Lennox LF24-115, LF24-200, LF24-145, LF24-175, LF24-230 Installation Instructions Manual

...
506682−01
*P506682-01*
E 2011 Lennox Industries Inc.
Dallas, Texas, USA
Litho U.S.A.
INSTALLATION INSTRUCTIONS
100,000 to 400,000 Btuh Series
UNIT HEATERS
506682−01 5/2011 Supersedes 503,523M
Table Of Contents
LF24 Unit Dimensions 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optional Accessories 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CSA Requirements in USA 3. . . . . . . . . . . . . . . . . . . . . . . . .
CSA Requirements in Canada 3. . . . . . . . . . . . . . . . . . . . . .
Additional Requirements 3. . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Heater Installation 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Combustion and Ventilation Air 4. . . . . . . . . . . . . . . . . . . . .
Rotation of Combustion Air Inducer 5. . . . . . . . . . . . . . . . . .
Venting 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Connections 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Typical LF24 Wiring Diagram 10. . . . . . . . . . . . . . . . . . . . . . .
Gas Connection 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Leak Check 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
Unit Start−Up 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
To Turn Off Gas to Unit 13. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heating Sequence of Operation 13. . . . . . . . . . . . . . . . . . . . .
Ignition Control LED 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
High Altitude Adjustment 13. . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Flow 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Pressure Adjustment 15. . . . . . . . . . . . . . . . . . . . . . . . . .
Limit Control Switch 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Louver Vane Adjustments 15. . . . . . . . . . . . . . . . . . . . . . . . . .
Combustion Air Pressure Switch 15. . . . . . . . . . . . . . . . . . . . .
Service 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up and Performance Checklist 16. . . . . . . . . . . . . . . . .
Template 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WHAT TO DO IF YOU SMELL GAS:
Do not store or use gasoline or other flammable vapors and liquids in the vi­cinity of this or any other appliance.
Installation and service must be per­formed by a qualified installer, service agency or the gas supplier.
S Do not try to light any appliance.
S Leave the building immediately.
S Do not touch any electrical switch; do not use
any phone in your building.
S Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s in­structions.
S If you cannot reach your gas supplier, call the
fire department.
FIRE OR EXPLOSION HAZARD.
Failure to follow safety warnings exact­ly could result in serious injury, death, or property damage.
WARNING
Be sure to read and understand the installation, operation and service in­structions in this manual.
Improper installation, adjustment, alter­ation, service or maintenance can cause serious injury, death or property damage.
Page 1
LF24 Unit Dimensions
1/2
(13)
TOP VIEW
SIDE VIEW
ADJUSTABLE
LOUVERS
GAS
VALVE
HEAT
EXCHANGER
DIRECT
DRIVE FAN
FLUE
OUTLET
ELECTRICAL INLETS
3/8" x 16 MOUNTING NUTS
FOR UNIT SUSPENSION
AIR
FLOW
COMBUSTION AIR
INDUCER
END VIEW
A
B
C
E
F
G
NOTE  LF24 models 100, 115, 145, 175 and 200 have a single fan. LF24 models 230, 250, 300, 345 and 400 have two fans.
D
*7-5/8
(194)
1/2
(13)
Additional
mounting nuts
furnished on
LF−230, LF24−250, LF24−300,
LF24−345 and
LF24−400 models
only.
H
NOTE  Two mounting nuts are furnished on LF24 models 100, 115, 145, 175 and 200. Four mounting nuts are furnished on LF24 models 230, 250, 300, 345 and 400 models.
Unit
A B C D E F G H
in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm
LF24-100 LF24-115 LF24−145
31-5/16 795 32-3/16 817 20-3/16 512 11-1/2 292 19-1/16 484 11-3/4 298 3-1/4 83 7-7/8 200
LF24−175 LF24−200
31-5/16 795 32-3/16 817 23-1/8 588 11-1/2 292 22-1/16 560 8−1/2 216 3-1/4 83 8−11/16 220
LF24-230* LF24−250* LF24−300*
31-5/16 795 32-3/16 817 41-1/8 1045 3-11/16 97 40 1016 17-3/4 451 3-1/2 89 8-11/16 220
LF24-345* LF24−400*
31-5/16 795 32-3/16 817 41-1/8 1045 3-11/16 97 40 1016 17-1/2 445 3-1/2 89 9-13/16 248
*Unit contains dual fans.
Shipping
The heater is completely assembled and is shipped with installation and operating instructions, warranty certificate and flue transition. Check the unit for shipping damage. The receiving party should contact the last carrier immediately if any shipping damage is found.
Page 2
Optional Accessories
TABLE 1
LF24−100 to LF24−230
Gas Heating Performance
Model No. − Stainless Steel LF24−100S LF24−115S LF24−145S LF24−175S LF24−200S
Model No. − Aluminized Steel LF24−100A LF24−115A LF24−145A LF24−175A LF24−200A
Optional Accessories − Must Be Ordered Extra
Discharge Nozzle
30_94K94 S S S
30_94K95 S S
45_95K98 S S S
45_95K99 S S
60_16L28 S S S
60_16L29 S S
90_15L96 S S S
90_15L97 S S
Hanging Bracket Kit
87277 S S S S S
High Altitude Pressure Switch Kit
10K73 S
1
S
1
S
1
S
2
− − −
LPG/Propane Kit
45L85 S
63J56 S S S
20L07 S
63J57
1
LF24−100 through −145 require replacement combustion air inducer pressure switch at altitudes over 5500 feet above sea level.
2
LF24−175 requires replacement combustion air inducer pressure switch at altitudes over 2500 feet above sea level.
TABLE 2
LF24−230 to LF24−400
Gas Heating Performance
Model No. − Stainless Steel LF24−230S LF24−250S LF24−300S LF24−345S LF24−400S
Model No. − Aluminized Steel LF24−230A LF24−250A LF24−300A LF24−345A LF24−400A
Optional Accessories − Must Be Ordered Extra
Discharge Nozzle
30_94K96 S S S S S
45_95K00 S S S S S
60_16L30 S S S S S
90_15L98 S S S S S
Hanging Bracket Kit
87277 S S S S S
LPG/Propane Kit
45L88 S S
63J57 S S
20L06 S
Page 3
CSA Requirements in USA
Installation of gas unit heaters must conform with local building codes or, in the absence of local codes, with the current edition of ANSI−Z223.1, National Fuel Gas Code.
Installation in aircraft hangers must be in accordance with the current edition of ANSI/NFPA No. 409, Standard for Aircraft Hangers.
Installation in parking structures must be in accordance with the current edition of ANSI/NFPA No. 88A, Standard for Parking Structures.
Installation in repair garages must be in accordance with the current edition of ANSI/NFPA No. 88B, Standard for Repair Garages.
Authorities having jurisdiction should be consulted before installation. Air for combustion and ventilation must conform to the methods outlined in the current edition of ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation, or applicable provisions of local building codes.
The National Fuel Gas Code (ANSI−Z223.1) is available from:
American National Standard Institute Inc. 11 West 42nd Street New York, NY 10036
These units are CSA international design−certified. These unit heaters are certified for clearances to combustible material as listed in table 1 and on unit rating plate.
Accessibility and service clearances must be observed in addition to fire protection clearances.
All electrical wiring and grounding for unit must be in accordance with the regulations of the current edition of ANSI/NFPA No. 70, National Electric Code.
The National Electric Code is available from:
National Fire Protection Association 1 Batterymarch Park PO Box 9101 Quincy, MA 02269−9101
CSA Requirements in Canada
These instructions are intended only as a general guide and do not supersede local codes in any way. Authorities having jurisdiction should be consulted before installation. The installation must conform with local building codes or, in the absence of local codes, with the current edition of CSA−B149 installation compliance codes. All electrical wiring and grounding for the unit must also comply with the current edition of CSA C22.1, Canadian Electrical Code.
These unit heaters are CSA−certified for clearances to combustible material listed on the rating plate and table 3. Adequate clearance must be provided around the appliance and around air openings into the combustion chamber. Provision must be made for service accessibility.
NOTE: Fire protection clearances may be exceeded to provide additional space for service and accessibility.
TABLE 3
UNIT CLEARANCES TO COMBUSTIBLE MATERIALS
Top
Sides Bottom Rear Flue
in mm in mm in mm in mm in mm
6 152 6 152 0 0 18 457 6 152
GARAGE / WAREHOUSE INSTALLATIONS
1 − In a storage area, clearance from the heater to
combustible materials must be such that the combustible material must not attain a temperature above 160°F (71°C) during continuous operation of the unit.
WARNING
Combustible materials that are affected by ex­posure to temperatures less than 160°F (plas­tics, plastic wrap, styrofoam, cardboard, etc.) must be stored well away from this heater. Dis­charge air temperatures for these units can ap­proach 200°F.
2 − Maintain an 8−foot (2.5 m) minimum clearance from
the floor to the bottom of the heater. Refer to the current edition of CSA−B149 installation compliance codes.
AIRCRAFT HANGER
1 − In an area where aircraft are housed or serviced, a
10−foot (3 m) minimum clearance from the highest surface of the aircraft to bottom of the heater must be maintained.
2 − In other areas, an 8−foot (2.5 m) minimum clearance
from the floor to bottom of heater must be maintained.
3 − Heaters should be located so that they are
protected from damage from aircraft or other appliances needed for servicing of aircraft. Refer to requirements of the enforcing authorities.
In a confined area, the heater must be installed in accordance with the current edition of CSA−B149 installation compliance codes. Be sure to check with local codes and ordinances for additional requirements.
Page 4
Additional Requirements
The Commonwealth of Massachusetts stipulates the following additional requirements:
1 − Gas furnaces shall be installed by a licensed
plumber or gas fitter only.
2 − The gas cock must be T handle" type.
Unit Heater Installation
WARNING
Improper installation, adjustment, alteration, ser­vice or maintenance can cause property damage, personal injury or loss of life. Installation and ser­vice must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
The appliance shall not be installed downstream from evaporator coils or cooling units.
Install the unit in the desired location as governed by clearances, vent connection, air direction, gas supply, electrical supply and service accessibility.
On LF24 models 100, 115, 145, 175, and 200, mounting nuts are furnished at the balance point (two positions only). On LF24 models 230, 250, 300, 345 and 400, mounting nuts are furnished at each corner of the unit. Mounting nuts will accommodate 3/8" x 16 threaded rods.
1 − Cut threaded rods to desired length and slide a 3/8"
nut onto the rod.
2 − Slide a flat washer onto the threaded rod AFTER the
nut (7/16" inside diameter X 1" outside diameter X 1/16" thick washer).
3 − Screw the rods (two or four) into the mounting nuts
on the unit.
4 − Tighten nuts to secure unit to rods.
IMPORTANT
Do not use the gas manifold pipe to lift unit. Any ex­cessive upward or downward force on the manifold pipe and bracket assembly can cause the ignition burner and igniter to become misaligned.
TABLE 4
MAXIMUM MOUNTING HEIGHTS
Model Number Feet (Meters)
LF24−100 and LF24−115 16 (4.9)
LF24−145, LF24−175, and
LF24−200
20 (6.1)
LF24−230, LF24−250,
LF24−300, LF24−345 and
LF24−400
30 (9.1)
Combustion and Ventilation Air
Adequate facilities for supplying air for combustion and ventilation must be provided in accordance with the current edition of ANSI Z223.1, section 5.3, and CSA−B149 installation compliance codes, or applicable provisions of local building codes.
All gas−fired appliances require air to be used for the combustion process. In many buildings today, there is a negative indoor air pressure caused by exhaust fans, etc. If sufficient quantities of combustion air are not available, the heater or another appliance will operate in an inefficient manner, resulting in incomplete combustion which can result in the production of excessive carbon monoxide.
CAUTION
Insufficient combustion air can cause headaches, nausea, dizziness, asphyxiation or death.
If indoor air is to be used for combustion, it must be free of the following substances or the life of the heat exchanger will be adversely affected: chlorine, carbon tetrachloride, cleaning solvent, halogen refrigerants, acids, cements and glues, printing inks, fluorides, paint removers, varnishes, or any other corrosives.
Rotation of Combustion Air Inducer (LF24−100, −115 and −145 Only)
The combustion air inducer on LF24 models −100, −115 and −145 may be rotated 90° either to the left or right of the original vertical position in order to better suit the application.
NOTE − It is not permissible to rotate the combustion air inducer on LF24 models −175, −200, −230, −250, −300,
−345 and −400.
Rotate the combustion air inducer assembly as follows:
1 − Remove the heater from the carton. Decide the best
unit heater orientation. The vent can be installed in one of three discharge positions: up, left, or right.
Page 5
2 − If the inducer is to be rotated, follow the instructions
in this section; otherwise, refer to instructions under Venting" section.
3 − Before making an electrical or gas connections,
remove the securing screws on the flue box/combustion air inducer. See figure 1.
FIGURE 1
FLUE BOX AND
COMBUSTION AIR INDUCER ASSEMBLY
VEST PANEL
FLUE BOX GASKET
FLUE BOX
COMBUSTION AIR INDUCER GASKET
COMBUSTION AIR INDUCER
4 − Remove the flue box/combustion air inducer
assembly, ensuring that the gasket is not damaged. If the gasket is damaged, replace it.
5 − Use a 1/4" socket to remove the three screws which
secure the combustion air inducer to the flue box. Remove the inducer and gasket from the flue box ensuring that the gasket is not damaged. If the gasket is damaged, replace it.
6 − Use the template provided in the back of this manual
to mark new hole locations. Use a 7/32" drill bit to drill holes in flue box.
7 − Place the gasket between the combustion air
inducer and the flue box. Rotate both the inducer and the gasket 90° to the desired position. Reinsert and tighten the three inducer securing screws (#8−16 X 1/2" HWHSMS).
8 − Place the gasket between the flue box and the vest
panel. Position the flue box/combustion air inducer assembly on the vest panel. Fasten the flue box to the vest panel using the flue box securing screws (#10−16 X 5/8" HWHSMS) and a 5/16" driver.
9 − The unit heater is now ready for installation as
described in the Venting section.
Venting
NOTE − The vent is a passageway, vertical or nearly so, used to convey flue gases from an appliance, or its vent connector, to the outside atmosphere. The vent connector is the pipe or duct that connects a fuel−gas burning appliance to a vent or chimney.
NOTE − Local codes may supersede any of these provisions.
GENERAL RECOMMENDATION AND REQUIREMENTS
LF24 unit heaters must be vented in compliance with the latest edition of the National Fuel Gas Code (NFPA 54 / ANSI Z223.1) in the USA and with CSA−B149.1 codes in Canada, as well as applicable provisions of local building codes, and the following instructions.
A sheet metal flue transition is supplied with this certified unit. It must not be modified or altered and must be installed on the outlet of the combustion air inducer assembly prior to the installation of the vent connector. Failure to comply with this requirement will void the certification of the unit by the approval agencies.
A single−wall vent connector may be used in all applications between the furnace and the vertical vent pipe.
A single−wall vent pipe used as a vent connector or as a vertical vent, must have all seams and joints sealed with pressure−sensitive aluminum tape or silicone rubber sealant. Aluminum tape must meet the provisions of SMACNA AFTS−100−73 Standards. The aluminum tape must have a temperature rating of 400°F (204°C). Silicone rubber sealant must have a temperature rating of 482°F (250°C), i.e., Dow Corning RTV−736 or equivalent.
All joints must be secured with at least two corrosion resistant screws. All joints must be checked for gas tightness after installation. Single−wall vent pipe used as vertical vent must not pass through any attic, interior wall, concealed space, or floor.
Loading...
+ 12 hidden pages