Lennox iHarmony 17A30 Installation And Setup Manual

iHarmony® Zoning System - Zone Sensor (17A30)
Installation and Setup Guide
507826-01 6/2018
©
Lennox Industries Inc.
Dallas, Texas, USA
Tables of Contents
Shipping and Packing List .................................... 2
Electrical Characteristics ...................................... 3
Dimensions ........................................................... 3
Unit Dimensions (H x W x D) .............................................. 3
Wall Plate Dimensions (H x W) ........................................... 3
Installation Guide .................................................. 3
Installation Considerations .................................................. 3
Unpacking Zone Sensor and Determining Best Location ... 4
Installing Zone Sensor ........................................................ 4
Zone Sensor Terminal Information ...................................... 6
Connecting Zone Sensor Wiring ......................................... 6
Install Zone Sensor to Backplate ........................................ 8
Setup Guide..........................................................8
Apply Power ........................................................................ 8
Menu > Advanced Settings ................................................. 8
Installer Checklist ...............................................12
Shipping and Packing List
Item Quantity
Zone sensor with backplate attached 1
Wall plate 1
Mounting screws (M3.5x25mm self-tapping screws) 2
Wall anchors 2
Warranty sheet 1
Installation and setup guide 1
User guide 1
WARNING
Improper installation, adjustment, alteration, ser­vice or maintenance can cause property damage, personal injury or loss of life.
Installation and service must be performed by a li­censed professional HVAC installer (or equivalent) or a service agency.
The 17A30 Zone Sensor can be used in systems controlled by any Lennox communicating thermostat.
The 17A30 zone sensor can also be used in combination with the 10C17 In-Zone thermostat.
2
CAUTION
This is a 12VDC low-voltage zone sensor. Do not install on voltages higher than 14VDC.
Electrical Characteristics
Dimensions
Unit Dimensions (H x W x D)
Dimensions: 3-5/16 x 4-5/16 x 7/8 in. (84 x 110 x 22mm)
Wall Plate Dimensions (H x W)
All values are at 77°F (25°C). This unit does employ mis-wire circuit protection.
Table 1. Zone Sensor Power Requirements
Min Nom Max Unit
Input Voltage
Input Current
10 12 14 VDC
- 61.5 133 mA
WARNING
Always turn off power at the main power source by switching the circuit breaker to the OFF position before installing or removing this zone sensor.
All wiring must conform to local and national building and electrical codes and ordinances.
Dimensions: 4-1/2” x 5-3/4” (114 x 146mm)
Installation Guide
installation ConsiDerations
The 17A30 zone sensor is a 12VDC low-voltage device and requires a common wire to the damper control module to operate.
• Shut off all power to system components before installing zone sensor
• Make sure that all wiring conforms to local and national building and electrical codes and ordinances
• Never install the zone sensor on outside walls or in direct sunlight
3
UnPaCking Zone sensor anD Determining Best loCation
This procedure is for either new or relocating a zone sensor installations.
1. Unpack the zone sensor.
2. Select a location for the zone sensor about 5
feet (1.5 meters) above the oor in an area with
good air circulation at average temperature.
3. Do not install the zone sensor where it can be affected by:
• Drafts or dead spots behind doors and in
corners
• Building entrances or automatic doors
• Heat generating equipment such as kitchen
appliances
• Hot or cold air from ducts
• Radiant heat from sun or appliances
• Concealed pipes and chimneys
• Non-heated (non-cooled) areas such as an
outside wall behind the zone sensor
installing Zone sensor
IMPORTANT
Installation uses 18 gauge thermostat wire with a wire run length NOT TO EXCEED 197 feet (60 meters) between damper control module and any one zone sensor.
Do not run wiring next to high voltage or high voltage ballast.
Load from any zone sensor connection is 1 AMP or less.
1. Run thermostat wiring from iHarmony damper control module to location where zone sensor will be installed.
2. Drill or make opening through wall for thermostat wiring 3/4” x 3/4” (19mm x 19mm).
3. Pull about 3 inches (76mm) of thermostat wire through the opening and removed outer thermostat wire jacket. This will help in routing the thermostat wiring to the proper zone sensor terminals.
4. Seal the hole in the wall with a suitable material to prevent drafts from entering the zone sensor case. Not doing so could affect the zone sensor’s internal temperature and humidity sensors.
4
5. Trim 1/4 inch (6 mm) insulation from end of each
Wall Plate (optional)
Zone Sensor Back Plate
Run thermostat wire
through openings
thermostat wire lead.
6. Use the provided wall plate as a template on where to drill the mounting holes.
NOTE: Installation of wall plate is optional. Use
a eld-provided level to allow for proper
alignment.
(Use a level) Align Wall Plate
Use unit wall plate as template to mark desired
mounting hole locations on wall.
7. Drill 3/16” (5 mm) holes in wall for provided wall anchors. Insert provided wall anchors into drilled holes.
8. Remove back plate from main zone sensor
assembly using a at-head screw driver.
9. Route wiring from wall through center openings on wall plate (use is optional) and back plate.
5
10. Secure back plate and wall plate (optional) to
Wall Plate (optional)
Zone Sensor Back Plate
Screw
PWR D+ D- C
wall with the two provided mounting screws.
Zone sensor terminal information
ConneCting Zone sensor Wiring
Use “Table 2. Terminal Designations” on page 6for connecting the thermostat wiring to the back plate terminals.
Table 2. Terminal Designations
Terminal Purpose
PWR Zone sensor power 12VDC input.
D+ Zone sensor data high.
D- Zone sensor data low.
C Zone sensor 12VDC return.
See “Figure 2. Connecting Zone Sensor to Damper Control Module” on page 7.
Figure 1. Backplate
NOTE: Remember to seal the hole in the wall with
a suitable material to prevent drafts from entering the zone sensor case. Not doing so could affect the zone sensor’s internal temperature and humidity sensors.
6
SENSE 24VAC PRESSURE SW
C SENSE
DATS
D+
PWR
D-
C
ZONE 5
D+
PWR
D-
C
ZONE 2/6
D+
PWR
D-
C
ZONE 3/7
D+
PWR
D-
C
ZONE 4/8
1 – 4
5 - 8
Zone Sensor
C
D-
D+
PWR
NOT USED
Unused wires
Single wire to terminal “C”.
Damper Control Module
17A30 Zone Sensor
PWR D+ D- C
SENSE 24VAC
PRESSURE SW
C SENSE
DATS
D+
PWR
D-
C
ZONE 5
D+
PWR
D-
C
ZONE 2/6
D+
PWR
D-
C
ZONE 3/7
D+
PWR
D-
C
ZONE 4/8
1 – 4
5 - 8
Figure 2. Connecting Zone Sensor to Damper
Control Module
Figure 3. Communicating and Low Voltage
Connections
install Zone sensor to BaCkPlate
The zone sensor assembly simply snaps onto the back plate. Once secure to the back plate apply power to the system. The zone sensor should boot up and go into the commissioning process.
Figure 4. Installing Zone Sensor
7
If power is applied and the zone sensor screen
zone number
zone 3
+
-
remains off, inspect and verify all wire connections.
Setup Guide
aPPly PoWer
After power is applied to the zone sensor for the
rst time it will display the Lennox® “splash screen”
and then the zone number selection screen. Set the address using the plus/minus buttons. Selections are 2, 3 or 4.
NOTE: Zone 1 is always the thermostat.
Figure 5. Zone Selection
CAUTION
When replacing a failed zone sensor, remember to set the new zone sensor to the same address as the one being replaced. Also, If an existing zone sensor has failed and being replaced by a zone sensor relocated from another zone in the home, remember to set relocated zone sensor’s address to match the one that has failed. Not doing so could contribute to incorrect zone operations and possible equipment damage.
menU > aDvanCeD settings
This represents the menu icon. Most procedures will start with menu and with directions to sub-menus.
Table 3 lists the settings that can be adjusted under this menu selection
Table 3. Advanced Settings
Menu Selection Setting
Zone Number
Reset
Restart Reboots the zone sensor.
Default value is 2. Minimum value is 2. Maximum value is 4. Adjustment is made with either the + or - selection tool..
Resets the zone sensor to factory default
settings. Select Conrm to reset all.
8
Alert Codes
Error
Message
Code
Type
Condition and
Email Notication Description
Table 4. Alert Codes
Thermostat Display
Text
System Action
Action to Clear / Recovery Condition
542
543
544
545
Critical
Temperature Sensor Error
Temperature Sensor Error
Temperature Sensor Error
Temperature Sensor Error
Problem (Zoning
Control)
Problem (Zoning
Control)
Problem (Zoning
Control)
Problem (Zoning
Control)
Indoor temp is displayed as “--” on the home screen.
Anytime there is a zone sensor temperature sensor error or any zone sensor loses communication with the damper control module, the entire system will go into central mode.
9
Error could be due to either a temperature sensor error or lost communication between zone sensor and damper control module.
If problem is due to temperature sensor issue, then zone sensor will need to be replace. If sensor auto corrects itself the alert will be automatically cleared and
1
system will return to normal zone
inside
0
operations. Error codes 542, 543, 544 and
545 could also be caused by lost communication with the damper control module. If this is the case, most likely an error code 551 is being displayed at the applicable zone sensor.
Check wiring between damper control module and the zone sensor reporting error code 551.
NOTE: If error is due to lost
communication 551,
error notication 542,
543, 544 and 545 will only be displayed at the thermostat.
Error
Code
Message
Type
Condition and
Email Notication Description
Table 4. Alert Codes
Thermostat Display
Text
System Action
Action to Clear / Recovery Condition
546 Critical
547 Critical
548 Critical
EEPROM error (Power ON)
EEPROM error (Operating)
Hum sensor error
(Without Humidier or Dehumidier): sensor
reads out of range 0% to 100%
Memory error
Memory error
Humidity sensor error
10
System will set itself to energy save mode and continue to operate.
System will operate in normal mode operation until power off.
This message indicates humidity sensor has malfunction.
Zone sensor will have to be replaced..
Zone sensor will have to be replaced.
Zone sensor will need to be replaced or if sensor auto corrects itself the alert will be automatically cleared and system will return to normal operation.
Error
Code
Message
Type
Condition and
Email Notication Description
551 Critical Lost communication
Table 4. Alert Codes
Thermostat Display
Text
Problem (Zoning
Control)
System Action
A pop-up display will appear indicating communication error.
Indoor temp is displayed as “--” on the home screen.
When any zone sensor loses communication with the damper control module, the entire system will go into central mode.
1
inside
0
Action to Clear / Recovery Condition
Once communication is reestablished the device will return to normal zone operations.
Any lost communication between the zone sensor and damper control module will result in the applicable error code being displayed 542, 543, 544 or 545 at the thermostat.
Check wiring between damper control module and the zone sensor reporting error code 551.
11
Installer Checklist
Table 5. Installation Checklist
Item Description Yes No
1 Is the zone sensor properly mounted to either a wall stud or wall? (Do not mount on exterior wall or near any
ventilation outputs, doorways or location that could be directly exposed to sunlight)
2 Are all terminals wiring properly connected and tight?
4 Have all the zone sensor features been explained to the homeowner?
5 Has user manual been given to homeowner?
6 Was the correct thermostat wiring gauge used?
7 Are unused thermostat wires (conductors) wired together to minimize electrical interference that could affect
electronic components in the zone sensor. (See “Figure 3. Communicating and Low Voltage Connections” on page 7.)
8 Was the hole in the wall sealed with a suitable material to prevent drafts from entering the zone sensor case.
Not doing so could affect the zone sensor internal temperature sensor.
9 Did the address get set correctly during initial power up of the zone sensor?
10 When replacing an existing zone sensor did you set the address of the new or relocated zone sensor to
match the address of the zone sensor being replaced?
12
Loading...