Lennox MPA036S4M-*P, MLA018S4M-*P, MLA030S4M-*P, MPB030S4M-*P, MPA048S4M-*P Installation Instructions Manual

...
INSTALLATION
©
2017 Lennox Industries Inc.
Dallas, Texas, USA
Table of Contents
General ...........................................................................1
Included Parts.................................................................2
Compatible Indoor Units .................................................2
Model Number Identication ...........................................2
Typical Multi-Zone System Components ........................3
Outdoor Unit Dimensions ...............................................4
Outdoor Unit Clearances ................................................4
Torque Requirements for Caps and Fasteners...............5
Outdoor Unit Installation .................................................5
Placement Considerations ..........................................5
Direct Sunlight, Rain, Snow and Ice Protection ..........5
Prevailing Winds .........................................................6
Buried Refrigerant Pipe Protection .............................7
Outdoor Unit Condensate Piping ................................7
Securing the Outdoor Unit ..........................................7
Refrigerant Piping Connections ......................................8
Indoor Unit Installation ....................................................9
Connecting Multiple Capacity Indoor Units .................9
Indoor / Outdoor Unit Match-Ups ..............................11
Leak Test and Evacuation ............................................16
Leak Test ..................................................................16
Triple Evacuation Procedure .....................................16
Wiring Connections ......................................................16
Outdoor Unit .............................................................17
Indoor Units...............................................................17
Unit Start-Up .................................................................24
Refrigerant Charge .......................................................24
WARNING
This product contains a chemical known to the State of California to cause cancer, birth defects, or other reproductive harm.
INSTRUCTIONS
MPA, MPB and MLA
MULTI-ZONE OUTDOOR
UNITS
MULTI-ZONE MINI-SPLIT OUTDOOR UNITS (208/230V) --
507549-05 3/2017 Supersedes 10/2016
THIS MANUAL MUST BE LEFT WITH THE OWNER
FOR FUTURE REFERENCE
WARNING
Installation and service must be performed by a li censed professional HVAC installer (or equivalent) or a service agency.
WARNING
The clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs, and HFCs) as of July, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for non-compliance.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
General
Refer to the Product Specications bulletin (EHB) for more
product information. These instructions are intended as a general guide and
do not supersede local or national codes in any way. Authorities having jurisdiction should be consulted before installation.
The MWMA, MWMB, M22A, M33A, M33B, MMDA, MCFA and MCFB indoor units are matched with a two to ve port
multi-zone outdoor heat pump unit to create a mini-split system that uses HFC-410A refrigerant.
Included Parts
Check the components for shipping damage. If you nd any damage, immediately contact the last carrier.
Package contains the following:
1 - Assembled Indoor Unit (The assembled indoor unit will include accessories specic to the unit, see each indoor unit’s
section within this manual for accessories included with that unit.)
1 - Assembled Outdoor Unit and the following items:
Parts Figure Qty Parts Figure Qty Parts Figure Qty
Drain connector 1
Installation and
owner’s manual
1 ea. Seal Ring 1
Line Set Adapters
MPA018S4M-*P MPB018S4M-*P MLA018S4M-*P
2 adapt. – 3/8” to 1/2”
MPA030S4M-*P MPB030S4M-*P MLA030S4M-*P
3 adapt. – 3/8” to 1/2”
MPA036S4M-*P MPB036S4M-*P MLA036S4M-*P
3 adapt. – 3/8” to 1/2” 1 adapt. – 1/2” to 3/8”
MPA048S4M-*P MPB048S4M-*P
3 adapt. – 3/8” to 1/2” 2 adapt. – 1/2” to 3/8”
Compatible Indoor Units
Indoor Unit Voltage Indoor Unit Voltage
MWMA009S4-*P
MWMA012S4-*P
MWMA018S4-*P
MWMA024S4-*P
M22A009S4-*P
M22A012S4-*P
M22A018S4-*P
1
The 24,000 Btu indoor unit is only allowed to be connected to MPA048S4M, MPB048S4M and MLA036S4M multi-zone outdoor units.
Only second generation (-2P) indoor units will work with MLA multi-zone outdoor units.
1
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
M33A024S4-*P
MMDA009S4-*P
MMDA012S4-*P
MMDA018S4-*P
MMDA024S4-*P
MCFB018S4-*P
MCFA024S4-*P
1
1
1
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
Model Number Identication
Series Type
M = Mini-Split
Unit Type
L = Low Ambient Heat Pump
P = Heat Pump
Major Design Sequence
A = 1st Generation
B = 2nd Generation
Nominal Cooling Capacity
018 = 1.5 ton
030 = 2.5 tons
036 = 3 tons
048 = 4 tons
M P A 018 S 4 M - 1 P
Voltage
P = 208/230V-1 phase-60hz
Minor Design Sequence
1 = 1st Revision
Refrigerant Circuits
M = Multiple Circuits
Refrigerant Type
4 = HFC-410A
Cooling Efciency
S = Standard Efciency
2
Typical Multi-Zone System Components
Filter
MPA018S4M Shown
Outdoor Unit Appearance May Vary by Capacity
Utility Bundle One per indoor unit
Return Air
Supply Air
Indoor unit wiring connections
(under access plate)
IMPORTANT - The refrigerant metering device for this system is located in the outdoor unit. This makes it necessary to insulate the refrigerant lines individually to
prevent sweating.
UV-rated tape (field-provided)
Access cover for power and control wiring connections
Condensate drain line (field-provided, one per indoor unit)
Liquid line shut off valve Gas line shut off valve
Port B
Liquid line shut off valve Gas line shut off valve
Port A
Wiring
Condensate drain line
(wrapped in foam insulation)
Refrigerant Line Set, Condensate Line
And Indoor / Outdoor Cable
(field-provided)
TAPE
Line set (wrapped in foam insulation)
See Outdoor Unit wiring diagram for individual system wiring.
Access cover for service valves
Liquid line shut off valve Gas line shut off valve
Port C
Liquid line shut off valve Gas line shut off valve
Port E
Liquid line shut off valve Gas line shut off valve
Port D
Up to 5 ports depending on outdoor unit model
MWMA009 Shown
Up to 5 ports depending on outdoor unit model
Indoor unit type may vary
L2L1
208/230V Outdoor Unit
Terminal Block
MPA048S4M shown
Liquid and vapor line service
and shut off valves
I
MPORTANT - Condensate drain line must always be located at the bottom of the bundle.)
Figure 1. Typical System Shown
3
Outdoor Unit Dimensions
A
E
D
B
C
TYPICAL APPEARANCE OF UNITS
Model
MPA018S4M-*P
MPA030S4M-*P
MPA036S4M-*P
MPA048S4M-*P
MPB018S4M-*P
MPB030S4M-*P
MPB036S4M-*P
MPB048S4M-*P
MLA018S4M-*P
MLA030S4M-*P
MLA036S4M-*P
Unit of
Measurement
A B C D E
inches 35-3/4 22 27-3/8 12-3/4 13-1/8
mm 911 559 695 324 333
inches 37-1/4 25-1/4 31-7/8 15-1/2 16
mm 946 641 810 394 406
inches 36-7/8 32-7/8 54-1/2 15-3/8 16
mm 937 835 1385 391 408
inches 36 21-1/4 27-5/8 13-1/4 13-3/4
mm 914 540 702 335 350
inches 40-3/4 26-1/2 31-7/8 15-1/8 15-7/8
mm 1035 673 810 386 403
inches 41-3/4 25 52-1/2 16-3/8 15-7/8
mm 1060 634 1333 415 404
inches 40-5/8 26-1/2 31-7/8 16-5/8 15-7/8
mm 1032 673 810 422 403
inches 41-1/8 25 52-1/2 15-3/8 15-7/8
mm 1045 635 1334 391 403
Figure 2. Outdoor Unit Dimensions - Inches (mm)
Outdoor Unit Clearances
12
(305)
1
Minimum rear clearance can be 6 inches (152 mm) when mounted on brackets
and with no obstructions on the other three sides.
Figure 3. Outdoor Unit Clearances - Inches (mm)
24 (610)
24
(610)
4
79
(2007)
Air Outlet
Air Inlet
1
12
(305)
Torque Requirements for Caps and Fasteners
When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. “Table 1. Torque
Requirements” provides torque values for fasteners.
IMPORTANT
Only use Allen wrenches of sufcient hardness (50Rc -
Rockwell scale minimum). Fully insert the wrench into the valve stem recess.
Service valve stems are factory-torqued from 9 ft.-lbs.
(12 N*m) for small valves, to 25 ft.-lbs. (34 N*m) for large
valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
See the Lennox Service and Application Notes C-08-1 for further details and information.
Table 1. Torque Requirements
Parts
Service valve cap 8 ft.-lb. 11
Sheet metal screws 16 in.-lb. 2
Machine screws #10 27 in.-lb. 3
Compressor bolts 7 ft.-lb. 10
Gauge port seal cap 8 ft.-lb. 11
Recommended Torque
U.S. Newton-Meter- N
Outdoor Unit Installation
Placement Considerations
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
Consider the following when positioning the unit:
• In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life of the unit. In coastal areas, the coil should be cleaned with potable water several times per year to avoid corrosive buildup (salt)
• Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent
property, not from the property where the unit is in­stalled. Install the unit as far as possible from the prop­erty line
• When possible, do not install the unit directly outside a window. Glass has a very high level of sound trans­mission
• Install unit level
Building Structure
Ground Level
Figure 4. Install Unit Level
• Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will not
be amplied
• Choose a location where the hot air discharged from the unit or the operation noise will not be a nuisance to neighbors
• Avoid installing the outdoor unit near a bedroom or other places where noise may cause a problem
There must be sufcient space to carry the unit into and out of the site
There must be unobstructed air ow around the air in­let and the air outlet
The unit must not be installed in areas where a am­mable gas leak may occur
Install the outdoor unit a minimum of 3 feet (1m) away from any antenna, power cord (line), radio, telephone,
security system, or intercom. Electrical interference
and radio frequencies from any of these sources may affect operation
• Since water drains from the outdoor unit during vari­ous stages of operation, do not place anything which may be damaged by moisture under the unit
Direct Sunlight, Rain, Snow and Ice Protection
• If the outdoor unit is subjected to prolonged exposure
to direct sunlight with temperatures over 100°F (38°C)
a canopy is recommended as illustrated in “Figure 5. Outdoor Unit on Pedestal (Stand) and Protective Can-
opy” on page 6 or “Figure 10. Dog House-Style Shelter” on page 7
IMPORTANT
The construction of a canopy or shade is necessary because of an ambient limit control set to 122°F (50°C) to protect the electronics. If the outdoor unit is placed in direct sunlight it is possible that the limit may activate and shut down the unit.
• Place unit away from overhanging roof lines which would allow water or ice to drop on, or in front of, coil or into unit. Construct a canopy as illustrated in “Figure 5. Outdoor Unit on Pedestal (Stand) and Protective Can-
opy” on page 6
5
• The unit base should be elevated above the depth of
Protective canopy
Air Inlet
Air Outlet
Air Outlet
Air Inlet
12 in
305 mm
79 in
2007 mm
average snows as illustrated in “Figure 6. Outdoor Unit
on Brackets above Snow Line” on page 6
• In heavy snow areas, do not place the unit where drift­ing will occur as illustrated in “Figure 7. Outdoor Unit
Air Flow Obstructed by Snow” on page 6
• Carefully consider how to manage defrost water dis­posal to prevent ice from blocking walkways or creat­ing a safety hazard near the outdoor unit as illustrated
in “Figure 8. Avoid Defrost Water Ice Hazard” on page
6
Protective canopy
24 in
610 mm
12 in
305 mm
Air Inlet
Air Outlet
Figure 7. Outdoor Unit Air Flow Obstructed by
Snow
Pedestal
(stand)
Side View
Front View
Pedestal (stand)
Figure 5. Outdoor Unit on Pedestal (Stand) and
Protective Canopy
Figure 6. Outdoor Unit on Brackets above Snow
Line
Figure 8. Avoid Defrost Water Ice Hazard
Prevailing Winds
Normally wind bafes are not required for a outdoor unit.
However, in order to maximize reliability and performance, the following best practices should be followed.
If unit coil cannot be installed away from prevailing winter winds, some method of protecting the coil is recommended.
However, minimum clearances as reference in “Figure 3. Outdoor Unit Clearances - Inches (mm)” on page 4
must be observed at all times. Common application examples are:
• When prevailing winds are from the air inlet side, then
position the wind barrier a minimum of 12 inches (305 mm) from the unit as illustrated in “Figure 9. Wind Bar­rier”
• When prevailing wind is into the discharge side, then position the wind barrier a minimum 79 inches (2007 mm) from the front of the unit as illustrated in “Figure
9. Wind Barrier”
• Outdoor unit can be installed in a dog house style shel-
ter as illustrated in”Figure 10. Dog House-Style Shel­ter”
• Outdoor unit can be installed in a alcove or under a roof overhang as illustrated in “Figure 11. Unit installed
in Alcove”
6
Prevailing Winter Winds from Air Inlet Side
Wind Barrier
Inlet Air
Discharge Air
Wind Barrier
Prevailing Winter Winds From Air Discharge Side
12” (305mm) Min. Distance
79” (2007mm) Min. Distance
Figure 9. Wind Barrier
Buried Refrigerant Pipe Protection
• All refrigerant lines must be insulated regardless of if
it is buried
• In addition to insulating each line of piping, buried lines must rest inside a sealed, watertight conduit
• The conduit must be designed so it cannot collect and retain water
Outdoor Unit Condensate Piping
Condensate formed during the heating and defrost
processes must be drained from heat pump units. Drain
holes are provided in the base of the units to ensure proper drainage. Heat pumps must be raised when installed on a concrete pad or the ground to allow drainage to occur. If the heat pump unit is installed on wall mounting bracket, insert the provided drain connector into one of the 1
inch (25 mm) drain holes and attached a eld-provided insulated drain hose to the connector. Use eld-provided
rubber plugs to cover any unused drain holes.
24 in
12 in
305 mm
610 mm
NOTE - Minimum clearances shown.
24 in
610 mm
Figure 10. Dog House-Style Shelter
24 in
610 mm
12 in
305 mm
NOTE - Minimum clearances shown.
12 in
305 mm
610 mm
24 in
12 in
305 mm
Drain Connector
Chassis
Condensate Drain (location varies per model)
Figure 12. Condensate Drain
Securing the Outdoor Unit
Slab or Roof Mounting
Install the unit a minimum of 4 inches (102 mm) above the roof or ground surface to avoid ice build-up around the unit. Place the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications.
CAUTION
Roof Damage!
This system contains both refrigerant and oil. Some
rubber roong material may absorb oil. This will cause
the rubber to swell when it comes into contact with oil. The rubber will then bubble and could cause leaks. Protect the roof surface to avoid exposure to refrigerant and oil during service and installation. Failure to follow this notice could result in damage to roof surface.
Figure 11. Unit installed in Alcove
7
Securing Outdoor Unit to Slab, Frame, or Rails
If the outdoor unit is installed on a eld-provided slab or
frame, use lag bolts or equivalent to secure the outdoor unit to the slab or frame.
Four Field-provided Anchor Bolts
Figure 13. Securing Outdoor Unit to Slab
Four Field-Provided
Anchor Bolts
Figure 14. Securing Outdoor Unit to Rails
Securing Outdoor Unit To Hanging Brackets
If the outdoor unit is installed on eld-provided wall
mounting brackets, use lag bolts or equivalent to secure the outdoor unit to the bracket. Minimum rear clearance can be reduced to 6 inches (152 mm) when mounted on brackets and with no obstructions on the other three sides. Allow for condensate disposal when placing units above one another.
6 in
152 mm
Air Inlet
Air Outlet
Figure 15. Securing Outdoor Unit to Brackets
Both lines must be individually insulated.
1. The seal on the unit refrigerant piping connections should remain in place until the last possible moment. This will prevent dust or water from getting into the refrigerant piping before it is connected.
2. CAREFULLY adjust refrigerant piping connections to suit the application.
3. Slowly loosen one of the are nuts to release the
factory nitrogen charge from the indoor units only.
4. Remove the are nuts from the connections on the unit and discard the seal from each of the piping connections.
5. Slide the are nuts onto the ends of the eld-provided
refrigerant piping before using a suitable aring tool to are the end of the copper pipe.
6. Apply recommended HFC-410A refrigerant lubricant
to the outside of the ared refrigerant lines.
IMPORTANT
The compressor in this unit contains PVE oil (Polyvinylether). PVE oil is formulated for hydrouorocarbon (HFC) refrigerants, such as HFC-
410A, which this system contains. While it may have some miscibility properties with mineral-based oil and
POE oil (Polyolester), it is not recommended to mix PVE
oil with any other type of refrigerant oil.
7. Align the threaded connections with the
ared refrigerant lines. Tighten the are nuts lightly at rst to obtain a smooth match as
illustrated in “Figure 16. Making Connections
(Male to Female Connection)” on page 9.
8. Once snug, continue another half-turn on each nut which should create a leak-free joint. A torque wrench
may be used to tighten are nuts using “Table 3. Flare Nut Torque Recommendations” on page 9
recommendations. Do not over-tighten a ared joint.
Flared connections should always be accessible and must be insulated to prevent condensation.
9. After refrigerant piping has been installed and checked
for leaks, apply insulation over all ared connections.
Table 2. Refrigerant Piping and Indoor Unit
Connection Sizes
Size
(Btuh)
9000 1/4 3/8
12000 1/4 1/2
18000 1/4 1/2
24000 3/8
Liquid Line
in.
Gas Line
in.
5/8
Refrigerant Piping Connections
Field piping consists of two copper lines connecting the outdoor unit to the indoor unit. “Table 1. Torque
Requirements” lists the connection sizes. The connections are made using the provided brass are nuts at the end of
the refrigerant piping connections.
8
A
B
CANT ON THE OUTSIDE OF
THE FLARE
Figure 16. Making Connections
(Male to Female Connection)
MALE FLARE
CONNECTION
• The largest cpacity indoor unit must be connected to
the lowest rerigerant connection ports on the outdoor
unit.
The 24,000 Btu indoor unit is only allowed to be
connected to MPA048S4M, MPB048S4M and MLA036S4M outdoor units.
NOTE: Each indoor unit must be piped AND wired to
the correct zone piping connections and wiring terminals. Make sure that indoor unit A is wired to the zone A terminal block and connected to the appropriate refrigerant pipe connections.
outdoor
wire
C
A
B
D
indoor
IMPORTANT
Always use two wrenches when tightening are nuts to avoid twisting refrigerant piping. DO NOT over-tighten are nuts.
TORQUE WRENCH
TO INDOOR
UNIT
TO OUTDOOR UNIT
Figure 17. Tighten Flare Nut
Table 3. Flare Nut Torque Recommendations
Outside
Diameter
Inches
1/4 15 ft.-lb. (20 N) 1/4 turn
3/8 26 ft.-lb. (35 N) 1/2 turn
1/2 41 ft.-lb. (56 N) 7/8 turn
5/8 48 ft.-lb. (65 N) 1 full turn
Recommended
Torque
No torque wrench available
Finger tighten and use an
appropriately sized wrench to
turn an additional:
BACKUP
WRENCH
pipe
Unit D
Unit C
Unit B
Unit A
L4(ft)
L3(ft)
L2(ft)
L1(ft)
Unit D
Unit C
Unit B
Unit A
Figure 18. Pipe and Wire Each Zone Separately
C(1/4in)
C(3/8in)
B(1/4in)
B(3/8in)
A(1/4in)
A(1/2in)
Indoor Unit Installation
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
Please refer to the installation instruction included with the indoor unit for setup.
IMPORTANT
Pipe and wire to each zone separately. Test each indoor unit separately to ensure proper
operation.
Connecting Multiple Capacity Indoor Units
Figure 19. Connecting Multiple Capacity Indoor
Units
9
INDOOR UNIT
INDOOR UNIT
NOTE - Minimum Line Set Length - 10 ft. (3 m) per Indoor Unit
INDOOR UNIT
Maximum
Elevation -
Outdoor Unit
BELOW
Indoor Units
49 ft.
(15 m)
NOTE - Maximum Line Set Length Includes ALL piping in measurement
NOTE - Maximum Difference in Elevation Between Indoor Units - 33 ft. (10 m).
Maximum Line Set
Furthest Indoor Unit
OUTDOOR UNIT
33 ft. (10 m) for MPA
INDOOR UNIT
ABOVE Indoor Unit
INDOOR UNIT
Outdoor Unit Model No.
Maximum Number of Indoor Units
Indoor Unit Connections ­Liquid / Gas
MPA018S4M-*P
MPB018S4M-*P
MLA018S4M-*P
Two Three Four Five
(2) 1/4 / 3/8 (3) 1/4 / 3/8
MPA030S4M-*P
MPB030S4M-*P
MLA030S4M-*P
Total Length of All Piping 98 ft. (30 m) 148 ft. (45 m) 197 ft. (60 m) 246 (75 m)
Maximum Line Set Length - Furthest Indoor
66 ft. (20 m) 82 ft. (25 m) 98 ft. (30 m) 98 ft. (30 m)
Unit
49 ft. (15 m) for MLA and MPB
Maximum
Elevation -
Outdoor Unit
MPA036S4M-*P
MPB036S4M-*P
MLA036S4M-*P
(3) 1/4 / 3/8
(1)1/4 / 1/2
MPA048S4M-*P
MPB048S4M-*P
(3) 1/4 / 3/8 (2) 1/4 / 1/2
Figure 20. Multi-Zone Systems with All Indoor Unit Models
10
Indoor / Outdoor Unit Match-Ups
Each system is formed of one outdoor unit and a selection of indoor units as referenced in the Product Specications (EHB). Only these combinations are allowed.
NOTE: Each indoor unit must be piped AND wired to
the correct zone piping connections and wiring terminals. Make sure that indoor unit A is wired to the zone A terminal block and connected to the appropriate refrigerant pipe connections.
Table 4. Match-Ups
Outdoor Model
MPA018S4M
MPB018S4M
Indoor Unit A
1/4” liq + 3/8” gas
Indoor Unit B 1/4” liq + 3/8” gas
MPA030S4M MPB030S4M
Indoor Unit A
1/4” liq + 3/8” gas
Indoor Unit B 1/4” liq + 3/8” gas
Indoor Unit C
1/4” liq + 3/8” gas
No. of
Zones
Indoor Unit
Capacity
(Unit No.)
1 012 (A)1 1/4 in. x 1/2 in.
2
2
2
009 (A) 1/4 in. x 3/8 in.
009 (B) 1/4 in. x 3/8 in.
009 (B) 1/4 in. x 3/8 in.
012 (A)1 1/4 in. x 1/2 in.
012 (A)1 1/4 in. x 1/2 in.
012 (B)1 1/4 in. x 1/2 in.
1 018 (A)1 1/4 in. x 1/2 in.
2
2
2
2
2
2
009 (A) 1/4 in. x 3/8 in.
009 (B) 1/4 in. x 3/8 in.
009 (B) 1/4 in. x 3/8 in.
012 (A)1 1/4 in. x 1/2 in.
009 (B) 1/4 in. x 3/8 in.
018 (A)1 1/4 in. x 1/2 in.
012 (A)1 1/4 in. x 1/2 in.
012 (B)1 1/4 in. x 1/2 in.
012 (B)1 1/4 in. x 1/2 in.
018 (A)1 1/4 in. x 1/2 in.
018 (A)1 1/4 in. x 1/2 in.
018 (B)1 1/4 in. x 1/2 in.
009 (A) 1/4 in. x 3/8 in.
3
009 (B) 1/4 in. x 3/8 in.
009 (C) 1/4 in. x 3/8 in.
009 (B) 1/4 in. x 3/8 in.
3
009 (C) 1/4 in. x 3/8 in.
012 (A)1 1/4 in. x 1/2 in.
Line Set
Required
(Liquid x Gas)
Outdoor Model
MPA030S4M MPB030S4M
Indoor Unit A
1/4” liq + 3/8” gas
Indoor Unit B 1/4” liq + 3/8” gas
Indoor Unit C
1/4” liq + 3/8” gas
MPA036S4M MPB036S4M
Indoor Unit A
1/4” liq + 1/2” gas
Indoor Unit B 1/4” liq + 3/8” gas
Indoor Unit C
1/4” liq + 3/8” gas
Indoor Unit D 1/4” liq + 3/8” gas
Table 4. Match-Ups
No. of Zones
2
2
Indoor Unit
Capacity
(Unit No.)
009 (C) 1/4 in. x 3/8 in.
3
012 (A)
012 (B)
009 (B) 1/4 in. x 3/8 in.
3
009 (C) 1/4 in. x 3/8 in.
018 (A)
012 (A)
3
012 (B)
012 (C)1 1/4 in. x 1/2 in.
2
4
009 (B) 1/4 in. x 3/8 in.
018 (A) 1/4 in. x 1/2 in.
009 (B) 1/4 in. x 3/8 in.
024 (A)
2
4
012 (A) 1/4 in. x 1/2 in.
012 (B)
012 (B)
024 (A)
2
012 (B)
018 (A) 1/4 in. x 1/2 in.
2 018 (A) 1/4 in. x 1/2 in.
018 (B)
009 (B) 1/4 in. x 3/8 in.
3
009 (C) 1/4 in. x 3/8 in.
009 (D) 1/4 in. x 3/8 in.
009 (B) 1/4 in. x 3/8 in.
3
009 (C) 1/4 in. x 3/8 in.
012 (A) 1/4 in. x 1/2 in.
009 (B) 1/4 in. x 3/8 in.
3
009 (C) 1/4 in. x 3/8 in.
018 (A) 1/4 in. x 1/2 in.
009 (C) 1/4 in. x 3/8 in.
3
012 (A) 1/4 in. x 1/2 in.
012 (B)
Line Set
Required
(Liquid x Gas)
1
1/4 in. x 1/2 in.
1
1/4 in. x 1/2 in.
1
1/4 in. x 1/2 in.
1
1/4 in. x 1/2 in.
1
1/4 in. x 1/2 in.
2,3
3/8 in. x 5/8 in.
1
1/4 in. x 1/2 in.
1
1/4 in. x 1/2 in.
2,3
3/8 in. x 5/8 in.
1
1/4 in. x 1/2 in.
1
1/4 in. x 1/2 in.
1
1/4 in. x 1/2 in.
11
Outdoor Model
MPA036S4M MPB036S4M
Indoor Unit A
1/4” liq + 1/2” gas
Indoor Unit B 1/4” liq + 3/8” gas
Indoor Unit C
1/4” liq + 3/8” gas
Indoor Unit D 1/4” liq + 3/8” gas
Table 4. Match-Ups
3
3
3
3
3
4
4
4
4
4
4
4
Indoor Unit
Capacity
(Unit No.)
009 (C) 1/4 in. x 3/8 in.
012 (B)1 1/4 in. x 1/2 in.
018 (A) 1/4 in. x 1/2 in.
009 (C) 1/4 in. x 3/8 in.
018 (A) 1/4 in. x 1/2 in.
018 (B)1 1/4 in. x 1/2 in.
012 (A) 1/4 in. x 1/2 in.
012 (B)1 1/4 in. x 1/2 in.
012 (C)1 1/4 in. x 1/2 in.
012 (C)1 1/4 in. x 1/2 in.
012 (B)1 1/4 in. x 1/2 in.
018 (A) 1/4 in. x 1/2 in.
012 (C)1 1/4 in. x 1/2 in.
018 (A) 1/4 in. x 1/2 in.
018 (B)1 1/4 in. x 1/2 in.
012 (B)1 1/4 in. x 1/2 in.
012 (C)1 1/4 in. x 1/2 in.
024 (A)
009 (B) 1/4 in. x 3/8 in.
009 (C) 1/4 in. x 3/8 in.
009 (D) 1/4 in. x 3/8 in.
009 (A)1 1/4 in. x 3/8 in.
009 (B) 1/4 in. x 3/8 in.
009 (C) 1/4 in. x 3/8 in.
009 (D) 1/4 in. x 3/8 in.
012 (A) 1/4 in. x 1/2 in.
009 (B) 1/4 in. x 3/8 in.
009 (C) 1/4 in. x 3/8 in.
009 (D) 1/4 in. x 3/8 in.
018 (A) 1/4 in. x 1/2 in.
009 (C) 1/4 in. x 3/8 in.
009 (D) 1/4 in. x 3/8 in.
012 (A) 1/4 in. x 1/2 in.
012 (B)1 1/4 in. x 1/2 in.
009 (C) 1/4 in. x 3/8 in.
009 (D) 1/4 in. x 3/8 in.
012 (B)1 1/4 in. x 1/2 in.
018 (A) 1/4 in. x 1/2 in.
009 (D) 1/4 in. x 3/8 in.
012 (A) 1/4 in. x 1/2 in.
012 (B)1 1/4 in. x 1/2 in.
012 (C)1 1/4 in. x 1/2 in.
No. of
Zones
3
Line Set
Required
(Liquid x Gas)
2,3
3/8 in. x 5/8 in.
Outdoor Model
MPA048S4M MPB048S4M
Indoor Unit A
1/4” liq + 1/2” gas
Indoor Unit B 1/4” liq + 1/2” gas
Indoor Unit C
1/4” liq + 3/8” gas
Indoor Unit D 1/4” liq + 3/8” gas
Indoor Unit E 1/4” liq + 3/8” gas
Table 4. Match-Ups
4
2
2
2
2
2
2
3
3
3
3
3
3
Indoor Unit
Capacity
(Unit No.)
012 (A) 1/4 in. x 1/2 in.
012 (B)
012 (C)1 1/4 in. x 1/2 in.
012 (D)1 1/4 in. x 1/2 in.
009 (B)
024 (A)
012 (B) 1/4 in. x 1/2 in.
018 (A) 1/4 in. x 1/2 in.
012 (B) 1/4 in. x 1/2 in.
024 (A)
018 (A) 1/4 in. x 1/2 in.
018 (B) 1/4 in. x 1/2 in.
018 (B) 1/4 in. x 1/2 in.
024 (A)
024 (A)
024 (B)
009 (A)
009 (B)
009 (C) 1/4 in. x 3/8 in.
009 (B)
009 (C) 1/4 in. x 3/8 in.
012 (A) 1/4 in. x 1/2 in.
009 (B)
009 (C) 1/4 in. x 3/8 in.
018 (A) 1/4 in. x 1/2 in.
009 (B)
009 (C) 1/4 in. x 3/8 in.
024 (A)
009 (C) 1/4 in. x 3/8 in.
012 (A) 1/4 in. x 1/2 in.
012 (B) 1/4 in. x 1/2 in.
009 (C) 1/4 in. x 3/8 in.
012 (B) 1/4 in. x 1/2 in.
018 (A) 1/4 in. x 1/2 in.
No. of Zones
Line Set
Required
(Liquid x Gas)
1
1/4 in. x 1/2 in.
1
1/4 in. x 3/8 in.
2, 3
3/8 in. x 5/8 in.
2, 3
3/8 in. x 5/8 in.
2, 3
3/8 in. x 5/8 in.
2, 3
3/8 in. x 5/8 in.
2, 3
3/8 in. x 5/8 in.
1
1/4 in. x 3/8 in.
1
1/4 in. x 3/8 in.
1
1/4 in. x 3/8 in.
1
1/4 in. x 3/8 in.
1
1/4 in. x 3/8 in.
2, 3
3/8 in. x 5/8 in.
12
Outdoor Model
MPA048S4M
MPB048S4M
Indoor Unit A
1/4” liq + 1/2” gas
Indoor Unit B 1/4” liq + 1/2” gas
Indoor Unit C
1/4” liq + 3/8” gas
Indoor Unit D 1/4” liq + 3/8” gas
Indoor Unit E 1/4” liq + 3/8” gas
Table 4. Match-Ups
3
3
3
3
3
3
3
3
3
3
3
3
4
4
Indoor Unit
Capacity
(Unit No.)
009 (C) 1/4 in. x 3/8 in.
012 (B) 1/4 in. x 1/2 in.
024 (A)
009 (C) 1/4 in. x 3/8 in.
018 (A) 1/4 in. x 1/2 in.
018 (B) 1/4 in. x 1/2 in.
009 (C) 1/4 in. x 3/8 in.
018 (B) 1/4 in. x 1/2 in.
024 (A)
009 (C) 1/4 in. x 3/8 in.
024 (A)
024 (B)
012 (A) 1/4 in. x 1/2 in.
012 (B) 1/4 in. x 1/2 in.
012 (C)1 1/4 in. x 1/2 in.
012 (B) 1/4 in. x 1/2 in.
012 (C)1 1/4 in. x 1/2 in.
018 (A) 1/4 in. x 1/2 in.
012 (C) 1/4 in. x 1/2 in.
018 (A) 1/4 in. x 1/2 in.
018 (B)1 1/4 in. x 1/2 in.
012 (B) 1/4 in. x 1/2 in.
012 (C)1 1/4 in. x 1/2 in.
024 (A)
012 (B) 1/4 in. x 1/2 in.
018 (C)1 1/4 in. x 1/2 in.
024 (A)
012 (C)1 1/4 in. x 1/2 in.
024 (A)
024 (B)
018 (A) 1/4 in. x 1/2 in.
018 (B) 1/4 in. x 1/2 in.
018 (C)1 1/4 in. x 1/2 in.
018 (B) 1/4 in. x 1/2 in.
018 (C)
024 (A)
009 (A)1 1/4 in. x 3/8 in.
009 (B)1 1/4 in. x 3/8 in.
009 (C) 1/4 in. x 3/8 in.
009 (D) 1/4 in. x 3/8 in.
009 (B)1 1/4 in. x 3/8 in.
009 (C) 1/4 in. x 3/8 in.
009 (D) 1/4 in. x 3/8 in.
012 (A) 1/4 in. x 1/2 in.
No. of
Zones
Line Set
Required
(Liquid x Gas)
2, 3
3/8 in. x 5/8 in.
2, 3
3/8 in. x 5/8 in.
2, 3
3/8 in. x 5/8 in.
2, 3
3/8 in. x 5/8 in.
2, 3
3/8 in. x 5/8 in.
2, 3
3/8 in. x 5/8 in.
2, 3
3/8 in. x 5/8 in.
2, 3
3/8 in. x 5/8 in.
1
1/4 in. x 1/2 in.
2, 3
3/8 in. x 5/8 in.
Outdoor Model
MPA048S4M
MPB048S4M
Indoor Unit A
1/4” liq + 1/2” gas
Indoor Unit B 1/4” liq + 1/2” gas
Indoor Unit C
1/4” liq + 3/8” gas
Indoor Unit D 1/4” liq + 3/8” gas
Indoor Unit E 1/4” liq + 3/8” gas
Table 4. Match-Ups
4
4
4
4
4
4
4
Indoor Unit
Capacity
(Unit No.)
009 (B)
009 (C) 1/4 in. x 3/8 in.
009 (D) 1/4 in. x 3/8 in.
018 (A) 1/4 in. x 1/2 in.
009 (B)
009 (C) 1/4 in. x 3/8 in.
009 (D) 1/4 in. x 3/8 in.
024 (A)
009 (C) 1/4 in. x 3/8 in.
009 (D) 1/4 in. x 3/8 in.
012 (A) 1/4 in. x 1/2 in.
012 (B) 1/4 in. x 1/2 in.
009 (C) 1/4 in. x 3/8 in.
009 (D) 1/4 in. x 3/8 in.
012 (B) 1/4 in. x 1/2 in.
018 (A) 1/4 in. x 1/2 in.
009 (C) 1/4 in. x 3/8 in.
009 (D) 1/4 in. x 3/8 in.
018 (A) 1/4 in. x 1/2 in.
018 (B) 1/4 in. x 1/2 in.
009 (C) 1/4 in. x 3/8 in.
009 (D) 1/4 in. x 3/8 in.
018 (B) 1/4 in. x 1/2 in.
024 (A)
009 (D) 1/4 in. x 3/8 in.
012 (A)
012 (B)
012 (C) 1/4 in. x 1/2 in.
No. of Zones
Line Set
Required
(Liquid x Gas)
1
1/4 in. x 3/8 in.
1
1/4 in. x 3/8 in.
2, 3
3/8 in. x 5/8 in.
2, 3
3/8 in. x 5/8 in.
1
1/4 in. x 1/2 in.
1
1/4 in. x 1/2 in.
13
Outdoor Model
MPA048S4M
MPB048S4M
Indoor Unit A
1/4” liq + 1/2” gas
Indoor Unit B 1/4” liq + 1/2” gas
Indoor Unit C
1/4” liq + 3/8” gas
Indoor Unit D 1/4” liq + 3/8” gas
Indoor Unit E 1/4” liq + 3/8” gas
Table 4. Match-Ups
4
4
4
4
5
5
5
5
5
5
Indoor Unit
Capacity
(Unit No.)
009 (D) 1/4 in. x 3/8 in.
012 (B) 1/4 in. x 1/2 in.
012 (C)1 1/4 in. x 1/2 in.
018 (A) 1/4 in. x 1/2 in.
009 (D) 1/4 in. x 3/8 in.
012 (C)1 1/4 in. x 1/2 in.
018 (A) 1/4 in. x 1/2 in.
018 (B) 1/4 in. x 1/2 in.
012 (A) 1/4 in. x 1/2 in.
012 (B) 1/4 in. x 1/2 in.
012 (C)1 1/4 in. x 1/2 in.
012 (D)1 1/4 in. x 1/2 in.
012 (B) 1/4 in. x 1/2 in.
012 (C)1 1/4 in. x 1/2 in.
012 (D)1 1/4 in. x 1/2 in.
018 (A) 1/4 in. x 1/2 in. 009 (A)1 1/4 in. x 3/8 in.
009 (B)1 1/4 in. x 3/8 in. 009 (C) 1/4 in. x 3/8 in. 009 (D) 1/4 in. x 3/8 in. 009 (E) 1/4 in. x 3/8 in. 009 (B)1 1/4 in. x 3/8 in. 009 (C) 1/4 in. x 3/8 in. 009 (D) 1/4 in. x 3/8 in. 009 (E) 1/4 in. x 3/8 in.
012 (A) 1/4 in. x 1/2 in.
009 (B)1 1/4 in. x 3/8 in. 009 (C) 1/4 in. x 3/8 in. 009 (D) 1/4 in. x 3/8 in. 009 (E) 1/4 in. x 3/8 in.
018 (A) 1/4 in. x 1/2 in.
009 (B)1 1/4 in. x 3/8 in. 009 (C) 1/4 in. x 3/8 in. 009 (D) 1/4 in. x 3/8 in. 009 (E) 1/4 in. x 3/8 in.
024 (A) 009 (C) 1/4 in. x 3/8 in.
009 (D) 1/4 in. x 3/8 in. 009 (E) 1/4 in. x 3/8 in.
012 (A) 1/4 in. x 1/2 in. 012 (B) 1/4 in. x 1/2 in. 009 (C) 1/4 in. x 3/8 in.
009 (D) 1/4 in. x 3/8 in. 009 (E) 1/4 in. x 3/8 in. 012 (B) 1/4 in. x 1/2 in.
018 (A) 1/4 in. x 1/2 in.
No. of
Zones
Line Set
Required
(Liquid x Gas)
2, 3
3/8 in. x 5/8 in.
Outdoor Model
MPA048S4M
MPB048S4M
Indoor Unit A
1/4” liq + 1/2” gas
Indoor Unit B 1/4” liq + 1/2” gas
Indoor Unit C
1/4” liq + 3/8” gas
Indoor Unit D 1/4” liq + 3/8” gas
Indoor Unit E 1/4” liq + 3/8” gas
MLA018S4M Indoor Unit A
1/4” liq + 3/8” gas
Indoor Unit B
1/4” liq + 3/8” gas
MLA030S4M Indoor Unit A
1/4” liq + 1/2” gas
Indoor Unit B
1/4” liq + 3/8” gas
Indoor Unit C
1/4” liq + 3/8” gas
Table 4. Match-Ups
5
5
5
5
2
2
2
2
2
2
2
2
2
2
2
2
3
Indoor Unit
Capacity
(Unit No.)
009 (D) 1/4 in. x 3/8 in. 009 (E) 1/4 in. x 3/8 in.
012 (A) 1/4 in. x 1/2 in. 012 (B) 1/4 in. x 1/2 in. 012 (C)1 1/4 in. x 1/2 in.
009 (D) 1/4 in. x 3/8 in. 009 (E) 1/4 in. x 3/8 in. 012 (B) 1/4 in. x 1/2 in.
012 (C)1 1/4 in. x 1/2 in. 018 (A) 1/4 in. x 1/2 in.
009 (E) 1/4 in. x 3/8 in.
012 (A) 1/4 in. x 1/2 in. 012 (B) 1/4 in. x 1/2 in. 012 (C)1 1/4 in. x 1/2 in.
012 (D)1 1/4 in. x 1/2 in.
012 (A) 1/4 in. x 1/2 in. 012 (B) 1/4 in. x 1/2 in. 012 (C)1 1/4 in. x 1/2 in.
012 (D)1 1/4 in. x 1/2 in. 012 (E)
009 (A) 1/4 in. x 3/8 in.
009 (B) 1/4 in. x 3/8 in.
012 (A)
009 (B) 1/4 in. x 3/8 in.
009 (B) 1/4 in. x 3/8 in.
018 (A)
012 (A)
012 (B)
009 (A)
009 (B) 1/4 in. x 3/8 in.
012 (A) 1/4 in. x 1/2 in.
009 (B) 1/4 in. x 3/8 in.
009 (B) 1/4 in. x 3/8 in.
018 (A) 1/4 in. x 1/2 in.
009 (B) 1/4 in. x 3/8 in.
024 (A)
012 (A) 1/4 in. x 1/2 in.
012 (B)
012 (B)
018 (A) 1/4 in. x 1/2 in.
024 (A)
012 (B)
018 (A) 1/4 in. x 1/2 in.
018 (B)
009 (A)
009 (B) 1/4 in. x 3/8 in.
009 (C) 1/4 in. x 3/8 in.
No. of Zones
Line Set
Required
(Liquid x Gas)
1
1/4 in. x 1/2 in.
1
1/4 in. x 1/2 in.
1
1/4 in. x 1/2 in.
1
1/4 in. x 1/2 in.
1
1/4 in. x 1/2 in.
1
1/4 in. x 3/8 in.
2, 3
3/8 in. x 5/8 in.
1
1/4 in. x 1/2 in.
1
1/4 in. x 1/2 in.
2, 3
3/8 in. x 5/8 in.
1
1/4 in. x 1/2 in.
1
1/4 in. x 1/2 in.
1
1/4 in. x 3/8 in.
14
Outdoor Model
MLA030S4M
Indoor Unit A
1/4” liq + 1/2” gas
Indoor Unit B
1/4” liq + 3/8” gas
Indoor Unit C
1/4” liq + 3/8” gas
MLA036S4M
Indoor Unit A
1/4” liq + 1/2” gas
Indoor Unit B
1/4” liq + 1/2” gas
Indoor Unit C
1/4” liq + 3/8” gas
Indoor Unit D
1/4” liq + 3/8” gas
Table 4. Match-Ups
3
3
3
3
3
2
2
2
2
2
2
2
2
3
3
Indoor Unit
Capacity
(Unit No.)
009 (B) 1/4 in. x 3/8 in.
009 (C) 1/4 in. x 3/8 in.
012 (A) 1/4 in. x 1/2 in.
009 (C) 1/4 in. x 3/8 in.
012 (A) 1/4 in. x 1/2 in.
012 (B)1 1/4 in. x 1/2 in.
009 (B) 1/4 in. x 3/8 in.
009 (C) 1/4 in. x 3/8 in.
018 (A) 1/4 in. x 1/2 in.
018 (A) 1/4 in. x 1/2 in.
012 (B)1 1/4 in. x 1/2 in.
009 (C) 1/4 in. x 3/8 in.
012 (A) 1/4 in. x 1/2 in.
012 (B)1 1/4 in. x 1/2 in.
012 (C)1 1/4 in. x 1/2 in.
009 (B)1 1/4 in. x 3/8 in.
018 (A) 1/4 in. x 1/2 in.
009 (B)1 1/4 in. x 3/8 in.
024 (A)
012 (A) 1/4 in. x 1/2 in.
012 (B) 1/4 in. x 1/2 in.
012 (B) 1/4 in. x 1/2 in.
018 (A) 1/4 in. x 1/2 in.
012 (B) 1/4 in. x 1/2 in.
024 (A)
018 (B) 1/4 in. x 1/2 in.
018 (A) 1/4 in. x 1/2 in.
018 (B) 1/4 in. x 1/2 in.
024 (A)
024 (B)
024 (A)
009 (A)1 1/4 in. x 3/8 in.
009 (B)1 1/4 in. x 3/8 in.
009 (C) 1/4 in. x 3/8 in.
009 (B)1 1/4 in. x 3/8 in.
009 (C) 1/4 in. x 3/8 in.
012 (A) 1/4 in. x 1/2 in.
No. of
Zones
Line Set
Required
(Liquid x Gas)
2, 3
3/8 in. x 5/8 in.
2, 3
3/8 in. x 5/8 in.
2, 3
3/8 in. x 5/8 in.
2, 3
3/8 in. x 5/8 in.
2, 3
3/8 in. x 5/8 in.
Outdoor Model
MLA036S4M
Indoor Unit A
1/4” liq + 1/2” gas
Indoor Unit B
1/4” liq + 1/2” gas
Indoor Unit C
1/4” liq + 3/8” gas
Indoor Unit D
1/4” liq + 3/8” gas
Table 4. Match-Ups
3
3
3
3
3
3
3
3
3
3
4
4
Indoor Unit
Capacity
(Unit No.)
009 (B)
009 (C) 1/4 in. x 3/8 in.
018 (A) 1/4 in. x 1/2 in.
009 (C) 1/4 in. x 3/8 in.
009 (B) 1 1/4 in. x 1/2 in.
024 (A)
009 (C) 1/4 in. x 3/8 in.
012 (A) 1/4 in. x 1/2 in.
012 (B) 1/4 in. x 1/2 in.
009 (C) 1/4 in. x 3/8 in.
012 (B) 1/4 in. x 1/2 in.
018 (A) 1/4 in. x 1/2 in.
009 (C) 1/4 in. x 3/8 in.
024 (A)
012 (B) 1/4 in. x 1/2 in.
009 (C) 1/4 in. x 3/8 in.
018 (A) 1/4 in. x 1/2 in.
018 (B) 1/4 in. x 1/2 in.
012 (A) 1/4 in. x 1/2 in.
012 (B) 1/4 in. x 1/2 in.
012 (C)1 1/4 in. x 1/2 in.
012 (B) 1/4 in. x 1/2 in.
012 (C)1 1/4 in. x 1/2 in.
018 (A) 1/4 in. x 1/2 in.
012 (B) 1/4 in. x 1/2 in.
012 (C)1 1/4 in. x 1/2 in.
024 (A)
012 (C)1 1/4 in. x 1/2 in.
018 (A) 1/4 in. x 1/2 in.
018 (B) 1/4 in. x 1/2 in.
009 (B)
009 (C) 1/4 in. x 3/8 in.
009 (D) 1/4 in. x 3/8 in.
009 (A)
009 (B)
009 (C) 1/4 in. x 3/8 in.
009 (D) 1/4 in. x 3/8 in.
012 (A) 1/4 in. x 1/2 in.
No. of Zones
Line Set
Required
(Liquid x Gas)
1
1/4 in. x 3/8 in.
2, 3
3/8 in. x 5/8 in.
2, 3
3/8 in. x 5/8 in.
2, 3
3/8 in. x 5/8 in.
1
1/4 in. x 3/8 in.
1
1/4 in. x 3/8 in.
1
1/4 in. x 3/8 in.
15
Table 4. Match-Ups
4
4
4
4
4
Indoor Unit
Capacity
(Unit No.)
009 (B)1 1/4 in. x 3/8 in.
009 (C) 1/4 in. x 3/8 in.
009 (D) 1/4 in. x 3/8 in.
018 (A) 1/4 in. x 1/2 in.
009 (C) 1/4 in. x 3/8 in.
009 (D) 1/4 in. x 3/8 in.
012 (A) 1/4 in. x 1/2 in.
012 (B) 1/4 in. x 1/2 in.
009 (C) 1/4 in. x 3/8 in.
009 (D) 1/4 in. x 3/8 in.
012 (B) 1/4 in. x 1/2 in.
018 (A) 1/4 in. x 1/2 in.
009 (D) 1/4 in. x 3/8 in.
012 (A) 1/4 in. x 1/2 in.
012 (B) 1/4 in. x 1/2 in.
012 (C)1 1/4 in. x 1/2 in.
012 (A) 1/4 in. x 1/2 in.
012 (B) 1/4 in. x 1/2 in.
012 (C)1 1/4 in. x 1/2 in.
012 (D)1 1/4 in. x 1/2 in.
Outdoor Model
MLA036S4M
Indoor Unit A
1/4” liq + 1/2” gas
Indoor Unit B
1/4” liq + 1/2” gas
Indoor Unit C
1/4” liq + 3/8” gas
Indoor Unit D
1/4” liq + 3/8” gas
1
3/8 x 1/2 in. gas pipe adaptor is required for line set connection to outdoor unit
(furnished with outdoor unit).
2
1/4 x 3/8 in. liquid pipe adaptor is required for line set connection to the 048
outdoor unit (furnished with outdoor unit).
3
1/2 x 5/8 in. gas pipe adaptor is required for line set connection to the 048
outdoor unit (furnished with outdoor unit).
4
Not a valid combination when using the MPA036S4M.
No. of
Zones
Line Set
Required
(Liquid x Gas)
Leak Test and Evacuation
Air and moisture remaining in the refrigerant system will have undesirable effects as indicated below:
• Pressure in the system rises
• Operating current rises
Cooling or heating efciency drops
• Moisture in the refrigerant circuit may freeze
• Water may lead to corrosion of parts in the refrigera­tion system
The line set between the indoor and outdoor units must be leak tested and evacuated to remove any non­condensables and moisture from the system.
there is any movement check system for leaks.
5. After the system is found to be free of leaks:
• Close valve on nitrogen cylinder.
• Relieve the nitrogen pressure by: loosening the charge hose connector at the nitrogen cylinder.
• When the system pressure is reduced to normal, disconnect the hose from the cylinder.
IMPORTANT
Use only oxygen-free nitrogen (OFN).
Triple Evacuation Procedure
A Micron or Torr gauge must be used for this procedure.
1. Discharge the oxygen-free nitrogen and evacuate the system to a reading of 8000 Microns (8 Torr) using all service valves.
2. Break the vacuum by allowing nitrogen into the port connections (liquid and gas line pipes) until a positive pressure is achieved.
3. Evacuate the system to a reading of 5000 Microns (5
Torr).
4. Break the vacuum by allowing nitrogen into the port connections (liquid and gas line pipes) until a positive pressure is achieved
5. Evacuate the system to a minimum reading of 500 Microns (0.5 Torr).
6. For a moisture-free system, ensure the vacuum is held without movement for a minimum of 4 hours.
7. If vacuum fails to hold, carry out steps 2 through 6 until vacuum holds.
Table 5. Pressure Test Specications
1 3 bar 44 psig Minimum of 10 minutes
2 15 bar 220 psig Minimum of 10 minutes
3 32 bar 470 psig Minimum of 10 minutes
4 45 bar 650 psig 1 hour. Stress test to prove the
integrity of the complete installation.
5 32 bar 470 psig 24 hours. Lower system pressure
test, after conrmation No. 4 was
successfully completed.
Leak Test
Use the following procedure to test for system leaks:
1. Connect the manifold gauge set and dry nitrogen gas cylinder to the liquid and gas service ports.
2. Open valve on nitrogen cylinder.
3. Pressurize the system per the pressure test specications in “Table 5. Pressure Test Specications”.
4. Check that the system pressure remains stable. If
16
Wiring Connections
IMPORTANT
Install unit so that unit disconnect is accessible.
Use specied wiring and cable to make electrical
connections. Clamp cables securely and make sure that connections are tight to avoid strain on wiring. Insecure wiring connections may result in equipment failure and
risk of re.
Wiring must be installed so that all cover plates can be securely closed.
WARNING
Electric Shock Hazard. Can cause injury or death. Unit
must be rounded in accordance with national and local codes.
Line voltage is present at all components when unit is
not in operation. Disconnect all remote electric power
supplies before opening access panel. Unit may have multiple power sources.
CAUTION
All terminal connections must be made as illustrated in the following diagrams. Improperly connected wiring could damage unit or cause communication errors between indoor and outdoor units.
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the
current Canadian Electrical Code (CEC).
Outdoor Unit
• Refer to unit nameplate for minimum circuit ampacity and maximum over-current protection size
• Make all electrical power wiring connections at the out­door unit
Be sure to reattach all electrical box covers after con­nections are complete
Indoor Units
Refer to the installation instruction included with the indoor unit for further details.
17
IMPORTANT
All diagrams (Figure 23 through Figure 33) are typical wiring diagrams. Refer to the wiring diagram on the unit for actual
wiring.
From Power
Supply
208/230V Outdoor Unit
Terminal Block
2(A)
1(A)
L2
3(A)
Outdoor Unit
Figure 21. Connection Diagram - Systems 30k and Below
1(B)
2(B)
3(B)
208/230V Indoor Unit B
Terminal Block
1 2 3
Indoor Unit B
208/230V Indoor Unit A
Terminal Block
1 2 3
Indoor Unit A
From Power
Supply
L2
To Indoor Unit A
208/230V Outdoor Unit
Terminal Block
1(A)
3(A)
2(A)
1(B)
3(B)
2(B)
To Indoor Unit B
Outdoor Unit
Figure 22. Connection Diagram - Systems 36k and Above
1(C)
2(C)
To Indoor Unit C
1(E)
3(E)
1(D)
3(C)
2(E)
3(D)
2(D)
208/230V Indoor Unit
Terminal Block
1 2 3
208/230V Indoor Unit
Terminal Block
1 2 3
Indoor Unit E
Indoor Unit D
18
CN6
INDOOR COIL OUTLET TEMP.SENSOR
OUTDOOR
T4
TEMP. SENSOR OUTDOOR
T3
L-OUT
2
CN38
COIL TEMP. SENSOR
T5
COMPRESSOR DISCHARGE TEMP.
CN11
CN12
RED
BLUE
CN39
BLACK
RED
L2
L1
BLUE
BROWN
2(A)
1(A)
BLACK
BLUE
BROWN
BLACK
1(B)
3(B)3(A)
2(B)
4 WAY VALVE
PAN HEATER
CRANKCASE HEATER
B
A
Figure 23. MPA018S4M-*P Outdoor Unit Wiring Diagram
L-PRO LOW PRESSURE SWITCH
2
H-PRO HIGH PRESSURE SWITCH
INDOOR COIL OUTLET TEMP.SENSOR
RED
YELLOW
4
C
CN11
CN12
RED
BLUE
B A
ELECTRONIC EXPANSION VALVE
OUTDOOR
T4
TEMP. SENSOR OUTDOOR
T3
COIL TEMP. SENSOR
T5
COMPRESSOR DISCHARGE TEMP.
CN38
6
ELECTRONIC
6
EXPANSION VALVE
6
Figure 24. MPA030S4M-*P Outdoor Unit Wiring Diagram
BLACK
RED
BLUE
BLACK
BROWN
3(A)
1(A)
L2
2(A)
BROWN
1(B)
BLACK
BLUE
2(B)
3(B) 3(C)
BLUE
BLACK
BROWN
1(C)
2(C)
PAN HEATER
CRANKCASE HEATER
4 WAY VALVE
19
BLACK
W
RED
COMP
V
BLUE
Y/G
U
DRIVER BOARD
YELLOW
L
CODE PART NAME
COMP
H-PRO
EEV
FM1
HEAT_Y
HEAT_D
COMPRESSOR
HIGH PRESSURE SWITCH
ELECTRIC EXPANSIVE VALVE
OUTDOOR DC FAN
CRANKCASE HEATER
PAN HEATER
BLACK
RED
BLUE
BLUE
BLUE
YELLOW
CN54
CN51
CN53
CN52
CN7
W
V
U
L-PRO
CN5 5
RED
BLACK
L
T5
SV
T3
T4
7
4-WAY1
SV
BLUE
BLUE
HEAT_Y
HEAT_D
T3
T4
H-PRO
L-PRO
PART NAMECODE
PFC INDUCTOR
LOW PRESSURE SWITCH
COMPRESSOR DISCHARGE TEMP.
4-WAY VALVE
CONDENSER TEMPERATURE SENSOR
OUTDOOR AMBIENT TEMPERATURE SENSOR
TP
FM1
CN12 CN11
6
CN20
CN3
ORANGE
CN4
CN10
ORANGE
ORANGE
ORANGE
CN8
CN9
7
CN7
CN33
CN22
CN40
CN44
MAIN BOARD
BLACK
CN5
RED
CN6
P-1
Y/G
CN1
CN2
RED
BLACK
A
CN21
B
CN17
C
CN18
D
CN2 9
CN30
CN2 7
CN2 8
M
6
M
6
M
EEV
6
M
indoor coil outlet temp. sensor
BLACK
BLUE
Y/G
W
V
RED
V
U
COMP
IPM & PFC BOARD
CN15
U
CN55
W
CN14
RED
BLUE
CN39
DCFAN2
Figure 25. MPA036S4M-*P Outdoor Unit Wiring Diagram
YELLOW
YELLOW
CN2
CN5
CN6
MAIN BOARD
D C
CN30
CN26
6
6
ELECTRONIC EXPANSION VALVE C
L
B
CN23
6
ELECTRONIC EXPANSION VALVE B
A
CN15
6
ELECTRONIC EXPANSION VALVE A
P-6
T2B-A B C D E
E D B A
INDOOR COIL OUTLET TEMP. SENSOR
CN13
C
P-4
P-5
CN13
CN16
CN21
CN29
CN37
BLACK
CN3
CN1
BLACK
E
3
D
3
C
3
B
3
A
3
9NC
YELLOW
01NC
RED
CN8
T5
CN9
Ferrite bead
CH3
D
BLACK
12
4
RED
CH2
CN8
CN6
CN3
Ferrite bead
7
CN7
5
CN11
5
BLACK
RED
3
5
BLACK
CH1
5
Ferrite bead
CT1
CN39
CN4
DCFAN1
BLUE
C N1 7
C N1 8
BLUE
C N2 4
C N2 5
C N1 9
C N2 0
E
CN33
6
ELECTRONIC
ELECTRONIC
EXPANSION
EXPANSION
VALVE E
VALVE D
HEA T_Y
HEA T_D
4-W AY
SV
WHITE
T4 T3
Y/G
BLACK
BLUE
BROWN
BLACK
BLUE
BROWN
BLACK
BLUE
BROWN
BLACK
BLUE
BROWN
BLACK
BLUE
BROWN
H-PRO
L-PRO
XT3
XT2
XT1
CODE
LPPUS REWOP Y
COMP
2L
1L
3(E)
2(E)
TO E
1(E)
3(D)
2(D)
TO D
1(D)
3(C)
2(C)
TO C
1(C)
3(B)
2(B)
TO B
1(B)
3(A)
2(A)
TO A
1(A)
CT1
D
DCFAN1,DCFAN2
HEAT_Y
HEAT_D
H-PRO
L
L-PRO
SV
T5
T3
T4
PART NAME
COMPRESSOR
AC CURRENT DETECTOR
DIODE MODULE
OUTDOOR DC FAN
CRANKCASE HEATER
PAN HEATER
HIGH PRESSURE SWITCH
PFC INDUCTOR
LOW PRESSURE SWITCH
4-WAY VALVE
DISCHARGE TEMP. SENSOR
OUTDOOR COIL TEMP. SENSOR
OUTDOOR TEMP. SENSOR
Figure 26. MPA048S4M-*P Outdoor Unit Wiring Diagram
20
INDO OR COI L OUTL ET TEMP. SENSOR
BR OW N
BL UE
HE AT 1
HE AT 2
RE AC TO R
BL UE
BL UE
OUTDOOR TEMPERATURE SE NSOR OUTDOOR COIL TEMPERATURE SENSOR
REACT0R2 R05094A
WHITE
WHITE
6
3
3
6
1(A)
3(A)
L2
2(A)
L1
BLACK
BLUE
BROWN
BLACK
BLUE
BROWN
BLACK
RED
1(B)
2(B)
3(B)
COMPRE SSOR DI SCHARG E TEMPER ATURE SENSOR
Figure 27. MPB018S4M-*P Outdoor Unit Wiring Diagram
HEAT1
SV
HEAT2
WHITE
WHITE
6
BLACK
BLUE
BROWN
BLACK
RED
L2
BROWN
BROWN
BLUE
BLUE
BLACK
BLACK
1(A)
3(A)
2(A)
1(B)
3(B)
2(B)
1(C)
2(C)
3(C)
3
3
6
6
CRANKCASE HEATER
PAN HEATER
Figure 28. MPB030S4M-*P Outdoor Unit Wiring Diagram
21
CO MP
FM 1
MAIN B OA RD
RED
BL ACK
U
V
W
Y/G
Y/G
L
L-PRO
T3
T4
H-PRO
Y/G
TP
V
U
CN19
CN51
CN55
W
EXV
BLACK
DRIVER BOARD
RED
7
7
YELLOW
BLUE
P-1
CN53
CN3
CN4
CN10
CN40
CN22
CN44
C N8
C N9
CN7
C N2
C N1
CN5
CN54
CN52
CN33
CN6
SV
4-WAY VALVE
BLUE
BLUE
HEAT_2
HEAT_1
BLACK
RED
BLUE
BLUE
BLUE
YELLOW
RED
BLACK
RED
BLACK
CN20
M
6
A
CN21
M
6
B
CN17
M
6
C
CN18
M
6
D
CN30
C N2 9
C N2 8
C N2
7
CODE PART NAME
COMPRESSOR
HEAT _2
4-WAY VALVE
COMP
EXV
ELECTRIC EXPANSIO N VALVE
H-PRO
L-PRO
LOW PRE SSURE SWITCH
HIGH PRESSURE SWIT CH
T3
T4
OUTDOOR COIL TEMPERATU RE SENSOR
OUTDOOR TEMPERAT URE SENSOR
PAN HEAT ER
SV
L
PFC INDUCTOR
T2B
INDOOR COIL OUTLET TEMPERAT URE SENSOR
TP
COMPRESSOR D ISCHARGE TEMPERAT URE SENSOR
FM1
OUTDOOR DC FAN
PART NAMECODE
BLUE
BLUE
RDE
BLACK
BLACK
RDE
EXV
EXV
EXV
HEAT _1
CRANKCAS E HEAT ER
Figure 29. MPB036S4M-*P Outdoor Unit Wiring Diagram
DR IV ER B OA RD
CODE
PART NAME
COMPRESSOR
D
HEAT _1
CT1
AC CURRENT DETECTOR
4-WAY VALVE
COMP
EXV
ELECTRIC EXPANSIO N VALVE
H-PRO
L-PRO
LOW PRESSURE SWITCH
HIGH PRESSURE SWITCH
T3
T4
OUTDOOR COIL TEMPERATU RE SENSOR
OUTDOOR TEMPERAT URE SENSOR
CRANKCAS E HEATER
DIODE MODULE
SV
L
PFC INDUCTOR
TP
COMPRESSOR DISCHA RGE TEMP ERATURE SENS OR
MAIN BOARD
FM1, FM2
OUTDOOR DC FAN
L2
L1
XT 1
D
12
3
4
5
P5
CN37
FAN1
RED
CN4
CN2
CN3
CN1
CO MP
U
V
W
Y/G
CN6
CN9
10
3
CN1
CN2
L
YELLOW
YELLOW
U
V
W
BLUE
BLACK
RED
Y/G
XT 2
XT 3
PO WE R S U PP LY
CN29
CN21
CN16
CN13
RED
BLACK
BLACK
RED
BLACK
P9
CH1
CT1
FM 2
FM 1
Y/G
Y/G
DC MOT OR DR IV ER B OA RD
CON1
FAN1
CN1
FAN2
3
3
P6
2
CN6
CN3
CN19
CN20
CN24
CN25
CN17
CN18
HEAT_2
HEAT_1
SV
4-WAY VALVE
BLUE
BLUE
ORAN GE
ORA NGE
RED
BLACK
CH2
CH2
CH2
~
~
~
Y/G
Y/G
HEAT_2
PAN HEATER
T2B
INDOOR COIL TEMPER ATUR E SENSOR
XT
TERMINAL STRIP
Figure 30. MPB048S4M-*P Outdoor Unit Wiring Diagram
22
INDUCTOR 1R25027
D R IV E R B O A R D
INDOOR COIL OUTLET TEMP SENSOR
OUTDOOR TEMP SENSOR
OUTDOOR TEMP SENSOR
COMPRESSOR DISCHARGE TEMP SENSOR
E X V
E X V
GN D P-1
SV
HE A T _1
4 WAY
CR A N K C AS E
VALVE
HE A T ER
INDUCTOR 2R0509A
Figure 31. MLA018S4M-*P Outdoor Unit Wiring Diagram
HE A T _1
HE A T _2
HE A T _2 PAN HE A T ER
TE M P. S EN S O R
IN D O O R C O IL O U T L ET
HEAT_1
CRANKCASE HEATER
HEAT_2
Figure 32. MLA030S4M-*P Outdoor Unit Wiring Diagram
COMPRESSOR DISCHARGE TEMP. SENSOR
OUTDOOR COIL TEMP. SENSOR
OUTDOOR TEMP. SENSOR
INDOOR COIL OUTLET TEMP. SENSOR
23
GN D P-1
HE A T _2
HE A T _1
IND O O R C OIL OU T L ET TE M P. S EN SO R
Figure 33. MLA036S4M-*P Outdoor Unit Wiring Diagram
HE A T _1
HE A T _2
AC CURRENT DETECTOR
PAN HEATER
COMPRESSOR DISCHARGE TEMP. SENSOR
OUTDOOR COIL TEMP. SENSOR
OUTDOOR TEMP. SENSOR
INDOOR COIL OUTLET TEMP. SENSOR
Unit Start-Up
IMPORTANT
Units should be energized 24 hours before unit start-up to prevent compressor damage as a result of slugging.
1. Inspect all factory-installed and eld-installed wiring for loose connections.
2. Verify that the manifold gauge set is connected.
3. Add additional refrigerant charge if required before opening valves and while system is still under a vacuum.
4. Open the liquid and gas line master valves and each
individual port’s service valve to release the refrigerant
charge contained in outdoor unit into the system.
5. Replace the stem caps and tighten to the value listed
in “Table 1. Torque Requirements” on page 5.
6. Check voltage supply at the outdoor unit terminal strip. The voltage must be within the range listed on the
unit’s nameplate. If not, do not start the equipment
until you have consulted with the power company and the voltage condition has been corrected.
7. Refer to the included user guide to operate the system using the provided remote control.
8. Visually check for binding of both indoor and outdoor fans.
Refrigerant Charge
The outdoor unit is factory-charged with refrigerant. Calculate the additional refrigerant required according to the length of the liquid pipe (one way) between the outdoor unit and indoor unit connections.
Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced performance.
Table 6. Refrigerant Charge
System
Two-port 50 ft. (15 m)
Three­port
Four-port 100 ft. (30 m)
Five-port 125 ft. (38 m)
Pre-charge Pipe Length
75 ft. (23 m)
Amount of Refrigerant to add
0.16 oz ((L1 ft + L2 ft) - 50 ft)
0.005 kg ((L1 m + L2 m) - 15 m)
0.16 oz ((L1 ft + L2 ft + L3 ft) - 75 ft)
0.005 kg ((L1 m + L2 m + L3 m) - 23
m)
0.16 oz ((L1 ft + L2 ft + L3 ft + L4 ft)
- 100 ft)
0.005 kg ((L1 m + L2 m + L3 m + L4 m) - 30 m)
0.16 oz ((L1 ft + L2 ft + L3 ft + L4 ft +
L5 ft) - 125 ft)
0.005 kg ((L1 m + L2 m + L3 m + L4 m + L5 m) - 38 m)
24
Loading...