Lennox LC22, LC31, LC60, LC45, LC76 Maintenance Manual

CONTENTS
1
Page
Compact Waterside Fan Coil Specification 2 Mounting 3 Pipework Connections 3 Duct Connections 3 Electrical Connections 4 Controls 4 Fan Speed Settings 5 Periodic Maintenance 6 Electrical Data 7 Coil Water Content 7 Weights 7 Minimum No. Spigots 7 Coil Connections 7
General Arrangement Drgs Unit Ref: Drg Ref: LC22 Z304255 (2 pages) 13-14 LC31 Z304256 LC45 Z304257 LC60 Z304258 LC76 Z304259
Example Wiring Diagrams 8-12
(2 pages) 15-16 (2 pages) 17-18 (2 pages) 19-20 (2 pages) 21-22
R
LENN X
EUROVENT
CERTIFIED PERFORMANCE
Manufacturer reserves the right to change any product specifications without notice.
CASINGS
The casings shall consist of durable 1.2mm (18 gauge) galvanised steel reinforced to form a rigid monoque structure. All edges to be radiused and access panels to be fixed with easy release self retaining fasteners.
DISCHARGE PLENUM
The discharge plenum shall be wholly lined with Class O acoustic insulation. The plenum shall be provided with 200mm diameter spigots for duct connection.
DRIP TRAY
The drip tray shall be manufactured such that when the unit is mounted level there shall be a positive fall for the condensate water to the drain connection from all areas of the drip tray. There shall be no areas where the water can collect in pools. The drip tray shall be of single component construction and be located under the coil assembly and extend to include the valve pack arrangement. The tray shall be fully insulated.
FANS
Double inlet double width fans shall be used, driven by a motor using cradle type resilient mountings. The fan impellers shall be 160mm diameter and of 'Tablock' construction to ensure good performance and low noise. Each impeller shall be dynamically balanced.
MOTORS
Motors shall be single speed permanent split capacitor type. The motors used shall comply with BS5000 Part 11 1973 (revised 1 989). Speed control shall be achieved by applying a variable voltage to the motor winding. Motors are to have maintenance free sealed f or life bearings and built in thermal overload protection.
INSULATION
Dual function thermal and acoustic insulation shall be used and shall be to Class 0 specification.
COILS
All heat exchangers shall be tested at a minimum of 25 bar pressure. The coils shall be manufactured using solid drawn copper tubes and aluminium fins. Each coil shall be fitted with an air vent and drain cock.
COIL CONNECTIONS
All are to be BS2871 Part 1: 1971 and suitable for brazed and compression fittings. Coil connections shall be at 40mm centres to enable easy fitment of industry standard water control valves.
FILTERS
Standard filters shall be of washable type. They shall have a performance classification of G2 in accordance with EN779 (EU2) and flame resistance to DIN 53438: Class 1
CONTROLS
All units shall be fitted with an illuminated On/Off switch and three speed selector switch. Adjacent to this switch are two additional switches that provide a fine tuning capability. In total a selection of 27 speeds are available with design settings factory set, and dependant on transformer tapping connections. The unit is supplied with a 24 volt AC transformer output to drive controllers and actuators. The control box shall be of a hinge arrangement with a single screw access to terminal strips for customer connection.
PACKAGING Units shall be supplied with shrink wrapped packaging to
prevent damage and dust contamination. Units shall be clearly marked with the model identification and site reference and supplied with installation instructions. The units will be despatched on pallets with 5 or 6 units per pallet dependant on unit sizes.
CERTIFICATION
Units shall be supplied with a CE label designating that they comply with CE requirements for safety .
COMPACT WATERSIDE FAN COIL SPECIFICATION
2
R
LENN X
Thank you for choosing the Lennox Quantum Compact Fan Coil Unit. Please read the following information carefully prior to installation. These instructions should be kept in a safe place for future reference.
WARNING:
ISOLATE FROM THE ELECTRICAL SUPPLY
BEFORE COMMENCING WORK.
These units can be installed virtually as delivered. They are intended for fitting behind a suspended ceiling or a similar ceiling void and have circular spigots for connecting to ducting. Similarly, they can have a fresh air spigot fitted when specified.
MOUNTING
In all cases, the units are fixed to the mounting face by means of four slots in the end flanges. Down rods, 10mm in diameter, should be used t o support units
1. Unistrut should be mounted to the slab (see dimensional data) and four 10mm down rods fix ed to the unistrut.
2. The down rods should have two nuts and two w ashers to lock the unit in position. The unit can then be lifted into location, hooking the slots (in the top panel) over the washers. The nuts must then be securely tightened.
3. Check to ensure the unit is level and adjust if necessary.
4. Check that water runs into the waste from the drain tray, by pouring wat er into it.
NOTE: To allow f or Service Clearances it is recommended that a minimum space of 50mm is provided from top of the unit to underside of slab.
Sufficient space should be provided to allow for clear and safe access to the control panel.
PIPEWORK CONNECTIONS
1. Water flow and return connection
Plain pipe connection tails are all to BS 2871, Part 1: 1971 and are suitable for brazed or compression fittings. Connection sizes are 22mm outside diameter on the cooling coil and 15mm on the heating coil. Actual final connection pipesizes will vary depending on valve configuration where fitted.
2. Condensate Tray Connection
An end facing 22mm outside diameter copper condensate drain connection tube to BS 2871, Part 1: 1971 is fitted as standard to the condensate tray on all units.
3. Air Vents and Drains
Brass air vent and drain tapping points are fitted as standard to all coils. These are positioned at the top and bottom of the header tubes.
DUCT CONNECTIONS
1. Discharge Air Side
An integral discharge plenum is fitted as standard complete with 19 7mm outside diameter circular spigots. These are to accept standard 200mm diameter flexible ducting. Blanking caps are available to order .
2. Inlet Air Side
When specified, units will be fitted with an Air Inlet Plenum, this will have the same number, size and position of circular spigots as on the discharge air side. Blanking caps are available subject to order .
3. Fresh Air Spigot
The fresh air spigot is available in a size of 100mm diameter.
4. Condensate pump
Condensate pump kits are available as an optional factory fitted option. Refer to diagrams indicating electrical wiring details.
5. Electrical heating element
LC22 2KW LC31 2KW LC45 2KW LC60 4KW LC76 4KW
Refer to diagrams indicating electrical wiring details.
MOUNTING / CONNECTIONS
3
R
LENN X
ELECTRICAL CONNECTIONS
ISOLATE ELECTRICAL SUPPLY BEFORE
ATTEMPTING SERVICE WORK.
A 230V, 50Hz, single phase supply is required. Wiring must be installed by a qualified electrician and conform to current local and national regulations.
1. Wire mains to unit via a double pole isolating switch, fused at 3 amp. Refer to diagrams indicating electrical wiring details.
2. The electrical connection is via a 2m flying lead with factory fitted connector into socket on control box where an electric heater is NOT fitted. If an electric heater is fitted, to connect mains supply to unit, slacken off the screw holding the control box front cover. Carefully pivot the cover to support it, making sure the wires connecting the cover to the unit are not strained. Connect the mains lead via grommet hole in the side panel to the LIVE, NEUTRAL and EARTH positions on the 12-way terminal block. Replace cover and tighten screw .
3. If a Condensate Lift Pump is specified, this will be pre-wired back to the control box, but the pump assembly will be taped to the unit and must be fixed to the end of the drip tray before installing the unit, using the screws supplied.
4. The fan motors are of the permanent split capacitor type and have a capacitor fixed to the outside of the motor. All motors have thermal overload protection as standard. Access to the fan tray is via removable panels on the bottom face of the unit.
CONTROLS
All units are fitted as standard with an ON/OFF switch and a FAN SPEED selector switch for three speeds.
When specified, the water control valves will have a controller that will be fitted to the exterior of the control box.
These are all fitted into the control box and pre-wired.
1. Fan Speed
Out of 6 speeds available, SL (Super Low), EL(Extra Low), L(Low), ML(Med/Low), M(Med), and H(High), the fan speed selector switch will be wired for three speeds. Speed adjustment and fine tuning is achieved by following the instructions indicated on the label that is positioned on the underside of the unit, adjacent to the control box.
Each model size has its specific settings, examples as detailed on page 5 of this document.
An example of adjusting the speed setting is described below:-
E.g.: If unit is selected for Medium/Low (ML) speed, then the speed selector switch is set at position II and other positions L and M, as below:
Position I = L (Low Speed) Position II = ML(Med/LowSpeed) Position III = M (Medium Speed)
If selected speed is EL then this would be Position II with SL and L other positions. If selected speed is H then this would be posiition III with M and ML other positions.
ELECTRICAL CONNECTIONS / CONTROLS
R
LENN X
4
FAN SPEED SETTINGS
5
R
LENN X
III
II
I
I I I
O O O
ON +5v +10v 3 spd
FAN SPEED SETTINGS
To achieve the design speed use a combination of main tappings on the transformer and switch positions on the outside of the control box.
LC22
SL EL
L
ML
M
H
Wh 120 120 135 135 150 150
Yel 135 135 150 150 165 165
Rd 150 150 165 165 180 180
3 spd
I II II II II
III
+ 10v
I O O
I O
I
+ 5v
O
I O O
I O
OUTPUT
VOLTS
130 140 150 160 170 190
SWITCH POSITIONS
MAIN TAPPINGS
LC31
LC45
LC60
LC76
SL EL
L
ML
M
H
SL EL
L
ML
M
H
SL EL
L
ML
M
H
SL EL
L
ML
M
H
Wh 120 120 135 135 150 150
Wh 120 120 135 150 165 165
Wh 120 120 135 135 150 150
Wh 120 120 135 150 165 165
Yel 135 135 150 150 165 165
Yel 135 135 150 165 180 180
Yel 135 135 150 150 165 165
Yel 135 135 150 165 180 180
Rd 150 150 165 165 180 180
Rd 150 150 165 180 195 195
Rd 150 150 165 165 180 180
Rd 150 150 165 180 195 195
3 spd
I II II II II
III
3 spd
I II II II II
III
3 spd
I II II II II
III
3 spd
I II II II II
III
+ 10v
I O O
I O 0
+ 10v
I O O O
I
I
+ 10v
I O O
I O
I
+ 10v
I
I O O O O
+ 5v
O
I O O
I O
+ 5v
O
I
I
I O O
+ 5v
O
I O O
I O
+ 5v
O O
I
I O
I
OUTPUT
VOLTS
130 140 150 160 170 180
OUTPUT
VOLTS
130 140 155 170 190 205
OUTPUT
VOLTS
130 140 150 160 170 190
OUTPUT
VOLTS
130 145 155 170 180 200
SWITCH POSITIONS
SWITCH POSITIONS
SWITCH POSITIONS
SWITCH POSITIONS
MAIN TAPPINGS
MAIN TAPPINGS
MAIN TAPPINGS
MAIN TAPPINGS
PERIODIC MAINTENANCE PROCEDURE
The following routine maintenance operations should be carried out twice a year or at such shorter intervals as may be dictated by climatic conditions or cleanliness of conditioned space.
1. Routine Precautions SWITCH OFF POWER SUPPLY AT THE MAINS OUTLET
BEFORE COMMENCING ANY WORK ON THE EQUIPMENT.
DO NOT OPERATE FAN FOR LONG PERIODS (OVER 2 HOURS) UNDER FREE AIR CONDITIONS. I.E WITHOUT DUCTWORK CONNECTED.
DO NOT USE STEAM JET OR HIGH PRESSURE HOT WATER TO CLEAN COIL SURFACES.
2. General
!
Thoroughly clean chassis, baseplate, drain tray .
!
Clean casing. The unit exterior surfaces should be
inspected monthly and any signs of corrosion or scratches should be treated immediately.
3. Routine Checks
!
Check voltage at supply point with unit running.
4. Condensate Trays
!
Check condensate drains are clean and free running.
! Check condensate hose connections are secure
and leak free.
!
Clean the condensate tray thoroughly .
!
Check and clean condensate pump if fitted.
!
Check operation of tray, drains or pump by introducing water into tray .
5. Controls
!
Check all connections for burning or wear . Replace if
necessary.
!
Ensure all electrical connections are secure.
!
Check functions of controls according to operating
procedures.
6. Fan Motor and Fan
A regular check on the fan/motor assembly is advisable to ascertain if any overheating of the motor is occurring and that the fan impeller is free running and has not sustained any damage.
Check that fans and fan motor are properly aligned.
Check all securing screws, bolts and nuts are tight.
7. Coil
The coil should be inspected every six months to ascertain if any foreign matter has accumulated between the fins and that the coil connections are free from leaks.
Should the fins become contaminated too frequently, it is advisable to check that the air filter is functioning correctly.
Use a soft brush and vacuum cleaner to remove any dust between fins. Comb fins if required.
DO NOT RUN UNIT WITHOUT FILTER FITTED.
8. Filter
Regular cleaning of return air filter is essential, every three to six months depending on the working environment of the unit. Dirty filters will reduce the air volume handled by the unit, thus adversely affecting its performance.
Clean the filter using a vacuum cleaner OR remove the filter from the unit and fully immerse in warm water with a mild detergent. Rinse in clear water, allow to dry before replacing.
PERIODIC MAINTENANCE
R
LENN X
6
H
M
ML
L EL SL
H
M
ML
L EL SL
H
M
ML
L EL SL
H
M
ML
L EL SL
H
M
ML
L EL SL
190 170 160 150 140 130 180 170 160 150 140 130 205 190 170 155 140 130 190 170 160 150 140 130 200 180 170 155 145 130
75 66 61 56 51
47 132 118 110 100
90
82 158 144 127 112
96
85 213 187 176 157 148 130 271 252 238 220 200
171
0.37
0.33
0.31
0.29
0.28
0.27
0.67
0.62
0.58
0.53
0.48
0.45
0.84
0.77
0.68
0.61
0.53
0.48
1.01
0.89
0.85
0.76
0.72
0.65
1.35
1.24
1.18
1.08
1.00
0.86
0.52
0.47
0.44
0.41
0.39
0.37
0.94
0.86
0.81
0.74
0.68
0.63
1.18
1.08
0.95
0.85
0.75
0.67
1.41
1.25
1.18
1.06
1.01
0.90
1.89
1.73
1.65
1.52
1.40
1.21
MODEL
LC22
LC31
LC45
LC60
LC76
MODEL
LC22
LC31
LC45 LC60 LC76
WEIGHT
kg
MINIMUM No. SPIGOTS COIL CONNECTIONS (mm)
Total CWFront LPHW
30 39 49 54 73
2 2 2 3 3
1 1 1 2 2
22 22 22 22 22
15 15 15 15 15
FAN SPEED VOLTS
MOTOR POWER
W
FULL LOAD
CURRENT
A
START
CURRENT
A
MODEL
WATER
CONTENT
(LITRES)
LC22 HEATING LC22/3 ROW LC22/4 ROW
0.19
1.32
1.50
MODEL
WATER
CONTENT
(LITRES)
LC31 HEATING LC31/3 ROW LC31/4 ROW
0.25
1.72
1.97
MODEL
WATER
CONTENT
(LITRES)
LC45 HEATING LC45/3 ROW LC45/4 ROW
0.35
2.47
2.83
MODEL
WATER
CONTENT
(LITRES)
LC60 HEATING LC60/3 ROW LC60/4 ROW
0.41
2.84
3.25
MODEL
WATER
CONTENT
(LITRES)
LC76 HEATING LC76/3 ROW LC76/4 ROW
0.53
3.73
4.27
7
R
LENN X
DATA
ELECTRICAL DATA
COIL WATER CONTENT
WEIGHTS, MINIMUM No. SPIGOTS, COIL CONNECTIONS
Loading...
+ 16 hidden pages