The Lennox ComfortSenset 3000 Series model L3711C
7-day programmable electronic thermostat provides
excellent temperature control and has a large,
easy-to-read display. This product includes a
programmable filter change reminder, an equipment
maintenance reminder, and a system check indicator to
notify the user when the equipment requires service.
Thermostat model L3711C is suitable for non−heat pump,
single-stage heat/single-stage cool applications with either
gas or electric furnace. Also, the thermostat provides autochangeover capability.
ComfortSenset 3000 Series
Model No. L3711C 7-Day
Programmable Thermostat
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
Introduction
This document describes the operation of Lennox model
L3711C thermostat. Refer to the installation manual for instructions regarding installation and wiring of the thermostat.
Initial Thermostat Power-up
When power is initially applied to the thermostat, the display will appear as shown in figure 1.
Copy tofrom
PROG
ABCD
HOLD
FAN ON
AUTO
FILTER
MAINTENANCE
OUTROOM
i88
Figure 1. Initial Power−Up Display
All display segments are momentarily activated. This occurs as a normal part of thermostat initialization.
MO TU WE TH FR SA SU
AM
I8:88
PM
COOL SETPOINT
SERVICE
88
HEAT SETPOINT
°
88
°
COOL
OFF
AUTO
EMG.
HEAT
°
Hi
Lo
02/08506072−01
*2P0208**P506072-01*
Within a few seconds, the HOME screen appears (see figure 2) with default settings as shown. After about 1 minute
of initialization time, the actual room temperature will be
displayed.
PROG
A B C D
HOLD
FAN ON
AUTO
MO
AM
PM
ROOM
I0:26
COOL
AUTO
°
EMG.
HEAT
OFF
70
Figure 2. Home Screen
At this point, the thermostat will be fully functional; its default temperature setpoint (not shown) is 70°F. At this
point, if the equipment has been fully powered and if a heat
demand were present, the system would begin operating.
NOTE − Temperature scale default is Fahrenheit units but
may be reset to show Celsius, if desired. See page 7.
Buttons, Backlight, Timers & Settings
Buttons are located behind the small door on the right−
hand side of the thermostat (see figure 3).
IMPORTANT
Do NOT begin pressing buttons until after you read
the following section describing each button.
A pale blue display backlight illuminates for 30 seconds
each time any button is pressed.
When the PROG or DAY/TIME button is pressed, a field
begins flashing, expecting another input. Start making
changes within 15 seconds or the HOME screen will return.
Heat
Cool
Prog
Auto
Day/Time
Copy
(DOOR
Fan
Settings
Hold
Enter
(Outside)
OPEN)
Figure 3. Thermostat Buttons
When an Arrow, HOLD, HEAT, or COOL button is pressed,
SETPOINT and the temperature setting appears for 15
seconds. If desired, start making changes within 15 seconds or the HOME screen will return. The backlight will
turn off 15 seconds after the HOME screen reappears.
DAY/TIME − Setting the Day and Time
Press the DAY/TIME button and set the CURRENT hour,
minute, and day of week as follows:
1. AM12" will flash on the screen. Press the UP/DOWN
arrows to change the hour. (AM" or PM" must correspond to time of day.) Press the DAY/TIME button OR,
if adjusting for daylight savings time, pressing the ENTER button stores the single change and exits to the
HOME screen, bypassing minutes and day of week.
2. Minutes will flash. Use the UP/DOWN arrow button to
display the minutes past the hour. Press the DAY/
TIME button.
3. Day MO" (Monday) will flash. Use UP or DOWN arrow
buttons to display the current day. Day selections are
abbreviated as MO, TU", WE", TH", FR", SA",
and SU". Press the DAY/TIME button.
4. The HOME screen reappears; confirm day and time
are correct. This completes day and time setting.
506072−01 02/08
Page 2
HEAT − Using the Heat Mode
COOL − Using the Cool Mode
Enabling and Disabling Heat Mode
The thermostat must be in the heat mode to control the
heating equipment. Press the HEAT button to enable or
disable heat mode. If the thermostat is in cool or off mode,
pressing the HEAT button enables the heat mode (indicated by HEAT in the lower right corner − see figure 4).
Heat
Cool
Prog
Auto
5:30
Day/Time
Copy
82
(DOOR
°
°
OPEN)
OFF
HEAT
Fan
Settings
Hold
Enter
(Outside)
70
66
Figure 4. Turn Heat ON/OFF
If the thermostat is in heat mode, heat mode is disabled
when the HEAT button is pressed. This is indicated by OFF
near the right side of the display as shown in figure 5.
ROOM
75
°
HEAT SETPOINT
75
Figure 5. Heat/Cool Mode Disabled
Heating Demand
Set the thermostat to heat mode to control the heating
equipment. Then, if the room temperature is lower than the
temperature setpoint, as shown in figure 6, the thermostat
detects a heating demand and will activate the heating
equipment to satisfy the demand.
ROOM
72
°
HEAT SETPOINT
75
Enabling and Disabling Cool Mode
Use the COOL button to enable or disable cool mode as
desired. If the thermostat is in heat or off mode, cool mode
is enabled when the COOL button is pressed. This is indicated by COOL on the right side of the display (see figure
7).
Heat
Cool
Prog
Auto
i0:30
Day/Time
Copy
70
(DOOR
Fan
Settings
Hold
Enter
(Outside)
75
66
Figure 7. Turn Cool ON/OFF
If the thermostat is in cool mode, pressing the COOL button disables cool mode (indicated by OFF, similar to figure
5).
Cooling Demand
Set the thermostat to cool mode to control the cooling
equipment. Then, if the room temperature is higher than
the temperature setpoint, as shown in figure 7, the thermostat detects a cooling demand and will activate the cooling
equipment to satisfy the demand.
Cooling operation is indicated by flashing snowflake"
icons in the display. When the actual temperature drops
below the temperature setpoint, the snowflake icons will
disappear. This indicates that the cooling demand has
been satisfied and that the cooling equipment has been
turned off.
NOTE − If no buttons are pressed during a demand for
cooling, the equipment must operate for at least 4 minutes.
After a demand has been satisfied, cooling equipment operation is locked out for 5 minutes. If another cooling demand occurs during this 5−minute interval, COOL" and the
snowflakes will flash; however, the cooling equipment will
not operate until the 5−minute delay has elapsed.
NOTE − The cooling setpoint cannot be lower than the
heating setpoint. Also, the difference between the cooling
and heating setpoint must be at least 4 degrees.
AUTO − Using the Autochangeover Mode
OPEN)
Figure 6. Heating Demand
Heating operation is indicated by a flame icon in the lower
right corner. When the actual temperature rises above the
temperature setpoint, the flame icon will disappear. This
indicates that the heating demand has been satisfied and
that the heating equipment has been turned off.
NOTE − Heating equipment is activated for at least 3 minutes if no buttons are pressed during the demand interval.
When in either heat mode or cool mode, autochangeover
can be enabled or disabled by pressing the AUTO button. If
enabled, AUTO appears at the lower right corner of the display. The thermostat will then automatically change over
from heating to cooling and vice versa, to keep the room
temperature in between the heating and cooling setpoints.
Autochangeover can be used in either of the thermostat
hold modes, or when the thermostat program is running.
These modes are described later.
Page 3
L3711C 7-DAY PROGRAMMABLE THERMOSTAT
Loading...
+ 5 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.