Lennox Merit Series 14HPX, Merit 14HPX-018, Merit 14HPX-024, Merit 14HPX-030, Merit 14HPX-036 Installation Instructions Manual

...
INSTALLATION
2009 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
INSTRUCTIONS
Merit® Series 14HPX Units
HEAT PUMP UNITS
506377−01 11/09 Supersedes 505,243M
TABLE OF CONTENTS
Shipping and Packing List 1. . . . . . . . . . . . . . . . . . . . . . . .
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Typical Unit Parts Arrangement 2. . . . . . . . . . . . . . . . . . .
Model Number Identification 3. . . . . . . . . . . . . . . . . . . . . .
General Information 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating Gauge Set and Service Valves 3. . . . . . . . . . .
Recovering Refrigerant from Existing System 5. . . . . . .
New Outdoor Unit Placement 6. . . . . . . . . . . . . . . . . . . . .
New or Replacement Line Set 6. . . . . . . . . . . . . . . . . . . . .
Metering Devices and Flushing the System 10. . . . . . . .
Testing for Leaks 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evacuating the System 12. . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Connections 13. . . . . . . . . . . . . . . . . . . . . . . . . .
Servicing Unit Delivered Void of Charge 16. . . . . . . . . . .
Start−Up 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Refrigerant 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing and Installing Louvers 21. . . . . . . . . . . . . . . . .
System Operation 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Defrost System 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up and Performance Checklist 28. . . . . . . . . . . . . .
Litho U.S.A.
IMPORTANT
This unit must be matched with an indoor coil as specified in Lennox Engineering Handbook. Coils previously charged with HCFC−22 must be flushed.
Shipping and Packing List
Check the unit components for shipping damage. If you find any damage, immediately contact the last carrier.
1 − Assembled 14HPX outdoor unit
General
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
11/09 506377−01
The Merit® 14HPX model is designed for use with HFC−410A refrigerant only. This unit must be installed with an approved indoor air handler or coil. See the Lennox 14HPX Engineering Handbook for approved indoor component matchups.
IMPORTANT
This model is designed for use in expansion valve systems only. An indoor expansion valve approved for use with HFC−410A refrigerant must be ordered separately, and installed prior to operating the system.
Page 1
*2P1109* *P506377-01*
Unit Dimensions − inches (mm)
A
SIDE VIEW
Model No. A B C
14HPX−018 24−1/4 (616) 29−1/4 (743) 28−1/2 (724)
14HPX−024 24−1/4 (616) 29−1/4 (743) 28−1/2 (724)
14HPX−030 24−1/4 (616) 33−1/4 (845) 32−1/2 (826)
14HPX−036 32−1/4 (819) 29−1/4 (743) 28−1/2 (724)
14HPX−042 32−1/4 (819) 37−1/4 (946) 36−1/2 (927)
14HPX−048 32-1/4 (819) 37−1/4 (946) 36−1/2 (927)
14HPX−060 32-1/4 (819) 43−1/4 (1099) 42−1/4 (1073)
A
OUTDOOR
COIL FAN
COMPRESSOR
DISCHARGE AIR
B
SUCTION AND LIQUID
LINE CONNECTION
OPTIONAL UNIT
STANDOFF KIT (4)
(FIELD INSTALLED)
SIDE VIEW
Typical Unit Parts Arrangement
CONTROL
CAPACITOR
GROUND
LUG
CUTOUT FOR HIGH VOLTAGE CONDUIT
CONTACTOR
DEFROST CONTROL BOARD
CHECK EXPANSION
CONTROL WIRE LOOP
NOTE  PLUMBING LAYOUT AND COMPRESSOR TYPE MAY VARY SLIGHTLY BETWEEN MODEL SIZES.
COMPRESSOR
HARNESS
DEFROST
THERMOSTAT
VALV E
EQUALIZER LINE
BI−FLOW FILTER
LIQUID LINE SERVICE
DRIER
TRUE SUCTION
PORT
HIGH PRESSURE
SWITCH (S4)
VALV E
COMPRESS0R
DISCHARGE LINE
MUFFLER
LOW PRESSURE SWITCH
REVERSING VALVE SOLENOID
VAPOR LINE SERVICE VALVE
REVERSING VALV E
506377−01 11/09
Page 2
Model Number Identification
HP X14 024
Nominal SEER
Unit Type
HP = Heat Pump
Refrigerant
X = R−410A
WARNING
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
General Information
These instructions are intended as a general guide and do not supersede national or local codes in any way. Consult authorities having jurisdiction before installation.
Operating Gauge Set and Service Valves
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
TORQUE REQUIREMENTS
When servicing or repairing heating, ventilating, and air conditioning components, ensure the fasteners are appropriately tightened. Table 1 lists torque values for fasteners.
230
2
Minor Revision Number
Voltage
230 = 208/230V−1phase−60hz
Cooling Capacity − Tons 018 = 1.5
024 = 2 030 = 2.5 036 = 3 042 = 3.5 048 = 4 060 = 5
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9 ft−lbs for small valves, to 25 ft−lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
See the Lennox Service and Application Notes #C−08−1 for further details and information.
IMPORTANT
To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.
When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. Table 1 provides torque values for fasteners.
Table 1. Torque Requirements
Parts Recommended Torque
Service valve cap 8 ft.− lb. 11 NM
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 NM
USING MANIFOLD GAUGE SET
When checking the system charge, only use a manifold gauge set that features low loss anti−blow back fittings.
Manifold gauge set used with HFC−410A refrigerant systems must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 − 800 psig on the high side and a low side of 30" vacuum to 250 psig with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psig of pressure with a 4000 psig burst rating.
Page 3
14HPX SERIES
OPERATING SERVICE VALVES
The liquid and vapor line service valves are used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging.
SERVICE VALVES
VARIOUS TYPES
OPEN TO BOTH INDOOR AND
OUTDOOR UNITS
SERVICE PORT CAP
SERVICE PORT
TO INDOOR
CORE
UNIT
SERVICE PORT
(VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE
Each valve is equipped with a service port which has a factory−installed valve stem. Figure 1 provides information on how to access and operating both angle and ball service valves.
SERVICE PORT CAP
SERVICE PORT
(VALVE STEM SHOWN CLOSED) INSERT HEX WRENCH HERE
CLOSED TO BOTH
INDOOR AND OUTDOOR
UNITS
TO INDOOR UNIT
FRONT-SEATED
TO INDOOR
STEM CAP
SERVICE PORT
CORE
VALVE STEM
UNIT
TO OUTDOOR
UNIT
(FRONT−SEATED
STEM CAP
ANGLE−TYPE
SERVICE VALVE
CLOSED)
TO OUTDOOR UNIT
WHEN SERVICE VALVE IS CLOSED, THE SERVICE PORT IS OPEN TO THE LINE SET AND INDOOR UNIT.
WHEN SERVICE VALVE IS OPEN, THE SERVICE PORT IS OPEN TO LINE SET, INDOOR AND OUTDOOR UNIT.
To Access Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge set to service port.
3. When testing is completed, replace service port cap and tighten as fol­lows:
With Torque Wrench: Finger tighten and torque cap per Table 1. Without Torque Wrench: Finger tighten and use an appropriately
sized wrench to turn an additional 1/6 turn clockwise.
Operating Angle Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16" for vapor line valve sizes) to back the stem out counterclockwise as far as it will go.
ANGLE−TYPE SERVICE VALVE
(BACK−SEATED OPENED)
TO OPEN ROTATE STEM COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT CORE
SERVICE PORT CAP
TO OUTDOOR UNIT
1/6 TURN
12
11
10
9
8
1
2
3
4
5
7
6
BALL (SHOWN CLOSED)
BALL−TYPE SERVICE
VAL VE
STEM CAP
Operating Ball Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrenched to open. To open valve, rotate stem counterclockwise 90°. To close rotate stem clockwise 90°.
VALVE STEM
Reinstall Stem Cap:
Stem cap protects the valve stem from damage and serves as the primary seal. Replace the stem cap and tighten as follows:
With Torque Wrench: Finger tighten and then torque cap per Table 1. Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turn
an additional 1/12 turn clockwise.
NOTE  A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
Figure 1. Angle and Ball Service Valves
506377−01 11/09
Page 4
9
10
8
11
1/6 TURN
12
1
2
3
4
5
7
6
Recovering Refrigerant from Existing System
RECOVERING
REFRIGERANT FROM SYSTEM
DISCONNECT POWER
Disconnect all power to the existing outdoor unit at the service
1
disconnect switch or main fuse box/breaker panel.
MAIN FUSE BOX/
BREAKER PANEL
SERVICE
DISCONNECT
SWITCH
RECOVERING REFRIGERANT
Remove existing refrigerant using one of the following procedures:
3
IMPORTANT  Some system configurations may contain higher than normal refrigerant charge due to either large internal coil volumes,
and/or long line sets.
CONNECT MANIFOLD GAUGE SET
Connect a gauge set, clean recovery cylinder and a recovery
2
machine to the service ports of the existing unit. Use the instructions provided with the recovery machine to make the connections.
MANIFOLD GAUGES
RECOVERY MACHINE
LOW
CLEAN RECOVERY CYLINDER
OUTDOOR UNIT
HIGH
METHOD 1:
Us this method if the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational and you plan to use the existing to flush the system.
Remove all refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.
METHOD 2:
Use this method if the existing outdoor unit is equipped with manual shut−off valves, and you plan to use new refrigerant to flush the system.
The following devices could prevent full system charge recovery into the outdoor unit:
Outdoor unit’s high or low−pressure switches (if applicable) when tripped can cycle the compressor OFF. Compressor can stop pumping due to tripped internal pressure relief valve. Compressor has internal vacuum protection that is designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets
a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed to go into a vacuum. Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seals.)
Once the compressor can not pump down to a lower pressure due to one of the above system conditions, shut off the vapor valve. Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.
Perform the following task:
A Start the existing system in the cooling mode and close the liquid line valve. B Use the compressor to pump as much of the existing HCFC−22 refrigerant into the outdoor unit until the outdoor system is full. Turn the outdoor unit
main power OFF and use a recovery machine to remove the remaining refrigerant from the system.
NOTE  It may be necessary to bypass the low pressure switches (if equipped) to ensure complete refrigerant evacuation.
C When the low side system pressures reach 0 psig, close the vapor line valve.
D Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.
Page 5
14HPX SERIES
New Outdoor Unit Placement
See Unit Dimensions on Page 2 for sizing mounting slab, platforms or supports. Refer to Figure 2 for mandatory installation clearance requirements.
*
INSTALL UNIT AWAY
FROM WINDOWS
NOTES:
*
*
*
Service panel access clearance of 30 in. (762 mm) must be
maintained.
Clearance to one of the other three sides must be 36 in. (914
Clearance on one of the remaining two sides may be 12 in. (305
.
mm)
mm) and the final side may be 6 in. (152 mm)
.
Clearance required on top of unit is 48 in. (1219 mm).
A clearance of 24 in. (610 mm) must be maintained between two
units.
Figure 2. Installation Clearances
CAUTION
In order to avoid injury, take proper precaution when lift­ing heavy objects.
TWO 90 ELBOWS INSTALLED IN LINE SET
WILL REDUCE LINE SET VIBRATION
Figure 3. Outside Unit Placement
PLACING OUTDOOR UNIT ON SLAB
When installing a unit at grade level, the top of the slab should be high enough above the grade so that water from higher ground would not collect around the unit as illustrated in Figure 4.
DISCHARGE AIR
BUILDING
STRUCTURE
MOUNTING SLAB
GROUND LEVEL
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line.
When possible, do not install the unit directly outside
a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in Figure 3.
506377−01 11/09
Figure 4. Typical Slab Mounting at Ground Level
Slab may be level or have a slope tolerance away from the building of not more than two degrees, or 2 inches per 5 feet (51 mm per 1524 mm) as illustrated in Figure 4.
INSTALLING OUTDOOR UNIT ON ROOF
Install the unit at a minimum of 4 inches (102 mm) above the surface of the roof. Ensure the weight of the unit is properly distributed over roof joists and rafters. Redwood or steel supports are recommended.
When possible, do not install the unit directly outside
a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in Figure 3.
Page 6
New or Replacement Line Set
This section provides information on new installation or replacement of existing line set. If a new or replacement line set is not required, then proceed to Brazing Connections on Page 9.
If refrigerant lines are routed through a wall, seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds.
Also, consider the following when placing and installing a high−efficiency air conditioner:
MATCHING WITH NEW OR EXISTING INDOOR COIL AND LINE SET
The RFC1−metering line consisted of a small bore copper line that ran from condenser to evaporator coil. Refrigerant was metered into the evaporator by utilizing temperature/pressure evaporation effects on refrigerant in the small RFC line. The length and bore of the RFC line corresponded to the size of cooling unit.
If the 14HPX is being used with either a new or existing indoor coil which is equipped with a liquid line which served as a metering device (RFCI), the liquid line must be replaced prior to the installation of the 14HPX unit. Typically a liquid line used to meter flow is 1/4" in diameter and copper.
LINE SET ISOLATION
REFRIGERANT LINE SET
Field refrigerant piping consists of liquid and suction lines from the outdoor unit (braze connections) to the indoor unit coil (flare or braze connections). Use Lennox L15 (braze, non−flare) series line set, or use field−fabricated refrigerant lines as listed in Table 2.
Table 2. Refrigerant Line Set (MM)
Field
Model
−018
−024
−030
−036
−042
−048
−060
NOTE  Some applications may required a field provided 7/8" to 1−1/8" adapter
Connections
Liquid Line
3/8 in. (10 mm)
3/8 in. (10 mm)
3/8 in. (10 mm)
Vapor Line
3/4 in (19 mm)
7/8 in (22 mm)
1−1/8 in. (29 mm)
Recommended Line Set
Liquid Line
3/8 in. (10 mm)
3/8 in. (10 mm)
3/8 in. (10 mm)
Vapor Line
3/4 in (19 mm)
7/8 in (22 mm)
1−1/8 in. (29 mm)
L15 Line Sets
L15−41 15 ft. − 50 ft. (4.6 m − 15 m)
L15−65 15 ft. − 50 ft. (4.6 m − 15 m)
Field Fabricated
NOTE  When installing refrigerant lines longer than 50 feet, contact Lennox Technical Support Product Applications for assistance or Lennox piping manual. To obtain the correct information from Lennox, be sure to communicate the following points:
Model (14HPX) and size of unit (e.g. −060). Line set diameters for the unit being installed as listed
in Table 2 and total length of installation.
Number of elbows and if there is a rise or drop of the
piping.
CAUTION
Brazing alloys and flux contain materials which are hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. Perform operations only in well ventilated areas.
Wear gloves and protective goggles or face shield to protect against burns.
Wash hands with soap and water after handling brazing alloys and flux.
IMPORTANT
The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.
IMPORTANT
If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC−410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity. Failure to properly flush the system per the instructions below will void the warranty.
Page 7
14HPX SERIES
LINE SET
INSTALLATION
Line Set Isolation  The following illustrations are
examples of proper refrigerant line set isolation:
REFRIGERANT LINE SET  TRANSITION
FROM VERTICAL TO HORIZONTAL
ANCHORED HEAVY NYLON WIRE TIE OR AUTOMOTIVE
MUFFLER-TYPE HANGER
AUTOMOTIVE
MUFFLER-TYPE HANGER
IMPORTANT  Refrigerant lines must not contact structure.
REFRIGERANT LINE SET  INSTALLING
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)
NOTE  Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.
IMPORTANT  Refrigerant lines must not contact wall
OUTSIDE WALL
VAPOR LINE
LIQUID LINE
WALL STUD
STRAP LIQUID LINE TO VAPOR LINE
LIQUID LINE
NON−CORROSIVE
METAL SLEEVE
VAPOR LINE − WRAPPED IN ARMAFLEX
REFRIGERANT LINE SET  INSTALLING
HORIZONTAL RUNS
To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties.
WIRE TIE (AROUND VAPOR LINE ONLY)
8 FEET (2.43 METERS)
STRAPPING
MATERIAL (AROUND
VAPOR LINE ONLY)
TAPE OR WIRE TIE
FLOOR JOIST OR
ROOF RAFTER
8 FEET (2.43 METERS)
NON−CORROSIVE METAL SLEEVE
STRAP THE VAPOR LINE TO THE JOIST OR RAFTER AT 8 FEET (2.43 METERS) INTERVALS THEN STRAP THE LIQUID LINE TO THE VAPOR LINE.
TAPE OR WIRE TIE
WIRE TIE
INSIDE WALL
WOOD BLOCK
BETWEEN STUDS
SLEEVE
VAPOR LINE WRAPPED
WITH ARMAFLEX
OUTSIDE
WALL
PVC
PIPE
FIBERGLASS
INSULATION
CAULK
STRAP
NON−CORROSIVE METAL SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
LIQUID LINE
NOTE  Similar installation practices should be used if line set is to be installed on exterior of outside wall.
FLOOR JOIST OR
ROOF RAFTER
506377−01 11/09
WARNING  Polyol ester (POE) oils used with HFC−410A refrigerant absorb moisture very quickly. It is very important that the
refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
Figure 5. Line Set Installation
Page 8
BRAZING
CONNECTIONS
CUT AND DEBUR
Cut ends of the refrigerant lines square
1
(free from nicks or dents) and debur the ends. The pipe must remain round and do not pinch end of the line.
ATTACHED GAUGES
A Connect gauge set low pressure side to liquid line service
3
valve.
B Connect gauge set center port to bottle of nitrogen with
regulator.
SERVICE PORT MUST BE OPEN TO ALLOW EXIT
INDOOR
UNIT
NOTE − Use silver alloy brazing rods with five or six percent minimum silver alloy for copper−to−copper brazing, 45 percent alloy for copper−to−brass and copper−to−steel brazing.
CAP AND CORE REMOVAL
Remove service cap and core
2
from both the vapor and liquid line service ports.
HIGHLOW
B
ATTACH
POINT FOR NITROGEN
VAPOR LINE
GAUGES
VAPOR LINE
SERVICE
VALV E
OUTDOOR
UNIT
USE REGULATOR TO FLOW
NITROGEN AT 1 TO 2 PSIG.
WRAP SERVICE VALVE
To protect components during
4
brazing, wrap a wet cloth around the liquid line service valve body and copper tube stub and use another wet cloth underneath the valve body to protect the base paint.
BRAZE LINE SET
Braze the liquid line to the liquid line
6
service valve. Turn off nitrogen flow.
POINT FLAME AWAY FROM
SERVICE VALVE
LIQUID LINE
LIQUID LINE SERVICE
5
NOTE  The fixed orifice or check expansion valve metering device at the indoor unit will allow low pressure nitrogen to flow through the system.
VALV E
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid line service valve and out of the valve stem port connection on the vapor service valve.
INSTALL SERVICE PORT CAPS ONLY
After all connections have been brazed, disconnect manifold gauge
7
set from service ports, cool down piping with wet rag and remove all wrappings. Do not reinstall cores until after evacuation procedure. Reinstall service port caps if desired to close off refrigerant ports.
A
LOW
NITROGEN
HIGH
USE REGULATOR TO
FLOW NITROGEN AT 1
TO 2 PSIG.
NITROGEN
WARNING  Allow braze joint to cool before removing the wet rag from the service valve. (TEMPERATURES ABOVE 250ºF CAN DAMAGE VALVE SEALS
IMPORTANT  Connect gauge set low pressure side to vapor line service valve and repeat procedure starting at paragraph 4 for brazing the liquid line to service port valve.
SERVICE PORT
Figure 6. Brazing Connections
Page 9
SERVICE PORT CORE
SERVICE PORT CAP
14HPX SERIES
Loading...
+ 19 hidden pages