Lennox LSBV-4228MN, LSBV-3628MN-H, LSBV-3628MP-H, LSBV-3628EN, LSBV-4228EN-H User Manual

...
INSTALLATION INSTRUCTIONS
CRESTLINE™ SERIES
B-VENTED GAS APPLIANCES P/N 850,042M REV. A 12/2008
LENNOX HEARTH PRODUCTS
This appliance may be installed in an aftermarket perma­nently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
In the Commonwealth of Massachusetts & New York:
Installation must be performed by a licensed plumber or gas fitter. See Table of Contents for location of additional New York & Commonwealth of Massachusetts requirements.
WARNING: IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLO­SION MAY RESULT CAUSING PROPERTY DAM­AGE, PERSONAL INJURY OR LOSS OF LIFE.
Do not store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance.
What to do if you smell gas:
MODELS
Millivolt Models Electronic Models
LSBV-3628MN LSBV-3628EN LSBV-3628MP LSBV-3628EN-H LSBV-3628MN-H LSBV-4228EN LSBV-3628MP-H LSBV-4228EN-H LSBV-4228MN LSBV-4228MP LSBV-4228MN-H LSBV-4228MP-H
Portland
US
AVERTISSEMENT: ASSUREZ-VOUS DE BIEN SUIVRE LES INSTRUCTIONS DONNÉES DANS CETTE NOTICE POUR RÉDUIRE AU MINIMUM LE RISQUE DINCENDIE DEXPLOSION OU POUR ÉVITER TOUT DOMMAGE MATÉRIEL, TOUTE BLESSURE OU LA MORT.
Ne pas entreposer ni utiliser dessence ni d’autre vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
OTL Report No. 116-F-45-5
• DO NOT light any appliance.
• DO NOT touch any electrical switches, do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow your gas suppliers instructions.
• If your gas supplier cannot be reached, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
INSTALLATEUR: Laissez cette notice avec lappareil. CONSOMMATEUR: Conservez cette notice pour consultation ultérieure.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
Ne pas tenter dallumer dappareil.
Ne touchez à aucun interrupteur. Ne pas vous
servir des téléphones se trouvant dans le bátiment où vous vous trouvez.
Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournisseur.
Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le service des incendies.
Linstallation et lentretien doivent être assurés par un installeur ou un service dentretien qualifié ou par le fournisseur de gaz.
A French manual is available upon request. Order P/N 506223-07. Ce manuel dinstallation est disponible en francais, simplement en faire
la demande. Numéro de la pièce 506223-07.
1
TABLE OF CONTENTS
Packaging........................................ page 2
Introduction..................................... page 2
Massachusetts and New York
Requirements ................................ page 2
General Information......................... page 2
Location .......................................... page 3
Appliance Specifications.................. page 4
Clearances ....................................... page 4
Gas Vent Rule.................................. page 4
Framing Specifications .................... page 5
Assembly Steps............................... page 5
Installation....................................... page 6
Vent System Installation.................. page 7
Field Wiring ..................................... page 7
Connecting Gas Line........................ page 8
Outside Air Kit Installation ............... page 8
Log and Rockwool Installation ........ page 9
Appliance Operation ........................ page 10
Manual Limit Switch........................ page 10
Millivolt Appliance Checkout............ page 11
Electronic Appliance Checkout......... page 11
Adjustments .................................... page 11
Finishing Requirements................... page 12
Cold Climate Insulation.................... page 12
Installation Accessories................... page 12
Gas Conversion Kits.................. page 14
This manual is part of a set of two supporting this product. Refer to manual 875,035M for Care & Operations.
Please read and understand these instructions before beginning your
installation.
PACKAGING
The assembled vented gas fireplace is pack­aged with:
1 - one foam packaged log set located in fire-
box area.
2 - one bag of glowing embers (rockwool)
located in the bottom compartment.
2
3 - one envelope containing the literature
package which consists of the homeowner's manual, installation instructions, and war­ranty; envelope is located in the control area.
INTRODUCTION
The millivolt appliances are designed to oper­ate on either natural or propane gas. A millivolt gas control valve with piezo ignition system provides safe, efficient operation.
The electronic appliances are designed to op­erate on either natural or propane gas. An electronic intermittent pilot system provides safe, efficient operation. External electrical power is required to operate these units.
These appliances comply with National Safety Standards and are tested and listed by Omni­Test Laboratories (Report No. 116-F-45-5) to ANSI Z21.50b (in Canada, CSA-2.22b), and CAN/CGA-2.17-M91 in both USA and Canada, as vented gas fireplaces.
Installation must conform to local codes. In the absence of local codes, installation must comply with the current National Fuel Gas Code, ANSI Z223.1 (NFPA 54). (In Canada, the current CAN/CGA B149 installation code.) Elec­trical wiring must comply with local codes. In the absence of local codes, installation must be in accordance with the National Electrical Code, NFPA 70 - (latest edition). (In Canada, the current CSA C22.1 Canadian Electric Code.)
These Crestline series appliances have been designed, tested and listed for use with Security Chimney's 10" B-vent system. Refer to page 12 for a complete listing of the 10" B-vent compo­nents available for use with these models.
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERATION MAY VOID THE WARRANTY, CERTIFICATION AND LISTINGS OF THIS UNIT.
WARNING: IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE. REFER TO THIS MANUAL. FOR ASSISTANCE OR ADDI­TIONAL INFORMATION CONSULT A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER.
Massachusetts And New York City, NY Requirements
These appliances are approved for installation in the following USA locations listed in the following:
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Massachusetts:
Installation of these fireplaces are approved for installation in the US state of Massachu­setts if the following additional requirements are met-
• Installation and repair must be done by a plumber or gas fitter licensed in the Common­wealth of Massachusetts.
• The flexible gas line connector used shall not exceed 36 inches (92 centimeters) in length.
• The individual manual shut-off must be a T­handle type valve.
New York City, NY:
Installation of these fireplaces are approved for installation in New York City in the US state of New York, if the following additional re­quirements are met-
• An outside air kit (FOAK-4 or FOAK-4LD) must be installed.
GENERAL INFORMATION
Note: Installation and repair should be per-
formed by a qualified service person. The appli­ance should be inspected annually by a quali­fied professional service technician. More fre­quent inspections and cleanings may be re­quired due to excessive lint from carpeting, bedding material, etc. It is imperative that the control compartment, burners and circulating air passage ways of the appliance be kept clean.
S'assurer que le brùleur et le compartiment des commandes sont propres. Voir les instruc­tions d'installation et d'utilisation qui accompagnent l'apareil.
Provide adequate clearances around air open­ings and adequate accessibility clearance for service and proper operation. Never obstruct the front openings of the appliance.
WARNING: THESE FIREPLACES ARE VENTED DECORATIVE GAS APPLIANCES. DO NOT BURN WOOD OR OTHER MATE­RIAL IN THESE APPLIANCES.
These appliances are designed to operate on natural or propane gas only. The use of other fuels or combination of fuels will degrade the perfor­mance of this system and may be dangerous.
Input of appliance are 45,000 BTU/HR for Pro­pane models and 50,00 BTU/HR for Natural Gas models.
Gas Orifice Size
Type Elevation
LSBV-3628
LSBV-4228
Natural
#26
#26
Propane
#45
#45
0 - 4500' (0 - 1370 m)
0 - 4500' (0 - 1370 m)
Nominal operating pressures for the manifold side of the gas control system are; 3.5 inches water column (0.87 kPa) for natural gas mod­els and 10 inches water column (2.49 kPa) for propane gas models.
Do not use these appliances if any part has been under water. Immediately call a qualified, pro­fessional service technician to inspect the ap­pliance and to replace any parts of the control system and any gas control which have been under water.
Ne pas se servir de cet appareil s'il a été plongé dans l'eau, complètement ou en partie. Appeler un technicien qualifié pour inspecter l'appareil et remplacer toute partie du système de contrôle et toute commande qui ont été plongés dans l'lau.
This appliance may be installed in an after­market permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not con­vertible for use with other gases, unless a certified kit is used.
Cet appareil peut être installé dans un maison préfabriquée (É.-U. seulement) ou mobile déjà installée à demeure si les réglements locaux le permettent. Cet appareil doit être utilisé uniquement avec les types de gaz indiqués sur la plaque signalétique. Ne pas l'utiliser avec d'autres gaz sauf si un kit de conversion certifié est installé.
The appliance and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at pressures in excess of 1/2 psig (3.5 kPa).
These appliances must not be connected to a chimney or flue serving a separate solid fuel burning appliance.
Do not place clothing or other materials on or near this appliance.
WARNING: FAILURE TO COMPLY WITH THE INSTALLATION AND OPERATING IN­STRUCTIONS PROVIDED IN THIS DOCU­MENT WILL RESULT IN AN IMPROP­ERLY INSTALLED AND OPERATING AP­PLIANCE, VOIDING ITS WARRANTY. ANY CHANGE TO THIS APPLIANCE AND/OR ITS OPERATING CONTROLS IS DANGER­OUS. IMPROPER INSTALLATION OR USE OF THIS APPLIANCE CAN CAUSE SERI­OUS INJURY OR DEATH FORM FIRE, BURNS, EXPLOSION OR CARBON MON­OXIDE POISONING.
Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning are similar to the flu with headaches, dizziness and/or nausea. If you have these signs, obtain fresh air immedi­ately. Turn off the gas supply to the appliance and have it serviced by a qualified profes­sional, as it may not be operating correctly.
WARNING: CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES. USE CAUTION AROUND THE APPLIANCE TO AVOID BURNS OR CLOTHING IGNITION. YOUNG CHILDREN SHOULD BE CARE­FULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE.
WARNING: DO NOT PLACE CLOTHING OR OTHER FLAMMABLE MATERIALS ON OR NEAR THIS APPLIANCE.
AVERTISSEMENT: SURVEILLER LES ENFANTS. GARDER LES VÊTEMENTS, LES MEUBLES, L'ESSENCE OU AUTRES LIQUIDES À VAPEUR INFLAMMABLES LIN DE L'APPAREIL.
WARNING: THIS APPLIANCE MAY ONLY BE FITTED WITH DOORS CERTIFIED FOR USE WITH THE APPLIANCE.
These appliances are equipped with an inte­gral combustion air door and actuator arm. Combustion air kits are optional and must be installed before removing the securing screw allowing the movement of the combustion air actuator arm (see Step 7 on page 8).
LOCATION
Test gage connections are provided on the front of the millivolt gas control valves (identified OUT for the manifold side and IN for inlet pressure side.
Minimum inlet gas pressure to the appliance is
5.0 inches water column (1.24 kPa) for natural gas and 11 inches water column (2.74 kPa) for propane for the purpose of input adjustment.
Maximum inlet gas supply pressure to the appliance is 10.5 inches water column (2.61kPa) for natural gas and 13.0 inches water column (3.23 kPa) for propane. The appliance must be isolated from the gas supply piping sys­tem (by closing its individual manual shut­off valve) during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5) kPa).
WARNING: B-VENT APPLIANCES ARE NOT DESIGNED TO OPERATE IN NEGA­TIVELY PRESSURED ENVIRONMENTS (PRESSURE WITHIN THE HOME IS LESS THAN PRESSURES OUTSIDE). SIGNIFI­CANT NEGATIVELY PRESSURED ENVI­RONMENTS CAUSED BY WEATHER, HOME DESIGN, OR OTHER DEVICES MAY IMPACT THE OPERATION OF THESE AP­PLIANCES. NEGATIVE PRESSURES MAY RESULT IN POOR FLAME APPEARANCE, SOOTING, DAMAGE TO PROPERTY AND/ OR SEVERE PERSONAL INJURY. DO NOT OPERATE THESE APPLIANCES IN NEGA­TIVELY PRESSURED ENVIRONMENTS.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Typical Locations
Figure 1
In selecting the location, the aesthetic and func­tional use of the appliance are primary concerns. However, vent system routing to the exterior and access to the fuel supply are also important. Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies. Consideration should be given to traf­fic ways, furniture, draperies, etc., due to el­evated surface temperatures. The location should also be free of electrical, plumbing or other heating/air conditioning ducting.
3
APPLIANCE SPECIFICATIONS
7-3/32
28-15/32
5-3/4
LSBV-36: 37 LSBV-42: 43
Front View
12-15/32
LSBV-36: 41-3/4 LSBV-42: 47-3/4
41-5/16
47-9/32
52-11/32
The appliance should be mounted on a fully supported base extending the full width and depth of the unit. The appliance may be located on or near conventional construction materi­als. However, if installed on combustible mate­rials, such as carpeting, vinyl tile, etc., a metal or wood barrier covering the entire bottom surface must be used.
These appliances may be used for bedroom installations in the United States and are listed accordingly. These units may not be installed
in bedrooms in Canada.
CLEARANCES
Minimum clearance to combustibles for the ap­pliance is as follows: sides and back - 3/8" (9.52 mm), floor - 0" (0 mm), adjacent wall - 0" (0 mm), ceiling - 37-1/2" (953 mm).
Venting
Gas Vent Rule – Gas vent caps are not permit-
ted within 8 feet (2.4 mm) of a vertical wall or similar obstruction. Gas vent caps that are located 8' or more from a portion of a building which extends at an angle greater than 45° upward from the horizontal may terminate in accordance with that in no case shall any discharge opening on the cap be less than 2' (610 mm) horizontally from the roof surface (National Fuel Gas Code ANSI Z223.1 (NFPA 54) 7.6.2) (CAN/CGA B149).
Table 1 (Figure 3)
, provided
4
Figure 2
Gas Line Or Switch Wire Outlet
8-7/8
Left Side View
8-15/32
1-7/16
LSBV-36: 23-1/2 LSBV-42: 29-1/2
Top View
Combustion
Air Inlet
7-7/16
Junction Box
15-27/32
1-25/32
Gas Line Or Switch Wire Outlet
Location
4-13/32
16-1/16
Right Side View
20-1/32
19/32
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
2-9/32
X
12
Roof Pitch is X/12
Minimum Height from Roof to Lowest Discharge Opening
Figure 3
Minimum Height
from Roof to Lowest
Roof Slope
Discharge Opening
Feet Meters
Flat to 6/12 1' 0" 0.3 Over 7/12 to 9/12 2' 0" 0.6 Over 10/12 to 12/12 4' 0" 1.2 Over 13/12 to 16/12 6' 0" 1.8 Over 17/12 to 21/12 8' 0" 2.4
Note: Venting terminals shall not be recessed into a wall or siding.
Table 1
FRAMING SPECIFICATIONS
ASSEMBLY STEPS
B
A
Fireplace Framing
Figure 4
Back Wall of Chase/Enclosure
Including Finising Materials
Rough Framing Face (Unfinished Shown)
if any
G
HH
Figure 5
Back Wall of Chase/Enclosure Including Finishing Materials if any
G
FATO Adapter
(Optional)
Outside Chase
Figure 6
C
A
Inside Chase
C
A
Header
FOAK
Combustion
Air Kit
Optional Locations
FOAK
Combustion
Air Kit
J
Rough Framing Face
(Unfinished Shown)
Back Wall of Chase/Enclosure Including Finishing Materials
if any
K
Corner Installation
D
C
A E
(Unfinished Shown)
Figure 7
Framing Dimensions
Fireplace Opening Width
LSBV-4228
(1226 mm)
(1344 mm)
(1765 mm)
(1248 mm)
A
B
C
D
E
F
G
H
J
K
LSBV-3628
42-1/4"
(1073 mm)
52-1/2"
(1344 mm)
23-9/16"
(599 mm)
11-1/4"
(286 mm)
63-1/2"
(1613 mm)
31-3/4"
(807 mm)
20-1/2"
(521 mm)
4"
(102 mm)
7-1/2"
(190 mm)
44-3/16"
(1122 mm)
Note: All framing dimensions calcu­lated for 1/2" dry wall at the appliance face. If sheathing the chase or finish­ing with other thickness materials, cal­culations will need to be made.
FOAK-4 Combustion Air Kit
Framing Face
48-1/4"
52-1/2"
29-9/16"
(751 mm)
14-1/4"
(362 mm)
69-1/2"
34-3/4"
(883 mm)
20-1/2"
(521 mm)
4"
(102 mm)
7-1/2"
(190 mm)
49-1/8"
G
Rough
The typical sequence of installation follows, however, each installation is unique resulting in variations to those described.
1. Construct the appliance framing.
F
2. Route gas supply line to appliance location.
3. Position the appliance.
4. Install the vent system and exterior termina-
tion.
5. Field wire and install operating control switch.
6. Make connection to gas supply.
7. Install (optional) outside Air Kit.
8. Install the logs and rockwool.
9. Checkout appliance operation.
10. Adjust burner to ensure proper flame ap-
pearance.
PRE-INSTALLATION NOTES
The fireplace may be installed directly on a combustible floor or raised on a platform of an appropriate height. Do not place fireplace on carpeting, vinyl or other soft floor coverings. It may, however, be placed on flat wood, ply­wood, particle board or other hard surfaces. Be sure fireplace rests on a solid continuous floor or platform with appropriate framing for sup­port and so that no cold air can enter the room from under the fireplace.
The fireplace may be positioned and then the framing built around it, or the framing may be constructed and the fireplace positioned into the opening.
Usually, no special floor support is needed for the fireplace, however, to be certain:
1. Estimate the total weight of the fireplace system and surround materials such as brick, stone, etc., to be installed.
2. Measure the square footage of the floor space to be occupied by the system, surrounds and hearth extensions.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
3. Note the floor construction, i.e. 2 x 6’s, 2 x 8’s or 2 x 10’s, single or double joists, type and thickness of floor boards.
5
4. Use this information and consult your local building code to determine if you need addi­tional support.
If you plan to raise the fireplace and hearth extension, build the platform assembly then position fireplace and hearth extension on top. Secure the platform to the floor to prevent possible shifting.
INSTALLING THE FIREPLACE
Step 1. Construct the Appliance Framing -
Frame appliance enclosure as illustrated in
Figures 4 through 7 Note: The framed depth, 20-1/2" (521 mm)
from a framed wall, must always be measured from a finished surface. If a wall covering such as drywall is to be attached to the rear wall, then the 20-1/2" (521 mm) must be measured from the drywall surface. It is important that this dimension be exact.
If the appliance is to be elevated above floor level, a solid continuous platform must be constructed.
on page 5.
Ensure that a sediment trap is installed in the existing gas line, if not, install a sediment trap upstream to prevent moisture and contami­nants from passing through trap to the appli­ance controls and burners. Failure to do so could prevent the appliance from operating reliably.
An external regulator must be used on all propane (L.P.G.) heaters to reduce the supply tank pressure to 13" w.c. (maximum). Any copper tubing used to supply propane (L.P.G.) from the tank must be internally tinned.
IMPORTANT: HOLD GAS VALVE SECURELY TO PREVENT MOVEMENT WHEN CONNECT­ING TO INLET GAS LINE
WARNING: CONNECTING DIRECTLY TO AN UNREGULATED PROPANE (L.P.G.) TANK MAY CAUSE AN EXPLOSION.
All appliances are equipped with a gas flex line and shutoff valve attached directly to the gas control valve. To quickly and easily complete the gas line routing, use the gas flex line kit.
Step 3. Position the Appliance - Slide the fireplace into prepared framing or position fire­place in its final position and frame later.
Refer to fireplace drawings and specifications on pages 4 and 5 for framing dimensions and details. Framing header may be positioned directly on the fireplace top spacers.
IMPORTANT: UNDER NO CIRCUMSTANCES CAN THE FIREPLACE TOP SPACERS
FIGURE 2 )
BE REMOVED OR MODIFIED, NOR
(refer to
MAY YOU NOTCH THE HEADER TO FIT AROUND OR BE INSTALLED LOWER THAN THE SPACERS. THE HEADER MAY BE IN DI­RECT CONTACT WITH THE TOP SPACERS BUT MAY NOT BE SUPPORTED BY THEM.
Fireplace should be secured to side framing members using the full length 1/2 inch nailing flanges that are integral to the appliance at each side. Use 6d nails or equivalent
(Figure 9 )
.
The header may rest on the top metal spacers, but must not be notched to fit around them.
Consult all local codes. Step 2. Route Gas Supply Line - Route gas
line
(Figure 8 )
using techniques and materi­als prescribed by local and/or national codes. It is recommended that a gas line of 1/2" or greater diameter be used to allow full gas volume to the fireplace. Undue pressure loss will occur if the pipe is too small. The appli­ance, as set up at the factory, is best suited for use with a gas line routed from the left side. The gas line may however be alternately routed from the right side.
This unit is provided with a gas line/switch wire outlet at both sides (see
Figure 2
). The gas line may be routed through this opening at either the right or left side. Route the Millivolt switch wire through the opening opposite form the gas line. To avoid cutting the Millivolt switch wire, do not route the switch wire through the opening with the gas line.
When rigid pipe is used, an ANSI approved manual shut-off valve and union must be in­stalled upstream of the fireplace.
3-1/2"
(79 mm)
10-1/2"
(269 mm)
Figure 8
RIGHT
SIDE
LEFT SIDE
7-1/4"
(184 mm)
3-1/2"
(79 mm)
6d Nail or Equivalent
Figure 9 Note: The nailing flanges and the area directly
behind the nailing tabs are exempt from the clearances described on the fireplace clearance label.
6
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Step 4. Install the Vent System & Exterior Termination -
Slip a 10" (254 mm) B-Vent system over the appliance collar (
Figure 10
) and secure with four sheetmetal screws (# 8 or larger). Minimum overall height of the vent system and appliance must be 12' (3.66 m) vertical (no offset) or 17' (5.18 m) when an offset up to 45 degrees from the vertical is used. The lower part of the offset must not begin less than 3' (0.914 m) above the top of the fireplace
(see Figure 11 )
.
Maximum overall height of the vent system and appliance should not exceed 40 feet (12.19m).
12 ft.
Minimum
17 ft.
Minimum
45 degrees
max.
3 ft.
Minimum
to Offset
10
Type B-Vent
Securing
Screws
Flue Outlet
Collar
Figure 10
Install the B-vent system in accordance with the vent manufacturer's instructions.
CAUTION: THIS APPLIANCE CANNOT BE VENTED HORIZONTALLY.
Note: Refer to the vent manufacturers installa-
tion instructions for variations of venting tech­niques. If common venting of several units is contemplated, it should be discussed with an architect and the local Building Department.
Step 5. Field Wiring – Refer to Section A for millivolt appliances and Section B for electronic appliances.
A. Millivolt Wiring – Units are fitted at the factory with an SIT millivolt gas control valve. The valve has been tested with and approved for use with these appliances and is listed accordingly. Refer to
Figure 12
for the wiring
diagram.
Figure 11
The gas valve has been set in place and has been pre-wired at the factory. Locate the wall switch (not provided) or optional remote control in the desired location and connect the millivolt wire
(see Figure 12 ).
CAUTION: DO NOT CONNECT THE WALL SWITCH TO A 120V POWER SUPPLY.
Note: The ends of the 18' coiled wire must be
connected to the wall switch (not supplied) for the appliance to operate.
B. Electronic Wiring – The electronic appli­ance must be connected to the main power supply. To install, route a 3-wire 120V 60Hz power supply to the appliance junction box and ground.
MILIVOLT WIRING DIAGRAM
WALL MOUNTED ON/OFF SWITCH
BLACK
WHITE
DAMPER SWITCH
Figure 12
Locate and install a low voltage (24V) wall switch (not supplied) in the desired location. Connect the low voltage wire to this switch
(
see Figure 13
on Page 8)
.
IMPORTANT: Ground lead must be con­nected to the green screw located on the outlet box. See
Figure 16
Failure to do so will result in a potential safety hazard. The appliance must be electrically grounded in accordance with local codes or, in the absence of local codes, the National Electrical Code, ANSI/NFPA 70-(latest edition). (In Canada, the current CSA C22-1 Cana­dian Electrical Code.)
THERMOPILE
BLACK
LIMIT SWITCH
BLACK
TP TH
TP
TH
on page 9.
GAS VALVE
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
7
PILOT BURNER IGNITER-SENSOR ASSEMBLY
CONNECTOR
BLUE
GROUND
GREEN
PURPLE
ELECTRONIC IGNITION
CONTROL BOARD
EV2
ORANGE
WHITE
WHITE
EV1
BLACK
GREEN LED
GAS VALVE
WHITE
ELECTRONIC WIRING DIAGRAM
W
Plug blower into this receptacle
Tab Intact
Green Ground Screw
BK
Green
Neutral Side of Receptacle
White
Black
Red
Hot Side of Receptacle
Ta b Broken
TRANSF
120 V.
24 V.
G 120 VAC - Black
Junction Box
r
neerG-dnuo e
-
tihW
lartueN
1. Route a 3-wire 120V 60Hz power supply line
to the appliance junction box wires and ground
(Figures 13 ).
2. After wiring is complete, replace the appli-
ance junction box cover and secure with the hex head screws previously removed.
Step 6. Connecting Gas Line – Make gas line connections. All codes require a shut-off valve mounted in the supply line.
Figure 16
on page 9 illustrates the method for con-
necting the gas supply. The flex-line method utilizing the gas flex line provided with the appliance is acceptable in the U.S., how­ever, Canadian requirements vary depend­ing on locality. Installation must be in com­pliance with local codes.
The gas control valve is located in the lower control compartment. To access the valve remove the refractory access panel and set aside
(Figure 14 ).
The control valve has a
3/8" (10 mm) NPT thread inlet port.
Secure all joints tightly using appropriate tools and sealing compounds (ensure pro­pane resistant compounds are used in pro­pane applications).
Turn on gas supply and test for gas leaks, using a gas leak test solution (also referred to as bubble leak solution).
DAMPER SWITCH
BLACK
WALL MOUNTED ON/OFF SWITCH
SIT Valve Shown
Refractory Access Panel
Figure 14
Note: Using a soapy water solution (50% dish
soap, 50% water) is an effective leak test solution but it is not recommended, because the soap residue that is left on the pipes/ fittings can result in corrosion over time. Never
use an open flame to check for leaks. A. Light the appliance (refer to the lighting
instructions label in the control compartment or in the Homeowner's Care and Operation Instructions).
B. Brush all joints and connections with the gas leak test solution to check for leaks. If bubbles are formed, or gas odor is detected, turn the gas control knob to the “OFF” posi­tion. Either tighten or refasten the leaking connection and retest as described above.
BLACK
LIMIT SWITCH
BLACK
CONNECTOR
C. When the gas lines are tested and leak free,
be sure to rinse off the leak testing solution. Step 7. Optional Outside Air Kits Combus-
tion (outside make-up air) kits, Model FOAK-4 or FAOK-4LD, may used with these appli­ances. Refer to the installation instructions packaged with the air kits for specific installa­tion information. The outside air kit must be installed before the fireplace is framed and enclosed in the finished wall.
Outside air drawn into the fireplace supplies air to the fire for combustion. Only one com­bustion air duct on the right side of the fire­place is necessary if installed.
If additional length of duct is necessary, pur­chase locally available U.L. Class 0 or Class 1 metallic ducting. The duct may extend up to 50' (15.24 m) in any direction.
There is one hand operated air gate shut-off, for utside make-up air, located at the right side of the fireplace opening behind the screen. To open, lift and pull the handle out. The combus­tion air damper should be
fireplace is in use
and, to prevent outside air from entering your home, fully closed when the fireplace is not in operation.
Figure 13
open when the
8
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Note: Supply wires may be alternatively connected to the outlet using the screw terminals, however the black supply wire must be wired to a terminal that is opposite (across the outlet) the point where the white supply wire is connected (Figure 15 ).
Green Wire Ground Connection
White
120 Vac 60 Hz
Red (Supply)
120 Vac 60 Hz
Black (Supply)
(Supply)
Bipolar Terminal Screw
120 Vac 60 Hz
CAUTION: NEVER LOCATE INLET OF AN OUT­SIDE AIR HOOD WHERE IT CAN BE BLOCKED BY SHRUBS, SNOW DRIFTS, ETC. NEVER LOCATE INLET IN GARAGE OR ANY AREA WHERE THERE IS ANOTHER FUEL BURNING APPLIANCE OR PRODUCTS EMITTING COM­BUSTIBLE GASES SUCH AS PAINT, GASO­LINE, ETC. IN COLD CLIMATES, IT IS REC­OMMENDED THE COMBUSTION AIR DUCT BE INSULATED.
Outside combustion air ducting may be run upwards or vertically through framing and ceiling joists, with the hood installed through an outside wall and 3' (1 m) below the termi­nation. Ducting may also be run downward through floor joists and under the home to a ventilated crawlspace not considered part of the living area of the home.
After installing the outside air kit, remove the cover from the shut off lever in the left side of the firebox opening.
Note: Do not terminate combustion air kit in attic space under any circumstances.
Figure 15
Gas Stub
Figure 16
1/2" x 3/8" Flare
Shut-Off Valve
Gas Flex Line (provided)
(Millivolt or Electronic)
3/8" Flex Tubing
Gas Valve
3/8" NPT Flare Fitting (Remove Before Hard Piping)
After completing the installation of the op­tional combustion air vent system the actuator arm must be put in service and tested to ensure proper operation before completing any enclosure around the firebox. Failure to do so may result in extensive and costly rework.
Operate the actuator through several cycles including the closed position. Ensuring proper operation and freedom of movement. Return the actuator arm to the closed position.
Step 8. Installing Logs and Rockwool – The logs are packaged within the firebox. Remove the rockwool from the packaging and tear into dime size pieces (see Homeowners Care and Operation Instructions). Do not use more than is necessary.
Displace Lava Rock to the center of the burner pan when removing and reinstalling the burner tube.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
9
MANUALLY-RESET BLOCKED FLUE SAFETY SWITCH
This appliance is equipped with a manually­reset blocked flue safety switch. Refer to
Figure 19
operation, the flame goes out (independently of the burner on/off wall switch), it may be due to the operation of this safety limit switch. First allow the appliance to cool. Then reset the safety switch by pushing the red reset button.
This reset button is located on the back of the limit switch, between the wire terminals (
Detail A of Figure 19
for its location. If during appliance
see
).
Figure 17
Refer to the Homeowners Care and Operation Instructions for detailed log description and placement instructions. Log set shown in this document of all sets are similar.
APPLIANCE OPERATION Step 9. Checking the System – With gas line
installed run initial system checkout before closing up the front of the unit. Follow the pilot lighting instructions provided in the Homeowner's Care and Operation Instructions. For piezo ignitor location see livolt appliances only).
(Figure 17 )
is typical, installation
Figure 18
(mil-
Note: Instructions are also found on the pull out lighting instructions label attached to the gas control valve.
When first lighting the appliance, it will take a few minutes for the line to purge itself of air. Once purging is complete, the pilot and burner will light and operate as indicated in the in­struction manual.
Subsequent lightings of the appliance will not require such purging. Inspect the pilot flame (remove logs, if necessary, handling carefully).
Figure 19
Detail A
Reset
Button
The appliance should then relight and remain lit. If this does not occur, turn off the appli-
ance and call a qualified service technician.
Wire Terminals
10
Piezo Ignitor
SIT Valve
Figure 18
Lintel Extension
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Manual Reset Limit Switch
Right Side Refractory Panel
Millivolt Appliance Checkout
The pilot flame should be steady, not lifting or floating. Flame should be blue in color with traces of orange at the outer edge.
The top 3/8" (9 mm) at the pilot generator (thermopile) should be engulfed in the pilot flame. The flame should project 1" (25 mm) beyond the hood at all three ports
Hood
Pilot Nozzels
Ignitor Rod
(Figure 20 ).
3/8
" Min
(9 mm)
Figure 20
Replace logs if removed for pilot inspection. To light the burner; rotate the gas valve control
knob counterclockwise to the “ON” position (“ON” will be to the right hand side of the valve). Turn “ON” the remote wall switch.
Electronic Appliance Checkout
To light the burner, turn ‘ON’ the optional remote wall switch. Ensure the ignitor lights the pilot. The pilot flame should engulf the flame rod as shown in
Figure 21.
Hood
Ignitor Rod
Flame
Sensor
Step 10. Adjustments – The following para-
graphs address adjustment concerns and pro­cedures.
Flame Appearance and Sooting
Proper flame appearance is a matter of taste. Generally most people prefer the warm glow of a yellow to orange flame. Appliances operated with air shutter openings that are too large, or with long vertical vent runs, will exhibit flames that are blue and transparent. These weak, blue and transparent flames are termed anemic.
If the air shutter opening is too small sooting may develop. Sooting is indicated by black puffs developing at the tips of very long orange flames. Sooting results in black deposits form­ing on the logs, appliance inside surfaces and on exterior surfaces adjacent to the vent termi­nation. Sooting is caused by incomplete com­bustion in the flames and a lack of combustion air entering the air shutter opening.
To achieve a warm yellow to orange flame with an orange body that does not soot, the shutter opening must be adjusted between these two extremes.
No smoke or soot should be present. Reposi­tion the log set if the flames impinge on any of them.
If sooting conditions exist, the air shutter opening on the main burner can be adjusted. Normally, the more offsets in the vent system, the greater the need for the air shutter to be opened further.
WARNING: AIR SHUTTER ADJUSTMENT SHOULD ONLY BE PERFORMED BY A QUALIFIED PROFESSIONAL SERVICE TECHNICIAN.
Adjustment
To adjust the flame, position the air shutter to the nominal setting
(Figure 22 ).
Allow the burner to operate for at least 30 minutes. Observe the flame continuously. If it appears weak or sooty as previously described, adjust the air shutter open or closed until desired effect is achieved.
Note: If the flame still appears anemic with the air shutter closed all the way (usually a result of lengthy vertical venting runs), turn off the appli­ance, turn off the gas supply, wait for the parts to cool and access the air shutter. The shutter is prevented from actually closing by a tab that is bent over into the opening. Remove this obstruction by bending back. Reassemble and restart the appliance and after 24 minutes reobserve the flame. Adjust the air shutter as described.
Orifice
Air Shutter
Adjusting Set Screw
Burner Tube
Models Shutter Setting
LSBV-3628
LSBV-4228
Gas
Type
Natural 1/8" (3.175 mm)
Propane 1/2" (12.7 mm)
Natural 1/8" (3.175 mm)
Propane 1/2" (12.7 mm)
Factory Air
Inches (mm)
Figure 22
Pilot Nozzels
Figure 21
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
When satisfied that the appliance operates prop­erly, proceed to finish the installation. Leave the control knob/lever in “ON” position and turn the remote switch “OFF.” Replace the refractory access panel.
11
Combustible Mantel and Trim (See Note)
Non Combustible Material
Finished Wall
Header
1-3/8"
Sheet Metal Spacer
INSTALLATION ACCESSORIES
The following accessory items are available for use in the installation of this appliance.
12"
Max.
18 5/8"
11-3/8"
Min.
18"
12"
Min.
Non-Combustible Material
Note: Mantel At Minimum Height Should Be Affixed to Framing Hinge Posts At Right And Left Of The Fireplace. Do Not Use Molly Bolts In Front Of The Fireplace.
10"
Min.
Typical Installation
Figure 23
FINISHING REQUIREMENTS Wall Details and Combustible Mantels
Complete finished interior wall. To install the appliance facing flush with the finished wall, position framework to accommodate the thick­ness of the finished wall
Figures 23 and 24
shelf projecting a maximum of 12" (305 mm) from the wall, and which must be installed a minimum distance of 12" (305mm) from the top of the firebox opening. No other mantel length/height combinations are allowable for this fireplace.
(Figure 23 )
. Both
show a combustible mantel
5"
3 Sheet Metal Screws #10 x 3/4" Max. Flat Head
Fireplace Opening
Max. Projection 12" (305 mm)
Combustible Mantel
Top Of Fireplace
0" Clearance to Combustible Side Wall
12" Min. (305 mm)
60"
(1524 mm)
Min. to Ceiling
12" Length 10KL1 24" Length 10KL2 36" Length 10KL3
Security 10" B-vent Adjustable Length 10KAL
Elbow 10" X 45 Degree 10KE45
Brace Support BV 10" 10KBS
A hearth extension is not required with this appliance. Any hearth extension used is for appearance only and does not have to conform to standard hearth extension installation re­quirements.
Note: Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined by the appliance front face (black sheet metal). Never allow combustible materials to be positioned in front of or overlapping the appliance front face.
12
Figure 24
COLD CLIMATE INSULATION
If you live in a cold climate, seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room. It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests, if floor is above ground level.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Firestop BV 10" 10KBF
INSTALLATION ACCESSORIES CONTINUED
Adjustable Flashing 1/12 - 7/12 10FA 10" Gas Vent 17/12 - 12/12 10FB
Storm Collar BV 10" 10KFC
Outside Air Kits Models FOAK-4 and FOAK-4LD
Outside Air kits are available with duct (FOAK-4) and without duct (FOAK-4LD) for use if outside combustion air is re­quired or desired. If model FOAK-4LD is used it must be used in conjunction with locally purchased, non-combustible Class 1 or Class 0 flexible duct.
Outside Combustion Air Kits (with duct) 81L87 FOAK-4 (without duct) 81L88 FOAK-4LD
Following Components Are Not Illustrated
Anchor Plate 10SP
Radiation Shield 10RS
Roof Brace XBS2
Flat Roof Flashing With Storm Collar 10KF
Rain Cap B-Vent 10KCGV
Chase Top Shroud Kits (Arch Top 3 x 3) H1988 CTSA-33 (Open Top 3 x 3) H1985 CTS0-33 (Open Top 4 x 4) H1987 CTSO-44 (Open Top 4 x 6) H1986 CTS0-46
Wall Switch Kit 85L87 FWSK
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
13
Gas Conversion Kits
-smetsySTIScinortcelE stiKnoisrevnoCsaGlarutaNotenaporP
sledoMepyTtinU.oNgolataC
8263-VBSL cinortcele3185H 8224-VBSL cinortcele3185H
WARNING: THIS CONVERSION KIT SHALL BE IN­STALLED BY A QUALIFIED SERVICE AGENCY IN AC­CORDANCE WITH THE MANUFACTURER'S INSTRUC­TIONS AND ALL APPLICABLE CODES AND REQUIRE­MENTS OF THE AUTHORIZED AGENCY HAVING JU­RISDICTION. IF THE INFORMATION IN THESE IN­STRUCTIONS ARE NOT FOLLOWED EXACTLY, A FIRE, EXPLOSION OR PRODUCTION OF CARBON MONOX­IDE MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE. THE INSTAL­LATION IS NOT PROPER AND COMPLETE UNTIL THE OPERATION OF THE CONVERTED APPLIANCE IS CHECKED AS SPECIFIED IN THE OWNER INSTRUC­TIONS SUPPLIED WITH THE KIT.
In Canada
THE CONVERSION SHALL BE CARRIED OUT IN ACCORDANCE WITH THE REQUIREMENTS OF THE PROVINCIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN1-B149.1 AND .2 INSTALLATION CODE.
LA CONVERSION DEVRA ÊTRE EFFECTUÉE CONFORMÉMENT AUX RECOMMANDATIONS DES AUTORITÉS PROVINCIALES AYANT JURIDICTION ET CONFORMÉMENT AUX EXIGENCES DU CODE D'INSTALLATION CAN1­B149.1 ET.2.
sledoMepyTtinU.oNgolataC
8263-VBSL tlovillim4185H 8224-VBSL tlovillim4185H
sledoMepyTtinU.oNgolataC
8263-VBSL cinortcele5185H 8224-VBSL cinortcele5185H
AVERTISSEMENT: CET ÉQUIPEMENT DE CONVERSION SERA INSTALLÉ PAR UNE AGENCE QUALIFIÉE DE SERVICE CONFORMÉMENT AUX INSTRUCTIONS DU FABRICANT ET TOUTES EXIGENCES ET CODES APPLICABLES DE L'AUTORISÉS AVOIR LA JURIDICTION. SI L'INFORMATION DANS CETTE INSTRUCTION N'EST PAS SUIVIE EXACTEMENT, UN FEU, EXPLOSION OU PRODUCTION DE PROTOXYDE DE CARBONE PEUT RÉSULTER LE DOMMAGES CAUSER DE PROPRIÉTÉ, PERTE OU BLESSURE PERSONNELLE DE VIE. L'AGENCE QUALIFIÉE DE SERVICE EST ESPONSABLE DE L'INSTALLATION PROPRE DE CET ÉQUIPMENT. L'INSTALLATION N'EST PAS PROPRE ET COMPLÉTE JUSQU'À L'OPÉRATION DE L'APPAREIL CONVERTI EST CHÉQUE SUIVANT LES CRITÈRES ÉTABLIS DANS LES INSTRUCTIONS DE PROPRIÉTAIRE PROVISIONNÉES AVEC L'ÉQUIPEMENT.
-smetsySTIStlovilliM stiKnoisrevnoCsaGenaporPoTlarutaN
sledoMepyTtinU.oNgolataC
8263-VBSL tlovillim2185H 8224-VBSL tlovillim2185H
-smetsySTIScinortcelE stiKnoisrevnoCsaGenaporPoTlarutaN
-smetsySTIStlovilliM stiKnoisrevnoCsaGlarutaNotenaporP
Gas conversion kits are available to adapt your appliance from the use of one type of gas to the use of another. These kits contain all the nec­essary components needed to complete the task including labeling that must be affixed to ensure safe operation.
Kit part numbers are listed here and the steps that follow detail the conversion procedure.
14
Step 1. Turn off the gas supply to the appli-
ance. Remove the front glass door (if used) from the appliance. Access the control com­partment.
Step 2. Carefully remove the logs. Exercise care as not to break the logs.
Step 3. Locate the screw securing the burner. Remove the burner and retain the securing screw.
Millivolt Appliances Step 4. SIT Systems - Refer to
the instructions provided with the kit. Using a Torx T20, remove and discard the three pres­sure regulator mounting screws.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Figure 25
and
Remove the pressure regulator, spring, pop­pet, diaphragm and bushing. Discard all re- moved components. Ensure the rubber gasket installed on the back of the replacement pres­sure regulator is properly positioned and install the new pressure regulator using the new screws supplied with the kit. Tighten screws to 25 In. lb. torque.
Pressure Regulator
Remove These Components
Figure 25
Step 5. Millivolt Systems – Attach manom-
eter to the manifold side pressure test fitting and verify manifold pressure reads 3.5 inches water column (0.87 kPa) for natural gas, and
10.0 inches water column (2.49 kPa) for pro­pane gas.
When reinstalling the ignitor assembly, use extreme care to prevent damage and break­age. Do not apply any leverage to the ignitor assembly while restoring the retainer clip to its original position. All Models
Step 6. See
Figure 26
and remove the pilot hood assembly to access the hexed pilot ori­fice. Remove and replace the orifice with the one provided with the kit.
Pilot Orifice
Figure 26
Electronic Appliances Step 7. SIT Electronic Valves - See
Figure 28
and the instructions provided with the kit. Remove the slotted cap screw, o-ring, pres­sure-regulating adjusting screw and spring, then discard.
Modify the pressure regulator from the kit. Using a standard tin snip cutting tool, proceed to trim shoulder off of the regulator.
Install new components and modified pres­sure regulator from the kit.
Pilot Orifice
Figure 27
SIT VALVE
Modified Kit Pressure Regulator
- After Trim
Remove These Components
Kit Pressure Regulator - Before Trim
Figure 28
Refer to
Figure 27
and replace the pilot orifice as follows: Remove the pilot hood assemble to access the hexed polot ofifice.
Remove the pilot orifice and replace it with the one provided with the conversion kit. Reinstall the pilot assembly by reversing the steps de­tailed here.
Step 8. Unscrew the orifice from the manifold and replace it with the one provided with the
.
See the following table for orifice sizes for
kit natural and propane models.
Figure 29
illus-
trates the orifice.
LSBV
Series
Orifice Size
Natural
Propane
3628 #26 #45 4228 #26 #45
Figure 29
Step 9. Reassemble all removed components
by reversing the procedures outlined in the preceding steps. Use pipe joint compound or Teflon tape on all pipe fittings before installing (ensure propane resistant compounds are used in propane applications, do not use pipe joint compounds on flare fittings).
Step 10. Attach the conversion label provided in the conversion kit to the rating plate on the appliance.
Step 11. Turn on gas supply and test for gas leaks. (See
step 6
on page 8.)
Attach manometer to the manifold side pres­sure test fitting and adjust screw until pres­sure reads 3.5 inches water column (0.87 kPa) for natural gas, and 10.0 inches water column (2.49 kPa) for propane gas.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
15
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information.
Printed in U.S.A. © 2007 by Lennox Hearth Products
P/N 850,042M REV. A 12/2008
16
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
1110 West Taft Avenue Orange, CA 92865
Loading...