Lennox Merit 14HPX, Merit 14HPX-018, Merit 14HPX-024, Merit 14HPX-030, Merit 14HPX-036 Installation Instructions Manual

...
Page 1
INSTALLATION
2009 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
INSTRUCTIONS
Merit® Series 14HPX Units
HEAT PUMP UNITS
506377−01 11/09 Supersedes 505,243M
TABLE OF CONTENTS
Shipping and Packing List 1. . . . . . . . . . . . . . . . . . . . . . . .
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Typical Unit Parts Arrangement 2. . . . . . . . . . . . . . . . . . .
Model Number Identification 3. . . . . . . . . . . . . . . . . . . . . .
General Information 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating Gauge Set and Service Valves 3. . . . . . . . . . .
Recovering Refrigerant from Existing System 5. . . . . . .
New Outdoor Unit Placement 6. . . . . . . . . . . . . . . . . . . . .
New or Replacement Line Set 6. . . . . . . . . . . . . . . . . . . . .
Metering Devices and Flushing the System 10. . . . . . . .
Testing for Leaks 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evacuating the System 12. . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Connections 13. . . . . . . . . . . . . . . . . . . . . . . . . .
Servicing Unit Delivered Void of Charge 16. . . . . . . . . . .
Start−Up 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Refrigerant 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing and Installing Louvers 21. . . . . . . . . . . . . . . . .
System Operation 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Defrost System 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up and Performance Checklist 28. . . . . . . . . . . . . .
Litho U.S.A.
IMPORTANT
This unit must be matched with an indoor coil as specified in Lennox Engineering Handbook. Coils previously charged with HCFC−22 must be flushed.
Shipping and Packing List
Check the unit components for shipping damage. If you find any damage, immediately contact the last carrier.
1 − Assembled 14HPX outdoor unit
General
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
11/09 506377−01
The Merit® 14HPX model is designed for use with HFC−410A refrigerant only. This unit must be installed with an approved indoor air handler or coil. See the Lennox 14HPX Engineering Handbook for approved indoor component matchups.
IMPORTANT
This model is designed for use in expansion valve systems only. An indoor expansion valve approved for use with HFC−410A refrigerant must be ordered separately, and installed prior to operating the system.
Page 1
*2P1109* *P506377-01*
Page 2
Unit Dimensions − inches (mm)
A
SIDE VIEW
Model No. A B C
14HPX−018 24−1/4 (616) 29−1/4 (743) 28−1/2 (724)
14HPX−024 24−1/4 (616) 29−1/4 (743) 28−1/2 (724)
14HPX−030 24−1/4 (616) 33−1/4 (845) 32−1/2 (826)
14HPX−036 32−1/4 (819) 29−1/4 (743) 28−1/2 (724)
14HPX−042 32−1/4 (819) 37−1/4 (946) 36−1/2 (927)
14HPX−048 32-1/4 (819) 37−1/4 (946) 36−1/2 (927)
14HPX−060 32-1/4 (819) 43−1/4 (1099) 42−1/4 (1073)
A
OUTDOOR
COIL FAN
COMPRESSOR
DISCHARGE AIR
B
SUCTION AND LIQUID
LINE CONNECTION
OPTIONAL UNIT
STANDOFF KIT (4)
(FIELD INSTALLED)
SIDE VIEW
Typical Unit Parts Arrangement
CONTROL
CAPACITOR
GROUND
LUG
CUTOUT FOR HIGH VOLTAGE CONDUIT
CONTACTOR
DEFROST CONTROL BOARD
CHECK EXPANSION
CONTROL WIRE LOOP
NOTE  PLUMBING LAYOUT AND COMPRESSOR TYPE MAY VARY SLIGHTLY BETWEEN MODEL SIZES.
COMPRESSOR
HARNESS
DEFROST
THERMOSTAT
VALV E
EQUALIZER LINE
BI−FLOW FILTER
LIQUID LINE SERVICE
DRIER
TRUE SUCTION
PORT
HIGH PRESSURE
SWITCH (S4)
VALV E
COMPRESS0R
DISCHARGE LINE
MUFFLER
LOW PRESSURE SWITCH
REVERSING VALVE SOLENOID
VAPOR LINE SERVICE VALVE
REVERSING VALV E
506377−01 11/09
Page 2
Page 3
Model Number Identification
HP X14 024
Nominal SEER
Unit Type
HP = Heat Pump
Refrigerant
X = R−410A
WARNING
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
General Information
These instructions are intended as a general guide and do not supersede national or local codes in any way. Consult authorities having jurisdiction before installation.
Operating Gauge Set and Service Valves
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
TORQUE REQUIREMENTS
When servicing or repairing heating, ventilating, and air conditioning components, ensure the fasteners are appropriately tightened. Table 1 lists torque values for fasteners.
230
2
Minor Revision Number
Voltage
230 = 208/230V−1phase−60hz
Cooling Capacity − Tons 018 = 1.5
024 = 2 030 = 2.5 036 = 3 042 = 3.5 048 = 4 060 = 5
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9 ft−lbs for small valves, to 25 ft−lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
See the Lennox Service and Application Notes #C−08−1 for further details and information.
IMPORTANT
To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.
When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. Table 1 provides torque values for fasteners.
Table 1. Torque Requirements
Parts Recommended Torque
Service valve cap 8 ft.− lb. 11 NM
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 NM
USING MANIFOLD GAUGE SET
When checking the system charge, only use a manifold gauge set that features low loss anti−blow back fittings.
Manifold gauge set used with HFC−410A refrigerant systems must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 − 800 psig on the high side and a low side of 30" vacuum to 250 psig with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psig of pressure with a 4000 psig burst rating.
Page 3
14HPX SERIES
Page 4
OPERATING SERVICE VALVES
The liquid and vapor line service valves are used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging.
SERVICE VALVES
VARIOUS TYPES
OPEN TO BOTH INDOOR AND
OUTDOOR UNITS
SERVICE PORT CAP
SERVICE PORT
TO INDOOR
CORE
UNIT
SERVICE PORT
(VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE
Each valve is equipped with a service port which has a factory−installed valve stem. Figure 1 provides information on how to access and operating both angle and ball service valves.
SERVICE PORT CAP
SERVICE PORT
(VALVE STEM SHOWN CLOSED) INSERT HEX WRENCH HERE
CLOSED TO BOTH
INDOOR AND OUTDOOR
UNITS
TO INDOOR UNIT
FRONT-SEATED
TO INDOOR
STEM CAP
SERVICE PORT
CORE
VALVE STEM
UNIT
TO OUTDOOR
UNIT
(FRONT−SEATED
STEM CAP
ANGLE−TYPE
SERVICE VALVE
CLOSED)
TO OUTDOOR UNIT
WHEN SERVICE VALVE IS CLOSED, THE SERVICE PORT IS OPEN TO THE LINE SET AND INDOOR UNIT.
WHEN SERVICE VALVE IS OPEN, THE SERVICE PORT IS OPEN TO LINE SET, INDOOR AND OUTDOOR UNIT.
To Access Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge set to service port.
3. When testing is completed, replace service port cap and tighten as fol­lows:
With Torque Wrench: Finger tighten and torque cap per Table 1. Without Torque Wrench: Finger tighten and use an appropriately
sized wrench to turn an additional 1/6 turn clockwise.
Operating Angle Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16" for vapor line valve sizes) to back the stem out counterclockwise as far as it will go.
ANGLE−TYPE SERVICE VALVE
(BACK−SEATED OPENED)
TO OPEN ROTATE STEM COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT CORE
SERVICE PORT CAP
TO OUTDOOR UNIT
1/6 TURN
12
11
10
9
8
1
2
3
4
5
7
6
BALL (SHOWN CLOSED)
BALL−TYPE SERVICE
VAL VE
STEM CAP
Operating Ball Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrenched to open. To open valve, rotate stem counterclockwise 90°. To close rotate stem clockwise 90°.
VALVE STEM
Reinstall Stem Cap:
Stem cap protects the valve stem from damage and serves as the primary seal. Replace the stem cap and tighten as follows:
With Torque Wrench: Finger tighten and then torque cap per Table 1. Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turn
an additional 1/12 turn clockwise.
NOTE  A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
Figure 1. Angle and Ball Service Valves
506377−01 11/09
Page 4
9
10
8
11
1/6 TURN
12
1
2
3
4
5
7
6
Page 5
Recovering Refrigerant from Existing System
RECOVERING
REFRIGERANT FROM SYSTEM
DISCONNECT POWER
Disconnect all power to the existing outdoor unit at the service
1
disconnect switch or main fuse box/breaker panel.
MAIN FUSE BOX/
BREAKER PANEL
SERVICE
DISCONNECT
SWITCH
RECOVERING REFRIGERANT
Remove existing refrigerant using one of the following procedures:
3
IMPORTANT  Some system configurations may contain higher than normal refrigerant charge due to either large internal coil volumes,
and/or long line sets.
CONNECT MANIFOLD GAUGE SET
Connect a gauge set, clean recovery cylinder and a recovery
2
machine to the service ports of the existing unit. Use the instructions provided with the recovery machine to make the connections.
MANIFOLD GAUGES
RECOVERY MACHINE
LOW
CLEAN RECOVERY CYLINDER
OUTDOOR UNIT
HIGH
METHOD 1:
Us this method if the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational and you plan to use the existing to flush the system.
Remove all refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.
METHOD 2:
Use this method if the existing outdoor unit is equipped with manual shut−off valves, and you plan to use new refrigerant to flush the system.
The following devices could prevent full system charge recovery into the outdoor unit:
Outdoor unit’s high or low−pressure switches (if applicable) when tripped can cycle the compressor OFF. Compressor can stop pumping due to tripped internal pressure relief valve. Compressor has internal vacuum protection that is designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets
a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed to go into a vacuum. Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seals.)
Once the compressor can not pump down to a lower pressure due to one of the above system conditions, shut off the vapor valve. Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.
Perform the following task:
A Start the existing system in the cooling mode and close the liquid line valve. B Use the compressor to pump as much of the existing HCFC−22 refrigerant into the outdoor unit until the outdoor system is full. Turn the outdoor unit
main power OFF and use a recovery machine to remove the remaining refrigerant from the system.
NOTE  It may be necessary to bypass the low pressure switches (if equipped) to ensure complete refrigerant evacuation.
C When the low side system pressures reach 0 psig, close the vapor line valve.
D Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.
Page 5
14HPX SERIES
Page 6
New Outdoor Unit Placement
See Unit Dimensions on Page 2 for sizing mounting slab, platforms or supports. Refer to Figure 2 for mandatory installation clearance requirements.
*
INSTALL UNIT AWAY
FROM WINDOWS
NOTES:
*
*
*
Service panel access clearance of 30 in. (762 mm) must be
maintained.
Clearance to one of the other three sides must be 36 in. (914
Clearance on one of the remaining two sides may be 12 in. (305
.
mm)
mm) and the final side may be 6 in. (152 mm)
.
Clearance required on top of unit is 48 in. (1219 mm).
A clearance of 24 in. (610 mm) must be maintained between two
units.
Figure 2. Installation Clearances
CAUTION
In order to avoid injury, take proper precaution when lift­ing heavy objects.
TWO 90 ELBOWS INSTALLED IN LINE SET
WILL REDUCE LINE SET VIBRATION
Figure 3. Outside Unit Placement
PLACING OUTDOOR UNIT ON SLAB
When installing a unit at grade level, the top of the slab should be high enough above the grade so that water from higher ground would not collect around the unit as illustrated in Figure 4.
DISCHARGE AIR
BUILDING
STRUCTURE
MOUNTING SLAB
GROUND LEVEL
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line.
When possible, do not install the unit directly outside
a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in Figure 3.
506377−01 11/09
Figure 4. Typical Slab Mounting at Ground Level
Slab may be level or have a slope tolerance away from the building of not more than two degrees, or 2 inches per 5 feet (51 mm per 1524 mm) as illustrated in Figure 4.
INSTALLING OUTDOOR UNIT ON ROOF
Install the unit at a minimum of 4 inches (102 mm) above the surface of the roof. Ensure the weight of the unit is properly distributed over roof joists and rafters. Redwood or steel supports are recommended.
When possible, do not install the unit directly outside
a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in Figure 3.
Page 6
Page 7
New or Replacement Line Set
This section provides information on new installation or replacement of existing line set. If a new or replacement line set is not required, then proceed to Brazing Connections on Page 9.
If refrigerant lines are routed through a wall, seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds.
Also, consider the following when placing and installing a high−efficiency air conditioner:
MATCHING WITH NEW OR EXISTING INDOOR COIL AND LINE SET
The RFC1−metering line consisted of a small bore copper line that ran from condenser to evaporator coil. Refrigerant was metered into the evaporator by utilizing temperature/pressure evaporation effects on refrigerant in the small RFC line. The length and bore of the RFC line corresponded to the size of cooling unit.
If the 14HPX is being used with either a new or existing indoor coil which is equipped with a liquid line which served as a metering device (RFCI), the liquid line must be replaced prior to the installation of the 14HPX unit. Typically a liquid line used to meter flow is 1/4" in diameter and copper.
LINE SET ISOLATION
REFRIGERANT LINE SET
Field refrigerant piping consists of liquid and suction lines from the outdoor unit (braze connections) to the indoor unit coil (flare or braze connections). Use Lennox L15 (braze, non−flare) series line set, or use field−fabricated refrigerant lines as listed in Table 2.
Table 2. Refrigerant Line Set (MM)
Field
Model
−018
−024
−030
−036
−042
−048
−060
NOTE  Some applications may required a field provided 7/8" to 1−1/8" adapter
Connections
Liquid Line
3/8 in. (10 mm)
3/8 in. (10 mm)
3/8 in. (10 mm)
Vapor Line
3/4 in (19 mm)
7/8 in (22 mm)
1−1/8 in. (29 mm)
Recommended Line Set
Liquid Line
3/8 in. (10 mm)
3/8 in. (10 mm)
3/8 in. (10 mm)
Vapor Line
3/4 in (19 mm)
7/8 in (22 mm)
1−1/8 in. (29 mm)
L15 Line Sets
L15−41 15 ft. − 50 ft. (4.6 m − 15 m)
L15−65 15 ft. − 50 ft. (4.6 m − 15 m)
Field Fabricated
NOTE  When installing refrigerant lines longer than 50 feet, contact Lennox Technical Support Product Applications for assistance or Lennox piping manual. To obtain the correct information from Lennox, be sure to communicate the following points:
Model (14HPX) and size of unit (e.g. −060). Line set diameters for the unit being installed as listed
in Table 2 and total length of installation.
Number of elbows and if there is a rise or drop of the
piping.
CAUTION
Brazing alloys and flux contain materials which are hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. Perform operations only in well ventilated areas.
Wear gloves and protective goggles or face shield to protect against burns.
Wash hands with soap and water after handling brazing alloys and flux.
IMPORTANT
The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.
IMPORTANT
If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC−410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity. Failure to properly flush the system per the instructions below will void the warranty.
Page 7
14HPX SERIES
Page 8
LINE SET
INSTALLATION
Line Set Isolation  The following illustrations are
examples of proper refrigerant line set isolation:
REFRIGERANT LINE SET  TRANSITION
FROM VERTICAL TO HORIZONTAL
ANCHORED HEAVY NYLON WIRE TIE OR AUTOMOTIVE
MUFFLER-TYPE HANGER
AUTOMOTIVE
MUFFLER-TYPE HANGER
IMPORTANT  Refrigerant lines must not contact structure.
REFRIGERANT LINE SET  INSTALLING
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)
NOTE  Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.
IMPORTANT  Refrigerant lines must not contact wall
OUTSIDE WALL
VAPOR LINE
LIQUID LINE
WALL STUD
STRAP LIQUID LINE TO VAPOR LINE
LIQUID LINE
NON−CORROSIVE
METAL SLEEVE
VAPOR LINE − WRAPPED IN ARMAFLEX
REFRIGERANT LINE SET  INSTALLING
HORIZONTAL RUNS
To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties.
WIRE TIE (AROUND VAPOR LINE ONLY)
8 FEET (2.43 METERS)
STRAPPING
MATERIAL (AROUND
VAPOR LINE ONLY)
TAPE OR WIRE TIE
FLOOR JOIST OR
ROOF RAFTER
8 FEET (2.43 METERS)
NON−CORROSIVE METAL SLEEVE
STRAP THE VAPOR LINE TO THE JOIST OR RAFTER AT 8 FEET (2.43 METERS) INTERVALS THEN STRAP THE LIQUID LINE TO THE VAPOR LINE.
TAPE OR WIRE TIE
WIRE TIE
INSIDE WALL
WOOD BLOCK
BETWEEN STUDS
SLEEVE
VAPOR LINE WRAPPED
WITH ARMAFLEX
OUTSIDE
WALL
PVC
PIPE
FIBERGLASS
INSULATION
CAULK
STRAP
NON−CORROSIVE METAL SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
LIQUID LINE
NOTE  Similar installation practices should be used if line set is to be installed on exterior of outside wall.
FLOOR JOIST OR
ROOF RAFTER
506377−01 11/09
WARNING  Polyol ester (POE) oils used with HFC−410A refrigerant absorb moisture very quickly. It is very important that the
refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
Figure 5. Line Set Installation
Page 8
Page 9
BRAZING
CONNECTIONS
CUT AND DEBUR
Cut ends of the refrigerant lines square
1
(free from nicks or dents) and debur the ends. The pipe must remain round and do not pinch end of the line.
ATTACHED GAUGES
A Connect gauge set low pressure side to liquid line service
3
valve.
B Connect gauge set center port to bottle of nitrogen with
regulator.
SERVICE PORT MUST BE OPEN TO ALLOW EXIT
INDOOR
UNIT
NOTE − Use silver alloy brazing rods with five or six percent minimum silver alloy for copper−to−copper brazing, 45 percent alloy for copper−to−brass and copper−to−steel brazing.
CAP AND CORE REMOVAL
Remove service cap and core
2
from both the vapor and liquid line service ports.
HIGHLOW
B
ATTACH
POINT FOR NITROGEN
VAPOR LINE
GAUGES
VAPOR LINE
SERVICE
VALV E
OUTDOOR
UNIT
USE REGULATOR TO FLOW
NITROGEN AT 1 TO 2 PSIG.
WRAP SERVICE VALVE
To protect components during
4
brazing, wrap a wet cloth around the liquid line service valve body and copper tube stub and use another wet cloth underneath the valve body to protect the base paint.
BRAZE LINE SET
Braze the liquid line to the liquid line
6
service valve. Turn off nitrogen flow.
POINT FLAME AWAY FROM
SERVICE VALVE
LIQUID LINE
LIQUID LINE SERVICE
5
NOTE  The fixed orifice or check expansion valve metering device at the indoor unit will allow low pressure nitrogen to flow through the system.
VALV E
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid line service valve and out of the valve stem port connection on the vapor service valve.
INSTALL SERVICE PORT CAPS ONLY
After all connections have been brazed, disconnect manifold gauge
7
set from service ports, cool down piping with wet rag and remove all wrappings. Do not reinstall cores until after evacuation procedure. Reinstall service port caps if desired to close off refrigerant ports.
A
LOW
NITROGEN
HIGH
USE REGULATOR TO
FLOW NITROGEN AT 1
TO 2 PSIG.
NITROGEN
WARNING  Allow braze joint to cool before removing the wet rag from the service valve. (TEMPERATURES ABOVE 250ºF CAN DAMAGE VALVE SEALS
IMPORTANT  Connect gauge set low pressure side to vapor line service valve and repeat procedure starting at paragraph 4 for brazing the liquid line to service port valve.
SERVICE PORT
Figure 6. Brazing Connections
Page 9
SERVICE PORT CORE
SERVICE PORT CAP
14HPX SERIES
Page 10
Metering Devices and Flushing the System
FLUSHING
LINE SET AND INDOOR COIL (1 OF 2)
TYPICAL FIXED ORIFICE REMOVAL PROCEDURE
1
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
TEFLON RING
FIXED ORIFICE
TYPICAL CHECK EXPANSION VALVE
REMOVAL AND REPLACEMENT PROCEDURE
TWO PIECE PATCH PLATE
(UNCASED COIL ONLY)
DISTRIBUTOR
TUBES
(Uncased Coil Shown)
ORIFICE
HOUSING
STUB END
TEFLON RING
CHECK
EXPANSION
VALV E
LIQUID LINE
TEFLON
RING
SENSING
LINE
BRASS NUT
DISTRIBUTOR
ASSEMBLY
(Uncased Coil Shown)
A On fully cased coils, remove the coil access and plumbing panels. B Remove any shipping clamps holding the liquid line and distributor
assembly.
C Using two wrenches, disconnect liquid line from liquid line orifice
housing. Take care not to twist or damage distributor tubes during this process.
D Remove and discard fixed orifice, valve stem assembly if present
and Teflon washer as illustrated above.
E Use a field−provided fitting to temporary reconnect the liquid line to
the indoor unit’s liquid line orifice housing.
REMOVE AND DISCARD
WHITE TEFLON SEAL (IF
PRESENT)
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
CONNECT GAUGES AND EQUIPMENT FOR FLUSHING PROCEDURE
2
VAPOR LINE
SERVICE VALVE
EXISTING
INDOOR
UNIT
LIQUID LINE SERVICE
RECOVERY
CYLINDER
A Inverted cylinder with clean refrigerant to the vapor service valve. B gauge set (low side) to the liquid line valve. C gauge set center port to inlet on the recovery machine with an empty
D Connect recovery tank to recovery machines per machine
VALV E
LIQUID
D
recovery tank to the gauge set.
instructions.
INVERTED CYLINDER CONTAINS CLEAN TO BE USED FOR FLUSHING.
A
1
VAPOR
OUTDOOR
B
NEW
UNIT
C
GAUGE
MANIFOLD
LOW
OPENED
TANK RETURN
INLET
DISCHARGE
RECOVERY MACHINE
CLOSED
HIGH
OR
A On fully cased coils, remove the coil access and plumbing panels. B Remove any shipping clamps holding the liquid line and distributor as-
C Disconnect the equalizer line from the check expansion valve equaliz-
D Remove the vapor line sensing bulb. E Disconnect the liquid line from the check expansion valve at the liquid
F Disconnect the check expansion valve from the liquid line orifice hous-
G Remove and discard check expansion valve and the two Teflon rings. H Use a field−provided fitting to temporary reconnect the liquid line to the
I Reverse above order to install.
CAUTION  This procedure should not be performed on systems
which contain contaminants (Example compressor burn out.
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER
LINE FITTING
SENSING BULB
sembly.
er line fitting on the vapor line.
line assembly.
ing. Take care not to twist or damage distributor tubes during this pro­cess.
indoor unit’s liquid line orifice housing.
EQUALIZER LINE
ASSEMBLY WITH
VAPOR
LINE
LIQUID LINE
BRASS NUT
LIQUID
FLUSHING LINE SET
The line set and indoor unit coil must be flushed with at least the
3
same amount of clean refrigerant that previously charged the sys­tem. Check the charge in the flushing cylinder before proceeding.
B
A Set the recovery machine for liquid recovery and start the recov-
ery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and in­door unit coil.
B Invert the cylinder of clean and open its valve to allow liquid re-
frigerant to flow into the system through the vapor line valve. Al­low the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine.
C After all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the vapor is recovered. Allow the recovery machine to pull down to 0 the sys­tem.
D Close the valve on the inverted drum and the gauge set valves.
Pump the remaining refrigerant out of the recovery machine and turn the machine off.
LINE
506377−01 11/09
Page 10
Page 11
Leak Testing the System
LEAK TEST
LINE SET AND INDOOR COIL
CONNECT GAUGE SET
A Connect an HFC−410A manifold gauge set high
1
pressure hose to the vapor valve service port.
B With both manifold valves closed, connect the
cylinder of HFC−410A refrigerant to the center port of the manifold gauge set.
NOTE  Later in the procedure, the HFC−410A container will be replaced by the nitrogen container.
NOTE  Normally, the high pressure hose is connected to the liquid line port. How­ever, connecting it to the vapor port better protects the manifold gauge set from high pressure damage.
HIGHLOW
MANIFOLD GAUGE SET
OUTDOOR UNIT
USE REGULATOR TO FLOW
NITROGEN AT 1 TO 2 PSIG.
NITROGEN
TEST FOR LEAKS
After the line set has been connected to the indoor unit and air conditioner, check the line set connections and
2
indoor unit for leaks. Use the following procedure to test for leaks: A With both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of the manifold gauge set. Open
the valve on the HFC−410A cylinder (vapor only).
B Open the high pressure side of the manifold to allow HFC−410A into the line set and indoor unit. Weigh in a trace amount of
HFC−410A. [A trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the HFC−410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC−410A cylinder.
C Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.
D Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the
line set and the indoor unit.
E After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable
with a leak detector.
F After leak testing disconnect gauges from service ports.
HFC−410A
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
B
TO VAPOR
SERVICE VALVE
Fire, Explosion and Personal Safety Hazard.
Failure to follow this warning could result in damage, personal injury or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause damage by fire and/or an explosion, that could result in personal injury or death.
IMPORTANT
A
WARNING
Leak detector must be capable of sensing HFC refrigerant.
Page 11
14HPX SERIES
Page 12
Evacuating the System
EVACUATING
LINE SET AND INDOOR COIL
CONNECT GAUGE
NOTE  Remove cores from service valves (if not al-
SET
ready done).
1
A Connect low side of manifold gauge set
with 1/4 SAE in−line tee to vapor line service valve
B Connect high side of manifold gauge
set to liquid line service valve
C Connect micron gauge available
connector on the 1/4 SAE in−line tee.
D Connect the vacuum pump (with
vacuum gauge) to the center port of the manifold gauge set. The center port line will be used later for both the HFC−410A and nitrogen containers.
USE REGULATOR TO FLOW
NITROGEN AT 1 TO 2 PSIG.
HFC−410A
VACUUM PUMP
OUTDOOR
UNIT
A
B
A34000 1/4 SAE TEE WITH SWIVEL COUPLER
500
C
D
MICRON
GAUGE
LOW
TO VAPOR
SERVICE VALVE
TO LIQUID LINE SERVICE VALVE
MANIFOLD
GAUGE SET
HIGH
NITROGEN
RECOMMEND
MINIMUM 3/8" HOSE
EVACUATE THE SYSTEM
A Open both manifold valves and start the vacuum pump.
2
B Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
NOTE  During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE  The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
C When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum
pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves.
D Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the
dry nitrogen from the line set and indoor unit.
E Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the
absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing the manifold gauge valves.
F When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an
upright cylinder of HFC−410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit.
G Perform the following:
Close manifold gauge valves. Shut off HFC−410A cylinder. Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with
core tool while maintaining a positive system pressure.
Replace the stem caps and secure finger tight, then tighten an additional one−sixth (1/6) of a turn as
illustrated.
11
10
9
8
7
12
6
1/6 TURN
1
2
3
4
5
506377−01 11/09
Page 12
Page 13
IMPORTANT
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns.
WARNING
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
Evacuating the system of non−condensables is critical for proper operation of the unit. Non−condensables are
defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Non−condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts.
Electrical
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air handler for low-voltage control power (24VAC − 40 VA minimum)
SIZE CIRCUIT AND INSTALL SERVICE DISCONNECT SWITCH
Refer to the unit nameplate for minimum circuit ampacity, and maximum fuse or circuit breaker (HACR per NEC). Install power wiring and properly sized disconnect switch.
MAIN FUSE BOX/ BREAKER PANEL
SERVICE
DISCONNECT
SWITCH
NOTE  Units are approved for use only with copper conductors. Ground unit at disconnect switch or to an earth ground.
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
INSTALL THERMOSTAT
Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight or drafts.
THERMOSTAT
5 FEET
(1.5M)
NOTE  24VAC, Class II circuit connections are made in the control panel.
Page 13
14HPX SERIES
Page 14
ROUTING HIGH VOLTAGE/ GROUND AND CONTROL WIRING
HIGH VOLTAGE / GROUND WIRES
Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring. To facilitate a conduit, a cutout is located in the bottom of the control panel. Connect conduit to the control panel using a proper conduit fitting.
CONTROL WIRING
Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit as illustrated.
A Run 24VAC control wires through hole with grommet.
B Make 24VAC thermostat wire connections to CMC1.
NOTE  Do not bundle any excess 24VAC control wires inside control panel.
NOTE  For proper voltages, select thermostat wire (control wires) gauge per Table above.
WIRE RUN LENGTH AWG# INSULATION TYPE
LESS THAN 100’ (30 METERS) 18 TEMPERATURE RATING
MORE THAN 100’ (30 METERS) 16 35ºC MINIMUM.
HIGH VOLTAGE FIELD WIRING
LOW VOLTAGE FIELD WIRING
FACTORY WIRING
SINGLE PHASE
DEFROST CONTROL
Thermostat
BOARD (CMC1)
TYPICAL CONTROL WIRING
Low Voltage Wiring
Indoor Unit
R
C
W1
G
O
Y1
power
common
1st. stage aux. heat
indoor blower
reversing valve
compressor
(SOME CONNECTIONS MAY NOT APPLY. REFER TO SPECIFIC THERMOSTAT AND INDOOR UNIT.)
R
C
W1
W2
W3
G
NOTE  Wire tie provides low voltage wire strain relief and to maintain separation of field installed low and high voltage circuits.
Outdoor Unit
power
common
1st. stage aux. heat
Low Voltage Wiring (with Auxiliary Heat)
Thermostat Indoor Unit Outdoor Unit
R
C
emergency heat
E
power
common
R
C
emer.
heat
relay
power
common
R
C
W1
O
Y1
R
C
HIGH VOLTAGE CONNECTIONS
(CONTACTOR)
GROUND
CUTOUT FOR HIGH VOLTAGE CONDUIT
506377−01 11/09
A
GROMMET AND WIRE TIE
FOR CONTROL WIRES
B
CONTROL WIRE CONNECTIONS
Page 14
W1
1st. stage aux. heat
indoor blower
G
reversing valve
O
compressor
Y1
(SOME CONNECTIONS MAY NOT APPLY. REFER TO
SPECIFIC THERMOSTAT AND INDOOR UNIT.)
W1
1st. stage aux. heat
W2
W3
G
outdoor t’stat
W1
O
Y1
Page 15
Figure 7. Typical Field Wiring Diagram
Page 15
14HPX SERIES
Page 16
GAUGE SET
CONNECTIONS FOR TESTING AND CHARGING
TRUE SUCTION PORT
B
CONNECTION
REFRIGERANT TANK
MANIFOLD GAUGE SET
LOW
HIGH
OUTDOOR UNIT
CHARGE IN
LIQUID PHASE
DIGITAL SCALE
D
TEMPERATURE
SENSOR
A Close manifold gauge set valves and connect the center hose to a cylinder of HFC−410A. Set
for liquid phase charging.
INSIDE OUTDOOR UNIT
B Connect the manifold gauge set’s low pressure side to the true suction port.
C Connect the manifold gauge set’s high pressure side to the liquid line service port.
D Position temperature sensor on liquid line near liquid line service port.
Figure 8. Gauge Set Connections
Servicing Units Delivered Void of Charge
If the outdoor unit is void of refrigerant, clean the system using the procedure described below.
1. Leak check system using procedure outlined on Page
11.
2. Evacuate the system using procedure outlined on Page 12.
3. Use nitrogen to break the vacuum and install a new filter drier in the system.
4. Evacuate the system again using procedure outlined on Page 12.
5. Weigh in refrigerant using procedure outlined in Figure
10.
Start−Up
IMPORTANT
Crankcase heater (if applicable) should be energized 24 hours before unit start−up to prevent compressor dam­age as a result of slugging.
1. Rotate fan to check for binding.
2. Inspect all factory and field-installed wiring for loose connections.
506377−01 11/09
LINE SERVICE
Page 16
A
C
TO LIQUID
VALV E
3. After evacuation is complete, open the liquid line and suction line service valves to release the refrigerant charge (contained in outdoor unit) into the system.
4. Replace the stem caps and tighten as specified in Operating Service Valves on Page 3.
5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit’s nameplate. If not, do not start the equipment until you have consulted with the power company and the voltage condition has been corrected.
6. Set the thermostat for a cooling demand. Turn on power to the indoor indoor unit and close the outdoor unit disconnect switch to start the unit.
7. Recheck voltage while the unit is running. Power must be within range shown on the nameplate.
8. Check system for sufficient refrigerate by using the procedures listed under Start−Up and Charging Procedures.
9. Recheck voltage while the unit is running. Power must be within range shown on the nameplate.
TEMPERATURE SENSOR
(LIQUID LINE)
LIQUID LINE SERVICE PORT
System Refrigerant
This section outlines procedures for:
1. Connecting gauge set for testing and charging;
2. Checking and adjusting indoor airflow;
3. Adding or removing refrigerant.
Page 17
ADDING OR REMOVING REFRIGERANT
This system uses HFC−410A refrigerant which operates at much higher pressures than . The pre−installed liquid line filter drier is approved for use with HFC−410A only. Do not replace it with components designed for use with . This unit is NOT approved for use with coils which use capillary tubes or fixed orifices as a refrigerant metering device.
Check airflow using the Delta−T (
DT) process using the illustration in Figure 9.
AIRFLOW
INDOOR COIL
Temperature of air entering indoor coil ºF
A
Wet−bulb ºF
80 24 24 24 23 23 22 22 22 20 19 18 17 16 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13
Dry−bulb
74 21 21 21 20 19 19 18 17 16 16 15 14 13 12 72 20 20 19 18 17 17 16 15 15 14 13 12 11 10 70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
57 58 59 60 61 62 63 64 65 66 67 68 69 70
DT
DRY
BULB
C
53º
T
19º
Drop
air flow
air flow
B
B
64º
All temperatures are expressed in ºF
INDOOR COIL
WET BULB
Use the following procedure to adjust for optimal air flow across the indoor coil:
1. Determine the desired DT  Measure entering air temperature using dry bulb (A) and wet bulb (B). DT
is the intersecting value of A and B in the Table (see triangle).
2. Find temperature drop across coil  Measure the coil’s dry bulb entering and leaving air temperatures (A and C). Temperature Drop Formula: (T
3. Determine if fan needs adjustment  If the difference between the measured T
DT (T
DT) is within +3º, no adjustment is needed. See example below:
Drop
) = A minus C.
Drop
and the desired
Drop
Assume DT = 15 and A temp. = 72º, these C temperatures would necessitate stated actions:
A
72º
DRY BULB
T
53º 19 – 15 = 4 Increase the airflow 58º 14 – 15 = −1 (within +3º range) no change 62º 10 – 15 = −5 Decrease the airflow
DT = ºF ACTION
Drop
4. Adjust the fan speed  See indoor unit instructions to increase/decrease fan speed.
Figure 9. Checking Indoor Airflow over Evaporator Coil using Delta−T Chart
Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and DT are within +3º.
Page 17
14HPX SERIES
Page 18
Use WEIGH IN method for adding initial refrigerant charge, and then use SUBCOOLING method for verifying refrigerant charge.
WEIGH IN
OUTDOOR UNIT VOID OF CHARGE
If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit. To calculate the total refrigerant charge:
CALCULATING SYSTEM CHARGE FOR
Amount specified on nameplate
Adjust amount. for variation in line set
length listed on line set length table below.
+
+
Additional charge specified per indoor
unit match−ups starting on Page 19.
Total charge
=
Refrigerant Charge per Line Set Length
Liquid Line
Set Diameter
3/8" (9.5 mm)
*If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
NOTE  Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.
NOTE  The above nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.
Ounces per 5 feet (g per 1.5 m)
adjust from 15 feet (4.6 m) line set*
3 ounce per 5’ (85 g per 1.5 m)
SUBCOOLING
USE COOLING
MODE
60ºF (15º)
USE HEATING
MODE
SATº LIQº – SCº =
Figure 10. Weigh In Method
1 Check the airflow as illustrated in figure 9 to be sure the indoor airflow is as required. (Make any air flow
adjustments before continuing with the following procedure.)
2 Measure outdoor ambient temperature; determine whether to use cooling mode or heating mode to
check charge.
3 Connect gauge set.
4 Check Liquid and Vapor line pressures. Compare pressures with Normal Operating Pressures table 10,
(The reference table is a general guide. Expect minor pressure variations. Significant differences may mean improper charge or other system problem.)
5 Set thermostat for heat/cool demand, depending on mode being used:
Using cooling modeWhen the outdoor ambient temperature is 60°F (15°C) and above. Target
subcooling values in table below are based on 70 to 80°F (21−27°C) indoor return air temperature; if necessary, operate heating to reach that temperature range; then set thermostat to cooling mode setpoint to 68ºF (20ºC). When pressures have stabilized, continue with step 6.
Using heating modeWhen the outdoor ambient temperature is below 60°F (15°C). Target subcooling
values in table below are based on 65−75°F (18−24°C) indoor return air temperature; if necessary, operate cooling to reach that temperature range; then set thermostat to heating mode setpoint to 77ºF (25ºC). When pressures have stabilized, continue with step 6.
6 Read the liquid line temperature; record in the LIQº space.
7 Read the liquid line pressure; then find its corresponding temperature in the temperature/ pressure chart
listed in table 11 and record it in the SATº space.
8 Subtract LIQº temp. from SATº temp. to determine subcooling; record it in SCº space.
9 Compare SCº results with table below, being sure to note any additional charge for line set and/or match−up.
10 If subcooling value is greater than shown in tables 3 through 8 for the applicable unit, remove refrigerant;
if less than shown, add refrigerant.
11 If refrigerant is added or removed, repeat steps 5 through 10 to verify charge.
506377−01 11/09
Figure 11. Subcooling Method
Page 18
Page 19
Table 3. 14HPX−018
g
g
g
g
g
g
g
g
Target
INDOOR MATCHUPS
CBX27UH−018/024 13 7 0 8 CBX32MV−018/024 15 7 0 0 CBX40UHV−024 15 7 0 0
Subcooling
Heat Cool
5ºF)(+1ºF)
(+
*Add
charge
lb oz
Table 4. 14HPX−024
Target
INDOOR MATCHUPS
CH23−41 16 8 0 2 CBX26UH−024 25 7 0 0 CBX27UH−018/024 15 8 1 2 CBX32M−018/024 16 8 0 14 CBX32M−030 15 8 1 3 CBX32MV−018/024 16 8 0 4 CBX32MV−024/030 15 8 1 2 CH33−25A 16 6 0 7 CH33−42B 14 11 1 10 CH33−36A 16 8 1 0 CH33−36C 16 8 0 4 CR33−30/36A/B/C 25 7 0 2 CX34−25A/B 16 8 0 14 CX34−31A/B 15 8 1 3 CX34−36A/B/C 16 8 1 8 CX34−38A/B S/N# 6007 and after 11 11 2 2 CX34−38A/B before S/N# 6007 14 11 2 2
Subcooling
Heat Cool
5ºF)(+1ºF)
(+
*Add
charge
lb oz
Table 5. 14HPX−030
Target
INDOOR MATCHUPS
C33−44C 11 6 2 3 CH23−41 11 6 0 8 CH23−51 6 6 1 12 CBX26UH−024 30 8 0 6 CBX26UH−030 29 8 2 3 CBX27UH−030 11 6 2 4 CBX32M−030 11 6 1 6 CBX32M−036 11 6 2 4 CBX32MV−024/030 11 6 1 6 CBX32MV−036 25 7 0 0 CBX40UHV−024, −030 11 6 1 6 CBX40UHV−036 25 6 0 0 CH33−36C 11 3 0 0 CH33−42B 6 6 1 12 CR33−30/36A/B/C 30 8 0 8 CX34−31A/B 11 6 1 6 CX34−38A/B S/N# 6007 and after 6 6 2 3 CX34−38A/B before S/N# 6007 11 6 2 3 CX34−43B/C 15 11 2 14
Subcooling
Heat Cool
5ºF)(+1ºF)
(+
*Add
charge
lb oz
Table 6. 14HPX−036
Target
INDOOR MATCHUPS
C33−44C 13 6 0 0 CBX26UH−036 26 5 0 0 CBX26UH−037 25 4 1 9 CBX27UH−036 13 6 0 3 CBX32M−036 13 6 0 2 CBX32M−042 13 6 0 3 CBX32MV−036 13 6 0 3 CBX32MV−048 11 8 2 5 CH33−50/60C 11 8 2 5 CH33−44B 13 6 1 7 CH33−48B 13 6 1 8
Subcooling
Heat Cool
5ºF)(+1ºF)
(+
*Add
charge
lb oz
Target
INDOOR MATCHUPS
14HPX−036 (Continued)
CR33−50/60C 25 4 1 15 CR33−48B/C 25 5 0 9 CX34−49C 13 6 2 4 CX34−43B/C, −50/60C 13 6 1 8 CX34−38A/B S/N# 6007 and after 6 6 0 0 CX34−38A/B before S/N# 6007 13 6 0 0
Subcooling
Heat Cool
5ºF)(+1ºF)
(+
*Add
charge
lb oz
Table 7. 14HPX−042
Target
INDOOR MATCHUPS
CH23−68 20 9 0 13 CBX26UH−042 27 6 0 0 CBX27UH−042 12 6 0 8 CBX32M−048 12 6 0 7 CBX32MV−048 12 6 0 8 CBX40UHV−042, −048 12 6 0 8 CH33−43 12 6 0 7 CH33−62D 12 6 0 10 CH33−50/60C 12 6 0 7 CH33−60D 12 6 0 4 CR33−50/60C,−60D 26 6 0 4 CX34−62C, −62D 12 6 0 9 CX34−49C 12 6 0 7 CX34−60D 12 6 0 4
Subcooling
Heat Cool
5ºF)(+1ºF)
(+
*Add
charge
lb oz
Table 8. 14HPX−048
Target
INDOOR MATCHUPS
CH23−68 20 9 2 9 CBX26UH−048 8 7 1 9 CBX27UH−048 11 8 1 2 CBX32M−048, −060 11 8 1 2 CBX32MV−048 25 8 0 0 CBX32MV−060 11 8 1 2 CBX32MV−068 10 7 1 12 CBX40UHV−048 25 6 0 0 CBX40UHV−060 12 6 0 8 CH33−50/60C 11 8 1 1 CH33−62D 10 7 1 14 CH33−60D 11 8 0 0 CR33−50/60C 35 5 0 0 CR33−60D 37 6 0 0 CX34−62C, −62D 10 7 1 7 CX34−49D 11 8 0 14 CX34−60D 11 8 0 0
Subcooling
Heat Cool
5ºF)(+1ºF)
(+
*Add
charge
lb oz
Table 9. 14HPX−060
Target
INDOOR MATCHUPS
CH23−68 12 5 0 0 CBX26UH−048 12 7 1 0 CBX26UH−060 14 4 0 0 CBX27UH−060 12 5 0 0 CBX32M−048, −060 12 5 0 0 CBX32MV−048, −060 12 5 0 0 CBX32MV−068 12 7 1 0 CH33−50/60C 12 5 0 0 CH33−62D 12 5 0 0 CX34−62C, −62D 12 7 1 0
Subcooling
Heat Cool
5ºF)(+1ºF)
(+
NOTE − *Add charge = Extra match up amount required in addition to charge indicated on Heat Pump nameplate (remember to also add any charge required for line set differences from 15 feet).
*Add
charge
lb oz
Page 19
14HPX SERIES
Page 20
Table 10. Normal Operating Pressures − Liquid +10 and Vapor +5 PSIG*
IMPORTANT
Use table 10 as a general guide when performing maintenance checks. This is not a procedure for charging the unit (Refer to Charging / Checking Charge section). Minor variations in these pressures may be expected due to differences in instal­lations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system.
14HPX−018 14HPX−024 14HPX−030 14HPX−036 14HPX−042 14HPX−048 14HPX−060
5F (5C)**
65 (18) 226 / 140 233 / 137 238 / 138 220 / 138 223 / 125 231 / 136 243 / 136
70 (21) 244 / 141 252 / 138 263 / 139 236 / 140 241 / 130 248 / 139 263 / 137
75 (24) 263 / 142 271 / 140 279 / 139 256 / 141 261 / 134 271 / 140 282 / 138
80 (27) 283 / 143 292 / 141 299 / 140 276 / 142 282 / 138 291 / 142 306 / 139
85 (29) 302 / 144 314 / 142 324 / 141 298 / 143 302 / 139 312 / 143 327 / 140
90 (32) 328 / 145 338 / 143 340 / 142 321 / 144 326 / 140 335 / 144 351 / 141
95 (35) 351 / 146 361 / 145 375 / 145 344 / 144 349 / 141 359 / 145 376 / 142
100 (38) 376 / 147 387 / 146 397 / 145 369 / 146 374 / 142 384 / 146 401 / 143
105 (41) 402 / 148 412 / 147 424 / 147 394 / 147 399 / 143 411 / 148 426 / 145
110 (38) 430 / 149 441 / 148 454 / 150 421 / 148 428 / 145 439 / 149 452 / 146
115 (45) 465 / 150 471 / 151 485 / 150 449 / 149 455 / 146 468 / 150 484 / 148
60 (15) 346 / 139 352 / 138 338 / 137 350 / 134 373 / 139 355 / 130 351 / 117
50 (10) 323 / 117 331 / 114 334 / 112 331 / 117 363 / 117 336 / 113 333 / 105
40 (4) 306 / 98 304 / 99 312 / 93 313 / 97 348 / 97 315 / 88 316 / 88
30 (−1) 278 / 84 299 / 80 302 / 74 298 / 83 336 / 74 296 / 72 308 / 70
20 (−7) 273 / 66 283 / 66 280 / 53 284 / 66 322 / 64 286 / 64 300 / 61
*IMPORTANTThese are most−popular−match−up pressures. Indoor match up and indoor load cause pressures to vary.
**Temperature of the air entering the outside coil (outdoor ambient temperature).
Liquid / Vapor Liquid / Vapor Liquid / Vapor Liquid/ Vapor Liquid / Vapor Liquid / Vapor Liquid / Vapor
Cooling
Heating
Table 11. HFC−410A Temperature  Pressure (Psig)
°F °C Psig °F °C Psig
−40 −40.0 11.6 60 15.6 170
−35 −37.2 14.9 65 18.3 185
−30 −34.4 18.5 70 21.1 201
−25 −31.7 22.5 75 23.9 217
−20 −28.9 26.9 80 26.7 235
−15 −26.1 31.7 85 29.4 254
−10 −23.3 36.8 90 32.2 274
−5 −20.6 42.5 95 35.0 295 0 −17.8 48.6 100 37.8 317 5 −15.0 55.2 105 40.6 340
10 −12.2 62.3 110 43.3 365 15 −9.4 70.0 115 46.1 391 20 −6.7 78.3 120 48.9 418 25 −3.9 87.3 30 −1.1 96.8 130 54.4 476 35 1.7 107 135 57.2 507 40 4.4 118 140 60.0 539 45 7.2 130 50 10.0 142 55 12.8 155
125 51.7 446
145 62.8 573 150 65.6 608
506377−01 11/09
Page 20
Page 21
Removing and Installing Louvers
WARNING
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and battered.
ORDER OF REMOVAL AND REINSTALLATION
When removing the unit panels. Remove panel A first, then B, C and finally D. When reinstalling pan­els, reverse that order starting with panel D, C, B and finally A.
REMOVAL
STEP 1
TO REMOVE PANEL, REMOVE MOUNTING SCREWS SECURING PANEL TO THE UNIT.
PANEL A
PANEL B
PANEL A
PANEL C
WARNING
PANEL D
INSTALLATION
TOP CAP
STEP 1
STARTING WITH PANEL D, INSERT PANEL UNDER UNIT TOP CAP LIP AND LIFT SLIGHTLY TO CLEAR SIDE LIP OF PANEL FROM BASE.
SIDE
GROOVE
STEP 2
SLIGHTLY LIFT PANEL A IN ORDER TO CLEAR SIDE LIPS OF PANEL FROM BASE OF UNIT.
STEP 3
TILT PANEL OUT SLIGHTLY AND PULL DOWNWARD TO REMOVE.
REPEAT STEPS 1, 2 AND 3 TO REMOVE PANELS B, C AND FINALLY D.
PANEL A
STEP 2
MOVE PANEL IN TOWARDS UNIT. ALIGN LEFT/RIGHT SIDE LIPS OF PANEL WITH GROOVE INSERTS ALONG LEFT/RIGHT SIDE OF UNIT.
STEP 3
SECURE PANEL, WITH MOUNTING SCREWS.
REPEAT STEPS 1 AND 2 TO INSTALL PANELS C, B AND FINALLY A.
BASE
Page 21
PANEL D
14HPX SERIES
Page 22
System Operation
The outdoor unit and indoor blower cycle on demand from the room thermostat. If the thermostat blower switch is in the ON position, the indoor blower operates continuously.
FILTER DRIER
The unit is equipped with a large−capacity biflow filter drier which keeps the system clean and dry. If replacement is necessary, order another of the same design and capacity. The replacement filter drier must be suitable for use with HFC−410A refrigerant.
TEST PINS
DEFROST
TERMINATION
PIN SETTINGS
SENSOR
PLUG IN
(COIL & AM-
BIENT
SENSORS)
DELAY
PINS
REVERSING
VALV E
LOW AMBIENT THERMOSTAT PINS
DIAGNOSTIC LEDS
24V TERMINAL STRIP CONNECTIONS
LOW PRESSURE SWITCH (OPTIONAL)
The 14HPX may be equipped with an optional auto−reset low pressure switch which is located on the vapor line. The switch shuts off the compressor when the vapor pressure falls below the factory setting. This switch, which is ignored during defrost operation, closes at pressures at or above 55 psig and opens at 25 psig. It is not adjustable.
HIGH PRESSURE SWITCH
The 14HPX is equipped with an auto-reset high pressure switch (single−pole, single−throw) which is located on the liquid line. The switch shuts off the compressor when discharge pressure rises above the factory setting. The switch is normally closed and is permanently adjusted to trip (open) at 590 + 10 psig (4412 + 69 kPa).
NOTE − A Schrader core is under the pressure switches.
Defrost System
DEFROST SYSTEM DESCRIPTION
The demand defrost controller measures differential temperatures to detect when the system is performing poorly because of ice build−up on the outdoor coil. The controller self−calibrates" when the defrost system starts and after each system defrost cycle. The defrost control board components are shown in figure 12.
The control monitors ambient temperature, outdoor coil temperature, and total run time to determine when a defrost cycle is required. The coil temperature probe is designed with a spring clip to allow mounting to the outside coil tubing. The location of the coil sensor is important for proper defrost operation.
NOTE − The demand defrost board accurately measures the performance of the system as frost accumulates on the outdoor coil. This typically will translate into longer running time between defrost cycles as more frost accumulates on the outdoor coil before the board initiates defrost cycles.
DIAGNOSTIC LEDS
The state (Off, On, Flashing) of two LEDs on the defrost board (DS1 [Red] and DS2 [Green]) indicate diagnostics conditions that are described in table 13.
PRESSURE
SWITCH CIR-
CUIT CONNEC-
TIONS
Note − Compo­nent Locations Vary by Board Manufacturer.
Figure 12. Defrost Control Board
DEFROST BOARD PRESSURE SWITCH CONNECTIONS
The unit’s automatic reset pressure switches (LO PS − S87 and HI PS − S4) are factory−wired into the defrost board on the LO−PS and HI−PS terminals, respectively.
(OPTIONAL) Low Pressure Switch (LO−PS)When the low pressure switch trips, the defrost board will cycle off the compressor, and the strike counter in the board will count one strike. The low pressure switch is ignored under the following conditions:
during the defrost cycle and 90 seconds after the
termination of defrost
when the average ambient sensor temperature is
below 15° F (−9°C)
for 90 seconds following the start up of the compressor during "test" mode
High Pressure Switch (HI−PS)When the high pressure switch trips, the defrost board will cycle off the compressor, and the strike counter in the board will count one strike.
DEFROST BOARD PRESSURE SWITCH SETTINGS High Pressure (auto reset) − trip at 590 psig; reset at 418.
Low Pressure (auto reset) − trip at 25 psig; reset at 40. 5−STRIKE LOCKOUT FEATURE
The internal control logic of the board counts the pressure switch trips only while the Y1 (Input) line is active. If a pressure switch opens and closes four times during a Y1 (Input), the control logic will reset the pressure switch trip counter to zero at the end of the Y1 (Input). If the pressure switch opens for a fifth time during the current Y1 (Input), the control will enter a lockout condition.
The 5−strike pressure switch lockout condition can be reset by cycling OFF the 24−volt power to the control board or by shorting the TEST pins between 1 and 2 seconds. All timer functions (run times) will also be reset.
If a pressure switch opens while the Y1 Out line is engaged, a 5−minute short cycle will occur after the switch closes.
506377−01 11/09
Page 22
Page 23
AMBIENT SENSOR
Figure 13. Sensor Locations
DEFROST SYSTEM SENSORS
Sensors connect to the defrost board through a field-replaceable harness assembly that plugs into the board. Through the sensors, the board detects outdoor ambient, coil, and discharge temperature fault conditions. As the detected temperature changes, the resistance across the sensor changes. Figure 14 shows how the resistance varies as the temperature changes for both type of sensors. Sensor resistance values can be checked by ohming across pins shown in table 12.
NOTE − When checking the ohms across a sensor, be aware that a sensor showing a resistance value that is not within the range shown in table 12, may be performing as designed. However, if a shorted or open circuit is detected, then the sensor may be faulty and the sensor harness will needs to be replaced.
Table 12. Sensor Temp. / Resistance Range
Temperature
Sensor
Outdoor (Ambient)
Coil −35 (−37) to 120
Discharge (if applicable)
Note: Sensor resistance decreases as sensed temperature increases (see figure 14).
Range °F (°C)
−35 (−37) to 120 (48)
(48)
24 (−4) to 350 (176)
Resistance values range (ohms)
280,000 to 3750 3 & 4
280,000 to 3750 5 & 6
41,000 to 103 1 & 2
Pins/Wire Color
(Black)
(Brown)
(Yellow)
Coil SensorThe coil temperature sensor (shown in figure 13) considers outdoor temperatures below −35°F (−37°C) or above 120°F (48°C) as a fault. If the coil temperature sensor is detected as being open, shorted or
Page 23
14HPX SERIES
Page 24
out of the temperature range of the sensor, the board will not perform demand or time/temperature defrost operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault condition.
Ambient and Coil Sensor
100
TEMPERATURE (ºF)
Ambient SensorThe ambient sensor (shown in figure
13) considers outdoor temperatures below −35°F (−37°C) or above 120°F (48°C) as a fault. If the ambient sensor is detected as being open, shorted or out of the temperature range of the sensor, the board will not perform demand defrost operation. The board will revert to time/temperature defrost operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault condition.
NOTE − Within a single room thermostat demand, if 5−strikes occur, the board will lockout the unit. Defrost board 24 volt power R" must be cycled OFF" or the TEST" pins on board must be shorted between 1 to 2 seconds to reset the board.
Defrost Temperature Termination Shunt (Jumper) PinsThe defrost board selections are: 50, 70, 90, and
100°F (10, 21, 32 and 38°C). The shunt termination pin is factory set at 50°F (10°C). If the temperature shunt is not installed, the default termination temperature is 90°F (32°C).
DELAY MODE
The defrost board has a field−selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. When a jumper is installed on the DELAY pins, the compressor will be cycled off for 30 seconds going in and out of the defrost mode. Units are shipped with jumper installed on DELAY pins.
NOTE − The 30 second off cycle is NOT functional when jumpering the TEST pins.
OPERATIONAL DESCRIPTION
The defrost control board has three basic operational modes: normal, calibration, and defrost.
Normal ModeThe demand defrost board monitors the O line, to determine the system operating mode (heat/cool), outdoor ambient temperature, coil temperature (outdoor coil) and compressor run time to determine when a defrost cycle is required.
5750
90
80
70
60
50
40
30
20
10
7450
9275
11775
15425
19975
26200
34375
46275
62700
0
10000 30000 50000 70000 90000
RESISTANCE (OHMS)
85300
Figure 14. Temperature/Resistance Chart
Calibration ModeThe board is considered uncalibrated
when power is applied to the board, after cool mode operation, or if the coil temperature exceeds the termination temperature when it is in heat mode.
Calibration of the board occurs after a defrost cycle to ensure that there is no ice on the coil. During calibration, the temperature of both the coil and the ambient sensor are measured to establish the temperature differential which is required to allow a defrost cycle.
Defrost ModeThe following paragraphs provide a detailed description of the defrost system operation.
DETAILED DEFROST SYSTEM OPERATION
Defrost CyclesThe demand defrost control board
initiates a defrost cycle based on either frost detection or time.
Frost DetectionIf the compressor runs longer than
30 minutes and the actual difference between the clear coil and frosted coil temperatures exceeds the maximum difference allowed by the control, a defrost cycle will be initiated.
IMPORTANT − The demand defrost control board will allow a greater accumulation of frost and will initiate fewer defrost cycles than a time/temperature defrost system.
TimeIf 6 hours of heating mode compressor run
time has elapsed since the last defrost cycle while the coil temperature remains below 35°F (2°C), the demand defrost control will initiate a defrost cycle.
ActuationWhen the reversing valve is de−energized, the Y1 circuit is energized, and the coil temperature is below 35°F (2°C), the board logs the compressor run time. If the board is not calibrated, a defrost cycle will be initiated after 30 minutes of heating mode compressor run time. The control will attempt to self−calibrate after this (and all other) defrost cycle(s).
Calibration success depends on stable system temperatures during the 20−minute calibration period. If the board fails to calibrate, another defrost cycle will be initiated after 45 minutes of heating mode compressor run time. Once the defrost board is calibrated, it initiates a demand defrost cycle when the difference between the clear coil and frosted coil temperatures exceeds the maximum difference allowed by the control OR after 6 hours of heating mode compressor run time has been logged since the last defrost cycle.
NOTE − If ambient or coil fault is detected, the board will not execute the TEST" mode.
Termination  The defrost cycle ends when the coil temperature exceeds the termination temperature or after 14 minutes of defrost operation. If the defrost is terminated by the 14−minute timer, another defrost cycle will be initiated after 30 minutes of run time.
Test Mode  A TEST option is provided for troubleshooting. See Figure 15 for this function.
506377−01 11/09
Page 24
Page 25
TEST
Placing the jumper on the field test pins allows the technician to:
Clear short cycle lockout Clear five−strike fault lockout Cycle the unit in and out of defrost mode Place the unit in defrost mode to clear the coil
When Y1 is energized and 24V power is being applied to the Control, a test cycle can be initiated by placing a jumper on the Control’s TEST pins for 2 to 5 seconds. If the jumper remains on the TEST pins for longer than five seconds, the Control will ignore the jumpered TEST pins and revert to normal operation.
The Control will initiate one test event each time a jumper is placed on the TEST pins. For each TEST the jumper must be removed for at least one second and then reapplied.
Y1 Active
Place a jumper on TEST pins for
longer than one second but less than two seconds.
Clears any short cycle lockout and five strike fault lockout function, if applicable. No other functions will be executed and unit will continue in the mode it was operating.
If in COOLING Mode
No further test mode operation will be executed until the jumper is removed from the TEST pins and reapplied.
Place a jumper on TEST pins for
more than two seconds.
Clears any short cycle lockout and five strike fault lockout function, if applicable.
ACTIVE
O Line Status
If in DEFROST Mode
The unit will terminate defrost and enter HEAT MODE uncalibrated with defrost timer set for 34 minute test.
INACTIVE
If in HEATING Mode
If no ambient or coil sensor exist, unit will go into DEFROST MODE.
If ambient or coil faults exist (open or shorted), unit will remain in HEAT MODE.
NOTE  Placing a jumper on the TEST pins will not bring the unit out of inactive mode. The only way manually activate the heat pump from an inactive mode is to cycle the 24VAC power to the Control.
If jumper on TEST pins remains in place for more than five seconds.
The unit will return to HEAT MODE un−calibrated with defrost timer set for 34 minutes.
Figure 15. Test Mode
Page 25
If jumper on TEST pins is remov e d before a m aximum o f five seconds.
The unit will remain in DEFROST MODE until termination on time or temperature.
14HPX SERIES
Page 26
DEFROST BOARD DIAGNOSTICS
See table 13 to determine defrost board operational conditions and to diagnose cause and solution to problems.
Table 13. Defrost Control Board Diagnostic LEDs
DS2 Green
OFF OFF Power problem No power (24V) to board terminals R
Simultaneous SLOW Flash
DS1 Red
Condition/Code Possible Cause(s) Solution
1
Check control transformer power (24V).
& C or board failure.
Normal operation Unit operating normally or in standby
mode.
2
If power is available to board and LED(s) do not light, replace board.
None required.
Alternating SLOW Flash
Simultaneous FAST Flash
Alternating FAST Flash
ON ON Circuit Board Failure Indicates that board has internal component failure. Cycle 24 volt power to board. If code does
FAULT & LOCKOUT CODES (Each fault adds 1 strike to that code’s counter; 5 strikes per code = LOCKOUT)
OFF SLOW
OFF ON
SLOW Flash
ON OFF
SLOW Flash
FAST Flash
OFF Fast
Fast Flash
Flash
OFF High Pressure Fault
ON Discharge Line Temperature
ON Discharge Line Temperature
Flash
OFF Discharge Sensor
5−minute anti−short cycle delay
Ambient Sensor Problem Sensor being detected open or shorted or out of temperature range. Board will revert to time/
Coil Sensor Problem Sensor being detected open or shorted or out of temperature range. Board will not perform
Low Pressure Fault
Low Pressure LOCKOUT
High Pressure LOCKOUT
Fault
Initial power up, safety trip, end of room thermostat demand.
temperature defrost operation. (System will still heat or cool).
demand or time/temperature defrost operation. (System will still heat or cool).
not clear, replace board.
1
Restricted air flow over indoor or out­door coil.
2
Improper refrigerant charge in sys­tem.
3
Improper metering device installed or incorrect operation of metering de­vice.
4
Incorrect or improper sensor location or connection to system.
This code detects shorted sensor or high discharge temperatures. If the discharge line temper­ature exceeds a temperature of 300ºF (148ºC) during compressor operation, the board will de−energize the compressor contactor output (and the defrost output if active). The compressor will remain off until the discharge temperature has dropped below 225ºF (107ºC).
None required (Jumper TEST pins to override)
1
Remove any blockages or restrictions from coils and/or fans. Check indoor and outdoor fan motor for proper current draws.
2
Check system charge using approach & subcooling temperatures.
3
Check system operating pressures and compare to unit charging charts.
4
Make sure all pressure switches and sensors have secure connections to system to prevent refrigerant leaks or errors in pressure and temperature mea­surements.
LOCKOUT
Discharge Sensor Fault The board detects open sensor or out of temperature sensor range. This fault is detected by
allowing the unit to run for 90 seconds before checking sensor resistance. If the sensor resist­ance is not within range after 90 seconds, the board will count one fault. After 5 faults, the board will lockout.
LOCKOUT
Maintenance
DEALER
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
506377−01 11/09
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each cooling season, the system should be checked as follows:
Page 26
Page 27
Outdoor Unit
1. Clean and inspect outdoor coil (may be flushed with a water hose). Ensure power is off before cleaning.
2. Outdoor unit fan motor is pre−lubricated and sealed. No further lubrication is needed.
3. Visually inspect all connecting lines, joints and coils for evidence of oil leaks.
4. Check all wiring for loose connections.
5. Check for correct voltage at unit (unit operating).
6. Check amp draw on outdoor fan motor.
Motor Nameplate:_________ Actual:__________.
7. Inspect drain holes in coil compartment base and clean if necessary.
HOMEOWNER
Cleaning of the outdoor unit’s coil should be performed by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your outdoor unit. The following maintenance may be performed by the homeowner.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
NOTE - If insufficient heating or cooling occurs, the unit should be gauged and refrigerant charge should be checked.
Outdoor Coil
It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are corrosive or which block airflow across the coil (e.g., pet urine, cottonwood seeds, fertilizers, fluids that may contain high levels of corrosive chemicals such as salts)
Outdoor Coil  The outdoor coil may be flushed with
a water hose.
Outdoor Coil (Sea Coast)  Moist air in ocean
locations can carry salt, which is corrosive to most metal. Units that are located near the ocean require frequent inspections and maintenance. These inspections will determine the necessary need to wash the unit including the outdoor coil. Consult your installing contractor for proper intervals/procedures for your geographic area or service contract.
Indoor Unit
1. Clean or change filters.
2. Lennox blower motors are prelubricated and permanently sealed. No more lubrication is needed.
3. Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
4. Belt Drive Blowers − Check belt for wear and proper tension.
5. Check all wiring for loose connections.
6. Check for correct voltage at unit. (blower operating)
7. Check amp draw on blower motor.
Motor Nameplate:_________ Actual:__________.
Indoor Coil
1. Clean coil if necessary.
2. Check connecting lines, joints and coil for evidence of oil leaks.
3. Check condensate line and clean if necessary.
IMPORTANT
Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soakers, waste water, etc.) will corrode the surface of steel and aluminum parts and diminish performance and longevity of the unit.
Outdoor Coil
The outdoor unit must be properly maintained to ensure its proper operation.
Please contact your dealer to schedule proper
inspection and maintenance for your equipment.
Make sure no obstructions restrict airflow to the
outdoor unit.
Grass clippings, leaves, or shrubs crowding the unit
can cause the unit to work harder and use more energy.
Keep shrubbery trimmed away from the unit and
periodically check for debris which collects around the unit.
Routine Maintenance
In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level.
1. Air Filter  Ask your Lennox dealer to show you
where your indoor unit’s filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed.
2. Disposable Filter  Disposable filters should be
replaced with a filter of the same type and size.
NOTE If you are unsure about the filter required for your system, call your Lennox dealer for assistance.
3. Reusable Filter  Many indoor units are equipped
with reusable foam filters. Clean foam filters with a mild soap and water solution; rinse thoroughly; allow filter to dry completely before returning it to the unit or grille.
Page 27
14HPX SERIES
Page 28
NOTE The filter and all access panels must be in place any time the unit is in operation.
4. Electronic Air Cleaner  Some systems are
equipped with an electronic air cleaner, designed to remove airborne particles from the air passing through the cleaner. If your system is so equipped, ask your dealer for maintenance instructions.
5. Indoor Unit  The indoor unit’s evaporator coil is
equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.)
Thermostat Operation
See the ComfortSense® 7000 thermostat homeowner manual for instructions on how to operate your thermostat.
Heat Pump Operation
Your new Lennox heat pump has several characteristics that you should be aware of:
Heat pumps satisfy heating demand by delivering
large amounts of warm air into the living space. This is quite different from gas- or oil-fired furnaces or an electric furnace which deliver lower volumes of considerably hotter air to heat the space.
Do not be alarmed if you notice frost on the outdoor coil
in the winter months. Frost develops on the outdoor coil during the heating cycle when temperatures are below 45°F (7°C). An electronic control activates a defrost cycle lasting 5 to 15 minutes at preset intervals to clear the outdoor coil of the frost.
During the defrost cycle, you may notice steam rising
from the outdoor unit. This is a normal occurrence. The thermostat may engage auxiliary heat during the defrost cycle to satisfy a heating demand; however,
the unit will return to normal operation at the conclusion of the defrost cycle.
Extended Power Outage
The heat pump is equipped with a compressor crankcase heater which protects the compressor from refrigerant slugging during cold weather operation.
If power to your unit has been interrupted for several hours or more, set the room thermostat selector to the EMERGENCY HEAT setting to obtain temporary heat without the risk of serious damage to the heat pump.
In EMERGENCY HEAT mode, all heating demand is satisfied by auxiliary heat; heat pump operation is locked out. After a six-hour compressor crankcase warm-up period, the thermostat can be switched to the HEAT setting and normal heat pump operation may resume.
Preservice Check
If your system fails to operate, check the following before calling for service:
Verify room thermostat settings are correct. Verify that all electrical disconnect switches are ON. Check for any blown fuses or tripped circuit breakers. Verify unit access panels are in place. Verify air filter is clean. If service is needed, locate and write down the unit
model number and have it handy before calling.
Accessories
For update−to−date information, see any of the following publications:
Lennox 14HPX Engineering Handbook Lennox Product Catalog Lennox Price Book
14HPX Check List
Job Name Job no. Date
Job Location City State
Installer City State
Unit Model No. Serial No. Service Technician
Nameplate Voltage
Rated Load Ampacity Compressor Outdoor Fan
Maximum Fuse or Circuit Breaker
Electrical Connections Tight? Indoor Filter clean? Supply Voltage (Unit Off)
Indoor Blower RPM S.P. Drop Over Indoor (Dry) Outdoor Coil Entering Air Temp.
Discharge Pressure Vapor Pressure Refrigerant Charge Checked?
Refrigerant Lines: Leak Checked? Properly Insulated? Outdoor Fan Checked?
Service Valves: Fully Opened? Caps Tight? Thermostat
Voltage With Compressor Operating Calibrated? Properly Set?  Level? 
Page 28
506377−01 11/09
Loading...