Lennox Merit 13ACD-018, Merit 13ACD-024, Merit 13ACD-030, Merit 13ACD-036, Merit 13ACD-042 Installation Instructions Manual

...
Page 1
INSTALLATION
,1,_,2008LennoxtndustriesInc,
®
Dallas,Texas,USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING
INSTRUCTIONS
AIR CONDITIONER UNITS
505,366M 01I08
Supersedes 11/07
Shipping and Packing List ...................... 1
13ACD Outdoor Unit ........................... 1
Unit Dimensions ............................... 2
General Information ........................... 2
Recovering Refrigerant from Existing System ..... 4
Removing Existing Outdoor Unit ................. 5
Positioning New Outdoor Unit ................... 5
New or Replacement Line Set ................... 6
Brazing Connections ........................... 8
Removing Indoor Unit Metering Device ............ 9
Installing New Indoor Unit Metering Device ........ 9
Testing for Leaks .............................. 11
Evacuating the System ......................... 12
Servicing Unit Delivered Void of Charge ........... 13
Electrical Connections ......................... 13
Start-Up and Charging Procedures ............... 14
System Operation ............................. 18
Maintenance .................................. 18
Homeowner Information ........................ 19
Start-Up and Performance Checklist ............. 20
_puTeCh ical
n
blications
Litho U.S.A.
CAUTION
IMPORTANT
01/08
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
Check the unit for shipping damage and listed times below are intact. If damaged, or if parts are missing, immediately
contact the last shipping carrier.
1 -- Assembled outdoor unit
1 -- Refrigerant flow control kit (Fixed Orifice)
13ACD Air Conditioners, which will also be referred to in this instruction as the outdoor unit, uses HCFC-22
refrigerant. This outdoor unit must be installed with a matching indoor unit and line set as outlined in the Lennox
13ACD Engineering Handbook.
This outdoor unit is designed for use in systems that use one of the following refrigerant metering devices:
Thermal expansion valve (TXV)
Fixed orifice
Page 1
505,366M
IIIIIIIIIIIIIIIIIIIIIIHIIIIIIIIIIIHlllllllll
Page 2
A A
OPTIONAL UNIT STAND-OFF KIT
OUTDOOR COIL FAN tDischarge Air
COMPRESSOR_
SUCTION ANDLIQUIDLINE
CONNECTIONS
(4) (FIELDqNSTALLED)
SIDE VIEW
SIDE VIEW
Model Number A B 13ACD-018 24-1/4 (616) 25-1/4 (641 )
13ACD-024 24-1/4 (616) 25-1/4 (641 ) 13ACD-030 24-1/4 (616) 33-1/4 (845)
13ACD-036 24-1/4 (616) 33-1/4 (845) 13ACD-042 28-1/4 (718) 29-1/4 (743) 13ACD-048 28-1/4 (718) 37-1/4 (946) 13ACD-060 28-1/4 (718) 33-1/4 (845)
WARNING
When servicing or repairing HVAC components, ensure caps and fasteners are appropriately tightened, Table 1
lists torque values for typical service and repair items.
Table 1. Torque Requirements
Part
Service valve cap 8 ft.- lb. Sheet metal screws 16 in.- lb.
Machine screws #10 28 in.- lb.
I
Compressor bolts 90 in.- lb. Gauge port seal cap 8 ft.- lb.
USING MANIFOLD GAUGE SETS
Recommended Torque
11 NM
2NM 3NM
10 NM 11 NM
When checking the system charge, use a manifold gauge set that features low-loss anti-blow back fittings. See figure
1 for a typical manifold gauge connection setup.
OPERATING SERVICE VALVES
IMPORTANT
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities
who have jurisdiction before installation.
505366M 01/08
The liquid and suction line service valves are typically used for removing refrigerant, flushing, leak testing, evacuating,
checking charge and charging,
Page 2
Page 3
OUTDOOR UNIT (Uncased Coil Shown)
LOW HIGH
PRESSURE PRESSURE
LIQUID LINE SUCTION LINE
COMPRESSOR-- I[ -" ..._
Figure 1. Typical Manifold Gauge Connection Setup
Each valve is equipped with a service port which has a
factory-installed valve stem.
t/6 TURN
1/12 TURN
Figure 2. Cap Tightening Distances
,A IMPORTANT
Operating Angle-Type Service Valve
To Access Angle-Type Service Port:
A service port cap protects the service port core from
contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and tighten as follows:
With Torque Wrench: Finger tighten and then tighten per table 1.
Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turn an additional
1/6 turn clockwise as illustrated in figure 2.
OUTDOOR - ORIFICE
COIL
TXV OR FIXED
To Open and Close Angle-Type Service Valve:
A valve stem cap protects the valve stem from
contamination and assures a leak-free seal,
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex-head extension (3/16" for liquid-line valve sizes and 5/16" for
suction-line valve sizes) to back the stem out counterclockwise as far as it will go.
3. Replace the stem cap and tighten as follows:
With Torque Wrench: Tighten finger tight and then
tighten per table 1.
Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional
1/12 turn clockwise as illustrated in figure 2.
NOTE - A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
NOTE- To prevent stripping of the cap, the wrench should be appropriately sized and fit snugly over the cap before tightening the cap.
SERVICE PORT CAP
STEM CAP
SERVICE PORT
CLOSED) INSERT HEX WRENCH HERE
SERVICE PORT
CLOSED TO BOTH
INDOOR AND
OUTDOOR UNITS
VALVE STEM
FRONT-SEATED
TOINDOOR
UNIT
TO OUTDOOR UNIT
Figure 3. Angle-Type Service Valve
(Font-Seated Closed)
Page 3
13ACD SERIES
Page 4
SERVICEPORT
SERVICEPORT
OPENTOBOTH
INDOORAND
OUTDOORUNITS
TOINDOOR
UNIT
STEMCAP
TOOUTDOORUNIT
Figure 4. Angle-Type Service Valve
(Back-Seated Opened)
Operating Bali-Type Service Valve
To Access Bali-Type Service Port:
SERVICEPORT
(VALVESTEMSHOWNOPEN)
INSERTHEXWRENCHHERE
To Open and Close Bali-Type Service Valve: A valve stem cap protects the valve stem from
contamination and assures a leak-free seal,
1. Remove stem cap with a wrench.
2. Use an appropriately sized wrench to open. To open valve, rotate stem counterclockwise 90° . To close
rotate stem clockwise 90°,
3. Replace the stem cap and tighten as follows:
With Torque Wrench: Finger tighten and then
tighten per table 1,
Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional
1/12 turn clockwise as illustrated in figure 2,
NOTE - A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque,
A service port cap protects the service port core from
contamination and serves as the primary leak seal.
OPEN TO LINE SET WHEN VALVE IS CLOSED, TO BOTH LINE SET AND UNIT WHEN VALVE IS OPEN.
TO OPEN ROTATE STEM COUNTERCLOCKWISE 90 ° . BALL(SHOWN
TO CLOSE ROTATE STEM CLOCKWISE 90 ° .
CORE
SERVlCEPORTCAP
TO INDOOR UNIT
CLOSED)
STEM CAP
VALVE STEM
Figure 5. Bali-Type Service Valve
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge to the service port,
3. When testing iscompleted, replace service port cap and
tighten as follows:
With Torque Wrench: Finger tighten and then tighten per table table 1,
Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turn an additional
1/6 turn clockwise as illustrated in figure 2,
Remove existing HCFC-22 refrigerant using one of the
following methods:
METHOD 1: Use this method if the existing outdoor unit is not equipped
with manual shut-off valves, and plan on using existing
HCFC-22 refrigerant to flush the system.
NOTE - Use recovery machine instructions for specific setup requirements.
Perform the following task:
1. Disconnect all power to the existing outdoor unit,
2, Connect to the existing unit a gauge set, clean
recovery cylinder and a recovery machine. Use the instructions provided with the recover machine on how to setup the connections,
3. Remove all HCFC-22 refrigerant from the existing system, Check gauges after shutdown to confirm that the entire system is completely void of refrigerant,
RECOVERY MACHINE
MANIFOLD GAUGES
c p. COVERY
/
OUTDOOR UNIT
Figure 6. Typical Refrigerant Recovery (Method 1)
505366M 01/08
Page 4
Page 5
METHOD2: Usethismethodiftheexistingoutdoorunitis equipped
with manualshut-offvalves,and planon usingnew
HCFC-22refrigeranttoflushthesystem, IMPORTANT:Somesystemconfigurationsmaycontain
higherthannormalrefrigerantchargeduetoeitherlarge internalcoilvolumes,and/orlonglinesets,Thefollowing
conditionsmaycausethecompressortostopfunctioning: Thefollowingdevicescouldpreventfull system charge
recovery into the outdoor unit:
Outdoor unit's high or low-pressure switches if tripped can cycled the compressor OFF.
Compressor can stop pumping due to tripped internal pressure relief valve.
Compressor has internal vacuum protection that is
designed to unload the scrolls (compressor stops
pumping) when the pressure ratio meets a certain
value or when the suction pressure is as high as 20
psig. (Compressor suction pressures should never be
allowed to go into a vacuum. Prolonged operation at
low suction pressures will result in overheating of the
scrolls and permanent damage to the scroll tips, drive
bearings and internal seals),
Once the compressor can not pump down to a lower pressure due to one of the above system conditions, shut
off the suction valve, Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in
the indoor coil and line set. Perform the following task:
1, Start the existing HCFC-22 system in the cooling
mode and close the liquid line valve,
2, Pump as much of the existing HCFC-22 refrigerant
with the compressor back into the outdoor unit until you have reached the limitations of the outdoor system, Turn the outdoor unit main power OFF and
use a recovery machine to remove the remaining refrigerant in the system,
NOTE - It may be necessary to bypass the low pressure switches if equipped to ensure complete refrigerant
evacuation.
3, When the low side system pressures reach 0 psig,
close the suction line valve,
4, Check gauges after shutdown to confirm that the
valves are not allowing refrigerant to flow back into the
low side of the system,
* SEE NOTES BELOW THIS FIGURE FOR FURTHER DETAILS.
Figure 7. Installation Clearances
NOTES:
Service clearance of 30 in. (762 mm) must be maintained on one of the sides adjacent to the control
box.
Clearance to one of the other three sides must be 36 in. (914 mm)
Clearance to one of the remaining two sides may be
12 in. (305 mm) and the final side may be 6 in. (152
mm)
48 in. (1219 mm) clearance required on top of unit.
A clearance of 24 in. (610 mm) must be maintained between two units
POSITIONING CONSIDERATIONS
CAUTION
Consider the following when positioning the unit:
Some localities are adopting sound ordinances based on the unit's sound level registered from the adjacent
property, not from the installation property. Install the unit as far as possible from the property line.
When possible, do not install the unit directly outside a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in figure 8.
INSTALL UNIT AWAY _ _I
FRO W
Perform the following task at the existing outdoor unit:
Disconnect line set at the service valves.
Disconnect electrical service at the disconnect switch.
Remove old outdoor unit.
See Unit Dimensions on page 2 to sizing mounting slab, platforms or supports. Refer to figure 7 for mandatory
installation clearance requirements.
Page 5
TWO 90 ° ELBOWS INSTALLED
IN LINE SET WILL REDUCE _ "_"_
LINE SET VIBRATION.
Figure 8. Outside Unit Placement
13ACD SERIES
Page 6
PLACING OUTDOOR UNIT ON SLAB When installing a unit at grade level, the top of the slab
should be high enough above the grade so that water from higher ground would not collect around the unit as illustrated in figure 9,
BUILDING
STRUCTURE
DISCHARGE AIR
MOUNTING
SLAB
GROUND LEVEL
Figure 9. Ground Level Slab Mounting
Slab may be level or have a slope tolerance away from the building of not more than two degrees, or two inches per 5
feet (51 mm per 1524 mm) as illustrated in figure 9,
INSTALLING OUTDOOR UNIT ON ROOF Install the unit a minimum of six inches (152 mm) above the
roof surface to avoid ice build-up around the unit, Locate the unit above a load bearing wall or area of the roof that
can adequately support the unit, Consult local codes for rooftop applications,
This section provides information on new installation or replacement of existing line set. If a new or replacement
line set is not required, then proceed to Brazing Connections on page 8,
If refrigerant lines are routed through a wall, seal and isolate the opening so vibration is not transmitted to the
building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated
from building structures (walls, ceilings, floors), the
refrigerant lines will not create unnecessary vibration and subsequent sounds,
Also, consider the following when placing and installing a high-efficiency air conditioner:
REFRIGERANT LINE SET Field refrigerant piping consists of liquid and suction lines
from the outdoor unit (braze connections) to the indoor unit coil (flare or braze connections). Use Lennox L15 (braze, non-flare) series line set, or use field-fabricated refrigerant
lines as listed in table 2,
Table 2. Refrigerant Line Set
Field
Model
-018
-024 (10mm) (19mm)
-030
-036
-042 (10mm) (22mm)
-048
-060 (10mm) (29mm)
Connections
Liquid Suction Line Line
3/8 in. 3/4 in
3/8 in. 7/8 in
3/8 in. 1-1/8 in.
Recommended Line Set
Liquid Suction L15
Line Line Line Sets
3/8 in. 3/4 in L15-41
(10 (19 ram) 15 ft, - 50 ft. mm) (4.6 m - 15 m)
3/8 in. 7/8 in L15-65
(10 (22 mm) 15 ft, - 50 ft. mm) (4.6 m- 15 m)
3/8 in, 1-1/8 in. Field
(10 (29 mm) Fabricated mm)
NOTE - When installing refrigerant lines longer than 50 feet, contact Lennox Technical Support Product Applications for assistance or Lennox piping manual. To obtain the correct information from Lennox, be sure to communicate the following points:
Model (13ACD) and size of unit (e.g, -060).
Line set diameters for the unit being installed as listed in table 2 and total length of installation,
Number of elbows and if there is a rise or drop of the piping.
MATCHING WITH NEW OR EXISTING INDOOR COIL
AND LINE SET The RFCl-metering line consisted of a small bore copper
line that ran from condenser to evaporator coil. Refrigerant was metered into the evaporator by utilizing
temperature/pressure evaporation effects on refrigerant in the small RFC line. The length and bore of the RFC line
corresponded to the size of cooling unit.
If the 13ACD is being used with either a new or existing
indoor coil which is equipped with a liquid line which served as a metering device (RFCI), the liquid line must be replaced prior to the installation of the 13ACD unit, Typically a liquid line used to meter flow is 1/4" in diameter and copper,
505366M 01/08
Page 6
Page 7
LINESETISOLATION Thisreferenceillustratesprocedures,whichensureproper
refrigerantlinesetisolation: Linesetfor heatpumpapplicationscannotbeinstalled
underground.For more informationsee the Lennox
Refrigerant Piping Design and Fabrication Guidelines, or contact Lennox Technical Support Product Applications
for assistance.
Installation of line set on horizontal runs is illustrated in figure 10.
Installation of line set on vertical runs is illustrated in
figure 11.
Installation of a transition from horizontal to
vertical is illustrated in figure 12.
TO HANG LINE SET FROM JOIST OR
RAFTER, USE EITHER METAL STRAPPING WIRE TIE
MATERIAL OR ANCHORED HEAVY NYLON (AROUND WIRE TIES. SUCTION LINE
STRAPPING MATERIAL ONLY)
(AROUND SUCTION
LINE ONLY)
TAPE OR
8 FEET
WIRE TIE
IMPORTANT - REFRIGERANT LINES
OUTSIDE WALL SUCTION LINE
NOTE - Similar installation
practices should be used if
line set is to be installed on exterior of outside wall.
SUCTION LINE WRAPPED
WITH ARMAFLEX
IMPORTANT!
MUST NOT CONTACT WALL.
LIQUID LINE
SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
METAL
SLEEVE
TAPE OR
WIRE TIE
FLOOR JOIST OR
ROOF RAFTER -- ,b _
STRAP THE SUCTION LINE TO THE JOIST OR RAFTER AT 8 FEET
INTERVALS THEN STRAP THE LIQUID LINE TO THE SUCTION LINE.
Figure 10. Refrigerant Line Set: Installing Horizontal
Runs
ANCHORED HEAVY
NYLON WIRE TIE
\
WAU / STU[ /
/ /
METAL SLEEVE
! _ STRAPUQU_DUNE
TO SUCTION LINE
\
X LIQUID LINE
SUCTION LINE - WRAPPED IN ARMAFLEX
CONTACT
STRUCTURE.
PVC _ CAULK
PIPE
FIBERGLASS
INSULATION
Figure 11. Refrigerant Line Set: Installing Vertical
Runs (New Construction Shown)
AUTOMOTIVE
MUFFLER-TYPE HANGER
WALL STUD
STRAP LIQUID LINE TO SUCTION LINE
UIDLINE
SUCTIONLINE-WRAPPEDIN ARMAFLEX
METAL SLEEVE
Figure 12. Refrigerant Line Set: Transition from Vertical to Horizontal
Page 7
13ACD SERIES
Page 8
1
CUT AND DEBUR
INDOOR UNIT
REMOVE CAP AND CORE FROM
BOTH LIQUID AND SUCTION
SERVICE PORTS
SERVICE PORT MUST BE
OPEN TO ALLOW EXIT
POINT FOR NITROGEN SERVICE
/. SUCTION LINE _ /VALVE
OUTDOOR
UNIT
LIQUtD LINE SERVICE/_
,4-,,
INSTALL CORE ONLY FOR
BOTH SERVICE PORTS AFTER
THEY HAVE COOLED.
Figure 13. Brazing Connections
Use the following procedure to braze the line set to the new outdoor unit, Figure 13 is provided as a general guide for
preparing to braze the line set to the outdoor unit,
A, WARNING I
VALVE
RAP /_
SER
VALVE _
3. Connect gauge low pressure side to liquid line service valve,
4, To protect components during brazing, wrap a wet
cloth around the liquid line service valve body and copper tube stub and use another wet cloth
underneath the valve body to protect the base paint.
5, Flow regulated nitrogen (at 1 to 2 psig) through the
refrigeration gauge set into the valve stem port connection on the liquid line service valve and out of
the valve stem port connection on the suction service valve, The TXV metering device at the indoor unit coil will allow low pressure nitrogen to flow through the system,)
NOTE - The fixed orifice or TXV metering device at the indoor unit will allow low pressure nitrogen to flow through the system,)
NOTE - Use silver alloy brazing rods with five or six percent
WARNING
1. Cut ends of the refrigerant lines square (free from nicks or dents). Debur the ends, The pipe must remain round, do not pinch end of the line,
2. Remove service cap and core from both the suction and liquid line service ports.
505366M 01/08
i minimum silver alloy for copper-to-copper brazing or 45percent silver alloy for copper-to-brass or copper-to-steel
brazing.
6, Braze the line to the liquid line service valve, Turn off
nitrogen flow,
,A IMPORTANT
7. After all connections have been brazed, disconnect manifold gauge set the from service ports and remove
wrapping. Reinstall the service port core for both of the outdoor unit's service valves.
Page 8
Page 9
TYPICAL TXV REMOVAL PROCEDURE
RemovetheexistingHCFC-22refrigerantflowcontrol orificeorthermalexpansionvalvefromtheindoorcoil.
REPLACEMENTPARTS If replacementpartsarenecessaryfortheindoorunit,
orderkit69J46.Thekitincludes:
10-- Brassnutsforliquidlineassemblies
20-- Teflonrings
10-- Liquidlineorificehousings
10-- Liquidlineassemblies
LIQUID LINE ORIFICE HOUSINGS (10)
_ ..._iE FL ON _%GS(s20 )NUT _
_ TRAIN ERCOPPER
LIQUID LINE
ASSEMBLY
LIQUID LINE ASSEMBLIES
(INCLUDES STRAINER) (10)
i
Figure 14. 69J46 Kit Components
TYPICAL FIXED ORIFICE REMOVAL PROCEDURE
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
TEFLON RING REMOVE AND DISCARD
FIXED VALVE STEM ASSEMBLY
". i s
DISTRIBUTOR " -
ASSEMBLY
VALVE STEM
VALVE STEM CAP (Uncased Coil Shown)
(IF PRESENT)
f
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
PISTON
/ RETAINER
TUBE
BRASS NUT
TWO PIECE
PATCH PLATE
JNCASED COIL LIQUID LINE STUB END
ONLY) \ ORIFICE HOUSING
)ISTRIBUTOR TXV
TUBES
RING
MALE EQUALIZER LINE /
FITTING / SUCTION
SENSING BULB LINE
/
LIQUID
LINE
Figure 16. Typical TXV Removal
1, On fully cased coils, remove the coil access and
plumbing panels.
2, Remove any shipping clamps holding the liquid line
and distributor assembly,
3, Disconnect the equalizer line from the TXV equalizer
line fitting on the suction line,
4, Remove the suction line sensing bulb as illustrated in
figure 16.
5, Disconnect the liquid line from the TXV at the liquid line
assembly,
6, Disconnect the TXV from the liquid line orifice housing.
Take care not to twist or damage distributor tubes during this process,
7. Remove and discard TXV and the two Teflon rings as illustrated in figure 16,
13ACD units can be configured for use in with HCFC-22
fixed orifice or TXV metering devices, This section
provides instructions on installing either a fixed orifice or TXV refrigerant metering device,
(Uncased Coil Shown)
Figure 15. Typical Fixed Orifice Removal
1. On fully cased coils, remove the coil access and plumbing panels.
2. Remove any shipping clamps holding the liquid line and distributor assembly.
3. Using two wrenches, disconnect liquid line from liquid line orifice housing. Take care not to twist or damage
distributor tubes during this process.
4. Remove and discard fixed orifice, valve stem assembly if present and Teflon ring as illustrated in
figure 15.
1/2 TURN
Figure 17. Tightening Distance
Page 9
13ACD SERIES
Page 10
TYPICAL FIXED ORIFICE INSTALLATION PROCEDURE
1, Installed the provided RFC orifice that was supplied
with the outdoor unit as illustrated in figure 18,
2, Ensure that the fixed orifice supplied with the outdoor
unit is installed with the nylon seat pointing toward the liquid line orifice housing,
3, Apply a small amount of refrigerant oil on the Teflon
ring and insert securely into the liquid line orifice housing,
4, Attach the liquid line assembly to the liquid line orifice
housing, Finger tighten and use an appropriately sized
wrench to turn an additional 1/2 turn clockwise as
illustrated in figure 17, or 20 ft-lb,
5. Place the supplied fixed orifice sticker on the indoor cabinet after installation,
t, I / L,OU,DL,NEOR,F,CEHOUS,NG
_%,_\%. ]_/ FIXED
_L_'_ I ORIFICE TEFLON
J_'___ _((((_ / WASHER
/ I-I Oj-- L'NE
(Uncased Coil Shown)
Figure 18. Typical Fixed Orifice Installation
See the 13ACD Engineering Handbook forapproved TXV indoor/outdoor unit match-ups and application
information. Table 4 lists both the Lennox catalog and part numbers for the TXV kit required for each unit model,
Figure 19 illustrates the kit components and quantities,
Table 3. Indoor Fixed Orifice Kits
Catalog
Model Number Part Number Drill Size
018 10W95 100484-07 0.055 024 98M 12 100484-12 0.062 030 11W00 100484-16 0.067 036 98M78 100484-24 0.076 042 10W86 100484-28 0.080
048 98M 14 100484-36 0.089 060 98M 15 100484-45 0.099
Use the Lennox catalog number to order a new or replacement fixed
orifice kit.
The kit includes:
1 -- Fixed orifice
1 -- Fixed orifice extractor
1 -- Teflon ring
1 -- Fixed orifice sticker
FIXED ORIFICE (1)
FIXED ORIFICE EXTRACTOR (1)
TEFLON RING (1)
._. FIXED ORIFICE STICKER (1)
Figure 19. Fixed Orifice Kit Components
TYPICAL TXV INSTALLATION PROCEDURE
The TXV unit can be installed internal or external to the indoor coil. In applications where an uncased coil is being
installed in a field-provided plenum, install the TXV in a manner that will provide access for field servicing of the
TXV, Refer to Figure 20 for reference during installation of TXV unit,
1, Install one of the provided Teflon rings around the
stubbed end of the TXV and lightly lubricate the connector threads and expose surface of the Teflon
ring with refrigerant oil.
2, Attach the stubbed end of the kit valve to the liquid line
orifice housing, Fingertighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise
as illustrated in figure 17, or 20 ft-lb.
3, Place the remaining Teflon washer around the other
end of the TXV. Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant
oil,
4, Attach the liquid line assembly to the TXV. Finger
tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in figure
17, or 20 ft-lb.
5, Attach the suction line sensing bulb in the proper
orientation as illustrated in figure 21 using the clamp an screws provided,
NOTE - Insulating the sensing bulb once installed may be required when the bulb location is external to the coil casing.
505366M 01_8
Page 10
Page 11
TWOPIECE (UncasedCoilShown)
PATCH PLATE
tNCASED COIL
ONLY) LIQUID LINE
DISTRIBUTOR TXV
TUBES. -
HOUSING
..._ORIFICE STUB END
RING
FLARE SEAL
CAP
,_ [__FLARE NUT
I X COPPERE OR --FLARE SEAL
I
-- MALE BRASS EQUALIZER
BONNET
MALE EQUALIZER LINE
FITTING (SEE SUCTION
FIGURE 22 FOR LINE
FURTHER DETAILS)
Sensing bulb insulation is required if mounted external to the coil casing. See figure 21 for bulb positioning,
Figure 20. Typical TXV Installation
Suction Line, 718", mount sensing bulb
/
Bulb
\
On lines smaller than at either the 3 or 9 o'clock
position,
LIQUID
LINE
_ LINE FITTING
SUCTION LINE
Figure 22. Copper Flare Seal Bonnet Removal
7, Connect the equalizer line from the TXV to the
equalizer suction port on the suction line. Finger tighten the flare nut plus 1/8 turn (7 ft-lbs) as illustrated in figure 17,
NOTE - To prevent any possibility of water damage,
properly insulate all parts of the TXV assembly that may
sweat due to temperature differences between the valve and its surrounding ambient temperatures,
See the 13ACD Engineering Handbook for approved TXV match-ups and application information.
Table 4. Indoor TXV Indoor Kits
Model Catalog Part
-018, -024, -030 and -036 26K34 LB-85663J
-042, -048 and -060 26K35 LB-85663k Use the Lennox catalog number to order a TXV kit.
Number Number
The above reference kits include:
1 -- TXV
2 -- Teflon rings
1 -- 1 1/4" wide copper mounting strap for sensing bulb
2 --#10 hex head bolts and nuts for securing sensing bulb
On 7/8" and larger lines,
Suction Line
_2_"Y A,.\\",_ t
mount sensing bulb at
either the 4 or 8 o'clock
position, never mount on
mof line.
(Bulb .
NO TE - Never mount on bottom of line.
Figure 21. TXV Sensing Bulb Installation
6, Remove and discard either the flare seal cap or flare
nut with copper flare seal bonnet from the equalizer line port on the suction line as illustrated in figure 22.
IMPORTANT
AND NUTS (2)
O_TEFLON
RINGS (2) _ _//7
J
STRAP (1) _
Figure 23. TXV Kit Components
Xk IMPORTANT
Page 11
13ACD SERIES
Page 12
WARNING
WARNING I
After the line set has been connected to both the indoor
and outdoor units, check the line set connections at both the indoor and outdoor units unit for leaks. Use the
following procedure to test for leaks:
1. Connect an HCFC-22 manifold gauge set high pressure hose to the suction valve service port,
NOTE - Normally, the high pressure hose is connected to
the fiquid line port; however, connecting it to the suction port better protects the manifold gauge set from high pressure damage,
2. With both manifold valves closed, connect the cylinder of HCFC-22 refrigerant to the center port of the manifold gauge set. Open the valve on the HCFC-22 cylinder (suction only).
3. Open the high pressure side of the manifold to allow HCFC-22 into the line set and indoor unit,
4. Weigh in a trace amount of HCFC-22. [A trace amount
is a maximum of two ounces (57 g) refrigerant or three
pounds (31 kPa) pressure],
5. Close the valve on the HCFC-22 cylinder and the valve on the high pressure side of the manifold gauge set,
6, Disconnect the HCFC-22 cylinder,
7. Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold
gauge set.
NOTE - Amounts of refrigerant will vary with line lengths.
8, Adjust dry nitrogen pressure to 150 psig (1034 kPa),
9. Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit,
10. After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector.
11. Check all joints for leaks,
12. Purge dry nitrogen and HFC-410A mixture.
13. Correct any leaks and recheck.
I
14. After leak testing disconnect gauges from service ports.
WARNING
,& IMPORTANT
Evacuating the system of non-condensables is critical for
proper operation of the unit. Non-condensables are defined as any gas that will not condense under
temperatures and pressures present during operation of an air conditioning system. Non-condensables and water
suction combine with refrigerant to produce substances that corrode copper piping and compressor parts,
1. Connect manifold gauge set to the service valve ports as follows:
low pressure gauge to suction line service valve
high pressure gauge to liquid line service valve
2. Connect micron gauge,
3. Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set,
4. Open both manifold valves and start the vacuum pump.
5. Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of
mercury).
NOTE - During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in sure indicates a relatively large leak, If this occurs, repeat the leak testing procedure.
NOTE - The term absolute pressure means the total actual pressure within a given volume or system, above
the absolute zero of pressure, Absolute pressure in a
vacuum is equal to atmospheric pressure minus vacuum
pressure,
6. When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034
kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor
unit, Close the manifold gauge valves.
505366M 01_8
Page 12
Page 13
DESCRIPTION
A4 i]ONTROL-TIMED OFF _I i]OMPRESSOR
54 i_OTOR-OUTDOOR FAN
_12 i]APACITOR-DUAL HRI i4EATER-COMPRESSOR
KI.-liCONTACTOR-COMPRESSOR
$4 iSWlTCH-HIGH PRESSURE
587 i_WITCH-LOW PRESS.COMP I
./_ FOR USE WITH COPPER
CONDUCTORS ONLY. REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT
AMPACITY AND MAXIMUM OVERCURRENT PROTECTION SIZE,
Z_ JUMPER IS USED WHEN TOC IS NOT USED
_LINE VOLTAGE FIELD INSTALLED I III CLASS II VOLTAGE FIELD INSTALLED
MP N NT
INDICATES OPTIONAL COMPONENTS
WARNING-
ELECTRIC SHOCK HAZARD, CAN CAUSE
INJURY OR DEATH, UNIT MUST BE
GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES.
OUTDOOR
PURPLE
CLACK
ORANGE
COMPRESSOR
CRANKCASE HEATER
208-23016011
L2.,_
_-_EOUIPMENT
= GROUND
HRI
r_
RED
DUAL CAPACITOR
CONTACTOR
OROUND
LUG
KI-I YELLOWl I IBt HIBF 587 OR SZ4
o-oiRE°I i SW,TcHPRESSORE
$ (I ]ORANGEI .
NOTE - A complete unit wiring diagram is located inside the unit control box cover.
A4
TIMED OFF
CONTROL
I I I
-L4_
I I
TO 24 VAC POWER
SOURCE
20 VA MINIMUN NEC CLASS 2
C YI
TO 24 VAC
P_ER SOURCE
20 VA MINIMUN NEC CLASS 2
Figure 24. Typical Wiring Diagram
7. Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the dry nitrogen from
the line set and indoor unit,
8. Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not
rise above 500 microns (29.9 inches of mercury) within
a 20-minute period after shutting off the vacuum pump and closing the manifold gauge valves.
9. When the absolute pressure requirement above has been met, disconnect the manifold hose from the
vacuum pump and connect it to an upright cylinder of
HCFC-22 refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set
and indoor unit,
10. Close manifold gauge valves and shut off the HCFC-22 cylinder and remove the manifold gauge
set,
If the system is void of refrigerant, clean the system using the procedure described below.
1. Use nitrogen to pressurize the system and check for leaks, Repair all leaks,
2. Evacuate the system to remove as much of the moisture as possible,
3. Use nitrogen to break the vacuum and install a new filter drier in the system.
4. Evacuate the system again. Then, weigh the appropriate amount of HCFC-22 refrigerant as listed on unit nameplate into the system,
5. Monitor the system to determine the amount of moisture remaining in the oil. It may be necessary to
replace the filter drier several times to achieve the required dryness level. If system dryness is not verified, the compressor will fail in the future.
I WARNING
Refer to the indoor unit installation instruction for additional
wiring application diagrams and refer to unit nameplate for
minimum circuit ampacity and maximum overcurrent protection size. Figures 26 and 24 illustrate typical outdoor unit wiring diagrams for the 13ACD series heat pumps.
In the U.S,A., wiring must conform with current local codes and the current National Electric Code (NEC),
Page 13
13ACD SERIES
Page 14
In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC),
HIGH VOLTAGE FIELD WIRING
LOW VOLTAGE
FIELD WIRING
-- FACTORY WIRING
GROMMET
THERMOSTAT
@ @
Q COOLING
Q BLOWER
POWER
HEAT
INDOOR
COMMON
INDOOR UNIT
@I OUTDOOR
QI
d
UNIT
Figure 25. Separating High/Low Voltage Field Wiring
(Typical Field Wiring)
WIRING CONNECTIONS
1, Install line voltage power supply to unit from a properly
sized disconnect switch. Any excess high voltage field
wiring should be trimmed or secured away from the
low voltage field wiring.
2, Ground unit at unit disconnect switch or to an earth
ground.
3, Connect conduit to the unit using provided conduit
bushing,
4, Install room thermostat (ordered separately) on an
inside wall approximately in the center of the conditioned area and five feet (1.5 m) from the floor.
It should not be installed on an outside wall or where it can be affected by sunlight, drafts or vibrations,
NOTE - For proper voltages, select thermostat wire gauge
per the following table:
Table 5. Wire Run Lengths
Wire run length AWG # Insulation type
Less than 100 feet (30 m) 18 Color-coded with a minimum More than 100 feet (30 m) 16 temperature rating of 35°C.
5, Install low voltage wiring from outdoor to indoor unit
and from thermostat to indoor unit as illustrated in
figures 26 and 24.
6, Do not bundle any excess 24VAC control wire inside
control box. Run control wire through installed wire tie and tighten wire tie to provided low voltage strain relief and to maintain separation of field installed low and high voltage circuits,
NOTE - 24VAC, Class II circuit connections are made in the low voltage junction box
NOTE - Units are approved for use only with copper conductors.
NOTE - To facilitate conduit, a hole is in the bottom of the control box. Connect conduit to the control box using a
proper conduit fitting.
NOTE - See unit wiring diagram for power supply connections. If indoor unit is not equipped with blower
relay. It must be field-provided and installed (P-8-325 f or
equivalent)
Figure 26. Typical Field Low Voltage Wiring
A IMPORTANT
1. Rotate fan to check for binding.
2, Inspect all factory- and field-installed wiring for loose
connections.
3, After evacuation is complete, open the liquid line and
suction line service valves to release the refrigerant charge (contained in outdoor unit) into the system.
4, Replace the stem caps and tighten as specified in
Operating Service Valves on page 2,
5, Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit's nameplate. If not, do not start the equipment until you have consulted with the power company and the
voltage condition has been corrected,
6, Set the thermostat for a cooling demand. Turn on
power to the indoor indoor unit and close the outdoor unit disconnect switch to start the unit.
7, Recheck voltage while the unit is running. Power must
be within range shown on the nameplate,
8, Check system for sufficient refrigerate by using the
procedures listed under Testing and Charging
System.
SETTING UP TO CHECK CHARGE
1, Close manifold gauge set valves. Connect the center
manifold hose to an upright cylinder of HCFC-22,
2, Connect the manifold gauge set to the unit's service
ports as illustrated in figure 1,
low pressure gauge to suction service port
high pressure gauge to #quid service port
INDOOR AIRFLOW CHECK Check airflow using the Delta-T (DT) process using the
illustration in figure 27.
DETERMINING CHARGE METHOD Use the illustration in figure 28 to determine the correct
charging method.
505366M 01/08
Page 14
Page 15
Delta-T
24 24 24 23 23 22 22 22 20 19 18 17 16 15
78
23 23 23 22 22 21 21 20 19 18 17 16 15 14
76
22 22 22 21 21 20 19 19 18 17 16 15 14 13
80
74
21 21 21 20 19 19 18 17 16 16 15 14 13 12 20 20 19 18 17 17 161L_5._15 14 13 12 11 10
19 19 18 18 17 17 16 15 15 14 13 12 11 10
I Wet-bulb °F
57 58 59 60 61 62 63 64 65 66 67 68 69 70 I
iNDOOR t WET
COIL BULB
Figure 27. Checking Indoor Airflow over Evaporator Coil using Delta-T Chart
(WHEN TO CHARGE?
Warm weather best
Can charge in colder weather CHARGE METHOD? Determine by:
Metering device type
Outdoor ambient temperature REQUIREMENTS:
Sufficient heat load in structure
Indoor temperature between 70-80°F (21-26°C)
Manifold gauge set connected to unit
Thermometers:
to measure outdoor ambient temperature to measure liquid line temperature to measure suction line temperature
1. Determine the desired DT--Measure entering air temperature using dry bulb (A) and wet bulb (B). DT is the intersecting value of A and B in the table (see triangle).
2. Find temperature drop across coil--Measure the coil's dry bulb entering and leaving air temperatures (A and C). Temperature Drop
Formula: (TDrop) = A minus C.
I
3. Determine if fan needs adjustment--If the difference between the
I
measured TDropand the desired DT (TDrop-DT} is within +3°, no ad-
justment is needed. See examples: Assume DT = 15 and A temp. =
72°, these C temperatures would necessitate stated actions: C° TDrop- DT = °F ACTION
53° 19 - 15 = 4 Increase the airflow
DRY
BULB
58° 14 - 15 = -1 (within +3 ° range) no change 62° 10 - 15 = -5 Decrease the airflow
4. Adjust the fan speed--See indoor unit instructions to increase/de- crease fan speed.
Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and DT are within +3 °.
APPROACH OR
SUBCOOLING
WEIGH-IN
SUPERHEAT
Figure 28. Determining Charge Method
WE G
Refrigerant Charge per Line Set Length
Liquid Line Ounces per 5 feet (g per 1.5 m)
Set Diameter adjust from 15 feet (4.6 m) line set*
3/8" (9.5 mm) 3 ounce per 5' (85 g per 1.5 m)
NOTE - *If line length is greater than !5 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this
amount.
Figure 29. HCFC-22 Weigh In TXV Method
BELOW
LENNOX
Page 15
1. Check Liquid and suction line pressures
2. Compare unit pressures with Table 6, Normal Operating Pressures.
3. Conduct leak check; evacuate as previously outlined,
4. Weigh in the unit nameplate charge plus any charge required for line set differences
over feet.
This nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.
13ACD SERIES
Page 16
ABOVE
If refrigerant added or
removed, verify charge using the approach method
BLOCK OUTDOOR COIL: [sometimes necessary with lower temperatures] Use cardboard or plastic sheet to
restrict the airflow through the outdoor coil to achieve
If value is greater than shown, remove refrigerant; if less than
shown, add refrigerant
SC ° (Subcooling) Values (F:+/-1.0 ° [C: +/-0.6°])
Any 7 (3.8) 12 (6.7) 9 (5) 10 (5.6) 14 (8) 10 (5.6) 13 (7.2) °F (°C)* -018 -024 -030 -036 -042 -048 -060 *Temperature of air entering outdoor coil
pressures from 200-250 psig (1379-1724 kPa). Higher pressures are needed to check charge. Block equal sections of air intake panels and move coverings sideways
until the liquid pressure is in the above noted ranges.
1. Confirm proper airflow across coil using figure
27.
2. Compare unit pressures with Table 6, Normal Operating Pressures.
3. Use SUBCOOLING to correctly charge unit or to verify the charge is correct.
4. Set thermostat to call for heat (must have a cooling load between 70-80°F (21-26°C)
5. Connect gauge set
6. Measure outdoor ambient temperature
7. When heat demand is satisfied, set thermostat to call for cooling
8. Allow temperatures and pressures to stabilize.
NOTE - If necessary, block outdoor coil to maintain 325 - 375 psig.
9. Record line temperature:
LIQo=
10. Measure liquid line pressure and use the value to determine saturation temperature:
SAT o=
11. Subtract to determine subcooling (SC°): SATo . LIQ o = SCo
12. Compare results with table to the left.
Figure 30. HCFC-22 Subcooling TXV Charge
ABOVE
H
........[XV
If value is greater than shown (high
approach), add refrigerant; if less than shown (liquid temp too close to ambient temp, low approach), remove
refrigerant.
APP ° (Approach) Values(F:+/-1.0 ° [C: +/-0.6°])
°F (°C)* -018 -024 -030 -036 -042 -048 -060 Any) 6 (3.3) 6 (3.3) 8 (4.4) 12 (6.7) 5 (2.8) 6 (3.3) 7 (3.8)
*Temperature of air entering outdoor coil
If refrigerant added or removed, retest to confirm that unit is
properly charged
Figure 31. HCFC-22 Approach TXV Charge
1. Confirm proper airflow across coil using figure
27.
2. Compare unit pressures with Table 6, Normal
Operating Pressures.
3. Use APPROACH to correctly charge unit or to verify the charge is correct.
4. Set thermostat to call for heat (must have a cooling load between 70-80°F (21-26°C).
5. Connect gauge set.
6. When heat demand is satisfied, set thermostat to call for cooling.
7. Allow temperatures and pressures to stabilize.
8. Record outdoor ambient temperature:
AMB°=
9. Record line temperature:
LIQo=
10. Subtract to determine approach (APP°):
LIQo . AMB o = App o
11. Compare results with table to the left.
505366M 01/08
Page 16
Page 17
f ER I A ....RFC
If refrigerant added or removed, retest to confirm
that unit is properly charged
If value is greater than
shown, add refrigerant; if
less than shown, remove refrigerant.
ABOVE
SH ° (Superheat) Values (+/-5°F)
Wet Bulb air enterinc indoor coil
°F* 50 52 54 56 '58 60 62 64 66 68 70 72 74 76 40 15 18 20 23 26 29 32 34 38 41 43 46 48 51
45 13 16 18 21 24 27 30 33 36 39 41 44 46 49
50 11 14 16 19 22 25 28 31 34 37 39 42 44 47 55 9 12 14 17 20 23 27 30 33 36 38 40 42 44
60 7 10 12 15 18 21 24 27 30 33 35 38 40 43 65 6 10 13 16 19 21 24 27 30 33 36 38 41
70 7 10 13 16 19 21 24 27 30 33 36 39 75 6 9 12 15 18 21 24 28 31 34 37 80 5 8 12 15 18 21 25 28 31 35 85 8 11 15 19 22 26 30 33
90 5 9 13 16 20 24 27 31 95 6 10 14 18 22 25 29
100 8 12 16 21 24 28 105 5 9 13 17 22 26
110 6 11 15 20 25 115 8 14 18 24
* Dry-bulb temperature (°F) of entering outdoor ambient air.
1. Confirm proper airflow across coil using figure27.
2. Compare unit pressures with Table 6, Normal Operating Pressures.
3. Use SUPERHEAT to correctly charge unit or to verify the charge is correct,
4. Set thermostat to call for heat (must have a cooling load between 70-80°F (21-26°C)
5. Connect gauge set,
6. When heat demand is satisfied, set thermostat to
call for cooling.
7. Allow temperatures and pressures to stabilize.
8. Measure the suction line pressure and use the use
value to determine saturation temperature: SAT o=
9. Record suction line temperature:
VAP o=
10. Subtract to determine superheat (SH°): VAP o. SAT o = SH o
11. Record the wet bulb temperature (air entering indoor coil):
WB =
12. Record outdoor ambient temperature,
13. Compare results with table to the left,
NOTE - Do not attempt to charge system where a dash appears, system could be ovemharged.
Superheat is taken at suction line service port. Suction line superheat must never be less than 5°t: at the suction line service port.
Figure 32. HCFC-22 Superheat RFC Charge
Page 17
13ACD SERIES
Page 18
Table 6. HCFC-22 Normal Operating Pressures (Liquid +10 and Suction +5 psig)
A IMPORTANT
13ACD -018 -024 -030 -036 -042 -048 -060
°F (°C)* Liquid/Suction Liquid/Suction Liquid/Suction Liquid / Suction Liquid/Suction Liquid/Suction Liquid / Suction
Expansion Valve (TXV)
65 (18) 138 / 79 148 / 79 147 / 75 155 / 79 147 / 78 144 / 77 152 / 73 70 (21) 148 / 80 160 / 79 159 / 75 169 / 80 158 / 78 152 / 77 164 / 75
75 (24) 160 / 80 174 / 80 172 / 76 183 / 81 172 / 79 163 / 78 177 / 77 80 (27) 174 / 81 188 / 81 186 / 77 199 / 81 189 / 79 179 / 78 192 / 78
85 (29) 188 / 81 203 / 81 201 / 77 215 / 82 205 / 80 195 / 79 208 / 79 90 (32) 204 / 81 220 / 82 216 / 78 233 / 82 222 / 81 212 / 80 225 / 80
95 (35) 219 / 82 236 / 83 233 / 79 252 / 83 241 / 81 229 / 80 243 / 80
100 (38) 236 / 82 253 / 83 250 / 80 271 / 83 259 / 82 245 / 81 261 / 81 105 (41) 253 / 83 272 / 84 268 / 80 291 / 84 279 / 82 265 / 81 280 / 82
110 (43) 272 / 84 291 / 85 287 / 81 311 / 85 299 / 83 287 / 82 299 / 83 115 (45) 291 / 84 311 / 85 306 / 82 331 / 86 320 / 84 309 / 83 320 / 83
Fixed Orifice (RFC)
65 (18) 139 / 67 147 / 71 148 / 65 162 / 75 158 / 72 151 / 71 152 / 68 70 (21) 149 / 70 159 / 73 161 / 67 174 / 76 170 / 75 161 / 73 165 / 71
75 (24) 161 /74 172 / 75 175 / 70 187 / 78 182 / 76 172 / 75 178 / 73 80 (27) 175 / 77 186 / 77 190 / 73 201 / 79 195 / 78 185 / 76 193 / 76 85 (29) 189 / 79 200 / 79 205 / 75 215 / 81 209 / 80 198 / 77 208 / 78
90 (32) 203 / 81 216 / 81 221 / 77 231 / 82 224 / 81 213 / 79 224 / 80 95 (35) 218 / 82 232 / 82 237 / 79 247 / 83 240 / 82 227 / 80 239 / 81
100 (38) 234 / 83 247 / 83 254 / 80 265 / 84 256 / 84 243 / 81 258 / 82 105 (41) 251 / 85 264 / 85 271 / 81 283 / 85 273 / 85 259 / 82 276 / 83
110 (43) 269 / 86 285 / 86 289 / 82 302 / 86 290 / 86 276 / 84 294 / 85 115 (45) 287 / 87 302 / 87 308 / 83 321 / 87 310 / 87 293 / 85 313 / 86
INSTALLING SERVICE VALVE CAPS
Disconnect gauge set and re-install both the liquid and suction service valve caps.
I WARNING
OUTDOOR UNIT
SERVICE VALVES _ /
INSTALL CAPS
Figure 33. Installing Service Valve Caps
The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch
is in the ON position, the indoor blower operates continuously.
505366M 01/08
WARNING
Page 18
Page 19
At the beginningof eachcoolingseason,thesystem
shouldbecheckedasfollows: OUTDOORUNIT
1, Cleanandinspectoutdoorcoil(maybeflushedwitha
waterhose).Ensurepowerisoffbeforecleaning,
2, Outdoorunitfanmotorispre-lubricatedandsealed.
Nofurtherlubricationisneeded.
3,Visuallyinspectallconnectinglines,jointsandcoilsfor
evidenceofoilleaks.
4, Checkallwiringforlooseconnections,
5, Checkforcorrectvoltageatunit(unitoperating),
6, Checkampdrawonoutdoorfanmotor,
UNITNAMEPLATE: ACTUAL:
7, Inspectdrainholesin coil compartmentbaseand
cleanifnecessary,
NOTE - If insufficient heating or cooling occurs, the unit should be gauged and refrigerant charge should be
checked.
INDOOR COIL
1. Clean coil if necessary.
2. Check connecting lines, joints and coil for evidence of oil leaks,
3. Check condensate line and clean if necessary,
INDOOR UNIT
IMPORTANT
NOTE - A white residue may appear on the coil guards and grilles on outdoor units, The residue is a non-toxic
byproduct of manufacturing the flexible coating. It can be removed by wiping the coil guard with a cloth.
9 PINS USED ON -048 AND _060; 6 PINS ALL
OTHERS
1, Clean or change filters,
2, Blower motors are prelubricated and permanently
sealed, No more lubrication is needed,
3, Adjust blower speed for cooling, Measure the pressure
drop over the coil to determine the correct blower CFM
Refer to the unit information service manual for pressure
drop tables and procedure.
4, Belt Drive Blowers - Check belt for wear and proper
tension,
5, Check all wiring for loose connections.
6. Check for correct voltage at unit, (blower operating)
7, Check amp draw on blower motor.
UNIT NAMEPLATE: ACTUAL:
OPTIONAL ACCESSORIES Refer to the Engineering Handbook for optional
accessories that may apply to this unit, The following may or may not apply:
kWARNING
PUSH Pli'
MESH SCREEN
Figure 34. Cleaning debris from mesh
Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each
cooling season, the system should be checked as follows:
1, Make sure power is off before cleaning. Clean and
inspect outdoor coil, The coil may be flushed with a water hose,
2, The outdoor coil is protected by an inner mesh screen
and a wire cage (see figure 34), If debris has collected between the mesh screen and the coil and cannot be
dislodged by spraying unpressurized water from inside coil surface to the outside, the mesh may be
removed by first removing the top of the unit which will allow for removal of the wire cage,
3, Then, using pliers to grip the head of the push pins, pull
straight out to extract the push pins along one side of the coil. If necessary, remove the push pins along the
back of the unit; it is usually unnecessary to fully remove the inner mesh screen,
4. Drape the mesh screen back and wash the coil. When all the debris has been removed from the coil, reinstall
the mesh screen by positioning it in its original position
Page19
13ACD SERIES
Page 20
and reinserting the push pin. No tool is required to push the pin back into the same slot in the fins.
5, If the push pin is loose and tends not to stay in place,
brush the fins with a fin brush (22 fins/in). Line up the push pin a couple fins to the right or left of the original hole and re-insert the pin.
THERMOSTAT OPERATION Thermostat operations vary from one thermostat to
another. The following provides general operation procedures. Refer to the user's information manual
provided with your thermostat for specific operation details.
Temperature Setting Levers
Fan Switch
System Switch Set the system switch for heating, cooling or auto
Temperature The temperature indicator displays the actual room
Indicator temperature.
Set the lever or dial to the desired temperature setpoints for both heating and cooling. Avoid frequent temperature adjustment; turning the unit off--then back on--before pressures can equalize will put unusual stress on the unit's compressor.
In AUTO or INT (intermittent) mode, the blower operates only when the thermostat calls for heating or cooling. This mode is generally preferred when humidity control is a priority. The ON or CONT mode provides continuous indoor blower operation, regardless of whether the compressor or furnace is operating. This mode is required when
constant air circulation or filtering is desired.
operation. The auto mode allows the system to automaticallyswitch from heating mode to cooling mode to maintain predetermined comfort settings.
PROGRAMMABLE THERMOSTATS
Your Lennox system may be controlled by a
programmable thermostat. These thermostats provide the added feature of programmable time-of-day setpoints for
both heating and cooling. Refer to the user's information manual provided with your thermostat for operation
details.
PRESERVICE CHECK
If your system fails to operate, check the following before
calling for service:
Make sure all electrical disconnect switches are ON.
Make sure the room thermostat temperature selector AND the system switch are properly set.
Replace any blown fuses, or reset circuit breakers.
Make sure unit access panels are in place.
Make sure air filter is clean.
Locate and record unit model number before calling.
Refer to the Lennox 13ACD Engineering Handbook for the
latest available accessories for this unit. Below is a list of accessories available at the time this instruction was
)ublish.
Optional Accessory
Compressor Start Kit Loss of Charge Kit
Sound Cover Replacement Liquid Line Drier
Plastic Feet Kit Crankcase Heater - 40W
High Pressure Kit
Catalog Number
10J42
94J47 69J03
12L71
94J45 93M04
94J46
Part Number
LB-31200BM LB-87620A
69J0301
12L7101
LB-87156A
100499-01
LB-87620A
Job Name Job Location Installer
Unit Model No,
Serial No. Nameplate Voltage Rated Load Ampacity
Compressor
Maximum Fuse or Circuit Breaker Electrical Connections Tight?
Indoor Blower RPM Discharge Pressure __
S.P. Drop Over Indoor (Dry)
Suction Pressure
Indoor Filter clean?
Service Valves: --- Fully Opened? _ Caps Tight? Voltage With Compressor Operating
Job no. Date
City State City State
Service Technician
Outdoor Fan
Supply Voltage (Unit Off) Outdoor Coil Entering Air Temp.
Refrigerant Charge Checked?
J Thermostat
Calibrated? _ Properly Set? _ Level?
505366M 01/08
Page 20
Loading...