Lennox LXRCC20 Application Manual

Providing indoor climate comfort
Application guide
LXRCC20-AGU-0509-E
LXRCC20 Remote control
LXRCC20
for two-pipe fan coil units with electrical heater
Outputs for on / off valve actuator and electrical heater Output for three-speed fan Control depending on the room or return air temperature Automatic heating / cooling changeover Operating modes: normal, energy saving and frost protection mode or OFF Operating mode changeover input for remote control Selectable control parameters Operating voltage AC 230 V
Use
Typical use:
Control of the room temperature in individual rooms that are heated or cooled with
two-pipe fan coil units equipped with an electrical heater.
For opening or closing a valve
for switching an electrical heater
for switching a three-speed fan.
1
Functions
The controller acquires the room temperature with its integrated sensor or external room temperature sensor (QAA32) or external return air temperature sensor (QAH11.1) – if used – and maintains the setpoint by delivering control commands to the 2-point­valve. The switching differential can be 1 or 4 K in heating mode and 0.5 or 2 K in cool­ing mode.
The fan is switched to the selected speed via control output Q1, Q2 or Q3.
When the function “Temperature-dependent fan control“ is activated (can be selected with DIP switch no.1), the fan is switched on / off depending on the temperature, that is, together with the valve.
It is switched off by
leaving the heating or cooling sequence, provided the function “Temperature-
dependent fan control“ is activated, or
manually changing to standby
, provided plant conditions do not call for frost
protection mode, or
activating an external operating mode changeover switch, provided plant conditions
do not call for energy saving or frost protection mode, or
by turning the controller’s power supply off.
To avoid overtemperatures of the electrical heater or to prevent the thermal cutout from responding, the fan will overrun for 30 seconds when the electrical heater is switched off. During that period of time, the fan LED flashes.
In the event of failure, the RCC20 cannot protect the electric heater against overtem­peratures. For this reason, the electric heater must be equipped with a separate safety device (thermal cutout).
The heating or cooling valve receives the OPEN command via control output Y11 when
1. the measured room temperature lies by half the switching differential below the setpoint (heating mode) or above the setpoint (cooling mode), and
2. the valve has been fully closed for more than one minute.
The heating or cooling valve receives the CLOSE command via control output Y11 when
1. the measured room temperature lies by half the switching differential above the setpoint (heating mode) or below the setpoint (cooling mode), and
2. the valve has been fully open for more than one minute.
Note: control output Y12 delivers a control command which is inverted to the
control command at output Y11 and can be used for normally open valves
The RCC20 provides control either depending on to the measured room temperature or depending on the fan coil unit’s return air temperature. Changeover is automatic if a QAH11.1 cable temperature sensor is used.
The water temperature acquired by the changeover sensor (QAH11.1 + ARG86.3) is used by the controller to switch from heating to cooling mode, or vice versa. When the water temperature lies above 28 °C, the controller switches to heating mode, below 16 °C it switches to cooling mode. If, immediately after switching on, the water tempera­ture lies between the 2 changeover points, the controller will start in heating mode. The water temperature is measured at minute-intervals and the operational status updated.
Fan operation
Note
ON
Heating and cooling mode
. . . . .
OFF
Return air tempera­ture
Automatic changeover
2
Loading...
+ 8 hidden pages