Lennox II-T C INS, II-T C FS User Manual

r
www.PelletKing.com
INSTALLATION AND OPERATION
FREESTANDING
AND INSERT
PELLET FIRED
STOVES
MANUAL
Freestanding Model Advantage II-T C FS
RETAIN THESE
INSTRUCTIONS
FOR FUTURE
REFERENCE
Freestanding Model
Advantage II-T C INS
These appliances must be properly installed and operated in orde to prevent the possibility of a house fire. Please read this entire owner's manual before installing and using your pellet stove. Fail­ure to follow these instructions could result in property damage, bodily injury or even death. Contact your local building or fire offi­cials to obtain a permit and information on any installation require­ments and inspection requirements in your area.
P/N 775096M, Rev. E, 11/03
IMPORTANT WARNINGS
www.PelletKing.com
CAUTION: eration and maintenance instructions exactly without deviation. Failure to follow these instructions may result in a possible fire hazard and will void the warranty. If this appliance is not properly installed, a house fire may result. Contact local building or fire officials about requirements and installation inspection in your area.
1. DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE CONNECTED TO ANOTHER APPLIANCE.
2. Do not connect this appliance to air ducts or any air distribution system.
3. Do not install a flue damper in the exhaust venting system of this appliance.
4. Do not use class B venting intended for gas appli­ances as a chimney or connector pipe on a pellet fired appliance.
5. The minimum clearances must be maintained for all combustible surfaces and materials including; furniture, carpet, drapes, clothing, wood, papers, etc. Do not store firewood within this clearance space.
6. INSTALLATION DISCLAIMER - This stoves exhaust system works with negative combustion chamber pressure and a slightly positive chimney pressure. Therefore, it is imperative that the exhaust system be gas tight (air tight, sealed connection) and in­stalled correctly. Since Lennox Hearth Products has no control over the installation of your stove, Lennox Hearth Products grants no warranty, im­plied or stated for the installation or maintenance of your stove, and assumes no responsibility for any consequential damage(s).
7. Burning any kind of fuel consumes oxygen. If out­side air is not ducted to the appliance, ensure that there is an adequate source of fresh air available to the room where the appliance is installed.
8. The stove will not operate using natural draft, nor without a power source for the blower and fuel feeding systems.
9. Never use gasoline, gasoline-type lantern fuel, kerosene, charcoal lighter fluid, or similar liquids to start or "freshen up" a fire in this heater. Keep all such liquids well away from the heater while it is in use.
10. CONTINUOUS OPERATION: When operated cor­rectly, this appliance cannot be overfired. Con­tinuous operation at a maximum burn can, how­ever, shorten the life of the electrical components (blowers, motors, and electronic controls), and is not recommended. Typical approved operation would include running at the low to mid range set­ting with occasional running on the maximum set­ting during the coldest periods of the winter. The room air blower speed control should be turned to high when operating the stove on the high heat setting.
11. CAUTION: NEVER PUT FINGERS NEAR AUGER. Pellet fuel is fed to the UltraGrate ger. This auger is driven by a high torque motor.
Read this manual thoroughly before starting installation. For your safety, follow the installation, op-
The auger is capable of doing serious harm to fin-
gers. Keep pellets in the hopper at all times and keep fingers away from auger. The auger can start and stop automatically at any time while the stove is running.
12. CAUTION: HOT WHILE IN OPERATION. An appli­ance hot enough to warm your home can severely burn anyone touching it. Keep children, clothing and furniture away. Contact may cause skin burns. Do not let children touch the appliance. Train them to stay a safe distance from the unit.
13. APPROVED FUEL: This appliance is designed spe-
TM
by a screw au-
cifically for use only with pelletized wood fuels only. With its advanced UltraGrate this appliance is designed and approved for the burning of wood residue pellets with up to 3% ash content. This appliance is NOT approved to burn cardboard, nut hulls, cherry pits, corn, etc. regard­less if it is in pellet form. Failure to comply with this restriction will void all warranties and the safety listing of the stove. Consult with your authorized Lennox Hearth Products dealer for approved pellet fuels.
14. FLY ASH BUILD-UP: For all wood pellet fuel­burning heaters, the combustion gases will contain small particles of fly ash. This will vary due to the ash content of the fuel being burned. Over time, the fly ash will collect in the exhaust venting sys­tem and restrict the flow of the flue gases. The ex­haust venting system should be inspected regu­larly and cleaned as necessary.
15. SOOT FORMATION: Incomplete combustion can occur during startup, shutdown, or incorrect op­eration of the room heater. This can lead to some soot collecting in the exhaust venting system. A precautionary inspection on a regular basis is ad­visable to determine the necessity of cleaning. The exhaust venting system should be inspected regu­larly and cleaned as necessary.
16. DISPOSING OF ASHES: Any ashes removed from the pellet stove must be deposited in a metal con­tainer with a tight-fitting lid. The closed container of ashes should be placed on a noncombustible floor or on the ground, well away from all combus­tible materials, outside of the dwelling pending fi­nal disposal. If the ashes are disposed of by burial in soil or otherwise locally dispersed, they should be retained in the closed container until all cinders have been thoroughly cooled.
17. SAVE THESE INSTRUCTIONS.
18. See the listing label located in the hopper (or see Safety / Listing Labels on page 43).
TM
technology,
PAGE 2
TABLE OF CONTENTS
www.PelletKing.com
Important Warnings ................................................ 2
Testing / Listing, EPA, Using this Manual................ 3
Planning Your Installation ..................................... 4-8
Manufactured (Mobile) Home Installation ................8
Installation .......................................................... 9-20
Care and Operation .......................................... 21-25
Routine Maintenance........................................ 26-30
Specifications.................................................... 31-32
Definitions ...............................................................33
Wiring Diagram .......................................................34
Troubleshooting ................................................ 35-37
Replacement Parts List / Diagrams .................. 38-41
Optional Accessories ..............................................42
Safety / Listing Label...............................................43
EPA and Colorado Compliance Label ....................44
Simple Operating Instructions Label.......................45
Installation Tips Label .............................................46
Ownership Records ................................................47
LISTING / TESTING
Listing: The listing laboratory is ITS (Intertek Testing Services) and the listing mark is Warnock Hersey.
Testing: In accordance with the specifications and proce­dures listed in UL 1482 / ULC S627 / CSA B366.2M / ULC S628 & ASTM E1509 for solid fuel room heater, report # 5515, 12-91and ASTM E1509 Report # 476-1244, 3-96. This appliance has been independently tested to UL, ULC and CSA standards. UL 1482 & ULC S627 states re­quirements for installations as a freestanding room heater, or hearth insert for masonry fireplaces listed to UBC 37 or ULC S628, or factory built (zero clearance) fireplaces listed to UL 127 or ULC S610.The safety-listing label is located on an inside hopper surface of the pellet stove. Please read this safety label carefully. It contains impor­tant information about installation and operation of this appliance. This appliance is tested and listed for residen­tial installation according to current national and local building codes as:
A Freestanding Room Heater –FS
A Insert Room Heater – INS
A Manufactured (mobile) Home Heater – FS & INS
EPA (Environmental Protection Agency)
Status: EPA – Certified to comply with July 1990 par­ticulate emission standards.
PRODUCT IS SUBJECT TO CHANGE WITHOUT NO­TICE.
CONGRATULATIONS ON THE PURCHASE OF YOUR NEW PELLET STOVE MANUFACTURED BY LENNOX HEARTH PRODUCTS.
When you purchased your new pellet stove, you joined the ranks of thousands of concerned individuals whose answer to their home heating needs reflects their concern for aesthetics, efficiency and our envi­ronment. We extend our continued support to help you achieve the maximum benefit and enjoyment available from your new pellet stove.
It is our goal at Lennox Hearth Products to provide you, our valued customer, with an appliance that will ensure you years of trouble free warmth and pleasure.
Thank you for selecting a Lennox Hearth Products stove as the answer to your home heating needs.
Sincerely, All of us at Lennox Hearth Products
PACKAGING LIST
The assembled pellet stove model Advantage II-T C FS and Advantage II-T C INS are packaged with an accessory pack­age, which contains the following:
One - Installation and operation instructions manual. One - Warranty. One - EPA Label. One - Colorado compliance certificate One - Power cord. One - Damper hex wrench One - Grate scraper/tool. One - Wall thermostat. One - Roll of thermostat wire. Two - Leveling bolts, 3/8"-16 x 3 1/2” (Insert only) One - Ash pan trim cover One - Trivet One - Control board (Insert) One - Video tape One - Fireplace warning label (insert only) One - Damper rod assembly with tag
Surround Kit (For Advantage II-T C INS Only)
(Purchased separately, see page 42) kit is packaged with:
One - Top surround panel. One - Left surround panel. One - Right surround panel with door.
Pedestal Kit (For Advantage II-T C FS Only)
(Included with freestanding stove) kit is packaged with:
One - Pedestal assembly. Three -Bolts, 3/8" x 1/2”. Three -Washers.
USING THIS MANUAL
Please read and carefully follow all of the instructions found in this manual. Please pay special attention to the safety instructions provided in this manual. The home­owner’s Care and Operation Instructions included here will assure you have many years of dependable and enjoyable service from your appliance.
PAGE 3
PLANNING YOUR INSTALLATION
www.PelletKing.com
QUESTIONS TO ASK LOCAL BUILDING OFFICIAL
A correct installation is critical and imperative for reduc­ing fire hazards and perilous conditions that can arise when wood pellet burning appliances are improperly installed. The installer must follow all of the manufac­turers’ instructions.
The installation of this appliance must conform to local codes and applicable state and federal requirements. Familiarity with these requirements before installation is essential. Important considerations to discuss with local building officials include:
1. Applicable codes (i.e. Uniform Mechanical Code, State or Regional Codes).
Electrical codes:
In USA, NEC, ANSI / NFPA 70 – Latest Edition In Canada, CSA C22.1 – Latest Edition
Power Supply Requirements
be plugged into a standard, 115 volt, 60 Hz grounded electrical outlet. The approximate power requirement is 362 Watts, and will peak up to 736 Watts for approxi­mately 6 minutes when the self-igniter is operating (it will turn off 2 minutes after flame detection). The power cord must be routed to avoid contact with any of the hot or sharp exterior surface areas of the stove. When in­stalled into a manufactured (mobile) home, the appli­ance must be electrically grounded to the steel chassis (see page 8, Manufactured [Mobile] Home Require- ments). These requirements must be met unless other­wise specified by state or local authorities.
WARNING - ELECTRICAL GROUNDING IN­STRUCTIONS: THIS APPLIANCE IS EQUIPPED WITH A THREE-PRONG (GROUNDING) PLUG FOR YOUR PROTECTION AGAINST SHOCK HAZARD AND SHOULD BE PLUGGED DI­RECTLY INTO A PROPERLY GROUNDED THREE-PRONG RECEPTACLE. DO NOT CUT OR REMOVE THE GROUNDING PRONG FROM THIS PLUG. DO NOT ROUTE POWER CORD UNDER OR IN FRONT OF APPLIANCE.
2. Local amendments?
3. Is a permit required - cost? You may wish to contact your insurance company to ask if they require this.
4. Is outside combustion air required?
5. Rooms where the installation is not allowed?
– The power cord must
INSTALLATION / MAINTENANCE STANDARDS
National Fire Protection Association – The primary NFPA standard that refers to installation and mainte­nance of pellet appliances and venting is NFPA 211 – Latest Edition: Chimneys, Fireplaces, Vents, and Solid Fuel appliances.
SELECTING A LOCATION The design of your home and where you place your stove will determine its value as a source of heat. A pel­let stove depends primarily on air circulation (convec­tion) to disperse its heat, and therefore, a central loca­tion is often best. There are other practical considera­tions, which must be considered before a final selection of locations is made.
Existing Chimneys Pellet Fuel Storage Aesthetic Considerations Roof Design (rafter locations & roof pitch) Room Traffic Proximity to Combustibles Electrical Wiring
The installation of this stove will require some research. Once your options are determined, consult with your local building department who will be able to give you the necessary installation requirements for your area (Is a building permit required? Rooms where installation may not be allowed, etc.).
WARNING: CHECK ALL LOCAL BUILDING AND SAFETY CODES BEFORE INSTALLATION. THE IN­STALLATION INSTRUCTIONS AND APPROPRIATE CODE REQUIREMENTS MUST BE FOLLOWED EX­ACTLY AND WITHOUT COMPROMISE. ALTERA­TIONS TO THE STOVE ARE NOT ALLOWED. DO NOT CONNECT THE STOVE TO A CHIMNEY SYS­TEM SERVING ANOTHER STOVE, APPLIANCE, OR ANY AIR DISTRIBUTION DUCT. FAILURE TO FOL­LOW THESE INSTRUCTIONS WILL VOID THE MANUFACTURERS WARRANTY.
SMOKE DETECTORS
Since there are always several potential sources of fire in any home, we recommend installing smoke detec­tors. If possible, install the smoke detector in a hallway adjacent to the room (to reduce the possibility of occa­sional false activation from the heat produced by the stove). If your local code requires a smoke detector be installed within the same room, you must follow the re­quirements of your local code. Check with your local building department for requirements in your area.
PAGE 4
PLANNING YOUR INSTALLATION
www.PelletKing.com
FLOOR PROTECTION – Advantage II-T C FS
(For USA and Can­ada) This appliance requires 3/8" (10 mm) minimum non­combustible floor protection designed for solid fuel burning appliances having a thermal conductivity of k = .84 BTU in/ft or equivalent. If the
6”
(153mm)
min.
floor protection is to be stone, tile, brick, etc., it must be mor­tared or grouted to form a continuous non-combustible sur­face (See Using Alternate Material As Floor Protector below). If a chimney connector extends horizontally over the floor, protection must cover the floor under the connector and at least 2" (51 mm) to either side. The floor protector must fully cover the area beneath the appliance and extend 6” to the front, 6” to the sides, and up to 6” from the back (see illustra­tion above and following note).
*Note: When installed at clearances less than 6”, the floor protection is only required to extend to the wall.
FLOOR PROTECTION / HEARTH EXTENSION USING AL­TERNATE MATERIAL AS FLOOR PROTECTOR
Floor Protection above for freestanding models and Hearth Requirements, page 8 for the insert model)
The hearth pad or alternate material used as a floor/hearth protector must be constructed of a durable noncombustible material having an equal or better thermal conductivity value (lower k value) of k = .84 BTU / IN FT resistance that equals or exceeds r = 1.19 HR °F FT with a minimum thickness of 3/8”. With these values, determine the minimum thickness of the alternate material required using the formula(s) and the table shown here (see chart - Approved Alternate Materials for Floor/Hearth Protection).
Note: Any noncombustible material having a minimum thickness of 3/8” (10 mm) whose k value is less than .84 or whose r value is more than 1.19 is acceptable. If the alternate material used has a higher k value or lower r value will require a greater thickness of the material used. In some cases, if the k value is less or the r value higher, a thinner material may be used.
Methods of determining floor protection equivalents:
To determine the thickness required for the alternate material when either the k value or r value is known, use either the k formula or r formula:
Example: Durock Cement tion. How thick must this material be? The following formulas give the means of determining minimum thickness required.
= minimum thickness required for alternate material
T
M
kM = k value per inch of alternate material TL = minimum thickness of listed material r
= r value per inch of alternate material
M
Using the k formula
Minimum k-value (per Inch) Specified min. thickness of = of alternate material alternate k-value (per inch) of listed material of listed material material
:
is to be used for the floor protec-
Top View
6”
153 mm
(153mm)
6”
153 mm
(also see
2
HR °F or a thermal
x thickness
2
6”
min.
IN/BTU
TM (inches) = kM x T .84
(inches) = 1.92 x .375 (3/8”)
T
M
.84
L
Answer using k: 2.29 x 0.375” = 0.858 = ~7/8” 7/8” thickness (minimum) Durock Cement will be required.
Using the r formula
(inches) = 1.19 x TL
T
M
r
(inches) = 1.19 x 375 (3/8”)
T
M
.52
:
M
Answer using r: 2.29 x 0. 375” = 0.858 = ~7/8” 7/8” thickness (minimum) Durock Cement will be required.
At times it is important to know what combination of materials are acceptable for use as floor protection. The “R values” are used to determine acceptable combinations of materials because “R val­ues” are additive where r and k values are not.
“R value” = 1 k
= r x thickness of material used
Example: Given that the required “R value” for a suitable floor pro­tector used must be equal to or greater than “R” = r x T .375” = .45.
Listed Material
Listed Material
Thermal Values
k (per inch) r (per inch) T
.84 1.19 3/8” (.375)
= 1.19 x
L
Specified Minimum
Thickness
L
Approved Alternate Materials for
Floor/Hearth Protection (**)
Alternative Materials
k (per inch) r (per inch) TM
Kaowool M Board .47 2.13 * 3/8” Micore 160 Micore 300 Durock Cement Hardibacker Hardibacker 500 Cultered Stone
Hearthstone Wonderboard 3.23 0.31 1 1/2”
Face brick 9.00 0.11 4 1/8”
Common brick 5.00 0.20
Cement mortar 5.00 0.20 2 1/4”
Ceramic tile 12.5 .08
Marble
Note: To convert inches to millimeters divide by .03937.
* After minimum thickness is calculated, the thickness can be no less than 3/8” (.375” / 10mm).
(**) If the floor protector to be used is a noncombustible material and is NOT listed on the chart above, the manufacturer of the material must provide either the listed k-value per inch or r-value per inch and the minimum acceptable thickness will need to be calculated per instruc­tions on this page.
Thermal Values * Minimum
.35 2.86 * 3/8”
.46 2.18 * 3/8”
1.92 .52 7/8”
1.95 .51 7/8”
2.30 .44 1 1/8”
2.82 .35 1 5/8”
~20.0 ~.05
Thickness
2 1/4”
5 5/8”
9”
PAGE 5
PLANNING YOUR INSTALLATION
www.PelletKing.com
Clearances to combustibles are determined from testing to applicable standards for allow­able heat transfer. The clearances allowed as shown here, do not take into account opera­tion or serviceability requirements.
CLEARANCES
Advantage II-T C FS - Standard residential or manufac­tured (mobile) home installation. These appliances re­quire the following minimum clearances to combustibles:
MINIMUM CLEARANCES TO COMBUSTIBLES
Advantage II-T C FS
Clearance to
Combustibles
A - Sidewall to unit ♦6” / 153 mm ♦6” / 153 mm
B – Backwall to unit *2” / 50 mm 9” / 230 mm
C – Sidewall to unit Corner
D - Alcove to Fuel Hopper
E – Max. Depth of Alcove
F – Flue to Wall n / a 3” / 77 mm
Measured to fuel hopper
Alcove Requirements – Minimum Height 50” / 127 cm
Minimum Width 36” / 966 mm Maximum. Depth 16" / 406 mm
Manufactured (Mobile) Home or Residential Installation
Horizontal Flue – Di­rectly Through Wall
Interior Vertical Flue
inch / millimeter inch / millimeter
*2” / 50 mm *2” / 50 mm
6” / 150 mm 6” / 150 mm
16” / 406 mm 16” / 406 mm
Minimum clearances specified may not allow for
ease of operation and maintenance (please take this in to account when planning the installation). If installed to the minimum clearances, removal of the appliance may be necessary for servicing.
Recommended clearance zone from the front of
the appliance to combustibles is 4 feet minimum.
* The certified back wall clearance as shown on the
listing label is 1" (see Safety / Listing Label) but for proper hopper lid operation in corner and parallel installations a 2" clearance is required.
Alcove - Advantage II-T C FS
*B
E
D D
Parallel Wall - Advantage II-T C FS
F
*B
Corner - Advantage II-T C FS
F
C
F
C
A
PAGE 6
PLANNING YOUR INSTALLATION
www.PelletKing.com
MASONRY AND FACTORY BUILT FIREPLACES
The model Advantage II-T C INS is approved for installa­tion into a solid fuel burning fireplace, either a masonry fireplace (built to UBC 37 or ULC S628 standards) or an approved factory-built / zero clearance fireplace (built to UL 127 or ULC S610 standards). (see pages 19 through 20 for additional information on venting).
Dimensions Into a Fireplace
Height 20 1/4” / 515 mm Width 30 1/4” / 768 mm Depth w/Tee 18 3/8” / 467 mm Depth–DV thru Masonry Wall 12 1/2” / 318 mm
Recommended clearance zone from the front of the ap­pliance to combustibles is 4 feet minimum.
CAUTION: The fireplace in which the Advantage II-T C INS is to be installed must be thoroughly cleaned if it has been used to burn wood or synthetic logs. Have the chimney and all inside surfaces of the fireplace brushed and vacuumed so that no soot, embers, or loose com­bustion deposits can be drawn into the heat circulation blower and blown into the living area. If any portion of the chimney system shows signs of structural or me­chanical weaknesses, such as: cracks, leaky joints, cor­roded or warped surfaces, the faulty portion must be repaired or replaced prior to installing this appliance.
IMPORTANT: When installing model Advantage II-T C INS into a factory built fireplace or heatform, the air flow within and around the fireplace shall not be altered by the installation of the insert (i.e. DO NOT BLOCK louvers or cooling air inlet or outlet ports, circulating air chambers in a steel fireplace liner or metal heat circulator). The factory built firebox must accept the insert without modification other than removing bolted or screwed together pieces such as smoke shelf / deflectors, ash lips, screen or door tracks and damper assemblies. Any fireplace component, which is removed, must be retained so they can be rein­stalled to restore the fireplace to its original operating con­dition. The removal of any part must not alter the integrity of the outer shell of the pre-engineered fireplace cabinet in any way. A Warning Label (provided with appliance) must be installed in the fireplace firebox so that it shall be visible upon removal of the fireplace insert (see Fireplace Warning Label, below). Use RTV high Temperature Sili­cone as an adhesive to affix the warning label.
Fireplace Warning Label
Provided in accessory package (insert only)
THIS FIREPLACE HAS BEEN ALTERED TO AC-
COMMODATE A FIREPLACE INSERT AND SHOULD BE INSPECTED BY A QUALIFIED PERSON PRIOR TO RE-USE AS A CONVENTIONAL FIREPLACE.
HEARTH / FLOOR PROTECTION - Advantage II-T C INS
In the USA and Canada, the area below and directly in front of the Advantage II-T C INS must be an approved fireplace hearth or protected by a non-combustible hearth / floor protector with a minimum thickness of 3/8” which has a thermal conductivity of k (per inch) = .84 or lower value (better thermal protection) or resistance of r (per inch) = 1.19 or higher value. See Floor Protection /
Hearth Extension Using Alternate Material as Floor Pro­tector on page 5 which explains minimum thermal pro-
tection requirements.
The protected area must extend 6” to the front of the face
of the Advantage II-T C INS.
MINIMUM CLEARANCES TO COMBUSTIBLES Masonry and Factory Built Fireplaces
inches / millimeters A - Insert to side wall 6 “ / 150 mm B - Insert to side trim 1” / 25 mm C - Hearth extension 6” / 150 mm D - Ins e r t t o m a n tel 18” / 457 mm E - Insert to top trim 1” / 25 mm
D
C
Front View
DE
B
A
Side View
E
PAGE 7
PLANNING YOUR INSTALLATION
www.PelletKing.com
MANUFACTURED (MOBILE) HOME INSTAL­LATION
Freestanding Model – Advantage II-T C FS In addition to the standard installation instructions, the following instructions may be required by lo­cal, state or federal building codes:
Stove must be permanently bolted to the floor.
An outside air inlet must be provided for com-
bustion and be unrestricted while unit is in use. Use a galvanized or stainless steel pipe for the duct (the outside air inlet on the stove is 1 5/8" diameter).
Stove must be permanently electrically
grounded to the steel chassis of the home. The location selected for ground attachment to the stove must be dedicated for this purpose.
See pages 13 through 18 for additional informa-
tion on venting requirements.
Do not install appliance in a sleeping room.
The structural integrity of the manufactured
home floor, walls, ceiling and roof must be maintained.
NOTE: The grounding of this product, at installa-
tion, must comply with NFPA-70 stan­dards, CSA C22.1 in Canada, as well as any local codes.
Model – Advantage II-T C FS
Pedestal Air Inlet
25”
MANUFACTURED (MOBILE) HOME EXHAUST VENT PIPE INSTALLATION GUIDELINES
Use only “PL” pellet vent pipe listed to UL 641 and ULC S609. The pipe should extend at least 3 feet above the part of the roof through which it passes. The top of the pipe should be at least 2 feet above the highest required elevation of any part of the manufactured (mobile) home within 10 feet of the pipe (see page 14, Manufactured [Mobile] Home Chimney Height Requirements).
If the exhaust vent exits the manufactured (mobile) home at a location other than the roof, and exits at a point 7 feet or less above the ground level on which the manufactured (mobile) home is position a guard or method of enclosing the pipe shall be provided at the point of exit for a height of up to 7 feet. The openings, if any, in this guard shall not allow a 3/4” rod to pass through. A 1/2” rod could pass through but should not be able to touch the pipe when inserted through the open­ing a distance of 4 inches.
Bolt
Bolt
Floor Protector
Floor
24 ¾”
12 ½”
Outside Air Inlet
1 5/8" diameter
Steel Chassis
Ground
6 7/8”
PAGE 8
To Chassis
INSTALLATION
www.PelletKing.com
REMOVING APPLIANCE FROM PALLET
1. After removing the packaging from the stove, lift the
hopper lid, and remove all pre-packaged items that were shipped in the hopper. Next, open the stove door and remove all pre-packaged items.
2. Using a 9/16” socket or open end wrench, remove
the bolts which secure stove to pallet. The bolts are located on the underside of the wooden pallet.
Underside of Pallet
Remove the two bolts from underneath the pallet.
ASH PAN COVER ASSEMBLY
Remove the ash pan cover trim from hopper. Remove polyfoam wrapping and press into place as shown in il­lustration below. The ash pan cover trim has two mag­nets attached which will secure it in place.
NOTE: Bolts may be used in manufactured (mobile) home installation to permanently secure stove to floor (see previous page).
Ash Pan Cover
INSTALLING PEDESTAL TO BODY
If your stove is a freestanding model, secure the pedes­tal to the stove body as follows:
1. Remove the pedestal from the box and place it be­side the stove body.
2. Lift the stove onto the pedestal base.
3. Install the three bolts and washers provided through the holes in the mounting flange of the pedestal and into the threaded pressed nuts in the stove bottom.
4. Tighten the fasteners using a socket or wrench.
Pedestal – Top View
Install three bolts
Attach stove to pedestal by inserting three bolts (provided with pedestal kit)
PAGE 9
INSTALLATION
www.PelletKing.com
INSTALLATION CHECK LIST
It is strongly recommended that you have an authorized Lennox Hearth Products dealer install your stove. If you install your stove yourself, you should review your instal­lation plan with an authorized Lennox Hearth Products dealer. Improper installation may void your warranty.
Check list:
Check off each item as you proceed with the installation
process.
Read the ENTIRE stove installation section first
Read the Insert or Freestanding section (whichever
applies).
Determine the appropriate measurements and loca-
tions for your installation.
Follow the general installation directions under Stove
Installation and the installation section appropriate to
your stove.
Be sure to pre-fit all items before you install, fasten,
or set up the stove permanently.
Prior to lighting your stove:
Review the Important Warnings section (page 2).
Review Fuel Specifications (page 25).
Review and follow instructions in the Care and Op-
eration Section (pages 21 to 25).
Plug power cord connector into corresponding con-
nector on the back of appliance (see illustrations on
page 12 showing connector locations).
Note
: Advantage II-T C INS – Route power cord be-
hind side surround panel.
After you have begun operation of your stove:
Review the routine cleaning / maintenance informa-
tion.
Enjoy the warmth from your new Lennox Hearth
Products pellet stove!
Advantage II-T C Insert It is important to level the appliance. In some installa­tions such as a recessed firebox floor (if the existing fire­place floor is lower than the hearth), install the 2 leveling bolts (3/8-16 x 3 1/2” long) into the 2 threaded holes at the rear base of the Advantage II-T C INS. Adjust bolts until appliance is level.
PAGE 10
INSTALLATION
www.PelletKing.com
INSTALLING SURROUND ASSEMBLY - Advantage II-T C INS (to be done after venting system is installed)
The surround kit (purchased separately) comes with a set of metal panels that enclose the fireplace opening when fitted together. Put the surround assembly together accord­ing to the following instructions (ref. see illustration below).
1. Remove panels from package.
2. Verify that you have all three panels and a package with “pop” rivets and #8 self-tapping screws. If you do not have a “pop” rivet tool, you should arrange to buy or borrow one for this installation.
3. Set the stove on the hearth so that the rear of the stove is accessible to complete all pipe connections.
4. Verify that the hopper cover is all the way to the front and open as high as your fireplace opening will allow. Secure the hopper cover with at least two #8 screws on all three sides. Tip: Spreading the side panels slightly may be nec­essary to complete this step.
5. Place four rivets and your “pop” rivet tool beside the stove and line up the right side panel (with control door) with the holes in the side of the stove. (When the side panel is properly installed, the hinge flange will be to the rear of the stove.) Attach the panel to the stove with four “pop” rivets.
6. Secure the left side surround panel to the stove using the procedure described in step #5.
7. Before proceeding further, check pipe connections to en­sure that all joints are sealed with high-temperature RTV silicone and properly secured. Refer to detailed venting in­structions on pages 16, 19 and 20.
8. The stove may now be pushed into the fireplace cavity to within 1 1/2” of the face of the fireplace.
9. Set the top surround panel in place over the two side pan­els. Carefully slide the panel downward into the “U” clips
attached to the back of the Advantage II-T C INS. Tip: Be careful to align the notched cutouts in the top surround panel with the stove side panels. Adjust side to side if nec­essary to align with the surround side panels.
10. Unwrap the control board carefully without touching any electrical components. Holding the sides of the control board, lower the bottom edge into the slot in the bottom of the control door opening Install the control board onto the right side panel (with door) us­ing the #8 hex head screw provided.
11. Connect the wiring harness from the Advantage II-T C INS into corresponding connector on control board.
12. Check the Advantage II-T C INS placement in the fireplace. To reposition, open the door and make any needed adjustment by pulling forward and then push­ing sideways. Once the unit has been centered to your satisfaction, close the door and push the Advan­tage II-T C INS back into place so the surround is flush with the face of the hearth. Tip: Before com­pleting this step, verify that the control board will not hit the edge of the fireplace opening.
If using the optional gold surround trim, remove the trim from its packaging and place the piece with the two mi­tered ends along the top panel. Place the two remaining side pieces on the surround so that the mitered ends align. Cut the non-mitered ends of the shroud trim with scissors, if necessary.
In factory built and masonry fireplaces, a means must be provided to prevent room air passage to the chimney cavity of the fireplace. This may be accom­plished by sealing the damper area around the chim­ney liner or pipe.
Top Surround Panel
Left Hinged
Surround Panel
PAGE 11
Right Hinged
Surround Panel
Optional Trim Optional Trim
INSTALLATION
www.PelletKing.com
THERMOSTAT INSTALLATION:
NOTE: Always Disconnect Power Before Performing The Thermostat Installation.
A 24 volt wall thermostat and 20 feet of 18-gage thermo­stat wire is included in your stove’s accessory package. It is recommended that the thermostat and thermostat wire be installed by an authorized Lennox Hearth Prod­ucts dealer.
Installation Steps:
1. Unplug stove power cord from the wall outlet.
2. Locate the thermostat terminal block on the back of the stove.
3. Loosen the two terminal screws on the terminal block and remove jumper.
4. Connect the two wires from your thermostat to the terminals (one per terminal). Ensure that the purple wires from the harness remain connected to the ter­minal block and tighten the terminal screws. Make sure the wires are firmly connected to the thermo­stat.
5. Plug in the stove and you are ready to operate with your thermostat!
IMPORTANT: IF THE WALL THERMOSTAT PRO­VIDED IS NOT FOR THE STOVE TO OPERATE
USED, THE JUMPER IS REQUIRED
Rear View of Advantage II-T C FS
Back of Stove
Thermostat
Terminal
Block
Thermostat Jumper
PAGE 12
INSTALLATION
www.PelletKing.com
VENTING REQUIREMENTS
It is recommended that only an authorized dealer install your pellet stove. The specified installation requirements must be followed to ensure conformity with both the safety listing of the appliance and local building codes. All clearances, installation instructions and precautions specified by the vent manufacturer must be followed.
Selecting a Location (Freestanding Models) - Review the appliance clearance requirements before installing the venting system (see page 6). Position the appliance far enough away from walls to allow adequate room for servicing. Choose the appliance location with the least amount of interference with the house framing, plumbing, wiring, etc.
Preferred Vent Configuration - For the best perform­ance, we recommend a vent run design which runs verti­cally and terminates above the roofline. This design will allow natural draft to improve the flow of flue gases and will aid in combustion and stove performance.
Type of Pipe - This stove requires type “PL” vent pipe (pellet vent pipe, sometimes referred to as “L-Vent pellet vent”), listed to UL 641 or ULC S609. Connect the pellet vent pipe or the “tee” to the flue collar using a minimum of three screws and seal as specified in “Pipe / Liner Joint Requirements” on this page. Do not use class B gas chimney or single wall chimney as a substitute.
Size of Pipe - These pellet appliances are approved for use with the following vent sizes: 3” (75mm) standard, or 4” (100mm), see page 15 - for determining correct size vent). When 4” pipe is used: for horizontal vent installa­tions use a 3” (75mm) to 4” (100mm) adapter - available from vent manufacturer. For vertical installations use a 3” (75mm) to 4” (100mm) “tee” - available from vent manufacturer.
Note: If installation requires in excess of 11 feet (3 1/3 meter) of pipe, it is recommended that 4” (100 mm) pipe be used.
Offsets - In every installation, a single or double clean­out “tee” is recommended for every ninety-degree offset (this tee will help collect ash residue and will allow for routine cleaning without the need to disconnect sections of pipe). Note: Offsets and horizontal runs accumulate fly ash and soot which reduces the exhaust flow and per­formance of the stove.
Total Offsets in venting system should not exceed 270° total in direction change.
Horizontal Runs - The maximum total horizontal run must not exceed 10 feet (3.1 meters).
Horizontal run of pipe requires 1/4” (7 mm) rise per foot.
Pipe Clearances / Requirements - See pipe manufac­turers instructions for installation of venting components and clearances. Follow pipe manufacturers installation precautions for passing pipe through a combustible wall or ceiling (i.e. use an approved thimble). Note: Pellet vent pipe requires 3” (75mm) clearance from outside of pipe unless otherwise specified by vent manufacturer ­all diameters: 3” (75mm) and 4” (100mm). A support bracket must be installed every 4’ (1.2m) of pellet vent pipe on the exterior wall of the house unless otherwise specified by vent manufacturer.
Pipe / Liner Joint Requirements - All pipe joints must be secured with a minimum of 3 screws. ALL horizontal joints must be sealed gas tight (air tight, sealed connec­tion). Use RTV high temperature silicone or Interam to provide a complete seal at the flue collar and on all joints.
Connection to Masonry Chimney through a Wall (Freestanding Models) - Be sure to verify the construc-
tion of a masonry chimney, as it may have combustible framing.
Approved liner when relining Masonry or Factory Built Fireplaces is 2100HT (degree F.) liner listed to UL 1777 or ULC S635.
Connection to an Existing Class A Chimney (Free­standing Models) - A chimney adapter can be used to
make the connection from 3” (75mm) or 4” (100mm) pel­let vent pipe (listed to UL 641 or ULC S609) to existing UL chimney system. Verify with the pipe manufacturer that your pipe brands will interconnect.
Horizontal-Vent Installations - On all horizontal-vent installations (short, horizontal runs with no vertical pipe); care should be taken when choosing a location for termi­nating the vent. It is not recommended to directly vent the exhaust on the prevailing wind side of the house. It is recommended that when an appliance is vented directly through a wall, a minimum of 8’ (2.5m) of vertical pipe should be installed to create some natural draft. This will reduce the possibility of smoke or odor entering the dwelling during appliance shutdown or loss of power.
PAGE 13
INSTALLATION
ON C
GHES
www.PelletKing.com
VENT TERMINATION
Do not terminate vent in an enclosed or semi-enclosed area such as: carports, garage, attic, crawl space, under a deck, porch, narrow walkway, closely fenced area, or any location that can build up a concentration of fumes such as a stairwell, covered breezeway etc.
Vent surfaces can get hot enough to cause burns if touched. Adults should supervise children when they are in the area of a hot stove. Non-combustible shielding or guards may be required.
Termination Cap: The termination of the outside chim­ney of the pellet stove shall be located in accordance with the following:
A. Higher than 3’ (.92m) above any forced air inlet (air
conditioner, etc.) located within 10’ (3m).
B. Not less than 4’ (1.2m) below, 4’ (1.2m) horizontally
from or 1’ (3.1m) above any gravity air inlet (door, window, etc.) which flue gases could re-enter the dwelling.
C. Not less than 2’ (.6m) from combustible materials
such as an adjacent buildings, fences, protruding parts of the structure, roof overhang, plants and shrubs, etc. and not less than 7’ (2.1m) above grade when located adjacent to the public sidewalks (ac­cess). The final termination of the exhaust system must be configured so that flue gases do not jeop­ardize the safety of people passing by, overheat combustible portions of nearby structures or enter the dwelling.
D. Not less than 3’ (.92m) below an eave (maximum
overhang of 3’ (.92m) or any construction that pro­jects more than 2” (51mm) from the plane of the wall.
E. The distance from the bottom of termination to grade
is 12” (305mm) minimum. This is conditional upon plants and nature of grade surface: Be careful to choose a location for the vent termination which does not expose people or shrubs to high heat from the exhaust gases. The exhaust gases are not hot enough to ignite grass, plants and shrubs located in the vicinity of the termination although they should be a minimum of 3’ (.92m) away. The grade surface under the termination must not be a lawn.
F. Since sparks may escape from the exhaust pipe of
any stove, use caution when positioning the vent pipe. Refer to pipe manufacturer’s instructions when installing and terminating the exhaust. The vent pipe should be horizontal and never run the pipe in a downward direction (recommend a 1/4” (7mm) rise per foot horizontal).
Notes:
It is not recommended to terminate exhaust vent on the prevailing wind side of the house.
It is not recommended using a termination cap with a screen (fly ash can collect in a screen re­sulting in blockage).
Site Built Residential Home Chimney Height Requirements
The vent termination height required is - USA, 1-foot minimum; Canada 3-feet minimum above the roof pene­tration point as illustrated below (Ref. USA - National Standard, NFPA 211, Clause 7-4.1 and Canada National Standard CSA B365-01, Clause 5.6). Check with your local building official for additional requirements for your area.
TERMINATION CAP MUST BE LISTED TO UL 641 AND ULC S609 *
USA 1 Foot Minimum
TERMINATION HEIGHT IS MEASURED ABOVE THE HIGHEST POINT WHERE IT PASSES THROUGH THE ROOF SURFACE.
Manufactured (Mobile) Home Chimney Height Requirements
The chimney must extend 3’ (.92m) above the level of roof penetration and a minimum of 2’ (.61m) higher than any roof surface within 10’ (3m) (see below). Check with your local building officials for additional requirements for your area.
REQUIRES A LISTED TERMINATI
AP *
TOP OF FLUE MUST BE 3’ HIGHER THAN
T POINT OF ROOF PENETRATION
HI
TOP OF FLUE MUST BE 2’ HIGHER THAN ANY PART OF ROOF WITHIN 10’ HORIZONTAL
To pass inspection in nearly any jurisdiction, the chimney must meet both safety and exhaust flow requirements. The (3’ by) 2’ by 10’ rule applies to both masonry and factory built chimneys.
* Ref. NFPA 211 Clause 7 – 4.1.2, Vents installed with a listed cap shall terminate in accordance with the terms of the cap’s listings.
PAGE 14
INSTALLATION
r
www.PelletKing.com
DETERMINING SIZE OF PIPE TO INSTALL
To determine what diameter pipe to use in an installation (3” or 4”), first find the “equivalent pipe length” using the follow­ing guidelines, then plot this figure and the altitude on the chart.
Fill out the installation chart, and calculate your total equivalent pipe length. After you have the total equivalent pipe length, use the Pipe Selection Chart below to determine if your installation requires 3” or 4” exhaust pipe
.
INSTALLATION CHART
Type of
Pipe
# of Elbows
or Feet of
pipe
Equivalent
Feet
Total
Equivalent
Feet
SAMPLE INSTALLATION CHART
Type of
Pipe
# of Elbows
or Feet of
pipe
Equivalent
Feet
Total
Equivalent
Feet
90o Elbows /
Tee (A & G)
o
45
Elbows (C)
Horizontal
(B & F)
Vertical
(E)
x 5 Ft. (1.5m)
x 3 Ft. (1m)
x 1 Ft. (.3m)
x .5 Ft.
(.15m)
A- 90 Degree Elbow E- 8’ Vertical Pipe B- 1’ Horizontal Pipe F- 2’ Horizontal Pipe C- 45 Degree Elbow G- 90 Degree Tee D- Standoff Braces H- Wall Thimble
NOTE: All equivalent pipe styles shown below are stan­dard for all freestanding models.
90o Elbows /
Tee (A & G)
o
45
Elbows (C)
Horizontal
(B & F)
Vertical
(E)
Total = 20
2 x 5 Ft. (1.5m) 10 (3m)
1 x 3 Ft. (1m) 3 (1m)
3 x 1 Ft. (.3m) 3 (1m)
8 x .5 Ft. (.15m) 4 (1.2m)
PIPE SELECTION CHART
30
4 “ Diameter Only
20
3 or 4”
10
Diamete
0 1 2 3 4 5 6 7 8 9 10
PAGE 15
Equivalent Pipe Length (Feet)
0
Altitude x 1000 Feet
Loading...
+ 33 hidden pages