INSTALLATION AND OPERATION INSTRUCTIONS
ME43
43" Wood Burning Fireplaces P/N 850,027M REV. F 01/2008
MODEL
ME43BK SP
This installation manual will enable you to obtain a safe, efficient and dependable installation of your fireplace system. Please read and understand these instructions before beginning your installation.
Do not alter or modify the fireplace or its components under any circum­stances. Any modification or alteration of the fireplace system, including but not limited to the fireplace, chimney components and accessories, may void the warranty, listings and approvals of this system and could result in an unsafe and potentially dangerous installation.
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNINGS
• Hot! Do not touch! The glass and surfaces of this appliance will be hot during operation and will retain heat for a while after shutting off the appli­ance. Severe burns may result.
• Carefully supervise children in the same room as appliance.
Listed to standards: ULC-S610 & UL-127
Report No. 192-5166
Lennox™ wood-burning fireplaces are designed for use as a supple­mental heater. They are not intended for continuous use as a primary heat source.
WARNINGS
• The fireplace cannot be operated without a door. Consult your dealer to select the correct door model.
• Important! To assure proper alignment of glass doors: Install this fireplace in a square and plumb condition, using shims as necessary at sides and/or bottom.
• Install the fireplace only as described in these instructions.
PIME43-F REV. 3
Page 2
IMPORTANT! GENERAL SAFETY PREC A UTIONS . READ AND UNDERSTAND THESE SAFETY RULES BEFORE YOUR FIRST FIRE.
WARNING
Never leave children unattended when there is a fire burning in the fireplace.
IMPORTANT
When burning wood, use SOLID NATURAL DRY WELL-SEASONED WOOD ONLY. Hardwoods are recommended (soft woods tend to burn very quickly).
• DO NOT burn treated wood, charcoal, coal, trash, card­board, driftwood, woods dipped in tar, Christmas tree greens, pitch, pine tar, creosote, chemi­cal chimney cleaners, flame colorants, polystyrene packag­ing, wood products with synthetic binders (i.e. plywood). Plywood, lumber and other misc. materi­als can produce abnormally high temperatures, sputtering and smoking fires and may contain hazardous chemicals to treat insects and fungus.
• Burning unapproved fuels can produce excessive tempera­tures, beyond the design capa­bilities of the fireplace and may produce excess sparks or may contain hazardous chemicals. Burning unapproved fuels can result in a chimney fire, a house fire, personal injury, death or loss of property.
To avoid the risk of damaging fireplace materials and increas­ing the risk of fire, do not use the fireplace to cook or warm food.
WARNING
CAUTION
NEVER use gasoline, gasoline­type lantern fuel, kerosene, charcoal lighter fluid, naphtha, engine oil or similar liquids to start or “freshen up” a fire in this fireplace. Keep any flammable liquids a safe distance from the fireplace at all times.
WARNING
The fireplace must be operated with the doors fully opened or fully closed. If the doors are left partly opened, gas and flame may be drawn out of the fireplace open­ing, creating risks of both fire and smoke.
WARNING
Never leave your fireplace unat­tended while it is burning.
CAUTION
Use care when selecting window treatments for windows located near the fireplace. Avoid using combustible flowing window treatments such as curtains on nearby windows that are of sufficient length to be blown in front of an open flame when the
window is opened. Keep any combustible furniture,
materials or decorative pillows at least 48" (1219 mm) from the front fireplace opening.
This fireplace has NOT been tested with an unvented gas log set. To reduce risk of fire or injury, do not install an unvented gas log set into this fireplace.
WARNING
WARNING
Be careful adding wood fuel to the fire or handling fireplace tools such as shovels, tongs or pokers.
WARNING
Never modify or alter your fire­place system in any way. To do so may create a potential fire hazard and void the warranty, listings and approvals of this system.
WARNING
The bottom refractory can be cracked by excessive abuse such as tossing heavy logs onto the grate or gouging with fireplace tools. Exercise caution when adding wood to your fireplace.
Neither the manufacturer nor the seller warrants “smoke free” operation nor are we responsible for inadequate system draft caused by mechanical systems, general construction conditions, inadequate chimney heights, adverse wind conditions and/or unusual environmental factors or conditions beyond our control.
Always ensure that the air inlet to the fireplace is free from debris and any other obstructions that can block the entrance of air.
An outside air kit must be installed on the ME43 fire­place.
WARNING
WARNING
WARNING
2
Page 3
CONGRATULATIONS!
In selecting this LENNOX™ wood-burning appliance you have chosen one of the fin­est fireplaces available. The ME43 wood fireplace is a clean burning fireplace that is designed to provide you dependable service as well as warmth and enjoyment for many years to come.
This fireplace must be installed with Security
Chimneys™ ASHT+, S-2100+ or AC (8" inside diameter) chimney System only. These sys­tems are intended for use in any application where a traditional masonry type fireplace would apply. The chimney system must always vent to the outside of the building.
Please carefully read and follow all of the instructions found in this manual. Please pay special attention to the safety instructions provided in this manual. This information will be useful to you now and in years to come, so keep the manual handy and refer to it as needed.
TABLE OF CONTENTS
SAFETY RULES FOR OPERATING YOUR FIREPLACE
Safety Rules .......................................Page 2
Parts Required ................................... Page 3
Optional Equipment ............................Page 3
Fireplace Maintenance
Creosote ............................................Page 4
Chimney maintenance ........................Page 4
Chimney fires .....................................Page 4
Door Frame Care ................................Page 4
Glass cleaning ....................................Page 4
Doors adjustment ..............................Page 4
Glass replacement ..............................Page 4
Removal of ashes ...............................Page 4
Fireplace Operation
Fuel .................................................... Page 5
First fires ............................................Page 5
Building a fire .....................................Page 5
Using the retractable
doors and firescreens ......................Page 5
How to use the outside air kit .............Page 5
Fireplace Installation
Pre-installation ...................................Page 5
Tools and building supplies ................Page 6
Precautions ........................................Page 6
Installation procedure ........................ Page 6
Locating the fireplace .........................Page 6
Adjacent walls ....................................Page 6
Enclosure ...........................................Page 6
Facing and mantel ..............................Page 7
Hearth extension ................................Page 8
Outside air installation .......................Page 8
UZY3 fan kit installation .................... Page 9
Framing Dimensions ..........................Page 10
Central forced air kit ........................... Page 11
Chase Enclosure ................................Page 11
Chimney System ...............................Page 12
Installing the Chimney System ........... Page 13
Offset Chimney Installation ................ Page 16
Chimney Component Chart ................ Page 17
Angled Wall Radiation Shield ............. Page 18
Universal Roof Support Installation ...Page 19
Multiple Terminations......................... Page 19
Parts and Components .......................Page 20
Replacement Parts .............................Page 22
Specifications .....................................Page 22
Clearances .........................................Page 22
Product Reference Information ..........Page 24
This appliance is designed for use with wood or certified pro­cessed solid fuel fire logs. Do not poke or stir the logs while they are burning. Use only fire logs that have been evaluated for the application in fireplace and refer to fire log warnings and caution markings on packaging prior to use.
Use only Lennox Fireplace glass doors,
specifically designed for ME43 fireplace. (See Page 22 for part numbers).
Do not operate the fireplace with both
firescreens and doors closed at the same time. Use the firescreen when doors are fully opened.
Always keep the fire screen or the doors
closed and the damper opened when using the fireplace. Keep the damper closed when the fireplace is not in use.
The ME43 fireplace is sold with a steel log
grate. If you have to replace it, we recom­mend for optimum efficiency, to replace it with an identical or similar Lennox model grate.
A fireplace insert heating unit may be installed
in the fireplace only if this unit has been certified with the ME43 fireplace.
CAUTION
This fireplace has been tested for installa-
tion in Canada to CAN/ULC S610-M87 and ANSI/UL 127-1996 under report number 192-5166. For installations in Canada, the
chimney clearance to combustibles must be 2 inches and the Cold Climate Kit must be installed.
The minimum installed height of the
completed fireplace system is 15' 0". The maximum height is 60' 0".
PARTS REQUIRED
Fireplace Model ME43BK SP
8" diameter chimney - Model Secure Temp™
(ASHT 1"), Secure Temp (S-2100+) or AC manu­factured by Security Chimneys International only, including:
- Chimney lengths
- Elbows (where necessary)
- Associated components as per these Installation Instructions
Door (included)
Outside Air Kit (included)
OPTIONAL EQUIPMENT
Additional Equipment (optional)
- Trim Kit and Door Capping available in Nickel and Gold
- UZY5 blower
- VRUW Blower motor speed control
- Forced Air Heating Kit
3
Page 4
FIREPLACE MAINTENANCE
Fastening
Screws
Interior Frame
Frame Screws
CREOSOTE
When wood is burned slowly, it produces tar and other organic vapors which combine with expelled moisture to form a black deposit called creosote. The creosote vapors condense in the relatively cool chimney flue of a slow burning fire. As a result, creosote residue accumulates on the flue lining. When ignited, this creosote makes an extremely hot fire. If the creosote accumulation is large, a creosote fire in the chimney can damage the chimney and over­heat the surrounding wood framing. Creosote formation in a chimney can be minimized by making small hot fires rather than slow burning, smouldering fires.
CHIMNEY MAINTENANCE
Regular chimney inspection and maintenance combined with proper operation will help pre­vent chimney fires. Keep your chimney clean. Do not allow more than a 1/16" (1.6mm) build-up of creosote in your chimney. The amount of creosote will depend on variables such as fre­quency of use and type of fire. We recommend that you follow the instructions below:
1. Initially, inspect the chimney system weekly. By doing this, you will learn how often it will be necessary to clean your chimney.
2. Have your chimney cleaned by a qualified chimney sweep. Chimney maintenance should only be conducted by a qualified technical or chimney sweep company.
3. Do not expect chemical cleaners to keep your chimney clean.
The raincap can be removed for inspection and/or cleaning of the chimney. Unscrew the braces which attach the raincap to the chimney. Using gloves, firmly grip the upper portion of the rain cap. Turn the cap and lift it off the chimney.
6. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to ensure that sparks and hot embers coming out of the chimney are not igniting the roof.
7. Do not use the fireplace again until your chimney and fireplace have been inspected by a qualified chimney sweep or a fire department inspector.
Door Frame Care
Use a glass cleaner and a soft cloth to polish the frame. Do not use abrasives such as steel wool or steel pads for they may scratch the door frame finish.
Glass Cleaning
The ME43 fireplace is designed to keep the glass clean under normal operating condi­tions. To clean the glass there are a number of specially designed cleaners. Your authorized LHP Dealer can recommend a suitable cleaner. Regular household glass cleaners will not clean creosote. Do not use abrasives such as steel pads, steel wool or oven cleaner as they will scratch the glass.
Doors Adjustment
Glass doors may lose their adjustment during transportation or installation of the fireplace. A wrong adjustment may cause a loss in combustion’s efficiency and control. The glass doors must be parallel, at the same height and must almost touch each other when closed. Maximum spacing between the doors is one sixteenth of an inch (1/16’’).
The glass doors can be adjusted by loosening the three (3) screws of the hinges’ supports (see fastening screws in Figure 1). If a minor angular adjustment is needed, you may loosen only two (2) of the three (3) screws using the other as a pivot point.
Glass Replacement
The glass used for the ME43 fireplace doors is a high temperature ceramic glass. If the glass breaks, it must be replaced with a ceramic glass such as Neoceram. Tempered or ordinary glass will not withstand the high temperatures of the ELITE ME43 fireplace. Replacement glass should be purchased from your local LHP dealer. Do not operate the unit with cracked or broken glass. To remove the glass panel, unscrew the frame screws, remove the interior frame and the glass panel.
Removal Of Ashes
Remove ashes only when the fire is out and the ashes are cold. Lift the front of the log grate until it rests against the rear refractory; then remove the ashes. Ashes should be placed in a metal container with a tight-fitting lid. The closed container of ashes should be placed on a non-combustible floor or on the ground, well away from all combustible materials, pending final disposal. If the ashes are disposed of by burial in soil or otherwise locally dispersed, they should be retained in the closed container until all cinders have thoroughly cooled. Do not leave the ashes in the house as they give off carbon monoxide and other toxic gases.
4
CHIMNEY FIRES
If you are having a chimney fire, follow these steps:
1. Close the glass doors and the air inlet.
2. Close the chimney outside air register.
3. Alert your family of the possible danger.
4. If you require assistance, alert your fire department.
5. If possible, use a dry chemical fire extin­guisher, baking soda or sand to control the fire. Do not use water as it may cause dangerous steam explosions.
Figure 1
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 5
OPERATING THE FIREPLACE
PUSH TO OPEN
PUSH TO OPEN
Fuel
The ME43 fireplace is designed to work best when fueled with seasoned cordwood. Hard­woods are preferred to softwoods since the energy content of wood is relative to its density. Hardwoods will result in a longer burning fire and less frequent refueling. A moisture con­tent of 15% to 20% (seasoned) is preferred. Excessively wet wood will be difficult to burn and will result in lower efficiency and increased creosoting.
Do not burn scrap or garbage, treated wood or wood such as driftwood from the ocean which has been exposed to salt or other chemicals. Salt or chemicals can corrode the firebox and chimney. Do not abuse the unit by burning large amounts of paper, cardboard, Christmas tree branches or building construction materi­als such as pressed wood, plywood or lumber. Intense firing with these may overheat the fireplace, causing damage to the unit, a fire, or even possibly igniting a chimney fire, if the chimney is creosoted.
First Fires
The first 5 or 6 fires should be small fires of short duration (about 30-60 minutes). The first fire should be especially short. This will help cure the refractory bricks. The first fires may produce slight smoking and some odor due to drying of the paint and steel and any dust accumulated on the fireplace will be burn off at this time. For this reason the room should be well ventilated during the first few fires.
HOW TO USE THE RETRACTABLE DOORS AND FIRESCREENS
The Lennox ME43 fireplace features retractable doors and firescreens in order to allow a wider view of the fire and save space when the doors are opened. To retract the doors, simply open them at 90° and push them into the opening on the side of the firebox. The same procedure applies for the retractable firescreens. (see
Figure 2
Note : Do not operate the fireplace with both fire­screen and doors closed at the same time.
).
Figure 2
HOW TO USE THE OUTSIDE AIR REGISTER (FIREPLACE)
The outside air register is located on the upper part of the top louver. The outside air register supplies oxygen to the fire and allows control of the fire when the doors are closed. The fresh air must come from outside the house (the air intake must not draw air from inside the house). This will minimize negative pressure in the house. The more you slide the register to the left, the more fresh air into the firebox and the more accelerated combustion you will get (see Figure 3). When starting a fire, the register should always be fully opened.
FIREPLACE INSTALLATION
Preinstallation
Please Read Before Installing:
1. Before beginning the installation of your fireplace, read these safety tips and instal­lation instructions carefully to be sure you understand them completely. Failure to follow them could cause a fireplace malfunc­tion resulting in serious bodily injury and/or property damage.
2. The ME43 fireplace has been tested and listed to UL and ULC standards by Warnock Hersey International Inc. These instructions were written to give you an outline for a fast and safe installation and trouble-free operation.
Building A Fire
To start a fire, place several crumpled up balls of newspaper in the firebox. Place small dry pieces of kindling on top of the paper, crisscrossing the kindling so that there is airspaces in between. Place the larger pieces of kindling on top of the pile. Keep the fuel far back enough so that air can get underneath. Open the air control fully and light the newspaper. Once the kindling fire is well established, cordwood can be added.
The unit will burn best with a minimum of two pieces of cordwood spaced 1" to 2" apart and al­lowing air to get under the fuel. Crisscrossing or arranging the fuel so that air can get underneath, will help the fire to get started easily.
Figure 3
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
5
Page 6
OPENING
WALL
FIREPLACE
STANDOFFS
18"
(460mm)
45°
Failure to use LHP parts or conduct variations
in techniques and construction materials described in this installation manual may create a serious fire hazard and may void the warranty and the WHI listing.
3. Always check your local building codes.
The installation must comply with their regulations. Before beginning the instal­lation, consult the local authorities and make sure your building permit complies with their requirements.
4. This fireplace must be installed with Security Chimneys™ chimney system models ASHT+,
S-2100+ or AC, of 8" inside diameter. These systems are intended for use in any applica­tion where a traditional masonry type fireplace would apply. The chimney system must always vent to the outside of the building.
5. To maintain top efficiency and to prevent build-up of soot and creosote, inspect and clean the chimney periodically during the heating season.
6. To prevent possible hazards due to poor combustion and to avoid affecting other fuel burning appliances (furnace, wood stove, etc.), ensure that the outside air kit is properly installed.
7. This fireplace is designed to allow the instal­lation of a gas burner. In such a case, the installation must conform with the National Gas Code ANSI Z223.1 and Z21.60.
WARNING
When using a gas burner, it is mandatory to keep the chimney outside air register opened.
8. This fireplace has provision for the installa­tion of a gas pipe and is intended only for connection to a decorative gas appliance incorporating an automatic shutoff device and complying with ANSI Z21.60-M96/CGA
2.26-M96, Standard for Decorative Gas Ap­pliances for Installation in Solid-Fuel Burning Fireplaces (reference Clause 4.1.3 T).
9. The ME43 fireplaces are sold with factory installed doors. The outside combustion air kit is mandatory and is included with the fireplace. Optional blowers and decorative trims are available.
Tools And Building Supplies Normally Required
Tools: Phillips screwdriver
Slot style screwdriver Hammer Saw and/or Sabersaw Level Measuring tape Plumb line Electric drill and bits Pliers Square
If gas pipe is used: Pipe wrench
Pipe cutter Pipe threader Pipe joint compound Pipe key valve
Building supplies: 2" x 3" or heavier lumber
Drywall panel or equivalent Silicone caulking (non-combustible) Overlay material for fireplace façade Hearth extension (non-combustible)
PRECAUTIONS!
The most important areas of concern dealing with the fireplace installation are clearances to combustible materials, secure assembly of components parts, the height of the chimney system, the proper use of accessory equip­ment and the techniques used in using finish­ing materials applied to fireplace surrounds, hearth extensions and wall coverings. Each of these topics will be covered in greater detail throughout this manual. Please give special
attention to these instructions as you progress with your installation.
Fireplace Installation Procedure
1. Move the fireplace into the desired position (follow the recommendations below for enclosure).
2. Install the outside air assembly (or assem­blies) - refer to Page 8.
3. Install the enclosure surrounding the fire­place (refer to the sections “Enclosure” below and “ Facing and Mantel” on Page 7).
4. Install the hearth extension (see Page 8). Make sure the gap between the fireplace and the hearth extension is sealed.
LOCATING THE LENNOX FIREPLACE
Do not place the fireplace on carpeting, vinyl or other soft surface floor coverings. It may, however, be directly placed on flat wood, plywood, particle board or other hard surface materials.
ADJACENT WALL
A wall perpendicular to and in front of the fire­place front facing must be at least 18" (460mm) from the fireplace opening. A wall at 45º to the front facing and starting at the fireplace’s outer edge is permitted. Projections within this area are permitted. See Figure 4.
Figure 4
ENCLOSURE
WARNING
Do not place loose insulation or any other material in the space around the fireplace or the chimney. Insulation placed on or around the fireplace or chim­ney may cause adjacent wood to overheat and catch on fire.
1. The fireplace must be installed against a finished wall (like drywall finish). It must not be installed against a vapor barrier or exposed insulation (see Figure 5).
2. Combustible materials like wood, plywood, particle board or drywall can be in direct contact with the fireplace standoffs. Two
inch (50mm) clearance to combustibles must be kept around the chimney.
6
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 7
WARNING
CEILING/FLOOR SEPARATION
MUST HAVE THE SAME INSULATION
LOCAL CODE REGULATION FOR CEILING MUST BE APPLIED TO THE CEILING/FLOOR SEPARATION, I.E. FIRESTOP, ETC.
MUST HAVE THE SAME FIRE RATING AS ADJACENT CEILING.
AS ADJACENT CEILING.
ROOF SUPPORT
ATTIC
FIRESTOP
FLASHING
NON COMBUSTIBLE CHASE TOP
FIREPLACE
2"
7 ft. Min.
FINISHED WALL
DRYWALL PANEL OR EQUIVALENT
SPACER
2" x 3" MIN.
FIREPLACE
18"
48"
Min.
52"
1"
8"
The top of the fireplace is not zero clearance. Do not place any insulating material in the space above the fireplace for a height of 7 feet from the base of the fireplace.
3. Do not block the fireplace’s hot air vents or air inlets as this will cause the fireplace to overheat.
Fireplace Facing
The fireplace should be framed using 2" x 3" (50mm x 75mm) or heavier lumber.
Figure 10
framing layout.
Combustible materials must be installed flush with the fireplace facing. They may not project out in front of the fireplace. Non­combustible materials such as brick, stone or ceramic tile, may project in front of and/or on the fireplace facing.
on Page 10 shows the general
Figure 6
WARNING
The header should rest on top of the metal spacers. Do not alter the spacers or notch the header to fit around them. Do not block the air inlet or outlet as this will cause the fireplace to overheat.
Figure 5
NOTE: Chase wall and floor must be insulated in the same manner than the rest of the building below the attic.
Mantel
A wood mantel, if installed, must be at least 48" (1.2 m) above the base of the fireplace (see Figure 7). There is no restriction regarding the length or the width of the mantel.
Figure 7
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
7
Page 8
OUTSIDE
INTAKE
ALUMINIUM TAPE
PLASTIC COVER
FLEXIBLE PIPE
SCREW
OPENING
FACING DOWN
WALL
OUTSIDE AIR CONNECTION TO THE FIREPLACE
FIREPLACE
CONNECTION
ALUMINIUM
TAPE
INSULATION
FLEXIBLE
PIPE
FIREPLACE
PLASTIC COVER
LOOP IS MANDATORY
7' MAX.
OUTSIDE AIR CONNECTION
Hearth Extension Requirements
(refer to Figure 7) A non-combustible hearth extension must
be built in front of the fireplace and extend out on both sides. Hearth extensions must be constructed according to the following guidelines:
1. A layer of sheet metal 0.018" (0.45mm) thick or 3/8" (9mm) thick insulating board or any other material (tiles, marble, granite) with equivalent heat resistance may be used. Check with the local building authorities before installing to determine what other materials are acceptable in your area.
2. The hearth extension should be secured to the floor. The gap between the fireplace and the hearth extension must be sealed with non-combustible caulking or cement.
3. On a raised base or raised hearth, a “Z” shape piece of metal must be fabricated to join the bottom of the fireplace to the floor.
Outside Air Assembly
The outside air assembly is mandatory for the fireplace.
During operation, the fireplace requires air for combustion and draws air out of the house. It may starve other fuel burning appliances such as gas or oil furnaces. As well, exhaust fans and fan driven appliances may compete for air, causing a negative pressure in the home, resulting in smoke entering the home from the fireplace. This situation is aggravated in modern airtight houses.
To overcome this potential problem, the
installation of an outside air assembly is required to provide outside combustion air to
the fireplace.
Outside Air Installation
The outside air assembly must be installed according to the following guidelines:
1. The maximum length of 4" I.D. (100 mm)
insulated flexible duct is 20 feet (6.1 m). If a longer duct is required, use a 6" I.D. (150mm) insulated flexible duct. The maximum length is 40 feet (12 m). Refer to Figures 8B and
for connections.
8C
2. The duct and register may be installed above
or below floor level.
3. The outside air register must not be installed
more than 7 feet (2.1 m) above the base of the fireplace.
(Detail A)
4. The outside air assembly must draw air from
outside the house. It must not draw air from the attic, the basement or a garage.
5. Locate the outside register where it will be
well away from automobile exhaust fumes or other vents.
6. The outside air register should be installed
where it is not likely to be blocked by snow or exposed to extreme wind.
7. It is recommended to install the outside air
register at floor level. However, if you must raise the air register above the fireplace level, you will have to make a loop to the floor with the flexible pipe to prevent from causing a draft in the outside air register (see Figure 8 Detail A).
8
(Detail B)
Figure 8
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
(Detail C)
Page 9
INSTALLATION OF THE FAN KIT MODEL
ELECTRICAL CONNECTION
WITH
GROUND CONNECTION
THERMODISC, AUTOMATIC
THERMAL FAN ACTIVATOR
CONNECTOR FOR
OPTIONAL RHEOSTAT
FAN WITH
MAGNET
FAN WITH
MAGNET
UZY3
Note: This fan kit can easily be installed when
the fireplace has a pre-installed junction box. You just have to plug them in.
Rating: 120 Volts, 60Hz, .63A.
The fans have magnetic blower mounts. The junction box (factory installed on approved fireplaces for the use of this fan kit) must be connected to 110 VAC service before perma­nently enclosing the fireplace. The access hole for connecting the 110 VAC is located on the lower right exterior side of the fireplace.
Installation instructions:
1. Open the bottom louver of the fireplace.
2. Place each fan kit into the fireplace side
opening 1" from the back of the fire­place.
3. Install the automatic fan activator on the
side of the firebox (the fan activator has a magnetic mount).
4. Plug the fan kit into the junction box.
5. Ground both fans to the back panel using
the green screws (see Figure 9).
NOTE: The fireplace must be electrically connected and grounded in accordance with local codes or in the absence of local codes, with the current CSA C22.1 Canadian Electrical Code. For U.S.A. installations, follow local codes and the National Electrical Code ANSI/NFPA No 70.
CAUTION: SHOULD THIS FAN REQUIRE SERVICING, THE POWER SUPPLY MUST BE DISCON­NECTED.
These fans require periodic maintenance. Check the area in front of the fans and wipe or vacuum at least once a month during the burn season.
Figure 9
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
9
Page 10
42-1/2”
(1080 mm)
17-1/8”
(435 mm)
28-5/16”
(719 mm)
42”
(1067 mm)
43”
(1092 mm)
43”
(1092 mm)
27-1/2”
(699 mm)
10-5/8”
(270 mm)
36”
(914 mm)
33”
(838mm)
21-1/4
(540 mm)
Knock-Out
for Ducting
Knock-Out
for Ducting
Outside Air
Intake
OUTSIDE CHASE
G
H
C
L
*
Back Wall of Chase/Enclosure Including Finising Materials if any
Rough Framing Face (Unfinished Shown)
* Zero Clearance From Back Spacer to Wall
Corner Installation
7' MIN.
2" X 3"
MIN.
K
Combustion Air Kit
F
21-1/2”
(546mm)
D
E
23-11/32”
(593mm)
J
B
Rough Framing Face (unfinished shown)
Notes
Due to Lennox' ongoing commitment to quality, all specifications, ratings and dimensions are subject to change without notice.
All framing dimensions calculated for 1/2" dry wall at the fireplace face. If sheathing the chase or finishing with other thickness materials, calculations will need to be made.
* The fireplace must not be in contact with any insulation or loose filling material. Cover the insulation with Drywall panels around the fireplace.
G
A
Combustible materials can N OT be used in the space directly above the fireplace. Do not fill the space above the fireplace with any material (Except the wood framing)
FRAMING DIMENSIONS
Fireplace Opening Width
A 42-1/2" 1080 mm
B 43-1/4" 1099 mm
C 33" 838 mm
D 16-1/2" 419 mm
E 85" 2159 mm
F 42-1/2" 1080 mm
G 27" 686 mm
H 26" 660 mm
J 60-1/8" 1527 mm
K 8" 203 mm
L 1" 25 mm
10
Figure 10 - Framing Dimensions
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 11
INSULATED
FLEX PIPE
CENTRAL FORCED AIR KIT
INSULATION
FAN
ALUMINUM TAPE
COLLAR
FLEX 5” O
5” O
INSULATED FLEX
FAN
FURNACE
AIR FLOW
NO-RETURN VALVE
The knock-outs provided on the sides of the ME43 fireplace allow the connection of insulated flexible pipe which enables you to heat adjacent rooms up to 50 feet from the fireplace.
The ducting system must be installed as de­scribed below :
1. Fix the adaptor at the side of the fireplace by
twist-locking the adaptor to the fireplace. You can use more than one outlet on the fireplace (Figure 11).
2. Attach the 5" flexible pipe, using the col
lars provided. Important: Make sure that
the plastic wrapping around the flexible pipe will not be in contact with the fire­place.
3. Route the flexible pipe to the chosen loca
tion. The ducting system can be installed either in an upper room or in a lower room.
4. Attach the flexible pipe to the fan, using
the collars (Figure 12).
5. Fix the decorative grill fan adaptor to the
fan.
6. Attach a standard 3" x 10" grill to the
adaptor.
7. Install the blower thermostat
of the house to be heated by the hot air duct. Do not install the blower thermostat in the room where the fireplace is located. A cooling thermostat can be installed in the same room as the unit. This thermostat will turn on the blower when the room where the fireplace is located becomes too hot.
This option requires electricity. Make sure that the connections to the fan have been made according to the local codes and comply with their requirements. It is possible to connect a flexible pipe to a central heating system. Make sure the pipe will be connected to the warm air supply duct, not to the return air duct (Figure 13). Contact your local furnace installer for installation guidelines.
in that part
-
-
Figure 11
Figure 12
Chase Enclosure
A chase is a vertical box-like structure construct­ed to surround the fireplace and chimney. Refer to Figure 14 for a typical chase configuration. As with all chimney installations, avoid overhead obstructions such as trees, power lines, etc. A chase should be constructed and insulated just like any outside wall. In a cold climate, we recommend the base of the chase should also be insulated between the solid continuous floor beneath the fireplace and the chase bottom. Chase insulation in a cold climate installation is not required for safety.
Figure 13
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
11
Page 12
Insulate Joists Same As Ceiling
Draft Stops
Firestop
CTDT Termination
Note: Non­Combustible Chase Flashing Must Be Used To Cover Chase Opening
Optional Insulation In Outside Walls Of Chase
Solid Continuous Surface
Outside Base
Insulation (Thermal Barrier)
8'
Level
2' min.
(610mm)
10' (3000mm)
3' min.
(915mm)
12
Figure 14
CHIMNEY SYSTEM
The ME43 fireplace is listed only with Security Chimneys™ International Ltd. chimney sys-
tems, models ASHT+ 8", S-2100+ 8", or AC 8". Do not connect the fireplace to a masonry
chimney, chimney liner, or other brand of factory-built chimney.
In areas with continuous temperatures below 0º F (-18º C), the use of an exterior chimney increases the likelihood of operating problems such as low draft, high rate of creosoting and poor start up characteristics. Exterior chim­neys are also prone to down-drafting and flow reversal. Installations located in a basement, in combination with outside chimneys, are especially prone to flow reversal. In cold areas, air cooled chimneys should not be used in an exterior installation.
AC chimney should not be used in cold areas, where temperatures are likely to fall below 32° F (0° C), or altitudes above 4000 feet.
A chimney venting a fireplace shall not vent any other appliance.
The minimum system heights are indicated in Table 1.
In altitude, add 18" (450mm) to the chimney for every 2000 feet (600 m) above sea level.
All chimney installations must include at least one support. The maximum length of chimney that can be supported by the fireplace is 12 feet (3.6 m) for S-2100+, 18 feet (5.4 m) for ASHT+ and 26 feet (8 m) for AC chimney.
The chimney must extend at least 3 feet (915mm) above its point of contact with the roof and at least 2 feet (610mm) higher than any wall, roof or building within 10 feet (3 m) of it (see Figure 15).
If the chimney extends higher than 5 feet (1500mm) above its point of contact with the roof, it must be secured using a roof brace or guide wires.
A rain cap must be installed on top of the chim­ney. Failure to install a rain cap may cause the fireplace to corrode and operate inefficiently.
Cut and frame square holes in all floors and the roof to provide a 2" (50mm) clearance between the chimney and any combustible materials. Do not fill this 2" (50mm) space with any material.
Portions of the chimney which may extend through accessible spaces must be enclosed to avoid contact with combustible materials or
damage the chimney.
Minimum System Heights
Fireplace Model ME43BK SP
Chimney Model ASHT+ / S-2100+ / AC
Vertical Installation 15 feet (4.57 m)
One Offset (2 elbows) 18 feet (5.49 m)
Two Offsets (4 elbows) 20 feet (6.10 m)
Table 1
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
WARNING
If insulation is used, the fireplace must not be placed directly against it. Insulation or vapor barriers, if used, must first be covered with drywall panels, plywood, particle board or other material to assure insulation and vapor barriers remain in place.
WARNING
Do not pack or fill required air spaces with insulation or other material. No material is allowed in these areas.
*Construction Materials:
• framing materials • paneling
• particle board • flooring
• dry wall • etc.
• plywood
Note: 2" clearance to combustibles around chimney components required.
Note: Do not insulate the chase cavity with blown or fill type insulation materials.
Note: Local codes may not require firestopping at the ceiling levels for outside chase installa­tions. However, it is recommended for safety and the reduction of heat loss.
Chimney Height
The total height of your completed fireplace system from the surface the fireplace rests on to the chimney top must not exceed 60' and must also meet minimum height requirements. Refer to the minimum system height chart.
Figure 15
Page 13
CHIMNEY INSTALLATION
ATTIC RADIANT FIRESTOP
FIRESTOP
ASHT+ & S-2100+
AC RSA
AC
AC RS
INSTRUCTIONS
STRAIGHT INSTALLATION
Cut and frame the holes in the ceiling, floor and roof where the chimney will pass (see Figure
16). Use a plumb-bob to line up the center of
the holes. The hole sizes are indicated in Table
2 for the floor and ceiling holes and in Table 3 on Page 15 for the roof holes.
From below, install a firestop in each ceiling/ floor separation through which the chimney will pass. At the attic level, install an attic radiation shield from above (see Figures 17A & 17B).
For ASHT+ and S-2100+ chimneys, place the first chimney length on the fireplace. To lock it into place, turn 1/4 of a turn clockwise. With the AC chimney you must use a starting section before installing the first chimney length (see Figure 18). Continue installing chimney lengths until you reach the desired height.
Figure 16
CHIMNEY MODEL SQUARE HOLE
SIZE OPENING
ASHT+ 14-3/8” (365 mm)
S-2100+ / HT6000+ 16” (406 mm)
AC 15" (380 mm)
Note: See Table 3 for Sloped Roof Framing
Table 2 - Flat Roof Framing
Every time the chimney passes through a roof or a wall, install the appropriate firestop. When you reach the desired height, install the roof support (see instructions included with the support).
Then, put the roof flashing in place and seal the joint between the roof and the flashing with roofing pitch. For sloping roofs, place the flashing under the upper shingles and on top of the lower shingles. Nail the flashing to the roof, using roofing nails (Figures 19A & 19B).
Place the storm collar over the flashing and tighten it with the bolt supplied. Finally, seal the joint between the storm collar and the chimney, using silicone caulking.
Install the chimney cap. Once the chimney cap is in place, the roof flashing can be washed with a solvent or vinegar and then painted with rust-proof paint.
Figure 17A
Figure 17B
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
13
Page 14
AC Model (Air Cooled Insulated, Galvalume Chimney)
Rain Cap
Flashing Collar
Flashing
Support
Attic Radiation Shield
Radiation Shield
Cooling Air Kit For Air Cooled Chimney ACZI
AC Air Cooled Chimney Start­ing Piece
14
Figure 18
Outside Combustion Air Kit (UZI)
Note: The Outside Air Kit is Mandatory
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 15
FLASHING
COLLAR
CHIMNEY
SPACER
(BUILT INTO
FLASHING)
AC CHIMNEY
Figure 19A
SLOPE ASHT+ S-2100+ AC
8" 8" 8"
* 14-3/8" (365mm) 16" (406mm) 15" (380mm)
2/12 14-5/8" (371mm) 16-1/4" (413mm) 15-3/8" (390mm)
4/12 15-1/4" (387mm) 16-7/8" (429mm) 16-1/8" (410mm)
6/12 16-1/8" (410mm) 17-7/8" (454mm) 16-7/8" (430mm)
8/12 17-3/8" (441mm) 19-1/4" (489mm) 18-1/4" (465mm)
10/12 18-3/4" (476mm) 20-7/8" (530mm) 19-5/8" (500mm)
12/12 20-3/8" (518mm) 22-5/8" (575mm) 21-3/8" (545mm)
*cross slope hole size
Table 3
Figure 19B
ROOF DOWN SLOPE HOLE SIZE
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
15
Page 16
OFFSET CHIMNEY INSTALLATION
ASHT+ and S2100+ Chimneys
AC chimney
The minimum chimney height (including the fireplace) when using elbows is:
Fireplace Model
Chimney Model 8" ASHT+/S-2100+/AC
Vertical Installation
Two (2) Elbows 18 feet (5.49 m)
Four (4) Elbows 20 feet (6.10 m)
Table 4
ME43BK SP
15 feet (4.57 m)
After reaching the location requiring the elbow, proceed as follows:
1. Install the first elbow. Turn it in the required direction. Fasten it to the chimney with the three (3) 1/2" (12mm) metal screws provided.
2. Install the necessary lengths to achieve the required offset. Lock the chimney lengths together: it is recommended to use three (3) 1/2" (12mm) screws. If the offset length is made of two (2) chimney lengths use an offset support halfway up the offset. If penetrating a wall, install a wall radiation shield (see Figure 22).
3. Use another elbow to turn the chimney vertically. Secure the elbow, using three (3) 1/2" (12mm) screws.
4. Use a plumb-bob to line up the center of the hole. Cut a hole for the chim­ney in the ceiling. Frame this hole as described previously (see Page 12).
5. From below, install a radiation shield (Figure 17A).
6. A support (ST+ or SO+) must be used on the first 15’ section (5 m).
7. Continue with the regular installa­tion.
1. Install the first elbow. Turn it in the required direction. To lock it in place, turn 1/8 of a turn. Fasten the straps at­tached to the elbow to the surrounding framing using nails or drywall screws (Figure 20).
2. Install the necessary chimney lengths to achieve the required offset. Lock the chimney lengths together. If penetrat­ing a wall, use a wall radiation shield (Figure 22).
3. Use another elbow to turn the chimney vertically. Lock it to the chimney. Fasten the straps attached to the elbow to the surrounding framing using nails or drywall screws.
4. Use a plumb-bob to line up the center of the hole. Cut a hole for the chim­ney in the ceiling. Frame this hole as described previously.
5. From below, install a radiation shield (see Figure 17B).
6. Continue with the regular installa­tion.
Note: An AC8SB starting section must be used before installing an elbow.
16
Page 17
8"
AC
S-2100+
8"
8"
ASHT+
12" & 48"
(1845 mm)
72-5/8"
(429 mm)
16-7/8"
32-5/8"
(829 mm)
66"
(1676 mm)
33"
(838 mm)
65-1/4"
(1657 mm)
24" & 36"
(1670 mm)
65-3/4"
(413 mm)
16-1/4"
(1391 mm)
54-3/4"
(1187 mm)
46-3/4"
31-1/2"
(800 mm)
66-3/4"
(1695 mm)
24" & 36"
(1695 mm)
66-3/4"
(413 mm)
16-1/4"
---
----
----
----
----
----
----
----
----
(527 mm)
20-3/4"
(190 mm)
7-1/2"
3"
(156 mm)
16-1/2"
(419 mm)
8"
10-1/2"
(267 mm)
18-1/2"
(470 mm)
(578 mm)
22-3/4"
(146 mm)
5-3/4"
3"
17-1/2"
8"
(445 mm)
(76 mm)
15
4"
(102 mm)
21-1/2"
(546 mm)
12" 18"
(692mm)
27-1/4"
(146 mm)
5-3/4"
24"
(838 mm)
33"
(184 mm)
7-1/4"
36"
(1130 mm)
44-1/2"
(260 mm)
10-1/4" 19-1/4"
(489 mm)
78-1/4"
(1988 mm)
36" & 36"
14-3/4"
(375 mm)
61"
(1550 mm)
18" & 36"
13-1/4"
(337 mm)
55-1/4"
(1403 mm)
12" & 36"8" & 36"
(1302 mm)
51-1/4"
(305 mm)
12"
23-1/2"
(597 mm)
52-3/4"
(1340mm) (1429 mm)
56-1/4"
(648 mm)
25-1/2"
(1562 mm)
61-1/2"
(724 mm)
28-1/2"
(1956 mm)
77"
(953 mm)
37-1/2"19-3/4"
(502 mm)
47"
(1194 mm)
13-3/4"
(349 mm)
36-1/2"
(927 mm)
10-3/4"
(273 mm)
31-1/4"
(794 mm)(660 mm)
26"
(197 mm)
7-3/4"
30
45
13-1/2"
(343 mm)
21-1/4"
(540 mm) (648 mm)
25-1/2"
(451 mm)
17-3/4"
(756 mm)
29-3/4"
(559 mm)
22"
(972 mm)
38-1/4"
(775 mm)
30-1/2" 55-1/4"
(1403 mm)
63"
(1600 mm)
42-1/2"
(1080 mm)
50-1/2"
(1283 mm)
38-1/4"
(972 mm)
46-1/4"
(1175 mm)(1099 mm)
43-1/4"
(1260 mm)
35-1/2"
15
4-1/4"
(108 mm)
20-1/4"
(514 mm)
12" 18"
(667 mm)
26-1/4"
(146 mm)
5-3/4"
24"
(813 mm)
32"
(184 mm)
7-1/4"
36"
(1105 mm)
43-1/2"
(260 mm)
10-1/4" 19-1/2"
(495 mm)
77-1/2"
(1967 mm)
36" & 36"
14-3/4"
(375 mm)
60"
(1524 mm)
18" & 36"
13-1/4"
(337 mm)
54-1/4"
(1378 mm)
12" & 36"8" & 36"
(1276 mm)
50-1/2"
(311 mm)
12-1/4"
25"
(635 mm)
51-1/4"
(1302 mm) (1391 mm)
54-3/4"
(686 mm)
27"
(1524 mm)
60"
(762 mm)
30"
(1918 mm)
75-1/2"
(991 mm)
39"21-1/2"
(546 mm)
45"
(1143 mm)
15-1/2"
(394 mm)
34-3/4"
(883 mm)
12-1/2"
(318 mm)
29-1/2"
(749 mm)(641 mm)
24-1/4"
(241 mm)
9-1/2"
30
30
9-3/8"
(238 mm)
25-3/4"
(654 mm) (787 mm)
31"
(314 mm)
12-3/8"
(1181 mm)
46-1/2"
(543 mm)
21-3/8"
(1448 mm)
57"
(695 mm)
27-3/8" 50-5/8"
(1286 mm)
97-1/4"
(2470 mm)
44-5/8"
(1134 mm)
86-7/8"
(2207 mm)
35-5/8"
(905 mm)
71-1/4"
(1810 mm)----
----
----
----
----
----
----
----
---
18" & 48"
(1992 mm)
78-7/16"
(468 mm)
18-7/16"
36" & 48"
(2432 mm)
95-3/4"
(584 mm)
23"
48" & 48"
(2727 mm)
107-3/8"
(665 mm)
26-3/16"14-1/8"
(359 mm)
62-1/2"
(1588 mm)
48"
11"
(280 mm)
50-7/8"
(1292 mm)
36"
6-1/8"
(156 mm)
33-1/2"
(851 mm)
18"12"
(703 mm)
27-11/16"
(122 mm)
4-13/16"
15
ONE LENGTH BETWEEN ELBOWS TWO LENGTHS BETWEEN ELBOWS
TWO LENGTHS BETWEEN ELBOWSONE LENGTH BETWEEN ELBOWS
&
LENGHT
DEVIATION
LENGTH
DEVIATION
LENGTH
DEVIATION
LENGTH
DEVIATION
LENGTH
DEVIATION
&
LENGTH
DEVIATION
LENGTH
DEVIATION
LENGTH
DEVIATION
LENGTH
DEVIATION
&
DEVIATION
LENGTH
ELBOW
ELBOW
CHIMNEY
CHIMNEY
Note: With the AC chimney, a starting length of 6" high must be used on top of the fireplace before installing
TWO LENGTHS BETWEEN ELBOWSONE LENGTH BETWEEN ELBOWS
ELBOW
CHIMNEY
DEVIATION
TOTAL LENGTH
Table 5
17
Page 18
NOTE: IN COLD FREGIONS IT IS RECOMMEDNED TO ENCLOSE THE CHIMNEY IN AN INSULATED CHASE
RAIN CAP
ANGLED INSULATED WALL RADIATION SHIELD
ROOF SUPPORT
STORM COLLAR
FLASHING
OFFSET SUPPORT
INSULATED
WALL
FRAME 2” X 4”
Figure 20
ANGLE WALL RADIATION SHIELD (INSULATED)
DRYWALL
INSULATED WALL
CHIMNEY AC
BRACE
STRAPS
ACRS (RADIATION SHIELD)
STRAPS
SUPPORT
AIR COOLED
ANGLED WALL RADIATION SHIELD (RSM+, RSMI30, RSMI45)
When traversing a combustible wall with the chimney at a 30° or 45° angle, an angled firestop and/or wall radiation shield must be installed. Only one is required (Figure 22). Table 6 gives recommended hole size for installing a wall radiation shield.
Note: 45° angle installation for Canada only.
In cold climate locations, we recommend that you use the insulated wall radiation shield since it will maintain the home’s thermal barrier.
RSM+ and RSMI30, RSMI45
Chimney
Angle Hole Size
Model
ASHT+ 8" I.D.
Canada Only
S-2100+ 8" I.D.
Canada Only
AC 8" I.D.
30º
45º
30º
45º
30º
14-3/8" x 36-1/2”
(365mm x 927mm)
14-3/8" x 24-3/4”
(556mm x 629mm)
16" x 40”
(406mm x 1016mm)
16" x 27-1/4”
(406mm x 692mm)
15-1/4" x 38-1/4”
(365mm x 927mm)
Table 6
18
Figure 21
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Figure 22
Page 19
UNIVERSAL ROOF SUPPORT INSTALLATION
18" (460mm)
16"
(410mm)
16"
(410mm)
18" (460mm)
18" (460mm)
This support has three possible uses:
1. For ASHT+ and S-2100+ chimneys, it must be used on a roof to support the chimney.
2. It may be used on a floor, ceiling or roof above an offset to support the chimney above the
offset.
3. It may be used on a floor, ceiling or roof as a supplementary support when the chimney height
exceeds 15 feet (4.6 m.).
Table 7 gives maximum height of supported chimney.
NOTE: For the AC chimney, a support section (AC8SL) must be used every 40’ (12 m) instead of the ST.
For roof support installation, refer to the instructions provided with the support.
UNIVERSAL OFFSET SUPPORT INSTALLATION
This support is used to support the chimney above an offset. When the chimney offset is used to traverse a wall, this support may be used on the wall to support the chimney. The maximum heights are given in Table 7. For offset support installation, refer to the instructions provided with the support.
CHIMNEY CHASE AND MULTIPLE TERMINATIONS
For the purpose of this manual, a chimney chase is considered a part of the chimney system rather than part of a building. The termination must be placed a minimum of 18" (460mm) above the chase.
For installation where more than one chimney is located in the same chase or within the same general area, we suggest that their termina­tions be separated by at least 16" (410mm) horizontally and 18" (460mm) vertically. This separation is to prevent smoke migrating from one chimney to another (see Figure 23).
Chimney Model
Maximum Height Of Supported Chimney
offset support roof support
ASHT+ 8" I.D. 20 feet (6.10 m) 24 feet (7.32 m)
S-2100+ 8" I.D. 14 feet (4.30 m) 16 feet (4.87 m)
AC 8" I.D. 40 feet (12.19 m) 50 feet (15.20 m)
Table 7
Figure 23
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
19
Page 20
ME43 COMPONENTS LISTS
Installation Accessories
Description Cat./ Part No.
Outside Air Kit (Required - included with fireplace)
Outside Air Coupler to connect outside air UZI to fireplace, UZIAD
UZIDF
Outside Air Ducting - includes 4" insulated flex x 10' long, UZI
UZI
Fireplace Options
Trim Kit - Gold H3426
Trim Kit - Brushed Nickel H3395
Door Capping - Gold H3393
Door Capping - Brushed Nickel H3394
Blower UZY5
Blower motor speed control VRUW
Forced Air Heating Kit
Starter Kit: For wall or furnace installations. Includes
blower (BISZY), flex adaptor and two clamps (BISAF), blower variable speed control (VRUW), thermo disc (VTU), blower flex adaptor (BISAVF), and back draft damper (BISBD)
BISFWK-1
Flex 5 inches ID x 15 feet Long 5FLEX15
Flex 5 inches ID x 25 feet Long 5FLEX25
Starter Kit Separate Components
Blower flex adaptor, includes damper (BISBD) BISAVF
Blower - 2 50 CFM BISZY
Flex adaptor and two clamps for fireplace connection BISAF
Blower motor speed control VRUW
Thermo disc - turns motor on when fireplace hot and off when cool
VTU
Back draft damper - prevents air blowing from furnace into fireplace
BISBD
Options
Heating/Cooling thermostat - 110 volt HCTW
Fl
ex -
choose 15 feet or 25 feet depending on installation
Fireplace Model ME43 - Approved Venting Components
- 8” diameter chimney - Model ASHT+, S-2100+, HT6000+, HT6103+
or AC manufactured by Security Chimneys International only.
Notes:
(P
rojet NovaTemp ) HT6000+ is equivalent to S-2100+ (Projet NovaTemp ) HT6103+ is equivalent to ASHT+ This appliance is equiped with the ASHT Chimney Adaptor. When other chimney is used, a chimney adaptor for that chimney will be required. Chimney Adaptor (S-2100+ / HT6000+) for CANADA ONLY -
If you want to
install a S-2100+ / HT6000+ chimney, an adaptor is available (8UCA).
AC Chimney is Not recommended at elevations above 4000 feet or in cold climates where temperatures are likely to fall below 32°
F (0° C).
When using AC chimney, an AC8SB starter section
must be used
before installing an elbow.
W hen an offset is needed
immediately off the
top of the fireplace, a starter section
(AC8SB30)
is available.
TM
TM
1.
2.
3.
4.
5.
20
Page 21
ME43 COMPONENTS LISTS
AC Chimney
(Air Cooled - 8” I.D.,13” O.D.)
Description Cat./Part No.
AC Starter Adaptors
An AC Adaptor Is Needed To Convert Fireplace For Use With AC Chimney
Starter Section (adaptor), 8” AC, AC8SB H3801
Starter 30
Elbow, AC, AC8SB30 H3802
Outside Air Kit
Required for AC chimney installation
Chimney Outside Air kit (Flex, Insulation, Outside Register and coupling), ACZI
H1967
Lengths & Misc. Chimney Components
18” Length, Dia. x 12” Long, AC6L18 H3798
36” Length, Dia. x 36” Long, AC8L36 H3799
48” Length, Dia. x 48” Long, AC8L48 H3800
15
Elbow, Dia., AC8E15 H3795
30
Elbow, Dia., AC8E30 H3796
Rain Termination Cap, Dia., AC8CPR H3794
Spark Arrester Screen (universal spark arrester band), PE+ PE
Wall Band, BM H0484
Supports
Offset Support, SO H0480
Support Section, AC8SL H3804
Roof Support, ST H0482
Roof Brace, BS2 H0483
Roof Flashings
Flat roof flashing, ACF H0494
1/12 - 7/12 (5 - 30), AC, Adj. Roof Flashing, FA H0495
8/12 - 12/12 (3
0 - 45
), AC,Adj. Roof Flashing, FB H0496
Storm collar, ACFC H0500
Misc.
Telescopic attic radiation shield, ACRST H0498
Firestop, ACBF H0485
Radiation Shield, ACRS H0486
8”
8”
8”
8”
8”
8”
8”
Secure Te
mp
High Temp. Insulated Stainless Steel Chimney
8”
Diameter, Listed to CAN/UCL-S604 & UL-103HT at 2100
F
Description
Part/Cat. No.
Lengths & Misc. Chimney Components
8” length, 8” Dia., 8L8 8L8
12” length, 8” Dia., 8L12 8L12
18” length, 8” Dia., 8L18 8L18
24” length, 8” Dia., 8L24 8L24
36” length, 8” Dia., 8L36 8L36
48” length, 8” Dia., 8L48 8L48
Adjustable Length
12”, 8”
Dia., 8LA 8LA
15
elbow,8” Dia., 8E15 8E15
30
elbow, Dia., 8E30 8E30
Rain Termination Cap, Dia., 8CC 8CC
Wall Band BM
Supports
Offset Support, SO SO
Roof Support, ST ST
Roof Brace, BS2 BS2
Firestops
Telescopic Attic Radiation Shield, 8TRS 8TRS
Firestop, 8BF 8BF
Radiation Shield, 8RS 8RS
Insulated Attic Radiation Shield, 8RSA 8RSA
Insulated Wall Radiation Shield, 8RSM 8RSM
Roof Flashings
Flat Roof Flashing, 8FR 8FR
1/12 - 7/12 (5-30), 8FAR 8FAR
8/12 - 12/12 (3
0
), 8FBR 8FBR
Storm Collar, 8FC 8FC
TM
8”
8”
-
45
ASHT+
21
Page 22
ME43 COMPONENTS LISTS
Attic Radiation Shield, ACRSA H0487
Wall Radiation Shield, 30, AC, RSM30 ACRSM30
Insulated Wall Radiation Shield, 30, ACRSMI30 H0489
Chimney Outside Air Kit (Flex, Insulation, Outside Register And Coupling), ACZI
Notes: AC Chimney is Not recommended at elevations above 4000 feet or in cold climates.
H1967
APPENDIX
SPECIFICATIONS
Weight 343 lbs Height 42" Width 43" Depth 26-5/8" Chimney weight ASHT+ 8.75 lb/feet Chimney weight S-2100+ 13.2 lb/feet Chimney weight AC 3.75 lb/feet
Replacement Parts
Description Cat. No.
Refractory PR-SR2028
Back Refractory PR-SR2027
Right Side Refractory PR-SR2025D
Left Side Refractory PR-SR2025G
Bottom Refractory PR-SR1722
Front Refractory Ash Lip PR-SR2026
Log Support Grate PR-HELS43
Top Louver PR-SR15P
Bottom Louver PR-SR15P
Louver Hinges PR-PIVOT
Rigid Firescreen (Right) PR-PARETIND-1
Rigid Firescreen (Left) PR-PARETING-1
Black Door (Left) PR-SR2060GNO
Black Door (Right) PR-SR2060DNO
Gold Plated Door (Left) PR-SR2060GOR
Gold Plated Door (Right) PR-SR2060DOR
Wooden Handle PR-SAC#69
Ceramic Glass Panel PR-VC10
Snap Disc, Blower VTU
Door Gasket Assembly PR-GASKPORTEHE-1
Damper PR-DAMPER43
Touch-up Paint, Aerosol, Black Metallic SBMB6309
70K99
CLEARANCE TO COMBUSTIBLES
The following clearances meet the minimum requirements for a safe installation :
Side wall: 18" (457mm)
Ceiling: 7 feet (2135mm) measured from the base of the fireplace
Fireplace enclosure: Bottom: 0" Side: 0" Back: 0" Top: Do not fill the space above the fireplace with any material (7 feet measured from the base of the fireplace)
Chimney: 2" (50mm)
Mantel: 48" (1219mm) from the base of the fireplace
22
Page 23
NOTES
23
Page 24
WARRANTY
Your fireplace is covered by a limited warranty. Please read the warranty to be familiar with its coverage.
Retain this manual. File it with your other documents for future refer­ence.
PRODUCT REFERENCE INFORMATION
We recommend that you record the following important information about your fireplace. Please contact your Lennox Hearth Products dealer for any questions or concerns. For the number of your nearest Lennox Hearth Products dealer, please call 1-800-9-LENNOX.
REPLACEMENT PARTS
See Page 22 for a complete replacement parts list. Use only parts sup­plied from the manufacturer.
Your Fireplace's Model Number ________________________________________
Normally, all parts should be ordered through your Lennox Hearth Products distributor or dealer. Parts will be shipped at prevailing prices at time of order.
When ordering repair parts, always give the following information:
1. The model number of the appliance.
2. The serial number of the appliance.
3. The part number.
4. The description of the part.
5. The quantity required.
6. The installation date of the appliance.
If you encounter any problems or have any questions concerning the installation or application of this system, please contact your dealer.
LENNOX HEARTH PRODUCTS 1110 West Taft Avenue Orange, CA 92865 Visit us at www.Lennox.com
Your Fireplace's Serial Number ________________________________________
The Date On Which Your Fireplace Was Installed ___________________________
Your Dealer's Name _________________________________________________
Your Dealer's Phone Number __________________________________________
The manufacturer reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information.
Printed in U.S.A. © 2005 by Lennox Hearth Products
P/N 850,027M REV. F 01/2008