Sequence of Operation ...............................................28
INSTALLATION
INSTRUCTIONS
MLA/MPA/MPB and
M22A/M33A/M33B Series
SINGLE-ZONE MINI-SPLIT SYSTEMS
(208/230V) --
Cassette-Mounted Indoor Unit
507546-06
10/2017
Supersedes 10/2016
THIS MANUAL MUST BE LEFT WITH THE OWNER
FOR FUTURE REFERENCE
WARNING
Improper installation, adjustment, alteration, ser vice or
maintenance can cause property damage, personal
injury or loss of life.
Installation and service must be performed by a li censed
professional HVAC installer (or equivalent) or a service
agency.
WARNING
The clean Air Act of 1990 bans the intentional venting of
refrigerant (CFCs, HCFCs, and HFCs) as of July, 1992.
Approved methods of recovery, recycling or reclaiming
must be followed. Fines and/or incarceration may be
levied for non-compliance.
WARNING
This product contains a chemical known to the State
of California to cause cancer, birth defects, or other
reproductive harm.
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and wear gloves and
protective clothing.
General
Refer to the Product Specications bulletin (EHB) for more
product information.
These instructions are intended as a general guide and
do not supersede local or national codes in any way.
Authorities having jurisdiction should be consulted before
installation.
The M22A, M33A and M33B ceiling cassette indoor units
are matched with an outdoor heat pump unit to create a
mini-split system that uses HFC-410A refrigerant.
Included Parts
Package 1 of 1 contains the following:
1 - Assembled Indoor Unit
The assembled indoor unit will include the following items:
PartsFigureQuantityPartsFigureQuantity
M0STAT60Q-1
Wireless controller
Wireless control
holder with 2
mounting screws
Batteries (AAA)2
1
1
Installation and owner’s
manual
Paper template for
installation
1 ea.
1
1 - Assembled Outdoor Unit and the following items:
PartsFigureQuantityPartsFigureQuantity
Drain connector1Seal ring1
2
Model Number Identication
CASSETTE NON-DUCTED INDOOR UNITS
M 22 A 012 S 4 - 1 P
Series Type
M = Mini-Split
Unit Type
22 = 2x2 Cassette Non-Ducted Unit
33 = 3x3 Cassette Non-Ducted Unit
Major Design Sequence
A = 1st Generation
B = 2nd Generation
Nominal Cooling Capacity
OUTDOOR HEAT PUMP UNITS
Series Type
M = Mini-Split
009 = .75 tons
012 = 1 tons
018 = 1.5 tons
024 = 2 tons
036 = 3 tons
048 = 4 tons
M P A 009 S 4 S - 1 P
Voltage
P = 208/230V-1 phase-60hz
Minor Design Sequence
1 = 1st Revision
2 = 2nd Revision
Refrigerant Type
4 = HFC-410A
Cooling Efciency
S = Standard Efciency
Voltage
P = 208/230V-1 phase-60hz
Unit Type
L = Low Ambient Heat Pump
P = Heat Pump
Major Design Sequence
A = 1st Generation
B = 2nd Generation
Nominal Cooling Capacity
009 = 0.75 tons
018 = 1.5 tons
030 = 2.5 tons
012 = 1 tons
024 = 2 tons
036 = 3 tons
048 = 4 tons
Minor Design Sequence
1 = 1st Revision
Refrigerant Circuits
S = Single Circuit
Refrigerant Type
4 = HFC-410A
Cooling Efciency
S = Standard Efciency
3
Indoor / Outdoor Unit Match-Ups
Outdoor UnitIndoor Unit Match-UpVoltage
MPA009S4S-*PM22A009S4-*P208/230V
MPA012S4S-*PM22A012S4-*P208/230V
MPA018S4S-*PM22A018S4-*P208/230V
MPA024S4S-*PM33A024S4-*P208/230V
MPA036S4S-*PM33A036S4-*P208/230V
MPA048S4S-*PM33A048S4-*P208/230V
MPB009S4S-*PM22A009S4-*P208/230V
MPB012S4S-*PM22A012S4-*P208/230V
MPB018S4S-*PM22A018S4-*P208/230V
MPB024S4S-*PM33A024S4-*P208/230V
MPB036S4S-*PM33A036S4-*P208/230V
MPB048S4S-*PM33B048S4-*P208/230V
MLA009S4S-*PM22A009S4-2P208/230V
MLA012S4S-*PM22A012S4-2P208/230V
MLA018S4S-*PM22A018S4-2P208/230V
MLA024S4S-*PM33A024S4-2P208/230V
4
Typical System Components
I
Indoor unit wiring connections
(under access plate)
Decorative panel
Indoor Unit
MPORTANT - Condensate drain line must always
be located at the bottom of the
bundle.)
Wiring
Condensate drain line
(wrapped in foam insulation)
Refrigerant Line Set, Condensat e Line
And Indoor / Outdoor Cable
(field-provided)
Line set
(wrapped in foam insulation)
Communication cable
036 and 048 only
Tape
Supply Air
Filter
Return Air
Supply Air
Wireless Remote
Control
Outdoor Unit
009-036 shown
Utility
Bundle
Access cover
for valves
UV-rated tape (field-provided)
IMPORTANT - The refrigerant
metering device for this system is
located in the outdoor unit. This
makes it necessary to insulate the
refrigerant lines individually to
prevent sweating.
208/230V Outdoor Unit
1 2 3 L1 L2
Access cover for power
and control wiring
connections
Condensate drain line
(field-provided)
To Indoor
Unit
Communication Cable
036 and 048 only
TO INDOOR COMM. BUS
NOTEφ
Terminal Block
To Power
LEY WO
L
ARG
Y
S2
S1
XT2
Use 2-conductor
shielded wire
Supply
Liquid and vapor shut off valves
Figure 1. Typical System Shown
5
System Dimensions
A
E
D
B
C
TYPICAL APPEARANCE OF UNITS
Outdoor Units
Table 1. Outdoor Unit Dimensions - Inches (mm)
Model
MPA009S4S-*P
MPA012S4S-*P
MPA018S4S-*P
MPA024S4S-*P
MPA036S4S-*P
MPA048S4S-*P
MPB009S4S-*P
MPB012S4S-*P
MPB018S4S-*P
MPB024S4S-*P
MPB036S4S-*P
MPB048S4S-*P
Unit of
Measurement
inches33-1/421-5/82211-3/812-3/4
mm845549559289324
inches36-1/82227-1/212-3/413
mm918559699324330
inches40-5/825-1/431-7/815-1/816
mm1032641810384406
inches40-1/42553-3/415-3/816
mm10236351365391406
inches33-1/819-1/821-7/811-7/811-3/4
mm842486556302298
inches34-1/420-1/421-7/813-1/813-3/8
mm870514556333340
inches3621-1/427-5/814-1/413-3/4
mm914540702362349
inches37-1/426-1/231-7/816-3/815-7/8
mm1032673810416403
inches41-1/82552-1/216-3/815-7/8
mm10456351334416403
ABCDE
MLA009S4S-*P
MLA012S4S-*P
MLA018S4S-*P
MLA024S4S-*P
inches34-1/420-1/421-3/412-1/413-3/8
mm8705145523 11594
inches3621-1/427-5/813-3/416
mm914540702349406
inches40-3/426-1/231-7/815-1/816
mm1035673810384406
6
Indoor Units
DRAIN
CONNECTION
GAS
PIPE
LIQUID
PIPE
SIDE VIEW
10-3/8
(264)
LEFT SIDE VIEW
INSTALLATION
HANGERS
LEVELING
ADJUSTMENT
NUT (4)
CEILING
Fresh Air Intake
(NOTE - Not Used)
AIR
OUTLET
21-1/2 (546)
22-1/2 (572)
BOTTOM VIEW (Body)
DIFFUSER
PANEL
AIR
INLET
23-5/8 (600)
(Ceiling Opening)
SIDE VIEW
20-5/8
(524)
AIR
OUTLET
RIGHT SIDE VIEW
22-1/2
(572)
25-1/2
(648)
Figure 2. M22A Indoor Cassette Unit Dimensions - inches (mm)
25-1/2 (648)
BOTTOM VIEW (Panel)
7
LEFT SIDE VIEW
GAS
PIPE
LIQUID
PIPE
Fresh Air Intake
(NOTE - Not Used)
26-3/4 (679)
30-3/4
(781)
A
33-1/8
(841)
DRAIN
CONNECTION
RIGHT SIDE VIEW
AIR
OUTLET
37-3/8
(949)
33-1/8 (841)
BOTTOM VIEW (Body)
DIFFUSER
PANEL
SIDE VIEW
AIR
INLET
AIR
OUTLET
Size
0248-1/8206
0369-5/8244
04811-1/4286
A
in.mm
Figure 3. M33A and M33B Indoor Cassette Unit Dimensions - inches (mm)
37-3/8 (949)
BOTTOM VIEW (Panel)
8
System Clearances
Outdoor Unit
12
(305)
Indoor Unit
24 (610)
24
(610)
1
Minimum rear clearance can be 6 inches (152 mm) when mounted on brackets
and with no obstructions on the other three sides.
Figure 4. Outdoor Unit Clearances - inches (mm)
79
(2007)
Air Outlet
36”
(914 mm)
Air Inlet
1
12
(305)
INSTALLATION
HANGERS
LEVELING
ADJUSTMENT
NUT (4)
CEILING
OUTLET
AIR
DIFFUSER
PANEL
AIR
AIR
INLET
23-5/8 (600)
(Ceiling Opening)
OUTLET
Minimum Clearance from Structural Ceiling to Drop Ceiling:
When servicing or repairing HVAC components, ensure
the fasteners are appropriately tightened. “Table 1. Torque
Requirements” on page 10 provides torque values for
fasteners.
IMPORTANT
Only use Allen wrenches of sufcient hardness (50Rc
- Rockwell Harness Scale minimum). Fully insert the
wrench into the valve stem recess.
Service valve stems are factory-torqued from 9 ft.-lbs.
(12 N) for small valves, to 25 ft.-lbs. (34 N) for large
valves) to prevent refrigerant loss during shipping and
handling. Using an Allen wrench rated at less than 50Rc
risks rounding or breaking off the wrench, or stripping
the valve stem recess.
See the Lennox Service and Application Notes C-08-1
for further details and information.
Table 1. Torque Requirements
Parts
Service valve cap8 ft.-lb.11
Sheet metal screws16 in.-lb.2
Machine screws #1027 in.-lb.3
Compressor bolts7 ft.-lb.10
Gauge port seal cap8 ft.-lb.11
Recommended Torque
U.S.Newton-Meter- N
Indoor Unit Installation
CAUTION
In order to avoid injury, take proper precaution when
lifting heavy objects.
Unit Placement Considerations
AVOID
Do not install the unit in the following locations:
• Areas exposed to petrochemicals or petrochemical
products
• Areas exposed to salt or other corrosive materials or
caustic gases
• Areas exposed to extreme voltage variations (such as
factories
• Tightly enclosed areas that may impede service of the
unit
• Areas exposed to fossil fuels (such as oil or gas in
kitchens)
• Areas exposed to strong electromagnetic forces
• Areas exposed to acids or alkaline detergents
DO
• Place the unit so that it is not exposed to direct sunlight
• Ensure the structural ceiling can support the weight of
the unit
• Select a location where the condensate line will have
the shortest run to a suitable drain per local codes.
• Allow sufcient space around unit for proper operation
and maintenance
• Install unit a minimum of 3 feet (1m) away from any
antenna, power cord (line) radio, telephone, security
system, or intercom. Electrical interference and radio
frequencies from any of these sources may affect operation
• Be sure to instruct customers how to properly operate the unit (especially maintenance of air lter, and operation procedure) by having them carry out operations
themselves while looking at the manual provided with
the controller
Installation of Cassette Base
It is important to place the cassette unit in the center of the
area that is being conditioned. This will provide the best air
distribution.
1. If the unit is to be installed in an application that
includes a drop-down tile ceiling, remove the ceiling
tiles necessary to accommodate installation of the
four-way cassette. Before removing the drop ceiling
support grid, use a plumb line or laser device to
identify the center point of the structural ceiling. Make
sure that the ceiling is supported before removing any
of the support grid. It may be necessary to add extra
support to maintain the structural integrity of the drop
ceiling.
2. If the unit is to be installed in an application that includes
a sheet rock (plasterboard) ceiling, the installation site
must be carefully measured and the sheet rock must
be cut to accommodate the cassette unit. First, identify
the center point of the installed cassette. Use a plumb
line to transfer the center mark to the oor for future
use. Use the provided template to mark the area of the
required opening. Carefully cut the required opening.
Make sure that the removal of the required ceiling
support does not affect the structural integrity of the
ceiling. It may be necessary to add extra support.
3. Use the unit as a template or use the provided paper
template to mark the location of the hanging brackets
on the oor. Use a plumb line or a laser to transfer the
bracket positions to the main structural ceiling.
4. Make sure that the structural ceiling is able to support
the weight of the cassette unit. It may be necessary to
add extra support. If the structural ceiling is constructed
of concrete, install anchors to accept four ⅜” threaded
rods to suspend the cassette base. If the structural
ceiling includes wooden joists, use angle iron or a
10
LATCH RELEASE
BUTTONS
45º
Press latch release
buttons at the same
time to release latch.
Tilt return air grille outward,
then, lift to remove grille
from panel.
CORNER ACCESS
COVER
Remove screws and loosen
straps to remove corner
covers from panel.
Unistrut channel xed securely in place to accept the
ANGLE IRON
BOLTED IN
PLACE ACROSS
WOODEN JOISTS
WOODEN JOIST
⅜” THREADED
ROD
ANGLE IRON
ACROSS
WOODEN JOISTS
ANCHOR
CONCRETE CEILING
USING ANCHORS
⅜” THREADED
ROD
⅜” threaded rods.
5. Slide one nut and one washer onto each threaded rod.
Use electrical tape to keep the washer from failing off.
Position the nuts slightly above the nal resting place
of the four suspension brackets.
Figure 6. Suspending Methods
6. Use either a mechanical lifting device or a minimum
of two people to raise the unit and insert the threaded
rods into the suspension brackets on the cassette
base. Slide a washer and then a nut onto each rod
below each suspension bracket. Use the leveling nut
(beneath suspension bracket) to adjust the cassette
base to the correct height. Remove the electrical
tape holding the upper washers and nuts in place
and tighten each of the four nuts above the brackets
down onto the brackets. This will ensure that the unit
remains level.
7. If the unit is being installed in an application that
includes a sheet rock (plasterboard) ceiling, it is
recommended to install an access panel in a suitable
location to allow nal connection of the refrigerant
piping, condensate line and electrical connections.
This will also allow access for future maintenance. If
this is not possible, make nal connections before
installing cassette cover panel.
Installation of M33 Cassette Cover Panel
IMPORTANT
Do not place the cover panel with the diffusers face down
on the oor or other surface. Louvers will be damaged if
pressure is applied to them.
1. Carefully remove the cassette cover panel from its
protective packaging and place the panel diffuserside-out on a clean, level surface.
2. Press the two grille latch release buttons at the same
time to release the grille as illustrated in “Figure 8.
Remove Return Air Grille”. Tilt the return air grille
outward at a 45º angle and lift the grille away from
the panel. Carefully place the return air grille off to the
side.
Figure 8. Remove Return Air Grille
3. Remove access covers from each corner of the panel.
⅜” THREADED
ROD
CASSETTE BASE
L
DROP CEILING
⅜” to ½”
LEVELING NUT
Figure 7. Suspending Hardware
SUSPENSION
BRACKET
Figure 9. Remove Corner Covers
11
REFRIGERANT
≥7/8 (22 mm)
5-3/4 (146)
⅜”
THREADED
ROD
CASSETTE
UNIT BASE
COVER PANEL
CEILING
LEVELING
NUT
air out
5/32-1/4 (4-6 mm)
CASSETTE BASE
CEILING
FOAM
INSULATION
COVER PANEL
SUPPLY AIR
LOUVER
FOAM
INSULATION
Side View Cutaway
1-7/8 (48 mm)
PIPING CONNECTIONS
CONDENSATE
DRAIN
CONNECTION
PANEL
HANGER
DETAIL B
CASSETTE BASE
HOOK
DETAIL A
DETAIL C
to make sure that the panel is properly aligned with the
cassette base.
MOTORS
d
COVER PANELLOUVER SWING
COVER PANEL
SECURING
SCREW
PHILLIPS
SCREWDRIVER
Figure 10. Install Cover Panel
4. Position the ceiling panel so that the arrow on the
panel is aligned with the arrow sticker on the cassette
base (both arrow stickers should be on the same side
of the cassette base).
NOTE: If the panel and the base are not properly aligned,
the airow will be blocked and the harness plugs
from the panel to the cassette base will not be long
enough to plug together.
5. Place the cover panel hangers on the two corners with
the louver swing motors. Place these two hangers
on the corresponding hooks on the corners of the
cassette base. See detail A in “Figure 10. Install Cover
Panel”. Then, place the other hangers from the other
two corners over their corresponding hooks on the
cassette base as shown in detail B in “Figure 10.
Install Cover Panel”.
6. Connect the six-pin harness plugs from each of the
two swing motors to the matching six-pin plugs from
the control box in the cassette base.
7. Connect the black harness from the display on the
cover panel to the corresponding black plug from the
control box in the cassette base.
8. Connect the black two-pin plug from the temperature
sensor to the corresponding black plug from the
control box in the cassette base.
9. Tighten the provided screws in the bracket in the cover
panel immediately below each panel hanger. See
detail C in “Figure 10. Install Cover Panel”. Adjust the
cover panel by turning slightly clockwise, if necessary,
Figure 11. Cover Panel in Place
11. Continue to tighten the cover panel securing screws
until the insulation between the cover panel and the
cassette base has been compressed to approximately
¼” (6 mm). The cover panel must form a seal with
the ceiling and the cassette base around the entire
perimeter of the unit.
LOOSEN UPPER NUT
CORNER PANEL
TIGHTEN LOWER NUT
Figure 12. Adjust Unit Height through Corner Panel
12. If it is necessary to adjust the cassette height after the
cover panel has been installed, access the leveling nut
through the removable access cover on each corner.
13. The return air grille must be reinstalled on the cover
panel. Align the four tabs on the grille with the four
slots in the cover panel. Tilt the panel back into place.
Press the opposite side of the cover gently until the
latches engage.
12
Indoor Unit Condensate Piping Connections
IMPORTANT
Make sure that drain piping is properly routed and
insulated to prevent both leaks and condensation.
1. Use a eld-provided hose clamp to secure the drain
line stub on the side of the cabinet to a eld-supplied
1-inch (25 mm) drain line.
NOTE: Take care not to over-tighten the hose clamps this
may damage the drain line stub.
NOTE: Connection between stub and drain line must be
watertight. Apply non hardening plumbing joint
compound if needed to ensure a watertight seal.
2. Conrm proper slope (not less than 1/4 inch per foot
(18 mm per m)) and routing of condensate lines to
ensure moisture is drained away from the indoor unit.
3. Drain should be as short as possible and should
not have any droops or kinks that would restrict
condensate ow and shall be approved resistant pipe.
There must be a 2-inch (51 mm) space between the
end of the condensate drain and the nal termination
point (ground, open drain, etc.) to ensure that the line
will drain freely.
4. After the system installation is complete, the
condensate drain line must be checked for leaks and
proper drainage. If a eld-provided condensate pump
has been installed, it must be checked to ensure proper
operation. This check is part of the start-up process
which must be done by the installing contractor.
IMPORTANT
Drain should have a slope of at least ¼ inch per foot and
should be approved corrosion-resistant pipe. You must
conrm operation of every drain and pump in the system
as part of the commissioning procedure.
7-7/8in.
2~3-15/16 in.
Cassette
Unit
Drain
(slope of at least ¼ inch per foot)
Max. 27-1/2"
3 ft. (1 m)
SUPPORT
STRAPS
Figure 14. Indoor Unit Condensate Drain
Outdoor Unit Installation
CAUTION
In order to avoid injury, take proper precaution when
lifting heavy objects.
Placement Considerations
Consider the following when positioning the unit:
• In coastal areas or other places with salty atmosphere
of sulfate gas, corrosion may shorten the life of the
unit. In coastal areas, the coil should be cleaned with
potable water several times per year to avoid corrosive
buildup (salt)
• Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent
property, not from the property where the unit is installed. Install the unit as far as possible from the property line
• When possible, do not install the unit directly outside
a window. Glass has a very high level of sound transmission.
• Install unit level
Cassette Base
Drain Pan
Pour water
here for test
Drain Plug
Figure 13. Test Condensate Drain
Cap
(Remove for test)
Building Structure
Ground
Level
Figure 15. Install Unit Level
• Choose a place solid enough to bear the weight and
vibration of the unit, where the operation noise will not
be amplied
• Choose a location where the hot air discharged from
the unit or the operation noise will not be a nuisance
to neighbors
• Avoid installing the outdoor unit near a bedroom or
other places where noise may cause a problem
13
• There must be sufcient space to carry the unit into
Protective canopy
Air Inlet
Air Outlet
and out of the site
• There must be unobstructed air ow around the air inlet and the air outlet
• The unit must not be installed in areas where a ammable gas leak may occur
• Install the outdoor unit a minimum of 3 feet (1m) away
from any antenna, power cord (line), radio, telephone,
security system, or intercom. Electrical interference
and radio frequencies from any of these sources may
affect operation
• Since water drains from the outdoor unit during various stages of operation, do not place anything which
may be damaged by moisture under the unit
Direct Sunlight, Rain, Snow and Ice Protection
• If the outdoor unit is subjected to prolong exposure to
direct sunlight with temperatures over 100°F (38°C) a
canopy is recommended as illustrated in “Figure 16.
Outdoor Unit on Pedestal (Stand) and Protective Canopy” or “Figure 21. Dog House-Style Shelter” on page
15.
IMPORTANT
The construction of a canopy or shade is necessary
because of an ambient limit control set to 122°F (50°C)
to protect the electronics. If the outdoor unit is placed in
direct sunlight it is possible that the limit may activate
and shut down the unit.
Protective canopy
24 in
610 mm
12 in
305 mm
Air Inlet
Air Outlet
Pedestal
(stand)
Side View
Front View
Pedestal
(stand)
Figure 16. Outdoor Unit on Pedestal (Stand) and
Protective Canopy
• Place unit away from overhanging roof lines which
would allow water or ice to drop on, or in front of, coil or
into unit. Construct a canopy as illustrated in “Figure
16. Outdoor Unit on Pedestal (Stand) and Protective
Canopy”
• The unit base should be elevated above the depth of
average snows as illustrated in “Figure 17. Outdoor
Unit on Brackets above Snow Line”
• In heavy snow areas, do not place the unit where drifting will occur as illustrated in “Figure 18. Outdoor Unit
Air Flow Obstructed by Snow”
• Carefully consider how to manage defrost water disposal to prevent ice from blocking walkways or creating a safety hazard near the outdoor unit as illustrated
in “Figure 19. Avoid Defrost Water Ice Hazard”
Figure 17. Outdoor Unit on Brackets above Snow
Line
12 in
79 in
2007 mm
Air Outlet
305 mm
Air Inlet
Figure 18. Outdoor Unit Air Flow Obstructed by
Snow
14
12 in
305 mm
24 in
610 mm
NOTE - Minimum clearances shown.
24 in
610 mm
12 in
305 mm
Figure 19. Avoid Defrost Water Ice Hazard
Prevailing Winds
Normally wind bafes are not required for a outdoor unit.
However, in order to maximize reliability and performance,
the following best practices should be followed.
If unit coil cannot be installed away from prevailing winter
winds, some method of protecting the coil is recommended.
However, minimum clearances as reference in “Figure 4.
Outdoor Unit Clearances - inches (mm)” on page 9
must be observed at all times.
Common application examples are:
• When prevailing winds are from the air inlet side, then
position the wind barrier a minimum of 12 inches (305
mm) from the unit as illustrated in “Figure 20. Wind
Barrier”
• When prevailing wind is into the discharge side, then
position the wind barrier a minimum 79 inches (2007
mm) from the front of the unit as illustrated in “Figure
20. Wind Barrier”
• Outdoor unit can be installed in a dog house style
shelter as illustrated in “Figure 21. Dog House-Style
Shelter”
• Outdoor unit can be installed in a alcove or under a
roof overhang as illustrated in “Figure 22. Unit installed
in Alcove”)
Prevailing Winter Winds from Air Inlet Side
Wind Barrier
Inlet Air
12” (305mm)
Min. Distance
Figure 21. Dog House-Style Shelter
24 in
610 mm
12 in
305 mm
12 in
305 mm
24 in
610 mm
NOTE - Minimum clearances shown.
Figure 22. Unit installed in Alcove
Buried Refrigerant Pipe Protection
• All refrigerant lines must be insulated regardless of if
it is buried
• In addition to insulating each line of piping, buried lines
must rest inside a sealed, watertight conduit
• The conduit must be designed so it cannot collect and
retain water
79” (2007mm)
Discharge Air
Wind Barrier
Prevailing Winter Winds From Air Discharge Side
Min. Distance
Figure 20. Wind Barrier
Outdoor Unit Condensate Piping
Condensate formed during the heating and defrost
processes must be drained from heat pump units. Drain
holes are provided in the base of the units to ensure proper
drainage. Heat pumps must be raised when installed on a
concrete pad or the ground to allow drainage to occur. If
the heat pump unit is installed on wall mounting bracket,
insert the provided drain connector into one of the 1
inch (25 mm) drain holes and attached a eld-provided
insulated drain hose to the connector. Use eld-provided
15
rubber plugs to cover any unused drain holes (see “Figure
23. Condensate Drain” on page 16).
Drain
Connector
Chassis
Condensate Drain
(location varies per model)
Figure 23. Condensate Drain
Securing the Outdoor Unit
Slab or Roof Mounting
Install the unit a minimum of 4 inches (102 mm) above the
roof or ground surface to avoid ice build-up around the
unit. Place the unit above a load bearing wall or area of
the roof that can adequately support the unit. Consult local
codes for rooftop applications.
Four Field-Provided
Anchor Bolts
Figure 25. Securing Outdoor Unit to Rails
Securing Outdoor Unit to Hanging Brackets
If the outdoor unit is installed on eld-provided wall
mounting brackets, use lag bolts or equivalent to secure
the outdoor unit to the bracket. Minimum rear clearance
can be reduced to 6 inches (152 mm) when mounted
on brackets and with no obstructions on the other three
sides. Allow for condensate disposal when placing units
above one another.
6 in
152 mm
Air Inlet
CAUTION
Roof Damage!
This system contains both refrigerant and oil. Some
rubber roong material may absorb oil. This will cause
the rubber to swell when it comes into contact with oil.
The rubber will then bubble and could cause leaks.
Protect the roof surface to avoid exposure to refrigerant
and oil during service and installation. Failure to follow
this notice could result in damage to roof surface.
Securing Outdoor Unit to Slab, Frame, or Rails
If the outdoor unit is installed on a eld-provided slab or
frame, use lag bolts or equivalent to secure the outdoor
unit to the slab or frame.
Air Outlet
Figure 26. Securing Outdoor Unit to Brackets
Four Field-provided Anchor Bolts
Figure 24. Securing Outdoor Unit to Slab
16
Refrigerant Piping Connections
Field piping consists of two copper lines connecting the
outdoor unit to the indoor unit. “Table 2. Refrigerant Piping
and Indoor Unit Connection Sizes”lists the connection
sizes. The connections are made using the provided brass
are nuts at the end of the refrigerant piping connections.
Both lines must be individually insulated.
1. The seal on the unit refrigerant piping connections
should remain in place until the last possible moment.
This will prevent dust or water from getting into the
refrigerant piping before it is connected.
2. CAREFULLY adjust refrigerant piping connections to
suit the application.
3. Slowly loosen one of the are nuts to release the
factory nitrogen charge from the indoor units only.
4. Remove the are nuts from the connections on the
unit and discard the seal from each of the piping
connections.
5. Slide the are nuts onto the ends of the eld-provided
refrigerant piping before using a suitable aring tool to
are the end of the copper pipe.
The compressor in this unit contains PVE
oil (Polyvinylether). PVE oil is formulated for
hydrouorocarbon (HFC) refrigerants, such as HFC-
410A, which this system contains. While it may have
some miscibility properties with mineral-based oil and
POE oil (Polyolester), it is not recommended to mix PVE
oil with any other type of refrigerant oil.
7. Align the threaded connections with the
ared refrigerant lines. Tighten the are nuts
lightly at rst to obtain a smooth match as
illustrated in “Figure 27. Making Connections
(Male to Female Connection)”.
8. Once snug, continue another half-turn on each nut
which should create a leak-free joint. A torque wrench
may be used to tighten are nuts using “Table 3.
Flare Nut Torque Recommendations” on page 17
recommendations. Do not over-tighten a ared joint.
Flared connections should always be accessible
and must be insulated to prevent condensation.
9. After refrigerant piping has been installed and checked
for leaks, apply insulation over all ared connections.
IMPORTANT
Always use two wrenches when tightening are nuts to
avoid twisting refrigerant piping. DO NOT over-tighten
are nuts.
TORQUE WRENCH
TO INDOOR
UNIT
TO OUTDOOR UNIT
Figure 28. Tighten Flare Nut
Table 3. Flare Nut Torque Recommendations
Outside
Diameter
Inches
1/415 ft.-lb. (20 N)1/4 turn
3/826 ft.-lb. (35 N)1/2 turn
1/241 ft.-lb. (56 N)7/8 turn
5/848 ft.-lb. (65 N)1 full turn
Recommended
Torque
No torque wrench available
Finger tighten and use an
appropriately sized wrench to
turn an additional:
BACKUP
WRENCH
17
Table 4. Refrigerant Line Set Requirements
OUTDOOR UNIT
OUTDOOR UNIT
INDOOR UNIT
INDOOR UNIT
Maximum Line Set
Length
Maximum Line Set
Length
Maximum
Elevation -
Outdooor
Unit BELOW
Indoor Unit
Maximum
Elevation -
Outdooor
Unit ABOVE
Indoor Unit
Minimum Line Set
Length - 10 ft. (3m)
Minimum Line Set
Length - 10 ft. (3m)
Outside Unit BELOW Indoor UnitOutside Unit ABOVE Indoor Unit
Do not allow for excess length of line sets to be left rolled up as part of the
required distance, or in general. This will also cause additional performance issues.
IMPORTANT
Each system size has a line set length and vertical elevation parameters.
Line Set Diameters (in.)
System Size (KBtu)
LiquidGas
0091/43/840 (12)40 (12)82 (25)
0121/41/240 (12)40 (12)82 (25)
0181/41/266 (20)66 (20)98 (30)
0243/85/882 (25)82 (25)164 (50)
036/0483/85/898 (30)98 (30)213 (65)
Maximum Elevation
Outdoor Unit BELOW
Indoor Unit - Feet
Leak Test and Evacuation
2. Open valve on nitrogen cylinder.
3. Pressurize the system per the pressure test
Air and moisture remaining in the refrigerant system will
have undesirable effects as indicated below:
4. Check that the system pressure remains stable. If
• Pressure in the system rises
• Operating current rises
5. After the system is found to be free of leaks:
• Cooling or heating efciency drops
• Moisture in the refrigerant circuit may freeze
• Water may lead to corrosion of parts in the refrigeration system
The line set between the indoor and outdoor units
must be leak tested and evacuated to remove any noncondensables and moisture from the system.
Use only oxygen-free nitrogen (OFN).
Leak Test
Use the following procedure to test for system leaks:
1. Connect the manifold gauge set and dry nitrogen gas
IMPORTANT
• When the system pressure is reduced to normal, dis-
1344303Minimum of 10 minutes
2152201517Minimum of 10 minutes
3324703241Minimum of 10 minutes
4456504482
5324703241
cylinder to the liquid and gas service ports.
(Meter)
Maximum Elevation
Outdoor Unit ABOVE
Indoor Unit - Feet
(Meter)
Maximum Line
Set Length - Feet
(Meters)
specications in “Table 5. Pressure Test Specications”.
there is any movement check system for leaks.
• Close valve on nitrogen cylinder
• Relieve the nitrogen pressure by loosening the
charge hose connector at the nitrogen cylinder
connect the hose from the cylinder.
Table 5. Pressure Test Specications
BarPsigkPaDuration
1 hour. Stress test to prove the
integrity of the complete installation.
24 hours. Lower system pressure
test, after conrmation No. 4 was
successfully completed.
18
Triple Evacuation Procedure
208/230V Outdoor Unit
Terminal Block
From Power
Supply
1 2 3 L1 L2
Terminal Block
1 2 3
208/230V Indoor Unit
Outdoor Unit Indoor Unit
A Micron or Torr gauge must be used for this procedure.
1. Discharge the oxygen-free nitrogen and evacuate the
system to a reading of 8000 Microns (8 Torr) using all
service valves.
2. Break the vacuum by allowing nitrogen into the port
connections (liquid line and gas line pipes) until a
positive pressure is achieved.
3. Evacuate the system to a reading of 5000 Microns (5
Torr).
4. Break the vacuum by allowing nitrogen into the port
connections (liquid line and gas line pipes) until a
positive pressure is achieved
5. Evacuate the system to a minimum reading of 500
Microns (0.5 Torr).
6. For a moisture-free system, ensure the vacuum is held
without movement for a minimum of 4 hours.
7. If vacuum fails to hold, carry out steps 2 through 6 until
vacuum holds.
Wiring Connections
IMPORTANT
Install unit so that unit disconnect is accessible.
Use specied wiring and cable to make electrical
connections. Clamp cables securely and make sure that
connections are tight to avoid strain on wiring. Insecure
wiring connections may result in equipment failure and
risk of re.
Wiring must be installed so that all cover plates can be
securely closed.
• Refer to unit nameplate for minimum circuit ampacity
and maximum over-current protection size
• Make all electrical power wiring connections at the outdoor unit
• Be sure to reattach all electrical box covers after connections are complete
Indoor Unit
• All indoor units are powered by the outdoor unit
• Communication Wiring (Indoor Units 30K and Below):
Use one stranded 4-conductor wire to provide power
and communication
• Communication Wiring (Indoor Units 36K and Above):
Use one stranded 3-conductor wire to provide power
and one stranded 2-conductor wire to provide communication
• Use minimum of 18 GA stranded wiring
NOTE: When installing a condensate pump, wire in-line
with the CN5 oat switch
WARNING
Electric Shock Hazard. Can cause injury or death. Unit
must be rounded in accordance with national and local
codes.
Line voltage is present at all components when unit is
not in operation. Disconnect all remote electric power
supplies before opening access panel. Unit may have
multiple power sources.
CAUTION
All terminal connections must be made as illustrated
in the following diagrams. Improperly connected wiring
could damage unit or cause communication errors
between indoor and outdoor units.
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the
current Canadian Electrical Code (CEC).
Refer to unit nameplate for minimum circuit ampacity and
maximum over-current protection size.
Outdoor Unit
Figure 29. Single Zone Wiring
IMPORTANT
This unit must be properly grounded and protected by a
circuit breaker. The ground wire for the unit must not be
connected to a gas or water pipe, a lightning conductor
or a telephone ground wire.
Do not connect power wires to the outdoor unit until
all other wiring and piping connections have been
completed.
Do not install the unit near a lighting appliance that
includes a ballast. The ballast may affect remote control
operation.
IMPORTANT
All diagrams (Figure 31 through Figure 43) are typical
wiring diagrams. Refer to the wiring diagram on the unit
for actual wiring.
19
208/230V Outdoor Unit
TO OUTDOOR UNIT
Power Terminal Block
L1 L2
From Power
Supply
Communication Terminal Block
Outdoor Unit
S1 S2
208/230V Outdoor Unit
Power Terminal Block
L1 L2
208/230V Indoor Unit
Power Terminal Block
L1 L2
CommunicationTerminal Block
Indoor Unit
E Y XYQS1E P
S2
Outdoor Unit
Figure 30. Single Zone Wiring 36K & 48K Only
TO PROGRAMMABLE
WIRED CONTROLLER
4
Note: The programmable
wired controller and regular
wired controller use the same
wiring connector.
P5
CN1 5
M
5
Motor
2
CN13
M
PU MP
2
CN5
W ATE R L E VE L S W IT CH
TO WIRED
CONTROLLER
2
D IS P LA Y
B O A R D
2
CN 40
10
CN 10 A
CN 10
INDOOR UNIT
MAINBOARD
CN3
E Y X
Indoor Unit
Alarm
Output
Remote
Control
5
Note1: Remove the JR6 jumper
for remote o n /off contr ol
ALA RM
JR6
ON - OFF
CN23
CN3 3
CN1
C N 1 1 0
JR6
P1
CN6
4
INDOOR COIL TEMP.SENSOR
BL A C K
ROO M T EMP .SEN SOR
WH ITE
T2
T1
NOTE:
COMPONENT IN DASH
LINE IS OPTIONAL
OR FIELD WIRING.
Figure 31. M22A009S4-*P, M22A012S4-*P, M22A018S4-*P, M33A024S4-*P Unit Wiring Diagram
To LVM
Comm.Bus
123
20
Y E L L O W
R E D( B R O W N)
B L U E (B L A C K )
Y/G
Note1:remove the JR6 jumper for
remote on/off control
• • • • •
COMPONENT IN DASH
LINE IS OPTIONAL
OR FIELD WIRING.
FAN
M
Remote
Control
Alarm
Output
Note: The
programmable
wired controller
and regular
wired controller
use the same
wiring con nector
INDOOR UNIT
5
O N - OF F
JR6
C N 23
A L A R M
E Y X
CN 1 5
JR6
C N 33
CN3
To LVM
Comm.Bus
MAIN BOARD
CN2
Q E P
S1
S2
Ferr ite b e ad
To O UTDOO R
Comm .Bus
CN13
CN40
CN10(CN10A)
CN5
CN1
R E D( B R O WN )
B L U E( B L A C K )
L1
L2
CN7
CN6
P4
Y/G
2
PUMP
2
10
DISPLAY
BOARD
INDOOR COIL OUTLET TEMP.SENSOR
4
BLACK
WHITE
P1
Y/G
POWER
M
4
PROGRAMMABLE
2
CONTROLLER
5
CON TRO LLE R
INDO OR C OIL T EMP .SENS OR
ROO M T EMP .SEN SOR
WA TE R L EV E L S WIT C H
TO
WIRED
TO WIR E
T2B
T2
T1
Figure 32. M33A036S4-*P, M33A048S4-*P and M33B048S4-*P Unit Wiring Diagram
OR
CN9-1
WHITE
REACTOR
COMPRESSOR
BLACK
CN28
CN32-1
WHITE
CN29
RED
BLUE
CN30
CN7
3
DC-FAN
COMPRESSOR
DISCHARGE TEMP. SENSOR
CN3
CN22
Y/G
COIL TEMP. SENS
OUTDOOR
CN21
OUTDOOR TEMP. SENSOR
6
CRANKCASE
4-WAY
VALVE
BLUE
BROWN
1
HEATER
PAN
HEATER
2
YELLOW
BLUE
RED
3
L2
Y/G
CN31
CN26
CN27
CN16
CN1
CN2
CN33
Y/G
Figure 33. 208/230V MPA009S4S-*P and MPA012S4S-*P Outdoor Unit Wiring Diagram
21
OUT DOOR
FAN
3
CN414
CRANKCASE HEATER
4-WAY VALVE
RED
Y/G
BLACK
YELLOW
Y/G
RED
CN6
BLUE
CN3
CN4
CN8
CN7
CN2
CN6-1
Y/G
CN15
CN18
RY1
OUTDOOR
MAIN
PCB
6
OUTDOOR TEMP.SENSOR
L-OUT
WHITE
CN1
O U TD OO R C O IL
TE M P.
CN14
BLACK
CN13
CN12
BLUE
RED
BLACK
CN10
COMPRESSOR
U
V
W
1
2
3
TEMP.SENSOR
BLUE
RED
BLACK
W
COMPRESSOR
Figure 34. 208/230V MPA018S4S-*P Outdoor Unit Wiring Diagram
BLUE
BLUE
U
V
Y/G
Compressor
L-OUT
Control Board
2
CN10
BLACK
RED
Y/G
PAN HEATER
Y/G
CRANK CASE HEATER
Figure 35. 208/230V MPA024S4S-*P Outdoor Unit Wiring Diagram
RED
COMPRESSOR DISCHARGE
TEMP.SENSOR
S
YELLOW
BLACK
22
CODEPART NAME
COMP
EXV
FM1
HEAT1
HEAT2
H-PRO
L
L-PRO
SV
T3
T4
COMPRESSOR
ELECTRIC EXPANSION
VALVE
OUTDOOR DC FAN
CRANKCASE HEATER
PAN HEATER
HIGH PRESSURE SWITCH
PFC INDUCTOR
LOW PRESSURE SWITCH
4 WAY VALVE
OUTDOOR COIL TEMP.
SENSOR
OUTDOOR TEMP. SENSOR
W
COMP
Y/G
U
DRIVER BOARD
YELLOW
BLACK
RED
V
BLUE
COMPRESSOR
DISCHARGE
TEMP. SENSOR
EXV
M
FM1
5
CN55
BLACK
RED
BLUE
BLUE
BLUE
YELLOW
CN54
CN51
CN53
CN52
CN19
7
W
V
U
RED
BLACK
4 WAY
SV
VALVE
HEAT1
HEAT2
ORANGE
ORANGE
CN3
CN4
CN10
ORANGE
ORANGE
CN22
CN40
CN44
CN20
CN33
MAIN BOARD
T3
T4
H-PRO
L-PRO
7
CN8
CN9
BLACK
CN5
CN7
CN6
RED
CN34
CN12 CN11
BLACK
CN2
P-1
RED
CN1
Y/G
L
CODE
COMP
CT1
D
DCFAN1,DCFAN2
HEAT_Y
HEAT_D
H-PRO
L
L-PRO
SV
T5
T3
T4
TH
PART NAME
COMPRESSOR
AC CURRENT DETECTOR
DIODE MODULE
OUTDOOR DC FAN
CRANKCASE HEATER
PAN HEATER
HIGH PRESSURE SWITCH
PFC INDUCTOR
LOW PRESSURE SWITCH
4-WAY VALVE
DISCHARGE
TEMP. SENSOR
OUTDOOR COIL
TEMP. SENSOR
OUTDOOR TEMP. SENSOR
HEATSINK TEMP. SENSOR
YELLOW
GRAY
S2
S1
XT2
TO INDOOR COMM. BUS
NOTEP lease use 2-core
shielded wire.
Figure 36. 208/230V MPA036S4S-*P Outdoor Unit Wiring Diagram
YELLOW
L
A
CN15
6
ELECTRONIC
EXPANSION
VALVE A
Y/G
P-6
Compressor and Outdoor
Fan Control Board
W
BLACK
BLUE
V
U
COMP
U
CN55
V
W
RED
Y/G
D
RED
BLUE
CN9
DCFAN2
CN8
BLACK
CN6
CN3
7
CN7
5
CN11
5
DCFAN1
HEAT_Y
HEAT_D
CN15
CN14
RED
CN39
BLACK
12
4
RED
3
5
5
4-WAY
SV
BLACK
BLUE
BLUE
CN4
CN39
CN18
CN25
CN20
CT1
CN2
CH5
CN17
CN24
CN19
YELLOW
CN5
CN6
MAIN BOARD
TO INDOOR UNIT
POWER SUPPLY
CN3
CN1
CN22
CN12
TH
RED
BLACK
( )
2)(1
L1
L2
Y/G
BLACK
WHITE
2
TO INDOOR COMM. BUS
NOTE:
shielded wire.
9NC
T4
T3
YELLOW
01NC
RED
CN8
T5
RED
BLACK
XT1
L1
L2
MAIN
PO W ER S UP PLY
Y/G
BLAC K
RED
LLEY OW
ARG Y
S2
S1
XT2
Please use 2-core
H-PRO
L-PRO
XT1
L2
L1
MAIN
POWER SUPPLY
L2
L2
)
)
2
2
(
(
L1
1
1
( )
( )
TO INDOOR UNIT
XT3
Figure 37. 208/230V MPA048S4S-*P Outdoor Unit Wiring Diagram
23
4-WAY VALVE
OUTDOOR
FAN
CN 7
3
6
CN 31
PAN
HEATER
CN 15
CN 60
CRANKCASE
HEATER
CN 17
BLUE
BROWN
BLACK
3
2
L2
RED
BLUE
Y/G
1
Y/G
CN 21
Y/G
CN 1A
Y/G
Y/G
COMPRESSOR
Y/G
CN 50
3
U
V
W
BLUE
RED
BLACK
EXV
OUTDOOR
MAIN
PCB
OUTDOOR
TEMP. SENS OR
COMPRES S OR
DISCHARGE
T E MP. SE NS OR
OU TDOOR C OIL
T E MP. SE NSO R
RED
BLACK
WHTIE
T5
T4
T3
Figure 38. 208/230V MPB009S4S-*P and MPB012S4S-*P Outdoor Unit Wiring Diagram
Figure 39. 208/230V MPB018S4S-*P and MPB024S4S-*P Outdoor Unit Wiring Diagram
COMPRESSOR
(T4)
(T3)
(T5)
24
CO MP
MAIN B OA RD
R ED
BLACK
U
V
W
Y/G
Y/G
L
L-PRO
T3
T4
CODEPA RT NAME
COMPRESSOR
HEAT 1
4-WAY VALVE
COMP
EXV
ELECTRIC EXPANSIO N
VALVE
H-PRO
L-PRO
LOW PRESSURE SW ITCH
HIGH PRE SSURE SW ITCH
T3
T4
OUTDOOR COIL
TEMPERATURE SENSOR
OUTDOOR
TEMPERATURE SENSOR
CRANKCAS E HEATER
POWER SUPPLY
H-PRO
SV
L
PFC INDUCTOR
T5
T5
COMPRESSOR DISCHARGE
TEMP ERA TURE SENS OR
RED
BLA CK
V
U
CN19
CN51
CN55
W
EXV
BLACK
DRIVER BOARD
RED
7
7
YELLOW
BLUE
P-1
FM1
OUTDOOR DC FAN
CN53
CN20
CN34
CN3
CN4
CN10
CN40
CN22
CN44
C N8
C N9
CN7
CN2
C N1
CN5
CN54
CN52
CN33
5
CN6
SV
4-WAY
VALVE
BLUE
BLUE
HEAT2
HEAT1
BLACK
RED
BLUE
BLUE
BLUE
YELLOW
RED
BLACK
RED
BLACK
TO INDOOR COMM. BUS
XT 2
YE LLO W
GR AY
S1
S2
XT 1
L1
L2
L1
L2
2)(1
()
RED
BLAC K
MAIN
TO INDOOR UNIT
POWER SUPPLY
FM1
Y/G
BLACK
BLACK
RED
RED
HEAT 2
PAN HEAT ER
NOTE: PLEASE USE 2-CORE
SHIELDED WIRE
Figure 40. 208/230V MPB036S4S-*P Outdoor Unit Wiring Diagram
25
DR IV ER B OA RD
CODE
PART NAME
COMPRESSOR
D
HEAT 1
CT1
AC CURRENT DETECTOR
4-WAY VALVE
COMP
EXV
ELECTRIC EXPANSIO N
VALVE
H-PRO
L-PRO
LOW PRESSURE SWIT CH
HIGH PRE SSURE SWITCH
T3
T4
OUTDOOR COIL
TEMPERATURE SENSOR
OUTDOOR
TEMPERATURE SENSOR
CRANKCAS E HEAT ER
DIODE MODULE
SV
L
PFC INDUCTOR
TH
HEATSINK
TEMPERATURE SENSOR
T5
COMPRESSOR DISCHARGE
TEMPERATURE SENSOR
MAIN BOARD
FM1,FM2
OUTDOOR DC FAN
EX V
O
UTDO
OR T E MP
. S E NS OR
O
UTDO OR C O
L
I T EMP .
SE
NSO R
D
12
3
4
5
P5
CN19
CN20
CN24
CN25
CN17
FAN1
CN18
HEAT1
HEAT2
SV
4-WAY
VALVE
BLUE
RED
BLUE
CN4
CN2
CN3
CN1
CO MP
U
V
W
Y/G
CN6
CN9
10
3
CN1
CN2
L
YELLOW
YELLOW
U
V
W
BLUE
BLACK
RED
RED/WIHTE
BLACK
RED
BLACK
CH1
CT1
FM 2
FM 1
Y/G
Y/G
DC MOT OR
DR IV ER B OA RD
CON1
FAN1
CN1
FAN2
3
3
P6
2
CN6
CN3
Y/G
BLACK
TO IND OOR COMM. BUS
XT 2
YE LLO W
GR AY
S1
S2
NOTE: PLEASE USE 2-CORE
SHIELDED WIRE
L2
L1
MAIN
POWER SUPPLY
XT1
TO INDOOR UNIT
L1
Y/G
XT2
1L21
L2
1
NL
N
L
P9
P7
P8
CN22
RED
BLUE/BLACK
ORAN GE
ORA NGE
RED
BLACK
CH2
CH2
CH2
~
~
~
COM PR E S S
OR D SI
CHA RG E
T EMP .
S
E
NS
OR
HEAT 2
PAN HEAT ER
Figure 41. 208/230V MPB048S4S-*P Outdoor Unit Wiring Diagram
Figure 42. 208/230V MLA009, 012 and 018S4S-*P Outdoor Unit Wiring Diagram
26
MAIN BOARD
U
V
W
Y/G
L
L-PRO
T3
T4
CODE
PART NAME
COMPRESSOR
4-WAY VALVE
COMP
CAP1
EEV
ELECTRIC EXPANSION
VALVE
H-PRO
L-PRO
LOW PRESSURE SWITCH
HIGH PRESSURE SWITCH
T3
T4
CONDENSER
TEMPERATURE SENSOR
OUTDOOR AMBIENT
TEMPERATURE SENSOR
H-PRO
SV
L
PFC INDUCTOR
TS
DISCHARGE
TEMPERATURE SENSOR
RED
BLACK
V
U
CN1 9
CN51
CN5 5
W
EEV
BLACK
DRIVER BOARD
RED
YELLOW
BLUE
P-1
FM1
OUTDOOR DC FAN
FAN MOTOR CAPACITOR
CN53
CN20
CN3
CN4
CN10
CN40
CN22
CN44
CN8
CN9
CN7
CN2
CN1
CN5
CN54
CN52
CN33
5(6 )
CN6
SV
4-WAY1
BLUE
BLUE
HEAT2
HEAT1
BLACK
RED
BLUE
BLUE
BLUE
YELLOW
RED
BLACK
RED
BLACK
L2
TO INDOOR U NIT
POWER SU PPLY
Y/G
2
L1
1
RED
RED
BLACK
YELLOW
S
BLACK
YELLOW
Crankcase H eater
Bas e Pan Hea ter
ONLY FOR
36K ODU
L1
L2
FM1
Y/G
3
3
Y/G
COMP
3
Figure 43. 208/230V MLA024S4S-*P Outdoor Unit Wiring Diagram
Unit Start-Up
IMPORTANT
Units should be energized 24 hours before unit start-up
to prevent compressor damage as a result of slugging.
1. Inspect all factory- and eld-installed wiring for loose
connections.
2. Verify that the manifold gauge set is connected.
3. Add additional refrigerant charge if required before
4. Open the liquid and gas line service valves to release
5. Replace the stem caps and tighten to the value listed
6. Check voltage supply at the outdoor unit terminal strip.
7. Refer to the included user guide to operate the system
8. Visually check for binding of both indoor and outdoor
opening valves and while system is still under a
vacuum.
the refrigerant charge contained in outdoor unit into
the system.
in “Table 1. Torque Requirements” on page 10.
The voltage must be within the range listed on the
unit’s nameplate. If not, do not start the equipment
until you have consulted with the power company and
the voltage condition has been corrected.
using the provided remote control.
fans.
Adding Refrigerant for Longer Line Set
The outdoor unit is factory-charged with refrigerant.
Calculate the additional refrigerant required according to
the diameter and the length of the liquid pipe between the
outdoor unit and indoor unit connections.
Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced performance.
Table 6. Additional Refrigerant Charge
System Size
(KBtu)
09>25 (7.5)0.161 oz/ft (15g/m)
12>25 (7.5)0.161 oz/ft (15g/m)
27
18>25 (7.5)0.161 oz/ft (15g/m)
24>25 (7.5)0.322 oz/ft (30g/m)
36>25 (7.5)0.322 oz/ft (30g/m)
48>25 (7.5)0.322 oz/ft (30g/m)
Pipe Length
(feet / meters)
Amount of Refrigerant
to add
Troubleshooting
Table 7. Troubleshooting Codes
Code Description
E0Indoor unit EEPROM error
E1Communication error between indoor unit and outdoor unit
E3Indoor fan speed error
E4Indoor return air temperature sensor error
E5Indoor coil temperature sensor error
ECLow refrigerant
EEHigh water level alarm
F0Outdoor current overload sensed
F1Outdoor ambient temperature sensor error
F2Outdoor coil temperature sensor error
F3Compressor discharge temperature sensor error
F4Outdoor unit EEPROM error
F5Outdoor unit fan speed error
P0Inverter module IPM error
P1High or low voltage protection
P3Outdoor unit low temperature lockout
P4Compressor drive error
--Mode conict
P6Compressor high-pressure or low-pressure switch open
4. Let each function run for 5 minutes, and perform the
following checks:
Table 8. Test Run Checklist
ChecksPassFail
No electrical leakage
Unit is properly grounded
All electrical terminals
properly covered
Indoor and outdoor units are
solidly installed
All pipe connection points do
not leak
Water drains properly from
drain hose
All piping is properly
insulated
Unit performs COOL function
properly
Unit performs HEAT function
properly
Indoor unit louvers rotate
properly
Indoor unit responds to
remote controller
Dry Mode Operation (Dehumidication)
Test Run
Pre-Checks
Only perform test run after you have completed the
following steps:
• Electrical Safety Checks – Conrm that the unit’s
electrical system is safe and operating properly
• Refrigerant Leak Checks – Check all are nut connec-
tions and conrm that the system is not leaking
• Conrm that gas and liquid valves are fully open
Procedure
You should perform the Test Run for at least 30 minutes.
1. Connect power to the unit.
2. Press the ON/OFF button on the remote controller to
turn it on.
3. Press the mode button to scroll through the following
functions, one at a time:
• COOL - Select lowest possible temperature
• HEAT - Select highest possible temperature
Procedure
1. Using the provided wireless remote control, press the
MODE button and select DRY mode.
2. Press the UP/ DOWN button to select the desired
temperature. The temperature setting range is from
62°F (17°C) to 86°F (30°C) in one degree increments.
NOTE: The blower is preset at a low speed and cannot be
changed therefore it will get cold and most likely
will over shoot the temperature setting by 6-10°F
(3-5°C) depending on the room size or other
various factors. Also the Follow Me mode does
not operate in this mode.
NOTE: In addition, the indoor units do not have a humidistat
installed therefore they are unable to determine
humidity levels. This product is not recommend as
a main source for dehumidication.
Sequence of Operation
When in dry mode operation the unit is actually in cooling
mode with a low speed blower operation. Set remote temp
to a lower room temp to begin the dry mode operation.
The compressor will stop when the room temperature is
4°F (2°C) lower than the temperature setting.
However there is a temperature compensation for cooling
mode that is two degrees Celsius. So the unit will stop
when the temperature is 8°F (4°C) lower than the room
temperature settings.
28
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.