2016 Lennox Industries Inc.
Dallas, Texas, USA
Table of Contents
General ...........................................................................1
Included Parts.................................................................2
Model Number Identication ...........................................3
Indoor / Outdoor Unit Match-Ups....................................4
Typical System Components ..........................................5
System Dimensions ........................................................6
Outdoor Units................................................................6
Indoor Units ..................................................................7
System Clearances ........................................................9
Outdoor Unit .................................................................9
Indoor Unit ....................................................................9
Torque Requirements for Caps and Fasteners.............10
Indoor Unit Installation ..................................................10
Unit Placement Considerations ..................................10
Installation of Cassette Base ......................................10
Installation of M33 Cassette Cover Panel...................11
Indoor Unit Condensate Piping Connections ..............13
Outdoor Unit Installation ...............................................13
Placement Considerations ..........................................13
Direct Sunlight, Rain, Snow and Ice Protection ..........14
Prevailing Winds .........................................................15
Buried Refrigerant Pipe Protection .............................15
Outdoor Unit Condensate Piping ................................15
Securing the Outdoor Unit ..........................................16
Refrigerant Piping Connections ....................................17
Leak Test and Evacuation ............................................18
Leak Test ....................................................................18
Triple Evacuation Procedure .......................................18
Wiring Connections ......................................................19
Outdoor Unit ..............................................................19
Indoor Unit ..................................................................19
Unit Start-Up .................................................................27
Adding Refrigerant for Longer Line Set ........................27
Troubleshooting ............................................................28
Test Run .......................................................................28
Pre-Checks .................................................................28
Procedure ...................................................................28
Dry Mode Operation (Dehumidication) .......................28
Procedure ...................................................................28
Sequence of Operation ...............................................28
INSTALLATION
INSTRUCTIONS
MLA/MPA/MPB and
M22A/M33A/M33B Series
SINGLE-ZONE MINI-SPLIT SYSTEMS
(208/230V) --
Cassette-Mounted Indoor Unit
507546-06
10/2017
Supersedes 10/2016
THIS MANUAL MUST BE LEFT WITH THE OWNER
FOR FUTURE REFERENCE
WARNING
Improper installation, adjustment, alteration, ser vice or
maintenance can cause property damage, personal
injury or loss of life.
Installation and service must be performed by a li censed
professional HVAC installer (or equivalent) or a service
agency.
WARNING
The clean Air Act of 1990 bans the intentional venting of
refrigerant (CFCs, HCFCs, and HFCs) as of July, 1992.
Approved methods of recovery, recycling or reclaiming
must be followed. Fines and/or incarceration may be
levied for non-compliance.
WARNING
This product contains a chemical known to the State
of California to cause cancer, birth defects, or other
reproductive harm.
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and wear gloves and
protective clothing.
General
Refer to the Product Specications bulletin (EHB) for more
product information.
These instructions are intended as a general guide and
do not supersede local or national codes in any way.
Authorities having jurisdiction should be consulted before
installation.
The M22A, M33A and M33B ceiling cassette indoor units
are matched with an outdoor heat pump unit to create a
mini-split system that uses HFC-410A refrigerant.

Included Parts
Package 1 of 1 contains the following:
1 - Assembled Indoor Unit
The assembled indoor unit will include the following items:
Parts Figure Quantity Parts Figure Quantity
M0STAT60Q-1
Wireless controller
Wireless control
holder with 2
mounting screws
Batteries (AAA) 2
1
1
Installation and owner’s
manual
Paper template for
installation
1 ea.
1
1 - Assembled Outdoor Unit and the following items:
Parts Figure Quantity Parts Figure Quantity
Drain connector 1 Seal ring 1
2

Model Number Identication
CASSETTE NON-DUCTED INDOOR UNITS
M 22 A 012 S 4 - 1 P
Series Type
M = Mini-Split
Unit Type
22 = 2x2 Cassette Non-Ducted Unit
33 = 3x3 Cassette Non-Ducted Unit
Major Design Sequence
A = 1st Generation
B = 2nd Generation
Nominal Cooling Capacity
OUTDOOR HEAT PUMP UNITS
Series Type
M = Mini-Split
009 = .75 tons
012 = 1 tons
018 = 1.5 tons
024 = 2 tons
036 = 3 tons
048 = 4 tons
M P A 009 S 4 S - 1 P
Voltage
P = 208/230V-1 phase-60hz
Minor Design Sequence
1 = 1st Revision
2 = 2nd Revision
Refrigerant Type
4 = HFC-410A
Cooling Efciency
S = Standard Efciency
Voltage
P = 208/230V-1 phase-60hz
Unit Type
L = Low Ambient Heat Pump
P = Heat Pump
Major Design Sequence
A = 1st Generation
B = 2nd Generation
Nominal Cooling Capacity
009 = 0.75 tons
018 = 1.5 tons
030 = 2.5 tons
012 = 1 tons
024 = 2 tons
036 = 3 tons
048 = 4 tons
Minor Design Sequence
1 = 1st Revision
Refrigerant Circuits
S = Single Circuit
Refrigerant Type
4 = HFC-410A
Cooling Efciency
S = Standard Efciency
3

Indoor / Outdoor Unit Match-Ups
Outdoor Unit Indoor Unit Match-Up Voltage
MPA009S4S-*P M22A009S4-*P 208/230V
MPA012S4S-*P M22A012S4-*P 208/230V
MPA018S4S-*P M22A018S4-*P 208/230V
MPA024S4S-*P M33A024S4-*P 208/230V
MPA036S4S-*P M33A036S4-*P 208/230V
MPA048S4S-*P M33A048S4-*P 208/230V
MPB009S4S-*P M22A009S4-*P 208/230V
MPB012S4S-*P M22A012S4-*P 208/230V
MPB018S4S-*P M22A018S4-*P 208/230V
MPB024S4S-*P M33A024S4-*P 208/230V
MPB036S4S-*P M33A036S4-*P 208/230V
MPB048S4S-*P M33B048S4-*P 208/230V
MLA009S4S-*P M22A009S4-2P 208/230V
MLA012S4S-*P M22A012S4-2P 208/230V
MLA018S4S-*P M22A018S4-2P 208/230V
MLA024S4S-*P M33A024S4-2P 208/230V
4

Typical System Components
Indoor unit wiring connections
(under access plate)
Decorative panel
Indoor Unit
MPORTANT - Condensate drain line must always
be located at the bottom of the
bundle.)
Wiring
Condensate drain line
(wrapped in foam insulation)
Refrigerant Line Set, Condensat e Line
And Indoor / Outdoor Cable
(field-provided)
Line set
(wrapped in foam insulation)
Communication cable
036 and 048 only
Tape
Supply Air
Filter
Return Air
Supply Air
Wireless Remote
Control
Outdoor Unit
009-036 shown
Utility
Bundle
Access cover
for valves
UV-rated tape (field-provided)
IMPORTANT - The refrigerant
metering device for this system is
located in the outdoor unit. This
makes it necessary to insulate the
refrigerant lines individually to
prevent sweating.
208/230V Outdoor Unit
1 2 3 L1 L2
Access cover for power
and control wiring
connections
Condensate drain line
(field-provided)
To Indoor
Unit
Communication Cable
036 and 048 only
TO INDOOR COMM. BUS
NOTEφ
Terminal Block
To Power
LEY WO
L
ARG
Y
S2
S1
XT2
Use 2-conductor
shielded wire
Supply
Liquid and vapor shut off valves
Figure 1. Typical System Shown
5

System Dimensions
A
E
D
B
C
TYPICAL APPEARANCE OF UNITS
Outdoor Units
Table 1. Outdoor Unit Dimensions - Inches (mm)
Model
MPA009S4S-*P
MPA012S4S-*P
MPA018S4S-*P
MPA024S4S-*P
MPA036S4S-*P
MPA048S4S-*P
MPB009S4S-*P
MPB012S4S-*P
MPB018S4S-*P
MPB024S4S-*P
MPB036S4S-*P
MPB048S4S-*P
Unit of
Measurement
inches 33-1/4 21-5/8 22 11-3/8 12-3/4
mm 845 549 559 289 324
inches 36-1/8 22 27-1/2 12-3/4 13
mm 918 559 699 324 330
inches 40-5/8 25-1/4 31-7/8 15-1/8 16
mm 1032 641 810 384 406
inches 40-1/4 25 53-3/4 15-3/8 16
mm 1023 635 1365 391 406
inches 33-1/8 19-1/8 21-7/8 11-7/8 11-3/4
mm 842 486 556 302 298
inches 34-1/4 20-1/4 21-7/8 13-1/8 13-3/8
mm 870 514 556 333 340
inches 36 21-1/4 27-5/8 14-1/4 13-3/4
mm 914 540 702 362 349
inches 37-1/4 26-1/2 31-7/8 16-3/8 15-7/8
mm 1032 673 810 416 403
inches 41-1/8 25 52-1/2 16-3/8 15-7/8
mm 1045 635 1334 416 403
A B C D E
MLA009S4S-*P
MLA012S4S-*P
MLA018S4S-*P
MLA024S4S-*P
inches 34-1/4 20-1/4 21-3/4 12-1/4 13-3/8
mm 870 514 552 3 11 594
inches 36 21-1/4 27-5/8 13-3/4 16
mm 914 540 702 349 406
inches 40-3/4 26-1/2 31-7/8 15-1/8 16
mm 1035 673 810 384 406
6

System Clearances
Outdoor Unit
12
(305)
Indoor Unit
24 (610)
24
(610)
1
Minimum rear clearance can be 6 inches (152 mm) when mounted on brackets
and with no obstructions on the other three sides.
Figure 4. Outdoor Unit Clearances - inches (mm)
79
(2007)
Air Outlet
36”
(914 mm)
Air Inlet
1
12
(305)
INSTALLATION
HANGERS
LEVELING
ADJUSTMENT
NUT (4)
CEILING
OUTLET
AIR
DIFFUSER
PANEL
AIR
AIR
INLET
23-5/8 (600)
(Ceiling Opening)
OUTLET
Minimum Clearance from Structural Ceiling to Drop Ceiling:
M22A009, M22A012, M22A018, M33A024 -- 10-1/4” (260 mm)
M33A036, M33A048, M33B048 -- 13” (330 mm)
Minimum Clearance to Floor - 98-1/2” (2500 mm)
Figure 5. Indoor Unit Clearances - inches (mm)
36”
(914 mm)
36”
(914 mm)
36”
(914 mm)
9