Lennox LZP-2 User Manual 2

Page 1
© 2004 Lennox Industries Inc.
Dallas, Texas, USA
Litho U.S.A.
504,926M 5/2004
LZP-2
ZONE CONTROL PANEL
USED WITH LENNOX HEATING AND COOLING EQUIPMENT
Shipping & Packing List
Package 1 of 1 contains the following:
(1) Model LZP-2 Zone Control Panel (1) Model 88K38 Temperature Sensor (1) Installation Instructions (1) Owners Manual (1) Warranty Card
Required Components (ordered separately):
24 VAC Transformer – The size of the transformer
needed is determined by the total power requirements for the control panel, thermostats and dampers. The control panel and thermostats together require 10VA. The dampers require 10VA each. The size of the transformer will depend on the greatest number of dampers that could be energized at any given time.
NOTE – When power closed/spring open dampers are used, at least one zone’s dampers will not be energized during a call for heating or cooling.
Thermostats – single-stage, electronic, 24-volt heat/cool thermostats which include a “C” (24VAC common) terminal. Do not use mechanical or power robbing thermostats.
Dampers – 2 or 3-wire, 24-volt dampers required. 2-wire, power closed/spring open preferred.
ZONING SYSTEM
TABLE 1 – TRANSFORMERS
Part Number Size Voltage Description
10P17 40VA 120/208/240V-24V
10P87 50VA 120/208/240V-24V
12P61 75VA 120/208/240V-24V
83P74 4" Square Electrical Box
FIGURE 1 – LENNOX®MODEL LZP-2 CONTROL PANEL LAYOUT
Page 2
Application
• Two zones
• Single-stage electric or gas furnace
• Single-stage air conditioner
• Multi-stage equipment can be used provided that it stages on it’s own internal controls
• Not applicable to heat pump systems
Installation
• Install the control panel indoors only.
• Do not install the control panel where the tempera­ture will exceed 140°F or will drop below 32°F.
• Do not install the control panel on foundation walls, HVAC equipment or duct system where moisture may condense on the enclosure.
• Do not install the control panel in a room where it will be exposed to elevated humidity levels such as a laundry room.
1. Remove the cover. Replace the cover when
installation is complete.
2. There are eight slots on the base of the enclosure
(see Figure 2).
3. Use #8 screws (field supplied) to install the base.
Features
• Adjustable high and low discharge air temperature limits
• ON/OFF duct air purge control
• LED indicators for outputs
• Time Delay Override
• 2 or 3-wire damper compatibility
FIGURE 2 – CONTROL PANEL AND ENCLOSURE BASE
CAUTION
Electrostatic discharge can damage the control. Touch a grounded metal object before touching the circuit board, and then only touch the circuit board on the edges when handling.
(8) Mounting
Slots
The above illustration shows a typical two zone control system.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer, service agency or the gas supplier.
D1
EQUIP.
W
G
Y
RC
RH
24VAC
R
C
DAS
W
D3
G
D5
Y
K1
J1
K4
K3
J3
J4
R43
R44
C18
R45
RV4
SPARE FUSE
MAIN FUSE
F1
F2
LENNOX
X3785 REV. 1
RV1
+
C5
RV5
LZP-2
D14
D13
D12
R17
D15
R20
D17
SW1
C10
TDO
Y1
C12
C15
RV6
PURGE
HT-160
CL-45
R4
R5
R3
D2
R2
GND
24VDC
C1
NORMAL
FLASHING
+
C3
U1
R10
C7
+
Q1
C8
U2
U6
C16
GAS
C9
R18
R19
ELECT.
NoPURGE
140
40
D11
U3
U4
TP4
R21
R39
R38
R37
C21
C19
C20
+
5VDC
R1
+
D4
R7
D8
D7
R8
D9
D10
+
R12
C6
R13
R11
K2
D19
D18
R23
U5
C13
R40
C22
+
+
R22
D20
R28
R30
D22
D23
+
R36
K5
R35
R41
R42
R47
R46
R6
C2
C4
D6
R14
ZONE 1
J2
Y
R9
R15
R16
RV2
G
R
NO
NC
C
DamperZ1
ZONE 2
J5
DamperZ2
W
Y
G
R
NO
NC
C
W
RV3
D16
C11
R25
R24
R26
R27
C14
R29
D21
C17
R34
R32
R33
R31
RV7
D24
RV8
Page 3
Installation (continued)
FIGURE 3 – DISCHARGE AIR SENSOR LOCATION
IMPORTANT: The discharge air sensor is required.
If a short or open circuit is detected between the Plenum Sensor terminals, the control panel will only respond to Zone 1 and the dampers will stay in the open position.
4. Install and Wire the Discharge Air Temperature Sensor
The tip of the sensor must be located in a region of fully mixed supply of air before the take-offs (not in a dead air space) in order for the system to work correctly.
a. Wire discharge air temperature probe to control
panel using thermostat wire. Note that the temperature sensor is not polarity sensitive.
b. Be sure that the tip of the sensor is located at
least 15 inches downstream from the leaving air side of the evaporator in the discharge plenum, and 1/3 of the depth (D/3) of the plenum (D) from the front of the plenum (the front is the side with the furnace or CB access doors), and centered side to side. Move the adjustable bracket along the length of the discharge air sensor to achieve proper sensor tip location (tip of sensor to be located at W ÷ 2). The sensor can be inserted from any side of the plenum, as long as the tip of the sensor is in the correct position. See Figure 3.
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
CAUTION
Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch.
15"
D/3
D
W
FRONT
Page 4
6. Install the thermostats. Refer to the instructions
provided with the thermostat.
Any 24-volt electronic thermostat with a “C” (24 VAC common) terminal can be used. Power robbing thermostats can cause unintended operation – DO NOT use mechanical or power robbing thermostats. Table 2 lists the required terminals and recommended Lennox thermostats:
18 AWG thermostat wire minimum recommended.
TABLE 2 – THERMOSTAT REQUIREMENTS
Recommended
Type Terminals
Thermostat
HEAT/COOL R, C, W, Y, G
SignatureStat 1H/1C (51M26)
Elite 1H/1C (49M55)
Thermostat Terminal Function
R 24 VAC Hot
C 24 VAC Common
W Heat
Y Cool
GFan
7. Install the dampers. Refer to the instructions provided with the damper.
18 AWG thermostat wire minimum recommended.
Installation (continued)
5. Install the required transformer selected from Table 1
– DO NOT USE the HVAC equipment transformer to power the control panel. Refer to the instructions provided with the transformer.
18 AWG thermostat wire minimum recommended.
Sizing the Transformer:
The system requires approximately 10 VA for the control panel and thermostats and 10 VA for each damper. The size of the transformer will depend on the greatest number of dampers that could be energized at any given time (at least one zone’s dampers will not be energized during a heating or cooling call when using power close, spring open dampers). The size of the transformer must not exceed 75VA. If the value is greater than 75VA, some dampers will need to be powered by a separate transformer – refer to Field Wiring Damper Diagram 2 on page 6.
For instance, if you have 3 dampers, then you would require 10VA for the system, 20VA (10VA X 2) for the dampers for a total of 30VA, so catalog number 10P17 would be an adequate transformer size at 40VA.
The transformers listed in this chart include a plate mount for a 4" square electrical box.
TABLE 1 – TRANSFORMERS
Part Number Size Voltage Description
10P17 40VA 120/208/240V-24V
10P87 50VA 120/208/240V-24V
12P61 75VA 120/208/240V-24V
83P74 4" Square Electrical Box
Loading...
+ 8 hidden pages