical elements. Clearances for all
horizontal elements are 3 in. (76 mm)
on top, 1 in. (25 mm) on sides and 1 in.
(25 mm) on the bottom.
1. Frame ceiling opening—Use a
plumb line from the ceiling above the
appliance to locate center of the vertical
run. Cut and/or frame an opening,
10 1/2 x 10 1/2 in. (267 x 267 mm)
inside dimensions, about this center
mark (Figure 14).
Figure 14: Framing Ceiling Opening
Min. 10 1/2 in.
(267 mm)
Min. 10 1/2 in.
(267 mm)
2. Attach vent components to
appliance—Secure Vent® SV4.5
direct vent system components are
unitized concentric pipe components
14
featuring positive twist lock connections
(Figure 15).
All of the appliances covered in this
document are fitted with collars having
locking inclined channels.The dimpled
end of the vent components fit over the
appliance collar to create the positive
twist lock connection.
To attach a vent component to the
appliance collar, align the dimpled
end over the collar, adjusting the
radial alignment until the four locking
dimples are aligned with the inlet of
the four inclined channels on the collar
(Figure 15).
Push the vent component against the
collar until it fully engages, then twist
the component clockwise, running the
dimples down and along the incline
channels until they seat at the end of
the channels. The unitized design of the
Secure Vent components will engage
and seal both the inner and outer pipe
without the need for sealant or screws.
If desired a #6 x 1/2 in. screw may be
used at the joint, but it is not required as
the pipe will securely lock when twisted.
NOTE: An elbow may also be attached
to the appliance collar. Attach in the
same manner as a vent section.
3. Attach vent components to each
other—Other vent sections may be
added to the previously installed section
in accordance with the requirements
of the vertical vent figures and tables.
To add another vent component to a
length of vent run, align the dimpled
end over the inclined channel end
of the previously installed section,
adjusting the radial alignment until the
four locking dimples are aligned with
the inlets of the four incline channels
of the previous section. Push the
vent component against the previous
section until it fully engages, then twist
the component clockwise running the
dimples down and along the incline
channels until they seat at the end of
the channels.This seating position is
indicated by the alignment of the arrow
and dimple (Figure 15).
4. Install firestop/spacer at ceiling—
When using Secure Vent, use SV4.5VF
firestop/spacer at ceiling joists; when
using Secure Flex®, use SF4.5VF
firestop/spacer. If there is living space
above the ceiling level, the firestop/
spacer must be installed on the bottom
side of the ceiling. If attic space is
above the ceiling, the firestop/spacer
must be installed on the top side of the
joist. Route the vent sections through
the framed opening and secure the
firestop/spacer with 8d nails or other
appropriate fasteners at each corner.
Maintain 1 in. (25 mm) clearance to
combustibles, framing members,
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
and attic or ceiling insulation when
running vertical chimney sections.
Attic insulation shield (H3907) may be
used to obtain the required clearances
indicated here (Installation Accessories on Page 32). The gap between the
vent pipe and a vertical firestop can be
sealed with non-combustible caulking.
5. Support the vertical vent run
sections—Support the vertical portion of
the venting system every 8 ft (2.4 m) above
the fireplace vent outlet. One method of
support is by utilizing field provided support
straps (conventional plumber’s tape).
Secure the plumber’s tape to the framing
members with nails or screws. Loop the
tape around the vent, securing the ends of
the tape to the framing. If desired, sheet
metal screws #6 x 1/2 in. length may be
used to secure the support straps to the
vent pipe(Figure 16).
NOTE: Proper venting support is
very important. The weight of the vent
must not be supported by the fireplace.
Figure 15: Twist Lock Vent Pipes
Align the dimple (four places)
of the upper vent section with
the opening of the locking
incline channel on the lower vent
section or appliance collar. Twist
vent component clockwise to
engage and seal until arrow and
Arrow
Dimple
Appliance Collar or
Vent Section
dimple align.
Locking
Incline
Channel
Connected Vent
Sections
Arrow
Figure 16: Supporting the Vertical
Vent Run
Blocking
Support Straps
(Plumber's tape)
8 feet (2.4 m)
Maximum
1/2 inch (12.7
mm) minimum
clearance to
combustibles
Page 15
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
C
D
Storm
Collar
SV4.5E90
(90
°
Elbow)
8 1/8 in.
(206 mm)
Swivel Joint
(360
°
swivel)
4 13/16 in.
(122 mm)
SV4.5E45
(45
°
Elbow)
Swivel Joint
(360
°
swivel)
6. Change vent direction to horizontal/
inclined run—At transition from or
to a horizontal/inclined run, install
the SV4.5E45 and SV4.5E90 elbows
in the same manner as the straight
vent sections. The elbows feature
a twist section to allow them to be
routed about the center axis of their
initial collar section to align with the
required direction of the next vent run
element. Twist elbow sections in a
clockwise direction only so as to avoid
the possiblity of unlocking any of the
previously connected vent sections
(Figure 15).
Figure 17: Vent Elbows
7. Continue installation of horizontal/
inclined sections—Continue with the
installation of the straight vent sections
in horizontal/inclined run as described
on Page 14. Install support straps
every 5 ft (1.52 m) along horizontal/
inclined vent runs using conventional
plumber’s tape.
It is very important that the horizontal/
inclined run be maintained in a straight
(no dips), slightly elevated plane. The
recommended incline is approximately
1/4 in. per foot (20 mm per meter)
horizontal, in a direction away from
the fireplace. Rise per foot run ratios
that are smaller are acceptable all the
way down to at or near level. Use a
carpenter’s level to measure from a
constant surface and adjust the support
straps as necessary.
It is important to maintain the required
clearances to combustibles:
• 1 in. (25 mm) at all sides for all
vertical runs; and
• 3 in. (76 mm) at the top,
• 1 in. (25 mm) at sides, and
• 1 in. (25 mm) at the bottom for all
horizontal/inclined runs.
8. Frame roof opening—Identify location
for vent at the roof. Cut and/or frame
opening (Table 16).
Table 16: Framing Dimensions for Roof
PitchCD
0/12
6/12
12/12
10 1/2 in.
(267 mm)
10 1/2 in.
(267 mm)
10 1/2 in.
(267 mm)
10 1/2 in.
(267 mm)
12 in.
(305 mm)
17 3/4 in.
(451 mm)
9. Install the roof flashing—Extend
the vent sections through the roof
structure. Install the roof flashing over
the vent section and position such that
the vent column rises vertically (use
carpenters level) (Figure 18 ). Nail along
perimeter to secure flashing or adjust
roofing to overlap the flashing edges
at top and sides only and trim where
necessary. Seal the top and both sides
of the flashing with waterproof caulking.
Figure 18: Installing the Roof Flashing
and Storm Collar
10. Install the storm collar—Install the
storm collar, supplied with the flashing,
over the vent/flashing joint (Figure 18).
Loosen the storm collar screw. Slide
collar down until it meets the top of the
flashing. Tighten the adjusting screw.
Apply non-combustible caulking or
mastic around the circumference of the
joint to provide a water tight seal.
11. Install the vertical termination—The
final step involves installation of the
SV4.5CGV-1 vertical termination.
Extend the vent sections to the height
as shown in Vertical Vent Termination Clearances on Page 6. The
SV4.5CGV-1 vertical termination
(Figure 19) installs in the exact same
fashion as any other Secure Vent®
section. Align the termination over the
end of the previously installed section,
adjusting the radial alignment until the
four locking dimples of the termination
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
are aligned with the inlets of the four
incline channels of the last vent section.
Push the termination down until it fully
engages, then twist the termination
clockwise running the dimples down
and along the incline channels until they
are seated at the end of the channels.
Figure 19: SV4.5CGV-1 Vertical
Termination
NOTE: If the vent system extends
more than 5 ft (1.5 m) above the roof
flashing, stabilizers may be necessary.
Additional screws may be used at
section joints for added stability. Guide
wires may be attached to the joint for
additional support on multiple joint
configurations.
15
Page 16
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
Vertical Vent Tables and Figures
NOTE: Secure Vent® rigid vent pipe
is shown in the figures. Secure Flex®
flexible vent pipe may also be used.
NOTE: It is very important that the
horizontal/inclined run be maintained
in a straight (no dips), slightly elevated
plane. The recommended incline is
approximately 1/4 in. per foot (20 mm
per meter) horizontal, in a direction
away from the fireplace. The rise per
foot run ratios that are smaller are
acceptable all the way down to at or
near level.
NOTE: SV4.5VF (Secure Vent), SF4.5VF
(Secure Flex) firestop/spacer must be
used anytime vent pipe passes through
a combustible floor or ceiling. SV4.5HF
(Secure Vent), SF4.5HF (Secure Flex)
firestop/spacer must be used anytime
vent pipe passes through a combustible
wall.
NOTE: Two 45° elbows may be used in
place of one 90° elbow. The same rise
to run ratios, as shown in the venting
figures for 90°, must be followed if 45°
elbows are used.
NOTE: An elbow is acceptable as 1 foot
of vertical rise, except where an elbow
is the only vertical component in the
system (Table 20).
Figure 20: Top Vent—Straight
Table 17: Top Vent—Two 90° Elbows
H
Ceiling
Firestop/Spacer
SV4.5VF*
Wall
Firestop/Spacer
V1
*When using Secure Flex, use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
H MaximumV Maximum
feetmetersfeetmeters
51.524elbow only
51.52410.305
103.04820.610
154.57230.914
206.09641.219
V + V1 + H = 40 ft (12.2 m) maximum
H = 20 ft (6.096 m) maximum
Install the U-shaped vent restrictor in any vent run
with more than 8 ft of vertical rise (Figure 12).
SV4.5HF**
V
u Ceiling Firestop /
Spacer (SV4.5VF)
When using
u
Secure Flex, use
Firestop / Spacer
SF4.5VF
A Vent Restrictor
(Figure 12) must
be used in this
application
A Vent Restrictor (Figure 12) must be used in
this application.
16
40 ft (12.2 m)
Maximum
If 20 ft of (H) horizontal vent run is needed,
then 4 ft minimum of (V) vertical vent will
be required.
This table shows a 1 (V) to 5 (H) ratio. For
every 1 ft of (V) vertical, you are allowed
5 ft of (H) horizontal run, up to a maximum
horizontal run of 20 ft.
An elbow is acceptable as 1 ft of vertical rise
except where an elbow is the only vertical
component in the system (Table 20).
WARNING
Under no circumstances, may
separate sections of concentric
flexible vent pipe be joined
together.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 17
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
Table 18: Top Vent—Three Elbows
H + H1 MaximumV Minimum
feetmetersfeetmeters
51.524Elbow Only
51.52410.305
103.04820.610
154.57230.914
206.09641.219
H + H1 = 20 ft (6.1 m) maximum
V + V1 + H + H1 = 40 ft (12.2 m) maximum
Install the U-shaped vent restrictor in any vent run with more than 8 ft of
vertical rise (Figure 12).
If 20 ft of (H) horizontal vent run is needed, then 4 ft minimum
of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 ft of (V)
vertical, you are allowed 5 ft of (H) horizontal run, up to a
maximum horizontal run of 20 ft.
An elbow is acceptable as 1 ft of vertical rise except where an
elbow is the only vertical component in the system (Table 20).
Ceiling
V
1
Firestop/Spacer
SV4.5VF*
Wall
Firestop/Spacer
SV4.5HF**
H
H
1
V
*When using Secure Flex, use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
17
Page 18
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
Horizontal Termination System
Figure 21, and Table 20 to Table 23 on
Page 20 illustrate the various horizontal
venting configurations that are possible for
use with these appliances. Secure Vent®
pipe applications are shown in these
figures; Secure Flex® pipe may also be
used. A horizontal vent table summarizes
each system’s minimum and maximum
vertical and horizontal length values that
can be used to design and install the vent
components in a variety of applications.
Both of these horizontal vent systems
terminate through an outside wall. Building
Codes limit or prohibit terminating in
specific areas. Refer to Figure 3 on
Page 5 for location guidelines.
Secure Vent SV4.5 direct vent system
components are unitized concentric pipe
components featuring positive twist
lock connection (Figure 15). All of the
appliances covered in this document are
fitted with collars having locking inclined
channels. The dimpled end of the vent
components fit over the appliance collar to
create the positive twist lock connection.
1. Plan the vent run—Analyze the vent
routing and determine the types and
quantities of sections required:
• 4 1/2 in. (114 mm),
• 10 1/2 in. (267 mm),
• 22 1/2 in. (572 mm),
• 34 1/2 in. (876 mm), and
• 46 1/2 in. (1181 mm)
net section lengths are available. It is
recommended that you plan the venting
so that a joint does not occur in the
ceiling or roof joists. Allow for elbows
as indicated in (Figure 17).
Maintain a minimum 1 in. (25 mm)
clearance to combustibles on the
vertical sections. Clearances for the
horizontal runs are:
• 3 in. (76 mm) on top,
• 1 in. (25 mm) on sides, and
• 1 in. (25 mm) at the bottom.
2. Frame exterior wall opening—
Locate the center of the vent outlet
on the exterior wall according to
the dimensions shown in Table 9
on Page 10. Cut and/or frame
an opening, 10 1/2 x 12 1/8 in.
(267 x 308 mm) inside dimensions,
about this center.
3. Frame ceiling opening—If the
vertical route is to penetrate a ceiling,
use plumb line to locate the center
above the appliance. Cut and/or
frame an opening, 10 1/2 x 10 1/2 in.
(267 x 267 mm) inside dimensions,
about this center (Figure 14).
4. Attach vent components to
appliance—To attach a vent
component to the appliance collar,
18
align the dimpled end over the collar,
adjusting the radial alignment until the
four locking dimples are aligned with
the inlets of the four incline channels on
the collar (Figure 15).
Push the vent component against the
collar until it fully engages, then twist
the component clockwise, running the
dimples down and along the incline
channels until they are seated at the end
of the channels. The unitized design
of the Secure Vent components will
engage and seal both the inner and
outer pipe elements with the same
procedure. Sealant and securing screws
are not required.
NOTE: An elbow may also be attached
to the appliance collar. Attach in
the same manner as you would a
vent section.
5. Attach vent components to each
other—Other vent sections may be
added to the previously installed section
in accordance with the requirements
of the vent tables. To add another vent
component to a length of vent run,
align the dimpled end of the component
over the inclined channel end of the
previously installed section, adjusting
the radial alignment until the four
locking dimples are aligned with the
inlets of the four incline channels of
the previous section. Push the vent
component against the previous section
until it fully engages, then twist the
component clockwise running the
dimples down and along the incline
channels until they seat at the end of
the channels.This seating position is
indicated by the alignment of the arrow
and dimple as shown in (Figure 15).
6. Install firestop/spacer at ceiling—
When using Secure Vent, use SV4.5VF
firestop/spacer at ceiling joists; when
using Secure Flex, use SF4.5VF
firestop/spacer. If there is living space
above the ceiling level, the firestop/
spacer must be installed on the bottom
side of the ceiling. If attic space is
above the ceiling, the firestop/ spacer
must be installed on the top side of the
joist. Route the vent sections through
the framed opening and secure the
firestop/spacer with 8d nails or other
appropriate fasteners at each corner.
NOTE: Maintain 1 in. (25 mm) clearance
to combustibles, framing members, and
attic or ceiling insulation when running
vertical chimney sections.
7. Support the vertical run sections—On
the vertical run, support the venting
system every 8 ft (2.4 m) above the
fireplace vent outlet with field provided
support straps (Plumber’s tape). Attach
the straps to the vent pipe and secure
to the framing members with nails or
screws (Figure 16).
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
8. Change vent direction—At transition
from or to a horizontal/inclined run,
install the SV4.5E45 and SV4.5E90
elbows in the same manner as the
straight vent sections. The elbows
feature a twist section to allow them
to be routed about the center axis of
their initial collar section to align with
the required direction of the next vent
run element. Twist elbow sections in a
clockwise direction only so as to avoid
the possiblity of unlocking any of the
previously connected vent sections
(Figure 17).
9. Continue installation of horizontal/
inclined sections—Continue with the
installation of the straight vent sections
in horizontal/inclined run as described
in Step 5. Install support straps
every 5 ft. (1.52 m) along horizontal/
inclined vent runs using conventional
plumber’s tape (Figure 21). It is very
important that the horizontal/inclined
run be maintained in a straight (no
dips), slightly elevated plane. The
recommended incline is approximately
1/4 in. per foot (20 mm per meter)
horizontal, in a direction away from
the fireplace. Rise per foot run ratios
are acceptable to at or near level. Use
a carpenter’s level to measure from a
constant surface and adjust the support
straps as necessary.
It is important to maintain the required
clearances to combustibles:
• 1 in. (25 mm) on all sides for all
vertical runs; and
• 3 in. (76 mm) at the top,
• 1 in. (25 mm) on sides, and
• 1 in. (25 mm) at the bottom for all
horizontal/inclined runs.
10. Assemble vent run to exterior wall—If
not previously measured, locate the
center of the vent at the exterior wall.
Prepare an opening as described in
Step 2. Assemble the vent system
to point where the terminus of the
last section is within 7 in. (178 mm)
to 11 1/4 in. (286 mm) inboard of
the exterior surface to which the
SV4.5HT termination is to be attached
(Figure 23). If the terminus of the last
section is not within this distance,
use the telescopic vent section
SV4.5LA, as the last vent section.
For wall thicknesses greater than that
shown in Figure 23, refer to Table 19
on Page 20. This table lists the
additional venting components needed
(in addition to the termination and
adaptor) for a particular range of wall
thicknesses.
Page 19
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
TYPICAL HORIZONTAL VENT INSTALLATION
SV4.5HT-2
Termination
10-1/2 in.
(267mm)
7 in.
(178)
5 1/8 in.
(130 mm)
12 1/8 in.
(308 mm)
Note: Centerline of Vent Piping is
NOT the Same as the Centerline of
the Framed Opening.
6 to 48 in. Vent Section,
Telescopic vent section,
Elbow or Appliance Collar
Min. Distance to Base
of Appliance.
Base of Appliance
3 in.
(76 mm)
1 in.
(25.4 mm)
Adapter
SV4.5RCH
To help minimize water
infiltration it is recommended that
the Firestop/Spacer (SV4.5HF)
be installed on the exterior
side of the wall.
Siding
Stucco
1 1/4 in. Maximum recess of
the Square Termination into
Exterior Finishing Material
Exterior Surface of
Framing
6 in. to 9 1/4 in.
(152 to 235 mm)**
Exterior Surface of Siding
Interior Surface of
Finished Wall
Maximum wall thickness
9 1/4 in. (235 mm)**
SV4.5HT-2
Square Termination
Maximum Extent of
Vent Run Sections
Relative to Exterior
Surface of Framing
Last Vent Section. Use
Telescopic Vent
Section (SV4.5LA), If
Necessary
Adapter
SV4.5RCH
SV4.5HT-2
Square Termination
*Use silicone caulking to seal
the top and sides of the
termination, up to the
underlayment, stucco, or
masonry wall surface.
** For thicknesses greater
than 9 1/4 in., see Venting
Components Required for
Various Exterior Wall Thicknesses,
when using Typical Termination Kits
*Caulk
*Caulk
11. Attach termination adaptor—Attach
the adaptor (SV4.5RCH, provided with
the termination) to the vent section
or telescoping vent section), elbow or
appliance collar as shown in Figure 23
in the same manner as any SV4.5 vent
component (Step 5).
12. Install Firestop/Spacer at exterior
wall—When using the square
termination, install SV4.5HF
(Secure Vent®), SF4.5HF (Secure Flex®)
firestop/spacer over the opening at
the exterior side of the framing, long
side up, with the 3 in. spacer clearance
at the top (Figure 22), and nail into
place. The firestop/spacer may also be
installed over the opening at the interior
side of the framing.
13. Install the desired termination
a. SV4.5HT-2 or SV4.5HTSS Square
termination—For the last step,
from outside the exterior wall,
slide the collars of the termination
onto the adaptor (the outer over
the outer and the inner inside the
inner) until the termination seats
against the exterior wall surface to
which it will be attached. Orient the
housing of the termination with the
arrow pointed upwards. Secure the
termination to the exterior wall. The
horizontal termination must not be
recessed into the exterior wall or
siding by more than the 1 1/4 in.
(32 mm) as shown in Figure 23.
b. SVHRK Snorkel Cap—The snorkel
cap is designed to be fitted into a
basement window box. The SVHRK
cap is for use with flex vent. The
vertical distance between the inlet
and outlet of the cap is 28 in.
(711 mm).
Figure 21: Typical Horizontal Vent Installation
Building
Support
Framing
SV4.5E90
ertical
V
Rise
Support
Brackets
Elbow
Ceiling
Firestop/Spacer
Horizontal / Inclined Run
SV4.5L6/12/24/36/48
Vent Sections
Support bracket spacing
every 5 ft (1.52 m)
Vertical Vent
Fireplace
Figure 22: Installing the Square Horizontal Termination
SV4.5HT-2
Termination
Exterior
Wall
SV4.5HT-2
Termination
Exterior
Wall
NOTE: The vent termination is hot while
in operation and for a period of time
following the use of the fireplace. To
prevent contact with hot surfaces, use
a termination guard (Page 32). This
can be purchased at your local dealer.
Horizontal terminations have been designed
to perform in a wide range of weather
conditions. Our terminations meet or exceed
industry standards.
When selecting the locations of your
horizontal terminations, do not place the
termination where water from eaves and
adjoining rooflines may create a heavy flow
of cascading water onto the termination
cap. If the cap must be placed where the
possibility of cascading water exists, it is
the responsibility of the builder to direct
the water away from the termination cap by
using gutters or other means.
Take care to carefully follow the installation
instructions for the termination, including
the use of silicone caulking where required.
Figure 23: Venting Connection and Exterior Wall Recessing of the Horizontal
Square Termination (SV4.5HT-2)
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
19
Page 20
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
Horizontal Vent Tables and Figures
NOTE: Secure Vent® components (rigid vent
pipe and terminal) are shown in the figures;
Secure Flex® components (flexible vent pipe
and terminal) may also be used.
NOTE: Two 45° elbows may be used in place
of one 90° elbow. The same rise to run ratios,
as shown in the venting figures for 90° elbows,
must be followed if 45° elbows are used.
NOTE: It is very important that the
horizontal/inclined run be maintained
in a straight (no dips), slightly elevated
plane. The recommended incline is
approximately 1/4 in. per foot (20 mm per
meter) horizontal, in a direction away from
the fireplace. Rise per foot run ratios are
acceptable to at or near level.
NOTE: SV4.5VF (Secure Vent), SF4.5VF
(Secure Flex) firestop/spacer must be
used anytime vent pipe passes through
a combustible floor or ceiling. SV4.5HF
(Secure Vent), SF4.5HF (Secure Flex)
firestop/spacer must be used anytime vent
pipe passes through a combustible wall.
Table 20: Top Vent—One 90° Elbow, Elbow Connection at Appliance
H
V
**When using Secure
Flex, use Wall Firestop/
Spacer SF4.5HF.
H MaximumV Minimum
feetmetersfeetmeters
30.914Elbow Only
Install the U-shaped vent restrictor in any vent run with more than 8 ft of vertical rise (Figure 12).
Square termination (SV4.5HT-2) shown.
See Table 19 as an aid in venting component selection for a particular range of exterior wall thicknesses.
Wall Firestop/
Spacer
SV4.5HF**
WARNING
Under no circumstances, may
separate sections of concentric
flexible vent pipe be joined together.
Table 19: Venting Components Required
for Various Exterior Wall Thicknesses,
when using Typical Termination Kits
Vent Components
Required
Termination Kit Only
Termination Kit and 6 in.
Vent Section (SV4.5L6)
Termination Kit and 12 in.
Vent Section (SV4.5L12)
Termination Kit and
Telescopic Section
(SV4.5L12)
Exterior Wall Thickness
6–9 1/4 in.
(152–235 mm)
10 3/4–14 in.
(2733–356 mm)
16 3/4–20 in.
(426–508 mm)
11 3/4–20 in.
(299–508 mm)
Table 21: Top Vent—One 90° Elbow, Elbow Connection NOT at Appliance
H
Ceiling
Wall Firestop/
Spacer SV4.5HF**
*When using Secure Flex, use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
H MaximumV Minimum
feetmetersfeetmeters
51.52410.305
103.04820.610
154.57230.914
206.09641.219
V + H = 40 ft (12.2 m) maximum
H = 20 ft (6.096 m) maximum
Firestop/
Spacer
SV4.5VF*
V
20
Install the U-shaped vent restrictor in any vent run with more than 8 ft of vertical rise (Figure 12).
Square termination (SV4.5HT-2) shown.
If 20 ft of (H) horizontal vent run is needed, then 4 ft minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 ft of (V) vertical, you are allowed 5 ft of (H) horizontal run, up to a
maximum horizontal run of 20 ft.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 21
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
Table 22: Top Vent—Two 90° Elbows
H + H1 MaximumV Minimum
feetmetersfeetmeters
30.914Elbow Only
51.52410.305
103.04820.610
154.57230.914
206.09641.219
V + H + H1 = 40 ft (12.2 m) maximum
H + H1 = 20 ft (6.096 m) maximum
Install the U-shaped vent restrictor in any vent run with more than 8 ft of
vertical rise (Figure 12).
Square termination (SV4.5HT-2) shown.
See Table 19 as an aid in venting component selection for a particular range of
exterior wall thicknesses.
If 20 ft of (H) horizontal vent run is needed, then 4 ft minimum of (V) vertical vent
will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 ft of (V) vertical, you are allowed
5 ft of (H) horizontal run, up to a maximum horizontal run of 20 ft.
An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only
vertical component in the system (Table 20).
Wall Firestop/Spacer
SV4.5HF**
H
1
*When using Secure Flex, use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
H
V
Wall Firestop/Spacer
SV4.5HF**
Ceiling Firestop/Spacer
SV4.5VF*
Table 23: Top Vent—Three 90° Elbows
H MaximumV Minimum
feetmetersfeetmeters
51.524Elbow Only
51.52410.305
103.04820.610
154.57230.914
206.09641.219
H + H1 = 20 ft (6.096 m) maximum
V + V1 +H + H1 = 40 ft (12.2 m) maximum
Install the U-shaped vent restrictor in any vent run with more than 8 ft of
vertical rise (Figure 12).
Square termination (SV4.5HT-2) shown.
See Table 19 as an aid in venting component selection for a particular range of
exterior wall thicknesses.
If 20 ft of (H) horizontal vent run is needed, then 4 ft minimum of (V) vertical vent
will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 ft of (V) vertical, you are allowed
5 ft of (H) horizontal run, up to a maximum horizontal run of 20 ft.
An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only
vertical component in the system (Table 20).
H
1
Wall Firestop/Spacer
SV4.5HF**
*When using Secure Flex, use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
Ceiling
Firestop/Spacer
SV4.5VF*
H
V
1
Wall Firestop/Spacer
SV4.5HF**
V
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
21
Page 22
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
5 in. (127 mm)
Radius Minimum
Flexible Vent Section
GEAR
CLAMPS
Adaptor
(SV4.5RF)
Apply ONLY MIL-PAC BLACK HIGH
TEMPERATURE SEALANT (Catalog No.
10K81) to the outside surface of both
collars of the adaptor (be especially
careful to fill the grooves of the outer
collar to be covered by the flexible
pipe) and slide flexible pipe over
inner and outer adaptor collars.
NOTE: OUTER PIPE IS PULLED AWAY TO
SHOW THE DETAIL OF THE INNER PIPE
FLEX VENT
1-3/4 in. (44 mm)
Flexible Pipe and
Adaptor Outer
Collar Overlap
1-3/4 in. (44 mm)
Flexible Pipe and
Adaptor Inner
Collar Overlap
SECURING SCREW
(3 PLACES EQUALLY SPACED
JUST BELOW GEAR CLAMP)
Attach Adaptor to Appliance
Collar, or Secure Vent Sections
SECURING SCREW
(3 PLACES EQUALLY SPACED
JUST BELOW GEAR CLAMP)
Venting Using Flexible Vent Pipe
Secure Flex® venting kits and components
may be used in any venting application
where rigid Secure Vent® (SV4.5) direct
vent components can be used. All
restrictions, clearances and allowances
that pertain to the rigid piping apply to the
flexible venting. Secure Flex kits may not
be modified. Also, under no circumstances
may separate sections of flex pipe be joined
together. Secure Flex kits may be added
to the end of a vent run made up of rigid
Secure Vent (SV4.5) vent sections provided
that doing so does not violate any of the
venting length, height, routing, horizontal
to vertical ratio requirements or clearance
considerations detailed in this manual.
Secure Flex kits come with an included
adaptor that can be fitted to the appliance
collar or the inclined channel end of the
last Secure Vent (SV4.5) vent section in
a rigid system in the exact same fashion
as any other Secure Vent section. Align
the dimpled end of the adaptor over the
previously installed section or appliance
collar, adjusting the radial alignment until
the four locking dimples of the adaptor are
aligned with the inlets of the four incline
channels of the last vent section or collar.
Push on the adaptor until it fully engages,
then twist the adaptor clockwise running
the dimples down and along the incline
channels until they seat at the end of the
channels.
Attach the flexible vent to the adaptor as
follows (Figure 24):
1. Install the Inner Flex Pipe
a. Install the small gear clamp loosely
around the inner flexible vent pipe,
push it back out of the way.
b. Apply a bead of Mill-Pac Black
(700 °F) high temperature sealant
(P/N 10K81) to the inner adaptor
collar, approximately 1/2 in. from
the end.
c. Pull and extend the inner flexible
vent pipe.
22
d. Slide the inner flex pipe over the
adaptor collar. Ensure the flexible
vent pipe completely engages the
adaptor collar to a distance of
1 3/4 in. from the end, and that it is
free from damage or tears.
e. Slide the gear clamp down and
tighten it fully to secure the flexible
vent to the adaptor inner collar
approximately 3/4 in. from the end of
the flex.
f. Install three screws 120° apart
through the flexible vent pipe and
into the adaptor collar just below
the gear clamp to provide additional
security to the connection.
Figure 24: Attaching the Flexible Vent
2. Install the Outer Flex Pipe
a. Install the large gear clamp loosely
around the outer flexible vent pipe,
push it back out of the way.
b. Apply a bead of Mill-Pac Black
(700 °F) high temperature sealant
(P/N 10K81) to the outer adaptor
collar; to the grooves of the collar
which extend approximately 1 inch
from the end and to the flat surface,
approximately 1 3/8 in. from
the end.
c. Pull and extend the outer flexible
vent pipe.
d. Slide the outer flex pipe over the
adaptor collar. Ensure the flexible
vent pipe completely engages the
adaptor collar to a distance of
1 3/4 in. from the end, and that it is
free from damage or tears.
e. Slide the gear clamp down and
tighten it fully to secure the flexible
vent to the adaptor outer collar
approximately 3/4 in. from the end
of the flex.
f. Install three (3) screws 120° apart
through the flexible vent pipe and
into the adaptor collar just below
the gear clamp to provide additional
security to the connection.
3. Route Flex Vent
a. Ensure the flex vent is properly
routed to provide the required
clearance. Do not allow the flexible
vent to bend in a radius tighter
than 5 in. (127 mm) (Figure 25).
Place the internal flex vent spacers
evenly and avoid kinking the inner
pipe. Support horizontal sections of
flex vent with metal straps at 24 in.
(610 mm) intervals.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
4. Install Firestop/Spacers at ceilings and walls
a. When Secure Flex penetrates a
wall or ceiling, a firestop/spacer
is required. Use the SF4.5 VF
firestop/spacer for ceilings and
the SF4.5 HF firestop/spacer for
walls. See the appropriate sections
and figures shown throughout the
venting section for their installation
requirements.
5. Attach Flex Vent to Termination
a. Secure Flex components can be
purchased separately and attached
to bulk lengths of Secure Flex
flexible tubing cut to size at the
job site. Secure the flexible vent to
the Secure Flex terminations in the
same manner (Figure 24) as it was
attached to the adaptor.
NOTE: Secure Flex vent must be attached
to Secure Flex terminations only. DO NOT
substitute Secure Vent terminations or
the Secure Vent adaptor for Secure Flex
components. The collars of Secure Flex
terminations and adaptors have a different
circumference than that used with the
Secure Vent pipe. Additionally, Secure Flex
components have an extended length center
tube for use in attaching the flexible vent.
Figure 25: Bending the Flexible Vent
Page 23
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
JUNCTION BOX
Field Wiring
CAUTION
The ground supply lead must be
connected to the wire attached to
the green ground screw located
on the outlet box (see wiring
diagrams). Failure to do so will
result in a potential safety hazard.
The appliance must be electrically
grounded in accordance with local
codes or, in the absence of local
codes, the National Electrical Code,
ANSI/NFPA 70—latest edition (in
Canada, the current CSA C22-1
Canadian Electrical Code).
CAUTION
Label all wires prior to disconnection
when servicing controls. Wiring
errors can cause improper and
dangerous operation.
ATTENTION
Au moment de l’entretien des
commandes, étiquetez tous les
fils avant de les débrancher. Des
erreurs de cáblage peuvent entraîner
un fonctionnement inadéquat et
dangereux.
Verify proper operation after servicing.
S’assurer que l’appareil fonctionne
adéquatement une fois l’entretien
terminé.
The gas valve is set in place and prewired at the factory for both millivolt and
electronic models.
Millivolt Wiring
Millivolt units are not provided with factoryinstalled controls; therefore, one of the
optional control switches is required to
operate the unit (Figure 26):
• ON/OFF Wall Switch,
• Unit-Mountable ON/OFF Switch *,
• Thermostat, or
• Remote Control.
See the fireplace Care and Operation
Instructions for details.
* If using a unit-mountable ON/OFF rocker switch with
an optional Style View Door, mount the rocker switch
on the door instead of the unit.
1. If installing an ON/OFF wall switch or
thermostat, mount it in a convenient
location on a wall near the fireplace.
2. Wire the control switch within the
millivolt control circuit using the 15 ft of
2-conductor wire supplied with the unit.
NOTE: The supplied 15 ft of
2-conductor wire has one end of
each conductor connected to the gas
valve circuit and the other end of each
conductor placed loose inside the
bottom compartment.
Figure 26: Wiring Diagram—
Millivolt Gas Valves
APPLIANCE- MOUNTED
ON/OFF SWITCH
(OPTIONAL)
BK/W(1)
BK/W(1)
THERMOPILE
TP-TH
TP
TH
GAS VALVE
Electronic Wiring
One of the following optional controls may
be used:
• ON/OFF Wall Switch,
• Remote Control.
See the fireplace Care and Operation
Instructions for details.
NOTE: Electronic models must be
connected to the main power supply.
1. Route a 3-wire, 120 Vac, 60 Hz,
1 ph power supply to the appliance
junction box.
2. Remove the electrical inlet cover plate
from the side of the unit by removing
the plate’s securing screws (Table 11
WALL MOUNTED CONFIGURATION FOR FAN SWITCH (OPTIONAL)
feed the power supply wire through
the knockout opening and into the unit
junction box.
4. Connect the black power supply wire
to the lower outlet’s red pigtail lead
(Figure 27 and Figure 28). Connect the
FAN
(OPTIONAL)
BK
JUNCTION BOX
BLACK
R
W
GR
AC
120 V
white power supply wire to the outlet’s
common terminal.
5. Connect the ground supply wire to
the pigtail lead attached to the outlet’s
green ground screw.
NOTE: Remote receiver should be
located in the wall, or if installed in the
control compartment, pulled all the way
forward and completely to the left or
CAUTION
right against the corner posts.
6. If a wall-mounted ON/OFF control is
In millivolt systems, do NOT
connect a wall switch to a 120 V
to be used, mount it in a convenient
location on a wall near the fireplace.
power supply.
Figure 27: Wiring Diagram—Electronic Gas Valves
R
BATTERY HOLDER
AC/DC
POWER
ADAPTOR
Y
G
O
B
PROFLAME VALVE
B
R
120V AC
B
W
G
OPTIONAL
REMOTE RECEIVER
ON/OFF SWITCH
WALL SWITCH
WIRING COLOR CODE
B = BLACK
BR = BROWN
GY = GRAY
PU = PURPLE
R = RED
P/N 580491-01
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
HOT
NEUTRAL
GROUND
LIMIT SWITCH
B-VENT MODELS
ONLY
BL = BLUE
G = GREEN
O = ORANGE
W = WHITE
Y = YELLOW
SCHEMATIC REPRESENTATION ONLY
W
BL
PILOT TUBE
SPARK WIRE CABLE
PILOT GROUND WIRE
R
R
ELECTRONIC PILOT ASSEMBLY
HOOD
Y
B
B
IGNITER ROD
FLAME SENSOR
B
Y
G
O
W
PROFLAME DFC BOARD
BL
G
DFC WIRE HARNESS
OPTIONAL CPI SWITCH
OFF (O) = INTERMITTENT PILOT MODE
ON (-) = STANDING PILOT MODE
B
PILOT
SENSOR
CABLE
23
Page 24
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
BLOWER CONTROL CIRCUIT WIRING
7. If an optional control is to be used, wire
it in the low voltage circuit as shown in
Figure 27.
NOTE: The supplied 15 ft of
2-conductor wire has one end of
each conductor connected to the gas
valve circuit and the other end of each
conductor placed loose inside the
bottom compartment.
8. After the wiring is complete, replace the
cover plate.
WARNING
Electronic models of these
appliances are equipped with
a three-prong (grounding) plug
utilized in connecting the electronic
components to the junction box
in the lower compartment. This
grounding plug provides protection
against shock hazard and should
be plugged directly into a properly
grounded three-prong receptacle.
DO NOT cut or remove the grounding
prong from the plug.
Wire the [Optional] Blower Kit After
Installation in the Framing
FBK-100 and FBK-200 Kits
An electrical outlet box is provided for the
installation of the FBK-100 and FBK-200
forced air blower kits. Electrical power
must be provided to the box to operate the
blower. Install the blower kit according to
the installation instructions provided with
the kit.
NOTE: The tab connecting the receptacles of
the outlet box must be broken (Figure 28).
NOTE: For fireplace models including a
factory-installed blower (models with FB
designation), an FBK2/FBK3 kit should be
installed for proper control. Refer to the
included instructions for more information.
Figure 28: Junction Box Wiring
120V, 60HZ, 1PH
neerG - dnuorG
etihW - lar
* Wall-mounted
ON/ OFF Blower
Switch or Variable
Speed Control Switch.
t
ueN
120 VAC - Black
Junction Box
Tab
Broken
Hot
Side of
Red
Black
White
Green
Plug blower
into this
receptacle
Ground
Blower
Tab Intact
Field Wired
Factory Wired
Receptacle
Neutral
Side of
Receptacle
Green
Ground
Screw
Connect the Gas Line
All codes require a shut-off valve mounted
in the supply line. Figure 29 illustrates two
methods for connecting the gas supply.
The flex-line method is acceptable in the
U.S., however, Canadian requirements vary
depending on locality. Installation must be
in compliance with local codes.
These appliances are equipped with a
gas flex line for use (where permitted) in
connecting the unit to the gas line. A gas
flex line is provided to aid in attaching the
direct vent appliance to the gas supply. The
gas flex line can only be used where local
codes permit. The flex line is rated for both
natural and propane gas. A manual shut off
valve is also provided with the flex line.
The gas control valve is located in the lower
control compartment (Figure 30).
Remove Control Compartment Door
Open the panel by grasping the control
compartment door on both sides and gently
pulling the top away from the fireplace to
disengage the magnetic fasteners. The door
is hinged at the bottom. If greater access
to the control compartment is required,
slide the door, first to one side and then
the other, so the tabs clear both of the
locating holes.
Millivolt and electronic control valves have a
3/8 in. (10 mm) NPT thread inlet port.
Secure all joints tightly using appropriate
tools and sealing compounds (ensure
propane resistant compounds are used
in propane applications). Optionally, seal
around the gas line to prevent cold air
leakage. Gas line holes and other openings
can be caulked or stuffed with unfaced
fiberglass insulation.
All codes require a shut-off valve mounted
in the supply line. The orientation of
the shut-off valve should face the front.
Figure 29 illustrates two methods for
connecting the gas supply. A sediment
trap is recommended to prevent moisture
and debris in the gas line from damaging
the valve.
WARNING
24
Never use an open flame to check
for leaks.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 25
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
Thermocouple
HoodIgniter Rod
Thermopile
Pilot
Nozzels
3/8 in.
(9 mm)
Min
Gas
Stub
1/2 x 3/8 in. Flare
Shut-Off Valve
3/8 in. Flex Tubing
3/8 NPT x 3/8 in.
Flare Fitting
3/8 in. Nipple
3/8 in. Union
3/8 in. Close Nipple
3/8 in. Shut-Off Valve
1/2 x 3/8 in.
Reducer
Gas
Valve
Optional Gas Flex Line Connector
Figure 29: Gas Line Connection
Figure 30: Millivolt Gas Valve—Lower Control Compartment
as indicated in the instruction manual.
Subsequent lighting of the appliance will
not require such purging. Inspect the pilot
flame (remove logs, if necessary, handling
carefully).
Millivolt Appliance Inspection
The pilot flame should be steady, not lifting
or floating. Flame should be blue in color
with traces of orange at the outer edge.
The top 3/8 in. (10 mm) at the pilot
generator (thermopile) and the top 1/8 in.
(3.175 mm) minimum (tip) of the quick
drop out thermocouple should be engulfed
in the pilot flame.
The flame should project 1 in. (25 mm)
beyond the hood at all three ports
(Figure 31). Replace logs if removed for
pilot inspection.
To light the burner; turn ON the remote wall
switch and rotate the gas valve control knob
counterclockwise to the ON position (ON
will be at the top side of the valve).
Figure 31: Millivolt Pilot
Test Factory and Field Connections for
Gas Leaks
Turn on gas supply and test for gas leaks,
using a gas leak test solution—also known
as bubble leak solution.
NOTE: Using a soapy water solution is
an effective leak test solution but it is not
recommended, because the soap residue
that is left on the pipes/fittings can result in
corrosion over time.
1. Light the appliance (refer to the lighting
2. Brush all joints and connections with
3. When the gas lines are tested and leak
Main Gas
Shut-Off Valve
Gas Valve
instructions label, in the control
compartment or in the Care and
Operation Instructions manual).
the gas leak test solution to check for
leaks. If bubbles are formed, or gas
odor is detected, turn the gas control
knob (OFF/PILOT/ON) to the OFF
position (millivolt units), or turn the
receiver or remote control to the OFF
position (electronic units). Either tighten
or refasten the leaking connection, and
then retest as described above.
free, rinse off the leak testing solution.
(Optional) Burner
ON/OFF Switch
Piezo
Door Latch
Verify Proper Appliance Operation
WARNING
For all electronic ignition
models, remove all firebox
contents, set the gas shutoff
valve in the closed position,
remove batteries from the battery
holder, and ensure the remote
/ wall receiver is in the OFF
position until ready to test/light
the fireplace.
With gas line installed, run initial system
checkout before closing up the front of the
unit. Follow the pilot lighting instructions
provided in the Care and Operation
Instructions. For piezo igniter location on
millivolt appliances, see Figure 30.
NOTE: Lighting instructions may be found
on the tags attached to a cable in the control
compartment. To access the instructions,
open the lower control compartment door
(Figure 30) by pulling simultaneously on
the left and right top corners of the door.
The door is hinged at the bottom (Remove Control Compartment Door on Page 24).
When lighting the appliance for the first
time, it will take a few minutes for the line to
purge itself of air. Once purging is complete,
the pilot and burner will light and operate
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Electronic Appliance Inspection
To light the burner, turn ON the wall or
remote control switch. Ensure the igniter
lights the pilot. The pilot flame should
engulf the flame rod (Figure 32).
Figure 32: Electronic Pilot
Ignitor
Igniter
Flame Rod
Sensor
PilotHood
Pilot Hood
25
Page 26
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
Install the Contemporary Media
WARNING
•DO NOT attempt to install
the logs until the appliance
installation has been
completed, the gas line
connected and tested for leaks
and the initial burner operation
has been checked out.
•The size and position of the log
set was engineered to give the
appliance a safe, reliable and
attractive flame pattern. Any
attempt to use a different log
set in the fireplace will void
the warranty and will result
in incomplete combustion,
sooting, and poor flame quality.
•Contemporary media gets very
hot and will remain hot up to
one hour after gas supply is
turned OFF. Handle only when
contemporary media is cool.
•If contemporary media is not
installed according to the
installation instructions, flame
impingement and improper
combustion could occur and
result in soot and/or excessive
productionof carbon monoxide
(CO), a colorless, odorless,
toxic gas.
•This appliance is not designed
to burn wood. Any attempt to
do so could cause irreparable
damage to the appliance and
prove hazardous to your safety.
•Only use materials listed here.
Only contemporary media
authorized have been tested for
use within the firebox and its
environment. Do not attempt
to use any different materials
in the fireplace. Doing so may
be dangerous and will void
the warranty and will result in
incomplete sooting, and poor
flame quality.
Table 24: Contemporary Media
Catalog
Number
H7536MTRSTumbled River Stone
H7537MCCG-OB
H7538MBSK
H7578MCCG-DW
H7579MCCG-SB
H7581MBLPK-35ZG
Remove the front glass enclosure panel
(Page 28).
This fireplace is designed to accept a
number of alternate contemporary media
options, allowing the homeowner to
customize this product to fit any decor.
Model
Number
Description
Contemporary Glass
Obsidian Black
Contemporary
Beach Sand
Contemporary Glass
Diamond White
Contemporary Glass
Deep Sea Blue
Merit Liner Kit,
Zen Garden
Zen Garden Firebox Liner
(MBLPK-35ZG)
1. Porcelain panels come installed in the
appliance. Remove them by bending the
tab, sliding the left and right side panels
out first, then removing the rear panel.
2. Remove the lintel by removing the two
screws securing it.
3. Insert the Zen Garden rear panel into
firebox and position against the rear
wall of the firebox (Table 25).
4. Carefully insert the Zen Garden left side
panel into firebox, at a slight angle away
from the sidewall. Position the side
panel as far back along the wall as it
will go (until it is against the rear panel)
and lower it into place, while standing
it upright and pressing it down over the
knife edge at the rear of the sub-floor.
The sub-floor knife edge will cut into
the refractory panel. Repeat the same
procedure for the Zen Garden right side
panel (Table 25).
5. Re-install the lintel and screws.
Tumbled River Stone (MTRS)
NOTE: Refractory panels should be installed
before the contemporary media is installed.
1. Place stones on the firebox sub-floor,
in any atheistically pleasing manner to
suite individual taste (Table 25).
NOTE: Ensure stones do not impinge on
the burner outlet.
Crushed Glass and Sand
(MCCG and MBSK)
NOTE: Refractory panels should be installed
before any of the contemporary media
are installed.
1. Pour out glass or sand on firebox sub-
floor, completely covering the sub-floor.
(Table 25).
NOTE: Avoid letting glass or sand fall
into the burner outlet. Make sure no
glass or sand falls into the burner ports.
Contemporary Facade
1. Refer to the Facade Installation
Instructions (P/N 506019-40) to install
the Contemporary Facade.
26
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 27
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
Table 25: MLDVTCD-35 Firebox Liner and Contemporary Media Placement
Rear Zen Garden Panel
Black Obsidian Contemporary Glass
Zen Garden Firebox Liner, Rear Panel
Left Zen Garden Panel
Right Zen Garden Panel
Diamond White Contemporary Glass
Zen Garden Firebox Liner, Side Panels
Burner Outlet
Burner Outlet
Tumbled River Stone
Burner Outlet
NOTE: River Stone And Beach Sand May Be Used Together
Tumbled River Stone
Contemporary Beach Sand
Burner Outlet
NOTE: Beach Sand And River Stone May Be Used Together
Crushed Glass and Sand
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
27
Page 28
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
Install the Glass Door
WARNING
•Do not attempt to substitute
the materials used on these
doors, or replace cracked or
broken glass.
•Handle this glass with
extreme care! Glass is
susceptible to damage—Do
not scratch or handle roughly
while reinstalling the glass
door frame.
•The glass door of this appliance
must only be replaced as a
complete unit as provided
by the manufacturer. Do not
attempt to replace broken,
cracked or chipped glass
separately.
•Do not attempt to touch the
front enclosure glass with your
hands while the fireplace is
in use.
WARNING
Do not operate appliance with
the glass front removed, cracked
or broken.
AVERTISSEMENT
Ne pas utiliser l’appareil si
le panneau frontal en verre
n’est pas en place, est craqué
ou brisé.
Only doors certified with the appliance shall
be used.
Seules des portes certifiées pour cet
appareil doivent être utilisées.
CAUTION
DO NOT abuse glass door by
striking or slamming shut.
NOTE: Visually inspect the gasket on the
backside of the glass door. The gasket
surface must be clean, free of irregularities,
and seated firmly. Ensure it is properly
located. Make sure the bead is not rolled
into the channel at the top of the door, but
remains flat against the top of the glass.
Open the lower control compartment door
(Page 24).
Position the glass door in front of the
firebox opening with the bottom of the
door held away from the fireplace at
approximately a 45° angle. Hook the top
flange of the glass door over the top of the
firebox frame.
Let the bottom of the glass door swing
gently in towards the fireplace ensuring
that the gasket seats evenly as the glass
door draws shut. Fasten the two latches
located beneath the firebox floor to the door
vee-flange.
Install the hood. Use a screwdriver to open
the hood clips slightly if needed. Engage the
back edge of the hood into the clips.
NOTE: The three hood clips are located
inside the top air channel above the door.
The clips are equally-spaced on the top
surface of the air channel opening.
Reinstall the lower control compartment door.
Figure 33: Glass Door
Hood
Glass
Door
Glass Door
Control
Compartment
Panel
Spring Latch
Remove the Glass Door
Open the lower control compartment door
(Remove Control Compartment Door on
Page 24). Locate the two (2) latches
at the top of the control compartment
and disengage them from the door frame
bottom vee-flange.
Pull the bottom of the glass door out a
few inches and grasp it on the right and
left. Gently lift to release the door from
the channel above the door. Pull the door
forward.
Adjust the Burner
Flame Appearance and Sooting
The flame should be blue at the base, and
yellow-orange in the body of the flame.
When the appliance is first lit, the entire
flame may be blue and will gradually turn
yellow-orange during the first 15 minutes
of operation. If the flame remains blue, or if
the flame is orange with evidence of sooting
(black tip), the air shutter opening may need
to be adjusted.
If the air shutter opening is closed too far,
sooting may develop. Sooting is indicated
by black puffs developing at the tips of very
long orange flames. Sooting results in black
deposits forming on the logs, appliance
inside surfaces, and on exterior surfaces
adjacent to the vent termination.
Sooting is caused by incomplete
combustion in the flames and lack of
combustion air entering the air shutter
opening. To achieve a warm yellow-orange
flame with an orange body that does not
soot, the shutter opening must be adjusted
between these two extremes.
Air Shutter Adjustment Guidelines
• If there is smoke or soot present, first
check the log set positioning to ensure
that the flames are not impinging on
any of the logs. If the log set is properly
positioned and a sooting condition still
exists, then the air shutter opening
should be increased.
• The more offsets in the vent system, the
larger the air shutter opening will need
to be.
• An appliance operated with the air
shutter opened too far, may have flames
that appear blue and transparent. These
weak, blue and transparent flames are
termed anemic.
• Propane models may exhibit flames
which candle or appear stringy. If this
is present and persists, adjust the air
shutter to a more closed position,
then operate the appliance for a few
more minutes to ensure that the flame
normalizes and the flames do not
appear sooty.
28
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 29
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
WARNING
•Air shutter adjustment
should only be performed
by a qualified professional
service technician.
•Ensure front glass panel
is in place and sealed
during adjustment.
CAUTION
•Soot will be produced if the
air shutter is closed too much.
Any damage due to sooting,
resulting from improperly
setting the air shutter, is not
covered under the warranty.
•The air shutter door and nearby
appliance surfaces are hot.
Exercise caution to avoid injury
while adjusting flame appearance.
1. Move the adjustment rod down to
decrease air flow and up to increase it.
(rod located in the lower control area).
Position the air shutter to the factory
setting as shown in Table 27.
2. Light the appliance (follow the lighting
procedure on the lighting label in the
control compartment or in the Care and
Operation Instructions).
3. Allow the burner to operate for at least
15 minutes while observing the flame
continuously to ensure that the proper
flame appearance has been achieved
(Figure 34). If the following conditions
are present, adjust accordingly.
• If flame appears weak or sooty, adjust
the air shutter, incrementally, to a
more open position until the proper
flame appearance is achieved.
• If flame remains blue, adjust the air
shutter, incrementally, to a more
closed position until the proper
flame appearance is achieved.
Figure 34: Burner Flame Appearance, MLDVTCD-35
Table 27: Factory Air Shutter Settings
ModelsGas Type
Natural GasClosed
MLDVTCD-35
Propane
Factory Air
Shutter Setting
Expose half of
the hole
Burner
Tube
Air Shutter
Adjustment Rod Down
(Fully-Closed Position)
Adjustment Set-Screw
Adjustment
Rod Up
(Fully-Open
Position)
Table 26: Air Shutter Adjustment Guidelines
Amount of
Primary Air
If air shutter
is closed
too far
If air shutter
is open
too far
Flame Color
Flame will
be orange
Flame will
be blue
Air Shutter
Adjustment
Air shutter
gap should be
increased
Air shutter
gap should be
decreased
4. When satisfied that the burner flame
appearance is normal, reinstall the
lower control compartment door, then
proceed to finish the installation.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
29
Page 30
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
Install the Hood
All models must have a hood installed prior
to operation.
Install the hood by sliding it into the slots
on the lower edge of the cabinet top.
Figure 35: Combustible Wall Framing
This Area
Must Remain
Clear of
Combustible
Finished Wall
Materials
Stand Off Must
Be Bent To
Vertical Position
Combustible
Material
May
Touch The
Appliance
Top
Hood
Combustible
Materials
1 in. Min.
(25 mm)
Top Of Appliance
3 in. Clearance Min.
3 in.
(76 mm)
Finishing Requirements
This contemporary unit is uniquely suited
for mid-wall installations with an available
self-finishing decorative contemporary
façade. The decorative contemporary
façade is listed in the accessories sections
of the Care And Operations manual and
consists of three elements that can be
mixed and matched for finishes to taste.
This appliance, without the decorative
contemporary façade, may be installed on
the floor as a traditional fireplace (Table 9),
but if the decorative contemporary façade is
to be installed, the unit must be raised on a
platform at least 6 in. high (Figure 36).
Figure 36: Contemporary Façade
Dimensions
35
(889)
44 3/4
(1137)
35 1/2
32 (813)
29
(737)
16 (406)
33 (838)
24 (610)
NOTE: When raising the MLDVTCD
appliance on a platform for mid-wall
installations, add the platform height to any
of the framing dimensions shown in Table 9
and adjust the gas line dimensions shown
in Figure 11 upwards accordingly.
The decorative contemporary façade may
be installed over drywall that is butted
directly against the sides of the fireplace,
or noncombustible wall finish materials,
no more than 3/4 in. thick, that are placed
in front of the fireplace black painted face.
DO NOT place the façade over combustible
materials that are placed in front of the
fireplace’s black finished face. Refer to the
installation instructions that accompany
the decorative contemporary façade for
installation details.
NOTE:
See Cold Climate Insulation on Page 4
and Vent Termination Clearances on Page 6.
Floor
Fireplace
6 in. minimum required
30
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 31
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
Attach the Safety-in-Operation Warnings
NOTE: It is the installer’s responsibility to ensure these warnings are properly affixed during installation. These warning labels are a critical step in informing
consumers of safe operation of this appliance.
Attaching Safety-inOperation Warnings
It is required that the safety instruction labels
furnished with the fireplace be affixed to the
operation and control point of the fireplace. A
safety instruction label must be affixed to the wall
switch plate where the fireplace is turned on and
off (Figure A) and if used on the remote control
handheld transmitter (Figure B). To properly
complete the installation of this fireplace, locate
the multi-lingual adhesive labels provided with
the Care and Operation Instructions and proceed
as follows:
1. Locate the wall switch or wall thermostat
that controls the fireplace (verify the switch
operates the fireplace by turning it on and
off). Clean the wall switch plate or wall
thermostat thoroughly to remove any dust
and oils. Affix the label to the surface of the
plate of the wall switch that controls the
fireplace (Figure A). Choose the language
primarily spoken in the home. If unknown,
affix the English language label.
2. If a remote control is used to control the
fireplace, locate the transmitter and clean
it thoroughly to remove any dust and oils.
Affix the label to the surface of handheld
transmitter (Figure B). Choose the language
primarily spoken in the home. If unknown,
affix the English language label.
3. If you are unable to locate the labels, please
call Lennox Hearth Products or your nearest
Lennox Hearth Products dealer to receive
additional safety instruction labels free
of charge.
Cat. No. H8024 Replacement Label Kit Étiquettes de remplacement, n° cat. H8024 Juego de etiquetas de repuesto - Nº de cat. H8024
LENNOX HEARTH PRODUCTS
1-800-655-2008
NOTE: English is red text on clear label. French
and Spanish are white text on black label.
SAFETY LABEL DIAGRAMSDIAGRAMMES DES ÉTIQUETTES DE SÉCURITÉDIAGRAMAS DE ETIQUETAS DE SEGURIDAD
Apposition des mises en garde
relatives à la sécurité d’utilisation
Il est impératif que les étiquettes de sécurité
fournies avec le foyer soient collées à côté des
dispositifs de contrôle du foyer. Une étiquette
de sécurité doit être collée sur la plaque de
l’interrupteur contrôlant l’allumage du foyer
(Figure A) et, le cas échéant, sur le boîtier de
la télécommande (Figure B). Pour achever
l’installation correcte de ce foyer, procédez
comme suit avec les étiquettes adhésives en
langues étrangères fournies avec les instructions
d’utilisation et d’entretien :
1. Repérez l’interrupteur ou le thermostat mural
qui contrôle le foyer (vérifiez que l’interrupteur
contrôle le fonctionnement du foyer en le faisant
basculer de Marche à Arrêt, et vice-versa). Nettoyez
soigneusement la plaque murale de l’interrupteur
ou le thermostat mural pour éliminer la poussière
et les traces de graisse ou d’huile. Collez l’étiquette
sur la surface de la plaque de l’interrupteur mural qui
contrôle le foyer (Figure A). Choisissez la langue
qui est principalement parlée dans la résidence du
propriétaire. En cas de doute, collez l’étiquette en
anglais.
2. Si une télécommande est utilisée pour
contrôler le foyer, nettoyez la soigneusement
pour éliminer la poussière et les traces de
graisse ou d’huile. Collez l’étiquette sur
le boîtier de la télécommande (Figure B).
Choisissez la langue qui est principalement
parlée dans la résidence du propriétaire. En
cas de doute, collez l’étiquette en anglais.
3. Si vous ne trouvez pas les étiquettes, veuillez
appeler Lennox Hearth Products ou votre
distributeur Lennox Hearth Products local
pour recevoir gratuitement des étiquettes
supplémentaires.
LENNOX HEARTH PRODUCTS
1-800-655-2008
Remarqué : Le texte anglais est rouge sur un
support transparent. Le texte français et espagnol
est blanc sur un support noir.
Colocación de advertencias de
seguridad en operación
Se requiere que las etiquetas de instrucciones de
seguridad incluidas con la chimenea se coloquen en
el punto de operación y control de la misma. Se debe
colocar una etiqueta de instrucciones de seguridad
en la placa del interruptor de pared desde el cual se
enciende y se apaga la chimenea (Figure A) y en
el transmisor de control remoto (Figure B) si se
usa. Para completar correctamente la instalación de
esta chimenea, encuentre las etiquetas adhesivas
multilingües incluidas con las instrucciones de
cuidado y operación y haga lo siguiente:
1. 1. Identifique el interruptor o el termostato
de pared que controla la chimenea (verifique
que el interruptor opera la chimenea
encendiéndola y apagándola). Limpie bien
la placa del interruptor o el termostato de
pared para quitar el polvo y aceite. Pegue
la etiqueta en la superficie de la placa
del interruptor que controla la chimenea
(Figure A). Seleccione el idioma que más se
habla en la casa. Si no sabe cuál es, use la
etiqueta en inglés.
2. Si se usa un control remoto para controlar
la chimenea, encuentre el transmisor y
límpielo bien para quitar el polvo y aceite.
Pegue la etiqueta en la superficie del
transmisor (Figure B). Seleccione el idioma
que más se habla en la casa. Si no sabe cuál
es, use la etiqueta en inglés.
3. Si no puede encontrar las etiquetas, sírvase
llamar a Lennox Hearth Products o al
distribuidor de Lennox Hearth Products
más cercano para recibir etiquetas de
instrucciones de seguridad adicionales
gratuitas.
LENNOX HEARTH PRODUCTS
1-800-655-2008
Nota: La etiqueta en inglés es transparente con
texto rojo. Las etiquetas en francés y español son
negras con texto blanco.
Figure A
Figure B
31
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 32
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
INSTALLATION ACCESSORIES
Listed Secure Vent® Components
Catalog
Number
H1968SV4.5HT-2
94L10SV4.5HTSS
H5817SV4.5-20SSWSK
H2152SV4.5CGV-1
77L70SV4.5L6
77L71SV4.5L12
77L72SV4.5L24
77L73SV4.5L36
77L74SV4.5L48
77L75SV4.5LA
77L76SV4.5E4545° Elbow
ModelDescription
Horizontal Square
Termination with
Firestop/Spacer
(H2246), and
Adaptor (74L61)
Rigid, Horizontal,
Small Square
Termination
with Firestop/
Spacer (H2246),
Adaptor (74L61)
(Ref. Instruction
P/N 750204M)
Rigid, Small, Square
Termination, 20 in.
with Shield and
Firestop
(Ref. Instruction
P/N 750247M
and 750204M)
Vertical Termination
Cap, High Wind
6 in. (152 mm)
Vent Section
12 in. (305 mm)
Vent Section
24 in. (610 mm)
Vent Section
36 in. (914 mm)
Vent Section
48 in. (1219 mm)
Vent Section
Telescopic Section
(2–7.5 in. Rigid)
Listed Secure Vent® Components
Catalog
Number
The following flashing comes packaged with a storm collar
77L78SV4.5FFlat Roof Flashing
77L79SV4.5FA
77L80SV4.5FB
77L81SV4.5SC6
H2246SV4.5HF
H2247SV4.5VF
96K93SV4.5SUSupport Strap
H3907SV4.5ARSA
H5816SV4.5TWSK
96K92SV4.5SPSupport Plate
87L02SV4.5HGS
H58204.5HTSK
99L03SV4.5HRK36
99L02SV4.5HRK14
ModelDescription
1/12 to 7/12
Adjustable Flashing
7/12 to 12/12
Adjustable Flashing
Storm Collar
(6 per box)
Firestop/Spacer
10-pack Horizontal
(3-1-1 spacing)
Firestop/Spacer
10-pack Vertical
(1-1-1 spacing)
Adjustable Attic
Insulation Shield
(12–22 in.)
Through Wall Shield
Kit (not shown)
(10-pack)
Termination Guard
Square (not shown)
Horizontal
Termination
Shroud Kit
Horizontal Riser
Kit, 36 in.
Horizontal Riser
Kit, 14 in.
32
77L77SV4.5E9090° Elbow
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
H8914SV4.5TK90HT2
H8915SV4.5TK90SS
Horizontal
Termination Kit HT-2
with 90° elbow
Horizontal
Termination Kit Small
Square with 90°
elbow
Page 33
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
S
e
a
l
a
n
t
Listed Secure Flex® Components
Catalog
Number
ModelDescription
These termination kits include firestop/spacer, gear clamps, and flex adaptor.
*All compressed flex vents can be expanded up to two times.
Chase Top Shroud Kit,
Arch Top, 3 x 3
Chase Top Shroud Kit,
Open Top, 3 x 3
Chase Top Shroud Kit,
Open Top, 4 x 4
Chase Top Shroud Kit,
Open Top, 4 x 6
sealant, 12-pack
for flex (6-pack)
for flex (6 pack)
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
33
Page 34
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
GAS CONVERSION KITS
WARNING
This conversion kit shall be
installed by a qualified service
agency in accordance with the
manufacturer’s instructions
and all applicable codes and
requirements of the authority
having jurisdiction. If the
information in these instruction
is not followed exactly, a fire,
explosion or production of carbon
monoxide may result causing
property damage, personal injury
or loss of life. The qualified
service agency is responsible
for the proper installation of
this kit. The installation is not
proper and complete until the
operation of the converted
appliance is checked as
specified in the manufacturer’s
instructions supplied with the
kit.The qualified service agency
performing this installation
assumes responsibility for this
conversion.
In Canada:
THE CONVERSION SHALL BE CARRIED
OUT BY A MANUFACTURER’S
AUTHORIZED REPRESENTATIVE, IN
ACCORDANCE WITH THE REQUIREMENTS
OF THE MANUFACTURER, PROVINCIAL
OR TERRITORIAL AUTHORITIES HAVING
JURISDICTION AND IN ACCORDANCE
WITH THE REQUIREMENTS OF THE
CAN/CGA-B149.1 OR CAN/CGA-B149.2
INSTALLATION CODES.
La conversion devra être effectuée
conformément aux recommandations
des autorités provinciales ayant
juridiction et conformément aux
exigences du code d’installation CAN/
CSA-B149.1.
Gas conversion kits are available to adapt
your appliance from the use of one type of
gas to the use of another. These kits contain
all the necessary components needed to
complete the task including labeling that
must be affixed to ensure safe operation.
Kit part numbers are listed here and the
following steps detail the conversion
procedure. Refer to the instructions
provided with the conversion kit when
performing any gas conversion.
Table 28: Millivolt SIT Systems,
Natural Gas To Propane Gas
Conversion Kits
ModelCatalog Number
MLDVTCD-35H7292
Table 29: Millivolt SIT Systems,
Propane Gas to Natural Gas
Conversion Kits
ModelCatalog Number
MLDVTCD-35H7293
Table 30: Electronic SIT Systems,
Natural Gas To Propane Gas
Conversion Kits
ModelCatalog Number
MLDVTCD35NE-2H8921
Table 31: Electronic SIT Systems,
Propane Gas To Natural Gas
Conversion Kits
ModelCatalog Number
MLDVTCD35NE-2H8926
AVERTISSEMENT
Cette trousse de conversion doit
être installée par un technicien
agréé, selon les instructions
du fabricant et selon toutes
les exigences et tous les
codes pertinents de l’autorité
compétente. Assurez-vous de
bien suivre les instructions dans
cette notice pour réduire au
minimum le risque d’incendie,
d’explosion ou la production de
monoxyde de carbone pouvant
causer des dommages matériels,
des blessures ou la mort. Le
tecnicien agréé est responsable
de l’installation de cette trousse.
L’installation n’est pas adéquate
ni complète tant que le bon
fonctionnement de l’appareil
converti n’a pas été vérifié selon
les instructions du fabricant
fournies avec la trousse. Le
fournisseur de service qualifié
ayant réalisé l’installation
assume les responsabilités liées
à la conversion.
34
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 35
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
Pressure
Regulator
Remove
These
Components
Pilot
Orifice
Installing Gas Conversion Kits
WARNING
The gas supply shall be shut
off prior to disconnecting
the electrical power, before
proceeding with the conversion.
AVERTISSEMENT
Avant d’effecteur la conversion,
coupez d’abord l’alimentation
en gaz, ensuite, coupez
l’alimentation electrique.
1. TURN OFF THE GAS SUPPLY TO THE
APPLIANCE and disconnect power
supply at the circuit breaker. Ensure
appliance is cold.
2. Open the lower control compartment
door (Figure 30 on Page 25) by
pushing on the right top corner of the
door. The door is hinged at the bottom.
[Optional] Remove the control
compartment door by sliding the hinge
pin, located at the door’s left side, to
the right until it disengages from the
left corner post hole. Pull the control
compartment door diagonally to the left,
away from the fireplace.
3. Remove the front glass door/frame
from the appliance (Page 28).
4. Carefully remove the contemporary
media (Page 26).
5. Remove the burner assembly with the
attached venturi tube.
Millivolt and Electronic Ignition
System Appliances
6. SIT Systems—Refer to Figure 37,
Figure 38, and the instructions
provided with the SIT Regulator
Conversion Kit. Using a Torx T20
driver (with 1/4 in. shank) or slotted
screwdriver, remove and discard the
pressure regulator mounting screws
(two screws for electronic models,
three screws for millivolt models),
pressure regulator tower, the diaphragm
assembly (if applicable) and the spring.
Discard all removed components.
Figure 37: Millivolt Valve
Regulator Conversion
Figure 38: Electronic Valve
Regulator Conversion
7. Ensure the rubber gasket installed on
the back of the replacement pressure
regulator is properly positioned, and
install the new pressure regulator
assembly using the supplied screws.
Tighten the screws to 25 lb-in.
8. Install the enclosed identification label
to the valve body where it can be
easily seen.
9. Remove the pilot hood assembly
to access the hexed pilot orifice
(Figure 39). Remove and replace
the orifice with the one provided
with the kit. Exercise extreme care to
prevent damage to or breakage of the
igniter assembly.
Figure 39: Millivolt Pilot
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Figure 40: Electronic Pilot
Ignitor
Igniter
Flame Rod
Sensor
PilotHood
Pilot Hood
10. Remove the orifice from the manifold
and replace it with the one provided
in the kit (Figure 41). See Table 4 on Page 4 for orifice sizes.
Figure 41: Orifice
11. Use pipe joint compound or Teflon®
tape on all pipe fittings before installing.
NOTE: Ensure propane resistant
compounds are used in propane
applications, do not use pipe joint
compounds on flare fittings.
12. Retrieve the burner and hold the venturi
tube above the orifice. Place the shutter
adjusting rod in the slot of the shutter
arm (see Table 27 on Page 29). Set
the burner assem bly into its position
and secure the trapezoidal plate with the
two screws previously removed.
13. Reinstall the baffle with the two baffle
securing screws.
14. Reassemble the remaining components.
15. Turn on gas supply and test for gas leaks (Page 25).
16. Relight the main burner. The
lighting instructions can be found
on the lighting label in the control
compartment or in the Care and
Operation Manual provided with the
appliance. Verify proper burner ignition
and operation (Page 25).
17. Inspect the pilot system for proper
flame. The pilot flame should engulf the
flame sensor (Page 25).
18. Using a manometer, test the inlet and
manifold gas pressures (Table 2 and Table 3).
ALWAYS TEST PRESSURES WITH THE
VALVE REGULATOR CONTROL AT THE
HIGHEST SETTING.
35
Page 36
LENNOX HEARTH PRODUCTS • MERIT® SERIES DIRECT-VENT GAS FIREPLACES • MLDVTCD-35 • INSTALLATION INSTRUCTIONS
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design,
materials, specifications, prices and also to discontinue colors, styles and products.
Consult your local distributor for fireplace code information.
LENNOX®, the LENNOX design, DAVE LENNOX, the image of DAVE LENNOX and other related
LENNOX marks are registered or common law trademarks of Lennox Industries Inc. and are used
with permission.