Improper installation, adjustment, alteration, ser
vice or maintenance can cause property damage,
personal injury or loss of life. Installation and ser
vice must be performed by a licensed professional
HVAC installer or equivalent, service agency, or the
gas supplier
Table Of Contents
DimensionsPage 2.................................
Parts ArrangementsPage 3.........................
Shipping and Packing ListPage 5....................
GeneralPage 5....................................
RequirementsPage 5...............................
Unit SupportPage 6................................
Duct ConnectionPage 6............................
Rigging Unit For LiftingPage 7.......................
Horizontal Air DischargePage 7......................
Condensate DrainsPage 7..........................
Gas PipingPage 9.................................
Pressure Test Gas PipingPage 10.....................
LGH/LCH036, 048,
060, 072 & 074
3, 4, 5 and 6 Ton
GAS AND COOLING PACKAGED UNITS
507410-05
4/2019
Supersedes 10/2018
High Altitude DeratePage 10.........................
Factory Unit Controller SettingsPage 70...............
CAUTION
As with any mechanical equipment, contact with
sharp sheet metal edges can result in personal in
jury. Take care while handling this equipment and
wear gloves and protective clothing.
RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE
LG STANDARD AND HIGH EFFICIENCY SHOWN
LGH/LCH036, 048, 060, 072 & 074 DIMENSIONS in. - Gas heat section shown
5−5/8
11
(143)
(279)
16−1/4
(413)
18
(457)
45
(1143)
47 (1194)
BASE
END VIEW
1 (25)
AA
7 (178)
29
(737)
47 (1194)
BASE
DD
43−3/8 (1102) 036 thru 074U
35−3/8 (899) 036 thru 048S, H
38−7/8 (987) 036 thru 048S, H
46−7/8 (1191) 060 thru 074S, H
46−7/8 (1191) 036 thru 074U
LIFTING HOLES
(For rigging)
43−3/8 (1102) 060 thru 074S, H
3−1/2 (89)
BOTTOM
RETURN
OPENING
BOTTOM
OPENING
6−5/8
(168)
26−1/2
(673)
CONDENSATE OUTLET
CONDENSATE
OUTLET
(EITHER SIDE)
26−1/2
(673)
AIR
SUPPLY
AIR
CENTER
OF
GRAVITY
BOTTOM
TOP VIEW (Base)
83−1/4
(2115)
FLUE/VENT
OUTLET
5−1/2
(140)
SIDE VIEW
19−1/2
5 (127)
20
(508)
FF
85−1/4 (2165)
BASE
(495)
25−3/4
(654)
9−1/2
(241)
EE
BOTTOM POWER ENTRY
3 X 8 (76 X 203)
ELECTRICAL
INLET
GAS
INLET
15 (381)
27
(686)
11
18−3/8
(467)
(279)
BB
CC
1 (25)
2 (51)
38-7/8 (987) 036 thru 048S, H
46-7/8 (1191) 060 thru 074S, H
46-7/8 (1191) 036 thru 074U
FORKLIFT SLOTS
(Front, Back and
Blower End)
Page 2
20
(508)
HORIZONTAL
SUPPLY AIR
OPENING
HORIZONTAL
5−1/2
RETURN AIR
(140)
OPENING
(Without Economizer)
BACK VIEW
85-1/4 (2165)
BASE
LGH/LCH036, 048, 060, 072, 074
29
(737)
5−1/2
(140)
LGH036, 048, 060S, H & 072, 074H PARTS ARRANGEMENT
FILTERS (4)
036, 048:16 X 20 X 2”
060, 072, 074: 20 X 20 X 2”
ECONOMIZER
(OPTIONAL)
CONDENSATE
DRAIN
COMBUSTION
AIR INDUCER
EVAPORATOR
COIL
BURNERS
REHEAT COIL
(OPTIONAL)
BLOWER
GAS VALVE
TXV
UNIT
CONTROLLER
BLOWER
MOTOR
(BELT DRIVE SHOWN)
COMPRESSOR
CONDENSER
FAN
COIL
GUARDS
(OPTIONAL)
CONDENSER
COIL
LCH036, 048, 060S, H & 072, 074H PARTS ARRANGEMENT
REHEAT COIL
(OPTIONAL)
ELECTRIC HEAT
(Optional)
BLOWER
CONTROLLER
TXV
UNIT
COMPRESSOR
FILTERS (4)
036, 048:16 X 20 X 2”
060, 072, 074: 20 X 20 X 2”
ECONOMIZER
(OPTIONAL)
CONDENSATE
DRAIN
(BELT DRIVE SHOWN)
EVAPORATOR
COIL
BLOWER
MOTOR
CONDENSER
FAN
CONDENSER
COIL
LGH/LCH036, 048, 060, 072, 074
Page 3
LGH036, 048, 060, 074U PARTS ARRANGEMENT
ECONOMIZER
(OPTIONAL)
CONDENSATE
DRAIN
FILTERS (4)
20 X 20 X 2”
GAS VALVE 1
(4-STG. GAS
HEAT SHOWN)
EVAPORATOR
COMBUSTION
AIR INDUCER
COIL
BURNERS
TXV
BLOWER
GAS VALVE 2
(4-STG. GAS
HEAT SHOWN)
CONDENSER
FAN
COIL
GUARDS
(OPTIONAL)
CONDENSER
COIL
COMPRESSOR
UNIT
CONTROLLER
LCH036, 048, 060, 074U PARTS ARRANGEMENT
FILTERS (4)
20 X 20 X 2”
ECONOMIZER
(OPTIONAL)
EVAPORATOR
COIL
CONDENSATE
DRAIN
ELECTRIC
HEAT
TXV
UNIT
CONTROLLER
BLOWER
COMPRESSOR
CONDENSER
FAN
COIL
GUARDS
(OPTIONAL)
CONDENSER
COIL
Page 4
LGH/LCH036, 048, 060, 072, 074
Shipping and Packing List
Package 1 of 1 contains:
1- Assembled unit
Check unit for shipping damage. Receiving party should
contact last carrier immediately if shipping damage is found.
General
These instructions are intended as a general guide
and do not supersede local codes in any way.
Authorities having jurisdiction should be consulted
before installation.
The LGH units are available in several heating inputs. The
LCH cooling packaged rooftop unit is the same basic
design as the LGH unit except for the heating section.
Optional electric heat is available for LCH units. LGH and
LCH units have identical refrigerant circuits with
respective 3, 4, 5, and 6 ton cooling capacities.
Standard and high efficiency units are equipped with a
lightweight, all-aluminum condenser coil; optional fin/tube
condenser coils are available. Ultra high efficiency units are
equipped with fin/tube condenser coils.
Units are equipped with the compressors shown in table 1.
TABLE 1
COMPRESSORS
UnitT'StatCompressor
072H2-StageSingle-Speed
036S, 048S, 060S,
036H, 048H, 060H, 074H
036U, 048U, 060U, 074U2- or 3-Stage
036U, 048U, 060U, 074UZone SensorVariable Speed
2- or 3-Stage 2-Step Capacity
Variable Speed,
2-Step Capacity
In addition to standard heating and cooling, hot gas
reheat units provide a dehumidifying mode of operation.
Refer to Reheat Operation section.
High efficiency units may be equipped with a Unit
Controller that is factory-configured for “Advanced Air
Flow Control”. This option allows the installer to enter both
the design-specified supply air CFM and outdoor air
CFM. See the Advanced Air Flow Control Start-Up
section. These units are equipped with a variable speed,
direct drive blower and an economizer.
Availability of units and options varies by brand.
Requirements
WARNING
Electric shock hazard and danger of
explosion. Can cause injury, death or
product or property damage. Turn off
gas and electrical power to unit before
performing any maintenance or
servicing operations on the unit. Follow
lighting instructions attached to unit
when putting unit back into operation
and after service or maintenance.
NOTICE
Roof Damage!
This system contains both refrigerant and oil.
Some rubber roofing material may absorb oil,
causing the rubber to swell. Bubbles in the rubber
roofing material can cause leaks. Protect the roof
surface to avoid exposure to refrigerant and oil
during service and installation. Failure to follow
this notice could result in damage to roof surface.
UNIT CLEARANCES
C
B
D
A
FIGURE 1
1
Unit
Clearance
Service
Clearance
Clearance to
Combustibles36(914)1(25)1(25)1(25)
A
in.(mm)Bin.(mm)Cin.(mm)Din.(mm)
48
(1219)36(914)36(914)36(914)
To p
Clearance
Unob
structed
Unob
structed
See figure 1 for unit clearances.
IMPORTANT
The Clean Air Act of 1990 bans the intentional vent
ing of refrigerant (CFC's and HCFC's) as of July 1,
1992. Approved methods of recovery, recycling or
reclaiming must be followed. Fines and/or incar
ceration may be levied for non-compliance.
LGH/LCH036, 048, 060, 072, 074
Minimum Opera
tion Clearance36(914)36(914)36(914)36(914)
Note - Entire perimeter of unit base requires support when elevated above
mounting surface.
1
Service Clearance - Required for removal of serviceable parts.
Clearance to Combustibles - Required clearance to combustible material
(gas units).
Minimum Operation Clearance - Required clearance for proper unit operation.
Page 5
Unob
structed
Use of this unit as a construction heater or air conditioner
is not recommended during any phase of construction.
Very low return air temperatures, harmful vapors and
operation of the unit with clogged or misplaced filters will
damage the unit.
If this unit has been used for heating or cooling of
buildings or structures under construction, the following
conditions must be met or the warranty will be void:
A room thermostat must control the unit. The use of
fixed jumpers that will provide continuous heating or
cooling is not allowed.
A pre-filter must be installed at the entry to the return
air duct.
The return air duct must be provided and sealed to
the unit.
Return air temperature range between 55°F (13°C)
and 80°F (27°C) must be maintained.
Air filters must be replaced and pre-filters must be
removed upon construction completion.
The input rate and temperature rise must be set per
the unit rating plate.
The heat exchanger, components, duct system, air
filters and evaporator coil must be thoroughly
cleaned following final construction clean-up.
The unit operating conditions (including airflow,
cooling operation, ignition, input rate, temperature
rise and venting) must be verified according to these
installation instructions.
Unit Support
In downflow discharge installations, install the unit on a
non-combustible surface only. Unit may be installed on
combustible surfaces when used in horizontal discharge
applications or in downflow discharge applications when
installed on an T1CURB / C1CURB / E1CURB roof
mounting frame.
NOTE - Securely fasten roof frame to roof per local codes.
CAUTION
To reduce the likelihood of supply / return air by
pass and promote a proper seal with the RTU, duct
work / duct drops / diffuser assemblies must be
supported independently to the building structure.
A-Downflow Discharge Application
Roof Mounting with T1CURB / C1CURB / E1CURB
1- The roof mounting frame must be installed, flashed
and sealed in accordance with the instructions
provided with the frame.
2- The roof mounting frame should be square and level
to 1/16” per linear foot (5mm per linear meter) in any
direction.
3- Duct must be attached to the roof mounting frame
and not to the unit; supply and return plenums must
be installed before setting the unit.
Installer's Roof Mounting Frame
Many types of roof frames can be used to install the unit
depending upon different roof structures. Items to keep
in mind when using the building frame or supports are:
1- The base is fully enclosed and insulated, so an
enclosed frame is not required.
2- The frames or supports must be constructed with
non-combustible materials and should be square and
level to 1/16” per linear foot (5mm per linear meter)
in any direction.
3- Frame or supports must be high enough to prevent
any form of moisture from entering unit.
Recommended minimum frame height is 14”
(356mm).
4- Duct must be attached to the roof mounting frame
and not to the unit. Supply and return plenums must
be installed before setting the unit.
5- Units require support along all four sides of unit base.
Supports must be constructed of steel or suitably
treated wood materials.
NOTE-When installing a unit on a combustible surface for
downflow discharge applications, a T1CURB / C1CURB /
E1CURB roof mounting frame is required.
B-Horizontal Discharge Applications
1- Units which are equipped with an optional
economizer and installed in horizontal airflow
applications must use a horizontal conversion kit.
2- Specified installation clearances must be maintained
when installing units. Refer to figure 1.
3- Top of support slab should be approximately 4”
(102mm) above the finished grade and located so no
run-off water from higher ground can collect around
the unit.
4- Units require support along all four sides of unit base.
Supports must be constructed of steel or suitably
treated wood materials.
Duct Connection
All exterior ducts, joints and openings in roof or building
walls must be insulated and weather-proofed with
flashing and sealing compounds in accordance with
applicable codes. Any duct passing through an
unconditioned space must be insulated.
CAUTION
In downflow applications, do not drill or punch
holes in base of unit. Leaking in roof may occur if
unit base is punctured.
Page 6
LGH/LCH036, 048, 060, 072, 074
Rigging Unit For Lifting
Rig unit for lifting by attaching four cables to holes in unit
base rail. See figure 2.
1- Detach wooden base protection before rigging.
2- Remove all six base protection brackets before
setting unit.
3- Connect rigging to the unit base using both holes in
each corner.
4- All panels must be in place for rigging.
UNIT SUPPLY AND RETURN AIR OPENINGS
HORIZONTAL
HORIZONTAL
RETURN AIR
OPENING
SUPPLY AIR
OPENING
5- Place field‐provided H‐style pick in place just above
top edge of unit. Frame must be of adequate
strength and length. (H-style pick prevents damage
to unit.)
Unit
LG
LC
*Maximum weight with all available
factory-installed accessories.
LIFTING POINT SHOULD
BE DIRECTLY ABOVE
CENTER OF GRAVITY
*Weight
Lbs. Kg.
435
960
423
933
IMPORTANT - ALL
PANELS MUST
BE IN PLACE
FOR RIGGING.
CAUTION - Do
not walk on unit.
FIGURE 2
Horizontal Air Discharge
Unit is shipped with panels covering the horizontal supply
and return air openings. Remove horizontal covers and
place over downflow openings for horizontal air discharge.
See figure 3. Secure in place with sheet metal screws.
Units Equipped With An Optional Economizer
1- Remove the horizontal supply air cover and position
over the downflow supply air opening. Secure with
sheet metal screws.
2- Leave the horizontal return air cover in place.
3- Locate the separately ordered horizontal air
discharge kit. Place the kit panel over the downflow
return air opening.
4- Remove and retain the barometric relief dampers and
lower hood.
LGH/LCH036, 048, 060, 072, 074
DOWNFLOW
RETURN AIR
OPENING
DOWNFLOW
SUPPLY AIR
OPENING
FIGURE 3
5- Install return air duct beneath outdoor air intake. See
figure 4. Install barometric relief damper in lower
hood and install in ductwork as shown in figure 4.
HORIZONTAL RETURN AIR DUCTWORK
WITH ECONOMIZER
HORIZONTAL
RETURN AIR
DUCT
INSTALL BAROMETRIC RELIEF DAMPERS
AND HOOD IN RETURN AIR DUCT
FIGURE 4
Condensate Drains
Make drain connection to the drain coupling provided on
unit. Older model units have a 3/4” N.P.T. coupling and
newer model units have a 1” N.P.T. coupling.
Note - The drain pan is made with a glass reinforced
engineered plastic capable of withstanding typical joint
torque but can be damaged with excessive force. Tighten
pipe nipple hand tight and turn an additional quarter turn.
A trap must be installed between drain connection and an
open vent for proper condensate removal. See figure 5 or
6. It is sometimes acceptable to drain condensate onto
the roof or grade; however, a tee should be fitted to the
trap to direct condensate downward. The condensate line
must be vented. Check local codes concerning
condensate disposal. Refer to pages 1 and 2 for
condensate drain location.
Page 7
UNITUNIT
CONDENSATE SIDE DRAIN CONNECTION
CAULK AROUND CONDENSATE COUPLING
Two hinge screws must be removed in addition to the
mullion screws. See figure 8.
UNITS WITH HINGED PANELS
NOTE - Allow clearance to
open doors when installing
condensate piping.
Minimum Pitch
1” (25 mm) per
10' (3 m) of line
OPEN VENT
UNIT
MOUNTING
FRAME
FIGURE 5
CONDENSATE BOTTOM DRAIN CONNECTION
UNIT
DRAIN PAN
CAULK AROUND
CONDENSATE COUPLING
OPEN VENT
CONDENSATE
DRAIN MULLION
REMOVE
TWO
SCREWS
FIGURE 8
2- Lift the front edge of the drain pan and slide pan out
of unit. See figure 9.
REMOVE DRAIN PAN
MOUNTING
FRAME
Minimum Pitch
1” (25 mm) per 10'
(3 m) of line
FIGURE 6
Units are shipped with the drain coupling facing the front
of the unit. Condensate can be drained from the back or
bottom of the unit with the following modifications. The
unit can be installed in either downflow or horizontal air
discharge regardless of condensate drain location.
Rear Drain Connection
1- Remove the condensate drain mullion. See figure 7.
Remove the two panels on each side of the mullion.
CONDENSATE
DRAIN MULLION
FIGURE 7
DRAIN PAN
FIGURE 9
3- Make sure the cap over the unit bottom drain hole is
secure.
4- Rotate the drain pan until the downward slope is
toward the back of the unit. Slide the drain pan back
into the unit. Be careful not to dislodge the cap over
the bottom drain hole.
5- From the back side of the unit, pull the drain pan
coupling through the rear condensate opening.
6- Replace the condensate drain mullion.
Bottom Drain Connection
1- Remove the condensate drain mullion. See figure 7.
2- Lift the front edge of the drain pan and slide pan out
of unit. See figure 9.
3- Turn the drain pan upside down and drill a pilot hole
through the bottom of the drain pan in the center of
the coupling. See figure 10.
Page 8
LGH/LCH036, 048, 060, 072, 074
BOTTOM CONDENSATE DRAIN
CAUTION: Be careful not to
damage the coupling threads
when drilling the hole.
After drilling the pilot
hole, drill a 7/8” hole from
the inside of the pan.
DRILL A PILOT
HOLE IN CENTER
OF COUPLING
FIGURE 10
4- From the inside of the pan, use a Vari-Bit® bit to
enlarge the hole to 7/8”. Do not damage coupling
threads.
5- Remove the cap over the unit bottom drain hole.
6- Slide the drain pan back into the unit.
When making piping connections a drip leg should be
installed on vertical pipe runs to serve as a trap for
sediment or condensate. A 1/8” N.P.T. plugged tap is
located on gas valve for test gauge connection. Refer to
Heating Start-Up section for tap location. Install a ground
joint union between the gas control manifold and the
main manual shut-off valve. See figure 11 for gas supply
piping entering outside the unit. Figure 12 shows
complete bottom gas entry piping.
Compounds used on threaded joints of gas piping shall be
resistant to the action of liquified petroleum gases.
Do not use Teflon® tape to seal gas piping. Use a
moderate amount of pipe compound on the gas pipe only.
Make sure the two end threads are bare.
CAUTION
If a flexible gas connector is required or allowed by
the authority that has jurisdiction, black iron pipe
shall be installed at the gas valve and extend out
side the furnace cabinet.
WARNING
Do not exceed 600 in-lbs (50 ft.-lbs) torque when at
taching the gas piping to the gas valve.
7- From the back side of the unit, pull the drain pan
coupling through the rear condensate opening.
8- From the front side of the unit, move the drain pan
until the bottom coupling settles into the unit bottom
drain opening. Once in place, check to make sure the
coupling is still positioned through the rear
condensate drain hole.
9- Use a field-provided 3/4” plug to seal side drain
connection.
10- Replace the condensate drain mullion.
Connect Gas Piping (Gas Units)
Before connecting field-provided piping, check with gas
company or authorities having jurisdiction for local code
requirements. When installing gas supply piping, length
of run from gas meter must be considered in determining
pipe size for 0.5” w.c. (.12kPa) maximum pressure drop.
Do not use supply pipe smaller than unit gas connection.
Operating pressures at the unit gas connection must be
as shown in table 2.
TABLE 2
OPERATING PRESSURE AT GAS CONNECTION “w.c.
Natural GasLP / Propane Gas
Min.Max.Min.Max.
036-0744.510.51113
IMPORTANT
Compounds used on threaded joints of gas piping
must be resistant to the actions of liquified petro
leum gases.
OUTSIDE OF UNIT GAS PIPE CONNECTION
TO GAS
VALV E
GROUND
JOINT UNION
TO GAS
SUPPLY
GAS PIPING
SUPPORT
MANUAL MAIN
SHUT-OFF VALVE
FIGURE 11
DRIP LEG
(REFER TO
LOCAL CODES)
LGH/LCH036, 048, 060, 072, 074
Page 9
BOTTOM ENTRY GAS PIPING COMPLETED
TO GAS
VALV E
STREET
ELBOW
GROUND
JOINT UNION
NOTE-In case emergency shut down is required, turn off
the main manual shut-off valve and disconnect main
power to unit. These devices should be properly labeled
by the installer.
PRESSURE TEST GAS LINE
7” NIPPLE
TO GAS
SUPPLY
2-1/2” NIPPLE
MANUAL MAIN
DRIP LEG
Grommets for both gas pipe openings are field provided.
SHUT-OFF VALVE
FIGURE 12
Pressure Test Gas Piping (Gas Units)
When pressure testing gas lines, the gas valve must
be disconnected and isolated. Gas valves can be
damaged if subjected to more than 0.5 psig (3.48kPa).
See figure 13.
NOTE-Codes may require that manual main shut-off
valve and union (furnished by installer) be installed in
gas line external to unit. Union must be of the ground
joint type.
After all connections have been made, check all piping
connections for gas leaks. Also check existing unit gas
connections up to the gas valve; loosening may occur
during installation. Use a leak detection solution or other
preferred means. Do not use matches candles or other
sources of ignition to check for gas leaks.
MANUAL MAIN
SHUT-OFF VALVE
GAS VALVE
CAP
FIGURE 13
High Altitude Derate
Locate the high altitude conversion sticker in the unit
literature bag. Fill out the conversion sticker and affix next
to the unit nameplate.
Refer to table 3 for high altitude adjustments.
TABLE 3
HIGH ALTITUDE DERATE
Altitude Ft.*Gas Manifold Pressure
2000-4500See Unit Nameplate
4500 And AboveDerate 2% / 1000 Ft. Above Sea Level
CAUTION
Some soaps used for leak detection are corrosive
to certain metals. Carefully rinse piping thoroughly
after leak test has been completed. Do not use
matches, candles, flame or othe sources of ignition
to check for gas leaks.
WARNING
Danger of explosion. Can cause injury
or product or property damage. Do not
use matches, candles, flame or other
sources of ignition to check for leaks.
*Units installed at 0-2000 feet do not need to be modified.
NOTE ‐ This is the only permissible derate for these units.
Page 10
LGH/LCH036, 048, 060, 072, 074
Electrical Connections
POWER SUPPLY
Do not apply power or close disconnect switch until
installation is complete. Refer to start-up directions.
Refer closely to unit wiring diagram.
Refer to unit nameplate for minimum circuit ampacity
and maximum fuse size.
1- Units are factory-wired for 230,460,575 volt supply.
For 208V supply
from the 208V terminal on the control transformer.
Move the wire from the transformer 240V terminal to
the 208V terminal. Place the insulated terminal cover
on the unused 240V terminal.
2- Route power through the bottom power entry area
and connect to L1, L2, and L3 on the top of K1 in
control area above compressor. Secure power
wiring with factory-installed wire ties provided in
control box. Route power to TB2 on units equipped
with electric heat. Route power to S48 or CB10 If
unit is equipped with the optional disconnect
switch or circuit breaker. See unit wiring diagram.
, remove the insulated terminal cover
CONTROL WIRING
B-Control Wiring
The Unit Controller will operate the unit from a
thermostat or zone sensor based on the System Mode.
The default System Mode is the thermostat mode. Refer
to the Unit Controller Installation and Setup Guide to
change the System Mode. Use the menu navigation
arrows and select button; see Settings - Install.
Thermostat Mode
1- Route thermostat cable or wires from subbase to
control area above compressor (refer to unit
dimensions to locate bottom and side power entry).
IMPORTANT - Unless field thermostat wires are rated
for maximum unit voltage, they must be routed away
from line voltage wiring. Use wire ties located near the
lower left corner of the controls mounting panel to
secure thermostat cable.
Use18 AWG wire for all applications using remotely
installed electro-mechanical and electronic
thermostats.
2- Install thermostat assembly in accordance with
instructions provided with thermostat.
3- Connect thermostat wiring to Unit Controller on the
lower side of the controls hat section.
CAUTION
Electrostatic discharge can affect electronic com
ponents. Take precautions during unit installation
and service to protect the electronic controls. Pre
cautions will help to avoid control exposure to elec
trostatic discharge by putting the unit, the control
and the technician at the same electrostatic poten
tial. Neutralize electrostatic charge by touching
hands and all tools on an unpainted unit surface,
such as the gas valve or blower deck, before per
forming any service procedure.
A-Thermostat Location
Room thermostat mounts vertically on a standard 2” X 4”
handy box or on any non-conductive flat surface.
Locate thermostat approximately 5 feet (1524mm)
above the floor in an area with good air circulation at
average temperature. Avoid locating the room
thermostat where it might be affected by:
-drafts or dead spots behind doors and in corners
4- Wire as shown in figure 14 for electro-mechanical
and electronic thermostats. If using other
temperature control devices or energy management
systems see instructions and wiring diagram
provided by manufacturer.
IMPORTANT-Terminal connections at the wall plate or
subbase must be made securely. Loose control wire
connections may allow unit to operate but not with proper
response to room demand.
Zone Sensor Mode
The Unit Controller will operate heating and cooling
based on the Unit Controller internal setpoints and the
temperature from the A2 zone sensor. An optional
Network Control Panel (NCP) can also be used to provide
setpoints. A thermostat or return air sensor can be used
as a back-up mode. Make zone sensor wiring
connections as shown in figure 15.
-hot or cold air from ducts
-radiant heat from sun or appliances
-concealed pipes and chimneys
LGH/LCH036, 048, 060, 072, 074
Page 11
24 V POWER
B
K55
A
OCP
FIELD WIRING WITH ELECTRONIC AND ELECTRO-MECHANICAL THERMOSTATS
(Thermostat Mode)
P297
1
A55
2
B
3
4
5
W1
W2
6
7
8
C
9
TO UNIT CONTROLLER
THERMOSTAT INPUTS
R
C
G
W1
S86
2
2
K55−1
7
5
W2
Y1
ALLOTHERTHERMOSTAT
Y2
SIGNALS REMAIN CONNECTED
AS SHOWN ON THE RIGHT.
TO R
TO G
TO Y1
J297A
R
C
G
W1
W2
Y1
2
Y2
OCP
P262
10
11
12
J262C
TO PROVIDE SUPERMARKET REHEAT SCHEME
USE S86 DEHUMIDISTAT AND K55.
FIGURE 14
FIELD WIRING IN ZONE SENSOR MODE
(Zone Sensor Mode)
UNIT CONTROLLER
SENSOR
24VAC
RC
AI1
IAQ
SENSOR
HUM
TMP
OUTPUTS
D01
D02
J298
A2 SENSOR
FIGURE 15
C-Hot Gas Reheat or Ultra High Efficiency Units Only -
1- Install humidity sensor in accordance with
instructions provided with sensor. A DDC input may
be used to initiate dehumidification instead of a
sensor.
2- Make wiring connections as shown in figure 14 for
Thermostat Mode or figure 15 for Zone Sensor
Mode. In addition, connect either a humidity
sensor or a dehumidification input. See figure 16
or 17 for humidity sensor wiring or figure 18 for
dehumidification input wiring.
10
Humidity Sensor Cable Applications:
Wire runs of 50 feet (mm) or less:
Use two separate shielded cables containing 20AWG
minimum, twisted pair conductors with overall shield.
Belden type 8762 or 88760 (plenum) or equivalent.
Connect both cable shield drain wires to the Unit
Controller as shown in figure 16.
Wire runs of 150 feet (mm) or less:
Use two separate shielded cables containing 18AWG
minimum, twisted pair conductors with overall shield.
Belden type 8760 or 88760 (plenum) or equivalent.
Connect both cable shield drain wires to the Unit
Controller as shown in figure 16.
FIELD WIRING REHEAT UNITS (Using A Humidity
Sensor With Less Than 150 Ft. Wire Runs)
P298J298A
R
A91
VIN
GND
VO
1
B
C
AI−1
3
4
HUM
5
C
2
6
TMP
7
D
8
DO−1
9
C
10
11
12
P262
J262B
5
Page 12
FIGURE 16
LGH/LCH036, 048, 060, 072, 074
Wire runs over 150 feet (mm):
Use a local, isolated 24VAC transformer such as
Lennox cat #18M13 (20VA minimum) to supply power
to RH sensor as shown in figure 17. Use two shielded
cables containing 20AWG minimum, twisted pair
conductors with overall shield. Belden type 8762 or
88760 (plenum) or equivalent.
FIELD WIRING REHEAT UNITS
(Using A Humidity Sensor With
More than 150 Ft. Wire Runs)
NOT
CONNECTED
A91
VIN
GND
VO
ISOLATED 24V
TRANSFORMER
DRAIN
NOT
CONNECTED
J298A
A55 UNIT
CONTROLLER
P298
1
2
B
3
4
C
5
6
7
D
8
9
10
R
C
AI-1
HUM
TMP
DO-1
C
DO-2
DI-1
FIGURE 17
FIELD WIRING REHEAT UNITS
(Using A Dehumidification Switch)
Blower Operation and Adjustments
Units are equipped with one of three factory-installed
blower options. The ninth character in the model number
identifies the blower as follows:
E= High efficiency three-, four- and five-ton units are
equipped with a variable speed, direct drive blower.
When these units are also equipped with an
economizer and configured for Advanced Air Flow
Control, the installer is able to enter the
design-specified supply and outdoor air CFM into
the Unit Controller. This eliminates the need to
manually take measurements and adjust settings.
See Advanced Air Flow Control Start-Up section.
Ultra high efficiency units are also equipped with a
variable speed, direct drive blower. The installer is
able to enter the design-specified supply air CFM
into the Unit Controller for optimal efficiency. The
Unit Controller calibrates the supply air volume
which eliminates the need to manually take duct
static measurements. Refer to D-Adjusting Unit
CFM - Ultra High Efficiency Direct Drive Blowers.
T= Units are equipped with a two-stage belt drive blower.
B= Units are equipped with a single-stage belt drive
blower.
Note - Six-ton, non-ultra high efficiency units are
available with belt drive blowers only.
J299
7
DEHUMIDIFICATION
SWITCH
Use 24 VAC (R) from any terminal
available on J299−2, −5, or −7.
8
9
10
FIGURE 18
LGH/LCH036, 048, 060, 072, 074
R
DI−4
C
IMPORTANT
Three phase scroll compressors must be phased
sequentially for correct compressor and blower
rotation. Follow “COOLING START-UP” section of
installation instructions to ensure proper compres
sor and blower operation.
Page 13
A-Blower Operation
Refer to the Unit Controller Installation and Setup Guide
to energize blower. Use the menu navigation arrows and
select button; see SERVICE > TEST.
B-Determining Unit CFM
1- The following measurements must be made with air
filters in place.
IMPORTANT - High Efficiency Units On units equipped with direct drive blowers, a low speed
adjustment less than 2/3 of high speed will improve
humidity removal; refer to product data for more
information.
2- With all access panels in place, measure static
pressure external to unit (from supply to return).
Blower performance data is based on static pressure
readings taken in locations shown in figure 19.
Note - Static pressure readings can vary if not taken
where shown.
3- Measure the indoor blower wheel RPM.
4- Referring to the Blower Data tables, use static
pressure and RPM readings to determine unit CFM.
Use the Accessory Air Resistance tables when
installing units with any of the options or accessories
listed. Refer to table 4 or 5 for minimum airflow when
electric heat is installed.
TABLE 4
MINIMUM AIRFLOW-LCH UNITS WITH ELECTRIC
HEAT (DIRECT DRIVE)
kW
LCH036H, U
LCH048H, U
LCH060H, U
LCH074U
Downflow & Horizontal Airflow
CFM
1080
1280
1600
TABLE 5
MINIMUM AIRFLOW-LCH UNITS WITH ELECTRIC
HEAT (BELT DRIVE)
kW
DownflowHorizontal
CFM
3019002000
22.515001600
1512001300
7.510501200
C-Adjusting Unit CFM - High Efficiency Direct Drive
Blowers
Note - To adjust CFM on units configured for optional
“Advanced Air Flow Control”, refer to Advanced Air Flow
Control Start-Up section.
The supply CFM can be adjusted by changing Unit
Controller settings. Refer to table 6 for menu paths and
default settings. Adjustments can also be made by using
optional software. Record any CFM changes on the
parameter settings label located on the inside of the
compressor access panel.
INSTALLATIONS WITH DUCTWORK
ROOFTOP UNIT
READING LOCATION
SUPPLY
MAIN
RE
TURN
FIRST BRANCH
OFF OF MAIN RUN
DUCT RUN
LOCATION OF STATIC PRESSURE READINGS
INSTALLATIONS WITH CEILING DIFFUSERS
ROOFTOP UNIT
RETURN AIR
SUPPLY
SUPPLY AIR
READING
LOCATION
SUPPLY AIR
READING
LOCATION
DIFFUSER
FIGURE 19
Page 14
LGH/LCH036, 048, 060, 072, 074
RE
TURN
RETURN AIR
READING
LOCATION
D-Adjusting Unit CFM - Ultra High Efficiency Direct
Drive Blowers
The supply CFM can be adjusted by changing Unit
Controller settings. Refer to table 7 for menu paths and
default settings. Record any CFM changes on the
parameter settings label located on the inside of the
compressor access panel.
CAUTION
The BLOWER CALIBRATION process starts the in
door blower at operational speeds and moves the
economizer damper blades. Before starting this pro
cess, replace any access panels and close all unit
doors except compressor compartment door.
Blower calibration is required only on units that are newly
installed or if there is a change in the duct work or air filters
after installation. After the new CFM values are entered,
use the down and up arrow buttons to select START
CALIBRATION. Push SAVE to start calibration. The
blower calibration status is displayed as a % complete.
Upon successful completion, the Unit Controller will
display CALIBRATION SUCCESS and go back to the
blower calibration screen. Press the MAIN MENU button
to go to the main menu and press the BACK button to go
to the status screen.
If only the CFM values are updated, use the down and up
arrow buttons to select “CALIBRATION DONE”. Push
SAVE to enter the updated values. This selection will not
initiate calibration, resulting in less setup time. Press the
MAIN MENU button to go to the main menu and press the
BACK button to go to the status screen.
IMPORTANT - On ultra high efficiency units, the default
value for Cooling Low CFM is lower than a traditional
singe- or two-speed unit. If operating the unit with a 2- or
3-stage controller (2- or 3-stage thermostat, DDC
controller, etc.), it is recommended to increase the
Cooling Low CFM default value to a suitable level for
part load cooling (typically 60% of full load CFM).
Minimum damper position during
high speed blower operation.
Minimum damper position during
low speed blower operation.
Percentage torque for indoor
blower smoke speed.
FREE COOLING
STAGE-UP DELAY
300 sec.300 sec.300 sec.300 sec.sec
Number of seconds to hold indoor
blower at low speed before switch
ing to indoor blower at high speed.
Installer: Circle applicable unit model number and record any parameter changes under “Field Setting” column. Settings need to be recorded by
installer for use when Unit Controller is replaced or reprogrammed.
TABLE 7
036, 048, 060, 074U DIRECT DRIVE PARAMETER SETTINGS
LGH/LCH036-074U4E Parameter Settings
Parameter
Note: Any changes to Smoke CFM setting must be adjusted before the other CFM settings. Use SETTINGS > RTU OPTIONS > EDIT
PARAMETERS = 12
0%0%0%0%% Minimum damper position for high speed blower operation.
0%0%0%0%% Minimum damper position for low speed blower operation.
50% 50% 50%50%% Minimum damper position for power exhaust operation.
10% 10% 10%10%% Deadband % for power exhaust operation.
300
300
300
sec.
sec.
sec.
300
sec.
Field
Setting
Description
Low heat blower speed (applies to 150kBtuh 4-stg. gas heat
only)
Number of seconds to hold indoor blower at low speed before
sec
switching to indoor blower at high speed.
Installer: Circle applicable unit model number and record any parameter changes under “Field Setting” column. Settings need to be recorded
by installer for use when Unit Controller is replaced or reprogrammed.
Page 16
LGH/LCH036, 048, 060, 072, 074
D-Adjusting Unit CFM - Belt Drive Blowers
The blower RPM can be adjusted at the motor pulley.
Loosen Allen screw and turn adjustable pulley clockwise
to increase CFM. Turn counterclockwise to decrease
CFM. See figure 21. Do not exceed minimum and
maximum number of pulley turns as shown in table 8.
TABLE 8
MINIMUM AND MAXIMUM PULLEY ADJUSTMENT
BeltMin. Turns OpenMaxi. Turns Open
A SectionNo minimum5
E-Blower Belt Adjustment - Belt Drive
Maximum life and wear can be obtained from belts only
if proper pulley alignment and belt tension are
maintained. Tension new belts after a 24-48 hour
period of operation. This will allow belt to stretch and
seat grooves. Make sure blower and motor pulley are
aligned as shown in figure 20.
1- Loosen four bolts securing motor base to mounting
frame. See figure 21.
2- To increase belt tension -
Slide blower motor downward to tighten the belt. This
increases the distance between the blower motor and
the blower housing.
PULLEY ALIGNMENT
ALIGNED
MOTOR
PULLEY
BELT
NOT ALIGNED
BLOWER
PULLEY
FIGURE 20
3- To loosen belt tension -
Slide blower motor upward to loosen the belt. This
decreases the distance between the blower motor
and the blower housing.
4- Tighten four bolts securing motor base to the
mounting frame.
F-Blower Belt Adjustment - Units Equipped With An
Optional Belt Tensioner
1- Remove blower belt.
2- Remove bracket from blower housing. See figure 23.
3- Remove the screw from the back side of the bracket.
4- Move the tensioner to the appropriate adjustment
hole and reinstall screw.
5- Replace bracket.
6- Replace blower belt. See figure 24.
TO INCREASE CFM
LOOSEN ALLEN SCREW &
TURN PULLEY CLOCKWISE
SIDE VIEW
MOTOR
TO INCREASE BELT TENSION
1-Loosen four bolts securing motor base to mounting
frame.
2-Slide the motor downward to tighten the belt.
3-Tighten four bolts on motor base.
TO DECREASE CFM
TURN PULLEY
COUNTERCLOCKWISE
ALLEN
SCREW
PULLEY
BLOWER ASSEMBLY
LOOSEN ALLEN
SCREW TO
ADJUST CFM
LOOSEN FOUR BOLTS AND
SLIDE BLOWER MOTOR
DOWNWARD TO TIGHTEN BELT
FIGURE 21
LGH/LCH036, 048, 060, 072, 074
Page 17
G-Check Belt Tension
Overtensioning belts shortens belt and bearing life.
Check belt tension as follows:
1- Measure span length X. See figure 22.
2- Apply perpendicular force to center of span (X) with
enough pressure to deflect belt 1/64” for every inch
of span length or 1.5mm per 100mm of span length.
Example: Deflection distance of a 40” span would be
40/64” or 5/8”.
Example: Deflection distance of a 400mm span
would be 6mm.
MEASURE BELT TENSION
FORCE
DEFLECTION 1/64” PER INCH OF SPAN
OR 1.5mm PER 100mm OF SPAN
FIGURE 22
3- Measure belt deflection force. For a used belt, the
deflection force should be 5 lbs. (35kPa). A new belt
deflection force should be 7 lbs. (48kPa).
A force below these values indicates an
undertensioned belt. A force above these values
indicates an overtensioned belt.
H-Field-Furnished Blower Drives
For field-furnished blower drives, use page 20 through 44
to determine BHP and RPM required. Reference page 45
to determine the drive kit number. Reference table 9 for
manufacturer's drive numbers.